About this file

This is an electrical engineering design drawing for Marshalling Cabinet #4, part of the Fermilab UIP Subproject 2 Kautz Road Substation Replacement project. The detailed technical drawing specifies a wall-mount enclosure with precise dimensions of 60" x 36" x 8", featuring white interior and ANSI 61 gray exterior finish. The bill of materials includes 600 Phoenix sectional terminal blocks (item 1603), 3 DIN rails (item 1604), 4 white Panduit wire ducts (item 1605), 16 Phoenix marker strips (item 1606), 16 Phoenix end covers (item 1607), and 32 Phoenix end clamps (item 1608). The drawing provides a comprehensive layout with side, top, and front view perspectives, including specific details for 16 individually labeled connection points (N1-N16) with precise measurements and mounting specifications. The document is dated June 19, 2025, and is marked "NOT FOR CONSTRUCTION" with a project location in Chicago, Illinois.

View the file

Other files

File Type Posted
Amend 05 to RFP KRS-369604-JK.pdf PDF
Questions on E-House RFP_R5_2025_1003.xlsx XLSX spreadsheet
MC1.pdf PDF
E-B2.PDF PDF
KRS Site Construction - Structural Drawings.pdf PDF
ComEd Battery and Fermilab Battery Monitoring System Specifications.pdf PDF
REVISED Attachment 10-PUR-466_Proposal Certifications_r4_09.24.25.pdf PDF
Amend 04 to RFP KRS-369604-JK.pdf PDF
E-2.pdf PDF
FermiForward-Approved Color Palette.pdf PDF
2025 - Security and Access Control r2.docx DOCX document
MC2.pdf PDF
E-337.pdf PDF
KRS Site Construction - Civil Drawings.pdf PDF
KRS Geotechnical Data Report.pdf PDF
REVISED Attachment 13-SARC_Subcontractor Annual RepsCerts Rev 5.pdf PDF
Hollow Metal Door - Rated Hardware Schedule.pdf PDF
Card Reader Details.pdf PDF
MC3.pdf PDF
E-339.pdf PDF
E-338.pdf PDF
E-3.pdf PDF
Amend 03 to RFP KRS-369604-JK.pdf PDF
E-Control House Site Visit-Sign-in Sheet.pdf PDF
Fermilab Site Map-Kautz Road Substation.pdf PDF
Amend 02 to RFP KRS-369604-JK.pdf PDF
Business Visitor Registration Instructions and Directions.pdf PDF
E-House_QandA_Amend02.pdf PDF
REVISED Attachment 13-SARC_Subcontractor Annual RepsCerts Rev 4.pdf PDF
Amend 01 to RFP KRS-369604-JK.pdf PDF
Attachment 2 - 010010_General_Requirements_3_2025 FFDG_.pdf PDF
Attachment 4 - 013300 Submittals FermiForward (3).pdf PDF
Attachment 6 -017900 - DEMONSTRATION AND TESTING.pdf PDF
Attachment 11 - 2025 Onsite NonProfessional Services Insurance Requirements.pdf PDF
Attachment 12 - PUR-568_Cost Accounting Standard Notices and Certification.pdf PDF
1. RFP for E-House.pdf PDF
Attachment 1 - Sample Subcontract .pdf PDF
Attachment 7-1 Pages 1-62 from 3-5-207C Dwg IFBr2.pdf PDF
Attachment 9 - FFDG General Terms and Conditions for Commercial Products and Commercial Services (01.2025).pdf PDF
Attachment 3 - 013100_ESH_Requirements_04-2025 FFDG.pdf PDF
Attachment 5 - 014100 Quality Requirements - March 2025 FermiForward.pdf PDF
Attachment 7-2 Pages 63-113 from 3-5-207C Dwg IFBr2.pdf PDF
Attachment 8 - 5-207C Control House Specs IFBr2.pdf PDF
Attachment 10 - PUR-466_Proposal Certifications_r3_06.23.25.pdf PDF
Attachment 13 -SARC_Subcontractor Annual RepsCerts Rev 3.pdf PDF
Attachment 14 SMALL BUSINESS SUBCONTRACTING PLAN template Far 52.219-9.pdf PDF
Show all 46

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

36.000

60.000

TOP VIEW

FRONT VIEW SIDE VIEW

SUBPANEL

9.126 0.905

1607 (QTY 1)

1608 (QTY 2)

PER GROUP

1603 (QTY 600)

GROUPS OF 40

3 X 3 PAN

D

U

IT

3 X 3 PAN

D

U

IT

3 X 3 PAN

D

U

IT

3 X 3 PAN

D

U

IT

N2

N3

N4

N7

N8

N9

N12

N13

1604 (QTY 3)

1.250 TYP.

1606 (QTY 15)

3 X 3 PAN

D

U

IT

3 X 3 PAN

D

U

IT

N5

N6

N10

N11

N15

N16

N14

Se p

, 2

- 7 :3

8A M

A ut oD es k D oc s:

\A R

U P\

-0

Fe rm iL ab C am pu s In fra st ru ct ur e\

Pr oj ec t F ile s\

_W

IP

M od el s\ E

- E le ct ric al \S he et s\ M

C #4

.d w g

90% FINAL DESIGN06/19/250 06/19/25

06/19/25

06/19/25

06/19/25

D. GURALCHUK

H. LOBO

R. SIERRA

R. TANDEL

NTS

3-5-207

ELECTRICAL

0 J U

N E

MC#4MARSHALLING CABINET #4

2) INTERIOR FINISH TO BE - GLOSS WHITE

EXTERIOR FINISH TO BE - SATIN ANSI 61 GRAY

UNLESS OTHERWISE NOTED:

1) ALL DIMENSIONS ARE IN INCHES.

BILL OF MATERIALS

ITEM DEVICE STYLE NUMBER

3044076 600

QTY MFR

PHOENIX

DESCRIPTION

SECTIONAL TERMINAL BLOCK, TYPE UT 2.5.

N1

NAMEPLATE LIST

NO. TEXT

3/8"

SIZE

2X6"

THIRD LINESECOND LINE

CABINET #4

FIRST LINE

TERMINATION

UNLESS OTHERWISE NOTED: -NAMEPLATE MOUNTING SHALL BE VIA DOUBLE ADHESIVE TAPE.

-COLOR SHALL BE WHITE WITH BLACK TEXT.

1604 DRS35X7.5S 3 MFR. DIN RAIL, STEEL, SLOTTED, 35MM H X 7.5MM D, CUT 56.78"

LONG

1605 G3X3WH6 4 PANDUIT WIRE DUCT, 3 X 3, WHITE, CUT 56.78" LONG

1601 A603608LP 1 HOFFMANHOFFMAN WALL-MOUNT ENCLOSURE, TYPE 12, 60" X 36" X 8",

WHITE INSIDE WITH ANSI 61 GRAY FINISH OUTSIDE.

1602 A60P36 1 HOFFMANPANEL, BACK, MOUNTING, 57x33

1606 1004076 16 PHOENIX MARKER STRIP, TYPE UBE/D WITH ES KMK-3, GRAY SNAP-ON

1607 3047028 16 PHOENIX END COVER, TYPE D-UT 2.5/10, FOR USE ON TYPE UT

TERMINAL BLOCKS.

1608 0800886 32 PHOENIX END CLAMP, E/NS 35N

N2 1/4".75X1.5"411

N3 1/4".75X1.5"412

N4 1/4".75X1.5"413

N5 1/4".75X1.5"414

N6 1/4".75X1.5"415

N7 1/4".75X1.5"421

N8 1/4".75X1.5"422

N9 1/4".75X1.5"423

N10 1/4".75X1.5"424

N11 1/4".75X1.5"425

N12 1/4".75X1.5"431

N13 1/4".75X1.5"432

N14 1/4".75X1.5"433

N15 1/4".75X1.5"434

N16 1/4".75X1.5"435

35 East Wacker Drive Suite 1800 Chicago IL 60601 USA t: +1 312 849 5610 www.arup.com

SCALE:

REVISIONS PROJECT NO.

SHEET NO.

REVISION NO.

DESIGNED

DRAWN

CHECKED

APPROVED

CONCEPT

DISCIPLINE REVIEW

ENG. REVIEWED

ISD APPROVED

SUBMITTED

A/E CONSULTANT FERMILAB DATE

N O

T

FO

R C

O N

ST

R

U C

TI

O

N

Arup US, Inc.

UIP - SUBPROJECT 2

KAUTZ ROAD SUBSTATION REPLACEMENT

DESCRIPTIONS

DATE

DATEREV.

AutoCAD SHX Text N1

Sheets and Views
Layout1

File details come from the government source that posted it. Updated .