GSA-DoED_Addendum-02_MEP_5.24.21.pdf
PDF 7 MB Posted
- Attached to
- Solicitation Notice - LBJ Consolidation & Switchgear Federal contract opportunity
- Solicitation number
- 47PM0121R0013
About this file
This is a solicitation notice for a construction contract to renovate floors 3, 4, 6, and 7 of the Lyndon B. Johnson Federal Building to consolidate the Department of Education. The scope of work includes interior alterations, open office construction, HVAC and electrical upgrades including a new switchgear system. The contract type is firm-fixed price. The NAICS code is 236220 and small business size standard is $39.5M average annual receipts. A virtual pre-proposal conference will be held on May 5th and proposals are due by June 4th. The solicitation and any amendments will be posted on SAM.gov. Interested firms must register in SAM. The selection process will follow FAR Part 15 procedures. No site visits will be conducted but the project site can be viewed virtually using the included StructionSite link.
View the file
Other files for this federal contract opportunity
Show all 50
Solicitation Notice - LBJ Consolidation & Switchgear has more files on GovTribe.
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
EF
MPP-1
M
M
M
M
TAHU-6
AHU-2
AHU-5
AHU-1
1" FOS/FOR
MUFFLER
40x40 OA
DUCT
THROUGH
ROOF TO
GOOSENECK
50 SF NFA
EXHAUST
LOUVER
8" EXHAUST
PIPE WITH 90
DEGREE
ELBOW UP
PROVIDE 400
GALLON
DAYTANK
WITH
TRANSFER
PUMP SET.
PREFERRED
UTILITIES
MODEL 11871
350 KW
GENERATOR
(SEE
ELECTRICAL
DRAWINGS)
PIPE IN PIPE 1"
FOS/FOR LINE
RUN IN 7TH
FLOOR
CEILING
PLENUM TO
FUEL OIL
RISER
ALD-R-2ALD-R-1
16" X 18" UP TO
ROOF EXHAUST FAN
EE
EE
XX� CWS/R UP
TO ROOFTOP
GENERATOR
RADIATOR
PROVIDE HEAT
EXCHANGERS, PIPING
AND ALL ASSOCIATED
APPURTENANCES
REQUIRED BY
MANUFACTURER
REMOVE &
RELOCATE
EXISTING
EF-23 ALONG
WITH STARTER
EXISTING
ENERGY
RECOVERY
PIPING TO
REMAIN
PROVIDE NEW
15000 CFM
EXHAUST FAN
1211109876543
A
B
C
D
E
SUB-STATION NO. 4
P 8
MA
TC
HL
IN
E
PENTHOUSE POWER PLAN (WEST)
SCALE: 1/8" = 1'-0"
0 8' 16' 1/8"=1'-0"
TRUE NORTH
PLAN NORTH
CHECKED BY
DRAWN BY
FLOOR NUMBER
DRAWING TITLE
SHEET
NUMBER
SUBMISSION DATE
SUBMISSION STAGE
GSA PM
GSA PROJECT NO.
PROJECT
DESCRIPTION
PROJECT TITLE
BUILDING NAME
ADDRESS
BUILDING NUMBER
PRIME CONTR. NO.
PRIME ORDER NO.
CONST. CONTR.
A/E
SUB A/E
CONST. CONTR. NO.
SHEET SIZE:
DATE DRAWN:
36 X 48
SH
EE
T I
DE
NT
IFI
CA
TIO
N
DISCIPLINE
PR
OJ
EC
T
ID
EN
TIF
IC
AT
IO
N
BU
ILD
IN
G
BIM FILE NAME
CO
NT
RA
CT
OR
S
RE
VI
SI
ON
B
LO
CK
GR
AP
HI
C
SC
AL
E
KE
Y
PL
AN
ST
AM
P
OR
S
EA
L
DE
SI
GN
ER
ID
EN
TIF
IC
AT
IO
N
OW
NE
R
ID
EN
TIF
IC
AT
IO
N
SHEET OF SHEETS
KRUECK & SEXTON ARCHITECTS, P.C.
400 MARYLAND AVENUE, SW
WASHINGTON, DC 20024
LYNDON B. JOHNSON FEDERAL BUILDING
DC0010ZZ
DC0010_M_3-4-6-7_r2020.rvt
WSP ENGINEERING
DEPARTMENT OF EDUCATION
CONSOLIDATION PROJECT
ISSUED FOR BID
HALLIE FUTTERMAN
RENOVATION OF FLOORS 3, 4, 6, & 7 OF THE EXISTING
BUILDING TO MEET THE DEPARTMENT OF
EDUCATION’S PROGRAMMATIC REQUIREMENTS.
GS-07-P-16-UC-D-7000
47PM0520F0002
47PM0520F0002
KRUECK & SEXTON ARCHITECTS
221 W ERIE ST
CHICAGO, IL 60654 (312) 787-0056
ARCHITECT
WSP ENGINEERING
ONE PENNSYLVANIA PLAZA, SECOND FLOOR
NEW YORK, NY 10119 (212) 465-5000
MEP ENGINEER
ATELIER TEN
45 E 20TH ST, 4TH FLOOR
NEW YORK, NY 10003 (312) 386-1400
SUSTAINABILITY CONSULTANT
THRESHOLD ACOUSTICS
141 W JACKSON BLVD, SUITE 2080
CHICAGO, IL 60604 (312) 386-1400
ACOUSTIC CONSULTANT
WEST EAST
MA
TC
HL
IN
E
GENERAL SERVICES ADMINISTRATION
NATIONAL CAPITAL REGION
PUBLIC BUILDING SERVICE, D.C. SERVICES DIV.
7TH & D STREET, S.W.
WASHINGTON, D.C. 20407
ISSUE
NO. DATE ISSUE
MECHANICAL
VARIES, SEE DRAWINGS
01 04/23/2021 ISSUED FOR BID
FORCADE DESIGN
1626 PAYNE STREET
EVANSTON, IL 60201 (847) 448-4270
5/
/2
4:
:4
PM
M-18-01
MECHANICAL GENERATOR PLAN - PENTHOUSE - WEST
4/23/21
04/23/21NM
PB
1/8" = 1'-0"1 Mechanical PENTHOUSE - WEST
12 13 14 15 16 17 18 19 20 21
D
E
C
B
A
PENTHOUSE POWER PLAN (EAST)
SCALE: 1/8" = 1'-0"
12 13 14 15 16 17 18 19 20 21
D
E
C
B
A
PENTHOUSE POWER PLAN (EAST)
SCALE: 1/8" = 1'-0"
MPP-1
M
M
M
M
AHU-6
AHU-2
AHU-5
AHU-1
EXISTING 1 1_
2" FUEL OIL RISER
PIPE IN PIPE 1"
FOS/FOR LINE
RUN IN 7TH
FLOOR
CEILING
PLENUM TO
GENERATOR
0 1' 2' 1 1/2"=1'-0"
TRUE NORTH
PLAN NORTH
CHECKED BY
DRAWN BY
FLOOR NUMBER
DRAWING TITLE
SHEET
NUMBER
SUBMISSION DATE
SUBMISSION STAGE
GSA PM
GSA PROJECT NO.
PROJECT
DESCRIPTION
PROJECT TITLE
BUILDING NAME
ADDRESS
BUILDING NUMBER
PRIME CONTR. NO.
PRIME ORDER NO.
CONST. CONTR.
A/E
SUB A/E
CONST. CONTR. NO.
SHEET SIZE:
DATE DRAWN:
36 X 48
SH
EE
T I
DE
NT
IFI
CA
TIO
N
DISCIPLINE
PR
OJ
EC
T
ID
EN
TIF
IC
AT
IO
N
BU
ILD
IN
G
BIM FILE NAME
CO
NT
RA
CT
OR
S
RE
VI
SI
ON
B
LO
CK
GR
AP
HI
C
SC
AL
E
KE
Y
PL
AN
ST
AM
P
OR
S
EA
L
DE
SI
GN
ER
ID
EN
TIF
IC
AT
IO
N
OW
NE
R
ID
EN
TIF
IC
AT
IO
N
SHEET OF SHEETS
KRUECK & SEXTON ARCHITECTS, P.C.
400 MARYLAND AVENUE, SW
WASHINGTON, DC 20024
LYNDON B. JOHNSON FEDERAL BUILDING
DC0010ZZ
DC0010_M_3-4-6-7_r2020.rvt
WSP ENGINEERING
DEPARTMENT OF EDUCATION
CONSOLIDATION PROJECT
ISSUED FOR BID
HALLIE FUTTERMAN
RENOVATION OF FLOORS 3, 4, 6, & 7 OF THE EXISTING
BUILDING TO MEET THE DEPARTMENT OF
EDUCATION’S PROGRAMMATIC REQUIREMENTS.
GS-07-P-16-UC-D-7000
47PM0520F0002
47PM0520F0002
KRUECK & SEXTON ARCHITECTS
221 W ERIE ST
CHICAGO, IL 60654 (312) 787-0056
ARCHITECT
WSP ENGINEERING
ONE PENNSYLVANIA PLAZA, SECOND FLOOR
NEW YORK, NY 10119 (212) 465-5000
MEP ENGINEER
ATELIER TEN
45 E 20TH ST, 4TH FLOOR
NEW YORK, NY 10003 (312) 386-1400
SUSTAINABILITY CONSULTANT
THRESHOLD ACOUSTICS
141 W JACKSON BLVD, SUITE 2080
CHICAGO, IL 60604 (312) 386-1400
ACOUSTIC CONSULTANT
WEST EAST
MA
TC
HL
IN
E
GENERAL SERVICES ADMINISTRATION
NATIONAL CAPITAL REGION
PUBLIC BUILDING SERVICE, D.C. SERVICES DIV.
7TH & D STREET, S.W.
WASHINGTON, D.C. 20407
ISSUE
NO. DATE ISSUE
MECHANICAL
VARIES, SEE DRAWINGS
01 04/23/2021 ISSUED FOR BID
FORCADE DESIGN
1626 PAYNE STREET
EVANSTON, IL 60201 (847) 448-4270
5/
/2
3:
:5
PM
M-18-02
MECHANICAL GENERATOR PLAN - PENTHOUSE - EAST
4/23/21
04/23/21Author
Checker
1/8" = 1'-0"1 Mechanical PENTHOUSE - EAST
SCOPE OF WORK
THE SCOPE OF WORK (SOW) AREAS FOR THIS PROJECT IS TO
REPLACE LIGHTING, POWER AND FIRE ALARM FOR FLOOR’S 3, 4,
6 AND 7TH FLOOR EXCEPT FOR THE EXISTING ELECTRICAL
ROOMS (8 PER FLOOR), TELECOM ROOMS (8 PER FLOOR),
STAIRWELLS, AND THE JANITOR’S CLOSETS. AS AN ADD
ALTERNATE WE ARE SHOWING A NEW STANDBY GENERATOR,
WHICH IS TO BE INSTALLED IN THE ROOF PENTHOUSE. ALSO,
INCLUDED THE ADD ALTERNATE IS THE NEW DISTRIBUTION FOR
THE STANDBY GENERATOR.
POWER - THE CONTRACTOR IS TO DEMOLISH ALL EXISTING
POWER CABLES FROM THE DEVICES ON THE FLOOR TO THE
EXISTING POWER PANELS IN THE ELECTRICAL CLOSETS FOR ALL
THE AREAS THAT ARE IN THE SOW. ALL NEW POWER WOULD BE
PROVIDED FROM THE EXISTING POWER PANELS AS SHOWN ON
THE CONTRACT DRAWINGS. THE ONLY EXCEPTION IS TO
PROVIDE NEW POWER PANEL FOR THE 7TH FLOOR SECURITY
ROOMS. ALL WORK IS TO BE DONE ONE FLOOR AT A TIME
EXCEPT FOR THE 7TH FLOOR. THE 7TH FLOOR WILL BE DONE IN 2
PHASES PER THE MATCH LINES INDICATED ON THE CONTRACT
DRAWINGS.
AS PART OF THE SCOPE OF WORK FOR THE 3RD, 4TH, 6TH FLOOR
TO THE EXISTING ELECTRICAL PANELS, THE EXISTING 2 SECTION
RP PANELS WILL NEED TO BE SEPARATED AND REFED WITHIN
THE ELECTRICAL CLOSET AS SHOWN ON THE ELECTRICAL
DETAIL SHEETS. ONE SECTION WILL FEED THE UN-SWITCHED
120/208 VOLT LOADS AND THE OTHER SECTION WILL FEED
SWITCHED LOADS. FOR THE 7TH FLOOR, SEVERAL 8 POLE
CONTACTORS PER PANEL SHALL BE PROVIDED TO CONTROL
THE CONTROLLED RECEPTACLES. ALL CONTACTOR SHALL BE
CONTROLLED BY BMS TIME CLOCK.
LIGHTING – ALL EXISTING ALL LIGHTING IS TO BE CONTROLLED
BY OCCUPANCY, DAYLIGHTING OR VACANCY SENSORS. THE
ENCLOSED 10’ BY 10’ OFFICES SHALL BE PROVIDED WITH
VACANCY SENSORS THAT WILL CONTROL 1 LIGHT FIXTURE. THE
10’ BY 15’ OFFICES WILL 2 LIGHT FIXTURES.
THE OVERALL AREA AND EMERGENCY LIGHTING SHALL BE
LOCALLY CONTROLLED BY ZONES AS SHOWN ON THE
CONTRACT DRAWINGS. A TYPICAL ZONE WILL HAVE
OCCUPANCY SENSORS, CORRIDOR SENSORS AND DAY LIGHT
SENSORS. THE CORRIDOR SENSOR WILL TURN ON ONLY THE
CORRIDOR LIGHT. THE DAY LIGHT SENSORS WILL DIM ONLY THE
FIRST ROW OF LIGHTS CLOSEST TO THE PERIMETER FAÇADE.
ONCE A PERSON ENTERS THE RESPECTIVE ZONE, THE
OCCUPANCY SENSOR WILL KEEP THE CORRIDOR LIGHT ON AND
TRIGGER THE OTHER 2 ROWS OF LIGHTS TO TURN ON. THIS
WILL THEN ALLOW DAYLIGHT SENSOR TO DIM THE DAY LIGHT
CONTROLLED LIGHT FIXTURE ONLY IF THE OVERALL ZONE IS
ACTIVATED. BATHROOMS SHALL HAVE ULTRASONIC TYPE
SENSORS. CONFERENCE ROOMS SHALL BE PROVIDED WITH 2
SLIDE DIMMERS AND A VACANCY SENSOR. THIS WILL ALLOW
FOR YOU TO ADJUST THE LIGHT LEVEL AS NEEDED IN THE
CENTER ABOVE THE CONFERENCE ROOM DESK OR THE ACCENT
LIGHT IN THE REAR OF THE CONFERENCE ROOM
INDEPENDENTLY.
PHASING – ALL FLOORS SHALL BE DONE ONE COMPLETE FLOOR
AT A TIME EXCEPT FOR THE 7TH FLOOR. THIS FLOORS SHALL BE
DONE IN 2 PHASES AS SHOWN ON THE CONTRACT DRAWING’S.
0 - - N.T.S.
CHECKED BY
DRAWN BY
FLOOR NUMBER
DRAWING TITLE
SHEET
NUMBER
SUBMISSION DATE
SUBMISSION STAGE
GSA PM
GSA PROJECT NO.
PROJECT
DESCRIPTION
PROJECT TITLE
BUILDING NAME
ADDRESS
BUILDING NUMBER
PRIME CONTR. NO.
PRIME ORDER NO.
CONST. CONTR.
A/E
SUB A/E
CONST. CONTR. NO.
SHEET SIZE:
DATE DRAWN:
36 X 48
S H
E E
T
ID
E N
TI
FI
C A
TI
O
N
DISCIPLINE
P R
O
JE
C T
ID
E
N
TI
FI
C
A
TI
O N
B U
IL
D
IN
G
BIM FILE NAME
C O
N
TR
A C
TO
R
S R
E V
IS
IO
N B
LO
C
K G
R A
P H
IC
S
C A
LE
K
E Y
P
LA
N S
TA
M
P O
R S
E A
L D
E S
IG
N
E R
ID
E
N
TI
FI
C
A
TI
O N
O W
N E
R
ID
E N
TI
FI
C A
TI
O
N
SHEET OF SHEETS
KRUECK & SEXTON ARCHITECTS, P.C.
400 MARYLAND AVENUE, SW
WASHINGTON, DC 20024
LYNDON B. JOHNSON FEDERAL BUILDING
DC0010ZZ
DC0010_E_3-4-6-7_r2020.rvt
WSP ENGINEERING
DEPARTMENT OF EDUCATION
CONSOLIDATION PROJECT
ISSUED FOR BID
HALLIE FUTTERMAN
RENOVATION OF FLOORS 3, 4, 6, & 7 OF THE EXISTING
BUILDING TO MEET THE DEPARTMENT OF
EDUCATION’S PROGRAMMATIC REQUIREMENTS.
GS-07-P-16-UC-D-7000
47PM0520F0002
47PM0520F0002
KRUECK & SEXTON ARCHITECTS
221 W ERIE ST
CHICAGO, IL 60654 (312) 787-0056
ARCHITECT
WSP ENGINEERING
ONE PENNSYLVANIA PLAZA, SECOND FLOOR
NEW YORK, NY 10119 (212) 465-5000
MEP ENGINEER
ATELIER TEN
45 E 20TH ST, 4TH FLOOR
NEW YORK, NY 10003 (312) 386-1400
SUSTAINABILITY CONSULTANT
THRESHOLD ACOUSTICS
141 W JACKSON BLVD, SUITE 2080
CHICAGO, IL 60604 (312) 386-1400
ACOUSTIC CONSULTANT
WEST EAST
M A
TC
H
LI
N
E
GENERAL SERVICES ADMINISTRATION
NATIONAL CAPITAL REGION
PUBLIC BUILDING SERVICE, D.C. SERVICES DIV.
7TH & D STREET, S.W.
WASHINGTON, D.C. 20407
ISSUE
NO. DATE ISSUE
ELECTRICAL
VARIES, SEE DRAWINGS
01 04/23/2021 ISSUED FOR BID
FORCADE DESIGN
1626 PAYNE STREET
EVANSTON, IL 60201 (847) 448-4270
ENVIRONMENTAL GRAPHICS CONSULTANT
/2
/2
:0
:4
P
M
E-00-01
ELECTRICAL DRAWING LIST, SCOPE OF WORK & NOTES
04/23/2021
04/23/21NJA
RO
1 62
ELECTRICAL DRAWING LIST
DRAWING NO. DESCRIPTION
E-00-01 ELECTRICAL DRAWING LIST, SCOPE OF WORK & NOTES
E-00-02 ELECTRICAL LEGENDS, SYMBOLS & ABBREVIATIONS
ELD-13-00 ELECTRICAL DEMOLITION LIGHTING PLAN - LEVEL 3 - OVERALL
ELD-14-00 ELECTRICAL DEMOLITION LIGHTING PLAN - LEVEL 4 - OVERALL
ELD-16-00 ELECTRICAL DEMOLITION LIGHTING PLAN - LEVEL 6 - OVERALL
ELD-17-00 ELECTRICAL DEMOLITION LIGHTING PLAN - LEVEL 7 - OVERALL
EPD-13-01 ELECTRICAL DEMOLITION POWER 3RD, 4TH & 6TH FLOOR PLANS - WEST
EPD-13-02 ELECTRICAL DEMOLITION POWER 3RD, 4TH & 6TH FLOOR PLANS - EAST
EPD-17-01 ELECTRICAL DEMOLITION POWER 7TH FLOOR PLAN - WEST
EPD-17-02 ELECTRICAL DEMOLITION POWER 7TH FLOOR PLAN - EAST
EL-13-00 ELECTRICAL LIGHTING PLAN - LEVEL 3 - OVERALL
EL-13-01 ELECTRICAL LIGHTING PLAN - LEVEL 3 - WEST
EL-13-02 ELECTRICAL LIGHTING PLAN - LEVEL 3 - EAST
EL-14-00 ELECTRICAL LIGHTING PLAN - LEVEL 4 - OVERALL
EL-14-01 ELECTRICAL LIGHTING PLAN - LEVEL 4 - WEST
EL-14-02 ELECTRICAL LIGHTING PLAN - LEVEL 4 - EAST
EL-16-00 ELECTRICAL LIGHTING PLAN - LEVEL 6 - OVERALL
EL-16-01 ELECTRICAL LIGHTING PLAN - LEVEL 6 - WEST
EL-16-02 ELECTRICAL LIGHTING PLAN - LEVEL 6 - EAST
EL-17-00 ELECTRICAL LIGHTING PLAN - LEVEL 7 - OVERALL
EL-17-01 ELECTRICAL LIGHTING PLAN - LEVEL 7 - WEST
EL-17-02 ELECTRICAL LIGHTING PLAN - LEVEL 7 - EAST
EP-13-00 ELECTRICAL POWER PLAN - LEVEL 3 - OVERALL
EP-13-01 ELECTRICAL POWER PLAN - LEVEL 3 - WEST
EP-13-02 ELECTRICAL POWER PLAN - LEVEL 3 - EAST
EP-14-00 ELECTRICAL POWER PLAN - LEVEL 4 - OVERALL
EP-14-01 ELECTRICAL POWER PLAN - LEVEL 4 - WEST
EP-14-02 ELECTRICAL POWER PLAN - LEVEL 4 - EAST
EP-16-00 ELECTRICAL POWER PLAN - LEVEL 6 - OVERALL
EP-16-01 ELECTRICAL POWER PLAN - LEVEL 6 - WEST
EP-16-02 ELECTRICAL POWER PLAN - LEVEL 6 - EAST
EP-17-00 ELECTRICAL POWER PLAN - LEVEL 7 - OVERALL
EP-17-01 ELECTRICAL POWER PLAN - LEVEL 7 - WEST
EP-17-02 ELECTRICAL POWER PLAN - LEVEL 7 - EAST
EP-18-01 ELECTRICAL POWER PLAN - PENTHOUSE - WEST
E-23-01 ELECTRICAL ENLARGED PLANS - LEVEL 3 - WEST
E-23-02 ELECTRICAL ENLARGED PLANS - LEVEL 3 - EAST
E-24-01 ELECTRICAL ENLARGED PLANS - LEVEL 4 - WEST
E-24-02 ELECTRICAL ENLARGED PLANS - LEVEL 4 - EAST
E-26-01 ELECTRICAL ENLARGED PLANS - LEVEL 6 - WEST
E-26-02 ELECTRICAL ENLARGED PLANS - LEVEL 6 - EAST
E-27-01 ELECTRICAL ENLARGED PLANS - LEVEL 7 - WEST
E-27-02 ELECTRICAL ENLARGED PLANS - LEVEL 7 - EAST
E-50-00 EXISTING POWER RISER DIAGRAM - WEST
E-50-01 EXISTING POWER RISER DIAGRAM - EAST
E-50-02 EXISTING EMERGENCY RISER DIAGRAM
E-50-03 EMERGENCY RISER DIAGRAM - MODIFICATION
E-60-00 ELECTRICAL PANEL SCHEDULES - LEVEL 3 - WEST
E-60-01 ELECTRICAL PANEL SCHEDULES - LEVEL 3 - EAST
E-60-02 ELECTRICAL PANEL SCHEDULES - LEVEL 4 - WEST
E-60-03 ELECTRICAL PANEL SCHEDULES - LEVEL 4 - EAST
E-60-04 ELECTRICAL PANEL SCHEDULES - LEVEL 6 - WEST
E-60-05 ELECTRICAL PANEL SCHEDULES - LEVEL 6 - EAST
E-60-06 ELECTRICAL PANEL SCHEDULES - LEVEL 7 - WEST
E-60-07 ELECTRICAL PANEL SCHEDULES - LEVEL 7 - EAST
E-60-08 ELECTRICAL LIGHT FIXTURE SCHEDULE
E-60-09 ELECTRICAL PANEL SCHEDULES - EM RISER MOD
E-70-00 ELECTRICAL DETAILS 1
E-70-01 ELECTRICAL LIGHTING DETAILS 1
E-70-02 ELECTRICAL LIGHTING DETAILS 2
E-70-03 ELECTRICAL LIGHTING DETAILS 3
E-70-04 ELECTRICAL DETAILS 2
GENERAL NOTES:
1. CONTRACTOR TO REPLACE ALL BREAKERS IN ALL
EXISTING 3RD , 4TH , 6 AND 7TH FLOOR LPD, RPD, CPD
AND CPH POWER PANELS WITH NEW CIRCUIT BREAKERS.
0 - - N.T.S.
CHECKED BY
DRAWN BY
FLOOR NUMBER
DRAWING TITLE
SHEET
NUMBER
SUBMISSION DATE
SUBMISSION STAGE
GSA PM
GSA PROJECT NO.
PROJECT
DESCRIPTION
PROJECT TITLE
BUILDING NAME
ADDRESS
BUILDING NUMBER
PRIME CONTR. NO.
PRIME ORDER NO.
CONST. CONTR.
A/E
SUB A/E
CONST. CONTR. NO.
SHEET SIZE:
DATE DRAWN:
36 X 48
S H
E E
T
ID
E N
TI
FI
C A
TI
O
N
DISCIPLINE
P R
O
JE
C T
ID
E
N
TI
FI
C
A
TI
O N
B U
IL
D
IN
G
BIM FILE NAME
C O
N
TR
A C
TO
R
S R
E V
IS
IO
N B
LO
C
K G
R A
P H
IC
S
C A
LE
K
E Y
P
LA
N S
TA
M
P O
R S
E A
L D
E S
IG
N
E R
ID
E
N
TI
FI
C
A
TI
O N
O W
N E
R
ID
E N
TI
FI
C A
TI
O
N
SHEET OF SHEETS
KRUECK & SEXTON ARCHITECTS, P.C.
400 MARYLAND AVENUE, SW
WASHINGTON, DC 20024
LYNDON B. JOHNSON FEDERAL BUILDING
DC0010ZZ
DC0010_E_3-4-6-7_r2020.rvt
WSP ENGINEERING
DEPARTMENT OF EDUCATION
CONSOLIDATION PROJECT
ISSUED FOR BID
HALLIE FUTTERMAN
RENOVATION OF FLOORS 3, 4, 6, & 7 OF THE EXISTING
BUILDING TO MEET THE DEPARTMENT OF
EDUCATION’S PROGRAMMATIC REQUIREMENTS.
GS-07-P-16-UC-D-7000
47PM0520F0002
47PM0520F0002
KRUECK & SEXTON ARCHITECTS
221 W ERIE ST
CHICAGO, IL 60654 (312) 787-0056
ARCHITECT
WSP ENGINEERING
ONE PENNSYLVANIA PLAZA, SECOND FLOOR
NEW YORK, NY 10119 (212) 465-5000
MEP ENGINEER
ATELIER TEN
45 E 20TH ST, 4TH FLOOR
NEW YORK, NY 10003 (312) 386-1400
SUSTAINABILITY CONSULTANT
THRESHOLD ACOUSTICS
141 W JACKSON BLVD, SUITE 2080
CHICAGO, IL 60604 (312) 386-1400
ACOUSTIC CONSULTANT
WEST EAST
M A
TC
H
LI
N
E
GENERAL SERVICES ADMINISTRATION
NATIONAL CAPITAL REGION
PUBLIC BUILDING SERVICE, D.C. SERVICES DIV.
7TH & D STREET, S.W.
WASHINGTON, D.C. 20407
ISSUE
NO. DATE ISSUE
ELECTRICAL
VARIES, SEE DRAWINGS
01 04/23/2021 ISSUED FOR BID
FORCADE DESIGN
1626 PAYNE STREET
EVANSTON, IL 60201 (847) 448-4270
ENVIRONMENTAL GRAPHICS CONSULTANT
/2
/2
:3
:3
A M
E-60-07
ELECTRICAL PANEL SCHEDULES - LEVEL 7 - EAST
04/23/2021
06/28/20NJA
RO
55 61
RPC7 (SEC-1) RPC7 (SEC-2) CPC7 LPC7
RPD7 (SEC-1) RPD7 (SEC-2) CPD7 LPD7
RPG7 - CPG7 ERD7
RPH7 - CPH7 -
NOTES:
TOTAL ESTIMATED DEMAND: 35.1 97.5
TOTAL CONNECTED LOAD: 49.6 137.7
ADDED CONNECTED LOAD: 49.6
REMOVED CONNECTED LOAD: 0
EXISTING CONNECTED LOAD: 0
Receptacle 38960 VA 24480 VA kVA AMPS
LOAD CLASSIFICATION CONNECTED LOAD (VA)
ESTIMATED DEMAND
(VA)
PANEL TOTALS
130 A / 150 A / 136 A
C71#41 SPARE -- 20 1 0 / 0 1 20 -- SPARE C71#42
C71#39 SPARE -- 20 1 0 / 0 1 20 -- SPARE C71#40
C71#37 SPARE -- 20 1 0 / 0 1 20 -- SPARE C71#38
C71#35 SPARE -- 20 1 0 / 0 1 20 -- SPARE C71#36
C71#33 SPARE -- 20 1 0 / 0 1 20 -- SPARE C71#34
C71#31 SPARE -- 20 1 0 / 0 1 20 -- SPARE C71#32
C71#29 SPARE -- 20 1 0 / 0 1 20 -- SPARE C71#30
C71#27 SPARE -- 20 1 0 / 0 1 20 -- SPARE C71#28
C71#25 7C255 - FOCUS ROOM RECEPTACLES 360 20 1 360 / 0 1 20 -- SPARE C71#26
C71#23 7B214, 7B215, 7B216 - OFFICE RECEPT. 540 20 1 540 / 720 1 20 720 XXXXX - WORKSTATION 14 RECEPT. C71#24
C71#21 7B214, 7B215, 7B216 - OFFICE RECEPT. 540 20 1 540 / 720 1 20 720 XXXXX - WORKSTATION 14 RECEPT. C71#22
C71#19 7B210, 7B211, 7B212, 7B213 - RECEPT. 720 20 1 720 / 720 1 20 720 XXXXX - WORKSTATION 13 RECEPT. C71#20
C71#17 7B210, 7B211, 7B212, 7B213 - RECEPT. 720 20 1 720 / 720 1 20 720 XXXXX - WORKSTATION 13 RECEPT. C71#18
C71#15 7B253, 7B254, 7B255 - CONF. RECEPT. 720 20 1 720 / 540 1 20 540 XXXXX, XXXXX - CONV. RECEPTACLES C71#16
C71#13 7B253, 7B254, 7B255 - CONF. RECEPT. 720 20 1 720 / 540 1 20 540 XXXXX, XXXXX - CONV. RECEPTACLES C71#14
C71#11 7B250, 7B251, 7B252 - CONF. RECEPT. 720 20 1 720 / 720 1 20 720 XXXXX - WORKSTATION 12 RECEPT. C71#12
C71#9 7B250, 7B251, 7B252 - CONF. RECEPT. 720 20 1 720 / 720 1 20 720 XXXXX - WORKSTATION 12 RECEPT. C71#10
C71#7 7B153, 7B154, 7B155 - CONF. RECEPT. 720 20 1 720 / 720 1 20 720 XXXXX - WORKSTATION 11 RECEPT. C71#8
C71#5 7B153, 7B154, 7B155 - CONF. RECEPT. 720 20 1 720 / 720 1 20 720 XXXXX - WORKSTATION 11 RECEPT. C71#6
C71#3 7B150, 7B151, 7B152 - CONF. RECEPT. 720 20 1 720 / 720 1 20 720 XXXXX - WORKSTATION 10 RECEPT. C71#4
C71#1 7B150, 7B151, 7B152 - CONF. RECEPT. 720 20 1 720 / 720 1 20 720 XXXXX - WORKSTATION 10 RECEPT. C71#2
CKT
NO.
DESCRIPTION
TOTAL
LOAD
(VA)
CIRCUIT
BREAKER
AMPS / POLES
A B C
CIRCUIT
BREAKER
POLES /...
TOTAL
LOAD
(VA)
DESCRIPTION CKT
NO.
AIC RATING: 10000 A NUMBER OF SECTIONS: 1 POLES PER SECTION: 42
AIC AVAILABLE: PANEL LUGS: MCB FEED THROUGH LUGS: YES
VOLTAGE: 120/208 WYE MOUNTING: SURFACE 200% NEUTRAL: NO
MCB: 150A BUS TYPE: COPPER ISOLATED GROUND BUS: NO
MAIN BUS: 225 A ENCLOSURE: NEMA 1 GROUND BUS: YES
LOCATION: ELECTRICAL 7BEL3 WIRES: 4W + G NEUTRAL BUS: YES
EXIST: RPC7 (SEC-1) FED FROM: NORMAL
NOTES:
TOTAL ESTIMATED DEMAND: 34.6 96.1
TOTAL CONNECTED LOAD: 38.0 105.5
ADDED CONNECTED LOAD: 38
REMOVED CONNECTED LOAD: 0
Receptacle 16820 VA 13410 VA EXISTING CONNECTED LOAD: 0
Other 1440 VA 1440 VA kVA AMPS
LOAD CLASSIFICATION CONNECTED LOAD (VA)
ESTIMATED DEMAND
(VA)
PANEL TOTALS
83 A / 127 A / 115 A
D71#41 XXXXX - DEDICATED FOR... 1,000 20 1 1000 / 1452 -- -- -- -- D71#42
D71#39 XXXXX - DEDICATED FOR VAV'S 1,000 20 1 1000 / 1452 -- -- -- -- D71#40
D71#37 XXXXX - DEDICATED FOR VAV'S 1,000 20 1 1000 / 1452 3 25 4,356 XXXXX - AC-7-7 DISCONNECT D71#38
D71#35 -- -- -- -- 2050 / 180 1 20 180 XXXXX - AC-7-7 COND. PUMP RECEPT. D71#36
D71#33 7C289 - RESTROOM INST. HEATER... 4,100 30 2 2050 / 0 1 20 -- SPARE D71#34
D71#31 SPARE -- 20 1 0 / 0 1 20 -- SPARE D71#32
D71#29 SPARE -- 20 1 0 / 540 1 20 540 7C290 - OFFICE RECEPTACLES D71#30
D71#27 SPARE -- 20 1 0 / 1440 1 20 1,440 7C288 - OFFICE POKE-THRU D71#28
D71#25 SPARE -- 20 1 0 / 720 1 20 720 7C288 - DEPUTY SEC. OFFICE RECEPT. D71#26
D71#23 -- -- -- -- 4150 / 540 1 20 540 7C288, 7C289 - CONV. RECEPTACLES D71#24
D71#21 7C202 - PANTRY INST. HEATER DISC. 8,300 60 2 4150 / 720 1 20 720 7C284, 7C285, 7C286, 7C287 - T.V.'S D71#22
D71#19 7C293 - CHIEF OF SEC. RECEPT. & T.V. 540 20 1 540 / 720 1 20 720 7C284, 7C285, 7C286, 7C287 - RECEPT. D71#20
D71#17 7C202 - PANTRY RECEPTACLE 180 20 1 180 / 720 1 20 720 7C284, 7C285, 7C286, 7C287 - RECEPT. D71#18
D71#15 7C202 - PANTRY RECEPTACLE 180 20 1 180 / 720 1 20 720 XXXXX - WORKSTATION 17 RECEPT. D71#16
D71#13 7C202 - PANTRY PRINTER RECEPT. 1,000 20 1 1000 / 720 1 20 720 XXXXX - WORKSTATION 17 RECEPT. D71#14
D71#11 7C210, 7C211, 7C212 - RECEPTACLES 540 20 1 540 / 720 1 20 720 XXXXX - WORKSTATION 16 RECEPT. D71#12
D71#9 7C210, 7C211, 7C212 - RECEPTACLES 540 20 1 540 / 720 1 20 720 XXXXX - WORKSTATION 16 RECEPT. D71#10
D71#7 7C150 - CONF. FLOOR BOX RECEPT. 1,500 20 1 1500 / 720 1 20 720 XXXXX - WORKSTATION 15 RECEPT. D71#8
D71#5 7C150, 7C251 - CONF/HUDDLE RECEPT. 540 20 1 540 / 720 1 20 720 XXXXX - WORKSTATION 15 RECEPT. D71#6
D71#3 7C150, 7C251, 7C253 - CONV. RECEPT. 720 20 1 720 / 1000 1 20 1,000 XXXXX - COPY/PRINTER D71#4
D71#1 7C150, 7C252 - CONF./FOCUS RECEPT. 720 20 1 720 / 900 1 20 900 XXXXX, XXXXX - CONV. RECEPT. & T.V. D71#2
CKT
NO.
DESCRIPTION
TOTAL
LOAD
(VA)
CIRCUIT
BREAKER
AMPS / POLES
A B C
CIRCUIT
BREAKER
POLES /...
TOTAL
LOAD
(VA)
DESCRIPTION CKT
NO.
AIC RATING: 0 A NUMBER OF SECTIONS: POLES PER SECTION:
AIC AVAILABLE: PANEL LUGS: MCB FEED THROUGH LUGS: NO
VOLTAGE: 120/208 WYE MOUNTING: 200% NEUTRAL: NO
MCB: BUS TYPE: ISOLATED GROUND BUS: NO
MAIN BUS: 225 A ENCLOSURE: GROUND BUS: NO
LOCATION: Space 4A256 WIRES: 3W NEUTRAL BUS: NO
EXIST: RPD7 FED FROM:
NOTES:
TOTAL ESTIMATED DEMAND: 17.8 49.4
TOTAL CONNECTED LOAD: 22.6 62.7
ADDED CONNECTED LOAD: 22.6
REMOVED CONNECTED LOAD: 0
EXISTING CONNECTED LOAD: 0
Receptacle 19600 VA 14800 VA kVA AMPS
LOAD CLASSIFICATION CONNECTED LOAD (VA)
ESTIMATED DEMAND
(VA)
PANEL TOTALS
83 A / 56 A / 51 A
G7#41 7BEL2 - DEDICATED FOR THERMOSTAT 1,000 20 1 1000 / 0 1 20 -- SPARE G7#42
G7#39 7BEL2 - DEDICATED FOR VAV'S 1,000 20 1 1000 / 0 1 20 -- SPARE G7#40
G7#37 7BEL2 - DEDICATED FOR VAV'S 1,000 20 1 1000 / 0 1 20 -- SPARE G7#38
G7#35 SPARE -- 20 1 0 / 0 1 20 -- SPARE G7#36
G7#33 SPARE -- 20 1 0 / 0 1 20 -- SPARE G7#34
G7#31 SPARE -- 20 1 0 / 0 1 20 -- SPARE G7#32
G7#29 SPARE -- 20 1 0 / 0 1 20 -- SPARE G7#30
G7#27 SPARE -- 20 1 0 / 360 1 20 360 7CMEN - CONV. RECEPTACLES G7#28
G7#25 SPARE -- 20 1 0 / 1500 1 20 1,500 7CPN - EAST PANTRY MICROWAVE G7#26
G7#23 XXXXX - COPY/PRINTER 1,000 20 1 1000 / 180 1 20 180 7CPN - ABOVE COUNTER RECEPTACLE G7#24
G7#21 XXXXX - COPY/PRINTER 1,000 20 1 1000 / 180 1 20 180 7CPN - ABOVE COUNTER RECEPTACLE G7#22
G7#19 XXXXX - CONVENIENCE RECEPTACLES 1,080 20 1 1080 / 1500 1 20 1,500 7CPN - EAST PANTRY MICROWAVE G7#20
G7#17 XXXXX - WORKSTATION 30 RECEPT. 720 20 1 720 / 1000 1 20 1,000 7CPN - REFRIGERATOR G7#18
G7#15 XXXXX - WORKSTATION 30 RECEPT. 720 20 1 720 / 180 1 20 180 7B102 - COPY T.V. RECEPTACLE G7#16
G7#13 XXXXX, XXXXX - OFFICE RECEPT. 1,080 20 1 1080 / 1000 1 20 1,000 7B102 - COPY/PRINTER G7#14
G7#11 XXXXX - WORKSTATION 29 RECEPT. 720 20 1 720 / 180 1 20 180 7B100 - CORRIDOR WATER FOUNTAIN G7#12
G7#9 XXXXX - WORKSTATION 29 RECEPT. 720 20 1 720 / 1080 1 20 1,080 7BLV2, 7CPN - CONV. RECEPT. & T.V.'S G7#10
G7#7 XXXXX - WORKSTATION 28 RECEPT. 720 20 1 720 / 540 1 20 540 7B114, 7B115, 7B116 - OFFICE RECEPT. G7#8
G7#5 XXXXX - WORKSTATION 28 RECEPT. 720 20 1 720 / 540 1 20 540 7B114, 7B115, 7B116 - OFFICE RECEPT. G7#6
G7#3 XXXXX - WORKSTATION 27 RECEPT. 720 20 1 720 / 720 1 20 720 7B110, 7B111, 7B112, 7B113 - RECEPT. G7#4
G7#1 XXXXX - WORKSTATION 27 RECEPT. 720 20 1 720 / 720 1 20 720 7B110, 7B111, 7B112, 7B113 - RECEPT. G7#2
CKT
NO.
DESCRIPTION
TOTAL
LOAD
(VA)
CIRCUIT
BREAKER
AMPS / POLES
A B C
CIRCUIT
BREAKER
POLES /...
TOTAL
LOAD
(VA)
DESCRIPTION CKT
NO.
AIC RATING: 0 A NUMBER OF SECTIONS: POLES PER SECTION:
AIC AVAILABLE: PANEL LUGS: MCB FEED THROUGH LUGS: NO
VOLTAGE: 120/208 WYE MOUNTING: 200% NEUTRAL: NO
MCB: BUS TYPE: ISOLATED GROUND BUS: NO
MAIN BUS: 100 A ENCLOSURE: GROUND BUS: NO
LOCATION: TELECOM-54 7BTL1-54 WIRES: 3W NEUTRAL BUS: NO
EXIST: RPG7 FED FROM:
NOTES:
TOTAL ESTIMATED DEMAND: 24.2 67.2
TOTAL CONNECTED LOAD: 29.9 82.9
ADDED CONNECTED LOAD: 29.9
REMOVED CONNECTED LOAD: 0
Receptacle 21320 VA 15660 VA EXISTING CONNECTED LOAD: 0
Other 1440 VA 1440 VA kVA AMPS
LOAD CLASSIFICATION CONNECTED LOAD (VA)
ESTIMATED DEMAND
(VA)
PANEL TOTALS
89 A / 82 A / 79 A
H7#41 XXXXX - DEDICATED FOR... 1,000 20 1 1000 / 0 1 20 -- SPARE H7#42
H7#39 XXXXX - DEDICATED FOR VAV'S 1,000 20 1 1000 / 0 1 20 -- SPARE H7#40
H7#37 XXXXX - DEDICATED FOR VAV'S 1,000 20 1 1000 / 0 1 20 -- SPARE H7#38
H7#35 SPARE -- 20 1 0 / 0 1 20 -- SPARE H7#36
H7#33 SPARE -- 20 1 0 / 0 1 20 -- SPARE H7#34
H7#31 SPARE -- 20 1 0 / 540 1 20 540 7C189 - CONV. RECEPTACLES H7#32
H7#29 SPARE -- 20 1 0 / 2050 -- -- -- -- H7#30
H7#27 SPARE -- 20 1 0 / 2050 2 30 4,100 7C188 - RESTROOM INST. HEATER... H7#28
H7#25 SPARE -- 20 1 0 / 1440 1 20 1,440 XXXXX - POKE-THRU H7#26
H7#23 7C185, 7C186 - OFFICE RECEPT. & T.V. 540 20 1 540 / 540 1 20 540 XXXXX, 7C188 - CONVENIENCE REC. H7#24
H7#21 7C185, 7C186 - OFFICE RECEPT. & T.V. 540 20 1 540 / 540 1 20 540 XXXXX, 7C188 - CONVENIENCE REC. H7#22
H7#19 7C102, XXXXX - CONV. RECEPTACLES 1,080 20 1 1080 / 1500 1 20 1,500 7C155 - CONF. FLOOR BOX RECEPT. H7#20
H7#17 XXXXX - COPY/PRINTER 1,000 20 1 1000 / 1500 1 20 1,500 7C155 - CONF. FLOOR BOX RECEPT. H7#18
H7#15 XXXXX, 7C101, 7C180 - CONV. RECEPT. 1,260 20 1 1260 / 1500 1 20 1,500 7C155 - CONF. FLOOR BOX RECEPT. H7#16
H7#13 7C102 - RECEPTION PRINTER 1,000 20 1 1000 / 1500 1 20 1,500 7C155 - CONF. FLOOR BOX RECEPT. H7#14
H7#11 7C102 - RECEPTION RECEPTACLES 360 20 1 360 / 900 1 20 900 7C155 - CONFERENCE ROOM RECEPT. H7#12
H7#9 XXXXX - WORKSTATION 33 RECEPT. 720 20 1 720 / 900 1 20 900 7C155 - CONFERENCE ROOM RECEPT. H7#10
H7#7 XXXXX - WORKSTATION 32 RECEPT. 720 20 1 720 / 540 1 20 540 7C105, 7C151 - CONV. RECEPTACLES H7#8
H7#5 XXXXX - WORKSTATION 32 RECEPT. 720 20 1 720 / 900 1 20 900 7C151, 7C172, 7C153, 7C154 - RECEPT. H7#6
H7#3 XXXXX - WORKSTATION 31 RECEPT. 720 20 1 720 / 540 1 20 540 7C110, 7C111, 7C112 - RECEPTACLES H7#4
H7#1 XXXXX - WORKSTATION 31 RECEPT. 720 20 1 720 / 540 1 20 540 7C110, 7C111, 7C112 - RECEPTACLES H7#2
CKT
NO.
DESCRIPTION
TOTAL
LOAD
(VA)
CIRCUIT
BREAKER
AMPS / POLES
A B C
CIRCUIT
BREAKER
POLES /...
TOTAL
LOAD
(VA)
DESCRIPTION CKT
NO.
AIC RATING: 0 A NUMBER OF SECTIONS: POLES PER SECTION:
AIC AVAILABLE: PANEL LUGS: MCB FEED THROUGH LUGS: NO
VOLTAGE: 120/208 WYE MOUNTING: 200% NEUTRAL: NO
MCB: BUS TYPE: ISOLATED GROUND BUS: NO
MAIN BUS: 100 A ENCLOSURE: GROUND BUS: NO
LOCATION: Space 4A258 WIRES: 3W NEUTRAL BUS: NO
EXIST: RPH7 FED FROM:
NOTES:
TOTAL ESTIMATED DEMAND: 26.7 74.0
TOTAL CONNECTED LOAD: 32.7 90.8
ADDED CONNECTED LOAD: 32.7
REMOVED CONNECTED LOAD: 0
EXISTING CONNECTED LOAD: 0
Receptacle 22040 VA 16020 VA kVA AMPS
LOAD CLASSIFICATION CONNECTED LOAD (VA)
ESTIMATED DEMAND
(VA)
PANEL TOTALS
80 A / 105 A / 90 A
C72#83 7BEL3 - DEDICATED FOR THERMOSTAT 1,000 20 1 1000 / 1452 -- -- -- -- C72#84
C72#81 7BEL3 - DEDICATED FOR VAV'S 1,000 20 1 1000 / 1452 -- -- -- -- C72#82
C72#79 7BEL3 - DEDICATED FOR VAV'S 1,000 20 1 1000 / 1452 3 25 4,356 7BTL3 - AC-7-5 DISCONNECT C72#80
C72#77 7CUNI, 7CWMN - CONV. RECEPTACLES 540 20 1 540 / 180 1 20 180 7BTL3 - AC-7-5 COND. PUMP RECEPT. C72#78
C72#75 7CPN - REFRIGERATOR 1,000 20 1 1000 / 0 1 20 -- SPARE C72#76
C72#73 7CPN - REFRIGERATOR 1,000 20 1 1000 / 0 1 20 -- SPARE C72#74
C72#71 7CPN - VENDING MACHINE 500 20 1 500 / 0 1 20 -- SPARE C72#72
C72#69 7CPN - VENDING MACHINE 500 20 1 500 / 0 1 20 -- SPARE C72#70
C72#67 XXXXX - CORRIDOR WATER FOUNTAIN 180 20 1 180 / 0 1 20 -- SPARE C72#68
C72#65 7B255 - CONF. FLOOR BOX RECEPT. 1,500 20 1 1500 / 0 1 20 -- SPARE C72#66
C72#63 7B255 - CONF. FLOOR BOX RECEPT. 1,500 20 1 1500 / 0 1 20 -- SPARE C72#64
C72#61 7B253, 7B254, 7B255 - CONF. RECEPT. 720 20 1 720 / 0 1 20 -- SPARE C72#62
C72#59 7B250, 7B251, 7B252 - CONF. RECEPT. 720 20 1 720 / 0 1 20 -- SPARE C72#60
C72#57 7B250 - CONF. FLOOR BOX RECEPT. 1,500 20 1 1500 / 0 1 20 -- SPARE C72#58
C72#55 7B250 - CONF. FLOOR BOX RECEPT. 1,500 20 1 1500 / 150 1 20 150 7CMEN, 7CWMN, 7CPN - FAUCET,... C72#56
C72#53 7B155 - CONF. FLOOR BOX RECEPT. 1,500 20 1 1500 / 1500 -- -- -- -- C72#54
C72#51 7B155 - CONF. FLOOR BOX RECEPT. 1,500 20 1 1500 / 1500 2 20 3,000 7CPN - EAST PANTRY EWH C72#52
C72#49 7B153, 7B154, 7B155 - CONF. RECEPT. 720 20 1 720 / 150 1 20 150 7C1VES, 7C2VES - DR WAVE... C72#50
C72#47 7B150, 7B151, 7B152 - RECEPTACLES 720 20 1 720 / 1000 1 20 1,000 XXXXX - COPY/PRINTER C72#48
C72#45 7B150 - CONF. FLOOR BOX RECEPT. 1,500 20 1 1500 / 1000 1 20 1,000 XXXXX - COPY/PRINTER C72#46
C72#43 7B150 - CONF. FLOOR BOX RECEPT. 1,500 20 1 1500 / 1260 1 20 1,260 XXXXX - CONVENIENCE RECEPTACLES C72#44
CKT
NO.
DESCRIPTION
TOTAL
LOAD
(VA)
CIRCUIT
BREAKER
AMPS / POLES
A B C
CIRCUIT
BREAKER
POLES /...
TOTAL
LOAD
(VA)
DESCRIPTION CKT
NO.
AIC RATING: 10000 A NUMBER OF SECTIONS: 1 POLES PER SECTION: 42
AIC AVAILABLE: PANEL LUGS: MLO FEED THROUGH LUGS: YES
VOLTAGE: 120/208 WYE MOUNTING: SURFACE 200% NEUTRAL: NO
MCB: N/A BUS TYPE: COPPER ISOLATED GROUND BUS: NO
MAIN BUS: 225 A ENCLOSURE: NEMA 1 GROUND BUS: YES
LOCATION: ELECTRICAL 7BEL3 WIRES: 4W + G NEUTRAL BUS: YES
EXIST: RPC7 (SEC-2) FED FROM: RPC7 (SEC-1) NORMAL
NOTES:
TOTAL ESTIMATED DEMAND: 5.2 14.5
TOTAL CONNECTED LOAD: 5.2 14.5
ADDED CONNECTED LOAD: 5.2
REMOVED CONNECTED LOAD: 0
EXISTING CONNECTED LOAD: 0
Receptacle 5220 VA 5220 VA kVA AMPS
LOAD CLASSIFICATION CONNECTED LOAD (VA)
ESTIMATED DEMAND
(VA)
PANEL TOTALS
18 A / 14 A / 12 A
CC7#17 SPARE -- 20 1 0 / 0 1 20 -- SPARE CC7#18
CC7#15 SPARE -- 20 1 0 / 0 1 20 -- SPARE CC7#16
CC7#13 SPARE -- 20 1 0 / 360 1 20 360 XXXXX - WORKSTATION 14 RECEPT. CC7#14
CC7#11 XXXXX - WORKSTATION 11 RECEPT. 360 20 1 360 / 360 1 20 360 XXXXX - WORKSTATION 14 RECEPT. CC7#12
CC7#9 XXXXX - WORKSTATION 11 RECEPT. 360 20 1 360 / 360 1 20 360 XXXXX - WORKSTATION 13 RECEPT. CC7#10
CC7#7 XXXXX - WORKSTATION 10 RECEPT. 360 20 1 360 / 360 1 20 360 XXXXX - WORKSTATION 13 RECEPT. CC7#8
CC7#5 XXXXX - WORKSTATION 10 RECEPT. 360 20 1 360 / 360 1 20 360 XXXXX - OFFICE CONVENIENCE REC. CC7#6
CC7#3 7B214, 7B215, 7B216 - OFFICE RECEPT. 540 20 1 540 / 360 1 20 360 XXXXX - WORKSTATION 12 RECEPT. CC7#4
CC7#1 7B210, 7B211, 7B212, 7B213 - RECEPT. 720 20 1 720 / 360 1 20 360 XXXXX - WORKSTATION 12 RECEPT. CC7#2
CKT
NO.
DESCRIPTION
TOTAL
LOAD
(VA)
CIRCUIT
BREAKER
AMPS / POLES
A B C
CIRCUIT
BREAKER
POLES /...
TOTAL
LOAD
(VA)
DESCRIPTION CKT
NO.
AIC RATING: 0 A NUMBER OF SECTIONS: POLES PER SECTION:
AIC AVAILABLE: PANEL LUGS: MCB FEED THROUGH LUGS: NO
VOLTAGE: 120/208 WYE MOUNTING: 200% NEUTRAL: NO
MCB: BUS TYPE: ISOLATED GROUND BUS: NO
MAIN BUS: 100 A ENCLOSURE: GROUND BUS: NO
LOCATION: ELECTRICAL 7BEL3 WIRES: 3W NEUTRAL BUS: NO
EXIST: CPC7 FED FROM:
NOTES:
TOTAL ESTIMATED DEMAND: 11.4 13.7
TOTAL CONNECTED LOAD: 11.4 13.7
ADDED CONNECTED LOAD: 11.4
REMOVED CONNECTED LOAD: 0
EXISTING CONNECTED LOAD: 0
Other 11260 VA 11260 VA kVA AMPS
LOAD CLASSIFICATION CONNECTED LOAD (VA)
ESTIMATED DEMAND
(VA)
PANEL TOTALS
17 A / 14 A / 11 A
LC7#23 SPACE -- -- -- ... -- -- -- SPACE LC7#24
LC7#21 SPACE -- -- -- ... -- -- -- SPACE LC7#22
LC7#19 SPACE -- -- -- ... -- -- -- SPACE LC7#20
LC7#17 LTG 7TH FLOOR EAST OPEN OFFICE 726 20 1 726 / 376 1 20 376 LTG 7TH FLOOR EAST CONF. ROOM LC7#18
LC7#15 LTG 7TH FLOOR EAST OPEN OFFICE 567 20 1 567 / 634 1 20 634 LTG 7TH FLOOR EAST CONF. ROOM LC7#16
LC7#13 LTG 7TH FLOOR EAST CORRIDOR 1,101 20 1 1101 / 724 1 20 724 LTG 7TH FLOOR EAST OFFICES LC7#14
LC7#11 LTG 7TH FLR. EAST... 1,338 20 1 1338 / 0 1 20 -- EXISTING VAV LC7#12
LC7#9 LTG 7TH FLOOR EAST CORRIDOR 1,102 20 1 1102 / 0 1 20 -- EXISTING VAV LC7#10
LC7#7 LTG 7TH FLOOR EAST OFFICES 603 20 1 603 / 0 1 20 -- EXISTING VAV LC7#8
LC7#5 LTG 7TH FLOOR EAST OFFICES 603 20 1 603 / 0 1 20 -- SPARE LC7#6
LC7#3 LTG 7TH FLOOR EAST CONF. ROOM 1,523 20 1 1523 / 0 1 20 -- EXISTING VAV LC7#4
LC7#1 LTG 7TH FLOOR EAST CONF. ROOM 2,119 20 1 2119 / 0 1 20 -- EXISTING VAV LC7#2
CKT
NO.
DESCRIPTION
TOTAL
LOAD
(VA)
CIRCUIT
BREAKER
AMPS / POLES
A B C
CIRCUIT
BREAKER
POLES /...
TOTAL
LOAD
(VA)
DESCRIPTION CKT
NO.
AIC RATING: 0 A NUMBER OF SECTIONS: POLES PER SECTION:
AIC AVAILABLE: PANEL LUGS: MCB FEED THROUGH LUGS: NO
VOLTAGE: 480/277 WYE MOUNTING: 200% NEUTRAL: NO
MCB: BUS TYPE: ISOLATED GROUND BUS: NO
MAIN BUS: 100 A ENCLOSURE: GROUND BUS: NO
LOCATION: ELECTRICAL 7BEL3 WIRES: 3W NEUTRAL BUS: NO
EXIST: LPC7 FED FROM:
NOTES:
TOTAL ESTIMATED DEMAND: 5.0 14.0
TOTAL CONNECTED LOAD: 5.0 14.0
ADDED CONNECTED LOAD: 5
REMOVED CONNECTED LOAD: 0
EXISTING CONNECTED LOAD: 0
Receptacle 5040 VA 5040 VA kVA AMPS
LOAD CLASSIFICATION CONNECTED LOAD (VA)
ESTIMATED DEMAND
(VA)
PANEL TOTALS
20 A / 12 A / 11 A
CD7#17 7CTL2 - TELECOM RACK RECEPT. 180 20 1 180 / 0 1 20 -- SPARE CD7#18
CD7#15 7CTL2 - TELECOM RACK RECEPT. 180 20 1 180 / 0 1 20 -- SPARE CD7#16
CD7#13 7CTL2 - TELECOM RACK RECEPT. 180 20 1 180 / 900 1 20 900 7C284, 7C285, 7C286, 7C287 - RECEPT. CD7#14
CD7#11 7CTL2 - TELECOM RACK RECEPT. 180 20 1 180 / 360 1 20 360 XXXXX - WORKSTATION 17 RECEPT. CD7#12
CD7#9 SPARE -- 20 1 0 / 360 1 20 360 XXXXX - WORKSTATION 17 RECEPT. CD7#10
CD7#7 SPARE -- 20 1 0 / 360 1 20 360 XXXXX - WORKSTATION 16 RECEPT. CD7#8
CD7#5 7C291 - CHIEF OF SECURITY RECEPT. 180 20 1 180 / 360 1 20 360 XXXXX - WORKSTATION 16 RECEPT. CD7#6
CD7#3 LOBBY, 7C189 - COMP. RECEPTACLES 540 20 1 540 / 360 1 20 360 XXXXX - WORKSTATION 15 RECEPT. CD7#4
CD7#1 7C210, 7C211, 7C212 - OFFICE RECEPT. 540 20 1 540 / 360 1 20 360 XXXXX - WORKSTATION 15 RECEPT. CD7#2
CKT
NO.
DESCRIPTION
TOTAL
LOAD
(VA)
CIRCUIT
BREAKER
AMPS / POLES
A B C
CIRCUIT
BREAKER
POLES /...
TOTAL
LOAD
(VA)
DESCRIPTION CKT
NO.
AIC RATING: 0 A NUMBER OF SECTIONS: POLES PER SECTION:
AIC AVAILABLE: PANEL LUGS: MCB FEED THROUGH LUGS: NO
VOLTAGE: 120/208 WYE MOUNTING: 200% NEUTRAL: NO
MCB: BUS TYPE: ISOLATED GROUND BUS: NO
MAIN BUS: 100 A ENCLOSURE: GROUND BUS: NO
LOCATION: Space 4A256 WIRES: 3W NEUTRAL BUS: NO
EXIST: CPD7 FED FROM:
NOTES:
TOTAL ESTIMATED DEMAND: 6.7 8.0
TOTAL CONNECTED LOAD: 6.7 8.0
ADDED CONNECTED LOAD: 6.7
REMOVED CONNECTED LOAD: 0
EXISTING CONNECTED LOAD: 0
Other 6673 VA 6673 VA kVA AMPS
LOAD CLASSIFICATION CONNECTED LOAD (VA)
ESTIMATED DEMAND
(VA)
PANEL TOTALS
10 A / 7 A / 8 A
LD7#23 SPACE -- -- -- 0 / 0 1 20 -- SPARE LD7#24
LD7#21 SPACE -- -- -- 0 / 0 1 20 -- SPARE LD7#22
LD7#19 SPARE -- 20 1 0 / 0 1 20 -- SPARE LD7#20
LD7#17 SPARE -- 20 1 0 / 0 1 20 -- EXISTING VAV LD7#18
LD7#15 LTG 7TH FLOOR EAST 195 20 1 195 / 0 1 20 -- EXISTING VAV LD7#16
LD7#13 LTG 7TH FLOOR EAST EXEC. OFFICES 1,436 20 1 1436 / 0 1 20 -- EXISTING VAV LD7#14
LD7#11 LTG 7TH FLOOR EAST CONF. ROOM 1,334 20 1 1334 / 0 1 20 -- EXISTING VAV LD7#12
LD7#9 LTG 7TH FLOOR EAST CONF. ROOM 268 20 1 268 / 0 1 20 -- EXISTING VAV LD7#10
LD7#7 LTG 7TH FLOOR EAST ARMORY 192 20 1 192 / 0 1 20 -- EXISTING VAV LD7#8
LD7#5 LTG 7TH FLR. EAST... 797 20 1 797 / 0 1 20 -- EXISTING VAV LD7#6
LD7#3 LTG 7TH FLOOR EAST CORRIDOR 1,373 20 1 1373 / 0 1 20 -- EXISTING VAV LD7#4
LD7#1 LTG 7TH FLOOR EAST OFFICES 1,079 20 1 1079 / 0 1 20 -- EXISTING VAV LD7#2
CKT
NO.
DESCRIPTION
TOTAL
LOAD
(VA)
CIRCUIT
BREAKER
AMPS / POLES
A B C
CIRCUIT
BREAKER
POLES /...
TOTAL
LOAD
(VA)
DESCRIPTION CKT
NO.
AIC RATING: 0 A NUMBER OF SECTIONS: POLES PER SECTION:
AIC AVAILABLE: PANEL LUGS: MCB FEED THROUGH LUGS: NO
VOLTAGE: 480/277 WYE MOUNTING: 200% NEUTRAL: NO
MCB: BUS TYPE: ISOLATED GROUND BUS: NO
MAIN BUS: 100 A ENCLOSURE: GROUND BUS: NO
LOCATION: Space 4A256 WIRES: 3W NEUTRAL BUS: NO
EXIST: LPD7 FED FROM:
NOTES:
TOTAL ESTIMATED DEMAND: 4.5 12.5
TOTAL CONNECTED LOAD: 4.5 12.5
ADDED CONNECTED LOAD: 4.5
REMOVED CONNECTED LOAD: 0
EXISTING CONNECTED LOAD: 0
Receptacle 4500 VA 4500 VA kVA AMPS
LOAD CLASSIFICATION CONNECTED LOAD (VA)
ESTIMATED DEMAND
(VA)
PANEL TOTALS
16 A / 14 A / 9 A
CG7#17 SPARE -- 20 1 0 / 0 1 20 -- SPARE CG7#18
CG7#15 SPARE -- 20 1 0 / 0 1 20 -- SPARE CG7#16
CG7#13 SPARE -- 20 1 0 / 0 1 20 -- SPARE CG7#14
CG7#11 XXXXX - WORKSTATION 29 RECEPT. 360 20 1 360 / 0 1 20 -- SPARE CG7#12
CG7#9 XXXXX - WORKSTATION 29 RECEPT. 360 20 1 360 / 540 1 20 540 7B114, 7B115, 7B116 - OFFICE RECEPT. CG7#10
CG7#7 XXXXX - WORKSTATION 28 RECEPT. 360 20 1 360 / 720 1 20 720 7B110, 7B111, 7B112, 7B113 - RECEPT. CG7#8
CG7#5 XXXXX - WORKSTATION 28 RECEPT. 360 20 1 360 / 360 1 20 360 XXXXX - WORKSTATION 30 RECEPT. CG7#6
CG7#3 XXXXX - WORKSTATION 27 RECEPT. 360 20 1 360 / 360 1 20 360 XXXXX - WORKSTATION 30 RECEPT. CG7#4
CG7#1 XXXXX - WORKSTATION 27 RECEPT. 360 20 1 360 / 360 1 20 360 XXXXX, XXXXX - OFFICE RECEPT. CG7#2
CKT
NO.
DESCRIPTION
TOTAL
LOAD
(VA)
CIRCUIT
BREAKER
AMPS / POLES
A B C
CIRCUIT
BREAKER
POLES /...
TOTAL
LOAD
(VA)
DESCRIPTION CKT
NO.
AIC RATING: 0 A NUMBER OF SECTIONS: POLES PER SECTION:
AIC AVAILABLE: PANEL LUGS: MCB FEED THROUGH LUGS: NO
VOLTAGE: 120/208 WYE MOUNTING: 200% NEUTRAL: NO
MCB: BUS TYPE: ISOLATED GROUND BUS: NO
MAIN BUS: 100 A ENCLOSURE: GROUND BUS: NO
LOCATION: TELECOM-54 7BTL1-54 WIRES: 3W NEUTRAL BUS: NO
EXIST: CPG7 FED FROM:
NOTES:
TOTAL ESTIMATED DEMAND: 4.0 11.0
TOTAL CONNECTED LOAD: 4.0 11.0
ADDED CONNECTED LOAD: 4
REMOVED CONNECTED LOAD: 0
EXISTING CONNECTED LOAD: 0
Receptacle 3960 VA 3960 VA kVA AMPS
LOAD CLASSIFICATION CONNECTED LOAD (VA)
ESTIMATED DEMAND
(VA)
PANEL TOTALS
12 A / 11 A / 11 A
CH7#17 SPARE -- 20 1 0 / 180 1 20 180 7C291 - CCTV CAMERA CH7#18
CH7#15 SPARE -- 20 1 0 / 180 1 20 180 7C291 - CCTV CAMERA CH7#16
CH7#13 SPARE -- 20 1 0 / 0 1 20 -- SPARE CH7#14
CH7#11 XXXXX, XXXXX, XXXXX - OFFICE... 540 20 1 540 / 0 1 20 -- SPARE CH7#12
CH7#9 XXXXX, XXXXX, XXXXX - W.S.... 360 20 1 360 / 0 1 20 -- SPARE CH7#10
CH7#7 XXXXX - WORKSTATION 32 RECEPT. 360 20 1 360 / 180 1 20 180 XXXXX - RECEPTACLE CH7#8
CH7#5 XXXXX - WORKSTATION 32 RECEPT. 360 20 1 360 / 180 1 20 180 XXXXX - OFFICE RECEPTACLES CH7#6
CH7#3 XXXXX - WORKSTATION 31 RECEPT. 360 20 1 360 / 360 1 20 360 XXXXX, 7C190 - RECEPTACLES CH7#4
CH7#1 XXXXX - WORKSTATION 31 RECEPT. 360 20 1 360 / 540 1 20 540 7C110M 7C111, 7C112 - OFFICE... CH7#2
CKT
NO.
DESCRIPTION
TOTAL
LOAD
(VA)
CIRCUIT
BREAKER
AMPS / POLES
A B C
CIRCUIT
BREAKER
POLES /...
TOTAL
LOAD
(VA)
DESCRIPTION CKT
NO.
AIC RATING: 0 A NUMBER OF SECTIONS: POLES PER SECTION:
AIC AVAILABLE: PANEL LUGS: MCB FEED THROUGH LUGS: NO
VOLTAGE: 120/208 WYE MOUNTING: 200% NEUTRAL: NO
MCB: BUS TYPE: ISOLATED GROUND BUS: NO
MAIN BUS: 100 A ENCLOSURE: GROUND BUS: NO
LOCATION: Space 4A258 WIRES: 3W NEUTRAL BUS: NO
EXIST: CPH7 FED FROM:
NOTES:
TOTAL ESTIMATED DEMAND: 7.4 20.6
TOTAL CONNECTED LOAD: 7.4 20.6
Receptacle 6220 VA 6220 VA kVA AMPS
LOAD CLASSIFICATION CONNECTED LOAD (VA)
ESTIMATED DEMAND
(VA)
PANEL TOTALS
27 A / 27 A / 12 A
ED7#41 ED7#42
ED7#39 ED7#40
ED7#37 ED7#38
ED7#35 ED7#36
ED7#33 ED7#34
ED7#31 ED7#32
ED7#29 ED7#30
ED7#27 ED7#28
ED7#25 ED7#26
ED7#23 ED7#24
ED7#21 ED7#22
ED7#19 ED7#20
ED7#17 ED7#18
ED7#15 ED7#16
ED7#13 ED7#14
ED7#11 ED7#12
ED7#9 RECEPTACLE ARMORY 7C214 360 20 1 360 / 1200 1 20 1,200 DOOR MAG-LOCKS ED7#10
ED7#7 XXXXX - WORKSTATION RECEPTACLES 720 20 1 720 / 720 1 20 720 XXXXX - WORKSTATION RECEPTACLES ED7#8
ED7#5 XXXXX - WORKSTATION RECEPTACLES 720 20 1 720 / 720 1 20 720 XXXXX - WORKSTATION RECEPTACLES ED7#6
ED7#3 XXXXX - WORKSTATION RECEPTACLES 720 20 1 720 / 720 1 20 720 XXXXX - WORKSTATION RECEPTACLES ED7#4
ED7#1 RECEPTACLE SPACE 4A249 540 20 1 540 / 1000 1 20 1,000 RECEPTACLE SPACE 4A249 ED7#2
CKT
NO.
DESCRIPTION
TOTAL
LOAD
(VA)
CIRCUIT
BREAKER
AMPS / POLES
A B C
CIRCUIT
BREAKER
POLES /...
TOTAL
LOAD
(VA)
DESCRIPTION CKT
NO.
AIC RATING: 10000 A NUMBER OF SECTIONS: 1 POLES PER SECTION: 42
AIC AVAILABLE: PANEL LUGS: MCB FEED THROUGH LUGS: NO
VOLTAGE: 120/208 WYE MOUNTING: 200% NEUTRAL: NO
MCB: 60A BUS TYPE: ISOLATED GROUND BUS: NO
MAIN BUS: 100 A ENCLOSURE: GROUND BUS: YES
LOCATION: Space 4A256 WIRES: 4W + G NEUTRAL BUS: YES
NEW: ERD7 FED FROM: 15 kVA, 277 V/480 V,...
0 - - N.T.S.
CHECKED BY
DRAWN BY
FLOOR NUMBER
DRAWING TITLE
SHEET
NUMBER
SUBMISSION DATE
SUBMISSION STAGE
GSA PM
GSA PROJECT NO.
PROJECT
DESCRIPTION
PROJECT TITLE
BUILDING NAME
ADDRESS
BUILDING NUMBER
PRIME CONTR. NO.
PRIME ORDER NO.
CONST. CONTR.
A/E
SUB A/E
CONST. CONTR. NO.
SHEET SIZE:
DATE DRAWN:
36 X 48
S H
E E
T
ID
E N
TI
FI
C A
TI
O
N
DISCIPLINE
P R
O
JE
C T
ID
E
N
TI
FI
C
A
TI
O N
B U
IL
D
IN
G
BIM FILE NAME
C O
N
TR
A C
TO
R
S R
E V
IS
IO
N B
LO
C
K G
R A
P H
IC
S
C A
LE
K
E Y
P
LA
N S
TA
M
P O
R S
E A
L D
E S
IG
N
E R
ID
E
N
TI
FI
C
A
TI
O N
O W
N E
R
ID
E N
TI
FI
C A
TI
O
N
SHEET OF SHEETS
KRUECK & SEXTON ARCHITECTS, P.C.
400 MARYLAND AVENUE, SW
WASHINGTON, DC 20024
LYNDON B. JOHNSON FEDERAL BUILDING
DC0010ZZ
DC0010_E_3-4-6-7_r2020.rvt
WSP ENGINEERING
DEPARTMENT OF EDUCATION
CONSOLIDATION PROJECT
ISSUED FOR BID
HALLIE FUTTERMAN
RENOVATION OF FLOORS 3, 4, 6, & 7 OF THE EXISTING
BUILDING TO MEET THE DEPARTMENT OF
EDUCATION’S PROGRAMMATIC REQUIREMENTS.
GS-07-P-16-UC-D-7000
47PM0520F0002
47PM0520F0002
KRUECK & SEXTON ARCHITECTS
221 W ERIE ST
CHICAGO, IL 60654 (312) 787-0056
ARCHITECT
WSP ENGINEERING
ONE PENNSYLVANIA PLAZA, SECOND FLOOR
NEW YORK, NY 10119 (212) 465-5000
MEP ENGINEER
ATELIER TEN
45 E 20TH ST, 4TH FLOOR
NEW YORK, NY 10003 (312) 386-1400
SUSTAINABILITY CONSULTANT
THRESHOLD ACOUSTICS
141 W JACKSON BLVD, SUITE 2080
CHICAGO, IL 60604 (312) 386-1400
ACOUSTIC CONSULTANT
WEST EAST
M A
TC
H
LI
N
E
GENERAL SERVICES ADMINISTRATION
NATIONAL CAPITAL REGION
PUBLIC BUILDING SERVICE, D.C. SERVICES DIV.
7TH & D STREET, S.W.
WASHINGTON, D.C. 20407
ISSUE
NO. DATE ISSUE
ELECTRICAL
VARIES, SEE DRAWINGS
01 04/23/2021 ISSUED FOR BID
FORCADE DESIGN
1626 PAYNE STREET
EVANSTON, IL 60201 (847) 448-4270
ENVIRONMENTAL GRAPHICS CONSULTANT
/2
/2
:3
:2
P
M
E-60-08
ELECTRICAL LIGHT FIXTURE SCHEDULE
04/23/2021
04/23/21NJA
RO
56 61
GENERAL NOTES:
1. CONTRACTOR TO REPLACE ALL BREAKERS IN ALL
EXISTING 3RD , 4TH , 6 AND 7TH FLOOR LPD, RPD, CPD
AND CPH POWER PANELS WITH NEW CIRCUIT BREAKERS.
0 - - N.T.S.
CHECKED BY
DRAWN BY
FLOOR NUMBER
DRAWING TITLE
SHEET
NUMBER
SUBMISSION DATE
SUBMISSION STAGE
GSA PM
GSA PROJECT NO.
PROJECT
DESCRIPTION
PROJECT TITLE
BUILDING NAME
ADDRESS
BUILDING NUMBER
PRIME CONTR. NO.
PRIME ORDER NO.
CONST. CONTR.
A/E
SUB A/E
CONST. CONTR. NO.
SHEET SIZE:
DATE DRAWN:
36 X 48
S H
E E
T
ID
E N
TI
FI
C A
TI
O
N
DISCIPLINE
P R
O
JE
C T
ID
E
N
TI
FI
C
A
TI
O N
B U
IL
D
IN
G
BIM FILE NAME
C O
N
TR
A C
TO
R
S R
E V
IS
IO
N B
LO
C
K G
R A
P H
IC
S
C A
LE
K
E Y
P
LA
N S
TA
M
P O
R S
E A
L D
E S
IG
N
E R
ID
E
N
TI
FI
C
A
TI
O N
O W
N E
R
ID
E N
TI
FI
C A
TI
O
N
SHEET OF SHEETS
KRUECK & SEXTON ARCHITECTS, P.C.
400 MARYLAND AVENUE, SW
WASHINGTON, DC 20024
LYNDON B. JOHNSON FEDERAL BUILDING
DC0010ZZ
DC0010_E_3-4-6-7_r2020.rvt
WSP ENGINEERING
DEPARTMENT OF EDUCATION
CONSOLIDATION PROJECT
ISSUED FOR BID
HALLIE FUTTERMAN
RENOVATION OF FLOORS 3, 4, 6, & 7 OF THE EXISTING
BUILDING TO MEET THE DEPARTMENT OF
EDUCATION’S PROGRAMMATIC REQUIREMENTS.
GS-07-P-16-UC-D-7000
47PM0520F0002
47PM0520F0002
KRUECK & SEXTON ARCHITECTS
221 W ERIE ST
CHICAGO, IL 60654 (312) 787-0056
ARCHITECT
WSP ENGINEERING
ONE PENNSYLVANIA PLAZA, SECOND FLOOR
NEW YORK, NY 10119 (212) 465-5000
MEP ENGINEER
ATELIER TEN
45 E 20TH ST, 4TH FLOOR
NEW YORK, NY 10003 (312) 386-1400
SUSTAINABILITY CONSULTANT
THRESHOLD ACOUSTICS
141 W JACKSON BLVD, SUITE 2080
CHICAGO, IL 60604 (312) 386-1400
ACOUSTIC CONSULTANT
WEST EAST
M A
TC
H
LI
N
E
GENERAL SERVICES ADMINISTRATION
NATIONAL CAPITAL REGION
PUBLIC BUILDING SERVICE, D.C. SERVICES DIV.
7TH & D STREET, S.W.
WASHINGTON, D.C. 20407
ISSUE
NO. DATE ISSUE
ELECTRICAL
VARIES, SEE DRAWINGS
01 04/23/2021 ISSUED FOR BID
FORCADE DESIGN
1626 PAYNE STREET
EVANSTON, IL 60201 (847) 448-4270
ENVIRONMENTAL GRAPHICS CONSULTANT
/2
/2
:2
:0
P
M
E-60-09
ELECTRICAL PANEL SCHEDULES - EM RISER MOD
04/23/2021
05/21/21NJA
RO
EMDP PP-A SB-PP-2C01 -
1C7 GEN SB-PP-7C01 -
90-31 PP-S - -
NOTES:
TOTAL ESTIMATED DEMAND: 0.0 0.0
TOTAL CONNECTED LOAD: 0.0 0.0
kVA AMPS
LOAD CLASSIFICATION CONNECTED LOAD (VA)
ESTIMATED DEMAND
(VA)
PANEL TOTALS
0 A / 0 A / 0 A
#23 SPARE -- 20 1 0 / 0 -- -- -- -- #24
#21 SPARE -- 20 1 0 / 0 -- -- -- -- #22
#19 SPARE -- 20 1 0 / 0 3 30 -- SPD #20
#17 SPARE -- 20 1 0 / 0 1 20 -- SPARE #18
#15 SPARE -- 20 1 0 / 0 1 20 -- SPARE #16
#13 SPARE -- 20 1 0 / 0 1 20 -- SPARE #14
#11 SPARE -- 20 1 0 / 0 1 20 -- SPARE #12
#9 SPARE -- 20 1 0 / 0 1 20 -- SPARE #10
#7 SPARE -- 20 1 0 / 0 1 20 -- SPARE #8
#5 SPARE -- 20 1 0 / 0 1 20 -- SPARE #6
#3 SPARE -- 20 1 0 / 0 1 20 -- SPARE #4
#1 SPARE -- 20 1 0 / 0 1 20 -- SPARE #2
CKT
NO.
DESCRIPTION
TOTAL
LOAD
(VA)
CIRCUIT
BREAKER
AMPS / POLES
A B C
CIRCUIT
BREAKER
POLES /...
TOTAL
LOAD
(VA)
DESCRIPTION CKT
NO.
AIC RATING: 22000 A NUMBER OF SECTIONS: 1 POLES PER SECTION: 24
AIC AVAILABLE: PANEL LUGS: MCB FEED THROUGH LUGS: NO
VOLTAGE: 120/208 WYE MOUNTING: SURFACE 200% NEUTRAL: NO
MCB: 60A BUS TYPE: COPPER ISOLATED GROUND BUS: NO
MAIN BUS: 100 A ENCLOSURE: NEMA 1 GROUND BUS: YES
LOCATION: WIRES: 4W + G NEUTRAL BUS: YES
NEW: 1C7 FED FROM: PP-S
NOTES:
TOTAL ESTIMATED DEMAND: 0.0 0.0
TOTAL CONNECTED LOAD: 0.0 0.0
kVA AMPS
LOAD CLASSIFICATION CONNECTED LOAD (VA)
ESTIMATED DEMAND
(VA)
PANEL TOTALS
0 A / 0 A / 0 A
#23 SPARE -- 20 1 0 / 0 -- -- -- -- #24
#21 SPARE -- 20 1 0 / 0 -- -- -- -- #22
#19 SPARE -- 20 1 0 / 0 3 30 -- SPD #20
#17 SPARE -- 20 1 0 / 0 1 20 -- SPARE #18
#15 SPARE -- 20 1 0 / 0 1 20 -- SPARE #16
#13 SPARE -- 20 1 0 / 0 1 20 -- SPARE #14
#11 SPARE -- 20 1 0 / 0 1 20 -- SPARE #12
#9 SPARE -- 20 1 0 / 0 1 20 -- SPARE #10
#7 SPARE -- 20 1 0 / 0 1 20 -- SPARE #8
#5 SPARE -- 20 1 0 / 0 1 20 -- SPARE #6
#3 SPARE -- 20 1 0 / 0 1 20 -- SPARE #4
#1 SPARE -- 20 1 0 / 0 1 20 -- SPARE #2
CKT
NO.
DESCRIPTION
TOTAL
LOAD
(VA)
CIRCUIT
BREAKER
AMPS / POLES
A B C
CIRCUIT
BREAKER
POLES /...
TOTAL
LOAD
(VA)
DESCRIPTION CKT
NO.
AIC RATING: 22000 A NUMBER OF SECTIONS: 1 POLES PER SECTION: 24
AIC AVAILABLE: PANEL LUGS: MCB FEED THROUGH LUGS: NO
VOLTAGE: 120/208 WYE MOUNTING: SURFACE 200% NEUTRAL: NO
MCB: 60A BUS TYPE: COPPER ISOLATED GROUND BUS: NO
MAIN BUS: 100 A ENCLOSURE: NEMA 1 GROUND BUS: YES
LOCATION: WIRES: 4W + G NEUTRAL BUS: YES
NEW: 90-31 FED FROM: PP-S
NOTES:
TOTAL ESTIMATED DEMAND: 0.0 0.0
TOTAL CONNECTED LOAD: 0.0 0.0
kVA AMPS
LOAD CLASSIFICATION CONNECTED LOAD (VA ESTIMATED DEMAND (VA) PANEL TOTALS
4 SPARE -- 3 100 A -- 0 VA
3 SPARE -- 3 100 A -- 0 VA
2 ATS #2 -- 3 400 A -- 0 VA REFER TO RISER DIAGRAM
1 ATS #1 -- 3 400 A -- 0 VA REFER TO RISER DIAGRAM
CKT
NO.
DESCRIPTION
LOAD
CLASSIFICATION
CIRCUIT BREAKER
POLES/AMPS
FRAME
TOTAL LOAD
(VA)
REMARKS
AIC RATING: 100000 A NUMBER OF SECTIONS: 1
AIC AVAILABLE: PANEL LUGS: MCB FEED THROUGH LUGS: NO
VOLTAGE: 480/277 WYE MOUNTING: SURFACE 200% NEUTRAL: NO
MCB: 600A BUS TYPE: COPPER ISOLATED GROUND BUS: NO
MAIN BUS: 600 A ENCLOSURE: NEMA 1 GROUND BUS: YES
LOCATION: WIRES: 4W + G NEUTRAL BUS: YES
NEW: EMDP FED FROM:
NOTES:
TOTAL ESTIMATED DEMAND: 9.2 25.5
TOTAL CONNECTED LOAD: 9.2 25.5
kVA AMPS
LOAD CLASSIFICATION CONNECTED LOAD (VA)
ESTIMATED DEMAND
(VA)
PANEL TOTALS
27 A / 27 A / 24 A
#41 SPARE -- 20 1 0 / 0 -- -- -- -- #42
#39 SPARE -- 20 1 0 / 0 -- -- -- -- #40
#37 SPARE -- 20 1 0 / 0 3 30 -- SPD #38
#35 SPARE -- 20 1 0 / 0 1 20 -- SPARE #36
#33 SPARE -- 20 1 0 / 0 1 20 -- SPARE #34
#31 SPARE -- 20 1 0 / 0 1 20 -- SPARE #32
#29 SPARE -- 20 1 0 / 0 1 20 -- SPARE #30
#27 SPARE -- 20 1 0 / 0 1 20 -- SPARE #28
#25 SPARE -- 20 1 0 / 0 1 20 -- SPARE #26
#23 SPARE -- 20 1 0 / 0 1 20 -- SPARE #24
#21 SPARE -- 20 1 0 / 0 1 20 -- SPARE #22
#19 SPARE -- 20 1 0 / 0 1 20 -- SPARE #20
#17 SPARE -- 20 1 0 / 0 1 20 -- SPARE #18
#15 SPARE -- 20 1 0 / 0 1 20 -- SPARE #16
#13 SPARE -- 20 1 0 / 0 1 20 -- SPARE #14
#11 -- -- -- -- 333 / 0 1 20 -- SPARE #12
#9 -- -- -- -- 333 / 0 1 20 -- SPARE #10
#7 OIL HEATER PUMP 1,000 20 3 333 / 0 1 20 -- SPARE #8
#5 GEN CONTROL PANEL 1,000 20 1 1000 / 1500 1 20 1,500 LOUVERS #6
#3 -- -- -- -- 1350 / 1500 1 20 1,500 LOUVERS #4
#1 JW HEATER PUMP 2,700 20 2 1350 / 1500 1 20 1,500 BATTERY CHARGER #2
CKT
NO.
DESCRIPTION
TOTAL
LOAD
(VA)
CIRCUIT
BREAKER
AMPS / POLES
A B C
CIRCUIT
BREAKER
POLES /...
TOTAL
LOAD
(VA)
DESCRIPTION CKT
NO.
AIC RATING: 22000 A NUMBER OF SECTIONS: 1 POLES PER SECTION: 42
AIC AVAILABLE: PANEL LUGS: MCB FEED THROUGH LUGS: NO
VOLTAGE: 120/208 WYE MOUNTING: SURFACE 200% NEUTRAL: NO
MCB: 175A BUS TYPE: COPPER ISOLATED GROUND BUS: NO
MAIN BUS: 225 A ENCLOSURE: NEMA 1 GROUND BUS: YES
LOCATION: WIRES: 4W + G NEUTRAL BUS: YES
NEW: GEN FED FROM:
NOTES:
TOTAL ESTIMATED DEMAND: 0.0 0.0
TOTAL CONNECTED LOAD: 0.0 0.0
kVA AMPS
LOAD CLASSIFICATION CONNECTED LOAD (VA ESTIMATED DEMAND (VA) PANEL TOTALS
12 SPACE -- -- -- -- 0 VA --
11 SPACE -- -- -- -- 0 VA --
10 SPACE -- -- -- -- 0 VA --
9 SPACE -- -- -- -- 0 VA --
8 PNL ERD7 15kVA XFMR -- 3 25 A -- 0 VA REFER TO RISER DIAGRAM
7 PNL ASB-PP-7C01 30 kVA XFMR -- 3 50 A -- 0 VA REFER TO RISER DIAGRAM
6 GEN PNL 30 kVA XFMR -- 3 50 A -- 0 VA REFER TO RISER DIAGRAM
5 UPS-B BY-PASS FEED -- 3 225 A -- 0 VA REFER TO RISER DIAGRAM
4 UPS-A NORMAL FEED -- 3 250 A -- 0 VA REFER TO RISER DIAGRAM
3 PNL PP-S 45 kVA XFMR -- 3 70 A -- 0 VA REFER TO RISER DIAGRAM
2 SPARE -- 3 100 A -- 0 VA
1 SPARE -- 3 100 A -- 0 VA
CKT
NO.
DESCRIPTION
LOAD
CLASSIFICATION
CIRCUIT BREAKER
POLES/AMPS
FRAME Load REMARKS
AIC RATING: 65000 A NUMBER OF SECTIONS: 1
AIC AVAILABLE: PANEL LUGS: MCB FEED THROUGH LUGS: NO
VOLTAGE: 480/277 WYE MOUNTING: SURFACE 200% NEUTRAL: NO
MCB: 400A BUS TYPE: COPPER ISOLATED GROUND BUS: NO
MAIN BUS: 400 A ENCLOSURE: NEMA 1 GROUND BUS: YES
LOCATION: WIRES: 4W + G NEUTRAL BUS: YES
NEW: PP-A FED FROM:
NOTES:
TOTAL ESTIMATED DEMAND: 0.0 0.0
TOTAL CONNECTED LOAD: 0.0 0.0
kVA AMPS
LOAD CLASSIFICATION CONNECTED LOAD (VA)
ESTIMATED DEMAND
(VA)
PANEL TOTALS
0 A / 0 A / 0 A
#41 SPARE -- 20 1 0 / 0 -- -- -- -- #42
#39 SPARE -- 20 1 0 / 0 -- -- -- -- #40
#37 SPARE -- 20 1 0 / 0 3 30 -- SPD #38
#35 SPARE -- 20 1 0 / 0 1 20 -- SPARE #36
#33 SPARE -- 20 1 0 / 0 1 20 -- SPARE #34
#31 SPARE -- 20 1 0 / 0 1 20 -- SPARE #32
#29 SPARE -- 20 1 0 / 0 1 20 -- SPARE #30
#27 SPARE -- 20 1 0 / 0 1 20 -- SPARE #28
#25 SPARE -- 20 1 0 / 0 1 20 -- SPARE #26
#23 SPARE -- 20 1 0 / 0 1 20 -- SPARE #24
#21 SPARE -- 20 1 0 / 0 1 20 -- SPARE #22
#19 SPARE -- 20 1 0 / 0 1 20 -- SPARE #20
#17 SPARE -- 20 1 0 / 0 1 20 -- SPARE #18
#15 SPARE -- 20 1 0 / 0 1 20 -- SPARE #16
#13 SPARE -- 20 1 0 / 0 1 20 -- SPARE #14
#11 SPARE -- 20 1 0 / 0 1 20 -- SPARE #12
#9 SPARE -- 20 1 0 / 0 1 20 -- SPARE #10
#7 SPARE -- 20 1 0 / 0 1 20 -- SPARE #8
#5 -- -- -- -- 0 / 0 -- -- -- -- #6
#3 -- -- -- -- 0 / 0 -- -- -- -- #4
#1 1C7 0 20 3 0 / 0 3 20 0 90-31 #2
CKT
NO.
DESCRIPTION
TOTAL
LOAD
(VA)
CIRCUIT
BREAKER
AMPS / POLES
A B C
CIRCUIT
BREAKER
POLES /...
TOTAL
LOAD
(VA)
DESCRIPTION CKT
NO.
AIC RATING: 22000 A NUMBER OF SECTIONS: 1 POLES PER SECTION: 42
AIC AVAILABLE: PANEL LUGS: MCB FEED THROUGH LUGS: NO
VOLTAGE: 120/208 WYE MOUNTING: SURFACE 200% NEUTRAL: NO
MCB: 175A BUS TYPE: COPPER ISOLATED GROUND BUS: NO
MAIN BUS: 225 A ENCLOSURE: NEMA 1 GROUND BUS: YES
LOCATION: WIRES: 4W + G NEUTRAL BUS: YES
NEW: PP-S FED FROM:
NOTES:
TOTAL ESTIMATED DEMAND: 0.0 0.0
TOTAL CONNECTED LOAD: 0.0 0.0
kVA AMPS
LOAD CLASSIFICATION CONNECTED LOAD (VA)
ESTIMATED DEMAND
(VA)
PANEL TOTALS
0 A / 0 A / 0 A
#23 SPARE -- 20 1 0 / 0 -- -- -- -- #24
#21 SPARE -- 20 1 0 / 0 -- -- -- -- #22
#19 SPARE -- 20 1 0 / 0 3 30 -- SPD #20
#17 SPARE -- 20 1 0 / 0 1 20 -- SPARE #18
#15 SPARE -- 20 1 0 / 0 1 20 -- SPARE #16
#13 SPARE -- 20 1 0 / 0 1 20 -- SPARE #14
#11 SPARE -- 20 1 0 / 0 1 20 -- SPARE #12
#9 SPARE -- 20 1 0 / 0 1 20 -- SPARE #10
#7 SPARE -- 20 1 0 / 0 1 20 -- SPARE #8
#5 SPARE -- 20 1 0 / 0 1 20 -- SPARE #6
#3 SPARE -- 20 1 0 / 0 1 20 -- SPARE #4
#1 SPARE -- 20 1 0 / 0 1 20 -- SPARE #2
CKT
NO.
DESCRIPTION
TOTAL
LOAD
(VA)
CIRCUIT
BREAKER
AMPS / POLES
A B C
CIRCUIT
BREAKER
POLES /...
TOTAL
LOAD
(VA)
DESCRIPTION CKT
NO.
AIC RATING: 22000 A NUMBER OF SECTIONS: 1 POLES PER SECTION: 24
AIC AVAILABLE: PANEL LUGS: MCB FEED THROUGH LUGS: NO
VOLTAGE: 120/208 WYE MOUNTING: SURFACE 200% NEUTRAL: NO
MCB: 60A BUS TYPE: COPPER ISOLATED GROUND BUS: NO
MAIN BUS: 100 A ENCLOSURE: NEMA 1 GROUND BUS: YES
LOCATION: WIRES: 4W + G NEUTRAL BUS: YES
NEW: SB-PP-2C01 FED FROM: SB-PP-7C01
NOTES:
TOTAL ESTIMATED DEMAND: 0.0 0.0
TOTAL CONNECTED LOAD: 0.0 0.0
kVA AMPS
LOAD CLASSIFICATION CONNECTED LOAD (VA)
ESTIMATED DEMAND
(VA)
PANEL TOTALS
0 A / 0 A / 0 A
#23 SPARE -- 20 1 0 / 0 -- -- -- -- #24
#21 SPARE -- 20 1 0 / 0 -- -- -- -- #22
#19 SPARE -- 20 1 0 / 0 3 30 -- SPD #20
#17 SPARE -- 20 1 0 / 0 1 20 -- SPARE #18
#15 SPARE -- 20 1 0 / 0 1 20 -- SPARE #16
#13 SPARE -- 20 1 0 / 0 1 20 -- SPARE #14
#11 SPARE -- 20 1 0 / 0 1 20 -- SPARE #12
#9 SPARE -- 20 1 0 / 0 1 20 -- SPARE #10
#7 SPARE -- 20 1 0 / 0 1 20 -- SPARE #8
#5 -- -- -- -- 0 / 0 1 20 -- SPARE #6
#3 -- -- -- -- 0 / 0 1 20 -- SPARE #4
#1 SB-PP-2C01 0 50 3 0 / 0 1 20 -- SPARE #2
CKT
NO.
DESCRIPTION
TOTAL
LOAD
(VA)
CIRCUIT
BREAKER
AMPS / POLES
A B C
CIRCUIT
BREAKER
POLES /...
TOTAL
LOAD
(VA)
DESCRIPTION CKT
NO.
AIC RATING: 22000 A NUMBER OF SECTIONS: 1 POLES PER SECTION: 24
AIC AVAILABLE: PANEL LUGS: MCB FEED THROUGH LUGS: NO
VOLTAGE: 120/208 WYE MOUNTING: SURFACE 200% NEUTRAL: NO
MCB: 100A BUS TYPE: COPPER ISOLATED GROUND BUS: NO
MAIN BUS: 100 A ENCLOSURE: NEMA 1 GROUND BUS: YES
LOCATION: WIRES: 4W + G NEUTRAL BUS: YES
NEW: SB-PP-7C01 FED FROM:
TV
TV
TV
T V
T V
AV
AV
A V
T V
T V
T V
T V
T V
T V
AG
A G
AG
AG
AG
T V
T V
A G
A G
R R
R P
R V
M V
M A
G
TV
A G
A G
T V
PP P P P P
TV
P P P P P P
P
A V
A V
A V
T V
T V
T V
T V
T V
T V
T V
P
P
P
PR
P R
P R
P R
P R
P R
P R
P
AGAG
P
AV
AV
P
A V
J
J
J
GFCI
GFCI
T V
A G
A G
T V
T V
J
J
J
C R
CR CR
PR
T V
T V
T V
T V
CR
P R
TV
C R
C R
CR
J
JJ
20a
20a
F F
E E
D D
C C
B B
A A
A A
B B
C C
D D
E E
F F
20a
20a
NO SCOPE
OF WORK IN
THIS AREA
NO SCOPE
OF WORK IN
THIS AREA
FURNITURE FEED VIA POKE-THROUGH, TYP.
WHERE WORKSTATIONS ARE NOT
ADJACENT TO A COLUMN. E-27-02
E-27-02
E-27-02
E-27-02
FED FROM ELEC ROOM '3CEL1', U.O.N.FED FROM ELEC ROOM '3BEL2', U.O.N.
FED…