Attachment N - UFGS 26 00 00 Electrical.pdf
PDF 3 MB Posted
- Attached to
- New Fort Bliss Paving IDIQ Contract
- Solicitation number
- W911SG27BA002
About this file
This is a Unified Facilities Guide Specifications (UFGS) document containing electrical construction specifications for federal building projects. The document covers multiple sections of detailed technical requirements for electrical systems installation, including basic electrical requirements, equipment wiring connections, medium-voltage and low-voltage cables, conductors, grounding and bonding systems, hangers and supports, raceways and boxes, and cable trays.
The specifications establish comprehensive standards for electrical work including material requirements (copper conductors, various insulation types, cable jackets), installation methods, testing procedures, and quality assurance protocols. All electrical materials and equipment must be new, listed by Underwriter's Laboratories, and comply with standards from IEEE, NEMA, UL, NFPA, ASTM, and ANSI. The document mandates specific conductor sizes and types for different applications (solid conductors for feeders and branch circuits 12 AWG and smaller, stranded for control circuits), prescribes color-coding requirements for phase identification, specifies voltage drop limits (maximum 3 percent for branch circuits), and requires operational testing of all circuit breakers, receptacles, and electrical equipment upon completion. Installation requirements include proper support spacing, firestopping at fire-rated assemblies, sealing of raceways at environmental boundaries, and compliance with the National Electrical Code as modified by local jurisdictions. The contractor must provide eight hours of minimum operation and maintenance training to facility staff and guarantee all materials and workmanship for one year, with manufacturer representatives available for field testing and inspection services.
View the file
Other files
Show 40 more
50 files listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SECTION 260502 - BASIC ELECTRICAL REQUIREMENTS
PART 1 - GENERAL
1.1 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
1.2 SUMMARY
A. This section supplements all sections of this Division and shall apply to all phases of work hereinafter specified, or required to provide a complete installation of electrical systems for the Project. The intent of the Specifications is to provide a complete electrical system that includes all documents that are a part of the Contract.
1. Work Included: Furnish all labor, material, services and skilled supervision necessary for the construction, erection, installation, connections, testing, and adjustment of all circuits and electrical equipment specified herein.
B. Equipment or Fixtures: Equipment and fixtures shall be connected to provide circuit continuity in accordance with the Specifications, whether or not each piece of conductor, conduit, or protective device is shown between such items of equipment or fixtures, and the point of circuit origin.
C. Work Installed but Furnished under Other Sections: The Electrical Work includes the installation or connection of certain materials and equipment furnished under other sections. Verify installation details. Foundations for apparatus and equipment will be furnished under other sections unless otherwise noted or detailed.
1.3 GENERAL REQUIREMENTS
A. Equipment Safety: All electrical materials and equipment shall be new and shall be listed by Underwriter's Laboratories and bear their label, or listed. Custom made equipment must have complete test data submitted by the manufacturer attesting to its safety.
B. Codes and Regulations:
1. Design, manufacture, testing and method of installation of all apparatus and materials furnished under the requirements of these specifications shall conform to the latest publications or standard rules of the following:
a. Institute of Electrical and Electronic Designers - IEEE
b. National Electrical Manufacturers' Association – NEMA
c. Underwriters' Laboratories, Inc. – UL
BASIC ELECTRICAL REQUIREMENTS 260502 - 1
e. National Fire Protection Association - NFPA
e. American Society for Testing and Materials - ASTM
f. American National Standards Institute - ANSI
g. American Standard Association - ASA
h. National Electrical Code - NEC, as modified by the City
i. Insulated Power Cable Designers Association - IPCEA
j. International Electrical Testing Association - NETA
C. The term "Code", when used within the specifications.
D. Requirements of Regulatory Agencies:
1. Codes, Permits and Fees: Where the Contract Documents exceed minimum requirements, the Contract Documents take precedence. Where provisions differ in regard to code application, size, quality, quantity or type of equipment, Contractor shall include in the bid, costs for the most costly provision either denoted in the specifications or on the drawings. This provision shall apply as an amendment to the Public Contracts Code.
a. Comply with all requirements for permits, licenses, fees and Code.
Permits, licenses, fees, inspections and arrangements required for the Work shall be obtained by the Contractor at his expense, unless otherwise specified.
b. Comply with the requirements of the applicable utility companies serving the Project. Make all arrangements with the utility companies for proper coordination of the Work.
E. Shop Drawings and Submittals: Submittals on all material prior to installation.
1. Shop drawings shall be submitted on, but not limited to, the following:
2. Low Voltage Electrical Power Conductors and Cables
3. Grounding and Bonding for Electrical Systems
4. Lighting Control Devices
F. Cutting and Patching:
1. Obtain written permission from the Owner before core drilling or cutting any structural members. Exact method and location of conduit penetrations and/or openings in concrete walls, floors, or ceilings shall be as approved by the Owner.
2. Use care in piercing waterproofing. After the part piercing the waterproofing has been set in place, seal openings and make absolutely watertight.
3. Seal all openings to meet the fire rating of the particular wall floor or ceiling.
1.3 JOB CONDITIONS
A. Existing Conditions:
BASIC ELECTRICAL REQUIREMENTS 260502 - 2
1. The contractor shall visit the site and verify existing conditions.
2. Electrical circuits affecting work shall be de energized while working on or near them.
1.4 TESTING AND ADJUSTMENT
A. Upon completion of all Electrical Work, the contractor shall provide all testing as follows:
1. Operational Test: Test all circuit breakers, receptacles and all other electrical equipment. Replace all faulty devices and equipment discovered during testing with new devices and equipment at no additional cost, and that part of the system
(or devices or equipment) shall then be retested.
1.5 FINAL INSPECTION AND ACCEPTANCE
A. After all requirements of the specifications and/or the drawings have been fully completed, representatives of the Owner will inspect the Work. The Contractor shall provide competent personnel to demonstrate the operation of any item of system, to the full satisfaction of each representative. The Contractor shall provide 8 hours of minimum scheduled operation and maintenance training to staff to be trained on each system indicated above. See specific sections for additional training/operation hours required.
1.6 WARRANTIES
A. Guarantee all materials, equipments, apparatus and workmanship to be free of defective material and faulty workmanship for period of one year unless extended guarantee periods are specified in individual sections.
END OF SECTION 260502
BASIC ELECTRICAL REQUIREMENTS 260502 - 3
SECTION 260503 - EQUIPMENT WIRING CONNECTIONS
A. Section includes electrical connections to equipment.
1.3 REFERENCES
A. National Electrical Manufacturers Association:
1. NEMA WD 1 - General Requirements for Wiring Devices.
2. NEMA WD 6 - Wiring Devices-Dimensional Requirements.
1.4 SUBMITTALS
A. Product Data: Submit wiring device manufacturer’s catalog information showing dimensions, configurations, and construction.
B. Manufacturer's installation instructions.
1.5 CLOSEOUT SUBMITTALS
A. Project Record Documents: Record actual locations, sizes, and configurations of equipment connections.
1.6 COORDINATION
A. Obtain and review shop drawings, product data, manufacturer’s wiring diagrams, and manufacturer's instructions for equipment furnished under other sections.
B. Determine connection locations and requirements.
C. Sequence rough-in of electrical connections to coordinate with installation of equipment.
D. Sequence electrical connections to coordinate with start-up of equipment.
EQUIPMENT WIRING CONNECTIONS 260503 - 1
PART 2 - PRODUCTS
2.1 CORD AND PLUGS
A. Manufacturers:
1. Hubbell.
2. Leviton.
3. Pass & Seymour.
B. Attachment Plug Construction: Conform to NEMA WD 1.
C. Configuration: NEMA WD 6; match receptacle configuration at outlet furnished for equipment.
D. Cord Construction: Type SO or SJO multiconductor flexible cord with identified equipment grounding conductor, suitable for use in damp locations.
E. Size: Suitable for connected load of equipment, length of cord, and rating of branch circuit overcurrent protection.
PART 3 - EXECUTION
3.1 EXAMINATION
A. Verify equipment is ready for electrical connection, for wiring, and to be energized.
3.2 EXISTING WORK
A. Remove exposed abandoned equipment wiring connections, including abandoned connections above accessible ceiling finishes.
B. Disconnect abandoned utilization equipment and remove wiring connections. Remove abandoned components when connected raceway is abandoned and removed. Install blank cover for abandoned boxes and enclosures not removed.
C. Extend existing equipment connections using materials and methods compatible with existing electrical installations, or as specified.
3.3 INSTALLATION
A. Make electrical connections.
B. Make conduit connections to equipment using flexible conduit. Use liquidtight flexible conduit with watertight connectors in damp or wet locations.
EQUIPMENT WIRING CONNECTIONS 260503 - 2
C. Connect heat producing equipment using wire and cable with insulation suitable for temperatures encountered.
D. Install receptacle outlet to accommodate connection with attachment plug.
E. Install cord and cap for field-supplied attachment plug.
F. Install suitable strain-relief clamps and fittings for cord connections at outlet boxes and equipment connection boxes.
G. Install disconnect switches, controllers, control stations, and control devices to complete equipment wiring requirements.
H. Install terminal block jumpers to complete equipment wiring requirements.
I. Install interconnecting conduit and wiring between devices and equipment to complete equipment wiring requirements.
3.4 ADJUSTING
A. Cooperate with utilization equipment installers and field service personnel during checkout and starting of equipment to allow testing and balancing and other startup operations. Provide personnel to operate electrical system and checkout wiring connection components and configurations.
END OF SECTION 260503
EQUIPMENT WIRING CONNECTIONS 260503 - 3
SECTION 260513 - MEDIUM-VOLTAGE CABLES
Conditions and other Division 1 Specification Sections, apply to this Section.
A. Section Includes:
1. Medium voltage cable.
2. Cable terminations.
3. Fireproofing tape.
4. Underground cable markers.
5. Bedding and cover materials.
A. International Electrical Testing Association:
1. NETA ATS - Acceptance Testing Specifications for Electrical Power
Distribution Equipment and Systems.
B. Institute of Electrical and Electronics Engineers.
1. IEEE 48 – Standard Test Procedures and Requirements for Alternating Current
Cable Terminations 2.5 kV thru 765 kV
2. IEEE C2 – National Electrical Safety Code.
C. National Electrical Manufacturers Association
1. NEMA WC 70 – Non-shielded Power Cables Rated 2000 Volts or Less for the
Distribution of Electrical Energy
2. NEMA WC 71 – Non-shielded Power Cables Rated 2001-5000 Volts for the
Distribution of Electric Energy
3. NEMA WC 74 – 5-46 kV Shielded Power Cable for Use in the Transmission and
Distribution of Electric Energy
MEDIUM-VOLTAGE CABLES 260513 - 1
1.4 SUBMITTALS
A. Product Data: Submit for cable, terminations, and accessories.
B. Test Reports: Indicate results of cable test in tabular form and in plots of current versus voltage for incremental voltage steps, and current versus time at 30 second intervals at maximum voltage.
A. Project Record Documents: Record actual sizes and locations of cables.
B. Operation and Maintenance Data: Submit instructions for testing and cleaning cable and accessories.
1.6 QUALIFICATIONS
A. Manufacturer: Company specializing in manufacturing products specified in this section with minimum three years of experience, and with service facilities within 100 miles of
Project.
1.7 DELIVERY, STORAGE, AND HANDLING
A. Protect cable ends from entrance of moisture.
2.1 MEDIUM VOLTAGE CABLE
1. The Okonite Company
2. General Cable
3. Southwire
B. Voltage: 5kV, 8kV, 15kV, 35kV.
C. Insulation Level: 133 percent of operating voltage.
D. Cable Continuous Operating Temperature Rating: MV-105.
E. Configuration: Single conductor.
MEDIUM-VOLTAGE CABLES 260513 - 2
F. Conductor: Copper, compact stranded
G. Conductor Shield: Metal tape insulation shielding
H. Insulation: Ethylene Propylene Rubber EPR
I. Cable Jacket: Sunlight-resistant PVC or Chlorosulfonated polyethylene, CPE.
2.2 CABLE TERMINATIONS
1. 3M Electrical Products Division.
2. Raychem.
3. Thomas & Betts.
B. Location: Indoor or Outdoor
C. Conductor Quantity: Single core
D. Type: Dual extrusion thick wall heat shrink
2.3 FIREPROOFING TAPE
1. 3M Electrical Products Division
2. Plymouth Rubber Co.
B. Product Description: Flexible, conformable fabric, coated on one side with flame retardant, flexible polymeric or chlorinated elastomer. Non-corrosive to and compatible with cable sheaths jackets. It does not support combustion.
C. Width: Approximately 3 inches
D. Thickness: Not less than 0.03 inch
E. Weight: Not less than 2.5 pounds per square yard
2.4 UNDERGROUND CABLE MARKERS
A. Trace Wire: Magnetic detectable conductor, red colored plastic covering, imprinted with
"Medium Voltage Cable" in large letters.
MEDIUM-VOLTAGE CABLES 260513 - 3
2.5 CABLE IDENTIFICATION
A. Colored Conductor Tape for Phases: Yellow colored, self-adhesive vinyl tape not less than 3 mils thick by 1 inch wide. 1 stripe for the A phase conductor, 2 stripes for the B phase conductor, 3 stripes for the C phase conductor. Tape shall be located at all terminations, splices and pull boxes.
B. B. Metal Tags: Brass with 1/4 inch embossed legend, punched for use with self-locking nylon tie fastener. Tags shall be located at all terminations, splices and pull boxes.
Legend shall include the feeder circuit breaker identifier and phase.
3.1 EXAMINATION
A. Verify excavations are to required grade, dry, and not over-excavated.
B. Verify conduit, duct, trench, and manholes are ready to receive cable.
C. Verify routing and termination locations of cable prior to rough-in.
3.2 PREPARATION
A. Use swab to clean conduits and ducts before pulling cables.
3.3 EXISTING WORK
A. Remove abandoned medium-voltage cable.
B. Maintain access to existing medium-voltage cable and other installations remaining active and requiring access. Modify installation or provide access panel.
C. Extend existing medium-voltage cable installations using materials and methods as specified.
D. Clean and repair existing medium-voltage cable to remain or to be reinstalled.
3.4 INSTALLATION
A. Avoid abrasion and other damage to cables during installation.
B. Use suitable manufacturer approved lubricants and pulling equipment.
C. Sustain cable pulling tensions and bending radii below manufacturer’s recommended
MEDIUM-VOLTAGE CABLES 260513 - 4
limits.
D. Ground cable shield at each termination and splice.
E. Install cables in manholes along wall providing longest route.
F. Arrange cable in manholes to avoid interference with duct entrances.
3.5 FIREPROOFING
A. Apply fireproofing tape to cables when installed in manholes, cable rooms, pull boxes, or other enclosures.
B. Smooth out irregularities, at splices or other locations, with insulation putty before applying fireproofing tape.
C. Apply fireproofing tape tightly around cables spirally in half-lapped wrapping or in butt jointed wrapping with second wrapping covering joints first.
D. Extend fireproofing 1 inch into conduit or duct.
E. Install tape with coated side toward cable.
F. Install random wrappings of plastic tape around fireproofing tape to prevent unraveling.
G. Install fireproofing to withstand a 200 Ampere arc for 30 seconds.
3.6 FIELD QUALITY CONTROL
A. Inspect exposed cable sections for physical damage.
B. Inspect cable for proper connections.
C. Inspect shield grounding, cable supports, and terminations for proper installation.
D. Tests as per applicable NETA standards.
3.7 PROTECTION OF INSTALLED CONSTRUCTION
A. Protect installed cables from entrance of moisture.
END OF SECTION 260513
MEDIUM-VOLTAGE CABLES 260513 - 5
SECTION 260519 - LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES
PART 1 – GENERAL
Conditions and other Division 1 Specification Sections, apply to this Section.
A. Section includes building wire and cable; nonmetallic-sheathed cable; direct burial cable;
service entrance cable; armored cable; metal clad cable; and wiring connectors and connections.
A. International Electrical Testing Association:
1. NETA ATS - Acceptance Testing Specifications for Electrical Power Distribution
Equipment and Systems.
B. National Fire Protection Association:
1. NFPA 70 - National Electrical Code.
2. NFPA 262 - Standard Method of Test for Flame Travel and Smoke of Wires and Cables for
Use in Air-Handling Spaces.
C. Underwriters Laboratories, Inc.:
1. UL 1277 - Standard for Safety for Electrical Power and Control Tray Cables with Optional
Optical-Fiber Members.
1.4 SYSTEM DESCRIPTION
A. Product Requirements: Provide products as follows:
1. Solid conductor for feeders and branch circuits 12 AWG.
2. Stranded conductors for control circuits.
3. Conductor not smaller than 12 AWG for power and lighting circuits.
4. Conductor not smaller than 14 AWG for control circuits.
5. Increase wire size in branch circuits to limit voltage drop to a maximum of 3 percent. B.
Wiring Methods: Provide the following wiring methods:
1. Concealed Dry Interior Locations: Use only building wire, Type THHN/THWN insulation, in raceway.
LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES 260519 - 1
2. Exposed Dry Interior Locations: Use only building wire, Type THHN/THWN insulation, in raceway.
3. Above Accessible Ceilings: Use only building wire, Type THHN/THWN insulation, in raceway.
4. Wet or Damp Interior Locations: Use only building wire, Type THHN/THWN insulation, in raceway.
5. Exterior Locations: Use only building wire, Type THHN/THWN insulation, in raceway.
6. Underground Locations: Use only building wire, Type THHN/THWN insulation, in raceway.
7. Other Locations: Use only building wire, Type THHN/THWN insulation, in raceway.
A. Project Record Documents: Record actual locations of components and circuits.
1.6 QUALITY ASSURANCE
A. Provide wiring materials located in plenums with peak optical density not greater than 0.5, average optical density not greater than 0.15, and flame spread not greater than 5 feet (1.5 m) when tested in accordance with NFPA 262.
2.1 BUILDING WIRE
1. General Cable Co.
2. Southwire Co.
3. Rome Cable Co.
B. Product Description: Single conductor insulated wire.
C. Conductor: Copper.
D. Insulation Voltage Rating: 600 volts.
E. Insulation Temperature Rating: 75 degrees C.
F. Insulation Material: Thermoplastic.
LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES 260519 - 2
2.2 ARMORED CABLE
1. General Cable.
2. Southwire Cable.
3. Rome Cable.
2.3 TERMINATIONS
A. Terminal Lugs for Wires 6 AWG and Smaller: Solderless, compression type copper.
B. Lugs for Wires 4 AWG and Larger: Color keyed, compression type copper, with insulating sealing collars.
3.1 PREPARATION
A. Completely and thoroughly swab raceway before installing wire.
3.2 INSTALLATION
A. Neatly train and lace wiring inside boxes, equipment, and panelboards.
B. Identify and color code wire and cable as described herein. Identify each conductor with its circuit number or other designation indicated.
C. Special Techniques--Building Wire in Raceway:
1. Pull conductors into raceway at same time.
2. Install building wire 4 AWG and larger with pulling equipment.
D. Special Techniques - Cable:
1. Protect exposed cable from damage.
2. Support cables above accessible ceiling, using spring metal clips or metal plastic cable ties to support cables from structure or ceiling suspension system. Do not rest cable on ceiling panels.
E. Special Techniques - Wiring Connections:
1. Clean conductor surfaces before installing lugs and connectors.
2. Make splices, taps, and terminations to carry full ampacity of conductors with no perceptible temperature rise.
LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES 260519 - 3
3. Tape uninsulated conductors and connectors with electrical tape to 150 percent of insulation rating of conductor.
4. Install split bolt connectors for copper conductor splices and taps, 6 AWG and larger.
5. Install solderless pressure connectors with insulating covers for copper conductor splices and taps, 8 AWG and smaller.
6. Install insulated spring wire connectors with plastic caps for copper conductor splices and taps, 10 AWG and smaller.
F. Install solid conductors for branch circuits 10 AWG and smaller. Do not place bare stranded conductors directly under screws.
G. Install terminal lugs on ends of 600 volt wires unless lugs are furnished on connected device, such as circuit breakers.
H. Size lugs in accordance with manufacturer’s recommendations terminating wire sizes. Install 2-hole type lugs to connect wires 4 AWG and larger to copper bus bars.
I. For terminal lugs fastened together such as on motors, transformers, and other apparatus, or when space between studs is small enough that lugs can turn and touch each other, insulate for dielectric strength of 2-1/2 times normal potential of circuit.
3.3 WIRE COLOR
A. General: All power and branch circuit conductors shall be provided with color-coded insulation or color-coded self-adhesive vinyl tape not less than 3 mils thick by 1 to 2 inches wide. Vinyl tape shall be used in vaults, pull and junction boxes, manholes and handholes. Identify the source and circuit number of each set of conductors with write-on tags.
B. Colors: Color coding shall be as follows:
Phase
A
208Y/120V Black
480Y/277V Brown
B Red Orange
C Blue Yellow
Neutral
Ground
White
Green
White with Black Stripe
Green
3.4 FIELD QUALITY CONTROL
A. Inspect and test in accordance with NETA ATS, except Section 4.
B. Perform inspections and tests listed in NETA ATS, Section 7.3.1.
END OF SECTION 260519
LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES 260519 - 4
CONDUCTORS AND CABLES 260523 - 1
SECTION 260523 - CONDUCTORS AND CABLES
1. Building wires and cables rated 600 V and less.
2. Connectors, splices, and terminations rated 600 V and less.
B. Related Requirements:
1. Section 260513 "Medium-Voltage Cables" for single-conductor and multiconductor cables, cable splices, and terminations for electrical distribution systems with 2001 to
35,000 V.
2. Section 260523 "Control-Voltage Electrical Power Cables" for control systems communications cables and Classes 1, 2 and 3 control cables.
3. Section 271500 "Communications Horizontal Cabling" for cabling used for voice and data circuits.
1.3 DEFINITIONS
A. VFC: Variable frequency controller.
1.4 ACTION SUBMITTALS
A. Product Data: For each type of product.
1.5 INFORMATIONAL SUBMITTALS
A. Qualification Data: For testing agency.
B. Field quality-control reports.
CONDUCTORS AND CABLES 260523 - 2
A. Testing Agency Qualifications: Member company of NETA or an NRTL.
1. Testing Agency's Field Supervisor: Certified by NETA to supervise on-site testing.
A. Aluminum and Copper Conductors: Comply with NEMA WC 70/ICEA.
B. Conductor Insulation: Comply with NEMA WC 70/ICEA for Type UF, Type USE and
Type SO.
C. Multiconductor Cable: Comply with NEMA WC 70/ICEA for armored cable, Type AC, metal-clad cable, Type MC, mineral-insulated, metal-sheathed cable, Type MI nonmetallic-sheathed cable, Type NM, Type SO and Type USE with ground wire.
2.2 CONNECTORS AND SPLICES
A. Description: Factory-fabricated connectors and splices of size, ampacity rating, material, type, and class for application and service indicated.
2.3 SYSTEM DESCRIPTION
A. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application.
B. Comply with NFPA 70.
3.1 CONDUCTOR MATERIAL APPLICATIONS
A. Feeders: Copper: Solid for No. 10 AWG and smaller; stranded for No. 8 AWG and larger.
B. Branch Circuits: Copper. Solid for No. 10 AWG and smaller; stranded for No. 8 AWG and larger, except VFC cable, which shall be extra flexible stranded.
3.2 CONDUCTOR INSULATION AND MULTICONDUCTOR CABLE APPLICATIONS AND
WIRING METHODS
A. Service Entrance: Type THHN, THWN, single conductors in raceway, Type XHHW single conductors in raceway, Mineral-insulated, metal-sheathed cable, Type MI or Type SE or
Type USE multiconductor cable.
CONDUCTORS AND CABLES 260523 - 3
B. Exposed Feeders: Type THHN, THWN, single conductors in raceway, Type XHHW single conductors in raceway, Armored cable, Type AC, Metal-clad cable, Type MC, Mineral-insulated, metal-sheathed cable, Type MI or Nonmetallic-sheathed cable, Type NM.
C. Feeders Concealed in Ceilings, Walls, Partitions, and Crawlspaces: Type THHN, THWN single conductors in raceway, Armored cable, Type AC, Metal-clad cable, Type MC], Mineral-
D. Feeders Concealed in Concrete, below Slabs-on-Grade, and Underground: Type THHN, THWN single conductors in raceway, Type XHHW-2, single conductors in raceway or Underground feeder cable, Type UF.
E. Feeders Installed below Raised Flooring: Type THHN, THWN single conductors in raceway, Armored cable, Type AC, Metal-clad cable, Type MC or Mineral-insulated, metal-sheathed cable, Type MI.
F. Feeders in Cable Tray: Type THHN, THWN single conductors in raceway, Type XHHW single conductors larger than No. 1/0 AWG, Armored cable, Type AC, Metal-clad cable, Type MC, Mineral-insulated, metal-sheathed cable, Type MI or Nonmetallic-sheathed cable, Type NM.
G. Exposed Branch Circuits, Including in Crawlspaces: Type THHN, THWN single conductors in raceway, Armored cable, Type AC, Metal-clad cable, Type MC, Mineral-insulated, metal-sheathed cable, Type MI or Nonmetallic-sheathed cable, Type NM.
H. Branch Circuits Concealed in Ceilings, Walls, and Partitions: Type THHN, THWN single conductors in raceway, Armored cable, Type AC, Metal-clad cable, Type MC, Mineral-
I. Branch Circuits Concealed in Concrete, below Slabs-on-Grade, and Underground:
Type THHN, THWN single conductors in raceway, Type XHHW single conductors in raceway or Underground branch-circuit cable, Type UF.
J. Branch Circuits Installed below Raised Flooring: Type THHN, THWN single conductors in raceway, Armored cable, Type AC, Metal-clad cable, Type MC or Mineral-insulated, metal-sheathed cable, Type MI.
K. Branch Circuits in Cable Tray: Type THHN, THWN single conductors in raceway, Type XHHW single conductors larger than No. 1/0 AWG, Armored cable, Type AC, Metal-clad cable, Type MC, Mineral-insulated, metal-sheathed cable, Type MI or Nonmetallic-sheathed cable, Type NM.
3.3 INSTALLATION OF CONDUCTORS AND CABLES
A. Conceal cables in finished walls, ceilings, and floors unless otherwise indicated.
B. Complete raceway installation between conductor and cable termination points according to
Section 260533 "Raceway and Boxes for Electrical Systems" prior to pulling conductors and cables.
CONDUCTORS AND CABLES 260523 - 4
C. Use manufacturer-approved pulling compound or lubricant where necessary; compound used must not deteriorate conductor or insulation. Do not exceed manufacturer's recommended maximum pulling tensions and sidewall pressure values.
D. Use pulling means, including fish tape, cable, rope, and basket-weave wire/cable grips, that will not damage cables or raceway.
E. Install exposed cables parallel and perpendicular to surfaces of exposed structural members, and follow surface contours where possible.
F. Support cables according to Section 260529 "Hangers and Supports for Electrical Systems."
G. Complete cable tray systems installation according to Section 260536 "Cable Trays for
Electrical Systems" prior to installing conductors and cables.
3.4 CONNECTIONS
A. Tighten electrical connectors and terminals according to manufacturer's published torque-tightening values. If manufacturer's torque values are not indicated, use those specified in
UL 486A-486B.
B. Make splices, terminations, and taps that are compatible with conductor material and that possess equivalent or better mechanical strength and insulation ratings than unspliced conductors.
C. Wiring at Outlets: Install conductor at each outlet, with at least 6 inches of slack.
3.5 FIRESTOPPING
A. Apply firestopping to electrical penetrations of fire-rated floor and wall assemblies to restore original fire-resistance rating of assembly according to Section 076413 "Penetration
Firestopping".
A. Testing Agency: Engage a qualified testing agency to perform tests and inspections.
B. Manufacturer's Field Service: Engage a factory-authorized service representative to test and inspect components, assemblies, and equipment installations, including connections.
C. Perform the following tests and inspections with the assistance of a factory-authorized service representative:
1. After installing conductors and cables and before electrical circuitry has been energized, test service entrance and feeder conductors and conductors feeding the following critical equipment and services for compliance with requirements.
CONDUCTORS AND CABLES 260523 - 5
2. Perform each visual and mechanical inspection and electrical test stated in NETA
Acceptance Testing Specification. Certify compliance with test parameters.
D. Test and Inspection Reports: Prepare a written report to record the following:
1. Procedures used.
2. Results that comply with requirements.
3. Results that do not comply with requirements and corrective action taken to achieve compliance with requirements.
E. Cables will be considered defective if they do not pass tests and inspections.
END OF SECTION 260523
GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS 260526 - 1
SECTION 260526 - GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS
A. Section Includes: Grounding systems and equipment.
B. Section includes grounding systems and equipment, plus the following special applications:
1. Overhead-line grounding.
2. Underground distribution grounding.
3. Ground bonding common with lightning protection system.
1.3 ACTION SUBMITTALS
A. Product Data: For each type of product indicated.
1.4 INFORMATIONAL SUBMITTALS
A. Informational Submittals: Plans showing dimensioned as-built locations of grounding features specified in "Field Quality Control" Article, including the following:
1. Ground rods.
2. Ground rings.
3. Grounding arrangements and connections for separately derived systems.
4. Grounding for sensitive electronic equipment.
B. Qualification Data: For qualified testing agency and testing agency's field supervisor.
C. Field quality-control reports.
A. Operation and Maintenance Data: For grounding to include in emergency, operation, and maintenance manuals. In addition to items specified in Section 017823 "Operation and
Maintenance Data," include the following:
GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS 260526 - 2
1. Instructions for periodic testing and inspection of grounding features at test wells, ground rings or grounding connections for separately derived systems based on
NETA MTS or NFPA 70B.
a. Tests shall determine if ground-resistance or impedance values remain within specified maximums, and instructions shall recommend corrective action if values do not.
b. Include recommended testing intervals.
A. Testing Agency Qualifications: Member company of NETA or an NRTL.
1. Testing Agency's Field Supervisor: Currently certified by NETA to supervise on-site testing.
B. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application.
C. Comply with UL 467 for grounding and bonding materials and equipment.
2.1 CONDUCTORS
A. Insulated Conductors: Copper or tinned-copper wire or cable insulated for 600 V unless otherwise required by applicable Code or authorities having jurisdiction.
B. Bare Copper Conductors:
1. Solid Conductors: ASTM B 3.
2. Stranded Conductors: ASTM B 8.
3. Tinned Conductors: ASTM B 33.
4. Bonding Cable: 28 kcmil, 14 strands of No. 17 AWG conductor, 1/4 inch (6 mm) in diameter.
5. Bonding Conductor: No. 4 or No. 6 AWG, stranded conductor.
6. Bonding Jumper: Copper tape, braided conductors terminated with copper ferrules; 1-5/8 inches (41 mm) wide and 1/16 inch (1.6 mm) thick.
7. Tinned Bonding Jumper: Tinned-copper tape, braided conductors terminated with copper ferrules; 1-5/8 inches (41 mm) wide and 1/16 inch (1.6 mm) thick.
C. Bare Grounding Conductor and Conductor Protector for Wood Poles:
1. No. 4 AWG minimum, soft-drawn copper.
2. Conductor Protector: Half-round PVC or wood molding; if wood, use pressure-treated fir, cypress, or cedar.
GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS 260526 - 3
2.2 CONNECTORS
A. Listed and labeled by an NRTL acceptable to authorities having jurisdiction for applications in which used and for specific types, sizes, and combinations of conductors and other items connected.
B. Bolted Connectors for Conductors and Pipes: Copper or copper alloy, pressure type with at least two bolts.
1. Pipe Connectors: Clamp type, sized for pipe.
C. Welded Connectors: Exothermic-welding kits of types recommended by kit manufacturer for materials being joined and installation conditions.
D. Bus-bar Connectors: Mechanical type, cast silicon bronze, solderless compression or exothermic-type wire terminals, and long-barrel, two-bolt connection to ground bus bar.
2.3 GROUNDING ELECTRODES
A. Ground Rods: Copper-clad or Zinc-coated; 3/4 inch by 10 feet or 5/8 by 96 inches in diameter.
B. Chemical-Enhanced Grounding Electrodes: Copper tube, straight or L-shaped, charged with nonhazardous electrolytic chemical salts.
1. Termination: Factory-attached No. 4/0 AWG bare conductor at least 48 inches long.
2. Backfill Material: Electrode manufacturer's recommended material.
3.1 APPLICATIONS
A. Conductors: Install solid conductor for No. 8 AWG and smaller, and stranded conductors for
No. 6 AWG and larger unless otherwise indicated.
B. Underground Grounding Conductors: Install bare tinned-copper conductor, No. 2/0 AWG minimum.
1. Bury at least 24 inches below grade.
2. Duct-Bank Grounding Conductor: Bury 12 inches above duct bank when indicated as part of duct-bank installation.
C. Isolated Grounding Conductors: Green-colored insulation with continuous yellow stripe. On feeders with isolated ground, identify grounding conductor where visible to normal inspection, with alternating bands of green and yellow tape, with at least three bands of green and two bands of yellow.
GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS 260526 - 4
D. Grounding Bus: Install in electrical and telephone equipment rooms, in rooms housing service equipment, and elsewhere as indicated.
1. Install bus on insulated spacers 2 inches minimum from wall, 6 inches above finished floor unless otherwise indicated.
2. Where indicated on both sides of doorways, route bus up to top of door frame, across top of doorway, and down to specified height above floor; connect to horizontal bus.
E. Conductor Terminations and Connections:
1. Pipe and Equipment Grounding Conductor Terminations: Bolted connectors.
2. Underground Connections: Welded connectors except at test wells and as otherwise indicated.
3. Connections to Ground Rods at Test Wells: Bolted connectors.
4. Connections to Structural Steel: Welded connectors.
3.2 GROUNDING OVERHEAD LINES
A. Comply with IEEE C2 grounding requirements.
B. Install two parallel ground rods if resistance to ground by a single, ground-rod electrode exceeds 25 ohms.
C. Drive ground rods until tops are 12 inches below finished grade in undisturbed earth.
D. Ground-Rod Connections: Install bolted connectors for underground connections and connections to rods.
E. Lightning Arrester Grounding Conductors: Separate from other grounding conductors.
F. Secondary Neutral and Transformer Enclosure: Interconnect and connect to grounding conductor.
G. Protect grounding conductors running on surface of wood poles with molding extended from grade level up to and through communication service and transformer spaces.
3.3 GROUNDING UNDERGROUND DISTRIBUTION SYSTEM COMPONENTS
A. Comply with IEEE C2 grounding requirements.
B. Grounding Manholes and Handholes: Install a driven ground rod through manhole or handhole floor, close to wall, and set rod depth so 4 inches will extend above finished floor. If necessary, install ground rod before manhole is placed and provide No. 1/0 AWG bare, tinned-copper conductor from ground rod into manhole through a waterproof sleeve in manhole wall. Protect ground rods passing through concrete floor with a double wrapping of pressure-sensitive insulating tape or heat-shrunk insulating sleeve from 2 inches above to 6 inches below concrete.
Seal floor opening with waterproof, nonshrink grout.
GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS 260526 - 5
C. Grounding Connections to Manhole Components: Bond exposed-metal parts such as inserts, cable racks, pulling irons, ladders, and cable shields within each manhole or handhole, to ground rod or grounding conductor. Make connections with No. 4 AWG minimum, stranded, hard-drawn copper bonding conductor. Train conductors level or plumb around corners and fasten to manhole walls. Connect to cable armor and cable shields according to written instructions by manufacturer of splicing and termination kits.
D. Pad-Mounted Transformers and Switches: Install two ground rods and ground ring around the pad. Ground pad-mounted equipment and noncurrent-carrying metal items associated with substations by connecting them to underground cable and grounding electrodes. Install tinned-copper conductor not less than No. 2 AWG for ground ring and for taps to equipment grounding terminals. Bury ground ring not less than 6 inches from the foundation.
3.4 EQUIPMENT GROUNDING
A. Install insulated equipment grounding conductors with all feeders and branch circuits.
B. Install insulated equipment grounding conductors with the following items, in addition to those required by NFPA 70:
1. Feeders and branch circuits.
2. Lighting circuits.
3. Receptacle circuits.
4. Single-phase motor and appliance branch circuits.
5. Three-phase motor and appliance branch circuits.
6. Flexible raceway runs.
7. Armored and metal-clad cable runs.
8. Busway Supply Circuits: Install insulated equipment grounding conductor from grounding bus in the switchgear, switchboard, or distribution panel to equipment grounding bar terminal on busway.
9. Computer and Rack-Mounted Electronic Equipment Circuits: Install insulated equipment grounding conductor in branch-circuit runs from equipment-area power panels and power-distribution units.
10. X-Ray Equipment Circuits: Install insulated equipment grounding conductor in circuits supplying x-ray equipment.
C. Air-Duct Equipment Circuits: Install insulated equipment grounding conductor to duct-mounted electrical devices operating at 120 V and more, including air cleaners, heaters, dampers, humidifiers, and other duct electrical equipment. Bond conductor to each unit and to air duct and connected metallic piping.
D. Water Heater, Heat-Tracing, and Antifrost Heating Cables: Install a separate insulated equipment grounding conductor to each electric water heater and heat-tracing cable. Bond conductor to heater units, piping, connected equipment, and components.
E. Isolated Grounding Receptacle Circuits: Install an insulated equipment grounding conductor connected to the receptacle grounding terminal. Isolate conductor from raceway and from panelboard grounding terminals. Terminate at equipment grounding conductor terminal of the applicable derived system or service unless otherwise indicated.
GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS 260526 - 6
F. Isolated Equipment Enclosure Circuits: For designated equipment supplied by a branch circuit or feeder, isolate equipment enclosure from supply circuit raceway with a nonmetallic raceway fitting listed for the purpose. Install fitting where raceway enters enclosure, and install a separate insulated equipment grounding conductor. Isolate conductor from raceway and from panelboard grounding terminals. Terminate at equipment grounding conductor terminal of the applicable derived system or service unless otherwise indicated.
G. Signal and Communication Equipment: In addition to grounding and bonding required by
NFPA 70, provide a separate grounding system complying with requirements in TIA/ATIS J-
STD-607-A.
1. For telephone, alarm, voice and data, and other communication equipment, provide
No. 4 AWG minimum insulated grounding conductor in raceway from grounding electrode system to each service location, terminal cabinet, wiring closet, and central equipment location.
2. Service and Central Equipment Locations and Wiring Closets: Terminate grounding conductor on a 1/4-by-4-by-12-inch grounding bus.
3. Terminal Cabinets: Terminate grounding conductor on cabinet grounding terminal.
H. Metal and Wood Poles Supporting Outdoor Lighting Fixtures: Install grounding electrode and a separate insulated equipment grounding conductor in addition to grounding conductor installed with branch-circuit conductors.
3.5 INSTALLATION
A. Grounding Conductors: Route along shortest and straightest paths possible unless otherwise indicated or required by Code. Avoid obstructing access or placing conductors where they may be subjected to strain, impact, or damage.
B. Ground Bonding Common with Lightning Protection System: Comply with NFPA 780 and
UL 96 when interconnecting with lightning protection system. Bond electrical power system ground directly to lightning protection system grounding conductor at closest point to electrical service grounding electrode. Use bonding conductor sized same as system grounding electrode conductor, and install in conduit.
C. Ground Rods: Drive rods until tops are 2 inches below finished floor or final grade unless otherwise indicated.
1. Interconnect ground rods with grounding electrode conductor below grade and as otherwise indicated. Make connections without exposing steel or damaging coating if any.
2. For grounding electrode system, install at least three rods spaced at least one-rod length from each other and located at least the same distance from other grounding electrodes, and connect to the service grounding electrode conductor.
GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS 260526 - 7
D. Test Wells: Ground rod driven through drilled hole in bottom of handhole. Handholes are specified in Section 260543 "Underground Ducts and Raceways for Electrical Systems," and shall be at least 12 inches deep, with cover.
1. Test Wells: Install at least one test well for each service unless otherwise indicated.
Install at the ground rod electrically closest to service entrance. Set top of test well flush with finished grade or floor.
E. Bonding Straps and Jumpers: Install in locations accessible for inspection and maintenance except where routed through short lengths of conduit.
1. Bonding to Structure: Bond straps directly to basic structure, taking care not to penetrate any adjacent parts.
2. Bonding to Equipment Mounted on Vibration Isolation Hangers and Supports: Install bonding so vibration is not transmitted to rigidly mounted equipment.
3. Use exothermic-welded connectors for outdoor locations; if a disconnect-type connection is required, use a bolted clamp.
F. Grounding and Bonding for Piping:
1. Metal Water Service Pipe: Install insulated copper grounding conductors, in conduit, from building's main service equipment, or grounding bus, to main metal water service entrances to building. Connect grounding conductors to main metal water service pipes;
use a bolted clamp connector or bolt a lug-type connector to a pipe flange by using one of the lug bolts of the flange. Where a dielectric main water fitting is installed, connect grounding conductor on street side of fitting. Bond metal grounding conductor conduit or sleeve to conductor at each end.
2. Water Meter Piping: Use braided-type bonding jumpers to electrically bypass water meters. Connect to pipe with a bolted connector.
3. Bond each aboveground portion of gas piping system downstream from equipment shutoff valve.
G. Bonding Interior Metal Ducts: Bond metal air ducts to equipment grounding conductors of associated fans, blowers, electric heaters, and air cleaners. Install [tinned ]bonding jumper to bond across flexible duct connections to achieve continuity.
H. Grounding for Steel Building Structure: Install a driven ground rod at base of each corner column and at intermediate exterior columns at distances not more than 60 feet apart.
I. Ground Ring: Install a grounding conductor, electrically connected to each building structure ground rod and to each steel column, extending around the perimeter of area or item indicated.
1. Install tinned-copper conductor not less than No. 2/0 AWG for ground ring and for taps to building steel.
2. Bury ground ring not less than 24 inches from building's foundation.
GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS 260526 - 8
J. Under Ground (Concrete-Encased Grounding Electrode): Fabricate according to NFPA 70; use a minimum of 20 feet of bare copper conductor not smaller than No. 4 AWG.
1. If concrete foundation is less than 20 feet long, coil excess conductor within base of foundation.
2. Bond grounding conductor to reinforcing steel in at least four locations and to anchor bolts. Extend grounding conductor below grade and connect to building's grounding grid or to grounding electrode external to concrete.
A. Testing Agency: Engage a qualified testing agency to perform tests and inspections.
B. Manufacturer's Field Service: Engage a factory-authorized service representative to inspect, test, and adjust components, assemblies, and equipment installations, including connections.
C. Perform tests and inspections.
1. Manufacturer's Field Service: Engage a factory-authorized service representative to inspect components, assemblies, and equipment installations, including connections, and to assist in testing.
D. Tests and Inspections:
1. After installing grounding system but before permanent electrical circuits have been energized, test for compliance with requirements.
2. Inspect physical and mechanical condition. Verify tightness of accessible, bolted, electrical connections with a calibrated torque wrench according to manufacturer's written instructions.
3. Test completed grounding system at each location where a maximum ground-resistance level is specified, at service disconnect enclosure grounding terminal, at ground test wells, and at individual ground rods. Make tests at ground rods before any conductors are connected.
a. Measure ground resistance no fewer than two full days after last trace of precipitation and without soil being moistened by any means other than natural drainage or seepage and without chemical treatment or other artificial means of reducing natural ground resistance.
b. Perform tests by fall-of-potential method according to IEEE 81.
4. Prepare dimensioned Drawings locating each test well, ground rod and ground-rod assembly, and other grounding electrodes. Identify each by letter in alphabetical order, and key to the record of tests and observations. Include the number of rods driven and their depth at each location, and include observations of weather and other phenomena that may affect test results. Describe measures taken to improve test results.
GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS 260526 - 9
E. Grounding system will be considered defective if it does not pass tests and inspections.
F. Prepare test and inspection reports.
G. Report measured ground resistances that exceed the following values:
1. Power and Lighting Equipment or System with Capacity of 500 kVA and Less: 10 ohms.
2. Power and Lighting Equipment or System with Capacity of 500 to 1000 kVA: 5 ohms.
3. Power and Lighting Equipment or System with Capacity More Than 1000 kVA: 3 ohms.
4. Substations and Pad-Mounted Equipment: 5 ohms.
5. Manhole Grounds: 10 ohms.
H. Excessive Ground Resistance: If resistance to ground exceeds specified values, notify Architect promptly and include recommendations to reduce ground resistance.
END OF SECTION 260526
HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS 260530 - 1
SECTION 260530 - HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS
A. This Section includes the following:
1. Hangers and supports for electrical equipment and systems.
2. Construction requirements for concrete bases.
A. EMT: Electrical metallic tubing.
B. IMC: Intermediate metal conduit.
C. RMC: Rigid metal conduit.
1.4 PERFORMANCE REQUIREMENTS
A. Delegated Design: Design supports for multiple raceways, including comprehensive engineering analysis by a qualified professional engineer, using performance requirements and design criteria indicated.
B. Design supports for multiple raceways capable of supporting combined weight of supported systems and its contents.
C. Design equipment supports capable of supporting combined operating weight of supported equipment and connected systems and components.
D. Rated Strength: Adequate in tension, shear, and pullout force to resist maximum loads calculated or imposed for this Project, with a minimum structural safety factor of five times the applied force.-
1.5 ACTION SUBMITTALS
A. Product Data: For the following:
HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS 260530 - 2
1. Steel slotted support systems.
2. Nonmetallic slotted support systems.
B. Shop Drawings: Signed and sealed by a qualified professional engineer. Show fabrication and installation details and include calculations for the following:
1. Trapeze hangers. Include Product Data for components.
2. Steel slotted channel systems. Include Product Data for components.
3. Nonmetallic slotted channel systems. Include Product Data for components.
4. Equipment supports.
1.6 INFORMATIONAL SUBMITTALS
A. Welding certificates.
1.7 QUALITY ASSURANCE
A. Welding: Qualify procedures and personnel according to AWS D1.1/D1.1M, "Structural
Welding Code - Steel."
B. Comply with NFPA 70.
1.8 COORDINATION
A. Coordinate size and location of concrete bases. Cast anchor-bolt inserts into bases. Concrete, reinforcement, and formwork requirements are specified together with concrete Specifications.
B. Coordinate installation of roof curbs, equipment supports, and roof penetrations. These items are specified in Section 07720 "Roof Accessories."
2.1 SUPPORT, ANCHORAGE, AND ATTACHMENT COMPONENTS
A. Steel Slotted Support Systems: Comply with MFMA-4, factory-fabricated components for field assembly.
1. Metallic Coatings: Hot-dip galvanized after fabrication and applied according to
MFMA-4.
2. Nonmetallic Coatings: Manufacturer's standard PVC, polyurethane, or polyester coating applied according to MFMA-4.
3. Painted Coatings: Manufacturer's standard painted coating applied according to MFMA-
4.
4. Channel Dimensions: Selected for applicable load criteria.
HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS 260530 - 3
B. Raceway and Cable Supports: As described in NECA 1 and NECA 101.
C. Conduit and Cable Support Devices: Steel and malleable-iron hangers, clamps, and associated fittings, designed for types and sizes of raceway or cable to be supported.
D. Support for Conductors in Vertical Conduit: Factory-fabricated assembly consisting of threaded body and insulating wedging plug or plugs for non-armored electrical conductors or cables in riser conduits.