1-SE-701.pdf
PDF 4 MB Posted
- Solicitation number
- 36C24224R0071
About this file
This document appears to be an engineering drawing and specification for seismic bracing details related to a new emergency department construction project at the Stratton VA Medical Center in Albany, NY.
The key details include:
- The project scope involves construction of a new emergency department addition to the main hospital, including demolition, site work, general construction, mechanical/plumbing/electrical/fire protection systems, and installation of equipment.
- The contract has a period of performance of 550 calendar days, with the successful contractor required to start work within 15 days of the notice to proceed.
- The contractor must provide a full-time, OSHA-certified superintendent dedicated solely to this project.
- The contractor is required to use the VISN 2 Autodesk Build construction management platform for all official project communication and collaboration, including RFIs, submittals, schedules, and other documents. Training on this platform must be completed within 12 calendar days of access being granted.
View the file
Other files
Show 40 more
Latest 50 of 56 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
HYMAN
HAYES
ASSOCIATES
800 TROY-SCHENECTADY
ROAD, STE 103
LATHAM, NY 12110
(518) 452-3470 www.hymanhayes.com
ENGINEERING LLP
FE PROJECT NO: 19-181
22 Mulberry St., Suite 2A, Middletown, NY 10940 t 845-343-1481; fx 855-320-8735
181 Church St., Suite 100, Poughkeepsie, NY 12601 t 845-454-9704; fx 855-320-8735 www.fellp.com
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
6/
/2
:3 9:
P
M
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
528-809
Project Director
AUGUST 16, 2024 JDFRevisions: Date:
STRATTON VA MEDICAL CENTER
NEW EMERGENCY DEPARTMENT100% FOR BID
SRB
OF ACOUSTIC CEILING GRID1
SEISMIC BRACING
SEISMIC BRACING NOTES:
ATTACHED TO SUSPENDED CEILING2
SEISMIC BRACING OF PARTITION
WITH SEISMIC BRACING3
COMMUNICATIONS RACEWAY DETAIL
SEISMIC BRACING FOR SUSPENDED MECHAINCAL EQUIPMENT4
CONDUIT IN TRAPEZE HANGER7
SEISMIC BRACING FOR PIPE AND
SEISMIC BRACING FOR DUCTWORK5 2-1/2" NOMINAL OR GREATER - SINGLE6
SEISMIC BRACING FOR PIPE AND CONDUIT
FIRE PROTECTION PIPING8
SEISMIC BRACING FOR
AutoCAD SHX Text
JOHN D. FELLENZER, P.E.
AutoCAD SHX Text
ALBANY, NY
AutoCAD SHX Text
NY PROFESSIONAL ENGINEER NO. 069373-1 ISSUED 1992; EXP. 9/25
AutoCAD SHX Text
SEISMIC: DETAILS
AutoCAD SHX Text
1-SE-701
AutoCAD SHX Text N.T.S.
AutoCAD SHX Text
1. SEISMIC DESIGN CATEGORY: "C". SEISMIC DESIGN CATEGORY: "C". 2. EACH TRADE SHALL BE RESPONSIBLE FOR EACH TRADE SHALL BE RESPONSIBLE FOR THE SEISMIC BRACING OF THEIR OWN ITEMS AND EQUIPMENT. 3. THE BRACING SHOWN ON THIS SHEET IS FOR THE BRACING SHOWN ON THIS SHEET IS FOR SEISMIC CONSIDERATIONS ONLY. ALL BRACING DESCRIBED BY OTHER DETAILS, NOTES, AND SPECIFICATIONS IS REQUIRED IN ADDITION TO THE WORK SHOWN HERE.
AutoCAD SHX Text N.T.S.
AutoCAD SHX Text
CABLE TRAY BASKET
AutoCAD SHX Text
COMMUNICATIONS CABLING
AutoCAD SHX Text
NOTE: 1. INSTALL SUPPORTS 8' ON CENTER.INSTALL SUPPORTS 8' ON CENTER.
AutoCAD SHX Text
SCREWED SUSPENSION ROD SUPPORTS (8MM MIN)
AutoCAD SHX Text
UNISTRUT
AutoCAD SHX Text
SECURE TO STRUCTURE ABOVE USING APPROVED ANCHORING/SECURING DEVICES
AutoCAD SHX Text
45 °MIN
AutoCAD SHX Text N.T.S.
AutoCAD SHX Text
NOTE: NOT REQUIRED FOR AIR TERMINAL UNITS.
AutoCAD SHX Text
EQUIPMENT WEIGHT 250 LBS. [114KG] OR LESS
AutoCAD SHX Text
SEISMIC BRACING FOR LIGHT SUSPENDED EQUIPMENT
AutoCAD SHX Text
HANGER ROD (TYP)
AutoCAD SHX Text
CROSS BRACING RODS ALL FOUR SIDES
AutoCAD SHX Text
LOCK NUTS (TYP)
AutoCAD SHX Text
CLAMP
AutoCAD SHX Text N.T.S.
AutoCAD SHX Text
CEILING SLAB
AutoCAD SHX Text
TRANSVERSE BRACE
AutoCAD SHX Text
%%UNOTES%%U:
AutoCAD SHX Text
REQUIRED DESIGN FORCE AT EACH HANGER/BRACE SHALL BE THAT FROM
AutoCAD SHX Text
THE SUM OF ALL ITEMS SUPPORTED. (SEE SEISMIC BRACING CRITERIA TABLE.)
AutoCAD SHX Text
MAXIMUM HANGER/BRACE SPACING SHALL BE THE MOST RESTRICTIVE FOR
AutoCAD SHX Text
ANY OF THE ITEMS SUPPORTED.
AutoCAD SHX Text 1.
AutoCAD SHX Text 2.
AutoCAD SHX Text N.T.S.
AutoCAD SHX Text
ATTACHMENT TO
AutoCAD SHX Text
STRUCTURE
AutoCAD SHX Text
THREADED ROD
AutoCAD SHX Text
ROD STIFFENERS AS REQD
AutoCAD SHX Text
SEISMIC CABLE
AutoCAD SHX Text
OPTIMUM
AutoCAD SHX Text
ANGLE
AutoCAD SHX Text 45%%d%%p15%%d
AutoCAD SHX Text
DUCTWORK
AutoCAD SHX Text N.T.S.
AutoCAD SHX Text
TENSION/COMPRESSION TRANSVERSE
AutoCAD SHX Text
(AND LONGITUDINAL) BRACE UP TO
AutoCAD SHX Text
(UNISTRUT P1354 MIN)
AutoCAD SHX Text
ADJUSTABLE HINGE
AutoCAD SHX Text 45°
AutoCAD SHX Text
MAX
AutoCAD SHX Text
RIGID ROOF STRUCTURE WHERE BRACE
AutoCAD SHX Text
LENGTH IS 9'-0" OR LESS. PROVIDE
AutoCAD SHX Text
MIN OF UNISTRUT P1000 CHANNEL
AutoCAD SHX Text
PIPE CLEVIS OR ADJUSTABLE STEEL
AutoCAD SHX Text
YOKE PIPE ROLL, AS REQD
AutoCAD SHX Text
%%UNOTE%%U:
AutoCAD SHX Text
SEE SEISMIC BRACING CRITERIA TABLE FOR
AutoCAD SHX Text
REQUIRED DESIGN FORCES.
AutoCAD SHX Text
DISTANCE TO SUPPORTING
AutoCAD SHX Text
STRUCTURE ABOVE LESS
AutoCAD SHX Text
THAN OR EQUAL TO 6'-0"
AutoCAD SHX Text
CRITERIA FOR SEISMIC BRACING OF PIPING AND UTILITIES
AutoCAD SHX Text
NOMINAL
AutoCAD SHX Text 2-1/2"
AutoCAD SHX Text
WEIGHT
AutoCAD SHX Text 4"
AutoCAD SHX Text 6"
AutoCAD SHX Text 8"
AutoCAD SHX Text 10"
AutoCAD SHX Text 12"
AutoCAD SHX Text 14"
AutoCAD SHX Text 16"
AutoCAD SHX Text
SEISMIC FORCE (LBS)/FT LENGTH
AutoCAD SHX Text
MAXIMUM ALLOWED SPAN BETWEEN
AutoCAD SHX Text
PIPE DIAMETER
AutoCAD SHX Text
PER FOOT
AutoCAD SHX Text
HORIZONTAL
AutoCAD SHX Text
VERTICAL
AutoCAD SHX Text
TRANSVERSE SEISMIC SUPPORTS
AutoCAD SHX Text 5.1
AutoCAD SHX Text 16.3
AutoCAD SHX Text 31.4
AutoCAD SHX Text 50.1
AutoCAD SHX Text 74.4
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 1.8
AutoCAD SHX Text 5.8
AutoCAD SHX Text 11.2
AutoCAD SHX Text
AutoCAD SHX Text 26.6
AutoCAD SHX Text 36.3
AutoCAD SHX Text 43.4
AutoCAD SHX Text 56.7
AutoCAD SHX Text %%P 0.4
AutoCAD SHX Text %%P 1.2
AutoCAD SHX Text %%P 2.2
AutoCAD SHX Text %%P 3.6
AutoCAD SHX Text %%P 5.3
AutoCAD SHX Text %%P 7.3
AutoCAD SHX Text %%P 8.7
AutoCAD SHX Text %%P 11.3
AutoCAD SHX Text 10'-0"
AutoCAD SHX Text 14'-0"
AutoCAD SHX Text 16'-0"
AutoCAD SHX Text 18'-0"
AutoCAD SHX Text 20'-0"
AutoCAD SHX Text 22'-0"
AutoCAD SHX Text 22'-0"
AutoCAD SHX Text 22'-0"
AutoCAD SHX Text
%%UNOTES%%U:
AutoCAD SHX Text
SEISMIC BRACE/SUPPORT SHALL BE PROVIDED AT EVERY LOCATION WHERE GRAVITY SUPPORT
AutoCAD SHX Text
IS PROVIDED.
AutoCAD SHX Text
DESIGN VALUES FOR PIPE SIZES NOT GIVEN MAY BE INTERPOLATED. WEIGHTS AND FORCES
AutoCAD SHX Text
GIVEN DO NOT INCLUDE INSULATION AND FITTINGS.
AutoCAD SHX Text
PROVIDE A MINIMUM OF ONE LONGITUDINAL BRACE AT EACH END OF EACH STRAIGHT LENGTH
AutoCAD SHX Text
OF PIPING.
AutoCAD SHX Text 1.
AutoCAD SHX Text 2.
AutoCAD SHX Text 3.
AutoCAD SHX Text
PRIMARY HANGER AS SHOWN ON DETAIL FOR SPECIFIC TRADE
AutoCAD SHX Text
CEILING SLAB
AutoCAD SHX Text N.T.S.
AutoCAD SHX Text N.T.S.
AutoCAD SHX Text
%%UNOTE%%U:
AutoCAD SHX Text
PROVIDE BRACING AT 8' ON CENTER AND AT ALL CORNERS.
AutoCAD SHX Text
%%UNOTE%%U:
AutoCAD SHX Text
CROSS SECTION AREA 6 SQUARE FEET OR LARGER.