Hollow Metal Door - Rated Hardware Schedule.pdf

PDF 119 KB Posted

Attached to
Kautz Road Substation Replacement Prefabricated Control House Building and associated Arc Safe 13. 8kV Medium Voltage Switchgear
Solicitation number
KRS-369604-JK
Issued by

About this file

This document is an engineering design guide for a Hollow Metal Door - Single Exterior (HW-1) specification from Fermilab's ISD Engineering department. The specification details a single exterior door measuring 3'-0" x 7'-0" x 1-3/4", constructed with galvanized steel and featuring a fire-rated UL label, manufactured by Steelcraft or an approved equivalent. The door is available in 1-hour (45-minute label) and 2-hour (90-minute label) fire ratings, with an entrance function that allows unlocking by key from outside and always being unlocked from inside.

Specific hardware requirements include 1-1/2 pair of McKinley hinges with non-removable pins, a Best lockset, Von Duprin panic hardware, a Norton closer, Zero weather-stripping, a Pemko door bottom sweep, a Hager drip cap, Rockwood flush bolts, a Zero threshold, optional Ives kick-plate, and various door stop options. A notable detail is that cylinders will be equipped with interchangeable core, small format, 7-pin tumbler inserts, with temporary inserts provided during construction and final cores/keys to be handled by Fermilab. The document includes specific manufacturer models, product numbers, and finish specifications for each component.

View the file

Other files

File Type Posted
Amend 05 to RFP KRS-369604-JK.pdf PDF
ComEd Battery and Fermilab Battery Monitoring System Specifications.pdf PDF
MC3.pdf PDF
E-339.pdf PDF
E-3.pdf PDF
2025 - Security and Access Control r2.docx DOCX document
E-337.pdf PDF
REVISED Attachment 10-PUR-466_Proposal Certifications_r4_09.24.25.pdf PDF
E-338.pdf PDF
REVISED Attachment 13-SARC_Subcontractor Annual RepsCerts Rev 5.pdf PDF
KRS Site Construction - Civil Drawings.pdf PDF
KRS Geotechnical Data Report.pdf PDF
KRS Site Construction - Structural Drawings.pdf PDF
MC1.pdf PDF
E-B2.PDF PDF
Card Reader Details.pdf PDF
Questions on E-House RFP_R5_2025_1003.xlsx XLSX spreadsheet
MC2.pdf PDF
FermiForward-Approved Color Palette.pdf PDF
MC4.pdf PDF
E-2.pdf PDF
Amend 04 to RFP KRS-369604-JK.pdf PDF
Amend 03 to RFP KRS-369604-JK.pdf PDF
E-Control House Site Visit-Sign-in Sheet.pdf PDF
Amend 02 to RFP KRS-369604-JK.pdf PDF
Business Visitor Registration Instructions and Directions.pdf PDF
E-House_QandA_Amend02.pdf PDF
Fermilab Site Map-Kautz Road Substation.pdf PDF
REVISED Attachment 13-SARC_Subcontractor Annual RepsCerts Rev 4.pdf PDF
Amend 01 to RFP KRS-369604-JK.pdf PDF
Attachment 7-2 Pages 63-113 from 3-5-207C Dwg IFBr2.pdf PDF
Attachment 14 SMALL BUSINESS SUBCONTRACTING PLAN template Far 52.219-9.pdf PDF
Attachment 13 -SARC_Subcontractor Annual RepsCerts Rev 3.pdf PDF
Attachment 9 - FFDG General Terms and Conditions for Commercial Products and Commercial Services (01.2025).pdf PDF
Attachment 3 - 013100_ESH_Requirements_04-2025 FFDG.pdf PDF
Attachment 10 - PUR-466_Proposal Certifications_r3_06.23.25.pdf PDF
Attachment 1 - Sample Subcontract .pdf PDF
Attachment 7-1 Pages 1-62 from 3-5-207C Dwg IFBr2.pdf PDF
Attachment 8 - 5-207C Control House Specs IFBr2.pdf PDF
Attachment 6 -017900 - DEMONSTRATION AND TESTING.pdf PDF
Attachment 2 - 010010_General_Requirements_3_2025 FFDG_.pdf PDF
Attachment 4 - 013300 Submittals FermiForward (3).pdf PDF
1. RFP for E-House.pdf PDF
Attachment 11 - 2025 Onsite NonProfessional Services Insurance Requirements.pdf PDF
Attachment 5 - 014100 Quality Requirements - March 2025 FermiForward.pdf PDF
Attachment 12 - PUR-568_Cost Accounting Standard Notices and Certification.pdf PDF
Show all 46

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ISD Engineering – Architectural General Section 3.0

Fermilab ISD-Engineering Design Guides Page 2 of 11 WARNING: This manual is subject to change. The current version is maintained on FESS Section website. Rev. 1, 08/2025

Hollow Metal Door – Single Exterior (HW-1)

1 HOUR FIRE RATED – 45 MINUTE LABEL

2 HOUR FIRE RATED – 90 MINUTE LABEL

Single Door – 3’-0” x 7’-0” x 1-3/4”

Use galvanized steel door and frame

Fire rated door with UL label

Manufactured by Steelcraft or approved equal.

Fire-rated core: manufacturer's standard vertical steel stiffener and/or laminated mineral board core for fire-rated doors.

Entrance function – unlocked by turning key outside, always unlocked from the inside

Item Description Comments

Hinges 1-1/2 Pair Hinges

Manufacturer: Mckinley Or Equal

Model: TA2714 4.5 X 4.5

Options: Non-Removable Pin

Finish: Satin Stainless

Product Number: 652

If door is higher than 7 ‘ or wider than 3’ look into the use of additional hinges or larger hinges.

Steel Base, Ball-Bearing Type.

Provide 1 Hinge For Every 30 ” Of

Door Height.

Lockset 1 Ea. (Function: Entrance)

Manufacturer: Best 93K7AB15D / S3 / 626 *

This is not panic hardware. If building occupancy requires see panic hardware set

Panic Hardware 1 set- Von Duprin 35a-F Rim Fire Exit Device series panic device with rods.

Finish to be 628 anodized aluminum.

Lever to be Von Duprin 360L.

Closer 1 Ea. 3. NORTON 7500 SERIES

Finish to be 689.

Pull or push side jamb mounting depending on the swing of the door.

Weather-stripping 1 Set - Zero #314AA. At exterior door

Door Bottom

Sweep

1 Ea. –

Manufacturer: Pemko Or Equal

Model Number: 18061CNB

At exterior door

Drip Cap 1 Ea.- Hager. At exterior door

Continued next page

ISD Engineering – Architectural General Section 3.0

Fermilab ISD-Engineering Design Guides Page 3 of 11 WARNING: This manual is subject to change. The current version is maintained on FESS Section website. Rev. 1, 08/2025

Item Description Comments

Flush Bolt Manufacturer: Rockwood

Model: 2842/2942

Product number: 630

Automatic flush bolts: ANSI/BHMA

A156.3, type 25, grade 1; minimum

3/4- inch (19-mm) throw; with dust-proof strikes; designed for mortising into door edge. Include wear plates.

Thresholds 1 Ea.- Zero #545A.

Finish Anodized Aluminum

Set threshold for doors in full be of sealant

Kick-plate

(if desired)

Ives .050 Stainless Steel Beveled 4 Sides with

Countersunk Screws. 10” High x Width of Door

Less 2”.

Door Stop 1 Ea. – Floor Stop – Ives FS13 Dome Stop US

26D for use without threshold or

Ives FS17 Dome Stop for use without threshold or

1 Ea. – Wall stop – Ives WS402CCV US 26D or

1 Ea. – Plunger –Ives FS1154 US 26D

Select one type of stop

* Cylinders: Equip locks with cylinders for interchangeable core, small format, 7 pin tumbler inserts. Furnish only temporary inserts for the construction period, and remove these when directed. Final cores and keys for installation will be Fermilab's responsibility.

File details come from the government source that posted it. Updated .