This is a technical drawing showing structured cabling plans for Unit A of Swartz Creek High School, prepared by Convergent Technology Partners. The drawing details the installation specifications for Category 6A UTP cabling throughout the school building, including classroom and corridor locations. The document is dated January 24, 2025, with an earlier design date of December 17, 2024.

The drawing includes detailed specifications for cable installation, requiring all UTP cable to be ANSI/TIA Category 6A standard, with wall locations using surface-mounted single-gang back boxes and white two-port faceplates. Technical requirements include concealed raceway installation below ceiling, service loops for ceiling locations, white 8P/8C (RJ45) jack terminations, and grounding requirements for telecom cabinets. The floor plan shows multiple classrooms, corridors (300 and 350), and includes a symbol legend indicating UTP locations, ceiling UTP locations, telecom cabinets, new telecom bus-bars, existing bus-bars, and old computer lab areas.

View the file

Other files

Show all 19

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

UNIT D

UNIT A

UNIT A

UNIT B

0' 5' 10' 20' 30' 40' 50'

NOT TO SCALE - BAR SCALE APPROXIMATE. FIELD VERIFY ALL DIMENSIONS

TGB

SYMBOL LEGEND

UTP LOCATION, QTY AS

NOTED

CEILING UTP LOCATION,

QTY AS NOTED

TELECOM CABINET

NEW TELECOM BUS-BAR

EXISTING BUS-BAR

OLD COMPUTER LAB

TGB

B C

A D

E F

G

GENERAL NOTES

1. ALL UTP CABLE SHALL BE ANSI/TIA

CATEGORY 6A. PLACE WALL LOCATIONS IN A

SURFACE MOUNTED SINGLE-GANG BACK BOX

WITH A WHITE TWO PORT FACEPLATE.

2. THE UNUSED TOP PORT OF THE FACEPLATE

IS TO BE FILLED WITH A BLANK KEYSTONE

JACK INSERT.

3. PLACE WALL LOCATIONS CENTERED BELOW

WHITEBOARD AT STANDARD HEIGHT.

4. LOCATIONS WITHOUT WHITEBOARDS,

CENTER THE INSTALLATION ON THE WALL AT

STANDARD HEIGHT.

5. ALL CABLE BELOW CEILING SHALL BE

CONCEALED IN RACEWAY PROVIDED BY

CONTRACTOR.

6. PROVIDE CEILING LOCATION WITH SERVICE

LOOP LONG ENOUGH TO REACH THE

FARTHEST LOCATION IN THE ASSOCIATED

ROOM. SECURELY FASTEN SERVICE LOOP TO

STRUCTURE.

7. TERMINATE ALL CATEGORY 6A CABLES ON

WHITE 8P/8C (RJ45) JACKS.

8. LOCATION OF BUS BLOCKS ARE ESTIMATED,

USE BEST PRACTICES FOR INSTALLATION

LOCATION.

9. FOR ESTIMATES ASSUME ALL CABINETS

NEED GROUNDING.

C O N V E R G E N T 6197 Miller Road Suite 4 Swartz Creek, MI 48473

Phone: 810.720.3820 www.ctpartners.net

T E C H N O L O G Y P A R T N E R S

TECHNOLOGY DESIGN I CONSULTING I PLANNING

1/24/2025 DESIGN DLF

12/17/2024 DESIGN EGH

DATE ISSUE AUTHOR

SWARTZ CREEK

COMMUNITY SCHOOLS

STRUCTURED CABLING

SWARTZ CREEK HIGH

SCHOOL

HS-T101A

T101A

NTS

HIGH SCHOOL UNIT A

KEYMAP