Division 8 Spec - Doors and windows.pdf

PDF 1 MB Posted

Attached to
Z1DA--MINOR-CONST 528-809 NEW EMERGENCY DEPARTMENT ALBANY VAMC
Solicitation number
36C24224R0071
Issued by

About this file

This document appears to be a solicitation for a federal contract opportunity to construct a new Emergency Department at the Samuel S. Stratton VA Medical Center in Albany, NY. The key details are:

The project involves demolition, site work, construction of a new Emergency Department addition to connect to the main hospital, and related work including mechanical, plumbing, electrical, fire protection, medical gas, and low-voltage systems. The period of performance is 550 calendar days. The contractor must utilize the VA's Autodesk Build construction management platform for project collaboration and documentation. A competent full-time superintendent is required. Key milestones include completing commissioning prior to training VA staff and performing a final inspection/punch list. The solicitation was issued by the Department of Veterans Affairs, Veterans Health Administration, VISN 2. Offerors must comply with all requirements outlined in the Statement of Work.

View the file

Other files

File Type Posted
36C24224R0071 0008.docx DOCX document
36C24224R0071 0007.docx DOCX document
1-SE-701.pdf PDF
36C24224R0071 0006.docx DOCX document
SK-ES-802.1.pdf PDF
36C24224R0071 0005.docx DOCX document
Albany VA ED Walk Through Sign in List.pdf PDF
Albany VAMC Geotech Report for New ED.pdf PDF
087100 Door hardware SET 14.pdf PDF
071352 Modified Bituminous Sheet Waterproofing.pdf PDF
Stratton ED_103177_SET.pdf PDF
Q40 - 1-HA-100.pdf PDF
36C24224R0071 0004.docx DOCX document
055000 Metal Fabrications.pdf PDF
Subbasement Structural Originals.pdf PDF
084113 Aluminum Framed Entrances and Storefront8-18-22.pdf PDF
088000 Glazing-8-18-22.pdf PDF
36C24224R0071 0003.docx DOCX document
36C24224R0071 0002.docx DOCX document
19-181 100 Specs VA 528-809 Volume I.pdf PDF
19-181 100 Specs VA 528-809 Volume II.pdf PDF
EXHIBIT B - Sample Transmittal Letter for Past Performance Evaluation Questionnaire.docx DOCX document
36C24224R0071 0001.docx DOCX document
072400 EIFS.pdf PDF
EXHIBIT C - Past Performance Questionnaire.docx DOCX document
divisions 27-28 Specs.pdf PDF
1-22-24 - VA STRATTON NEW EMERGENCY DEPT SS_Part1.pdf PDF
2022-02-22 VA 528-809 Submittal Register-Divisions 01 - 34 FE.xlsx XLSX spreadsheet
Division 3 specs - concrete.pdf PDF
000115 List of Drawing Sheets.pdf PDF
Division 26 Specs - electrical.pdf PDF
Division 23 Specs - HVAC.pdf PDF
Division 7 Specs - Thermal and Moisture Protection.pdf PDF
1-22-24 - VA STRATTON NEW EMERGENCY DEPT SS_Part7.pdf PDF
Division 5 specs - Metals.pdf PDF
1-22-24 - VA STRATTON NEW EMERGENCY DEPT SS_Part8.pdf PDF
1-22-24 - VA STRATTON NEW EMERGENCY DEPT SS_Part10.pdf PDF
1-22-24 - VA STRATTON NEW EMERGENCY DEPT SS_Part2.pdf PDF
000110 TOC.pdf PDF
Division 9 specs - Finishes.pdf PDF
WD Albany NY20240002 07-12-2024.docx DOCX document
Division 6 Specs - wood and plastics.pdf PDF
Division 4 Specs - Masonry.pdf PDF
Division 2 specs - existing conditions.pdf PDF
Division 21-22 Specs.pdf PDF
1-22-24 - VA STRATTON NEW EMERGENCY DEPT SS_Part4.pdf PDF
Divisions 31-34 Specs.pdf PDF
1-22-24 - VA STRATTON NEW EMERGENCY DEPT SS_Part5.pdf PDF
1-22-24 - VA STRATTON NEW EMERGENCY DEPT SS_Part11.pdf PDF
1-22-24 - VA STRATTON NEW EMERGENCY DEPT SS_Part9.pdf PDF
Show 40 more

Latest 50 of 56 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SAMUEL S. STRATTON VA MEDICAL CENTER

DESIGN NEW EMERGENCY DEPARTMENT

VA PROJECT NO. 528-809

01-01-21

08 11 13 - 1

SECTION 08 11 13

HOLLOW METAL DOORS AND FRAMES

PART 1 - GENERAL

1.1 SUMMARY

A. Section Includes:

1. Hollow metal doors hung in hollow metal frames at interior and exterior locations.

2. Hollow metal door frames for wood doors at interior locations.

3. Glazed openings in hollow metal doors.

1.2 RELATED WORK

A. Section 05 50 00, METAL FABRICATIONS: Frames fabricated of structural steel.

B. Section 08 34 53, SECURITY DOORS AND FRAMES: Forced Entry and Ballistic

Resistant doors.

C. Section 08 41 13, ALUMINUM-FRAMED ENTRANCES AND STOREFRONTS: Aluminum frames entrance work.

D. Section 08 71 00, DOOR HARDWARE: Door Hardware:

E. Section 08 80 00, GLAZING: Glazing.

F. Card Readers and Biometric Devices: Section 28 13 00, PHYSICAL ACCESS

CONTROL SYSTEM.

G. Intrusion Alarm: Section 28 16 00, INTRUSION DETECTION SYSTEM.

H. Security Monitors: Section 28 23 00, VIDEO SURVEILLANCE.

1.3 APPLICABLE PUBLICATIONS

A. Comply with references to extent specified in this section.

B. American National Standard Institute (ANSI):

A250.8-2014.............Standard Steel Doors and Frames

C. ASTM International (ASTM):

A240/A240M-15b..........Chromium and Chromium-Nickel Stainless Steel

Plate, Sheet, and Strip for Pressure Vessels and for General Applications

A653/A653M-15...........Steel Sheet, Zinc-Coated (Galvanized) or

Zinc-Iron Alloy-Coated (Galvannealed) by the

Hot-Dip

A1008/A1008M-15.........Steel, Sheet, Cold-Rolled, Carbon, Structural, High Strength Low Alloy and High Strength Low

08 11 13 - 2

Alloy with Improved Formability, Solution

Hardened, and Bake Hardenable

B209-14.................Aluminum and Aluminum-Alloy Sheet and Plate

B209M-14................Aluminum and Aluminum-Alloy Sheet and Plate

(Metric)

B221-14.................Aluminum and Aluminum-Alloy Extruded Bars, Rods, Wire, Profiles, and Tubes

B221M-13................Aluminum and Aluminum-Alloy Extruded Bars, Rods, Wire, Profiles, and Tubes (Metric)

D3656/D3656M-13.........Insect Screening and Louver Cloth Woven from

Vinyl Coated Glass Yarns

E90-09..................Laboratory Measurement of Airborne Sound

Transmission Loss of Building Partitions and

Elements

D. Federal Specifications (Fed. Spec.):

L-S-125B................Screening, Insect, Nonmetallic

E. Master Painters Institute (MPI):

No. 18..................Primer, Zinc Rich, Organic

F. National Association of Architectural Metal Manufacturers (NAAMM):

AMP 500-06..............Metal Finishes Manual

G. National Fire Protection Association (NFPA):

80-16...................Fire Doors and Other Opening Protectives

H. UL LLC (UL):

10C-09..................Positive Pressure Fire Tests of Door Assemblies

1784-15.................Air Leakage Tests of Door Assemblies and Other

Opening Protectives

I. Department of Veterans Affairs

VA Physical Security and Resiliency Design Manual October 1, 2020

1.4 SUBMITTALS

A. Submittal Procedures: Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES.

B. Submittal Drawings:

1. Show size, configuration, and fabrication and installation details.

C. Manufacturer's Literature and Data:

1. Description of each product.

08 11 13 - 3

2. Include schedule showing each door and frame requirements, fire label, -and smoke control label for openings.

3. Installation instructions.

D. Test reports: Certify each product complies with specifications.

1. Sound rated door.

E. Qualifications: Substantiate qualifications comply with specifications.

1. Manufacturer with project experience list .

F. Blast Design Calculations.

1. Submit calculations for review and approval prepared by qualified blast consultant, with a minimum of 5 years of experience in design of blast resistant systems, verifying door assembly including anchors comply with specified blast resistance performance. The magnitudes of the design threats W1, W2 and GP1, GP2 are defined in the Physical Security and Resiliency Design Standards Data

Definitions which is a document separate from the referenced VA

Security and Resiliency Design Manual. The Physical Security and

Resiliency Design Standards Data Definitions are provided on a need-to-know basis by the structural blast specialist performing the blast design on VA projects. It is the responsibility of the delegated engineer responsible for the design of blast resistant doors to request and obtain the Physical Security and Resiliency

Design Data Standard Data Definitions from the VA Office of

Construction and Facilities Management (CFM). Any associated delays or increased costs due to failure to obtain this information will be borne by the contractor.

1.5 QUALITY ASSURANCE

A. Manufacturer Qualifications:

1. Regularly manufactures specified products.

2. Manufactured specified products with satisfactory service on five similar installations for minimum five years.

a. Project Experience List: Provide contact names and addresses for completed projects.

1.6 DELIVERY

A. Fasten temporary steel spreaders across the bottom of each door frame before shipment.

B. Deliver products in manufacturer's original sealed packaging.

08 11 13 - 4

C. Mark packaging, legibly. Indicate manufacturer's name or brand, type, production run number, and manufacture date.

D. Before installation, return or dispose of products within distorted, damaged, or opened packaging.

1.7 STORAGE AND HANDLING

A. Store products indoors in dry, weathertight, conditioned, facility.

B. Protect products from damage during handling and construction operations.

1.8 WARRANTY

A. Construction Warranty: FAR clause 52.246-21, "Warranty of

Construction."

PART 2 - PRODUCTS

2.1 SYSTEM PERFORMANCE

A. Design hollow metal doors and frames complying with specified performance:

1. Fire Doors and Frames: UL 10C; NFPA 80 labeled.

a. Fire Ratings: See drawings.

2. Stair Doors: Temperature rise rated fire doors.

3. Smoke Control Doors and Frames: UL 1784; NFPA 80 labeled, maximum

0.15424 cubic meter/second/square meter (3.0 cubic feet/minute/square foot) at 24.9 Pa (0.10 inches water gauge) pressure differential.

4. Sound Rated Doors and Frames: Minimum 45 sound transmission class

(STC) when tested according to ASTM E90.

5. Thermal Transmittance: U-value 0.37 U-value), maximum at exterior doors.

6. All doors to receive door closer reinforcement plates, both faces typical all doors.

7. All doors to receive hinge reinforcement, minimum two (2) hinges per door.

8. Blast Resistant Doors: Door, Frame and Anchorage:

a. Standoff Distance: 50 feet (Mission Critical Protected)

b. Design Threat W1 at the standoff distance not to exceed pressure and impulse associated with GP2 threat for Mission Critical

Protected buildings.

08 11 13 - 5

c. Frame Rotation not to exceed L/40 (Mission Critical Protected) while experiencing design level pressure and impulse.

9. Blast Performance Requirements: All exterior metal doors must meet the design requirements for Mission Critical facilities per Section

6.3.3 of the VA Physical Security and Resilience Design Manual

(2020).

a. Exterior metal doors must open towards the exterior of the building, and must have heavy gauge panels (14-gauge minimum) with heavy duty frames and anchorages. The door frames and anchorages must be designed to resist a design blast load of 13.5 psi peak reflected pressure and 51 psi-msec reflected impulse while sustaining deformations no greater than L/40 (or 3 degrees support rotation).

b. Double doors must have a heavy-duty removable vertical mullion.

The vertical mullions and its connections at top and bottom must be designed to withstand the same design blast loads and maximum deformations as the door.

c. Any glazing on exterior metal doors must meet the blast performance requirements stated in Section 088000 of the specifications.

d. Explosive test data, developed by an experienced testing facility approved by the U.S. Government (USG), may be used to supplement the analytical methods where a direct analytical representation is not feasible.

e. Glazing: Glazing shall meet the blast requirements shown in

Specification 08 80 00.

2.2 MATERIALS

A. Sheet Steel: ASTM A1008/A1008M, cold-rolled.

B. Galvanized Sheet Steel: ASTM A653.

C. Aluminum Sheet: ASTM B209M (ASTM B209).

D. Aluminum Extrusions: ASTM B221M (ASTM B221).

2.3 PRODUCTS - GENERAL

A. Basis of Design: Section 09 06 00, SCHEDULE FOR FINISHES.

B. Provide hollow metal doors and frames from one manufacturer.

08 11 13 - 6

2.4 HOLLOW METAL DOORS

A. Hollow Metal Doors: ANSI A250.8; 44 mm (1-3/4 inches) thick. See drawings for sizes and designs.

1. Interior Doors: Level 3 and Physical Performance Level A, extra-heavy duty; Model 2, seamless at all locations unless otherwise noted.

2. Exterior Doors: Level 3 and Physical Performance Level A, extra-heavy duty; Model 2, seamless at all locations unless otherwise noted.

B. Door Faces:

1. Interior Doors: Galvanized sheet steel minimum Z180 or ZF180 (G60 or

A60) coating .

2. Exterior Doors: Galvanized sheet steel minimum Z180 or ZF180 (G60 or

A60) coating .

3. Provide 16 gauge steel door closer reinforcement plates, both faces, typical ALL doors. Factory install plates at interior core faces.

Weld continuous to top channel and face per manufacturer’s requirements. Size as required to secure hardware specified.

4. Provide 16 gauge steel door high frequency hinge reinforcement plates, minimum tw0 (2) hinges per door, typical ALL doors. Factory install plates at interior of door frame. Weld per manufacturer’s requirements. Size as required to secure hardware specified.

C. Door Cores:

1. Interior Doors: Kraft paper honeycomb or vertical steel stiffeners.

2. Exterior Doors: Polystyrene or polyurethane.

3. Fire Doors: Manufacturer's standard complying with specified fire rating performance.

2.5 HOLLOW METAL FRAME

A. Hollow Metal Frames: ANSI A250.8; Knock-down face welded. See drawings for sizes and designs.

1. Provide 16 gauge steel door closer frame reinforcement plates, both faces, typical ALL doors. Factory install plates at interior faces of door head. Weld continuous to faces of frames per manufacturer’s requirements. Size as required to secure hardware specified.

08 11 13 - 7

2. Provide 16 gauge steel door frame high frequency hinge reinforcement plates, minimum tw0 (2) hinges per door, typical ALL doors. Factory install plates at interior of door frame. Weld per manufacturer’s requirements. Size as required to secure hardware specified.

3. Interior Frames:

a. Level 3 Hollow Metal Doors: 1.3 mm (0.053 inch) thick.

b. Wood Doors and Borrowed Lights: 1.0 mm (0.042 inch) 1.3 mm

(0.053 inch) thick.

4. Interior Borrowed Light Frames: 1.3 mm (0.051 inch) thick.

5. Interior Frames for Lead Lined Doors:

a. Openings with Structural Steel Subframe: 1.3 mm (0.053 inch) thick.

b. Lead Lining: See Section 13 49 00, RADIATION PROTECTION.

c. Interior Automatic Operator Door Frames: 1.7 mm (0.067 inch) thick.

d. Exterior Frames:

1) Level 3 Hollow Metal Doors: 1.3 mm (0.053 inch) thick.

B. Frame Materials:

1. Interior Frames: Galvanized sheet steel minimum Z180 or ZF180 (G60 or A60) coating .

2. Exterior Frames: Galvanized sheet steel minimum Z180 or ZF180 (G60 or A60) coating.

2.6 FABRICATION

A. Hardware Preparation: ANSI A250.8; for hardware specified in Section

08 71 00, DOOR HARDWARE.

B. Hollow Metal Door Fabrication:

1. Close top edge of exterior doors flush and seal to prevent water intrusion.

2. Fill spaces between vertical steel stiffeners with insulation.

C. Fire and Smoke Control Doors:

1. Close top and vertical edges flush.

2. Apply steel astragal to active leaf at pair and double egress doors.

a. Exception: Where vertical rod exit devices are specified for both leaves swinging in same direction.

3. Fire and Smoke Control Door Clearances: NFPA 80.

D. Custom Metal Hollow Doors:

08 11 13 - 8

1. Provide custom hollow metal doors where nonstandard steel doors are shown on drawings.

a. Provide door sizes, design, materials, construction, gauges, and finish as specified for standard steel doors.

E. Sound Rated Doors:

1. Seals: Integral spring type automatic door bottom seal.

2. Fabricate vision panel cutouts and frames to receive double glazing as shown on drawings.

F. Detention Doors:

1. Vision panels:

a. Weld 3 mm (1/8 inch) thick steel channel reinforcements around cut-outs in doors to accommodate vision lights.

b. Fabricate glazing stops on room side of doors, of 3 mm (1/8 inch) thick steel sheets mitered and welded at corners, and continuously welded both sides into doors.

c. Fabricate glazing bead for corridor side of doors of 9 mm

(3/8 inch) by 19 mm (3/4 inch) steel bar, miter and weld at the corners, and fasten to doors with 6 mm (1/4 inch) countersunk screws near corners and centers of both sides of opening.

1) Back-up screw holes with 3 mm (1/8 inch) thick reinforcements or weld nuts to back of frames to receive screws.

d. Size rabbet for safety glass and glazing cushions specified.

G. Hollow Metal Frame Fabrication:

1. Fasten mortar guards to back of hardware reinforcements, except on lead-lined frames.

2. Concealed Closers in Head Frame: Provide 1 mm (0.042 inch) thick steel removable stop sections for access to concealed face plates and control valves, except when cover plates are furnished with closer.

3. Terminated Stops: ANSI A250.8.

4. Borrowed Light and Panel Opening Frames:

a. Provide integral stop on exterior, corridor, or secure side of door.

b. Design rabbet width and depth to receive glazing material or panel shown on drawings.

5. Frame Anchors:

08 11 13 - 9

a. Floor anchors:

1) Provide extension type floor anchors to compensate for depth of floor fills.

2) Provide 1.3 mm (0.053 inch) thick steel clip angles welded to jamb and drilled to receive floor fasteners.

3) Provide 50 mm by 50 mm by 9 mm (2 inch by 2 inch by 3/8 inch) clip angle for lead lined frames, drilled for floor fasteners.

4) Provide mullion 2.3 mm (0.093 inch) thick steel channel anchors, drilled for two floor fasteners and frame anchor screws.

5) Provide continuous 1 mm (0.042 inch) thick steel rough bucks drilled for floor fasteners and frame anchor screws for sill sections.

a) Space floor bolts50 mm (24 inches) on center.

b. Jamb anchors:

1) Place anchors on jambs:

a) Near top and bottom of each frame.

b) At intermediate points at maximum 600 mm (24 inches) spacing.

2) Form jamb anchors from steel minimum 1 mm (0.042 inch) thick.

3) Anchors set in masonry: Provide adjustable anchors designed for friction fit against frame and extended into masonry minimum 250 mm (10 inches). Provide one of following types:

a) Wire Loop Type: 5 mm (3/16 inch) diameter wire.

b) T-Shape type.

c) Strap and stirrup type: Corrugated or perforated sheet steel.

4) Anchors for stud partitions: Provide tabs for securing anchor to sides of studs. Provide one of the following:

a) Welded type.

b) Lock-in snap-in type.

5) Anchors for frames set in prepared openings:

a) Steel pipe spacers 6 mm (1/4 inch) inside diameter, welded to plate reinforcing at jamb stops, or hat shaped formed strap spacers 50 mm (2 inches) wide, welded to jamb near stop.

08 11 13 - 10

b) Drill jamb stop and strap spacers for 6 mm (1/4 inch) flat head bolts to pass through frame and spacers.

c) Two piece frames: Subframe or rough buck drilled for 6 mm

(1/4 inch) bolts.

6) Anchors for observation windows and other continuous frames set in stud partitions.

a) Weld clip anchors to sills and heads of continuous frames over 1200 mm (4 feet) long.

b) Space maximum 600 mm (24 inches) on centers.

7) Modify frame anchors to fit special frame and wall construction.

8) Provide special anchors where shown on drawings and where required to suit application.

H. Sound Rated Door Frames:

1. Seals: Integral continuous gaskets on frames.

2.7 FINISHES

A. Steel and Galvanized Steel: ANSI A250.8; shop primed.

B. Finish exposed surfaces after fabrication.

C. Aluminum Anodized Finish: NAAMM AMP 500.

1. Clear Anodized Finish: AA-C22A41; Class I Architectural, 0.018 mm

(0.7 mil) thick.

2.8 ACCESSORIES

A. Primers: ANSI A250.8.

B. Barrier Coating: ASTM D1187/D1187M.

C. Welding Materials: AWS D1.1/D1.1M, type to suit application.

D. Clips Connecting Members and Sleeves: Match door faces.

E. Fasteners: Galvanized steel.

1. Metal Framing: Steel drill screws.

2. Masonry and Concrete: Expansion bolts and power actuated drive pins.

F. Anchors: Galvanized steel.

G. Galvanizing Repair Paint: MPI No. 18.

H. Insulation: Unfaced mineral wool.

PART 3 - EXECUTION

3.1 PREPARATION

A. Examine and verify substrate suitability for product installation.

B. Protect existing construction and completed work from damage.

08 11 13 - 11

C. Apply barrier coating to metal surfaces in contact with cementitious materials to minimum 0.7 mm (30 mils) dry film thickness.

3.2 INSTALLATION - GENERAL

A. Install products according to manufacturer's instructions and approved submittal drawings.

1. When manufacturer's instructions deviate from specifications, submit proposed resolution for Contracting Officer's Representative consideration.

2. Install fire doors and frames according to NFPA 80.

3. Install smoke control doors and frames according to NFPA 105.

3.3 FRAME INSTALLATION

A. Apply barrier coating to concealed surfaces of frames built into masonry.

B. Plumb, align, and brace frames until permanent anchors are set.

1. Use triangular bracing near each corner on both sides of frames with temporary wood spreaders at midpoint.

2. Use wood spreaders at bottom of frame when shipping spreader is removed.

3. Where construction permits concealment, leave shipping spreaders in place after installation, otherwise remove spreaders when frames are set and anchored.

4. Remove wood spreaders and braces when walls are built and jamb anchors are secured.

C. Floor Anchors:

1. Anchor frame jambs to floor with two expansion bolts.

a. Lead Lined Frames: Use 9 mm (3/8 inch) diameter bolts.

b. Other Frames: Use 6 mm (1/4 inch) diameter bolts.

2. Power actuated drive pins are acceptable to secure frame anchors to concrete floors.

D. Jamb Anchors:

1. Masonry Walls:

a. Embed anchors in mortar.

b. Fill space between frame and masonry with grout or mortar as walls are built.

2. Metal Framed Walls: Secure anchors to sides of studs with two fasteners through anchor tabs.

08 11 13 - 12

3. Prepared Masonry and Concrete Openings:

a. Direct Securement: 6 mm (1/4 inch) diameter expansion bolts through spacers.

b. Subframe or Rough Buck Securement:

1) 6 mm (1/4 inch) diameter expansion bolts on 600 mm (24 inch) centers.

2) Power activated drive pins on 600 mm (24 inches) centers.

c. Secure two-piece frames to subframe or rough buck with machine screws on both faces.

E. Frames for Sound Rated Doors: Fill frames with insulation.

F. Lead Lined Frames:

1. Extend jambs and anchor with clip angles to structure above.

a. Fasteners to Concrete: Minimum two, 9 mm (3/8 inch) diameter expansion bolts or power actuated drive pins.

b. Connection to Structural Steel: Welded.

G. Touch up damaged factory finishes.

1. Repair galvanized surfaces with galvanized repair paint.

2. Repair painted surfaces with touch up primer.

3.4 DOOR INSTALLATION

A. Install doors plumb and level.

B. Adjust doors for smooth operation.

C. Touch up damaged factory finishes.

1. Repair galvanized surfaces with galvanized repair paint.

2. Repair painted surfaces with touch up primer.

3.5 CLEANING

A. Clean exposed door and frame surfaces. Remove contaminants and stains.

3.6 PROTECTION

A. Protect doors and frames from traffic and construction operations.

B. Remove protective materials immediately before acceptance.

C. Repair damage.

- - - E N D - - -

08 14 00 - 1

SECTION 08 14 00

INTERIOR WOOD DOORS

A. Section Includes:

1. Interior flush wood doors transparent finish.

a. Unrated Doors

b. Fire rated Doors

c. Smoke rated doors

1.2 RELATED WORK

A. Section 08 71 00, DOOR HARDWARE: Door Hardware including hardware location (height).

B. Section 08 11 13, HOLLOW METAL DOORS AND FRAMES: Installation of Doors.

C. Section 08 71 00, DOOR HARDWARE: Installation of Door Hardware.

D. Section 09 06 00, SCHEDULE FOR FINISHES: Door Finish.

1.3 APPLICABLE PUBLICATIONS

A. Comply with references to extent specified in this section.

B. American National Standards Institute/Window and Door Manufacturers

Association (ANSI/WDMA):

1. I.S. 1A-13 - Architectural Wood Flush Doors.

C. ASTM International (ASTM):

1. E90-09(2016) - Laboratory Measurements of Airborne Sound

Transmission Loss of Building Partitions and Elements.

D. National Fire Protection Association (NFPA):

1. 80-16 - Fire Doors and Other Opening Protectives.

2. 252-12 - Fire Tests of Door Assemblies.

E. UL LLC (UL):

1. 10C-09 - Positive Pressure Fire Tests of Door Assemblies.

F. Window and Door Manufacturers Association (WDMA):

1. TM 7-14 - Cycle-Slam Test.

2. TM 8-14 - Hinge Loading Test.

3. TM 10-14 - Screw Holding Capacity.

1.4 SUBMITTALS

A. Submittal Procedures: Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES.

B. Submittal Drawings:

08 14 00 - 2

1. Show size, configuration, and fabrication and installation details.

2. Include details of glazing.

3. Indicate project specific requirements not included in

Manufacturer's Literature and Data submittal.

C. Manufacturer's Literature and Data:

1. Description of each product.

2. Fire rated doors showing conformance with NFPA 80.

D. Samples:

1. Corner section of flush veneered door 300 mm (12 inches) square, showing details of construction, labeled to show grade and type number and conformance to specified standard.

2. Veneer sample 200 mm by 275 mm (8 inch by 11 inch) showing specified wood species sanded to receive a transparent finish. Factory finish veneer sample where the prefinished option is accepted.

E. Test Reports: Indicate each product complies products comply with specifications.

1. Screw Holding Capacity Test.

2. Cycle-Slam Test.

3. Hinge-Loading Test.

F. Operation and Maintenance Data:

1. Care instructions for each exposed finish product.

1.5 QUALITY ASSURANCE

A. Manufacturer Qualifications:

1. Regularly and presently manufactures specified products.

2. Manufactures specified products with satisfactory service on five similar installations for minimum five years.

1.6 DELIVERY

A. Deliver products in manufacturer's original sealed packaging.

1. Minimum 0.15 mm (6 mil) polyethylene bags or cardboard packaging to remain unbroken during delivery and storage.

B. Mark packaging, legibly. Indicate manufacturer's name or brand, type, color, and manufacture date.

1. Identify door opening corresponding to Door Schedule.

08 14 00 - 3

C. Before installation, return or dispose of products within distorted, damaged, or opened packaging. Retain packaging for door protection after installation.

1.7 STORAGE AND HANDLING

A. Store products indoors in dry, weathertight conditioned facility.

1. Store doors according to ANSI/WDMA I.S. 1A.

B. Protect products from damage during handling and construction operations.

1.8 FIELD CONDITIONS

A. Environment:

1. Product Temperature: Minimum 21 degrees C (70 degrees F) for minimum

48 hours before installation.

2. Work Area Ambient Temperature Range: 21 to 27 degrees C (70 to

80 degrees F) continuously, beginning 48 hours before installation.

3. Install products when building is permanently enclosed and when wet construction is completed, dried, and cured.

Comply with door manufacturer's instructions for relative humidity.

1.9 WARRANTY

A. Construction Warranty: FAR clause 52.246-21, "Warranty of

Construction."

B. Manufacturer's Warranty: Warrant interior factory finished flush wood doors against material and manufacturing defects.

1. Warranty Period: Lifetime of original installation.

PART 2 - PRODUCTS

2.1 PRODUCTS - GENERAL

A. Basis of Design: Section 09 06 00, SCHEDULE FOR FINISHES.

B. Provide each product from one manufacturer.

2.2 FLUSH WOOD DOORS

A. General:

1. ANSI/WDMA I.S. 1A, Extra Heavy Duty.

2. Adhesive: Type II.

3. Core: Structural composite lumber, except when mineral core is required for fire rating.

4. Thickness: 44 mm (1-3/4 inches) unless otherwise shown or specified.

5. Provide 16 gauge steel closer frame reinforcement per wood door manufacturer, both faces, typical ALL doors. Factory install per

08 14 00 - 4 manufacturer’s requirements. Size as required to secure hardware specified.

6. Provide door frame high frequency hinge reinforcement plates, minimum tw0 (2) hinges per door, typical all doors. See 2.2.C. 5 typical ALL doors. Factory install per manufacturer’s requirements.

Size as required to secure hardware specified.

B. Faces:

1. ANSI/WDMA I.S. 1A.

2. One species throughout project unless scheduled or otherwise shown.

3. Transparent Finished Faces: Premium Grade. rotary cut, white oak .

A Grade face veneer.

4. Match face veneers for doors for uniform effect of color and grain at joints.

5. Door Edges: Same species as door face veneer, except maple is acceptable for stile face veneer on birch doors.

6. In existing buildings, where doors are required to have transparent finish, use wood species, grade, and assembly of face veneers to match existing doors.

7. Painted Finishes: Custom Grade, mill option close grained hardwood, premium or medium density overlay.

8. Factory sand doors indicated for field finishing.

C. Wood For Stops and Moldings for Flush Doors Required to Have

Transparent Finish:

1. Solid wood of same species as face veneer, except maple is acceptable on birch doors.

2. Glazing:

a. On non-fire-rated doors, use applied wood stops nailed tightly on room side and attached on opposite side with flathead, countersunk wood screws, spaced approximately 125 mm (5 inches) on center.

D. Fire-Rated Wood Doors (as indicated on Drawings):

1. Fire Resistance Rating:

a. B Label: 1-1/2 hours.

b. C Label: 3/4 hour.

2. Provide 20-minute smoke-rated doors in smoke-rated barriers.

3. Labels:

08 14 00 - 5

a. Comply with NFPA 252, UL 10C, and labeled by qualified testing and inspection agency showing fire resistance rating.

1) Metal labels with raised or incised markings.

4. Performance Criteria for Stiles of Doors Utilizing Standard Mortise

Leaf Hinges:

a. Hinge Loading: WDMA TM 8. Average of 10 test samples for Extra

Heavy Duty doors.

b. Direct Screw Withdrawal: WDMA TM 10 for Extra Heavy-Duty doors.

Average of 10 test samples using a steel, fully threaded #12 wood screw.

c. Cycle-Slam: 1,000,000 cycles with no loose hinge screws or other visible signs of failure when tested according to WDMA TM 7.

5. Hardware Reinforcement:

a. Provide fire and smoke rated doors with hardware reinforcement blocking.

b. Size of lock blocks as required to secure hardware specified.

c. Top, Bottom and Intermediate Rail Blocks: Minimum 125 mm

(5 inches) by full core width.

d. Reinforcement blocking in compliance with labeling requirements.

Mineral material similar to core is not acceptable.

6. Other Core Components: Manufacturer's standard as allowed by labeling requirements.

7. Glazed Vision Panel Frame: Steel approved for use in labeled doors.

8. Astragal: Steel type for pairs of doors.

E. Smoke Barrier Doors:

1. Glazed Vision Panel Frame: Steel approved for use in labeled doors.

F. Sound Rated Doors:

1. Fabricated as specified for flush wood doors with additional construction requirements to comply with specified sound transmission class (STC).

2. STC Rating of door assembly in place when tested according to

ASTM E90 by independent acoustical testing laboratory minimum 35

a. Accessories:

1) Frame Gaskets and Automatic Door Bottom Seal: As specified in

Section 08 71 00, DOOR HARDWARE.

08 14 00 - 6

2.3 FABRICATION

A. Factory machine interior wood doors to receive hardware, bevels, undercuts, cutouts, accessories and fitting for frame.

1. Factory fit fire rated doors according to NFPA 80.

B. Rout doors for hardware using templates and location heights specified in Section 08 71 00, DOOR HARDWARE.

C. Factory fit doors to frame, bevel lock edge of doors 3 mm (1/8 inch) for each 50 mm (2 inches) of door thickness.

D. Clearances between Doors and Frames and Floors:

1. Fire Rated Doors: Comply with NFPA 80.

a. Doors with Automatic Bottom Seal: Maximum clearance 10 mm

(3/8 inch) at threshold.

b. Other Door Bottoms: Maximum 3 mm (1/8 inch) clearance at the jambs, heads, and meeting stiles, and a 19 mm (3/4 inch) clearance at bottom, except as otherwise specified.

2. Door Jambs, Heads, and Meeting Stiles: Maximum 3 mm (1/8 inch).

E. Provide cutouts for glazed openings.

F. Factory finish surfaces, including both faces, top and bottom and edges of the doors smooth to touch.

G. Identify each door on top edge.

1. Mark with stamp, brand or other indelible mark, giving manufacturer’s name, door’s trade name, construction of door, date of manufacture and quality.

2. Mark door or provide separate certification including name of inspection organization.

3. Identify door manufacturing standard, including glue type.

4. Identify veneer and quality certification.

5. Identification of preservative treatment for stile and rail doors.

2.4 FINISHES

A. Factory Transparent Finish:

1. Factory finish flush wood doors.

a. ANSI/WDMA I.S. 1A Section F-3 Finish System Descriptions for

System 5, Conversion Varnish or System 7, Catalyzed Vinyl.

b. Use stain when required to produce finish specified in Section

09 06 00, SCHEDULE FOR FINISHES.

08 14 00 - 7

PART 3 - EXECUTION

3.1 PREPARATION

A. Examine and verify substrate suitability for product installation.

1. Verify door frames are properly anchored.

2. Verify door frames are plumb, square, in plane, and within tolerances for door installation.

B. Protect existing construction and completed work from damage.

C. Install astragal on active leaf of pair of smoke doors and one leaf of double egress smoke doors.

3.2 INSTALLATION

A. Install products according to manufacturer's instructions and approved submittal drawings.

1. Install fire rated doors according to NFPA 80.

2. When manufacturer's instructions deviate from specifications, submit proposed resolution for Contracting Officer's Representative consideration.

3.3 PROTECTION

A. After installation, place shipping container over door and tape in place.

1. Do not apply tape to door faces and edges.

B. Provide protective covering over exposed hardware in addition to covering door.

C. Maintain covering in good condition until removal is directed by

Contracting Officer's Representative.

- - E N D - -

08 31 13 - 1

SECTION 08 31 13

ACCESS DOORS AND FRAMES

A. Section Includes:

1. Access doors and panels installed in walls and ceilings.

1.2 RELATED WORK

A. Section 05 50 00, METAL FABRICATIONS: Wire Mesh and Screen Access

Doors.

B. Section 08 71 00, DOOR HARDWARE: Lock Cylinders.

C. Section 09 91 00, PAINTING: Field Painting.

D. Section 09 06 00, SCHEDULE FOR FINISHES: Finish Color.

E. Section 21 13 13, WET-PIPE SPRINKLER SYSTEMS: Access Doors for Control or Drain Valves.

F. Section 22 40 00, PLUMBING FIXTURES: Access Doors for Plumbing Valves.

G. Section 23 31 00, HVAC DUCTS AND CASINGS: Locations of Access Doors for

Ductwork Cleanouts.

1.3 APPLICABLE PUBLICATIONS

A. Comply with references to extent specified in this section.

B. American Welding Society (AWS):

D1.3/D1.3M-2018.........Structural Welding Code - Sheet Steel

(6th Edition.

C. ASTM International (ASTM):

A653/A653M-20...........Steel Sheet, Zinc-Coated (Galvanized) or

Zinc-Iron Alloy-Coated (Galvannealed) by the

Hot-Sip Process.

A1008/A1008M-18.........Steel, Sheet, Cold-Rolled, Carbon, Structural, High-Strength Low-Alloy, High-Strength

Low-Alloy with Improved Formability, Solution

Hardened, and Bake Hardenable.

A666-15.................Annealed or Cold-Worked Austenitic Stainless-

Steel sheet, Strip, Plate, and Flat Bar.

E119-20.................Fire Test of Building Construction and

Materials.

D. National Fire Protection Association (NFPA):

80-2019 Edition.........Fire Doors and Other Opening Protectives.

08 31 13 - 2

252-2017 Edition........Fire Tests of Door Assemblies.

E. National Association of Architectural Metal Manufacturers (NAAMM):

AMP 500-06..............Metal Finishes Manual.

F. UL LLC (UL):

Listed..................Online Certifications Directory.

10B-08 (Edition 10).....Standard for Fire Tests of Door Assemblies.

263-11 (Edition 14).....Fire Tests of Building Construction and

Materials.

PART 2 - SUBMITTALS

A. Submittal Procedures: Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES.

B. Submittal Drawings:

1. Show size, configuration, and fabrication and installation details.

C. Manufacturer's Literature and Data:

1. Description of each product.

2. Installation instructions.

2.2 DELIVERY

A. Deliver products in manufacturer's original sealed packaging.

B. Mark packaging, legibly. Indicate manufacturer's name or brand, type, color, production run number, and manufacture date.

C. Before installation, return or dispose of products within distorted, damaged, or opened packaging.

2.3 STORAGE AND HANDLING

A. Store products indoors in dry, weathertight facility.

B. Protect products from damage during handling and construction operations.

2.4 FIELD CONDITIONS

A. Field Measurements: Verify field conditions affecting access door fabrication and installation. Show field measurements on Submittal

Drawings.

1. Coordinate field measurement and fabrication schedule to avoid delay.

2.5 WARRANTY

A. Construction Warranty: FAR clause 52.246-21, "Warranty of

Construction."

08 31 13 - 3

2.6 MATERIALS

A. Steel Sheet: ASTM A1008/A1008M.

B. Galvanized Steel: ASTM A653/A653M.

C. Stainless Steel: ASTM A666; Type 302 or Type 304.

2.7 PRODUCTS - GENERAL

A. Basis of Design: Section 09 06 00, SCHEDULE FOR FINISHES.

B. Provide each product from one manufacturer.

2.8 ACCESS DOORS, FIRE-RATED

A. Door Construction:

1. Ceiling Access Door Construction: ASTM E119 or UL 263.

2. Wall Access Doors: NFPA 252 or UL 10B.

B. Label: Class B opening according to UL 10B or test by another nationally recognized laboratory. 1 hour fire-rated with maximum temperature rise of 120 degrees C (216 degrees F).

C. Door Panel: Minimum 0.9 mm (0.0359 inch) thick steel or stainless steel(at wet locations) sheet, with mineral-fiber insulation core, insulated sandwich type construction.

D. Frame: Minimum 1.5 mm (0.0598 inch) thick steel sheet, depth and configuration to suit material and construction type where installed.

1. Frame Flange: Provide at units installed in concrete, masonry, or gypsum board.

2. Exposed Joints in Flange: Weld and grind smooth.

E. Provide automatic closing device.

F. Hinge: Continuous stainless steel hinge with stainless steel pin.

G. Lock: Self-latching, mortise type with provision for fitting flush a standard screw-in type lock cylinder.

1. Lock cylinder specified in Section 08 71 00, DOOR HARDWARE.

2. Latch release device operable from inside of door.

H. Anchors for Fire-Rated Access Doors: Comply with requirements of applicable fire test.

2.9 ACCESS DOORS, FLUSH PANEL, NON-RATED

A. Door Panel:

1. 1.9 mm (0.07 inch) thick steel (1.5 mm (0.06 inch) thick stainless steel at wet locations) sheet.

2. Reinforce to maintain flat surface.

08 31 13 - 4

B. Frame:

1. 1.5 mm (0.06 inch) thick steel or stainless steel sheet, depth and configuration to suit material and construction type where installed.

2. Frame Flange: Provide at units installed in concrete, masonry, and gypsum board.

3. Exposed Joints in Flange: Weld and grind smooth.

C. Hinge:

1. Concealed spring hinge, 175 degrees of opening.

D. Lock:

1. Flush, screwdriver-operated cam lock.

2.10 ACCESS DOOR, RECESSED PANEL, NON-RATED

A. Door Panel:

1. 1.2 mm (0.05 inch) thick steel or stainless steel sheet to form a

25 mm (1 inch) deep recessed pan to accommodate installation of acoustical units and other materials where shown in walls and ceiling.

2. Reinforce to prevent sagging.

B. Frame:

1. 1.5 mm (0.06 inch) thick steel sheet of depth and configuration to suit installation in suspension system of ceiling or wall framing.

2. Extend sides of frame to protect edge of acoustical units when door panel is in open position.

3. Provide shims, bushings, clips and other devices necessary for installation.

C. Hinge: Continuous stainless steel hinge with stainless steel pin, or concealed hinge.

D. Lock:

1. Flush screwdriver-operated cam lock.

2.11 FABRICATION - GENERAL

A. Size: Minimum 600 mm (24 inches) square door unless otherwise shown or as required to suit opening in suspension system of ceiling.

B. Component Fabrication: Straight, square, flat and in same plane where required.

08 31 13 - 5

1. Exposed Edges: Slightly rounded, without burrs, snags and sharp edges.

2. Exposed Welds: Continuous, ground smooth.

3. Welding: AWS D1.3/D1.3M.

C. Locks and Non-Continuous Hinges: Provide in numbers required to maintain alignment of door panel with frame. For fire-rated doors, provide hinges and locks as required by fire test.

D. Anchoring: Make provisions in frame for anchoring to adjacent construction. Provide anchors in size, number and location on four sides to secure access door to substrate. Provide anchors as required by fire test.

2.12 FINISHES

A. Steel Paint Finish:

1. Powder-Coat Finish: Manufacturer's standard two-coat finish system consisting of the following:

a. One coat primer.

b. One coat thermosetting topcoat.

c. Dry-film Thickness: 0.05 mm (2 mils) minimum.

d. Color: Refer to Section 09 06 00, SCHEDULE FOR FINISHES.

B. Stainless Steel Exposed Surfaces: NAAMM AMP 500; No.06 Metal Finishes.

2.13 ACCESSORIES

A. Fasteners: Type and size recommended by access door manufacturer, to suit application.

1. Stainless Steel Access Doors: Stainless steel fasteners.

2. Other Access Doors: Galvanized steel fasteners.

PART 3 - EXECUTION

3.1 PREPARATION

A. Examine and verify substrate suitability for product installation.

1. Verify access door locations and sizes provide required maintenance access to installed building services components.

B. Protect existing construction and completed work from damage.

3.2 INSTALLATION - GENERAL

A. Install products according to manufacturer's instructions and approved submittal drawings.

08 31 13 - 6

1. When manufacturer's instructions deviate from specifications, submit proposed resolution for Contracting Officer's Representative consideration.

B. Install access doors and panels permitting access to service valves, traps, dampers, cleanouts, and other mechanical, electrical and conveyor control items concealed in walls and partitions, and concealed above gypsum board and plaster ceilings.

C. Install fire rated access door according to NFPA 80.

D. Install fire-rated doors in fire-rated partitions and ceilings.

E. Install flush access panels in partitions and in gypsum board and plaster ceilings.

3.3 ACCESS DOOR AND FRAME INSTALLATION

A. Wall Installations: Install access doors in openings with sides vertical.

B. Ceiling Installations: Install access doors parallel to ceiling suspension grid or room partitions.

C. Frames without Flanges: Install frame flush with surrounding finish surfaces.

D. Frames with Flanges: Overlap opening, with face uniformly spaced from finish surface.

E. Recessed Panel Access Doors: Install with face of surrounding materials flush with door panel installed finish.

F. Secure frames to adjacent construction with fasteners.

G. Install type, size and quantity of anchoring device suitable for material surrounding opening to maintain alignment, and resist displacement, during normal use of access door.

H. Field Painting Primed Access Doors: Comply with the requirements of

Section 09 91 00, PAINTING.

3.4 ADJUSTMENT

A. Adjust hardware so door panel opens freely.

B. Adjust door when closed so door panel is centered in frame.

- - E N D - -

08 32 13 - 1

SECTION 08 32 13

ICU SLIDING GLASS DOORS

A. Section Includes:

1. Interior, single slide, manual or automatic sliding ICU/CCU entrances; tracked or trackless for individual special-care rooms.

2. Entrances shall be rated as an effective barrier limiting the passage of smoke.

1.2 RELATED WORK

A. Drawings and general provisions of the Contract, including General and

Supplementary Conditions and Division 1 Specification Sections, apply to this Section.

B. Section 09 06 00, SCHEDULE FOR FINISHES Door Finish and Color.

C. Section 08 80 00, GLAZING. Glass and Glazing:

D. Section 08 71 00, DOOR HARDWARE: Hardware.

E. Section 09 06 00, SCHEDULE FOR FINISHES: Aluminum Finish and Color.

1.3 COORDINATION

A. Field Measurements: Verify actual dimensions of openings to receive

ICU/CCU entrances by field measurements before fabrication.

B. Templates: Distribute for doors, frames, and other work specified to be factory prepared for installing ICU/CCU entrances.

1.4 APPLICABLE PUBLICATIONS

A. Comply with references to extent specified in this section. Refer to the version year adopted by the Authority Having Jurisdiction or the latest edition.

B. American Welding Society (AWS):

D1.2/D1.2M-2014.........Structural Welding Code - Aluminum

C. ASTM International (ASTM):

B209-14.................Aluminum and Aluminum-Alloy Sheet and Plate

B209M-14................Aluminum and Aluminum-Alloy Sheet and Plate

(Metric)

B221-14.................Aluminum and Aluminum-Alloy Extruded Bars, Rods, Wire, Profiles, and Tubes

08 32 13 - 2

B221M-13................Aluminum and Aluminum-Alloy Extruded Bars, Rods, Wire, Profiles, and Tubes (Metric)

D. National Association of Architectural Metal Manufacturers (NAAMM):

AMP 500-04..............Metal Finishes Manual for Architectural Metal

Products

E. National Fenestration Rating Council (NFRC):

500-17..................Determining Fenestration Product Condensation

Resistance Values

F. National Fire Protection Association (NFPA):

NFPA 70-20..............National Electric Code

NFPA 105-19.............Standard for the Installation of Smoke Door

Assemblies

G. Underwriters Laboratories UL:

UL 1784-20..............Air Leakage Tests for Door Assemblies

1.5 PREINSTALLATION MEETINGS

A. Conduct preinstallation meeting at project site minimum 30 days before beginning Work of this section.

1. Required Participants:

a. Contracting Officer's Representative.

b. Architect/Engineer.

c. Contractor.

d. Installer.

e. Manufacturer's field representative.

2. Meeting Agenda: Distribute agenda to participants minimum 3 days before meeting.

a. Installation schedule.

b. Installation sequence.

c. Preparatory work.

d. Protection before, during, and after installation.

e. Installation.

f. Terminations.

g. Transitions and connections to other work.

h. Other items affecting successful completion.

3. Document and distribute meeting minutes to participants to record decisions affecting installation.

08 32 13 - 3

1.6 SUBMITTALS

A. Submittal Procedures: Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES.

B. Submittal Drawings: Minimum 1 to 2 (half size) scale.

1. Show size, configuration, and fabrication and installation details.

2. Show anchorage and reinforcement.

3. Show interface and relationship to adjacent work.

C. Manufacturer's Literature and Data:

1. Description of each product.

2. Doors, each type.

3. Entrance and Storefront construction.

4. Installation instructions.

5. Warranty.

D. Samples:

1. Door Corner Section: Minimum 450 mm x 450 mm (18 x 18 inches) for each specified door type, showing head rail and hinge stile, door closer reinforcement, and internal reinforcement.

2. Aluminum Anodized Finish: Provide sample extrusions minimum 150 mm

(6 inches) long for each specified color in sets of three showing maximum color range.

3. Aluminum Paint Finish: Provide sample extrusions minimum 150 mm

(6 inches) long for each specified color.

E. Test reports: Certify each product complies with specifications.

F. Certificates: Certify each product complies with specifications.

1. Certify anodized finish thickness.

G. Qualifications: Substantiate qualifications comply with specifications.

1. Manufacturer with project experience list.

2. Installer with project experience list.

3. Welders and welding procedures.

H. Delegated Design Drawings and Calculations: Signed and sealed by responsible design professional.

1. Show location and magnitude of loads applied to building structural frame.

2. Identify deviations from details shown on drawings.

I. Operation and Maintenance Data:

1. Care instructions for each exposed finish product.

08 32 13 - 4

1.7 QUALITY ASSURANCE

A. Manufacturer Qualifications:

1. Regularly manufactures specified products.

2. Manufactured specified products with satisfactory service on five similar installations for minimum five years.

a. Project Experience List: Provide contact names and addresses for completed projects.

B. Installer Qualifications: Product manufacturer and Manufacturer authorized representative.

1. Regularly installs specified products.

2. Installed specified products with satisfactory service on five similar installations for minimum five years.

a. Project Experience List: Provide contact names and addresses for completed projects.

C. Welders and Welding Procedures Qualifications: AWS D1.2/D1.2M.

1.8 DELIVERY, STORAGE AND HANDLING

A. Deliver products in manufacturer's original sealed packaging.

B. Mark packaging, legibly. Indicate manufacturer's name or brand, type, color, production run number, and manufacture date.

C. Before installation, return or dispose of products within distorted, damaged, or opened packaging.

D. Store products indoors in dry, weathertight conditioned facility.

E. Protect products from damage during handling and construction operations.

1.9 WARRANTY

A. Construction Warranty: FAR clause 52.246-21, "Warranty of

Construction." Warranty Period for Five years for but not limited to, the following: Structural failure including excessive deflection

1. Faulty operation of hardware

2. Excessive deterioration/failure of metals, metal finishes, glass and other materials.

B. Manufacturer's Warranty: Warrant painted finish against material and manufacturing defects.

1. Warranty Period: 20 years.

08 32 13 - 5

PART 2 - PRODUCTS

2.1 SYSTEM PERFORMANCE

A. ICU/CCU Entrance Assemblies

1. General: Provide manufacturer's standard ICU/CCU entrance assemblies including doors, sidelites, framing, headers, carrier assemblies, roller tracks, pivots, and accessories required for a complete installation. All components are to be from a single source from a single manufacturer.

2. Performance Requirements:

a. Opening Force: Not more than 5-pound force (22.2 N) to fully open door.

b. Air Leakage: Entrance assemblies for /smoke control and pressurized rooms shall be listed and labeled for smoke and draft control by qualified testing agency acceptable to authorities having jurisdiction, based on testing according to UL 1784 and having maximum air leakage as required by NFPA 105 unless otherwise indicated.

c. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application.

3. Breakaway Hardware: Release hardware that allows indicated panels to swing out in direction of egress to full 90 degrees from closed door position.

4. Maximum Force to Open Panel: 50 pound force (222 N) Insert value.

5. Release Position: At any point in sliding-door travel.

B. Sliding ICU/CCU Entrances:

1. Configuration: As indicated on the drawings.

2. Performance: Standard assembly and Smoke-control assembly/

Pressurized-entrance assembly as indicated. Breakaway Capability:

Sliding panels and sidelites, from fully open position.

3. Mounting: Between jambs Surface.

4. Floor Track: Trackless across sliding-door opening and surface-mounted, roller guide track system at sidelites.

5. Stile Design: Wide stile; more than 5-inch (100-mm) nominal width

6. Top Rail Design: 5-inch (125-mm) nominal height.

08 32 13 - 6

7. Bottom Rail Design: 6 1/2-inch (125-mm) nominal height with weather sweep.

8. Muntin Bars: None .

9. Glazing Stops and Gaskets: Square.

10. Glazing: Clear tempered.

a. Factory Glazing: Install glazing at the factory.

11. Finish framing and door(s) with Class I, clear anodic finish.

a. Metal Cladding: No. 4, directional-satin-finish stainless steel

C. Delegated Design: Prepare submittal documents including design calculations and drawings signed and sealed by registered design professional, licensed in state where work is located.

1. Minor deviations to details shown on drawings to accommodate manufacturer’s standard products may be accepted by Contracting

Officer's Representative when deviations do not affect design concept and specified performance.

D. Design aluminum framed entrances and storefronts complying with specified performance:

1. General: Provide ICU/CCU entrances capable of withstanding structural loads and thermal movements based on testing manufacturer's standard units in assemblies similar to those indicated for this Project.

2. Fixed Framing Air Infiltration Resistance: ASTM E283;

0.30 liter/second/square meter (0.06 cubic feet/minute/square foot), maximum at 300 Pa (6.24 psf), minimum, pressure differential.

2.2 MATERIALS

A. Aluminum:

1. Sheet Metal: ASTM B209M (ASTM B209), minimum 1.6 mm (0.063 inch) thick.

2. Extrusions: ASTM B221M (ASTM B221).

a. Framing: Minimum 3 mm (0.125 inch) wall thickness.

b. Glazing Beads, Moldings, and Trim: Minimum 1.25 mm (0.050 inch) thick.

3. Alloy 6063 temper T5 for doors, door frames, fixed glass sidelites.

4. Color Anodized Aluminum: Provide aluminum alloy required to produce specified color.

B. Stainless Steel: ASTM A240/A240M; Type 302 or Type 304.

08 32 13 - 7

2.3 PRODUCTS - GENERAL

A. Basis of Design: Horton Automatics Profiler-ICU Telescoping Trackless

Series 3-Panel, Type:310T SO-SX-SX or SX-SX- SO as per drawings.

B. See Section 09 06 00, SCHEDULE FOR FINISHES.

C. Provide aluminum framed entrances and storefronts from one manufacturer and from one production run.

2.4 FRAMES

A. Framing Members: Extruded aluminum.

B. Stops: Provide integral fixed stops and glass rebates and snap-on removable stops.

C. Provide concealed screws, bolts and other fasteners.

D. Secure cover boxes to frames in back of lock strike cutouts.

2.5 STILE AND RAIL DOORS

A. Stiles and Rails: Extruded aluminum.

1. Thickness: 45 mm (1-3/4 inch).

2. Wide Stile Vertical Rails: 127 mm (5 inches) wide

3. Wide Stile Bottom Rail: 165 mm (6-1/2 inches) wide.

B. Sliding Door Lok: Basis-of-Design – INOX PD9570 Emergency Egress

Sliding Door Lock. Deadbolt locking Classroom function, deadbolt retracted by handle (inside for egress,) and key (outside.)

1. Keying to match facility standard. Coordinate cylinders with

Facility Standard. Key all ICU doors alike.

2. Handing as indicated on Drawings.

3. Finish: US32D Satin Stainless Steel

4. Lever: ‘Munich’ XGT202 (Solid version)

5. Strike: Install in ICU jamb frame per manufacturer’s Standard requirements.

C. Glass Rebates: Integral with stiles and rails.

D. Glazing Beads: Extruded aluminum, 1.3 mm (0.050 inch) thick.

This is the start of the file's text. The full file is on GovTribe.