Division 9 specs - Finishes.pdf
PDF 1 MB Posted
- Solicitation number
- 36C24224R0071
About this file
This document is a solicitation for construction of a new Emergency Department at the Stratton VA Medical Center in Albany, NY. The project involves demolition, site work, general construction, alterations, mechanical, plumbing, electrical, fire alarm, sprinkler, and medical gas work for the new department. Key details include:
The successful offeror shall begin work within 15 calendar days of the notice to proceed and complete all work within 550 calendar days. The contractor must provide a competent, dedicated full-time superintendent for the project. Commissioning and punch list completion are required prior to final inspection. The contractor shall utilize the VISN 2 Autodesk Build construction management platform for project collaboration and communication. No additional time or cost will be provided for failure to use the required platform. The solicitation is issued by the Department of Veterans Affairs Veterans Health Administration, Veterans Integrated Service Network 2.
View the file
Other files
Show 40 more
Latest 50 of 56 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SAMUEL S. STRATTON VA MEDICAL CENTER
DESIGN NEW EMERGENCY DEPARTMENT
VA PROJECT NO. 528-809
01-01-21
09 05 16 - 1
SECTION 09 05 16
SUBSURFACE PREPARATION FOR FLOOR FINISHES
PART 1 - GENERAL
1.1 DESCRIPTION
A. This section specifies subsurface preparation requirements for areas to receive the installation of applied and resinous flooring. This section includes testing concrete for moisture and pH, remedial floor coating for concrete floor slabs having unsatisfactory moisture or pH conditions, floor leveling and repair as required.
1.2 RELATED WORK
A. Section 07 92 00, JOINT SEALANTS.
B. Section 09 65 16, RESILIENT SHEET FLOORING, C. Section 09 65 19, RESILIENT TILE FLOORING, D. Section 09 67 23 60, RESINOUS (Urethane and Epoxy Mortar) FLOORING, E. Section 09 68 00, WALKOFF MAT CARPETING.
1.3 SUBMITTALS
A. Submit in accordance with Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA and TEST DATA.
B. Written approval confirming product compatibility with subfloor material manufacturer and the flooring manufacturer
C. Product Data:
1. Moisture remediation system
2. Underlayment Primer
3. Cementitious Self-Leveling Underlayment
4. Cementitious Trowel-Applied Underlayment (Not suitable for resinous floor finishes)
D. Test Data:
1. Moisture test and pH results performed by a qualified independent testing agency or warranty holding manufacturer’s technical representative.
1.4 DELIVERY AND STORAGE
A. Deliver materials in containers with labels legible and intact and grade-seals unbroken.
B. Store material to prevent damage or contamination.
09 05 16 - 2
1.5 APPLICABLE PUBLICATIONS
A. Publications listed below form a part of this specification to the extent referenced. Publications are referenced in text by basic designation only.
B. ASTM International(ASTM):
D638-14(2014)...........Standard Test Method for Tensile Properties of
Plastics
D4259-18(2019)..........Standard Practice for Preparation of Concrete by Abrasion Prior to Coating Application.
C109/C109M-20b(2020)....Standard Test Method for Compressive Strength of Hydraulic Cement Mortars (Using 2-in. or
[50-mm] Cube Specimens
7234-19(2020)...........Standard Test Method for Pull-Off Adhesion
Strength of Coatings on Concrete Using Portable
Pull-Off Adhesion Testers
E96/E96M-16(2016).......Standard Test Methods for Water Vapor
Transmission of Materials
F710-1e1(2020)..........Standard Practice for Preparing Concrete Floors to Receive Resilient Flooring
F1869-16a...............Standard Test Method for Measuring Moisture
Vapor Emission Rate of Concrete Subfloor Using
Anhydrous Calcium Chloride
F2170-19a(2020).........Standard Test Method for Determining Relative
Humidity in Concrete Floor Slabs Using in situ
Probes
C348-20(2020)...........Standard Test Method for Flexural Strength of
Hydraulic-Cement Mortars
C191-19(2020)...........Standard Test Method for Time of Setting of
Hydraulic Cement by Vicat Needle
PART 2 - PRODUCTS
2.1 MOISTURE REMEDIATION COATING (MRC)
A. System Descriptions:
1. High-solids, epoxy system designed to suppress excess moisture in concrete prior to an overlayment. For use under resinous products, 09 05 16 - 3
VCT, tile and carpet where issues caused by moisture vapor are a concern.
B. Products: Subject to compliance with applicable fire, health, environmental, and safety requirements for storage, handling, installation, and clean up.
C. System Components: Verify specific requirements as systems vary by manufacturer. Verify build up layers and installation method. Verify compatibility with substrate. Use manufacturer’s standard components, compatible with each other and as follows:
1. Liquid applied coating:
a. Resin: epoxy.
b. Formulation Description: Multiple component high solids.
c. Application: Per manufacturer’s written installation requirements.
d. Thickness: minimum 10 mils
D. Material Vapor Permeance: Application shall achieve a permeance rating of less than 0.1 perm in accordance with ASTM E96/E96M.
E. Maximum RH requirement: 100% testing in accordance with ASTM F2170.
Property Test Value
Tensile Strength
ASTM D638 4,400 psi
Volatile Organic Compound
Limits (V.O.C.)
SCAMD Rule 1113
(Ammended
02/05/2016)
25 grams per liter
Permeance ASTM E96 0.1 perms
Tensile Modulus ASTM D638 1.9X105 psi
Percent Elongation ASTM D638 12%
Cure Rate Per manufacture’s
Data
4 hours Tack free with 24hr recoat window
Bond Strength ASTM D7234 100% bond to concrete failure
09 05 16 - 4
2.2 CEMENTITIOUS SELF-LEVELING UNDERLAYMENT
A. System Descriptions:
1. High performance self-leveling underlayment resurfacer. Single component, self-leveling, cementitious material designed for easy application as an underlayment for all types of flooring materials.
It is used for substrate repair and leveling.
B. Products: Subject to compliance with applicable fire, health, environmental, and safety requirements for storage, handling, installation, and clean up. Gypsum-based products are unacceptable.
C. System Characteristics:
1. Wearing Surface: smooth
2. Thickness: Per architectural drawings, ranging from feathered edge to 1”, per application. Applications greater than 1” require additional 3/8” aggregate to mix or as recommended by manufacturer.
D. Underlayment shall be calcium aluminate cement-based, containing
Portland cement. Gypsum-based products are unacceptable.
E. Compressive Strength: Minimum 4100 psi in 28 days in accordance with
ASTM C109/C109M.
F. Flexural Strength: Minimum 1000 psi in 28 days in accordance with ASTM
C348
G. Dry Time: Underlayment shall receive the application of moisture insensitive tile in 6 hours, floor coverings in 16 hours, and resinous flooring in 3-7 days.
H. Primer: compatible and as recommended by manufacturer for use over intended substrate
I. System Components: Manufacturer's standard components that are compatible with each other and as follows:
1. Primer:
a. Resin: copolymer
b. Formulation Description: single component ready to use.
c. Application Method: Squeegee and medium nap roller.
d. All puddles shall be removed, and material shall be allowed to dry, 1-2 hours at 70F/21C.
e. Number of Coats: (1) one.
09 05 16 - 5
2. Grout Resurfacing Base:
a. Formulation Description: Single component, cementitious self-leveling high-early and high-ultimate strength grout.
b. Application Method: colloidal mix pump, cam rake, spike roll.
1) Thickness of Coats: Per architectural scope, 1” lifts.
2) Number of Coats: More than one if needed.
c. Aggregates: for applications greater than 1inch, require additional 3/8” aggregate to mix.
J.
2.3 CEMENTITIOUS TROWEL-APPLIED UNDERLAYMENT (NOT SUITABLE FOR RESINOUS FLOOR
FINISHES)
A. Underlayment shall be calcium aluminate cement-based, containing
Portland cement. Gypsum-based products are unacceptable.
B. Compressive Strength: Minimum 4000 psi in 28 days
C. Trowel-applied underlayment shall not contain silica quartz (sand).
D. Dry Time: Underlayment shall receive the application of floor covering in 15-20 minutes.
PART 3 - EXECUTION
3.1 ENVIRONMENTAL REQUIREMENTS
A. Maintain ambient temperature of work areas at not less than 16 degree C
(60 degrees F), without interruption, for not less than 24 hours before testing and not less than three days after testing.
B. Maintain higher temperatures for a longer period of time where required by manufacturer's recommendation.
C. Do not install materials when the temperatures of the substrate or materials are not within 60-85 degrees F/ 16-30 degrees C.
Property Test Value
Compressive Strength
ASTM C109/C109M
2,200 psi @ 24 hrs
3,000 psi @ 7 days
Initial set time
Final Set time
ASTM C191
30-45 min.
1 to 1.5 hours
Bond Strength
ASTM D7234
100% bond to concrete failure
09 05 16 - 6
3.2 SURFACE PREPARATION
A. Concrete shall meet the requirements of ASTM F710 and be sound, solid, clean, and free of all oil, grease, dirt, curing compounds, and any substance that might act as a bond-breaker before application. As required prepare slab by mechanical methods. No chemicals or solvents shall be used.
B. General: Prepare and clean substrates according to flooring manufacturer's written instructions for substrate indicated.
C. Prepare concrete substrates if required per ASTM D4259 as follows:
1. Dry abrasive blasting.
2. Wet abrasive blasting.
3. Vacuum-assisted abrasive blasting.
4. Centrifugal-shot abrasive blasting.
5. Comply with manufacturer's written instructions.
D. Repair damaged and deteriorated concrete according to flooring manufacturer's written recommendations.
E. Verify that concrete substrates are dry.
F. Perform anhydrous calcium chloride test, ASTM F 1869. Proceed with application only after substrates have maximum moisture-vapor-emission rate of per flooring manufactures formal and project specific written recommendation.
G. Perform in situ probe test, ASTM F2170. Proceed with application only after substrates do not exceed a maximum potential equilibrium relative humidity per flooring manufacture’s formal and project specific written recommendation.
H. Provide a written report showing test placement and results.
I. Prepare joints in accordance with Section 07 92 00, JOINT SEALANTS and material manufacturer’s instructions.
J. Alkalinity: Measure surface pH in accordance with procedures provided in ASTM F710 or as outlined by qualified testing agency or flooring manufacturer’s technical representative.
K. Tolerances: Subsurface shall meet the flatness and levelness tolerance specified on drawings or recommended by the floor finish manufacturer.
Tolerance shall also not to exceed 1/4” deviation in 10’. As required, install underlayment to achieve required tolerance.
09 05 16 - 7
L. Other Subsurface: For all other subsurface conditions, such as wood or metal, contact the floor finish or underlayment manufacturer, as appropriate, for proper preparation practices.
3.3 MOISTURE REMEDIATION COATING
A. Where results of relative humidity testing (ASTM F2170) exceed the requirements of the specified flooring manufacturer, apply remedial coating as specified to correct excessive moisture condition.
B. Prior to remedial floor coating installation mechanically prepare the concrete surface to provide a concrete surface profile in accordance with ASTM D4259.
C. Mix and apply moisture remediation coating in accordance with manufacturer’s instructions.
3.4 CEMENTITOUS UNDERLAYMENT
A. Install cementitious self-leveling underlayment as required to correct surface defects, floor flatness or levelness corrections to meet the tolerance requirements as or detailed on drawings, address non-moving cracks or joints, provide a smooth surface for the installation of floor covering, or meet elevation requirements detailed on drawings.
B. Mix and apply in accordance with manufacturer's instructions.
3.5 PROTECTION
A. Prior to the installation of the finish flooring, the surface of the underlayment should be protected from abuse by other trades by the use of plywood, tempered hardwood, or other suitable protection course
3.6 FIELD QUALITY CONTROL
A. Where specified, field sampling of products shall be conducted by a qualified, independent testing facility.
- - - E N D - - -
09 06 00 - i
Article I. SECTION 09 06 00
SCHEDULE FOR FINISHES
SECTION 09 06 00-SCHEDULE FOR FINISHES
VAMC: SAMUEL S. STRATTON VA MEDICAL CENTER
Location: Albany, NY
Project no. and Name: VA PROJECT NO. 528-809 - DESIGN NEW EMERGENCY DEPARTMENT
Submission: 100%
Date: 9-15-2021
09 06 00 - ii
09 06 00 - 1
SECTION 09 06 00
SCHEDULE FOR FINISHES
A. This section contains a coordinated system in which requirements for materials specified in other sections shown are identified by abbreviated material names and finish codes in the room finish schedule or shown for other locations.
1.2 MANUFACTURERS
A. Manufacturer’s trade names and numbers used herein are only to identify colors, finishes, textures and patterns. Products of other manufacturer’s equivalent to colors, finishes, textures and patterns of manufacturers listed that meet requirements of technical specifications will be acceptable upon approval in writing by contracting officer for finish requirements.
1.3 SUBMITTALS
A. Submit in accordance with SECTION 01 33 23, SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES provide quadruplicate samples for color approval of materials and finishes specified in this section.
09 06 00 - 2
1.4 APPLICABLE PUBLICATIONS
A. Publications listed below form a part of this specification to the extent referenced. Publications are referenced in text by basic designation only.
B. MASTER PAINTING INSTITUTE: (MPI)
6/1/2019................Architectural Painting Specification Manual
PART 2 - PRODUCTS
2.1 NOT USED
2.2 DIVISION 31 - EARTHWORK
A. SECTION 32 17 23, PAVEMENT MARKINGS.
Color Manufacturer MFG. Color Name/No.
Yellow - Conform to MPI No. 97
White - Conform to MPI No. 97
B. BOLLARDS
Material Finish Style Name/ No. Manufacturer Mfg. Color
Name/No.
STEEL PAINT 10” DECORATIVE IDEAL SHIELD TBD MFG. STANDARD
STEEL / Concrete Paint Impact Rated Black
C. SITE AND STREET FURNISHINGS
09 06 00 - 3
Item Style Name/No. Finish Manufacture Mfg. Color
Name/No.
Benches 694854BK Outdoor powder coated paint
Global Industrial Black
2.3 DIVISION 03 – CONCRETE
A. SECTION 03 30 00, CAST IN PLACE CONCRETE // SECTION 03 30 53, (SHORT FORM) CAST-IN-PLACE CONCRETE //
Surface Finish Description
Exposed Smooth - form
B. SECTION 03 45 00, PRECAST ARCHITECTURAL CONCRETE
Finish Color Texture Finish Manufacturer Mfg. Color
Name/No.
N/A N/A N/A N/A N/A
09 06 00 - 4
2.4 DIVISON 04 – MASONRY
Section 04 05 13, MASONRY MORTARING and Section 04 05 16, MASONRY GROUTING
Finish Code Manufacturer Mfg. Color Name
- West Brook Type N – TBD Manufacturer
Standard
- West Brook
A. Section 04 20 00, UNIT MASONRY
B. UNIT MASONRY (04 20 00)
Stone Type Color Manufacturer Mfg. Color & Texture
No.
Architectural Concrete Block
(CMU-1)
8”H x 16”W x 4” D
(nominal)
Westbrook Concrete
Block Co - Connecticut
GFP-351
Ground Face Polish
Architectural Concrete Block
(CMU-2)
12”H x 24”W x 4”D
(nominal)
Westbrook Concrete
Block Co - Connecticut
GFT-226D
1. CONCRETE MASONRY UNIT (CMU)
Type Size Pattern Finish Mfg. Color
Name/No.
CMU Standard 8”H x16”W x 4”D
(nominal)
N/A N/A N/A
CMU Standard 8”H x16”W x 8”D
(nominal)
N/A N/A N/A
09 06 00 - 5
Textured Face
2.5 DIVISION 05 – METALS
A. SECTION 05 12 00, STRUCTURAL STEEL FRAMING – confirm no exposed
Component Finish Color
Structural steel primer red
B. SECTION 05 50 00, METAL FABRICATIONS
Item Finish
Frames for Lead Lined Doors Coronado Industrial Coating DTM, Semi-Gloss, "INDIAN
RIVER" 985
Loose Lintels Galvanized
Steel Ladders Galvanized
Steel Ladder Rungs Galvanized
Steel Pipe Railings and Gates (not on Steel
Stairs)
Paint
Aluminum Railings Anodized
Stainless Steel Railings N/A
C. SECTION 05 51 00, INTERIOR METAL STAIRS
Newel Posts Coronado Industrial Coating, Corotech DTM Semi Gloss Paint
984 Stone Hearth
Guard Rails Coronado Industrial Coating, Corotech DTM Semi Gloss Paint
984 Stone Hearth
09 06 00 - 6
Handrails Coronado Industrial Coating, Corotech DTM Semi Gloss Paint
984 Stone Hearth
Stringers Coronado Industrial Coating, Corotech DTM Semi Gloss Paint
984 Stone Hearth
Risers Coronado Industrial Coating, Corotech DTM Semi Gloss Paint
984 Stone Hearth
Underside Coronado Industrial Coating, 984 Stone Hearth
A. SECTION 05 51 00, EXTERIOR METAL STAIRS
Newel Posts Coronado Industrial Coating, Corotech DTM Semi Gloss Paint
Black (RAL 9005)
Guard Rails Coronado Industrial Coating, Corotech DTM Semi Gloss Paint
Black (RAL 9005)
Handrails Coronado Industrial Coating, Corotech DTM Semi Gloss Paint
Black (RAL 9005)
Stringers Coronado Industrial Coating, Corotech DTM Semi Gloss Paint
Black (RAL 9005)
Risers Coronado Industrial Coating, Corotech DTM Semi Gloss Paint
Black (RAL 9005)
Underside Coronado Industrial Coating, Black (RAL 9005)
2.6 DIVISION 06 WOOD, PLASTICS, AND COMPOSITES
09 06 00 - 7
A. SECTION 06 20 00, FINISH CARPENTRY
B. MISC. ACCESSORIES AT RECEPTION
Finish code/Item Material Manufacturer Color Mfg. Color Name/No.
(QT-1) Quartz Countertop Wilsonart Quartz Lorraine Q1012
(SSM-1) Solid Surface
Countertop
Corian Solid Surface Elegant Gray
(PL-1) Plastic Laminate
(Cabinet)
Pionite Surface
Systems
Mocha Almond Fudge WX600-N SUEDE
(PL-2) Plastic Laminate
(Countertop)
Wilsonart Standard
Laminate
Natural Cotton 4946-38
(FTP-1) Fabric Wrapped
Tack Panel
Stinson-Luther II LUT 212 Neutra
(FTP-2) Fabric Wrapped
Tack Panel
Stinson-Luther II LUT 210 Milky Way
(WB-1) Wall Base Roppe/6” High Vinyl #171 Sandstone
(DP-1) SOELBERG
(Basis of Design)
¾” MDF custom
Soelberg Panel
Painted (PT-8) (See millwork
Details for Panel
Dimensions)
(AWP-1) SOELBERG
(Basis of Design)
½” Acoustical Panel COLOR: FOG (See millwork
Details for Panel
Dimensions)
Counter Supports Solid metal
Rakks Bracket
Black EH-Surface Mount
Grommets for Cable
Pass thru countertops
Molded plastic
Doug Mockett and
Company, Inc, “VG series”, Black, 2-1/2” outside Diameter with matching caps
09 06 00 - 8
2.7 DIVISION 07 - THERMAL AND MOISTURE PROTECTION
A. SECTION 07 40 00, ROOFING AND SIDING PANELS
Type Shape Ext. Finish Int. Finish Manufacturer Mfg. Color Name/No.
Metal Wall
Panel (MP-1)
N/A 200H Series, Fluropon
- Kingspan -
Benchmark
“Natural Suede” (Mica)
Metal Wall
Panel (MP-2)
N/A 200H Series, Fluropon
- Kingspan -
Benchmark
“Champagne Bronze”
(Mica)
Metal Wall
Panel (MP-3)
N/A 200H Series, Fluropon
- Kingspan -
Benchmark
“Bone White”
B. SETION 07 53 23, THERMOPLASTIC POLYOLEFIN (TPO) ROOFING
Color Manufacturer Mfg. Color Name/No.
Component Material Manufacturer Mfg. Color Name/No.
Drop-In Deal Tray Stainless Steel C.R. Laurence Co., Inc. Brushed Stainless Steel, 12” wide x 10” deep x 1 9/16” high stranded Drop-In Tray
Speak Thru Stainless Steel C.R. Laurence Co., Inc. Brushed Stainless Steel 5” diameter
09 06 00 - 9
White Carlisle (BOD) White
C. SECTION 07 60 00, FLASHING AND SHEET METAL
Item Material Finish
Copings Aluminum Painted, Manufacturer’s Finish.
Color selected from Manuf. Full range of standard finishes
Roof Insulated Expansion Joint Covers See 07 95 13, EXPANSION JOINT
COVER ASSEMBLIES
N/A
Scuppers N/A N/A
D. SECTION 07 71 00, ROOF SPECIALITIES and 07 72 00, ROOF ACCESSORIES
Item Material Finish Manufacturer Manufacturer/Color
Name/Number.
Equipment Support Galv. Steel Paint
Copings Extruded Aluminum Painted, Manufacturer’s
Finish
PAC – CLAD (BOD) Color selected from
Manuf. Full range of standard finishes
E. SECTION 07 92 00, JOINT SEALANTS
Location Color Manufacturer Manufacturer Color
Masonry Expansion Joints Match adjacent mortar joints
Tremco -
09 06 00 - 10
CMU Control Joints Match adjacent mortar joints
Tremco -
New to Existing Walls Match adjacent material to join
Tremco -
Building Expansion Joints Match adjacent expansion joint
Tremco -
Masonry Sealed Joints Match adjacent material to join
Tremco -
F. SECTION 07 95 13, EXPANSION JOINT COVER ASSEMBLIES
Item/Location Finish code Manufacturer Mfg. Color Name/No.
Floor Component
Cover Plate Frame
Casket or Sealant
(Interior Floor)
EXP-1 Construction
Specialties
GFST-200
Color: Greige
Wall Component
Cover Plate Frame
Casket or Sealant
(Interior Wall)
EXP-2 Construction
Specialties
GFS-WL
Color: Greige
Exterior Wall
Seal Cover
EXP-3 Construction
Specialties
SF-800
Color: Greige
Exterior Horizontal
Cover Plate Frame
Thermoplastic Joint
EXP-4 EMSEAL Horizontal Colorseal -
Color: TBD
2.8 DIVISION 08 - OPENINGS
A. SECTION 08 11 13, HOLLOW METAL DOORS AND FRAMES
09 06 00 - 11
1. Paint both sides of door and frames same color including ferrous metal louvers, and hardware attached to door
Component Color of Paint Type and Gloss
Door Coronado Industrial Coatings Corotech DTM Semi-gloss, Color: “Indian River” 985
Frame Coronado Industrial Coatings Corotech DTM Semi-gloss, Color: “Indian River” 985
Window frame Coronado Industrial Coatings Corotech DTM Semi-gloss, Color: “Indian River” 985
B. SECTION 08 14 00, INTERIOR WOOD DOORS
Component Finish/Color
Doors Mohawk Doors, Premium 2000 series
Species: White Birch
Color: TBD
C. SECTION 08 31 13, ACCESS DOORS AND FRAMES
Material Finish/Color
Steel Coronado Industrial Coatings Corotech DTM Semi-gloss, Color: to match adjacent wall
D. SECTION 08 41 13, ALUMINUM-FRAMED ENTRANCES AND STOREFRONTS
Material Finish Manufacturer Manufacturer Color
Name/No.
Aluminum Clear Anodized Kawneer -
Glass SEE 088000 GLAZING - -
09 06 00 - 12
E. SECTION 08 44 13, GLAZED ALUMINUM CURTAIN WALLS
Component Material Finish Manufacturer Mfg. Color Name/No.
Frame Aluminum Clear Anodized Kawneer -
F. SECTION 08 51 13, ALUMINUM WINDOWS
Type Finish Glazing Manufacturer Mfg. Color Name/No.
Fixed Clear Anodized SEE 088000 GLAZING Kawneer -
G. WINDOW SILLS
Room No. and Name Material Finish
ALL EXTERIOR WINDOWS Aluminum (With Windows) Clear Anodized
H. SECTION 08 71 00, BUILDERS HARDWARE
See Hardware Specifications
SECTION 08 80 00, GLAZING
Glazing Type Manufacturer Mfg. Color Name/No.
MG #1 - Clear
IL #1 - Gray/Bronze Tint
IL #2 - Spandrel – Gray Bronze
FR #1 - Clear
09 06 00 - 13
SG #1 - Clear
SG #2 - Clear
SG #3 - Gray/Bronze
I. SECTION 08 90 00, LOUVERS AND VENTS
Item Location Material/ Manufacturer Mfg. Color Name/No.
Supply/Return Coordinated with APC-1 See MEP Drawings White
Supply/Return Coordinated with APC-2 See MEP Drawings Match Selected Grid Color
09 06 00 - 14
2.9 DIVISION 09 - FINISHES
A. SECTION 09 29 00, GYPSUM WALLBOARD - REVEALS
Finish code Color Manufacturer Mfg. Color Name/No
Reveal Molding (REV-1) Aluminum, Clear Anodized, Satin
Fry Reglet #DRM-50-100
Reveal End Caps
Aluminum, Clear Anodized, Satin
Fry Reglet (associated with #DRM-50-
100)
B. SECTION 09 30 13, CERAMIC/PORCELAIN TILING
Finish code Integral Manufacturer Mfg. Color Name/No. Color
PWT-1 WALL TILE DALTILE Avery (Glazed
Porcelain)
White AV17
PWT-2 WALL TILE DALTILE Brickwork (Glazed
Porcelain)
Patio BW03
PWT-3 WALL TILE DALTILE Raine (Marble Tile) Cumulus Grey M019
PWT-4 WALL TILE DALTILE Clio (Mosaic Tile) Hera CL15
C. SECTION 09 30 13, CERAMIC/PORCELAIN TILE GROUT
Location Manufacturer Type Mfg. Color Name/No.
Coordinate w/ Tile (PWT-1) Laticrete #255 MultiMax #17 Marble Beige
Coordinate w/ Tile (PWT-2) Laticrete #255 MultiMax #57 Desert Khaki
Coordinate w/ Tile (PWT-3) Laticrete #255 MultiMax #90 Light Pewter
Coordinate w/ Tile (PWT-4) Laticrete #255 MultiMax #17 Marble Beige
09 06 00 - 15
D. SECTION 09 30 13, EDGE GUARD OR TRIM (W)
Item Manufacturer Mfg. Color Name/No
Clear Anodized Aluminum, Satin Schluter Rondec RO 100 AE
Clear Anodized Aluminum, Satin Schluter Rondec E/RO 100 AE (Outside Corner)
Clear Anodized Aluminum, Satin Schluter Rondec I/RO 100 AE (Inside Corner)
Clear Anodized Aluminum, Satin Schluter Rondec MC/RO 100 AE (Inside Corner)
Clear Anodized Aluminum, Satin Schluter Rondec DB(Top of Wainscoting Tile)
E. SECTION 09 51 00, ACOUSTICAL CEILINGS
Finish Code Component Color Pattern Manufacturer Mfg Name/No.
APC-1 Tegular Tile White Armstrong Optima HealthZone
(SP)– 3354 2’x2’
Tegular
(Coordinated w/ ACT-1) Exposed
Suspension System
White Armstrong Prelude XL, 15/16”
Grid
APC-2 Woodworks Tegular
Panels
Effects Sesame Armstrong W1 - Woodworks Tegular
Panels 6484
12”x48”x3/4”
(Coordinated w/ ACT-2) Exposed
Suspension System
Light Grey (LG) Armstrong Suprafine XL 9/16 exposed Tee Suspension
1. SECTION 09 30 13, MARBLE WINDOW STOOLS
Finish Code Manufacturer Mfg. Color Name/No.
SSM-1 Corian Solid Surface Elegant Gray
09 06 00 - 16
System
F. SECTION 09 54 23, LINEAR METAL CEILINGS (LMC)
Finish Code Strip Material Strip Face Size Manufacturer Mfg Name/No.
(LMC-1) Metal 6” x 96” Armstrong Linear & Linear
Exterior, Smooth
Texture, M1
Unperforated – Color:
Effects Sesame
(LMC-2) Metal 6” x 96” Armstrong Linear & Linear
Exterior, Smooth
Texture, M1
Unperforated - Color:
White Exterior
G. SECTION 09 54 00 – SPECIALTY CEILING MATERIALS
Room No. and
Name
Component Material Manufacturer Mfg. Color Name/No.
Waiting E102A Suspended
Acoustical Panels
Fiberglas Armstrong Soundscapes Acoustical Panels Model
Number 3920 – Color: White
H. SECTION 09 63 16, RESILIENT BASE & ACCESSORIES
Finish Code Material/ Component Size Manufacturer Mfg Name/No.
WB-1 Resilient Base 6 in. Roppe #171 Sandstone
A. SECTION 09 65 13, RESILIENT BASE STAIR TREADS AND ACCESSORIES
Finish Code Item Height Manufacturer Mfg Name/No.
RST1 Resilient Tread - Roppe #171 Sandstone
09 06 00 - 17
B. SECTION 09 65 19, LUXURY VINYL TILE FLOORING
Finish Code Manufacturer Size Mfg Name/No.
LVT-1 Armstrong Flooring 6” x 48” Biome
LVT-2 Armstrong Flooring 18” x 18” Coalesce
LVT-3 Armstrong Flooring 6” x 36” Coalesce
LVT-4 Armstrong Flooring 6” x 36” Coalesce
LVT-5 Armstrong Flooring 18” x 18” Coalesce
LVT-6 Armstrong Flooring 18” x 36” Coalesce
C. SECTION 09 65 16, [ RESILIENT SHEET FLOORING], HEAT WELDED SEAMS (WSF)
Finish Code Manufacturer Pattern name Mfg. Color Name/No.
WSF-1 Mannington Biospec Choices Biospec MD – Linen (15420)
1. SECTION 09 65 16, [RESILIENT SHEET FLOORING], WELDING RODS (WSF)
Finish code Manufacturer Mfg. Color Name/No.
WR1 Mannington With WSF-1, #842311
2. SECTION 09 65 16, [RESILIENT SHEET FLOORING], CAP STRIPS (WSF)
09 06 00 - 18
N/A N/A N/A
D. SECTION 09 65 16, TRANSITION STRIPS (TS)
TS1 Johnsonite CRS-XX-A – Color TA4 Gateway WG
E. SECTION 09 65 13, RESILIENT BASE AND ACCESSORIES
Finish Code Item Height Manufacturer Mfg Name/No.
(WB-1) Wall Base Roppe/6” High Vinyl Roppe #171 Sandstone
F. SECTION 09 68 00, CARPETING (CP)
Finish Code Manufacture Mfg. Color Name/No.
WOM-1 CONSTRUCTION SPECIALTIES / PEDITRED – G3 COLOR: 9332 ANTHRACITE
WOM-2 J & J FLOORING / INCOGNITO WALK-OFF
MODULAR
COLOR: 1837 OPERATIVE
G. SECTION 09 67 23.20, RESINOUS FLOORING / RESINOUS (EPOXY BASE)
RES-1 Stonhard Stonblend GSI-G – Color: Wolf Gray
RES-B Stonhard Stonblend GSI-Base – Color: Wolf Gray
09 06 00 - 19
H. SECTION 09 96 59, RESINOUS SPECIALTY GLAZED COATING SYSTEMS FOR WALLS, CEILINGS WALLBOARD
RES-W Stonhard Stonehard – Stonglaze VSI – Color: Bone
I. SECTION 09 91 00, PAINTING
1. MPI gloss and Sheen
Standards
Gloss @60 Sheen @85
Gloss level 1 A traditional matte finish-flat Max 5 units, and Max 10 units
Gloss level 2 A high side sheen flat-“a velvet-like” finish Max 10 units, and 10-35 units
Gloss level 3 A traditional “egg-shell like” finish 10-25 units, and 10-35 units
Gloss level 4 A “satin-like” finish 20-35 units, and Min. 35 units
Gloss level 5 A traditional semi-gloss 35-70 units
Gloss level 6 A traditional gloss 70-85 units
Gloss level 7 A high gloss More than 85 units
2. Paint code Gloss Manufacturer Mfg. Color Name/No.
(PT-1) Eggshell Finish BENJAMIN MOORE MARITIME WHITE 963
(PT-2) Eggshell Finish BENJAMIN MOORE INDIAN RIVER 985
(PT-3) Eggshell Finish BENJAMIN MOORE SIOUX FALLS 705
(PT-4) Eggshell Finish BENJAMIN MOORE WINTER SOLSTICE 1605
(PT-5) Eggshell Finish BENJAMIN MOORE IMPERIAL GRAY 1571
09 06 00 - 20
(PT-6) Eggshell Finish BENJAMIN MOORE STONE HEARTH 984
(PT-7) Eggshell Finish BENJAMIN MOORE SUPER WHITE OC 152
(PT-8) Level 4 finish BENJAMIN MOORE INDIAN RIVER 985
(Acrylic Paint)
(EPX-1) EPOXY PAINT BENJAMIN MOORE MARITIME WHITE 963
3. Stain Code (S) Gloss and
Transparency
Manufacturer Mfg. Color Name/No.
S Semi Minwax Basis of Design: “Greenwood MW 413”
09 06 00 - 21
2.10 DIVISION 10 - SPECIALTIES
A. SECTION 10 21 23, CUBICLE CURTAIN TRACKS
Item Manufacturer Mfg. Color Name/No.
Cubicle Curtain Track
InPro
Optitrac/”White”
Privacy Curtain
Standard textile - Stranded Stranded – Storm CM004506
(Panel With 72”)
B. SECTION 10 21 16, PREFABRICATED SHOWER AND DRESSING COMPARTMENTS
Room No. and
Name
Component Material Manufacturer Mfg. Color Name/No.
Toilet/SHWR –
MD E107A,
Toilet/SHWR –
MD E145A,
Toilet/SHWR
E154A
ADA Transfer Shower Acrylic
(one-piece)
Aqua Bath Co. C4136TD-FUS 3/4”
(Verify Orientation with
Drawings)
C. SECTION 10 26 00, WALL AND DOOR PROTECTION
Item Material Manufacturer Mfg. Color Name/No.
Corner Guards (CG-1) Vinyl
InPro Corporation
Model #150
3” wing, 90 degree
Color: #0104 Antique White
Corner Guards (CG-2)-
End wall
Vinyl
Model #160D
2” wing, End wall Protector
09 06 00 - 22
Color: #0104 Antique White
Wall Guard (WG-1)
Vinyl
700 Wall Guard
7 7/8” high
Color: #0104 Antique White
Wall Guard (WG-2) Vinyl
1600 Wall Guard
6” high
Color: #0104 Antique White
Wall Guard (WG-3) Vinyl InPro Corporation 1400 wall guard
4” high
Color: #0104 Antique White
Hand Rail (HR-1) Vinyl InPro Corporation INPRO, 2000 Handrail Color #0119
Pepperdust
Chair Rail (CR-1) Wood (Maple) Stain Grade 1x Wood Trim with
Eased Edges, Stain Color: TBD
Crash Rail (CR-2) Vinyl Inpro 200 Wall Guard Crash Rail
Wall Protection (WP-1) Vinyl Wolf Gordon Rampart (Impact Resistant)/Ennis
– Color: #5586 STONE
Wall Protection (WP-2) Vinyl Wolf Gordon Rampart (Impact Resistant)/Ennis
– Color: #5053 ANTIMONY
Wall Protection (WP-3) Vinyl (Rigid) InPro Corporation .040"; COLOR #0104 ANTIQUE WHITE
Wall Protection (WP-4) Vinyl (Rigid) InPro Corporation .040"; COLOR #660 SAGE GREEN
Top Caps (TC-1) Vinyl Wolf Gordon Top Vinyl Cap – WC-98-10
(10’ length)
Color: TBD by Architect
D. SECTION 10 28 00, TOILET, BATH AND LAUNDRY ACCESSORIES
Item Material/Finish Manufacturer Mfg. Number
09 06 00 - 23
Toilet Tissue Dispenser
(TTD1)
Plastic Bay West Silhouette Dubl-Serv OptiCore
Dispenser, #BW80200
Paper Towel Dispenser
(PTD1)
Plastic Bay West Silhouette OptiServ Hands Free
Disp-Black, #BW86500
Soap Dispenser
(SD1)
Plastic Steris Acute/Kare #1307Q5
Hand Sanitizer (HS1) Plastic Skilcraft #1049-06
Mirror (MR1) Stainless Steel Bobrick B-165 1830, 18” x 30”
Mirror (MR2) Stainless Steel Bobrick B-166 1830, 18” x 30”
Mirror (MR3) Stainless Steel American Standard 0600, 18” x 30”
Baby Changing Station (DCS1) Stainless Steel/Poly. Koala Kare KB110-SSWM
Crutch Hook (Inside
Equipment Room Cabinet)
Stainless Steel with
Satin Finish
Bradley Model 9992
Utility Shelf with Mop/Broom
Holders and Rag Hooks
Stainless Steel with
Satin Finish
Bobrick B-224
Clothes Hooks (CH) Stainless Steel with
Satin Finish
Bobrick B-6707
Recessed Specimen Pass-
Through Cabinet
Stainless Steel with
Satin Finish
Bobrick B-505
Infection Prevention Center
(PPE)
Stainless Steel Peter Pepper
Products
ICX-1, 22¾”w x 18”h x 4”d
E. SECTION 10 13 00, EXTERIOR DIRECTORIES / SECTION 10 14 00, EXTERIOR SIGNAGE
Component Finish Manufacturer Mfg. Color Name/No.
See Signage Specification Section 101400
09 06 00 - 24
F. SECTION 10 13 00, INTERIOR DIRECTORIES / 10 14 00, INTERIOR SIGNAGE
Sign Type Component Manufacturer Mfg. Color Name/No.
See Signage Specification Section 101400
G. SECTION 10 44 13, FIRE EXTNGUISHER CABINETS
Component Material Finish
Larsen’s Mfg./Cabinet Door Stainless Steel #2409-6R Semi-Rec. 2 1/2”
09 06 00 - 25
2.11 DIVISION 11 – EQUIPMENT
A. SECTION 11 12 00, PARKING CONTROL EQUIPMENT
Component Material Manufacturer Mfg. Color Name/No.
Gate and Arm - Nice- HiSecurity StrongArm 20
2.12 DIVISION 12- FURNISHINGS
A. SECTION 12 36 00, COUNTERTOPS
Type Finish/Color Manufacturer
(QT-1) Quartz Countertop See Section 06 20 00 Finish Carpentry
(SSM-1) Solid Surface
Countertop
See Section 06 20 00 Finish Carpentry
(PL-2) Plastic Laminate
Countertop
See Section 06 20 00 Finish Carpentry
B. SECTION 12 24 00, WINDOW SHADES
Component Material Manufacturer Mfg. Color Name/No.
Manual Flex Shades clear anodized (standard) Draper Techmatic Roller Shade.
Manually operated with a stainless-steel bead chain clutch
Fabric Sheerweave Fabric Phifer Opaque: SB9020 Ivory by
Phifer, 5% openness
Translucent: White/Bone
09 06 00 - 26
2.13 2.12 DIVISION 14 – CONVEYING EQUIPMENT
A. A. SECTION 14 92 00, PNEUMATIC TUBE SYSTEM
Manufacturer Material Finish/Color
Swisslog Exposed Metal Paint/Manuf. Standard
09 06 00 - 27
2.15 DIVISION 22 - PLUMBING
A. SECTION 22 40 00, PLUMBING FIXTURES
Item Color
Water Closet See Plumbing Drawings
Urinal See Plumbing Drawings
Bathtubs N/A
Lavatories See Plumbing Drawings
Service Sink Corner See Plumbing Drawings
Service Sink See Plumbing Drawings
Clinic Service Sink See Plumbing Drawings
Plaster Sink N/A
Laundry Tub N/A
2.16 DIVISON 26 - ELECTRICAL
A. SECTION 26 51 00, INTERIOR LIGHTING
Fixture Type Exterior Finish Color
See Electrical Drawing Manufacturer’s Standard All White U.N.O.
B. SECTION 26 56 00, EXTERIOR LIGHTING
Type and Component Exterior Finish Manufacturer Mfg. Name/No.
See Electrical Drawings See Electrical Drawings See Electrical Drawings See Electrical Drawings
09 06 00 - 28
PART 3 - EXECUTION
3.1 FINISH SCHEDULES & MISCELLANEOUS ABBREVIATIONS
FINISH SCHEDULE & MISCELLANEOUS ABBREVIATIONS
Term Abbreviation
Accordion Folding
Partition
AFP
Acoustical Ceiling APC
Acoustical Ceiling, Special Faced
APC (SP)
Acoustical Wall Panel AWP
Acoustical Wall
Treatment
AWT
Acoustical Wallcovering AWF
Anodized Aluminum
Colored
AAC
Anodized Aluminum
Natural Finish
AA
Carpet CP
Carpet Module Tile CPT
Ceramic Glazed Facing CGFB
Brick
Ceramic Mosaic Tile FTCT
Concrete C
Concrete Masonry Unit CMU
Divider Strips Marble DS MB
Divider Panel DP
Epoxy Coating EC
Epoxy Resin Flooring ERF
Existing E
Exterior EXT
Exterior Finish System EFS
Exterior Paint EXT-P
Epoxy Paint EXP
Fabric Wallcovering WF
Facing Tile SCT
Fluorocarbon FC
Folding Panel Partition FP
Gypsum Wallboard GWB
High Glazed Coating SC
Linear Metal Ceiling LMC
Linear Wood Ceiling LWC
09 06 00 - 29
Luxury Vinyl Tile LVT
Marble MB
Material MAT
Mortar M
Multi-Color Coating MC
Moisture Remediation
Coating
MRC
Natural Finish NF
Paint P
Paver Tile PVT
Perforated Metal Facing
(Tile or Panels)
PMF
Plaster PL
Plaster High Strength HSPL
Plaster Keene Cement KC
Plastic Laminate HPDL
Polypropylene Fabric
Wallcovering
PFW
Quarry Tile QT
Resinous Flooring RES
Resinous Wall Base RES-B
Resinous Wall Covering RES-W
Resilient Stair Tread RST
Rubber Base RB
Rubber Tile Flooring RT
Spandrel Glass SLG
Stain ST
Stone Flooring SF
Structural Clay SC
Suspension Decorative
Grids
SDG
Textured Metal Ceiling
Panel
TMC
Veneer Plaster VP
Vinyl Coated Fabric
Wallcovering
W
Vinyl Composition Tile VCT
Vinyl Sheet Flooring VSF
Vinyl Wall Base WB
Vinyl Sheet Flooring
(Welded Seams)
WSF
Wood WD
09 06 00 - 30
3.2 FINISH SCHEDULE SYMBOLS
Symbol Definition
** Same finish as adjoining walls
- No color required
E- Existing
XX To match existing
EFTR Existing finish to remain
RM Remove
3.3 ROOM FINISH SCHEDULE
A. Match adjoining or existing similar surfaces colors, textures or patterns where disturbed or damaged by alterations or new work when not scheduled.
B. ROOM FINISH SCHEDULE
SEE FINISH SCHEDULE ON DRAWING 1-AS-903
--- E N D---
06-01-18
09 22 16 - 1
SECTION 09 22 16
NON-STRUCTURAL METAL FRAMING
This section specifies steel studs wall systems, shaft wall systems, ceiling or soffit suspended or furred framing, wall furring, fasteners, and accessories for the screw attachment of gypsum board, plaster bases or other building boards.
1.2 RELATED WORK
A. Load bearing framing: Section 05 40 00, COLD-FORMED METAL FRAMING.
B. Support for wall mounted items: Section 05 50 00, METAL FABRICATIONS.
D. Ceiling suspension systems for acoustical tile or panels and lay in gypsum board panels: Section 09 51 00, ACOUSTICAL CEILINGS Section 09
29 00, GYPSUM BOARD.
1.3 TERMINOLOGY
A. Description of terms shall be in accordance with ASTM C754, ASTM C11, ASTM C841 and as specified.
B. Underside of Structure Overhead: In spaces where steel trusses or bar joists are shown, the underside of structure overhead shall be the underside of the floor or roof construction supported by beams, trusses, or bar joists. In interstitial spaces with walk-on floors the underside of the walk-on floor is the underside of structure overhead.
C. Thickness of steel specified is the minimum bare (uncoated) steel thickness.
1.4 SUBMITTALS
A. Submit in accordance with Section 01 33 23, SHOP DRAWINGS, PRODUCT
DATA, AND SAMPLES.
B. Manufacturer's Literature and Data:
1. Studs, runners and accessories.
2. Hanger inserts.
3. Channels (Rolled steel).
4. Furring channels.
5. Screws, clips and other fasteners.
C. Shop Drawings:
1. Typical ceiling suspension system.
09 22 16 - 2
2. Typical metal stud and furring construction system including details around openings and corner details.
3. Typical shaft wall assembly
4. Typical fire rated assembly and column fireproofing showing details of construction same as that used in fire rating test.
D. Test Results: Fire rating test designation, each fire rating required for each assembly.
1.5 DELIVERY, IDENTIFICATION, HANDLING AND STORAGE
In accordance with the requirements of ASTM C754.
1.6 APPLICABLE PUBLICATIONS
A. The publications listed below form a part of this specification to the extent referenced. The publications are referenced in the text by the basic designation only.
B. American Society For Testing And Materials (ASTM)
A641-09.................Zinc-Coated (Galvanized) Carbon Steel Wire
A653/653M-11............Specification for Steel Sheet, Zinc Coated
(Galvanized) or Zinc-Iron Alloy-Coated
(Galvannealed) by Hot-Dip Process.
C11-10..................Terminology Relating to Gypsum and Related
Building Materials and Systems
C635-07.................Manufacture, Performance, and Testing of Metal
Suspension System for Acoustical Tile and
Lay-in Panel Ceilings
C636-08.................Installation of Metal Ceiling Suspension
Systems for Acoustical Tile and Lay-in Panels
C645-09.................Non-Structural Steel Framing Members
C754-11.................Installation of Steel Framing Members to
Receive Screw-Attached Gypsum Panel Products
C841-03(R2008)..........Installation of Interior Lathing and Furring
C954-10.................Steel Drill Screws for the Application of
Gypsum Panel Products or Metal Plaster Bases to
Steel Studs from 0.033 in. (0.84 mm) to 0.112
in. (2.84 mm) in Thickness
E580-11.................Application of Ceiling Suspension Systems for
Acoustical Tile and Lay-in Panels in Areas
Requiring Moderate Seismic Restraint.
09 22 16 - 3
PART 2 - PRODUCTS
2.1 PROTECTIVE COATING
Galvanize steel studs, runners (track), rigid (hat section) furring channels, "Z" shaped furring channels, and resilient furring channels, with coating designation of G40 or equivalent.
2.2 STEEL STUDS AND RUNNERS (TRACK)
A. ASTM C645, modified for thickness specified and sizes as shown.
1. Use C 645 steel, 0.75 mm (0.0296-inch) minimum base-metal (30 mil).
2. Runners same thickness as studs.
3. Exception: Members that can show certified third party testing with gypsum board in accordance with ICC ES AC86 (Approved May 2012) need not meet the minimum thickness limitation or minimum section properties set forth in ASTM C 645. The submission of an evaluation report is acceptable to show conformance to this requirement. Use C
645 steel, 0.48mm (0.019 inch) minimum base-metal (19 mil).
B. Provide not less than two cutouts in web of each stud, approximately
300 mm (12 inches) from each end, and intermediate cutouts on approximately 600 mm (24-inch) centers.
C. Doubled studs for openings and studs for supporting concrete backer-board.
D. Studs 3600 mm (12 feet) or less in length shall be in one piece.
E. Shaft Wall Framing:
1. Conform to rated wall construction.
2. C-H Studs or C-T Studs.
3. E Studs.
4. J Runners.
5. Steel Jamb-Strut.
2.3 FURRING CHANNELS
A. Rigid furring channels (hat shape): ASTM C645.
B. Resilient furring channels:
1. Not less than 0.45 mm (0.0179-inch) thick bare metal.
2. Semi-hat shape, only one flange for anchorage with channel web leg slotted on anchorage side, channel web leg on other side stiffens fastener surface but shall not contact anchorage surface other channel leg is attached to.
09 22 16 - 4
C. "Z" Furring Channels:
1. Not less than 0.45 mm (0.0179-inch)-thick base metal, with 32 mm
(1-1/4 inch) and 19 mm (3/4-inch) flanges.
2. Web furring depth to suit thickness of insulation.
D. Rolled Steel Channels: ASTM C754, cold rolled; or, ASTM C841, cold rolled.
2.4 FASTENERS, CLIPS, AND OTHER METAL ACCESSORIES
A. ASTM C754, except as otherwise specified.
B. For fire rated construction: Type and size same as used in fire rating test.
C. Fasteners for steel studs thicker than 0.84 mm (0.033-inch) thick. Use
ASTM C954 steel drill screws of size and type recommended by the manufacturer of the material being fastened.
D. Clips: ASTM C841 (paragraph 6.11), manufacturer’s standard items.
Clips used in lieu of tie wire shall have holding power equivalent to that provided by the tie wire for the specific application.
E. Concrete ceiling hanger inserts (anchorage for hanger wire and hanger straps): Steel, zinc-coated (galvanized), manufacturers standard items, designed to support twice the hanger loads imposed and the type of hanger used.
F. Tie Wire and Hanger Wire:
1. ASTM A641, soft temper, Class 1 coating.
2. Gage (diameter) as specified in ASTM C754 or ASTM C841.
G. Attachments for Wall Furring:
1. Manufacturers standard items fabricated from zinc-coated (galvanized) steel sheet.
2. For concrete or masonry walls: Metal slots with adjustable inserts or adjustable wall furring brackets. Spacers may be fabricated from 1 mm
(0.0396-inch) thick galvanized steel with corrugated edges.
H. Power Actuated Fasteners: Type and size as recommended by the manufacturer of the material being fastened.
2.5 SUSPENDED CEILING SYSTEM FOR GYPSUM BOARD (OPTION)
A. Conform to ASTM C635, heavy duty, with not less than 35 mm (1-3/8 inch) wide knurled capped flange face designed for screw attachment of gypsum board.
09 22 16 - 5
B. Wall track channel with 35 mm (1-3/8 inch) wide flange.
PART 3 - EXECUTION
3.1 INSTALLATION CRITERIA
A. Where fire rated construction is required for walls, partitions, columns, beams and floor-ceiling assemblies, the construction shall be same as that used in fire rating test.
B. Construction requirements for fire rated assemblies and materials shall be as shown and specified, the provisions of the Scope paragraph (1.2) of ASTM C754 and ASTM C841 regarding details of construction shall not apply.
3.2 INSTALLING STUDS
A. Install studs in accordance with ASTM C754, except as otherwise shown or specified.
B. Space studs not more than 610 mm (24 inches) on center.
C. Cut studs 6 mm to 9 mm (1/4 to 3/8-inch) less than floor to underside of structure overhead when extended to underside of structure overhead.
D. Where studs are shown to terminate above suspended ceilings, provide bracing as shown or extend studs to underside of structure overhead.
E. Extend studs to underside of structure overhead for fire, rated partitions, smoke partitions, shafts, and sound rated partitions and insulated exterior wall furring.
F. Where shown, studs may terminate at ceiling as shown.
G. Openings:
1. Frame jambs of openings in stud partitions and furring with two studs placed back to back or as shown.
2. Fasten back to back studs together with 9 mm (3/8-inch) long Type S pan head screws at not less than 600 mm (two feet) on center, staggered along webs.
3. Studs fastened flange to flange shall have splice plates on both sides approximately 50 X 75 mm (2 by 3 inches) screwed to each stud with two screws in each stud. Locate splice plates at 600 mm (24 inches) on center between runner tracks.
H. Fastening Studs:
1. Fasten studs located adjacent to partition intersections, corners and studs at jambs of openings to flange of runner tracks with two screws through each end of each stud and flange of runner.
09 22 16 - 6
2. Do not fasten studs to top runner track when studs extend to underside of structure overhead.
I. Chase Wall Partitions:
1. Locate cross braces for chase wall partitions to permit the installation of pipes, conduits, carriers and similar items.
2. Use studs or runners as cross bracing not less than 63 mm (2-1/2 inches wide).
J. Form building seismic or expansion joints with double studs back to back spaced 75 mm (three inches) apart plus the width of the seismic or expansion joint.
K. Form control joint, with double studs spaced 13 mm (1/2-inch) apart.
3.3 INSTALLING WALL FURRING FOR FINISH APPLIED TO ONE SIDE ONLY
A. In accordance with ASTM C754, or ASTM C841 except as otherwise specified or shown.
B. Wall furring-Stud System:
1. Framed with 63 mm (2-1/2 inch) or narrower studs, 600 mm (24 inches) on center.
2. Brace as specified in ASTM C754 for Wall Furring-Stud System or brace with sections or runners or studs placed horizontally at not less than three foot vertical intervals on side without finish.
3. Securely fasten braces to each stud with two Type S pan head screws at each bearing.
C. Direct attachment to masonry or concrete; rigid channels or "Z" channels:
1. Install rigid (hat section) furring channels at 600 mm (24 inches) on center, horizontally or vertically.
2. Install "Z" furring channels vertically spaced not more than 600 mm
(24 inches) on center.
3. At corners where rigid furring channels are positioned horizontally, provide mitered joints in furring channels.
4. Ends of spliced furring channels shall be nested not less than
200 mm (8 inches).
5. Fasten furring channels to walls with power-actuated drive pins or hardened steel concrete nails. Where channels are spliced, provide two fasteners in each flange.
09 22 16 - 7
6. Locate furring channels at interior and exterior corners in accordance with wall finish material manufacturers printed erection instructions. Locate "Z" channels within 100 mm (4 inches) of corner.
D. Installing Wall Furring-Bracket System: Space furring channels not more than 400 mm (16 inches) on center.
3.4 INSTALLING SUPPORTS REQUIRED BY OTHER TRADES
A. Provide for attachment and support of electrical outlets, plumbing, laboratory or heating fixtures, recessed type plumbing fixture accessories, access panel frames, wall bumpers, wood seats, toilet stall partitions, dressing booth partitions, urinal screens, chalkboards, tackboards, wall-hung casework, handrail brackets, recessed fire extinguisher cabinets and other items like auto door buttons and auto door operators supported by stud construction.
B. Provide additional studs where required. Install metal backing plates, or special metal shapes as required, securely fastened to metal studs.
3.5 INSTALLING SHAFT WALL SYSTEM
A. Conform to UL Design No. U438 for two-hour fire rating.
B. Position J runners at floor and ceiling with the short leg toward finish side of wall. Securely attach runners to structural supports with power driven fasteners at both ends and 600 mm (24 inches) on center.
C. After liner panels have been erected, cut C-H studs and E studs, from 9 mm (3/8-inch) to not more than 13 mm (1/2-inch) less than floor-to-ceiling height. Install C-H studs between liner panels with liner panels inserted in the groove.
D. Install full-length steel E studs over shaft wall line at intersections, corners, hinged door jambs, columns, and both sides of closure panels.
E. Suitably frame all openings to maintain structural support for wall:
1. Provide necessary liner fillers and shims to conform to label frame requirements.
2. Frame openings cut within a liner panel with E studs around perimeter.
3. Frame openings with vertical E studs at jambs, horizontal J runner at head and sill.
09 22 16 - 8
F. Elevator Shafts:
1. Frame elevator door frames with 0.87 mm (0.0341-inch) thick J strut or J stud jambs having 75 mm (three-inch) long legs on the shaft side.
2. Protrusions including fasteners other than flange of shaft wall framing system or offsets from vertical alignments more than 3 mm
(1/8-inch) are not permitted unless shown.
3. Align shaft walls for plumb vertical flush alignment from top to bottom of shaft.
3.6 INSTALLING FURRED AND SUSPENDED CEILINGS OR SOFFITS
A. Install furred and suspended ceilings or soffits in accordance with
ASTM C754 or ASTM C841 except as otherwise specified or shown for screw attached gypsum board ceilings and for plaster ceilings or soffits.
1. Space framing at 400 mm (16-inch) centers for metal lath anchorage.
2. Space framing at 600 mm (24-inch) centers for gypsum board anchorage.
B. New exposed concrete slabs:
1. Use metal inserts required for attachment and support of hangers or hanger wires with tied wire loops for embedding in concrete.
2. Furnish for installation under Division 3, CONCRETE.
3. Suspended ceilings under concrete rib construction shall have runner channels at right angles to ribs and be supported from ribs with hangers at ends and at 1200 mm (48-inch) maximum intervals along channels. Stagger hangers at alternate channels.
C. Concrete slabs on steel decking composite construction:
1. Use pull down tabs when available.
2. Use power activated fasteners when direct attachment to structural framing can not be accomplished.
D. Where bar joists or beams are more than 1200 mm (48 inches) apart, provide intermediate hangers so that spacing between supports does not exceed 1200 mm (48 inches). Use clips, bolts, or wire ties for direct attachment to steel framing.
E. Existing concrete construction exposed or concrete on steel decking:
1. Use power actuated fasteners either eye pin, threaded studs or drive pins for type of hanger attachment required.
09 22 16 - 9
2. Install fasteners at approximate mid height of concrete beams or joists. Do not install in bottom of beams or joists.
F. Steel decking without concrete topping:
1. Do not fasten to steel decking 0.76 mm (0.0299-inch) or thinner.
2. Toggle bolt to decking 0.9 mm (0.0359-inch) or thicker only where anchorage to steel framing is not possible.
G. Installing suspended ceiling system for gypsum board (ASTM C635
Option):
1. Install only for ceilings to receive screw attached gypsum board.
2. Install in accordance with ASTM C636.
a. Install main runners spaced 1200 mm (48 inches) on center.
b. Install 1200 mm (four foot) tees not over 600 mm (24 inches) on center; locate for edge support of gypsum board.
c. Install wall track channel at perimeter.
H. Installing Ceiling Bracing System:
1. Construct bracing of 38 mm (1-1/2 inch) channels for lengths up to
2400 mm (8 feet) and 50 mm (2 inch) channels for lengths over 2400 mm (8 feet) with ends bent to form surfaces for anchorage to carrying channels and overhead construction. Lap channels not less than 600 mm (2 feet) at midpoint back to back. Screw or bolt lap together with two fasteners.
2. Install bracing at an approximate 45 degree angle to carrying channels and structure overhead; secure as specified to structure overhead with two fasteners and to carrying channels with two fasteners or wire ties.
3. Brace suspended ceiling or soffit framing in seismic areas in accordance with ASTM E580.
3.7 TOLERANCES
A. Fastening surface for application of subsequent materials shall not vary more than 3 mm (1/8-inch) from the layout line.
B. Plumb and align vertical members within 3 mm (1/8-inch.)
C. Level or align ceilings within 3 mm (1/8-inch.)
04-01-20
09 29 00 - 1
SECTION 09 29 00
GYPSUM BOARD
This section specifies installation and finishing of gypsum board.
1.2 RELATED WORK
A. Installation of steel framing members for walls, partitions, furring, soffits, and ceilings: Section 05 40 00, COLD-FORMED METAL FRAMING, and
Section 09 22 16, NON-STRUCTURAL METAL FRAMING.
B. Sound deadening board: Section 07 21 13, THERMAL INSULATION.
C. Acoustical Sealants: Section 07 92 00, JOINT SEALANTS.
D. Tile Backer Board: Section 093013 CERAMIC/PORCELAIN…
This is the start of the file's text. The full file is on GovTribe.