GSA-DoED_Addendum-02_MEP_5.24.21.pdf

PDF 7 MB Posted

Attached to
Solicitation Notice - LBJ Consolidation & Switchgear Federal contract opportunity
Solicitation number
47PM0121R0013
Issued by
General Services Administration Public Buildings Service

About this file

This is a solicitation notice for a construction contract to renovate floors 3, 4, 6, and 7 of the Lyndon B. Johnson Federal Building to consolidate the Department of Education. The scope of work includes interior alterations, open office construction, HVAC and electrical upgrades including a new switchgear system. The contract type is firm-fixed price. The NAICS code is 236220 and small business size standard is $39.5M average annual receipts. A virtual pre-proposal conference will be held on May 5th and proposals are due by June 4th. The solicitation and any amendments will be posted on SAM.gov. Interested firms must register in SAM. The selection process will follow FAR Part 15 procedures. No site visits will be conducted but the project site can be viewed virtually using the included StructionSite link.

View the file

Other files for this federal contract opportunity

Other files attached to Solicitation Notice - LBJ Consolidation & Switchgear, newest first.
File Type Posted
Bid Spreadsheet_Rev_6.7.21.xlsx XLSX spreadsheet
SF30 47PM0121R0013_0004.pdf PDF
AS-50-06 - Sign Types Detail Sheet.pdf PDF
RFIs (Round 2) and Response 6.4.21.pdf PDF
SF30 47PM0121R0013_0003.pdf PDF
PBS Past Performance Form.docx DOCX document
Solicitation 47PM0121R0013 revised 20210525.pdf PDF
SF30 47PM0121R0013_0002.pdf PDF
RFI and Response_5.24.21.pdf PDF
WageDet DC20210002 20210507.pdf PDF
GSA-DoED_Addendum-02_5.24.21.pdf PDF
014000 Quality Assurance and Control_5.24.21 Revision.pdf PDF
Bid Spreadsheet_Rev 1_5.24.21.xlsx XLSX spreadsheet
SF30 47PM0121R0013_0001.pdf PDF
PreProposal Minutes Attendee List.pdf PDF
1914_GSA-DoED_Issue for Bid - Architectural_210423_Vol 1 SMALL.pdf PDF
GSA LBJ DoED IFB SPEC Vol 1rev.pdf PDF
LBJ 1959 Full Set Vol 2.pdf PDF
LBJ 1995 Architectural Set.pdf PDF
1914_GSA-DoED_Issue for Bid - Architectural_210423_Vol 2.pdf PDF
1914_GSA-DoED_Issue for Bid - Architectural_210423_Vol 3.pdf PDF
LBJ 1959 Full Set Vol 1.pdf PDF
SOW LBJ Consolidation Construction Services.pdf PDF
Instructions LBJ Virtual Site Walk READ ME.pdf PDF
Drawings - ARCH Vol 1.pdf PDF
Drawing - Signage.pdf PDF
Drawing - TELE.pdf PDF
1914_GSA-DoED_Switchgear - Electrical_210423.pdf PDF
Layout for staging - switchgear.pdf PDF
2019.07.12_LBJ_BPP 100% Submission.pdf PDF
Solicitation 47PM0121R0013.pdf PDF
Reps and Certs 47PM0121R0013.pdf PDF
Drawing - PLUM.pdf PDF
SPEC Vol 1 GSA LBJ DoED.pdf PDF
SPEC Vol 2 GSA LBJ DoED.pdf PDF
LBJ_2ndFl_bathrooms-Staging.pdf PDF
GSA527.pdf PDF
Drawing - HVAC.pdf PDF
Drawing - FA.pdf PDF
Drawing - ELEC.pdf PDF
Drawing - AV.pdf PDF
1914_GSA-DoED_L2 L5 - Combined_210423.pdf PDF
Contractor Site Office.pdf PDF
Narrative Modernization Issue for Bid LBJ 2021April23.pdf PDF
SF1442 47PM0121R0013.pdf PDF
Agreement (draft) RFP 47PM0121R0013.pdf PDF
Bid Spreadsheet.xlsx XLSX spreadsheet
Drawings - ARCH Vol 2.pdf PDF
Drawing - FP.pdf PDF
LBJ_5thFl_bathrooms-Staging.pdf PDF
Show all 50

Solicitation Notice - LBJ Consolidation & Switchgear has more files on GovTribe.

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

EF

MPP-1

M

M

M

M

TAHU-6

AHU-2

AHU-5

AHU-1

1" FOS/FOR

MUFFLER

40x40 OA

DUCT

THROUGH

ROOF TO

GOOSENECK

50 SF NFA

EXHAUST

LOUVER

8" EXHAUST

PIPE WITH 90

DEGREE

ELBOW UP

PROVIDE 400

GALLON

DAYTANK

WITH

TRANSFER

PUMP SET.

PREFERRED

UTILITIES

MODEL 11871

350 KW

GENERATOR

(SEE

ELECTRICAL

DRAWINGS)

PIPE IN PIPE 1"

FOS/FOR LINE

RUN IN 7TH

FLOOR

CEILING

PLENUM TO

FUEL OIL

RISER

ALD-R-2ALD-R-1

16" X 18" UP TO

ROOF EXHAUST FAN

EE

EE

XX� CWS/R UP

TO ROOFTOP

GENERATOR

RADIATOR

PROVIDE HEAT

EXCHANGERS, PIPING

AND ALL ASSOCIATED

APPURTENANCES

REQUIRED BY

MANUFACTURER

REMOVE &

RELOCATE

EXISTING

EF-23 ALONG

WITH STARTER

EXISTING

ENERGY

RECOVERY

PIPING TO

REMAIN

PROVIDE NEW

15000 CFM

EXHAUST FAN

1211109876543

A

B

C

D

E

SUB-STATION NO. 4

P 8

MA

TC

HL

IN

E

PENTHOUSE POWER PLAN (WEST)

SCALE: 1/8" = 1'-0"

0 8' 16' 1/8"=1'-0"

TRUE NORTH

PLAN NORTH

CHECKED BY

DRAWN BY

FLOOR NUMBER

DRAWING TITLE

SHEET

NUMBER

SUBMISSION DATE

SUBMISSION STAGE

GSA PM

GSA PROJECT NO.

PROJECT

DESCRIPTION

PROJECT TITLE

BUILDING NAME

ADDRESS

BUILDING NUMBER

PRIME CONTR. NO.

PRIME ORDER NO.

CONST. CONTR.

A/E

SUB A/E

CONST. CONTR. NO.

SHEET SIZE:

DATE DRAWN:

36 X 48

SH

EE

T I

DE

NT

IFI

CA

TIO

N

DISCIPLINE

PR

OJ

EC

T

ID

EN

TIF

IC

AT

IO

N

BU

ILD

IN

G

BIM FILE NAME

CO

NT

RA

CT

OR

S

RE

VI

SI

ON

B

LO

CK

GR

AP

HI

C

SC

AL

E

KE

Y

PL

AN

ST

AM

P

OR

S

EA

L

DE

SI

GN

ER

ID

EN

TIF

IC

AT

IO

N

OW

NE

R

ID

EN

TIF

IC

AT

IO

N

SHEET OF SHEETS

KRUECK & SEXTON ARCHITECTS, P.C.

400 MARYLAND AVENUE, SW

WASHINGTON, DC 20024

LYNDON B. JOHNSON FEDERAL BUILDING

DC0010ZZ

DC0010_M_3-4-6-7_r2020.rvt

WSP ENGINEERING

DEPARTMENT OF EDUCATION

CONSOLIDATION PROJECT

ISSUED FOR BID

HALLIE FUTTERMAN

RENOVATION OF FLOORS 3, 4, 6, & 7 OF THE EXISTING

BUILDING TO MEET THE DEPARTMENT OF

EDUCATION’S PROGRAMMATIC REQUIREMENTS.

GS-07-P-16-UC-D-7000

47PM0520F0002

47PM0520F0002

KRUECK & SEXTON ARCHITECTS

221 W ERIE ST

CHICAGO, IL 60654 (312) 787-0056

ARCHITECT

WSP ENGINEERING

ONE PENNSYLVANIA PLAZA, SECOND FLOOR

NEW YORK, NY 10119 (212) 465-5000

MEP ENGINEER

ATELIER TEN

45 E 20TH ST, 4TH FLOOR

NEW YORK, NY 10003 (312) 386-1400

SUSTAINABILITY CONSULTANT

THRESHOLD ACOUSTICS

141 W JACKSON BLVD, SUITE 2080

CHICAGO, IL 60604 (312) 386-1400

ACOUSTIC CONSULTANT

WEST EAST

MA

TC

HL

IN

E

GENERAL SERVICES ADMINISTRATION

NATIONAL CAPITAL REGION

PUBLIC BUILDING SERVICE, D.C. SERVICES DIV.

7TH & D STREET, S.W.

WASHINGTON, D.C. 20407

ISSUE

NO. DATE ISSUE

MECHANICAL

VARIES, SEE DRAWINGS

01 04/23/2021 ISSUED FOR BID

FORCADE DESIGN

1626 PAYNE STREET

EVANSTON, IL 60201 (847) 448-4270

5/

/2

4:

:4

PM

M-18-01

MECHANICAL GENERATOR PLAN - PENTHOUSE - WEST

4/23/21

04/23/21NM

PB

1/8" = 1'-0"1 Mechanical PENTHOUSE - WEST

12 13 14 15 16 17 18 19 20 21

D

E

C

B

A

PENTHOUSE POWER PLAN (EAST)

SCALE: 1/8" = 1'-0"

12 13 14 15 16 17 18 19 20 21

D

E

C

B

A

PENTHOUSE POWER PLAN (EAST)

SCALE: 1/8" = 1'-0"

MPP-1

M

M

M

M

AHU-6

AHU-2

AHU-5

AHU-1

EXISTING 1 1_

2" FUEL OIL RISER

PIPE IN PIPE 1"

FOS/FOR LINE

RUN IN 7TH

FLOOR

CEILING

PLENUM TO

GENERATOR

0 1' 2' 1 1/2"=1'-0"

TRUE NORTH

PLAN NORTH

CHECKED BY

DRAWN BY

FLOOR NUMBER

DRAWING TITLE

SHEET

NUMBER

SUBMISSION DATE

SUBMISSION STAGE

GSA PM

GSA PROJECT NO.

PROJECT

DESCRIPTION

PROJECT TITLE

BUILDING NAME

ADDRESS

BUILDING NUMBER

PRIME CONTR. NO.

PRIME ORDER NO.

CONST. CONTR.

A/E

SUB A/E

CONST. CONTR. NO.

SHEET SIZE:

DATE DRAWN:

36 X 48

SH

EE

T I

DE

NT

IFI

CA

TIO

N

DISCIPLINE

PR

OJ

EC

T

ID

EN

TIF

IC

AT

IO

N

BU

ILD

IN

G

BIM FILE NAME

CO

NT

RA

CT

OR

S

RE

VI

SI

ON

B

LO

CK

GR

AP

HI

C

SC

AL

E

KE

Y

PL

AN

ST

AM

P

OR

S

EA

L

DE

SI

GN

ER

ID

EN

TIF

IC

AT

IO

N

OW

NE

R

ID

EN

TIF

IC

AT

IO

N

SHEET OF SHEETS

KRUECK & SEXTON ARCHITECTS, P.C.

400 MARYLAND AVENUE, SW

WASHINGTON, DC 20024

LYNDON B. JOHNSON FEDERAL BUILDING

DC0010ZZ

DC0010_M_3-4-6-7_r2020.rvt

WSP ENGINEERING

DEPARTMENT OF EDUCATION

CONSOLIDATION PROJECT

ISSUED FOR BID

HALLIE FUTTERMAN

RENOVATION OF FLOORS 3, 4, 6, & 7 OF THE EXISTING

BUILDING TO MEET THE DEPARTMENT OF

EDUCATION’S PROGRAMMATIC REQUIREMENTS.

GS-07-P-16-UC-D-7000

47PM0520F0002

47PM0520F0002

KRUECK & SEXTON ARCHITECTS

221 W ERIE ST

CHICAGO, IL 60654 (312) 787-0056

ARCHITECT

WSP ENGINEERING

ONE PENNSYLVANIA PLAZA, SECOND FLOOR

NEW YORK, NY 10119 (212) 465-5000

MEP ENGINEER

ATELIER TEN

45 E 20TH ST, 4TH FLOOR

NEW YORK, NY 10003 (312) 386-1400

SUSTAINABILITY CONSULTANT

THRESHOLD ACOUSTICS

141 W JACKSON BLVD, SUITE 2080

CHICAGO, IL 60604 (312) 386-1400

ACOUSTIC CONSULTANT

WEST EAST

MA

TC

HL

IN

E

GENERAL SERVICES ADMINISTRATION

NATIONAL CAPITAL REGION

PUBLIC BUILDING SERVICE, D.C. SERVICES DIV.

7TH & D STREET, S.W.

WASHINGTON, D.C. 20407

ISSUE

NO. DATE ISSUE

MECHANICAL

VARIES, SEE DRAWINGS

01 04/23/2021 ISSUED FOR BID

FORCADE DESIGN

1626 PAYNE STREET

EVANSTON, IL 60201 (847) 448-4270

5/

/2

3:

:5

PM

M-18-02

MECHANICAL GENERATOR PLAN - PENTHOUSE - EAST

4/23/21

04/23/21Author

Checker

1/8" = 1'-0"1 Mechanical PENTHOUSE - EAST

SCOPE OF WORK

THE SCOPE OF WORK (SOW) AREAS FOR THIS PROJECT IS TO

REPLACE LIGHTING, POWER AND FIRE ALARM FOR FLOOR’S 3, 4,

6 AND 7TH FLOOR EXCEPT FOR THE EXISTING ELECTRICAL

ROOMS (8 PER FLOOR), TELECOM ROOMS (8 PER FLOOR),

STAIRWELLS, AND THE JANITOR’S CLOSETS. AS AN ADD

ALTERNATE WE ARE SHOWING A NEW STANDBY GENERATOR,

WHICH IS TO BE INSTALLED IN THE ROOF PENTHOUSE. ALSO,

INCLUDED THE ADD ALTERNATE IS THE NEW DISTRIBUTION FOR

THE STANDBY GENERATOR.

POWER - THE CONTRACTOR IS TO DEMOLISH ALL EXISTING

POWER CABLES FROM THE DEVICES ON THE FLOOR TO THE

EXISTING POWER PANELS IN THE ELECTRICAL CLOSETS FOR ALL

THE AREAS THAT ARE IN THE SOW. ALL NEW POWER WOULD BE

PROVIDED FROM THE EXISTING POWER PANELS AS SHOWN ON

THE CONTRACT DRAWINGS. THE ONLY EXCEPTION IS TO

PROVIDE NEW POWER PANEL FOR THE 7TH FLOOR SECURITY

ROOMS. ALL WORK IS TO BE DONE ONE FLOOR AT A TIME

EXCEPT FOR THE 7TH FLOOR. THE 7TH FLOOR WILL BE DONE IN 2

PHASES PER THE MATCH LINES INDICATED ON THE CONTRACT

DRAWINGS.

AS PART OF THE SCOPE OF WORK FOR THE 3RD, 4TH, 6TH FLOOR

TO THE EXISTING ELECTRICAL PANELS, THE EXISTING 2 SECTION

RP PANELS WILL NEED TO BE SEPARATED AND REFED WITHIN

THE ELECTRICAL CLOSET AS SHOWN ON THE ELECTRICAL

DETAIL SHEETS. ONE SECTION WILL FEED THE UN-SWITCHED

120/208 VOLT LOADS AND THE OTHER SECTION WILL FEED

SWITCHED LOADS. FOR THE 7TH FLOOR, SEVERAL 8 POLE

CONTACTORS PER PANEL SHALL BE PROVIDED TO CONTROL

THE CONTROLLED RECEPTACLES. ALL CONTACTOR SHALL BE

CONTROLLED BY BMS TIME CLOCK.

LIGHTING – ALL EXISTING ALL LIGHTING IS TO BE CONTROLLED

BY OCCUPANCY, DAYLIGHTING OR VACANCY SENSORS. THE

ENCLOSED 10’ BY 10’ OFFICES SHALL BE PROVIDED WITH

VACANCY SENSORS THAT WILL CONTROL 1 LIGHT FIXTURE. THE

10’ BY 15’ OFFICES WILL 2 LIGHT FIXTURES.

THE OVERALL AREA AND EMERGENCY LIGHTING SHALL BE

LOCALLY CONTROLLED BY ZONES AS SHOWN ON THE

CONTRACT DRAWINGS. A TYPICAL ZONE WILL HAVE

OCCUPANCY SENSORS, CORRIDOR SENSORS AND DAY LIGHT

SENSORS. THE CORRIDOR SENSOR WILL TURN ON ONLY THE

CORRIDOR LIGHT. THE DAY LIGHT SENSORS WILL DIM ONLY THE

FIRST ROW OF LIGHTS CLOSEST TO THE PERIMETER FAÇADE.

ONCE A PERSON ENTERS THE RESPECTIVE ZONE, THE

OCCUPANCY SENSOR WILL KEEP THE CORRIDOR LIGHT ON AND

TRIGGER THE OTHER 2 ROWS OF LIGHTS TO TURN ON. THIS

WILL THEN ALLOW DAYLIGHT SENSOR TO DIM THE DAY LIGHT

CONTROLLED LIGHT FIXTURE ONLY IF THE OVERALL ZONE IS

ACTIVATED. BATHROOMS SHALL HAVE ULTRASONIC TYPE

SENSORS. CONFERENCE ROOMS SHALL BE PROVIDED WITH 2

SLIDE DIMMERS AND A VACANCY SENSOR. THIS WILL ALLOW

FOR YOU TO ADJUST THE LIGHT LEVEL AS NEEDED IN THE

CENTER ABOVE THE CONFERENCE ROOM DESK OR THE ACCENT

LIGHT IN THE REAR OF THE CONFERENCE ROOM

INDEPENDENTLY.

PHASING – ALL FLOORS SHALL BE DONE ONE COMPLETE FLOOR

AT A TIME EXCEPT FOR THE 7TH FLOOR. THIS FLOORS SHALL BE

DONE IN 2 PHASES AS SHOWN ON THE CONTRACT DRAWING’S.

0 - - N.T.S.

CHECKED BY

DRAWN BY

FLOOR NUMBER

DRAWING TITLE

SHEET

NUMBER

SUBMISSION DATE

SUBMISSION STAGE

GSA PM

GSA PROJECT NO.

PROJECT

DESCRIPTION

PROJECT TITLE

BUILDING NAME

ADDRESS

BUILDING NUMBER

PRIME CONTR. NO.

PRIME ORDER NO.

CONST. CONTR.

A/E

SUB A/E

CONST. CONTR. NO.

SHEET SIZE:

DATE DRAWN:

36 X 48

S H

E E

T

ID

E N

TI

FI

C A

TI

O

N

DISCIPLINE

P R

O

JE

C T

ID

E

N

TI

FI

C

A

TI

O N

B U

IL

D

IN

G

BIM FILE NAME

C O

N

TR

A C

TO

R

S R

E V

IS

IO

N B

LO

C

K G

R A

P H

IC

S

C A

LE

K

E Y

P

LA

N S

TA

M

P O

R S

E A

L D

E S

IG

N

E R

ID

E

N

TI

FI

C

A

TI

O N

O W

N E

R

ID

E N

TI

FI

C A

TI

O

N

SHEET OF SHEETS

KRUECK & SEXTON ARCHITECTS, P.C.

400 MARYLAND AVENUE, SW

WASHINGTON, DC 20024

LYNDON B. JOHNSON FEDERAL BUILDING

DC0010ZZ

DC0010_E_3-4-6-7_r2020.rvt

WSP ENGINEERING

DEPARTMENT OF EDUCATION

CONSOLIDATION PROJECT

ISSUED FOR BID

HALLIE FUTTERMAN

RENOVATION OF FLOORS 3, 4, 6, & 7 OF THE EXISTING

BUILDING TO MEET THE DEPARTMENT OF

EDUCATION’S PROGRAMMATIC REQUIREMENTS.

GS-07-P-16-UC-D-7000

47PM0520F0002

47PM0520F0002

KRUECK & SEXTON ARCHITECTS

221 W ERIE ST

CHICAGO, IL 60654 (312) 787-0056

ARCHITECT

WSP ENGINEERING

ONE PENNSYLVANIA PLAZA, SECOND FLOOR

NEW YORK, NY 10119 (212) 465-5000

MEP ENGINEER

ATELIER TEN

45 E 20TH ST, 4TH FLOOR

NEW YORK, NY 10003 (312) 386-1400

SUSTAINABILITY CONSULTANT

THRESHOLD ACOUSTICS

141 W JACKSON BLVD, SUITE 2080

CHICAGO, IL 60604 (312) 386-1400

ACOUSTIC CONSULTANT

WEST EAST

M A

TC

H

LI

N

E

GENERAL SERVICES ADMINISTRATION

NATIONAL CAPITAL REGION

PUBLIC BUILDING SERVICE, D.C. SERVICES DIV.

7TH & D STREET, S.W.

WASHINGTON, D.C. 20407

ISSUE

NO. DATE ISSUE

ELECTRICAL

VARIES, SEE DRAWINGS

01 04/23/2021 ISSUED FOR BID

FORCADE DESIGN

1626 PAYNE STREET

EVANSTON, IL 60201 (847) 448-4270

ENVIRONMENTAL GRAPHICS CONSULTANT

/2

/2

:0

:4

P

M

E-00-01

ELECTRICAL DRAWING LIST, SCOPE OF WORK & NOTES

04/23/2021

04/23/21NJA

RO

1 62

ELECTRICAL DRAWING LIST

DRAWING NO. DESCRIPTION

E-00-01 ELECTRICAL DRAWING LIST, SCOPE OF WORK & NOTES

E-00-02 ELECTRICAL LEGENDS, SYMBOLS & ABBREVIATIONS

ELD-13-00 ELECTRICAL DEMOLITION LIGHTING PLAN - LEVEL 3 - OVERALL

ELD-14-00 ELECTRICAL DEMOLITION LIGHTING PLAN - LEVEL 4 - OVERALL

ELD-16-00 ELECTRICAL DEMOLITION LIGHTING PLAN - LEVEL 6 - OVERALL

ELD-17-00 ELECTRICAL DEMOLITION LIGHTING PLAN - LEVEL 7 - OVERALL

EPD-13-01 ELECTRICAL DEMOLITION POWER 3RD, 4TH & 6TH FLOOR PLANS - WEST

EPD-13-02 ELECTRICAL DEMOLITION POWER 3RD, 4TH & 6TH FLOOR PLANS - EAST

EPD-17-01 ELECTRICAL DEMOLITION POWER 7TH FLOOR PLAN - WEST

EPD-17-02 ELECTRICAL DEMOLITION POWER 7TH FLOOR PLAN - EAST

EL-13-00 ELECTRICAL LIGHTING PLAN - LEVEL 3 - OVERALL

EL-13-01 ELECTRICAL LIGHTING PLAN - LEVEL 3 - WEST

EL-13-02 ELECTRICAL LIGHTING PLAN - LEVEL 3 - EAST

EL-14-00 ELECTRICAL LIGHTING PLAN - LEVEL 4 - OVERALL

EL-14-01 ELECTRICAL LIGHTING PLAN - LEVEL 4 - WEST

EL-14-02 ELECTRICAL LIGHTING PLAN - LEVEL 4 - EAST

EL-16-00 ELECTRICAL LIGHTING PLAN - LEVEL 6 - OVERALL

EL-16-01 ELECTRICAL LIGHTING PLAN - LEVEL 6 - WEST

EL-16-02 ELECTRICAL LIGHTING PLAN - LEVEL 6 - EAST

EL-17-00 ELECTRICAL LIGHTING PLAN - LEVEL 7 - OVERALL

EL-17-01 ELECTRICAL LIGHTING PLAN - LEVEL 7 - WEST

EL-17-02 ELECTRICAL LIGHTING PLAN - LEVEL 7 - EAST

EP-13-00 ELECTRICAL POWER PLAN - LEVEL 3 - OVERALL

EP-13-01 ELECTRICAL POWER PLAN - LEVEL 3 - WEST

EP-13-02 ELECTRICAL POWER PLAN - LEVEL 3 - EAST

EP-14-00 ELECTRICAL POWER PLAN - LEVEL 4 - OVERALL

EP-14-01 ELECTRICAL POWER PLAN - LEVEL 4 - WEST

EP-14-02 ELECTRICAL POWER PLAN - LEVEL 4 - EAST

EP-16-00 ELECTRICAL POWER PLAN - LEVEL 6 - OVERALL

EP-16-01 ELECTRICAL POWER PLAN - LEVEL 6 - WEST

EP-16-02 ELECTRICAL POWER PLAN - LEVEL 6 - EAST

EP-17-00 ELECTRICAL POWER PLAN - LEVEL 7 - OVERALL

EP-17-01 ELECTRICAL POWER PLAN - LEVEL 7 - WEST

EP-17-02 ELECTRICAL POWER PLAN - LEVEL 7 - EAST

EP-18-01 ELECTRICAL POWER PLAN - PENTHOUSE - WEST

E-23-01 ELECTRICAL ENLARGED PLANS - LEVEL 3 - WEST

E-23-02 ELECTRICAL ENLARGED PLANS - LEVEL 3 - EAST

E-24-01 ELECTRICAL ENLARGED PLANS - LEVEL 4 - WEST

E-24-02 ELECTRICAL ENLARGED PLANS - LEVEL 4 - EAST

E-26-01 ELECTRICAL ENLARGED PLANS - LEVEL 6 - WEST

E-26-02 ELECTRICAL ENLARGED PLANS - LEVEL 6 - EAST

E-27-01 ELECTRICAL ENLARGED PLANS - LEVEL 7 - WEST

E-27-02 ELECTRICAL ENLARGED PLANS - LEVEL 7 - EAST

E-50-00 EXISTING POWER RISER DIAGRAM - WEST

E-50-01 EXISTING POWER RISER DIAGRAM - EAST

E-50-02 EXISTING EMERGENCY RISER DIAGRAM

E-50-03 EMERGENCY RISER DIAGRAM - MODIFICATION

E-60-00 ELECTRICAL PANEL SCHEDULES - LEVEL 3 - WEST

E-60-01 ELECTRICAL PANEL SCHEDULES - LEVEL 3 - EAST

E-60-02 ELECTRICAL PANEL SCHEDULES - LEVEL 4 - WEST

E-60-03 ELECTRICAL PANEL SCHEDULES - LEVEL 4 - EAST

E-60-04 ELECTRICAL PANEL SCHEDULES - LEVEL 6 - WEST

E-60-05 ELECTRICAL PANEL SCHEDULES - LEVEL 6 - EAST

E-60-06 ELECTRICAL PANEL SCHEDULES - LEVEL 7 - WEST

E-60-07 ELECTRICAL PANEL SCHEDULES - LEVEL 7 - EAST

E-60-08 ELECTRICAL LIGHT FIXTURE SCHEDULE

E-60-09 ELECTRICAL PANEL SCHEDULES - EM RISER MOD

E-70-00 ELECTRICAL DETAILS 1

E-70-01 ELECTRICAL LIGHTING DETAILS 1

E-70-02 ELECTRICAL LIGHTING DETAILS 2

E-70-03 ELECTRICAL LIGHTING DETAILS 3

E-70-04 ELECTRICAL DETAILS 2

GENERAL NOTES:

1. CONTRACTOR TO REPLACE ALL BREAKERS IN ALL

EXISTING 3RD , 4TH , 6 AND 7TH FLOOR LPD, RPD, CPD

AND CPH POWER PANELS WITH NEW CIRCUIT BREAKERS.

0 - - N.T.S.

CHECKED BY

DRAWN BY

FLOOR NUMBER

DRAWING TITLE

SHEET

NUMBER

SUBMISSION DATE

SUBMISSION STAGE

GSA PM

GSA PROJECT NO.

PROJECT

DESCRIPTION

PROJECT TITLE

BUILDING NAME

ADDRESS

BUILDING NUMBER

PRIME CONTR. NO.

PRIME ORDER NO.

CONST. CONTR.

A/E

SUB A/E

CONST. CONTR. NO.

SHEET SIZE:

DATE DRAWN:

36 X 48

S H

E E

T

ID

E N

TI

FI

C A

TI

O

N

DISCIPLINE

P R

O

JE

C T

ID

E

N

TI

FI

C

A

TI

O N

B U

IL

D

IN

G

BIM FILE NAME

C O

N

TR

A C

TO

R

S R

E V

IS

IO

N B

LO

C

K G

R A

P H

IC

S

C A

LE

K

E Y

P

LA

N S

TA

M

P O

R S

E A

L D

E S

IG

N

E R

ID

E

N

TI

FI

C

A

TI

O N

O W

N E

R

ID

E N

TI

FI

C A

TI

O

N

SHEET OF SHEETS

KRUECK & SEXTON ARCHITECTS, P.C.

400 MARYLAND AVENUE, SW

WASHINGTON, DC 20024

LYNDON B. JOHNSON FEDERAL BUILDING

DC0010ZZ

DC0010_E_3-4-6-7_r2020.rvt

WSP ENGINEERING

DEPARTMENT OF EDUCATION

CONSOLIDATION PROJECT

ISSUED FOR BID

HALLIE FUTTERMAN

RENOVATION OF FLOORS 3, 4, 6, & 7 OF THE EXISTING

BUILDING TO MEET THE DEPARTMENT OF

EDUCATION’S PROGRAMMATIC REQUIREMENTS.

GS-07-P-16-UC-D-7000

47PM0520F0002

47PM0520F0002

KRUECK & SEXTON ARCHITECTS

221 W ERIE ST

CHICAGO, IL 60654 (312) 787-0056

ARCHITECT

WSP ENGINEERING

ONE PENNSYLVANIA PLAZA, SECOND FLOOR

NEW YORK, NY 10119 (212) 465-5000

MEP ENGINEER

ATELIER TEN

45 E 20TH ST, 4TH FLOOR

NEW YORK, NY 10003 (312) 386-1400

SUSTAINABILITY CONSULTANT

THRESHOLD ACOUSTICS

141 W JACKSON BLVD, SUITE 2080

CHICAGO, IL 60604 (312) 386-1400

ACOUSTIC CONSULTANT

WEST EAST

M A

TC

H

LI

N

E

GENERAL SERVICES ADMINISTRATION

NATIONAL CAPITAL REGION

PUBLIC BUILDING SERVICE, D.C. SERVICES DIV.

7TH & D STREET, S.W.

WASHINGTON, D.C. 20407

ISSUE

NO. DATE ISSUE

ELECTRICAL

VARIES, SEE DRAWINGS

01 04/23/2021 ISSUED FOR BID

FORCADE DESIGN

1626 PAYNE STREET

EVANSTON, IL 60201 (847) 448-4270

ENVIRONMENTAL GRAPHICS CONSULTANT

/2

/2

:3

:3

A M

E-60-07

ELECTRICAL PANEL SCHEDULES - LEVEL 7 - EAST

04/23/2021

06/28/20NJA

RO

55 61

RPC7 (SEC-1) RPC7 (SEC-2) CPC7 LPC7

RPD7 (SEC-1) RPD7 (SEC-2) CPD7 LPD7

RPG7 - CPG7 ERD7

RPH7 - CPH7 -

NOTES:

TOTAL ESTIMATED DEMAND: 35.1 97.5

TOTAL CONNECTED LOAD: 49.6 137.7

ADDED CONNECTED LOAD: 49.6

REMOVED CONNECTED LOAD: 0

EXISTING CONNECTED LOAD: 0

Receptacle 38960 VA 24480 VA kVA AMPS

LOAD CLASSIFICATION CONNECTED LOAD (VA)

ESTIMATED DEMAND

(VA)

PANEL TOTALS

130 A / 150 A / 136 A

C71#41 SPARE -- 20 1 0 / 0 1 20 -- SPARE C71#42

C71#39 SPARE -- 20 1 0 / 0 1 20 -- SPARE C71#40

C71#37 SPARE -- 20 1 0 / 0 1 20 -- SPARE C71#38

C71#35 SPARE -- 20 1 0 / 0 1 20 -- SPARE C71#36

C71#33 SPARE -- 20 1 0 / 0 1 20 -- SPARE C71#34

C71#31 SPARE -- 20 1 0 / 0 1 20 -- SPARE C71#32

C71#29 SPARE -- 20 1 0 / 0 1 20 -- SPARE C71#30

C71#27 SPARE -- 20 1 0 / 0 1 20 -- SPARE C71#28

C71#25 7C255 - FOCUS ROOM RECEPTACLES 360 20 1 360 / 0 1 20 -- SPARE C71#26

C71#23 7B214, 7B215, 7B216 - OFFICE RECEPT. 540 20 1 540 / 720 1 20 720 XXXXX - WORKSTATION 14 RECEPT. C71#24

C71#21 7B214, 7B215, 7B216 - OFFICE RECEPT. 540 20 1 540 / 720 1 20 720 XXXXX - WORKSTATION 14 RECEPT. C71#22

C71#19 7B210, 7B211, 7B212, 7B213 - RECEPT. 720 20 1 720 / 720 1 20 720 XXXXX - WORKSTATION 13 RECEPT. C71#20

C71#17 7B210, 7B211, 7B212, 7B213 - RECEPT. 720 20 1 720 / 720 1 20 720 XXXXX - WORKSTATION 13 RECEPT. C71#18

C71#15 7B253, 7B254, 7B255 - CONF. RECEPT. 720 20 1 720 / 540 1 20 540 XXXXX, XXXXX - CONV. RECEPTACLES C71#16

C71#13 7B253, 7B254, 7B255 - CONF. RECEPT. 720 20 1 720 / 540 1 20 540 XXXXX, XXXXX - CONV. RECEPTACLES C71#14

C71#11 7B250, 7B251, 7B252 - CONF. RECEPT. 720 20 1 720 / 720 1 20 720 XXXXX - WORKSTATION 12 RECEPT. C71#12

C71#9 7B250, 7B251, 7B252 - CONF. RECEPT. 720 20 1 720 / 720 1 20 720 XXXXX - WORKSTATION 12 RECEPT. C71#10

C71#7 7B153, 7B154, 7B155 - CONF. RECEPT. 720 20 1 720 / 720 1 20 720 XXXXX - WORKSTATION 11 RECEPT. C71#8

C71#5 7B153, 7B154, 7B155 - CONF. RECEPT. 720 20 1 720 / 720 1 20 720 XXXXX - WORKSTATION 11 RECEPT. C71#6

C71#3 7B150, 7B151, 7B152 - CONF. RECEPT. 720 20 1 720 / 720 1 20 720 XXXXX - WORKSTATION 10 RECEPT. C71#4

C71#1 7B150, 7B151, 7B152 - CONF. RECEPT. 720 20 1 720 / 720 1 20 720 XXXXX - WORKSTATION 10 RECEPT. C71#2

CKT

NO.

DESCRIPTION

TOTAL

LOAD

(VA)

CIRCUIT

BREAKER

AMPS / POLES

A B C

CIRCUIT

BREAKER

POLES /...

TOTAL

LOAD

(VA)

DESCRIPTION CKT

NO.

AIC RATING: 10000 A NUMBER OF SECTIONS: 1 POLES PER SECTION: 42

AIC AVAILABLE: PANEL LUGS: MCB FEED THROUGH LUGS: YES

VOLTAGE: 120/208 WYE MOUNTING: SURFACE 200% NEUTRAL: NO

MCB: 150A BUS TYPE: COPPER ISOLATED GROUND BUS: NO

MAIN BUS: 225 A ENCLOSURE: NEMA 1 GROUND BUS: YES

LOCATION: ELECTRICAL 7BEL3 WIRES: 4W + G NEUTRAL BUS: YES

EXIST: RPC7 (SEC-1) FED FROM: NORMAL

NOTES:

TOTAL ESTIMATED DEMAND: 34.6 96.1

TOTAL CONNECTED LOAD: 38.0 105.5

ADDED CONNECTED LOAD: 38

REMOVED CONNECTED LOAD: 0

Receptacle 16820 VA 13410 VA EXISTING CONNECTED LOAD: 0

Other 1440 VA 1440 VA kVA AMPS

LOAD CLASSIFICATION CONNECTED LOAD (VA)

ESTIMATED DEMAND

(VA)

PANEL TOTALS

83 A / 127 A / 115 A

D71#41 XXXXX - DEDICATED FOR... 1,000 20 1 1000 / 1452 -- -- -- -- D71#42

D71#39 XXXXX - DEDICATED FOR VAV'S 1,000 20 1 1000 / 1452 -- -- -- -- D71#40

D71#37 XXXXX - DEDICATED FOR VAV'S 1,000 20 1 1000 / 1452 3 25 4,356 XXXXX - AC-7-7 DISCONNECT D71#38

D71#35 -- -- -- -- 2050 / 180 1 20 180 XXXXX - AC-7-7 COND. PUMP RECEPT. D71#36

D71#33 7C289 - RESTROOM INST. HEATER... 4,100 30 2 2050 / 0 1 20 -- SPARE D71#34

D71#31 SPARE -- 20 1 0 / 0 1 20 -- SPARE D71#32

D71#29 SPARE -- 20 1 0 / 540 1 20 540 7C290 - OFFICE RECEPTACLES D71#30

D71#27 SPARE -- 20 1 0 / 1440 1 20 1,440 7C288 - OFFICE POKE-THRU D71#28

D71#25 SPARE -- 20 1 0 / 720 1 20 720 7C288 - DEPUTY SEC. OFFICE RECEPT. D71#26

D71#23 -- -- -- -- 4150 / 540 1 20 540 7C288, 7C289 - CONV. RECEPTACLES D71#24

D71#21 7C202 - PANTRY INST. HEATER DISC. 8,300 60 2 4150 / 720 1 20 720 7C284, 7C285, 7C286, 7C287 - T.V.'S D71#22

D71#19 7C293 - CHIEF OF SEC. RECEPT. & T.V. 540 20 1 540 / 720 1 20 720 7C284, 7C285, 7C286, 7C287 - RECEPT. D71#20

D71#17 7C202 - PANTRY RECEPTACLE 180 20 1 180 / 720 1 20 720 7C284, 7C285, 7C286, 7C287 - RECEPT. D71#18

D71#15 7C202 - PANTRY RECEPTACLE 180 20 1 180 / 720 1 20 720 XXXXX - WORKSTATION 17 RECEPT. D71#16

D71#13 7C202 - PANTRY PRINTER RECEPT. 1,000 20 1 1000 / 720 1 20 720 XXXXX - WORKSTATION 17 RECEPT. D71#14

D71#11 7C210, 7C211, 7C212 - RECEPTACLES 540 20 1 540 / 720 1 20 720 XXXXX - WORKSTATION 16 RECEPT. D71#12

D71#9 7C210, 7C211, 7C212 - RECEPTACLES 540 20 1 540 / 720 1 20 720 XXXXX - WORKSTATION 16 RECEPT. D71#10

D71#7 7C150 - CONF. FLOOR BOX RECEPT. 1,500 20 1 1500 / 720 1 20 720 XXXXX - WORKSTATION 15 RECEPT. D71#8

D71#5 7C150, 7C251 - CONF/HUDDLE RECEPT. 540 20 1 540 / 720 1 20 720 XXXXX - WORKSTATION 15 RECEPT. D71#6

D71#3 7C150, 7C251, 7C253 - CONV. RECEPT. 720 20 1 720 / 1000 1 20 1,000 XXXXX - COPY/PRINTER D71#4

D71#1 7C150, 7C252 - CONF./FOCUS RECEPT. 720 20 1 720 / 900 1 20 900 XXXXX, XXXXX - CONV. RECEPT. & T.V. D71#2

CKT

NO.

DESCRIPTION

TOTAL

LOAD

(VA)

CIRCUIT

BREAKER

AMPS / POLES

A B C

CIRCUIT

BREAKER

POLES /...

TOTAL

LOAD

(VA)

DESCRIPTION CKT

NO.

AIC RATING: 0 A NUMBER OF SECTIONS: POLES PER SECTION:

AIC AVAILABLE: PANEL LUGS: MCB FEED THROUGH LUGS: NO

VOLTAGE: 120/208 WYE MOUNTING: 200% NEUTRAL: NO

MCB: BUS TYPE: ISOLATED GROUND BUS: NO

MAIN BUS: 225 A ENCLOSURE: GROUND BUS: NO

LOCATION: Space 4A256 WIRES: 3W NEUTRAL BUS: NO

EXIST: RPD7 FED FROM:

NOTES:

TOTAL ESTIMATED DEMAND: 17.8 49.4

TOTAL CONNECTED LOAD: 22.6 62.7

ADDED CONNECTED LOAD: 22.6

REMOVED CONNECTED LOAD: 0

EXISTING CONNECTED LOAD: 0

Receptacle 19600 VA 14800 VA kVA AMPS

LOAD CLASSIFICATION CONNECTED LOAD (VA)

ESTIMATED DEMAND

(VA)

PANEL TOTALS

83 A / 56 A / 51 A

G7#41 7BEL2 - DEDICATED FOR THERMOSTAT 1,000 20 1 1000 / 0 1 20 -- SPARE G7#42

G7#39 7BEL2 - DEDICATED FOR VAV'S 1,000 20 1 1000 / 0 1 20 -- SPARE G7#40

G7#37 7BEL2 - DEDICATED FOR VAV'S 1,000 20 1 1000 / 0 1 20 -- SPARE G7#38

G7#35 SPARE -- 20 1 0 / 0 1 20 -- SPARE G7#36

G7#33 SPARE -- 20 1 0 / 0 1 20 -- SPARE G7#34

G7#31 SPARE -- 20 1 0 / 0 1 20 -- SPARE G7#32

G7#29 SPARE -- 20 1 0 / 0 1 20 -- SPARE G7#30

G7#27 SPARE -- 20 1 0 / 360 1 20 360 7CMEN - CONV. RECEPTACLES G7#28

G7#25 SPARE -- 20 1 0 / 1500 1 20 1,500 7CPN - EAST PANTRY MICROWAVE G7#26

G7#23 XXXXX - COPY/PRINTER 1,000 20 1 1000 / 180 1 20 180 7CPN - ABOVE COUNTER RECEPTACLE G7#24

G7#21 XXXXX - COPY/PRINTER 1,000 20 1 1000 / 180 1 20 180 7CPN - ABOVE COUNTER RECEPTACLE G7#22

G7#19 XXXXX - CONVENIENCE RECEPTACLES 1,080 20 1 1080 / 1500 1 20 1,500 7CPN - EAST PANTRY MICROWAVE G7#20

G7#17 XXXXX - WORKSTATION 30 RECEPT. 720 20 1 720 / 1000 1 20 1,000 7CPN - REFRIGERATOR G7#18

G7#15 XXXXX - WORKSTATION 30 RECEPT. 720 20 1 720 / 180 1 20 180 7B102 - COPY T.V. RECEPTACLE G7#16

G7#13 XXXXX, XXXXX - OFFICE RECEPT. 1,080 20 1 1080 / 1000 1 20 1,000 7B102 - COPY/PRINTER G7#14

G7#11 XXXXX - WORKSTATION 29 RECEPT. 720 20 1 720 / 180 1 20 180 7B100 - CORRIDOR WATER FOUNTAIN G7#12

G7#9 XXXXX - WORKSTATION 29 RECEPT. 720 20 1 720 / 1080 1 20 1,080 7BLV2, 7CPN - CONV. RECEPT. & T.V.'S G7#10

G7#7 XXXXX - WORKSTATION 28 RECEPT. 720 20 1 720 / 540 1 20 540 7B114, 7B115, 7B116 - OFFICE RECEPT. G7#8

G7#5 XXXXX - WORKSTATION 28 RECEPT. 720 20 1 720 / 540 1 20 540 7B114, 7B115, 7B116 - OFFICE RECEPT. G7#6

G7#3 XXXXX - WORKSTATION 27 RECEPT. 720 20 1 720 / 720 1 20 720 7B110, 7B111, 7B112, 7B113 - RECEPT. G7#4

G7#1 XXXXX - WORKSTATION 27 RECEPT. 720 20 1 720 / 720 1 20 720 7B110, 7B111, 7B112, 7B113 - RECEPT. G7#2

CKT

NO.

DESCRIPTION

TOTAL

LOAD

(VA)

CIRCUIT

BREAKER

AMPS / POLES

A B C

CIRCUIT

BREAKER

POLES /...

TOTAL

LOAD

(VA)

DESCRIPTION CKT

NO.

AIC RATING: 0 A NUMBER OF SECTIONS: POLES PER SECTION:

AIC AVAILABLE: PANEL LUGS: MCB FEED THROUGH LUGS: NO

VOLTAGE: 120/208 WYE MOUNTING: 200% NEUTRAL: NO

MCB: BUS TYPE: ISOLATED GROUND BUS: NO

MAIN BUS: 100 A ENCLOSURE: GROUND BUS: NO

LOCATION: TELECOM-54 7BTL1-54 WIRES: 3W NEUTRAL BUS: NO

EXIST: RPG7 FED FROM:

NOTES:

TOTAL ESTIMATED DEMAND: 24.2 67.2

TOTAL CONNECTED LOAD: 29.9 82.9

ADDED CONNECTED LOAD: 29.9

REMOVED CONNECTED LOAD: 0

Receptacle 21320 VA 15660 VA EXISTING CONNECTED LOAD: 0

Other 1440 VA 1440 VA kVA AMPS

LOAD CLASSIFICATION CONNECTED LOAD (VA)

ESTIMATED DEMAND

(VA)

PANEL TOTALS

89 A / 82 A / 79 A

H7#41 XXXXX - DEDICATED FOR... 1,000 20 1 1000 / 0 1 20 -- SPARE H7#42

H7#39 XXXXX - DEDICATED FOR VAV'S 1,000 20 1 1000 / 0 1 20 -- SPARE H7#40

H7#37 XXXXX - DEDICATED FOR VAV'S 1,000 20 1 1000 / 0 1 20 -- SPARE H7#38

H7#35 SPARE -- 20 1 0 / 0 1 20 -- SPARE H7#36

H7#33 SPARE -- 20 1 0 / 0 1 20 -- SPARE H7#34

H7#31 SPARE -- 20 1 0 / 540 1 20 540 7C189 - CONV. RECEPTACLES H7#32

H7#29 SPARE -- 20 1 0 / 2050 -- -- -- -- H7#30

H7#27 SPARE -- 20 1 0 / 2050 2 30 4,100 7C188 - RESTROOM INST. HEATER... H7#28

H7#25 SPARE -- 20 1 0 / 1440 1 20 1,440 XXXXX - POKE-THRU H7#26

H7#23 7C185, 7C186 - OFFICE RECEPT. & T.V. 540 20 1 540 / 540 1 20 540 XXXXX, 7C188 - CONVENIENCE REC. H7#24

H7#21 7C185, 7C186 - OFFICE RECEPT. & T.V. 540 20 1 540 / 540 1 20 540 XXXXX, 7C188 - CONVENIENCE REC. H7#22

H7#19 7C102, XXXXX - CONV. RECEPTACLES 1,080 20 1 1080 / 1500 1 20 1,500 7C155 - CONF. FLOOR BOX RECEPT. H7#20

H7#17 XXXXX - COPY/PRINTER 1,000 20 1 1000 / 1500 1 20 1,500 7C155 - CONF. FLOOR BOX RECEPT. H7#18

H7#15 XXXXX, 7C101, 7C180 - CONV. RECEPT. 1,260 20 1 1260 / 1500 1 20 1,500 7C155 - CONF. FLOOR BOX RECEPT. H7#16

H7#13 7C102 - RECEPTION PRINTER 1,000 20 1 1000 / 1500 1 20 1,500 7C155 - CONF. FLOOR BOX RECEPT. H7#14

H7#11 7C102 - RECEPTION RECEPTACLES 360 20 1 360 / 900 1 20 900 7C155 - CONFERENCE ROOM RECEPT. H7#12

H7#9 XXXXX - WORKSTATION 33 RECEPT. 720 20 1 720 / 900 1 20 900 7C155 - CONFERENCE ROOM RECEPT. H7#10

H7#7 XXXXX - WORKSTATION 32 RECEPT. 720 20 1 720 / 540 1 20 540 7C105, 7C151 - CONV. RECEPTACLES H7#8

H7#5 XXXXX - WORKSTATION 32 RECEPT. 720 20 1 720 / 900 1 20 900 7C151, 7C172, 7C153, 7C154 - RECEPT. H7#6

H7#3 XXXXX - WORKSTATION 31 RECEPT. 720 20 1 720 / 540 1 20 540 7C110, 7C111, 7C112 - RECEPTACLES H7#4

H7#1 XXXXX - WORKSTATION 31 RECEPT. 720 20 1 720 / 540 1 20 540 7C110, 7C111, 7C112 - RECEPTACLES H7#2

CKT

NO.

DESCRIPTION

TOTAL

LOAD

(VA)

CIRCUIT

BREAKER

AMPS / POLES

A B C

CIRCUIT

BREAKER

POLES /...

TOTAL

LOAD

(VA)

DESCRIPTION CKT

NO.

AIC RATING: 0 A NUMBER OF SECTIONS: POLES PER SECTION:

AIC AVAILABLE: PANEL LUGS: MCB FEED THROUGH LUGS: NO

VOLTAGE: 120/208 WYE MOUNTING: 200% NEUTRAL: NO

MCB: BUS TYPE: ISOLATED GROUND BUS: NO

MAIN BUS: 100 A ENCLOSURE: GROUND BUS: NO

LOCATION: Space 4A258 WIRES: 3W NEUTRAL BUS: NO

EXIST: RPH7 FED FROM:

NOTES:

TOTAL ESTIMATED DEMAND: 26.7 74.0

TOTAL CONNECTED LOAD: 32.7 90.8

ADDED CONNECTED LOAD: 32.7

REMOVED CONNECTED LOAD: 0

EXISTING CONNECTED LOAD: 0

Receptacle 22040 VA 16020 VA kVA AMPS

LOAD CLASSIFICATION CONNECTED LOAD (VA)

ESTIMATED DEMAND

(VA)

PANEL TOTALS

80 A / 105 A / 90 A

C72#83 7BEL3 - DEDICATED FOR THERMOSTAT 1,000 20 1 1000 / 1452 -- -- -- -- C72#84

C72#81 7BEL3 - DEDICATED FOR VAV'S 1,000 20 1 1000 / 1452 -- -- -- -- C72#82

C72#79 7BEL3 - DEDICATED FOR VAV'S 1,000 20 1 1000 / 1452 3 25 4,356 7BTL3 - AC-7-5 DISCONNECT C72#80

C72#77 7CUNI, 7CWMN - CONV. RECEPTACLES 540 20 1 540 / 180 1 20 180 7BTL3 - AC-7-5 COND. PUMP RECEPT. C72#78

C72#75 7CPN - REFRIGERATOR 1,000 20 1 1000 / 0 1 20 -- SPARE C72#76

C72#73 7CPN - REFRIGERATOR 1,000 20 1 1000 / 0 1 20 -- SPARE C72#74

C72#71 7CPN - VENDING MACHINE 500 20 1 500 / 0 1 20 -- SPARE C72#72

C72#69 7CPN - VENDING MACHINE 500 20 1 500 / 0 1 20 -- SPARE C72#70

C72#67 XXXXX - CORRIDOR WATER FOUNTAIN 180 20 1 180 / 0 1 20 -- SPARE C72#68

C72#65 7B255 - CONF. FLOOR BOX RECEPT. 1,500 20 1 1500 / 0 1 20 -- SPARE C72#66

C72#63 7B255 - CONF. FLOOR BOX RECEPT. 1,500 20 1 1500 / 0 1 20 -- SPARE C72#64

C72#61 7B253, 7B254, 7B255 - CONF. RECEPT. 720 20 1 720 / 0 1 20 -- SPARE C72#62

C72#59 7B250, 7B251, 7B252 - CONF. RECEPT. 720 20 1 720 / 0 1 20 -- SPARE C72#60

C72#57 7B250 - CONF. FLOOR BOX RECEPT. 1,500 20 1 1500 / 0 1 20 -- SPARE C72#58

C72#55 7B250 - CONF. FLOOR BOX RECEPT. 1,500 20 1 1500 / 150 1 20 150 7CMEN, 7CWMN, 7CPN - FAUCET,... C72#56

C72#53 7B155 - CONF. FLOOR BOX RECEPT. 1,500 20 1 1500 / 1500 -- -- -- -- C72#54

C72#51 7B155 - CONF. FLOOR BOX RECEPT. 1,500 20 1 1500 / 1500 2 20 3,000 7CPN - EAST PANTRY EWH C72#52

C72#49 7B153, 7B154, 7B155 - CONF. RECEPT. 720 20 1 720 / 150 1 20 150 7C1VES, 7C2VES - DR WAVE... C72#50

C72#47 7B150, 7B151, 7B152 - RECEPTACLES 720 20 1 720 / 1000 1 20 1,000 XXXXX - COPY/PRINTER C72#48

C72#45 7B150 - CONF. FLOOR BOX RECEPT. 1,500 20 1 1500 / 1000 1 20 1,000 XXXXX - COPY/PRINTER C72#46

C72#43 7B150 - CONF. FLOOR BOX RECEPT. 1,500 20 1 1500 / 1260 1 20 1,260 XXXXX - CONVENIENCE RECEPTACLES C72#44

CKT

NO.

DESCRIPTION

TOTAL

LOAD

(VA)

CIRCUIT

BREAKER

AMPS / POLES

A B C

CIRCUIT

BREAKER

POLES /...

TOTAL

LOAD

(VA)

DESCRIPTION CKT

NO.

AIC RATING: 10000 A NUMBER OF SECTIONS: 1 POLES PER SECTION: 42

AIC AVAILABLE: PANEL LUGS: MLO FEED THROUGH LUGS: YES

VOLTAGE: 120/208 WYE MOUNTING: SURFACE 200% NEUTRAL: NO

MCB: N/A BUS TYPE: COPPER ISOLATED GROUND BUS: NO

MAIN BUS: 225 A ENCLOSURE: NEMA 1 GROUND BUS: YES

LOCATION: ELECTRICAL 7BEL3 WIRES: 4W + G NEUTRAL BUS: YES

EXIST: RPC7 (SEC-2) FED FROM: RPC7 (SEC-1) NORMAL

NOTES:

TOTAL ESTIMATED DEMAND: 5.2 14.5

TOTAL CONNECTED LOAD: 5.2 14.5

ADDED CONNECTED LOAD: 5.2

REMOVED CONNECTED LOAD: 0

EXISTING CONNECTED LOAD: 0

Receptacle 5220 VA 5220 VA kVA AMPS

LOAD CLASSIFICATION CONNECTED LOAD (VA)

ESTIMATED DEMAND

(VA)

PANEL TOTALS

18 A / 14 A / 12 A

CC7#17 SPARE -- 20 1 0 / 0 1 20 -- SPARE CC7#18

CC7#15 SPARE -- 20 1 0 / 0 1 20 -- SPARE CC7#16

CC7#13 SPARE -- 20 1 0 / 360 1 20 360 XXXXX - WORKSTATION 14 RECEPT. CC7#14

CC7#11 XXXXX - WORKSTATION 11 RECEPT. 360 20 1 360 / 360 1 20 360 XXXXX - WORKSTATION 14 RECEPT. CC7#12

CC7#9 XXXXX - WORKSTATION 11 RECEPT. 360 20 1 360 / 360 1 20 360 XXXXX - WORKSTATION 13 RECEPT. CC7#10

CC7#7 XXXXX - WORKSTATION 10 RECEPT. 360 20 1 360 / 360 1 20 360 XXXXX - WORKSTATION 13 RECEPT. CC7#8

CC7#5 XXXXX - WORKSTATION 10 RECEPT. 360 20 1 360 / 360 1 20 360 XXXXX - OFFICE CONVENIENCE REC. CC7#6

CC7#3 7B214, 7B215, 7B216 - OFFICE RECEPT. 540 20 1 540 / 360 1 20 360 XXXXX - WORKSTATION 12 RECEPT. CC7#4

CC7#1 7B210, 7B211, 7B212, 7B213 - RECEPT. 720 20 1 720 / 360 1 20 360 XXXXX - WORKSTATION 12 RECEPT. CC7#2

CKT

NO.

DESCRIPTION

TOTAL

LOAD

(VA)

CIRCUIT

BREAKER

AMPS / POLES

A B C

CIRCUIT

BREAKER

POLES /...

TOTAL

LOAD

(VA)

DESCRIPTION CKT

NO.

AIC RATING: 0 A NUMBER OF SECTIONS: POLES PER SECTION:

AIC AVAILABLE: PANEL LUGS: MCB FEED THROUGH LUGS: NO

VOLTAGE: 120/208 WYE MOUNTING: 200% NEUTRAL: NO

MCB: BUS TYPE: ISOLATED GROUND BUS: NO

MAIN BUS: 100 A ENCLOSURE: GROUND BUS: NO

LOCATION: ELECTRICAL 7BEL3 WIRES: 3W NEUTRAL BUS: NO

EXIST: CPC7 FED FROM:

NOTES:

TOTAL ESTIMATED DEMAND: 11.4 13.7

TOTAL CONNECTED LOAD: 11.4 13.7

ADDED CONNECTED LOAD: 11.4

REMOVED CONNECTED LOAD: 0

EXISTING CONNECTED LOAD: 0

Other 11260 VA 11260 VA kVA AMPS

LOAD CLASSIFICATION CONNECTED LOAD (VA)

ESTIMATED DEMAND

(VA)

PANEL TOTALS

17 A / 14 A / 11 A

LC7#23 SPACE -- -- -- ... -- -- -- SPACE LC7#24

LC7#21 SPACE -- -- -- ... -- -- -- SPACE LC7#22

LC7#19 SPACE -- -- -- ... -- -- -- SPACE LC7#20

LC7#17 LTG 7TH FLOOR EAST OPEN OFFICE 726 20 1 726 / 376 1 20 376 LTG 7TH FLOOR EAST CONF. ROOM LC7#18

LC7#15 LTG 7TH FLOOR EAST OPEN OFFICE 567 20 1 567 / 634 1 20 634 LTG 7TH FLOOR EAST CONF. ROOM LC7#16

LC7#13 LTG 7TH FLOOR EAST CORRIDOR 1,101 20 1 1101 / 724 1 20 724 LTG 7TH FLOOR EAST OFFICES LC7#14

LC7#11 LTG 7TH FLR. EAST... 1,338 20 1 1338 / 0 1 20 -- EXISTING VAV LC7#12

LC7#9 LTG 7TH FLOOR EAST CORRIDOR 1,102 20 1 1102 / 0 1 20 -- EXISTING VAV LC7#10

LC7#7 LTG 7TH FLOOR EAST OFFICES 603 20 1 603 / 0 1 20 -- EXISTING VAV LC7#8

LC7#5 LTG 7TH FLOOR EAST OFFICES 603 20 1 603 / 0 1 20 -- SPARE LC7#6

LC7#3 LTG 7TH FLOOR EAST CONF. ROOM 1,523 20 1 1523 / 0 1 20 -- EXISTING VAV LC7#4

LC7#1 LTG 7TH FLOOR EAST CONF. ROOM 2,119 20 1 2119 / 0 1 20 -- EXISTING VAV LC7#2

CKT

NO.

DESCRIPTION

TOTAL

LOAD

(VA)

CIRCUIT

BREAKER

AMPS / POLES

A B C

CIRCUIT

BREAKER

POLES /...

TOTAL

LOAD

(VA)

DESCRIPTION CKT

NO.

AIC RATING: 0 A NUMBER OF SECTIONS: POLES PER SECTION:

AIC AVAILABLE: PANEL LUGS: MCB FEED THROUGH LUGS: NO

VOLTAGE: 480/277 WYE MOUNTING: 200% NEUTRAL: NO

MCB: BUS TYPE: ISOLATED GROUND BUS: NO

MAIN BUS: 100 A ENCLOSURE: GROUND BUS: NO

LOCATION: ELECTRICAL 7BEL3 WIRES: 3W NEUTRAL BUS: NO

EXIST: LPC7 FED FROM:

NOTES:

TOTAL ESTIMATED DEMAND: 5.0 14.0

TOTAL CONNECTED LOAD: 5.0 14.0

ADDED CONNECTED LOAD: 5

REMOVED CONNECTED LOAD: 0

EXISTING CONNECTED LOAD: 0

Receptacle 5040 VA 5040 VA kVA AMPS

LOAD CLASSIFICATION CONNECTED LOAD (VA)

ESTIMATED DEMAND

(VA)

PANEL TOTALS

20 A / 12 A / 11 A

CD7#17 7CTL2 - TELECOM RACK RECEPT. 180 20 1 180 / 0 1 20 -- SPARE CD7#18

CD7#15 7CTL2 - TELECOM RACK RECEPT. 180 20 1 180 / 0 1 20 -- SPARE CD7#16

CD7#13 7CTL2 - TELECOM RACK RECEPT. 180 20 1 180 / 900 1 20 900 7C284, 7C285, 7C286, 7C287 - RECEPT. CD7#14

CD7#11 7CTL2 - TELECOM RACK RECEPT. 180 20 1 180 / 360 1 20 360 XXXXX - WORKSTATION 17 RECEPT. CD7#12

CD7#9 SPARE -- 20 1 0 / 360 1 20 360 XXXXX - WORKSTATION 17 RECEPT. CD7#10

CD7#7 SPARE -- 20 1 0 / 360 1 20 360 XXXXX - WORKSTATION 16 RECEPT. CD7#8

CD7#5 7C291 - CHIEF OF SECURITY RECEPT. 180 20 1 180 / 360 1 20 360 XXXXX - WORKSTATION 16 RECEPT. CD7#6

CD7#3 LOBBY, 7C189 - COMP. RECEPTACLES 540 20 1 540 / 360 1 20 360 XXXXX - WORKSTATION 15 RECEPT. CD7#4

CD7#1 7C210, 7C211, 7C212 - OFFICE RECEPT. 540 20 1 540 / 360 1 20 360 XXXXX - WORKSTATION 15 RECEPT. CD7#2

CKT

NO.

DESCRIPTION

TOTAL

LOAD

(VA)

CIRCUIT

BREAKER

AMPS / POLES

A B C

CIRCUIT

BREAKER

POLES /...

TOTAL

LOAD

(VA)

DESCRIPTION CKT

NO.

AIC RATING: 0 A NUMBER OF SECTIONS: POLES PER SECTION:

AIC AVAILABLE: PANEL LUGS: MCB FEED THROUGH LUGS: NO

VOLTAGE: 120/208 WYE MOUNTING: 200% NEUTRAL: NO

MCB: BUS TYPE: ISOLATED GROUND BUS: NO

MAIN BUS: 100 A ENCLOSURE: GROUND BUS: NO

LOCATION: Space 4A256 WIRES: 3W NEUTRAL BUS: NO

EXIST: CPD7 FED FROM:

NOTES:

TOTAL ESTIMATED DEMAND: 6.7 8.0

TOTAL CONNECTED LOAD: 6.7 8.0

ADDED CONNECTED LOAD: 6.7

REMOVED CONNECTED LOAD: 0

EXISTING CONNECTED LOAD: 0

Other 6673 VA 6673 VA kVA AMPS

LOAD CLASSIFICATION CONNECTED LOAD (VA)

ESTIMATED DEMAND

(VA)

PANEL TOTALS

10 A / 7 A / 8 A

LD7#23 SPACE -- -- -- 0 / 0 1 20 -- SPARE LD7#24

LD7#21 SPACE -- -- -- 0 / 0 1 20 -- SPARE LD7#22

LD7#19 SPARE -- 20 1 0 / 0 1 20 -- SPARE LD7#20

LD7#17 SPARE -- 20 1 0 / 0 1 20 -- EXISTING VAV LD7#18

LD7#15 LTG 7TH FLOOR EAST 195 20 1 195 / 0 1 20 -- EXISTING VAV LD7#16

LD7#13 LTG 7TH FLOOR EAST EXEC. OFFICES 1,436 20 1 1436 / 0 1 20 -- EXISTING VAV LD7#14

LD7#11 LTG 7TH FLOOR EAST CONF. ROOM 1,334 20 1 1334 / 0 1 20 -- EXISTING VAV LD7#12

LD7#9 LTG 7TH FLOOR EAST CONF. ROOM 268 20 1 268 / 0 1 20 -- EXISTING VAV LD7#10

LD7#7 LTG 7TH FLOOR EAST ARMORY 192 20 1 192 / 0 1 20 -- EXISTING VAV LD7#8

LD7#5 LTG 7TH FLR. EAST... 797 20 1 797 / 0 1 20 -- EXISTING VAV LD7#6

LD7#3 LTG 7TH FLOOR EAST CORRIDOR 1,373 20 1 1373 / 0 1 20 -- EXISTING VAV LD7#4

LD7#1 LTG 7TH FLOOR EAST OFFICES 1,079 20 1 1079 / 0 1 20 -- EXISTING VAV LD7#2

CKT

NO.

DESCRIPTION

TOTAL

LOAD

(VA)

CIRCUIT

BREAKER

AMPS / POLES

A B C

CIRCUIT

BREAKER

POLES /...

TOTAL

LOAD

(VA)

DESCRIPTION CKT

NO.

AIC RATING: 0 A NUMBER OF SECTIONS: POLES PER SECTION:

AIC AVAILABLE: PANEL LUGS: MCB FEED THROUGH LUGS: NO

VOLTAGE: 480/277 WYE MOUNTING: 200% NEUTRAL: NO

MCB: BUS TYPE: ISOLATED GROUND BUS: NO

MAIN BUS: 100 A ENCLOSURE: GROUND BUS: NO

LOCATION: Space 4A256 WIRES: 3W NEUTRAL BUS: NO

EXIST: LPD7 FED FROM:

NOTES:

TOTAL ESTIMATED DEMAND: 4.5 12.5

TOTAL CONNECTED LOAD: 4.5 12.5

ADDED CONNECTED LOAD: 4.5

REMOVED CONNECTED LOAD: 0

EXISTING CONNECTED LOAD: 0

Receptacle 4500 VA 4500 VA kVA AMPS

LOAD CLASSIFICATION CONNECTED LOAD (VA)

ESTIMATED DEMAND

(VA)

PANEL TOTALS

16 A / 14 A / 9 A

CG7#17 SPARE -- 20 1 0 / 0 1 20 -- SPARE CG7#18

CG7#15 SPARE -- 20 1 0 / 0 1 20 -- SPARE CG7#16

CG7#13 SPARE -- 20 1 0 / 0 1 20 -- SPARE CG7#14

CG7#11 XXXXX - WORKSTATION 29 RECEPT. 360 20 1 360 / 0 1 20 -- SPARE CG7#12

CG7#9 XXXXX - WORKSTATION 29 RECEPT. 360 20 1 360 / 540 1 20 540 7B114, 7B115, 7B116 - OFFICE RECEPT. CG7#10

CG7#7 XXXXX - WORKSTATION 28 RECEPT. 360 20 1 360 / 720 1 20 720 7B110, 7B111, 7B112, 7B113 - RECEPT. CG7#8

CG7#5 XXXXX - WORKSTATION 28 RECEPT. 360 20 1 360 / 360 1 20 360 XXXXX - WORKSTATION 30 RECEPT. CG7#6

CG7#3 XXXXX - WORKSTATION 27 RECEPT. 360 20 1 360 / 360 1 20 360 XXXXX - WORKSTATION 30 RECEPT. CG7#4

CG7#1 XXXXX - WORKSTATION 27 RECEPT. 360 20 1 360 / 360 1 20 360 XXXXX, XXXXX - OFFICE RECEPT. CG7#2

CKT

NO.

DESCRIPTION

TOTAL

LOAD

(VA)

CIRCUIT

BREAKER

AMPS / POLES

A B C

CIRCUIT

BREAKER

POLES /...

TOTAL

LOAD

(VA)

DESCRIPTION CKT

NO.

AIC RATING: 0 A NUMBER OF SECTIONS: POLES PER SECTION:

AIC AVAILABLE: PANEL LUGS: MCB FEED THROUGH LUGS: NO

VOLTAGE: 120/208 WYE MOUNTING: 200% NEUTRAL: NO

MCB: BUS TYPE: ISOLATED GROUND BUS: NO

MAIN BUS: 100 A ENCLOSURE: GROUND BUS: NO

LOCATION: TELECOM-54 7BTL1-54 WIRES: 3W NEUTRAL BUS: NO

EXIST: CPG7 FED FROM:

NOTES:

TOTAL ESTIMATED DEMAND: 4.0 11.0

TOTAL CONNECTED LOAD: 4.0 11.0

ADDED CONNECTED LOAD: 4

REMOVED CONNECTED LOAD: 0

EXISTING CONNECTED LOAD: 0

Receptacle 3960 VA 3960 VA kVA AMPS

LOAD CLASSIFICATION CONNECTED LOAD (VA)

ESTIMATED DEMAND

(VA)

PANEL TOTALS

12 A / 11 A / 11 A

CH7#17 SPARE -- 20 1 0 / 180 1 20 180 7C291 - CCTV CAMERA CH7#18

CH7#15 SPARE -- 20 1 0 / 180 1 20 180 7C291 - CCTV CAMERA CH7#16

CH7#13 SPARE -- 20 1 0 / 0 1 20 -- SPARE CH7#14

CH7#11 XXXXX, XXXXX, XXXXX - OFFICE... 540 20 1 540 / 0 1 20 -- SPARE CH7#12

CH7#9 XXXXX, XXXXX, XXXXX - W.S.... 360 20 1 360 / 0 1 20 -- SPARE CH7#10

CH7#7 XXXXX - WORKSTATION 32 RECEPT. 360 20 1 360 / 180 1 20 180 XXXXX - RECEPTACLE CH7#8

CH7#5 XXXXX - WORKSTATION 32 RECEPT. 360 20 1 360 / 180 1 20 180 XXXXX - OFFICE RECEPTACLES CH7#6

CH7#3 XXXXX - WORKSTATION 31 RECEPT. 360 20 1 360 / 360 1 20 360 XXXXX, 7C190 - RECEPTACLES CH7#4

CH7#1 XXXXX - WORKSTATION 31 RECEPT. 360 20 1 360 / 540 1 20 540 7C110M 7C111, 7C112 - OFFICE... CH7#2

CKT

NO.

DESCRIPTION

TOTAL

LOAD

(VA)

CIRCUIT

BREAKER

AMPS / POLES

A B C

CIRCUIT

BREAKER

POLES /...

TOTAL

LOAD

(VA)

DESCRIPTION CKT

NO.

AIC RATING: 0 A NUMBER OF SECTIONS: POLES PER SECTION:

AIC AVAILABLE: PANEL LUGS: MCB FEED THROUGH LUGS: NO

VOLTAGE: 120/208 WYE MOUNTING: 200% NEUTRAL: NO

MCB: BUS TYPE: ISOLATED GROUND BUS: NO

MAIN BUS: 100 A ENCLOSURE: GROUND BUS: NO

LOCATION: Space 4A258 WIRES: 3W NEUTRAL BUS: NO

EXIST: CPH7 FED FROM:

NOTES:

TOTAL ESTIMATED DEMAND: 7.4 20.6

TOTAL CONNECTED LOAD: 7.4 20.6

Receptacle 6220 VA 6220 VA kVA AMPS

LOAD CLASSIFICATION CONNECTED LOAD (VA)

ESTIMATED DEMAND

(VA)

PANEL TOTALS

27 A / 27 A / 12 A

ED7#41 ED7#42

ED7#39 ED7#40

ED7#37 ED7#38

ED7#35 ED7#36

ED7#33 ED7#34

ED7#31 ED7#32

ED7#29 ED7#30

ED7#27 ED7#28

ED7#25 ED7#26

ED7#23 ED7#24

ED7#21 ED7#22

ED7#19 ED7#20

ED7#17 ED7#18

ED7#15 ED7#16

ED7#13 ED7#14

ED7#11 ED7#12

ED7#9 RECEPTACLE ARMORY 7C214 360 20 1 360 / 1200 1 20 1,200 DOOR MAG-LOCKS ED7#10

ED7#7 XXXXX - WORKSTATION RECEPTACLES 720 20 1 720 / 720 1 20 720 XXXXX - WORKSTATION RECEPTACLES ED7#8

ED7#5 XXXXX - WORKSTATION RECEPTACLES 720 20 1 720 / 720 1 20 720 XXXXX - WORKSTATION RECEPTACLES ED7#6

ED7#3 XXXXX - WORKSTATION RECEPTACLES 720 20 1 720 / 720 1 20 720 XXXXX - WORKSTATION RECEPTACLES ED7#4

ED7#1 RECEPTACLE SPACE 4A249 540 20 1 540 / 1000 1 20 1,000 RECEPTACLE SPACE 4A249 ED7#2

CKT

NO.

DESCRIPTION

TOTAL

LOAD

(VA)

CIRCUIT

BREAKER

AMPS / POLES

A B C

CIRCUIT

BREAKER

POLES /...

TOTAL

LOAD

(VA)

DESCRIPTION CKT

NO.

AIC RATING: 10000 A NUMBER OF SECTIONS: 1 POLES PER SECTION: 42

AIC AVAILABLE: PANEL LUGS: MCB FEED THROUGH LUGS: NO

VOLTAGE: 120/208 WYE MOUNTING: 200% NEUTRAL: NO

MCB: 60A BUS TYPE: ISOLATED GROUND BUS: NO

MAIN BUS: 100 A ENCLOSURE: GROUND BUS: YES

LOCATION: Space 4A256 WIRES: 4W + G NEUTRAL BUS: YES

NEW: ERD7 FED FROM: 15 kVA, 277 V/480 V,...

0 - - N.T.S.

CHECKED BY

DRAWN BY

FLOOR NUMBER

DRAWING TITLE

SHEET

NUMBER

SUBMISSION DATE

SUBMISSION STAGE

GSA PM

GSA PROJECT NO.

PROJECT

DESCRIPTION

PROJECT TITLE

BUILDING NAME

ADDRESS

BUILDING NUMBER

PRIME CONTR. NO.

PRIME ORDER NO.

CONST. CONTR.

A/E

SUB A/E

CONST. CONTR. NO.

SHEET SIZE:

DATE DRAWN:

36 X 48

S H

E E

T

ID

E N

TI

FI

C A

TI

O

N

DISCIPLINE

P R

O

JE

C T

ID

E

N

TI

FI

C

A

TI

O N

B U

IL

D

IN

G

BIM FILE NAME

C O

N

TR

A C

TO

R

S R

E V

IS

IO

N B

LO

C

K G

R A

P H

IC

S

C A

LE

K

E Y

P

LA

N S

TA

M

P O

R S

E A

L D

E S

IG

N

E R

ID

E

N

TI

FI

C

A

TI

O N

O W

N E

R

ID

E N

TI

FI

C A

TI

O

N

SHEET OF SHEETS

KRUECK & SEXTON ARCHITECTS, P.C.

400 MARYLAND AVENUE, SW

WASHINGTON, DC 20024

LYNDON B. JOHNSON FEDERAL BUILDING

DC0010ZZ

DC0010_E_3-4-6-7_r2020.rvt

WSP ENGINEERING

DEPARTMENT OF EDUCATION

CONSOLIDATION PROJECT

ISSUED FOR BID

HALLIE FUTTERMAN

RENOVATION OF FLOORS 3, 4, 6, & 7 OF THE EXISTING

BUILDING TO MEET THE DEPARTMENT OF

EDUCATION’S PROGRAMMATIC REQUIREMENTS.

GS-07-P-16-UC-D-7000

47PM0520F0002

47PM0520F0002

KRUECK & SEXTON ARCHITECTS

221 W ERIE ST

CHICAGO, IL 60654 (312) 787-0056

ARCHITECT

WSP ENGINEERING

ONE PENNSYLVANIA PLAZA, SECOND FLOOR

NEW YORK, NY 10119 (212) 465-5000

MEP ENGINEER

ATELIER TEN

45 E 20TH ST, 4TH FLOOR

NEW YORK, NY 10003 (312) 386-1400

SUSTAINABILITY CONSULTANT

THRESHOLD ACOUSTICS

141 W JACKSON BLVD, SUITE 2080

CHICAGO, IL 60604 (312) 386-1400

ACOUSTIC CONSULTANT

WEST EAST

M A

TC

H

LI

N

E

GENERAL SERVICES ADMINISTRATION

NATIONAL CAPITAL REGION

PUBLIC BUILDING SERVICE, D.C. SERVICES DIV.

7TH & D STREET, S.W.

WASHINGTON, D.C. 20407

ISSUE

NO. DATE ISSUE

ELECTRICAL

VARIES, SEE DRAWINGS

01 04/23/2021 ISSUED FOR BID

FORCADE DESIGN

1626 PAYNE STREET

EVANSTON, IL 60201 (847) 448-4270

ENVIRONMENTAL GRAPHICS CONSULTANT

/2

/2

:3

:2

P

M

E-60-08

ELECTRICAL LIGHT FIXTURE SCHEDULE

04/23/2021

04/23/21NJA

RO

56 61

GENERAL NOTES:

1. CONTRACTOR TO REPLACE ALL BREAKERS IN ALL

EXISTING 3RD , 4TH , 6 AND 7TH FLOOR LPD, RPD, CPD

AND CPH POWER PANELS WITH NEW CIRCUIT BREAKERS.

0 - - N.T.S.

CHECKED BY

DRAWN BY

FLOOR NUMBER

DRAWING TITLE

SHEET

NUMBER

SUBMISSION DATE

SUBMISSION STAGE

GSA PM

GSA PROJECT NO.

PROJECT

DESCRIPTION

PROJECT TITLE

BUILDING NAME

ADDRESS

BUILDING NUMBER

PRIME CONTR. NO.

PRIME ORDER NO.

CONST. CONTR.

A/E

SUB A/E

CONST. CONTR. NO.

SHEET SIZE:

DATE DRAWN:

36 X 48

S H

E E

T

ID

E N

TI

FI

C A

TI

O

N

DISCIPLINE

P R

O

JE

C T

ID

E

N

TI

FI

C

A

TI

O N

B U

IL

D

IN

G

BIM FILE NAME

C O

N

TR

A C

TO

R

S R

E V

IS

IO

N B

LO

C

K G

R A

P H

IC

S

C A

LE

K

E Y

P

LA

N S

TA

M

P O

R S

E A

L D

E S

IG

N

E R

ID

E

N

TI

FI

C

A

TI

O N

O W

N E

R

ID

E N

TI

FI

C A

TI

O

N

SHEET OF SHEETS

KRUECK & SEXTON ARCHITECTS, P.C.

400 MARYLAND AVENUE, SW

WASHINGTON, DC 20024

LYNDON B. JOHNSON FEDERAL BUILDING

DC0010ZZ

DC0010_E_3-4-6-7_r2020.rvt

WSP ENGINEERING

DEPARTMENT OF EDUCATION

CONSOLIDATION PROJECT

ISSUED FOR BID

HALLIE FUTTERMAN

RENOVATION OF FLOORS 3, 4, 6, & 7 OF THE EXISTING

BUILDING TO MEET THE DEPARTMENT OF

EDUCATION’S PROGRAMMATIC REQUIREMENTS.

GS-07-P-16-UC-D-7000

47PM0520F0002

47PM0520F0002

KRUECK & SEXTON ARCHITECTS

221 W ERIE ST

CHICAGO, IL 60654 (312) 787-0056

ARCHITECT

WSP ENGINEERING

ONE PENNSYLVANIA PLAZA, SECOND FLOOR

NEW YORK, NY 10119 (212) 465-5000

MEP ENGINEER

ATELIER TEN

45 E 20TH ST, 4TH FLOOR

NEW YORK, NY 10003 (312) 386-1400

SUSTAINABILITY CONSULTANT

THRESHOLD ACOUSTICS

141 W JACKSON BLVD, SUITE 2080

CHICAGO, IL 60604 (312) 386-1400

ACOUSTIC CONSULTANT

WEST EAST

M A

TC

H

LI

N

E

GENERAL SERVICES ADMINISTRATION

NATIONAL CAPITAL REGION

PUBLIC BUILDING SERVICE, D.C. SERVICES DIV.

7TH & D STREET, S.W.

WASHINGTON, D.C. 20407

ISSUE

NO. DATE ISSUE

ELECTRICAL

VARIES, SEE DRAWINGS

01 04/23/2021 ISSUED FOR BID

FORCADE DESIGN

1626 PAYNE STREET

EVANSTON, IL 60201 (847) 448-4270

ENVIRONMENTAL GRAPHICS CONSULTANT

/2

/2

:2

:0

P

M

E-60-09

ELECTRICAL PANEL SCHEDULES - EM RISER MOD

04/23/2021

05/21/21NJA

RO

EMDP PP-A SB-PP-2C01 -

1C7 GEN SB-PP-7C01 -

90-31 PP-S - -

NOTES:

TOTAL ESTIMATED DEMAND: 0.0 0.0

TOTAL CONNECTED LOAD: 0.0 0.0

kVA AMPS

LOAD CLASSIFICATION CONNECTED LOAD (VA)

ESTIMATED DEMAND

(VA)

PANEL TOTALS

0 A / 0 A / 0 A

#23 SPARE -- 20 1 0 / 0 -- -- -- -- #24

#21 SPARE -- 20 1 0 / 0 -- -- -- -- #22

#19 SPARE -- 20 1 0 / 0 3 30 -- SPD #20

#17 SPARE -- 20 1 0 / 0 1 20 -- SPARE #18

#15 SPARE -- 20 1 0 / 0 1 20 -- SPARE #16

#13 SPARE -- 20 1 0 / 0 1 20 -- SPARE #14

#11 SPARE -- 20 1 0 / 0 1 20 -- SPARE #12

#9 SPARE -- 20 1 0 / 0 1 20 -- SPARE #10

#7 SPARE -- 20 1 0 / 0 1 20 -- SPARE #8

#5 SPARE -- 20 1 0 / 0 1 20 -- SPARE #6

#3 SPARE -- 20 1 0 / 0 1 20 -- SPARE #4

#1 SPARE -- 20 1 0 / 0 1 20 -- SPARE #2

CKT

NO.

DESCRIPTION

TOTAL

LOAD

(VA)

CIRCUIT

BREAKER

AMPS / POLES

A B C

CIRCUIT

BREAKER

POLES /...

TOTAL

LOAD

(VA)

DESCRIPTION CKT

NO.

AIC RATING: 22000 A NUMBER OF SECTIONS: 1 POLES PER SECTION: 24

AIC AVAILABLE: PANEL LUGS: MCB FEED THROUGH LUGS: NO

VOLTAGE: 120/208 WYE MOUNTING: SURFACE 200% NEUTRAL: NO

MCB: 60A BUS TYPE: COPPER ISOLATED GROUND BUS: NO

MAIN BUS: 100 A ENCLOSURE: NEMA 1 GROUND BUS: YES

LOCATION: WIRES: 4W + G NEUTRAL BUS: YES

NEW: 1C7 FED FROM: PP-S

NOTES:

TOTAL ESTIMATED DEMAND: 0.0 0.0

TOTAL CONNECTED LOAD: 0.0 0.0

kVA AMPS

LOAD CLASSIFICATION CONNECTED LOAD (VA)

ESTIMATED DEMAND

(VA)

PANEL TOTALS

0 A / 0 A / 0 A

#23 SPARE -- 20 1 0 / 0 -- -- -- -- #24

#21 SPARE -- 20 1 0 / 0 -- -- -- -- #22

#19 SPARE -- 20 1 0 / 0 3 30 -- SPD #20

#17 SPARE -- 20 1 0 / 0 1 20 -- SPARE #18

#15 SPARE -- 20 1 0 / 0 1 20 -- SPARE #16

#13 SPARE -- 20 1 0 / 0 1 20 -- SPARE #14

#11 SPARE -- 20 1 0 / 0 1 20 -- SPARE #12

#9 SPARE -- 20 1 0 / 0 1 20 -- SPARE #10

#7 SPARE -- 20 1 0 / 0 1 20 -- SPARE #8

#5 SPARE -- 20 1 0 / 0 1 20 -- SPARE #6

#3 SPARE -- 20 1 0 / 0 1 20 -- SPARE #4

#1 SPARE -- 20 1 0 / 0 1 20 -- SPARE #2

CKT

NO.

DESCRIPTION

TOTAL

LOAD

(VA)

CIRCUIT

BREAKER

AMPS / POLES

A B C

CIRCUIT

BREAKER

POLES /...

TOTAL

LOAD

(VA)

DESCRIPTION CKT

NO.

AIC RATING: 22000 A NUMBER OF SECTIONS: 1 POLES PER SECTION: 24

AIC AVAILABLE: PANEL LUGS: MCB FEED THROUGH LUGS: NO

VOLTAGE: 120/208 WYE MOUNTING: SURFACE 200% NEUTRAL: NO

MCB: 60A BUS TYPE: COPPER ISOLATED GROUND BUS: NO

MAIN BUS: 100 A ENCLOSURE: NEMA 1 GROUND BUS: YES

LOCATION: WIRES: 4W + G NEUTRAL BUS: YES

NEW: 90-31 FED FROM: PP-S

NOTES:

TOTAL ESTIMATED DEMAND: 0.0 0.0

TOTAL CONNECTED LOAD: 0.0 0.0

kVA AMPS

LOAD CLASSIFICATION CONNECTED LOAD (VA ESTIMATED DEMAND (VA) PANEL TOTALS

4 SPARE -- 3 100 A -- 0 VA

3 SPARE -- 3 100 A -- 0 VA

2 ATS #2 -- 3 400 A -- 0 VA REFER TO RISER DIAGRAM

1 ATS #1 -- 3 400 A -- 0 VA REFER TO RISER DIAGRAM

CKT

NO.

DESCRIPTION

LOAD

CLASSIFICATION

CIRCUIT BREAKER

POLES/AMPS

FRAME

TOTAL LOAD

(VA)

REMARKS

AIC RATING: 100000 A NUMBER OF SECTIONS: 1

AIC AVAILABLE: PANEL LUGS: MCB FEED THROUGH LUGS: NO

VOLTAGE: 480/277 WYE MOUNTING: SURFACE 200% NEUTRAL: NO

MCB: 600A BUS TYPE: COPPER ISOLATED GROUND BUS: NO

MAIN BUS: 600 A ENCLOSURE: NEMA 1 GROUND BUS: YES

LOCATION: WIRES: 4W + G NEUTRAL BUS: YES

NEW: EMDP FED FROM:

NOTES:

TOTAL ESTIMATED DEMAND: 9.2 25.5

TOTAL CONNECTED LOAD: 9.2 25.5

kVA AMPS

LOAD CLASSIFICATION CONNECTED LOAD (VA)

ESTIMATED DEMAND

(VA)

PANEL TOTALS

27 A / 27 A / 24 A

#41 SPARE -- 20 1 0 / 0 -- -- -- -- #42

#39 SPARE -- 20 1 0 / 0 -- -- -- -- #40

#37 SPARE -- 20 1 0 / 0 3 30 -- SPD #38

#35 SPARE -- 20 1 0 / 0 1 20 -- SPARE #36

#33 SPARE -- 20 1 0 / 0 1 20 -- SPARE #34

#31 SPARE -- 20 1 0 / 0 1 20 -- SPARE #32

#29 SPARE -- 20 1 0 / 0 1 20 -- SPARE #30

#27 SPARE -- 20 1 0 / 0 1 20 -- SPARE #28

#25 SPARE -- 20 1 0 / 0 1 20 -- SPARE #26

#23 SPARE -- 20 1 0 / 0 1 20 -- SPARE #24

#21 SPARE -- 20 1 0 / 0 1 20 -- SPARE #22

#19 SPARE -- 20 1 0 / 0 1 20 -- SPARE #20

#17 SPARE -- 20 1 0 / 0 1 20 -- SPARE #18

#15 SPARE -- 20 1 0 / 0 1 20 -- SPARE #16

#13 SPARE -- 20 1 0 / 0 1 20 -- SPARE #14

#11 -- -- -- -- 333 / 0 1 20 -- SPARE #12

#9 -- -- -- -- 333 / 0 1 20 -- SPARE #10

#7 OIL HEATER PUMP 1,000 20 3 333 / 0 1 20 -- SPARE #8

#5 GEN CONTROL PANEL 1,000 20 1 1000 / 1500 1 20 1,500 LOUVERS #6

#3 -- -- -- -- 1350 / 1500 1 20 1,500 LOUVERS #4

#1 JW HEATER PUMP 2,700 20 2 1350 / 1500 1 20 1,500 BATTERY CHARGER #2

CKT

NO.

DESCRIPTION

TOTAL

LOAD

(VA)

CIRCUIT

BREAKER

AMPS / POLES

A B C

CIRCUIT

BREAKER

POLES /...

TOTAL

LOAD

(VA)

DESCRIPTION CKT

NO.

AIC RATING: 22000 A NUMBER OF SECTIONS: 1 POLES PER SECTION: 42

AIC AVAILABLE: PANEL LUGS: MCB FEED THROUGH LUGS: NO

VOLTAGE: 120/208 WYE MOUNTING: SURFACE 200% NEUTRAL: NO

MCB: 175A BUS TYPE: COPPER ISOLATED GROUND BUS: NO

MAIN BUS: 225 A ENCLOSURE: NEMA 1 GROUND BUS: YES

LOCATION: WIRES: 4W + G NEUTRAL BUS: YES

NEW: GEN FED FROM:

NOTES:

TOTAL ESTIMATED DEMAND: 0.0 0.0

TOTAL CONNECTED LOAD: 0.0 0.0

kVA AMPS

LOAD CLASSIFICATION CONNECTED LOAD (VA ESTIMATED DEMAND (VA) PANEL TOTALS

12 SPACE -- -- -- -- 0 VA --

11 SPACE -- -- -- -- 0 VA --

10 SPACE -- -- -- -- 0 VA --

9 SPACE -- -- -- -- 0 VA --

8 PNL ERD7 15kVA XFMR -- 3 25 A -- 0 VA REFER TO RISER DIAGRAM

7 PNL ASB-PP-7C01 30 kVA XFMR -- 3 50 A -- 0 VA REFER TO RISER DIAGRAM

6 GEN PNL 30 kVA XFMR -- 3 50 A -- 0 VA REFER TO RISER DIAGRAM

5 UPS-B BY-PASS FEED -- 3 225 A -- 0 VA REFER TO RISER DIAGRAM

4 UPS-A NORMAL FEED -- 3 250 A -- 0 VA REFER TO RISER DIAGRAM

3 PNL PP-S 45 kVA XFMR -- 3 70 A -- 0 VA REFER TO RISER DIAGRAM

2 SPARE -- 3 100 A -- 0 VA

1 SPARE -- 3 100 A -- 0 VA

CKT

NO.

DESCRIPTION

LOAD

CLASSIFICATION

CIRCUIT BREAKER

POLES/AMPS

FRAME Load REMARKS

AIC RATING: 65000 A NUMBER OF SECTIONS: 1

AIC AVAILABLE: PANEL LUGS: MCB FEED THROUGH LUGS: NO

VOLTAGE: 480/277 WYE MOUNTING: SURFACE 200% NEUTRAL: NO

MCB: 400A BUS TYPE: COPPER ISOLATED GROUND BUS: NO

MAIN BUS: 400 A ENCLOSURE: NEMA 1 GROUND BUS: YES

LOCATION: WIRES: 4W + G NEUTRAL BUS: YES

NEW: PP-A FED FROM:

NOTES:

TOTAL ESTIMATED DEMAND: 0.0 0.0

TOTAL CONNECTED LOAD: 0.0 0.0

kVA AMPS

LOAD CLASSIFICATION CONNECTED LOAD (VA)

ESTIMATED DEMAND

(VA)

PANEL TOTALS

0 A / 0 A / 0 A

#41 SPARE -- 20 1 0 / 0 -- -- -- -- #42

#39 SPARE -- 20 1 0 / 0 -- -- -- -- #40

#37 SPARE -- 20 1 0 / 0 3 30 -- SPD #38

#35 SPARE -- 20 1 0 / 0 1 20 -- SPARE #36

#33 SPARE -- 20 1 0 / 0 1 20 -- SPARE #34

#31 SPARE -- 20 1 0 / 0 1 20 -- SPARE #32

#29 SPARE -- 20 1 0 / 0 1 20 -- SPARE #30

#27 SPARE -- 20 1 0 / 0 1 20 -- SPARE #28

#25 SPARE -- 20 1 0 / 0 1 20 -- SPARE #26

#23 SPARE -- 20 1 0 / 0 1 20 -- SPARE #24

#21 SPARE -- 20 1 0 / 0 1 20 -- SPARE #22

#19 SPARE -- 20 1 0 / 0 1 20 -- SPARE #20

#17 SPARE -- 20 1 0 / 0 1 20 -- SPARE #18

#15 SPARE -- 20 1 0 / 0 1 20 -- SPARE #16

#13 SPARE -- 20 1 0 / 0 1 20 -- SPARE #14

#11 SPARE -- 20 1 0 / 0 1 20 -- SPARE #12

#9 SPARE -- 20 1 0 / 0 1 20 -- SPARE #10

#7 SPARE -- 20 1 0 / 0 1 20 -- SPARE #8

#5 -- -- -- -- 0 / 0 -- -- -- -- #6

#3 -- -- -- -- 0 / 0 -- -- -- -- #4

#1 1C7 0 20 3 0 / 0 3 20 0 90-31 #2

CKT

NO.

DESCRIPTION

TOTAL

LOAD

(VA)

CIRCUIT

BREAKER

AMPS / POLES

A B C

CIRCUIT

BREAKER

POLES /...

TOTAL

LOAD

(VA)

DESCRIPTION CKT

NO.

AIC RATING: 22000 A NUMBER OF SECTIONS: 1 POLES PER SECTION: 42

AIC AVAILABLE: PANEL LUGS: MCB FEED THROUGH LUGS: NO

VOLTAGE: 120/208 WYE MOUNTING: SURFACE 200% NEUTRAL: NO

MCB: 175A BUS TYPE: COPPER ISOLATED GROUND BUS: NO

MAIN BUS: 225 A ENCLOSURE: NEMA 1 GROUND BUS: YES

LOCATION: WIRES: 4W + G NEUTRAL BUS: YES

NEW: PP-S FED FROM:

NOTES:

TOTAL ESTIMATED DEMAND: 0.0 0.0

TOTAL CONNECTED LOAD: 0.0 0.0

kVA AMPS

LOAD CLASSIFICATION CONNECTED LOAD (VA)

ESTIMATED DEMAND

(VA)

PANEL TOTALS

0 A / 0 A / 0 A

#23 SPARE -- 20 1 0 / 0 -- -- -- -- #24

#21 SPARE -- 20 1 0 / 0 -- -- -- -- #22

#19 SPARE -- 20 1 0 / 0 3 30 -- SPD #20

#17 SPARE -- 20 1 0 / 0 1 20 -- SPARE #18

#15 SPARE -- 20 1 0 / 0 1 20 -- SPARE #16

#13 SPARE -- 20 1 0 / 0 1 20 -- SPARE #14

#11 SPARE -- 20 1 0 / 0 1 20 -- SPARE #12

#9 SPARE -- 20 1 0 / 0 1 20 -- SPARE #10

#7 SPARE -- 20 1 0 / 0 1 20 -- SPARE #8

#5 SPARE -- 20 1 0 / 0 1 20 -- SPARE #6

#3 SPARE -- 20 1 0 / 0 1 20 -- SPARE #4

#1 SPARE -- 20 1 0 / 0 1 20 -- SPARE #2

CKT

NO.

DESCRIPTION

TOTAL

LOAD

(VA)

CIRCUIT

BREAKER

AMPS / POLES

A B C

CIRCUIT

BREAKER

POLES /...

TOTAL

LOAD

(VA)

DESCRIPTION CKT

NO.

AIC RATING: 22000 A NUMBER OF SECTIONS: 1 POLES PER SECTION: 24

AIC AVAILABLE: PANEL LUGS: MCB FEED THROUGH LUGS: NO

VOLTAGE: 120/208 WYE MOUNTING: SURFACE 200% NEUTRAL: NO

MCB: 60A BUS TYPE: COPPER ISOLATED GROUND BUS: NO

MAIN BUS: 100 A ENCLOSURE: NEMA 1 GROUND BUS: YES

LOCATION: WIRES: 4W + G NEUTRAL BUS: YES

NEW: SB-PP-2C01 FED FROM: SB-PP-7C01

NOTES:

TOTAL ESTIMATED DEMAND: 0.0 0.0

TOTAL CONNECTED LOAD: 0.0 0.0

kVA AMPS

LOAD CLASSIFICATION CONNECTED LOAD (VA)

ESTIMATED DEMAND

(VA)

PANEL TOTALS

0 A / 0 A / 0 A

#23 SPARE -- 20 1 0 / 0 -- -- -- -- #24

#21 SPARE -- 20 1 0 / 0 -- -- -- -- #22

#19 SPARE -- 20 1 0 / 0 3 30 -- SPD #20

#17 SPARE -- 20 1 0 / 0 1 20 -- SPARE #18

#15 SPARE -- 20 1 0 / 0 1 20 -- SPARE #16

#13 SPARE -- 20 1 0 / 0 1 20 -- SPARE #14

#11 SPARE -- 20 1 0 / 0 1 20 -- SPARE #12

#9 SPARE -- 20 1 0 / 0 1 20 -- SPARE #10

#7 SPARE -- 20 1 0 / 0 1 20 -- SPARE #8

#5 -- -- -- -- 0 / 0 1 20 -- SPARE #6

#3 -- -- -- -- 0 / 0 1 20 -- SPARE #4

#1 SB-PP-2C01 0 50 3 0 / 0 1 20 -- SPARE #2

CKT

NO.

DESCRIPTION

TOTAL

LOAD

(VA)

CIRCUIT

BREAKER

AMPS / POLES

A B C

CIRCUIT

BREAKER

POLES /...

TOTAL

LOAD

(VA)

DESCRIPTION CKT

NO.

AIC RATING: 22000 A NUMBER OF SECTIONS: 1 POLES PER SECTION: 24

AIC AVAILABLE: PANEL LUGS: MCB FEED THROUGH LUGS: NO

VOLTAGE: 120/208 WYE MOUNTING: SURFACE 200% NEUTRAL: NO

MCB: 100A BUS TYPE: COPPER ISOLATED GROUND BUS: NO

MAIN BUS: 100 A ENCLOSURE: NEMA 1 GROUND BUS: YES

LOCATION: WIRES: 4W + G NEUTRAL BUS: YES

NEW: SB-PP-7C01 FED FROM:

TV

TV

TV

T V

T V

AV

AV

A V

T V

T V

T V

T V

T V

T V

AG

A G

AG

AG

AG

T V

T V

A G

A G

R R

R P

R V

M V

M A

G

TV

A G

A G

T V

PP P P P P

TV

P P P P P P

P

A V

A V

A V

T V

T V

T V

T V

T V

T V

T V

P

P

P

PR

P R

P R

P R

P R

P R

P R

P

AGAG

P

AV

AV

P

A V

J

J

J

GFCI

GFCI

T V

A G

A G

T V

T V

J

J

J

C R

CR CR

PR

T V

T V

T V

T V

CR

P R

TV

C R

C R

CR

J

JJ

20a

20a

F F

E E

D D

C C

B B

A A

A A

B B

C C

D D

E E

F F

20a

20a

NO SCOPE

OF WORK IN

THIS AREA

NO SCOPE

OF WORK IN

THIS AREA

FURNITURE FEED VIA POKE-THROUGH, TYP.

WHERE WORKSTATIONS ARE NOT

ADJACENT TO A COLUMN. E-27-02

E-27-02

E-27-02

E-27-02

FED FROM ELEC ROOM '3CEL1', U.O.N.FED FROM ELEC ROOM '3BEL2', U.O.N.

FED…