QandA-Minos Roof and Masonry Wall1_Response_Final.pdf
PDF 178 KB Posted
- Solicitation number
- ISD_384202_DA
About this file
This is a Request for Information (RFI) and Responses document addressing 37 clarifications regarding a high-bay roof replacement and masonry wall repair project at Fermilab's Minos Service Building.
The project involves two phases: Phase 1 comprises a lump-sum masonry wall investigation and roof system scope, while Phase 2 consists of unit-price masonry repair work with quantities determined after field investigation. The roofing system is specified as a Sika Sarnafil adhered PVC membrane assembly (FM Assembly No. 461650-0-0) with R-30 minimum insulation (5.2 inches total, including 2.6-inch base layer and 2.6-inch tapered layer), 30-year total system labor and material warranty, and FM Approvals/RoofNav compliance. The anticipated Notice to Proceed date is approximately November 16, 2026, with a 140-calendar-day contract period. The bid bond requirement is 20 percent of the total proposed evaluation price, including lump-sum base items and extended unit-price totals. Key masonry work includes tuckpointing, brick replacement, coping stone resetting/replacement, through-wall flashing and membrane installation, weep/cavity restoration, and masonry joint/crack sealing. Approximately 125 matching 8x8 face bricks are available from the owner at no cost, with contractors responsible for furnishing any additional brick required. The roofing installer must be Sika-authorized with NRCA ProCertified Foreman credentials and five years' experience with the specified system. Masonry subcontractors must demonstrate documented successful performance on comparable projects. No retention will be held for the one-year leak detection test, but bidders must include pricing for testing until completion one year after initial testing. The building, constructed in 2004, has been tested for hazardous materials with results provided. Unforeseen metal deck repairs discovered after removal will be addressed through the change order process. Lightning rod reinstallation by qualified certified personnel is required in accordance with NFPA 780.
View the file
Other files
Show all 31
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
RFI # Question RESPONSE
Detail 3/A-02 identifies exterior-grade fire-treated wood blocking as part of the proposed roof assembly.
Please confirm whether the wood blocking shown is intended to be new blocking furnished and installed by the Contractor, or existing blocking to remain and be reused. If existing blocking is intended to remain, please confirm that replacement is required only where existing blocking is deteriorated, damaged, or otherwise unsuitable for the new roofing assembly.
Per the Detail 3/A-02 Sika Sarnaclad PVC scupper detail (Detail 1-5), the wood existing nailers can be retained if nailer is properly attached and If there is no visible damage/ deterioration.
The existing nailer may remain in place as long as it is installed correctly for new roof assembly as per manufacturers guidelines.
External grade fire treated wood blocking/nailer will be required if existing nailer is replaced.
The roof hatch detail requires removal of the existing 2'-0" x 8'-0" roof hatch and existing L5x3x1/4 frame, installation of new metal decking, and states “provide supplemental steel supports as required.” Please identify the required supplemental steel framing members, sizes, locations, connections, and attachment requirements necessary to support the new deck infill. Please also confirm that no other new structural steel framing is required as part of the project.
No supplemental steel is expected at the hatch opening, and the metal deck infill can be installed over existing roof framing.
During removal of the hatch, if interferences are identified requiring supplemental steel, subcontractor is to contact Construction Coordinator and Project Manager.
The Statement of Work, Section 2.0.B.1, indicates that the metal roof coping at the curtain wall parapet is to remain and be protected. The Project Manual indicates removal and replacement of roofing trim, fascia, gravel stops and coping. Please clarify the limits of existing coping to remain versus coping to be removed and replaced.
As stated in Statement of Work, existing coping at curtain wall parapets shall remain in place and be protected. All other roof edge metal associated with the roof replacement shall be removed and replaced per Section 076200 Sheet Metal Flashing and Trim and drawings.
Refer to Amendment 02- Revision 1 on revised Sheet A-01, Roof Plan dated 09/25/26 showing locations referring to Keynote A9 - Roof coping to remain and to be protected. Any deterioration or deformities must be communicated to Construction Coordinator and Project Manager before proceeding.
Sheet G-01 identifies RoofNav Assembly No. 213439-0-0 and FM Assembly No. 461650-0-0. Specification 075419 and the Statement of Work identify the Sika Sarnafil adhered assembly as RoofNav Assembly No.
461650-0-0. Please confirm the required FM RoofNav assembly/listing number to be used for bidding and construction.
Refer to Amendment 02-Revision 01 on sheet G-01. Please use FM Approvals/RoofNAVnumber 461650-0-0. ON sheet G-01 within the Design requirements for new roof, item 3 and item 4 should be FM Assembly NO/ RoofNAV Assembly no: 461650-0- 0.
Drawing G-02, Part 4 – Warranty Requirements, references a twenty (20) year total system labor and material warranty. Specification 075419 requires a thirty (30) year manufacturer special warranty and identifies installer qualifications and testing associated with the 30-year warranty. Please confirm the required warranty duration and warranty type for the new high-bay roof system.
Refer to Amendment 02- Revision 01 on sheet G-02 On drawing G-02, Part 4: warranty requirements, item E is revised to state the following:
E. UPON COMPLETION AND INSPECTION BY THE ROOFING MANUFACTURER'S REPRESENTATIVE, SUBCONTRACTOR SHALL ISSUE A THIRTY (30) YEAR TOTAL SYSTEM LABOR AND MATERIAL WARRANTY WITHOUT MONETARY LIMITATION COVERING ALL
DEFECTS IN MATERIAL AND WORKMANSHIP FOR THE TERM OF THE WARRANTY.
The Statement of Work requires inspection and repair of the existing metal roof decking "if necessary."
Because the condition and quantity of concealed deck repairs cannot be determined until the existing roofing is removed, please confirm whether bidders are to include an allowance/assumed quantity for deck repair in the base bid. If not, please confirm that unforeseen deteriorated decking discovered after tear-off will be addressed by Change Order.
Actual quantities will be measured in the field and reconciled through the change order process per the contract documents.
General Notes on Sheet G-02 identify potential work resulting from the masonry investigation including fluid-applied air barrier behind the veneer, grouting of CMU backup, stainless-steel parapet anchors, exterior insulation, and vertical expansion joints. These items do not appear to have corresponding unit-price items on the Price Proposal Form. Please identify which listed unit-price item each of these scopes is to be included under, or confirm that any such work determined necessary following the investigation will be separately priced and authorized.
Because the scope of repair of masonry wall is unknown, subcontractor must be prepared to correct items as required after investigation. Please refer to the information stated Request for Proposal Unit prices - Masonry Wall Repair- Phase 2. Field quantities will be determined after field investigation and will be field verified jointly by the Subcontractor, A/E and FFDG.
Please confirm whether the existing high-bay roofing system, flashings, mastics, coatings, or associated materials have been tested for asbestos or other hazardous materials. If testing has been performed, please provide the applicable survey/report.
The building was built in 2004. Please see enclosed report titled: PLM Results Report - Lab F - MINOS - F38FC - NWA
9 Camera curbs? Refer to keynote A4 on Roof Plan sheet A-01 of drawing set.
Please confirm whether the existing FFDG stock of matching face brick will be made available to the Contractor at no cost for use in Phase 2 repairs. If so, please provide the approximate quantity available.
Please also confirm that any additional brick required beyond the available stock is to be furnished by the Contractor under Unit Price Item 003-B.
Please refer to Drawing G-02 for estimated take offs. The current available face brick available at no cost to use in repairs is approximately 125 bricks (8x8).
Additional brick required beyond brick furnished by FFDG is to be furnished by the Subcontractor under Price Proposal Form - Subcontract Line Item Number 003-B.
Please provide the anticipated Notice to Proceed date. The project schedule requires masonry investigation and repair during the initial portion of the 140-calendar-day contract period. Sections
040120.63 and 040120.64 establish cold-weather requirements, including heating materials and existing masonry and providing heated enclosures when required. Please confirm that bidders are to include all required cold-weather protection, temporary enclosures, heating, and maintenance of curing temperatures within the applicable masonry investigation and unit prices.
The anticipated NTP date is approximately within the week of 11/16/2026. As per Statement of Work- 2.0 Scope of Work, Masonry Wall Repair- item C; Subcontractor will need to coordinate with FFDG Construction Coordinator and FFDG Architect/ Project manager for repair scope investigation as per sheet G-03. FFDG in cooperation with SGH Engineers and subcontractor will determine the finalized schedule at preconstruction meeting.
Please include necessary cold weather requirements in your bid according to Sections 040120.63 and 040120.64.
Metal deck deterioration: Where deteriorated metal roof deck is discovered only after the existing roofing is removed, please confirm whether deck repair/replacement is included in the Phase 1 lump-sum roof price without a stated allowance/quantity, or whether concealed deterioration beyond the documented scope will be handled as separately authorized work. If bidders are expected to carry an allowance or assumed quantity, please provide that basis.
Refer to RFI #6 response.
Hazardous materials: Please confirm whether existing roofing, coatings, masonry materials, sealants, or related materials within the work area have been surveyed/tested for asbestos, lead, PCBs, or other hazardous materials. If reports exist, please provide or identify them. Please also confirm the contractual treatment of previously unidentified hazardous material encountered during demolition or investigation.
Refer to RFI #8 response. Regarding contractual treatment of previously unidentified hazardous material, refer to the Project Manual, Section 013300 - Hazardous Materials: "If materials suspected of containing hazardous materials are encountered, do not disturb; immediately notify FFDG Construction Coordinator and Architect. Hazardous materials will be removed by Owner under a separate contract."
Concealed masonry conditions: Phase 2 quantities are to be established following the masonry investigation and jointly verified. Please confirm how concealed conditions requiring work that does not correspond to one of the listed Phase 2 unit-price items will be authorized and priced.
Refer to RFI # 7 response
Site logistics: Please confirm any project-specific restrictions not otherwise shown in the solicitation documents concerning contractor staging/laydown, dumpsters, overnight equipment/material storage, crane or aerial-lift use, delivery hours, and working hours that bidders should incorporate into pricing.
Refer to specification section 010010 General Requirements and Section 013100 ES&H Requirements Part 6. Refer to Sheet G- 03 Vicinity Plan has hours listed in the legend.
All bidders are required to submit a Corporate Quality Assurance Plan . The awarded Subcontractor will be required to submit a Project Quality Control Plan for review by FFDG as stated in Specification Section 014100 Quality Requirements.
Refer to Addendum 02-Revision 01- Sheet G-01 for Aerial Site Plan Utility Locations and Utilities Legend for more information on where existing Utilities are located and Site Plan - NUMSB 785 for suitable staging areas, possible dumpster locations, and area that must remain open. All areas in front of high bay doors and entrances must remain clear.
Bid bond basis: Please confirm the dollar basis to which the required 20% bid bond applies, specifically whether it is calculated from the Phase 1 lump-sum price only or from a total evaluated proposal amount incorporating the estimated Phase 2 quantities.
The bid bond amount shall be not less than 20% of the Total Proposed Evaluation Price, which includes all lump sum base items and the extended totals of all estimated unit-price items.
Past performance: Where specialized roofing and masonry work will be performed by proposed qualified subcontractors, please confirm whether relevant past performance and project experience of those key subcontractors may be submitted and considered in satisfying/evaluating the solicitation's experience and reference requirements.
Experience & Past Performance – Specialty Subcontractors (Roofing & Masonry) For specialized scopes (PVC roofing and brick masonry repair/repointing), the Owner will credit and evaluate the past performance and project experience of proposed specialty subcontractors toward the solicitation’s experience and reference requirements, subject to all of the following:
1. Roofing Installer Qualifications (Section 075419): The proposed roofing subcontractor must be approved/authorized/licensed by the roofing manufacturer; and employ an NRCA ProCertified Roofing Foreman or NRCA ProCertified thermoplastic system installers. The subcontractor must have ≥5 years experience with the proposed manufacturer’s system; provide ≥5 similar projects (last 3 years) with client contacts; and comply with required testing (e.g., fastener pull tests). Evidence shall include manufacturer certificates, FM/UL/Research listings, and independent product test reports required under Section 075419
2. Masonry Specialist Qualifications (Sections 040120.63 & 040120.64): The proposed masonry repair and repointing subcontractors must be experienced specialist firms with documented successful performance on comparable work; provide qualification statements for field supervisors and workers; include certification (at least one worker per crew) from the patching compound manufacturer when patching is required; and submit a written quality -control program per the specifications
3. Prime SubContractor Role: The Offeror must demonstrate successful past performance managing specialty subcontractors on similar projects and commit (in its proposal) that the named subcontractors will perform the major portion of the specialized scope for which their experience is considered.
Substitution Restrictions: Post-award substitution of any named specialty subcontractor whose experience was considered during evaluation requires prior Owner approval and submission of equivalent or superior qualifications and experience. The Owner may reject substitutions that diminish the evaluated capability.
4. Submission Timing: All specialty subcontractor experience, references, manufacturer approvals/certifications, and quality-control program documentation must be submitted with the proposal. Late submittals may be deemed non -responsive for experience evaluation.
Professional liability insurance: Please clarify the applicability of the stated Contractor's Professional Liability requirement to this construction scope, including whether the requirement applies to the prime contractor, only to a design professional performing delegated/design services, or to another specifically identified party.
Applicable to subcontracts that have design/build, delegated design, or construction management services requirements.
19 What quantity of brick is available for contractor to use? Refer to RFI #10 response 20 Will Fermilab provide a crane, or do we need to provide or own crane? Fermilab will not provide a crane.
Please confirm the masonry scope includes the entire exterior masonry wall, not just the area at the high bay roof.
Masonry wall repair scope includes the masonry wall in it's entirety. Please refer to drawings, sheet G-02 and Statement of Work.
Warranty term. For the roofing, the specifications call for a 30-year, 120 mph warranty, but plan sheet G- 02, Part 4, item E states 20 years. Please clarify which term governs.
Refer to RFI #5 response.
Please clarify the roof insulation requirements. Section 075419, 2.7, A., 5., a and b specifies a base layer of
2.6 inches and an upper layer of 2.6 inches (tapered). Is the intent that the upper or tapered layer has a
2.6 inch starting thickness? Also, is the required R-value an average of 30 or a minimum of 30?
Based on Specification section 075419, the roof insulation requirements are as follows:
The tapered insulation layer shall begin at a minimum thickness of 2.6 inches as defined in Section 075419, 2.7.A.5. The total required thermal resistance of the roof insulation assembly is a minimum R-30, not an average value. The tapered insulation layout must be configured such that the complete insulation assembly meets or exceeds R -30 at all locations on the roof.
Overflow scuppers. Depending on the answer to the insulation question, the new insulation package may bury the existing overflow scuppers. Based on their current locations directly below the existing coping caps, there may not be available height to raise them. How should the overflow scuppers be addressed?
Refer to sheet G-06, Detail C/A-14 for reference only showing the existing overflow scupper design. If additional insulation reduces the opening of the overflow scupper, this must be communicated to Construction Coordinator and Project Manager before proceeding. It is expected that the overflow scupper provide a minimum 3" x 12" wide overflow opening.
FM insured status. Is the building FM insured? This directly affects the required fastening and insulation adhesive patterns.
Fermilab is requiring that the roofing assembly meets FM Approvals/RoofNAVnumber 461650-0-0 and meet manufacturer requirements for assembly to meet wind load and design load requirements. Refer to project manual for more information.
Leak detection retention. The scope includes a leak detection system with a test performed after installation and again one year later. Will any retention be held for the year until the final test is performed?
Retention will not be held, however we are asking bidders to include a price for testing (as per spec) and this will be withheld until test is completed one year after initial testing. Refer to revised Price Proposal Form enclosed with Amendment 02.
Masonry Wall Repair Scope: The Price Proposal Form identifies Phase 1 as a lump-sum masonry wall investigation and Phase 2 as unit-price masonry repair work, with final quantities to be determined after the field investigation.
The SOW and drawings identify several potential repair conditions, including tuckpointing, brick replacement, coping stone resetting/replacement, through-wall flashing and membrane work, weep/cavity restoration, and masonry joint/crack sealing.
Please confirm whether the masonry unit-price items listed on the Price Proposal Form are intended to represent the complete pricing basis for Phase 2 masonry repair work.
If additional masonry-related work beyond the listed unit-price items is expected to be included in the proposal, please identify the required scope and pricing basis so all bidders can price the work consistently.
Refer to RFI #7 response.
Electrical Scope: The contract documents reference relocation and reinstallation of existing rooftop equipment and also identify existing electrical conduits located below the roof deck and within the deck flutes that require coordination during the roofing work.
Please clarify whether any specific electrical work is required as part of this project.
If electrical work is required, please identify the intended scope, including whether the contractor is expected to provide any of the following:
•Disconnect and reconnect of exisƟng rooŌop equipment;
•Temporary electrical power or temporary disconnects;
•ModificaƟon, relocaƟon, or replacement of exisƟng conduit or wiring;
•Electrical work associated with antennas, cameras, roof-mounted equipment, or other exisƟng systems;
•Any other Division 26 work required for compleƟon of the project.
If no separate electrical installation scope is intended and the electrical references are limited to protection and coordination with existing systems, please confirm.
As noted in #3 of General Notes for Drawing A-01, the subcontractor is responsible for locating any existing conduit locations in flutes of metal decking. Conduits must be located , coordinated, and marked on roofing materials prior to installation of any mechanical fasteners. Confirmation with Fermilab construction coordinator is required prior to installation of mechanical fasteners.
There is no existing rooftop equipment requiring electrical work. No separate electrical installation scope that is part of this contract other than installer requirements for lightning rod reinstallation.
Lightning Rod reinstallation: : Addendum 02 -Revision 01- sheet A-01 - keynote A11 is revised to state:
EXISTING LIGHTNING ROD TO REMAIN. PRIOR TO REMOVAL, THE SUBCONTRACTOR SHALL DOCUMENT EXISTING CONDITIONS.
PROVIDE REMOVAL, TEMPORARY PROTECTION, REINSTALLATION, ADJUSTMENT, AND CERTIFICATION OF THE EXISTING LIGHTNING PROTECTION SYSTEM BY A QUALIFIED LIGHTNING PROTECTION SUBCONTRACTOR. THE LIGHTNING PROTECTION SUBCONTRACTOR SHALL EMPLOY PERSONNEL CERTIFIED BY THE LIGHTNING PROTECTION INSTITUTE (LPI) AS A MASTER INSTALLER OR MASTER INSTALLER/DESIGNER, OR BE A UL LISTED LIGHTNING PROTECTION SYSTEM INSTALLER.
REINSTALLATION OF LIGHTNING ROD SHALL BE IN ACCORDANCE WITH NFPA 780 AND UL 96A. PROVIDE FINAL INSPECTION AND
CERTIFICATION DOCUMENTATION AT PROJECT COMPLETION.
Unforeseen metal deck repair pricing: Please clarify the pricing basis for unforeseen metal roof deck repairs discovered after removal of the existing roofing system. Should bidders include an assumed allowance or quantity in the base bid, or will unforeseen deck repairs be addressed separately after existing conditions are exposed?
Refer to RFI #2 response.
Please clarify the required extent of masonry wall dismantling during the Phase 1 scope investigation. Is the contractor required to open only one location at the highest point of the wall, or should multiple exploratory openings be included to investigate coping, flashing, membrane, cavity, and drainage conditions?
The investigative area is at the highest point of the wall above the high bay area. No other areas are expected to be opened unless investigation deems additional areas to be tested. Please include in your estimate a fee for multiple openings.
Please provide the anticipated size and number of masonry/coping exploratory openings to be included in the lump-sum investigation price. The documents require investigation of concealed conditions but do not establish a defined quantity.
Refer to RFI #30 response.
Following exploratory demolition, should the contractor fully reconstruct the opened masonry/coping condition during Phase 1, or only provide temporary weatherproofing until FFDG approves the permanent repair approach? The SOW states that opened portions must be weather-tight at completion of the investigation.
Bidders to provide a price for Phase 1 investigation showing that closing of investigation areas are permanent and weather-tight.
Please confirm whether the contractor should assume full-height/full-length scaffold access along the entire curved masonry wall for the duration of the repair work, or whether localized lifts/scaffolding are acceptable.
The contract documents do not dictate the contractor’s means and methods for accessing the curved masonry wall. Either full-height scaffolding or localized lifts/scaffolding may be used at the contractor’s discretion, provided the selected approach allows the work to meet all specified performance, safety, and quality requirements.
The design intent requires that the masonry repair be completed in accordance with the drawings and specifications; however, the contractor is responsible for determining the appropriate temporary access systems and construction sequencing necessary to achieve this.
Please confirm that exploratory masonry/coping removal, investigation, temporary weatherproofing, documentation, and preparation of the repair approach are included in the lump-sum Phase 1 investigation price, while permanent repairs identified after investigation will be paid under the applicable unit-price items.
Confirmed.
Are we responsible for any third-party testing associated with the phase 1 investigation? Engineers - Simpson Gumpertz and Heger (SGH) have been contracted by FFDG to provide investigation services for wall repair.
Their scope of work is to work with Subcontractor and FFDG to investigate the wall repair. SGH will assess, report findings and recommendations for the observed brick veneer on cmu wall (exterior wall) deterioration and water infiltration issues at the Minos Service Building.
If any additional third party testing is required, Subcontractor must include this in their Phase I investigation price.
Can you explain the scope of work behind item 003-G? Is this at existing control/expansion joints? It is expected that any Masonry Joint/ Crack injection and sealing: Deep-fill sealant or specialized elastometric joint sealant at coping/ wall stress points will occur at existing locations. There may be additional locations/ quantities and factors determined after field investigation and this will be field verified jointly by the Subcontractor, SGH and FFDG.
The contract documents identify the new high-bay roofing system as a Sika Sarnafil adhered PVC assembly and require the roofing installer to be an authorized Sika Sarnafil applicator. The roofing specification also references the possibility of approved equal products meeting the specified performance requirements.
Please confirm whether a Johns Manville roofing system meeting the specified membrane thickness, FM RoofNav, wind-uplift, warranty, and other performance requirements would be considered an acceptable substitute for the specified Sika Sarnafil system.
If substitutions are permitted, please also confirm whether the Sika Authorized Applicator qualification requirement would be waived or replaced by the applicable Johns Manville installer qualification requirements for the substituted system.
Substitution of the specified PVC roofing system by another roofing manufacturer is not permitted. Refer to the revisions to Section 075419 Polyvinyl-Chloride (PVC) Roofing (pg. 7 of the Section 075419 document) with Amendment 02.