Kautz Road Substation Replacement Prefabricated Control House Building and associated Arc Safe 13. 8kV Medium Voltage Switchgear
Solicitation number
KRS-369604-JK
Issued by

About this file

This document is a Battery Monitoring System (BMS) Specification and Statement of Work (SOW) for a project at Fermi Lab's New 13kV Building. The specification requires installing a BMS for two new 125V station batteries, each with 58 vented lead-acid cells. The BMS will use Phoenix Broadband's Power Agent and must include individual cell monitoring, with sensors using crimped connections and tab washers. The system requires IP communication to ComEd's SCADA/IT system and must monitor parameters including string voltage, cell voltage, float current, discharge current, DC ripple current, cell temperature, cell internal resistance, and electrolyte levels.

Key technical requirements include wall-mounting the BMS controller near the battery, using a junction box with air vents, installing a CAT5 cable to fiber converter, obtaining DC power from the DC panel, and implementing communication protocols like SNMP and TCP/IP. The specification mandates corrosion-resistant and flame-resistant materials, a ground detection system, and detailed alarm capabilities. The installation also requires a placard stating that existing battery and charger preventive maintenance records must continue to be obtained and recorded. The project involves coordination between ComEd's Substation Engineering, Equipment Standards, and SCADA/IT teams, with final configuration and point assignments to be completed by Equipment Standards.

View the file

Other files

File Type Posted
Amend 05 to RFP KRS-369604-JK.pdf PDF
MC3.pdf PDF
E-339.pdf PDF
E-3.pdf PDF
2025 - Security and Access Control r2.docx DOCX document
E-337.pdf PDF
REVISED Attachment 10-PUR-466_Proposal Certifications_r4_09.24.25.pdf PDF
E-338.pdf PDF
Hollow Metal Door - Rated Hardware Schedule.pdf PDF
REVISED Attachment 13-SARC_Subcontractor Annual RepsCerts Rev 5.pdf PDF
KRS Site Construction - Civil Drawings.pdf PDF
KRS Geotechnical Data Report.pdf PDF
KRS Site Construction - Structural Drawings.pdf PDF
MC1.pdf PDF
E-B2.PDF PDF
Card Reader Details.pdf PDF
Questions on E-House RFP_R5_2025_1003.xlsx XLSX spreadsheet
MC2.pdf PDF
FermiForward-Approved Color Palette.pdf PDF
MC4.pdf PDF
E-2.pdf PDF
Amend 04 to RFP KRS-369604-JK.pdf PDF
Amend 03 to RFP KRS-369604-JK.pdf PDF
E-Control House Site Visit-Sign-in Sheet.pdf PDF
Amend 02 to RFP KRS-369604-JK.pdf PDF
Business Visitor Registration Instructions and Directions.pdf PDF
E-House_QandA_Amend02.pdf PDF
Fermilab Site Map-Kautz Road Substation.pdf PDF
REVISED Attachment 13-SARC_Subcontractor Annual RepsCerts Rev 4.pdf PDF
Amend 01 to RFP KRS-369604-JK.pdf PDF
Attachment 7-2 Pages 63-113 from 3-5-207C Dwg IFBr2.pdf PDF
Attachment 14 SMALL BUSINESS SUBCONTRACTING PLAN template Far 52.219-9.pdf PDF
Attachment 13 -SARC_Subcontractor Annual RepsCerts Rev 3.pdf PDF
Attachment 9 - FFDG General Terms and Conditions for Commercial Products and Commercial Services (01.2025).pdf PDF
Attachment 3 - 013100_ESH_Requirements_04-2025 FFDG.pdf PDF
Attachment 10 - PUR-466_Proposal Certifications_r3_06.23.25.pdf PDF
Attachment 1 - Sample Subcontract .pdf PDF
Attachment 7-1 Pages 1-62 from 3-5-207C Dwg IFBr2.pdf PDF
Attachment 8 - 5-207C Control House Specs IFBr2.pdf PDF
Attachment 6 -017900 - DEMONSTRATION AND TESTING.pdf PDF
Attachment 2 - 010010_General_Requirements_3_2025 FFDG_.pdf PDF
Attachment 4 - 013300 Submittals FermiForward (3).pdf PDF
1. RFP for E-House.pdf PDF
Attachment 11 - 2025 Onsite NonProfessional Services Insurance Requirements.pdf PDF
Attachment 5 - 014100 Quality Requirements - March 2025 FermiForward.pdf PDF
Attachment 12 - PUR-568_Cost Accounting Standard Notices and Certification.pdf PDF
Show all 46

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

REVISES SPEC. DATED 01-15-2013

06-18-2013 06-18-2013 C-1504 C-1504 PAGE 1 of 4 PAGE 1 of 4

COMMONWEALTH EDISON COMPANY

SYSTEM STANDARD

NEW BATTERY INSTALLATION

1. SCOPE

1.1. This specification covers the procedures to be followed when installing new stationary lead-acid storage batteries.

2. RECEIVING

2.1. Immediately upon delivery of the battery, examine for possible damage caused in transit.

Damaged cartons or packing material stained from leaking acid would be an indication of rough handling and should be noted on delivery of receipt.

2.2. Damaged or stained cartons should be opened immediately and contents inspected. If cell damage is found request an inspection by the carrier, file a damage claim, and notify the department responsible for purchasing the battery.

3. UNPACKING

3.1. Support the cells from the bottom when handling and unpacking. Never lift cells by their posts.

At all times exercise care when handling cells to prevent scratching of plastic jars and covers which could result in stressing and rupturing of the jar.

3.2. At the first opportunity, check the electrolyte level in each cell. Electrolyte levels may range from the high level line to slightly below the low level line. If the plates are covered but the level is below the low level mark, make no water additions until cells have been on float charge for one week. If the electrolyte level is below the top of the plates with less than 1/2" of the plate exposed, contact the manufacturer immediately for the purpose of adding sulphuric acid. If the level is 1/2" or more below the top of the plates, file a claim for concealed damage against the carrier and order a new cell.

3.3. Make certain that all accessories (intercell connectors, bolts, nuts, washers, terminal plates, cables, and flame arresters) have been received. If parts are missing contact the manufacturer.

4. STORAGE

4.1. The battery should be installed and given its initial charge as soon after receipt as possible.

4.2. The storage interval from date of shipment to date of initial charge should not exceed six (6) months for lead-calcium type batteries, with boost charges repeated at each additional six (6) month storage interval.

4.3. Connect the cells with temporary jumpers so that the initial boost or charge can be given to individual cells, group of cells, or preferably to the entire battery. Lead-calcium cells should be charged at 2.33 volts per cell (1.5 volts per cell if Nickel Cadmium) for approximately 144 hours (six days). This time period is for cell temperatures of 70°F to 90°F.

C-1504 C-1504 PAGE 2 of 4 PAGE 2 of 4

COMMONWEALTH EDISON COMPANY

SYSTEM STANDARD

5. RACKS

5.1. Assemble racks in accordance with manufacturer's instructions. To provide sufficient stability, two and three tier racks must be securely anchored to either the floor or wall.

5.2. Metal racks shall be connected solidly to the station grounding system.

6. PLACEMENT OF CELLS

6.1. Determine beforehand the proper location of the positive and negative terminal of the battery so correct positioning of the initial cell on each rack row can be established.

6.2. Mark the center of the rack, determine the number of cells to be placed in each row, and proceed to place the first cell at the center working out to the two ends.

6.3. The standard spacing between cells is 1/2" at the top of the jars.

6.4. Cells shall be installed with the plates perpendicular to rack length.

6.5. Check so that the positive (+) terminal of each cell adjoins the negative (-) terminal of the next cell.

7. CONNECTING CELLS

7.1. The cell posts have been coated with corrosive resistant grease at the factory. Remove this grease from the contact surface with a dry cloth, neutralize the area with a bicarbonate and water solution and dry thoroughly. Clean the post contact surface with a plastic or fiber bristle brush or "scotch brite" scouring pad to provide a bright, shiny finish. Immediately coat with NO-OX-ID grease. Use care so as not to remove the lead plating and expose any bare copper.

7.2. The contact surface of the lead plated intercell connectors should be gently brushed the same as the posts until a bright, shiny surface is obtained and then apply a thin coat of NO-OX-ID grease to the contact surface of the intercell connector. If required, heat the NO-OX-ID grease to a cream-like consistency on an electric hot plate (160°F to 185°F) using extreme care not to overheat.

7.3. Install intercell connectors, adjust them to a level position and finger tighten hardware. Tighten the connections using two insulated wrenches in which one of them is a torque wrench (inch -pounds). Initially, torque the connections within each row to five inch-pounds below the manufacturer's recommended value.

7.4. After all the calls within the row have been connected, re-torque the connections to the manufacturer's recommended value.

7.5. Complete connecting of cells by installing necessary inter-row, inter-tier or inter-rack cable connectors. Do not connect battery to charger or bus at this time.

7.6. Before connecting the main terminals and charger leads to the battery, re-check to be certain that the cells are connected positive (+) to negative (-) throughout the battery string and then measure the total voltage of the cells in the battery. The measurement should be equal to the voltage of one of the cells (2.05 volts) times the number of cells. If the reading is less than this value, one or more of the cells are installed backwards.

7.7. Do not cutover battery and charger to station load via disconnect switch (if applicable) until

C-1504 C-1504 PAGE 3 of 4 PAGE 3 of 4

COMMONWEALTH EDISON COMPANY

SYSTEM STANDARD

sections 8.0 thru 10.0 are completed.

8. COMPLETING INSTALLATION

8.1. Remove cell vent caps and install the flame arresters.

8.2. Install plastic cell numbers and battery terminal polarity labels to cell jars. The positive terminal cell is usually designated as cell #1 in the series string. NOTE: Do not cover up cell electrolyte level line area with labels.

8.3. Mount hydrometer holder on wall close to battery.

8.4. "No Smoking" signs should be posted in the battery area.

8.5. Do not cutover battery and charger to station load via disconnect switch (if applicable) until sections 9.0 thru 10.0 are completed.

9. INITIAL CHARGE

9.1. As soon as possible after installation, the battery should be given an initial charge of 2.33 volts per cell for a lead-calcium battery (135.1 volts for a 58 cell battery) or 1.5 volts per cell for a Nickel Cadmium battery (54.0 volts for a 36 cell battery) for approximately 144 hours (six days).

If 144 hours is not feasible,72 hours is acceptable.

NOTE: Manufacturer’s recommended initial charge requirements may be followed in lieu of 9.1, but do not exceed 2.5 VPC (lead-calcium) at a maximum of 36 hours (cell temperatures between 60°F to 90°F) or when manufacturer recommended charge completion criteria is met.

9.2. On completion of this charge, a voltage and specific gravity reading of each cell should be taken and recorded.

9.3. Do not cutover battery and charger to station load via disconnect switch (if applicable) until section 10.0 is completed.

10. FINAL TEST AND INSPECTION

After the initial charge of the battery, at a minimum perform the following:

10.1. Measure and record overall battery float and equalize voltage at the terminals. Acceptable battery terminal voltages are as follows:

• Lead Calcium and Lead Selenium: 2.20-2.25 Volts per cell float and 2.33 Volts per cell equalize.

• Plante: 2.17-2.19 Volts per cell float and 2.33 Volts per cell equalize.

• Nickel Cadmium: 1.42-1.45 Volts per cell float and 1.50 Volts per cell equalize.

10.2. Check and adjust the charger current limit setting as required.

10.3. Check general appearance and cleanliness of battery and battery rack (Reference

IEEE-450-2010 Annex E for guidance).

10.4. Check for unintentional battery grounds.

10.5. Measure and record AC ripple volts at the battery terminals. Acceptable battery charger (per

EM12925) AC ripple:

10.5.1. Nominal charger output voltage 12/24/48: No greater than 30mV rms

10.5.2. Nominal charger output voltage 120/130: No greater than 100mV rms

10.5.3. Nominal charger output voltage 240/260: No greater than 200mV rms

C-1504 C-1504 PAGE 4 of 4 PAGE 4 of 4

COMMONWEALTH EDISON COMPANY

SYSTEM STANDARD

10.6. Check set points and operation of all charger alarms

10.7. Clean dust from charger cabinet, as required.

10.8. Measure and record cell-to-cell and terminal connection resistance (establishes baseline).

10.9. Measure and record internal impedance of each individual cell (establishes baseline).

10.10. At the completion of the prescribed testing and inspection, record the completion date.

10.11. Prior to final cutover of battery and charger to station load, verify that appropriate Battery &

Charger Preventative Maintenance (PM) are in place and active in records database (e.g.

Passport). Contact PM Coordinator, T&S PM SPOC and / or Battery SME for verification.

Once verification is completed, cutover battery and charger to station load. See 11.3 and 11.4 if installed by contractor.

NOTE: COMPLETION DATE OF THE FINAL TEST AND INSPECTION SHALL BE USED TO START

/ ANCHOR NEW BATTERY AND CHARGER PM RECORDS. SEE 11.3 AND 11.4 IF INSTALLED BY

CONTRACTOR.

11. RECORDS

11.1. Battery and charger nameplate information and final test and inspection completion date shall be entered in appropriate equipment database (e.g. CASCADE). See 11.3 and 11.4 if installed by contractor.

11.2. A copy of the final test and inspection record shall be retained by the Regional Battery Specialist and at the earliest opportunity, the final test and inspection record shall be entered in appropriate equipment database (e.g. CASCADE) and time stamped based on date of completion. See 11.3 and 11.4 if installed by contractor.

11.3. If installation, final test and inspection are to be performed by contractor, the contractor shall provide the following to the Project Manager, Regional Battery Specialist, Substation Engineering (Lead Responsible Engineer) and Equipment Standards IMMEDIATELY (within 10 days) after completion but no later than the first substation line cut-over:

11.3.1. Final test and inspection records

11.3.2. Battery and charger nameplate information

11.3.3. Battery and charger manufacturer acceptance test records.

11.3.4. Recorded date(s) of installation, final test and inspection completion.

Final cutover of battery and charger to station load shall be completed by Regional Battery Specialist.

11.4. If installation, final test and inspection are to be performed by contractor, the Regional Battery Specialist shall perform the following:

11.4.1. Review the contractor’s test and inspection results. Once deemed acceptable by the Regional Battery Specialist, the Regional Battery Specialist shall follow 11.1 & 11.2, and note the date of acceptance of the contractor’s test results. This date of acceptance shall be used to start / anchor new Battery and Charger PM Records.

NOTE: Regional Battery Specialist may choose to repeat tests prescribed herein to verify contractor’s test results.

11.4.2. Final cutover of battery and charger shall be completed by Regional Battery Specialist upon acceptance of all contractor test records and verification of active Preventative Maintenance Battery & Charger Records in records database (e.g. Passport).

REVISES SPEC. DATED 10-23-1995

11-04-2013 11-04-2013

EM12925 EM12925

PAGE 1 of 6 PAGE 1 of 6

COMMONWEALTH EDISON COMPANY

SYSTEM STANDARD

BATTERY CHARGERS

UTILITY TYPE

1. SCOPE

1.1. This specification covers stationary type battery chargers that are designed to supply direct-current power from an alternating current source, to float and equalize the charge to a lead-acid storage battery while simultaneously supplying power to the connected D.C. system load.

2. GENERAL SPECIFICATION

2.1. Chargers shall be in accordance with this specification and unless otherwise noted shall be in accordance with applicable ANSI, IEEE, and NEMA Standards of latest issue.

2.2. The charger shall be self-cooled, and designed to operate continuously at rated capacity in ambient temperatures of 0° to 50°C (32° to 122°F) and a maximum 95% relative humidity (without condensation).

3. TYPE

3.1. The charger shall be a solid state, constant potential, filtered type, using full wave silicon diode rectifiers. Rectifiers shall have surge protection.

3.2. The charger control circuit shall be the Magnetic-Amplifier or Silicon Controlled Rectifier (SCR) Type and shall be fully automatic.

4. RATING

4.1. AC input: The nominal AC input voltages shall be 120, 208, 240 or 480 volts.

4.2. DC output: The nominal DC output voltages shall be 12, 24, 32, 48, 125 or 250 volts.

5. ELECTRICAL REQUIREMENTS

5.1. The charger shall be self-protected with a means to limit output current to a safe value under any continuous load condition including a fully discharged battery without tripping AC or DC circuit breakers.

5.2. Separate and independent controls shall be provided for adjustment of the floating and equalizing voltage levels with a toggle switch to select the operating mode. Floating range shall be 2.21 Volts per Cell (VPC), ± 4% and equalizing range shall be 2.33 VPC, ± 4% (lead-acid batteries).

5.3. Chargers with a DC output rating of 20 amps or more shall be provided with load-sharing

EM12925 EM12925

PAGE 2 of 6 PAGE 2 of 6

COMMONWEALTH EDISON COMPANY

SYSTEM STANDARD

circuitry for parallel operation. The circuitry shall be such as to assure that the load is equally divided between two chargers of the same rating connected in parallel for all output levels.

5.4. Output voltage deviation shall not exceed ± ½% for floating voltage and ± 1% for equalizing voltage (for load changes from zero to full rated current, with AC supply voltage variation of ±10% and frequency variation of ±5%).

5.5. The charger shall be provided with a means to prevent the DC control circuit from drawing energy from the battery in case of loss of AC supply. Alarm lights and relays will present a slight load (typically less than 250 mA) to the battery.

5.6. The audible noise generated by the charger shall not exceed 60 dbA at 5 feet when measured in accordance with NEMA PE5-8.11.

5.7. The stability and response of the charger shall not exceed the limits specified in NEMA

PE5-8.12.

5.8. The AC and DC transient voltage withstand capabilities of the charger shall equal or exceed the values specified in the ANSI / IEEE C37.90a test as described in NEMA PE5-8.13.

5.9. The insulation withstand capability of the charger shall equal or exceed the values specified in

NEMA PE5-8.2.

6. ACCESSORIES

6.1. Equalization Control Timer: One 0-72 hour interval timer, manually adjustable, with positive acting relay which will automatically remove the equalizing charge and restore the floating charge.

6.2. AC Input Circuit Breaker: One 2-pole breaker for single-phase input or one 3-pole breaker for three-phase input, with thermal-magnetic trip elements in each pole. Interrupting capacity of the breaker shall be as specified in the inquiry. Chargers used in outdoor applications shall use magnetic type breakers to avoid nuisance tripping due to temperature variations.

6.3. DC Output Circuit Breaker: One 2-pole C8 with thermal-magnetic trip elements in each pole.

Chargers used in outdoor applications shall use magnetic type breakers to avoid nuisance tripping due to temperature variations.

6.4. DC Ammeter and DC voltmeter: Meters shall have 2% of full scale accuracy when mounted on the steel panel (Weston Model #301 or equivalent) and shall have external zero-adjust device.

Option: Replacement of analog DC-Ammeter and DC-Voltmeter with digital meters is acceptable only if the digital meters provide a ± 1% accuracy.

Ammeter: Range shall be 150% of the charger output rating.

Voltmeter: Range shall be approximately 120% of normal output voltage. The voltmeter (1000 ohms per volt) shall be paralleled with a wire-wound resistor such that the combined resistance

EM12925 EM12925

PAGE 3 of 6 PAGE 3 of 6

COMMONWEALTH EDISON COMPANY

SYSTEM STANDARD

shall be approximately 100 ohms per volt. See Table 1 below. The meter shall be connected directly to the battery side of the DC circuit breaker so as to monitor the battery voltage at all times independent of the DC breaker position. Voltmeter shall have a scale of two (2) volts / division.

Table 1. Ground Detection System - Resistor Values

Nominal Charger Voltage

DC Voltmeter Scale Resistor Value (Ohms)

Resistor Wattage (Watts)

12 20 3.3K 0.5 24 35 6.8K 1 32 50 8.2K 5 48 75 13K 5

130 160 33K 5

6.5. Ground Detection System: Which uses a toggle switch or two push-buttons to disconnect the

DC voltmeter from the output circuit and measure voltage from positive or negative to ground.

The resistors noted in Table 1 are in parallel to the Voltmeter and are based on ComEd calculations for the system’s critical resistance as of the date of this specification.

6.6. For SCR Type Chargers Only: A high DC voltage shutdown relay, energized from the charger side of the DC circuit breaker, which shall provide:

a. Charger shutdown by means of shunt trip device on the AC circuit breaker, or by disabling the control circuit of the SCR's.

b. Isolated form "C" contacts for Purchaser's alarm.

7. ACCESSORIES

7.1. The following accessories shall be provided .

a. A low DC voltage alarm relay, energized from the battery side of the DC circuit breaker and with isolated form "C" contacts for Purchaser's alarm.

b. A high DC voltage alarm relay, energized from the battery side of the DC circuit breaker and with isolated form "C" contacts for Purchaser's alarm.

c. An AC power failure alarm relay with isolated form "C" contacts for Purchaser's alarm.

d. A 6 to 10 second time delay for the alarms.

e. A high DC voltage shutdown circuit which automatically resets the charger after a high DC voltage condition has occurred. The reset interval and shutdown delays are adjustable.

The default setting is a 20 second delay before the high DC voltage shutdown occurs and the default delay setting is 60 minutes before the charger attempts to automatically restart.

EM12925 EM12925

PAGE 4 of 6 PAGE 4 of 6

COMMONWEALTH EDISON COMPANY

SYSTEM STANDARD

After the time delay, the charger shall turn back on and operate. If the high voltage is still there the charger shall cycle again. This will be a continuous cycle until the high voltage condition is cleared.

8. MECHANICAL REQUIREMENTS

8.1. Cabinet: The rectifiers, transformers and accessories shall be mounted in an indoor, self-ventilated, wall or floor mounted (as specified in inquiry) steel cabinet complete with dripproof cover.

The meters, controls and circuit breakers shall be mounted on the front, hinged panel of the cabinet. On floor mounted cabinet, they shall be a minimum of 36" above the floor. Floor mounting shall not block air entrance for convection cooling.

The steel cabinet shall have an acid and corrosion resistant finish, with undercoat and finish coat applied in accordance with accepted commercial practice. Preferred finish color shall be ANSI No. 61 light grey. Vendor may propose alternate finish color for approval.

8.2. Nameplates: Nameplate shall contain information in accordance with NEMA PE5-4.6, shall be made of metal and shall be mounted with rust-proof screws or rivets on front panel. The timer, float/equalize switch, ground detection switch, rheostats, meters and circuit breakers, shall be clearly identified. Name plates made of adhesive type Mylar material are optional. Two nameplates shall be provided, one inside the charger front door and one on the outside front door.

8.3. The total temperature limitations for insulating materials, buses, and connections shall not exceed those specified in NEMA PE5-4.10. Control and power conductor insulation shall be rated 600 Volts, 105°C maximum total temperature.

9. AUXILLARY WIRING

9.1. Control wire shall be terminated with insulated ring-tongue compression-type lugs, EM-40276.

Connections for external alarm or control shall be terminated on terminal block EM-19622, with provisions in side of cabinet for conduit entrance.

9.2. AC and DC power conductors shall be terminated with insulated ring-tongue compression-type lugs, EM-40276 and brought to terminals or terminal blocks suitable for terminating Purchaser's conductors with same type lugs.

9.3. The AC input and DC output terminals shall be located so that Purchaser's conductors can be installed in the cabinet from conduit entrances to respective AC or DC terminals as follows:

a. Without being forced to be in contact with transformers, rectifiers or other heat sources;

b. Without requiring sharp bends near the terminals;

EM12925 EM12925

PAGE 5 of 6 PAGE 5 of 6

COMMONWEALTH EDISON COMPANY

c. With conduit entrance on one side for DC output conductors

d. With conduit entrance on other side and on bottom for AC power input conductors.

10. INSPECTION AND TESTS

10.1. Purchaser reserves the right to make factory inspection (as set forth in ComEd Exhibit "A") before shipment of equipment.

10.2. The following production tests shall be made in accordance with NEMA PE5 and reported in accordance with EM-10011: Dielectric, Voltage Adjustment, Voltage Regulation, Current Limit, and Ripple Voltage. In addition, tests associated with the specific requirements of this specification shall be made such as but not limited to the Ground Detection System and alarms.

11. SHIPPING

11.1. Packaging, handling, and routing shall conform to the conditions set forth in ComEd Exhibit "A".

11.2. Containers and packing slips shall be clearly marked to indicate the contents, ComEd Purchase

Order Number, and any other pertinent information, as requested on Purchase Order, to fully describe the contents.

12. DRAWINGS, INSTRUCTION BOOKS AND SPARE PARTS LIST

12.1. Unless otherwise specified in the inquiry, Vendor shall forward within 30 days after receipt of order and for Purchasers' record only, four copies of drawings necessary to show the physical requirements, electrical ratings, connections and schematic diagrams.

12.2. Drawings, Instruction Books, and Parts List shall be furnished in accordance with EM-10011.

Instructions books shall contain installation instructions, theory of operation, trouble shooting instructions with typical component operating currents and voltages, list of replaceable parts, and limited life components.

12.3. One Instruction Book shall be furnished with the equipment.

12.4. Production test reports shall be forwarded as soon as available.

13. SUPPLEMENTARY SPECIFICATIONS

13.1. The equipment shall be furnished in accordance with the following Purchaser's specifications:

Exhibit "A" General Conditions

EM-10011 Manufacturers Drawings, Test Reports, Instruction Books, and Parts List

EM-10013 General Drawing Guidelines for Equipment

EM-19622 Technical Blocks

EM12925 EM12925

PAGE 6 of 6 PAGE 6 of 6

COMMONWEALTH EDISON COMPANY

EM-40275 Uninsulated Copper Lug Connectors

EM-0276 Insulated Copper Lug Connectors

C-2324 Point-to-Point Style of Connections for Vendor's Wiring Diagrams

C-2325 General Wiring Requirements

13.2. Approved vendor part numbers to be in accordance with the following:

EM-12917 Substation Battery Chargers (Utility Type Only)

14. APPROVED VENDOR DOCUMENTS

14.1. F2-CE/U – LaMarche Vendor Specification meeting EM12925 requirements

15. INFORMATION TO BE FURNISHED IN PROPOSALS

15.1. Proposals shall confront to the conditions set forth in ComEd Exhibit "A".

15.2. Proposals shall include a complete description of the equipment offered, technical information and prices as follows:

a. Price, F.O.B. destination.

b. Delivery time after receipt of order.

c. Outline drawing showing dimensions, instrument and control device location on front panel, mounting details and dimensioned locations for side, or bottom conduit entrances which will permit installation of Purchaser's conductors without interference with transformers etc.

d. Weight, net and shipping.

e. Schematic diagram.

f. Taps on transformer.

g. Rectifier element type, input and output rating.

h. List of limited life components and their recommended replacement time intervals.

i. Technical data on the proposed unit with measurements made in accordance with NEMA

PE-5:

• Power Factor Efficiency Audible Noise

• Electro-magnetic interference, conducted and radiated, including distortion imposed on AC source

• Ripple voltage

• Stability and dynamic response

• Heat loss at rated load, BTU/hour

ESS-W407-4 Fermi Lab Battery Monitoring System Specification

PROJECT DESCRIPTION:

A new Battery Monitoring System (BMS) for the 125V Battery system located at ESS-W407-4 Fermi Lab is required. There will be a total of two batteries, with a BMS for EACH.

Each Station Battery will consist of a 58 cell vented lead acid battery. BMS monitoring will have an IP communication connection to the ComEd SCADA/IT system. See Figure 1.

New Battery: TBD

Figure 1. General Battery Monitoring Schematic

DEFINITIONS:

Battery Monitoring System (BMS) – Composed on all necessary controllers and peripherals necessary to accomplish the intent of this specification.

Battery Sensor – Phoenix Sensor module mounted on or near battery cell.

REQUIREMENTS:

The BMS shall use Phoenix Broadband BMS PBT-PA-BMS-SC3 as a baseline with the following delta requirements.

Performance

1. Measured parameters (minimum):

a. String Voltage

b. Cell Voltage

c. String Float Current

d. Discharge Current [ Need Discharge current sensor..preferred split core]

ESS-W407-4 Fermi Lab Battery Monitoring System Specification Page 1 of 3 Rev N/C.11-13-2014

ComEd / Phoenix Broadband Limited Only

e. DC Ripple Current

f. Cell / Ambient Temperature

g. Cell Internal ohmic value

h. Cell Electrolyte level (high/low signal)

Design and Construction

2. Physical Interfaces:

a. Communication Port: RJ-45 connector.

b. Alarm Output Port: RS-485 Port or RJ-45 Port

c. User Setup Interface port: USB 3.0 or RJ-45.

d. Power Input: 3-pin plug-in screw terminal block

e. Mounting: The BMS controller shall be Wall mountable near battery.

3. Corrosion Resistance. Metals and alloys used in the BMS that are exposed to corrosive environmental conditions shall be corrosion resistant or metallurgically processed to resist corrosion. Dissimilar metal combinations that promote corrosion through galvanic action shall be insulated to prevent corrosion.

4. Flame Resistant. Wherever possible, materials used shall be flame resistant. Plenum CAT5e cables shall be used.

5. Battery Sensors. Sensor circuit boards shall be conformally coated. In addition, sensor housing shall be appropriately sealed such that no electrolyte or foreign debris can enter the cavity (hermitic seal is not required).

a. Battery sensors shall use crimped connections with associated tab washers.

b. Phoenix Broadband shall provide the appropriate tab washers suitable for the Battery design.

c. In addition, in case the battery design allows for it, Phoenix broadband shall include appropriate fitting hardware to fasten the tab washers onto spare holes in the battery posts (ref TDC 550 Clearing).

d. Include THREE spares for Battery Sensors and Electrolyte Sensors.

Power Requirements

6. Input Voltages. The BMS shall be capable of operating from the DC powered battery bus that consists of nominal supply voltages of 125 Vdc. DC-to-DC converter can be used to accomplish this.

Communications

7. Protocols. The BMS shall be capable of SNMP and TCP/IP at a minimum. DNP3 capability is desired.

8. Alarms/Discretes.

a. The BMS shall be capable of providing three Alarm outputs at a minimum via the Alarm Output

Port defined herein.

b. The BMS shall be capable of providing hi/low alarms for each measured parameter defined herein.

c. Alarm outputs shall be programmable by user.

ESS-W407-4 Fermi Lab Battery Monitoring System Specification Page 2 of 3 Rev N/C.11-13-2014

d. Programmable Alarm outputs capable of combining different measured parameters into ‘AND’ conditions are desired.

BMS Internal Software. The BMS shall be capable of working with Windows XP Service Pack 3 operating systems or greater. In addition, there shall be security features to restrict access to monitoring programmable features.

e. The BMS shall have non-volatile memory such that with loss of power or communication, the BMS shall retain all user defined settings and alarm thresholds/outputs.

f. Prior to entering any menu or web server imbedded within the BMS, an Exelon web banner shall be displayed as follows: “This Battery Monitoring System and its information are to be utilized for official Exelon (Company) business conducted by the Company’s authorized users. Every user must adhere to all Company policies relating to the use of electronic resources and there should be no expectation of privacy while using any Exelon electronic resource, including this Battery Monitoring System. The Company reserves and exercises its right to monitor, record, analyze and disclose all communications. Use of this system constitutes consent to these terms. “

Hardware Delivery:

• TBD

Point of Contacts:

• PROJECT MANAGER - TBD

• Hugo Castaneda – T&S Equipment Standards (630-442-2349) hugo.castaneda@comed.com

Request for Proposal:

Battery Monitor System proposal/quote from Phoenix Broadband that meets this specification shall be provided. The quote shall reference this specification and include the following:

a. Adherence to hardware delivery date requirement

b. Two Quotes

i. A single quote for material. The quote shall include pricing for all material (e.g. peripherals, controller, etc) required to accomplish the intent of this specification. Quote shall include PO placement need date. Quote shall include unique Phoenix Part/Kit number that identifies the BMS as described herein. This part/kit number will be used for placing PO.

Quote shall include (3) spare Sensor Monitors and (3) spare Electrolyte sensors.

ii. A single quote for installation supervision and commissioning services.

c.

References:

• TSS 118 Wallace BMS installation drawing 118E-301B

• TDC 550 Clearing BMS installation

ESS-W407-4 Fermi Lab Battery Monitoring System Specification Page 3 of 3 Rev N/C.11-13-2014 mailto:hugo.castaneda@comed.com

ESS-W407-4 Fermi Lab Battery Monitoring System Specification / Statement of Work (SOW)

Project Description:

Install a Battery Monitoring System (BMS) and communications EACH new 125V Battery Systems located at Fermi Lab – New 13kV Building. BMS monitoring will have an IP communication connection to the ComEd SCADA/IT system. Note if there will be multiple Batteries, each battery system will contain a BMS.

Requirements:

Install a BMS consisting of the Phoenix Broadband Power Agent. The following are the required interfaces (see Figure 1):

1. BMS installation is on all Station Battery cells. The BMS will consist of individual monitors with separate leads to each cell posts. [PROVIDED BY OEM]

2. Wall mount Battery Monitor controller near battery.

3. Install a wall mounted junction box or small cabinet for Battery Monitor Controller.

Junction box shall have air vents. [PROVIDED BY CONTRACTOR OF CHOICE]

4. CAT 5 cable to Fiber converter required from the BMS controller to the SCADA/IT cabinet communication line. [PROVIDED BY CONTRACTOR OF CHOICE]

5. DC Power supply from DC Panel to BMS Controller (Conduit Line) is required. This shall power the Battery Monitor and Media Converter (RMC 40). [PROVIDED BY CONTRACTOR

OF CHOICE]

6. Final test and checkout of BMS is required. Procedures to be provided by Equipment standards.

7. Battery sensors shall use crimped connections with associated tab washers.

a. OEM (Phoenix Broadband) shall provide the appropriate tab washers suitable for the

Battery design. [PROVIDED BY OEM]

b. In addition, in case the battery design allows for it, a design option shall be included for appropriate fitting hardware to fasten the tab washers onto spare holes in the battery posts (ref TSS 78 Franklin Park). [PROVIDED BY CONTRACTOR OF CHOICE]

8. Required Signage: An approximately 8” (W) x 6” (H) placard shall be mounted on Battery Monitoring Cabinet. It shall have a white background with black lettings. The wording shall match that of Figure 1. [PROVIDED BY CONTRACTOR OF CHOICE]

ESS-W407-4 Fermi Lab Battery Monitoring System Specification / SOW Page 1 of 4 Rev N/C. 11-13-2014

Figure 1 - Required Placard

Figure 2. General Battery Monitoring Schematic

Statement of Work:

1. Engineering drawings to be completed by engineering contractor of choice with guidance and overview provided via ComEd Substation Engineering & Equipment standards.

2. Procurement of all other materials to be done by ComEd (or by Contractor of Choice).

3. Connect the BMS Controller to local Ethernet Network (remote access). Assign BMS

Controller an IP Address.

4. Route cable from BMS Controller to SCADA / IT Switch interface using fiber Ethernet media converter.

5. SSC and TG Support required

6. SCADA / IT to assign IP Address, SCADA points and data points for PI Historian. Equipment

Standards shall coordinate this effort.

Page 2 of 4 Rev N/C. 11-13-2014

Recommendations:

1. Installation of Battery Monitor System be done concurrently with Station Battery install (if

Station Battery will be replaced).

Point of Contacts:

1. Hugo Castaneda – ComEd T&S Equipment Standards (630-442-2349) hugo.castaneda@comed.com

2. Greg Voice – ComEd T&S Equipment Standards greg.voice@comed.com

3. Steve Cassidy – Phoenix Broadband (215-317-4285) steve@phoenixbroadband.com

Proposals:

• Battery Monitor quote from Phoenix Broadband shall be obtained. TBD.

References:

1. TDC 550 Clearing drawings

Adobe Acrobat Document

Page 3 of 4 Rev N/C. 11-13-2014 mailto:hugo.castaneda@comed.com mailto:greg.voice@comed.com mailto:steve@phoenixbroadband.com

Typical Installation Pictures (exact BMS not shown):

Figure 3. Typical Battery bank with BMS wire leads on cell post.

Figure 4. Typical location of BMS controller near Station Battery.

BMS Controller:

Wall Mount near Station Battery

Page 4 of 4 Rev N/C. 11-13-2014

C1504_06-18-2013
EM10312
EM10312-Page1-2011-01-31 Model (1).pdf
EM10312-Page2-2011-01-31 Model (1).pdf
EM12917
EM12918
EM12918-01-2011-02-28 Model (1).pdf
EM12918-02-2011-02-28 Model (1).pdf
EM12918-03-2011-02-28 Model (1).pdf
EM12918-04-2011-02-28 Model (1).pdf
EM12925 11-04-2013
EM12926
EM12926
Fermi Lab - Phoenix Battery Monitoring System Spec - RFQ
FermiLab - Battery Monitoring System Spec - SOW