This document provides details of a solicitation notice for construction services related to the LBJ Consolidation and Switchgear project. The General Services Administration Public Buildings Service is seeking a firm fixed price contract to perform repair, alteration, and construction services including interior alterations and open workspace construction as well as significant renovations to the major switchgear and electrical systems servicing the building. The work will renovate floors 3, 4, 6, and 7 totaling approximately 198,369 square feet of open office space as well as 10,000 square feet of bathroom reconstruction for the Department of Education to allow for approximately 600 additional employees to occupy the LBJ Building. Interested firms must attend the pre-proposal conference on May 5, 2021 and submit a proposal by June 4, 2021. The North American Industry Classification code for this work is 236220 and has a small business size standard of $39.5 million in average annual receipts over the past three years.
View the file
Other files for this federal contract opportunity
Show all 50
Solicitation Notice - LBJ Consolidation & Switchgear has more files on GovTribe.
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
N
SYMBOL
ALL SYMBOLS SHOWN MAY NOT APPEAR IN ALL DRAWINGS. SYMBOLS ARE SHOWN SCHEMATIC AND MAY NOT BE TO SCALE.
DATA SYMBOLS LEGEND
DESCRIPTION
DATA AND/OR VOICE OUTLET, N=CABLE QUANTITY. PROVIDE
DOUBLE GANG BACK, 2 1/8" DEEP, WITH SINGLE GANG DEVICE
COVER AND 1" CONDUIT STUBBED ABOVE ACCESSIBLE CEILING
SPACE.
DATA BACKBOX SCHEDULE
SYMBOL DESCRIPTION
AA
DOUBLE GANG BACK BOX, 2 1/8" DEEP, WITH SINGLE GANG DEVICE COVER AND 1" CONDUIT PATHWAY STUBBED
ABOVE ACCESSIBLE CEILING SPACE.
BB
CC
DD
WALL PHONE STYLE FACEPLATE, DOUBLE GANG BACK BOX, 2 1/8" DEEP, WITH SINGLE GANG DEVICE COVER AND
1" CONDUIT PATHWAY STUBBED ABOVE ACCESSIBLE CEILING SPACE.
REFER TO ELECTRICAL (E) SHEETS FOR ROUGH IN REQUIREMENTS.
OUTLET TO BE HOUSED ABOVE ACCESSIBLE CEILING. CABLE TO LOCATION SHOWN ON THE FLOOR PLANS AND
LEAVE A MINIMUM 50 FEET COILED AT THE LOCATION.
N
N N
N N
MNTG. HT. UNO
(SEE NOTE 1)
BACK BOX
AA 18" WALL AFF
AA
BB
BB
48" WALL AFF
CC FLOOR
= EMPTY BACK BOX
= 1 DATA CABLE
= 2 DATA CABLES
= 3 DATA CABLES
= 4 DATA CABLES
= 1 VOICE CABLE
= 2 VOICE CABLES
= 1 DATA / 1 VOICE CABLES
= 2 DATA / 1 VOICE CABLES
= 2 DATA / 2 VOICE CABLES
2V
3D,1V
= 3 DATA / 1 VOICE CABLES
= 1 DATA / 3 VOICE CABLES
1D,3V
OR
W W
OR
OR
N N
OR
OR
W W
48" WALL AFF
42" WALL AFF
OR
N
WAP
DATA AND/OR VOICE OUTLET, WALL PHONE STYLE FACEPLATE, 1
DATA/VOICE CABLE. PROVIDE DOUBLE GANGE BACK BOX, 2 1/8"
DEEP, WITH SINGLE GANGE DEVICE COVER AND 1" CONDUIT
STUBBED ABOVE ACCESSIBLE CEILING SPACE.
DATA AND/OR VOICE OUTLET, WALL PHONE STYLE FACEPLATE, 1
DATA/VOICE CABLE, MOUNTED ABOVE COUNTER. PROVIDE DOUBLE
GANGE BACK BOX, 2 1/8" DEEP, WITH SINGLE GANGE DEVICE COVER
AND 1" CONDUIT STUBBED ABOVE ACCESSIBLE CEILING SPACE.
DATA AND/OR VOICE OUTLET, N = CABLE QUANTITY, MOUNTED
ABOVE COUNTER. PROVIDE DOUBLE GANGE BACK BOX, 2 1/8" DEEP,
WITH SINGLE GANGE DEVICE COVER AND 1" CONDUIT STUBBED
ABOVE ACCESSIBLE CEILING SPACE.
FLOOR MOUNTED DATA AND/OR VOICE OUTLET, N = CABLE
QUANTITY. REFER TO ELECTRICAL SHEETS FOR ROUGH IN
REQUIREMENTS.
CEILING MOUNTED DATA AND/OR VOICE OUTLET, N = CABLE
QUANTITY. OUTLET TO BE HOUSED ABOVE ACCESSIBLE CEILING.
CABLE TO LOCATION SHOWN ON FLOOR PLANS.
DD
ABOVE
ACCESSIBLE
CEILING
DD
ABOVE
ACCESSIBLE
CEILING
CEILING MOUNTED WIRELESS ACCESS POINT, N = CABLE QUANTITY.
OUTLET TO BE HOUSED ABOVE ACCESSIBLE CEILING. CABLE TO
LOCATION SHOWN ON FLOOR PLANS.
DATA NOTES:
1. REFER TO ARCHITECTURAL ELEVATIONS FOR EXACT MOUNTING HEIGHTS OF ALL DEVICES.
2. 48" AFF INDICATES TO THE TOP OF THE DEVICE
3. 18" AFF INDICATES TO THE CENTER OF DEVICE
4. 60" AFF INDICATES TO THE BOTTOM OF DEVICE
5. 80" AFF INDICATES TO THE BOTTOM OF DEVICE
6. ALL OTHER MOUNTING HEIGHTS REFER TO CENTERLINE OF DEVICE
FN
SYSTEMS FURNITURE DATA OUTLET. N = CABLE QUANTITY.
PROVIDE AND INSTALL FOUR PORT SYSTEMS FURNITURE
FACEPLATE ONTO FURNITURE RACEWAY SYSTEM.
N/A SYSTEMS
FURNITURE
COMMUNICATIONS ABBREVIATIONS (FOR CLARIFICATION ONLY)
• EX EXISTING
• AFF ABOVE FINISHED FLOOR
• AFC ABOVE FINISHED CEILING
• BFC BELOW FINISHED CEILING
• W WALL PHONE
• MON MONITOR
J
CT
LR
JUNCTION BOX - SIZE AND MOUNTING AS REQUIRED.
MEDIUM DETAIL LEVEL
COARSE DETAIL LEVEL
FINE DETAIL LEVEL
CABLE TRAY - MAIN CABLE PATH SEE DETAIL FOR MORE INFORMATION.
MEDIUM DETAIL LEVEL
COARSE DETAIL LEVEL
FINE DETAIL LEVEL
LADDER RUNWAY - SIZE AND LOCATION AS SHOWN ON DRAWINGS.
FS 2", UNLESS NOTED OTHERWISE, HILTI SPEED SLEEVE FIRE RATED PATHWAY DEVICE, PART NUMBER 2097882, THROUGH RATED WALL.
2", UNLESS NOTED OTHERWISE, EMT SLEEVE EQUIPPED WITH PLASTIC BUSHING ON BOTH ENDS, THROUGH WALL.
RATING SHALL MATCH WALL BEING PENETRATED. REFER TO ARCHITECTURAL DRAWINGS FOR WALL RATINGS.
VERTICAL CORE AND SLEEVE THROUGH FLOOR. PROVIDE EMT SLEEVE, EQUIPPED WITH PLASTIC BUSHING ON BOTH ENDS. REFER TO FLOOR PLAN FOR SIZING. RATING SHALL MATCH FLOOR BEING PENETRATED. REFER TO
ARCHITECTURAL DRAWINGS FOR FLOOR RATINGS.
2-POST FREESTANDING EQUIPMENT RACK. SIZE AND LOCATION AS SHOWN.
4-POST FREESTANDING EQUIPMENT RACK. SIZE AND LOCATION AS SHOWN.
VERTICAL WIRE MANAGER. SIZE AND LOCATION AS SHOWN.
GROUND BUSS BAR - 1/4" x 2" x 10", PANDUIT OR EQUAL.
• TV TELEVISION
• CT CABLE TRAY
• PRT PRINTER
• CPU COMPUTER
• MFD MULTI_FUNCTION DEVICE
SYMBOL
ALL SYMBOLS SHOWN MAY NOT APPEAR IN ALL DRAWINGS. SYMBOLS ARE SHOWN SCHEMATIC AND MAY NOT BE TO SCALE.
COMMUNICATIONS GENERAL SYMBOLS LEGEND
DESCRIPTION
FLOOR BOX FEEDER FOR SYSTEMS FURNITURE WORK AREA OUTLETS.
TV1
SYMBOL
ALL SYMBOLS SHOWN MAY NOT APPEAR IN ALL DRAWINGS. SYMBOLS ARE SHOWN SCHEMATIC AND MAY NOT BE TO SCALE.
TELEVISION SYMBOLS LEGEND
DESCRIPTION
TELEVISION OUTLET, ONE COAX CABLE
DATA BACKBOX SCHEDULE
SYMBOL DESCRIPTION
AA
DOUBLE GANG BACK BOX, 2 1/8" DEEP, WITH SINGLE GANG DEVICE COVER AND 1" CONDUIT PATHWAY STUBBED
ABOVE ACCESSIBLE CEILING SPACE. FOR TV4 CONDUIT SIZE 1 1/4".
BB
CC
DATA NOTES:
1. REFER TO ARCHITECTURAL ELEVATIONS FOR EXACT MOUNTING HEIGHTS OF ALL DEVICES.
2. 48" AFF INDICATES TO THE TOP OF THE DEVICE
3. 18" AFF INDICATES TO THE CENTER OF DEVICE
4. 50" AFF INDICATES TO THE BOTTOM OF DEVICE
5. 80" AFF INDICATES TO THE BOTTOM OF DEVICE
6. ALL OTHER MOUNTING HEIGHTS REFER TO CENTERLINE OF DEVICE
7. COORDINATE FINAL OUTLET LOCATION WITH TELEVISION MOUNTING BRACKETS
MNTG. HT. UNO
(SEE NOTE 1)
BACK BOX
AA
TV2
TELEVISION OUTLET, ONE DATA CABLE AA
TV3
TELEVISION OUTLET, ONE DATA CABLE & ONE COAX CABLE AA
DOUBLE GANG BACK BOX, 2 1/8" DEEP, WITH DUAL GANG DEVICE COVER AND 1" CONDUIT PATHWAY STUBBED
ABOVE ACCESSIBLE CEILING SPACE.
OUTLET TO BE HOUSED ABOVE ACCESSIBLE CEILING. IF LOCATED IN NON ACCESSIBLE CEILING SPACE PROVIDE
BACK BOX "AA".
NOTE 7
TV4
TELEVISION OUTLET, TWO DATA, ONE COAX & ONE HDMI
NOTE 7
NOTE 7
NOTE 7
0 - - N.T.S.
CHECKED BY
DRAWN BY
FLOOR NUMBER
DRAWING TITLE
SHEET
NUMBER
SUBMISSION DATE
SUBMISSION STAGE
GSA PM
GSA PROJECT NO.
PROJECT
DESCRIPTION
PROJECT TITLE
BULDING NAME
ADDRESS
BUILDING NUMBER
PRIME CONTR. NO.
PRIME ORDER NO.
CONST. CONTR.
A/E
SUB A/E
CONST. CONTR. NO.
SHEET SIZE:
DATE DRAWN:
36 X 48
S H
E E
T
ID
E N
TI
FI
C A
TI
O
N
DISCIPLINE
P R
O
JE
C T
ID
E
N
TI
FI
C
A
TI
O N
B U
IL
D
IN
G
BIM FILE NAME
C O
N
TR
A C
TO
R
S R
E V
IS
IO
N B
LO
C
K G
R A
P H
IC
S
C A
LE
K
E Y
P
LA
N S
TA
M
P O
R S
E A
L D
E S
IG
N
E R
ID
E
N
TI
FI
C
A
TI
O N
O W
N E
R
ID
E N
TI
FI
C A
TI
O
N
SHEET OF SHEETS
KRUECK & SEXTON ARCHITECTS, P.C.
400 MARYLAND AVENUE, SW
WASHINGTON, DC 20024
LYNDON B. JOHNSON FEDERAL BUILDING
DC0010ZZ
DC0010_A_3-4-6-7_r2020.rvt
WSP ENGINEERING
DEPARTMENT OF EDUCATION
CONSOLIDATION PROJECT
ISSUE FOR BID
HALLIE FUTTERMAN
RENOVATION OF FLOORS 3, 4, 6, & 7 OF THE EXISTING
BUILDING TO MEET THE DEPARTMENT OF
EDUCATION’S PROGRAMMATIC REQUIREMENTS.
GS-07-P-16-UC-D-7000
47PM0520F0002
47PM0520F0002
KRUECK & SEXTON ARCHITECTS
221 W ERIE ST
CHICAGO, IL 60654 (312) 707-0056
ARCHITECT
WSP ENGINEERING
ONE PENNSYLVANIA PLAZA, SECOND FLOOR
NEW YORK, NY 10119 (212) 465-5000
MEP ENGINEER
ATELIER TEN
45 E 20TH ST, 4TH FLOOR
NEW YORK, NY 10003 (312) 386-1400
SUSTAINABILITY CONSULTANT
THRESHOLD ACOUSTICS
141 W JACKSON BLVD, SUITE 2080
CHICAGO, IL 60604 (312) 386-1400
ACOUSTIC CONSULTANT
WEST EAST
M A
TC
H
LI
N
E
GENERAL SERVICES ADMINISTRATION
NATIONAL CAPITAL REGION
PUBLIC BUILDING SERVICE, D.C. SERVICES DIV.
7TH & D STREET, S.W.
WASHINGTON, D.C. 20407
ISSUE
NO. DATE ISSUE
COMMUNICATIONS
VARIES, SEE DRAWINGS
01 04/23/2021 ISSUED FOR BID
/2
/2
:4
:1
P
M
T-00-01
TELECOM LEGENDS, SYMBOLS, AND ABBREVIATIONS
04/23/21
04/20/21FT
JMM
1. ALL COMMUNICATIONS PRODUCTS AND INSTALLATIONS SHALL COMPLY WITH ALL APPLICABLE STATE
AND LOCAL CODES. REFER TO SPECIFICATIONS FOR MATERIALS AND METHODS FOR
COMMUNICATIONS CONSTRUCTION.
2. CONTRACTOR SHALL OBTAIN ALL NECESSARY PERMITS, PAY ALL FEES AND COMPLY WITH ALL NATIONAL, STATE AND MUNICIPAL LAWS, CODES AND ORDINANCES RELATING TO BUILDING AND
PUBLIC SAFETY.
3. CONTRACTOR SHALL FURNISH ALL MATERIALS, EQUIPMENT AND LABOR REQUIRED FOR A COMPLETE
WORKING AND COORDINATED SYSTEM.
4. UNLESS OTHERWISE NOTED, ALL EQUIPMENT AND MATERIALS SHALL BE NEW AND U.L. LISTED OR LABELED. EQUIPMENT AND MATERIALS SHALL BE INSTALLED IN ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS, AND LISTING OR LABELING REQUIREMENTS AND RESTRICTIONS. PROVIDE DATA
DEPICTED IN THE COMMUNICATIONS SPECIFICATIONS.
5. CONTRACTOR SHALL PROVIDE SHOP DRAWINGS FOR APPROVAL FOR ALL COMMUNICAITONS
MATERIALS PROPOSED TO BE PROVIDED UNDER THIS CONTRACT. ANY DEVIATIONS FROM ITEMS
SPECIFIED SHALL BE CLEARLY IDENTIFIED. NO WORK IS AUTHORIZED WITHOUT SHOP DRAWINGS
REVIEWED BY ENGINEER.
6. REFER TO AND COORDINATE WITH ARCHITECTURAL DRAWINGS FOR EXACT LOCATION OF ALL DEVICES
AND EQUIPMENT.
7. REFER TO AND COORDINATE WITH DIVISION 23 FOR THE LOCATION OF ALL ITEMS LOCATED IN THE CEILING INCLUDING, BUT NOT LIMITED TO, SUPPLY-AIR DIFFUSERS, RETURN-AIR DIFFUSERS AND FIRE
SPRINKLER HEADS.
8. ALL PENETRATIONS THROUGH FIRE RATED WALLS OR PARTITIONS SHALL BE MADE IN ACCORDANCE WITH U.L. 483 "FIRE RESISTANCE DIRECTORY". PENETRATIONS SHALL BE SLEEVED AND SEALED WITH A U.L. APPROVED FIRE RATED SEALANT. REFER TO ARCHITECTURAL PLANS FOR ALL RATED WALLS.
9. CONTRACTOR SHALL COORDINATE AND SCHEDULE ALL OUTAGES WITH OWNER'S REPRESENTATIVE.
10. CONTRACTOR SHALL WARRANTY WORK FOR (1) YEAR FROM COMPLETION OF THE PROJECT AND
PROVIDE OWNER AS BUILT DRAWINGS.
11. SPACE ALLOCATIONS FOR MATERIAL, EQUIPMENT AND DEVICES HAVE BEEN MADE ON THE BASIS OF
PRESENT AND KNOWN FUTURE REQUIREMENTS AND THE DIMENSIONS OF ITEMS OF EQUIPMENT OR DEVICES OF A PARTICULAR MANUFACTURER WHETHER INDICATED OR NOT. THE CONTRACOR SHALL VERIFY THAT ALL MATERIALS, EQUIPMENT AND DEVICES PROPOSED FOR USE ON THIS PROJECT ARE
WITHIN THE CONSTRAINTS OF THE ALLOCATED SPACE.
12. ALL EMPTY CONDUIT SYSTEMS SHALL CONTAIN A PULL WIRE FOR FUTURE PULLING OF CONDUCTORS.
GENERAL NOTES:
1. INFORMATION PROVIDED ON THESE DRAWINGS HAS BEEN TAKEN FROM DESIGN DRAWING AND FIELD OBSERVATIONS. CONTRACTOR SHALL VERIFY ALL EXISTING CONDITIONS PRIOR TO PRICING AND
COMMENCEMENT OF WORK.
2. WHERE EXISTING WALLS ARE DEMOLISHED, REMOVE ALL EXISTING WIRING DEVICES AND THEIR
ASSOCIATED CONDUITS AND WIRING BACK TO THE POINT OF ORGINATION.
3. PROVIDE FOR ANY AND ALL DEMOLITION WORK NECESSARY TO ACCOMMODATE ALL NEW
CONSTRUCTION, INCLUDING ARCHITECTURAL, MECHANICAL, PLUMBING OR ELECTRICAL WORK.
4. IF DEMOLITION IS REQUIRED TO INSTALL AN ITEM, THE CONTRACTOR SHALL RESTORE THE AREA TO
PREVIOUS CONDITION, OR REPLACE DAMAGED ITEMS WITH NEW ITEMS TO MATCH EXISTING.
5. SPACE ALLOCATIONS FOR MATERIALS, EQUIPMENT AND DEVICES HAVE BEEN MADE ON THE BASIS OF
PRESENT AND KNOWN FUTURE REQUIREMENTS AND DIMENSIONS OF ITEMS OF EQUIPMENT OR
DEVICES OF A PARTICULAR MANUFACTURER, WHETHER INDICATED OR NOT. THE CONTRACTOR SHALL VERIFY THAT ALL MATERIALS, EQUIPMENT AND DEVICES PROPOSED FOR USE ON THIS PROJECT ARE
WITHIN THE CONSTRAINTS OF THE ALLOCATED SPACE.
6. VERIFY THAT ANY DEVICES LOCATED OUTSIDE OF CONSTRUCTION AREA REMAINS IN PROPER
OPERATING FUNCTION.
7. ANY EXISTING CABLING TO REMAIN WITHIN CONSTRUCTION AREA NOT SUPPORTED PROPERLY SHALL
BE SUPPORTED AS PART OF THE PROJECT.
8. EXISTING ABANDONED CABLE LOCATED IN CONSTRUCTION AREA SHALL BE REMOVED BACK TO POINT
OF ORIGINATION PER NEC ARTICLES 725.25, 770.25 & 800.25.
9. RETURN ALL IT INFRASTRUCTURE (I.E. COMPUTERS, PHONES, WIRELESS ACCESS POINTS, ETC.) TO THE IT DEPARTMENT. COORDINATE WITH OWNER'S IT REPRESENTATIVE AS TO PROPER LOCATION.
GENERAL DEMO NOTES:
(312) 787-0056
FORCADE DESIGN
1626 PAYNE STREET
EVANSTON, IL 60201 (847) 448-4270
19" RELAY
RACK
FRONT
" R
EL
AY
RA
C
K
FR
O N
T
3a
3a
20a
20a
F F
E E
D D
C C
B B
A A
A A
B B
C C
D D
E E
F F
3a
3a
20a
20a
A A
B B
C C
D D
E E
F F
3a
3a
20a
20a
3a
3a
20a
20a
F F
E E
D D
C C
B B
A A
A A
B B
C C
D D
E E
F F
3a
3a
20a
20a
A. REFER TO AND COORDINATE WITH ARCHITECTURAL FLOOR PLANS,
ELEVATIONS AND DETAILS FOR ADDITIONAL DETAILS PERTAINING
TO THIS SHEET.
B. REFER TO SHEET T-00-01 FOR SYMBOLS APPEARING ON THIS
SHEET.
C. WHERE EXISTING WALLS ARE DEMOLISHED, REMOVE ALL EXISTING
COMMUNICATIONS/LOW VOLTAGE DEVICES AND THEIR
ASSOCIATED CONDUITS AND WIRING BACK TO ORIGINATION.
EXISTING CABLING PASSING THROUGH DEMO AREA, NOT BEING
DEMOLISHED, SHALL BE SUPPORTED UTILIZING J-HOOK CABLE
SUPPORTS PER TIA STANDARDS.
D. EXISTING EQUIPMENT RACKS AND WALL BOARD CURRENTLY
LOCATED WITHIN THE EXISTING TELECOM ROOMS SHALL REMAIN
AS IS AND REUSED.
E. THERE IS NO SCOPE FOR WAPs. THE EXISTING WAPs AND CABLING
MUST BE FUNCTIONAL UPON SUBSTANTIAL COMPLETION. THE
CONTRACTOR CAN DETERMINE WHETHER TO REMOVE OR
PROTECT IN PLACE. ALL WORK SHALL BE COORDINATED WITH THE
GENERAL CONTRACTOR AND FINAL TESTING OF THE SYSTEM
SHALL BE COORDINATED WITH THE GOVERNMENT.
0 16' 32' 1/16"=1'-0"
SENSITIVE BUT UNCLASSIFIED (SBU) PROPERTY OF THE UNITED STATES GOVERNMENT COPYING, DISSEMINATION, OR DISTRIBUTION OF THIS DOCUMENT TO UNAUTHORIZED RECIPIENTS IS PROHIBITED.
Do not remove this notice. Properly destroy or return documents when no longer needed.
TRUE NORTH
PLAN NORTH
CHECKED BY
DRAWN BY
FLOOR NUMBER
DRAWING TITLE
SHEET
NUMBER
SUBMISSION DATE
SUBMISSION STAGE
GSA PM
GSA PROJECT NO.
PROJECT
DESCRIPTION
PROJECT TITLE
BULDING NAME
ADDRESS
BUILDING NUMBER
PRIME CONTR. NO.
PRIME ORDER NO.
CONST. CONTR.
A/E
SUB A/E
CONST. CONTR. NO.
SHEET SIZE:
DATE DRAWN:
36 X 48
S H
E E
T
ID
E N
TI
FI
C A
TI
O
N
DISCIPLINE
P R
O
JE
C T
ID
E
N
TI
FI
C
A
TI
O N
B U
IL
D
IN
G
BIM FILE NAME
C O
N
TR
A C
TO
R
S R
E V
IS
IO
N B
LO
C
K G
R A
P H
IC
S
C A
LE
K
E Y
P
LA
N S
TA
M
P O
R S
E A
L D
E S
IG
N
E R
ID
E
N
TI
FI
C
A
TI
O N
O W
N E
R
ID
E N
TI
FI
C A
TI
O
N
SHEET OF SHEETS
KRUECK & SEXTON ARCHITECTS, P.C.
400 MARYLAND AVENUE, SW
WASHINGTON, DC 20024
LYNDON B. JOHNSON FEDERAL BUILDING
DC0010ZZ
DC0010_A_3-4-6-7_r2020.rvt
WSP ENGINEERING
DEPARTMENT OF EDUCATION
CONSOLIDATION PROJECT
ISSUE FOR BID
HALLIE FUTTERMAN
RENOVATION OF FLOORS 3, 4, 6, & 7 OF THE EXISTING
BUILDING TO MEET THE DEPARTMENT OF
EDUCATION’S PROGRAMMATIC REQUIREMENTS.
GS-07-P-16-UC-D-7000
47PM0520F0002
47PM0520F0002
KRUECK & SEXTON ARCHITECTS
221 W ERIE ST
CHICAGO, IL 60654 (312) 707-0056
ARCHITECT
WSP ENGINEERING
ONE PENNSYLVANIA PLAZA, SECOND FLOOR
NEW YORK, NY 10119 (212) 465-5000
MEP ENGINEER
ATELIER TEN
45 E 20TH ST, 4TH FLOOR
NEW YORK, NY 10003 (312) 386-1400
SUSTAINABILITY CONSULTANT
THRESHOLD ACOUSTICS
141 W JACKSON BLVD, SUITE 2080
CHICAGO, IL 60604 (312) 386-1400
ACOUSTIC CONSULTANT
WEST EAST
M A
TC
H
LI
N
E
GENERAL NOTESLEGEND KEY NOTES
GENERAL SERVICES ADMINISTRATION
NATIONAL CAPITAL REGION
PUBLIC BUILDING SERVICE, D.C. SERVICES DIV.
7TH & D STREET, S.W.
WASHINGTON, D.C. 20407
ISSUE
NO. DATE ISSUE
COMMUNICATIONS
VARIES, SEE DRAWINGS
01 04/23/2021 ISSUED FOR BID
/2
/2
:4
:0
P
M
TD-13-01
TELECOMMUNICATIONS DEMOLITION - LEVEL 3
04/23/21
04/20/21FT
JMM
1/16" = 1'-0"
TELECOM_LEVEL 3_FLOOR PLAN_DEMO
1. EXISTING EQUIPMENT WITHIN THIS ROOM TO REMAIN . PROTECT
IN PLACE.
(312) 787-0056
FORCADE DESIGN
FRONT
19" RELAY
RACK
FRONT
19" RELAY
RACKFRONT
19" RELAY
RACKFRONT
19" RELAY
RACKFRONT
19" RELAY
RACKFRONT
3a
3a
20a
20a
F F
E E
D D
C C
B B
A A
A A
B B
C C
D D
E E
F F
3a
3a
20a
20a
A A
B B
C C
D D
E E
F F
3a
3a
20a
20a
3a
3a
20a
20a
F F
E E
D D
C C
B B
A A
A A
B B
C C
D D
E E
F F
3a
3a
20a
20a
A. REFER TO AND COORDINATE WITH ARCHITECTURAL FLOOR PLANS,
ELEVATIONS AND DETAILS FOR ADDITIONAL DETAILS PERTAINING
TO THIS SHEET.
B. REFER TO SHEET T-00-01 FOR SYMBOLS APPEARING ON THIS
SHEET.
C. WHERE EXISTING WALLS ARE DEMOLISHED, REMOVE ALL EXISTING
COMMUNICATIONS/LOW VOLTAGE DEVICES AND THEIR
ASSOCIATED CONDUITS AND WIRING BACK TO ORIGINATION.
EXISTING CABLING PASSING THROUGH DEMO AREA, NOT BEING
DEMOLISHED, SHALL BE SUPPORTED UTILIZING J-HOOK CABLE
SUPPORTS PER TIA STANDARDS.
D. EXISTING EQUIPMENT RACKS AND WALL BOARD CURRENTLY
LOCATED WITHIN THE EXISTING TELECOM ROOMS SHALL REMAIN
AS IS AND REUSED.
E. THERE IS NO SCOPE FOR WAPs. THE EXISTING WAPs AND CABLING
MUST BE FUNCTIONAL UPON SUBSTANTIAL COMPLETION. THE
CONTRACTOR CAN DETERMINE WHETHER TO REMOVE OR
PROTECT IN PLACE. ALL WORK SHALL BE COORDINATED WITH THE
GENERAL CONTRACTOR AND FINAL TESTING OF THE SYSTEM
SHALL BE COORDINATED WITH THE GOVERNMENT.
0 16' 32' 1/16"=1'-0"
SENSITIVE BUT UNCLASSIFIED (SBU) PROPERTY OF THE UNITED STATES GOVERNMENT COPYING, DISSEMINATION, OR DISTRIBUTION OF THIS DOCUMENT TO UNAUTHORIZED RECIPIENTS IS PROHIBITED.
Do not remove this notice. Properly destroy or return documents when no longer needed.
TRUE NORTH
PLAN NORTH
CHECKED BY
DRAWN BY
FLOOR NUMBER
DRAWING TITLE
SHEET
NUMBER
SUBMISSION DATE
SUBMISSION STAGE
GSA PM
GSA PROJECT NO.
PROJECT
DESCRIPTION
PROJECT TITLE
BULDING NAME
ADDRESS
BUILDING NUMBER
PRIME CONTR. NO.
PRIME ORDER NO.
CONST. CONTR.
A/E
SUB A/E
CONST. CONTR. NO.
SHEET SIZE:
DATE DRAWN:
36 X 48
S H
E E
T
ID
E N
TI
FI
C A
TI
O
N
DISCIPLINE
P R
O
JE
C T
ID
E
N
TI
FI
C
A
TI
O N
B U
IL
D
IN
G
BIM FILE NAME
C O
N
TR
A C
TO
R
S R
E V
IS
IO
N B
LO
C
K G
R A
P H
IC
S
C A
LE
K
E Y
P
LA
N S
TA
M
P O
R S
E A
L D
E S
IG
N
E R
ID
E
N
TI
FI
C
A
TI
O N
O W
N E
R
ID
E N
TI
FI
C A
TI
O
N
SHEET OF SHEETS
KRUECK & SEXTON ARCHITECTS, P.C.
400 MARYLAND AVENUE, SW
WASHINGTON, DC 20024
LYNDON B. JOHNSON FEDERAL BUILDING
DC0010ZZ
DC0010_A_3-4-6-7_r2020.rvt
WSP ENGINEERING
DEPARTMENT OF EDUCATION
CONSOLIDATION PROJECT
ISSUE FOR BID
HALLIE FUTTERMAN
RENOVATION OF FLOORS 3, 4, 6, & 7 OF THE EXISTING
BUILDING TO MEET THE DEPARTMENT OF
EDUCATION’S PROGRAMMATIC REQUIREMENTS.
GS-07-P-16-UC-D-7000
47PM0520F0002
47PM0520F0002
KRUECK & SEXTON ARCHITECTS
221 W ERIE ST
CHICAGO, IL 60654 (312) 707-0056
ARCHITECT
WSP ENGINEERING
ONE PENNSYLVANIA PLAZA, SECOND FLOOR
NEW YORK, NY 10119 (212) 465-5000
MEP ENGINEER
ATELIER TEN
45 E 20TH ST, 4TH FLOOR
NEW YORK, NY 10003 (312) 386-1400
SUSTAINABILITY CONSULTANT
THRESHOLD ACOUSTICS
141 W JACKSON BLVD, SUITE 2080
CHICAGO, IL 60604 (312) 386-1400
ACOUSTIC CONSULTANT
WEST EAST
M A
TC
H
LI
N
E
GENERAL NOTESLEGEND KEY NOTES
GENERAL SERVICES ADMINISTRATION
NATIONAL CAPITAL REGION
PUBLIC BUILDING SERVICE, D.C. SERVICES DIV.
7TH & D STREET, S.W.
WASHINGTON, D.C. 20407
ISSUE
NO. DATE ISSUE
COMMUNICATIONS
VARIES, SEE DRAWINGS
01 04/23/2021 ISSUED FOR BID
/2
/2
:4
:1
P
M
TD-14-01
TELECOMMUNICATIONS DEMOLITION - LEVEL 4
04/23/21
04/20/21FT
JMM
1/16" = 1'-0"
TELECOM_LEVEL 4_FLOOR PLAN_DEMO
1. EXISTING EQUIPMENT WITHIN THIS ROOM TO REMAIN . PROTECT
IN PLACE.
(312) 787-0056
FORCADE DESIGN
FRONT
19" RELAY
RACK
FRONT
19" RELAY
RACKFRONT
19" RELAY
RACKFRONT
19" RELAY
RACKFRONT
19" RELAY
RACKFRONT
3a
3a
20a
20a
F F
E E
D D
C C
B B
A A
A A
B B
C C
D D
E E
F F
3a
3a
20a
20a
A A
B B
C C
D D
E E
F F
3a
3a
20a
20a
3a
3a
20a
20a
F F
E E
D D
C C
B B
A A
A A
B B
C C
D D
E E
F F
3a
3a
20a
20a
A. REFER TO AND COORDINATE WITH ARCHITECTURAL FLOOR PLANS,
ELEVATIONS AND DETAILS FOR ADDITIONAL DETAILS PERTAINING
TO THIS SHEET.
B. REFER TO SHEET T-00-01 FOR SYMBOLS APPEARING ON THIS
SHEET.
C. WHERE EXISTING WALLS ARE DEMOLISHED, REMOVE ALL EXISTING
COMMUNICATIONS/LOW VOLTAGE DEVICES AND THEIR
ASSOCIATED CONDUITS AND WIRING BACK TO ORIGINATION.
EXISTING CABLING PASSING THROUGH DEMO AREA, NOT BEING
DEMOLISHED, SHALL BE SUPPORTED UTILIZING J-HOOK CABLE
SUPPORTS PER TIA STANDARDS.
D. EXISTING EQUIPMENT RACKS AND WALL BOARD CURRENTLY
LOCATED WITHIN THE EXISTING TELECOM ROOMS SHALL REMAIN
AS IS AND REUSED.
E. THERE IS NO SCOPE FOR WAPs. THE EXISTING WAPs AND CABLING
MUST BE FUNCTIONAL UPON SUBSTANTIAL COMPLETION. THE
CONTRACTOR CAN DETERMINE WHETHER TO REMOVE OR
PROTECT IN PLACE. ALL WORK SHALL BE COORDINATED WITH THE
GENERAL CONTRACTOR AND FINAL TESTING OF THE SYSTEM
SHALL BE COORDINATED WITH THE GOVERNMENT.
0 16' 32' 1/16"=1'-0"
SENSITIVE BUT UNCLASSIFIED (SBU) PROPERTY OF THE UNITED STATES GOVERNMENT COPYING, DISSEMINATION, OR DISTRIBUTION OF THIS DOCUMENT TO UNAUTHORIZED RECIPIENTS IS PROHIBITED.
Do not remove this notice. Properly destroy or return documents when no longer needed.
TRUE NORTH
PLAN NORTH
CHECKED BY
DRAWN BY
FLOOR NUMBER
DRAWING TITLE
SHEET
NUMBER
SUBMISSION DATE
SUBMISSION STAGE
GSA PM
GSA PROJECT NO.
PROJECT
DESCRIPTION
PROJECT TITLE
BULDING NAME
ADDRESS
BUILDING NUMBER
PRIME CONTR. NO.
PRIME ORDER NO.
CONST. CONTR.
A/E
SUB A/E
CONST. CONTR. NO.
SHEET SIZE:
DATE DRAWN:
36 X 48
S H
E E
T
ID
E N
TI
FI
C A
TI
O
N
DISCIPLINE
P R
O
JE
C T
ID
E
N
TI
FI
C
A
TI
O N
B U
IL
D
IN
G
BIM FILE NAME
C O
N
TR
A C
TO
R
S R
E V
IS
IO
N B
LO
C
K G
R A
P H
IC
S
C A
LE
K
E Y
P
LA
N S
TA
M
P O
R S
E A
L D
E S
IG
N
E R
ID
E
N
TI
FI
C
A
TI
O N
O W
N E
R
ID
E N
TI
FI
C A
TI
O
N
SHEET OF SHEETS
KRUECK & SEXTON ARCHITECTS, P.C.
400 MARYLAND AVENUE, SW
WASHINGTON, DC 20024
LYNDON B. JOHNSON FEDERAL BUILDING
DC0010ZZ
DC0010_A_3-4-6-7_r2020.rvt
WSP ENGINEERING
DEPARTMENT OF EDUCATION
CONSOLIDATION PROJECT
ISSUE FOR BID
HALLIE FUTTERMAN
RENOVATION OF FLOORS 3, 4, 6, & 7 OF THE EXISTING
BUILDING TO MEET THE DEPARTMENT OF
EDUCATION’S PROGRAMMATIC REQUIREMENTS.
GS-07-P-16-UC-D-7000
47PM0520F0002
47PM0520F0002
KRUECK & SEXTON ARCHITECTS
221 W ERIE ST
CHICAGO, IL 60654 (312) 707-0056
ARCHITECT
WSP ENGINEERING
ONE PENNSYLVANIA PLAZA, SECOND FLOOR
NEW YORK, NY 10119 (212) 465-5000
MEP ENGINEER
ATELIER TEN
45 E 20TH ST, 4TH FLOOR
NEW YORK, NY 10003 (312) 386-1400
SUSTAINABILITY CONSULTANT
THRESHOLD ACOUSTICS
141 W JACKSON BLVD, SUITE 2080
CHICAGO, IL 60604 (312) 386-1400
ACOUSTIC CONSULTANT
WEST EAST
M A
TC
H
LI
N
E
GENERAL NOTESLEGEND KEY NOTES
GENERAL SERVICES ADMINISTRATION
NATIONAL CAPITAL REGION
PUBLIC BUILDING SERVICE, D.C. SERVICES DIV.
7TH & D STREET, S.W.
WASHINGTON, D.C. 20407
ISSUE
NO. DATE ISSUE
COMMUNICATIONS
VARIES, SEE DRAWINGS
01 04/23/2021 ISSUED FOR BID
/2
/2
:4
:1
P
M
TD-16-01
TELECOMMUNICATIONS DEMOLITION - LEVEL 6
04/23/21
04/20/21FT
JMM
1/16" = 1'-0"
TELECOM_LEVEL 6_FLOOR PLAN_DEMO
1. EXISTING EQUIPMENT WITHIN THIS ROOM TO REMAIN . PROTECT
IN PLACE.
(312) 787-0056
FORCADE DESIGN
3a
3a
20a
20a
F F
E E
D D
C C
B B
A A
A A
B B
C C
D D
E E
F F
3a
3a
20a
20a
A A
B B
C C
D D
E E
F F
3a
3a
20a
20a
3a
3a
20a
20a
F F
E E
D D
C C
B B
A A
A A
B B
C C
D D
E E
F F
3a
3a
20a
20a
A. REFER TO AND COORDINATE WITH ARCHITECTURAL FLOOR PLANS,
ELEVATIONS AND DETAILS FOR ADDITIONAL DETAILS PERTAINING
TO THIS SHEET.
B. REFER TO SHEET T-00-01 FOR SYMBOLS APPEARING ON THIS
SHEET.
C. WHERE EXISTING WALLS ARE DEMOLISHED, REMOVE ALL EXISTING
COMMUNICATIONS/LOW VOLTAGE DEVICES AND THEIR
ASSOCIATED CONDUITS AND WIRING BACK TO ORIGINATION.
EXISTING CABLING PASSING THROUGH DEMO AREA, NOT BEING
DEMOLISHED, SHALL BE SUPPORTED UTILIZING J-HOOK CABLE
SUPPORTS PER TIA STANDARDS.
D. EXISTING EQUIPMENT RACKS AND WALL BOARD CURRENTLY
LOCATED WITHIN THE EXISTING TELECOM ROOMS SHALL REMAIN
AS IS AND REUSED.
E. THERE IS NO SCOPE FOR WAPs. THE EXISTING WAPs AND CABLING
MUST BE FUNCTIONAL UPON SUBSTANTIAL COMPLETION. THE
CONTRACTOR CAN DETERMINE WHETHER TO REMOVE OR
PROTECT IN PLACE. ALL WORK SHALL BE COORDINATED WITH THE
GENERAL CONTRACTOR AND FINAL TESTING OF THE SYSTEM
SHALL BE COORDINATED WITH THE GOVERNMENT.
0 16' 32' 1/16"=1'-0"
SENSITIVE BUT UNCLASSIFIED (SBU) PROPERTY OF THE UNITED STATES GOVERNMENT COPYING, DISSEMINATION, OR DISTRIBUTION OF THIS DOCUMENT TO UNAUTHORIZED RECIPIENTS IS PROHIBITED.
Do not remove this notice. Properly destroy or return documents when no longer needed.
TRUE NORTH
PLAN NORTH
CHECKED BY
DRAWN BY
FLOOR NUMBER
DRAWING TITLE
SHEET
NUMBER
SUBMISSION DATE
SUBMISSION STAGE
GSA PM
GSA PROJECT NO.
PROJECT
DESCRIPTION
PROJECT TITLE
BULDING NAME
ADDRESS
BUILDING NUMBER
PRIME CONTR. NO.
PRIME ORDER NO.
CONST. CONTR.
A/E
SUB A/E
CONST. CONTR. NO.
SHEET SIZE:
DATE DRAWN:
36 X 48
S H
E E
T
ID
E N
TI
FI
C A
TI
O
N
DISCIPLINE
P R
O
JE
C T
ID
E
N
TI
FI
C
A
TI
O N
B U
IL
D
IN
G
BIM FILE NAME
C O
N
TR
A C
TO
R
S R
E V
IS
IO
N B
LO
C
K G
R A
P H
IC
S
C A
LE
K
E Y
P
LA
N S
TA
M
P O
R S
E A
L D
E S
IG
N
E R
ID
E
N
TI
FI
C
A
TI
O N
O W
N E
R
ID
E N
TI
FI
C A
TI
O
N
SHEET OF SHEETS
KRUECK & SEXTON ARCHITECTS, P.C.
400 MARYLAND AVENUE, SW
WASHINGTON, DC 20024
LYNDON B. JOHNSON FEDERAL BUILDING
DC0010ZZ
DC0010_A_3-4-6-7_r2020.rvt
WSP ENGINEERING
DEPARTMENT OF EDUCATION
CONSOLIDATION PROJECT
ISSUE FOR BID
HALLIE FUTTERMAN
RENOVATION OF FLOORS 3, 4, 6, & 7 OF THE EXISTING
BUILDING TO MEET THE DEPARTMENT OF
EDUCATION’S PROGRAMMATIC REQUIREMENTS.
GS-07-P-16-UC-D-7000
47PM0520F0002
47PM0520F0002
KRUECK & SEXTON ARCHITECTS
221 W ERIE ST
CHICAGO, IL 60654 (312) 707-0056
ARCHITECT
WSP ENGINEERING
ONE PENNSYLVANIA PLAZA, SECOND FLOOR
NEW YORK, NY 10119 (212) 465-5000
MEP ENGINEER
ATELIER TEN
45 E 20TH ST, 4TH FLOOR
NEW YORK, NY 10003 (312) 386-1400
SUSTAINABILITY CONSULTANT
THRESHOLD ACOUSTICS
141 W JACKSON BLVD, SUITE 2080
CHICAGO, IL 60604 (312) 386-1400
ACOUSTIC CONSULTANT
WEST EAST
M A
TC
H
LI
N
E
GENERAL NOTESLEGEND KEY NOTES
GENERAL SERVICES ADMINISTRATION
NATIONAL CAPITAL REGION
PUBLIC BUILDING SERVICE, D.C. SERVICES DIV.
7TH & D STREET, S.W.
WASHINGTON, D.C. 20407
ISSUE
NO. DATE ISSUE
COMMUNICATIONS
VARIES, SEE DRAWINGS
01 04/23/2021 ISSUED FOR BID
/2
/2
:4
:1
P
M
TD-17-01
TELECOMMUNICATIONS DEMOLITION - LEVEL 7
04/23/21
04/20/21FT
JMM
1/16" = 1'-0"
TELECOM_LEVEL 7_FLOOR PLAN_DEMO
1. EXISTING EQUIPMENT WITHIN THIS ROOM TO REMAIN . PROTECT
IN PLACE.
(312) 787-0056
FORCADE DESIGN
FEC
F E
C
FEC
F E
C
FEC
F E
C
FEC
F E
C
F E
C
F E
C F
E C
F E
C
FEC
F E
C
FECFEC
F E
C
FEC
FEC
F E
C
FEC
F E
C
FEC
F E
C
FEC
F E
C
F E
C
F E
C F
E C
F E
C
FEC
F E
C
FECFEC
F E
C
3a
3a
20a
20a
F F
E E
D D
C C
B B
A A
A A
B B
C C
D D
E E
F F
3a
3a
20a
20a
ZZ_T-43-05
Sim
T-43-04
Sim
ZZ_T-43-06
Sim
T-43-03
Sim
A A
B B
C C
D D
E E
F F
3a
3a
20a
20a
3a
3a
20a
20a
F F
E E
D D
C C
B B
A A
A. REFER TO AND COORDINATE WITH ARCHITECTURAL FLOOR PLANS,
ELEVATIONS AND DETAILS FOR ADDITIONAL DETAILS PERTAINING
TO THIS SHEET.
B. REFER TO SHEET T-00-01 FOR SYMBOLS APPEARING ON THIS
SHEET.
C. ALL DEVICES WITHIN ROOMS CONTAINING HARD PAN CEILINGS
SHALL HAVE CONDUITS ROUTED TO ABOVE ACCESSIBLE CEILING
SPACE IN CORRIDOR.
D. COMMUNICATIONS CONDUIT PATHWAYS SHALL NOT CONTAIN ANY
LENGTH GREATER THAN 100 FEET BETWEEN PULL POINTS. NO
SECTION OF CONDUIT SHALL CONTAIN MORE THAN TWO 90-
DEGREE BENDS, OR EQUIVALENT, BETWEEN PULL POINTS. IF
THERE IS REVERSE BEND IN THE SECTION, A PULL POINT SHALL BE
INSTALLED. PULL BOXES SHALL NOT BE USED IN LIEU OF BENDS.
THE INSIDE RADIUS OF ALL CONDUIT BENDS SHALL BE AT LEAST 10
TIMES THE INTERNAL DIAMETER. BENDS IN CONDUIT SHALL NOT
CONTAIN ANY KINKS OR OTHER DISCONTINUITIES THAT MAY HAVE
A DETRIMENTAL EFFECT ON THE CABLE SHEATH DURING
INSTALLATION. NO DAISY CHAINING OF BACK BOXES ALLOWED
UNLESS OTHERWISE NOTED.
E. ALL CABLING SHALL BE SUPPORTED ABOVE ACCESSIBLE CEILING
SPACE USING LOW-VOLTAGE SUPPORTS SIZED AT 40% FILL BASED
ON CURRENT NEEDS.
F. CABLE TRAY SHOWN SHALL BE MOUNTED AT MINIMUM OF 6" AFC
THROUGHOUT DURATION OF SCOPE.
0 8' 16' 1/8"=1'-0"
SENSITIVE BUT UNCLASSIFIED (SBU) PROPERTY OF THE UNITED STATES GOVERNMENT COPYING, DISSEMINATION, OR DISTRIBUTION OF THIS DOCUMENT TO UNAUTHORIZED RECIPIENTS IS PROHIBITED.
Do not remove this notice. Properly destroy or return documents when no longer needed.
TRUE NORTH
PLAN NORTH
CHECKED BY
DRAWN BY
FLOOR NUMBER
DRAWING TITLE
SHEET
NUMBER
SUBMISSION DATE
SUBMISSION STAGE
GSA PM
GSA PROJECT NO.
PROJECT
DESCRIPTION
PROJECT TITLE
BULDING NAME
ADDRESS
BUILDING NUMBER
PRIME CONTR. NO.
PRIME ORDER NO.
CONST. CONTR.
A/E
SUB A/E
CONST. CONTR. NO.
SHEET SIZE:
DATE DRAWN:
36 X 48
S H
E E
T
ID
E N
TI
FI
C A
TI
O
N
DISCIPLINE
P R
O
JE
C T
ID
E
N
TI
FI
C
A
TI
O N
B U
IL
D
IN
G
BIM FILE NAME
C O
N
TR
A C
TO
R
S R
E V
IS
IO
N B
LO
C
K G
R A
P H
IC
S
C A
LE
K
E Y
P
LA
N S
TA
M
P O
R S
E A
L D
E S
IG
N
E R
ID
E
N
TI
FI
C
A
TI
O N
O W
N E
R
ID
E N
TI
FI
C A
TI
O
N
SHEET OF SHEETS
KRUECK & SEXTON ARCHITECTS, P.C.
400 MARYLAND AVENUE, SW
WASHINGTON, DC 20024
LYNDON B. JOHNSON FEDERAL BUILDING
DC0010ZZ
DC0010_A_3-4-6-7_r2020.rvt
WSP ENGINEERING
DEPARTMENT OF EDUCATION
CONSOLIDATION PROJECT
ISSUE FOR BID
HALLIE FUTTERMAN
RENOVATION OF FLOORS 3, 4, 6, & 7 OF THE EXISTING
BUILDING TO MEET THE DEPARTMENT OF
EDUCATION’S PROGRAMMATIC REQUIREMENTS.
GS-07-P-16-UC-D-7000
47PM0520F0002
47PM0520F0002
KRUECK & SEXTON ARCHITECTS
221 W ERIE ST
CHICAGO, IL 60654 (312) 707-0056
ARCHITECT
WSP ENGINEERING
ONE PENNSYLVANIA PLAZA, SECOND FLOOR
NEW YORK, NY 10119 (212) 465-5000
MEP ENGINEER
ATELIER TEN
45 E 20TH ST, 4TH FLOOR
NEW YORK, NY 10003 (312) 386-1400
SUSTAINABILITY CONSULTANT
THRESHOLD ACOUSTICS
141 W JACKSON BLVD, SUITE 2080
CHICAGO, IL 60604 (312) 386-1400
ACOUSTIC CONSULTANT
WEST EAST
M A
TC
H
LI
N
E
GENERAL NOTESLEGEND KEY NOTES
GENERAL SERVICES ADMINISTRATION
NATIONAL CAPITAL REGION
PUBLIC BUILDING SERVICE, D.C. SERVICES DIV.
7TH & D STREET, S.W.
WASHINGTON, D.C. 20407
ISSUE
NO. DATE ISSUE
COMMUNICATIONS
VARIES, SEE DRAWINGS
01 04/23/2021 ISSUED FOR BID
/2
/2
:4
:1
P
M
T-13-00
TELECOMMUNICATIONS PLAN - LEVEL 3
04/23/21
04/20/21FT
JMM
1/16" = 1'-0"
TELECOM_LEVEL 3_FLOOR PLAN
REFER TO
SHEET
T-13-01
REFER TO
SHEET
T-13-02
REFER TO
SHEET
T-13-01
REFER TO
SHEET
T-13-02
(312) 787-0056
FORCADE DESIGN
3a
3a
F F
E E
D D
C C
B B
A A
A A
B B
C C
D D
E E
F F
3a
3a
TV3
T-43-01
T-43-04
TV3
1 11 1
1 1 1 1
222222
2 2
TV3
2 2 2
F1F1
F1 F1
TV3
2 2 2 2 2 2 2 2 2 2
TV3
F1F1
F1F1
T E
LE
C
O M
B
T L4
T E
LE
C
O M
B
T L3
T E
LE
C
O M
A
T L2
T E
LE
C
O M
B
T L4
12"X4"12"X4" 12"X4" 12"X4" 12"X4"
12"X4"12"X4"12"X4"12"X4"12"X4"
"X
4"
F1F1
F1F1
F1F1
F1F1
F1F1
F1F1
F1F1
F1F1
F1F1
F1F1
F1F1
F1F1
F1F1
F1F1
F1F1
F1F1
F1F1
F1F1
F1F1
F1F1
F1F1
F1F1
F1F1
F1F1
F1F1
F1F1
F1F1
F1F1
F1F1
F1F1
F1F1
F1F1
F1F1
F1F1
F1F1
F1F1
F1F1
F1F1
F1F1
F1F1
F1F1
F1F1
F1F1
F1F1
F1F1
F1F1
F1F1
F1F1
F1F1
F1F1
F1F1
F1F1
F1F1
F1F1
F1F1
F1F1
F1F1
F1F1
F1
F1
F1
F1F1
F1F1
F1F1
F1F1
F1F1
F1F1
F1F1
F1F1
F1F1
F1F1
F1F1
F1F1
F1
F1
F1 2 2 2 2 2
222 2
TV3
TV3
TV3
2 2 2
TV3
TV3
3a
3a
F F
E E
D D
C C
B B
A A
TV3
TV3
TV3
TV3
TV3
TV3TV3
TV3TV3
RESTROOM (W)
3AWMN
TELECOM
3BTL1
TELECOM
3BTL4
OFFICE
3B112
OFFICE
3B111
OFFICE
3B110
STORAGE
3BS03
ELECTRICAL
3AEL2
STAIR 1
3AST
STAIR 2
3BST1
WEST PANTRY
3APN
COPY
3A203
OFFICE
3B212
OFFICE
3B211
OFFICE
3B210
OFFICE
3A111
OFFICE
3A112
OFFICE
3A110
OFFICE
3A114
OFFICE
3A113
OFFICE
3A115
OFFICE
3A211
OFFICE
3A212
OFFICE
3A210
OFFICE
3A214
OFFICE
3A213
OFFICE
3A215
CONFERENCE
3A156
CONFERENCE
3A150
HUDDLE ROOM
3A251
HUDDLE ROOM
3A151
FOCUS
3A153
FOCUS
3A152
FOCUS
3A253
FOCUS
3A252
FOCUS
3A255
FOCUS
3A155
FOCUS
3A154
FOCUS
3A254
CONFERENCE
3B150
CONFERENCE
3B151
CONFERENCE
3B251
CONFERENCE
3B250
WEST ELEVATOR LOBBY
3BLV1
ELECTRICAL
3BEL1
ELECTRICAL
3BEL4
RESTROOM (M)
3AMEN
JANITOR
3AJA1
VESTIBULE
3A2VES
Room
ELECTRICAL
3AEL1
TELECOM
3ATL1
Room
Room
FUTURE CLOSET
3ATL2
CORRIDOR
3A201
CORRIDOR
3A101
CORRIDOR
3A180
MOTHER'S ROOM
3AMRM
CORRIDOR
3A103
CORRIDOR
3A202
OPEN OFFICE
3A245
CORRIDOR
3A102
OPEN OFFICE
3A145
VESTIBULE
3A1VES
Room
7C536
Room
7C537
Room
7C538
Room
7C539
Room
7C541
Room
7C542
Room
7C543
Room
7C544
Room
7C545
AV CLOSET
3A104
OFFICE
3A192
OFFICE
3A191
OFFICE
3A190
OFFICE
3A292
OFFICE
3A291
OFFICE
3A290
OFFICE
3A294
CONFERENCE
3A160
OFFICE
3A130
OFFICE
3A132
OFFICE
3A133
OFFICE
3A131
OFFICE
3A230
OFFICE
3A232
OFFICE
3A233
OFFICE
3A231
OFFICE
3A293
OFFICE
3A295
OFFICE
3A194
OFFICE
3A193
ASSISTANT SECRETARY'S
SUITE
3A181
CORRIDOR
3A200
CORRIDOR
3A100
OFFICE
3B113
OFFICE
3B213
CONFERENCE
3B152
CONFERENCE
3B153
CONFERENCE
3B252
CONFERENCE
3B253
OPEN OFFICE
3B245
OPEN OFFICE
3B145
CORRIDOR
3B200
1 1
1 1
2 2
4"
4"
A. REFER TO AND COORDINATE WITH ARCHITECTURAL FLOOR PLANS,
ELEVATIONS AND DETAILS FOR ADDITIONAL DETAILS PERTAINING
TO THIS SHEET.
B. REFER TO SHEET T-00-01 FOR SYMBOLS APPEARING ON THIS
SHEET.
C. ALL DEVICES WITHIN ROOMS CONTAINING HARD PAN CEILINGS
SHALL HAVE CONDUITS ROUTED TO ABOVE ACCESSIBLE CEILING
SPACE IN CORRIDOR.
D. COMMUNICATIONS CONDUIT PATHWAYS SHALL NOT CONTAIN ANY
LENGTH GREATER THAN 100 FEET BETWEEN PULL POINTS. NO
SECTION OF CONDUIT SHALL CONTAIN MORE THAN TWO 90-
DEGREE BENDS, OR EQUIVALENT, BETWEEN PULL POINTS. IF
THERE IS REVERSE BEND IN THE SECTION, A PULL POINT SHALL BE
INSTALLED. PULL BOXES SHALL NOT BE USED IN LIEU OF BENDS.
THE INSIDE RADIUS OF ALL CONDUIT BENDS SHALL BE AT LEAST 10
TIMES THE INTERNAL DIAMETER. BENDS IN CONDUIT SHALL NOT
CONTAIN ANY KINKS OR OTHER DISCONTINUITIES THAT MAY HAVE
A DETRIMENTAL EFFECT ON THE CABLE SHEATH DURING
INSTALLATION. NO DAISY CHAINING OF BACK BOXES ALLOWED
UNLESS OTHERWISE NOTED.
E. ALL CABLING SHALL BE SUPPORTED ABOVE ACCESSIBLE CEILING
SPACE USING LOW-VOLTAGE SUPPORTS SIZED AT 40% FILL BASED
ON CURRENT NEEDS.
F. BACK BOXES LOCATED IN FABRIC WALL AREAS SHALL BE
PROVIDED WITH BACK BOX EXTENSIONS TO PREVENT CRUSHING
OF WALL SURFACES.
0 8' 16' 1/8"=1'-0"
SENSITIVE BUT UNCLASSIFIED (SBU) PROPERTY OF THE UNITED STATES GOVERNMENT COPYING, DISSEMINATION, OR DISTRIBUTION OF THIS DOCUMENT TO UNAUTHORIZED RECIPIENTS IS PROHIBITED.
Do not remove this notice. Properly destroy or return documents when no longer needed.
TRUE NORTH
PLAN NORTH
CHECKED BY
DRAWN BY
FLOOR NUMBER
DRAWING TITLE
SHEET
NUMBER
SUBMISSION DATE
SUBMISSION STAGE
GSA PM
GSA PROJECT NO.
PROJECT
DESCRIPTION
PROJECT TITLE
BULDING NAME
ADDRESS
BUILDING NUMBER
PRIME CONTR. NO.
PRIME ORDER NO.
CONST. CONTR.
A/E
SUB A/E
CONST. CONTR. NO.
SHEET SIZE:
DATE DRAWN:
36 X 48
S H
E E
T
ID
E N
TI
FI
C A
TI
O
N
DISCIPLINE
P R
O
JE
C T
ID
E
N
TI
FI
C
A
TI
O N
B U
IL
D
IN
G
BIM FILE NAME
C O
N
TR
A C
TO
R
S R
E V
IS
IO
N B
LO
C
K G
R A
P H
IC
S
C A
LE
K
E Y
P
LA
N S
TA
M
P O
R S
E A
L D
E S
IG
N
E R
ID
E
N
TI
FI
C
A
TI
O N
O W
N E
R
ID
E N
TI
FI
C A
TI
O
N
SHEET OF SHEETS
KRUECK & SEXTON ARCHITECTS, P.C.
400 MARYLAND AVENUE, SW
WASHINGTON, DC 20024
LYNDON B. JOHNSON FEDERAL BUILDING
DC0010ZZ
DC0010_A_3-4-6-7_r2020.rvt
WSP ENGINEERING
DEPARTMENT OF EDUCATION
CONSOLIDATION PROJECT
ISSUE FOR BID
HALLIE FUTTERMAN
RENOVATION OF FLOORS 3, 4, 6, & 7 OF THE EXISTING
BUILDING TO MEET THE DEPARTMENT OF
EDUCATION’S PROGRAMMATIC REQUIREMENTS.
GS-07-P-16-UC-D-7000
47PM0520F0002
47PM0520F0002
KRUECK & SEXTON ARCHITECTS
221 W ERIE ST
CHICAGO, IL 60654 (312) 707-0056
ARCHITECT
WSP ENGINEERING
ONE PENNSYLVANIA PLAZA, SECOND FLOOR
NEW YORK, NY 10119 (212) 465-5000
MEP ENGINEER
ATELIER TEN
45 E 20TH ST, 4TH FLOOR
NEW YORK, NY 10003 (312) 386-1400
SUSTAINABILITY CONSULTANT
THRESHOLD ACOUSTICS
141 W JACKSON BLVD, SUITE 2080
CHICAGO, IL 60604 (312) 386-1400
ACOUSTIC CONSULTANT
WEST EAST
M A
TC
H
LI
N
E
GENERAL NOTESLEGEND KEY NOTES
GENERAL SERVICES ADMINISTRATION
NATIONAL CAPITAL REGION
PUBLIC BUILDING SERVICE, D.C. SERVICES DIV.
7TH & D STREET, S.W.
WASHINGTON, D.C. 20407
ISSUE
NO. DATE ISSUE
COMMUNICATIONS
VARIES, SEE DRAWINGS
01 04/23/2021 ISSUED FOR BID
/2
/2
:4
:4
P
M
T-13-01
TELECOMMUNICATIONS PLAN - LEVEL 3 - WEST
04/23/21
04/20/21FT
JMM
1/8" = 1'-0"
TELECOM_LEVEL 3_FLOOR PLAN__WEST
1 1
1. PROVIDE (3) 4" CONDUITS AS SHOWN.
2. REFER TO SHEET T-50-03 FOR TYPICAL CONDUIT PATHWAY
DETAILS TO FURNITURE.
2 2 2 2 2 2 2 2 2 2
2222222222
(312) 787-0056
FORCADE DESIGN
20a
20a
F F
E E
D D
C C
B B
A A
A A
B B
C C
D D
E E
F F
20a
20a
T-43-03
T-43-02
2 2
2 2
2 2
2 2
2 2 2 2 2 2 2 2 2 2
TV3
TV3
21 1
1 1111
1 1 1 1 1
2 2 2 2 2 2
2 2 2 2 2
F1F1
F1 F1
TV3
TV3
TV3
TV3
2 2 2
2 2
T E
LE
C
O M
B
T L4
T E
LE
C
O M
B
T L3
T E
LE
C
O M
B
T L3
T E
LE
C
O M
C
T L
12"X4" 12"X4" 12"X4" 12"X4" 12"X4"
12"X4"12"X4"12"X4"12"X4"12"X4"
"X
4"
F1F1
F1F1
F1F1
F1F1
F1F1
F1F1
F1F1
F1F1
F1F1
F1F1
F1F1
F1F1
F1F1
F1F1
F1F1
F1F1
2 2 2 2
2 2 2 2
TV3
TV3
TV3
TV3
TV3
2 2 2 2 2
20a
20a
F F
E E
D D
C C
B B
A A
TV3TV3 TV3TV3 TV3TV3
TV3TV3TV3TV3TV3TV3
TV3
TV3
TV3
2 2 22
1 1
1 1
2 2 22
2 2 22
2 2
2 2
2 2
2 2
2 2
2 2
RESTROOM (W)
3CWMN
ELECTRICAL
3BEL2
ELECTRICAL
3BEL3
OFFICE
3B114
OFFICE
3B113
OFFICE
3B115
OFFICE
3B116
Room
FREIGHT ELEV. LOBBY
3BFLV
STAIR 4
3CST
STAIR 3
3BST2
EAST PANTRY
3BPN
COPY
3B102
OFFICE
3B214
OFFICE
3B213
OFFICE
3B215
OFFICE
3B216
OFFICE
3C111
OFFICE
3C112
OFFICE
3C110
OFFICE
3C114
OFFICE
3C113
OFFICE
3C115
OFFICE
3C211
OFFICE
3C212
OFFICE
3C210
OFFICE
3C214
OFFICE
3C213
OFFICE
3C215
CORRIDOR
3C180
CONFERENCE
3C156
CONFERENCE
3C150
HUDDLE ROOM
3C251
HUDDLE ROOM
3C151
FOCUS
3C153
FOCUS
3C152
FOCUS
3C253
FOCUS
3C252
FOCUS
3C255
FOCUS
3C155
FOCUS
3C154
FOCUS
3C254
CONFERENCE
3C256
CONFERENCE
3B152
CONFERENCE
3B153 CONFERENCE
3B155
CONFERENCE
3B154
CONFERENCE
3B252
CONFERENCE
3B253
CONFERENCE
3B255
CONFERENCE
3B254
CORRIDOR
3B101
TELECOM
3BTL2
TELECOM
3BTL3
FOCUS ROOM
3C257
RESTROOM (M)
3CMEN
JANITOR
3CJA
ELECTRICAL
3CEL2
Room
TELECOM
3CTL2
TELECOM
3CTL1
ELECTRICAL
3CEL1
EAST ELEVATOR LOBBY
3BLV2
VESTIBULE
3C2VES
CORRIDOR
3C201
CORRIDOR
3C101
CORRIDOR
3C102
CORRIDOR
3B100
OPEN OFFICE
3B245
OPEN OFFICE
3C145
OPEN OFFICE
3C245
CORRIDOR
3C200
OPEN OFFICE
3B145
CORRIDOR
3B200
VESTIBULE
3C1VES
Room
7C535 Room
7C546
Room
7C547
Room
7C548
Room
7C549
Room
7C550
Room
7C551
Room
7C552
Room
7C553 Room
7C554
Room
7C555
CORRIDOR
3C100
OFFICE
3C193
OFFICE
3C192
OFFICE
3C191
OFFICE
3C190
OFFICE
3C194
OFFICE
3C293
OFFICE
3C292
OFFICE
3C291
OFFICE
3C290
OFFICE
3C294
OFFICE
3C295
ASSISTANT SECRETARY'S
SUITE
3C181
CONFERENCE
3C160
OFFICE
3C284
OFFICE
3C240
OFFICE
3C285
OFFICE
3C243
OFFICE
3B230
OFFICE
3B232
OFFICE
3B231
OFFICE
3B233
OFFICE
3C288
OFFICE
3C286
OFFICE
3C287
OFFICE
3C289
OFFICE
3C238
OFFICE
3C239
OFFICE
3C241
OFFICE
3C242
OFFICE
3B237
OFFICE
3B236
OFFICE
3B241
OFFICE
3B240
OFFICE
3B234
OFFICE
3B235
OFFICE
3B238
OFFICE
3B239
OFFICE
3C184
OFFICE
3C140
OFFICE
3C185
OFFICE
3C143
OFFICE
3C138
OFFICE
3C139
OFFICE
3C141
OFFICE
3C142
OFFICE
3C188
OFFICE
3C186
OFFICE
3C187
OFFICE
3C189
OFFICE
3B130
OFFICE
3B132
OFFICE
3B131
OFFICE
3B133
OFFICE
3B137
OFFICE
3B136
OFFICE
3B141
OFFICE
3B140
OFFICE
3B134
OFFICE
3B135
OFFICE
3B138
OFFICE
3B139
OFFICE
3C195
OFFICE
3C196
COLLABORATION
3C271
COLLABORATION
3B270
COLLABORATION
3B271
COLLABORATION
3B170
COLLABORATION
3B171
COLLABORATION
3C171
OFFICE
3C136
OFFICE
3C134
OFFICE
3C137
OFFICE
3C135
OFFICE
3C131
OFFICE
3C130
OFFICE
3C133
OFFICE
3C132
COLLABORATION
3C170
OFFICE
3C236
OFFICE
3C234
OFFICE
3C237
OFFICE
3C235
OFFICE
3C231
OFFICE
3C230
OFFICE
3C233
OFFICE
3C232
COLLABORATION
3C270
FOCUS
3C161
FOCUS
3C261
1 11 1
A. REFER TO AND COORDINATE WITH ARCHITECTURAL FLOOR PLANS,
ELEVATIONS AND DETAILS FOR ADDITIONAL DETAILS PERTAINING
TO THIS SHEET.
B. REFER TO SHEET T-00-01 FOR SYMBOLS APPEARING ON THIS
SHEET.
C. ALL DEVICES WITHIN ROOMS CONTAINING HARD PAN CEILINGS
SHALL HAVE CONDUITS ROUTED TO ABOVE ACCESSIBLE CEILING
SPACE IN CORRIDOR.
D. COMMUNICATIONS CONDUIT PATHWAYS SHALL NOT CONTAIN ANY
LENGTH GREATER THAN 100 FEET BETWEEN PULL POINTS. NO
SECTION OF CONDUIT SHALL CONTAIN MORE THAN TWO 90-
DEGREE BENDS, OR EQUIVALENT, BETWEEN PULL POINTS. IF
THERE IS REVERSE BEND IN THE SECTION, A PULL POINT SHALL BE
INSTALLED. PULL BOXES SHALL NOT BE USED IN LIEU OF BENDS.
THE INSIDE RADIUS OF ALL CONDUIT BENDS SHALL BE AT LEAST 10
TIMES THE INTERNAL DIAMETER. BENDS IN CONDUIT SHALL NOT
CONTAIN ANY KINKS OR OTHER DISCONTINUITIES THAT MAY HAVE
A DETRIMENTAL EFFECT ON THE CABLE SHEATH DURING
INSTALLATION. NO DAISY CHAINING OF BACK BOXES ALLOWED
UNLESS OTHERWISE NOTED.
E. ALL CABLING SHALL BE SUPPORTED ABOVE ACCESSIBLE CEILING
SPACE USING LOW-VOLTAGE SUPPORTS SIZED AT 40% FILL BASED
ON CURRENT NEEDS.
F. BACK BOXES LOCATED IN FABRIC WALL AREAS SHALL BE
PROVIDED WITH BACK BOX EXTENSIONS TO PREVENT CRUSHING
OF WALL SURFACES.
0 8' 16' 1/8"=1'-0"
SENSITIVE BUT UNCLASSIFIED (SBU) PROPERTY OF THE UNITED STATES GOVERNMENT COPYING, DISSEMINATION, OR DISTRIBUTION OF THIS DOCUMENT TO UNAUTHORIZED RECIPIENTS IS PROHIBITED.
Do not remove this notice. Properly destroy or return documents when no longer needed.
TRUE NORTH
PLAN NORTH
CHECKED BY
DRAWN BY
FLOOR NUMBER
DRAWING TITLE
SHEET
NUMBER
SUBMISSION DATE
SUBMISSION STAGE
GSA PM
GSA PROJECT NO.
PROJECT
DESCRIPTION
PROJECT TITLE
BULDING NAME
ADDRESS
BUILDING NUMBER
PRIME CONTR. NO.
PRIME ORDER NO.
CONST. CONTR.
A/E
SUB A/E
CONST. CONTR. NO.
SHEET SIZE:
DATE DRAWN:
36 X 48
S H
E E
T
ID
E N
TI
FI
C A
TI
O
N
DISCIPLINE
P R
O
JE
C T
ID
E
N
TI
FI
C
A
TI
O N
B U
IL
D
IN
G
BIM FILE NAME
C O
N
TR
A C
TO
R
S R
E V
IS
IO
N B
LO
C
K G
R A
P H
IC
S
C A
LE
K
E Y
P
LA
N S
TA
M
P O
R S
E A
L D
E S
IG
N
E R
ID
E
N
TI
FI
C
A
TI
O N
O W
N E
R
ID
E N
TI
FI
C A
TI
O
N
SHEET OF SHEETS
KRUECK & SEXTON ARCHITECTS, P.C.
400 MARYLAND AVENUE, SW
WASHINGTON, DC 20024
LYNDON B. JOHNSON FEDERAL BUILDING
DC0010ZZ
DC0010_A_3-4-6-7_r2020.rvt
WSP ENGINEERING
DEPARTMENT OF EDUCATION
CONSOLIDATION PROJECT
ISSUE FOR BID
HALLIE FUTTERMAN
RENOVATION OF FLOORS 3, 4, 6, & 7 OF THE EXISTING
BUILDING TO MEET THE DEPARTMENT OF
EDUCATION’S PROGRAMMATIC REQUIREMENTS.
GS-07-P-16-UC-D-7000
47PM0520F0002
47PM0520F0002
KRUECK & SEXTON ARCHITECTS
221 W ERIE ST
CHICAGO, IL 60654 (312) 707-0056
ARCHITECT
WSP ENGINEERING
ONE PENNSYLVANIA PLAZA, SECOND FLOOR
NEW YORK, NY 10119 (212) 465-5000
MEP ENGINEER
ATELIER TEN
45 E 20TH ST, 4TH FLOOR
NEW YORK, NY 10003 (312) 386-1400
SUSTAINABILITY CONSULTANT
THRESHOLD ACOUSTICS
141 W JACKSON BLVD, SUITE 2080
CHICAGO, IL 60604 (312) 386-1400
ACOUSTIC CONSULTANT
WEST EAST
M A
TC
H
LI
N
E
GENERAL NOTESLEGEND KEY NOTES
GENERAL SERVICES ADMINISTRATION
NATIONAL CAPITAL REGION
PUBLIC BUILDING SERVICE, D.C. SERVICES DIV.
7TH & D STREET, S.W.
WASHINGTON, D.C. 20407
ISSUE
NO. DATE ISSUE
COMMUNICATIONS
VARIES, SEE DRAWINGS
01 04/23/2021 ISSUED FOR BID
/2
/2
:4
:0
P
M
T-13-02
TELECOMMUNICATIONS PLAN - LEVEL 3 - EAST
04/23/21
04/20/21FT
JMM
1/8" = 1'-0"
TELECOM_LEVEL 3_FLOOR PLAN__EAST
2 2
1. PROVIDE (3) 4" CONDUITS AS SHOWN.
2. REFER TO SHEET T-50-03 FOR TYPICAL CONDUIT PATHWAY
DETAILS TO FURNITURE.
(312) 787-0056
FORCADE DESIGN
F E
C
FEC
F E
C
FEC
F E
C
FEC
F E
C
F E
C
F E
C F
E C
F E
C
FEC
F E
C
FECFEC
F E
C
J
J
J J J J J J J J
J J J J J J JJ
FEC
FEC
F E
C
FEC
F E
C
FEC
F E
C
FEC
F E
C
F E
C
F E
C F
E C
F E
C
FEC
F E
C
FECFEC
F E
C
3a
3a
20a
20a
F F
E E
D D
C C
B B
A A
A A
B B
C C
D D
E E
F F
3a
3a
20a
20a
TV3
TV3TV3
TV3
TV3
TV3
TV3 TV3
TV3
TV3
ZZ_T-43-05
Sim
T-43-04
Sim
ZZ_T-43-06
Sim
T-43-03
Sim
A A
B B
C C
D D
E E
F F
3a
3a
20a
20a
3a
3a
20a
20a
F F
E E
D D
C C
B B
A A
A. REFER TO AND COORDINATE WITH ARCHITECTURAL FLOOR PLANS,
ELEVATIONS AND DETAILS FOR ADDITIONAL DETAILS PERTAINING
TO THIS SHEET.
B. REFER TO SHEET T-00-01 FOR SYMBOLS APPEARING ON THIS
SHEET.
C. ALL DEVICES WITHIN ROOMS CONTAINING HARD PAN CEILINGS
SHALL HAVE CONDUITS ROUTED TO ABOVE ACCESSIBLE CEILING
SPACE IN CORRIDOR.
D. COMMUNICATIONS CONDUIT PATHWAYS SHALL NOT CONTAIN ANY
LENGTH GREATER THAN 100 FEET BETWEEN PULL POINTS. NO
SECTION OF CONDUIT SHALL CONTAIN MORE THAN TWO 90-
DEGREE BENDS, OR EQUIVALENT, BETWEEN PULL POINTS. IF
THERE IS REVERSE BEND IN THE SECTION, A PULL POINT SHALL BE
INSTALLED. PULL BOXES SHALL NOT BE USED IN LIEU OF BENDS.
THE INSIDE RADIUS OF ALL CONDUIT BENDS SHALL BE AT LEAST 10
TIMES THE INTERNAL DIAMETER. BENDS IN CONDUIT SHALL NOT
CONTAIN ANY KINKS OR OTHER DISCONTINUITIES THAT MAY HAVE
A DETRIMENTAL EFFECT ON THE CABLE SHEATH DURING
INSTALLATION. NO DAISY CHAINING OF BACK BOXES ALLOWED
UNLESS OTHERWISE NOTED.
E. ALL CABLING SHALL BE SUPPORTED ABOVE ACCESSIBLE CEILING
SPACE USING LOW-VOLTAGE SUPPORTS SIZED AT 40% FILL BASED
ON CURRENT NEEDS.
F. CABLE TRAY SHOWN SHALL BE MOUNTED AT MINIMUM OF 6" AFC
THROUGHOUT DURATION OF SCOPE.
0 16' 32' 1/16"=1'-0"
SENSITIVE BUT UNCLASSIFIED (SBU) PROPERTY OF THE UNITED STATES GOVERNMENT COPYING, DISSEMINATION, OR DISTRIBUTION OF THIS DOCUMENT TO UNAUTHORIZED RECIPIENTS IS PROHIBITED.
Do not remove this notice. Properly destroy or return documents when no longer needed.
TRUE NORTH
PLAN NORTH
CHECKED BY
DRAWN BY
FLOOR NUMBER
DRAWING TITLE
SHEET
NUMBER
SUBMISSION DATE
SUBMISSION STAGE
GSA PM
GSA PROJECT NO.
PROJECT
DESCRIPTION
PROJECT TITLE
BULDING NAME
ADDRESS
BUILDING NUMBER
PRIME CONTR. NO.
PRIME ORDER NO.
CONST. CONTR.
A/E
SUB A/E
CONST. CONTR. NO.
SHEET SIZE:
DATE DRAWN:
36 X 48
S H
E E
T
ID
E N
TI
FI
C A
TI
O
N
DISCIPLINE
P R
O
JE
C T
ID
E
N
TI
FI
C
A
TI
O N
B U
IL
D
IN
G
BIM FILE NAME
C O
N
TR
A C
TO
R
S R
E V
IS
IO
N B
LO
C
K G
R A
P H
IC
S
C A
LE
K
E Y
P
LA
N S
TA
M
P O
R S
E A
L D
E S
IG
N
E R
ID
E
N
TI
FI
C
A
TI
O N
O W
N E
R
ID
E N
TI
FI
C A
TI
O
N
SHEET OF SHEETS
KRUECK & SEXTON ARCHITECTS, P.C.
400 MARYLAND AVENUE, SW
WASHINGTON, DC 20024
LYNDON B. JOHNSON FEDERAL BUILDING
DC0010ZZ
DC0010_A_3-4-6-7_r2020.rvt
WSP ENGINEERING
DEPARTMENT OF EDUCATION
CONSOLIDATION PROJECT
ISSUE FOR BID
HALLIE FUTTERMAN
RENOVATION OF FLOORS 3, 4, 6, & 7 OF THE EXISTING
BUILDING TO MEET THE DEPARTMENT OF
EDUCATION’S PROGRAMMATIC REQUIREMENTS.
GS-07-P-16-UC-D-7000
47PM0520F0002
47PM0520F0002
KRUECK & SEXTON ARCHITECTS
221 W ERIE ST
CHICAGO, IL 60654 (312) 707-0056
ARCHITECT
WSP ENGINEERING
ONE PENNSYLVANIA PLAZA, SECOND FLOOR
NEW YORK, NY 10119 (212) 465-5000
MEP ENGINEER
ATELIER TEN
45 E 20TH ST, 4TH FLOOR
NEW YORK, NY 10003 (312) 386-1400
SUSTAINABILITY CONSULTANT
THRESHOLD ACOUSTICS
141 W JACKSON BLVD, SUITE 2080
CHICAGO, IL 60604 (312) 386-1400
ACOUSTIC CONSULTANT
WEST EAST
M A
TC
H
LI
N
E
GENERAL NOTESLEGEND KEY NOTES
GENERAL SERVICES ADMINISTRATION
NATIONAL CAPITAL REGION
PUBLIC BUILDING SERVICE, D.C. SERVICES DIV.
7TH & D STREET, S.W.
WASHINGTON, D.C. 20407
ISSUE
NO. DATE ISSUE
COMMUNICATIONS
VARIES, SEE DRAWINGS
01 04/23/2021 ISSUED FOR BID
/2
/2
:4
:0
P
M
T-14-00
TELECOMMUNICATIONS PLAN - LEVEL 4
04/23/21
04/20/21FT
JMM
1/16" = 1'-0"
TELECOM_LEVEL 4_FLOOR PLAN
REFER TO
SHEET
T-14-01
REFER TO
SHEET
T-14-02
REFER TO
SHEET
T-14-01
REFER TO
SHEET
T-14-02
(312) 787-0056
FORCADE DESIGN
3a
3a
F F
E E
D D
C C
B B
A A
A A
B B
C C
D D
E E
F F
3a
3a
F1 F1
2 2
2 2
2 2
2 2
2 2 2
2 2 2 2 2 2
2 2 2 2 2 2
2 2 2
2 2 2 2
F1
F1
F1
F1
TV3
TV3
TV3
TV3
TV3
1 111
T E
LE
C
O M
B
T L4
T E
LE
C
O M
B
T L3
12"X4"12"X4" 12"X4" 12"X4" 12"X4"
12"X4"12"X4"12"X4"12"X4"12"X4"
"X
4" 2
1 1
2 2
2 2
F1 F1
F1 F1
F1 F1
F1 F1
F1 F1
F1 F1
F1 F1
F1 F1
F1 F1
F1 F1
F1 F1
F1 F1
F1 F1
F1 F1
F1 F1
F1 F1
F1 F1
F1 F1
F1 F1
F1 F1
F1 F1
F1 F1
F1 F1
F1
F1
F1
F1 F1
F1 F1
F1 F1
F1 F1
F1 F1
F1 F1
F1 F1
F1 F1
F1 F1
F1 F1
F1 F1
F1 F1
T-44-04
F1 F1
F1 F1
F1 F1
F1 F1
F1 F1
F1 F1
F1 F1
F1 F1
F1 F1
F1 F1
F1 F1
F1 F1
F1 F1
F1 F1
F1 F1
F1 F1
F1
F1
F1
F1 F1
F1 F1
F1 F1
F1 F1
F1 F1
F1 F1
F1 F1
F1 F1
F1 F1
F1 F1
F1 F1
F1 F1
2 2 2 2 2 2
2 2 2 2 2 2
T-44-01
TV3
TV3
TV3
T E
LE
C
O M
A
T L2
T E
LE
C
O M
B
T L4
TV3
TV3
3a
3a
F F
E E
D D
C C
B B
A A
2 2 2
RESTROOM (W)
4AWMN
TELECOM
4BTL1
TELECOM
4BTL4
OFFICE
4B112
OFFICE
4B111
OFFICE
4B110Room
STORAGE
4BS03
ELECTRICAL
4AEL2
STAIR 1
4AST
STAIR 2
4BST1
WEST PANTRY
4APN
COPY
4A203
OFFICE
4B212
OFFICE
4B211
OFFICE
4B210
OFFICE
4A111
OFFICE
4A112
OFFICE
4A110
OFFICE
4A114
OFFICE
4A113
OFFICE
4A115
OFFICE
4A211
OFFICE
4A212
OFFICE
4A210
OFFICE
4A214
OFFICE
4A213
OFFICE
4A215
CONFERENCE
4A156
CONFERENCE
4A150
HUDDLE ROOM
4A251
HUDDLE ROOM
4A151
FOCUS
4A153
FOCUS
4A152
FOCUS
4A253
FOCUS
4A252
FOCUS
4A255
FOCUS
4A155
FOCUS
4A154
FOCUS
4A254
CONFERENCE
4B150
CONFERENCE
4B151
CONFERENCE
4B251
CONFERENCE
4B250
ELECTRICAL
4BEL1
ELECTRICAL
4BEL4
Room
4BS01
Room
Room
4BS02
RESTROOM (M)
4AMEN
JANITOR
4AJA1
MOTHER'S ROOM
4AMRM
Room
ELECTRICAL
4AEL1
TELECOM
4ATL1
Room
Room
Room
FUTURE CLOSET
4ATL2
OFFICE
4A133
OFFICE
4A132
OFFICE
4A131
OFFICE
4A130
OFFICE
4A233
OFFICE
4A232
OFFICE
4A231
OFFICE
4A230
OFFICE
4A192
OFFICE
4A191
OFFICE
4A190
OFFICE
4A292
OFFICE
4A291
OFFICE
4A290
OFFICE
4A293
OFFICE
4A294
WEST ELEVATOR LOBBY
4BLV1
CORRIDOR
4B200
COLLABORATION
4A170
COLLABORATION
4A270
OFFICE
4A237
OFFICE
4A236
OFFICE
4A235
OFFICE
4A234
COLLABORATION
4A271
OFFICE
4A136
OFFICE
4A135
OFFICE
4A134
COLLABORATION
4A171
ASSISTANT SECRETARY'S
SUITE
4A181
CONFERENCE
4A160
CORRIDOR
4A101
OPEN OFFICE
4A245
OPEN OFFICE
4A246
OPEN OFFICE
4A145
OPEN OFFICE
4A146
CORRIDOR
4A102
CORRIDOR
4A103
CORRIDOR
4A202
VESTIBULE
4A2VES
CORRIDOR
4A200
OFFICE
4A295
OFFICE
4A194
OFFICE
4A193
CORRIDOR
4A180
CORRIDOR
4A201
AV CLOSET
4A104
VESTIBULE
4A1VES
CORRIDOR
4A100
OFFICE
4B113
OFFICE
4B213
CONFERENCE
4B152
CONFERENCE
4B153
CONFERENCE
4B252
CONFERENCE
4B253
OPEN OFFICE
4B245
OPEN OFFICE
4B145
CORRIDOR
4B100
ASSISTANT SECRETARY'S
SUITE
4A181
TV3
TV3
TV3
TV3
TV3
OFFICE
4A137
4"
4"
A. REFER TO AND COORDINATE WITH ARCHITECTURAL FLOOR PLANS,
ELEVATIONS AND DETAILS FOR ADDITIONAL DETAILS PERTAINING
TO THIS SHEET.
B. REFER TO SHEET T-00-01 FOR SYMBOLS APPEARING ON THIS
SHEET.
C. ALL DEVICES WITHIN ROOMS CONTAINING HARD PAN CEILINGS
SHALL HAVE CONDUITS ROUTED TO ABOVE ACCESSIBLE CEILING
SPACE IN CORRIDOR.
D. COMMUNICATIONS CONDUIT PATHWAYS SHALL NOT CONTAIN ANY
LENGTH GREATER THAN 100 FEET BETWEEN PULL POINTS. NO
SECTION OF CONDUIT SHALL CONTAIN MORE THAN TWO 90-
DEGREE BENDS, OR EQUIVALENT, BETWEEN PULL POINTS. IF
THERE IS REVERSE BEND IN THE SECTION, A PULL POINT SHALL BE
INSTALLED. PULL BOXES SHALL NOT BE USED IN LIEU OF BENDS.
THE INSIDE RADIUS OF ALL CONDUIT BENDS SHALL BE AT LEAST 10
TIMES THE INTERNAL DIAMETER. BENDS IN CONDUIT SHALL NOT
CONTAIN ANY KINKS OR OTHER DISCONTINUITIES THAT MAY HAVE
A DETRIMENTAL EFFECT ON THE CABLE SHEATH DURING
INSTALLATION. NO DAISY CHAINING OF BACK BOXES ALLOWED
UNLESS OTHERWISE NOTED.
E. ALL CABLING SHALL BE SUPPORTED ABOVE ACCESSIBLE CEILING
SPACE USING LOW-VOLTAGE SUPPORTS SIZED AT 40% FILL BASED
ON CURRENT NEEDS.
F. BACK BOXES LOCATED IN FABRIC WALL AREAS SHALL BE
PROVIDED WITH BACK BOX EXTENSIONS TO PREVENT CRUSHING
OF WALL SURFACES.
0 8' 16' 1/8"=1'-0"
SENSITIVE BUT UNCLASSIFIED (SBU) PROPERTY OF THE UNITED STATES GOVERNMENT COPYING, DISSEMINATION, OR DISTRIBUTION OF THIS DOCUMENT TO UNAUTHORIZED RECIPIENTS IS PROHIBITED.
Do not remove this notice. Properly destroy or return documents when no longer needed.
TRUE NORTH
PLAN NORTH
CHECKED BY
DRAWN BY
FLOOR NUMBER
DRAWING TITLE
SHEET
NUMBER
SUBMISSION DATE
SUBMISSION STAGE
GSA PM
GSA PROJECT NO.
PROJECT
DESCRIPTION
PROJECT TITLE
BULDING NAME
ADDRESS
BUILDING NUMBER
PRIME CONTR. NO.
PRIME ORDER NO.
CONST. CONTR.
A/E
SUB A/E
CONST. CONTR. NO.
SHEET SIZE:
DATE DRAWN:
36 X 48
S H
E E
T
ID
E N
TI
FI
C A
TI
O
N
DISCIPLINE
P R
O
JE
C T
ID
E
N
TI
FI
C
A
TI
O N
B U
IL
D
IN
G
BIM FILE NAME
C O
N
TR
A C
TO
R
S R
E V
IS
IO
N B
LO
C
K G
R A
P H
IC
S
C A
LE
K
E Y
P
LA
N S
TA
M
P O
R S
E A
L D
E S
IG
N
E R
ID
E
N
TI
FI
C
A
TI
O N
O W
N E
R
ID
E N
TI
FI
C A
TI
O
N
SHEET OF SHEETS
KRUECK & SEXTON ARCHITECTS, P.C.
400 MARYLAND AVENUE, SW
WASHINGTON, DC 20024
LYNDON B. JOHNSON FEDERAL BUILDING
DC0010ZZ
DC0010_A_3-4-6-7_r2020.rvt
WSP ENGINEERING
DEPARTMENT OF EDUCATION
CONSOLIDATION PROJECT
ISSUE FOR BID
HALLIE FUTTERMAN
RENOVATION OF FLOORS 3, 4, 6, & 7 OF THE EXISTING
BUILDING TO MEET THE DEPARTMENT OF
EDUCATION’S PROGRAMMATIC REQUIREMENTS.
GS-07-P-16-UC-D-7000
47PM0520F0002
47PM0520F0002
KRUECK & SEXTON ARCHITECTS
221 W ERIE ST
CHICAGO, IL 60654 (312) 707-0056
ARCHITECT
WSP ENGINEERING
ONE PENNSYLVANIA PLAZA, SECOND FLOOR
NEW YORK, NY 10119 (212) 465-5000
MEP ENGINEER
ATELIER TEN
45 E 20TH ST, 4TH FLOOR
NEW YORK, NY 10003 (312) 386-1400
SUSTAINABILITY CONSULTANT
THRESHOLD ACOUSTICS
141 W JACKSON BLVD, SUITE 2080
CHICAGO, IL 60604 (312) 386-1400
ACOUSTIC CONSULTANT
WEST EAST
M A
TC
H
LI
N
E
GENERAL NOTESLEGEND KEY NOTES
GENERAL SERVICES ADMINISTRATION
NATIONAL CAPITAL REGION
PUBLIC BUILDING SERVICE, D.C. SERVICES DIV.
7TH & D STREET, S.W.
WASHINGTON, D.C. 20407
ISSUE
NO. DATE ISSUE
COMMUNICATIONS
VARIES, SEE DRAWINGS
01 04/23/2021 ISSUED FOR BID
/2
/2
:4
:1
P
M
T-14-01
TELECOMMUNICATIONS PLAN - LEVEL 4 - WEST
04/23/21
04/20/21FT
JMM
1/8" = 1'-0"
TELECOM_LEVEL 4_FLOOR PLAN__WEST
1 1
2 2 2 2 2 2 2 2 2 2
2222222222
1. PROVIDE (3) 4" CONDUITS AS SHOWN.
2. REFER TO SHEET T-50-03 FOR TYPICAL CONDUIT PATHWAY
DETAILS TO FURNITURE.
(312) 787-0056
FORCADE DESIGN
20a
20a
F F
E E
D D
C C
B B
A A
A A
B B
C C
D D
E E
F F
20a
20a
2 2
2 2
2 2 2 2
2 2 2 2 2 2 2 2 2
2 2 2
222222
TV3
TV3 2
TV3
TV3
TV3
F1
F1
F1
F1
1 1 1 1
T E
LE
C
O M
B
T L4
T E
LE
C
O M
B
T L3
12"X4" 12"X4" 12"X4" 12"X4" 12"X4"
12"X4"12"X4"12"X4"12"X4"12"X4"
"X
4"
TV3
1 1
2 2
F1 F1
F1 F1
F1 F1
F1 F1
F1 F1
F1 F1
F1 F1
F1 F1
F1 F1
F1 F1
F1 F1
F1 F1
F1
F1
F1
F1 F1
F1 F1
F1 F1
F1 F1
F1 F1
F1 F1
F1 F1
F1 F1
F1 F1
F1 F1
F1 F1
F1 F1
F1 F1
F1 F1
F1 F1
F1 F1
F1 F1
F1 F1
F1 F1
F1 F1
F1 F1
F1 F1
F1 F1
F1 F1
T-44-03
F1 F1
F1 F1
F1 F1
F1 F1
F1 F1
F1 F1
F1 F1
F1 F1
F1 F1
F1 F1
F1 F1
F1 F1
F1
F1
F1
F1 F1
F1 F1
F1 F1
F1 F1
F1 F1
F1 F1
F1 F1
F1 F1
F1 F1
F1 F1
F1 F1
F1 F1
F1 F1
F1 F1
F1 F1
F1 F1
F1 F1
F1 F1
F1 F1
F1 F1
F1 F1
F1 F1
F1 F1
F1 F1
2 2 2 2
2 2 2 2
T-44-02
2 2
TV3
TV3
TV3
T E
LE
C
O M
B
T L3
T E
LE
C
O M
C
T L
TV3
TV3
20a
20a
F F
E E
D D
C C
B B
A A
2 2 2
RESTROOM (W)
4CWMN
ELECTRICAL
4BEL2
ELECTRICAL
4BEL3
OFFICE
4B114
OFFICE
4B113
OFFICE
4B115
OFFICE
4B116
STAIR 4
4CST
Room
Room
FREIGHT ELEV. LOBBY
4BFLV
STAIR 3
4BST2
Room
EAST PANTRY
4BPN
COPY
4B102
OFFICE
4B214
OFFICE
4B213
OFFICE
4B215
OFFICE
4B216
OFFICE
4C111
OFFICE
4C112
OFFICE
4C110
OFFICE
4C114
OFFICE
4C113
OFFICE
4C115
OFFICE
4C211
OFFICE
4C212
OFFICE
4C210
OFFICE
4C214
OFFICE
4C213
OFFICE
4C215
CONFERENCE
4C156
CONFERENCE
4C150
HUDDLE ROOM
4C251
HUDDLE ROOM
4C151
FOCUS
4C153
FOCUS
4C152
FOCUS
4C253
FOCUS
4C252
FOCUS
4C255
FOCUS
4C155
FOCUS
4C154
FOCUS
4C254
CONFERENCE
4C256
CONFERENCE
4B152
CONFERENCE
4B153 CONFERENCE
4B155
CONFERENCE
4B154
CONFERENCE
4B252
CONFERENCE
4B253
CONFERENCE
4B255
CONFERENCE
4B254
CORRIDOR
4B101
TELECOM
4BTL2
TELECOM
4BTL3
Room
Room
Room
Room
Room
FOCUS ROOM
4C257
RESTROOM (M)
4CMEN
JANITOR
4CJA
ELECTRICAL
4CEL2
Room
TELECOM
4CTL2
Room
TELECOM
4CTL1
ELECTRICAL
4CEL1
OFFICE
4B133
OFFICE
4B132
OFFICE
4B131
OFFICE
4B130
OFFICE
4B233
OFFICE
4B232
OFFICE
4B231
OFFICE
4B230
OFFICE
4C192
OFFICE
4C191
OFFICE
4C190
OFFICE
4C292
OFFICE
4C291
OFFICE
4C290
EAST ELEVATOR LOBBY
4BLV2
COLLABORATION
4B170
COLLABORATION
4B270
ASSISTANT SECRETARY'S
SUITE
4C181
CONFERENCE
4C160
CORRIDOR
4C101
CORRIDOR
4C201
CORRIDOR
4C180
OPEN OFFICE
4B245 OPEN OFFICE
4C245
OPEN OFFICE
4B145
OPEN OFFICE
4C145
CORRIDOR
4C100
CORRIDOR
4C200
CORRIDOR
4C102
VESTIBULE
4C2VES
CORRIDOR
4B100
FOCUS
4C261
FOCUS
4C262
OFFICE
4C294
OFFICE
4C194
OFFICE
4C293
OFFICE
4C193
VESTIBULE
4C1VES
TV3
TV3
TV3
TV3
A. REFER TO AND COORDINATE WITH ARCHITECTURAL FLOOR PLANS,
ELEVATIONS AND DETAILS FOR ADDITIONAL DETAILS PERTAINING
TO THIS SHEET.
B. REFER TO SHEET T-00-01 FOR SYMBOLS APPEARING ON THIS
SHEET.
C. ALL DEVICES WITHIN ROOMS CONTAINING HARD PAN CEILINGS
SHALL HAVE CONDUITS ROUTED TO ABOVE ACCESSIBLE CEILING
SPACE IN CORRIDOR.
D. COMMUNICATIONS CONDUIT PATHWAYS SHALL NOT CONTAIN ANY
LENGTH GREATER THAN 100 FEET BETWEEN PULL POINTS. NO
SECTION OF CONDUIT SHALL CONTAIN MORE THAN TWO 90-
DEGREE BENDS, OR EQUIVALENT, BETWEEN PULL POINTS. IF
THERE IS REVERSE BEND IN THE SECTION, A PULL POINT SHALL BE
INSTALLED. PULL BOXES SHALL NOT BE USED IN LIEU OF BENDS.
THE INSIDE RADIUS OF ALL CONDUIT BENDS SHALL BE AT LEAST 10
TIMES THE INTERNAL DIAMETER. BENDS IN CONDUIT SHALL NOT
CONTAIN ANY KINKS OR OTHER DISCONTINUITIES THAT…