Division 9 specs - Finishes.pdf

PDF 1 MB Posted

Attached to
Z1DA--MINOR-CONST 528-809 NEW EMERGENCY DEPARTMENT ALBANY VAMC
Solicitation number
36C24224R0071
Issued by

About this file

This document is a solicitation for construction of a new Emergency Department at the Stratton VA Medical Center in Albany, NY. The project involves demolition, site work, general construction, alterations, mechanical, plumbing, electrical, fire alarm, sprinkler, and medical gas work for the new department. Key details include:

The successful offeror shall begin work within 15 calendar days of the notice to proceed and complete all work within 550 calendar days. The contractor must provide a competent, dedicated full-time superintendent for the project. Commissioning and punch list completion are required prior to final inspection. The contractor shall utilize the VISN 2 Autodesk Build construction management platform for project collaboration and communication. No additional time or cost will be provided for failure to use the required platform. The solicitation is issued by the Department of Veterans Affairs Veterans Health Administration, Veterans Integrated Service Network 2.

View the file

Other files

File Type Posted
36C24224R0071 0008.docx DOCX document
36C24224R0071 0007.docx DOCX document
1-SE-701.pdf PDF
36C24224R0071 0006.docx DOCX document
SK-ES-802.1.pdf PDF
36C24224R0071 0005.docx DOCX document
Albany VA ED Walk Through Sign in List.pdf PDF
Albany VAMC Geotech Report for New ED.pdf PDF
087100 Door hardware SET 14.pdf PDF
071352 Modified Bituminous Sheet Waterproofing.pdf PDF
Stratton ED_103177_SET.pdf PDF
Q40 - 1-HA-100.pdf PDF
36C24224R0071 0004.docx DOCX document
055000 Metal Fabrications.pdf PDF
Subbasement Structural Originals.pdf PDF
084113 Aluminum Framed Entrances and Storefront8-18-22.pdf PDF
088000 Glazing-8-18-22.pdf PDF
36C24224R0071 0003.docx DOCX document
36C24224R0071 0002.docx DOCX document
19-181 100 Specs VA 528-809 Volume I.pdf PDF
19-181 100 Specs VA 528-809 Volume II.pdf PDF
EXHIBIT B - Sample Transmittal Letter for Past Performance Evaluation Questionnaire.docx DOCX document
36C24224R0071 0001.docx DOCX document
072400 EIFS.pdf PDF
EXHIBIT C - Past Performance Questionnaire.docx DOCX document
divisions 27-28 Specs.pdf PDF
1-22-24 - VA STRATTON NEW EMERGENCY DEPT SS_Part1.pdf PDF
2022-02-22 VA 528-809 Submittal Register-Divisions 01 - 34 FE.xlsx XLSX spreadsheet
Division 3 specs - concrete.pdf PDF
000115 List of Drawing Sheets.pdf PDF
Division 26 Specs - electrical.pdf PDF
Division 23 Specs - HVAC.pdf PDF
Division 7 Specs - Thermal and Moisture Protection.pdf PDF
1-22-24 - VA STRATTON NEW EMERGENCY DEPT SS_Part7.pdf PDF
Division 5 specs - Metals.pdf PDF
1-22-24 - VA STRATTON NEW EMERGENCY DEPT SS_Part8.pdf PDF
1-22-24 - VA STRATTON NEW EMERGENCY DEPT SS_Part10.pdf PDF
1-22-24 - VA STRATTON NEW EMERGENCY DEPT SS_Part2.pdf PDF
000110 TOC.pdf PDF
WD Albany NY20240002 07-12-2024.docx DOCX document
Division 6 Specs - wood and plastics.pdf PDF
Division 4 Specs - Masonry.pdf PDF
Division 2 specs - existing conditions.pdf PDF
Division 21-22 Specs.pdf PDF
1-22-24 - VA STRATTON NEW EMERGENCY DEPT SS_Part4.pdf PDF
Divisions 31-34 Specs.pdf PDF
Division 8 Spec - Doors and windows.pdf PDF
1-22-24 - VA STRATTON NEW EMERGENCY DEPT SS_Part5.pdf PDF
1-22-24 - VA STRATTON NEW EMERGENCY DEPT SS_Part11.pdf PDF
1-22-24 - VA STRATTON NEW EMERGENCY DEPT SS_Part9.pdf PDF
Show 40 more

Latest 50 of 56 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SAMUEL S. STRATTON VA MEDICAL CENTER

DESIGN NEW EMERGENCY DEPARTMENT

VA PROJECT NO. 528-809

01-01-21

09 05 16 - 1

SECTION 09 05 16

SUBSURFACE PREPARATION FOR FLOOR FINISHES

PART 1 - GENERAL

1.1 DESCRIPTION

A. This section specifies subsurface preparation requirements for areas to receive the installation of applied and resinous flooring. This section includes testing concrete for moisture and pH, remedial floor coating for concrete floor slabs having unsatisfactory moisture or pH conditions, floor leveling and repair as required.

1.2 RELATED WORK

A. Section 07 92 00, JOINT SEALANTS.

B. Section 09 65 16, RESILIENT SHEET FLOORING, C. Section 09 65 19, RESILIENT TILE FLOORING, D. Section 09 67 23 60, RESINOUS (Urethane and Epoxy Mortar) FLOORING, E. Section 09 68 00, WALKOFF MAT CARPETING.

1.3 SUBMITTALS

A. Submit in accordance with Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA and TEST DATA.

B. Written approval confirming product compatibility with subfloor material manufacturer and the flooring manufacturer

C. Product Data:

1. Moisture remediation system

2. Underlayment Primer

3. Cementitious Self-Leveling Underlayment

4. Cementitious Trowel-Applied Underlayment (Not suitable for resinous floor finishes)

D. Test Data:

1. Moisture test and pH results performed by a qualified independent testing agency or warranty holding manufacturer’s technical representative.

1.4 DELIVERY AND STORAGE

A. Deliver materials in containers with labels legible and intact and grade-seals unbroken.

B. Store material to prevent damage or contamination.

09 05 16 - 2

1.5 APPLICABLE PUBLICATIONS

A. Publications listed below form a part of this specification to the extent referenced. Publications are referenced in text by basic designation only.

B. ASTM International(ASTM):

D638-14(2014)...........Standard Test Method for Tensile Properties of

Plastics

D4259-18(2019)..........Standard Practice for Preparation of Concrete by Abrasion Prior to Coating Application.

C109/C109M-20b(2020)....Standard Test Method for Compressive Strength of Hydraulic Cement Mortars (Using 2-in. or

[50-mm] Cube Specimens

7234-19(2020)...........Standard Test Method for Pull-Off Adhesion

Strength of Coatings on Concrete Using Portable

Pull-Off Adhesion Testers

E96/E96M-16(2016).......Standard Test Methods for Water Vapor

Transmission of Materials

F710-1e1(2020)..........Standard Practice for Preparing Concrete Floors to Receive Resilient Flooring

F1869-16a...............Standard Test Method for Measuring Moisture

Vapor Emission Rate of Concrete Subfloor Using

Anhydrous Calcium Chloride

F2170-19a(2020).........Standard Test Method for Determining Relative

Humidity in Concrete Floor Slabs Using in situ

Probes

C348-20(2020)...........Standard Test Method for Flexural Strength of

Hydraulic-Cement Mortars

C191-19(2020)...........Standard Test Method for Time of Setting of

Hydraulic Cement by Vicat Needle

PART 2 - PRODUCTS

2.1 MOISTURE REMEDIATION COATING (MRC)

A. System Descriptions:

1. High-solids, epoxy system designed to suppress excess moisture in concrete prior to an overlayment. For use under resinous products, 09 05 16 - 3

VCT, tile and carpet where issues caused by moisture vapor are a concern.

B. Products: Subject to compliance with applicable fire, health, environmental, and safety requirements for storage, handling, installation, and clean up.

C. System Components: Verify specific requirements as systems vary by manufacturer. Verify build up layers and installation method. Verify compatibility with substrate. Use manufacturer’s standard components, compatible with each other and as follows:

1. Liquid applied coating:

a. Resin: epoxy.

b. Formulation Description: Multiple component high solids.

c. Application: Per manufacturer’s written installation requirements.

d. Thickness: minimum 10 mils

D. Material Vapor Permeance: Application shall achieve a permeance rating of less than 0.1 perm in accordance with ASTM E96/E96M.

E. Maximum RH requirement: 100% testing in accordance with ASTM F2170.

Property Test Value

Tensile Strength

ASTM D638 4,400 psi

Volatile Organic Compound

Limits (V.O.C.)

SCAMD Rule 1113

(Ammended

02/05/2016)

25 grams per liter

Permeance ASTM E96 0.1 perms

Tensile Modulus ASTM D638 1.9X105 psi

Percent Elongation ASTM D638 12%

Cure Rate Per manufacture’s

Data

4 hours Tack free with 24hr recoat window

Bond Strength ASTM D7234 100% bond to concrete failure

09 05 16 - 4

2.2 CEMENTITIOUS SELF-LEVELING UNDERLAYMENT

A. System Descriptions:

1. High performance self-leveling underlayment resurfacer. Single component, self-leveling, cementitious material designed for easy application as an underlayment for all types of flooring materials.

It is used for substrate repair and leveling.

B. Products: Subject to compliance with applicable fire, health, environmental, and safety requirements for storage, handling, installation, and clean up. Gypsum-based products are unacceptable.

C. System Characteristics:

1. Wearing Surface: smooth

2. Thickness: Per architectural drawings, ranging from feathered edge to 1”, per application. Applications greater than 1” require additional 3/8” aggregate to mix or as recommended by manufacturer.

D. Underlayment shall be calcium aluminate cement-based, containing

Portland cement. Gypsum-based products are unacceptable.

E. Compressive Strength: Minimum 4100 psi in 28 days in accordance with

ASTM C109/C109M.

F. Flexural Strength: Minimum 1000 psi in 28 days in accordance with ASTM

C348

G. Dry Time: Underlayment shall receive the application of moisture insensitive tile in 6 hours, floor coverings in 16 hours, and resinous flooring in 3-7 days.

H. Primer: compatible and as recommended by manufacturer for use over intended substrate

I. System Components: Manufacturer's standard components that are compatible with each other and as follows:

1. Primer:

a. Resin: copolymer

b. Formulation Description: single component ready to use.

c. Application Method: Squeegee and medium nap roller.

d. All puddles shall be removed, and material shall be allowed to dry, 1-2 hours at 70F/21C.

e. Number of Coats: (1) one.

09 05 16 - 5

2. Grout Resurfacing Base:

a. Formulation Description: Single component, cementitious self-leveling high-early and high-ultimate strength grout.

b. Application Method: colloidal mix pump, cam rake, spike roll.

1) Thickness of Coats: Per architectural scope, 1” lifts.

2) Number of Coats: More than one if needed.

c. Aggregates: for applications greater than 1inch, require additional 3/8” aggregate to mix.

J.

2.3 CEMENTITIOUS TROWEL-APPLIED UNDERLAYMENT (NOT SUITABLE FOR RESINOUS FLOOR

FINISHES)

A. Underlayment shall be calcium aluminate cement-based, containing

Portland cement. Gypsum-based products are unacceptable.

B. Compressive Strength: Minimum 4000 psi in 28 days

C. Trowel-applied underlayment shall not contain silica quartz (sand).

D. Dry Time: Underlayment shall receive the application of floor covering in 15-20 minutes.

PART 3 - EXECUTION

3.1 ENVIRONMENTAL REQUIREMENTS

A. Maintain ambient temperature of work areas at not less than 16 degree C

(60 degrees F), without interruption, for not less than 24 hours before testing and not less than three days after testing.

B. Maintain higher temperatures for a longer period of time where required by manufacturer's recommendation.

C. Do not install materials when the temperatures of the substrate or materials are not within 60-85 degrees F/ 16-30 degrees C.

Property Test Value

Compressive Strength

ASTM C109/C109M

2,200 psi @ 24 hrs

3,000 psi @ 7 days

Initial set time

Final Set time

ASTM C191

30-45 min.

1 to 1.5 hours

Bond Strength

ASTM D7234

100% bond to concrete failure

09 05 16 - 6

3.2 SURFACE PREPARATION

A. Concrete shall meet the requirements of ASTM F710 and be sound, solid, clean, and free of all oil, grease, dirt, curing compounds, and any substance that might act as a bond-breaker before application. As required prepare slab by mechanical methods. No chemicals or solvents shall be used.

B. General: Prepare and clean substrates according to flooring manufacturer's written instructions for substrate indicated.

C. Prepare concrete substrates if required per ASTM D4259 as follows:

1. Dry abrasive blasting.

2. Wet abrasive blasting.

3. Vacuum-assisted abrasive blasting.

4. Centrifugal-shot abrasive blasting.

5. Comply with manufacturer's written instructions.

D. Repair damaged and deteriorated concrete according to flooring manufacturer's written recommendations.

E. Verify that concrete substrates are dry.

F. Perform anhydrous calcium chloride test, ASTM F 1869. Proceed with application only after substrates have maximum moisture-vapor-emission rate of per flooring manufactures formal and project specific written recommendation.

G. Perform in situ probe test, ASTM F2170. Proceed with application only after substrates do not exceed a maximum potential equilibrium relative humidity per flooring manufacture’s formal and project specific written recommendation.

H. Provide a written report showing test placement and results.

I. Prepare joints in accordance with Section 07 92 00, JOINT SEALANTS and material manufacturer’s instructions.

J. Alkalinity: Measure surface pH in accordance with procedures provided in ASTM F710 or as outlined by qualified testing agency or flooring manufacturer’s technical representative.

K. Tolerances: Subsurface shall meet the flatness and levelness tolerance specified on drawings or recommended by the floor finish manufacturer.

Tolerance shall also not to exceed 1/4” deviation in 10’. As required, install underlayment to achieve required tolerance.

09 05 16 - 7

L. Other Subsurface: For all other subsurface conditions, such as wood or metal, contact the floor finish or underlayment manufacturer, as appropriate, for proper preparation practices.

3.3 MOISTURE REMEDIATION COATING

A. Where results of relative humidity testing (ASTM F2170) exceed the requirements of the specified flooring manufacturer, apply remedial coating as specified to correct excessive moisture condition.

B. Prior to remedial floor coating installation mechanically prepare the concrete surface to provide a concrete surface profile in accordance with ASTM D4259.

C. Mix and apply moisture remediation coating in accordance with manufacturer’s instructions.

3.4 CEMENTITOUS UNDERLAYMENT

A. Install cementitious self-leveling underlayment as required to correct surface defects, floor flatness or levelness corrections to meet the tolerance requirements as or detailed on drawings, address non-moving cracks or joints, provide a smooth surface for the installation of floor covering, or meet elevation requirements detailed on drawings.

B. Mix and apply in accordance with manufacturer's instructions.

3.5 PROTECTION

A. Prior to the installation of the finish flooring, the surface of the underlayment should be protected from abuse by other trades by the use of plywood, tempered hardwood, or other suitable protection course

3.6 FIELD QUALITY CONTROL

A. Where specified, field sampling of products shall be conducted by a qualified, independent testing facility.

- - - E N D - - -

09 06 00 - i

Article I. SECTION 09 06 00

SCHEDULE FOR FINISHES

SECTION 09 06 00-SCHEDULE FOR FINISHES

VAMC: SAMUEL S. STRATTON VA MEDICAL CENTER

Location: Albany, NY

Project no. and Name: VA PROJECT NO. 528-809 - DESIGN NEW EMERGENCY DEPARTMENT

Submission: 100%

Date: 9-15-2021

09 06 00 - ii

09 06 00 - 1

SECTION 09 06 00

SCHEDULE FOR FINISHES

A. This section contains a coordinated system in which requirements for materials specified in other sections shown are identified by abbreviated material names and finish codes in the room finish schedule or shown for other locations.

1.2 MANUFACTURERS

A. Manufacturer’s trade names and numbers used herein are only to identify colors, finishes, textures and patterns. Products of other manufacturer’s equivalent to colors, finishes, textures and patterns of manufacturers listed that meet requirements of technical specifications will be acceptable upon approval in writing by contracting officer for finish requirements.

1.3 SUBMITTALS

A. Submit in accordance with SECTION 01 33 23, SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES provide quadruplicate samples for color approval of materials and finishes specified in this section.

09 06 00 - 2

1.4 APPLICABLE PUBLICATIONS

A. Publications listed below form a part of this specification to the extent referenced. Publications are referenced in text by basic designation only.

B. MASTER PAINTING INSTITUTE: (MPI)

6/1/2019................Architectural Painting Specification Manual

PART 2 - PRODUCTS

2.1 NOT USED

2.2 DIVISION 31 - EARTHWORK

A. SECTION 32 17 23, PAVEMENT MARKINGS.

Color Manufacturer MFG. Color Name/No.

Yellow - Conform to MPI No. 97

White - Conform to MPI No. 97

B. BOLLARDS

Material Finish Style Name/ No. Manufacturer Mfg. Color

Name/No.

STEEL PAINT 10” DECORATIVE IDEAL SHIELD TBD MFG. STANDARD

STEEL / Concrete Paint Impact Rated Black

C. SITE AND STREET FURNISHINGS

09 06 00 - 3

Item Style Name/No. Finish Manufacture Mfg. Color

Name/No.

Benches 694854BK Outdoor powder coated paint

Global Industrial Black

2.3 DIVISION 03 – CONCRETE

A. SECTION 03 30 00, CAST IN PLACE CONCRETE // SECTION 03 30 53, (SHORT FORM) CAST-IN-PLACE CONCRETE //

Surface Finish Description

Exposed Smooth - form

B. SECTION 03 45 00, PRECAST ARCHITECTURAL CONCRETE

Finish Color Texture Finish Manufacturer Mfg. Color

Name/No.

N/A N/A N/A N/A N/A

09 06 00 - 4

2.4 DIVISON 04 – MASONRY

Section 04 05 13, MASONRY MORTARING and Section 04 05 16, MASONRY GROUTING

Finish Code Manufacturer Mfg. Color Name

- West Brook Type N – TBD Manufacturer

Standard

- West Brook

A. Section 04 20 00, UNIT MASONRY

B. UNIT MASONRY (04 20 00)

Stone Type Color Manufacturer Mfg. Color & Texture

No.

Architectural Concrete Block

(CMU-1)

8”H x 16”W x 4” D

(nominal)

Westbrook Concrete

Block Co - Connecticut

GFP-351

Ground Face Polish

Architectural Concrete Block

(CMU-2)

12”H x 24”W x 4”D

(nominal)

Westbrook Concrete

Block Co - Connecticut

GFT-226D

1. CONCRETE MASONRY UNIT (CMU)

Type Size Pattern Finish Mfg. Color

Name/No.

CMU Standard 8”H x16”W x 4”D

(nominal)

N/A N/A N/A

CMU Standard 8”H x16”W x 8”D

(nominal)

N/A N/A N/A

09 06 00 - 5

Textured Face

2.5 DIVISION 05 – METALS

A. SECTION 05 12 00, STRUCTURAL STEEL FRAMING – confirm no exposed

Component Finish Color

Structural steel primer red

B. SECTION 05 50 00, METAL FABRICATIONS

Item Finish

Frames for Lead Lined Doors Coronado Industrial Coating DTM, Semi-Gloss, "INDIAN

RIVER" 985

Loose Lintels Galvanized

Steel Ladders Galvanized

Steel Ladder Rungs Galvanized

Steel Pipe Railings and Gates (not on Steel

Stairs)

Paint

Aluminum Railings Anodized

Stainless Steel Railings N/A

C. SECTION 05 51 00, INTERIOR METAL STAIRS

Newel Posts Coronado Industrial Coating, Corotech DTM Semi Gloss Paint

984 Stone Hearth

Guard Rails Coronado Industrial Coating, Corotech DTM Semi Gloss Paint

984 Stone Hearth

09 06 00 - 6

Handrails Coronado Industrial Coating, Corotech DTM Semi Gloss Paint

984 Stone Hearth

Stringers Coronado Industrial Coating, Corotech DTM Semi Gloss Paint

984 Stone Hearth

Risers Coronado Industrial Coating, Corotech DTM Semi Gloss Paint

984 Stone Hearth

Underside Coronado Industrial Coating, 984 Stone Hearth

A. SECTION 05 51 00, EXTERIOR METAL STAIRS

Newel Posts Coronado Industrial Coating, Corotech DTM Semi Gloss Paint

Black (RAL 9005)

Guard Rails Coronado Industrial Coating, Corotech DTM Semi Gloss Paint

Black (RAL 9005)

Handrails Coronado Industrial Coating, Corotech DTM Semi Gloss Paint

Black (RAL 9005)

Stringers Coronado Industrial Coating, Corotech DTM Semi Gloss Paint

Black (RAL 9005)

Risers Coronado Industrial Coating, Corotech DTM Semi Gloss Paint

Black (RAL 9005)

Underside Coronado Industrial Coating, Black (RAL 9005)

2.6 DIVISION 06 WOOD, PLASTICS, AND COMPOSITES

09 06 00 - 7

A. SECTION 06 20 00, FINISH CARPENTRY

B. MISC. ACCESSORIES AT RECEPTION

Finish code/Item Material Manufacturer Color Mfg. Color Name/No.

(QT-1) Quartz Countertop Wilsonart Quartz Lorraine Q1012

(SSM-1) Solid Surface

Countertop

Corian Solid Surface Elegant Gray

(PL-1) Plastic Laminate

(Cabinet)

Pionite Surface

Systems

Mocha Almond Fudge WX600-N SUEDE

(PL-2) Plastic Laminate

(Countertop)

Wilsonart Standard

Laminate

Natural Cotton 4946-38

(FTP-1) Fabric Wrapped

Tack Panel

Stinson-Luther II LUT 212 Neutra

(FTP-2) Fabric Wrapped

Tack Panel

Stinson-Luther II LUT 210 Milky Way

(WB-1) Wall Base Roppe/6” High Vinyl #171 Sandstone

(DP-1) SOELBERG

(Basis of Design)

¾” MDF custom

Soelberg Panel

Painted (PT-8) (See millwork

Details for Panel

Dimensions)

(AWP-1) SOELBERG

(Basis of Design)

½” Acoustical Panel COLOR: FOG (See millwork

Details for Panel

Dimensions)

Counter Supports Solid metal

Rakks Bracket

Black EH-Surface Mount

Grommets for Cable

Pass thru countertops

Molded plastic

Doug Mockett and

Company, Inc, “VG series”, Black, 2-1/2” outside Diameter with matching caps

09 06 00 - 8

2.7 DIVISION 07 - THERMAL AND MOISTURE PROTECTION

A. SECTION 07 40 00, ROOFING AND SIDING PANELS

Type Shape Ext. Finish Int. Finish Manufacturer Mfg. Color Name/No.

Metal Wall

Panel (MP-1)

N/A 200H Series, Fluropon

- Kingspan -

Benchmark

“Natural Suede” (Mica)

Metal Wall

Panel (MP-2)

N/A 200H Series, Fluropon

- Kingspan -

Benchmark

“Champagne Bronze”

(Mica)

Metal Wall

Panel (MP-3)

N/A 200H Series, Fluropon

- Kingspan -

Benchmark

“Bone White”

B. SETION 07 53 23, THERMOPLASTIC POLYOLEFIN (TPO) ROOFING

Color Manufacturer Mfg. Color Name/No.

Component Material Manufacturer Mfg. Color Name/No.

Drop-In Deal Tray Stainless Steel C.R. Laurence Co., Inc. Brushed Stainless Steel, 12” wide x 10” deep x 1 9/16” high stranded Drop-In Tray

Speak Thru Stainless Steel C.R. Laurence Co., Inc. Brushed Stainless Steel 5” diameter

09 06 00 - 9

White Carlisle (BOD) White

C. SECTION 07 60 00, FLASHING AND SHEET METAL

Item Material Finish

Copings Aluminum Painted, Manufacturer’s Finish.

Color selected from Manuf. Full range of standard finishes

Roof Insulated Expansion Joint Covers See 07 95 13, EXPANSION JOINT

COVER ASSEMBLIES

N/A

Scuppers N/A N/A

D. SECTION 07 71 00, ROOF SPECIALITIES and 07 72 00, ROOF ACCESSORIES

Item Material Finish Manufacturer Manufacturer/Color

Name/Number.

Equipment Support Galv. Steel Paint

Copings Extruded Aluminum Painted, Manufacturer’s

Finish

PAC – CLAD (BOD) Color selected from

Manuf. Full range of standard finishes

E. SECTION 07 92 00, JOINT SEALANTS

Location Color Manufacturer Manufacturer Color

Masonry Expansion Joints Match adjacent mortar joints

Tremco -

09 06 00 - 10

CMU Control Joints Match adjacent mortar joints

Tremco -

New to Existing Walls Match adjacent material to join

Tremco -

Building Expansion Joints Match adjacent expansion joint

Tremco -

Masonry Sealed Joints Match adjacent material to join

Tremco -

F. SECTION 07 95 13, EXPANSION JOINT COVER ASSEMBLIES

Item/Location Finish code Manufacturer Mfg. Color Name/No.

Floor Component

Cover Plate Frame

Casket or Sealant

(Interior Floor)

EXP-1 Construction

Specialties

GFST-200

Color: Greige

Wall Component

Cover Plate Frame

Casket or Sealant

(Interior Wall)

EXP-2 Construction

Specialties

GFS-WL

Color: Greige

Exterior Wall

Seal Cover

EXP-3 Construction

Specialties

SF-800

Color: Greige

Exterior Horizontal

Cover Plate Frame

Thermoplastic Joint

EXP-4 EMSEAL Horizontal Colorseal -

Color: TBD

2.8 DIVISION 08 - OPENINGS

A. SECTION 08 11 13, HOLLOW METAL DOORS AND FRAMES

09 06 00 - 11

1. Paint both sides of door and frames same color including ferrous metal louvers, and hardware attached to door

Component Color of Paint Type and Gloss

Door Coronado Industrial Coatings Corotech DTM Semi-gloss, Color: “Indian River” 985

Frame Coronado Industrial Coatings Corotech DTM Semi-gloss, Color: “Indian River” 985

Window frame Coronado Industrial Coatings Corotech DTM Semi-gloss, Color: “Indian River” 985

B. SECTION 08 14 00, INTERIOR WOOD DOORS

Component Finish/Color

Doors Mohawk Doors, Premium 2000 series

Species: White Birch

Color: TBD

C. SECTION 08 31 13, ACCESS DOORS AND FRAMES

Material Finish/Color

Steel Coronado Industrial Coatings Corotech DTM Semi-gloss, Color: to match adjacent wall

D. SECTION 08 41 13, ALUMINUM-FRAMED ENTRANCES AND STOREFRONTS

Material Finish Manufacturer Manufacturer Color

Name/No.

Aluminum Clear Anodized Kawneer -

Glass SEE 088000 GLAZING - -

09 06 00 - 12

E. SECTION 08 44 13, GLAZED ALUMINUM CURTAIN WALLS

Component Material Finish Manufacturer Mfg. Color Name/No.

Frame Aluminum Clear Anodized Kawneer -

F. SECTION 08 51 13, ALUMINUM WINDOWS

Type Finish Glazing Manufacturer Mfg. Color Name/No.

Fixed Clear Anodized SEE 088000 GLAZING Kawneer -

G. WINDOW SILLS

Room No. and Name Material Finish

ALL EXTERIOR WINDOWS Aluminum (With Windows) Clear Anodized

H. SECTION 08 71 00, BUILDERS HARDWARE

See Hardware Specifications

SECTION 08 80 00, GLAZING

Glazing Type Manufacturer Mfg. Color Name/No.

MG #1 - Clear

IL #1 - Gray/Bronze Tint

IL #2 - Spandrel – Gray Bronze

FR #1 - Clear

09 06 00 - 13

SG #1 - Clear

SG #2 - Clear

SG #3 - Gray/Bronze

I. SECTION 08 90 00, LOUVERS AND VENTS

Item Location Material/ Manufacturer Mfg. Color Name/No.

Supply/Return Coordinated with APC-1 See MEP Drawings White

Supply/Return Coordinated with APC-2 See MEP Drawings Match Selected Grid Color

09 06 00 - 14

2.9 DIVISION 09 - FINISHES

A. SECTION 09 29 00, GYPSUM WALLBOARD - REVEALS

Finish code Color Manufacturer Mfg. Color Name/No

Reveal Molding (REV-1) Aluminum, Clear Anodized, Satin

Fry Reglet #DRM-50-100

Reveal End Caps

Aluminum, Clear Anodized, Satin

Fry Reglet (associated with #DRM-50-

100)

B. SECTION 09 30 13, CERAMIC/PORCELAIN TILING

Finish code Integral Manufacturer Mfg. Color Name/No. Color

PWT-1 WALL TILE DALTILE Avery (Glazed

Porcelain)

White AV17

PWT-2 WALL TILE DALTILE Brickwork (Glazed

Porcelain)

Patio BW03

PWT-3 WALL TILE DALTILE Raine (Marble Tile) Cumulus Grey M019

PWT-4 WALL TILE DALTILE Clio (Mosaic Tile) Hera CL15

C. SECTION 09 30 13, CERAMIC/PORCELAIN TILE GROUT

Location Manufacturer Type Mfg. Color Name/No.

Coordinate w/ Tile (PWT-1) Laticrete #255 MultiMax #17 Marble Beige

Coordinate w/ Tile (PWT-2) Laticrete #255 MultiMax #57 Desert Khaki

Coordinate w/ Tile (PWT-3) Laticrete #255 MultiMax #90 Light Pewter

Coordinate w/ Tile (PWT-4) Laticrete #255 MultiMax #17 Marble Beige

09 06 00 - 15

D. SECTION 09 30 13, EDGE GUARD OR TRIM (W)

Item Manufacturer Mfg. Color Name/No

Clear Anodized Aluminum, Satin Schluter Rondec RO 100 AE

Clear Anodized Aluminum, Satin Schluter Rondec E/RO 100 AE (Outside Corner)

Clear Anodized Aluminum, Satin Schluter Rondec I/RO 100 AE (Inside Corner)

Clear Anodized Aluminum, Satin Schluter Rondec MC/RO 100 AE (Inside Corner)

Clear Anodized Aluminum, Satin Schluter Rondec DB(Top of Wainscoting Tile)

E. SECTION 09 51 00, ACOUSTICAL CEILINGS

Finish Code Component Color Pattern Manufacturer Mfg Name/No.

APC-1 Tegular Tile White Armstrong Optima HealthZone

(SP)– 3354 2’x2’

Tegular

(Coordinated w/ ACT-1) Exposed

Suspension System

White Armstrong Prelude XL, 15/16”

Grid

APC-2 Woodworks Tegular

Panels

Effects Sesame Armstrong W1 - Woodworks Tegular

Panels 6484

12”x48”x3/4”

(Coordinated w/ ACT-2) Exposed

Suspension System

Light Grey (LG) Armstrong Suprafine XL 9/16 exposed Tee Suspension

1. SECTION 09 30 13, MARBLE WINDOW STOOLS

Finish Code Manufacturer Mfg. Color Name/No.

SSM-1 Corian Solid Surface Elegant Gray

09 06 00 - 16

System

F. SECTION 09 54 23, LINEAR METAL CEILINGS (LMC)

Finish Code Strip Material Strip Face Size Manufacturer Mfg Name/No.

(LMC-1) Metal 6” x 96” Armstrong Linear & Linear

Exterior, Smooth

Texture, M1

Unperforated – Color:

Effects Sesame

(LMC-2) Metal 6” x 96” Armstrong Linear & Linear

Exterior, Smooth

Texture, M1

Unperforated - Color:

White Exterior

G. SECTION 09 54 00 – SPECIALTY CEILING MATERIALS

Room No. and

Name

Component Material Manufacturer Mfg. Color Name/No.

Waiting E102A Suspended

Acoustical Panels

Fiberglas Armstrong Soundscapes Acoustical Panels Model

Number 3920 – Color: White

H. SECTION 09 63 16, RESILIENT BASE & ACCESSORIES

Finish Code Material/ Component Size Manufacturer Mfg Name/No.

WB-1 Resilient Base 6 in. Roppe #171 Sandstone

A. SECTION 09 65 13, RESILIENT BASE STAIR TREADS AND ACCESSORIES

Finish Code Item Height Manufacturer Mfg Name/No.

RST1 Resilient Tread - Roppe #171 Sandstone

09 06 00 - 17

B. SECTION 09 65 19, LUXURY VINYL TILE FLOORING

Finish Code Manufacturer Size Mfg Name/No.

LVT-1 Armstrong Flooring 6” x 48” Biome

LVT-2 Armstrong Flooring 18” x 18” Coalesce

LVT-3 Armstrong Flooring 6” x 36” Coalesce

LVT-4 Armstrong Flooring 6” x 36” Coalesce

LVT-5 Armstrong Flooring 18” x 18” Coalesce

LVT-6 Armstrong Flooring 18” x 36” Coalesce

C. SECTION 09 65 16, [ RESILIENT SHEET FLOORING], HEAT WELDED SEAMS (WSF)

Finish Code Manufacturer Pattern name Mfg. Color Name/No.

WSF-1 Mannington Biospec Choices Biospec MD – Linen (15420)

1. SECTION 09 65 16, [RESILIENT SHEET FLOORING], WELDING RODS (WSF)

Finish code Manufacturer Mfg. Color Name/No.

WR1 Mannington With WSF-1, #842311

2. SECTION 09 65 16, [RESILIENT SHEET FLOORING], CAP STRIPS (WSF)

09 06 00 - 18

N/A N/A N/A

D. SECTION 09 65 16, TRANSITION STRIPS (TS)

TS1 Johnsonite CRS-XX-A – Color TA4 Gateway WG

E. SECTION 09 65 13, RESILIENT BASE AND ACCESSORIES

Finish Code Item Height Manufacturer Mfg Name/No.

(WB-1) Wall Base Roppe/6” High Vinyl Roppe #171 Sandstone

F. SECTION 09 68 00, CARPETING (CP)

Finish Code Manufacture Mfg. Color Name/No.

WOM-1 CONSTRUCTION SPECIALTIES / PEDITRED – G3 COLOR: 9332 ANTHRACITE

WOM-2 J & J FLOORING / INCOGNITO WALK-OFF

MODULAR

COLOR: 1837 OPERATIVE

G. SECTION 09 67 23.20, RESINOUS FLOORING / RESINOUS (EPOXY BASE)

RES-1 Stonhard Stonblend GSI-G – Color: Wolf Gray

RES-B Stonhard Stonblend GSI-Base – Color: Wolf Gray

09 06 00 - 19

H. SECTION 09 96 59, RESINOUS SPECIALTY GLAZED COATING SYSTEMS FOR WALLS, CEILINGS WALLBOARD

RES-W Stonhard Stonehard – Stonglaze VSI – Color: Bone

I. SECTION 09 91 00, PAINTING

1. MPI gloss and Sheen

Standards

Gloss @60 Sheen @85

Gloss level 1 A traditional matte finish-flat Max 5 units, and Max 10 units

Gloss level 2 A high side sheen flat-“a velvet-like” finish Max 10 units, and 10-35 units

Gloss level 3 A traditional “egg-shell like” finish 10-25 units, and 10-35 units

Gloss level 4 A “satin-like” finish 20-35 units, and Min. 35 units

Gloss level 5 A traditional semi-gloss 35-70 units

Gloss level 6 A traditional gloss 70-85 units

Gloss level 7 A high gloss More than 85 units

2. Paint code Gloss Manufacturer Mfg. Color Name/No.

(PT-1) Eggshell Finish BENJAMIN MOORE MARITIME WHITE 963

(PT-2) Eggshell Finish BENJAMIN MOORE INDIAN RIVER 985

(PT-3) Eggshell Finish BENJAMIN MOORE SIOUX FALLS 705

(PT-4) Eggshell Finish BENJAMIN MOORE WINTER SOLSTICE 1605

(PT-5) Eggshell Finish BENJAMIN MOORE IMPERIAL GRAY 1571

09 06 00 - 20

(PT-6) Eggshell Finish BENJAMIN MOORE STONE HEARTH 984

(PT-7) Eggshell Finish BENJAMIN MOORE SUPER WHITE OC 152

(PT-8) Level 4 finish BENJAMIN MOORE INDIAN RIVER 985

(Acrylic Paint)

(EPX-1) EPOXY PAINT BENJAMIN MOORE MARITIME WHITE 963

3. Stain Code (S) Gloss and

Transparency

Manufacturer Mfg. Color Name/No.

S Semi Minwax Basis of Design: “Greenwood MW 413”

09 06 00 - 21

2.10 DIVISION 10 - SPECIALTIES

A. SECTION 10 21 23, CUBICLE CURTAIN TRACKS

Item Manufacturer Mfg. Color Name/No.

Cubicle Curtain Track

InPro

Optitrac/”White”

Privacy Curtain

Standard textile - Stranded Stranded – Storm CM004506

(Panel With 72”)

B. SECTION 10 21 16, PREFABRICATED SHOWER AND DRESSING COMPARTMENTS

Room No. and

Name

Component Material Manufacturer Mfg. Color Name/No.

Toilet/SHWR –

MD E107A,

Toilet/SHWR –

MD E145A,

Toilet/SHWR

E154A

ADA Transfer Shower Acrylic

(one-piece)

Aqua Bath Co. C4136TD-FUS 3/4”

(Verify Orientation with

Drawings)

C. SECTION 10 26 00, WALL AND DOOR PROTECTION

Item Material Manufacturer Mfg. Color Name/No.

Corner Guards (CG-1) Vinyl

InPro Corporation

Model #150

3” wing, 90 degree

Color: #0104 Antique White

Corner Guards (CG-2)-

End wall

Vinyl

Model #160D

2” wing, End wall Protector

09 06 00 - 22

Color: #0104 Antique White

Wall Guard (WG-1)

Vinyl

700 Wall Guard

7 7/8” high

Color: #0104 Antique White

Wall Guard (WG-2) Vinyl

1600 Wall Guard

6” high

Color: #0104 Antique White

Wall Guard (WG-3) Vinyl InPro Corporation 1400 wall guard

4” high

Color: #0104 Antique White

Hand Rail (HR-1) Vinyl InPro Corporation INPRO, 2000 Handrail Color #0119

Pepperdust

Chair Rail (CR-1) Wood (Maple) Stain Grade 1x Wood Trim with

Eased Edges, Stain Color: TBD

Crash Rail (CR-2) Vinyl Inpro 200 Wall Guard Crash Rail

Wall Protection (WP-1) Vinyl Wolf Gordon Rampart (Impact Resistant)/Ennis

– Color: #5586 STONE

Wall Protection (WP-2) Vinyl Wolf Gordon Rampart (Impact Resistant)/Ennis

– Color: #5053 ANTIMONY

Wall Protection (WP-3) Vinyl (Rigid) InPro Corporation .040"; COLOR #0104 ANTIQUE WHITE

Wall Protection (WP-4) Vinyl (Rigid) InPro Corporation .040"; COLOR #660 SAGE GREEN

Top Caps (TC-1) Vinyl Wolf Gordon Top Vinyl Cap – WC-98-10

(10’ length)

Color: TBD by Architect

D. SECTION 10 28 00, TOILET, BATH AND LAUNDRY ACCESSORIES

Item Material/Finish Manufacturer Mfg. Number

09 06 00 - 23

Toilet Tissue Dispenser

(TTD1)

Plastic Bay West Silhouette Dubl-Serv OptiCore

Dispenser, #BW80200

Paper Towel Dispenser

(PTD1)

Plastic Bay West Silhouette OptiServ Hands Free

Disp-Black, #BW86500

Soap Dispenser

(SD1)

Plastic Steris Acute/Kare #1307Q5

Hand Sanitizer (HS1) Plastic Skilcraft #1049-06

Mirror (MR1) Stainless Steel Bobrick B-165 1830, 18” x 30”

Mirror (MR2) Stainless Steel Bobrick B-166 1830, 18” x 30”

Mirror (MR3) Stainless Steel American Standard 0600, 18” x 30”

Baby Changing Station (DCS1) Stainless Steel/Poly. Koala Kare KB110-SSWM

Crutch Hook (Inside

Equipment Room Cabinet)

Stainless Steel with

Satin Finish

Bradley Model 9992

Utility Shelf with Mop/Broom

Holders and Rag Hooks

Stainless Steel with

Satin Finish

Bobrick B-224

Clothes Hooks (CH) Stainless Steel with

Satin Finish

Bobrick B-6707

Recessed Specimen Pass-

Through Cabinet

Stainless Steel with

Satin Finish

Bobrick B-505

Infection Prevention Center

(PPE)

Stainless Steel Peter Pepper

Products

ICX-1, 22¾”w x 18”h x 4”d

E. SECTION 10 13 00, EXTERIOR DIRECTORIES / SECTION 10 14 00, EXTERIOR SIGNAGE

Component Finish Manufacturer Mfg. Color Name/No.

See Signage Specification Section 101400

09 06 00 - 24

F. SECTION 10 13 00, INTERIOR DIRECTORIES / 10 14 00, INTERIOR SIGNAGE

Sign Type Component Manufacturer Mfg. Color Name/No.

See Signage Specification Section 101400

G. SECTION 10 44 13, FIRE EXTNGUISHER CABINETS

Component Material Finish

Larsen’s Mfg./Cabinet Door Stainless Steel #2409-6R Semi-Rec. 2 1/2”

09 06 00 - 25

2.11 DIVISION 11 – EQUIPMENT

A. SECTION 11 12 00, PARKING CONTROL EQUIPMENT

Component Material Manufacturer Mfg. Color Name/No.

Gate and Arm - Nice- HiSecurity StrongArm 20

2.12 DIVISION 12- FURNISHINGS

A. SECTION 12 36 00, COUNTERTOPS

Type Finish/Color Manufacturer

(QT-1) Quartz Countertop See Section 06 20 00 Finish Carpentry

(SSM-1) Solid Surface

Countertop

See Section 06 20 00 Finish Carpentry

(PL-2) Plastic Laminate

Countertop

See Section 06 20 00 Finish Carpentry

B. SECTION 12 24 00, WINDOW SHADES

Component Material Manufacturer Mfg. Color Name/No.

Manual Flex Shades clear anodized (standard) Draper Techmatic Roller Shade.

Manually operated with a stainless-steel bead chain clutch

Fabric Sheerweave Fabric Phifer Opaque: SB9020 Ivory by

Phifer, 5% openness

Translucent: White/Bone

09 06 00 - 26

2.13 2.12 DIVISION 14 – CONVEYING EQUIPMENT

A. A. SECTION 14 92 00, PNEUMATIC TUBE SYSTEM

Manufacturer Material Finish/Color

Swisslog Exposed Metal Paint/Manuf. Standard

09 06 00 - 27

2.15 DIVISION 22 - PLUMBING

A. SECTION 22 40 00, PLUMBING FIXTURES

Item Color

Water Closet See Plumbing Drawings

Urinal See Plumbing Drawings

Bathtubs N/A

Lavatories See Plumbing Drawings

Service Sink Corner See Plumbing Drawings

Service Sink See Plumbing Drawings

Clinic Service Sink See Plumbing Drawings

Plaster Sink N/A

Laundry Tub N/A

2.16 DIVISON 26 - ELECTRICAL

A. SECTION 26 51 00, INTERIOR LIGHTING

Fixture Type Exterior Finish Color

See Electrical Drawing Manufacturer’s Standard All White U.N.O.

B. SECTION 26 56 00, EXTERIOR LIGHTING

Type and Component Exterior Finish Manufacturer Mfg. Name/No.

See Electrical Drawings See Electrical Drawings See Electrical Drawings See Electrical Drawings

09 06 00 - 28

PART 3 - EXECUTION

3.1 FINISH SCHEDULES & MISCELLANEOUS ABBREVIATIONS

FINISH SCHEDULE & MISCELLANEOUS ABBREVIATIONS

Term Abbreviation

Accordion Folding

Partition

AFP

Acoustical Ceiling APC

Acoustical Ceiling, Special Faced

APC (SP)

Acoustical Wall Panel AWP

Acoustical Wall

Treatment

AWT

Acoustical Wallcovering AWF

Anodized Aluminum

Colored

AAC

Anodized Aluminum

Natural Finish

AA

Carpet CP

Carpet Module Tile CPT

Ceramic Glazed Facing CGFB

Brick

Ceramic Mosaic Tile FTCT

Concrete C

Concrete Masonry Unit CMU

Divider Strips Marble DS MB

Divider Panel DP

Epoxy Coating EC

Epoxy Resin Flooring ERF

Existing E

Exterior EXT

Exterior Finish System EFS

Exterior Paint EXT-P

Epoxy Paint EXP

Fabric Wallcovering WF

Facing Tile SCT

Fluorocarbon FC

Folding Panel Partition FP

Gypsum Wallboard GWB

High Glazed Coating SC

Linear Metal Ceiling LMC

Linear Wood Ceiling LWC

09 06 00 - 29

Luxury Vinyl Tile LVT

Marble MB

Material MAT

Mortar M

Multi-Color Coating MC

Moisture Remediation

Coating

MRC

Natural Finish NF

Paint P

Paver Tile PVT

Perforated Metal Facing

(Tile or Panels)

PMF

Plaster PL

Plaster High Strength HSPL

Plaster Keene Cement KC

Plastic Laminate HPDL

Polypropylene Fabric

Wallcovering

PFW

Quarry Tile QT

Resinous Flooring RES

Resinous Wall Base RES-B

Resinous Wall Covering RES-W

Resilient Stair Tread RST

Rubber Base RB

Rubber Tile Flooring RT

Spandrel Glass SLG

Stain ST

Stone Flooring SF

Structural Clay SC

Suspension Decorative

Grids

SDG

Textured Metal Ceiling

Panel

TMC

Veneer Plaster VP

Vinyl Coated Fabric

Wallcovering

W

Vinyl Composition Tile VCT

Vinyl Sheet Flooring VSF

Vinyl Wall Base WB

Vinyl Sheet Flooring

(Welded Seams)

WSF

Wood WD

09 06 00 - 30

3.2 FINISH SCHEDULE SYMBOLS

Symbol Definition

** Same finish as adjoining walls

- No color required

E- Existing

XX To match existing

EFTR Existing finish to remain

RM Remove

3.3 ROOM FINISH SCHEDULE

A. Match adjoining or existing similar surfaces colors, textures or patterns where disturbed or damaged by alterations or new work when not scheduled.

B. ROOM FINISH SCHEDULE

SEE FINISH SCHEDULE ON DRAWING 1-AS-903

--- E N D---

06-01-18

09 22 16 - 1

SECTION 09 22 16

NON-STRUCTURAL METAL FRAMING

This section specifies steel studs wall systems, shaft wall systems, ceiling or soffit suspended or furred framing, wall furring, fasteners, and accessories for the screw attachment of gypsum board, plaster bases or other building boards.

1.2 RELATED WORK

A. Load bearing framing: Section 05 40 00, COLD-FORMED METAL FRAMING.

B. Support for wall mounted items: Section 05 50 00, METAL FABRICATIONS.

D. Ceiling suspension systems for acoustical tile or panels and lay in gypsum board panels: Section 09 51 00, ACOUSTICAL CEILINGS Section 09

29 00, GYPSUM BOARD.

1.3 TERMINOLOGY

A. Description of terms shall be in accordance with ASTM C754, ASTM C11, ASTM C841 and as specified.

B. Underside of Structure Overhead: In spaces where steel trusses or bar joists are shown, the underside of structure overhead shall be the underside of the floor or roof construction supported by beams, trusses, or bar joists. In interstitial spaces with walk-on floors the underside of the walk-on floor is the underside of structure overhead.

C. Thickness of steel specified is the minimum bare (uncoated) steel thickness.

1.4 SUBMITTALS

A. Submit in accordance with Section 01 33 23, SHOP DRAWINGS, PRODUCT

DATA, AND SAMPLES.

B. Manufacturer's Literature and Data:

1. Studs, runners and accessories.

2. Hanger inserts.

3. Channels (Rolled steel).

4. Furring channels.

5. Screws, clips and other fasteners.

C. Shop Drawings:

1. Typical ceiling suspension system.

09 22 16 - 2

2. Typical metal stud and furring construction system including details around openings and corner details.

3. Typical shaft wall assembly

4. Typical fire rated assembly and column fireproofing showing details of construction same as that used in fire rating test.

D. Test Results: Fire rating test designation, each fire rating required for each assembly.

1.5 DELIVERY, IDENTIFICATION, HANDLING AND STORAGE

In accordance with the requirements of ASTM C754.

1.6 APPLICABLE PUBLICATIONS

A. The publications listed below form a part of this specification to the extent referenced. The publications are referenced in the text by the basic designation only.

B. American Society For Testing And Materials (ASTM)

A641-09.................Zinc-Coated (Galvanized) Carbon Steel Wire

A653/653M-11............Specification for Steel Sheet, Zinc Coated

(Galvanized) or Zinc-Iron Alloy-Coated

(Galvannealed) by Hot-Dip Process.

C11-10..................Terminology Relating to Gypsum and Related

Building Materials and Systems

C635-07.................Manufacture, Performance, and Testing of Metal

Suspension System for Acoustical Tile and

Lay-in Panel Ceilings

C636-08.................Installation of Metal Ceiling Suspension

Systems for Acoustical Tile and Lay-in Panels

C645-09.................Non-Structural Steel Framing Members

C754-11.................Installation of Steel Framing Members to

Receive Screw-Attached Gypsum Panel Products

C841-03(R2008)..........Installation of Interior Lathing and Furring

C954-10.................Steel Drill Screws for the Application of

Gypsum Panel Products or Metal Plaster Bases to

Steel Studs from 0.033 in. (0.84 mm) to 0.112

in. (2.84 mm) in Thickness

E580-11.................Application of Ceiling Suspension Systems for

Acoustical Tile and Lay-in Panels in Areas

Requiring Moderate Seismic Restraint.

09 22 16 - 3

PART 2 - PRODUCTS

2.1 PROTECTIVE COATING

Galvanize steel studs, runners (track), rigid (hat section) furring channels, "Z" shaped furring channels, and resilient furring channels, with coating designation of G40 or equivalent.

2.2 STEEL STUDS AND RUNNERS (TRACK)

A. ASTM C645, modified for thickness specified and sizes as shown.

1. Use C 645 steel, 0.75 mm (0.0296-inch) minimum base-metal (30 mil).

2. Runners same thickness as studs.

3. Exception: Members that can show certified third party testing with gypsum board in accordance with ICC ES AC86 (Approved May 2012) need not meet the minimum thickness limitation or minimum section properties set forth in ASTM C 645. The submission of an evaluation report is acceptable to show conformance to this requirement. Use C

645 steel, 0.48mm (0.019 inch) minimum base-metal (19 mil).

B. Provide not less than two cutouts in web of each stud, approximately

300 mm (12 inches) from each end, and intermediate cutouts on approximately 600 mm (24-inch) centers.

C. Doubled studs for openings and studs for supporting concrete backer-board.

D. Studs 3600 mm (12 feet) or less in length shall be in one piece.

E. Shaft Wall Framing:

1. Conform to rated wall construction.

2. C-H Studs or C-T Studs.

3. E Studs.

4. J Runners.

5. Steel Jamb-Strut.

2.3 FURRING CHANNELS

A. Rigid furring channels (hat shape): ASTM C645.

B. Resilient furring channels:

1. Not less than 0.45 mm (0.0179-inch) thick bare metal.

2. Semi-hat shape, only one flange for anchorage with channel web leg slotted on anchorage side, channel web leg on other side stiffens fastener surface but shall not contact anchorage surface other channel leg is attached to.

09 22 16 - 4

C. "Z" Furring Channels:

1. Not less than 0.45 mm (0.0179-inch)-thick base metal, with 32 mm

(1-1/4 inch) and 19 mm (3/4-inch) flanges.

2. Web furring depth to suit thickness of insulation.

D. Rolled Steel Channels: ASTM C754, cold rolled; or, ASTM C841, cold rolled.

2.4 FASTENERS, CLIPS, AND OTHER METAL ACCESSORIES

A. ASTM C754, except as otherwise specified.

B. For fire rated construction: Type and size same as used in fire rating test.

C. Fasteners for steel studs thicker than 0.84 mm (0.033-inch) thick. Use

ASTM C954 steel drill screws of size and type recommended by the manufacturer of the material being fastened.

D. Clips: ASTM C841 (paragraph 6.11), manufacturer’s standard items.

Clips used in lieu of tie wire shall have holding power equivalent to that provided by the tie wire for the specific application.

E. Concrete ceiling hanger inserts (anchorage for hanger wire and hanger straps): Steel, zinc-coated (galvanized), manufacturers standard items, designed to support twice the hanger loads imposed and the type of hanger used.

F. Tie Wire and Hanger Wire:

1. ASTM A641, soft temper, Class 1 coating.

2. Gage (diameter) as specified in ASTM C754 or ASTM C841.

G. Attachments for Wall Furring:

1. Manufacturers standard items fabricated from zinc-coated (galvanized) steel sheet.

2. For concrete or masonry walls: Metal slots with adjustable inserts or adjustable wall furring brackets. Spacers may be fabricated from 1 mm

(0.0396-inch) thick galvanized steel with corrugated edges.

H. Power Actuated Fasteners: Type and size as recommended by the manufacturer of the material being fastened.

2.5 SUSPENDED CEILING SYSTEM FOR GYPSUM BOARD (OPTION)

A. Conform to ASTM C635, heavy duty, with not less than 35 mm (1-3/8 inch) wide knurled capped flange face designed for screw attachment of gypsum board.

09 22 16 - 5

B. Wall track channel with 35 mm (1-3/8 inch) wide flange.

PART 3 - EXECUTION

3.1 INSTALLATION CRITERIA

A. Where fire rated construction is required for walls, partitions, columns, beams and floor-ceiling assemblies, the construction shall be same as that used in fire rating test.

B. Construction requirements for fire rated assemblies and materials shall be as shown and specified, the provisions of the Scope paragraph (1.2) of ASTM C754 and ASTM C841 regarding details of construction shall not apply.

3.2 INSTALLING STUDS

A. Install studs in accordance with ASTM C754, except as otherwise shown or specified.

B. Space studs not more than 610 mm (24 inches) on center.

C. Cut studs 6 mm to 9 mm (1/4 to 3/8-inch) less than floor to underside of structure overhead when extended to underside of structure overhead.

D. Where studs are shown to terminate above suspended ceilings, provide bracing as shown or extend studs to underside of structure overhead.

E. Extend studs to underside of structure overhead for fire, rated partitions, smoke partitions, shafts, and sound rated partitions and insulated exterior wall furring.

F. Where shown, studs may terminate at ceiling as shown.

G. Openings:

1. Frame jambs of openings in stud partitions and furring with two studs placed back to back or as shown.

2. Fasten back to back studs together with 9 mm (3/8-inch) long Type S pan head screws at not less than 600 mm (two feet) on center, staggered along webs.

3. Studs fastened flange to flange shall have splice plates on both sides approximately 50 X 75 mm (2 by 3 inches) screwed to each stud with two screws in each stud. Locate splice plates at 600 mm (24 inches) on center between runner tracks.

H. Fastening Studs:

1. Fasten studs located adjacent to partition intersections, corners and studs at jambs of openings to flange of runner tracks with two screws through each end of each stud and flange of runner.

09 22 16 - 6

2. Do not fasten studs to top runner track when studs extend to underside of structure overhead.

I. Chase Wall Partitions:

1. Locate cross braces for chase wall partitions to permit the installation of pipes, conduits, carriers and similar items.

2. Use studs or runners as cross bracing not less than 63 mm (2-1/2 inches wide).

J. Form building seismic or expansion joints with double studs back to back spaced 75 mm (three inches) apart plus the width of the seismic or expansion joint.

K. Form control joint, with double studs spaced 13 mm (1/2-inch) apart.

3.3 INSTALLING WALL FURRING FOR FINISH APPLIED TO ONE SIDE ONLY

A. In accordance with ASTM C754, or ASTM C841 except as otherwise specified or shown.

B. Wall furring-Stud System:

1. Framed with 63 mm (2-1/2 inch) or narrower studs, 600 mm (24 inches) on center.

2. Brace as specified in ASTM C754 for Wall Furring-Stud System or brace with sections or runners or studs placed horizontally at not less than three foot vertical intervals on side without finish.

3. Securely fasten braces to each stud with two Type S pan head screws at each bearing.

C. Direct attachment to masonry or concrete; rigid channels or "Z" channels:

1. Install rigid (hat section) furring channels at 600 mm (24 inches) on center, horizontally or vertically.

2. Install "Z" furring channels vertically spaced not more than 600 mm

(24 inches) on center.

3. At corners where rigid furring channels are positioned horizontally, provide mitered joints in furring channels.

4. Ends of spliced furring channels shall be nested not less than

200 mm (8 inches).

5. Fasten furring channels to walls with power-actuated drive pins or hardened steel concrete nails. Where channels are spliced, provide two fasteners in each flange.

09 22 16 - 7

6. Locate furring channels at interior and exterior corners in accordance with wall finish material manufacturers printed erection instructions. Locate "Z" channels within 100 mm (4 inches) of corner.

D. Installing Wall Furring-Bracket System: Space furring channels not more than 400 mm (16 inches) on center.

3.4 INSTALLING SUPPORTS REQUIRED BY OTHER TRADES

A. Provide for attachment and support of electrical outlets, plumbing, laboratory or heating fixtures, recessed type plumbing fixture accessories, access panel frames, wall bumpers, wood seats, toilet stall partitions, dressing booth partitions, urinal screens, chalkboards, tackboards, wall-hung casework, handrail brackets, recessed fire extinguisher cabinets and other items like auto door buttons and auto door operators supported by stud construction.

B. Provide additional studs where required. Install metal backing plates, or special metal shapes as required, securely fastened to metal studs.

3.5 INSTALLING SHAFT WALL SYSTEM

A. Conform to UL Design No. U438 for two-hour fire rating.

B. Position J runners at floor and ceiling with the short leg toward finish side of wall. Securely attach runners to structural supports with power driven fasteners at both ends and 600 mm (24 inches) on center.

C. After liner panels have been erected, cut C-H studs and E studs, from 9 mm (3/8-inch) to not more than 13 mm (1/2-inch) less than floor-to-ceiling height. Install C-H studs between liner panels with liner panels inserted in the groove.

D. Install full-length steel E studs over shaft wall line at intersections, corners, hinged door jambs, columns, and both sides of closure panels.

E. Suitably frame all openings to maintain structural support for wall:

1. Provide necessary liner fillers and shims to conform to label frame requirements.

2. Frame openings cut within a liner panel with E studs around perimeter.

3. Frame openings with vertical E studs at jambs, horizontal J runner at head and sill.

09 22 16 - 8

F. Elevator Shafts:

1. Frame elevator door frames with 0.87 mm (0.0341-inch) thick J strut or J stud jambs having 75 mm (three-inch) long legs on the shaft side.

2. Protrusions including fasteners other than flange of shaft wall framing system or offsets from vertical alignments more than 3 mm

(1/8-inch) are not permitted unless shown.

3. Align shaft walls for plumb vertical flush alignment from top to bottom of shaft.

3.6 INSTALLING FURRED AND SUSPENDED CEILINGS OR SOFFITS

A. Install furred and suspended ceilings or soffits in accordance with

ASTM C754 or ASTM C841 except as otherwise specified or shown for screw attached gypsum board ceilings and for plaster ceilings or soffits.

1. Space framing at 400 mm (16-inch) centers for metal lath anchorage.

2. Space framing at 600 mm (24-inch) centers for gypsum board anchorage.

B. New exposed concrete slabs:

1. Use metal inserts required for attachment and support of hangers or hanger wires with tied wire loops for embedding in concrete.

2. Furnish for installation under Division 3, CONCRETE.

3. Suspended ceilings under concrete rib construction shall have runner channels at right angles to ribs and be supported from ribs with hangers at ends and at 1200 mm (48-inch) maximum intervals along channels. Stagger hangers at alternate channels.

C. Concrete slabs on steel decking composite construction:

1. Use pull down tabs when available.

2. Use power activated fasteners when direct attachment to structural framing can not be accomplished.

D. Where bar joists or beams are more than 1200 mm (48 inches) apart, provide intermediate hangers so that spacing between supports does not exceed 1200 mm (48 inches). Use clips, bolts, or wire ties for direct attachment to steel framing.

E. Existing concrete construction exposed or concrete on steel decking:

1. Use power actuated fasteners either eye pin, threaded studs or drive pins for type of hanger attachment required.

09 22 16 - 9

2. Install fasteners at approximate mid height of concrete beams or joists. Do not install in bottom of beams or joists.

F. Steel decking without concrete topping:

1. Do not fasten to steel decking 0.76 mm (0.0299-inch) or thinner.

2. Toggle bolt to decking 0.9 mm (0.0359-inch) or thicker only where anchorage to steel framing is not possible.

G. Installing suspended ceiling system for gypsum board (ASTM C635

Option):

1. Install only for ceilings to receive screw attached gypsum board.

2. Install in accordance with ASTM C636.

a. Install main runners spaced 1200 mm (48 inches) on center.

b. Install 1200 mm (four foot) tees not over 600 mm (24 inches) on center; locate for edge support of gypsum board.

c. Install wall track channel at perimeter.

H. Installing Ceiling Bracing System:

1. Construct bracing of 38 mm (1-1/2 inch) channels for lengths up to

2400 mm (8 feet) and 50 mm (2 inch) channels for lengths over 2400 mm (8 feet) with ends bent to form surfaces for anchorage to carrying channels and overhead construction. Lap channels not less than 600 mm (2 feet) at midpoint back to back. Screw or bolt lap together with two fasteners.

2. Install bracing at an approximate 45 degree angle to carrying channels and structure overhead; secure as specified to structure overhead with two fasteners and to carrying channels with two fasteners or wire ties.

3. Brace suspended ceiling or soffit framing in seismic areas in accordance with ASTM E580.

3.7 TOLERANCES

A. Fastening surface for application of subsequent materials shall not vary more than 3 mm (1/8-inch) from the layout line.

B. Plumb and align vertical members within 3 mm (1/8-inch.)

C. Level or align ceilings within 3 mm (1/8-inch.)

04-01-20

09 29 00 - 1

SECTION 09 29 00

GYPSUM BOARD

This section specifies installation and finishing of gypsum board.

1.2 RELATED WORK

A. Installation of steel framing members for walls, partitions, furring, soffits, and ceilings: Section 05 40 00, COLD-FORMED METAL FRAMING, and

Section 09 22 16, NON-STRUCTURAL METAL FRAMING.

B. Sound deadening board: Section 07 21 13, THERMAL INSULATION.

C. Acoustical Sealants: Section 07 92 00, JOINT SEALANTS.

D. Tile Backer Board: Section 093013 CERAMIC/PORCELAIN…