Attachment D.6 -5_618-22-100_MPLS_PT_IFB_FIRE_230404.pdf

PDF 5 MB Posted

Attached to
618-22-100 Renovate for Expanded Polytrauma Phase 1
Solicitation number
36C26323R0058_1
Issued by

About this file

This solicitation is for a construction project to renovate space at the Minneapolis VA Health Care System to expand polytrauma care. The project involves general construction, electrical, plumbing and other trades. The total estimated value is between $10-20 million. The solicitation is set aside for verified service-disabled veteran-owned small businesses. Offerors must be verified in VetCert as an SDVOSB. Applicable taxes shall be included in pricing. The agency is the VA Veterans Health Administration VISN 23.

View the file

Other files

File Type Posted
36C26323R0058 0001.pdf PDF
See Attached document - Attachment 1 Questions and Answers Request 7.12.2023.doc DOC document
See Attached document - Attachment 5 618-22-100 Prebid Sign-in Roster.pdf PDF
See Attached document - Attachment 2 MPLS Expand Polytrauma Program - Pre Bid Walk Through.pdf PDF
See Attached document - Attachment 7 Polytrauma Structural Coordination.pdf PDF
See Attached document - Attachment 6 618-21-700.MPLS.POLYTRAUMA.PG104i.pdf PDF
See Attached document - Attachment 4 Polytrauma Addendum Summary.docx DOCX document
See Attached document - Attachment 3 Site Visit Agenda Poly Trauma Agenda June 26 2023.docx DOCX document
Attachment D.5 - 4_618-22-100_MPLS_PT_IFB_EQUIP_230404.pdf PDF
Attachment C Specifications Polytrauma 1477 pages.pdf PDF
Attachment D.7-6_618-22-100_MPLS_PT_IFB_PLUMB_230404.pdf PDF
Attachment D.9 - 8_618-22-100_MPLS_PT_IFB_MECH_230404.pdf PDF
Attachment A - Final SOW-618-22-100 - REV4 4.18 (6 pages).pdf PDF
Attachment D.11 - 10_618-22-100_MPLS_PT_IFB_ELEC_230404.pdf PDF
Attachment I VAAR 852.219-75 Limitations on Subcontracting Cert of Compliance (2 Pages).pdf PDF
Attachment F - VA6500 Appendix C and Appendix D.pdf PDF
Attachment H Questions Request Form (1 page).doc DOC document
Attachment K Combined Single Source Justifications_Redacted.pdf PDF
Attachment D.1 - 618-22-100_MPLS_PT_IFB_GENERAL_230404.pdf PDF
Attachment E - 618-22-100_MPLS_PT_TripleC-CA-SubmittalLOG.xlsx XLSX spreadsheet
Attachment D.2 - 2_618-22-100_MPLS_PT_IFB_ARCH_230404.pdf PDF
Attachment J Wage Determination MN20230117 05.19.2023.pdf PDF
Attachment D.3 - 3_618-22-100_MPLS_PT_IFB_INTERIORS_230404.pdf PDF
Attachment D.12 - 11_618-22-100_MPLS_PT_IFB_TELECOM_230404.pdf PDF
Attachment B Price Schedule Breakdown (1 Page).pdf PDF
Attachment F - VA6500 Appendix C 1-2-3a-6a-7a-7d-9 and Appendix D (6 pages).pdf PDF
Attachment D.4 - 4_618-22-100_MPLS_PT_IFB_EQUIP_230404 (2).pdf PDF
Attachment D.1 - 4_618-22-100_MPLS_PT_IFB_EQUIP_230404.pdf PDF
Attachment D.1 - 4_618-22-100_MPLS_PT_IFB_EQUIP_230404 (1).pdf PDF
Attachment G - Past Performance Questionnaire (3 Pages).docx DOCX document
36C26323R0058 1.pdf PDF
Attachment F - VA6500 Appendix C 1-2-3a-6a-7a-7d-9 and Appendix D.pdf PDF
Attachment D.10 - 9_618-22-100_MPLS_PT_IFB_MECH_230404.pdf PDF
Attachment D.8 - 7_618-22-100_MPLS_PT_IFB_PLUMB_230404.pdf PDF
Attachment D.4 - 4_618-22-100_MPLS_PT_IFB_EQUIP_230404.pdf PDF
Show all 35

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

FIRE PROTECTION SYMBOL LEGEND

DRAWING NUMBER WHERE DETAILED

SECTION LETTER

DRAWING NUMBER WHERE DETAILED

DETAIL NUMBER

DRAWING NUMBER WHERE DETAILED

ELEVATION LETTER

SECTION, ELEVATION, AND DETAIL TITLES

FX200

FX500

FX300

ELEVATION

DETAIL

SECTION

FX-100

A

FX500

A

C.P.

DISCHARGE NOZZLE

CONTROL PANEL

CLEAN AGENT FIRE SUPPRESSION

FIRE HOSE VALVE CABINET

FIRE HOSE CABINET

ALARM BELL

WATER MOTOR GONG

PENETRATION

TEST PLUG (PRESS/TEMP)

WH

PRESSURE GAUGE AND GAUGE COCK

NEW PIPE CONNECTION TO EXISTING PIPING

EXISTING PIPE TO BE REMOVED

EXISTING PIPING TO REMAIN

NEW PIPING

FLEXIBLE CONNECTION

ORIFICE UNION

FLANGED UNION

UNION

RISE IN PIPE

DROP IN PIPE

CAPPED OUTLET

SIDE CONNECTION

BOTTOM CONNECTION, 45° OR 90°

TOP CONNECTION, 45° OR 90°

ECCENTRIC REDUCER

REDUCER OR INCREASER

DIRECTION OF FLOW

MAV MANUAL AIR VENT (MAV)

AAV AUTOMATIC AIR VENT (AAV)

AG AIR GAP FITTING

WALL HYDRANT

POINT OF CONNECTION TO EXISTING

KEYED NOTE

SCHEMATIC SYMBOLS

ABBREVIATIONSYMBOL DESCRIPTION

XX

STANDPIPE VALVE

INSPECTOR'S TEST CONNECTION (VERTICAL)DFP

D

FP INSPECTOR'S TEST CONNECTION (HORIZONTAL)

FP WET PIPE FIRE RISERFP

(E)FDC

FDC

FLOW SWITCH

FDC (E) EXISTING FIRE DEPARTMENT INLET CONNECTION

FIRE DEPARTMENT INLET CONNECTIONFDC

FLOW CONTROL VALVE

ATMOSPHERIC VACUUM BREAKER

PRESSURE STYLE VACUUM BREAKER

DIAPHRAGM (PROCESS SYSTEMS)

OS&Y VALVE

GATE VALVE

GLOBE VALVE

BUTTERFLY VALVE

BALL VALVE

CHECK VALVE

WATER PRESSURE REDUCING VALVE

PRESSURE RELIEF VALVE

TEMPERATURE AND PRESSURE RELIEF VALVE

VALVE IN VERTICAL

REDUCED PRESSURE BACKFLOW PREVENTER (RPBP)

DRAIN VALVE

FP ROOF MANIFOLD

AUTO BALL DRIP VALVE

OR OR

OR

ABBREVIATION DESCRIPTIONSYMBOL

VALVE SYMBOLS

ABBREVIATIONS

SYMBOL DESCRIPTION

NEW PENDANT STYLE SPRINKLER HEAD

FP

SP STANDPIPE; WETSP

FP FIRE PROTECTION; WET PIPE

ABBREVIATIONSYMBOL DESCRIPTION

PIPING SYMBOLS

FIRE PROTECTION-INTERIOR

ORDINARY GROUP 1 HAZARD

ORDINARY GROUP 2 HAZARD

OH1

OH2

DEMO PENDANT STYLE SPRINKLER HEAD

UPRIGHT STYLE SPRINKLER HEAD

DEMO UPRIGHT STYLE SPRINKLER HEAD

F.D.C.(E)FIRE DEPARTMENT INLET CONNECTION F.D.C.

REDUCED PRESSURE BACKFLOW PREVENTER

F.H.(E)F.H.

CONSTRUCTION

FIRE HYDRANT

VALVE WITH VALVE BOX

FIRE PROTECTION

POST INDICATOR VALVE

PIV PIV(E)

F F(E)

EXISTINGNEWDESCRIPTION

SITE UTILITY SYMBOLS

DRAWING NUMBER WHERE DETAILED

SECTION LETTER

DRAWING NUMBER WHERE DETAILED

DETAIL NUMBER

SECTION, ELEVATION, AND DETAIL SYMBOLS

FX-100

A

DRAWING NUMBER WHERE DETAILED

ELEVATION LETTER

GENERAL NOTES:

NOTE: NOT ALL ABBREVIATIONS AND

SYMBOLS APPLY TO THIS PROJECT.

1. ALL NEW PIPING FOR SPRINKLER HEADS SHALL BE HARD PIPED. FLEXIBLE CONNECTIONS ARE PERMISSIBLE AS THEY ARE

PERMITTED BY THE VAFPDM.

2. ALL PIPING IN FINISHED ROOMS OR SPACES SHALL BE CONCEALED IN FURRED CHASES OR SUSPENDED CEILINGS, UNLESS

OTHERWISE NOTED.

3. PROVIDE ACCESS PANELS OR DOORS IN INACCESSIBLE CEILINGS AND/OR CHASES FOR ALL VALVES. THEY SHALL BE FURNISHED UNDER DIVISION 23 AND INSTALLED UNDER THE ARCHITECTURAL SPECIFICATION. ACCESS DOOR RATING SHALL MATCH

CLASSIFICATION OF WALL AND CEILING FIRE RATING.

COORDINATE THE LOCATION OF SPRINKLER HEADS AND ACCESS DOORS WITH THE ARCHITECTURAL REFLECTED CEILING PLAN(S).

4. REFER TO THE ARCHITECTURAL DRAWINGS FOR EXACT LOCATION OF ALL FIRE RATED AND/OR SMOKE RATED WALLS AND ASSEMBLIES. ALL PIPE PENETRATIONS OF FIRE, SMOKE AND FULL HEIGHT WALLS SHALL BE CAULKED AIRTIGHT TO THE ADJACENT

STRUCTURE BY MEANS OF U.L. APPROVED FIRE PROOF CAULKING MATERIAL.

5. CONTRACTOR SHALL COORDINATE ALL FIRE PROTECTION PIPING WITH DUCTWORK, PIPING, PLUMBING, STRUCTURAL AND ELECTRICAL SYSTEMS AND SHALL PROVIDE NECESSARY OFFSETS TO AVOID CONFLICTS AND TO MAINTAIN EQUIPMENT ACCESS

AND SERVICEABILITY.

6. CONTRACTOR SHALL FURNISH ALL NECESSARY STRUCTURES, INSERTS, SLEEVES, AND HANGING DEVICES FOR INSTALLATION OF

PIPING.

7. CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING ALL NECESSARY MISCELLANEOUS ANGLES, CHANNELS, UNISTRUT, ETC., AS MAY BE REQUIRED TO ADEQUATELY SUPPORT FIRE PROTECTION PIPING AND EQUIPMENT IN A MANNER APPROVED BY THE

ARCHITECT, WHICH WILL NOT OVERLOAD THE BUILDING STRUCTURAL SYSTEM.

8. IT IS CRITICAL THAT THE CONTRACTOR PERFORM A COMPLETE REVIEW OF ALL SUBMITTALS PRIOR TO SUBMISSION TO THE AE/COR. INCOMPLETE, INCORRECT AND UNCLEAR SUBMITTALS WILL BE RETURNED AND MARKED AS "REVISE AND RESUBMIT". ALL SUBMITTALS MUST CLEARLY INDICATE THE EQUIPMENT SELECTIONS FOR THE PROJECT. TECHNICAL DRAWINGS OF COMPLETE ASSEMBLIES, REFLECTING ACCURATE PROJECT CONDITIONS, SHALL BE SUBMITTED WITH EQUIPMENT SELECTIONS TO ENSURE SPACE ALLOWANCES ARE REFLECTED IN THE ACTUAL SPACE AVAILABLE. WHERE SIZE DEVIATIONS DIFFER FROM THE BASIS OF DESIGN, CONTRACTOR SHALL HIGHLIGHT THE DIFFERENCES FOR AE/COR REVIEW WITHIN THE SUBMITTAL. CONTRACTOR SHALL PROVIDE INSTALLATION ROUTE AND VERIFICATION THAT ACCESS POINTS, PLACEMENT ROUTE, SUPPORTS, AND REQUIRED EQUIPMENT CLEARANCES ARE IDENTIFIED ON THE ROUTE DRAWING. SAFETY PROTOCOLS FOR SUBJECT STATION SHALL BE REFLECTED ON EQUIPMENT CLEARANCES. PLATFORMS AND INTERFACE AREAS (FILTER, GAUGES, MONITORS, VALVES, ETC.)

SHALL HAVE PROPER CLEARANCE AS DEFINED BY THE MANUFACTURER, VA SAFETY PERSONNEL AND SERVICE PERSONNEL.

ACCESS POINTS OF USE SHALL BE CLEARLY IDENTIFIED ON THE DRAWINGS.

1. THE DEMOLITION DRAWINGS REFLECT INFORMATION ON EXISTING BUILDING SERVICES GATHERED BY SITE INSPECTION, DISCUSSIONS WITH MAINTENANCE PERSONNEL AND PREVIOUS CONSTRUCTION DRAWINGS. THE EXACT LOCATION, ARRANGEMENT, AND SIZES OF PIPELINES IN THE EXISTING BUILDING MAY BE DIFFERENT FROM THAT SHOWN ON THESE

DRAWINGS.

2. THE CONTRACTOR SHALL COORDINATE THE SHUTDOWN OF EXISTING BUILDING SERVICES FOR REMOVALS WITH OWNER

AUTHORIZED REPRESENTATIVE AND SHALL CONFORM TO THEIR REQUIREMENTS.

3. DISRUPTION OF NORMAL FACILITY ACTIVITIES ARE TO BE KEPT TO AN ABSOLUTE MINIMUM. DUST, DEBRIS, AND FUMES SHALL BE CONTROLLED SO AS NOT TO AFFECT THE HEALTH AND SAFETY OF OCCUPIED AREAS WITHIN THE FACILITY WHICH ARE OUTSIDE THE AREA OF WORK. COORDINATE WITH THE ARCHITECT AND THE OWNER'S REPRESENTATIVE WITH REGARD TO ALL ACTIVITIES TO BE CONDUCTED OUTSIDE OF THE SUITE REMODEL AREA WHICH MAY AFFECT THE OPERATION OF THE FACILITY. THE CONTRACTOR SHALL PROVIDE TEMPORARY VENTILATION (MAINTAIN WORK ZONE AT NEGATIVE PRESSURE), FILTRATION, AIR PURIFIERS, DUST SCREENS, ETC. FOR ALL WORK AREAS AFFECTED BY DEMOLITION FOR NEW INSTALLATION TO MINIMIZE DUST

AND FUMES.

4. THE CONTRACTOR SHALL PRESENT AN AREA BY AREA WORK PLAN WELL IN ADVANCE TO THE ARCHITECT AND THE OWNER'S AUTHORIZED REPRESENTATIVE FOR APPROVAL PRIOR TO BEGINNING WORK. THE WORK PLAN SHALL INCLUDE AN OUTLINE OF ALL ACTIVITIES OF ALL SUBCONTRACTORS. THE CONTRACTOR SHALL COORDINATE WITH THE OWNER'S AUTHORIZED REPRESENTATIVE TO ESTABLISH ACCEPTABLE ROUTING AND ACCESS FOR MATERIALS REQUIRED FOR THE NEW INSTALLATION.

5. GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATION OF ALL TRADES INCLUDING MECHANICAL, PLUMBING, ELECTRICAL, FURNITURE, AND ARCHITECTURAL. ANY DISCREPANCIES SHALL BE REPORTED IMMEDIATELY TO THE ARCHITECT

PRIOR TO START OF WORK.

6. ALL NEW TO EXISTING PIPE CONNECTIONS SHALL BE FIELD VERIFIED PRIOR TO ORDERING AND FABRICATING NEW PIPING OR

FITTINGS.

GENERAL DEMO NOTES:

• CONTRACTOR SHALL REPLACE AND RELOCATE EXISTING FIRE SPRINKLER HEAD DROPS TO SERVE THE NEW SPRINKLERS AT THE

NEW LOCATIONS.

• WHERE REQUIRED, CONTRACTOR SHALL REPLACE EXISTING FIRE PROTECTION BRANCH PIPING TO SERVE THE NEW LOCATIONS.

• CONTRACTOR SHALL PROVIDE COMPLETE FIRE PROTECTION SYSTEM COORDINATION DRAWINGS TO ENSURE ALL REQUIRED

CLEARANCES ARE MAINTAINED AND THAT NO CONFLICTS EXIST WITH ANY OTHER MECHANICAL, PLUMBING, ELECTRICAL, COMMUNICATIONS, OR STRUCTURAL SYSTEMS.

• CONTRACTOR SHALL MAINTAIN COMPLIANCE WITH THE 2022 NFPA 13 FOR ALL SURROUNDING SPACES DURING AND AFTER

RENOVATION.

• FOR TELECOMMUNICATION ROOMS (TR), THE CONTRACTOR IS RESPONSIBLE FOR PROVIDING A NEW FIRE EXTINGUISHER CABINET WITH A TYPE 2A:10B:C FIRE EXTINGUISHER LOCATED NO GREATER THAN 75 FEET AWAY FROM THE NEW TR.

CONTRACTOR TO COORDINATE THE NEW LOCATION WITH THE COR.

FIRE PROTECTION SCOPE OF WORK:

DN DOWN

YH YARD HYDRANT

ABOVE FINISHED FLOOR

ABOVE FINISHED GRADE

BOTTOM OF PIPE

ELEVATION

FINISHED FLOOR ELEVATION

FEET

GALLONS PER MINUTE

HORSEPOWER

HEAD

INCHES

INVERT

NOT APPLICABLE

NOT IN CONTRACT

NUMBER

NORMALLY CLOSED

NORMALLY OPEN

OUTSIDE SCREW AND YOKE

PHASE

POUNDS PER SQUARE INCH GAUGE

STATIC PRESSURE

TYPICAL

YARD BOX

AFF

AFG

BOP

EL

FFE

FT

GPM

HP

HD

IN

INV

NA

NIC

No. # N.C.

N.O.

OS&Y

PSIG

SP

TYP

YB

PH

QUICK RESPONSE SPRINKLERQRS

NOT TO SCALENTS

CONTRACTING OFFICER'S REPRESENTATIVECOR

FIRE ALARM STROBE/HORN WALL MOUNTED

FIRE ALARM STROBE/HORN CEILING MOUNTED

HEAT/SMOKE DETECTORH

PIPE RING HANGER

TOLCO FIG. 200

BAR JOIST OR STEEL

MEMBER BY

STRUCTURAL

1" MIN.

1" MIN.

SPRINKLER PIPE PER

PLAN

ALL THREAD ROD

TOLCO FIG. 100

REVERSIBLE BEAM CLAMP

(TYPICAL)

TOLCO FIG. 65

RESTRAINING STRAP

(TYPICAL)

TOLCO FIG. 69/69R

BASIS OF DESIGN IS TOLCO FIGURE

NUMBERS OR APPROVED EQUAL.

PIPE PER PLAN PIPE RING HANGER

TOLCO FIG. 200

ALL THREAD ROD

TOLCO FIG. 100

USE 3/8" CONCRETE INSERT FOR

UP TO 4" PIPE

USE 1/2" CONCRETE INSERT FOR

6" AND 8" PIPE

INSERT SHALL BE PLACED WITHIN

THICKEST PORTION OF

CONCRETE DECKING, TYPICAL

CONCRETE

DECKING

BASIS OF DESIGN IS TOLCO FIGURE

NUMBERS OR APPROVED EQUAL.

INSERT IS NOT

PERMITTED WITHIN

DECKING VALLEY,

TYPICAL

BASIS OF DESIGN IS TOLCO FIGURE

NUMBERS OR APPROVED EQUAL.

PIPE CLAMP

FOR SWAY

BRACING

TOLCO FIG. 4A

SPRINKLER PIPE PER PLAN

STEEL PIPE

LATERAL

BRACE

NO-THREAD SWIVEL

SWAY BRACE

ATTACHMENT TYP.

TOLCO FIG. 909

SWAY BRACE

ATTACHMENT

TO STEEL

TOLCO FIG. 800

BAR JOIST OR STEEL

MEMBER BY STRUCTURAL

BASIS OF DESIGN IS TOLCO FIGURE

NUMBERS OR APPROVED EQUAL.

SWAY BRACE

ATTACHMENT

TOLCO FIG.

SPRINKLER PIPE PER

PLAN

STEEL PIPE

LATERAL

BRACE

NO-THREAD SWIVEL

SWAY BRACE

ATTACHMENT

TOLCO FIG. 909

SWAY BRACE

ATTACHMENT

TO STEEL

TOLCO FIG. 800

BAR JOIST OR STEEL

MEMBER BY STRUCTURAL

NO-THREAD SWIVEL

SWAY BRACE

ATTACHMENT TYP.

TOLCO FIG. 909

BASIS OF DESIGN IS TOLCO FIGURE

NUMBERS OR APPROVED EQUAL.

"FAST CLAMP" BRANCH LINE

RESTRAINT ATTACHMENT

TYP.

TOLCO FIG. 909

BAR JOIST OR STEEL

MEMBER BY STRUCTURAL

SPRINKLER PIPE PER

PLAN

STEEL PIPE

LATERAL

BRACE

on e-ei gh th in ch o ne fo ot on e-qu ar te r ne fo ot th re e-ei gh th s ne fo ot on e-ha lf ne fo ot th re e-qu ar te r ne fo ot in ch on e ne fo ot on e an d on e-ha lf ne fo ot th re e in es ne fo ot

REVISIONS DATE

General Notes:

GENERAL CONTRACTOR AND/OR ALL SUBCONTRACTORS SHALL FIELD VERIFY ALL DIMENSIONS SHOWN ON THESE PLANS AND SHALL BE RESPONSIBLE FOR VARIATIONS BETWEEN PLAN DIMENSIONS AND ACTUAL FIELD DIMENSIONS. WHERE VARIATIONS ARE FOUND TO OCCUR, THE CONTRACTOR SHALL NOTIFY THE PROJECT ENGINEER IN WRITING PRIOR TO PROCEEDING WITH CONSTRUCTION; NO ADJUSTMENT TO

THE WORK WILL BE MADE WITHOUT THE PRIOR APPROVAL OF THE PROJECT ENGINEER.

GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR GENERAL DEMOLITION INCLUDING REMOVAL OF WALLS, PARTITIONS, DOORS & CEILING & FLOORS. ANY AND ALL CUTTING OF CONCRETE FLOORS, WALLS OR STRUCTURE SHALL BE THE GENERAL CONTRACTOR'S RESPONSIBILITY. CORE DRILLING THROUGH CONCRETE WALLS, FLOORS OR STRUCTURE FOR PIPING OR CONDUIT SHALL BE THE RESPONSIBILITY OF THE SUBCONTRACTOR BY TRADE; FIRESTOPPING OF THESE OPENINGS SHALL BE DONE BY THE RESPECTIVE SUBCONTRACTOR. REMOVAL OF DEBRIS RESULTING FROM DEMOLITION, CUTTING, AND/OR DRILLING IS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR. PATCHING AND REPAIR OF CONCRETE WALLS, FLOOR, OR STRUCTURE SHALL BE THE RESPONSIBILITY OF THE GENERAL CONTRACTOR; THIS WILL BE ACCOMPLISHED UPON COMPLETION OF THE INSTALLATION OF ANY AND ALL UTILITIES INSTALLED

BY THE VARIOUS SUBCONTRACTORS.

Approved: Division Chief

Issue Date Checked Drawn

DrawingNumber

Building Number

Project NumberDrawing Title Project Title

Location Drawing Scale

Approved: Service DirectorPlot Scale U.S. Department of Veterans Affairs

Office of Construction and Facilities Management

FULLY SPRINKLERED

Phase

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

TRUE NORTH

PLAN NORTH

KEYPLAN

A/E:

TRIPLE C - The A/E Group

Mat Perkins

(520) 481-8548

A

B D

EF

G

H

J

K

L

M

C

LINE INDICATES

PHASE 1 SCOPE AREA

B

IM

/6

-2

-1

E x p a n d e d P o ly tr a u m a P ro g ra m P h a s e

/6 -2

-7

.M

P L S

.P O

L Y

T R

A U

M A

.G e n e ra l.

S h e e ts

.r v t

/3

/2

:4

:5

P

M As indicated

04/03/2023 K. Luke K.Hutchinson

618-22-100

1390 - FX001

FIRE PROTECTION ABBREVIATIONS,

SYMBOLS, AND DETAILS

1 Veterans Drive, Minneapolis, MN 55417

B70

RENOVATE FOR EXPANDED

POLYTRAUMA PROGRAM

ISSUED FOR BIDDING

NTS

F2

WIDE FLANGE BEAM CLAMP

NTS

F4

DROP-IN ANCHOR

NTS

F5

LONGITUDINAL BRACE DETAIL

NTS

F7

LATERAL BRACE DETAIL

NTS

F9

4-WAY BRACE DETAIL

04/03/2023

H

H H

HHH

H

H

H

H

H

H

H

H

H

H

H

H

H

H

H

H

H

H

H

H

H

H

H

H

H

H

H

H

H

H

H

H

H

H

H

H H

H

H

H

H

H

HH

H

H

H

H

H

H

H

H

H

H

H

H

H

HH

H

H

H

H H

H

H

H

H

HH

H

H

H

H

H H

H

H

H

H H

H

H

H

H

H

HH

H

H

H

H

4G-109B

4G-111

4G-112

4G-114

4S-6

4H-121

4H-122

4H-123

C4-116

4G-116 4G-115 4G-111C 4G-111B 4G-111A

4H-114

4H-115 4H-116 4H-117

4H-118

4H-120

E

C-6

M-8

4L-101

4L-140

C4-126

C4-115

C4-137

4L-102

4L-102A

4H-102

4H-103

4H-104

4H-105

4H-106

4H-107

4H-109 4H-110

4H-111

4H-113

4G-117

4H-101A

4H-101B

C4-110

C4-114

4H-112

4K-101

4H-108C4-138

4H-108A

STAIRWELL 8

SW8

4K-142A

4K-142

4K-140

4K-140A

4K-138A

4K-138

4K-136

4K-136A

4K-134

4K-134A

4K-133A

4K-133

4K-132

4K-131A

4K-131

4K-129

4K-126

4K-127

4K-125 4K-123 4K-122

C4-132

4K-120

4K-121

4K-119

C4-133

4K-117

4K-109

4K-108

4K-106

4K-104

4K-103

4K-101

4H-108

4K-102

4K-107

4K-113

4K-112

4K-1054K-102A

4K-124

4K-124A

4K-124B

STAIRWELL 7

SW7

4K-118

4K-128

4K-130

4K-130A

4K-121A

4K-115

4K-110

4K-111

C-7

C4-131

4K-114

4K-135

4K-137

4K-139

4K-141

4K-143

C4-135

C4-134

C4-138

C4-127

STAIRWELL 8

SW8

4K-116

TTUUVVWWXX

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

AREA NOT IN SCOPE OF WORK

ALL SPRINKLERS AND FIRE DEVICES ARE EXISTING TO REMAIN

/F1 FXD104 /F1 FXD104

TTUUVVWWXXYY

TYP.

1 TYP.

TYP.

AREA NOT IN SCOPE OF WORK

ALL SPRINKLERS AND FIRE DEVICES ARE EXISTING TO REMAIN

AREA NOT IN SCOPE OF WORK

ALL SPRINKLERS AND FIRE DEVICES ARE EXISTING TO REMAIN

/F6 FXD104 /F6 FXD104

WALL SYMBOL LEGEND

CONTRACTOR SHALL CONFIRM ALL FIRE RATED WALL ASSEMBLIES

PROPOSED EXTERIOR WALL.

SEE WALL SECTIONS

1 HR FIRE AND SMOKE

BARRIER

2 HR FIRE AND SMOKE

BARRIER (SHAFT)

SMOKE BARRIER PARTITION

DEMOLISHED WALL,

FIXTURE OR FURNISHING

EXISTING WALL, FIXTURE

OR FURNISHING TO REMAIN

NOT IN CONTRACT - NO

WORK SCHEDULED

on e-ei gh th ne fo ot on e-qu ar te r ne fo ot th re e-ei gh th s ne fo ot on e-ha lf ne fo ot th re e-qu ar te r ne fo ot in ch on e ne fo ot on e an d on e-ha lf ne fo ot th re e in ne fo ot

REVISIONS DATE

General Notes:

GENERAL CONTRACTOR AND/OR ALL SUBCONTRACTORS SHALL FIELD VERIFY ALL DIMENSIONS SHOWN ON THESE PLANS AND SHALL BE RESPONSIBLE FOR VARIATIONS BETWEEN PLAN DIMENSIONS AND ACTUAL FIELD DIMENSIONS. WHERE VARIATIONS ARE FOUND TO OCCUR, THE CONTRACTOR SHALL NOTIFY THE PROJECT ENGINEER IN WRITING PRIOR TO PROCEEDING WITH CONSTRUCTION; NO ADJUSTMENT TO

THE WORK WILL BE MADE WITHOUT THE PRIOR APPROVAL OF THE PROJECT ENGINEER.

GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR GENERAL DEMOLITION INCLUDING REMOVAL OF WALLS, PARTITIONS, DOORS & CEILING & FLOORS. ANY AND ALL CUTTING OF CONCRETE FLOORS, WALLS OR STRUCTURE SHALL BE THE GENERAL CONTRACTOR'S RESPONSIBILITY. CORE DRILLING THROUGH CONCRETE WALLS, FLOORS OR STRUCTURE FOR PIPING OR CONDUIT SHALL BE THE RESPONSIBILITY OF THE SUBCONTRACTOR BY TRADE; FIRESTOPPING OF THESE OPENINGS SHALL BE DONE BY THE RESPECTIVE SUBCONTRACTOR. REMOVAL OF DEBRIS RESULTING FROM DEMOLITION, CUTTING, AND/OR DRILLING IS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR. PATCHING AND REPAIR OF CONCRETE WALLS, FLOOR, OR STRUCTURE SHALL BE THE RESPONSIBILITY OF THE GENERAL CONTRACTOR; THIS WILL BE ACCOMPLISHED UPON COMPLETION OF THE INSTALLATION OF ANY AND ALL UTILITIES INSTALLED

BY THE VARIOUS SUBCONTRACTORS.

Approved: Division Chief

Issue Date Checked Drawn

DrawingNumber

Building Number

Project NumberDrawing Title Project Title

Location Drawing Scale

Approved: Service DirectorPlot Scale U.S. Department of Veterans Affairs

Office of Construction and Facilities Management

FULLY SPRINKLERED

Phase

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

TRUE NORTH

PLAN NORTH

KEYPLAN

A/E:

TRIPLE C - The A/E Group

Mat Perkins

(520) 481-8548

A

B D

EF

G

H

J

K

L

M

C

GENERAL NOTES

LINE INDICATES

PHASE 1 SCOPE AREA

B

IM

/6

-2

-1

E x p a n d e d P o ly tr a u m a P ro g ra m P h a s e

/6 -2

-7

.M

P L S

.P O

L Y

T R

A U

M A

.M E

P .B

.L

.r v t

/4

/2

:4

:1

A

M As indicated

04/03/2023 K. Luke K.Hutchinson

618-22-100

1390 -

FXD104

FIRE PROTECTION DEMO PLANS - FOURTH

LEVEL - AREA 4H&4K

1 Veterans Drive, Minneapolis, MN 55417

B70

RENOVATE FOR EXPANDED

POLYTRAUMA PROGRAM - PHASE 1

ISSUED FOR BIDDING

1/8" = 1'-0" F6

FIRE PROTECTION DEMO RCP - FOURTH LEVEL - AREA 4K

1/8" = 1'-0"

F1

FIRE PROTECTION DEMO RCP - FOURTH LEVEL - AREA 4H

CONTRACTOR SHALL PROVIDE THE FOLLOWING PRIOR TO

COMMENCEMENT OF WORK FOR REVIEW AND APPROVAL:

A. SHOP DRAWING IDENTIFYING MAIN PIPE SIZES AND LOCATIONS,

LOCATION OF PIPE BRACING, HANGERS AND SPRINKLER HEADS

AND DETAILS

B. CUT SHEETS AND SUBMITTAL FOR ALL PIPING, FITTINGS,

SPRINKLER HEADS, HANGERS AND SUPPORT ATTACHMENTS

A. EXISTING CONDITIONS ARE BASED ON EXISTING PLANS AND FIELD VERIFICATION

WHERE FEASIBLE. ACTUAL CONDITIONS MAY DIFFER FROM THOSE INDICATED.

CONTRACTOR SHALL FIELD VERIFY IN ADVANCE THE LOCATION AND CONDITION OF

THE EXISTING SYSTEMS SHOWN TO BE MODIFIED OR REMOVED. CONTRACTOR TO

NOTIFY ARCHITECT SHOULD CONDITIONS BE FOUND TO DIFFER SIGNIFICANTLY

FROM THE CONSTRUCTION DOCUMENTS.

B. DETAILED SCHEDULE, INCLUDING PROJECTED SERVICE INTERRUPTION DATES WITH

DURATIONS, AND DETAILED PHASING PLAN IS TO BE PROVIDED TO THE COR PRIOR

TO THE START OF WORK. THIS SUBMITTAL MUST BE ACCEPTED BY THE COR PRIOR

TO THE START OF WORK.

C. REFER TO ARCHITECTURAL DRAWINGS FOR EXACT DIMENSIONAL DATA, CEILING

HEIGHTS, AND SQUARE FOOTAGE.

D. CONTRACTOR SHALL COORDINATE ALL WORK WITH BUILDING OWNER AND OTHER

TRADES PRIOR TO CONSTRUCTION.

E. ALL PIPING TO BE ROUTED WITHIN CEILING SPACE OR CONCEALED IN FURRED

CHASES UNLESS NOTED OTHERWISE.

F. ALL AREAS ARE DESIGNED AS LIGHT HAZARD OCCUPANCY UNLESS NOTED

OTHERWISE ON PLAN.

G. ALL SPRINKLERS SYSTEMS SHALL BE INSTALLED IN ACCORDANCE WITH THE 2022

NFPA 13.

H. ALL MATERIALS, DEVICES, HANGERS AND SUPPORTS SHALL BE NEW AND UL LISTED

FOR USE IN FIRE PROTECTION SYSTEMS.

I. ALL NEW SPRINKLERS SHALL BE PROVIDED WITH NEW ESCUTCHEONS TO MATCH

EXISTING BUILDING STANDARDS.

J. INSTALL QUICK RESPONSE SPRINKLERS (QRS) IN ALL AREAS, EXCEPT WHERE

SPECIFICALLY PROHIBITED AS DEFINED BY 2022 NFPA 13.

K. PIPING TO BE SCHEDULE 40 BLACK STEEL WITH CAST IRON FITTINGS.

L. ANY FLOOR, WALL, OR CEILING CUTTING OR FILLING THAT IS REQUIRED TO

COMPLETE THIS PROJECT, THE CONTRACTOR SHALL PATCH AND PAINT AND

RETURN TO MATCH EXISTING CONDITIONS AND FINISHES.

M. CONTRACTOR TO PROVIDE GALVANIC PROTECTION AS REQUIRED AT CONNECTIONS

BETWEEN ALL DISSIMILAR METALS.

N. CONTRACTOR TO VALIDATE AND VERIFY ALL FIRE RATED AND/OR SMOKE RATED

WALLS AND ASSEMBLIES INDICATED ON PLANS IN WORK AREA. PROVIDE ALL PIPING

PENETRATIONS OF FIRE, SMOKE AND FULL HEIGHT WALLS SHALL BE CAULKED

AIRTIGHT TO THE ADJACENT STRUCTURE BY MEANS OF U.L. APPROVED FIRE PROOF

CAULKING MATERIAL. CONTRACTOR SHALL PROVIDE SPECIAL INSPECTIONS OF ALL

UL RATED PENETRATIONS BY A LICENSED INSPECTOR.

O. ALL NEW PIPES TO BE CLEANED AND TESTED PRIOR TO COMMISSIONING.

P. THE SPRINKLER CONTRACTOR SHALL COORDINATE AND PERFORM ALL FIRE

PROTECTION WORK IN ACCORDANCE WITH VA REQUIREMENTS TO ENSURE THAT

CONTINUOUS SPRINKLER COVERAGE IS PROVIDED THROUGHOUT THE PROJECT.

THE SPRINKLER CONTRACTOR SHALL COORDINATE ALL FIRE PROTECTION SYSTEM

SHUTDOWNS, INCLUDING POINTS OF TIE IN, ETC. WITH THE VA PRIOR TO

PERFORMING WORK.

Q. CONTRACTOR IS RESPONSIBLE FOR MAINTAINING COMPLIANCE WITH THE 2022

NFPA 13 FOR SURROUNDING SPACES DURING AND AFTER RENOVATION.

CONTRACTOR IS RESPONSIBLE FOR FIELD VERIFYING SPRINKLER HEAD LOCATIONS

AND PIPING TO BE MODIFIED BY THE RENOVATION PRIOR TO COMMENCING WORK.

R. DURING CONSTRUCTION ENSURE ALL SPRINKLERS ARE THE CORRECT DISTANCE

TO THE DECK WHEN THE CEILING IS NOT INSTALLED.

S. ALL SPRINKLER HEADS WILL BE REPLACED DURING THIS PROJECT. ALL SPRINKLER

HEADS TO BE PENDENT TYPE, SEE HAZARD CHART FOR ADDITIONAL INFORMATION.

NOTE: NOT ALL KEYNOTES

ARE USED ON EACH SHEETKEYNOTES

1. EXISTING PENDENT SPRINKLER HEAD AND BRANCH PIPING TO BE REMOVED BACK

TO NEAREST BRANCH LINE OR MAIN. RECONFIGURE EXISTING SPRINKLER SYSTEM

AS REQUIRED FOR NEW SPRINKLER HEAD LOCATIONS.

2. EXISTING 6" STAND PIPE, FIRE PROTECTION RISER.

3. REMOVE EXISTING HEAT/SMOKE DETECTOR. COORDINATE WITH COR.

4. REMOVE EXISTING FIRE ALARM STROBE/HORN. COORDINATE WITH COR.

5. EXISTING FIRE SUPPRESSION CONTROL VALVE ASSEMBLY TO REMAIN

CONTRACTOR TO COORDINATE SHUTDOWN WITH COR PRIOR TO

COMMENCEMENT OF WORK.

6. EXISTING PIPING DROP FROM INTERSTITIAL SPACE TO PLENUM SPACE BELOW TO

REMAIN. PROTECT IN PLACE.

7. CONTRACTOR TO FIELD COORDINATE EXTENTS OF DEMO FOR EXISTING PIPING

RECONFIGURATION.

8. EXISTING 2-1/2" FDV, T CAP AND PIPING CONNECTED TO STANDPIPE ARE LOCATED

IN PLENUM SPACE ABOVE AND ARE EXISTING TO REMAIN. PROTECT IN PLACE.

SHOWN ON RCP LEVEL FOR COORDINATION AND REFERENCE ONLY.

9. EXISTING 6" STAND PIPE, FIRE PROTECTION RISER AND FIRE SPRINKER PIPING

BETWEEN STANDPIPIES ARE LOCATED IN INTERSTITIAL SPACE ABOVE AND ARE

EXISTING TO REMAIN. SHOWN ON RCP LEVEL FOR COORDINATION AND

REFERENCE ONLY.

10. EXISTING 2-1/2" FIRE LINE DOWN TO PLENUM.

11. EXISTING 2" FIRE LINE DRAIN TO REMAIN, PROTECT IN PLACE.

12. EXISTING 2-1/2" FIRE LINE DOWN TO F.V.C, DEMOLISH AND REPLACE F.V.C ON

NEAREST WALL.

13. EXISTING 4" STANDPIPE TO REMAIN, PROTECT IN PLACE.

TTUUVVWWXX

MECHANICAL

4K-124

WS

WS

ZONE #105

ZONE #106

TYP.

4TH LEVEL INTERSTITIAL

4H

2 1/2" F

2" F

2 1/2" F

2 1/2" F

S M

O K

E Z

O N

E

S M

O K

E Z

O N

E

S M

O K

E Z

O N

E

S M

O K

E Z

O N

E

S M

O K

E Z

O N

E

S M

O K

E Z

O N

E

SMOKE ZONE #_ _ _

SMOKE ZONE #_ _ _

/F1 FXD104i /F1 FXD104i

TTUUVVWWXXYY

WS

WS

ZONE #104

ZONE #107

4TH LEVEL INTERSTITIAL

4H

2 1/2" F

2 1/2" F

2" F

2" F

2" F

TYP.

/F6 FXD104i /F6 FXD104i

WALL SYMBOL LEGEND

CONTRACTOR SHALL CONFIRM ALL FIRE RATED WALL ASSEMBLIES

PROPOSED EXTERIOR WALL.

SEE WALL SECTIONS

1 HR FIRE AND SMOKE

BARRIER

2 HR FIRE AND SMOKE

BARRIER (SHAFT)

SMOKE BARRIER PARTITION

DEMOLISHED WALL,

FIXTURE OR FURNISHING

EXISTING WALL, FIXTURE

OR FURNISHING TO REMAIN

NOT IN CONTRACT - NO

WORK SCHEDULED

on e-ei gh th ne fo ot on e-qu ar te r ne fo ot th re e-ei gh th s ne fo ot on e-ha lf ne fo ot th re e-qu ar te r ne fo ot in ch on e ne fo ot on e an d on e-ha lf ne fo ot th re e in ne fo ot

REVISIONS DATE

General Notes:

GENERAL CONTRACTOR AND/OR ALL SUBCONTRACTORS SHALL FIELD VERIFY ALL DIMENSIONS SHOWN ON THESE PLANS AND SHALL BE RESPONSIBLE FOR VARIATIONS BETWEEN PLAN DIMENSIONS AND ACTUAL FIELD DIMENSIONS. WHERE VARIATIONS ARE FOUND TO OCCUR, THE CONTRACTOR SHALL NOTIFY THE PROJECT ENGINEER IN WRITING PRIOR TO PROCEEDING WITH CONSTRUCTION; NO ADJUSTMENT TO

THE WORK WILL BE MADE WITHOUT THE PRIOR APPROVAL OF THE PROJECT ENGINEER.

GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR GENERAL DEMOLITION INCLUDING REMOVAL OF WALLS, PARTITIONS, DOORS & CEILING & FLOORS. ANY AND ALL CUTTING OF CONCRETE FLOORS, WALLS OR STRUCTURE SHALL BE THE GENERAL CONTRACTOR'S RESPONSIBILITY. CORE DRILLING THROUGH CONCRETE WALLS, FLOORS OR STRUCTURE FOR PIPING OR CONDUIT SHALL BE THE RESPONSIBILITY OF THE SUBCONTRACTOR BY TRADE; FIRESTOPPING OF THESE OPENINGS SHALL BE DONE BY THE RESPECTIVE SUBCONTRACTOR. REMOVAL OF DEBRIS RESULTING FROM DEMOLITION, CUTTING, AND/OR DRILLING IS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR. PATCHING AND REPAIR OF CONCRETE WALLS, FLOOR, OR STRUCTURE SHALL BE THE RESPONSIBILITY OF THE GENERAL CONTRACTOR; THIS WILL BE ACCOMPLISHED UPON COMPLETION OF THE INSTALLATION OF ANY AND ALL UTILITIES INSTALLED

BY THE VARIOUS SUBCONTRACTORS.

Approved: Division Chief

Issue Date Checked Drawn

DrawingNumber

Building Number

Project NumberDrawing Title Project Title

Location Drawing Scale

Approved: Service DirectorPlot Scale U.S. Department of Veterans Affairs

Office of Construction and Facilities Management

FULLY SPRINKLERED

Phase

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

TRUE NORTH

PLAN NORTH

KEYPLAN

A/E:

TRIPLE C - The A/E Group

Mat Perkins

(520) 481-8548

A

B D

EF

G

H

J

K

L

M

C

GENERAL NOTES

LINE INDICATES

PHASE 1 SCOPE AREA

B

IM

/6

-2

-1

E x p a n d e d P o ly tr a u m a P ro g ra m P h a s e

/6 -2

-7

.M

P L S

.P O

L Y

T R

A U

M A

.M E

P .B

.L

.r v t

/3

/2

:2

:4

P

M As indicated

04/03/2023 K. Luke K.Hutchinson

618-22-100

1390 - FXD104i

FIRE PROTECTION DEMO PLANS - FOURTH

LEVEL INTERSTITIAL - AREA 4H&K

1 Veterans Drive, Minneapolis, MN 55417

B70

RENOVATE FOR EXPANDED

POLYTRAUMA PROGRAM - PHASE 1

ISSUED FOR BIDDING

1. EXISTING PENDENT SPRINKLER HEAD AND BRANCH PIPING TO BE REMOVED BACK

TO NEAREST BRANCH LINE OR MAIN. RECONFIGURE EXISTING SPRINKLER SYSTEM

AS REQUIRED FOR NEW SPRINKLER HEAD LOCATIONS.

2. EXISTING 6" STAND PIPE, FIRE PROTECTION RISER.

3. REMOVE EXISTING HEAT/SMOKE DETECTOR. COORDINATE WITH COR.

4. REMOVE EXISTING FIRE ALARM STROBE/HORN. COORDINATE WITH COR.

5. EXISTING FIRE SUPPRESSION CONTROL VALVE ASSEMBLY TO REMAIN,

CONTRACTOR TO COORDINATE SHUTDOWN WITH COR PRIOR TO

COMMENCEMENT OF WORK.

6. EXISTING PIPING DROP FROM INTERSTITIAL SPACE TO PLENUM SPACE BELOW TO

REMAIN, PROTECT IN PLACE.

7. CONTRACTOR TO FIELD COORDINATE EXTENTS OF DEMO FOR EXISTING PIPING

RECONFIGURATION.

8. EXISTING 2-1/2" FDV, T CAP AND PIPING CONNECTED TO STANDPIPE ARE LOCATED

IN PLENUM SPACE ABOVE AND ARE EXISTING TO REMAIN. PROTECT IN PLACE.

SHOWN ON RCP LEVEL FOR COORDINATION AND REFERENCE ONLY.

9. EXISTING 6" STAND PIPE, FIRE PROTECTION RISER AND FIRE SPRINKLER PIPING

BETWEEN STANDPIPIES ARE LOCATED IN INTERSTITIAL SPACE ABOVE AND ARE

EXISTING TO REMAIN. SHOWN ON RCP LEVEL FOR COORDINATION AND

REFERENCE ONLY.

10. EXISTING 2-1/2" FIRE LINE DOWN TO PLENUM.

11. EXISTING 2" FIRE LINE DRAIN TO REMAIN, PROTECT IN PLACE.

12. EXISTING 2-1/2" FIRE LINE DOWN TO F.V.C TO BE DEMOLISHED AND RELOCATED

TO NEW F.V.C.

13. EXISTING 4" STANDPIPE TO REMAIN, PROTECT IN PLACE.

NOT TO SCALE

B2

SUPPRESSION CONTROL VALVE ASSEMBLY AREA K- REFERENCE PHOTOS

1/8" = 1'-0" F6

FIRE PROTECTION DEMO PLAN - FOURTH LEVEL INTERSTITIAL - AREA 4K

1/8" = 1'-0"

F1

FIRE PROTECTION DEMO PLAN - FOURTH LEVEL INTERSTITIAL - AREA 4H

CONTRACTOR SHALL PROVIDE THE FOLLOWING PRIOR TO

COMMENCEMENT OF WORK FOR REVIEW AND APPROVAL:

A. SHOP DRAWING IDENTIFYING MAIN PIPE SIZES AND LOCATIONS,

LOCATION OF PIPE BRACING, HANGERS AND SPRINKLER HEADS

AND DETAILS

B. CUT SHEETS AND SUBMITTAL FOR ALL PIPING, FITTINGS,

SPRINKLER HEADS, HANGERS AND SUPPORT ATTACHMENTS

A. EXISTING CONDITIONS ARE BASED ON EXISTING PLANS AND FIELD VERIFICATION

WHERE FEASIBLE. ACTUAL CONDITIONS MAY DIFFER FROM THOSE INDICATED.

CONTRACTOR SHALL FIELD VERIFY IN ADVANCE THE LOCATION AND CONDITION OF

THE EXISTING SYSTEMS SHOWN TO BE MODIFIED OR REMOVED. CONTRACTOR TO

NOTIFY ARCHITECT SHOULD CONDITIONS BE FOUND TO DIFFER SIGNIFICANTLY

FROM THE CONSTRUCTION DOCUMENTS.

B. DETAILED SCHEDULE, INCLUDING PROJECTED SERVICE INTERRUPTION DATES WITH

DURATIONS, AND DETAILED PHASING PLAN IS TO BE PROVIDED TO THE COR PRIOR

TO THE START OF WORK. THIS SUBMITTAL MUST BE ACCEPTED BY THE COR PRIOR

TO THE START OF WORK.

C. REFER TO ARCHITECTURAL DRAWINGS FOR EXACT DIMENSIONAL DATA, CEILING

HEIGHTS, AND SQUARE FOOTAGE.

D. CONTRACTOR SHALL COORDINATE ALL WORK WITH BUILDING OWNER AND OTHER

TRADES PRIOR TO CONSTRUCTION.

E. ALL PIPING TO BE ROUTED WITHIN CEILING SPACE OR CONCEALED IN FURRED

CHASES UNLESS NOTED OTHERWISE.

F. ALL AREAS ARE DESIGNED AS LIGHT HAZARD OCCUPANCY UNLESS NOTED

OTHERWISE ON PLAN.

G. ALL SPRINKLERS SYSTEMS SHALL BE INSTALLED IN ACCORDANCE WITH THE 2022

NFPA 13.

H. ALL MATERIALS, DEVICES, HANGERS AND SUPPORTS SHALL BE NEW AND UL LISTED

FOR USE IN FIRE PROTECTION SYSTEMS.

I. ALL NEW SPRINKLERS SHALL BE PROVIDED WITH NEW ESCUTCHEONS TO MATCH

EXISTING BUILDING STANDARDS.

J. INSTALL QUICK RESPONSE SPRINKLERS (QRS) IN ALL AREAS, EXCEPT WHERE

SPECIFICALLY PROHIBITED AS DEFINED BY 2022 NFPA 13.

K. PIPING TO BE SCHEDULE 40 BLACK STEEL WITH CAST IRON FITTINGS.

L. ANY FLOOR, WALL, OR CEILING CUTTING OR FILLING THAT IS REQUIRED TO

COMPLETE THIS PROJECT, THE CONTRACTOR SHALL PATCH AND PAINT AND

RETURN TO MATCH EXISTING CONDITIONS AND FINISHES.

M. CONTRACTOR TO PROVIDE GALVANIC PROTECTION AS REQUIRED AT CONNECTIONS

BETWEEN ALL DISSIMILAR METALS.

N. CONTRACTOR TO VALIDATE AND VERIFY ALL FIRE RATED AND/OR SMOKE RATED

WALLS AND ASSEMBLIES INDICATED ON PLANS IN WORK AREA. PROVIDE ALL PIPING

PENETRATIONS OF FIRE, SMOKE AND FULL HEIGHT WALLS SHALL BE CAULKED

AIRTIGHT TO THE ADJACENT STRUCTURE BY MEANS OF UL APPROVED FIRE PROOF

CAULKING MATERIAL. CONTRACTOR SHALL PROVIDE SPECIAL INSPECTIONS OF ALL

UL RATED PENETRATIONS BY A LICENSED INSPECTOR.

O. ALL NEW PIPES TO BE CLEANED AND TESTED PRIOR TO COMMISSIONING.

P. THE SPRINKLER CONTRACTOR SHALL COORDINATE AND PERFORM ALL FIRE

PROTECTION WORK IN ACCORDANCE WITH VA REQUIREMENTS TO ENSURE THAT

CONTINUOUS SPRINKLER COVERAGE IS PROVIDED THROUGHOUT THE PROJECT.

THE SPRINKLER CONTRACTOR SHALL COORDINATE ALL FIRE PROTECTION SYSTEM

SHUTDOWNS, INCLUDING POINTS OF TIE IN, ETC. WITH THE VA PRIOR TO

PERFORMING WORK.

Q. CONTRACTOR IS RESPONSIBLE FOR MAINTAINING COMPLIANCE WITH THE 2022

NFPA 13 FOR SURROUNDING SPACES DURING AND AFTER RENOVATION.

CONTRACTOR IS RESPONSIBLE FOR FIELD VERIFYING SPRINKLER HEAD LOCATIONS

AND PIPING TO BE MODIFIED BY THE RENOVATION PRIOR TO COMMENCING WORK.

R. DURING CONSTRUCTION, ENSURE ALL SPRINKLERS ARE THE CORRECT DISTANCE

TO THE DECK WHEN THE CEILING IS NOT INSTALLED.

S. ALL SPRINKLER HEADS WILL BE REPLACED DURING THIS PROJECT. ALL SPRINKLER

HEADS TO BE PENDENT TYPE, SEE HAZARD CHART FOR ADDITIONAL INFORMATION.

NOTE: NOT ALL KEYNOTES

ARE USED ON EACH SHEETKEYNOTES

H

H

H

HH

H

H

H H

F A

C P

TTUUVVWWXXYY

AREA NOT IN SCOPE OF WORK

SPRINKLERS AND FIRE ALARM

DEVICES ARE EXISTING TO REMAIN

4G-111

4G-112

4G-114

SHAFT

4S-6

4G-116 4G-115 4G-111C 4G-111B 4G-111A

ELEVATORS

E 4L-101

4L-140

4L-102

4L-102A

4J-101

4J-1024J-103

4J-102B 4J-103B

4J-102A4J-103A

C4-142

C4-141

C4-139

NOURISH.

4H-110

BREAK RM

4H-113

TR

4H-114

ELEV. LOBBY

4H-115

ELEV. LOBBY

C4-115

FAMILY CONF.

4H-111

CENTRAL NURSE STATION

4H-107

M LOCKERS

4H-105

TLT

4H-102

TLT

4H-101

W LOCKERS

4H-104

NURSING MOTHERS RM

4H-104A

MED RM

4H-107A

FAMILY ROOM

4H-109

STAFF CORR.

4H-103

CORR.

C4-137

ENTRY CORR.

C4-114

CARTS

C4-126

ANM + 1

4K-101

REC STOR

4K-127

STOR.

4H-108A

DINING ACUTE

4H-108

TLT

4K-103A

CARTS

4K-149

VACANT (FINISH PHASE 2)

4H-100

HAND WASH

4K-152

NURSE MNGR

4H-106

P1:S23 P1:S22

P1:S8

P1:S45

P1:S46 P1:S13

P1:S52

P1:S56 P1:S55

P1:S54 P1:S53

P1:S80P1:S68

P1:S67

P1:S66

N1-18P1:S57

P1:S69

P1:S70

P1:S64

P1:S61

P1:S65

P1:S60

P1:S59

P1:S71

P1:S58

P1:S72

P1:S73

P1:S74

P1:S77 P1:S79

P1:S78

P1:S76

P1:S75

N1-8N1-13

N1-15 N1-14

N1-16 N1-17

N1-25

N1-22N1-21

N1-26

N1-20N1-19

5 5

5 5

TYP.

5 5

6 6

6 6

P1:S38

6' - 11" 7' - 5 1/2"

5' - 0 1/2"

/2

/2

AREA NOT IN SCOPE OF WORK

SPRINKLERS AND FIRE ALARM

DEVICES ARE EXISTING TO REMAIN

5' - 10 1/2" 10' - 0" 10' - 0" 6' - 5 1/2"

" 2' - 10 1/2"

/2

TYP.

/2

5' - 0 1/2" 6' - 11 1/2"

TYP.

2' - 11" 4' - 11"

/2

6' - 4" 6' - 6 1/2"

TYP.

4' - 1"

/2

6' - 2"

HOLD

7' - 6"

6' - 11" 4' - 1 1/2"

5' - 10 1/2" 8' - 0" 4' - 10"

/2

/2

/2

4' - 10"

TYP.

4' - 6"

4' - 8 1/2"

5' - 0 1/2" 8' - 0" 10' - 0" 14' - 0" 7' - 0 1/2"

OFFICE

4H-123

/2

/2

5' - 10" 5' - 1 1/2"

4' - 0"

TYP.

4' - 1"

/2

/2

TYP.

3' - 11 1/2"3' - 11 1/2"

5' - 7 1/2" 10' - 0" 10' - 0" 10' - 0" 8' - 0" 5' - 7 1/2"

2' - 9" 8' - 0"

HOLD

7' - 6"

"TYP.

/2

TYP.

/2

4' - 6 1/2" 7' - 3"

1' - 11"

HOLD

7' - 6" 14' - 0" 5' - 2"

/2

/2

5' - 3 1/2"

TYP.

TYP.

2' - 9" 13' - 8" 14' - 0" 10' - 2" 2' - 3 1/2"

TR IS NOT IN SCOPE.

SPRINKLERS AND FIRE ALARM

DEVICES ARE A PART OF EHRM

SCOPE.

/2

5' - 2 1/2" 4

5' - 0 1/2" 6' - 0" 5' - 7 1/2"

TYP.

1' - 6" 8' - 0" 7' - 2 1/2"

/2

TYP.

5' - 1" 14' - 0" 5' - 11 1/2"

/2

/2

TYP.

3' - 0" 10' - 0" 6' - 1 1/2"

/2

TYP.

CORR.

C4-137A

3' - 9" 8' - 0" 5' - 9"

TYP.

CORR.

C4-137

4' - 5 1/2" 12' - 0" 12' - 0" 12' - 0" 12' - 0" 10' - 0" 12' - 0" 1' - 7 1/2"4

/2

TYP.

4' - 0" 9' - 8" 8' - 0" 4' - 5 1/2"

/2

/2

/2

6' - 8" 6' - 6"

TYP.

7 4

/2

/2

5' - 11"

TYP.

/2

4' - 5"

/2

4' - 10" 5' - 0"

TYP.

H O

L D

/2

/2

6' - 0" 7

/2

5' - 7" 8' - 0" 2' - 1 1/2"

TYP.

HOLD

7' - 6" 3' - 4"

/2

HAC

4H-112

STAIRWELL 8

SW8

/F6 FX104 /F6 FX104

TTUUVVWWXX

STORAGE

4K-116B

SOILED UTILITY

4K-118

CLEAN

4K-117

THERAPIST OFFICE

4K-116C

PRIVATE PT

4K-116D

PRIVATE OT

4K-116A

THERAPY GYM

4K-116

REC THERAPY

4K-128

LINEN

4K-109

LAUNDRY

4K-126

STOR.

4K-121

NOURISH.

4H-110

BREAK RM

4H-113

PATIENT ROOM

4K-123

PATIENT ROOM

4K-122

PATIENT ROOM

4K-120

TLT

4K-119A

TLT

4K-120A

TLT

4K-122A

TLT

4K-123A

LSB

4K-106

SW +1

4K-104

TEAM RM

4K-102

FAMILY CONF.

4H-111

NURSE STN

4K-111

CORR.

C4-127

ANM + 1

4K-101

REC STOR

4K-127

PATIENT ROOM

4K-119

STAFF TLT

4K-107

BARIATRIC / SURGE PATIENT ROOM

4K-103

PATIENT ROOM

4K-105

PATIENT ROOM

4K-108

PATIENT ROOM

4K-110

PATIENT ROOM

4K-112

TLT

4K-105A

TLT

4K-108A

TLT

4K-110A

TLT

4K-112A

PATIENT ROOM

4K-113

PATIENT ROOM

4K-114

TLT

4K-113A

TLT

4K-114A

PATIENT ROOM

4K-115

CORR.

C4-131

TLT

4K-115A

TLT

4K-103A

NURSE

4K-151

NURSE

4K-155

NURSE

4K-154

NURSE

4K-153

NURSE

4K-150

CARTS

4K-149

STAIRWELL 7

SW7

CORR.

C4-132

HAND WASH

4K-152

P1:S1

P1:S2

P1:S3

P1:S4

P1:S5

P1:S6

P1:S7

P1:S30

P1:S31

P1:S32

P1:S35

P1:S37

P1:S34

P1:S24

P1:S26

P1:S25

P1:S27

P1:S29

P1:S28

P1:S33

P1:S47

P1:S48

P1:S36

P1:S41P1:S42

P1:S43P1:S44P1:S12

P1:S11

P1:S10

P1:S9

P1:S14

P1:S15

P1:S16

P1:S17

P1:S18

P1:S19

P1:S20

P1:S21

P1:S22 P1:S23P1:S45

P1:S46

P1:S51

P1:S50

P1:S49

P1:S39

N1-2

N1-3

N1-4

N1-5

N1-6

N1-7

N1-8

N1-9

N1-10

N1-11

N1-12

N1-13

N1-1

5 5

TYP.

5 5

TYP.

P1:S40

MED SUPPLY

4K-125

5' - 10 1/2" 14' - 0" 6' - 10"

/2

7' - 4 1/2" 14' - 0" 5' - 5 1/2"

6' - 4 1/2" 7' - 4"

/2

7' - 4 1/2" 14' - 0" 5' - 4"

HOLD

7' - 6"

/2

5' - 2 1/2"

/2

5' - 2 1/2"

/2

6' - 10 1/2" 14' - 0" 5' - 10"

TYP.

6' - 9 1/2"

5' - 11" 14' - 0" 6' - 9 1/2"

/2

TYP.

5' - 11" 14' - 0" 6' - 9 1/2"

/2

TYP.

6' - 9 1/2"

6' - 9 1/2"

/2

5' - 9" 14' - 0" 6' - 11 1/2"

/2

TYP.

5' - 9" 14' - 0" 6' - 11 1/2"

/2

TYP.

7 6' - 11 1/2"

/2

" 1' - 10"

HOLD

7' - 6"

/2

/2

TYP.

6' - 3" 14' - 0" 10' - 0" 8' - 0" 4' - 11"

6' - 8"

5' - 8"

/2

CHUTE

4K-118A

2' - 11"

/2

/2

5' - 11"

/2

/2

5' - 6 1/2" 4' - 10"

TYP.

/2

2' - 11" 7' - 5 1/2"

TYP.

/2

/2

5' - 8 1/2" 10' - 0" 6' - 4 1/2"

TYP.

5' - 5" 12' - 0" 7' - 4 1/2"

/2

TYP.

/2

/2

TYP.

TYP.

TYP.

4' - 0"

TYP.

4' - 0"

/2

/2

TYP.

TYP.

TYP.

TYP.

4' - 0" 13' - 6" 13' - 6" 4' - 0"

9' - 6" 9' - 6"

/2

TYP.

TYP.

4' - 0"

TYP.

4' - 0"

TYP.

TYP.

TYP.

3' - 4 1/2"

/2

6' - 1" 14' - 0" 6' - 7 1/2"6

/2

6' - 10" 6' - 0"

HOLD

7' - 6" 14' - 0" 5' - 2"

TYP.

/2

6' - 6 1/2" 7' - 2"

TYP.

/2

5' - 2 1/2" 7' - 2"

5' - 2 1/2" 7' - 2"

"7

7' - 4 1/2" 14' - 0" 5' - 4"

/2

/2

/2

6' - 4 1/2" 7' - 4"

TYP.

TYP.

/2

/2

7' - 4 1/2" 14' - 0" 5' - 4"

/2

TYP.

5' - 2 1/2" 7' - 2"

5' - 2 1/2" 7' - 2"

7' - 4 1/2" 14' - 0" 5' - 4"

/2

6' - 4 1/2" 7' - 4"

TYP.

/2

H O

LD

5' - 11 1/2"

HOLD

7' - 6"

TYP.

6' - 9 1/2" 6' - 0"

C4-137

/2

HOLD

7' - 6" 2' - 4 1/2"

2' - 0 1/2"

TYP.

HOLD

7' - 11" 2' - 3"

/2

4' - 0 1/2"

/2

4' - 8 1/2"

/2 "4' - 0 1/2"

4' - 10 1/2"

TYP.

/2

/2

4' - 5"

6' - 11"

TYP.

/2

5' - 11"

/2 " 5' - 0"

6' - 0"

6' - 7" 8' - 0" 2' - 1 1/2"

AREA NOT IN SCOPE OF WORK

SPRINKLERS AND FIRE ALARM

DEVICES ARE EXISTING TO REMAIN

"2' - 11"

5' - 0"

STAIRWELL 8

SW8

6' - 0" 8' - 0" 10' - 0" 2' - 2"

/F2 FX104 /F2 FX104

WALL SYMBOL LEGEND

CONTRACTOR SHALL CONFIRM ALL FIRE RATED WALL ASSEMBLIES

PROPOSED EXTERIOR WALL.

SEE WALL SECTIONS

1 HR FIRE AND SMOKE

BARRIER

2 HR FIRE AND SMOKE

BARRIER (SHAFT)

SMOKE BARRIER PARTITION

DEMOLISHED WALL,

FIXTURE OR FURNISHING

EXISTING WALL, FIXTURE

OR FURNISHING TO REMAIN

NOT IN CONTRACT - NO

WORK SCHEDULED

on e-ei gh th ne fo ot on e-qu ar te r ne fo ot th re e-ei gh th s ne fo ot on e-ha lf ne fo ot th re e-qu ar te r ne fo ot in ch on e ne fo ot on e an d on e-ha lf ne fo ot th re e in ne fo ot

REVISIONS DATE

General Notes:

GENERAL CONTRACTOR AND/OR ALL SUBCONTRACTORS SHALL FIELD VERIFY ALL DIMENSIONS SHOWN ON THESE PLANS AND SHALL BE RESPONSIBLE FOR VARIATIONS BETWEEN PLAN DIMENSIONS AND ACTUAL FIELD DIMENSIONS. WHERE VARIATIONS ARE FOUND TO OCCUR, THE CONTRACTOR SHALL NOTIFY THE PROJECT ENGINEER IN WRITING PRIOR TO PROCEEDING WITH CONSTRUCTION; NO ADJUSTMENT TO

THE WORK WILL BE MADE WITHOUT THE PRIOR APPROVAL OF THE PROJECT ENGINEER.

GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR GENERAL DEMOLITION INCLUDING REMOVAL OF WALLS, PARTITIONS, DOORS & CEILING & FLOORS. ANY AND ALL CUTTING OF CONCRETE FLOORS, WALLS OR STRUCTURE SHALL BE THE GENERAL CONTRACTOR'S RESPONSIBILITY. CORE DRILLING THROUGH CONCRETE WALLS, FLOORS OR STRUCTURE FOR PIPING OR CONDUIT SHALL BE THE RESPONSIBILITY OF THE SUBCONTRACTOR BY TRADE; FIRESTOPPING OF THESE OPENINGS SHALL BE DONE BY THE RESPECTIVE SUBCONTRACTOR. REMOVAL OF DEBRIS RESULTING FROM DEMOLITION, CUTTING, AND/OR DRILLING IS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR. PATCHING AND REPAIR OF CONCRETE WALLS, FLOOR, OR STRUCTURE SHALL BE THE RESPONSIBILITY OF THE GENERAL CONTRACTOR; THIS WILL BE ACCOMPLISHED UPON COMPLETION OF THE INSTALLATION OF ANY AND ALL UTILITIES INSTALLED

BY THE VARIOUS SUBCONTRACTORS.

Approved: Division Chief

Issue Date Checked Drawn

DrawingNumber

Building Number

Project NumberDrawing Title Project Title

Location Drawing Scale

Approved: Service DirectorPlot Scale U.S. Department of Veterans Affairs

Office of Construction and Facilities Management

FULLY SPRINKLERED

Phase

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

TRUE NORTH

PLAN NORTH

KEYPLAN

A/E:

TRIPLE C - The A/E Group

Mat Perkins

(520) 481-8548

A

B D

EF

G

H

J

K

L

M

C

GENERAL NOTES

LINE INDICATES

PHASE 1 SCOPE AREA

B

IM

/6

-2

-1

E x p a n d e d P o ly tr a u m a P ro g ra m P h a s e

/6 -2

-7

.M

P L S

.P O

L Y

T R

A U

M A

.M E

P .B

.L

.r v t

/4

/2

:4

:1

A

M As indicated

04/03/2023 K. Luke K.Hutchinson

618-22-100

1390 - FX104

FIRE PROTECTION PLANS - FOURTH LEVEL -

AREA 4H&4K

1 Veterans Drive, Minneapolis, MN 55417

B70

RENOVATE FOR EXPANDED

POLYTRAUMA PROGRAM - PHASE 1

ISSUED FOR BIDDING

CONTRACTOR SHALL PROVIDE THE FOLLOWING PRIOR TO

COMMENCEMENT OF WORK FOR REVIEW AND APPROVAL:

A. SHOP DRAWING IDENTIFYING MAIN PIPE SIZES AND LOCATIONS,

LOCATION OF PIPE BRACING, HANGERS AND SPRINKLER HEADS

AND DETAILS

B. CUT SHEETS AND SUBMITTAL FOR ALL PIPING, FITTINGS,

SPRINKLER HEADS, HANGERS AND SUPPORT ATTACHMENTS

A. EXISTING CONDITIONS ARE BASED ON EXISTING PLANS AND FIELD VERIFICATION

WHERE FEASIBLE. ACTUAL CONDITIONS MAY DIFFER FROM THOSE INDICATED.

CONTRACTOR SHALL FIELD VERIFY IN ADVANCE THE LOCATION AND CONDITION OF

THE EXISTING SYSTEMS SHOWN TO BE MODIFIED OR REMOVED. CONTRACTOR TO

NOTIFY ARCHITECT SHOULD CONDITIONS BE FOUND TO DIFFER SIGNIFICANTLY

FROM THE CONSTRUCTION DOCUMENTS.

B. DETAILED SCHEDULE, INCLUDING PROJECTED SERVICE INTERRUPTION DATES WITH

DURATIONS, AND DETAILED PHASING PLAN IS TO BE PROVIDED TO THE COR PRIOR

TO THE START OF WORK. THIS SUBMITTAL MUST BE ACCEPTED BY THE COR PRIOR

TO THE START OF WORK.

C. REFER TO ARCHITECTURAL DRAWINGS FOR EXACT DIMENSIONAL DATA, CEILING

HEIGHTS, AND SQUARE FOOTAGE.

D. CONTRACTOR SHALL COORDINATE ALL WORK WITH BUILDING OWNER AND OTHER

TRADES PRIOR TO CONSTRUCTION.

E. ALL PIPING TO BE ROUTED WITHIN CEILING SPACE OR CONCEALED IN FURRED

CHASES UNLESS NOTED OTHERWISE.

F. ALL AREAS ARE DESIGNED AS LIGHT HAZARD OCCUPANCY UNLESS NOTED

OTHERWISE ON PLAN.

G. ALL SPRINKLERS SYSTEMS SHALL BE INSTALLED IN ACCORDANCE WITH THE 2022

NFPA 13.

H. ALL MATERIALS, DEVICES, HANGERS AND SUPPORTS SHALL BE NEW AND UL LISTED

FOR USE IN FIRE PROTECTION SYSTEMS.

I. ALL NEW SPRINKLERS SHALL BE PROVIDED WITH NEW ESCUTCHEONS TO MATCH

EXISTING BUILDING STANDARDS.

J. INSTALL QUICK RESPONSE SPRINKLERS (QRS) IN ALL AREAS, EXCEPT WHERE

SPECIFICALLY PROHIBITED AS DEFINED BY 2022 NFPA 13.

K. PIPING TO BE SCHEDULE 40 BLACK STEEL WITH CAST IRON FITTINGS.

L. ANY FLOOR, WALL, OR CEILING CUTTING OR FILLING THAT IS REQUIRED TO

COMPLETE THIS PROJECT, THE CONTRACTOR SHALL PATCH AND PAINT AND

RETURN TO MATCH EXISTING CONDITIONS AND FINISHES.

M. CONTRACTOR TO PROVIDE GALVANIC PROTECTION AS REQUIRED AT CONNECTIONS

BETWEEN ALL DISSIMILAR METALS.

N. CONTRACTOR TO VALIDATE AND VERIFY ALL FIRE RATED AND/OR SMOKE RATED

WALLS AND ASSEMBLIES INDICATED ON PLANS IN WORK AREA. PROVIDE ALL PIPING

PENETRATIONS OF FIRE, SMOKE AND FULL HEIGHT WALLS SHALL BE CAULKED

AIRTIGHT TO THE ADJACENT STRUCTURE BY MEANS OF U.L. APPROVED FIRE PROOF

CAULKING MATERIAL. CONTRACTOR SHALL PROVIDE SPECIAL INSPECTIONS OF ALL

UL RATED PENETRATIONS BY A LICENSED INSPECTOR.

O. ALL NEW PIPES TO BE CLEANED AND TESTED PRIOR TO COMMISSIONING.

P. THE SPRINKLER CONTRACTOR SHALL COORDINATE AND PERFORM ALL FIRE

PROTECTION WORK IN ACCORDANCE WITH VA REQUIREMENTS TO ENSURE THAT

CONTINUOUS SPRINKLER COVERAGE IS PROVIDED THROUGHOUT THE PROJECT.

THE SPRINKLER CONTRACTOR SHALL COORDINATE ALL FIRE PROTECTION SYSTEM

SHUTDOWNS, INCLUDING POINTS OF TIE IN, ETC. WITH THE VA PRIOR TO

PERFORMING WORK.

Q. CONTRACTOR IS RESPONSIBLE FOR MAINTAINING COMPLIANCE WITH THE 2022

NFPA 13 FOR SURROUNDING SPACES DURING AND AFTER RENOVATION.

CONTRACTOR IS RESPONSIBLE FOR FIELD VERIFYING SPRINKLER HEAD LOCATIONS

AND PIPING TO BE MODIFIED BY THE RENOVATION PRIOR TO COMMENCING WORK.

R. DURING CONSTRUCTION ENSURE ALL SPRINKLERS ARE THE CORRECT DISTANCE

TO THE DECK WHEN THE CEILING IS NOT INSTALLED.

S. ALL SPRINKLER HEADS WILL BE REPLACED DURING THIS PROJECT. ALL SPRINKLER

HEADS TO BE PENDENT TYPE, SEE HAZARD CHART FOR ADDITIONAL INFORMATION.

1. PROVIDE NEW FIRE SUPPRESSION SYSTEM FOR THE RENOVATED AREA. INSTALL

SPRINKLER HEADS AND PIPING HANGERS IN ACCORDANCE WITH THE 2022 NFPA

13. SEE SHEET FX001 FOR ADDITIONAL INFORMATION.

2. EXISTING 6" STAND PIPE, FIRE PROTECTION RISER.

3. EXISTING FIRE SUPPRESSION CONTROL VALVE ASSEMBLY, CONTRACTOR TO

COORDINATE SHUTDOWN WITH COR PRIOR TO COMMENCEMENT OF WORK.

4. EXISTING PIPING DROP FROM INTERSTITIAL SPACE TO PLENUM SPACE BELOW TO

REMAIN, PROTECT IN PLACE.

5. PROVIDE NEW HEAT/SMOKE DETECTOR.

6. PROVIDE NEW FIRE ALARM STROBE/HORN.

7. PROVIDE NEW SPRINKLER HEAD, CONTRACTOR TO ARM OVER TO CLOSEST

EXISTING SPRINKLER PIPING. REFER TO FIRE PROTECTION SPRINKLER SYSTEM

DESIGN CRITERIA CHART FOR SPRINKLER TYPE BASED ON HAZARD

CLASSIFICATION PER ROOM. SPRINKLER HEADS AND FIRE ALARM DEVICES TO BE

CENTERED IN CEILING GRID TILES UNLESS OTHERWISE DIMENSIONED OR NOTED.

COORDINATE FINAL SPRINKLER HEAD AND FIRE ALARM DEVICE LOCATIONS WITH

FINAL LOCATIONS OF THE CEILING GRID TILES. SEE ARCHITECTURAL RCP FOR

ADDITIONAL INFORMATION AND COORDINATION WITH SPRINKLER HEADS, FIRE

ALARM DEVICES AND ARCHITECTURAL CEILING GRID. CONTRACTOR MUST

MAINTAIN REQUIREMENTS WITH THE 2022 NFPA FOR REQUIRED DIMENSIONS FOR

SPRINKLER HEAD LOCATIONS AT ALL TIMES.

8. ARCHITECTURAL FRAMING/WALLS FOR CEILING BULKHEADS, FOR REFERENCE

ONLY. SEE ARCHITECTURAL CEILING PLANS FOR ADDITIONAL INFORMATION.

9. EXISTING 2-1/2" FDV, T CAP AND PIPING CONNECTED TO STANDPIPE ARE LOCATED

IN PLENUM SPACE AND ARE EXISTING TO REMAIN. PROTECT IN PLACE. SHOWN ON

RCP LEVEL FOR COORDINATION AND REFERENCE ONLY.

10. PROVIDE NEW F.V.C FOR THE RENOVATED AREA.

NOTE: NOT ALL KEYNOTES

ARE USED ON EACH SHEET

1/8" = 1'-0" F2

FIRE PROTECTION RCP - FOURTH LEVEL - AREA H

1/8" = 1'-0"

F6

FIRE PROTECTION RCP - FOURTH LEVEL - AREA 4K

KEYNOTES

FATC 5

(E)

FA - 1FA - 2FA - 3FA - 4FA - 5FA - 6FA - 7FA - 8FA - 9FA - 10FA - 11FA - 12FA - 13FA - 14FA - 15FA - 16FA - 17FA - 18FA - 19FA - 20FA - 21FA - 22FA - 23FA - 24FA - 25FA - 27FA - 28FA - 29FA - 30FA - 31FA - 32FA - 33FA - 34FA - 35FA - 36FA - 37FA - 38FA - 39FA - 40FA - 41

FA - 42FA - 43FA - 44FA - 45FA - 46FA - 47FA - 48FA - 49FA - 50FA - 51FA - 52

SP - 1SP - 2SP - 3SP - 4SP - 5SP - 6SP - 7SP - 8SP - 9SP - 10SP - 11SP - 12SP - 13SP - 14SP - 15SP - 16SP - 17

(E) FATC 6

(E) FATC 4

BPS5

(E)

(E) FATC 6

EOL

(N) (N) (N) (N) (N) (N) (N) (N) (N) (N) (N) (N) (N) (N) (N) (N) (N)

(N) (N) (N) (N) (N) (N) (N) (N) (N) (N) (N) (N) (N) (N) (N) (N) (N)(N) (N) (N) (N) (N) (N) (N) (N) (N) (N) (N) (N) (N) (N) (N) (N) (N)

(N) (N) (N) (N) (N) (N) (N) (N) (N) (N) (N)

(N) (N) (N) (N) (N) (N)

Note: Provide new duct mounted smoke detectors and fire smoke dampers per mechanical drawings.

Provide fire alarm control points per the schedule above.

(N) (N) (N) (N) (N)(N) (N)

SP - 18SP - 19SP - 20SP - 21SP - 22SP - 25SP - 26

FA - 53FA - 54FA - 55FA - 56FA - 57FA - 58FA - 59FA - 60FA - 61FA - 64FA - 65FA - 66FA - 67FA - 68FA - 69FA - 70FA - 71FA - 72FA - 73FA - 74FA - 75FA - 76FA - 77FA - 78FA - 79

(N) (N) (N) (N) (N) (N) (N) (N) (N) (N) (N) (N) (N) (N)(N) (N) (N) (N) (N) (N) (N) (N) (N) (N) (N) on e-ei gh th ne fo ot on e-qu ar te r ne fo ot th re e-ei gh th s ne fo ot on e-ha lf ne fo ot th re e-qu ar te r ne fo ot in ch on e ne fo ot on e an d on e-ha lf ne fo ot th re e in ne fo ot

REVISIONS DATE

General Notes:

GENERAL CONTRACTOR AND/OR ALL SUBCONTRACTORS SHALL FIELD VERIFY ALL DIMENSIONS SHOWN ON THESE PLANS AND SHALL BE RESPONSIBLE FOR VARIATIONS BETWEEN PLAN DIMENSIONS AND ACTUAL FIELD DIMENSIONS. WHERE VARIATIONS ARE FOUND TO OCCUR, THE CONTRACTOR SHALL NOTIFY THE PROJECT ENGINEER IN WRITING PRIOR TO PROCEEDING WITH CONSTRUCTION; NO ADJUSTMENT TO

THE WORK WILL BE MADE WITHOUT THE PRIOR APPROVAL OF THE PROJECT ENGINEER.

GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR GENERAL DEMOLITION INCLUDING REMOVAL OF WALLS, PARTITIONS, DOORS & CEILING & FLOORS. ANY AND ALL CUTTING OF CONCRETE FLOORS, WALLS OR STRUCTURE SHALL BE THE GENERAL CONTRACTOR'S RESPONSIBILITY. CORE DRILLING THROUGH CONCRETE WALLS, FLOORS OR STRUCTURE FOR PIPING OR CONDUIT SHALL BE THE RESPONSIBILITY OF THE SUBCONTRACTOR BY TRADE; FIRESTOPPING OF THESE OPENINGS SHALL BE DONE BY THE RESPECTIVE SUBCONTRACTOR. REMOVAL OF DEBRIS RESULTING FROM DEMOLITION, CUTTING, AND/OR DRILLING IS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR. PATCHING AND REPAIR OF CONCRETE WALLS, FLOOR, OR STRUCTURE SHALL BE THE RESPONSIBILITY OF THE GENERAL CONTRACTOR; THIS WILL BE ACCOMPLISHED UPON COMPLETION OF THE INSTALLATION OF ANY AND ALL UTILITIES INSTALLED

BY THE VARIOUS SUBCONTRACTORS.

Approved: Division Chief

Issue Date Checked Drawn

DrawingNumber

Building Number

Project NumberDrawing Title Project Title

Location Drawing Scale

Approved: Service DirectorPlot Scale U.S. Department of Veterans Affairs

Office of Construction and Facilities Management

FULLY SPRINKLERED

Phase

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

TRUE NORTH

PLAN NORTH

KEYPLAN

A/E:

TRIPLE C - The A/E Group

Mat Perkins

(520) 481-8548

A

B D

EF

G

H

J

K

L

M

C

LINE INDICATES

PHASE 1 SCOPE AREA

B

IM

/6

-2

-1

E x p a n d e d P o ly tr a u m a P ro g ra m P h a s e

/6 -2

-7

.M

P L S

.P O

L Y

T R

A U

M A

.G e n e ra l.

S h e e ts

.r v t

/3

/2

:4

:0

P

M As indicated

04/03/2023 K. Luke N.Wicklund

618-22-100

1390 - FX501

FIRE PROTECTION DETAILS AND

SCHEDULES

1 Veterans Drive, Minneapolis, MN 55417

B70

RENOVATE FOR EXPANDED

POLYTRAUMA PROGRAM

ISSUED FOR BIDDING

NTS

F3

FIRE ALARM RISER

NTS

C2

FIRE PROTECTION WIRE SCHEDULE

on e-ei gh th ne fo ot on e-qu ar te r ne fo ot th re e-ei gh th s ne fo ot on e-ha lf ne fo ot th re e-qu ar te r ne fo ot in ch on e ne fo ot on e an d on e-ha lf ne fo ot th re e in ne fo ot

REVISIONS DATE

General Notes:

GENERAL CONTRACTOR AND/OR ALL SUBCONTRACTORS SHALL FIELD VERIFY ALL DIMENSIONS SHOWN ON THESE PLANS AND SHALL BE RESPONSIBLE FOR VARIATIONS BETWEEN PLAN DIMENSIONS AND ACTUAL FIELD DIMENSIONS. WHERE VARIATIONS ARE FOUND TO OCCUR, THE CONTRACTOR SHALL NOTIFY THE PROJECT ENGINEER IN WRITING PRIOR TO PROCEEDING WITH CONSTRUCTION; NO ADJUSTMENT TO

THE WORK WILL BE MADE WITHOUT THE PRIOR APPROVAL OF THE PROJECT ENGINEER.

GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR GENERAL DEMOLITION INCLUDING REMOVAL OF WALLS, PARTITIONS, DOORS & CEILING & FLOORS. ANY AND ALL CUTTING OF CONCRETE FLOORS, WALLS OR STRUCTURE SHALL BE THE GENERAL CONTRACTOR'S RESPONSIBILITY. CORE DRILLING THROUGH CONCRETE WALLS, FLOORS OR STRUCTURE FOR PIPING OR CONDUIT SHALL BE THE RESPONSIBILITY OF THE SUBCONTRACTOR BY TRADE; FIRESTOPPING OF THESE OPENINGS SHALL BE DONE BY THE RESPECTIVE SUBCONTRACTOR. REMOVAL OF DEBRIS RESULTING FROM DEMOLITION, CUTTING, AND/OR DRILLING IS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR. PATCHING AND REPAIR OF CONCRETE WALLS, FLOOR, OR STRUCTURE SHALL BE THE RESPONSIBILITY OF THE GENERAL CONTRACTOR; THIS WILL BE ACCOMPLISHED UPON COMPLETION OF THE INSTALLATION OF ANY AND ALL UTILITIES INSTALLED

BY THE VARIOUS SUBCONTRACTORS.

Approved: Division Chief

Issue Date Checked Drawn

DrawingNumber

Building Number

Project NumberDrawing Title Project Title

Location Drawing Scale

Approved: Service DirectorPlot Scale U.S. Department of Veterans Affairs

Office of Construction and Facilities Management

FULLY SPRINKLERED

Phase

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

TRUE NORTH

PLAN NORTH

KEYPLAN

A/E:

TRIPLE C - The A/E Group

Mat Perkins

(520) 481-8548

A

B D

EF

G

H

J

K

L

M

C

LINE INDICATES

PHASE 1 SCOPE AREA

B

IM

/6

-2

-1

E x p a n d e d P o ly tr a u m a P ro g ra m P h a s e

/6 -2

-7

.M

P L S

.P O

L Y

T R

A U

M A

.G e n e ra l.

S h e e ts

.r v t

/3

/2

:4

:0

P

M As indicated

04/03/2023 K. Luke K.Hutchinson

618-22-100

1390 - FX502

FIRE PROTECTION DETAILS AND

SCHEDULES

1 Veterans Drive, Minneapolis, MN 55417

B70

RENOVATE FOR EXPANDED

POLYTRAUMA PROGRAM

ISSUED FOR BIDDING

NTS

E1

FIRE PROTECTION LABELING

NTS

B5

HORN-STROBE DETAIL

NTS

B1

SMOKE/HEAT DETECTOR DETAIL

NOT TO SCALE

D5

FIRE ALARM MOUNTING DEVICE LOCATIONS

on e-ei gh th ne fo ot on e-qu ar te r ne fo ot th re e-ei gh th s ne fo ot on e-ha lf ne fo ot th re e-qu ar te r ne fo ot in ch on e ne fo ot on e an d on e-ha lf ne fo ot th re e in ne fo ot

REVISIONS DATE

General Notes:

GENERAL CONTRACTOR AND/OR ALL SUBCONTRACTORS SHALL FIELD VERIFY ALL DIMENSIONS SHOWN ON THESE PLANS AND SHALL BE RESPONSIBLE FOR VARIATIONS BETWEEN PLAN DIMENSIONS AND ACTUAL FIELD DIMENSIONS. WHERE VARIATIONS ARE FOUND TO OCCUR, THE CONTRACTOR SHALL NOTIFY THE PROJECT ENGINEER IN WRITING PRIOR TO PROCEEDING WITH CONSTRUCTION; NO ADJUSTMENT TO

THE WORK WILL BE MADE WITHOUT THE PRIOR APPROVAL OF THE PROJECT ENGINEER.

GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR GENERAL DEMOLITION INCLUDING REMOVAL OF WALLS, PARTITIONS, DOORS & CEILING & FLOORS. ANY AND ALL CUTTING OF CONCRETE FLOORS, WALLS OR STRUCTURE SHALL BE THE GENERAL CONTRACTOR'S RESPONSIBILITY. CORE DRILLING THROUGH CONCRETE WALLS, FLOORS OR STRUCTURE FOR PIPING OR CONDUIT SHALL BE THE RESPONSIBILITY OF THE SUBCONTRACTOR BY TRADE; FIRESTOPPING OF THESE OPENINGS SHALL BE DONE BY THE RESPECTIVE SUBCONTRACTOR. REMOVAL OF DEBRIS RESULTING FROM DEMOLITION, CUTTING, AND/OR DRILLING IS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR. PATCHING AND REPAIR OF CONCRETE WALLS, FLOOR, OR STRUCTURE SHALL BE THE RESPONSIBILITY OF THE GENERAL CONTRACTOR; THIS WILL BE ACCOMPLISHED UPON COMPLETION OF THE INSTALLATION OF ANY AND ALL UTILITIES INSTALLED

BY THE VARIOUS SUBCONTRACTORS.

Approved: Division Chief

Issue Date Checked Drawn

DrawingNumber

Building Number

Project NumberDrawing Title Project Title

Location Drawing Scale

Approved: Service DirectorPlot Scale U.S. Department of Veterans Affairs

Office of Construction and Facilities Management

FULLY SPRINKLERED

Phase

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

TRUE NORTH

PLAN NORTH

KEYPLAN

A/E:

TRIPLE C - The A/E Group

Mat Perkins

(520) 481-8548

A

B D

EF

G

H

J

K

L

M

C

LINE INDICATES

PHASE 1 SCOPE AREA

B

IM

/6

-2

-1

E x p a n d e d P o ly tr a u m a P ro g ra m P h a s e

/6 -2

-7

.M

P L S

.P O

L Y

T R

A U

M A

.G e n e ra l.

S h e e ts

.r v t

/3

/2

:4

:1

P

M

04/03/2023 K. Luke K.Hutchinson

618-22-100

1390 - FX901

FIRE PROTECTION CUTSHEETS & BASIS OF

DESIGN

1 Veterans Drive, Minneapolis, MN 55417

B70

RENOVATE FOR EXPANDED

POLYTRAUMA PROGRAM

ISSUED FOR BIDDING