This solicitation notice announces a Request for Proposal for construction and switchgear repair services at the Lyndon B. Johnson Federal Building. The General Services Administration is seeking a single firm fixed-price contract to renovate floors 3, 4, 6, and 7 as open office space for approximately 600 Department of Education employees. Scope of work includes interior alterations, open workspace construction, and upgrades to HVAC, power distribution, and life safety systems. Significant renovations to the building's major switchgear and electrical systems are also required. The North American Industry Classification System codes applicable are 236220. The small business size standard is $39.5 million. A virtual pre-proposal conference will be held on May 5th and proposals are due by June 4th. The solicitation and any amendments will be posted to SAM.gov.
View the file
Other files for this federal contract opportunity
Show all 50
Solicitation Notice - LBJ Consolidation & Switchgear has more files on GovTribe.
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
FEC
X
A A
B B
C C
D D
E E
F F
3a
3a
3a
3a
F F
E E
D D
C C
B B
A A
GENERATOR ON ISOLATORS,
SEE ELECTRICAL DRAWINGS
AND SPECIFICATIONS.
12'-10"
M
IN
6" CONCRETE PAD,
3000 PSI STRENGTH
EXT'G CONCRETE PAD WITH EXT'G
EQUIPMENT TO REMAIN. VERIFY
LOCATION AND DIMENSIONS IN
FIELD. VIF SIZE AND LOCATION OF
ASSOCIATED OVERHEAD PIPING
AND DUCTS. PROTECT PAD,
EQUIPMENT, PIPING, DUCTS, ETC AS
REQUIRED DURING CONSTRUCTION.
XPH02PH01
STAIR 2
PBST1
STORAGE
P007
SWITCHGEAR
ROOM
P008
GENERATOR
ROOM
P009
SEE ELECTRICAL
DRAWINGS
STATIONARY EXTRUDED ALUMINUM
LOUVER FOR COMBUSTION AIR.
INFILL EXT'G DOOR OPENING TO
MATCH EXT'G ADJACENT WALL
CONSTRUCTION. WALL FINISH TO
MATCH ADJACENT FINISHES. MAINTAIN
CONTINUOUS WEATHER BARRIER
ACORSS CONSTRUCTION. TYP.
WALL FINISH TO MATCH
ADJACENT FINISHES.
PENETRATION FOR EXHAUST PIPE
EXT'G CONDUITS AND DISCONNECT TO
BE RELOCATED BE ELECTRIC PRIOR
TO RELOCATION OF DOOR XPH02. VIF
EXT'G LOCATION.
NOTE: REFER TO MECHANICAL AND
ELECTRICAL DRAWINGS FOR ROUTING
OF FUEL OIL SUPPLY, GENERATOR
EXHAUST, ELEC PANELS, FEED, ATS,
RELOCATED UNIT HEATER, ETC.
REMOTE RADIATOR ON ROOF
ABOVE. SEE MECHANICAL AND
ELECTRICAL DRAWINGS.
PENETRATION FOR FUEL OIL.
NOT IN SCOPE OF WORK
EXISTING WALL, PARTITION,
OR COLUMN TO REMAIN
NEW WALL OR PARTITION
EXISTING DOOR TO BE REMAIN
NEW DOOR
RECESSED, SEMI RECESSED
AND FIRE RATED FIRE
EXTINGUISHERS. REFER TO
FEC SCHEDULE 5/A-51-01.
CONSTRUCTION PLAN
1. VERIFY ALL DIMENSIONS IN FIELD.
2. VERIFY EXISTING CONDITIONS IN THE FIELD PRIOR TO BEGINNING WORK. NOTIFY
ARCHITECT IMMEDIATELY IF FIELD CONDITIONS DO NOT MATCH CONDITIONS
SHOWN ON DRAWINGS.
3. PROVIDE BLOCKING AT WALL MOUNTED ELEMENTS & FURNITURE, TYP.
4. REFER TO PARTITION TYPES FOR THICKNESSES OF PARTITIONS.
5. PARTITION DIMENSIONS ARE SHOWN TO FINISH FACE OF MATERIAL, TYP., U.N.O.
6. FURNITURE AND EQUIPMENT IS PROVIDED BY OWNER AND IS SHOWN FOR
COORDINATION PURPOSES ONLY, U.N.O.
7. ALL PENETRATIONS THROUGH FULL HEIGHT WALLS TO BE ACOUTICALLY SEALED.
8. ALL NEW WALLS TO BE FINISHED AND PREPPED FOR NOTED FINISH.
9. ANY BLOCKING TO BE FIRE RETARDANT, TYP.
10. ALL DOORS AT GYP. BD. PARTITIONS TO BE LOCATED 4" FROM EDGE OF JAMB TO
CORNER, UNLESS NOTED OTHERWISE.
11. TYPICAL PLANS (1/4" = 1'-0" DRAWINGS) SHOW TYPICAL CONDITIONS AND
DIMENSIONS. VERIFY ALL PARTITIONS, DOORS, EQUIPMENT, DEVICES, AND SPECIAL
CONDITIONS IN 1/8" = 1'-0" DRAWINGS.
12. POWER & DATA DEVICES TO BE CENTERED ON WALL FACE / COLUMN FACE U.N.O.
13. PROVIDE SHALLOW BACK BOXES AT ALL LOCATIONS WITH LIMITED CAVITY SPACE.
14. COORDINATE DEVICES WITH AV, TELECOMMUNICATIONS, AND ELECTRICAL
DRAWINGS. COORDINATE WITH FURNITURE PROVIDED BY OWNER, TYP.
15. PRESERVE FIRE RATING AND STC RATING OF ALL EXT'G TO REMAIN PARTITIONS,
WALLS, PENETRATIONS, DOORS, ETC.
16. PROVIDE FLOOR TRANSITION THRESHOLD AT ALL EXISTING DOOR LOCATIONS.
THRESHOLD TO BE CENTERED UNDERNEATH DOOR LEAF, TYP. BOD: TARKETT CRS-
XX-A.
0 1' 2' 1 1/2"=1'-0"
SENSITIVE BUT UNCLASSIFIED (SBU) PROPERTY OF THE UNITED STATES GOVERNMENT COPYING, DISSEMINATION, OR DISTRIBUTION OF THIS DOCUMENT TO UNAUTHORIZED RECIPIENTS IS PROHIBITED.
Do not remove this notice. Properly destroy or return documents when no longer needed.
TRUE NORTH
PLAN NORTH
CHECKED BY
DRAWN BY
FLOOR NUMBER
DRAWING TITLE
SHEET
NUMBER
SUBMISSION DATE
SUBMISSION STAGE
GSA PM
GSA PROJECT NO.
PROJECT
DESCRIPTION
PROJECT TITLE
BUILDING NAME
ADDRESS
BUILDING NUMBER
PRIME CONTR. NO.
PRIME ORDER NO.
CONST. CONTR.
A/E
SUB A/E
CONST. CONTR. NO.
SHEET SIZE:
DATE DRAWN:
36 X 48
S H
E E
T
ID
E N
TI
FI
C A
TI
O
N
DISCIPLINE
P R
O
JE
C T
ID
E
N
TI
FI
C
A
TI
O N
B U
IL
D
IN
G
BIM FILE NAME
C O
N
TR
A C
TO
R
S R
E V
IS
IO
N B
LO
C
K G
R A
P H
IC
S
C A
LE
K
E Y
P
LA
N S
TA
M
P O
R S
E A
L D
E S
IG
N
E R
ID
E
N
TI
FI
C
A
TI
O N
O W
N E
R
ID
E N
TI
FI
C A
TI
O
N
SHEET OF SHEETS
KRUECK & SEXTON ARCHITECTS, P.C.
400 MARYLAND AVENUE, SW
WASHINGTON, DC 20024
LYNDON B. JOHNSON FEDERAL BUILDING
DC0010ZZ
DC0010_A_3-4-6-7_r2020.rvt
WSP ENGINEERING
DEPARTMENT OF EDUCATION
CONSOLIDATION PROJECT
ISSUED FOR BID
HALLIE FUTTERMAN
RENOVATION OF FLOORS 3, 4, 6, & 7 OF THE EXISTING
BUILDING TO MEET THE DEPARTMENT OF
EDUCATION’S PROGRAMMATIC REQUIREMENTS.
GS-07-P-16-UC-D-7000
47PM0520F0002
47PM0520F0002
KRUECK & SEXTON ARCHITECTS
221 W ERIE ST
CHICAGO, IL 60654 (312) 787-0056
ARCHITECT
WSP ENGINEERING
ONE PENNSYLVANIA PLAZA, SECOND FLOOR
NEW YORK, NY 10119 (212) 465-5000
MEP ENGINEER
ATELIER TEN
45 E 20TH ST, 4TH FLOOR
NEW YORK, NY 10003 (312) 386-1400
SUSTAINABILITY CONSULTANT
THRESHOLD ACOUSTICS
141 W JACKSON BLVD, SUITE 2080
CHICAGO, IL 60604 (312) 386-1400
ACOUSTIC CONSULTANT
WEST EAST
M A
TC
H
LI
N
E
GENERAL NOTESLEGEND KEY NOTES
GENERAL SERVICES ADMINISTRATION
NATIONAL CAPITAL REGION
PUBLIC BUILDING SERVICE, D.C. SERVICES DIV.
7TH & D STREET, S.W.
WASHINGTON, D.C. 20407
ISSUE
NO. DATE ISSUE
ARCHITECTURAL
VARIES, SEE DRAWINGS
04/23/2021
2020 - 2021
FORCADE DESIGN
1626 PAYNE STREET
EVANSTON, IL 60201 (847) 448-4270
ENVIRONMENTAL GRAPHICS CONSULTANT
/2
/2
:0
:3
P
M
A-18-01
FLOOR PLANS - PENTHOUSE
Author
Checker
04/23/2021
05/07/2021
05/21/2021
ISSUED FOR BID
△2: ADDENDUM 01
△3: REVISION 2, ADDENDUM No. 2
1/8" = 1'-0"1
PENTHOUSE FLOOR
OPEN
TO
BEYOND
OPEN
TO
BEYOND
OPEN
TO
BEYOND
OPEN
TO
BEYOND
OPEN
TO
BEYOND
OPEN
TO
BEYOND
WC-1
PT-02
TPT-2
HK-1
PT-02B PT-02B
A88 A88 A88 A82
/4
A104
TPT-2
HK-1
WC-1
PT-02B PT-02B
PT-02PT-02
/4
PTD-2
A90A88 A90 A82 A104
WC-2
GB-2
PT-02B
PT-02 PT-02
TPT-1
HK-1
CU-3
PT-02B
HK-1
UR-1
A90A90 A82A88
/4
UR-2
PT-02B
PT-02
TPT-1
HK-1HK-1
GB-1
A88 A82 A104
UPT-1
PT-02
UR-1 UR-2
UPT-1
UR-1
WR-2
A88
MR-1 MR-1 MR-1
LAV-1 LAV-1 LAV-1
WR-1
WR-1
A88 A89A89
A87 PT-02B
A90A90 A82 A88
PT-02
P-2
A-50-01
A-50-01
AP-1
A143 A143
WC-1
TPT-2
GB-1
PT-02
WC-2
WC-1 WC-1WC-2
MR-2
CU-1 CU-1CU-2
CU-3CU-3
SC-1 SC-1
A T
T H
E S
E
S T
A L L
S O
N L
Y
T Y
P U
.N .O
PT-02B
A88
A88A90A90
TPT-1
HK-1
HK-1
PT-02B A87
GB-2
HK-1
HK-1
GB-2
GB-2
HK-1 HK-1 HK-1
A82
AP-1
A143 A143
WC-1
TPT-1
HK-1
PT-02B
PT-02 PT-02
PT-02B
A90 A82A90A88A104
WC-1
TPT-1
HK-1
PT-02B
PT-02
A82A88 A104
TPT-1
PT-02B
PT-02
A88 A82
PTD-2
A104
TPT-1
HK-1
WC-1
PT-02
PT-02BPT-02B
PT-02
PTD-2
A90 A82A90A88 A104
MR-2 PT-02
ALIGN
MR-1 MR-1 MR-1 MR-1
LAV-1 LAV-1 LAV-1 LAV-1
WR-1
WR-1
PTD-2 PTD-2
A90A90 A82 A88
PT-02BA87
A87A89A89
A-50-01
A-50-01
AP-1
A143
TPT-1
T Y
P U
.N .O
GB-1
WC-1
PT-02
WC-2
WC-1WC-1 WC-2WC-1
CU-5 CU-5CU-5CU-5
CU-4 CU-4
SC-1 SC-1
TPT-1
GB-2
HK-1
PT-02
GB-2GB-2
HK-1
HK-1
HK-1 HK-1
PT-02B A87
A82A90A90A88
HK-1 HK-1
AP-1
A143 A143
WR-2
PT-02B
P-2
MR-2
A88
PTD. DOOR AND FRAME
PT-02B
PT-02
A88
A90 A88
P-2
PT-02B
A88
PT-02B
P-2
A88
PT-02B
WR-2
P-2
A88
PTD. DOOR AND FRAME
WR-2
PT-02B
P-2
A88
WR-2
PT-02B
P-2
A91
A88
RB-03
P-2
PTD. DOOR AND FRAME
INTERIOR ELEVATION
1. SEE REFLECTED CEILING PLANS FOR CEILING HEIGHTS.
2. INSTALL ALL PRODUCTS PER MANUF. SPECIFICATIONS, U.N.O.
3. PROVIDE BLOCKING IN ALL LOCATIONS OF WALL MOUNTED, HUNG, OR
RECESSED ELEMENTS (INCLUDING BUT NOT LIMITED TO ARCHITECTURAL
WOODWORK, FIRE EXTINGUISHER CABINETS, GRAB BARS, EQUIPMENT,
TOILET ACCESSORIES, AND TOILET CUBICLES) AND ANY OTHER LOCATION
WHERE BLOCKING IS DEEMED NECESSARY. BLOCKING LOCATIONS ARE NOT
LIMITED TO THE AREAS SPECIFICALLY CALLED OUT IN PLAN AND ELEVATION.
4. SEE ACCESSIBILITY SHEETS FOR MOUNTING HEIGHTS.
EXISTING HISTORIC MARBLE
VINYL FILM
0 4' 8' 1/4"=1'-0"
SENSITIVE BUT UNCLASSIFIED (SBU) PROPERTY OF THE UNITED STATES GOVERNMENT COPYING, DISSEMINATION, OR DISTRIBUTION OF THIS DOCUMENT TO UNAUTHORIZED RECIPIENTS IS PROHIBITED.
Do not remove this notice. Properly destroy or return documents when no longer needed.
CHECKED BY
DRAWN BY
FLOOR NUMBER
DRAWING TITLE
SHEET
NUMBER
SUBMISSION DATE
SUBMISSION STAGE
GSA PM
GSA PROJECT NO.
PROJECT
DESCRIPTION
PROJECT TITLE
BUILDING NAME
ADDRESS
BUILDING NUMBER
PRIME CONTR. NO.
PRIME ORDER NO.
CONST. CONTR.
A/E
SUB A/E
CONST. CONTR. NO.
SHEET SIZE:
DATE DRAWN:
36 X 48
S H
E E
T
ID
E N
TI
FI
C A
TI
O
N
DISCIPLINE
P R
O
JE
C T
ID
E
N
TI
FI
C
A
TI
O N
B U
IL
D
IN
G
BIM FILE NAME
C O
N
TR
A C
TO
R
S R
E V
IS
IO
N B
LO
C
K G
R A
P H
IC
S
C A
LE
K
E Y
P
LA
N S
TA
M
P O
R S
E A
L D
E S
IG
N
E R
ID
E
N
TI
FI
C
A
TI
O N
O W
N E
R
ID
E N
TI
FI
C A
TI
O
N
SHEET OF SHEETS
KRUECK & SEXTON ARCHITECTS, P.C.
400 MARYLAND AVENUE, SW
WASHINGTON, DC 20024
LYNDON B. JOHNSON FEDERAL BUILDING
DC0010ZZ
DC0010_A_3-4-6-7_r2020.rvt
WSP ENGINEERING
DEPARTMENT OF EDUCATION
CONSOLIDATION PROJECT
ISSUED FOR BID
HALLIE FUTTERMAN
RENOVATION OF FLOORS 3, 4, 6, & 7 OF THE EXISTING
BUILDING TO MEET THE DEPARTMENT OF
EDUCATION’S PROGRAMMATIC REQUIREMENTS.
GS-07-P-16-UC-D-7000
47PM0520F0002
47PM0520F0002
KRUECK & SEXTON ARCHITECTS
221 W ERIE ST
CHICAGO, IL 60654 (312) 787-0056
ARCHITECT
WSP ENGINEERING
ONE PENNSYLVANIA PLAZA, SECOND FLOOR
NEW YORK, NY 10119 (212) 465-5000
MEP ENGINEER
ATELIER TEN
45 E 20TH ST, 4TH FLOOR
NEW YORK, NY 10003 (312) 386-1400
SUSTAINABILITY CONSULTANT
THRESHOLD ACOUSTICS
141 W JACKSON BLVD, SUITE 2080
CHICAGO, IL 60604 (312) 386-1400
ACOUSTIC CONSULTANT
WEST EAST
M A
TC
H
LI
N
E
GENERAL NOTESLEGEND KEY NOTES
GENERAL SERVICES ADMINISTRATION
NATIONAL CAPITAL REGION
PUBLIC BUILDING SERVICE, D.C. SERVICES DIV.
7TH & D STREET, S.W.
WASHINGTON, D.C. 20407
ISSUE
NO. DATE ISSUE
ARCHITECTURAL
VARIES, SEE DRAWINGS
04/23/2021
2020 - 2021
FORCADE DESIGN
1626 PAYNE STREET
EVANSTON, IL 60201 (847) 448-4270
ENVIRONMENTAL GRAPHICS CONSULTANT
/2
/2
:0
:5
P
M
A-20-07
ELEVATIONS - RESTROOMS
RT + VW + SK
AC + SP
04/23/2021
05/07/2021
05/21/2021
ISSUED FOR BID
△2: ADDENDUM 01
△3: REVISION 2, ADDENDUM No. 2
A82 SHADED AREA (ALIGNING WITH TOP OF TOILET STALLS TO
CEILING) REPRESENTS B.O.D. AS FULL HEIGHT PT-02 ON CEMENT
BOARD PANEL; AND A DEDUCT ALTERNATE TO BE PAINTED P-2
MOISTURE RESISTANCE PANEL.
A87 ALIGN WALL, WALL BASE AND FLOOR PORCELAIN TILE GROUT
JOINTS, TYP. REFER TO FINISH FLOOR PLANS FOR WORKING
POINTS
A88 PROVIDE PORCELAIN TILE TRIM EDGE AT GYP. BD. TILE
TERMINATION CONDITION. REFER TO TRIM AND MILLWORK
HARDWARE SCHEDULE. B.O.D. MANUF. SCHLUTER -STAINLESS
STEEL SCHIENE OR APPROVED EQUAL.
A89 MIRROR TO BE CENTERED W/ CENTER LINE OF LAVATORIES, TYP.
A90 PROVIDE PORCELAIN TILE EDGE TRIM AT OUTSIDE CORNERS, TYP
AT PORCELAIN TILE WALLS. B.O.D. MANUF. SCHLUTER - STAINLESS
STEEL QUADEC E OR APPROVED EQUAL.
A91 PROVIDE STAINLESS STEEL CORNER GUARD (FULL HEIGHT)
A103 PTD. DOOR AND FRAME
A104 WALL GRAZER LIGHT FIXTURE
A143 CLEANOUT. REFER TO PLUMBING DRAWINGS
1/4" = 1'-0"6
ELEVATION - EAST RESTROOM (MEN)
1/4" = 1'-0"5
ELEVATION - EAST RESTROOM (MEN)
1/4" = 1'-0"4
ELEVATION - EAST RESTROOM (MEN)
1/4" = 1'-0"3
ELEVATION - EAST RESTROOM (MEN)
1/4" = 1'-0"2
ELEVATION - EAST RESTROOM (MEN)
1/4" = 1'-0"1
ELEVATION - EAST RESTROOM (MEN)
1/4" = 1'-0"12
ELEVATION - EAST RESTROOM (WOMEN)
1/4" = 1'-0"11
ELEVATION - EAST RESTROOM (WOMEN)
1/4" = 1'-0"10
ELEVATION - EAST RESTROOM (WOMEN)
1/4" = 1'-0"9
ELEVATION - EAST RESTROOM (WOMEN)
1/4" = 1'-0"8
ELEVATION - EAST RESTROOM (WOMEN)
1/4" = 1'-0"7
ELEVATION - EAST RESTROOM (WOMEN)
1/4" = 1'-0"17
ELEVATION - EAST VESTIBULE (MEN)
1/4" = 1'-0"16
ELEVATION - EAST VESTIBULE (MEN)
1/4" = 1'-0"15
ELEVATION - EAST VESTIBULE (WOMEN)
1/4" = 1'-0"14
ELEVATION - EAST VESTIBULE (WOMEN)
1/4" = 1'-0"13
ELEVATION - EAST VESTIBULE (WOMEN)
1/4" = 1'-0"18
ELEVATION - EAST VESTIBULE (WOMEN)
1/4" = 1'-0"19
ELEV - WEST VESTIBULE (WMN)
V S
ABA
ABA
ABA
ABA
ABA
ABA
A .F
.F
3'-4" A.F.F.
3'-4" A.F.F.
3'-4" A.F.F.
3'-4" A.F.F.
V S
FEC
R
FEC
SR
T
T
ABA
ABA
ABA
ABA
ABA
ABA
A .F
.F
3'-4" A.F.F.
3'-4" A.F.F.
3'-4" A.F.F.
3'-4" A.F.F.
C R
FEC
SR
FEC
R
V S
T
T
ABA
ABA
ABA
ABA
ABA
ABA
A .F
.F
3'-4" A.F.F.
3'-4" A.F.F.
3'-4" A.F.F.
3'-4" A.F.F.
C R
FEC
SR
FEC
R
V S
T
T
ABA
ABA
ABA
ABA
ABA
ABA
A .F
.F
3'-4" A.F.F.
3'-4" A.F.F.
3'-4" A.F.F.
3'-4" A.F.F.
V S
FEC
R
FEC
SR
T
T
FEC
X
T
LV
RS
ABA
VS
CR
TV
H
J
A-20-04
A-20-07
A-20-07
A-20-07
A-20-07
A-20-07
A-20-07
JANITOR
VESTIBULE
RESTROOM (M)
RESTROOM (W)
FOCUS ROOM
VESTIBULE
A-42-02
A-42-04
V
.I .F
HOLD
5'-0" , TYP
/4
V
.I .F
/4
V
.I .F
/4
V .I .F
CLEAR
12'-0 1/2" V.I.F.
H O
L D
E Q
E
Q
/2
V
.I .F
/2
V
.I .F
HOLD
5'-0" , TYP.
E Q
E
Q
E Q
E
Q
E Q
E
Q
H O
L D
H O
L D
H O
L D
H O
L D
H O
L D
E
Q
E Q
E Q
E
Q
E Q
E Q
E Q
E Q
ALIGNE
Q
E
Q
E Q
E
Q
E Q
E
Q
M
IN
M
IN
ALIGN FACE OF GYP.
BD. WITH CEILING
GRID AT CORRIDOR
A73
A74
3' - 6" HOLD
3' - 6" HOLD
18" MIN
/4
E
Q
/2
/2
/2
E
Q
/2
/2
8A
1C
A110
A98
E Q
E
Q
ALIGN
A117
A110
A-20-06
G10
A140
A140
AP-1
A143
A143
A143
A143
3'-6"
RESTROOM (W)
VESTIBULE
MOTHER'S ROOM
VESTIBULE
RESTROOM (M)
JANITOR
/4
V .I .F
V
.I .F
V
.I .F
E Q
E
Q
3' - 0" HOLD
CLEAR
12'-1 1/4" V.I.F.8
/4
V
.I .F
/4
V
.I .F
M
IN
/4
V
.I .F
E Q
.3
E Q
.2
E Q
.1
A-42-03
A-42-02
OPP.
5'-0" TYP., HOLD
HOLD
5'-0" , TYP.
E Q
E
Q
E Q
E
Q E
Q
/2
/2
/2
E
Q
/4
V .I .F
H O
L D
H O
L D
H O
L D
E
Q E
Q E
Q
E
Q E
Q E
Q E
Q
3'-0" HOLD
ALIGNALIGN
E Q
E
Q
1C
8A
5'-0" TYP. HOLD
A98
E Q
E
Q
E Q
E
Q
E Q
E
Q
E Q
E
Q
A110
A-20-07
2 1
A-20-07
A-20-07
8 7
A-20-07
2'-2"
A110
ALIGN
A .F
.F
A .F
.F
A117
A118
A140
A140
M
IN
3'-6"
A-20-04
10 12
A-20-07
19-
RESTROOM (W)
VESTIBULE
MOTHER'S ROOM
VESTIBULE
RESTROOM (M)
JANITOR
A-42-03
A-42-02
OPP.
MR-1
MR-1
MR-1
WC-1
WC-1
WC-1
HK-1
HK-1
CU-1
CU-2
HK-1
GB-2
WC-2
WC-2
GB-2
GB-2
GB-1
SC-1
CU-3
UR-1
UR-1
UR-2
UPT-1
@ URINALS
TYP. U.N.O.
MR-1
MR-1
MR-1
MR-1
WC-2
WC-2
WC-1
WC-1
SC-1
CU-4
CU-5
WC-1
WC-1
MR-2
WR-2
MR-2
CU-5
LAV-1
WR-1
WR-1
LAV-1
LAV-1
TPT-2
TPT-1
TPT-1
HK-1
HK-1
GB-2
GB-2
GB-1
GB-2
TPT-1
HK-1
TPT-1
HK-1
HK-1
HK-1
WR-1
WR-1
LAV-1
LAV-1
LAV-1
LAV-1
PTD-2
PTD-2
A-20-07
2 1
A-20-07
A-20-07
8 7
A-20-07
A117
A118
A140
WR-2
A140
3'-0"MR-2
A-20-04
A-20-07
A-20-07
A-20-07
A-20-07
A-20-07
A-20-07
JANITOR
VESTIBULE
RESTROOM (M)
RESTROOM (W)
FOCUS ROOM
VESTIBULE
A-42-02
A-42-04
WC-1
WC-1
WC-1
MR-1
WC-2
WC-2
UR-1
UR-1
UR-2
UPT-1
GB-2
GB-2
GB-1
GB-2
GB-3
CU-2
HK-1
CU-1
HK-1
HK-1
WC-2
WC-2
WC-1
WC-1 MR-1
WC-1
WC-1
GB-2
GB-1
CU-4
SC-1
GB-2
CU-5
GB-2
CU-5
HK-1
MR-2
MR-2
WR-2
MR-1
MR-1
MR-1
MR-1
WR-1
LAV-1
LAV-1
LAV-1
MR-1
WR-1
WR-1
LAV-1
LAV-1
WR-1 LAV-1
LAV-1
A117
TPT-1
TYP. U.N.O.
TPT-2
A-20-06
G10
A140
WR-2
A140
CONSTRUCTION PLAN
1. VERIFY ALL DIMENSIONS IN FIELD.
2. VERIFY EXISTING CONDITIONS IN THE FIELD PRIOR TO BEGINNING WORK. NOTIFY
ARCHITECT IMMEDIATELY IF FIELD CONDITIONS DO NOT MATCH CONDITIONS
SHOWN ON DRAWINGS.
3. PROVIDE BLOCKING AT WALL MOUNTED ELEMENTS & FURNITURE, TYP.
4. REFER TO PARTITION TYPES FOR THICKNESSES OF PARTITIONS.
5. PARTITION DIMENSIONS ARE SHOWN TO FINISH FACE OF MATERIAL, TYP., U.N.O.
6. FURNITURE AND EQUIPMENT IS PROVIDED BY OWNER AND IS SHOWN FOR
COORDINATION PURPOSES ONLY, U.N.O.
7. ALL PENETRATIONS THROUGH FULL HEIGHT WALLS TO BE ACOUTICALLY SEALED.
8. ALL NEW WALLS TO BE FINISHED AND PREPPED FOR NOTED FINISH.
9. ANY BLOCKING TO BE FIRE RETARDANT, TYP.
10. ALL DOORS AT GYP. BD. PARTITIONS TO BE LOCATED 4" FROM EDGE OF JAMB TO
CORNER, UNLESS NOTED OTHERWISE.
11. TYPICAL PLANS (1/4" = 1'-0" DRAWINGS) SHOW TYPICAL CONDITIONS AND
DIMENSIONS. VERIFY ALL PARTITIONS, DOORS, EQUIPMENT, DEVICES, AND SPECIAL
CONDITIONS IN 1/8" = 1'-0" DRAWINGS.
12. POWER & DATA DEVICES TO BE CENTERED ON WALL FACE / COLUMN FACE U.N.O.
13. PROVIDE SHALLOW BACK BOXES AT ALL LOCATIONS WITH LIMITED CAVITY SPACE.
14. COORDINATE DEVICES WITH AV, TELECOMMUNICATIONS, AND ELECTRICAL
DRAWINGS. COORDINATE WITH FURNITURE PROVIDED BY OWNER, TYP.
15. PRESERVE FIRE RATING AND STC RATING OF ALL EXT'G TO REMAIN PARTITIONS,
WALLS, PENETRATIONS, DOORS, ETC.
16. PROVIDE FLOOR TRANSITION THRESHOLD AT ALL EXISTING DOOR LOCATIONS.
THRESHOLD TO BE CENTERED UNDERNEATH DOOR LEAF, TYP. BOD: TARKETT CRS-
XX-A.
REFLECTED CEILING PLAN
1. SEE FLOOR PLANS FOR DIMENSIONS.
2. COORDINATE ARCHITECTURAL REFLECTED CEILING PLAN WITH AV, MECHANICAL,
ELECTRICAL, FIRE ALARM, AND FIRE PROTECTION DRAWINGS. PROVIDE
COORDINATED DRAWINGS FOR REVIEW PRIOR TO CONSTRUCTION.
3. CONTRACTOR SHALL LOCATE MECHANICAL ITEMS AROUND LIGHTING LAYOUT AND
IN THE APPROXIMATE LOCATION OF THE MECHANICAL DRAWINGS.
4. SUPPORT CONDUIT, BOXES AND OTHER EQUIPMENT WITH UNISTRUT HANGERS
ATTACHED TO STRUCTURAL ELEMENTS.
5. START POINT FOR CEILING GRIDS TO BE CENTER OF ROOM UNLESS NOTED BY A
START POINT.
6. PROVIDE NON-SAG TYPE GYPSUM BOARD PANELS AT CEILING OF ALL WET AREAS
SUCH AS TOILET ROOMS, UNLESS NOTED OTHERWISE.
7. REFER TO INTERIOR ELEVATIONS FOR ADDITIONAL INFORMATION REGARDING
SOFFIT HEIGHTS AND LOCATIONS.
8. COORDINATE LOCATION OF EXIT SIGNS WITH CODE COMPLIANCE PLANS,
ARCHITECTURAL DRAWINGS, AND ELECTRICAL DRAWINGS.
9. ROUTE ALL CONDUITS ON EXPOSED CEILINGS SQUARE TO BUILDING WALLS AND
GROUP TOGETHER.
10. ALL PARTITION AND SOFFIT FRAMING SHALL EXTEND TO UNDERSIDE OF
STRUCTURE, UNLESS NOTED OTHERWISE.
11. PROVIDE RADIUS FITTED CEILING TRACK ACCESSORY AT ALL BULLNOSED WALL
CORNERS.
12. LOCATE DEVICES AT CENTER LINE OF CEILING TILES, U.N.O.
13. TYPICAL RCPs (1/4" = 1'-0" DRAWINGS) SHOW TYPICAL CONDITIONS. VERIFY ALL
EQUIPMENT, DEVICES, AND SPECIAL CONDITIONS IN 1/8" = 1'-0" DRAWINGS.
14. CONFIRM LOCATION OF SECURITION EQUIPMENT (I.E. CARD READERS, SECURITY
CAMERAS, ETC.) WITH OWNER & ARCHITECT PRIOR TO INSTALLATION.
CONTRACTOR TO PROVIDE CONDUIT IF REQUIRED.
CPT-01
CPT-02
PL-01
WF-01
PT-01
CPT-03
NOT IN SCOPE OF WORK
EXISTING WALL, PARTITION,
OR COLUMN TO REMAIN
NEW WALL OR PARTITION
EXISTING DOOR TO BE REMAIN
NEW DOOR
RECESSED, SEMI RECESSED
AND FIRE RATED FIRE
EXTINGUISHERS. REFER TO
FEC SCHEDULE 5/A-51-01.
OUTLET - DUPLEX
OUTLET - QUAD
DATA
SWITCH - SINGLE
THERMOSTAT -
WALL MOUNTED
LOW VOLTAGE DIMMER -
WALL MOUNTED
ROOM SCHEDULER -
WALL MOUNTED
ABA DOOR ACTUATOR
VACANCY SENSOR -
WALL MOUNTED
CARD READER
TELEVISION
POKE-THRU (QUAD
RECEPTACLE, HDMI, AND
2 DATA CONNECTIONS)
HDMI CONNECTION
POWER/ DATA WHIP TO
FURNITURE SYSTEM
FINISH PLAN
1. FOR FINISH MATERIAL WHEN MORE THAN ONE MATERIAL OCCURS THE FINISH IS
INDICATED THUS "/".
2. SEE INTERIOR ELEVATIONS AND PARTITION TYPES FOR ADDITIONAL FINISH
INFORMATION.
3. PAINT ALL INTERIOR AND EXTERIOR HOLLOW METAL DOORS, BORROWED LITES,
AND FRAMES.
4. PROVIDE TRANSITION STRIP AT ALL LOCATIONS WHERE FLOORING MATERIAL
CHANGES.
5. EXTEND SCHEDULED PAINT ON WALLS UP TO 1'-0" ABOVE THE FINISHED CEILING.
IN ROOMS NOT SCHEDULED TO RECEIVE A CEILING, EXTEND SCHEDULED PAINT
UP THE ENTIRE HEIGHT OF THE PARTITION, UNLESS NOTED OTHERWISE.
6. AT ALL EXPOSED AREAS, PAINT ALL WALLS, STRUCTURE, INCLUDING, BUT NOT
LIMITED TO, CONCRETE, COLUMNS, PIPING, CONDUIT, DUCTWORK AND OTHER
EQUIPMENT ETC.
7. DO NOT PAINT DOOR AND FRAME FIRE RATING LABELS.
8. PROVIDE LEVEL 4 DRYWALL FINISH AT ALL LOCATIONS SCHEDULED TO RECEIVE
PAINT UNLESS NOTED OTHERWISE.
9. EXCEPT FOR FACTORY FINISHED ITEMS, ALL EXPOSED MECHANICAL AND
ELECTRICAL EQUIPMENT, LOUVERS, PIPING, CONDUITS, ETC. SHALL BE PAINTED
UNLESS OTHERWISE NOTED. REFER TO SPECIFICATIONS FOR PAINTING SYSTEMS.
10. SEE REFLECTED CEILING PLANS FOR CEILING FINISHES.
11. TYPICAL FINISHES PER FLOOR U.N.O.
REFER TO MATERIAL SCHEDULE FOR VARIABLE FINISHES PER LEVEL: FLOOR:
CPT-01; BASE: RB-02; WALL PAINT: P-02; CEILING: P-01A; COVES & FASCIA: P-01A
12. TYPICAL FINISHES FOR EXISTING DOORS TO REMAIN:
EXISTING DOORS AND HOLLOW METAL FRAMES AT CORES TO MATCH ADJACENT
WALLS (P-3), U.N.O.
13. COVERPLATES FOR DEVICES / LIGHTSWITCHES ON FWP, ACCENT PAINT WALLS,
GLASS TILE, CV,WV OR GL PANELS TO BE MTL-02 STAINLESS STEEL.
0 4' 8' 1/4"=1'-0"
SENSITIVE BUT UNCLASSIFIED (SBU) PROPERTY OF THE UNITED STATES GOVERNMENT COPYING, DISSEMINATION, OR DISTRIBUTION OF THIS DOCUMENT TO UNAUTHORIZED RECIPIENTS IS PROHIBITED.
Do not remove this notice. Properly destroy or return documents when no longer needed.
TRUE NORTH
PLAN NORTH
CHECKED BY
DRAWN BY
FLOOR NUMBER
DRAWING TITLE
SHEET
NUMBER
SUBMISSION DATE
SUBMISSION STAGE
GSA PM
GSA PROJECT NO.
PROJECT
DESCRIPTION
PROJECT TITLE
BUILDING NAME
ADDRESS
BUILDING NUMBER
PRIME CONTR. NO.
PRIME ORDER NO.
CONST. CONTR.
A/E
SUB A/E
CONST. CONTR. NO.
SHEET SIZE:
DATE DRAWN:
36 X 48
S H
E E
T
ID
E N
TI
FI
C A
TI
O
N
DISCIPLINE
P R
O
JE
C T
ID
E
N
TI
FI
C
A
TI
O N
B U
IL
D
IN
G
BIM FILE NAME
C O
N
TR
A C
TO
R
S R
E V
IS
IO
N B
LO
C
K G
R A
P H
IC
S
C A
LE
K
E Y
P
LA
N S
TA
M
P O
R S
E A
L D
E S
IG
N
E R
ID
E
N
TI
FI
C
A
TI
O N
O W
N E
R
ID
E N
TI
FI
C A
TI
O
N
SHEET OF SHEETS
KRUECK & SEXTON ARCHITECTS, P.C.
400 MARYLAND AVENUE, SW
WASHINGTON, DC 20024
LYNDON B. JOHNSON FEDERAL BUILDING
DC0010ZZ
DC0010_A_3-4-6-7_r2020.rvt
WSP ENGINEERING
DEPARTMENT OF EDUCATION
CONSOLIDATION PROJECT
ISSUED FOR BID
HALLIE FUTTERMAN
RENOVATION OF FLOORS 3, 4, 6, & 7 OF THE EXISTING
BUILDING TO MEET THE DEPARTMENT OF
EDUCATION’S PROGRAMMATIC REQUIREMENTS.
GS-07-P-16-UC-D-7000
47PM0520F0002
47PM0520F0002
KRUECK & SEXTON ARCHITECTS
221 W ERIE ST
CHICAGO, IL 60654 (312) 787-0056
ARCHITECT
WSP ENGINEERING
ONE PENNSYLVANIA PLAZA, SECOND FLOOR
NEW YORK, NY 10119 (212) 465-5000
MEP ENGINEER
ATELIER TEN
45 E 20TH ST, 4TH FLOOR
NEW YORK, NY 10003 (312) 386-1400
SUSTAINABILITY CONSULTANT
THRESHOLD ACOUSTICS
141 W JACKSON BLVD, SUITE 2080
CHICAGO, IL 60604 (312) 386-1400
ACOUSTIC CONSULTANT
WEST EAST
M A
TC
H
LI
N
E
GENERAL NOTESLEGEND KEY NOTES
GENERAL SERVICES ADMINISTRATION
NATIONAL CAPITAL REGION
PUBLIC BUILDING SERVICE, D.C. SERVICES DIV.
7TH & D STREET, S.W.
WASHINGTON, D.C. 20407
ISSUE
NO. DATE ISSUE
ARCHITECTURAL
VARIES, SEE DRAWINGS
04/23/2021
2020 - 2021
FORCADE DESIGN
1626 PAYNE STREET
EVANSTON, IL 60201 (847) 448-4270
ENVIRONMENTAL GRAPHICS CONSULTANT
/2
/2
:0
:1
P
M
A-42-05A
TYPICAL PLANS - FLOOR AND ACCESSORIES -
RESTROOMS
RT + VW + SK
AC + SP
04/23/2021
05/07/2021
05/21/2021
ISSUED FOR BID
△2: ADDENDUM 01
△3: REVISION 2, ADDENDUM No. 2
1/4" = 1'-0"1
TYPICAL RESTROOM AREA - EAST
1/4" = 1'-0"3
TYPICAL RESTROOM AREA - WEST
A73 IN PREPARATION TO RECEIVE NEW WALL FINISH, REPLACE ANY
DAMAGED OR MISSING GYPSUM BOARD LAYERS, TYP. AT CORE
RESTROOMS
A74 REVISED EXISTING PARTITION FRAMING AS NEEDED TO
ACCOMMODATE REVISED PLUMBING FIXTURES AND ACCESSORIES
LAYOUT, TYP. AT CORE RESTROOMS
A98 SOLID SURFACE JOINT.
A110 VANITY STRUCTURAL SUPPORT MEMBER SIZE, QUANTITIES AND
SPACING TO BE DELEGATED DESIGN. G.C. TO COORDINATE
LOCATION TO AVOID VANITY AND TRASH GROMMET LOCATIONS.
A117 REFER TO ELEV. FOR MIRROR ALIGNMENT WITH TILE GROUTS
A118 ALIGN MIRROR WITH FLOOR TILE GROUTS
A140 EXISTING FLOOR DRAIN TO REMAIN, RAISE FLOOR DRAIN IF
NEEDED TO BE FLUSH WITH NEW FLOOR. PROVIDE NEW COVER
PLATE.
A143 CLEANOUT. REFER TO PLUMBING DRAWINGS
PLUMBING FIXTURES SCHEDULE
Type Mark Areas Description Manufacturer Model Finish / Color Type Comments
DF-1 Corridor Water Cooler - dual height w/ bottle filler (Refrigerated)
Elkay LZWS-LRPBM28K Stainless Steel Coordinate and verify in field the chase clearance to meet manfu. requirements.
FA-1 Public Restrooms Faucet and Soap Dispenser at Restrooms Bradley Corporation Metro Serie Verge S53-3300 (0.35GPM), 6-3300
Satin Stainless Steel Soap Dispenser to be single Top Fill, Pair with LAV-1, Power source to be hardwired
FA-2 Mother's Room Faucet and Soap Dispenser at Mother's Room and Private Restrooms
Kallista P-24409 (1.2gpm) and P23180 Stainless Steel Pair with LAV-2 and SNK-2
FA-3 Pantry Faucet at Pantry Kohler Purist - Pull Out (1.5 gpm) Satin Stainless Steel Pair with SNK-3 Faucet and Soap Dispenser.
LAV-1 Public Restrooms Undermount lavatory at Public Restrooms Kohler Vetricyl Rectangle K-2882 White Pair with FA-1 Faucet and Soap Dispenser, provide Insulation p trap cover. b.o.d. Lav Guard 2
LAV-2 Private Restrooms Undermount lavatory at Private Restrooms Kohler Rhythm K-2602-SU Satin Stainless Steel Pair with FA-2 Faucet and Soap Dispenser, provide insulationp trap cover, b.o.d. Lav Guard 2
SNK-2 Mother's Room Undermount sink at Mother's Room Elkay Lustertone ELUHAD211555 Stainless Steel Pair with FA-2 Faucet and Soap Dispenser.
provide Insulation p trap cover, b.o.d. Lav Guard 2
SNK-3 Pantry Drop-in pantry sink at Pantry Just Manuf. Co SL_ADA_2133_A_GR_3_6 Satin Stainless Steel 1 hole. Pair with FA-3 Faucet. provide Insulation p trap cover , refer to plumbing drawings.
UR-1 Public restrooms Urinal and Flushometer Sloan WEUS -1000.1201(0.125 gpf) White Standard height.
UR-2 Public restrooms Urinal and Flushometer - Barrier Free Height Sloan WEUS -1000.1201(0.125 gpf) White Barrier Free height.
WC-1 Public restrooms and private restrooms Water Closet and Flushometer Combo - Barrier Free Height
Sloan WETS-2451.1201 Alternate ADA installation(1.1 gpf)
White Barrier Free height. Provide Commercial Elongated Toilet Seat: Kohler K-4670-SC
WC-2 Public restrooms and private restrooms Water Closet and Flushometer Combo Sloan WETS-2451.1201 (1.1 gpf) White Standard height. Provide Commercial Elongated Toilet Seat: Kohler K-4670-SC
RESTROOMS ACCESSORIES SCHEDULE
Type Mark ITEM Description Manufacturer Model Selection Type Comments
AP-1 RESTROOMS 16x12 General Purpose Access Panel Cendrex 16x12. General Purpose Access Door for all access types Satin Stainless Steel Outside perimeter of flange to be aligned with tile grout. Provide blocking behind flange so the back side of flange is flush with face of tile.
CU-1 RESTROOMS Combination Unit: 2-Stall Seat Cover/Toilet Tissue Dispenser Bradley Corporation 592 Satin Stainless Steel Refer to Plan for door swing location and spindle hand.
CU-2 RESTROOMS Combination Unit: 1 Stall Seat Cover/ Toilet Tissue Dispenser Bradley Corporation 5922-10 Semirecessed Satin Stainless Steel Refer to Plan for door swing location and spindle hand.
CU-3 RESTROOMS Combination Unit: 2 Stall Toilet Tissue Dispenser Bradley Corporation 5422 Semirecessed Satin Stainless Steel Semi-Recessed
CU-4 RESTROOMS Combination Unit: 2-Stall Toilet Tissue Dispenser, Napkin Disposal Bradley Corporation 594 Satin Stainless Steel Refer to Plan for door swing location and spindle hand.
CU-5 RESTROOMS Combination Unit: 2 Stall Seat Cover, Tissue Dispenser & Napkin Disposal Bradley Corporation 591 Satin Stainless Steel Refer to Plan for door swing location and spindle hand.
FEC
GB-1 RESTROOMS 36" stainless steel grab bar Bobrick B-5806-36 Brushed Stainless Steel Provide blocking on wall as required
GB-2 RESTROOMS 42" stainless steel grab bar Bobrick B-5806-48 Brushed Stainless Steel Provide blocking on wall as required
GB-3 PRIVATE RESTROOMS 36" and 42" set stainless steel grab bars Seachrome Series 790 Series Straight Grab bars Stainless Steel Polished Provide blocking on wall as required
GL-07 PRIVATE RESTROOMS Frameless Mirror - see elevation Refer to elevations
HK-1 RESTROOMS Stainless steel hook Bobrick B-549 Brushed Stainless Steel At Barrier Free Stalls provide two (barrier free height and standard)_, for standard stalls, provide only one at standard height.
HK-2 PRIVATE RESTROOMS Hook at Private Restroom Kallista One Chrome Provide 2 (ABAAS height and Standard Height).
MR-1 RESTROOMS Framed LED lit mirror Bobrick B-167 2436 Stainless Steel Integral L1 light fixture. Refer to lighting schedule.
MR-2 RESTROOMS Framed Mirror Bobrick B-165 24"x60"
PTD-1 PANTRY AND MOTHER'S
ROOM
Paper Towel Dispenser Bobrick B-526 Brushed Stainless Steel Provided by GC
PTD-2 RESTROOMS TrimLineSeries™ Surface Mount Paper Towel Dispenser Bradley Corporation 250-15 Brushed Stainless Steel
SC-1 RESTROOMS Seat Cover Dispenser -Stall mount Bradley Corporation 582 Brushed Stainless Steel
TP-1 PRIVATE RESTROOMS Toilet Paper at Private Restroom Kallista One Chrome
TPT-1 RESTROOMS Floor mount toilet partition system 9" bottom gap. Bobrick Privada HPL - refer to finish schedule for type
Provide 9" bottom gap. Provide occupancy indicator and recessed leg. Alternate #
2. Bradley Corporation Series 500 (9" bottom gap)
TPT-2 RESTROOMS Floor mount toilet partition system 4" bottom gap. Bobrick Privada HPL - refer to finish schedule for type
Provide 4" bottom gap. Provide occupancy indicator and recessed leg. Alternate #
2. Bradley Corporation Series 500 (9" bottom gap)
UPT-1 RESTROOMS Wall mount urinal partition Bobrick Privada HPL - refer to finish schedule for type
1'-6" deep. Alternate #2. Bradley Corporation/ B00- Stainless Steel and cont.
hinges.
WR-1 RESTROOMS 6" Diam Circular Waste Chute and Waste Receptacle Mocket /Simplehuman TM1A stainless steel - 6" deep / 23 Gal 30.9" H x 15.5" W x 16.5" D/ receptacle: Slim Oval Top Can - 13 Gal. (27" H)
Satin Stainless Steel / Satin Stainless Steel
Provide Simplehuman Slim Oval Top Can - 13 Gallon Brushed SS (27" H)
WR-2 RESTROOMS TrimLineSeries™ Recessed Waste Receptacle Bobrick B-35643 Satin Stainless Steel
1/4" = 1'-0"4
WEST RESTROOM -ACCESSORIES
1/4" = 1'-0"2
EAST RESTROOM -ACCESSORIES
A-50-01
A-50-01
UPPER CABINET
BASE CABINET
BULKHEAD AND
CEILING AS
SCHEDULED.
WALL TILE.
REFER TO
ELEVATIONS
P.LAM HINGED DOOR
PANEL WITH ATTACHED
RECESSED BASE
SINK AS SCHEDULED.
INSTALLATION TO MEET
ABAAS KNEE CLEARANCE
WALL FINISH AS
SCHEDULED ON GYP. BD.
PARTITION @ PANTRY
P.LAM BACK PANEL
SOLID SURFACE
BACKSPLASH WITH
STRAIGHT EDGE
@MOTHER'S ROOM ONLY
FAUCET AS SCHEDULED.
2'-4" @ MOTHER'S ROOM
2'-1" @ PANTRY
8" MIN
/2
/4
R
V L
/8
R
V L
11"
ABAAS KNEE CLEARANCE
AREA TO BE MAINTAINED.
SOLID SURFACE
COUNTERTOP WITH 1/8"
QUICK MITER
P.LAM BASE AS
BLOCKING AS REQUIRED
ST.S PULLS. SEE GENERAL
NOTE 15.
FIXED WD. VENEER PANEL
ATTACHED TO PANEL
PROVIDE CUTOUT. G.C. TO
COORD. SIZE. PER
PLUMBING DOCS.
ALIGN WITH BASE CABINET PANEL
S E
E E
L E
V A
T
IO
N S
3/4"
P.LAM HINGED DOOR
PANEL WITH ATTACHED
RECESSED BASE
ST.S PULLS. SEE GENERAL
NOTE 15.
P.LAM ADJUSTABLE
SHELVES AND
HARDWARE
P.LAM PIECE FOR REVEAL
/4
T
Y P
MILLWORK
1. COORDINATE LOCATIONS OF GROMMETS WITH OWNER PRIOR TO CUTTING
INTO COUNTER, UNLESS NOTED OTHERWISE.
2. THE CASEWORK CODE SYMBOLS ARE SHOWN ON THE FLOOR PLANS OR
ELEVATIONS.
3. FIELD VERIFY ALL DIMENSIONS PRIOR TO FABRICATION.
4. VERIFY ALL LOCATIONS, MOUNTING HEIGHTS AND CLEARANCES. NOTIFY
ARCHITECT OF DISCREPANCIES PRIOR TO FABRICATION.
5. COORDINATE WORK WITH OTHER TRADES INTERFACING WITH CASEWORK
AND MILLWORK, INCLUDING PLUMBING, MECHANICAL AND ELECTRICAL
SYSTEMS.
6. PROVIDE ALL REQUIRED AND NECESSARY BACKING, STRUCTURAL SUPPORT
AND ANCHORS.
7. COORDINATE ANY WALL REINFORCEMENT WITH PROPER TRADE PRIOR TO
WALL CONSTRUCTION.
8. PROVIDE END UNITS WITH EXPOSED SIDES FINISHED TO MATCH OTHER
EXPOSED FINISHES ON ADJACENT UNITS.
9. PROVIDE ALL FILLERS, SCRIBES, TRIMS, FINISHED ENDS, FINISHED BACKS,
WORK SURFACES, BACKSPLASHES, AND CUTOUTS REQUIRED FOR FINISHED
INSTALLATION.
10. PROVIDE SHELVES WITH FINISHED SURFACES ON ALL SIDES.
11. PROVIDE ADJUSTABLE SHELVES WITH 4 SUPPORTS EACH MINIMUM.
12. PROVIDE BACKSPLASH, COUNTERTOP, CONTINUOUS SHELVING AND CABINET
FLOOR BASE WHICH RUN CONTINUOUS ACROSS MODULES. MINIMIZE
EXPOSED JOINTS IN ALL CONTINUOUS SURFACES.
13. COORDINATE SINK WHERE SHOWN IN PLAN OR ELEVATIONS. PROVIDE FALSE
DRAWER FRONTS WHERE REQUIRED TO MATCH ADJACENT CASE PROFILE.
PROVIDE REQUIRED SUPPORT FOR SINKS.
14. PROVIDE BACKSPLASH BEHIND THE ENTIRE LENGTH OF COUNTERTOPS AND
ALONG THE SIDE WHERE IT MEETS THE WALL.
15. PROVIDE STAINLESS STEEL PULLS (TAGGED IN ELEVATIONS AS "PUL") AS
SHOWN ON DETAILS AND ELEVATIONS. B.O.D. MANUF. HAFELE, MOD.
CONTEMPORARY. SIZE VARIES. PROVIDE PULLS LENGTH THAT MATCHES THE
CABINET WIDTH MINUS 2" (1" ON EACH SIDE) OR NEXT SMALLER INCREMENT
SIZE AVAILABLE.
16. PROVIDE WOODWORK LOCKS ON TYPICAL PANTRY WOODWORK LOCKS ON
PANTRY DOORS (DO NOT INCLUDE FOR PANTRY DRAWERS AND RECYCLING).
PROVIDE WRAP AROUND
PLUMBING
STEEL ANGLE FRAME
SUPPORT. AND CONNECT
TO IN WALL CONCEALED
SUPPORT STRUCTURE AND
BLOCKING.
SOLID SURFACE
COUNTERTOP WITH 1/8"
QUIRK MITER
8"
11"
LAVATORY AS
SCHEDULED.
INSTALLATION TO MEET
ABAAS KNEE CLEARANCE.
STRUCTURAL STEEL
TUBE W/ BASE PLATE
FASTENED TO EXISTING
SLAB. "DELEGATED
DESIGN"
5 1/2" 1'-11"
UPPER PORTION OF THE
WALL AS SCHEDULED.
MIRROR AS SCHEDULED
T O
R E
F L E
C T
IV
E
S U
R F
A C
E
M A
X
LARGE FORMAT
PORCELAIN TILE AND BASE
ON 1 LAYER OF CEMENT
BOARD / METAL STUD
ABAAS KNEE CLEARANCE
TO BE MAINTAINED.
5 1/2" 1'-11"
TRASH CAN AS
SCHEDULED
STEEL ANGLE FRAME
SUPPORT. AND CONNECT
TO IN WALL CONCEALED
SUPPORT STRUCTURE
AND BLOCKING.
UPPER PORTION OF THE
WALL AS SCHEDULED.
SOLID SURFACE
COUNTERTOP WITH 1/8"
QUIRK MITER
CEMENT BOARD ON METAL
STUD SHORT WALL IN
PREPARATION TO LARGE
FORMAT PORCELAIN TILE
T O
R E
F L E
C T
IV
E
S U
R F
A C
E
M A
X
EQ. EQ.
MIRROR AS SCHEDULED
LARGE FORMAT
PORCELAIN TILE
TRASH RING AS SCHEDULED
WALL FINISH AS
SCHEDULED ON GYP. BD.
PARTITION
MELAMINE BACK PANEL
P.LAM BASE
BLOCKING AS REQUIRED
2'-4" @ MOTHER'S ROOM
2'-1" @ PANTRY SOLID SURFACE
COUNTERTOP WITH 1/8"
QUIRK MITER
ST.S PULLS. SEE GENERAL
NOTE 15.
PTD-1 PAPER TOWEL
DISPENSER ON FIXED
P.LAM PANEL.
P.LAM DRAWER FRONT
PANEL
DRAWER HARDWARE
FIXED P.LAM PANEL STRIPS.
E Q
E Q
E Q
T Y
P
/8
R
V L
T Y
P
/2
/4
SOLID SURFACE
BACKSPLASH W/ STRAIGHT
EDGE @ MOTHER'S ROOM
ONLY. NO BACKSPLASH @
PANTRY.
ADJUSTABLE PLASTIC
LAMINATE SHELVES AND
HARDWARE
P.LAM HINGED DOOR
PANEL WITH ATTACHED
RECESSED BASE
WALL FINISH AS
SCHEDULED ON GYP. BD.
PARTITION @ PANTRY
SOLID SURFACE
COUNTERTOP WITH 1/8"
QUIRK MITER
MELAMINE BACK PANEL
P.LAM BASE
BLOCKING AS REQUIRED
ST.S PULLS. SEE GENERAL
NOTE 15.
FIXED PLASTIC LAMINATE
PANEL
/2
/4
/8
R
V L T
Y P
REFER TO FLOOR PLANS
2'-1" U.N.O
3"
T Y
P
SOLID SURFACE FULL
HEIGHT BACKSPLASH W/
STRAIGHT EDGE @
SUPPORT ONLY. NOT
BACKSPLASH @ PANTRY.
ADJUSTABLE PLASTIC
LAMINATE SHELVES AND
HARDWARE (FOR TRASH
CAN STOP)
WALL FINISH AS SCHEDULED ON
GYP. BD. PARTITION
SOLID SURFACE COUNTERTOP
WITH 1/8" QUIRCK MITER
MELAMINE BACK PANEL
SOLID SURFACE BACKSPLASH
WITH STRAIGHT EDGE
@MOTHERS ROOM ONLY. NO
BACKSPLASH @ PANTRY
BLOCKING AS REQUIRED
ST.S PULLS. SEE GENERAL
NOTE 15.
P.LAM PROVIDE P.LAM EDGE .
TRASH RECEPTACLE. REFER
TO COMMENTS ON WR-3
P.LAM HINGED DOOR PANEL
2'-4" @ MOTHER'S ROOM
2'-1" @ PANTRY
P.LAM BASE
END P.LAM PANEL BEYOND
TILTED WD VENEER PANEL W/
OPENING
/2
T Y
P
3"
/4
M
IN
EQ. 1'-0" EQ.
GYP BD WALL. PROVIDE
BLOCKING AS
REQUIRED FOR
ATTACHMENT OF
STANDARDS
3/4" PL-02 P.LAM SHELF (3
TOTAL)
KNAPE & VOGT #185
STEEL BRACKETS
KNAPE & VOGT #85 STEEL
BRACKETS STANDARDS
SCREW ATTACH TO METAL
STUDS OR BLOCKING AS
REQUIRED
1' - 8"
/2
METAL BASE AT WALL AS
SCHEDULED.
SUPPORT STRUCTURE
"DELEGATED DESIGN"
/4
R
V L
/4
/4
R
V L
SOLID SURFACE
COUNTERTOP WITH 1/8"
QUIRK MITER
WOOD VENEER FIXED
PANEL AND BACK PANEL
WRAPPED PANEL AT BACK
WALL
WRAPPED PANEL AT
BACK WALL
WALL GRAZER LIGHT
FIXTURE
/4
R
V L
2'-0"
3/4" RVL.
GLASS PANELS AS
SCHEDULED.
GLASS PANELS AS
SCHEDULED.
MTL. CORNER TRIM
GLASS PANELS AS
SCHEDULED.
GLASS PANELS AS
SCHEDULED.
GLASS PANEL MTL.
EDGE
1 1/2" GAP
ABAAS KNEE CLEARANCE
AREA TO BE MAINTAINED.
3/4" 2'-0"
PROVIDE WRAP AROUND
PLUMBING
WOOD VENEER FIXED
PANEL, PROVIDE BLOCKING
AS REQUIRED
SOLID SURFACE
COUNTERTOP WITH
MITERED STRAIGHT EDGE
UNDERMOUNT SINK AS
SCHEDULED
8"
10 1/4"
PARTITION AS SCHEDULED,
REFER TO ELEVATIONS FOR
FINISHES
MIRROR AS SCHEDULED,
B/ REFLECTIVE SURFACE
AT 3'-4" MAX.
REFER TO PLANS AND
ELEVATIONS FOR FINISHES
LAVATORY INSTALLATION
TO MEET ABAAS KNEE
CLEARANCE.
/4
REFER TO PLAN
S E
E E
L E
V A
T
IO
N S
/4
R
V L
BACKGROUND P.LAM
PANEL ON NON
STRUCTRUAL METAL
FRAMING
P.LAM FIXED PANEL
ATTACHED TO
BACKGROUND PANEL
P.LAM PIECE FOR
REVEAL
PARTITION AS
SCHEDULED
PROVIDE KICKERS IF
REQUIRED.
T Y
P
/4
T
Y P
FIXED SIDE WOOD
VENENER PANEL OF COAT
CLOSET BEYOND
MELAMINE BACK PANEL
BLOCKING AS REQUIRED
S E
E E
L E
V A
T
IO
N
H O
L D
E Q
E Q
E Q
/4
SOLID SURFACE
COUNTERTOP WITH
MITERED CORNERS AND
STRIGHT EDGE
ST.S PULLS. SEE GENERAL
NOTE 15.
FIXED WOOD VENEER
PANEL.
FIXED WOOD VENEER
PANEL. PROVIDE 3/4" X 3/4"
RVL. AT END OF VISIBLE
PANEL.
S E
E E
L E
V A
T
IO
N S
3/4"
REF. TO PLANS
3/4"
WOOD VENEER PANEL
BASE
3"
/4
R
V L
WOOD VENEER HINGED
DOOR PANEL WITH
ATTACHED RECESSED
BASE
ST.S PULLS. SEE GENERAL
NOTE 15.
WOOD VENEER
ADJUSTABLE SHELVES
AND HARDWARE
WOOD VENEER DRAWER
FRONT PANEL
DRAWER HARDWARE
FIXED WOOD VENEER
PANEL STRIPS.
A L
IG
N
WOOD VENEER SIDE
PANEL
S E
E E
L E
V A
T
IO
N S
3/4"
WOOD VENEER BASE
/4
R
V L
WOOD VENEER HINGED
DOOR PANEL WITH
ATTACHED RECESSED
BASE
VERTICAL S.ST. PULLS AS
24" APROX. LONG. SEE
NOTE 15 FOR B.O.D. MANUF.
AND MODEL.
WOOD VENEER FIXED
SHELVES
CHROME PLATED STEEL
ROD W/ METAL
END BRACKETS;
PROVIDE CENTER
SUPPORT AT LOCATION
WHERE ROD LENGTH
EXCEEDS 4'-0"
REFER TO PLANS
ADJUSTABLE SHELF
ADD CHROME PLATED
STEEL ROOD END
BRACKET. PROVIDE ROD
BUT DO NOT INSTALL.
A B
A A
S C
O M
P L
IA
N T
3"
/4
/4
1'-3"
3/4" X 3/4" X 1/8" CONT.
ALUM. ANGLE
A L
IG
N
S E
E E
L E
V A
T
IO
N
3/4"
/4
R
V L
(P.LAM @ SUPPORT AND WOOD
VENEER @ EX. PANTRY) HINGED
DOOR PANEL WITH ATTACHED
RECESSED BASE
ST.S PULLS. SEE GENERAL
NOTE 15.
(P.LAM @ SUPPORT AND WOOD
VENEER @ EX. PANTRY)
ADJUSTABLE SHELVES AND
HARDWARE
(P.LAM @ SUPPORT AND WOOD
VENEER @ EX. PANTRY) PIECE
FOR REVEAL
1' - 4"
H O
L D
UNDERCOUNTER LIGHT FIXTURE AS
SCHEDULED. REFER TO PLANS FOR
LOCATIONS.
3/4" PL-02 SHELF
CHROME PLATED STEEL ROD W/
METAL
END BRACKETS; PROVIDE
CENTER SUPPORT AT LOCATION
WHERE ROD LENGTH EXCEEDS
4'-0"
3/4" X 3/4" X 1/8" CONT. ALUM.
ANGLE
PARTITION AS SCHEDULED,
PROVIDE ADDITIONAL
BLOCKING AS REQUIRED
3"
1'-3"
/2
A .F
.F
ADJUSTABLE PLASTIC
LAMINATE SHELVES AND
HARDWARE
WALL FINISH AS
SCHEDULED ON GYP. BD.
PARTITION
FULL HEIGHT SOLID
SURFACE BACKSPLASH
WITH STRAIGHT EDGE.
PROVIDE CLEAR SEALANT.
/2
/4
/8
R
V L T
Y P
REFER TO FLOOR PLANS
ALIGN WITH COLUMN, V.I.F.
3"
T Y
P
ADJUSTABLE PLASTIC
LAMINATE SHELVES AND
HARDWARE
P.LAM HINGED DOOR
PANEL WITH ATTACHED
RECESSED BASE
SOLID SURFACE
COUNTERTOP WITH 1/8"
QUIRK MITER
MELAMINE BACK PANEL
P.LAM BASE
BLOCKING AS REQUIRED
ST.S PULLS. SEE GENERAL
NOTE 15.
FIXED PLASTIC LAMINATE
PANEL
WD VENEER HINGED
DOOR PANEL WITH
ATTACHED RECESSED
BASE
ABAAS KNEE CLEARANCE
AREA TO BE MAINTAINED.
SINK AS SCHEDULED.
INSTALLATION TO
MEET ABAAS KNEE
CLEARANCE.
WALL FINISH AS
SCHEDULED ON GYP. BD.
PARTITION
SOLID SURFACE
COUNTERTOP WITH 1/8"
QUICK MITER
P.LAM BACK PANEL
METAL BASE AS
SCHEDULED
FULL HEIGHT SOLID
SURFACE BACKSPLASH
WITH STRAIGHT EDGE.
PROVIDE CLEAR SEALANT.
BLOCKING AS REQUIRED
ST.S PULLS. SEE GENERAL
NOTE 15.
FAUCET AS SCHEDULED.
FIXED WD. VENEER PANEL
ATTACHED TO PANEL
PROVIDE CUTOUT. G.C. TO
COORD. SIZE. PER
PLUMBING DOCS.
2' - 4"
8" MIN
/2
/4
R
V L
/8
R
V L
11"
S E
E E
L E
V A
T
IO
N
MELAMINE BACK PANEL
BLOCKING AS REQUIRED
SOLID SURFACE
COUNTERTOP WITH 1/8"
QUIRK MITER
ST.S PULLS. SEE GENERAL
NOTE 15.
METAL BASE AS
SCHEDULED
WOOD VENEER DRAWER
FRONT PANEL
DRAWER HARDWARE
FIXED WD VENEER PANEL
STRIPS.
FULL HEIGHT SOLID
SURFACE BACKSPLASH
WITH STRAIGHT EDGE.
PROVIDE CLEAR SEALANT.
E Q
E Q
E Q
T Y
P
/8
R
V L
2'-4"
PTD-1 PAPER TOWEL
DISPENSER ON FIXED P.LAM
PANEL
/2
/4
R
V L
S
E E
E L
E V
A T
IO
N
ADJUSTABLE PLASTIC
LAMINATE SHELVES AND
HARDWARE (FOR TRASH
CAN STOP)
SOLID SURFACE COUNTERTOP
WITH 1/8" QUIRK MITER
MELAMINE BACK PANEL
PAINTED BLOCKING AS
REQUIRED
ST.S PULLS. SEE GENERAL
NOTE 15.
WD VENEER PROVIDE P.LAM
EDGE .
TRASH RECEPTACLE. REFER
TO COMMENTS ON WR-3
WD VENEER HINGED DOOR PANEL
MTL BASE AS SCHEDULED
TILTED WD VENEER PANEL W/
OPENING
FULL HEIGHT SOLID
SURFACE BACKSPLASH
WITH STRAIGHT EDGE.
PROVIDE CLEAR SEALANT.
2'-4".
/2
T Y
P
3"
/4
M
IN
1' - 0" 5 1/2"
WALL FINISH AS
SCHEDULED ON GYP.
BD. PARTITION
SOLID SURFACE
COUNTERTOP WITH
1/8" QUICK MITER
FULL HEIGHT SOLID
SURFACE BACKSPLASH
WITH STRAIGHT EDGE @ EX.
PANTRY ONLY, 3" H AT
MOTHER'S ROOM
BLOCKING AS
REQUIRED
FINISHED WD. VENEER
EDGE @ EX. PANTRY
P.LAM @ MOTHER'S ROOM
S E
E E
L E
V A
T
IO
N S
/2
/4
UNDERCOUNTER
REFRIGERATOR
2'-4".
R E
F E
R T
O A
P P
L
IA
N C
E A
S S
C H
E D
U L E
D
PROVIDE AND COORD.
COUTOUT FOR POWER
OUTLET AS SCHEDULED.
REFER TO ELEVATIONS,
TYP. HEIGHTS AND FLOOR
PLANS.
/4
M
IN
PROVIDE AND COORD.
COUTOUT FOR POWER
OUTLET AS SCHEDULED.
REFER TO ELEVATIONS,
TYP. HEIGHTS AND FLOOR
PLANS.
WOOD VENEER PANEL
WRAPPED PANEL AT BACK WALL
SOLID SURFACE COUNTERTOP
WITH 1/8" QUIRK MITER
CONCEALED SUPPORTS TO IN WALL
STRUCTURE. "DELEGATED DESIGN"
METAL PLATE AS SCHEDULED
WALL BASE AS SCHEDULED
/4
WRAPPED PANEL AT BACK WALL
S E
E E
L E
V A
T
IO
N
G .C
T
O C
O O
R D
P
A N
E L I N
T E
R U
P T
IO
N
0 1/4' 1/2' 6"=1'-0"
KEY NOTES
GENERAL NOTES
LEGEND
CHECKED BY
DRAWN BY
FLOOR NUMBER
DRAWING TITLE
SHEET
NUMBER
SUBMISSION DATE
SUBMISSION STAGE
GSA PM
GSA PROJECT NO.
PROJECT
DESCRIPTION
PROJECT TITLE
BUILDING NAME
ADDRESS
BUILDING NUMBER
PRIME CONTR. NO.
PRIME ORDER NO.
CONST. CONTR.
A/E
SUB A/E
CONST. CONTR. NO.
SHEET SIZE:
DATE DRAWN:
36 X 48
S H
E E
T
ID
E N
TI
FI
C A
TI
O
N
DISCIPLINE
P R
O
JE
C T
ID
E
N
TI
FI
C
A
TI
O N
B U
IL
D
IN
G
BIM FILE NAME
C O
N
TR
A C
TO
R
S R
E V
IS
IO
N B
LO
C
K G
R A
P H
IC
S
C A
LE
K
E Y
P
LA
N S
TA
M
P O
R S
E A
L D
E S
IG
N
E R
ID
E
N
TI
FI
C
A
TI
O N
O W
N E
R
ID
E N
TI
FI
C A
TI
O
N
SHEET OF SHEETS
KRUECK & SEXTON ARCHITECTS, P.C.
400 MARYLAND AVENUE, SW
WASHINGTON, DC 20024
LYNDON B. JOHNSON FEDERAL BUILDING
DC0010ZZ
DC0010_A_3-4-6-7_r2020.rvt
WSP ENGINEERING
DEPARTMENT OF EDUCATION
CONSOLIDATION PROJECT
ISSUED FOR BID
HALLIE FUTTERMAN
RENOVATION OF FLOORS 3, 4, 6, & 7 OF THE EXISTING
BUILDING TO MEET THE DEPARTMENT OF
EDUCATION’S PROGRAMMATIC REQUIREMENTS.
GS-07-P-16-UC-D-7000
47PM0520F0002
47PM0520F0002
KRUECK & SEXTON ARCHITECTS
221 W ERIE ST
CHICAGO, IL 60654 (312) 787-0056
ARCHITECT
WSP ENGINEERING
ONE PENNSYLVANIA PLAZA, SECOND FLOOR
NEW YORK, NY 10119 (212) 465-5000
MEP ENGINEER
ATELIER TEN
45 E 20TH ST, 4TH FLOOR
NEW YORK, NY 10003 (312) 386-1400
SUSTAINABILITY CONSULTANT
THRESHOLD ACOUSTICS
141 W JACKSON BLVD, SUITE 2080
CHICAGO, IL 60604 (312) 386-1400
ACOUSTIC CONSULTANT
WEST EAST
M A
TC
H
LI
N
E
GENERAL SERVICES ADMINISTRATION
NATIONAL CAPITAL REGION
PUBLIC BUILDING SERVICE, D.C. SERVICES DIV.
7TH & D STREET, S.W.
WASHINGTON, D.C. 20407
ISSUE
NO. DATE ISSUE
ARCHITECTURAL
VARIES, SEE DRAWINGS
04/23/2021
2020 - 2021
FORCADE DESIGN
1626 PAYNE STREET
EVANSTON, IL 60201 (847) 448-4270
ENVIRONMENTAL GRAPHICS CONSULTANT
/2
/2
:0
:2
P
M
A-50-01
MILLWORK DETAILS
RT + VW + SK
AC + SP
04/23/2021
05/07/2021
05/21/2021
ISSUED FOR BID
△2: ADDENDUM 01
△3: REVISION 2, ADDENDUM No. 2
S E
N S
IT
IV
E B
U T
U N
C L
A S
S
IF
IE
D
S
B U
P
R O
P E
R T
Y O
F T
H E
U N
IT
E
D S
T A
T E
S G
O V
E R
N M
E N
T F
O R
O F
F
IC
E U
S E
O N
L Y
D o n o t re m o ve t h is n o ti ce
P ro p er ly d es tr o y o r re tu rn d o cu m en ts w h en n o lo n g er n ee d ed
A156 UNDERCOUNTER LIGHT FIXTURE AS SCHEDULED. REFER TO
PLANS FOR LOCATIONS.
3/4" = 1'-0"12
MILWORK - FULL SECTION
DETAIL AT PANTRY
1" = 1'-0"22
BASE CABINET SECTION SINK
AT PANTRY & MOTHER'S ROOM
1" = 1'-0"14
WALL UPPER CABINET
AT PANTRY
1" = 1'-0"1
VANITY COUNTERTOP
AT RESTROOMS
1" = 1'-0"2
VANITY COUNTER- TRASH
AT RESTROOMS
1" = 1'-0"19
BASE CABINET DR.AND P. TOW
AT PANTRY & MOTHERS ROOM
1" = 1'-0"20
BASE CABINET SECTION
AT PANTRY AND SUPPORT
1" = 1'-0"21
BASE CABINET - TRASH AT
PANTRY AND MOTHER'S ROOM
1" = 1'-0"15
ADJUSTABLE SHELVES ON
HEAVY DUTY STANDARDS AT
PANTRY CLOSET
1" = 1'-0"4
CREDENZA
AT SECRETARY'S OFFICE
1" = 1'-0"16
BASE CABINET SECTION
AT PRIVATE RESTROOMS
1" = 1'-0"13
FIXED OVERHEAD PLAM DETAL
AT PANTRY
1" = 1'-0"17
BASE CABINET DRAWERS
AT PRIVATE RESTROOMS
1" = 1'-0"18
FULL HEIGHT COAT
AT PRIVATE RESTROOMS
1" = 1'-0"6
WALL UPPER CABINET
AT EX. PANTRY AND SUPPORT
1" = 1'-0"3
HAT SHELF AND COAT ROD
AT SUPPORT
1" = 1'-0"7
BASE CABINET SECTION
AT EX. PANTRY
1" = 1'-0"9
BASE CABINET SECTION SINK
AT EX. PANTRY
1" = 1'-0"10
BASE CABINET
AT EX. PANTRY
1" = 1'-0"8
BASE CABINET - TRASH
AT EX. PANTRY
1" = 1'-0"11
BASE CABINET- REFR. AT EX.
PANTRY AND MOTHER'S RM
1" = 1'-0"5
STONE CREDENZA AT CONF.
FEC
R
FEC
FSR
FEC
SR
WATER
CLOSET
(BARRIER
FREE)
URINAL URINAL
(BARRIER
FREE)
LAVATORY
(BARRIER
FREE)
LAVATORY
FINISH
FLOOR
M A
X
M A
X
S P
IG
O
T H
T
M A
X
DRINKING FOUNTAIN
(BARRIER FREE)
/2
M
IN
5 1/4" MAX9" MIN
M
IN
M A
X
17"-19"
ALL HANDICAP SINKS WITH
EXPOSED DRAIN PIPING ARE TO
RECEIVE AN UNDERLAVATORY
GUARD.
WATER
CLOSET
" 4
PAPER
TOWEL
DISPENSER
FINISH FLOOR
WASTE
RECEPTACLE
SOAP
DISPENSER
(WALL
MOUNTED)
MIRROR UNIT
B R
E F
L S
U R
F
UNDERLAVATORY
GUARD
ALL EXPOSED DRAIN PIPING ARE TO
RECEIVE AN UNDERLAVATORY GUARD
STALL
(BARRIER
FREE)
3'-0" 6"
8"
V.I.F.
1'-6"
1 1/2"ø
STAINLESS
STEEL GRAB
BARS
CU-1
8"
CU-2 CU-3 AND SC-1
(BARRIER FREE)
CU-4 AND SC-1
(BARRIER FREE)
CU-5
8" 2"8"
M
IN
2"8" 8"
M
IN
M
IN
M
IN
M
IN
SC-1SC-1 CU-3 CU-3 CU-5CU-2CU-1
STALLS (COMBINATION UNITS)
B A
R R
IE
R
F R
E E
S T
A N
D A
R D
HOOKS
FIRE
EXTINGUISHER
CABINET
(SEE LEGEND)
C E
N T
E R
O F
H A
N D
L E
M A
X
FINISH FLOOR
NOTE: TYPICAL MOUNTING HEIGHT OF ALL
PUBLIC ACCESSIBLE EQUIPMENT SHALL BE 48"
MAX ABOVE FINISH FLOOR AS MEASURED TO
THE CENTER OF THE OPERATING MECHANISM
(PULL HANDLE, SWITCH, LEVER, ETC.)
WRITABLE
SURFACE BOARD
REFER TO INTERIOR ELEVATIONS
FOR ADDITIONAL INFORMATION
M
IN
MOUNTING HEIGHTS
1. NOT ALL PLUMBING FIXTURES, TOILET / BATH ACCESSORIES, AND SPECIALTY
EQUIPMENT MAY BE USED. SEE PLANS, INTERIOR ELEVATIONS, AND
SCHEDULES FOR ACCESSORIES USED.
2. PROVIDE BLOCKING, BRACKETS AND MISCELLANEOUS MATERIALS
NECESSARY FOR THE INSTALLATION OF ACCESSORIES.
3. LOCATE TOILET ACCESSORIES AS SHOWN AND MOUNT AT HEIGHTS
INDICATED.
4. GRAB BARS MUST BE CAPABLE OF RESISTING A FULL LOAD OF 400 LBS
EXERTED AT ANY POINT IN ANY DIRECTION.
5. WRAP ALL EXPOSED PIPING UNDER LAVATORIES WITH PROTECTIVE
INSULATION.
6. FIXTURE DESIGNATIONS SHOWN SHALL BE USED IN CONJUNCTION WITH
ARCHITECTURAL (A-SERIES) SHEETS ONLY. DESIGNATIONS ON M.E.P.
DOCUMENTS MAY VARY.
7. COORDINATE LOCATION OF REAR GRAB BARS WITH WATER CLOSET FLUSH
VALVES.
8. FIXTURES AND ACCESSORIES SHALL BE INSTALLED IN ACCORDANCE WITH
THE LATEST EDITIONS OF THE APPLICABLE PLUMBING CODE.
9. FIXTURES AND ACCESSORIES DESIGNATED AS "ACCESSIBLE" SHALL BE
INSTALLED IN ACCORDANCE WITH THE LATEST EDITIONS OF THE AMERICANS
WITH DISABILITIES ACT GUIDELINES (CURRENT EDITION)
10. FIXTURES AND ACCESSORIES DESIGNATED AS "ACCESSIBLE" SHALL BE
INSTALLED IN ACCORDANCE WITH THE LATEST EDITIONS OF THE
INTERNATIONAL PLUMBING CODE AND THE AMERICANS WITH DISABILITIES
ACT GUIDELINES (CURRENT EDITION)
" 4
5"
FIRE ALARM DEVICE
THERMOSTAT OR CARD READER
DIMMER LIGHT SWITCH
DATA / TEL. / ELECTRICAL OUTLET
SEE DOOR SCHED.
S E
E D
O O
R S
C H
E D
.7
M A
X
M
A X
E
Q E
Q
DOOR PUSH / PULL BAR
LOCKSET STRIKE
CENTER ALL EQUIPMENT VERTICALLY, TYP
SEE DOOR SCHED.
S E
E D
O O
R S
C H
E D
8" MAX.
LOCATIONS WITH MULTIPLE OUTLETS
EQ EQ
DATA / TEL. / ELECTRICAL OUTLET
HORIZONTALLY MOUNTED, TYP. @ COUNTERS
LOCATIONS WITH MULTIPLE OUTLETS
FINISH COUNTERTOP SURFACE
FIRE EXTINGUISHER TYPE 2-A, AND ABAAS 1HR RATED
SEMI RECESSED FIRE EXTINGUISHER CABINET. B.O.D.
LARSEN 'S ARCHITECTURAL SERIES, FIRE RATED
VERTICAL DUO, STAINLESS STEEL, SQUARE TRIM 1 1/2",
SEMI RECESSED SS FS2409-5R RESTABLISH PARTITION
FIRE RATING AROUND THE NEW FEC OPENING.
FIRE EXTINGUISHER TYPE 2-A AND ABAAS RECESSED
FIRE EXTINGUISHER CABINET. B.O.D. LARSEN 'S
ARCHITECTRUAL SERIES, VERTICAL DUO, STAINLESS
STEEL, FLAT TRIM FULLY RECESSED 2409-R1.
FIRE EXTINGUISHER TYPE 2-A, AND ABAAS RECESSED
FIRE EXTINGUISHER CABINET. B.O.D. LARSEN 'S
ARCHITECTURAL SERIES, VERTICAL DUO, STAINLESS
STEEL, SQUARE TRIM 1 1/2", SEMI RECESSED 2409-5R.
0 4' 8' 1/4"=1'-0"
KEY NOTES
GENERAL NOTES
LEGEND
CHECKED BY
DRAWN BY
FLOOR NUMBER
DRAWING TITLE
SHEET
NUMBER
SUBMISSION DATE
SUBMISSION STAGE
GSA PM
GSA PROJECT NO.
PROJECT
DESCRIPTION
PROJECT TITLE
BUILDING NAME
ADDRESS
BUILDING NUMBER
PRIME CONTR. NO.
PRIME ORDER NO.
CONST. CONTR.
A/E
SUB A/E
CONST. CONTR. NO.
SHEET SIZE:
DATE DRAWN:
36 X 48
S H
E E
T
ID
E N
TI
FI
C A
TI
O
N
DISCIPLINE
P R
O
JE
C T
ID
E
N
TI
FI
C
A
TI
O N
B U
IL
D
IN
G
BIM FILE NAME
C O
N
TR
A C
TO
R
S R
E V
IS
IO
N B
LO
C
K G
R A
P H
IC
S
C A
LE
K
E Y
P
LA
N S
TA
M
P O
R S
E A
L D
E S
IG
N
E R
ID
E
N
TI
FI
C
A
TI
O N
O W
N E
R
ID
E N
TI
FI
C A
TI
O
N
SHEET OF SHEETS
KRUECK & SEXTON ARCHITECTS, P.C.
400 MARYLAND AVENUE, SW
WASHINGTON, DC 20024
LYNDON B. JOHNSON FEDERAL BUILDING
DC0010ZZ
DC0010_A_3-4-6-7_r2020.rvt
WSP ENGINEERING
DEPARTMENT OF EDUCATION
CONSOLIDATION PROJECT
ISSUED FOR BID
HALLIE FUTTERMAN
RENOVATION OF FLOORS 3, 4, 6, & 7 OF THE EXISTING
BUILDING TO MEET THE DEPARTMENT OF
EDUCATION’S PROGRAMMATIC REQUIREMENTS.
GS-07-P-16-UC-D-7000
47PM0520F0002
47PM0520F0002
KRUECK & SEXTON ARCHITECTS
221 W ERIE ST
CHICAGO, IL 60654 (312) 787-0056
ARCHITECT
WSP ENGINEERING
ONE PENNSYLVANIA PLAZA, SECOND FLOOR
NEW YORK, NY 10119 (212) 465-5000
MEP ENGINEER
ATELIER TEN
45 E 20TH ST, 4TH FLOOR
NEW YORK, NY 10003 (312) 386-1400
SUSTAINABILITY CONSULTANT
THRESHOLD ACOUSTICS
141 W JACKSON BLVD, SUITE 2080
CHICAGO, IL 60604 (312) 386-1400
ACOUSTIC CONSULTANT
WEST EAST
M A
TC
H
LI
N
E
GENERAL SERVICES ADMINISTRATION
NATIONAL CAPITAL REGION
PUBLIC BUILDING SERVICE, D.C. SERVICES DIV.
7TH & D STREET, S.W.
WASHINGTON, D.C. 20407
ISSUE
NO. DATE ISSUE
ARCHITECTURAL
VARIES, SEE DRAWINGS
04/23/2021
2020 - 2021
FORCADE DESIGN
1626 PAYNE STREET
EVANSTON, IL 60201 (847) 448-4270
ENVIRONMENTAL GRAPHICS CONSULTANT
/2
/2
:0
:3
P
M
A-51-01
MOUNTING HEIGHTS
RT + VW + SK
AC + SP
04/23/2021
05/07/2021
05/21/2021
ISSUED FOR BID
△2: ADDENDUM 01
△3: REVISION 2, ADDENDUM No. 2
1/4" = 1'-0"
MOUNTING HEIGHTS - PLUMBING FIXTURES
1/4" = 1'-0"
MOUNTING HEIGHTS - TOILET / BATH ACCESSORIES
1/4" = 1'-0"
MOUNTING HEIGHTS - SPECIALTY EQUIPMENT
1/2" = 1'-0"3
STANDARD ALIGNMENT RELATIONSHIP
RESTROOMS ACCESSORIES SCHEDULE
Type Mark ITEM Description Manufacturer Model Selection Type Comments
AP-1 RESTROOMS 16x12 General Purpose Access Panel Cendrex 16x12. General Purpose Access Door for all access types Satin Stainless Steel Outside perimeter of flange to be aligned with tile grout. Provide blocking behind flange so the back side of flange is flush with face of tile.
CU-1 RESTROOMS Combination Unit: 2-Stall Seat Cover/Toilet Tissue Dispenser Bradley Corporation 592 Satin Stainless Steel Refer to Plan for door swing location and spindle hand.
CU-2 RESTROOMS Combination Unit: 1 Stall Seat Cover/ Toilet Tissue Dispenser Bradley Corporation 5922-10 Semirecessed Satin Stainless Steel Refer to Plan for door swing location and spindle hand.
CU-3 RESTROOMS Combination Unit: 2 Stall Toilet Tissue Dispenser Bradley Corporation 5422 Semirecessed Satin Stainless Steel Semi-Recessed
CU-4 RESTROOMS Combination Unit: 2-Stall Toilet Tissue Dispenser, Napkin Disposal Bradley Corporation 594 Satin Stainless Steel Refer to Plan for door swing location and spindle hand.
CU-5 RESTROOMS Combination Unit: 2 Stall Seat Cover, Tissue Dispenser & Napkin Disposal Bradley Corporation 591 Satin Stainless Steel Refer to Plan for door swing location and spindle hand.
FEC
GB-1 RESTROOMS 36" stainless steel grab bar Bobrick B-5806-36 Brushed Stainless Steel Provide blocking on wall as required
GB-2 RESTROOMS 42" stainless steel grab bar Bobrick B-5806-48 Brushed Stainless Steel Provide blocking on wall as required
GB-3 PRIVATE RESTROOMS 36" and 42" set stainless steel grab bars Seachrome Series 790 Series Straight Grab bars Stainless Steel Polished Provide blocking on wall as required
GL-07 PRIVATE RESTROOMS Frameless Mirror - see elevation Refer to elevations
HK-1 RESTROOMS Stainless steel hook Bobrick B-549 Brushed Stainless Steel At Barrier Free Stalls provide two (barrier free height and standard)_, for standard stalls, provide only one at standard height.
HK-2 PRIVATE RESTROOMS Hook at Private Restroom Kallista One Chrome Provide 2 (ABAAS height and Standard Height).
MR-1 RESTROOMS Framed LED lit mirror Bobrick B-167 2436 Stainless Steel Integral L1 light fixture. Refer to lighting schedule.
MR-2 RESTROOMS Framed Mirror Bobrick B-165 24"x60"
PTD-1 PANTRY AND MOTHER'S
ROOM
Paper Towel Dispenser Bobrick B-526 Brushed Stainless Steel Provided by GC
PTD-2 RESTROOMS TrimLineSeries™ Surface Mount Paper Towel Dispenser Bradley Corporation 250-15 Brushed Stainless Steel
SC-1 RESTROOMS Seat Cover Dispenser -Stall mount Bradley Corporation 582 Brushed Stainless Steel
TP-1 PRIVATE RESTROOMS Toilet Paper at Private Restroom Kallista One Chrome
TPT-1 RESTROOMS Floor mount toilet partition system 9" bottom gap. Bobrick Privada HPL - refer to finish schedule for type
Provide 9" bottom gap. Provide occupancy indicator and recessed leg. Alternate #
2. Bradley Corporation Series 500 (9" bottom gap)
TPT-2 RESTROOMS Floor mount toilet partition system 4" bottom gap. Bobrick Privada HPL - refer to finish schedule for type
Provide 4" bottom gap. Provide occupancy indicator and recessed leg. Alternate #
2. Bradley Corporation Series 500 (9" bottom gap)
UPT-1 RESTROOMS Wall mount urinal partition Bobrick Privada HPL - refer to finish schedule for type
1'-6" deep. Alternate #2. Bradley Corporation/ B00- Stainless Steel and cont.
hinges.
WR-1 RESTROOMS 6" Diam Circular Waste Chute and Waste Receptacle Mocket /Simplehuman TM1A stainless steel - 6" deep / 23 Gal 30.9" H x 15.5" W x 16.5" D/ receptacle: Slim Oval Top Can - 13 Gal. (27" H)
Satin Stainless Steel / Satin Stainless Steel
Provide Simplehuman Slim Oval Top Can - 13 Gallon Brushed SS (27" H)
WR-2 RESTROOMS TrimLineSeries™ Recessed Waste Receptacle Bobrick B-35643 Satin Stainless Steel
PLUMBING FIXTURES SCHEDULE
Type Mark Areas Description Manufacturer Model Finish / Color Type Comments
DF-1 Corridor Water Cooler - dual height w/ bottle filler (Refrigerated)
Elkay LZWS-LRPBM28K Stainless Steel Coordinate and verify in field the chase clearance to meet manfu. requirements.
FA-1 Public Restrooms Faucet and Soap Dispenser at Restrooms Bradley Corporation Metro Serie Verge S53-3300 (0.35GPM), 6-3300
Satin Stainless Steel Soap Dispenser to be single Top Fill, Pair with LAV-1, Power source to be hardwired
FA-2 Mother's Room Faucet and Soap Dispenser at…