HIGH SCHOOL HS-T101-HS-T102.pdf

PDF 341 KB Posted

Attached to
2025 E-Rate Network Cabling Additions
Solicitation number
RFP-SCC-250000001194-2
Issued by
Michigan

About this file

This is a technical drawing/specification sheet for structured cabling work at Swartz Creek High School, prepared by Convergent Technology Partners. The document shows detailed floor plans for Unit 2A and 2B of the high school's second floor, with specifications for Category 6A UTP cable installation. The design was completed in December 2024/January 2025 and includes placement requirements for wall locations, ceiling drops, telecom cabinets, and bus-bars.

The technical specifications require all UTP cable to be ANSI/TIA Category 6A standard, with wall locations to be installed in surface-mounted single-gang back boxes with white two-port faceplates. The document includes specific installation requirements such as centering wall locations below whiteboards at standard height, concealing cables below ceiling in contractor-provided raceway, and providing ceiling locations with adequate service loops. All Category 6A cables must terminate on white 8P/8C (RJ45) jacks, and all cabinets require grounding. The floor plan shows multiple classrooms, including former computer lab spaces, with detailed placement of UTP locations and telecom infrastructure.

View the file

Other files

Show all 19

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

UNIT 2B

UNIT 2A

0' 5' 10' 20' 30' 40' 50'

NOT TO SCALE - BAR SCALE APPROXIMATE. FIELD VERIFY ALL DIMENSIONS

1 1

1 1

UNIT 2B

UNIT 2A

0' 5' 10' 20' 30' 40' 50'

NOT TO SCALE - BAR SCALE APPROXIMATE. FIELD VERIFY ALL DIMENSIONS

TGB

SYMBOL LEGEND

UTP LOCATION, QTY AS

NOTED

CEILING UTP LOCATION,

QTY AS NOTED

TELECOM CABINET

NEW TELECOM BUS-BAR

EXISTING BUS-BAR

OLD COMPUTER LAB

TGB

A2 B2

GENERAL NOTES

1. ALL UTP CABLE SHALL BE ANSI/TIA

CATEGORY 6A. PLACE WALL LOCATIONS IN A

SURFACE MOUNTED SINGLE-GANG BACK BOX

WITH A WHITE TWO PORT FACEPLATE.

2. THE UNUSED TOP PORT OF THE FACEPLATE

IS TO BE FILLED WITH A BLANK KEYSTONE

JACK INSERT.

3. PLACE WALL LOCATIONS CENTERED BELOW

WHITEBOARD AT STANDARD HEIGHT.

4. LOCATIONS WITHOUT WHITEBOARDS,

CENTER THE INSTALLATION ON THE WALL AT

STANDARD HEIGHT.

5. ALL CABLE BELOW CEILING SHALL BE

CONCEALED IN RACEWAY PROVIDED BY

CONTRACTOR.

6. PROVIDE CEILING LOCATION WITH SERVICE

LOOP LONG ENOUGH TO REACH THE

FARTHEST LOCATION IN THE ASSOCIATED

ROOM. SECURELY FASTEN SERVICE LOOP TO

STRUCTURE.

7. TERMINATE ALL CATEGORY 6A CABLES ON

WHITE 8P/8C (RJ45) JACKS.

8. LOCATION OF BUS BLOCKS ARE ESTIMATED,

USE BEST PRACTICES FOR INSTALLATION

LOCATION.

9. FOR ESTIMATES ASSUME ALL CABINETS

NEED GROUNDING.

C O N V E R G E N T 6197 Miller Road Suite 4 Swartz Creek, MI 48473

Phone: 810.720.3820 www.ctpartners.net

T E C H N O L O G Y P A R T N E R S

TECHNOLOGY DESIGN I CONSULTING I PLANNING

1/24/2025 DESIGN DLF

12/17/2024 DESIGN EGH

DATE ISSUE AUTHOR

SWARTZ CREEK

COMMUNITY SCHOOLS

STRUCTURED CABLING

SWARTZ CREEK HIGH

SCHOOL

HS-T102

T1012

NTS

H.S. 2ND FLOOR UNIT A

T1012

NTS

H.S. 2ND FLOOR UNIT B

KEYMAP

Sheets and Views
HS-T102

File details come from the government source that posted it. Updated .