This is a technical drawing showing structured cabling plans for Unit A of Swartz Creek High School, prepared by Convergent Technology Partners. The drawing details the installation specifications for Category 6A UTP cabling throughout the school building, including classroom and corridor locations. The document is dated January 24, 2025, with an earlier design date of December 17, 2024.
The drawing includes detailed specifications for cable installation, requiring all UTP cable to be ANSI/TIA Category 6A standard, with wall locations using surface-mounted single-gang back boxes and white two-port faceplates. Technical requirements include concealed raceway installation below ceiling, service loops for ceiling locations, white 8P/8C (RJ45) jack terminations, and grounding requirements for telecom cabinets. The floor plan shows multiple classrooms, corridors (300 and 350), and includes a symbol legend indicating UTP locations, ceiling UTP locations, telecom cabinets, new telecom bus-bars, existing bus-bars, and old computer lab areas.
View the file
Other files
Show all 19
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
UNIT D
UNIT A
UNIT A
UNIT B
0' 5' 10' 20' 30' 40' 50'
NOT TO SCALE - BAR SCALE APPROXIMATE. FIELD VERIFY ALL DIMENSIONS
TGB
SYMBOL LEGEND
UTP LOCATION, QTY AS
NOTED
CEILING UTP LOCATION,
QTY AS NOTED
TELECOM CABINET
NEW TELECOM BUS-BAR
EXISTING BUS-BAR
OLD COMPUTER LAB
TGB
B C
A D
E F
G
GENERAL NOTES
1. ALL UTP CABLE SHALL BE ANSI/TIA
CATEGORY 6A. PLACE WALL LOCATIONS IN A
SURFACE MOUNTED SINGLE-GANG BACK BOX
WITH A WHITE TWO PORT FACEPLATE.
2. THE UNUSED TOP PORT OF THE FACEPLATE
IS TO BE FILLED WITH A BLANK KEYSTONE
JACK INSERT.
3. PLACE WALL LOCATIONS CENTERED BELOW
WHITEBOARD AT STANDARD HEIGHT.
4. LOCATIONS WITHOUT WHITEBOARDS,
CENTER THE INSTALLATION ON THE WALL AT
STANDARD HEIGHT.
5. ALL CABLE BELOW CEILING SHALL BE
CONCEALED IN RACEWAY PROVIDED BY
CONTRACTOR.
6. PROVIDE CEILING LOCATION WITH SERVICE
LOOP LONG ENOUGH TO REACH THE
FARTHEST LOCATION IN THE ASSOCIATED
ROOM. SECURELY FASTEN SERVICE LOOP TO
STRUCTURE.
7. TERMINATE ALL CATEGORY 6A CABLES ON
WHITE 8P/8C (RJ45) JACKS.
8. LOCATION OF BUS BLOCKS ARE ESTIMATED,
USE BEST PRACTICES FOR INSTALLATION
LOCATION.
9. FOR ESTIMATES ASSUME ALL CABINETS
NEED GROUNDING.
C O N V E R G E N T 6197 Miller Road Suite 4 Swartz Creek, MI 48473
Phone: 810.720.3820 www.ctpartners.net
T E C H N O L O G Y P A R T N E R S
TECHNOLOGY DESIGN I CONSULTING I PLANNING
1/24/2025 DESIGN DLF
12/17/2024 DESIGN EGH
DATE ISSUE AUTHOR
SWARTZ CREEK
COMMUNITY SCHOOLS
STRUCTURED CABLING
SWARTZ CREEK HIGH
SCHOOL
HS-T101A
T101A
NTS
HIGH SCHOOL UNIT A
KEYMAP
| Sheets and Views |
| HS-T101A |