Drawing - TELE.pdf

PDF 33 MB Posted

Attached to
Solicitation Notice - LBJ Consolidation & Switchgear Federal contract opportunity
Solicitation number
47PM0121R0013
Issued by
General Services Administration Public Buildings Service

About this file

This document provides details of a solicitation notice for construction services related to the LBJ Consolidation and Switchgear project. The General Services Administration Public Buildings Service is seeking a firm fixed price contract to perform repair, alteration, and construction services including interior alterations and open workspace construction as well as significant renovations to the major switchgear and electrical systems servicing the building. The work will renovate floors 3, 4, 6, and 7 totaling approximately 198,369 square feet of open office space as well as 10,000 square feet of bathroom reconstruction for the Department of Education to allow for approximately 600 additional employees to occupy the LBJ Building. Interested firms must attend the pre-proposal conference on May 5, 2021 and submit a proposal by June 4, 2021. The North American Industry Classification code for this work is 236220 and has a small business size standard of $39.5 million in average annual receipts over the past three years.

View the file

Other files for this federal contract opportunity

Other files attached to Solicitation Notice - LBJ Consolidation & Switchgear, newest first.
File Type Posted
Bid Spreadsheet_Rev_6.7.21.xlsx XLSX spreadsheet
AS-50-06 - Sign Types Detail Sheet.pdf PDF
Solicitation 47PM0121R0013 revised 20210604.pdf PDF
AS-50-03 - Sign Types Detail Sheet.pdf PDF
RFIs (Round 2) and Response 6.4.21.pdf PDF
GSA-DoED_Addendum-02_MEP_5.24.21.pdf PDF
Bid Spreadsheet_Rev 1_5.24.21.xlsx XLSX spreadsheet
012400 Options_5.24.21 Revision.pdf PDF
26 32 13 - ENGINE GENERATOR(S) AND ACCESSORIES.pdf PDF
PBS Past Performance Form.docx DOCX document
Solicitation 47PM0121R0013 revised 20210525.pdf PDF
SF30 47PM0121R0013_0002.pdf PDF
RFI and Response_5.24.21.pdf PDF
1914_GSA-DoED_Issue for Bid - Architectural_210423_Vol 3.pdf PDF
LBJ 1959 Full Set Vol 1.pdf PDF
SF30 47PM0121R0013_0001.pdf PDF
PreProposal Minutes Attendee List.pdf PDF
1914_GSA-DoED_Issue for Bid - Architectural_210423_Vol 1 SMALL.pdf PDF
GSA LBJ DoED IFB SPEC Vol 1rev.pdf PDF
LBJ 1959 Full Set Vol 2.pdf PDF
LBJ 1995 Architectural Set.pdf PDF
1914_GSA-DoED_Issue for Bid - Architectural_210423_Vol 2.pdf PDF
SOW LBJ Consolidation Construction Services.pdf PDF
Instructions LBJ Virtual Site Walk READ ME.pdf PDF
Drawings - ARCH Vol 1.pdf PDF
Drawing - Signage.pdf PDF
1914_GSA-DoED_Switchgear - Electrical_210423.pdf PDF
Layout for staging - switchgear.pdf PDF
2019.07.12_LBJ_BPP 100% Submission.pdf PDF
SF1442 47PM0121R0013.pdf PDF
Agreement (draft) RFP 47PM0121R0013.pdf PDF
Bid Spreadsheet.xlsx XLSX spreadsheet
Drawings - ARCH Vol 2.pdf PDF
Drawing - FP.pdf PDF
LBJ_5thFl_bathrooms-Staging.pdf PDF
SFLLL.pdf PDF
Solicitation 47PM0121R0013.pdf PDF
Reps and Certs 47PM0121R0013.pdf PDF
Drawing - PLUM.pdf PDF
SPEC Vol 1 GSA LBJ DoED.pdf PDF
SPEC Vol 2 GSA LBJ DoED.pdf PDF
LBJ_2ndFl_bathrooms-Staging.pdf PDF
GSA527.pdf PDF
Drawing - HVAC.pdf PDF
Drawing - FA.pdf PDF
Drawing - ELEC.pdf PDF
Drawing - AV.pdf PDF
1914_GSA-DoED_L2 L5 - Combined_210423.pdf PDF
Contractor Site Office.pdf PDF
Narrative Modernization Issue for Bid LBJ 2021April23.pdf PDF
Show all 50

Solicitation Notice - LBJ Consolidation & Switchgear has more files on GovTribe.

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

N

SYMBOL

ALL SYMBOLS SHOWN MAY NOT APPEAR IN ALL DRAWINGS. SYMBOLS ARE SHOWN SCHEMATIC AND MAY NOT BE TO SCALE.

DATA SYMBOLS LEGEND

DESCRIPTION

DATA AND/OR VOICE OUTLET, N=CABLE QUANTITY. PROVIDE

DOUBLE GANG BACK, 2 1/8" DEEP, WITH SINGLE GANG DEVICE

COVER AND 1" CONDUIT STUBBED ABOVE ACCESSIBLE CEILING

SPACE.

DATA BACKBOX SCHEDULE

SYMBOL DESCRIPTION

AA

DOUBLE GANG BACK BOX, 2 1/8" DEEP, WITH SINGLE GANG DEVICE COVER AND 1" CONDUIT PATHWAY STUBBED

ABOVE ACCESSIBLE CEILING SPACE.

BB

CC

DD

WALL PHONE STYLE FACEPLATE, DOUBLE GANG BACK BOX, 2 1/8" DEEP, WITH SINGLE GANG DEVICE COVER AND

1" CONDUIT PATHWAY STUBBED ABOVE ACCESSIBLE CEILING SPACE.

REFER TO ELECTRICAL (E) SHEETS FOR ROUGH IN REQUIREMENTS.

OUTLET TO BE HOUSED ABOVE ACCESSIBLE CEILING. CABLE TO LOCATION SHOWN ON THE FLOOR PLANS AND

LEAVE A MINIMUM 50 FEET COILED AT THE LOCATION.

N

N N

N N

MNTG. HT. UNO

(SEE NOTE 1)

BACK BOX

AA 18" WALL AFF

AA

BB

BB

48" WALL AFF

CC FLOOR

= EMPTY BACK BOX

= 1 DATA CABLE

= 2 DATA CABLES

= 3 DATA CABLES

= 4 DATA CABLES

= 1 VOICE CABLE

= 2 VOICE CABLES

= 1 DATA / 1 VOICE CABLES

= 2 DATA / 1 VOICE CABLES

= 2 DATA / 2 VOICE CABLES

2V

3D,1V

= 3 DATA / 1 VOICE CABLES

= 1 DATA / 3 VOICE CABLES

1D,3V

OR

W W

OR

OR

N N

OR

OR

W W

48" WALL AFF

42" WALL AFF

OR

N

WAP

DATA AND/OR VOICE OUTLET, WALL PHONE STYLE FACEPLATE, 1

DATA/VOICE CABLE. PROVIDE DOUBLE GANGE BACK BOX, 2 1/8"

DEEP, WITH SINGLE GANGE DEVICE COVER AND 1" CONDUIT

STUBBED ABOVE ACCESSIBLE CEILING SPACE.

DATA AND/OR VOICE OUTLET, WALL PHONE STYLE FACEPLATE, 1

DATA/VOICE CABLE, MOUNTED ABOVE COUNTER. PROVIDE DOUBLE

GANGE BACK BOX, 2 1/8" DEEP, WITH SINGLE GANGE DEVICE COVER

AND 1" CONDUIT STUBBED ABOVE ACCESSIBLE CEILING SPACE.

DATA AND/OR VOICE OUTLET, N = CABLE QUANTITY, MOUNTED

ABOVE COUNTER. PROVIDE DOUBLE GANGE BACK BOX, 2 1/8" DEEP,

WITH SINGLE GANGE DEVICE COVER AND 1" CONDUIT STUBBED

ABOVE ACCESSIBLE CEILING SPACE.

FLOOR MOUNTED DATA AND/OR VOICE OUTLET, N = CABLE

QUANTITY. REFER TO ELECTRICAL SHEETS FOR ROUGH IN

REQUIREMENTS.

CEILING MOUNTED DATA AND/OR VOICE OUTLET, N = CABLE

QUANTITY. OUTLET TO BE HOUSED ABOVE ACCESSIBLE CEILING.

CABLE TO LOCATION SHOWN ON FLOOR PLANS.

DD

ABOVE

ACCESSIBLE

CEILING

DD

ABOVE

ACCESSIBLE

CEILING

CEILING MOUNTED WIRELESS ACCESS POINT, N = CABLE QUANTITY.

OUTLET TO BE HOUSED ABOVE ACCESSIBLE CEILING. CABLE TO

LOCATION SHOWN ON FLOOR PLANS.

DATA NOTES:

1. REFER TO ARCHITECTURAL ELEVATIONS FOR EXACT MOUNTING HEIGHTS OF ALL DEVICES.

2. 48" AFF INDICATES TO THE TOP OF THE DEVICE

3. 18" AFF INDICATES TO THE CENTER OF DEVICE

4. 60" AFF INDICATES TO THE BOTTOM OF DEVICE

5. 80" AFF INDICATES TO THE BOTTOM OF DEVICE

6. ALL OTHER MOUNTING HEIGHTS REFER TO CENTERLINE OF DEVICE

FN

SYSTEMS FURNITURE DATA OUTLET. N = CABLE QUANTITY.

PROVIDE AND INSTALL FOUR PORT SYSTEMS FURNITURE

FACEPLATE ONTO FURNITURE RACEWAY SYSTEM.

N/A SYSTEMS

FURNITURE

COMMUNICATIONS ABBREVIATIONS (FOR CLARIFICATION ONLY)

• EX EXISTING

• AFF ABOVE FINISHED FLOOR

• AFC ABOVE FINISHED CEILING

• BFC BELOW FINISHED CEILING

• W WALL PHONE

• MON MONITOR

J

CT

LR

JUNCTION BOX - SIZE AND MOUNTING AS REQUIRED.

MEDIUM DETAIL LEVEL

COARSE DETAIL LEVEL

FINE DETAIL LEVEL

CABLE TRAY - MAIN CABLE PATH SEE DETAIL FOR MORE INFORMATION.

MEDIUM DETAIL LEVEL

COARSE DETAIL LEVEL

FINE DETAIL LEVEL

LADDER RUNWAY - SIZE AND LOCATION AS SHOWN ON DRAWINGS.

FS 2", UNLESS NOTED OTHERWISE, HILTI SPEED SLEEVE FIRE RATED PATHWAY DEVICE, PART NUMBER 2097882, THROUGH RATED WALL.

2", UNLESS NOTED OTHERWISE, EMT SLEEVE EQUIPPED WITH PLASTIC BUSHING ON BOTH ENDS, THROUGH WALL.

RATING SHALL MATCH WALL BEING PENETRATED. REFER TO ARCHITECTURAL DRAWINGS FOR WALL RATINGS.

VERTICAL CORE AND SLEEVE THROUGH FLOOR. PROVIDE EMT SLEEVE, EQUIPPED WITH PLASTIC BUSHING ON BOTH ENDS. REFER TO FLOOR PLAN FOR SIZING. RATING SHALL MATCH FLOOR BEING PENETRATED. REFER TO

ARCHITECTURAL DRAWINGS FOR FLOOR RATINGS.

2-POST FREESTANDING EQUIPMENT RACK. SIZE AND LOCATION AS SHOWN.

4-POST FREESTANDING EQUIPMENT RACK. SIZE AND LOCATION AS SHOWN.

VERTICAL WIRE MANAGER. SIZE AND LOCATION AS SHOWN.

GROUND BUSS BAR - 1/4" x 2" x 10", PANDUIT OR EQUAL.

• TV TELEVISION

• CT CABLE TRAY

• PRT PRINTER

• CPU COMPUTER

• MFD MULTI_FUNCTION DEVICE

SYMBOL

ALL SYMBOLS SHOWN MAY NOT APPEAR IN ALL DRAWINGS. SYMBOLS ARE SHOWN SCHEMATIC AND MAY NOT BE TO SCALE.

COMMUNICATIONS GENERAL SYMBOLS LEGEND

DESCRIPTION

FLOOR BOX FEEDER FOR SYSTEMS FURNITURE WORK AREA OUTLETS.

TV1

SYMBOL

ALL SYMBOLS SHOWN MAY NOT APPEAR IN ALL DRAWINGS. SYMBOLS ARE SHOWN SCHEMATIC AND MAY NOT BE TO SCALE.

TELEVISION SYMBOLS LEGEND

DESCRIPTION

TELEVISION OUTLET, ONE COAX CABLE

DATA BACKBOX SCHEDULE

SYMBOL DESCRIPTION

AA

DOUBLE GANG BACK BOX, 2 1/8" DEEP, WITH SINGLE GANG DEVICE COVER AND 1" CONDUIT PATHWAY STUBBED

ABOVE ACCESSIBLE CEILING SPACE. FOR TV4 CONDUIT SIZE 1 1/4".

BB

CC

DATA NOTES:

1. REFER TO ARCHITECTURAL ELEVATIONS FOR EXACT MOUNTING HEIGHTS OF ALL DEVICES.

2. 48" AFF INDICATES TO THE TOP OF THE DEVICE

3. 18" AFF INDICATES TO THE CENTER OF DEVICE

4. 50" AFF INDICATES TO THE BOTTOM OF DEVICE

5. 80" AFF INDICATES TO THE BOTTOM OF DEVICE

6. ALL OTHER MOUNTING HEIGHTS REFER TO CENTERLINE OF DEVICE

7. COORDINATE FINAL OUTLET LOCATION WITH TELEVISION MOUNTING BRACKETS

MNTG. HT. UNO

(SEE NOTE 1)

BACK BOX

AA

TV2

TELEVISION OUTLET, ONE DATA CABLE AA

TV3

TELEVISION OUTLET, ONE DATA CABLE & ONE COAX CABLE AA

DOUBLE GANG BACK BOX, 2 1/8" DEEP, WITH DUAL GANG DEVICE COVER AND 1" CONDUIT PATHWAY STUBBED

ABOVE ACCESSIBLE CEILING SPACE.

OUTLET TO BE HOUSED ABOVE ACCESSIBLE CEILING. IF LOCATED IN NON ACCESSIBLE CEILING SPACE PROVIDE

BACK BOX "AA".

NOTE 7

TV4

TELEVISION OUTLET, TWO DATA, ONE COAX & ONE HDMI

NOTE 7

NOTE 7

NOTE 7

0 - - N.T.S.

CHECKED BY

DRAWN BY

FLOOR NUMBER

DRAWING TITLE

SHEET

NUMBER

SUBMISSION DATE

SUBMISSION STAGE

GSA PM

GSA PROJECT NO.

PROJECT

DESCRIPTION

PROJECT TITLE

BULDING NAME

ADDRESS

BUILDING NUMBER

PRIME CONTR. NO.

PRIME ORDER NO.

CONST. CONTR.

A/E

SUB A/E

CONST. CONTR. NO.

SHEET SIZE:

DATE DRAWN:

36 X 48

S H

E E

T

ID

E N

TI

FI

C A

TI

O

N

DISCIPLINE

P R

O

JE

C T

ID

E

N

TI

FI

C

A

TI

O N

B U

IL

D

IN

G

BIM FILE NAME

C O

N

TR

A C

TO

R

S R

E V

IS

IO

N B

LO

C

K G

R A

P H

IC

S

C A

LE

K

E Y

P

LA

N S

TA

M

P O

R S

E A

L D

E S

IG

N

E R

ID

E

N

TI

FI

C

A

TI

O N

O W

N E

R

ID

E N

TI

FI

C A

TI

O

N

SHEET OF SHEETS

KRUECK & SEXTON ARCHITECTS, P.C.

400 MARYLAND AVENUE, SW

WASHINGTON, DC 20024

LYNDON B. JOHNSON FEDERAL BUILDING

DC0010ZZ

DC0010_A_3-4-6-7_r2020.rvt

WSP ENGINEERING

DEPARTMENT OF EDUCATION

CONSOLIDATION PROJECT

ISSUE FOR BID

HALLIE FUTTERMAN

RENOVATION OF FLOORS 3, 4, 6, & 7 OF THE EXISTING

BUILDING TO MEET THE DEPARTMENT OF

EDUCATION’S PROGRAMMATIC REQUIREMENTS.

GS-07-P-16-UC-D-7000

47PM0520F0002

47PM0520F0002

KRUECK & SEXTON ARCHITECTS

221 W ERIE ST

CHICAGO, IL 60654 (312) 707-0056

ARCHITECT

WSP ENGINEERING

ONE PENNSYLVANIA PLAZA, SECOND FLOOR

NEW YORK, NY 10119 (212) 465-5000

MEP ENGINEER

ATELIER TEN

45 E 20TH ST, 4TH FLOOR

NEW YORK, NY 10003 (312) 386-1400

SUSTAINABILITY CONSULTANT

THRESHOLD ACOUSTICS

141 W JACKSON BLVD, SUITE 2080

CHICAGO, IL 60604 (312) 386-1400

ACOUSTIC CONSULTANT

WEST EAST

M A

TC

H

LI

N

E

GENERAL SERVICES ADMINISTRATION

NATIONAL CAPITAL REGION

PUBLIC BUILDING SERVICE, D.C. SERVICES DIV.

7TH & D STREET, S.W.

WASHINGTON, D.C. 20407

ISSUE

NO. DATE ISSUE

COMMUNICATIONS

VARIES, SEE DRAWINGS

01 04/23/2021 ISSUED FOR BID

/2

/2

:4

:1

P

M

T-00-01

TELECOM LEGENDS, SYMBOLS, AND ABBREVIATIONS

04/23/21

04/20/21FT

JMM

1. ALL COMMUNICATIONS PRODUCTS AND INSTALLATIONS SHALL COMPLY WITH ALL APPLICABLE STATE

AND LOCAL CODES. REFER TO SPECIFICATIONS FOR MATERIALS AND METHODS FOR

COMMUNICATIONS CONSTRUCTION.

2. CONTRACTOR SHALL OBTAIN ALL NECESSARY PERMITS, PAY ALL FEES AND COMPLY WITH ALL NATIONAL, STATE AND MUNICIPAL LAWS, CODES AND ORDINANCES RELATING TO BUILDING AND

PUBLIC SAFETY.

3. CONTRACTOR SHALL FURNISH ALL MATERIALS, EQUIPMENT AND LABOR REQUIRED FOR A COMPLETE

WORKING AND COORDINATED SYSTEM.

4. UNLESS OTHERWISE NOTED, ALL EQUIPMENT AND MATERIALS SHALL BE NEW AND U.L. LISTED OR LABELED. EQUIPMENT AND MATERIALS SHALL BE INSTALLED IN ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS, AND LISTING OR LABELING REQUIREMENTS AND RESTRICTIONS. PROVIDE DATA

DEPICTED IN THE COMMUNICATIONS SPECIFICATIONS.

5. CONTRACTOR SHALL PROVIDE SHOP DRAWINGS FOR APPROVAL FOR ALL COMMUNICAITONS

MATERIALS PROPOSED TO BE PROVIDED UNDER THIS CONTRACT. ANY DEVIATIONS FROM ITEMS

SPECIFIED SHALL BE CLEARLY IDENTIFIED. NO WORK IS AUTHORIZED WITHOUT SHOP DRAWINGS

REVIEWED BY ENGINEER.

6. REFER TO AND COORDINATE WITH ARCHITECTURAL DRAWINGS FOR EXACT LOCATION OF ALL DEVICES

AND EQUIPMENT.

7. REFER TO AND COORDINATE WITH DIVISION 23 FOR THE LOCATION OF ALL ITEMS LOCATED IN THE CEILING INCLUDING, BUT NOT LIMITED TO, SUPPLY-AIR DIFFUSERS, RETURN-AIR DIFFUSERS AND FIRE

SPRINKLER HEADS.

8. ALL PENETRATIONS THROUGH FIRE RATED WALLS OR PARTITIONS SHALL BE MADE IN ACCORDANCE WITH U.L. 483 "FIRE RESISTANCE DIRECTORY". PENETRATIONS SHALL BE SLEEVED AND SEALED WITH A U.L. APPROVED FIRE RATED SEALANT. REFER TO ARCHITECTURAL PLANS FOR ALL RATED WALLS.

9. CONTRACTOR SHALL COORDINATE AND SCHEDULE ALL OUTAGES WITH OWNER'S REPRESENTATIVE.

10. CONTRACTOR SHALL WARRANTY WORK FOR (1) YEAR FROM COMPLETION OF THE PROJECT AND

PROVIDE OWNER AS BUILT DRAWINGS.

11. SPACE ALLOCATIONS FOR MATERIAL, EQUIPMENT AND DEVICES HAVE BEEN MADE ON THE BASIS OF

PRESENT AND KNOWN FUTURE REQUIREMENTS AND THE DIMENSIONS OF ITEMS OF EQUIPMENT OR DEVICES OF A PARTICULAR MANUFACTURER WHETHER INDICATED OR NOT. THE CONTRACOR SHALL VERIFY THAT ALL MATERIALS, EQUIPMENT AND DEVICES PROPOSED FOR USE ON THIS PROJECT ARE

WITHIN THE CONSTRAINTS OF THE ALLOCATED SPACE.

12. ALL EMPTY CONDUIT SYSTEMS SHALL CONTAIN A PULL WIRE FOR FUTURE PULLING OF CONDUCTORS.

GENERAL NOTES:

1. INFORMATION PROVIDED ON THESE DRAWINGS HAS BEEN TAKEN FROM DESIGN DRAWING AND FIELD OBSERVATIONS. CONTRACTOR SHALL VERIFY ALL EXISTING CONDITIONS PRIOR TO PRICING AND

COMMENCEMENT OF WORK.

2. WHERE EXISTING WALLS ARE DEMOLISHED, REMOVE ALL EXISTING WIRING DEVICES AND THEIR

ASSOCIATED CONDUITS AND WIRING BACK TO THE POINT OF ORGINATION.

3. PROVIDE FOR ANY AND ALL DEMOLITION WORK NECESSARY TO ACCOMMODATE ALL NEW

CONSTRUCTION, INCLUDING ARCHITECTURAL, MECHANICAL, PLUMBING OR ELECTRICAL WORK.

4. IF DEMOLITION IS REQUIRED TO INSTALL AN ITEM, THE CONTRACTOR SHALL RESTORE THE AREA TO

PREVIOUS CONDITION, OR REPLACE DAMAGED ITEMS WITH NEW ITEMS TO MATCH EXISTING.

5. SPACE ALLOCATIONS FOR MATERIALS, EQUIPMENT AND DEVICES HAVE BEEN MADE ON THE BASIS OF

PRESENT AND KNOWN FUTURE REQUIREMENTS AND DIMENSIONS OF ITEMS OF EQUIPMENT OR

DEVICES OF A PARTICULAR MANUFACTURER, WHETHER INDICATED OR NOT. THE CONTRACTOR SHALL VERIFY THAT ALL MATERIALS, EQUIPMENT AND DEVICES PROPOSED FOR USE ON THIS PROJECT ARE

WITHIN THE CONSTRAINTS OF THE ALLOCATED SPACE.

6. VERIFY THAT ANY DEVICES LOCATED OUTSIDE OF CONSTRUCTION AREA REMAINS IN PROPER

OPERATING FUNCTION.

7. ANY EXISTING CABLING TO REMAIN WITHIN CONSTRUCTION AREA NOT SUPPORTED PROPERLY SHALL

BE SUPPORTED AS PART OF THE PROJECT.

8. EXISTING ABANDONED CABLE LOCATED IN CONSTRUCTION AREA SHALL BE REMOVED BACK TO POINT

OF ORIGINATION PER NEC ARTICLES 725.25, 770.25 & 800.25.

9. RETURN ALL IT INFRASTRUCTURE (I.E. COMPUTERS, PHONES, WIRELESS ACCESS POINTS, ETC.) TO THE IT DEPARTMENT. COORDINATE WITH OWNER'S IT REPRESENTATIVE AS TO PROPER LOCATION.

GENERAL DEMO NOTES:

(312) 787-0056

FORCADE DESIGN

1626 PAYNE STREET

EVANSTON, IL 60201 (847) 448-4270

19" RELAY

RACK

FRONT

" R

EL

AY

RA

C

K

FR

O N

T

3a

3a

20a

20a

F F

E E

D D

C C

B B

A A

A A

B B

C C

D D

E E

F F

3a

3a

20a

20a

A A

B B

C C

D D

E E

F F

3a

3a

20a

20a

3a

3a

20a

20a

F F

E E

D D

C C

B B

A A

A A

B B

C C

D D

E E

F F

3a

3a

20a

20a

A. REFER TO AND COORDINATE WITH ARCHITECTURAL FLOOR PLANS,

ELEVATIONS AND DETAILS FOR ADDITIONAL DETAILS PERTAINING

TO THIS SHEET.

B. REFER TO SHEET T-00-01 FOR SYMBOLS APPEARING ON THIS

SHEET.

C. WHERE EXISTING WALLS ARE DEMOLISHED, REMOVE ALL EXISTING

COMMUNICATIONS/LOW VOLTAGE DEVICES AND THEIR

ASSOCIATED CONDUITS AND WIRING BACK TO ORIGINATION.

EXISTING CABLING PASSING THROUGH DEMO AREA, NOT BEING

DEMOLISHED, SHALL BE SUPPORTED UTILIZING J-HOOK CABLE

SUPPORTS PER TIA STANDARDS.

D. EXISTING EQUIPMENT RACKS AND WALL BOARD CURRENTLY

LOCATED WITHIN THE EXISTING TELECOM ROOMS SHALL REMAIN

AS IS AND REUSED.

E. THERE IS NO SCOPE FOR WAPs. THE EXISTING WAPs AND CABLING

MUST BE FUNCTIONAL UPON SUBSTANTIAL COMPLETION. THE

CONTRACTOR CAN DETERMINE WHETHER TO REMOVE OR

PROTECT IN PLACE. ALL WORK SHALL BE COORDINATED WITH THE

GENERAL CONTRACTOR AND FINAL TESTING OF THE SYSTEM

SHALL BE COORDINATED WITH THE GOVERNMENT.

0 16' 32' 1/16"=1'-0"

SENSITIVE BUT UNCLASSIFIED (SBU) PROPERTY OF THE UNITED STATES GOVERNMENT COPYING, DISSEMINATION, OR DISTRIBUTION OF THIS DOCUMENT TO UNAUTHORIZED RECIPIENTS IS PROHIBITED.

Do not remove this notice. Properly destroy or return documents when no longer needed.

TRUE NORTH

PLAN NORTH

CHECKED BY

DRAWN BY

FLOOR NUMBER

DRAWING TITLE

SHEET

NUMBER

SUBMISSION DATE

SUBMISSION STAGE

GSA PM

GSA PROJECT NO.

PROJECT

DESCRIPTION

PROJECT TITLE

BULDING NAME

ADDRESS

BUILDING NUMBER

PRIME CONTR. NO.

PRIME ORDER NO.

CONST. CONTR.

A/E

SUB A/E

CONST. CONTR. NO.

SHEET SIZE:

DATE DRAWN:

36 X 48

S H

E E

T

ID

E N

TI

FI

C A

TI

O

N

DISCIPLINE

P R

O

JE

C T

ID

E

N

TI

FI

C

A

TI

O N

B U

IL

D

IN

G

BIM FILE NAME

C O

N

TR

A C

TO

R

S R

E V

IS

IO

N B

LO

C

K G

R A

P H

IC

S

C A

LE

K

E Y

P

LA

N S

TA

M

P O

R S

E A

L D

E S

IG

N

E R

ID

E

N

TI

FI

C

A

TI

O N

O W

N E

R

ID

E N

TI

FI

C A

TI

O

N

SHEET OF SHEETS

KRUECK & SEXTON ARCHITECTS, P.C.

400 MARYLAND AVENUE, SW

WASHINGTON, DC 20024

LYNDON B. JOHNSON FEDERAL BUILDING

DC0010ZZ

DC0010_A_3-4-6-7_r2020.rvt

WSP ENGINEERING

DEPARTMENT OF EDUCATION

CONSOLIDATION PROJECT

ISSUE FOR BID

HALLIE FUTTERMAN

RENOVATION OF FLOORS 3, 4, 6, & 7 OF THE EXISTING

BUILDING TO MEET THE DEPARTMENT OF

EDUCATION’S PROGRAMMATIC REQUIREMENTS.

GS-07-P-16-UC-D-7000

47PM0520F0002

47PM0520F0002

KRUECK & SEXTON ARCHITECTS

221 W ERIE ST

CHICAGO, IL 60654 (312) 707-0056

ARCHITECT

WSP ENGINEERING

ONE PENNSYLVANIA PLAZA, SECOND FLOOR

NEW YORK, NY 10119 (212) 465-5000

MEP ENGINEER

ATELIER TEN

45 E 20TH ST, 4TH FLOOR

NEW YORK, NY 10003 (312) 386-1400

SUSTAINABILITY CONSULTANT

THRESHOLD ACOUSTICS

141 W JACKSON BLVD, SUITE 2080

CHICAGO, IL 60604 (312) 386-1400

ACOUSTIC CONSULTANT

WEST EAST

M A

TC

H

LI

N

E

GENERAL NOTESLEGEND KEY NOTES

GENERAL SERVICES ADMINISTRATION

NATIONAL CAPITAL REGION

PUBLIC BUILDING SERVICE, D.C. SERVICES DIV.

7TH & D STREET, S.W.

WASHINGTON, D.C. 20407

ISSUE

NO. DATE ISSUE

COMMUNICATIONS

VARIES, SEE DRAWINGS

01 04/23/2021 ISSUED FOR BID

/2

/2

:4

:0

P

M

TD-13-01

TELECOMMUNICATIONS DEMOLITION - LEVEL 3

04/23/21

04/20/21FT

JMM

1/16" = 1'-0"

TELECOM_LEVEL 3_FLOOR PLAN_DEMO

1. EXISTING EQUIPMENT WITHIN THIS ROOM TO REMAIN . PROTECT

IN PLACE.

(312) 787-0056

FORCADE DESIGN

FRONT

19" RELAY

RACK

FRONT

19" RELAY

RACKFRONT

19" RELAY

RACKFRONT

19" RELAY

RACKFRONT

19" RELAY

RACKFRONT

3a

3a

20a

20a

F F

E E

D D

C C

B B

A A

A A

B B

C C

D D

E E

F F

3a

3a

20a

20a

A A

B B

C C

D D

E E

F F

3a

3a

20a

20a

3a

3a

20a

20a

F F

E E

D D

C C

B B

A A

A A

B B

C C

D D

E E

F F

3a

3a

20a

20a

A. REFER TO AND COORDINATE WITH ARCHITECTURAL FLOOR PLANS,

ELEVATIONS AND DETAILS FOR ADDITIONAL DETAILS PERTAINING

TO THIS SHEET.

B. REFER TO SHEET T-00-01 FOR SYMBOLS APPEARING ON THIS

SHEET.

C. WHERE EXISTING WALLS ARE DEMOLISHED, REMOVE ALL EXISTING

COMMUNICATIONS/LOW VOLTAGE DEVICES AND THEIR

ASSOCIATED CONDUITS AND WIRING BACK TO ORIGINATION.

EXISTING CABLING PASSING THROUGH DEMO AREA, NOT BEING

DEMOLISHED, SHALL BE SUPPORTED UTILIZING J-HOOK CABLE

SUPPORTS PER TIA STANDARDS.

D. EXISTING EQUIPMENT RACKS AND WALL BOARD CURRENTLY

LOCATED WITHIN THE EXISTING TELECOM ROOMS SHALL REMAIN

AS IS AND REUSED.

E. THERE IS NO SCOPE FOR WAPs. THE EXISTING WAPs AND CABLING

MUST BE FUNCTIONAL UPON SUBSTANTIAL COMPLETION. THE

CONTRACTOR CAN DETERMINE WHETHER TO REMOVE OR

PROTECT IN PLACE. ALL WORK SHALL BE COORDINATED WITH THE

GENERAL CONTRACTOR AND FINAL TESTING OF THE SYSTEM

SHALL BE COORDINATED WITH THE GOVERNMENT.

0 16' 32' 1/16"=1'-0"

SENSITIVE BUT UNCLASSIFIED (SBU) PROPERTY OF THE UNITED STATES GOVERNMENT COPYING, DISSEMINATION, OR DISTRIBUTION OF THIS DOCUMENT TO UNAUTHORIZED RECIPIENTS IS PROHIBITED.

Do not remove this notice. Properly destroy or return documents when no longer needed.

TRUE NORTH

PLAN NORTH

CHECKED BY

DRAWN BY

FLOOR NUMBER

DRAWING TITLE

SHEET

NUMBER

SUBMISSION DATE

SUBMISSION STAGE

GSA PM

GSA PROJECT NO.

PROJECT

DESCRIPTION

PROJECT TITLE

BULDING NAME

ADDRESS

BUILDING NUMBER

PRIME CONTR. NO.

PRIME ORDER NO.

CONST. CONTR.

A/E

SUB A/E

CONST. CONTR. NO.

SHEET SIZE:

DATE DRAWN:

36 X 48

S H

E E

T

ID

E N

TI

FI

C A

TI

O

N

DISCIPLINE

P R

O

JE

C T

ID

E

N

TI

FI

C

A

TI

O N

B U

IL

D

IN

G

BIM FILE NAME

C O

N

TR

A C

TO

R

S R

E V

IS

IO

N B

LO

C

K G

R A

P H

IC

S

C A

LE

K

E Y

P

LA

N S

TA

M

P O

R S

E A

L D

E S

IG

N

E R

ID

E

N

TI

FI

C

A

TI

O N

O W

N E

R

ID

E N

TI

FI

C A

TI

O

N

SHEET OF SHEETS

KRUECK & SEXTON ARCHITECTS, P.C.

400 MARYLAND AVENUE, SW

WASHINGTON, DC 20024

LYNDON B. JOHNSON FEDERAL BUILDING

DC0010ZZ

DC0010_A_3-4-6-7_r2020.rvt

WSP ENGINEERING

DEPARTMENT OF EDUCATION

CONSOLIDATION PROJECT

ISSUE FOR BID

HALLIE FUTTERMAN

RENOVATION OF FLOORS 3, 4, 6, & 7 OF THE EXISTING

BUILDING TO MEET THE DEPARTMENT OF

EDUCATION’S PROGRAMMATIC REQUIREMENTS.

GS-07-P-16-UC-D-7000

47PM0520F0002

47PM0520F0002

KRUECK & SEXTON ARCHITECTS

221 W ERIE ST

CHICAGO, IL 60654 (312) 707-0056

ARCHITECT

WSP ENGINEERING

ONE PENNSYLVANIA PLAZA, SECOND FLOOR

NEW YORK, NY 10119 (212) 465-5000

MEP ENGINEER

ATELIER TEN

45 E 20TH ST, 4TH FLOOR

NEW YORK, NY 10003 (312) 386-1400

SUSTAINABILITY CONSULTANT

THRESHOLD ACOUSTICS

141 W JACKSON BLVD, SUITE 2080

CHICAGO, IL 60604 (312) 386-1400

ACOUSTIC CONSULTANT

WEST EAST

M A

TC

H

LI

N

E

GENERAL NOTESLEGEND KEY NOTES

GENERAL SERVICES ADMINISTRATION

NATIONAL CAPITAL REGION

PUBLIC BUILDING SERVICE, D.C. SERVICES DIV.

7TH & D STREET, S.W.

WASHINGTON, D.C. 20407

ISSUE

NO. DATE ISSUE

COMMUNICATIONS

VARIES, SEE DRAWINGS

01 04/23/2021 ISSUED FOR BID

/2

/2

:4

:1

P

M

TD-14-01

TELECOMMUNICATIONS DEMOLITION - LEVEL 4

04/23/21

04/20/21FT

JMM

1/16" = 1'-0"

TELECOM_LEVEL 4_FLOOR PLAN_DEMO

1. EXISTING EQUIPMENT WITHIN THIS ROOM TO REMAIN . PROTECT

IN PLACE.

(312) 787-0056

FORCADE DESIGN

FRONT

19" RELAY

RACK

FRONT

19" RELAY

RACKFRONT

19" RELAY

RACKFRONT

19" RELAY

RACKFRONT

19" RELAY

RACKFRONT

3a

3a

20a

20a

F F

E E

D D

C C

B B

A A

A A

B B

C C

D D

E E

F F

3a

3a

20a

20a

A A

B B

C C

D D

E E

F F

3a

3a

20a

20a

3a

3a

20a

20a

F F

E E

D D

C C

B B

A A

A A

B B

C C

D D

E E

F F

3a

3a

20a

20a

A. REFER TO AND COORDINATE WITH ARCHITECTURAL FLOOR PLANS,

ELEVATIONS AND DETAILS FOR ADDITIONAL DETAILS PERTAINING

TO THIS SHEET.

B. REFER TO SHEET T-00-01 FOR SYMBOLS APPEARING ON THIS

SHEET.

C. WHERE EXISTING WALLS ARE DEMOLISHED, REMOVE ALL EXISTING

COMMUNICATIONS/LOW VOLTAGE DEVICES AND THEIR

ASSOCIATED CONDUITS AND WIRING BACK TO ORIGINATION.

EXISTING CABLING PASSING THROUGH DEMO AREA, NOT BEING

DEMOLISHED, SHALL BE SUPPORTED UTILIZING J-HOOK CABLE

SUPPORTS PER TIA STANDARDS.

D. EXISTING EQUIPMENT RACKS AND WALL BOARD CURRENTLY

LOCATED WITHIN THE EXISTING TELECOM ROOMS SHALL REMAIN

AS IS AND REUSED.

E. THERE IS NO SCOPE FOR WAPs. THE EXISTING WAPs AND CABLING

MUST BE FUNCTIONAL UPON SUBSTANTIAL COMPLETION. THE

CONTRACTOR CAN DETERMINE WHETHER TO REMOVE OR

PROTECT IN PLACE. ALL WORK SHALL BE COORDINATED WITH THE

GENERAL CONTRACTOR AND FINAL TESTING OF THE SYSTEM

SHALL BE COORDINATED WITH THE GOVERNMENT.

0 16' 32' 1/16"=1'-0"

SENSITIVE BUT UNCLASSIFIED (SBU) PROPERTY OF THE UNITED STATES GOVERNMENT COPYING, DISSEMINATION, OR DISTRIBUTION OF THIS DOCUMENT TO UNAUTHORIZED RECIPIENTS IS PROHIBITED.

Do not remove this notice. Properly destroy or return documents when no longer needed.

TRUE NORTH

PLAN NORTH

CHECKED BY

DRAWN BY

FLOOR NUMBER

DRAWING TITLE

SHEET

NUMBER

SUBMISSION DATE

SUBMISSION STAGE

GSA PM

GSA PROJECT NO.

PROJECT

DESCRIPTION

PROJECT TITLE

BULDING NAME

ADDRESS

BUILDING NUMBER

PRIME CONTR. NO.

PRIME ORDER NO.

CONST. CONTR.

A/E

SUB A/E

CONST. CONTR. NO.

SHEET SIZE:

DATE DRAWN:

36 X 48

S H

E E

T

ID

E N

TI

FI

C A

TI

O

N

DISCIPLINE

P R

O

JE

C T

ID

E

N

TI

FI

C

A

TI

O N

B U

IL

D

IN

G

BIM FILE NAME

C O

N

TR

A C

TO

R

S R

E V

IS

IO

N B

LO

C

K G

R A

P H

IC

S

C A

LE

K

E Y

P

LA

N S

TA

M

P O

R S

E A

L D

E S

IG

N

E R

ID

E

N

TI

FI

C

A

TI

O N

O W

N E

R

ID

E N

TI

FI

C A

TI

O

N

SHEET OF SHEETS

KRUECK & SEXTON ARCHITECTS, P.C.

400 MARYLAND AVENUE, SW

WASHINGTON, DC 20024

LYNDON B. JOHNSON FEDERAL BUILDING

DC0010ZZ

DC0010_A_3-4-6-7_r2020.rvt

WSP ENGINEERING

DEPARTMENT OF EDUCATION

CONSOLIDATION PROJECT

ISSUE FOR BID

HALLIE FUTTERMAN

RENOVATION OF FLOORS 3, 4, 6, & 7 OF THE EXISTING

BUILDING TO MEET THE DEPARTMENT OF

EDUCATION’S PROGRAMMATIC REQUIREMENTS.

GS-07-P-16-UC-D-7000

47PM0520F0002

47PM0520F0002

KRUECK & SEXTON ARCHITECTS

221 W ERIE ST

CHICAGO, IL 60654 (312) 707-0056

ARCHITECT

WSP ENGINEERING

ONE PENNSYLVANIA PLAZA, SECOND FLOOR

NEW YORK, NY 10119 (212) 465-5000

MEP ENGINEER

ATELIER TEN

45 E 20TH ST, 4TH FLOOR

NEW YORK, NY 10003 (312) 386-1400

SUSTAINABILITY CONSULTANT

THRESHOLD ACOUSTICS

141 W JACKSON BLVD, SUITE 2080

CHICAGO, IL 60604 (312) 386-1400

ACOUSTIC CONSULTANT

WEST EAST

M A

TC

H

LI

N

E

GENERAL NOTESLEGEND KEY NOTES

GENERAL SERVICES ADMINISTRATION

NATIONAL CAPITAL REGION

PUBLIC BUILDING SERVICE, D.C. SERVICES DIV.

7TH & D STREET, S.W.

WASHINGTON, D.C. 20407

ISSUE

NO. DATE ISSUE

COMMUNICATIONS

VARIES, SEE DRAWINGS

01 04/23/2021 ISSUED FOR BID

/2

/2

:4

:1

P

M

TD-16-01

TELECOMMUNICATIONS DEMOLITION - LEVEL 6

04/23/21

04/20/21FT

JMM

1/16" = 1'-0"

TELECOM_LEVEL 6_FLOOR PLAN_DEMO

1. EXISTING EQUIPMENT WITHIN THIS ROOM TO REMAIN . PROTECT

IN PLACE.

(312) 787-0056

FORCADE DESIGN

3a

3a

20a

20a

F F

E E

D D

C C

B B

A A

A A

B B

C C

D D

E E

F F

3a

3a

20a

20a

A A

B B

C C

D D

E E

F F

3a

3a

20a

20a

3a

3a

20a

20a

F F

E E

D D

C C

B B

A A

A A

B B

C C

D D

E E

F F

3a

3a

20a

20a

A. REFER TO AND COORDINATE WITH ARCHITECTURAL FLOOR PLANS,

ELEVATIONS AND DETAILS FOR ADDITIONAL DETAILS PERTAINING

TO THIS SHEET.

B. REFER TO SHEET T-00-01 FOR SYMBOLS APPEARING ON THIS

SHEET.

C. WHERE EXISTING WALLS ARE DEMOLISHED, REMOVE ALL EXISTING

COMMUNICATIONS/LOW VOLTAGE DEVICES AND THEIR

ASSOCIATED CONDUITS AND WIRING BACK TO ORIGINATION.

EXISTING CABLING PASSING THROUGH DEMO AREA, NOT BEING

DEMOLISHED, SHALL BE SUPPORTED UTILIZING J-HOOK CABLE

SUPPORTS PER TIA STANDARDS.

D. EXISTING EQUIPMENT RACKS AND WALL BOARD CURRENTLY

LOCATED WITHIN THE EXISTING TELECOM ROOMS SHALL REMAIN

AS IS AND REUSED.

E. THERE IS NO SCOPE FOR WAPs. THE EXISTING WAPs AND CABLING

MUST BE FUNCTIONAL UPON SUBSTANTIAL COMPLETION. THE

CONTRACTOR CAN DETERMINE WHETHER TO REMOVE OR

PROTECT IN PLACE. ALL WORK SHALL BE COORDINATED WITH THE

GENERAL CONTRACTOR AND FINAL TESTING OF THE SYSTEM

SHALL BE COORDINATED WITH THE GOVERNMENT.

0 16' 32' 1/16"=1'-0"

SENSITIVE BUT UNCLASSIFIED (SBU) PROPERTY OF THE UNITED STATES GOVERNMENT COPYING, DISSEMINATION, OR DISTRIBUTION OF THIS DOCUMENT TO UNAUTHORIZED RECIPIENTS IS PROHIBITED.

Do not remove this notice. Properly destroy or return documents when no longer needed.

TRUE NORTH

PLAN NORTH

CHECKED BY

DRAWN BY

FLOOR NUMBER

DRAWING TITLE

SHEET

NUMBER

SUBMISSION DATE

SUBMISSION STAGE

GSA PM

GSA PROJECT NO.

PROJECT

DESCRIPTION

PROJECT TITLE

BULDING NAME

ADDRESS

BUILDING NUMBER

PRIME CONTR. NO.

PRIME ORDER NO.

CONST. CONTR.

A/E

SUB A/E

CONST. CONTR. NO.

SHEET SIZE:

DATE DRAWN:

36 X 48

S H

E E

T

ID

E N

TI

FI

C A

TI

O

N

DISCIPLINE

P R

O

JE

C T

ID

E

N

TI

FI

C

A

TI

O N

B U

IL

D

IN

G

BIM FILE NAME

C O

N

TR

A C

TO

R

S R

E V

IS

IO

N B

LO

C

K G

R A

P H

IC

S

C A

LE

K

E Y

P

LA

N S

TA

M

P O

R S

E A

L D

E S

IG

N

E R

ID

E

N

TI

FI

C

A

TI

O N

O W

N E

R

ID

E N

TI

FI

C A

TI

O

N

SHEET OF SHEETS

KRUECK & SEXTON ARCHITECTS, P.C.

400 MARYLAND AVENUE, SW

WASHINGTON, DC 20024

LYNDON B. JOHNSON FEDERAL BUILDING

DC0010ZZ

DC0010_A_3-4-6-7_r2020.rvt

WSP ENGINEERING

DEPARTMENT OF EDUCATION

CONSOLIDATION PROJECT

ISSUE FOR BID

HALLIE FUTTERMAN

RENOVATION OF FLOORS 3, 4, 6, & 7 OF THE EXISTING

BUILDING TO MEET THE DEPARTMENT OF

EDUCATION’S PROGRAMMATIC REQUIREMENTS.

GS-07-P-16-UC-D-7000

47PM0520F0002

47PM0520F0002

KRUECK & SEXTON ARCHITECTS

221 W ERIE ST

CHICAGO, IL 60654 (312) 707-0056

ARCHITECT

WSP ENGINEERING

ONE PENNSYLVANIA PLAZA, SECOND FLOOR

NEW YORK, NY 10119 (212) 465-5000

MEP ENGINEER

ATELIER TEN

45 E 20TH ST, 4TH FLOOR

NEW YORK, NY 10003 (312) 386-1400

SUSTAINABILITY CONSULTANT

THRESHOLD ACOUSTICS

141 W JACKSON BLVD, SUITE 2080

CHICAGO, IL 60604 (312) 386-1400

ACOUSTIC CONSULTANT

WEST EAST

M A

TC

H

LI

N

E

GENERAL NOTESLEGEND KEY NOTES

GENERAL SERVICES ADMINISTRATION

NATIONAL CAPITAL REGION

PUBLIC BUILDING SERVICE, D.C. SERVICES DIV.

7TH & D STREET, S.W.

WASHINGTON, D.C. 20407

ISSUE

NO. DATE ISSUE

COMMUNICATIONS

VARIES, SEE DRAWINGS

01 04/23/2021 ISSUED FOR BID

/2

/2

:4

:1

P

M

TD-17-01

TELECOMMUNICATIONS DEMOLITION - LEVEL 7

04/23/21

04/20/21FT

JMM

1/16" = 1'-0"

TELECOM_LEVEL 7_FLOOR PLAN_DEMO

1. EXISTING EQUIPMENT WITHIN THIS ROOM TO REMAIN . PROTECT

IN PLACE.

(312) 787-0056

FORCADE DESIGN

FEC

F E

C

FEC

F E

C

FEC

F E

C

FEC

F E

C

F E

C

F E

C F

E C

F E

C

FEC

F E

C

FECFEC

F E

C

FEC

FEC

F E

C

FEC

F E

C

FEC

F E

C

FEC

F E

C

F E

C

F E

C F

E C

F E

C

FEC

F E

C

FECFEC

F E

C

3a

3a

20a

20a

F F

E E

D D

C C

B B

A A

A A

B B

C C

D D

E E

F F

3a

3a

20a

20a

ZZ_T-43-05

Sim

T-43-04

Sim

ZZ_T-43-06

Sim

T-43-03

Sim

A A

B B

C C

D D

E E

F F

3a

3a

20a

20a

3a

3a

20a

20a

F F

E E

D D

C C

B B

A A

A. REFER TO AND COORDINATE WITH ARCHITECTURAL FLOOR PLANS,

ELEVATIONS AND DETAILS FOR ADDITIONAL DETAILS PERTAINING

TO THIS SHEET.

B. REFER TO SHEET T-00-01 FOR SYMBOLS APPEARING ON THIS

SHEET.

C. ALL DEVICES WITHIN ROOMS CONTAINING HARD PAN CEILINGS

SHALL HAVE CONDUITS ROUTED TO ABOVE ACCESSIBLE CEILING

SPACE IN CORRIDOR.

D. COMMUNICATIONS CONDUIT PATHWAYS SHALL NOT CONTAIN ANY

LENGTH GREATER THAN 100 FEET BETWEEN PULL POINTS. NO

SECTION OF CONDUIT SHALL CONTAIN MORE THAN TWO 90-

DEGREE BENDS, OR EQUIVALENT, BETWEEN PULL POINTS. IF

THERE IS REVERSE BEND IN THE SECTION, A PULL POINT SHALL BE

INSTALLED. PULL BOXES SHALL NOT BE USED IN LIEU OF BENDS.

THE INSIDE RADIUS OF ALL CONDUIT BENDS SHALL BE AT LEAST 10

TIMES THE INTERNAL DIAMETER. BENDS IN CONDUIT SHALL NOT

CONTAIN ANY KINKS OR OTHER DISCONTINUITIES THAT MAY HAVE

A DETRIMENTAL EFFECT ON THE CABLE SHEATH DURING

INSTALLATION. NO DAISY CHAINING OF BACK BOXES ALLOWED

UNLESS OTHERWISE NOTED.

E. ALL CABLING SHALL BE SUPPORTED ABOVE ACCESSIBLE CEILING

SPACE USING LOW-VOLTAGE SUPPORTS SIZED AT 40% FILL BASED

ON CURRENT NEEDS.

F. CABLE TRAY SHOWN SHALL BE MOUNTED AT MINIMUM OF 6" AFC

THROUGHOUT DURATION OF SCOPE.

0 8' 16' 1/8"=1'-0"

SENSITIVE BUT UNCLASSIFIED (SBU) PROPERTY OF THE UNITED STATES GOVERNMENT COPYING, DISSEMINATION, OR DISTRIBUTION OF THIS DOCUMENT TO UNAUTHORIZED RECIPIENTS IS PROHIBITED.

Do not remove this notice. Properly destroy or return documents when no longer needed.

TRUE NORTH

PLAN NORTH

CHECKED BY

DRAWN BY

FLOOR NUMBER

DRAWING TITLE

SHEET

NUMBER

SUBMISSION DATE

SUBMISSION STAGE

GSA PM

GSA PROJECT NO.

PROJECT

DESCRIPTION

PROJECT TITLE

BULDING NAME

ADDRESS

BUILDING NUMBER

PRIME CONTR. NO.

PRIME ORDER NO.

CONST. CONTR.

A/E

SUB A/E

CONST. CONTR. NO.

SHEET SIZE:

DATE DRAWN:

36 X 48

S H

E E

T

ID

E N

TI

FI

C A

TI

O

N

DISCIPLINE

P R

O

JE

C T

ID

E

N

TI

FI

C

A

TI

O N

B U

IL

D

IN

G

BIM FILE NAME

C O

N

TR

A C

TO

R

S R

E V

IS

IO

N B

LO

C

K G

R A

P H

IC

S

C A

LE

K

E Y

P

LA

N S

TA

M

P O

R S

E A

L D

E S

IG

N

E R

ID

E

N

TI

FI

C

A

TI

O N

O W

N E

R

ID

E N

TI

FI

C A

TI

O

N

SHEET OF SHEETS

KRUECK & SEXTON ARCHITECTS, P.C.

400 MARYLAND AVENUE, SW

WASHINGTON, DC 20024

LYNDON B. JOHNSON FEDERAL BUILDING

DC0010ZZ

DC0010_A_3-4-6-7_r2020.rvt

WSP ENGINEERING

DEPARTMENT OF EDUCATION

CONSOLIDATION PROJECT

ISSUE FOR BID

HALLIE FUTTERMAN

RENOVATION OF FLOORS 3, 4, 6, & 7 OF THE EXISTING

BUILDING TO MEET THE DEPARTMENT OF

EDUCATION’S PROGRAMMATIC REQUIREMENTS.

GS-07-P-16-UC-D-7000

47PM0520F0002

47PM0520F0002

KRUECK & SEXTON ARCHITECTS

221 W ERIE ST

CHICAGO, IL 60654 (312) 707-0056

ARCHITECT

WSP ENGINEERING

ONE PENNSYLVANIA PLAZA, SECOND FLOOR

NEW YORK, NY 10119 (212) 465-5000

MEP ENGINEER

ATELIER TEN

45 E 20TH ST, 4TH FLOOR

NEW YORK, NY 10003 (312) 386-1400

SUSTAINABILITY CONSULTANT

THRESHOLD ACOUSTICS

141 W JACKSON BLVD, SUITE 2080

CHICAGO, IL 60604 (312) 386-1400

ACOUSTIC CONSULTANT

WEST EAST

M A

TC

H

LI

N

E

GENERAL NOTESLEGEND KEY NOTES

GENERAL SERVICES ADMINISTRATION

NATIONAL CAPITAL REGION

PUBLIC BUILDING SERVICE, D.C. SERVICES DIV.

7TH & D STREET, S.W.

WASHINGTON, D.C. 20407

ISSUE

NO. DATE ISSUE

COMMUNICATIONS

VARIES, SEE DRAWINGS

01 04/23/2021 ISSUED FOR BID

/2

/2

:4

:1

P

M

T-13-00

TELECOMMUNICATIONS PLAN - LEVEL 3

04/23/21

04/20/21FT

JMM

1/16" = 1'-0"

TELECOM_LEVEL 3_FLOOR PLAN

REFER TO

SHEET

T-13-01

REFER TO

SHEET

T-13-02

REFER TO

SHEET

T-13-01

REFER TO

SHEET

T-13-02

(312) 787-0056

FORCADE DESIGN

3a

3a

F F

E E

D D

C C

B B

A A

A A

B B

C C

D D

E E

F F

3a

3a

TV3

T-43-01

T-43-04

TV3

1 11 1

1 1 1 1

222222

2 2

TV3

2 2 2

F1F1

F1 F1

TV3

2 2 2 2 2 2 2 2 2 2

TV3

F1F1

F1F1

T E

LE

C

O M

B

T L4

T E

LE

C

O M

B

T L3

T E

LE

C

O M

A

T L2

T E

LE

C

O M

B

T L4

12"X4"12"X4" 12"X4" 12"X4" 12"X4"

12"X4"12"X4"12"X4"12"X4"12"X4"

"X

4"

F1F1

F1F1

F1F1

F1F1

F1F1

F1F1

F1F1

F1F1

F1F1

F1F1

F1F1

F1F1

F1F1

F1F1

F1F1

F1F1

F1F1

F1F1

F1F1

F1F1

F1F1

F1F1

F1F1

F1F1

F1F1

F1F1

F1F1

F1F1

F1F1

F1F1

F1F1

F1F1

F1F1

F1F1

F1F1

F1F1

F1F1

F1F1

F1F1

F1F1

F1F1

F1F1

F1F1

F1F1

F1F1

F1F1

F1F1

F1F1

F1F1

F1F1

F1F1

F1F1

F1F1

F1F1

F1F1

F1F1

F1F1

F1F1

F1

F1

F1

F1F1

F1F1

F1F1

F1F1

F1F1

F1F1

F1F1

F1F1

F1F1

F1F1

F1F1

F1F1

F1

F1

F1 2 2 2 2 2

222 2

TV3

TV3

TV3

2 2 2

TV3

TV3

3a

3a

F F

E E

D D

C C

B B

A A

TV3

TV3

TV3

TV3

TV3

TV3TV3

TV3TV3

RESTROOM (W)

3AWMN

TELECOM

3BTL1

TELECOM

3BTL4

OFFICE

3B112

OFFICE

3B111

OFFICE

3B110

STORAGE

3BS03

ELECTRICAL

3AEL2

STAIR 1

3AST

STAIR 2

3BST1

WEST PANTRY

3APN

COPY

3A203

OFFICE

3B212

OFFICE

3B211

OFFICE

3B210

OFFICE

3A111

OFFICE

3A112

OFFICE

3A110

OFFICE

3A114

OFFICE

3A113

OFFICE

3A115

OFFICE

3A211

OFFICE

3A212

OFFICE

3A210

OFFICE

3A214

OFFICE

3A213

OFFICE

3A215

CONFERENCE

3A156

CONFERENCE

3A150

HUDDLE ROOM

3A251

HUDDLE ROOM

3A151

FOCUS

3A153

FOCUS

3A152

FOCUS

3A253

FOCUS

3A252

FOCUS

3A255

FOCUS

3A155

FOCUS

3A154

FOCUS

3A254

CONFERENCE

3B150

CONFERENCE

3B151

CONFERENCE

3B251

CONFERENCE

3B250

WEST ELEVATOR LOBBY

3BLV1

ELECTRICAL

3BEL1

ELECTRICAL

3BEL4

RESTROOM (M)

3AMEN

JANITOR

3AJA1

VESTIBULE

3A2VES

Room

ELECTRICAL

3AEL1

TELECOM

3ATL1

Room

Room

FUTURE CLOSET

3ATL2

CORRIDOR

3A201

CORRIDOR

3A101

CORRIDOR

3A180

MOTHER'S ROOM

3AMRM

CORRIDOR

3A103

CORRIDOR

3A202

OPEN OFFICE

3A245

CORRIDOR

3A102

OPEN OFFICE

3A145

VESTIBULE

3A1VES

Room

7C536

Room

7C537

Room

7C538

Room

7C539

Room

7C541

Room

7C542

Room

7C543

Room

7C544

Room

7C545

AV CLOSET

3A104

OFFICE

3A192

OFFICE

3A191

OFFICE

3A190

OFFICE

3A292

OFFICE

3A291

OFFICE

3A290

OFFICE

3A294

CONFERENCE

3A160

OFFICE

3A130

OFFICE

3A132

OFFICE

3A133

OFFICE

3A131

OFFICE

3A230

OFFICE

3A232

OFFICE

3A233

OFFICE

3A231

OFFICE

3A293

OFFICE

3A295

OFFICE

3A194

OFFICE

3A193

ASSISTANT SECRETARY'S

SUITE

3A181

CORRIDOR

3A200

CORRIDOR

3A100

OFFICE

3B113

OFFICE

3B213

CONFERENCE

3B152

CONFERENCE

3B153

CONFERENCE

3B252

CONFERENCE

3B253

OPEN OFFICE

3B245

OPEN OFFICE

3B145

CORRIDOR

3B200

1 1

1 1

2 2

4"

4"

A. REFER TO AND COORDINATE WITH ARCHITECTURAL FLOOR PLANS,

ELEVATIONS AND DETAILS FOR ADDITIONAL DETAILS PERTAINING

TO THIS SHEET.

B. REFER TO SHEET T-00-01 FOR SYMBOLS APPEARING ON THIS

SHEET.

C. ALL DEVICES WITHIN ROOMS CONTAINING HARD PAN CEILINGS

SHALL HAVE CONDUITS ROUTED TO ABOVE ACCESSIBLE CEILING

SPACE IN CORRIDOR.

D. COMMUNICATIONS CONDUIT PATHWAYS SHALL NOT CONTAIN ANY

LENGTH GREATER THAN 100 FEET BETWEEN PULL POINTS. NO

SECTION OF CONDUIT SHALL CONTAIN MORE THAN TWO 90-

DEGREE BENDS, OR EQUIVALENT, BETWEEN PULL POINTS. IF

THERE IS REVERSE BEND IN THE SECTION, A PULL POINT SHALL BE

INSTALLED. PULL BOXES SHALL NOT BE USED IN LIEU OF BENDS.

THE INSIDE RADIUS OF ALL CONDUIT BENDS SHALL BE AT LEAST 10

TIMES THE INTERNAL DIAMETER. BENDS IN CONDUIT SHALL NOT

CONTAIN ANY KINKS OR OTHER DISCONTINUITIES THAT MAY HAVE

A DETRIMENTAL EFFECT ON THE CABLE SHEATH DURING

INSTALLATION. NO DAISY CHAINING OF BACK BOXES ALLOWED

UNLESS OTHERWISE NOTED.

E. ALL CABLING SHALL BE SUPPORTED ABOVE ACCESSIBLE CEILING

SPACE USING LOW-VOLTAGE SUPPORTS SIZED AT 40% FILL BASED

ON CURRENT NEEDS.

F. BACK BOXES LOCATED IN FABRIC WALL AREAS SHALL BE

PROVIDED WITH BACK BOX EXTENSIONS TO PREVENT CRUSHING

OF WALL SURFACES.

0 8' 16' 1/8"=1'-0"

SENSITIVE BUT UNCLASSIFIED (SBU) PROPERTY OF THE UNITED STATES GOVERNMENT COPYING, DISSEMINATION, OR DISTRIBUTION OF THIS DOCUMENT TO UNAUTHORIZED RECIPIENTS IS PROHIBITED.

Do not remove this notice. Properly destroy or return documents when no longer needed.

TRUE NORTH

PLAN NORTH

CHECKED BY

DRAWN BY

FLOOR NUMBER

DRAWING TITLE

SHEET

NUMBER

SUBMISSION DATE

SUBMISSION STAGE

GSA PM

GSA PROJECT NO.

PROJECT

DESCRIPTION

PROJECT TITLE

BULDING NAME

ADDRESS

BUILDING NUMBER

PRIME CONTR. NO.

PRIME ORDER NO.

CONST. CONTR.

A/E

SUB A/E

CONST. CONTR. NO.

SHEET SIZE:

DATE DRAWN:

36 X 48

S H

E E

T

ID

E N

TI

FI

C A

TI

O

N

DISCIPLINE

P R

O

JE

C T

ID

E

N

TI

FI

C

A

TI

O N

B U

IL

D

IN

G

BIM FILE NAME

C O

N

TR

A C

TO

R

S R

E V

IS

IO

N B

LO

C

K G

R A

P H

IC

S

C A

LE

K

E Y

P

LA

N S

TA

M

P O

R S

E A

L D

E S

IG

N

E R

ID

E

N

TI

FI

C

A

TI

O N

O W

N E

R

ID

E N

TI

FI

C A

TI

O

N

SHEET OF SHEETS

KRUECK & SEXTON ARCHITECTS, P.C.

400 MARYLAND AVENUE, SW

WASHINGTON, DC 20024

LYNDON B. JOHNSON FEDERAL BUILDING

DC0010ZZ

DC0010_A_3-4-6-7_r2020.rvt

WSP ENGINEERING

DEPARTMENT OF EDUCATION

CONSOLIDATION PROJECT

ISSUE FOR BID

HALLIE FUTTERMAN

RENOVATION OF FLOORS 3, 4, 6, & 7 OF THE EXISTING

BUILDING TO MEET THE DEPARTMENT OF

EDUCATION’S PROGRAMMATIC REQUIREMENTS.

GS-07-P-16-UC-D-7000

47PM0520F0002

47PM0520F0002

KRUECK & SEXTON ARCHITECTS

221 W ERIE ST

CHICAGO, IL 60654 (312) 707-0056

ARCHITECT

WSP ENGINEERING

ONE PENNSYLVANIA PLAZA, SECOND FLOOR

NEW YORK, NY 10119 (212) 465-5000

MEP ENGINEER

ATELIER TEN

45 E 20TH ST, 4TH FLOOR

NEW YORK, NY 10003 (312) 386-1400

SUSTAINABILITY CONSULTANT

THRESHOLD ACOUSTICS

141 W JACKSON BLVD, SUITE 2080

CHICAGO, IL 60604 (312) 386-1400

ACOUSTIC CONSULTANT

WEST EAST

M A

TC

H

LI

N

E

GENERAL NOTESLEGEND KEY NOTES

GENERAL SERVICES ADMINISTRATION

NATIONAL CAPITAL REGION

PUBLIC BUILDING SERVICE, D.C. SERVICES DIV.

7TH & D STREET, S.W.

WASHINGTON, D.C. 20407

ISSUE

NO. DATE ISSUE

COMMUNICATIONS

VARIES, SEE DRAWINGS

01 04/23/2021 ISSUED FOR BID

/2

/2

:4

:4

P

M

T-13-01

TELECOMMUNICATIONS PLAN - LEVEL 3 - WEST

04/23/21

04/20/21FT

JMM

1/8" = 1'-0"

TELECOM_LEVEL 3_FLOOR PLAN__WEST

1 1

1. PROVIDE (3) 4" CONDUITS AS SHOWN.

2. REFER TO SHEET T-50-03 FOR TYPICAL CONDUIT PATHWAY

DETAILS TO FURNITURE.

2 2 2 2 2 2 2 2 2 2

2222222222

(312) 787-0056

FORCADE DESIGN

20a

20a

F F

E E

D D

C C

B B

A A

A A

B B

C C

D D

E E

F F

20a

20a

T-43-03

T-43-02

2 2

2 2

2 2

2 2

2 2 2 2 2 2 2 2 2 2

TV3

TV3

21 1

1 1111

1 1 1 1 1

2 2 2 2 2 2

2 2 2 2 2

F1F1

F1 F1

TV3

TV3

TV3

TV3

2 2 2

2 2

T E

LE

C

O M

B

T L4

T E

LE

C

O M

B

T L3

T E

LE

C

O M

B

T L3

T E

LE

C

O M

C

T L

12"X4" 12"X4" 12"X4" 12"X4" 12"X4"

12"X4"12"X4"12"X4"12"X4"12"X4"

"X

4"

F1F1

F1F1

F1F1

F1F1

F1F1

F1F1

F1F1

F1F1

F1F1

F1F1

F1F1

F1F1

F1F1

F1F1

F1F1

F1F1

2 2 2 2

2 2 2 2

TV3

TV3

TV3

TV3

TV3

2 2 2 2 2

20a

20a

F F

E E

D D

C C

B B

A A

TV3TV3 TV3TV3 TV3TV3

TV3TV3TV3TV3TV3TV3

TV3

TV3

TV3

2 2 22

1 1

1 1

2 2 22

2 2 22

2 2

2 2

2 2

2 2

2 2

2 2

RESTROOM (W)

3CWMN

ELECTRICAL

3BEL2

ELECTRICAL

3BEL3

OFFICE

3B114

OFFICE

3B113

OFFICE

3B115

OFFICE

3B116

Room

FREIGHT ELEV. LOBBY

3BFLV

STAIR 4

3CST

STAIR 3

3BST2

EAST PANTRY

3BPN

COPY

3B102

OFFICE

3B214

OFFICE

3B213

OFFICE

3B215

OFFICE

3B216

OFFICE

3C111

OFFICE

3C112

OFFICE

3C110

OFFICE

3C114

OFFICE

3C113

OFFICE

3C115

OFFICE

3C211

OFFICE

3C212

OFFICE

3C210

OFFICE

3C214

OFFICE

3C213

OFFICE

3C215

CORRIDOR

3C180

CONFERENCE

3C156

CONFERENCE

3C150

HUDDLE ROOM

3C251

HUDDLE ROOM

3C151

FOCUS

3C153

FOCUS

3C152

FOCUS

3C253

FOCUS

3C252

FOCUS

3C255

FOCUS

3C155

FOCUS

3C154

FOCUS

3C254

CONFERENCE

3C256

CONFERENCE

3B152

CONFERENCE

3B153 CONFERENCE

3B155

CONFERENCE

3B154

CONFERENCE

3B252

CONFERENCE

3B253

CONFERENCE

3B255

CONFERENCE

3B254

CORRIDOR

3B101

TELECOM

3BTL2

TELECOM

3BTL3

FOCUS ROOM

3C257

RESTROOM (M)

3CMEN

JANITOR

3CJA

ELECTRICAL

3CEL2

Room

TELECOM

3CTL2

TELECOM

3CTL1

ELECTRICAL

3CEL1

EAST ELEVATOR LOBBY

3BLV2

VESTIBULE

3C2VES

CORRIDOR

3C201

CORRIDOR

3C101

CORRIDOR

3C102

CORRIDOR

3B100

OPEN OFFICE

3B245

OPEN OFFICE

3C145

OPEN OFFICE

3C245

CORRIDOR

3C200

OPEN OFFICE

3B145

CORRIDOR

3B200

VESTIBULE

3C1VES

Room

7C535 Room

7C546

Room

7C547

Room

7C548

Room

7C549

Room

7C550

Room

7C551

Room

7C552

Room

7C553 Room

7C554

Room

7C555

CORRIDOR

3C100

OFFICE

3C193

OFFICE

3C192

OFFICE

3C191

OFFICE

3C190

OFFICE

3C194

OFFICE

3C293

OFFICE

3C292

OFFICE

3C291

OFFICE

3C290

OFFICE

3C294

OFFICE

3C295

ASSISTANT SECRETARY'S

SUITE

3C181

CONFERENCE

3C160

OFFICE

3C284

OFFICE

3C240

OFFICE

3C285

OFFICE

3C243

OFFICE

3B230

OFFICE

3B232

OFFICE

3B231

OFFICE

3B233

OFFICE

3C288

OFFICE

3C286

OFFICE

3C287

OFFICE

3C289

OFFICE

3C238

OFFICE

3C239

OFFICE

3C241

OFFICE

3C242

OFFICE

3B237

OFFICE

3B236

OFFICE

3B241

OFFICE

3B240

OFFICE

3B234

OFFICE

3B235

OFFICE

3B238

OFFICE

3B239

OFFICE

3C184

OFFICE

3C140

OFFICE

3C185

OFFICE

3C143

OFFICE

3C138

OFFICE

3C139

OFFICE

3C141

OFFICE

3C142

OFFICE

3C188

OFFICE

3C186

OFFICE

3C187

OFFICE

3C189

OFFICE

3B130

OFFICE

3B132

OFFICE

3B131

OFFICE

3B133

OFFICE

3B137

OFFICE

3B136

OFFICE

3B141

OFFICE

3B140

OFFICE

3B134

OFFICE

3B135

OFFICE

3B138

OFFICE

3B139

OFFICE

3C195

OFFICE

3C196

COLLABORATION

3C271

COLLABORATION

3B270

COLLABORATION

3B271

COLLABORATION

3B170

COLLABORATION

3B171

COLLABORATION

3C171

OFFICE

3C136

OFFICE

3C134

OFFICE

3C137

OFFICE

3C135

OFFICE

3C131

OFFICE

3C130

OFFICE

3C133

OFFICE

3C132

COLLABORATION

3C170

OFFICE

3C236

OFFICE

3C234

OFFICE

3C237

OFFICE

3C235

OFFICE

3C231

OFFICE

3C230

OFFICE

3C233

OFFICE

3C232

COLLABORATION

3C270

FOCUS

3C161

FOCUS

3C261

1 11 1

A. REFER TO AND COORDINATE WITH ARCHITECTURAL FLOOR PLANS,

ELEVATIONS AND DETAILS FOR ADDITIONAL DETAILS PERTAINING

TO THIS SHEET.

B. REFER TO SHEET T-00-01 FOR SYMBOLS APPEARING ON THIS

SHEET.

C. ALL DEVICES WITHIN ROOMS CONTAINING HARD PAN CEILINGS

SHALL HAVE CONDUITS ROUTED TO ABOVE ACCESSIBLE CEILING

SPACE IN CORRIDOR.

D. COMMUNICATIONS CONDUIT PATHWAYS SHALL NOT CONTAIN ANY

LENGTH GREATER THAN 100 FEET BETWEEN PULL POINTS. NO

SECTION OF CONDUIT SHALL CONTAIN MORE THAN TWO 90-

DEGREE BENDS, OR EQUIVALENT, BETWEEN PULL POINTS. IF

THERE IS REVERSE BEND IN THE SECTION, A PULL POINT SHALL BE

INSTALLED. PULL BOXES SHALL NOT BE USED IN LIEU OF BENDS.

THE INSIDE RADIUS OF ALL CONDUIT BENDS SHALL BE AT LEAST 10

TIMES THE INTERNAL DIAMETER. BENDS IN CONDUIT SHALL NOT

CONTAIN ANY KINKS OR OTHER DISCONTINUITIES THAT MAY HAVE

A DETRIMENTAL EFFECT ON THE CABLE SHEATH DURING

INSTALLATION. NO DAISY CHAINING OF BACK BOXES ALLOWED

UNLESS OTHERWISE NOTED.

E. ALL CABLING SHALL BE SUPPORTED ABOVE ACCESSIBLE CEILING

SPACE USING LOW-VOLTAGE SUPPORTS SIZED AT 40% FILL BASED

ON CURRENT NEEDS.

F. BACK BOXES LOCATED IN FABRIC WALL AREAS SHALL BE

PROVIDED WITH BACK BOX EXTENSIONS TO PREVENT CRUSHING

OF WALL SURFACES.

0 8' 16' 1/8"=1'-0"

SENSITIVE BUT UNCLASSIFIED (SBU) PROPERTY OF THE UNITED STATES GOVERNMENT COPYING, DISSEMINATION, OR DISTRIBUTION OF THIS DOCUMENT TO UNAUTHORIZED RECIPIENTS IS PROHIBITED.

Do not remove this notice. Properly destroy or return documents when no longer needed.

TRUE NORTH

PLAN NORTH

CHECKED BY

DRAWN BY

FLOOR NUMBER

DRAWING TITLE

SHEET

NUMBER

SUBMISSION DATE

SUBMISSION STAGE

GSA PM

GSA PROJECT NO.

PROJECT

DESCRIPTION

PROJECT TITLE

BULDING NAME

ADDRESS

BUILDING NUMBER

PRIME CONTR. NO.

PRIME ORDER NO.

CONST. CONTR.

A/E

SUB A/E

CONST. CONTR. NO.

SHEET SIZE:

DATE DRAWN:

36 X 48

S H

E E

T

ID

E N

TI

FI

C A

TI

O

N

DISCIPLINE

P R

O

JE

C T

ID

E

N

TI

FI

C

A

TI

O N

B U

IL

D

IN

G

BIM FILE NAME

C O

N

TR

A C

TO

R

S R

E V

IS

IO

N B

LO

C

K G

R A

P H

IC

S

C A

LE

K

E Y

P

LA

N S

TA

M

P O

R S

E A

L D

E S

IG

N

E R

ID

E

N

TI

FI

C

A

TI

O N

O W

N E

R

ID

E N

TI

FI

C A

TI

O

N

SHEET OF SHEETS

KRUECK & SEXTON ARCHITECTS, P.C.

400 MARYLAND AVENUE, SW

WASHINGTON, DC 20024

LYNDON B. JOHNSON FEDERAL BUILDING

DC0010ZZ

DC0010_A_3-4-6-7_r2020.rvt

WSP ENGINEERING

DEPARTMENT OF EDUCATION

CONSOLIDATION PROJECT

ISSUE FOR BID

HALLIE FUTTERMAN

RENOVATION OF FLOORS 3, 4, 6, & 7 OF THE EXISTING

BUILDING TO MEET THE DEPARTMENT OF

EDUCATION’S PROGRAMMATIC REQUIREMENTS.

GS-07-P-16-UC-D-7000

47PM0520F0002

47PM0520F0002

KRUECK & SEXTON ARCHITECTS

221 W ERIE ST

CHICAGO, IL 60654 (312) 707-0056

ARCHITECT

WSP ENGINEERING

ONE PENNSYLVANIA PLAZA, SECOND FLOOR

NEW YORK, NY 10119 (212) 465-5000

MEP ENGINEER

ATELIER TEN

45 E 20TH ST, 4TH FLOOR

NEW YORK, NY 10003 (312) 386-1400

SUSTAINABILITY CONSULTANT

THRESHOLD ACOUSTICS

141 W JACKSON BLVD, SUITE 2080

CHICAGO, IL 60604 (312) 386-1400

ACOUSTIC CONSULTANT

WEST EAST

M A

TC

H

LI

N

E

GENERAL NOTESLEGEND KEY NOTES

GENERAL SERVICES ADMINISTRATION

NATIONAL CAPITAL REGION

PUBLIC BUILDING SERVICE, D.C. SERVICES DIV.

7TH & D STREET, S.W.

WASHINGTON, D.C. 20407

ISSUE

NO. DATE ISSUE

COMMUNICATIONS

VARIES, SEE DRAWINGS

01 04/23/2021 ISSUED FOR BID

/2

/2

:4

:0

P

M

T-13-02

TELECOMMUNICATIONS PLAN - LEVEL 3 - EAST

04/23/21

04/20/21FT

JMM

1/8" = 1'-0"

TELECOM_LEVEL 3_FLOOR PLAN__EAST

2 2

1. PROVIDE (3) 4" CONDUITS AS SHOWN.

2. REFER TO SHEET T-50-03 FOR TYPICAL CONDUIT PATHWAY

DETAILS TO FURNITURE.

(312) 787-0056

FORCADE DESIGN

F E

C

FEC

F E

C

FEC

F E

C

FEC

F E

C

F E

C

F E

C F

E C

F E

C

FEC

F E

C

FECFEC

F E

C

J

J

J J J J J J J J

J J J J J J JJ

FEC

FEC

F E

C

FEC

F E

C

FEC

F E

C

FEC

F E

C

F E

C

F E

C F

E C

F E

C

FEC

F E

C

FECFEC

F E

C

3a

3a

20a

20a

F F

E E

D D

C C

B B

A A

A A

B B

C C

D D

E E

F F

3a

3a

20a

20a

TV3

TV3TV3

TV3

TV3

TV3

TV3 TV3

TV3

TV3

ZZ_T-43-05

Sim

T-43-04

Sim

ZZ_T-43-06

Sim

T-43-03

Sim

A A

B B

C C

D D

E E

F F

3a

3a

20a

20a

3a

3a

20a

20a

F F

E E

D D

C C

B B

A A

A. REFER TO AND COORDINATE WITH ARCHITECTURAL FLOOR PLANS,

ELEVATIONS AND DETAILS FOR ADDITIONAL DETAILS PERTAINING

TO THIS SHEET.

B. REFER TO SHEET T-00-01 FOR SYMBOLS APPEARING ON THIS

SHEET.

C. ALL DEVICES WITHIN ROOMS CONTAINING HARD PAN CEILINGS

SHALL HAVE CONDUITS ROUTED TO ABOVE ACCESSIBLE CEILING

SPACE IN CORRIDOR.

D. COMMUNICATIONS CONDUIT PATHWAYS SHALL NOT CONTAIN ANY

LENGTH GREATER THAN 100 FEET BETWEEN PULL POINTS. NO

SECTION OF CONDUIT SHALL CONTAIN MORE THAN TWO 90-

DEGREE BENDS, OR EQUIVALENT, BETWEEN PULL POINTS. IF

THERE IS REVERSE BEND IN THE SECTION, A PULL POINT SHALL BE

INSTALLED. PULL BOXES SHALL NOT BE USED IN LIEU OF BENDS.

THE INSIDE RADIUS OF ALL CONDUIT BENDS SHALL BE AT LEAST 10

TIMES THE INTERNAL DIAMETER. BENDS IN CONDUIT SHALL NOT

CONTAIN ANY KINKS OR OTHER DISCONTINUITIES THAT MAY HAVE

A DETRIMENTAL EFFECT ON THE CABLE SHEATH DURING

INSTALLATION. NO DAISY CHAINING OF BACK BOXES ALLOWED

UNLESS OTHERWISE NOTED.

E. ALL CABLING SHALL BE SUPPORTED ABOVE ACCESSIBLE CEILING

SPACE USING LOW-VOLTAGE SUPPORTS SIZED AT 40% FILL BASED

ON CURRENT NEEDS.

F. CABLE TRAY SHOWN SHALL BE MOUNTED AT MINIMUM OF 6" AFC

THROUGHOUT DURATION OF SCOPE.

0 16' 32' 1/16"=1'-0"

SENSITIVE BUT UNCLASSIFIED (SBU) PROPERTY OF THE UNITED STATES GOVERNMENT COPYING, DISSEMINATION, OR DISTRIBUTION OF THIS DOCUMENT TO UNAUTHORIZED RECIPIENTS IS PROHIBITED.

Do not remove this notice. Properly destroy or return documents when no longer needed.

TRUE NORTH

PLAN NORTH

CHECKED BY

DRAWN BY

FLOOR NUMBER

DRAWING TITLE

SHEET

NUMBER

SUBMISSION DATE

SUBMISSION STAGE

GSA PM

GSA PROJECT NO.

PROJECT

DESCRIPTION

PROJECT TITLE

BULDING NAME

ADDRESS

BUILDING NUMBER

PRIME CONTR. NO.

PRIME ORDER NO.

CONST. CONTR.

A/E

SUB A/E

CONST. CONTR. NO.

SHEET SIZE:

DATE DRAWN:

36 X 48

S H

E E

T

ID

E N

TI

FI

C A

TI

O

N

DISCIPLINE

P R

O

JE

C T

ID

E

N

TI

FI

C

A

TI

O N

B U

IL

D

IN

G

BIM FILE NAME

C O

N

TR

A C

TO

R

S R

E V

IS

IO

N B

LO

C

K G

R A

P H

IC

S

C A

LE

K

E Y

P

LA

N S

TA

M

P O

R S

E A

L D

E S

IG

N

E R

ID

E

N

TI

FI

C

A

TI

O N

O W

N E

R

ID

E N

TI

FI

C A

TI

O

N

SHEET OF SHEETS

KRUECK & SEXTON ARCHITECTS, P.C.

400 MARYLAND AVENUE, SW

WASHINGTON, DC 20024

LYNDON B. JOHNSON FEDERAL BUILDING

DC0010ZZ

DC0010_A_3-4-6-7_r2020.rvt

WSP ENGINEERING

DEPARTMENT OF EDUCATION

CONSOLIDATION PROJECT

ISSUE FOR BID

HALLIE FUTTERMAN

RENOVATION OF FLOORS 3, 4, 6, & 7 OF THE EXISTING

BUILDING TO MEET THE DEPARTMENT OF

EDUCATION’S PROGRAMMATIC REQUIREMENTS.

GS-07-P-16-UC-D-7000

47PM0520F0002

47PM0520F0002

KRUECK & SEXTON ARCHITECTS

221 W ERIE ST

CHICAGO, IL 60654 (312) 707-0056

ARCHITECT

WSP ENGINEERING

ONE PENNSYLVANIA PLAZA, SECOND FLOOR

NEW YORK, NY 10119 (212) 465-5000

MEP ENGINEER

ATELIER TEN

45 E 20TH ST, 4TH FLOOR

NEW YORK, NY 10003 (312) 386-1400

SUSTAINABILITY CONSULTANT

THRESHOLD ACOUSTICS

141 W JACKSON BLVD, SUITE 2080

CHICAGO, IL 60604 (312) 386-1400

ACOUSTIC CONSULTANT

WEST EAST

M A

TC

H

LI

N

E

GENERAL NOTESLEGEND KEY NOTES

GENERAL SERVICES ADMINISTRATION

NATIONAL CAPITAL REGION

PUBLIC BUILDING SERVICE, D.C. SERVICES DIV.

7TH & D STREET, S.W.

WASHINGTON, D.C. 20407

ISSUE

NO. DATE ISSUE

COMMUNICATIONS

VARIES, SEE DRAWINGS

01 04/23/2021 ISSUED FOR BID

/2

/2

:4

:0

P

M

T-14-00

TELECOMMUNICATIONS PLAN - LEVEL 4

04/23/21

04/20/21FT

JMM

1/16" = 1'-0"

TELECOM_LEVEL 4_FLOOR PLAN

REFER TO

SHEET

T-14-01

REFER TO

SHEET

T-14-02

REFER TO

SHEET

T-14-01

REFER TO

SHEET

T-14-02

(312) 787-0056

FORCADE DESIGN

3a

3a

F F

E E

D D

C C

B B

A A

A A

B B

C C

D D

E E

F F

3a

3a

F1 F1

2 2

2 2

2 2

2 2

2 2 2

2 2 2 2 2 2

2 2 2 2 2 2

2 2 2

2 2 2 2

F1

F1

F1

F1

TV3

TV3

TV3

TV3

TV3

1 111

T E

LE

C

O M

B

T L4

T E

LE

C

O M

B

T L3

12"X4"12"X4" 12"X4" 12"X4" 12"X4"

12"X4"12"X4"12"X4"12"X4"12"X4"

"X

4" 2

1 1

2 2

2 2

F1 F1

F1 F1

F1 F1

F1 F1

F1 F1

F1 F1

F1 F1

F1 F1

F1 F1

F1 F1

F1 F1

F1 F1

F1 F1

F1 F1

F1 F1

F1 F1

F1 F1

F1 F1

F1 F1

F1 F1

F1 F1

F1 F1

F1 F1

F1

F1

F1

F1 F1

F1 F1

F1 F1

F1 F1

F1 F1

F1 F1

F1 F1

F1 F1

F1 F1

F1 F1

F1 F1

F1 F1

T-44-04

F1 F1

F1 F1

F1 F1

F1 F1

F1 F1

F1 F1

F1 F1

F1 F1

F1 F1

F1 F1

F1 F1

F1 F1

F1 F1

F1 F1

F1 F1

F1 F1

F1

F1

F1

F1 F1

F1 F1

F1 F1

F1 F1

F1 F1

F1 F1

F1 F1

F1 F1

F1 F1

F1 F1

F1 F1

F1 F1

2 2 2 2 2 2

2 2 2 2 2 2

T-44-01

TV3

TV3

TV3

T E

LE

C

O M

A

T L2

T E

LE

C

O M

B

T L4

TV3

TV3

3a

3a

F F

E E

D D

C C

B B

A A

2 2 2

RESTROOM (W)

4AWMN

TELECOM

4BTL1

TELECOM

4BTL4

OFFICE

4B112

OFFICE

4B111

OFFICE

4B110Room

STORAGE

4BS03

ELECTRICAL

4AEL2

STAIR 1

4AST

STAIR 2

4BST1

WEST PANTRY

4APN

COPY

4A203

OFFICE

4B212

OFFICE

4B211

OFFICE

4B210

OFFICE

4A111

OFFICE

4A112

OFFICE

4A110

OFFICE

4A114

OFFICE

4A113

OFFICE

4A115

OFFICE

4A211

OFFICE

4A212

OFFICE

4A210

OFFICE

4A214

OFFICE

4A213

OFFICE

4A215

CONFERENCE

4A156

CONFERENCE

4A150

HUDDLE ROOM

4A251

HUDDLE ROOM

4A151

FOCUS

4A153

FOCUS

4A152

FOCUS

4A253

FOCUS

4A252

FOCUS

4A255

FOCUS

4A155

FOCUS

4A154

FOCUS

4A254

CONFERENCE

4B150

CONFERENCE

4B151

CONFERENCE

4B251

CONFERENCE

4B250

ELECTRICAL

4BEL1

ELECTRICAL

4BEL4

Room

4BS01

Room

Room

4BS02

RESTROOM (M)

4AMEN

JANITOR

4AJA1

MOTHER'S ROOM

4AMRM

Room

ELECTRICAL

4AEL1

TELECOM

4ATL1

Room

Room

Room

FUTURE CLOSET

4ATL2

OFFICE

4A133

OFFICE

4A132

OFFICE

4A131

OFFICE

4A130

OFFICE

4A233

OFFICE

4A232

OFFICE

4A231

OFFICE

4A230

OFFICE

4A192

OFFICE

4A191

OFFICE

4A190

OFFICE

4A292

OFFICE

4A291

OFFICE

4A290

OFFICE

4A293

OFFICE

4A294

WEST ELEVATOR LOBBY

4BLV1

CORRIDOR

4B200

COLLABORATION

4A170

COLLABORATION

4A270

OFFICE

4A237

OFFICE

4A236

OFFICE

4A235

OFFICE

4A234

COLLABORATION

4A271

OFFICE

4A136

OFFICE

4A135

OFFICE

4A134

COLLABORATION

4A171

ASSISTANT SECRETARY'S

SUITE

4A181

CONFERENCE

4A160

CORRIDOR

4A101

OPEN OFFICE

4A245

OPEN OFFICE

4A246

OPEN OFFICE

4A145

OPEN OFFICE

4A146

CORRIDOR

4A102

CORRIDOR

4A103

CORRIDOR

4A202

VESTIBULE

4A2VES

CORRIDOR

4A200

OFFICE

4A295

OFFICE

4A194

OFFICE

4A193

CORRIDOR

4A180

CORRIDOR

4A201

AV CLOSET

4A104

VESTIBULE

4A1VES

CORRIDOR

4A100

OFFICE

4B113

OFFICE

4B213

CONFERENCE

4B152

CONFERENCE

4B153

CONFERENCE

4B252

CONFERENCE

4B253

OPEN OFFICE

4B245

OPEN OFFICE

4B145

CORRIDOR

4B100

ASSISTANT SECRETARY'S

SUITE

4A181

TV3

TV3

TV3

TV3

TV3

OFFICE

4A137

4"

4"

A. REFER TO AND COORDINATE WITH ARCHITECTURAL FLOOR PLANS,

ELEVATIONS AND DETAILS FOR ADDITIONAL DETAILS PERTAINING

TO THIS SHEET.

B. REFER TO SHEET T-00-01 FOR SYMBOLS APPEARING ON THIS

SHEET.

C. ALL DEVICES WITHIN ROOMS CONTAINING HARD PAN CEILINGS

SHALL HAVE CONDUITS ROUTED TO ABOVE ACCESSIBLE CEILING

SPACE IN CORRIDOR.

D. COMMUNICATIONS CONDUIT PATHWAYS SHALL NOT CONTAIN ANY

LENGTH GREATER THAN 100 FEET BETWEEN PULL POINTS. NO

SECTION OF CONDUIT SHALL CONTAIN MORE THAN TWO 90-

DEGREE BENDS, OR EQUIVALENT, BETWEEN PULL POINTS. IF

THERE IS REVERSE BEND IN THE SECTION, A PULL POINT SHALL BE

INSTALLED. PULL BOXES SHALL NOT BE USED IN LIEU OF BENDS.

THE INSIDE RADIUS OF ALL CONDUIT BENDS SHALL BE AT LEAST 10

TIMES THE INTERNAL DIAMETER. BENDS IN CONDUIT SHALL NOT

CONTAIN ANY KINKS OR OTHER DISCONTINUITIES THAT MAY HAVE

A DETRIMENTAL EFFECT ON THE CABLE SHEATH DURING

INSTALLATION. NO DAISY CHAINING OF BACK BOXES ALLOWED

UNLESS OTHERWISE NOTED.

E. ALL CABLING SHALL BE SUPPORTED ABOVE ACCESSIBLE CEILING

SPACE USING LOW-VOLTAGE SUPPORTS SIZED AT 40% FILL BASED

ON CURRENT NEEDS.

F. BACK BOXES LOCATED IN FABRIC WALL AREAS SHALL BE

PROVIDED WITH BACK BOX EXTENSIONS TO PREVENT CRUSHING

OF WALL SURFACES.

0 8' 16' 1/8"=1'-0"

SENSITIVE BUT UNCLASSIFIED (SBU) PROPERTY OF THE UNITED STATES GOVERNMENT COPYING, DISSEMINATION, OR DISTRIBUTION OF THIS DOCUMENT TO UNAUTHORIZED RECIPIENTS IS PROHIBITED.

Do not remove this notice. Properly destroy or return documents when no longer needed.

TRUE NORTH

PLAN NORTH

CHECKED BY

DRAWN BY

FLOOR NUMBER

DRAWING TITLE

SHEET

NUMBER

SUBMISSION DATE

SUBMISSION STAGE

GSA PM

GSA PROJECT NO.

PROJECT

DESCRIPTION

PROJECT TITLE

BULDING NAME

ADDRESS

BUILDING NUMBER

PRIME CONTR. NO.

PRIME ORDER NO.

CONST. CONTR.

A/E

SUB A/E

CONST. CONTR. NO.

SHEET SIZE:

DATE DRAWN:

36 X 48

S H

E E

T

ID

E N

TI

FI

C A

TI

O

N

DISCIPLINE

P R

O

JE

C T

ID

E

N

TI

FI

C

A

TI

O N

B U

IL

D

IN

G

BIM FILE NAME

C O

N

TR

A C

TO

R

S R

E V

IS

IO

N B

LO

C

K G

R A

P H

IC

S

C A

LE

K

E Y

P

LA

N S

TA

M

P O

R S

E A

L D

E S

IG

N

E R

ID

E

N

TI

FI

C

A

TI

O N

O W

N E

R

ID

E N

TI

FI

C A

TI

O

N

SHEET OF SHEETS

KRUECK & SEXTON ARCHITECTS, P.C.

400 MARYLAND AVENUE, SW

WASHINGTON, DC 20024

LYNDON B. JOHNSON FEDERAL BUILDING

DC0010ZZ

DC0010_A_3-4-6-7_r2020.rvt

WSP ENGINEERING

DEPARTMENT OF EDUCATION

CONSOLIDATION PROJECT

ISSUE FOR BID

HALLIE FUTTERMAN

RENOVATION OF FLOORS 3, 4, 6, & 7 OF THE EXISTING

BUILDING TO MEET THE DEPARTMENT OF

EDUCATION’S PROGRAMMATIC REQUIREMENTS.

GS-07-P-16-UC-D-7000

47PM0520F0002

47PM0520F0002

KRUECK & SEXTON ARCHITECTS

221 W ERIE ST

CHICAGO, IL 60654 (312) 707-0056

ARCHITECT

WSP ENGINEERING

ONE PENNSYLVANIA PLAZA, SECOND FLOOR

NEW YORK, NY 10119 (212) 465-5000

MEP ENGINEER

ATELIER TEN

45 E 20TH ST, 4TH FLOOR

NEW YORK, NY 10003 (312) 386-1400

SUSTAINABILITY CONSULTANT

THRESHOLD ACOUSTICS

141 W JACKSON BLVD, SUITE 2080

CHICAGO, IL 60604 (312) 386-1400

ACOUSTIC CONSULTANT

WEST EAST

M A

TC

H

LI

N

E

GENERAL NOTESLEGEND KEY NOTES

GENERAL SERVICES ADMINISTRATION

NATIONAL CAPITAL REGION

PUBLIC BUILDING SERVICE, D.C. SERVICES DIV.

7TH & D STREET, S.W.

WASHINGTON, D.C. 20407

ISSUE

NO. DATE ISSUE

COMMUNICATIONS

VARIES, SEE DRAWINGS

01 04/23/2021 ISSUED FOR BID

/2

/2

:4

:1

P

M

T-14-01

TELECOMMUNICATIONS PLAN - LEVEL 4 - WEST

04/23/21

04/20/21FT

JMM

1/8" = 1'-0"

TELECOM_LEVEL 4_FLOOR PLAN__WEST

1 1

2 2 2 2 2 2 2 2 2 2

2222222222

1. PROVIDE (3) 4" CONDUITS AS SHOWN.

2. REFER TO SHEET T-50-03 FOR TYPICAL CONDUIT PATHWAY

DETAILS TO FURNITURE.

(312) 787-0056

FORCADE DESIGN

20a

20a

F F

E E

D D

C C

B B

A A

A A

B B

C C

D D

E E

F F

20a

20a

2 2

2 2

2 2 2 2

2 2 2 2 2 2 2 2 2

2 2 2

222222

TV3

TV3 2

TV3

TV3

TV3

F1

F1

F1

F1

1 1 1 1

T E

LE

C

O M

B

T L4

T E

LE

C

O M

B

T L3

12"X4" 12"X4" 12"X4" 12"X4" 12"X4"

12"X4"12"X4"12"X4"12"X4"12"X4"

"X

4"

TV3

1 1

2 2

F1 F1

F1 F1

F1 F1

F1 F1

F1 F1

F1 F1

F1 F1

F1 F1

F1 F1

F1 F1

F1 F1

F1 F1

F1

F1

F1

F1 F1

F1 F1

F1 F1

F1 F1

F1 F1

F1 F1

F1 F1

F1 F1

F1 F1

F1 F1

F1 F1

F1 F1

F1 F1

F1 F1

F1 F1

F1 F1

F1 F1

F1 F1

F1 F1

F1 F1

F1 F1

F1 F1

F1 F1

F1 F1

T-44-03

F1 F1

F1 F1

F1 F1

F1 F1

F1 F1

F1 F1

F1 F1

F1 F1

F1 F1

F1 F1

F1 F1

F1 F1

F1

F1

F1

F1 F1

F1 F1

F1 F1

F1 F1

F1 F1

F1 F1

F1 F1

F1 F1

F1 F1

F1 F1

F1 F1

F1 F1

F1 F1

F1 F1

F1 F1

F1 F1

F1 F1

F1 F1

F1 F1

F1 F1

F1 F1

F1 F1

F1 F1

F1 F1

2 2 2 2

2 2 2 2

T-44-02

2 2

TV3

TV3

TV3

T E

LE

C

O M

B

T L3

T E

LE

C

O M

C

T L

TV3

TV3

20a

20a

F F

E E

D D

C C

B B

A A

2 2 2

RESTROOM (W)

4CWMN

ELECTRICAL

4BEL2

ELECTRICAL

4BEL3

OFFICE

4B114

OFFICE

4B113

OFFICE

4B115

OFFICE

4B116

STAIR 4

4CST

Room

Room

FREIGHT ELEV. LOBBY

4BFLV

STAIR 3

4BST2

Room

EAST PANTRY

4BPN

COPY

4B102

OFFICE

4B214

OFFICE

4B213

OFFICE

4B215

OFFICE

4B216

OFFICE

4C111

OFFICE

4C112

OFFICE

4C110

OFFICE

4C114

OFFICE

4C113

OFFICE

4C115

OFFICE

4C211

OFFICE

4C212

OFFICE

4C210

OFFICE

4C214

OFFICE

4C213

OFFICE

4C215

CONFERENCE

4C156

CONFERENCE

4C150

HUDDLE ROOM

4C251

HUDDLE ROOM

4C151

FOCUS

4C153

FOCUS

4C152

FOCUS

4C253

FOCUS

4C252

FOCUS

4C255

FOCUS

4C155

FOCUS

4C154

FOCUS

4C254

CONFERENCE

4C256

CONFERENCE

4B152

CONFERENCE

4B153 CONFERENCE

4B155

CONFERENCE

4B154

CONFERENCE

4B252

CONFERENCE

4B253

CONFERENCE

4B255

CONFERENCE

4B254

CORRIDOR

4B101

TELECOM

4BTL2

TELECOM

4BTL3

Room

Room

Room

Room

Room

FOCUS ROOM

4C257

RESTROOM (M)

4CMEN

JANITOR

4CJA

ELECTRICAL

4CEL2

Room

TELECOM

4CTL2

Room

TELECOM

4CTL1

ELECTRICAL

4CEL1

OFFICE

4B133

OFFICE

4B132

OFFICE

4B131

OFFICE

4B130

OFFICE

4B233

OFFICE

4B232

OFFICE

4B231

OFFICE

4B230

OFFICE

4C192

OFFICE

4C191

OFFICE

4C190

OFFICE

4C292

OFFICE

4C291

OFFICE

4C290

EAST ELEVATOR LOBBY

4BLV2

COLLABORATION

4B170

COLLABORATION

4B270

ASSISTANT SECRETARY'S

SUITE

4C181

CONFERENCE

4C160

CORRIDOR

4C101

CORRIDOR

4C201

CORRIDOR

4C180

OPEN OFFICE

4B245 OPEN OFFICE

4C245

OPEN OFFICE

4B145

OPEN OFFICE

4C145

CORRIDOR

4C100

CORRIDOR

4C200

CORRIDOR

4C102

VESTIBULE

4C2VES

CORRIDOR

4B100

FOCUS

4C261

FOCUS

4C262

OFFICE

4C294

OFFICE

4C194

OFFICE

4C293

OFFICE

4C193

VESTIBULE

4C1VES

TV3

TV3

TV3

TV3

A. REFER TO AND COORDINATE WITH ARCHITECTURAL FLOOR PLANS,

ELEVATIONS AND DETAILS FOR ADDITIONAL DETAILS PERTAINING

TO THIS SHEET.

B. REFER TO SHEET T-00-01 FOR SYMBOLS APPEARING ON THIS

SHEET.

C. ALL DEVICES WITHIN ROOMS CONTAINING HARD PAN CEILINGS

SHALL HAVE CONDUITS ROUTED TO ABOVE ACCESSIBLE CEILING

SPACE IN CORRIDOR.

D. COMMUNICATIONS CONDUIT PATHWAYS SHALL NOT CONTAIN ANY

LENGTH GREATER THAN 100 FEET BETWEEN PULL POINTS. NO

SECTION OF CONDUIT SHALL CONTAIN MORE THAN TWO 90-

DEGREE BENDS, OR EQUIVALENT, BETWEEN PULL POINTS. IF

THERE IS REVERSE BEND IN THE SECTION, A PULL POINT SHALL BE

INSTALLED. PULL BOXES SHALL NOT BE USED IN LIEU OF BENDS.

THE INSIDE RADIUS OF ALL CONDUIT BENDS SHALL BE AT LEAST 10

TIMES THE INTERNAL DIAMETER. BENDS IN CONDUIT SHALL NOT

CONTAIN ANY KINKS OR OTHER DISCONTINUITIES THAT…