KRS Site Construction - Civil Drawings.pdf
PDF 3 MB Posted
- Solicitation number
- KRS-369604-JK
About this file
This document is a set of civil engineering design drawings for the Fermilab Kautz Road Substation Replacement project, dated June 19, 2025. The project involves replacing an existing substation and includes detailed plans for site demolition, external improvements, utilities, and construction details. Key elements include removing existing infrastructure, installing a new (P) Switchgear Building, implementing storm drainage systems, and reinstating landscape areas. The drawings specify technical requirements for asphalt pavement, hardstand reinstatement, utility connections, and erosion control measures, with precise elevations, grades, and construction specifications for the Fermilab site in Illinois.
The design documents outline comprehensive site modifications such as removing existing concrete, fencing, and underground utilities, and installing new concrete pads, pedestrian gates, chain link fencing, and storm drain infrastructure. Specific technical details include a proposed 40-foot switchgear building, asphalt pavement with 12-inch crushed aggregate base, storm drain connections to an existing lift station, and erosion control measures like fiber rolls and silt fencing. The plans are prepared by Arup US, Inc. and are marked "Not for Construction", suggesting they are in a preliminary or review stage of the design process.
View the file
Other files
Show all 46
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
1. THE STAMPED CONSTRUCTION DRAWINGS AND PROJECT SPECIFICATIONS ARE INTENDED TO WORK WITH AND BE COMPLEMENTARY TO EACH OTHER, AND BOTH SHALL BE CONSIDERED TO BE A PART OF THE CONTRACT DOCUMENTS. WHERE A DISCREPANCY IS FOUND, PROJECT DRAWINGS SHALL TAKE PRECEDENCE OVER PROJECT SPECIFICATIONS, AND PROJECT SPECIFICATIONS SHALL
TAKE PRECEDENCE OVER STANDARD SPECIFICATIONS.
2. NOTES AND DETAILS ON DRAWINGS SHALL TAKE PRECEDENCE OVER GENERAL NOTES AND TYPICAL DETAILS. IN THE EVENT THAT CERTAIN DETAILS ARE NOT FULLY SHOWN OR NOTED ON DRAWINGS, THEIR CONSTRUCTION SHALL BE OF THE SAME TYPE AS FOR
SIMILAR CONDITIONS THAT ARE SHOWN OR NOTED, SUBJECT TO THE ENGINEER'S APPROVAL.
3. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE REVIEW OF ALL PROJECT DRAWINGS AND SPECIFICATIONS PRIOR TO THE START OF CONSTRUCTION. ANY DISCREPANCIES THAT CANNOT BE RESOLVED THROUGH THE CLARIFICATIONS IN THESE NOTES SHALL BE BROUGHT TO THE ATTENTION OF THE ENGINEER SO THAT A CLARIFICATION CAN BE ISSUED. ANY WORK PERFORMED PRIOR TO RECEIPT OF SUCH CLARIFICATION WILL BE DONE AT THE SOLE RISK OF THE CONTRACTOR.
4. THE CONTRACTOR SHALL VERIFY ALL EXISTING CONDITIONS, DIMENSIONS, AND ELEVATIONS PRIOR TO COMMENCING WITH THE WORK AND NOTIFY THE ENGINEER OF ANY DISCREPANCIES WITH THE INFORMATION SHOWN ON THE DRAWINGS.
5. ANY DEVIATIONS FROM THESE PLANS, EXCEPT MINOR FIELD CHANGES REQUIRED TO JOIN EXISTING CONDITIONS AND APPROVED BY THE INSPECTOR, MUST BE REVIEWED AND APPROVED BY THE ENGINEER. THE ENGINEER SHALL NOT BE RESPONSIBLE FOR ANY
UNAUTHORIZED CHANGES TO THE PLANS.
6. THESE DRAWINGS WERE DEVELOPED SOLELY TO SUPPORT THE CONSTRUCTION OF THIS PROJECT AND SHALL NOT BE REPRODUCED NOR USED FOR ANY OTHER PROJECT WITHOUT WRITTEN PERMISSION OF THE ENGINEER. NEITHER ARUP NOR THE ENGINEER STAMPING THESE PLANS SHALL BE RESPONSIBLE FOR, OR LIABLE FOR, ANY UNAUTHORIZED USE OF THESE PLANS.
7. ALL IMPROVEMENTS SHOWN HEREIN HAVE BEEN DESIGNED FOR THE FINAL SITE CONDITION OF THE PROJECT. ALL TEMPORARY WORK NECESSARY TO FACILITATE THE CONSTRUCTION OF THE APPROVED DRAWINGS IS CONSIDERED PART OF THE MEANS AND METHODS OF CONSTRUCTION AND SHALL BE DESIGNED, INSTALLED, AND CARRIED OUT BY THE CONTRACTOR IN ACCORDANCE WITH THE REQUIREMENTS OF THE PROJECT GOVERNING CODE(S) AND THE AUTHORITY HAVING JURISDICTION (AHJ). WHERE DEEMED NECESSARY BY THE AHJ, TEMPORARY WORK SHALL BE DESIGNED BY A QUALIFIED AND LICENSED ENGINEER REGISTERED IN THE
STATE OF ILLINOIS.
8. ALL ELEVATIONS AND DIMENSIONS ARE IN FEET AND DECIMALS THEREOF UNLESS NOTED OTHERWISE.
9. NOTED DIMENSIONS SHALL TAKE PRECEDENCE OVER SCALED DIMENSIONS. DIMENSIONS ON PLANS SHALL BE ASSUMED TO BE
HORIZONTAL MEASUREMENTS UNLESS NOTED OTHERWISE.
10. DIMENSIONS TO PIPELINES ARE TO CENTERLINES UNLESS NOTED OTHERWISE.
11. THE CONTRACTOR SHALL PROTECT ALL EXISTING STRUCTURES AND OTHER IMPROVEMENTS IN AND AROUND THE AREA OF WORK UNLESS INDICATED HEREIN TO BE REMOVED. ANY DAMAGE TO EXISTING IMPROVEMENTS, INCLUDING THOSE COMPLETED BY THE CONTRACTOR, SHALL BE REPAIRED OR REPLACED AT NO COST AND TO THE SATISFACTION OF THE OWNER.
12. THE CONTRACTOR SHALL ASSUME SOLE AND COMPLETE RESPONSIBILITY FOR THE JOB SITE CONDITIONS INCLUDING SAFETY OF ALL PERSONS AND PROPERTY DURING THE COURSE OF CONSTRUCTION OF THIS PROJECT. THIS REQUIREMENT SHALL APPLY
CONTINUOUSLY, AND SHALL NOT BE LIMITED TO NORMAL WORKING HOURS.
13. THE CONTRACTOR'S SAFETY PLAN SHALL BE DEVELOPED AND IMPLEMENTED IN ACCORDANCE WITH ALL SAFETY ORDERS OF THE IL
OSHA TITLE 8 REGULATIONS.
14. ALL FIXTURES, EQUIPMENT, PIPING, FITTINGS, AND MATERIALS SHALL BE LISTED AND LABELED FOR THEIR INTENDED PURPOSE.
1. THE EXISTENCE, LOCATION, AND CHARACTERISTICS OF UNDERGROUND UTILITY INFORMATION SHOWN ON THESE PLANS HAVE BEEN OBTAINED FROM A REVIEW OF AVAILABLE DATA, INCLUDING FERMILAB RECORD DRAWINGS, AND GIS DATA PROVIDED BY THE OWNER. NO REPRESENTATION IS MADE AS TO THE ACCURACY NOR COMPLETENESS OF SAID UTILITY INFORMATION. THE CONTRACTOR SHALL TAKE PRECAUTIONARY MEASURES TO PROTECT THE UTILITY LINES SHOWN AND ANY OTHER LINES NOT OF
RECORD OR NOT SHOWN ON THESE PLANS.
2. THE CONTRACTOR SHALL POTHOLE TO IDENTIFY ANY POTENTIAL UTILITY CONFLICTS WITH GRAVITY DRAINS, UTILITIES, OR FOUNDATIONS PRIOR TO CONSTRUCTION. THE CONTRACTOR SHALL INCLUDE CONTINGENCY FOR LOCALIZED RELOCATION OF PRESSURIZED OR DRY UTILITIES IF SUCH CLASHES EXIST. THE CONTRACTOR WILL BE RESPONSIBLE FOR COORDINATION WITH THE
UTILITY OWNER(S).
3. UNLESS NOTED OR OTHERWISE AGREED WITH ENGINEER AND OWNER, ALL EXISTING UTILITIES SHALL BE PROTECTED AND MAINTAINED IN WORKING ORDER. ANY PLANNED DISRUPTIONS SHALL COMPLY WITH OWNER'S PROCEDURES.
4. CONTRACTOR IS RESPONSIBLE FOR AS-BUILT RECORD DRAWINGS AND SURVEYING, TO BE PRODUCED FOR RECORD TO OWNER AND
ENGINEER.
5. ALL CIRCUIT BREAKER AND DISCONNECT SWITCHING SHALL BE PERFORMED BY FERMIFORWARD. SUBCONTRACTOR SHALL ADHERE TO FERMIFORWARD LOCK-OUT AND AND TAG-OUT PROCEDURES FOR CIRCUIT DE-ENERGIZING AND BACKFEED ISOLATION.
SURVEY
GENERAL NOTES
GRADING
UTILITIES
1. ALL EARTH MOVING OPERATIONS SHALL BE PERFORMED IN ACCORDANCE WITH THE APPROVED GEOTECHNICAL REPORT BY XXXX, INCLUDING ANY APPROVED SUPPLEMENTAL REPORTS OR LETTERS.
2. EXCAVATED MATERIAL SHALL BE STOCK PILED IN LOCATION(S) APPROVED BY THE OWNER PER ILLINOIS URBAN MANUAL PRACTICE
STANDARD CODE 927.
3. NO EXCAVATED OR FILL MATERIAL SHALL BE PLACED IN ANY DRAINAGE PATH, WHETHER IT IS A PAVED FLOWLINE, SWALE, CREEK, OR FLOODPLAIN, UNLESS NOTED OTHERWISE.
4. ALL DEBRIS, FOREIGN MATERIAL, AND EXCESS EXCAVATED MATERIAL SHALL BE REMOVED FROM THE SITE AND DISPOSED OF AT APPROVED DISPOSAL SITES. THE CONTRACTOR SHALL OBTAIN NECESSARY PERMITS FOR THE TRANSPORTATION OF MATERIAL TO
AND FROM THE SITE.
5. ALL TRENCHES SHALL BE BACKFILLED PER DETAILS AND SPECIFICATIONS WITH APPROPRIATE TESTS TO VERIFY COMPACTION
VALUES.
6. WATER SHALL BE PROVIDED ON SITE BY CONTRACTOR AND USED TO CONTROL DUST DURING CONSTRUCTION OPERATIONS, UNLESS
OTHER DUST CONTROL MEASURES ARE APPROVED BY THE ENGINEER.
1. THE ORIGINAL SOURCE OF THE EXISTING CONDITIONS, INCLUDING EXISTING IMPROVEMENTS AND TOPOGRAPHY, IS FROM GIS DATA PROVIDED FROM THE OWNER. NO REPRESENTATION IS MADE AS TO THE ACCURACY NOR COMPLETENESS OF SAID EXISTING
IMPROVEMENTS AND TOPOGRAPHY.
2. ADDITIONAL SURVEY AND POTHOLING FOR FIELD VERIFICATION SHALL BE COMPLETED PRIOR TO CONSTRUCTION. NOTIFY THE
ENGINEER OF ANY DISCREPANCIES WITH THE PLANS PRIOR TO CONSTRUCTION.
ABBREVIATIONS
A/E ARCHITECTURAL/ENGINEERING
AB AGGREGATE BASE
AC, ASPH ASPHALT CONCRETE
ADA AMERICANS WITH DISABILITIES ACT
ADD'L ADDITIONAL
ALT ALTERNATE, ALTERNATIVE
ALUM ALUMINUM
APWA AMERICAN PUBLIC WORKS ASSOCIATION
APPROX APPROXIMATELY
ASTM AMERICAN SOCIETY FOR TESTING AND MATERIALS
AVG AVERAGE
BFP BACKFLOW PREVENTER
BIM BUILDING INFORMATION MODELLING
BLDG BUILDING
BM BENCHMARK
BOP BOTTOM OF PIPE
BOT BOTTOM
BW BACK OF WALK
C/C CENTER TO CENTER
CA CABLE
CAB CRUSHED AGGREGATE BASE
CAD COMPUTER-AIDED DESIGN
CFR CODE OF FEDERAL REGULATIONS
CHW CHILLED WATER
CIP CAST IRON PIPE
CJ CONTRACTION JOINT, CONTROL JOINT
CL CENTERLINE
CMB CRUSHED MISCELLANEOUS BASE
CO COMPANY
COMM COMMUNICATIONS
CONC CONCRETE
CONST CONSTRUCTION
CONT CONTINUED/CONTINUITY
CPC CALIFORNIA PLUMBING CODE
CPWR COOLING POND WATER RETURN
CPWS COOLING POND WATER SUPPLY
CUB CENTRAL UTILITY BUILDING
CW, W COLD WATER, DOMESTIC WATER
CY CUBIC YARDS
DEMO DEMOLISH, DEMOLITION
DEPT DEPARTMENT
DET DETAIL
DI DUCTILE IRON
DIA DIAMETER
DIP DUCTILE IRON PIPE
DWG DRAWING
DWP DEPARTMENT OF WATER AND POWER
DUCT DUCTBANK
DWY DRIVEWAY
E EAST, EASTING
E-LC ELECTRICAL LOW VOLTAGE
EG EXISTING GRADE, EXISTING GROUND
EL, ELEV ELEVATION
ELEC ELECTRICAL
EP EDGE OF PAVEMENT
ES&H ENVIRONMENT, SAFETY, & HEALTH FOR PROJECTS
EX, EXIST, (E) EXISTING
f'c COMPRESSIVE STRENGTH OF CONCRETE
FDC FIRE DEPARTMENT CONNECTION
FDRS FEEDERS
FESS FACILITIES ENGINEERING SERVICES SECTION
FF FINISHED FLOOR ELEVATION
FG FINISHED GRADE, FINISHED GROUND
FH FIRE HYDRANT
FIN FINISHED
FLG FLANGE
FM FERMIFORWARD
FO FIBER OPTIC
FS FINISHED SURFACE
FT FOOT
FU FIXTURE UNITS
FW FIRE WATER
G NATURAL GAS
GAL GALVANIZED
GB GRADE BREAK
GIS GEOGRAPHICAL INFORMATION SYSTEM
GM GAS METER
HD HEAD
HDPE HIGH DENSITY POLYETHYLENE
HP HIGH POINT, HINGE POINT
HT HEIGHT
HWY HIGHWAY
ICW INDUSTRIAL COOLING WATER
ID INSIDE DIAMETER
IDOT ILLINOIS DEPARTMENT OF TRANSPORTATION
IE INVERT ELEVATION
IJ ISOLATION JOINT
INV INVERT
ABBREVIATIONS
IRR IRRIGATION
KRS KAUTZ ROAD SUBSTATION
KV KILOVOLTS
L LENGTH
LP LOW POINT
LT LEFT
MAX MAXIMUM
MECH MECHANICAL
MH MAINTENANCE HOLE
MIL MILLIMETER
MIN MINIMUM
MISC MISCELLANEOUS
N NORTH, NORTHING
N/A NOT APPLICABLE
NAD NORTH AMERICAN DATUM
NAVD NORTH AMERICAN VERTICAL DATUM
NO NUMBER
NPDES NATIONAL POLLUTANT DISCHARGE ELIMINATION SYSTEM
NTS NOT TO SCALE
OC ON CENTER
OD OUTSIDE DIAMETER
OH OVERHEAD
ORD ORDINANCE
OSHA OCCUPATIONAL SAFETY AND HEALTH ADMINISTRATION
(P), PROP PROPOSED
PCC PORTLAND CEMENT CONCRETE
PE POLYETHYLENE
PIP2 PROTON IMPROVEMENT PLAN II
PIV POST INDICATOR VALVE
PL PROPERTY LINE
PMH POWER MANHOLE
POC POINT OF CONNECTION
PP POLYPROPYLENE
PRV PRESSURE REGULATING VALVE
PSI POUNDS PER SQUARE INCH
PVC POLYVINYL CHLORIDE
PWR POWER
R RADIUS
RD ROAD
REINF REINFORCED
REQ'D REQUIRED
RET RETENTION
REV REVISION
ROW RIGHT OF WAY
RR RAIL ROAD
RT RIGHT OR ROUTE
S SOUTH
SCE SOUTHERN CALIFORNIA EDISON
SCG SOUTHERN CALIFORNIA GAS COMPANY
SCH SCHEDULE
SD STORM DRAIN
SEC SECTION
SF SQUARE FEET
SHT SHEET
SPEC SPECIFICATION
SPPWC STANDARD PLANS FOR PUBLIC WORKS CONSTRUCTION
SQ SQUARE
SS SANITARY SEWER
SSFM SANITARY SEWER FORCE MAIN
SSMH SANITARY SEWER MANHOLE
SSPWC STANDARD SPECIFICATIONS FOR PUBLIC WORKS CONSTRUCTION
ST STREET
STA STATION
STD STANDARD
STL STEEL
SWGR SWITCHGEAR
SWPPP STORM WATER POLLUTION PREVENTION PLAN
T, TEL TELEPHONE/COMMUNICATIONS
T&B TOP AND BOTTOM
TC TOP OF CURB
TEMP TEMPORARY, TEMPERATURE
TG TOP OF GRATE
THK THICK
TOC TOP OF CONCRETE
TP TOP OF PIPE
TYP TYPICAL
UG UNDERGROUND
UIP UTILITIES INFRASTRUCTURE PROJECT
VAR VARIES
VCP VITRIFIED CLAY PIPE
VIF VERIFY IN FIELD
VOL VOLUME
W WEST, DOMESTIC WATER, WIDE
W/ WITH
W/O WITHOUT
WM WATER METER
XFMR TRANSFORMER
35 East Wacker Drive Suite 1800 Chicago IL 60601 USA t: +1 312 849 5610 www.arup.com
SCALE:
REVISIONS PROJECT NO.
SHEET NO.
REVISION NO.
DESIGNED
DRAWN
CHECKED
APPROVED
CONCEPT
DISCIPLINE REVIEW
ENG. REVIEWED
ISD APPROVED
SUBMITTED
A/E CONSULTANT FERMILAB DATE
N O
T
FO
R C
O N
ST
R
U C
TI
O
N
Arup US, Inc.
UIP - SUBPROJECT 2
KAUTZ ROAD SUBSTATION REPLACEMENT
DESCRIPTIONS
DATE
DATEREV.
Ju n
, 2
- 2 :3
6P M
A ut oD es k D oc s:
\A R
U P\
-0
Fe rm iL ab C am pu s In fra st ru ct ur e\
Pr oj ec t F ile s\
_W
IP
M od el s\ C
C iv il\
S he et s\ C
1- 3-
5-
7.
dw g
90% FINAL DESIGN06/19/250 06/19/25
06/19/25
06/19/25
06/19/25
J. SANDBERG
J. WOOD
J. BORGHESI
G. RUVALCABA
NTS
3-5-207
CIVIL
JU
N
E
, 2
C-1GENERAL NOTES AND
ABBREVIATIONS
(E) KAUTZ ROAD SUBSTATION
40'
75.5'
62'
TYP.
35 East Wacker Drive Suite 1800 Chicago IL 60601 USA t: +1 312 849 5610 www.arup.com
SCALE:
REVISIONS PROJECT NO.
SHEET NO.
REVISION NO.
DESIGNED
DRAWN
CHECKED
APPROVED
CONCEPT
DISCIPLINE REVIEW
ENG. REVIEWED
ISD APPROVED
SUBMITTED
A/E CONSULTANT FERMILAB DATE
N O
T
FO
R C
O N
ST
R
U C
TI
O
N
Arup US, Inc.
UIP - SUBPROJECT 2
KAUTZ ROAD SUBSTATION REPLACEMENT
DESCRIPTIONS
DATE
DATEREV.
SCALE FEET
20 20 400
1. REFER TO SURVEY AND UTILITY NOTES ON SHEET C-1 FOR
THE SOURCE OF EXISTING TOPOGRAPHIC AND UTILITY
INFORMATION SHOWN ON THIS PLAN.
2. DAMAGE TO ANY EXISTING IMPROVEMENTS THAT ARE TO
REMAIN SHALL BE REPAIRED, AT THE CONTRACTOR'S
COSTS, TO THE SATISFACTION OF THE OWNER.
3. CONTRACTOR MUST PROVIDE AND MAINTAIN ALL
TEMPORARY MEASURES TO CONTROL DUST, NOISE, AIR
QUALITY, EROSION, AND SEDIMENT AND WASTE CONTROL IN
COMPLIANCE WITH ALL APPLICABLE FEDERAL, STATE,
LOCAL CODE AND REGULATIONS, PROJECT CONDITIONS OF
APPROVAL, AND MITIGATION MONITORING AND REPORTING
PROGRAM.
4. CLEARING WORK SHALL NOT BEGIN UNTIL FENCES,
BARRICADES, EROSION AND SEDIMENT CONTROL
MEASURES, WARNING SIGNS, AND OTHER PEDESTRIAN
CONTROL DEVICES ARE INSTALLED.
NOTES
LEGEND
CONTROL CABLE
ELECTRICAL LOW VOLTAGE
ELECTRICAL DUCTBANK
STORM DRAIN
REMOVE HARDSTAND, REUSE IF
POSSIBLE AS BASE MATERIAL,
DISPOSE EXCESS
REMOVE AND DISPOSE
EXISTING CONCRETE
REMOVE AND DISPOSE
EXISTING STORM PIPE
REMOVE AND DISPOSE
OF EXISTING FENCE
KEYNOTES
PROTECT IN PLACE EXISTING FENCE
2 PROTECT IN PLACE EXISTING DRAINAGE CHANNEL
3 PROTECT IN PLACE EXISTING SWING GATE
4 PROTECT IN PLACE EXISTING CONCRETE HEADWALL
5 PROTECT IN PLACE EXISTING LIFT STATION
6 PROTECT IN PLACE EXISTING STORM DRAIN MANHOLE
7 PROTECT IN PLACE EXISTING HANDHOLE
8 PROTECT IN PLACE EXISTING TETRA-DUCT
9 PROTECT IN PLACE EXISTING 8" INDUSTRIAL
COOLING WATER
10 PROTECT IN PLACE EXISTING 6" DUCTILE IRON
INDUSTRIAL COOLING WATER
11 PROTECT IN PLACE EXISTING 6" PERFORATED CMP
PIPE UNDERDRAIN
12 PROTECT IN PLACE EXISTING 4" DUCTILE IRON
STORM DRAIN
13 PROTECT IN PLACE EXISTING TRANSFORMER CONCRETE
PAD
14 PROTECT IN PLACE EXISTING 4" SUMP OUTLET STORM
DRAIN PIPE
15 PROTECT IN PLACE EXISTING 6" PVC STORM DRAIN
16 PROTECT IN PLACE EXISTING PEDESTRIAN GATE
17 PROTECT IN PLACE EXISTING HELIUM PIPES
PROTECT IN PLACE EXISTING 18-5" CONDUITS
CONCRETE ENCASED DUCT BANK
PROTECT IN PLACE EXISTING CONCRETE PAD (REFER TO
ELECTRICAL AND STRUCTURAL PLANS FOR EQUIPMENT
AND PAD REMOVALS)
RELOCATE EXISTING POLE (REFER TO ELECTRICAL PLANS)20
21 REMOVE EXISTING 6" PVC STORM DRAIN
22 REMOVE EXISTING STORM DRAIN MANHOLE
23 REMOVE EXISTING SWITCH PAD
24 REMOVE EXISTING SWING GATE
25 REMOVE EXISTING PEDESTRIAN GATE
26 REMOVE EXISTING FENCE
27 REMOVE EXISTING PAD
EXISTING COLUMNS
PROTECT IN PLACE EXISTING UNDERGROUND
ELECTRICAL DUCTBANKS
PROTECT IN PLACE EXISTING COLUMNS AND
FOUNDATION
REMOVE AND DISPOSE OF EXISTING CONCRETE PAD
(REFER TO ELECTRICAL AND STRUCTURAL PLANS FOR
EQUIPMENT AND PAD REMOVALS)
REMOVE AND DISPOSE EXISTING
UNDERGROUND CONDUIT
31 REMOVE AND DISPOSE OF EXISTING BELOW
GROUND CONDUIT, REFER TO ELECTRICAL PLANS
FOR LIMITS
32 REMOVE AND DISPOSE OF EXISTING CONTAINMENT
AREA WALL
E
S
W
TRUE
NORTH
Ju n
, 2
- 1 :4
2P M
A ut oD es k D oc s:
\A R
U P\
-0
Fe rm iL ab C am pu s In fra st ru ct ur e\
Pr oj ec t F ile s\
_W
IP
M od el s\ C
C iv il\
S he et s\ C
2- 3-
5-
7.
dw g
90% FINAL DESIGN06/19/250 06/19/25
06/19/25
06/19/25
06/19/25
J. SANDBERG
J. WOOD
J. BORGHESI
G. RUVALCABA
1" = 20'
3-5-207
CIVIL
JU
N
E
, 2
C-2EXISTING CONDITIONS
AND DEMOLITION PLAN
KAUTZ ROAD SUBSTATION
(E) SWITCHGEAR BUILDING
35 East Wacker Drive Suite 1800 Chicago IL 60601 USA t: +1 312 849 5610 www.arup.com
SCALE:
REVISIONS PROJECT NO.
SHEET NO.
REVISION NO.
DESIGNED
DRAWN
CHECKED
APPROVED
CONCEPT
DISCIPLINE REVIEW
ENG. REVIEWED
ISD APPROVED
SUBMITTED
A/E CONSULTANT FERMILAB DATE
N O
T
FO
R C
O N
ST
R
U C
TI
O
N
Arup US, Inc.
UIP - SUBPROJECT 2
KAUTZ ROAD SUBSTATION REPLACEMENT
DESCRIPTIONS
DATE
DATEREV.
SCALE FEET
20 20 400
1. REFER TO SURVEY AND UTILITY NOTES ON SHEET C-1 FOR
THE SOURCE OF EXISTING TOPOGRAPHIC AND UTILITY
INFORMATION SHOWN ON THIS PLAN.
2. ALL EROSION AND SEDIMENT CONTROL MEASURES SHALL
BE IN PLACE PRIOR TO CONSTRUCTION ACTIVITIES TO
PROTECT ADJACENT AND DOWNSTREAM PROPERTIES
FROM SEDIMENT RUNOFF. MEASURES INCLUDE, BUT ARE
NOT LIMITED TO, STABILIZED CONSTRUCTION ACCESS,
FIBER ROLLS, AND INLET PROTECTION. REFER TO PROJECT
STORMWATER POLLUTION PREVENTION PLAN (SWPPP) (BY
OTHERS) FOR SITE SPECIFIC DETAILS. THIS PLAN DEPICTS
THE MINIMUM TEMPORARY EROSION AND SEDIMENT
CONTROL (TESC) MEASURES AND IS FOR PERMITTING
PURPOSES ONLY.
3. THE CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING
TESC MEASURES THAT PROVIDE ADEQUATE PROTECTION
TO OFF-SITE DRAINAGE SYSTEMS AND DOWNSTREAM
WATER BODIES DURING DEMOLITION AND ALL SUBSEQUENT
CONSTRUCTION PHASES, IN CONFORMANCE WITH THE
CONSTRUCTION GENERAL PERMIT AND PROJECT SWPPP.
4. THE CONTRACTOR SHALL BE RESPONSIBLE FOR UPDATING
THE PROJECT SWPPP AND ASSOCIATED TESC PLANS IN
ACCORDANCE WITH THEIR PROPOSED PHASING STRATEGY.
5. THE INSTALLATION AND MAINTENANCE OF ALL EROSION
AND SEDIMENT CONTROL MEASURES SHALL BE IN
ACCORDANCE WITH FERMIFORWARD'S ES&H MANUAL
(FESHM) AND ILLINOIS URBAN MANUAL.
6. THE CONTRACTOR SHALL INSPECT ALL DISTURBED AREAS,
CONTROLS, VEHICLE ENTRY AND EXIT POINTS AND
MAINTAIN EROSION CONTROL MEASURES AND REMOVE
SEDIMENT THEREFROM ON A WEEKLY BASIS AND WITHIN
TWENTY FOUR HOURS AFTER EACH STORM EVENT AND
DISPOSE OF SEDIMENTS IN AN UPLAND AREA SUCH THAT
THEY DO NOT ENCUMBER OTHER DRAINAGE STRUCTURES
OR PROTECTED AREAS.
7. THE CONTRACTOR SHALL CONTROL CONSTRUCTION SUCH
THAT SEDIMENTATION SHALL NOT AFFECT REGULATORY
PROTECTED AREAS, WHETHER SUCH SEDIMENTATION IS
CAUSED BY WATER, WIND, OR DIRECT DEPOSIT.
8. THE CONTRACTOR SHALL PREVENT DUST, SEDIMENT, AND
DEBRIS FROM EXITING THE SITE, AND SHALL BE
RESPONSIBLE FOR CLEANUP, REPAIRS, AND CORRECTIVE
ACTION IF SUCH OCCURS. THE CONTRACTOR SHALL
ENSURE THAT SEDIMENT AND OTHER SUBSTANCES ARE
NOT TRACKED OFF-SITE OR ONTO AREAS WHICH DRAIN TO
SWALES, DITCHED, WATERWAYS, ETC.
9. THE CONTRACTOR SHALL PERFORM CONSTRUCTION
SEQUENCING SUCH THAT EARTH MATERIALS ARE EXPOSED
FOR A MINIMUM OF TIME BEFORE THEY ARE COVERED,
SEEDED, OR OTHERWISE STABILIZED TO PREVENT EROSION
AS DEFINED IN THE ILLINOIS URBAN MANUAL PRACTICE
STANDARD CODE 927. ALL STOCKPILES NOT ACTIVELY
BEING USED SHALL BE COVERED.
10. AT MINIMUM, THE FOLLOWING SOIL STABILIZATION
MEASURES SHALL BE PROVIDED DURING CONSTRUCTION
AS REQUIRED TO MINIMIZE SOIL EROSION AT
CONSTRUCTION ACCESS POINT(S):
10.1. TEMPORARY STABILIZED CONSTRUCTION ENTRANCE,
INSTALLED AT LOCATIONS DESIGNATED BY
CONTRACTOR TO REDUCE TRACKING OF MUD AND DIRT
ONTO PUBLIC ROADS BY CONSTRUCTION EQUIPMENT;
10.2. TEMPORARY STABILIZED CONSTRUCTION ROADWAYS IN
LOCATIONS DESIGNATED BY CONTRACTOR TO
PREVENT EROSION AND TO CONTROL TRACKING OF
MUD AND SOIL MATERIALS ONTO PUBLIC ROADS;
10.3. TEMPORARY STABILIZED CONSTRUCTION EXIT TIRE
WASH LOCATE AT EGRESS POINT TO REMOVE
SEDIMENTS FROM UNDER CARRIAGES AND TO
PREVENT SEDIMENTS FROM BEING TRANSPORTED
ONTO PUBLIC ROADS.
11. THE NEXT DOWNSTREAM CATCH BASIN/ DRAINAGE INLET
SHALL BE PROTECTED.
11.1. DRAIN INLETS SUSCEPTIBLE TO EROSION FROM THE
CONSTRUCTION OF THIS PROJECT SHALL BE
PROTECTED DURING CONSTRUCTION.
12. SEE SPECIFICATIONS FOR ADDITIONAL NOTES.
NOTES
LEGEND
FIBER ROLL
SILT FENCE, PER SPECIFICATIONS
ROCK OUTLET PROTECTION,
PER ILLINOIS URBAN MANUAL
PRACTICE STANDARD CODE 910
INLET PROTECTION, PER
SPECIFICATIONS
DIRECTION OF RUNOFF
STABILIZED CONSTRUCTION
ENTRANCE, PER SPECIFICATIONS
KEYNOTES
EXISTING DRAINAGE CHANNEL
Ju n
, 2
- 3 :1
2P M
A ut oD es k D oc s:
\A R
U P\
-0
Fe rm iL ab C am pu s In fra st ru ct ur e\
Pr oj ec t F ile s\
_W
IP
M od el s\ C
C iv il\
S he et s\ C
3- 3-
5-
7.
dw g
90% FINAL DESIGN06/19/250 06/19/25
06/19/25
06/19/25
06/19/25
J. SANDBERG
J. WOOD
J. BORGHESI
G. RUVALCABA
1" = 20'
3-5-207
CIVIL
JU
N
E
, 2
C-3EROSION AND SEDIMENT
CONTROL PLAN
E
S
W
TRUE
NORTH
KAUTZ ROAD SUBSTATION
40.0'
(P) SWITCHGEAR
BUILDING
5.0'
9.0'
.0
9.
0'
5.0'
5.0'
5.0'
192.0'
5.0'
5.
0'
34.0'
(738.0 FG)
(738.8 FG)
(739.0 FG)
(738.0 FG)
739.6 FF
739.6 FF
(738.0 FG)
(738.8 FG)
(739.0 FG)
.7
.0
13.0'
.0
10.0'
.0
35 East Wacker Drive Suite 1800 Chicago IL 60601 USA t: +1 312 849 5610 www.arup.com
SCALE:
REVISIONS PROJECT NO.
SHEET NO.
REVISION NO.
DESIGNED
DRAWN
CHECKED
APPROVED
CONCEPT
DISCIPLINE REVIEW
ENG. REVIEWED
ISD APPROVED
SUBMITTED
A/E CONSULTANT FERMILAB DATE
N O
T
FO
R C
O N
ST
R
U C
TI
O
N
Arup US, Inc.
UIP - SUBPROJECT 2
KAUTZ ROAD SUBSTATION REPLACEMENT
DESCRIPTIONS
DATE
DATEREV.
SCALE FEET
20 20 400
1. REFER TO SURVEY AND UTILITY NOTES ON SHEET C-1 FOR
THE SOURCE OF EXISTING TOPOGRAPHIC AND UTILITY
INFORMATION SHOWN ON THIS PLAN.
2. MINIMUM 6" THICK CONCRETE PAD AT DOOR SHALL BE AT
FINISHED FLOOR ELEVATION AND SLOPE AWAY FROM THE
BUILDING AT 2% MAXIMUM. CONCRETE SHALL BE TYPE
520-C-2500.
3. COORDINATION FOR VENTING, DRAINAGE, AND WILDLIFE
PROTECTION OF VOID SPACE UNDER PROPOSED
SWITCHGEAR BUILDING IS ONGOING AND WILL BE FINALIZED
IN THE CONSTRUCTION DOCUMENTATION.
4. CONTRACTOR TO ENSURE DISTURBED GROUND SURFACE
THAT IS NOT PAVED TO BE REINSTATED PER DETAIL 2,
SHEET C-5.
NOTES
LEGEND
PROPOSED ASPHALT
PAVEMENT (16,500 SQ.FT),
SEE DETAIL 1 SHEET C-5
KEYNOTES
PROPOSED PEDESTRIAN GATE
PROPOSED TYMETAL PEDESTRIAN DOUBLE
SWING GATE OR APPROVED EQUAL
PROPOSED CHAIN LINK FENCE WITH BARBED WIRE,
REFER TO ELECTRICAL PLANS FOR FENCE GROUNDING
4 PROPOSED SWING GATE
5 EXISTING BASEMENT EXTENT
RELOCATED POLE, REFER TO
STRUCTURAL PLANS FOR DETAIL
7 PROPOSED CONCRETE PAD, TYP. (SEE NOTE 2)
PROPOSED CONCRETE PAD, REFER TO
STRUCTURAL PLANS
ELECTRIFIED FENCE,
REFER TO ELECTRICAL PLANS
10 FIRE WALL, SEE STRUCTURAL, SHEET S-210
PROPOSED CONCRETE PAD
(SEE NOTE 2)
PROPOSED FENCE
PROPOSED TYMETAL PEDESTRIAN SWING GATE
OR APPROVED EQUAL
MINIMUM 1% SLOPE AWAY FROM DOORWAY
FOR PROPER DRAINAGE
PROPOSED ELECTRIFIED FENCE
13 CONCRETE PAD FOR NEMA 3R FIBER OPTIC
CABINET, REFER TO STRUCTURAL PLANS
E
S
W
TRUE
NORTH
Ju n
, 2
- 1 :4
3P M
A ut oD es k D oc s:
\A R
U P\
-0
Fe rm iL ab C am pu s In fra st ru ct ur e\
Pr oj ec t F ile s\
_W
IP
M od el s\ C
C iv il\
S he et s\ C
4- 3-
5-
7.
dw g
90% FINAL DESIGN06/19/250 06/19/25
06/19/25
06/19/25
06/19/25
J. SANDBERG
J. WOOD
J. BORGHESI
G. RUVALCABA
1" = 20'
3-5-207
CIVIL
JU
N
E
, 2
C-4EXTERNAL IMPROVEMENTS
PLAN
NOTES:
1. REINSTATE TO MATCH EXISTING TOTAL PAVEMENT SECTION WHERE POSSIBLE. SECTION SHALL NOT BE LESS THAN MINIMUM SECTION SHOWN ABOVE.
2. IN THE ABSENCE OF A SITE SPECIFIC GEOTECHNICAL REPORT, THIS SECTION IS BASED ON AS-BUILTS. A SITE SPECIFIC GEOTECHNICAL REPORT WILL
ADVISE ON THE FINAL PAVEMENT SECTION.
3. PAVEMENT AREAS THAT ARE REPAIRED SHOULD HAVE A SMOOTH TRANSITION TO NOT INTERFERE WITH FUTURE SNOW PLOWING.
-NTS
HARDSTAND REINSTATEMENT
-NTS
ASPHALT PAVEMENT
3" ASPHALT
5 12" CRUSHED
AGGREGATE BASE
12" MIN. COMPACTED
CA-1 AGGREGATE
BASE COURSE.
SUITABLE SUB-BASE MATERIAL
6" MIN. COMPACTED CA-6
AGGREGATE SURFACE COURSE.
95% COMPACTED
SUBGRADE
35 East Wacker Drive Suite 1800 Chicago IL 60601 USA t: +1 312 849 5610 www.arup.com
SCALE:
REVISIONS PROJECT NO.
SHEET NO.
REVISION NO.
DESIGNED
DRAWN
CHECKED
APPROVED
CONCEPT
DISCIPLINE REVIEW
ENG. REVIEWED
ISD APPROVED
SUBMITTED
A/E CONSULTANT FERMILAB DATE
N O
T
FO
R C
O N
ST
R
U C
TI
O
N
Arup US, Inc.
UIP - SUBPROJECT 2
KAUTZ ROAD SUBSTATION REPLACEMENT
DESCRIPTIONS
DATE
DATEREV.
Ju n
, 2
- 2 :3
6P M
A ut oD es k D oc s:
\A R
U P\
-0
Fe rm iL ab C am pu s In fra st ru ct ur e\
Pr oj ec t F ile s\
_W
IP
M od el s\ C
C iv il\
S he et s\ C
5- 3-
5-
7.
dw g
90% FINAL DESIGN06/19/250 06/19/25
06/19/25
06/19/25
06/19/25
J. SANDBERG
J. WOOD
J. BORGHESI
G. RUVALCABA
NTS
3-5-207
CIVIL
JU
N
E
, 2
C-5EXTERNAL IMPROVEMENTS
DETAILS
(P) SWITCHGEAR
BUILDING
CONNECT (P) 6" SD
TO (E) LIFT STATION
IE 732.00 (VIF)
(E) 6" SD
IE OUT: 736.5 (VIF)
TYP.
MH
RIM: 739.2
IE OUT: 734.5
SEE NOTE 2
PROPOSED 2"
PVC DUCT, REFER
TO ELECTRICAL
PROPOSED (2) - 4"
CONDUIT, REFER
TO ELECTRICAL
PLANS
PROPOSED 2"
PVC DUCT, REFER
TO ELECTRICAL
PROPOSED
COMED CONDUIT,
REFER TO
ELECTRICAL
PROPOSED 2"
PVC DUCT, REFER
TO ELECTRICAL
MH
1.50%
L=78.62'
1.50% L=45.04'
(P) SDMH
STATION = 0+54.30
RIM:739.00
(P) SDMH W/ OIL STOP VALVE
STATION = 0+09.26
RIM:739.00
RIM: 739.0
IE OUT: 734.00
E E
E E
E E
E E
E E
E E
E E
E E
E E
E E
E E
E
E
E
EEEEEE
0+00 0+40 0+80
-0+80 -0+40 1+20 1+60 2+00 2+40
1.50% L = 78.62'
EXISTING GROUND
(P) SDMH
STATION = 0+54.30
RIM: 739.001
IE IN: 733.18
IE OUT: 733.18
CONNECT TO
EXISTING LIFT
STATION
IE 732.00 (VIF)
(P) 6" PVC SD
(E) 18- 5" CONDUIT DUCTBANK
STATION = 0+84.69
TOP = 736.33 (VIF)
(E) 26-5" CONDUIT DUCTBANK
STATION = 0+97.86
TOP = 737.29 (VIF)
(P) SDMH W/ OIL STOP VALVE
STATION = 0+09.26
RIM 739.0
IE IN: 736.36 (VIF)
IE OUT: 733.85 1.50%
L=45.04'
(E) 6" PVC SD
35 East Wacker Drive Suite 1800 Chicago IL 60601 USA t: +1 312 849 5610 www.arup.com
SCALE:
REVISIONS PROJECT NO.
SHEET NO.
REVISION NO.
DESIGNED
DRAWN
CHECKED
APPROVED
CONCEPT
DISCIPLINE REVIEW
ENG. REVIEWED
ISD APPROVED
SUBMITTED
A/E CONSULTANT FERMILAB DATE
N O
T
FO
R C
O N
ST
R
U C
TI
O
N
Arup US, Inc.
UIP - SUBPROJECT 2
KAUTZ ROAD SUBSTATION REPLACEMENT
DESCRIPTIONS
DATE
DATEREV.
SCALE FEET
20 20 400
1. REFER TO SURVEY AND UTILITY NOTES ON SHEET C-1 FOR
THE SOURCE OF EXISTING TOPOGRAPHIC AND UTILITY
INFORMATION SHOWN ON THIS PLAN.
2. CONTRACTOR TO PROTECT AND SUPPORT EXISTING
DUCTBANK DURING CONSTRUCTION TO ENSURE DUCTBANK
REMAINS STABLE.
NOTES
LEGEND
EXISTING STORM DRAIN
PROPOSED STORM DRAIN
EXISTING MANHOLE
PROPOSED MANHOLE,
PER DETAIL 1/ C-7
PROPOSED CLEANOUT,
PER DETAIL 3/ C-7
EXISTING LIFT STATION
KEYNOTES
PROPOSED 12-5" CONDUITS DUCT BANK, PER
SEPARATE PACKAGE (BID OPTION)
2 CONNECT TO DOWNSPOUT WITH ADAPTER (TYP)
3 PROPOSED 4" PVC STORM DRAIN, 2.00% MIN.
4 PROPOSED 6" PVC STORM DRAIN
PROPOSED STORM DRAIN CLEANOUT PER DETAIL 3,
SHEET C-7
MH
6 EXISTING CONTAINMENT WALL
COMED TO PULL EXISTING FIBER BACK FROM KAUTZ ROAD
SUBSTATION TO HANDHOLE AT THE SOUTHEAST CORNER
OF SITE AND COMPLETE ANY REQUIRED SPLICING. NEW
CONDUIT TO BE INSTALLED BETWEEN EXISTING
HANDHOLES AS SHOWN FOR TEMPORARY COMED FIBER
PATH DURING CONSTRUCTION OF THE KAUTZ ROAD
SUBSTATION TO BE INSTALLED BY CONTRACTOR. COMED
TO ROUTE FIBER BACK INTO CONTROL BUILDING ONCE
CONSTRUCTION IS COMPLETE.
PROPOSED COMED FIBER
H: 1" = 20', V: 1" = 2.5'
STORM DRAIN PROFILE
1" = 20'
STORM DRAIN PLAN
A
1" = 2'-6"
2.5 2.5 5
SCALE FEET
E
S
W
TRUE
NORTH
Ju n
, 2
- 2 :4
7P M
A ut oD es k D oc s:
\A R
U P\
-0
Fe rm iL ab C am pu s In fra st ru ct ur e\
Pr oj ec t F ile s\
_W
IP
M od el s\ C
C iv il\
S he et s\ C
6- 3-
5-
7.
dw g
90% FINAL DESIGN06/19/250 06/19/25
06/19/25
06/19/25
06/19/25
J. SANDBERG
J. WOOD
J. BORGHESI
G. RUVALCABA
1" = 20'
3-5-207
CIVIL
JU
N
E
, 2
C-6COMPOSITE UTILITIES
PLAN
1. BACKFILL 95% DENSITY COMPACTED SOIL
2. SUBCONTRACTOR TO CONFIRM REQUIRED DISTANCE FROM INVERT OF DISCHARGE PIPE TO
BOTTOM OF MANHOLE FOR MOUNTING OF OIL STOP VALVE PRIOR TO ORDERING MANHOLES.
3. CONTRACTOR TO SUBMIT SHOP DRAWINGS STAMPED BY IL STRUCTURAL ENGINEER PRIOR TO
CONSTRUCTION.
-NTS
MANHOLE
LAWN AREAS MAINTAINED TO BE SEEDED
W/ SEED MIX PER FERMIFORWARD
ALL OTHER TURF AREAS ARE TO BE
SEEDED W/ SEED MIX PER FERMIFORWARD
NTS
TRENCH RESTORATION IN TURF AREAS 2
1. ANY AREAS REQUIRING PAVEMENT REPLACEMENT SHALL MATCH EXISTING PAVEMENT MATERIALS
AND THICKNESS.
2. BACKFILL THROUGH PAVEMENT AREAS SHALL BE COMPACTED CA-6 AGGREGATE TO PAVEMENT
SUB-BASE LEVEL.
NOTES
NOTE
FIN. GRADE RIM ELEV. (SEE PROFILE)
FG
45º ELBOW
45º WYE
4" PIPE RISER
4" SUBSOIL DRAIN
TREADED CAP
6-8" DIA VALVE BOX WITH
SOLID COVER MARKED "STORM"
NTS
STORM CLEANOUT 3
NTS
SD CONNECTION INTO SWITCHGEAR BUILDING 4
FINISHED GRADE
EXCAVATION
BACKFILL
COMPACTED TO
95% DENSITY
TOP SOIL
(MIN. 6")
SAND BACKFILL FA-6,
OR APPROVED EQUAL
SAND BACKFILL FA-6,
OR APPROVED EQUAL
IDOT CA-6
TRENCH BACKFILL
(HARDSTAND
COMPACT CA-6)
4" MOIST, WELL
COMPACTED SAND
BEDDING
NEW PIPE UTILITY
TRACER WIRE INTEGRAL
TO PIPING OR
MECHANICALLY
FASTENED TO PIPING AND
TERMINATED AT SURFACE
LEVEL TRACER WIRE
BOXES
POLYPROPYLENE
COATED STEPS @ 12"
ON CENTER
X-85 EXTERNAL GASKET CHIMNEY
SEAL AS MANUFACTURED BY
CRETEX SPECIALITY PRODUCTS
OR APPROVED EQUAL
PRECAST CONC.
MANHOLE SECTIONS
COMPACT SOIL
(SEE NOTE 1)
4" SAND CUSHION
6.0" PRECAST REINF.
CONC. SLAB OR
CAST-IN PLACE
ADJUSTABLE COLLARS
AS REQUIRED (12" MAX)
GRAVITY OPERATED
OIL STOP VALVE AS
MANUFACTURED BY
AFL INDUSTRIES, OR
APPROVED EQUAL
WHERE REQUIRED
1" DIA. VENT PIPE
(2) 1/2" DIA. S.S.
ANCHORS AND
STRAPS (TYP.)
PIPE
NEENAH R-1642 H-20 LOADING FRAME W/ TYPE "D"
SELF SEALING LID, MARKED STORM OR APPROVED
EQUAL
45° BEND
45° BEND
4" STORM PIPE
RAINWATER LEADER
4" STORM PIPE
AIR GAP
SUBSTATION WALL
MATCH EXISTING
(P) CONTAINMENT WALL PER STRUCTURAL
(E) TRANSFORMER
FOUNDATION
(P) CLAYMAX BENTONITE
LAYER OR APPROVED
EQUAL
1.5" WASHED GRAVEL
(P) 6" MIN. CLAY LINER (P) GEOTEXTILE FABRIC
(P) COMPACTED CA-6 BASE
12" COVER STORM 36" MIN. COVER SANITARY
VARIES
TRENCH EXCAVATION, IN
ACCORDANCE WITH 29 CFR PART 1926
12" MIN.
1/2 O.D.
TYP
4" BEDDING MIN.
48"
8"
MIN.
30"
24"
6"
48"
6"
REFER TO
STRUCTURAL PLANS
12' MIN.
NTS
OIL CONTAINMENT REINSTATEMENT 5
INVERT PER PLAN
35 East Wacker Drive Suite 1800 Chicago IL 60601 USA t: +1 312 849 5610 www.arup.com
SCALE:
REVISIONS PROJECT NO.
SHEET NO.
REVISION NO.
DESIGNED
DRAWN
CHECKED
APPROVED
CONCEPT
DISCIPLINE REVIEW
ENG. REVIEWED
ISD APPROVED
SUBMITTED
A/E CONSULTANT FERMILAB DATE
N O
T
FO
R C
O N
ST
R
U C
TI
O
N
Arup US, Inc.
UIP - SUBPROJECT 2
KAUTZ ROAD SUBSTATION REPLACEMENT
DESCRIPTIONS
DATE
DATEREV.
Ju n
, 2
- 2 :3
5P M
A ut oD es k D oc s:
\A R
U P\
-0
Fe rm iL ab C am pu s In fra st ru ct ur e\
Pr oj ec t F ile s\
_W
IP
M od el s\ C
C iv il\
S he et s\ C
7- 3-
5-
7.
dw g
90% FINAL DESIGN06/19/250 06/19/25
06/19/25
06/19/25
06/19/25
J. SANDBERG
J. WOOD
J. BORGHESI
G. RUVALCABA
NTS
3-5-207
CIVIL
JU
N
E
, 2
C-7COMPOSITE UTILITIES
DETAILS
| C-1 - CIVIL GENERAL NOTES AND ABBREVIATIONS |
| C-2 - CIVIL EXISTING CONDITIONS AND DEMOLITION PLAN |
| C-3 - CIVIL EROSION AND SEDIMENT CONTROL PLAN |
| C-4 - CIVIL EXTERNAL IMPROVEMENTS PLAN |
| C-5 - CIVIL EXTERNAL IMPROVEMENTS DETAILS |
| C-6 - CIVIL COMPOSITE UTILITIES PLAN |
| C-7 - CIVIL COMPOSITE UTILITIES DETAILS |
File details come from the government source that posted it. Updated .