Division 4 Specs - Masonry.pdf

PDF 222 KB Posted

Attached to
Z1DA--MINOR-CONST 528-809 NEW EMERGENCY DEPARTMENT ALBANY VAMC
Solicitation number
36C24224R0071
Issued by

About this file

This document is a solicitation for a construction project to build a new Emergency Department at the Stratton VA Medical Center in Albany, NY. The key details are:

The project involves demolition, site work, building construction, and installation of systems and equipment for a new 550-calendar day Emergency Department addition to the existing medical center. The contractor must provide a competent full-time OSHA-certified superintendent and utilize the Autodesk Build construction management platform for project collaboration and communication. The contractor must complete all punch list items within the 550-calendar day period of performance. The agency is the Department of Veterans Affairs, Veterans Integrated Service Network 2. There are no set-asides identified, and no information provided about incumbents or pricing terms.

View the file

Other files

File Type Posted
36C24224R0071 0008.docx DOCX document
36C24224R0071 0007.docx DOCX document
1-SE-701.pdf PDF
36C24224R0071 0006.docx DOCX document
SK-ES-802.1.pdf PDF
36C24224R0071 0005.docx DOCX document
Albany VA ED Walk Through Sign in List.pdf PDF
Albany VAMC Geotech Report for New ED.pdf PDF
087100 Door hardware SET 14.pdf PDF
071352 Modified Bituminous Sheet Waterproofing.pdf PDF
Stratton ED_103177_SET.pdf PDF
Q40 - 1-HA-100.pdf PDF
36C24224R0071 0004.docx DOCX document
055000 Metal Fabrications.pdf PDF
Subbasement Structural Originals.pdf PDF
084113 Aluminum Framed Entrances and Storefront8-18-22.pdf PDF
088000 Glazing-8-18-22.pdf PDF
36C24224R0071 0003.docx DOCX document
36C24224R0071 0002.docx DOCX document
19-181 100 Specs VA 528-809 Volume I.pdf PDF
19-181 100 Specs VA 528-809 Volume II.pdf PDF
EXHIBIT B - Sample Transmittal Letter for Past Performance Evaluation Questionnaire.docx DOCX document
36C24224R0071 0001.docx DOCX document
072400 EIFS.pdf PDF
EXHIBIT C - Past Performance Questionnaire.docx DOCX document
divisions 27-28 Specs.pdf PDF
1-22-24 - VA STRATTON NEW EMERGENCY DEPT SS_Part1.pdf PDF
2022-02-22 VA 528-809 Submittal Register-Divisions 01 - 34 FE.xlsx XLSX spreadsheet
Division 3 specs - concrete.pdf PDF
000115 List of Drawing Sheets.pdf PDF
Division 26 Specs - electrical.pdf PDF
Division 23 Specs - HVAC.pdf PDF
Division 7 Specs - Thermal and Moisture Protection.pdf PDF
1-22-24 - VA STRATTON NEW EMERGENCY DEPT SS_Part7.pdf PDF
Division 5 specs - Metals.pdf PDF
1-22-24 - VA STRATTON NEW EMERGENCY DEPT SS_Part8.pdf PDF
1-22-24 - VA STRATTON NEW EMERGENCY DEPT SS_Part10.pdf PDF
1-22-24 - VA STRATTON NEW EMERGENCY DEPT SS_Part2.pdf PDF
000110 TOC.pdf PDF
Division 9 specs - Finishes.pdf PDF
WD Albany NY20240002 07-12-2024.docx DOCX document
Division 6 Specs - wood and plastics.pdf PDF
Division 2 specs - existing conditions.pdf PDF
Division 21-22 Specs.pdf PDF
1-22-24 - VA STRATTON NEW EMERGENCY DEPT SS_Part4.pdf PDF
Divisions 31-34 Specs.pdf PDF
Division 8 Spec - Doors and windows.pdf PDF
1-22-24 - VA STRATTON NEW EMERGENCY DEPT SS_Part5.pdf PDF
1-22-24 - VA STRATTON NEW EMERGENCY DEPT SS_Part11.pdf PDF
1-22-24 - VA STRATTON NEW EMERGENCY DEPT SS_Part9.pdf PDF
Show 40 more

Latest 50 of 56 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SAMUEL S. STRATTON VA MEDICAL CENTER

DESIGN NEW EMERGENCY DEPARTMENT

VA PROJECT NO. 528-809

10-01-17

04 05 13 - 1

SECTION 04 05 13

MASONRY MORTARING

PART 1 - GENERAL

1.1 SUMMARY

A. Section Includes:

1. Masonry mortar installed by other / masonry sections.

1.2 RELATED REQUIREMENTS

A. Mortar used in Section:

1. Section 04 05 16, MASONRY GROUTING.

2. Section 04 20 00, UNIT MASONRY.

B. Mortar Color: Section 09 06 00, SCHEDULE FOR FINISHES.

1.3 APPLICABLE PUBLICATIONS

A. Comply with references to extent specified in this section.

B. ASTM International (ASTM):

1. C40/C40M-11 - Organic Impurities in Fine Aggregates for Concrete.

2. C91/C91M-12 - Masonry Cement.

3. C144-11 -Aggregate for Masonry Mortar.

4. C150/C150M-15 - Portland Cement.

5. C207-06(2011) - Hydrated Lime for Masonry Purposes.

6. C270-14a - Mortar of Unit Masonry.

7. C595/C595M-15e1 - Blended Hydraulic Cements.

8. C780-15 - Preconstruction and Construction Evaluation of Mortars for

Plain and Reinforced Unit Masonry.

9. C979/C979M-10 - Pigments for Integrally Colored Concrete.

10. C1329/C1329M-15 - Mortar Cement.

1.4 SUBMITTALS

A. Submittal Procedures: Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES.

B. Manufacturer's Literature and Data:

1. Description of each product.

C. Test Reports: Certify each product complies with specifications.

1. Mortar.

2. Admixtures.

D. Certificates: Certify each product complies with specifications.

04 05 13 - 2

1. Portland cement.

2. Masonry cement.

3. Mortar cement.

4. Hydrated lime.

5. Fine aggregate.

6. Color admixture.

E. Qualifications: Substantiate qualifications comply with specifications.

1. Testing laboratory.

1.5 QUALITY ASSURANCE

A. Preconstruction Testing:

1. Engage independent testing laboratory to tests and submit reports.

a. Deliver samples to laboratory in number and quantity required for testing.

2. Test mortar and materials specified.

3. Mortar:

a. Test for compressive strength and water retention according to

ASTM C270.

b. Minimum Mortar compressive strengths 28 days:

1) Type S: 12.4 MPa (1,800 psi).

2) Type N: 5.1 MPa (750 psi).

4. Non Staining Cement: Test for water soluble alkali.

a. Water Soluble Alkali: Maximum 0.03 percent.

5. Sand: Test for deleterious substances, organic impurities, soundness and grading.

1.6 DELIVERY

A. Deliver products in manufacturer's original sealed packaging.

B. Mark packaging, legibly. Indicate manufacturer's name or brand, type, color, production run number, and manufacture date.

C. Before installation, return or dispose of products within distorted, damaged, or opened packaging.

1.7 STORAGE AND HANDLING

A. Store masonry materials under waterproof covers on planking clear of ground.

1. Protect loose, bulk materials from contamination.

04 05 13 - 3

B. Protect products from damage during handling and construction operations.

1.8 WARRANTY

A. Construction Warranty: FAR clause 52.246-21, "Warranty of

Construction."

PART 2 - PRODUCTS

2.1 MATERIALS

A. Hydrated Lime: ASTM C207, Type S.

B. Aggregate for Masonry Mortar: ASTM C144 and as follows:

1. Light colored sand for mortar for laying face brick.

2. Test sand for color value according to ASTM C40/C40M. Sand producing color darker than specified standard is unacceptable.

C. Blended Hydraulic Cement: ASTM C595/C595M, Type IS, IP.

D. Masonry Cement: ASTM C91/C91M. Type N, S, Or M.

1. Use white masonry cement whenever white mortar is specified.

E. Mortar Cement: ASTM C1329/C1329M, Type N, S or M.

F. Portland Cement: ASTM C150/C150M, Type I.

1. Use white Portland cement wherever white mortar is specified.

G. Pigments: ASTM C979/C979M; inorganic, inert, mineral pigments only, unaffected by atmospheric conditions, nonfading, alkali resistant, and water insoluble.

H. Water: Potable, free of substances that are detrimental to mortar, masonry, and metal.

2.2 PRODUCTS - GENERAL

A. Basis of Design: Section 09 06 00, SCHEDULE FOR FINISHES.

B. Provide each product from one manufacturer

2.3 MIXES

A. Pointing Mortar for New Work:

1. For Cast Stone or Precast Concrete: Proportion by volume; one part white Portland cement, two parts white sand, and 1/5 part hydrated lime.

2. Pointing Mortar for Glazed Structural Facing Tile:

04 05 13 - 4

a. Proportion by volume: One part white Portland cement, two parts of graded white sand passing Number 50 sieve, and 1/8 part hydrated lime.

B. Tuck Pointing Mortar for Repair Work: Tuck pointing mortar specified in

Section 04 01 00, MAINTENANCE OF MASONRY.

C. Masonry Mortar: ASTM C270.

1. Admixtures:

a. Do not use mortar admixtures, and color admixtures unless approved by Contracting Officer's Representative.

b. Do not use antifreeze compounds.

PART 3 - (review with architect)EXECUTION

3.1 PREPARATION

A. Examine and verify substrate suitability for product installation.

B. Protect existing construction and completed work from damage.

3.2 MIXING

A. Measure ingredients by volume using known capacity container.

B. Mix for 3 to 5 minutes in a mechanically operated mortar mixer.

C. Mix water with dry ingredients in sufficient amount to provide a workable mixture which will adhere to vertical surfaces of masonry units.

D. Mortar Stiffened Because of Water Loss Through Evaporation:

1. Re-temper by adding water to restore to proper consistency and workability.

2. Discard mortar reaching initial set or unused within two hours of mixing.

E. Pointing Mortar:

1. Mix dry ingredients with enough water to produce damp mixture of workable consistency retaining shape when formed into ball.

2. Allow mortar to stand in dampened condition for 60 to 90 minutes.

3. Add water to bring mortar to a workable consistency before use.

3.3 MORTARING

A. Type S Mortar: Use for masonry containing vertical reinforcing bars

(non-engineered) // and engineered reinforced unit masonry work .

04 05 13 - 5

B. Brick Veneer Over Frame Back Up Walls: Use Type S Portland cement-lime mortar.

C. Type N Mortar: Use for other masonry work.

D. Type N Mortar: Use for pointing items and tuck pointing specified.

3.4 FIELD QUALITY CONTROL

A. Field Tests: Performed by testing laboratory specified in Section

01 45 29, TESTING LABORATORY SERVICES.

1. Take and test samples during progress of work according to

ASTM C780.

- - E N D - -

01-01-21

04 05 16 - 1

SECTION 04 05 16

MASONRY GROUTING

PART 1 - GENERAL

1.1 SUMMARY

A. Section Includes: Grout for filling hollow concrete masonry cores.

RELATED WORK

B. Section 03 45 00, PRECAST ARCHITECTURAL CONCRETE: Grout

C. Section 04 20 00, UNIT MASONRY: Grout

D. Section 04 72 00, CAST STONE MASONRY: Grout

E. Section 09 06 00, SCHEDULE FOR FINISHES: Grout Color

F. Section 09 30 13, CERAMIC/PORCELAIN TILING: Ready-Mixed Grout.

G. Section 09 91 00, PAINTING

1.2 APPLICABLE PUBLICATIONS

A. Comply with references to extent specified in this section

American National Standards Institute (ANSI):

A118.6-19 - ............Standard Cement Grouts for Tile Installation.

B. ASTM International (ASTM):

C40/C40M-20 - ..........Organic Impurities in Fine Aggregates for

Concrete.

C150/C150M-20 - ........Portland Cement.

C207-18 - ..............Hydrated Lime for Masonry Purposes.

C404-18 - ..............Aggregates for Masonry Grout.

C476-20 - ..............Grout for Masonry.

C595/C595M-20 - ........Blended Hydraulic Cement.

C979/C979M-16 - ........Pigments for Integrally Colored Concrete.

C1019-19 - .............Sampling and Testing Grout.

1.3 SUBMITTALS

A. Submittal Procedures: Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES. All items indicated below are required submittals requiring Contracting Officer’s Representative (COR) review and approval.

B. Manufacturer's Literature and Data:

1. Description of each product.

C. Sustainable Construction Submittals:

04 05 16 - 2

SPEC WRITER NOTE: Retain sustainable construction submittals appropriate to product.

1. Recycled Content: Identify pre-consumer recycled content percentage by weight.

D. Test Reports: Certify each product complies with specifications.

1. Grout, each type.

2. Cement.

3. Aggregate.

E. Certificates: Certify each product complies with specifications.

1. Blended hydraulic cement.

2. Portland cement.

3. Grout.

4. Hydrated lime.

5. Aggregate.

1.4 QUALITY ASSURANCE

A. Preconstruction Testing:

1. Engage independent testing laboratory to perform tests and submit reports.

a. Deliver samples to laboratory in number and quantity required for testing.

2. Grout:

a. Test compressive strength according to ASTM C1019 standard.

SPEC WRITER NOTE: The nonstaining requirement applies only to grout required to be nonstaining to limestone.

3. Cement:

a. Test for water soluble alkali (nonstaining) when nonstaining cement is specified.

b. Nonstaining cement containing more than 0.03 percent water soluble alkali.

4. Aggregate:

a. Test for deleterious substances, organic impurities, soundness and grading.

1.5 DELIVERY

A. Deliver products in manufacturer's original sealed packaging.

04 05 16 - 3

B. Mark packaging, legibly. Indicate manufacturer's name or brand, type, production run number, and manufacture date.

1.6 STORAGE AND HANDLING

A. Store masonry materials under waterproof covers on planking clear of ground, and protect damage from handling, dirt, stain, water and wind.

B. Protect products from damage during handling and construction operations.

1.7 WARRANTY

A. Construction Warranty: FAR clause 52.246-21, "Warranty of

Construction."

PART 2 - PRODUCTS

2.1 MATERIALS

A. Grout Components:

1. Hydrated Lime: ASTM C207, Type S.

2. Aggregate For Masonry Grout: ASTM C404, Size 8.

3. Portland Cement: ASTM C150, Type I.

4. Water: Potable, free of substances that are detrimental to grout, masonry, and metal.

2.2 MIXES

A. Grout: ASTM C476; fine grout and coarse grout.

PART 3 - EXECUTION

3.1 PREPARATION

A. Examine and verify substrate suitability for product installation.

B. Protect existing construction and completed work from damage.

C. Clean mortar from masonry cells protruding more than 13 mm (1/2 inch) to permit grout flow.

D. Remove debris from grout spaces.

E. Verify reinforcement is correctly placed before placing grout.

3.2 MIXING

A. Mix grout in mechanically operated mixer.

1. Mix grout for five minutes, minimum.

B. Measure ingredients by volume using container of known capacity.

04 05 16 - 4

C. Mix water with grout dry ingredients.

1. Slump Range: 200 to 275 mm (8 to 11 inches).

3.3 GROUTING

A. Install grout according to Section 04 20 00, UNIT MASONRY.

B. Use fine grout for filling wall cavities and hollow concrete masonry units where smallest cell dimension is 50 mm (2 inches) or less.

C. Use either fine grout or coarse grout for filling wall cavities and hollow concrete masonry units where smallest cell dimension is greater than 50 mm (2 inches).

D. Use grout for filling bond beam or lintel units.

08-01-17

04 20 00 - 1

SECTION 04 20 00

UNIT MASONRY

PART 1 - GENERAL

1.1 SUMMARY

A. Section Includes: Concrete masonry unit (CMU) assemblies for:

1. Exterior walls.

2. Interior walls and partitions.

1.2 RELATED REQUIREMENTS

A. Sealants and Sealant Installation: Section 07 92 00, JOINT SEALANTS.

B. Color and Texture of Masonry Units: Section 09 06 00, SCHEDULE FOR

FINISHES.

1.3 APPLICABLE PUBLICATIONS

A. Comply with references to extent specified in this section.

B. American Concrete Institute (ACI):

1. 315-99 - Details and Detailing of Concrete Reinforcement.

2. 530.1/ASCE 6/TMS 602-13 - Specification for Masonry Structures.

C. ASTM International (ASTM):

1. A951/A951M-14 - Steel Wire for Masonry Joint Reinforcement.

2. A1064/A1064M-15 - Carbon-Steel Wire and Welded Wire Reinforcement, Plain and Deformed, for Concrete.

3. C55-14a - Concrete Building Brick.

4. C90-14 - Load-Bearing Concrete Masonry Units.

5. D1056-14 - Flexible Cellular Materials - Sponge or Expanded Rubber.

6. F1667-15 - Driven Fasteners: Nails, Spikes, and Staples.

D. American Welding Society (AWS):

1. D1.4/D1.4M-11 - Structural Welding Code - Reinforcing Steel.

E. Federal Specifications (Fed. Spec.):

1. FF-S-107C(2) - Screws, Tapping and Drive.

1.4 SUBMITTALS

A. Submittal Procedures: Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES.

B. Submittal Drawings:

1. Fabrication, bending, and placement of reinforcing bars. Comply with

ACI 315. Show bar schedules, diagrams of bent bars, stirrup spacing, lateral ties and other arrangements and assemblies.

04 20 00 - 2

2. Special masonry shapes, profiles, and placement.

3. Masonry units for typical window and door openings, and, for special conditions as affected by structural conditions.

C. Manufacturer's Literature and Data:

1. Description of each product.

2. Installation instructions.

D. Samples:

1. Concrete masonry units, when exposed in finish work.

2. Anchors and Ties: Each type.

3. Joint Reinforcing: 1200 mm (48 inches) long each type.

E. Sustainable Construction Submittals:

1. Recycled Content: Identify post-consumer and pre-consumer recycled content percentage by weight.

F. Test reports: Certify products comply with specifications.

G. Certificates: Certify products comply with specifications.

1. Solid and load-bearing concrete masonry units, including fire-resistant rated units.

H. Delegated Design Drawings and Calculations: Signed and sealed by responsible design professional.

1.5 QUALITY ASSURANCE

A. Welders and Welding Procedures Qualifications: AWS D1.4/D1.4M.

B. Mockups:

1. Before starting masonry, build a mockup panel minimum 1800 mm by

1800 mm (6 feet by 6 feet) with 600 mm (24 inch) 90 degree return for outside corner.

a. Use masonry units from random cubes of units delivered on site.

b. Include structural backup, reinforcing, ties, and anchors.

2. Mockup panel approved by Contracting Officer's Representative set workmanship and aesthetic quality for masonry work.

3. Clean sample panel to test cleaning methods.

4. Remove mockup panel when directed by Contracting Officer's

Representative.

1.6 DELIVERY

A. Deliver products in manufacturer's original sealed packaging.

04 20 00 - 3

B. Mark packaging, legibly. Indicate manufacturer's name or brand, type, color, production run number, and manufacture date.

C. Before installation, return or dispose of products within distorted, damaged, or opened packaging.

1.7 STORAGE AND HANDLING

A. Store products above grade, protected from contamination.

B. Protect products from damage during handling and construction operations.

1.8 FIELD CONDITIONS

A. Hot and Cold Weather Requirements: Comply with

ACI 530.1/ASCE 6/TMS 602.

1.9 WARRANTY

A. Construction Warranty: FAR clause 52.246-21, "Warranty of

Construction."

PART 2 - PRODUCTS

2.1 SYSTEM PERFORMANCE

A. Delegated Design: Prepare submittal documents including design calculations and drawings signed and sealed by registered design professional, licensed in state where work is located.

2.2 PRODUCTS - GENERAL

A. Basis of Design: Section 09 06 00, SCHEDULE FOR FINISHES.

B. Provide each product from one manufacturer and from one production run.

C. Sustainable Construction Requirements:

1. Concrete Masonry Unit Recycled Content: 30% total recycled content, minimum.

a. Pre-Consumer Recycled Content: 30% minimum.

2. Steel Recycled Content: 30 percent total recycled content, minimum.

2.3 UNIT MASONRY PRODUCTS

A. Concrete Masonry Units (CMU):

1. Hollow and Solid Load-Bearing Concrete Masonry Units: ASTM C90.

a. Unit Weight: Normal weight.

2. Sizes:

04 20 00 - 4

a. Modular, 200 mm by 400 mm (8 inches by 16 inches) nominal face dimension; thickness as indicated on drawings.

1) Polished Face, Textured as indicated in Section

09 06 00, SCHEDULE FOR FINISHES

2) Polished face, Smooth as indicated in Section 09 06 00, SCHEDULE FOR FINISHES

b. Modular, 300 mm by 600 mm (12 inches by 24 inches) nominal face dimension; thickness as indicated on drawings.

1) Polished Face, Textured as indicated in Section

09 06 00, SCHEDULE FOR FINISHES

3. Polished face, Smooth as indicated in Section 09 06 00, SCHEDULE FOR

FINISHES For molded faces used as a finished surface, use concrete masonry units with uniform fine to medium surface texture unless specified otherwise. See Section 09 06 00, SCHEDULE FOR FINISHES

2.4 ANCHORS, TIES, AND REINFORCEMENT

A. Steel Reinforcing Bars: ASTM A615/A615M; Grade 60, deformed bars.

B. Joint Reinforcement:

1. Form from wire complying with ASTM A951/A951M.

2. Hot dipped galvanized after fabrication.

3. Width of joint reinforcement 40 mm (1.6 inches) less than nominal thickness of masonry wall or partition.

4. Cross wires welded to longitudinal wires.

5. Joint reinforcement minimum 3000 mm (10 feet) long, factory cut.

6. Joint reinforcement with crimp formed drip is not acceptable.

7. Maximum spacing of cross wires 400 mm (16 inch) to longitudinal wires.

8. Trussed Design:

a. Longitudinal and cross wires minimum 4 mm (0.16 inch nominal) diameter.

C. Adjustable Veneer Anchor for Framed Walls:

1. Two piece, adjustable anchor and tie.

2. Anchor and tie may be either loop or angle type; provide only one type throughout.

3. Loop Type:

04 20 00 - 5

a. Anchor: Screw-on galvanized steel anchor strap 2.75 mm

(0.11 inch) by 19 mm (3/4 inch) wide by 225 mm (9 inches) long, with 9 mm (0.35 inch) offset and 100 mm (4 inch) adjustment. Provide 5 mm (0.20 inch) hole at each end for fasteners.

b. Ties: Triangular tie, fabricated of 5 mm (0.20 inch) diameter galvanized cold drawn steel wire. Ties long enough to engage anchor and be embedded minimum 50 mm (2 inches) into bed joint of masonry veneer.

4. Angle Type:

a. Anchor: Minimum 2 mm (16 gage) thick galvanized steel angle shaped anchor strap. Provide hole in vertical leg for fastener. Provide hole near end of outstanding leg to suit upstanding portion of tie.

b. Tie: Fabricate from 5 mm (0.20 inch) diameter galvanized cold drawn steel wire. Form "L" shape to be embedded minimum 50 mm

(2 inches) into the bed joint of masonry veneer and provide upstanding leg to fit through hole in anchor and be long enough to allow 50 mm (2 inches) of vertical adjustment.

D. Individual Ties:

1. Rectangular ties: Form from 5 mm (3/16 inch) diameter galvanized steel rod to rectangular shape minimum 50 mm (2 inches) wide by sufficient length for ends of ties to extend within 25 mm

(1 inch) of each face of wall. Ties that are crimped to form drip are not acceptable.

2. Adjustable Cavity Wall Ties:

a. Adjustable wall ties may be furnished at Contractor's option.

b. Two piece type permitting up to 40 mm (1-1/2 inch) adjustment.

c. Form ties from 5 mm (3/16 inch) diameter galvanized steel wire.

d. Form one piece to rectangular shape 105 mm (4-1/8 inches) wide by length required to extend into bed joint 50 mm

(2 inches).

e. Form other piece to 75 mm (3 inch) long by 75 mm (3 inch) wide shape, having 75 mm (3 inch) long bent section for

04 20 00 - 6 engaging 105 mm (4-1/8 inch) wide piece to form adjustable connection.

E. Adjustable Steel Column Anchor:

1. Two-piece anchor consisting of a 6 mm (1/4 inch) diameter steel rod to be welded to steel with offset ends, rod to permit 100 mm

(4 inch) vertical adjustment of wire anchor.

2. Triangular shaped wire anchor 100 mm (4 inches) wide formed from 5

(3/16 inch) diameter galvanized wire, to extend minimum 75 mm

(3 inches) into joints of masonry.

F. Adjustable Steel Beam Anchor:

1. Z or C type steel strap, 30 mm (1 1/4 inches) wide, 3 mm (1/8 inch) thick.

2. Flange hook minimum 38 mm (1 1/2 inches) long.

3. Length to embed in masonry minimum 50 mm (2 inches) in 100 mm

(4 inch) nominal thick masonry and 100 mm (4 inches) in thicker masonry.

4. Bend masonry end minimum 40 mm (1 1/2 inches).

2.5 ACCESSORIES

A. Weeps:

1. Weep Hole Wicks: Glass fiber ropes, 10 mm (3/8 inch) minimum diameter, 300 mm (12 inches) long.

2. Weep Tubing: Round, polyethylene, 9 mm (3/8 inch) diameter, 100 mm

(4 inches) long.

3. Weep Hole: Flexible PVC louvered configuration with rectangular closure strip at top.

B. Cavity Drain Material: Open mesh polyester sheets or strips to prevent mortar droppings from clogging the cavity.

C. Preformed Compressible Joint Filler:

1. Thickness and depth to fill joint.

2. Closed Cell Neoprene: ASTM D1056, Type 2, Class A, Grade 1, B2F1.

3. Non-Combustible Type: ASTM C612, Type 5, Max. Temp.1800 degrees F.

D. Box Board:

1. Mineral Fiber Board: ASTM C612, Type 1.

2. 25 mm (1 inch) thickness.

3. Other spacing material having similar characteristics is acceptable subject to Contracting Officer's Representative's approval.

04 20 00 - 7

E. Masonry Cleaner:

1. Detergent type cleaner selected for each type masonry.

2. Acid cleaners are not acceptable.

3. Use soap less type specially prepared for cleaning brick or concrete masonry as appropriate.

F. Fasteners:

1. Screws: FS-FF-S-107, Type A, AB, SF thread forming or cutting.

G. Welding Materials: AWS D1.4/D1.4M, type to suit application.

PART 3 - EXECUTION

3.1 INSTALLATION - GENERAL

A. Install products according to manufacturer's instructions and approved submittal drawings.

1. When manufacturer's instructions deviate from specifications, submit proposed resolution for Contracting Officer's Representative consideration.

B. Keep finish work free from mortar smears or spatters, and leave neat and clean.

C. Wall Openings:

1. Fill hollow metal frames built into masonry walls and partitions solid with mortar as laying of masonry progresses.

2. When items are not available when walls are built, prepare openings for subsequent installation.

D. Tooling Joints:

1. Do not tool until mortar has stiffened enough to retain thumb print when thumb is pressed against mortar.

2. Tool while mortar is soft enough to be compressed into joints and not raked out.

3. Finish joints in exterior face masonry work with jointing tool, and provide smooth, water-tight concave joint unless specified otherwise.

4. Tool Exposed interior joints in finish work concave unless specified

E. Use minimum 100 mm (4 inches) nominal thick masonry for fireproofing steel columns unless indicated otherwise.

04 20 00 - 8

F. Before connecting new masonry with previously laid masonry, remove loosened masonry or mortar, and clean and wet work in place as specified under wetting.

G. Structural Steel Encased in Masonry:

1. Where structural steel is encased in masonry and voids between steel and masonry are filled with mortar, provide minimum 25 mm

(1 inch) mortar free expansion space between masonry and steel by applying box board material to steel before masonry is laid.

2. Do not install spacing material where steel is bearing on masonry or masonry is bearing on steel.

H. Chases:

1. Do not install chases in masonry walls and partitions exposed to view in finished work, including painted or coated finishes on masonry.

2. Masonry 100 mm (4 inch) nominal thick may have electrical conduits

25 mm (1 inch) or less in diameter when covered with soaps, or other finishes.

3. Fill recess chases after installation of conduit, with mortar and finish flush.

4. When pipes or conduits, or both occur in hollow masonry unit partitions retain minimum one web of hollow masonry units.

I. Wetting and Wetting Test:

1. Test and wet brick and clay tile according to BIA TN 11B.

2. Do not wet concrete masonry units or glazed structural facing tile before laying.

J. Temporary Formwork: Provide formwork and shores as required for temporary support of reinforced masonry elements.

K. Construct formwork to conform to shape, line and dimensions indicated on drawings. Make sufficiently tight to prevent mortar, grout, or concrete leakage. Brace, tie and support formwork as required to maintain position and shape during construction and curing of reinforced masonry.

L. Do not remove forms and shores until reinforced masonry members have hardened sufficiently to carry their own weight and other reasonable temporary construction loads.

M. Minimum Curing Times Before Removing Shores and Forms:

04 20 00 - 9

1. Girders and Beams: 10 days.

2. Slabs: 7 days.

3. Reinforced Masonry Soffits: 7 days.

3.2 INSTALLATION - ANCHORAGE

A. Veneer to Framed Walls:

1. Install adjustable veneer anchors.

2. Fasten anchor to stud through sheathing with self-drilling and tapping screw, one at both ends of loop type anchor.

3. Space anchors maximum 400 mm (16 inches) on center vertically at each stud.

B. Veneer to Concrete Walls:

1. Anchor new masonry facing to existing concrete with adjustable cavity wall ties spaced at 400 mm, (16 inches) maximum vertical intervals, and at 400 mm (16 inches) maximum horizontal intervals. Fasten ties to concrete with power actuated fasteners or concrete nails.

C. Masonry Facing to Backup and Cavity Wall Ties:

1. Use individual ties for new work.

2. Stagger ties in alternate courses, and space at 400 mm (16 inches) maximum vertically, and 400 mm (16 inches) horizontally.

3. At openings, provide additional ties spaced maximum 900 mm

(36 inches) apart vertically around perimeter of opening, and within 300 mm (12 inches) from edge of opening.

4. Anchor new masonry facing to existing masonry with adjustable cavity wall ties spaced at 400 mm (16 inch) maximum vertical intervals and at every second masonry unit horizontally. Fasten ties to masonry with masonry nails.

5. Option: Install joint reinforcing for multiple wythes and cavity wall ties spaced maximum 400 mm (16 inches) vertically.

6. Tie interior and exterior wythes of reinforced masonry walls together with individual ties. Provide ties at intervals maximum

400 mm (16 inches) on center horizontally, and 400 mm (16 inches) on center vertically. Lay ties in the same line vertically in order to facilitate vibrating of the grout pours.

D. Anchorage of Abutting Masonry:

04 20 00 - 10

1. Anchor interior 100 mm (4 inch) thick masonry partitions to exterior walls with wall ties. Space ties at 600 mm (24 inches) maximum vertical intervals. Extend ties 100 mm (4 inches) minimum into masonry.

2. Anchor interior masonry bearing walls or interior masonry partitions over 100 mm (4 inches) thick to walls with rigid wall anchors spaced at 400 mm (16 inch) maximum vertical intervals.

3. Anchor abutting interior masonry partitions to existing concrete and existing masonry construction, with adjustable wall ties. Extend ties minimum 100 mm (4 inches) into joints of new masonry. Fasten ties to existing concrete and masonry construction, with powder actuated drive pins, nail or other means that provides rigid anchorage. Install anchors at 400 mm (16 inch) maximum vertical intervals.

E. Masonry Furring:

1. Anchor masonry furring less than 100 mm (4 inches) nominal thick to masonry walls or to concrete with adjustable wall ties or dovetail anchors.

2. Space at maximum 400 mm (16 inches) on center in both directions.

F. Anchorage to Steel Beams or Columns:

1. Use adjustable beam anchors on each flange.

2. At columns weld steel rod to steel columns at 300 mm (12 inch) intervals, and place wire ties in masonry courses at 400 mm

(16 inches) maximum vertically.

3.3 INSTALLATION - REINFORCEMENT

A. Joint Reinforcement:

1. Install joint reinforcement in CMU wythe of combination brick and

CMU, cavity walls, and single wythe concrete masonry unit walls or partitions.

2. Reinforcing is acceptable in lieu of individual ties for anchoring brick facing to CMU backup in exterior masonry walls.

3. Locate joint reinforcement in mortar joints at 400 mm (16 inch) maximum vertical intervals.

4. Additional joint reinforcement is required in mortar joints at both

200 mm (8 inches) and 400 (16 inches) above and below windows, doors, louvers and similar openings in masonry.

04 20 00 - 11

5. Wherever brick masonry is backed up with stacked bond masonry, install multiple wythe joint reinforcement in every two courses of CMU backup, and in corresponding joint of facing brick.

3.4 INSTALLATION - CMU CONTROL JOINTS

A. Provide CMU control joints (CJ) where indicated on drawings.

B. Keep joint free of mortar and other debris.

C. Joints Occur In Masonry Walls:

1. Install preformed compressible joint filler in brick wythe.

2. Install cross shaped shear keys in concrete masonry unit wythe with preformed compressible joint filler on both sides of shear key.

D. Use standard notched concrete masonry units (sash blocks) made in full and half-length units where shear keys are used to create a continuous vertical joint.

E. Interrupt joint reinforcement at expansion and control joints.

F. Fill opening in exposed face of expansion and control joints with sealant as specified in Section 07 92 00, JOINT SEALANTS.

3.5 INSTALLATION - BUILDING EXPANSION AND SEISMIC JOINTS

A. Keep expansion and seismic joints open and free of mortar. Remove mortar and other debris.

B. Install non-combustible, compressible type joint filler to fill space completely except where sealant is shown on joints in exposed finish work.

C. Fill opening in exposed face of expansion and seismic joints with sealant as specified in Section 07 92 00, JOINT SEALANTS.

3.6 INSTALLATION - ISOLATION JOINT

A. Where full height walls and partitions lie parallel or perpendicular to and under structural beams and shelf angles, provide minimum 9 mm

(3/8 inch) separation between walls and partitions and bottom of beams and shelf angles.

B. Insert continuous full width strip of non-combustible type compressible joint filler.

C. Fill opening in exposed face of isolation joints with sealant as specified in Section 07 92 00, JOINT SEALANTS.

3.7 INSTALLATION - CONCRETE MASONRY UNITS

A. Types and Uses:

04 20 00 - 12

1. Provide special concrete masonry shapes as required, including lintel and bond beam units, sash units, and corner units. Provide solid concrete masonry units, where full units cannot be installed, or where needed for anchorage of accessories.

2. Provide solid load-bearing concrete masonry units or grout cell of hollow units at jambs of openings in walls, where structural members impose loads directly on concrete masonry, and where shown.

B. Laying:

1. Lay concrete masonry units with 9 mm (3/8 inch) joints, with a bond overlap of minimum 1/4 of unit length, except where stack bond is indicated on drawings.

2. Do not wet concrete masonry units before laying.

3. Bond external corners of partitions by overlapping alternate courses.

4. Lay first course in a full mortar bed.

5. Set anchorage items as work progress.

6. Provide 6 mm (1/4 inch) open joint for sealant between existing construction, exterior walls, concrete work, and abutting masonry partitions.

7. Lay concrete masonry units with full face shell mortar beds and fill head joint beds for depth equivalent to face shell thickness.

8. Do not wedge masonry against steel reinforcing. Minimum 13 mm

(1/2 inch) clear distance between reinforcing and masonry units.

9. At time of placement, ensure steel reinforcement is free of loose rust, mud, oil, and other contamination capable of affecting bond.

10. Place steel reinforcement at spacing indicated on drawings before grouting.

11. Splice reinforcement or attach reinforcement to dowels by placing in contact and securing with wire ties.

12. Rake joints 6 to 10 mm (1/4 to 3/8 inch) deep for pointing with colored mortar when colored mortar is not full depth.

C. Waterproofing Parging:

04 20 00 - 13

1. Parge earth side of concrete masonry unit walls at below-grade locations with mortar applied in two coats, each coat 6 mm

(1/4 inch) thick.

2. Clean wall surfaces to receive parging of dirt, oil, or grease, and moisten before application of first coat.

3. Roughen first coat when partially set, permit to hardened for 24 hours, and moisten before application of second coat.

4. Keep second coat damp for minimum 48 hours.

5. Thicken parging and round to form a cove at the junction of outside wall face and footing.

3.8 POINTING

A. Fill joints with pointing mortar using rubber float trowel to apply mortar solidly into raked joints.

B. Wipe off excess mortar from joints of glazed masonry units with dry cloth.

C. Tool exposed joints to smooth concave joint.

D. At joints with existing work, match existing joint.

3.9 PLACING REINFORCEMENT

A. General: Clean reinforcement of loose rust, mill scale, earth, ice or other materials which will reduce bond to mortar or grout. Do not use reinforcement bars with kinks or bends not shown on drawings or approved submittal drawings, or bars with reduced cross-section due to excessive rusting or other causes.

B. Position reinforcement accurately at spacing indicated on drawings.

Support and secure vertical bars against displacement. Install horizontal reinforcement as masonry work progresses. Where vertical bars are shown in close proximity, provide clear distance between bars of minimum one bar diameter or 25 mm (1 inch), whichever is greater.

C. Splice reinforcement bars only where indicated on drawings, unless approved by Contracting Officer's Representative. Provide lapped splices. In splicing vertical bars or attaching to dowels, lap ends, place in contact and wire tie.

D. Provide minimum lap as indicated on approved submittal drawings, or if not indicated, minimum 48 bar diameters.

04 20 00 - 14

E. Embed metal ties in mortar joints as work progresses, with minimum mortar cover of 15 mm (5/8 inch) on exterior face of walls and 13 mm

(1/2 inch) at other locations.

F. Embed prefabricated horizontal joint reinforcement as work progresses, with minimum cover of 15 mm (5/8 inch) on exterior face of walls and

13 mm (1/2 inch) at other locations. Lap joint reinforcement minimum

150 mm (6 inches) at ends. Use prefabricated “L” and “T” sections to provide continuity at corners and intersections. Cut and bend joint reinforcement for continuity at returns, offsets, column fireproofing, pipe enclosures and other special conditions.

G. Anchoring: Anchor reinforced masonry work to supporting structure as indicated on drawings.

H. Anchor reinforced masonry walls at intersections with non-reinforced masonry.

3.10 INSTALLATION OF REINFORCED CONCRETE UNIT MASONRY

A. Do not wet concrete masonry units (CMU).

B. Lay CMU units with full-face shell mortar beds. Fill vertical head joints (end joints between units) solidly with mortar from face of unit to distance behind face equal to thickness of longitudinal face shells. Solidly bed cross-webs of starting courses in mortar. Maintain head and bed 9 mm (3/8 inch) joint widths.

C. Where solid CMU units are shown, lay with full mortar head and bed joints.

D. Walls:

1. Pattern Bond: Lay CMU wall units in 1/2-running bond with vertical joints in each course centered on units in courses above and below, unless otherwise indicated. Bond and interlock each course at corners and intersections. Use special-shaped units where shown, and as required for corners, jambs, sash, control joints, lintels, bond beams and other special conditions.

2. Maintain vertical continuity of core or cell cavities, which are to be reinforced and grouted, to provide minimum clear dimension indicated and to provide minimum clearance and grout coverage for vertical reinforcement bars. Keep cavities free of mortar.

Solidly bed webs in mortar where adjacent to reinforced cores or cells.

04 20 00 - 15

3. Where horizontally reinforced beams (bond beams) are indicated on drawings, use special units or modify regular units to allow for placement of continuous horizontal reinforcement bars. Place small mesh expanded metal lath or wire screening in mortar joints under bond beam courses over cores or cells of non-reinforced vertical cells, or provide units with solid bottoms.

E. Columns, Piers and Pilasters:

1. Use CMU units of size, shape and shown. If not shown, use units which provide minimum clearances and grout coverage for number and size of vertical reinforcement bars shown.

2. Provide pattern bond shown, or if not shown, alternate head joints in vertical alignment.

F. Grouting:

1. Use fine grout for filling spaces less than 100 mm (4 inches) in one or both horizontal directions.

2. Use coarse grout for filling 100 mm (4 inch) spaces or larger in both horizontal directions.

3. Grouting Technique: At Contractor’s option, use either low-lift or high-lift grouting techniques.

G. Low-Lift Grouting:

1. Provide minimum clear dimension of 50 mm (2 inches) and clear area of 5160 sq. mm (8 sq. inches) in vertical cores to be grouted.

2. Place vertical reinforcement before grouting of CMU. Extend above elevation of maximum pour height as required for splicing.

Support in position at vertical intervals not exceeding 192 bar diameters nor 3 m (10 feet).

3. Lay CMU to maximum pour height. Do not exceed 1.5 m (5 feet) height, or if bond beam occurs below 1.5 m (5 feet) height, stop pour

38 mm (1-1/2 inches) below top of bond beam.

4. Rod or vibrate grout during placing. Place grout continuously; do not interrupt pouring of grout for more than one hour. Terminate grout pours 38 mm (1-1/2 inches) below top course of pour.

5. Bond Beams: Stop grout in vertical cells 38 mm (1-1/2 inches) below bond beam course. Place horizontal reinforcement in bond beams;

lap at corners and intersections as indicated on drawings. Place

04 20 00 - 16 grout in bond beam course before filling vertical cores above bond beam.

3.11 CONSTRUCTION TOLERANCES

A. Lay masonry units plumb, level and true to line within tolerances according to ACI 530.1/ASCE 6/TMS 602 and as follows:

B. Maximum variation from plumb:

1. In 3000 mm (10 feet) - 6 mm (1/4 inch).

2. In 6000 mm (20 feet) - 9 mm (3/8 inch).

3. In 12,000 mm (40 feet) or more - 13 mm (1/2 inch).

C. Maximum variation from level:

1. In any bay or up to 6000 mm (20 feet) - 6 mm (1/4 inch).

2. In 12,000 mm (40 feet) or more - 13 mm (1/2 inch).

D. Maximum variation from linear building lines:

1. In any bay or up to 6000 mm (20 feet) - 13 mm (1/2 inch).

2. In 12,000 mm (40 feet) or more - 19 mm (3/4 inch).

E. Maximum variation in cross-sectional dimensions of columns and thickness of walls from dimensions shown:

1. Minus 6 mm (1/4 inch).

2. Plus 13 mm (1/2 inch).

F. Maximum variation in prepared opening dimensions:

1. Accurate to minus 0 mm (0 inch).

2. Plus 6 mm (1/4 inch).

3.12 CLEANING AND REPAIR

A. General:

1. Clean exposed masonry surfaces on completion.

2. Protect adjoining construction materials and landscaping during cleaning operations.

3. Cut out defective exposed new joints to depth of approximately 19 mm

(3/4 inch) and repoint.

4. Remove mortar droppings and other foreign substances from wall surfaces.

B. Concrete Masonry Units:

1. Immediately following setting, brush exposed surfaces free of mortar or other foreign matter.

2. Allow mud to dry before brushing.

04 20 00 - 17

04 72 00 - 1

SECTION 04 72 00

CAST STONE MASONRY

PART 1 - GENERAL

1.1 DESCRIPTION

A. This section specifies manufactured concrete units to simulate a natural stone.

B. Installation of cast stone units.

1.2 RELATED WORK

A. Section 04 05 13, MASONRY MORTARING, Setting and pointing mortar.

B. Section 04 05 16, MASONRY GROUTING, Setting and pointing mortar.

C. Section 07 92 00, JOINT SEALANTS, Joint sealant and application.

D. Section 09 06 00, SCHEDULE FOR FINISHES, Color and texture.

1.3 SUBMITTALS

A. Submit in accordance with Section 01 33 23, SHOP DRAWINGS, PRODUCT

DATA, AND SAMPLES. All items indicated below are required submittals requiring Contracting Officer’s Representative (COR) review and approval.

B. Samples:

1. Cast stone, sample panel, size 100 by 300 by 300 mm (4 by 12 by 12 inches) each color and finish.

2. Show finish on two 100 mm (4-inch) edges and 300 by 300 mm (12 by 12 inch) surface.

C. Shop Drawings:

1. Cast stone showing exposed faces, profiles, cross sections, anchorage, reinforcing, jointing and sizes.

2. Setting drawings with setting mark.

D. Certificates: Test results indicating that the cast stone meets specification requirements and proof of plant certification.

E. Submit manufacturers test results of cast stone previously made by manufacturer.

F. Laboratory Data: Description of testing laboratories facilities and qualifications of its principals and key personnel.

G. List of jobs furnished by the manufacturer, which were similar in scope and at least three (3) years of age.

1.4 PRODUCT DELIVERY, STORAGE AND HANDLING

A. Store cast stone under waterproof covers on planking clear of ground.

04 72 00 - 2

B. Protect from handling, dirt, stain, and water damage.

C. Mark production units with the identification marks as shown on the shop drawings.

D. Package units and protect them from staining or damage during shipping and storage.

E. Provide an itemized list of product to support the bill of lading.

1.5 WARRANTY

A. Warranty exterior masonry walls against moisture leaks, any defects and subject to terms of "Warranty of Construction", FAR clause 52.246-21, except that warranty period shall be two years.

1.6 APPLICABLE PUBLICATIONS

A. Publications listed below form a part of this specification to extent referenced. Publications are referenced in text by the basic designation only. Comply with applicable provisions and recommendations of the following, except as otherwise shown or specified.

B. Cast Stone Institute Technical Manual and Cast Stone Institute standard specifications.

C. ASTM International(ASTM):

A167-99(R2009)..........Stainless and Heat Resisting Chromium-Nickel

Steel Plate, Sheet, and Strip

A615/A615M-20...........Standard Specification for Deformed and Plain

Carbon Steel Bars for Concrete Reinforcement

A1064/A1064M-18a........Standard Specification for Carbon-Steel Wire and Welded Wire Reinforcement, Plain and

Deformed, for Concrete

C33/C33M-18.............Standard Specification for Concrete Aggregates

C150/C150M-20...........Standard Specification for Portland Cement

C979/C979M-16...........Standard Specification for Pigments for

Integrally Colored Concrete

C1194-19................Standard Test Method for Compressive Strength of Architectural Cast Stone

C1195-19a...............Standard Test Method for Absorption of

Architectural Cast Stone

C1364-19................Standard Specification for Architectural Cast

Stone.

04 72 00 - 3

D2244-16................Standard Practice for Calculation of Color

Differences from Instrumentally Measured Color

Coordinates.

1.7 QUALITY ASSURANCE

A. The Manufacturer:

1. Must have 5 years minimum continuous operating experience and have facilities for manufacturing cast stone as described herein.

Manufacturer shall have sufficient plant facilities to produce the shapes, quantities and size of cast stone required in accordance with the project schedule.

2. Must be a member of the Cast Stone Institute.

3. Must have a certified plant (certification by the Cast Stone

Institute).

B. Stone setter: Must have 5 years’ experience setting cast or natural building stone.

C. Testing: One (1) sample from production units may be selected at random from the field for each 500 cubic feet (14 meters squared) delivered to the job:

1. Three (3) field cut cube specimens from each of these sample shall have an average minimum compressive strength of not less than 85 percent with no single specimen testing less than 75 percent of design strength as specified.

2. Three (3) field cut cube specimens from each of these samples shall have an average maximum cold-water absorption of 6 percent.

3. Field specimens shall be tested in accordance with ASTMC 1194 and C

1195.

4. Manufacturer shall submit a written list of projects similar and at least three (3) years of age, along with owner, architect and contractor references.

1.8 MANUFACTURING TOLERANCES

A. Cross section dimensions shall not deviate by more than + 1/8 inch (3

mm) from approved dimension.

B. Length of units shall not deviate by more than length /360 or + 1/8 inch (3mm), whichever is greater, not to exceed + 1/4 inch (6 mm).

Maximum length of any unit shall not exceed 15 times the average thickness of such unit unless otherwise agreed by the manufacturer.

04 72 00 - 4

C. Warp bow or twist of units shall not exceed length/360 or + 1/8 inch (3 mm), whichever is greater.

D. Location of dowel holes, anchor slots, flashing grooves, false joints and similar features – On formed sides of unit, 1/8 inch (3 mm), on unformed sides of unit, 3/8 inch (9 mm) maximum deviation.

1.9 MOCK-UP

A. Provide full size unit(s) for use in construction of sample wall. The mock-up becomes the standard of workmanship for the project.

PART 2 - PRODUCTS

2.1 ARCHITECTURAL CAST STONE

A. Comply with ASTM C 1364

B. Physical properties: Provide the following:

1. Compressive Strength – ASTM C 1194: 6,500 psi (45 Mpa) minimum for products at 28 days.

2. Absorption – ASTM C 1195: 6 percent maximum by the cold water method, or 10 percent maximum by the boiling method for products as

28 days.

3. Air Content – ASTM C173 or C231, for wet cast product shall be 4-8 percent for units exposed to freeze-thaw environments. Air entrainment is not required for vibrant dry tamp (VDT) products.

4. Freeze thaw - ASTM C 1364L The cumulative percent weight loss (CPWL) shall be less than 5 percent after 300 cycles of freezing and thawing.

5. Linear Shrinkage - ASTM C 426L Shrinkage shall not exceed 0.065 percent.

C. Job site testing – One (1) sample from production units may be selected at random from the field for each 500 cubic feet (14 cubic meters) delivered to the job site:

1. Three (3) field cut cube specimens from each of these samples shall have an average minimum compressive strength of not less than 85 percent with no single specimen testing less than 75 percent of design strength as allowed by ACI 318.

2. Three (3) field cut cube specimens from each of these samples shall have an average maximum cold-water absorption of 6 percent.

3. Field specimens shall be tested in accordance with ASTM C 1194 and C

1195.

04 72 00 - 5

2.2 RAW MATERIALS

A. Portland cement – Type I or Type III, white and/or grey, ASTM C 150.

B. Coarse aggregates – Granite, quartz or limestone, ASTM C 33, except for gradation, and are optional for the vibrant dry tamp (VDT) casting method.

C. Fine aggregates – Manufactured or natural sands, ASTM C 33, except for gradation.

D. Colors – Inorganic iron oxide pigments, ASTM C 979 except that carbon black pigments shall not be used.

E. Admixtures- Comply with the following:

1. ASTM C 260 for air-entraining admixtures.

2. ASTM C 494/C 495 M Types A-G for water reducing, retarding, accelerating and high range admixtures.

3. Other admixtures: integral water repellents and other chemicals, for which no ASTM Standard exists, shall be previously established as suitable for use in concrete by proven field performance or through laboratory testing.

4. ASTM C 618 mineral admixtures of dark and variable colors shall not be used in surfaces intended to be exposed to view.

5. ASTM C 989 granulated blast furnace slag may be used to improve physical properties. Tests are required to verify these features.

F. Water – Potable

G. Reinforcing bars:

1. ASTM A 615/A 615M. Grade 40 or 60 steel galvanized or epoxy coated when cover is less than 1.5 inch (37 mm).

2. Welded Wire Fabric: ASTM A 1064 where applicable for wet cast units.

H. All anchors, dowels and other anchoring devices and shims shall be standard building stone anchors commercially available in a non-corrosive material such as zinc plated, galvanized steel, brass, or stainless steel Type 302 or 304.

2.3 COLOR AND FINISH

A. Match sample on file.

B. All surfaces intended to be exposed to view shall have a fine-grained texture similar to natural stone, with no air voids in excess of 1/32 inch (0.8 mm) and the density of such voids shall be less than 3

04 72 00 - 6 occurrences per any 1 inch (25 mm) and not obvious under direct daylight illumination at a 5 feet (1.5 meters) distance.

C. Units shall exhibit a texture approximately equal to the approved sample when viewed under direct daylight illumination at a 10 feet (3 meters) distance.

D. ASTM D 2244 permissible variation in color between units of comparable age subjected to similar weathering exposure.

1. Total color difference – not greater than 6 units.

2. Total hue difference-not greater than 2 units.

2.4 REINFORCING

A. Reinforce the units as required by the drawings or for safe handling and structural stress.

1. Minimum reinforcing shall be 0.25 percent of the cross section area.

B. Reinforcement shall be non-corrosive where faces exposed to weather are covered with less than 1.5inch (38 mm) of concrete material. All reinforcement shall have minimum coverage of twice the diameter of the bars.

C. Minor chipping resulting from shipment and delivery shall not be grounds for rejection. Minor chips shall not be obvious under direct daylight illumination from a 20 foot (6 meter) distance.

D. The occurrence of crazing or efflorescence shall not constitute a cause for rejection.

E. Remove cement film, if required, from exposed surface prior to packaging for shipment.

2.5 CURING

A. Cure units in a warm curing chamber 100 degrees F (37.8 degrees C) at

95 percent relative humidity for approximately 12 hours, or cure in a

95 percent moist environment at a minimum 70 degrees F (21.1 degrees C) for 16 hours after casting. Additional yard curing at 95 percent relative humidity shall be 350-degree-days (i.e. 7 days @ 50 degrees F

(10.0 degrees C) or 5 days @ 70 degrees F (21.0 degrees C) prior to shipping. Form cured units shall be protected from moisture evaporation with curing blankets or curing compounds after casting.

04 72 00 - 7

PART 3 - EXECUTION

3.1 EXAMINATION

A. Installing contractor shall check cast stone materials for fit and finish prior to installation. Do not set unacceptable units.

3.2 SETTING TOLERANCES

A. Comply with Cast Stone Institute Technical Manual.

B. Set stones 1/8 inch (3 mm) or less, within the plane of adjacent units.

C. Joints, plus – 1/6 inch (1.5 mm), minus – 1/8 inch (3 mm).

3.3 JOINTING

A. Joint size:

1. At stone/CMU joints 3/8 inch (9.5 cm).

2. At stone/CMU joints in vertical position 1/4 inch (6 mm) (3/8 inch

(9.5 mm) optional).

3. Stone/stone joint exposed on top 3/8 inch (.5 mm).

B. Joint Materials:

1. Mortar, Type N, ASTM C 270.

2. Use a full bed of mortar at all bed joints.

3. Flush vertical joints full with mortar.

4. Leave all joints with exposed tops or under relieving angles open for sealant.

5. Leave head joints in coping and projecting components open for sealant.

C. Location of joints:

1. As shown on shop drawings.

2. At control and expansion joints unless otherwise shown.

3.4 SETTING

A. Drench units with clean water prior to setting.

B. Fill dowel holes and anchor slots completely with mortar or non-shrink grout.

C. Set units in full bed of mortar, unless otherwise detailed.

D. Rake mortar joints 3/4 inch (18 mm) for pointing.

E. Remove excess mortar from unit faces immediately after setting.

F. Tuck point unit joints to a slight concave profile.

3.5 JOINT PROTECTION

A. Comply with requirements of Section 07 92 00, JOINT SEALANTS.

04 72 00 - 8

B. Prime ends of units, insert properly sized backing rod and install required sealant.

3.6 REPAIR AND CLEANING

A. Repair chips with…