This document summarizes a federal construction solicitation for renovations to expand polytrauma care at the Minneapolis VA Medical Center. The solicitation is set aside for verified Service-Disabled Veteran-Owned Small Businesses and seeks general construction, electrical, plumbing and other trades to complete Phase 1 renovations. The construction magnitude is estimated between $10-20 million. The primary objective is to expand and consolidate polytrauma care services. Bidders must price all applicable taxes and the Department of Veterans Affairs Veterans Health Administration VISN 23 is the contracting agency.
View the file
Other files
Show all 35
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PRE-POSITIONED SLEEVE PRE-POSITIONED SLEEVE
CORE DRILLED SLEEVE CORE DRILLED SLEEVE
FOR 1-1/4" AND LARGER
6 7
CONCRETE STRUCTURE
PIPE SLEEVE SIZED FOR PIPE WITH INSULATION
WATER STOP
EXTEND SLEEVE 4" ABOVE FINISHED FLOOR LEVEL
MINIMUM 18" LONG ALUMINUM
INSULATION JACKET
INSULATION - SEE SPECS FOR
THICKNESS
PIPE
SEAL WITH WATERPROOF
CAULKING
MINIMUM 3/4" POURED LEAD
MULTI-COMPONENT PLASTIC CEMENT
PIPE SLEEVE (I.D. MIN. 1" LARGER THAN O.D. OF PIPE)
WATERPROOF GROUT
CORE DRILL MIN. 1" LARGER
HOLE THAN O.D. OF PIPE SLEEVE
(12" MAXIMUM CORE DRILL SIZE)
13NOTES:
1. SEAL SLEEVE WITH UL RATED SEALANT TO MATCH
RATING OF WALL OR CEILING. MAINTAIN REQUIRED
MINIMUM CONTACT OF SEALANT AND CLEARANCES OF
PIPE IN PENETRATION.
2. PROVIDE ESCUTCHEON PLATES AT ALL EXPOSED
PENETRATIONS.
TEST TEE
TRAP MONITOR
END OF STEAM MAIN
12" MINIMUM DROP
6" DIRT LEG
LINE SIZE (TYPICAL)
CHECK VALVE
BALL OR GATE VALVE.
(TYPICAL, SEE SPECIFICATION)
RETURN
NTS
F6
PIPE PENETRATION DETAIL
on e-ei gh th in ch o ne fo ot on e-qu ar te r ne fo ot th re e-ei gh th s ne fo ot on e-ha lf ne fo ot th re e-qu ar te r ne fo ot in ch on e ne fo ot on e an d on e-ha lf ne fo ot th re e in es ne fo ot
REVISIONS DATE
General Notes:
GENERAL CONTRACTOR AND/OR ALL SUBCONTRACTORS SHALL FIELD VERIFY ALL DIMENSIONS SHOWN ON THESE PLANS AND SHALL BE RESPONSIBLE FOR VARIATIONS BETWEEN PLAN DIMENSIONS AND ACTUAL FIELD DIMENSIONS. WHERE VARIATIONS ARE FOUND TO OCCUR, THE CONTRACTOR SHALL NOTIFY THE PROJECT ENGINEER IN WRITING PRIOR TO PROCEEDING WITH CONSTRUCTION; NO ADJUSTMENT TO
THE WORK WILL BE MADE WITHOUT THE PRIOR APPROVAL OF THE PROJECT ENGINEER.
GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR GENERAL DEMOLITION INCLUDING REMOVAL OF WALLS, PARTITIONS, DOORS & CEILING & FLOORS. ANY AND ALL CUTTING OF CONCRETE FLOORS, WALLS OR STRUCTURE SHALL BE THE GENERAL CONTRACTOR'S RESPONSIBILITY. CORE DRILLING THROUGH CONCRETE WALLS, FLOORS OR STRUCTURE FOR PIPING OR CONDUIT SHALL BE THE RESPONSIBILITY OF THE SUBCONTRACTOR BY TRADE; FIRESTOPPING OF THESE OPENINGS SHALL BE DONE BY THE RESPECTIVE SUBCONTRACTOR. REMOVAL OF DEBRIS RESULTING FROM DEMOLITION, CUTTING, AND/OR DRILLING IS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR. PATCHING AND REPAIR OF CONCRETE WALLS, FLOOR, OR STRUCTURE SHALL BE THE RESPONSIBILITY OF THE GENERAL CONTRACTOR; THIS WILL BE ACCOMPLISHED UPON COMPLETION OF THE INSTALLATION OF ANY AND ALL UTILITIES INSTALLED
BY THE VARIOUS SUBCONTRACTORS.
Approved: Division Chief
Issue Date Checked Drawn
DrawingNumber
Building Number
Project NumberDrawing Title Project Title
Location Drawing Scale
Approved: Service DirectorPlot Scale U.S. Department of Veterans Affairs
Office of Construction and Facilities Management
FULLY SPRINKLERED
Phase
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
TRUE NORTH
PLAN NORTH
KEYPLAN
A/E:
TRIPLE C - The A/E Group
Mat Perkins
(520) 481-8548
A
B D
EF
G
H
J
K
L
M
C
LINE INDICATES
PHASE 1 SCOPE AREA
B
IM
/6
-2
-1
E x p a n d e d P o ly tr a u m a P ro g ra m P h a s e
/6 -2
-7
.M
P L S
.P O
L Y
T R
A U
M A
.G e n e ra l.
S h e e ts
.r v t
/3
/2
:4
:2
P
M As indicated
04/03/2023 K. Luke N. Harper
618-22-100
1390 - M-501
MECHANICAL DETAILS
1 Veterans Drive, Minneapolis, MN 55417
B70
RENOVATE FOR EXPANDED
POLYTRAUMA PROGRAM
ISSUED FOR BIDDING
NTS
C6
VIBRATION ISOLATION BASE
NTS
E4
CONCRETE EQUIPMENT BASE
NTS
C4
SECURING HANGER RODS IN CONCRETE
NTS
B1
STEAM LINE DRIP POCKET AND STEAM TRAP ASSEMBLY
NTS
A4
TERMINAL UNIT WATER COILS - PIPING CONNECTIONS
NTS
D1
DUCTWORK RADIUS ELBOWS
NTS
E1
DUCTWORK TRANSITIONS (WITH EQUIPMENT MOUNTED IN DUCT)
NTS
F1
VOLUME DAMPER DETAIL
SCALE: 6" = 1'-0"
A8
STEAM DRIP TRAP DETAIL
SCALE: 1 1/2" = 1'-0"
C8
STEAM HUMIDIFIER DETAIL
TRAP MONITOR BUILT
INTO BUILDING
AUTOMATION
TEST TEE
STRAINER
04/03/2023
NOTE:
SEE SPECIFICATION SECTION "PUMPS" FOR Y STRAINER
OPTION.
DESIGNER'S
NOTE:
CHECK VALVE IS OPTIONAL FOR SINGLE PUMPS, EXCEPT FOR COOLING TOWER
PUMP.
FIRST 3 HANGERS FOR EACH PIPE AND BRANCH
SHALL BE SPRING & NEOPRENE TYPE. TYPE "H"
FOR 4" [100mm] DIA. PIPE AND SMALLER. TYPE "H-P" FOR 5" [125mm] DIA. PIPE AND LARGER.
RIGID PIPE
HANGER
(TYPICAL)
INSTALL HANGER AS CLOSE TO
PIPE ELBOW AS POSSIBLE
(TYPICAL)1/2" [15mm]
FLEXIBLE
CONNECTOR
SUCTION DIFFUSER WITH
BUILT-IN STRAINER
DRAIN
1" [25mm] MIN. DIA. PIPE
STAND
CONCRETE INERTIA
BASE (SEE DETAIL)
PRESSURE
GAUGE
FLEXIBLE
CONNECTOR
1" [25mm] MIN.
DIA. PIPE STAND
FLOOR
VIBRATION
ISOLATOR
(TYPICAL)
PUMP
OPTIONAL
STRAINER
BUTTER OR BALL
SHUT OFF VALVE, TYP.
CHECK
VALVE
DDC PRESSURE SENSOR CONNECTED TO
BAS
20 30
RISE
PLAN
NOTES
1. ANGLE A=30 MAXIMUM WHEN AIR FLOWS IN
DIRECTION OF ARROWS. (SUPPLY AIR)
2. ANGLE A=15 WHEN AIR FLOWS IN OPPOSITE
DIRECTION OF ARROWS (R.A. OR EXHAUST)
20°
A°
A°
A°
A°
3.73xH
FBFT
FT FB
A°A°
A°
A°
PLAN VIEW PLAN VIEW PLAN VIEW
TRANSITION
w/ EQUIPMENT
ELEVATION
PLAN
DUCT OFFSET
FT FB
FBFT
A°
A° A°
A°
ELEVATION ELEVATION ELEVATION BRANCH DUCT
PLAN
45° W
1/2 W
(4"MIN.)
PLAN A
A
B
C
(1) NECK DIA. MIN.
PROVIDE QUADRANT
LOCKING HAND DAMPER
WITH ACCESS DOOR
WHERE SHOWN ON PLANS
BRANCH
DUCT
BRANCH MAIN
FIXED CEILINGS
SECTION A
FLEX DUCT. DIAMETER
EQUALTO DIFFUSER NECK
SIZE (MAX. LENGTH 4'-0")
SPIN IN FITTING
W/HAND DAMPER
SECTION B
LAY-IN CEILINGS
PLAN B
RIGID DUCT WHERE
RUN-OUT EXCEEDS 4'-0"
PROVIDE HAND DAMPER
WITH ACCESS DOOR
SHEET METAL
PLENUM
RIGID DUCT WHERE
RUN-OUT EXCEEDS 4'-0"
FLEX. DUCT FOR LAY-IN
CEILING APPLICATION
EXHAUST / DUCTED RETURN
GRILLE. SEE FLOOR PLAN
FOR SIZE, TYPE, AND LOCATION
SECTION C
RETURN/EXHAUST REGISTER
FOR LAY-IN AND FIXED CEILINGS
PLAN C
NOTE:
NO DRISTEAM PRODUCTS.
REFERENCE F1/M501 FOR STEAM POCKET ASSEMBLY DETAIL.
REFERENCE B1, B3, B6/M504 FOR STEAM TRAP ASSEMBLY DETAILS.
AIR FLOW
HWS
1. METAL STRAP SUPPORT FROM STRUCTURE (TYPICAL)
2. MANUAL AIR VENT ON HWR PIPING. MUST BE A GALVANIZED 6" HOSE.
3. FACTORY FABRICATED SOUND ATTENUATOR
4. HOT WATER COIL
5. VALVE ACTUATOR
6. HIGH VELOCITY FLEXIBLE SUPPLY DUCT 12" MIN., 24" MAX.
7. DRAIN
8. TEMPERATURE-PRESSURE FITTING (TYP.)
9. LOW VELOCITY DUCTWORK TO DISTRIBUTION
10. REFER TO PLANS FOR PIPE SIZES
11. 2-WAY CONTROL VALVE, NORMALLY CLOSED. FAIL TO COOL
12. BALL VALVE (TYP)
13. UNION (TYP)
14. REDUCER (TYP)
15. HIGH VELOCITY RIGID SUPPLY DUCT, 3 FT. MINIMUM STRAIGHT RUN PRIOR
TO TERMINAL UNIT CONNECTION. SEE SCHEDULE FOR VALVE AND DUCT SIZES
16. FLOW BALANCING VALVE, OR FLOW LIMITING VALVE, SEE SPECIFICATIONS
17. TRANSITION FROM 2" LARGER DUCT DIAMETER THAN VALVE CONNECTION SIZE
18. INCLUDE A BLOW DOWN VALVE OFF THE TEE ON HEATING WATER SUPPLY LINE
HWR
22-1/2 2-PIECE
ELBOW
A
R R R
A A
30 2-PIECE
ELBOW
45 ELBOW
(3" THRU 8")
45 3-PIECE
ELBOW
60 3-PIECE
ELBOW
90 ELBOW
(3" THRU 8")
90 5-PIECE
ELBOW
CONCENTRIC REDUCER
RL=A-B (MIN)
ECCENTRIC REDUCER
RL=2(AB)
LATERAL TEE LATERAL CROSS REDUCING
LATERAL TEE
RL=A-B (MIN)
REDUCING
LATERAL CROSS
A
R
A
R
A
RL
B A
RL
B
A A
R R
A
L
C C
A L
D
A
C
RL B
L
A L
C
RL B
D
A
C
L L RL
A
C
B
C
A
L
A
C
B
L RL
COMBINATION TEE REDUCING
COMBINATION TEE
SPUN TEE REDUCING
SPUN TEE
CONICAL LATERAL REDUCING
CONICAL LATERAL
TANGENTIAL TEE
TYPE: ONE TAP
L=C+2"
TYPE: TWO TAPS
L=C+D+4"
CONICAL TEE
L=C+4"
REDUCING
CONICAL TEE
L=C+4" X=(C/2)+2"
5"MIN.
5"MIN.
L=LARGER OF
(C OR D)+4"
CONICAL CROSS
L=1.414 C+5"
(MAX)
Q=(A/2)+.707C+3"
(MAX)
H=.707A+.5C+3"
(MAX)
5"MIN.5"MIN.
NOTE: SEE SPECIFICATIONS FOR DUCT MATERIALS AND CONSTRUCTION
L
Q
A 1"
1" 4"
H C
L
Q
A 1"
4" H
C 1"
RL
B
1"
A
1" 1"
L
1"
C D
C
A
L
5"MIN.
C
A
L RL
B
C
A L
D
NTS
F8
LOW PRESSURE DUCT FITTINGS
NTS
C6
DIFFUSER AND REGISTER CONNECTION
NTS
F4
MECHANICAL EQUIPMENT - DRAIN CONNECTION
NTS
F1
STEAM HUMIDIFIER - PIPING CONNECTIONS
NTS
C1
SINGLE DUCT VAV TERMINAL UNIT WITH REHEAT COIL - 2 WAY VALVE
NTS
F6
MEDIUM PRESSURE AND ROUND DUCT FITTINGS
on e-ei gh th ne fo ot on e-qu ar te r ne fo ot th re e-ei gh th s ne fo ot on e-ha lf ne fo ot th re e-qu ar te r ne fo ot in ch on e ne fo ot on e an d on e-ha lf ne fo ot th re e in ne fo ot
REVISIONS DATE
General Notes:
GENERAL CONTRACTOR AND/OR ALL SUBCONTRACTORS SHALL FIELD VERIFY ALL DIMENSIONS SHOWN ON THESE PLANS AND SHALL BE RESPONSIBLE FOR VARIATIONS BETWEEN PLAN DIMENSIONS AND ACTUAL FIELD DIMENSIONS. WHERE VARIATIONS ARE FOUND TO OCCUR, THE CONTRACTOR SHALL NOTIFY THE PROJECT ENGINEER IN WRITING PRIOR TO PROCEEDING WITH CONSTRUCTION; NO ADJUSTMENT TO
THE WORK WILL BE MADE WITHOUT THE PRIOR APPROVAL OF THE PROJECT ENGINEER.
GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR GENERAL DEMOLITION INCLUDING REMOVAL OF WALLS, PARTITIONS, DOORS & CEILING & FLOORS. ANY AND ALL CUTTING OF CONCRETE FLOORS, WALLS OR STRUCTURE SHALL BE THE GENERAL CONTRACTOR'S RESPONSIBILITY. CORE DRILLING THROUGH CONCRETE WALLS, FLOORS OR STRUCTURE FOR PIPING OR CONDUIT SHALL BE THE RESPONSIBILITY OF THE SUBCONTRACTOR BY TRADE; FIRESTOPPING OF THESE OPENINGS SHALL BE DONE BY THE RESPECTIVE SUBCONTRACTOR. REMOVAL OF DEBRIS RESULTING FROM DEMOLITION, CUTTING, AND/OR DRILLING IS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR. PATCHING AND REPAIR OF CONCRETE WALLS, FLOOR, OR STRUCTURE SHALL BE THE RESPONSIBILITY OF THE GENERAL CONTRACTOR; THIS WILL BE ACCOMPLISHED UPON COMPLETION OF THE INSTALLATION OF ANY AND ALL UTILITIES INSTALLED
BY THE VARIOUS SUBCONTRACTORS.
Approved: Division Chief
Issue Date Checked Drawn
DrawingNumber
Building Number
Project NumberDrawing Title Project Title
Location Drawing Scale
Approved: Service DirectorPlot Scale U.S. Department of Veterans Affairs
Office of Construction and Facilities Management
FULLY SPRINKLERED
Phase
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
TRUE NORTH
PLAN NORTH
KEYPLAN
A/E:
TRIPLE C - The A/E Group
Mat Perkins
(520) 481-8548
A
B D
EF
G
H
J
K
L
M
C
LINE INDICATES
PHASE 1 SCOPE AREA
B
IM
/6
-2
-1
E x p a n d e d P o ly tr a u m a P ro g ra m P h a s e
/6 -2
-7
.M
P L S
.P O
L Y
T R
A U
M A
.G e n e ra l.
S h e e ts
.r v t
/3
/2
:4
:3
P
M As indicated
04/03/2023 K. Luke N. Harper
618-22-100
1390 - M-502
MECHANICAL DETAILS
1 Veterans Drive, Minneapolis, MN 55417
B70
RENOVATE FOR EXPANDED
POLYTRAUMA PROGRAM
ISSUED FOR BIDDING
NTS
C4
DUCT CONNECTIONS - AIR TERMINAL UNITS
NTS
C8
DOUBLE SUCTION FLOOR-MOUNTED PUMPS
FILL OPENING WITH
GROUT OR SEALANT
DEPENDING UPON
BUILDING MATERIALS
PENETRATED
PIPE SLEEVE OR
SHEET METAL SLEEVE
SEAL ALL AROUND
WITH RESILIENT
NON-HARDENING
SEALER-TYP BUILDING WALL OR FLOOR
1/2" TO 5/8" ANNULAR
SPACE-PACK SPACE
WITH MINERAL WOOL OR
FIBERGLASS MATERIAL
PIPE OR ELECTRICAL CONDUIT
UL LISTED FIRE-CAULK AT RATED
PARTITIONS, FLOOR AND INTERSTITIAL
PENETRATIONS
5 FT
6 8 10
9 1110 12
-1312 14 -16 -
1614 17 2219 23
2725 28 3230
20 241814 16128 1064 532 2 1/21 1/21 1 1/4THRU 3/4
7 7
7 98
SIDE VIEW TRAPEZE HANGER FOR UP TO
1000 LB. UNIFORM LOAD
ADJUSTABLE CLEVIS HANGER TYPE 1 - SEE SPECIFICATIONS ADJUSTABLE CLEVIS HANGER TYPE 43 - SEE SPECIFICATIONS
MAXIMUM PIPE/TUBING SUPPORT SPACING
NOTE: FOR TRAPEZE HANGER TAKE SPACING OF SMALLEST SIZE ON TRAPEZE.
NOM. SIZE
PIPE
TUBING
IN.
FT.
FT.
M A
X
PROVIDE INSULATION
SHIELD & INSERT FOR
ALL PIPING (8" MIN.)
BAND
1-5/8" 12 GAUGE
CHANNEL OR
2"x2"x1/4"
ANGLE
1/2" DIA. HANGER
RODS WITH
36" MAX. SPACING
ON EACH CHANNEL
WELD
SADDLE
INSULATION SHIELD
AT HANGER
PROVIDE HIGH
COMPRESSIVE
STRENGTH INSULATION (9
PSF MIN. DENSITY) UNDER
INSULATION SHIELD
INSULATION (VAPOR
BARRIER TYPE IS
REQUIRED FOR LOW
TEMPERATURE PIPE)
HANGER ROD
NOTES:
SEE SPEC FOR
DETAILED HANGER
REQUIREMENTS
SUPPLY WATER SHALL BE CONNECTED
TO AIR LEAVING SIDE OF COIL
COLLECT ALL DRAINS, INSTALL HOSE
CONNECTION AND CAP
TEMP. AND PRESS. FITTING TYP.
PRESSURE GAUGE
THERMOMETER
UNION
AUTOMATIC TWO-WAY CONTROL VALVE
BUTTERFLY VALVE
MANUAL AIR VENT
1/2" GATE VALVE AND DRAIN
DASHED PIPING AND COILS INDICATE
TYPICAL PIPING REQUIREMENTS FOR
MULTIPLE COILS
FLOW CONTROL VALVE, SEE
SPECIFICATIONS SECT. 15080
CONNECTION
STRAINER WITH HOSE BIBB
DRAINS AND VENTS FOR SEASONAL MAINTENANCE
GENERAL NOTES
1 PROVIDE MANUAL AIR VENTS AT ALL
HIGH POINTS IN SYSTEM.
2 SEE PLANS AND/OR PIPING
SCHEMATIC FOR PIPE SIZES.
3 TEMP./PRESS. FITTINGS INSTALLED
IN PIPING 2" AND SMALLER SHALL
BE INSTALLED IN ELBOW OR IN THE
BRANCH SIDE OF A 2" TEE.
COIL
COIL
AIR FLOW
CHS
CHR
1" OVERLAP
ON ALL SIDES
OF DAMPER
AIRFLOW
1" OVERLAP
ON ALL SIDES
OF DAMPER
AIRFLOW
MULTIBLADE NON-AIRFOIL
(LOW VELOCITY APPLICATIONS
1500 FPM & LESS)
MULTIBLADE AIRFOIL
(HIGH VELOCITY APPLICATIONS
IN EXCESS OF 1500 FPM)
WALL OR FLOOR
SLEEVE - SEE MANUFACTURER'S INSTALLATION NOTES
MOUNTING ANGLES CONTINUOUS AROUND SLEEVE WITH MINIMUM 1" OVERLAP
SQUARE OR RECTANGULAR DAMPER FRAME FOR ROUND OR OVAL DUCTS,
PROVIDE DUCT TRANSITION
BREAKAWAY DUCT CONNECTION - SEE INSTALLATION NOTES
INSTALL DAMPER ASSEMBLY PER MANUFACTURER'S INSTALLATION INSTRUCTIONS
1/4" MINIMUM EXPANSION CLEARANCE - SEE MANUFACTURER'S INSTALLATION NOTES
APPROVED SEALING MATERIAL IN ACCORDANCE WITH MANUFACTURER'S
INSTALLATION INSTRUCTIONS
U.L. APPROVED DAMPER ACTUATOR ASSEMBLY WITH MOUNTING BRACKET,
ELECTRIC FUSE LINK, AND OPERATING JACK SHAFT LINKAGE. DAMPER
ACTUATOR SHALL BE MOUNTED ON DUCT OUTSIDE AIR STREAM\
INTEGRAL FACTORY WIRED FOR SINGLE POINT POWER CONNECTION, NO FLOW
SMOKE DETECTOR WITH BUILT-IN TEST SWITCH RATED FOR 0-3000 FPM, MOUNTED
INTERNALLY TO THE DAMPER SLEEVE
* FUSIBLE ROD IS NOT REQUIRED FOR SMOKE DAMPER APPLICATION
6" 6"6"6"
10 3
ECCENTRIC
FLEX CONNECTOR
STEAM TRAP
MONITOR
TEST TEE
STEAM TRAP MONITOR CONNECTED
TO BMS, SEE MECHANICAL
CONTROLS DRAWINGS
MODULATING
CONTROL VALVE
NTS
D4
PIPE PENETRATION DETAIL
NTS
B7
PIPE SUPPORTS
NTS
F4
CHILLED WATER COIL PIPING SCHEMATIC WITH 2-WAY VALVE
NTS
F1
SMOKE DAMPER AND COMBINATION FIRE SMOKE DAMPER DETAIL
on e-ei gh th ne fo ot on e-qu ar te r ne fo ot th re e-ei gh th s ne fo ot on e-ha lf ne fo ot th re e-qu ar te r ne fo ot in ch on e ne fo ot on e an d on e-ha lf ne fo ot th re e in ne fo ot
REVISIONS DATE
General Notes:
GENERAL CONTRACTOR AND/OR ALL SUBCONTRACTORS SHALL FIELD VERIFY ALL DIMENSIONS SHOWN ON THESE PLANS AND SHALL BE RESPONSIBLE FOR VARIATIONS BETWEEN PLAN DIMENSIONS AND ACTUAL FIELD DIMENSIONS. WHERE VARIATIONS ARE FOUND TO OCCUR, THE CONTRACTOR SHALL NOTIFY THE PROJECT ENGINEER IN WRITING PRIOR TO PROCEEDING WITH CONSTRUCTION; NO ADJUSTMENT TO
THE WORK WILL BE MADE WITHOUT THE PRIOR APPROVAL OF THE PROJECT ENGINEER.
GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR GENERAL DEMOLITION INCLUDING REMOVAL OF WALLS, PARTITIONS, DOORS & CEILING & FLOORS. ANY AND ALL CUTTING OF CONCRETE FLOORS, WALLS OR STRUCTURE SHALL BE THE GENERAL CONTRACTOR'S RESPONSIBILITY. CORE DRILLING THROUGH CONCRETE WALLS, FLOORS OR STRUCTURE FOR PIPING OR CONDUIT SHALL BE THE RESPONSIBILITY OF THE SUBCONTRACTOR BY TRADE; FIRESTOPPING OF THESE OPENINGS SHALL BE DONE BY THE RESPECTIVE SUBCONTRACTOR. REMOVAL OF DEBRIS RESULTING FROM DEMOLITION, CUTTING, AND/OR DRILLING IS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR. PATCHING AND REPAIR OF CONCRETE WALLS, FLOOR, OR STRUCTURE SHALL BE THE RESPONSIBILITY OF THE GENERAL CONTRACTOR; THIS WILL BE ACCOMPLISHED UPON COMPLETION OF THE INSTALLATION OF ANY AND ALL UTILITIES INSTALLED
BY THE VARIOUS SUBCONTRACTORS.
Approved: Division Chief
Issue Date Checked Drawn
DrawingNumber
Building Number
Project NumberDrawing Title Project Title
Location Drawing Scale
Approved: Service DirectorPlot Scale U.S. Department of Veterans Affairs
Office of Construction and Facilities Management
FULLY SPRINKLERED
Phase
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
TRUE NORTH
PLAN NORTH
KEYPLAN
A/E:
TRIPLE C - The A/E Group
Mat Perkins
(520) 481-8548
A
B D
EF
G
H
J
K
L
M
C
LINE INDICATES
PHASE 1 SCOPE AREA
B
IM
/6
-2
-1
E x p a n d e d P o ly tr a u m a P ro g ra m P h a s e
/6 -2
-7
.M
P L S
.P O
L Y
T R
A U
M A
.G e n e ra l.
S h e e ts
.r v t
/3
/2
:4
:3
P
M As indicated
04/03/2023 K. Luke N. Harper
618-22-100
1390 - M-503
MECHANICAL DETAILS
1 Veterans Drive, Minneapolis, MN 55417
B70
RENOVATE FOR EXPANDED
POLYTRAUMA PROGRAM
ISSUED FOR BIDDING
NTS
D7
DUCTWORK SQUARE VANE ELBOWS
NTS
B4
STEAM COIL DIAGRAM
NTS
B1
STEAM SAFETY VALVE
12" = 1'-0" F7
AIR HANDLING UNIT STEAM COIL PIPING DETAIL
STEAM TRAP
MONITOR
TEST TEE
STEAM TRAP
MONITOR
TEST TEE
STEAM TRAP
MONITOR
TEST TEE
on e-ei gh th ne fo ot on e-qu ar te r ne fo ot th re e-ei gh th s ne fo ot on e-ha lf ne fo ot th re e-qu ar te r ne fo ot in ch on e ne fo ot on e an d on e-ha lf ne fo ot th re e in ne fo ot
REVISIONS DATE
General Notes:
GENERAL CONTRACTOR AND/OR ALL SUBCONTRACTORS SHALL FIELD VERIFY ALL DIMENSIONS SHOWN ON THESE PLANS AND SHALL BE RESPONSIBLE FOR VARIATIONS BETWEEN PLAN DIMENSIONS AND ACTUAL FIELD DIMENSIONS. WHERE VARIATIONS ARE FOUND TO OCCUR, THE CONTRACTOR SHALL NOTIFY THE PROJECT ENGINEER IN WRITING PRIOR TO PROCEEDING WITH CONSTRUCTION; NO ADJUSTMENT TO
THE WORK WILL BE MADE WITHOUT THE PRIOR APPROVAL OF THE PROJECT ENGINEER.
GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR GENERAL DEMOLITION INCLUDING REMOVAL OF WALLS, PARTITIONS, DOORS & CEILING & FLOORS. ANY AND ALL CUTTING OF CONCRETE FLOORS, WALLS OR STRUCTURE SHALL BE THE GENERAL CONTRACTOR'S RESPONSIBILITY. CORE DRILLING THROUGH CONCRETE WALLS, FLOORS OR STRUCTURE FOR PIPING OR CONDUIT SHALL BE THE RESPONSIBILITY OF THE SUBCONTRACTOR BY TRADE; FIRESTOPPING OF THESE OPENINGS SHALL BE DONE BY THE RESPECTIVE SUBCONTRACTOR. REMOVAL OF DEBRIS RESULTING FROM DEMOLITION, CUTTING, AND/OR DRILLING IS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR. PATCHING AND REPAIR OF CONCRETE WALLS, FLOOR, OR STRUCTURE SHALL BE THE RESPONSIBILITY OF THE GENERAL CONTRACTOR; THIS WILL BE ACCOMPLISHED UPON COMPLETION OF THE INSTALLATION OF ANY AND ALL UTILITIES INSTALLED
BY THE VARIOUS SUBCONTRACTORS.
Approved: Division Chief
Issue Date Checked Drawn
DrawingNumber
Building Number
Project NumberDrawing Title Project Title
Location Drawing Scale
Approved: Service DirectorPlot Scale U.S. Department of Veterans Affairs
Office of Construction and Facilities Management
FULLY SPRINKLERED
Phase
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
TRUE NORTH
PLAN NORTH
KEYPLAN
A/E:
TRIPLE C - The A/E Group
Mat Perkins
(520) 481-8548
A
B D
EF
G
H
J
K
L
M
C
LINE INDICATES
PHASE 1 SCOPE AREA
B
IM
/6
-2
-1
E x p a n d e d P o ly tr a u m a P ro g ra m P h a s e
/6 -2
-7
.M
P L S
.P O
L Y
T R
A U
M A
.G e n e ra l.
S h e e ts
.r v t
/3
/2
:4
:4
P
M As indicated
04/03/2023 M. Perkins N. Harper
618-22-100
1390 - M-504
MECHANICAL DETAILS
1 Veterans Drive, Minneapolis, MN 55417
B70
RENOVATE FOR EXPANDED
POLYTRAUMA PROGRAM
ISSUED FOR BIDDING
NTS
B1
INVERTED BUCKET STEAM TRAP ASSEMBLY
NTS
B3
FLOAT AND THERMOSTATIC STEAM TRAP ASSEMBLY
NTS
B6
THERMOSTATIC STEAM TRAP ASSEMBLY
NTS
B8
SUPPLY DUCTWORK TAKE-OFFS
NTS
C8
SUPPLY DUCT TAKE-OFFS - AIR TERMINAL UNIT
NTS
D8
ALTERNATIVE SUPPLY DUCT TAKEOFF - AIR TERMINAL UNITS
NTS
F8
EXHAUST OR RETURN BRANCH DUCTWORK
on e-ei gh th ne fo ot on e-qu ar te r ne fo ot th re e-ei gh th s ne fo ot on e-ha lf ne fo ot th re e-qu ar te r ne fo ot in ch on e ne fo ot on e an d on e-ha lf ne fo ot th re e in ne fo ot
REVISIONS DATE
General Notes:
GENERAL CONTRACTOR AND/OR ALL SUBCONTRACTORS SHALL FIELD VERIFY ALL DIMENSIONS SHOWN ON THESE PLANS AND SHALL BE RESPONSIBLE FOR VARIATIONS BETWEEN PLAN DIMENSIONS AND ACTUAL FIELD DIMENSIONS. WHERE VARIATIONS ARE FOUND TO OCCUR, THE CONTRACTOR SHALL NOTIFY THE PROJECT ENGINEER IN WRITING PRIOR TO PROCEEDING WITH CONSTRUCTION; NO ADJUSTMENT TO
THE WORK WILL BE MADE WITHOUT THE PRIOR APPROVAL OF THE PROJECT ENGINEER.
GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR GENERAL DEMOLITION INCLUDING REMOVAL OF WALLS, PARTITIONS, DOORS & CEILING & FLOORS. ANY AND ALL CUTTING OF CONCRETE FLOORS, WALLS OR STRUCTURE SHALL BE THE GENERAL CONTRACTOR'S RESPONSIBILITY. CORE DRILLING THROUGH CONCRETE WALLS, FLOORS OR STRUCTURE FOR PIPING OR CONDUIT SHALL BE THE RESPONSIBILITY OF THE SUBCONTRACTOR BY TRADE; FIRESTOPPING OF THESE OPENINGS SHALL BE DONE BY THE RESPECTIVE SUBCONTRACTOR. REMOVAL OF DEBRIS RESULTING FROM DEMOLITION, CUTTING, AND/OR DRILLING IS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR. PATCHING AND REPAIR OF CONCRETE WALLS, FLOOR, OR STRUCTURE SHALL BE THE RESPONSIBILITY OF THE GENERAL CONTRACTOR; THIS WILL BE ACCOMPLISHED UPON COMPLETION OF THE INSTALLATION OF ANY AND ALL UTILITIES INSTALLED
BY THE VARIOUS SUBCONTRACTORS.
Approved: Division Chief
Issue Date Checked Drawn
DrawingNumber
Building Number
Project NumberDrawing Title Project Title
Location Drawing Scale
Approved: Service DirectorPlot Scale U.S. Department of Veterans Affairs
Office of Construction and Facilities Management
FULLY SPRINKLERED
Phase
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
TRUE NORTH
PLAN NORTH
KEYPLAN
A/E:
TRIPLE C - The A/E Group
Mat Perkins
(520) 481-8548
A
B D
EF
G
H
J
K
L
M
C
LINE INDICATES
PHASE 1 SCOPE AREA
B
IM
/6
-2
-1
E x p a n d e d P o ly tr a u m a P ro g ra m P h a s e
/6 -2
-7
.M
P L S
.P O
L Y
T R
A U
M A
.G e n e ra l.
S h e e ts
.r v t
/3
/2
:4
:4
P
M As indicated
04/03/2023 M. Perkins N. Harper
618-22-100
1390 - M-505
MECHANICAL DETAILS
1 Veterans Drive, Minneapolis, MN 55417
B70
RENOVATE FOR EXPANDED
POLYTRAUMA PROGRAM
ISSUED FOR BIDDING
NTS
B1
ACCESS PANEL AND DOOR DETAIL
NTS
A3
ACCESS SECTION FOR ROUND/OVAL DUCT
NTS
D1
FLEXIBLE DUCT CONNECTIONS
NTS
F1
SECTION THRU FIRE DAMPER INSTALLATION
NTS
F3
ROUND DUCT HANGERS
NTS
C3
DUCT RISER SUPPORTS
NTS
E3
EXHAUST OR RETURN BRANCH DUCTWORK
NTS
F6
OUTSIDE AIR INTAKE FOR AIR HANDLER UNIT FOR MISSION CRITICAL FACILITY
NTS
C5
ACCESS DOOR SWING DETAIL FOR AIR HANDLING UNITS
NTS
F8
SECTION THRU FIRE DAMPER INSTALLATION
NOTES:
1. THE COOLING COIL FIN SPACING SHALL NOT EXCEED 132 FINS PER FOOT [400 FINS PER METER].
2. COIL FRAMES SHALL BE STAINLESS STEEL CONSTRUCTION.
3. PROVE MOISTURE ELIMINATOR ON DISCHARGE SIDE OF COILS.
ei gh th ne fo ot on e-qu ar te r ne fo ot th re e-ei gh th s ne fo ot on e-ha lf ne fo ot th re e-qu ar te r ne fo ot in ch on e ne fo ot on e an d on e-ha lf ne fo ot th re e in ne fo ot
REVISIONS DATE
General Notes:
GENERAL CONTRACTOR AND/OR ALL SUBCONTRACTORS SHALL FIELD VERIFY ALL DIMENSIONS SHOWN ON THESE PLANS AND SHALL BE RESPONSIBLE FOR VARIATIONS BETWEEN PLAN DIMENSIONS AND ACTUAL FIELD DIMENSIONS. WHERE VARIATIONS ARE FOUND TO OCCUR, THE CONTRACTOR SHALL NOTIFY THE PROJECT ENGINEER IN WRITING PRIOR TO PROCEEDING WITH CONSTRUCTION; NO ADJUSTMENT TO
THE WORK WILL BE MADE WITHOUT THE PRIOR APPROVAL OF THE PROJECT ENGINEER.
GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR GENERAL DEMOLITION INCLUDING REMOVAL OF WALLS, PARTITIONS, DOORS & CEILING & FLOORS. ANY AND ALL CUTTING OF CONCRETE FLOORS, WALLS OR STRUCTURE SHALL BE THE GENERAL CONTRACTOR'S RESPONSIBILITY. CORE DRILLING THROUGH CONCRETE WALLS, FLOORS OR STRUCTURE FOR PIPING OR CONDUIT SHALL BE THE RESPONSIBILITY OF THE SUBCONTRACTOR BY TRADE; FIRESTOPPING OF THESE OPENINGS SHALL BE DONE BY THE RESPECTIVE SUBCONTRACTOR. REMOVAL OF DEBRIS RESULTING FROM DEMOLITION, CUTTING, AND/OR DRILLING IS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR. PATCHING AND REPAIR OF CONCRETE WALLS, FLOOR, OR STRUCTURE SHALL BE THE RESPONSIBILITY OF THE GENERAL CONTRACTOR; THIS WILL BE ACCOMPLISHED UPON COMPLETION OF THE INSTALLATION OF ANY AND ALL UTILITIES INSTALLED
BY THE VARIOUS SUBCONTRACTORS.
Approved: Division Chief
Issue Date Checked Drawn
DrawingNumber
Building Number
Project NumberDrawing Title Project Title
Location Drawing Scale
Approved: Service DirectorPlot Scale U.S. Department of Veterans Affairs
Office of Construction and Facilities Management
FULLY SPRINKLERED
Phase
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
TRUE NORTH
PLAN NORTH
KEYPLAN
A/E:
TRIPLE C - The A/E Group
Mat Perkins
(520) 481-8548
A
B D
EF
G
H
J
K
L
M
C
LINE INDICATES
PHASE 1 SCOPE AREA
B
IM
/6
-2
-1
E x p a n d e d P o ly tr a u m a P ro g ra m P h a s e
/6 -2
-7
.M
P L S
.P O
L Y
T R
A U
M A
.M E
P .B
.L
.r v t
/3
/2
:2
:3
P
M 12" = 1'-0"
04/03/2023 K. Luke N.Harper
618-22-100
1390 - M-700
MECHANICAL SCHEDULES
1 Veterans Drive, Minneapolis, MN 55417
B70
RENOVATE FOR EXPANDED
POLYTRAUMA PROGRAM - PHASE 1
ISSUED FOR BIDDING
AIR HANDLING UNIT NOTES:
1. FLOORS IN ALL WET UNIT SECTIONS (HUMIDIFIER SECTION AND
COOLING COIL SECTION) TO BE OF STAINLESS STEEL (TYPE 304).
2. CONTRACTOR SHALL COORDINATE SUPPLY FAN NUMBERS WITH
LOCAL HOSPITAL REPRESENTATIVES.
3. INCLUDE SHAFT GROUNDING ON ALL FAN MOTORS.
4. CABINET SHALL BE 2" FOAM-INJECTED (R-13) WITH THERMAL
BREAKS.
5. PROVIDE LED MARINE LIGHTS IN NON-FILTER SECTIONS. LIGHTS
SHALL BE TIED TOGETHER BY DIV. 26 USING A SINGLE POINT, 120V
LANDING WITH A MASTER LIGHT SWITH.
6. FURNISH OSA AIRFLOW MONITOR, THERMAL DISPERSION TYPE.
7. FURNISH DISCONNECTS AND VFDs FOR EACH FAN MOTOR. VFDs
SHALL BE PROVIDED WITH 3% LINE REACTORS.
8. FURNISH UNIT WITH SINGLE-POINT POWER, EXCEPT FOR
SEPARATE LIGHTING CIRCUIT AS DESCRIBED IN NOTE 5.
9. PROVIDE STAINLESS STEEL, SLOPED AND INSULATED DRAIN PAN.
SPECIAL NOTE TO CONTRACTOR: A PRE-CONSTRUCTION TAB SHALL BE
PERFORMED FOR EXISTING AHU-32 AND ALL SPACES WITHIN THE EXISTING
POLYTRAUMA 4K & 4H WING. CONTRACTOR SHALL ALSO PROVIDE
TRAVERSE READINGS ON ALL DUCTWORK MAINS (INCLUDING AREAS
SERVED OUTSIDE THE AREA OF WORK). THESE SHALL BE SUBMITTED FOR
VA/AE REVIEW PRIOR TO SUBMITTING ON NEW HVAC EQUIPMENT.
NOTES:
1. PROVIDE SQUARE TO ROUND ADAPTORS.
2. COORDINATE AIR DISTRIBUTION DEVICES WITH ARCHITECTURAL & LIGHTING CEILING GRIDS.
3. CONTRACTOR SHALL FURNISH AND INSTALL MANUAL VOLUME DAMPER AT EACH BRANCH DUCTWORK TAKE-OFF TO AIR DISTRIBUTION DEVICES.
1. PROVIDE SQUARE TO ROUND ADAPTORS.
2. COORDINATE AIR DISTRIBUTION DEVICES WITH ARCHITECTURAL & LIGHTING CEILING GRIDS.
3. CONTRACTOR SHALL FURNISH AND INSTALL MANUAL VOLUME DAMPER AT EACH BRANCH DUCTWORK TAKE-OFF TO AIR DISTRIBUTION DEVICES.
INCLUDE SHAFT GROUNDING ON ALL FAN MOTORS 5 HP AND GREATER. FURNISH DDC CONTROLS WITH EACH UNIT.
SPECIAL NOTE TO CONTRACTOR: A PRE-CONSTRUCTION TAB SHALL BE PERFORMED FOR EXISTING RF-27, EF-57, EF-62, SF-38 AND ALL SPACES WITHIN THE EXISTING POLYTRAUMA 4K & 4H WING. CONTRACTOR SHALL ALSO PROVIDE TRAVERSE READINGS ON ALL DUCTWORK MAINS (INCLUDING AREAS SERVED OUTSIDE THE AREA OF WORK). THESE SHALL BE
SUBMITTED FOR VA/AE REVIEW PRIOR TO SUBMITTING ON NEW HVAC EQUIPMENT.
INSUL. BACKPAN
INSUL. BACKPAN
INSUL. BACKPAN
INSUL. BACKPAN
INSUL. BACKPAN
INSUL. BACKPAN
INSUL. BACKPAN
INSUL. BACKPAN
INSUL. BACKPAN
INSUL. BACKPAN
INSUL. BACKPAN
INSUL. BACKPAN
ei gh th ne fo ot on e-qu ar te r ne fo ot th re e-ei gh th s ne fo ot on e-ha lf ne fo ot th re e-qu ar te r ne fo ot in ch on e ne fo ot on e an d on e-ha lf ne fo ot th re e in ne fo ot
REVISIONS DATE
General Notes:
GENERAL CONTRACTOR AND/OR ALL SUBCONTRACTORS SHALL FIELD VERIFY ALL DIMENSIONS SHOWN ON THESE PLANS AND SHALL BE RESPONSIBLE FOR VARIATIONS BETWEEN PLAN DIMENSIONS AND ACTUAL FIELD DIMENSIONS. WHERE VARIATIONS ARE FOUND TO OCCUR, THE CONTRACTOR SHALL NOTIFY THE PROJECT ENGINEER IN WRITING PRIOR TO PROCEEDING WITH CONSTRUCTION; NO ADJUSTMENT TO
THE WORK WILL BE MADE WITHOUT THE PRIOR APPROVAL OF THE PROJECT ENGINEER.
GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR GENERAL DEMOLITION INCLUDING REMOVAL OF WALLS, PARTITIONS, DOORS & CEILING & FLOORS. ANY AND ALL CUTTING OF CONCRETE FLOORS, WALLS OR STRUCTURE SHALL BE THE GENERAL CONTRACTOR'S RESPONSIBILITY. CORE DRILLING THROUGH CONCRETE WALLS, FLOORS OR STRUCTURE FOR PIPING OR CONDUIT SHALL BE THE RESPONSIBILITY OF THE SUBCONTRACTOR BY TRADE; FIRESTOPPING OF THESE OPENINGS SHALL BE DONE BY THE RESPECTIVE SUBCONTRACTOR. REMOVAL OF DEBRIS RESULTING FROM DEMOLITION, CUTTING, AND/OR DRILLING IS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR. PATCHING AND REPAIR OF CONCRETE WALLS, FLOOR, OR STRUCTURE SHALL BE THE RESPONSIBILITY OF THE GENERAL CONTRACTOR; THIS WILL BE ACCOMPLISHED UPON COMPLETION OF THE INSTALLATION OF ANY AND ALL UTILITIES INSTALLED
BY THE VARIOUS SUBCONTRACTORS.
Approved: Division Chief
Issue Date Checked Drawn
DrawingNumber
Building Number
Project NumberDrawing Title Project Title
Location Drawing Scale
Approved: Service DirectorPlot Scale U.S. Department of Veterans Affairs
Office of Construction and Facilities Management
FULLY SPRINKLERED
Phase
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
TRUE NORTH
PLAN NORTH
KEYPLAN
A/E:
TRIPLE C - The A/E Group
Mat Perkins
(520) 481-8548
A
B D
EF
G
H
J
K
L
M
C
LINE INDICATES
PHASE 1 SCOPE AREA
B
IM
/6
-2
-1
E x p a n d e d P o ly tr a u m a P ro g ra m P h a s e
/6 -2
-7
.M
P L S
.P O
L Y
T R
A U
M A
.M E
P .B
.L
.r v t
/3
/2
:2
:3
P
M
04/03/2023 K. Luke N.Harper
618-22-100
1390 - M-701
MECHANICAL SCHEDULES
1 Veterans Drive, Minneapolis, MN 55417
B70
RENOVATE FOR EXPANDED
POLYTRAUMA PROGRAM - PHASE 1
ISSUED FOR BIDDING
SINGLE DUCT CONSTANT VOLUME AND VARIABLE AIR VOLUME TERMINAL UNITS WITH HOT WATER REHEAT COILS: FURNISH AND INSTALL SINGLE DUCT VARIABLE AIR VOLUME CONTROL ASSEMBLIES OF SIZES AND CAPACITIES SHOWN ON THE DRAWINGS. ALL UNITS SHALL BE CAPABLE OF VARIABLE AIR VOLUME CONTROL WITH TERMINAL HOT WATER REHEAT. VALVE ASSEMBLY SHALL BE NORMALLY OPEN ARRANGEMENT, PRESSURE INDEPENDENT AND SHALL BE CAPABLE OF FIELD RESET TO ANY DESIRED AIR FLOW BETWEEN ZERO AND THE MAXIMUM SCHEDULED CFM. ALL TERMINAL UNITS SHALL BE FURNISHED WITH ACOUSTICALLY LINED CASINGS CONSTRUCTED OF 22 GAUGE GALVANIZED STEEL INTERNAL LINING OF 1" THICKNESS, 1- 1/2 POUND DENSITY, UL 181 AND ASTM C1071 REQUIREMENTS. EACH UNIT SHALL BE FURNISHED WITH A FACTORY ATTENUATOR SECTION HAVING THE SAME CONSTRUCTION AND LINER AS ABOVE. DAMPER BLADE SHALL BE CONSTRUCTED OF EXTRUDED ALUMINUM WITH RUSTPROOF SELF LUBRICATING BEARINGS. DAMPER SHALL SEAL AGAINST GASKETED STOPS. THE DAMPER LEAKAGE SHALL BE CERTIFIED TO NOT EXCEED 2 PERCENT LEAKAGE AT 6" INLET STATIC PRESSURE AS DETERMINED BY AIR DIFFUSION COUNCIL STANDARDS. A FLOW MEASURING PROBE SHALL BE INSTALLED IN THE UNIT INTAKE AND PROVIDE TOTAL AND STATIC PRESSURE CONNECTIONS ON THE INLET COLLAR EXTERIOR. SOUND RATINGS SHALL NOT EXCEED THOSE SCHEDULED AT 3 INCH STATIC PRESSURE. RADIATED NOISE CRITERIA ADDITIONALLY ASSUMES A CEILING STC OF 35-39. ALL TERMINALS SHALL BE END OUTLET. TERMINALS SHALL BE SHIPPED WITH APPROPRIATE IDENTIFICATION INCLUDING MODEL, SIZE AND CFM MARKED ON THE UNIT. SEE FLOOR PLANS FOR LOCATION AND MAXIMUM AND MINIMUM AIR FLOW REQUIREMENTS AND HEATING WATER GPM OF EACH UNIT. PERMANENTLY AFFIXED ENGRAVED METAL NAMEPLATE
CONTAINING MODEL AND SERIAL NUMBER.
UNITS SHALL BE TITUS.
HEATING: COILS SHALL BE 2 ROWS MINIMUM SELECTED FOR HOT WATER DUTY AT 180 DEGREES F EWT, 160 DEGREES F LWT, AND SHALL BE CAPABLE OF RAISING THE MINIMUM AIR FLOW SCHEDULED ON THE DRAWINGS FROM 55 DEGREES EAT TO 95 DEGREES LAT, USING 4.3 GPM PER 1000 CFM OF AIR FLOW. COILS SHALL BE SELECTED FOR SAME END CONNECTIONS, ARI CERTIFIED, AND SELECTED SUCH THAT MAXIMUM STATIC PRESSURE DROP THROUGH THE ENTIRE VAV REHEAT ASSEMBLY SHALL NOT EXCEED 0.55" APD. WATER PD THROUGH COIL SHALL NOT EXCEED 10 FT.
TERMINAL UNIT CONTROLS: UNIT CONTROL SYSTEM SHALL INCLUDE DIRECT DIGITAL VARIABLE VOLUME TERMINAL UNIT CONTROLLER MOUNTED IN NEMA I ENCLOSURE, 120/24 VAC CONTROL TRANSFORMER SIZED FOR THE REQUIRED CONTROL 24 VAC LOADS, A DETAILED POINT TO POINT WIRING DIAGRAM, AND 24 VAC FLOATING POINT AIR VALVE ACTUATOR AND HOT WATER REHEAT COIL CONTROL VALVE WITH ELECTRONIC FULLY MODULATING ACTUATOR SHALL BE FURNISHED AND INSTALLED BY TEMPERATURE CONTROL SUB-CONTRACTOR UNDER SPECIFICATION SECTION 230923. SECTION 230923 SHALL PROVIDE AND CONNECT ALL CONTROL WIRING, SAFETY DISCONNECT, TRANSFORMER SECONDARY FUSING, ETC. IN ACCORDANCE WITH THE DETAILED POINT TO POINT WIRING DIAGRAM, AND PERFORM A PRELIMINARY STARTUP AND TESTING PROCEDURE ON THE INSTALLED ASSEMBLY. THE TERMINAL UNIT HOT WATER VALVE SHALL BE FURNISHED UNDER SECTION 230923 FOR FIELD PIPING INSTALLATION BY THE CONTRACTOR. ALL REQUIRED DDC SYSTEM COMMUNICATIONS WIRING, AND SPACE TEMPERATURE SENSOR STATION
SHALL BE SUPPLIED AND INSTALLED UNDER SECTION 230900.
SEE NOTES,
THIS SHEET.
SEE NOTES,
THIS SHEET.
SEE NOTES,
THIS SHEET.
SEE NOTES,
THIS SHEET.
SEE NOTES,
THIS SHEET.
SEE NOTES,
THIS SHEET.
SEE NOTES,
THIS SHEET.
SEE NOTES,
THIS SHEET.
SEE NOTES,
THIS SHEET.
SEE NOTES,
THIS SHEET.
SEE NOTES,
THIS SHEET.
SEE NOTES,
THIS SHEET.
SEE NOTES,
THIS SHEET.
SEE NOTES,
THIS SHEET.
SEE NOTES,
THIS SHEET.
SEE NOTES,
THIS SHEET.
SEE NOTES,
THIS SHEET.
SEE NOTES,
THIS SHEET.
SEE NOTES,
THIS SHEET.
SEE NOTES,
THIS SHEET.
SEE NOTES,
THIS SHEET.
SEE NOTES,
THIS SHEET.
SEE NOTES,
THIS SHEET.
SEE NOTES,
THIS SHEET.
SEE NOTES,
THIS SHEET.
SEE NOTES,
THIS SHEET.
SEE NOTES,
THIS SHEET.
SEE NOTES,
THIS SHEET.
SEE NOTES,
THIS SHEET.
SEE NOTES,
THIS SHEET.
SEE NOTES,
THIS SHEET.
SEE NOTES,
THIS SHEET.
SEE NOTES,
THIS SHEET.
SEE NOTES,
THIS SHEET.
SEE NOTES,
THIS SHEET.
SEE NOTES,
THIS SHEET.
SEE NOTES,
THIS SHEET.
SEE NOTES,
THIS SHEET.
SEE NOTES,
THIS SHEET.
NOTES:
1. STEAM DISTRIBUTORS SHALL STAINLESS STEEL.
2. VALVE ASSEMBLIES SHALL HAVE STAINLESS STEEL SEAT, STEM AND PLUG.
3. FURNISH WITH MODULATING CONTROL.
4. PROVIDE ELECTRIC ACTUATOR/LINKAGE.
ei gh th ne fo ot on e-qu ar te r ne fo ot th re e-ei gh th s ne fo ot on e-ha lf ne fo ot th re e-qu ar te r ne fo ot in ch on e ne fo ot on e an d on e-ha lf ne fo ot th re e in ne fo ot
REVISIONS DATE
General Notes:
GENERAL CONTRACTOR AND/OR ALL SUBCONTRACTORS SHALL FIELD VERIFY ALL DIMENSIONS SHOWN ON THESE PLANS AND SHALL BE RESPONSIBLE FOR VARIATIONS BETWEEN PLAN DIMENSIONS AND ACTUAL FIELD DIMENSIONS. WHERE VARIATIONS ARE FOUND TO OCCUR, THE CONTRACTOR SHALL NOTIFY THE PROJECT ENGINEER IN WRITING PRIOR TO PROCEEDING WITH CONSTRUCTION; NO ADJUSTMENT TO
THE WORK WILL BE MADE WITHOUT THE PRIOR APPROVAL OF THE PROJECT ENGINEER.
GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR GENERAL DEMOLITION INCLUDING REMOVAL OF WALLS, PARTITIONS, DOORS & CEILING & FLOORS. ANY AND ALL CUTTING OF CONCRETE FLOORS, WALLS OR STRUCTURE SHALL BE THE GENERAL CONTRACTOR'S RESPONSIBILITY. CORE DRILLING THROUGH CONCRETE WALLS, FLOORS OR STRUCTURE FOR PIPING OR CONDUIT SHALL BE THE RESPONSIBILITY OF THE SUBCONTRACTOR BY TRADE; FIRESTOPPING OF THESE OPENINGS SHALL BE DONE BY THE RESPECTIVE SUBCONTRACTOR. REMOVAL OF DEBRIS RESULTING FROM DEMOLITION, CUTTING, AND/OR DRILLING IS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR. PATCHING AND REPAIR OF CONCRETE WALLS, FLOOR, OR STRUCTURE SHALL BE THE RESPONSIBILITY OF THE GENERAL CONTRACTOR; THIS WILL BE ACCOMPLISHED UPON COMPLETION OF THE INSTALLATION OF ANY AND ALL UTILITIES INSTALLED
BY THE VARIOUS SUBCONTRACTORS.
Approved: Division Chief
Issue Date Checked Drawn
DrawingNumber
Building Number
Project NumberDrawing Title Project Title
Location Drawing Scale
Approved: Service DirectorPlot Scale U.S. Department of Veterans Affairs
Office of Construction and Facilities Management
FULLY SPRINKLERED
Phase
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
TRUE NORTH
PLAN NORTH
KEYPLAN
A/E:
TRIPLE C - The A/E Group
Mat Perkins
(520) 481-8548
A
B D
EF
G
H
J
K
L
M
C
LINE INDICATES
PHASE 1 SCOPE AREA
B
IM
/6
-2
-1
E x p a n d e d P o ly tr a u m a P ro g ra m P h a s e
/6 -2
-7
.M
P L S
.P O
L Y
T R
A U
M A
.M E
P .B
.L
.r v t
/3
/2
:2
:4
P
M
04/03/2023 K. Luke M. RIFFLE
618-22-100
1390 - M-702
MECHANICAL SCHEDULES
1 Veterans Drive, Minneapolis, MN 55417
B70
RENOVATE FOR EXPANDED
POLYTRAUMA PROGRAM - PHASE 1
ISSUED FOR BIDDING
LA LEVEL ALARM
AT ANALYTICAL TRANSMITTER
AY ANALYTICAL SIGNAL CONVERTER
ACV ANALYTICAL CONTROL VALVE
AIT ANALYTICAL INDICATING CONTROLLER
EY VOLTAGE SIGNAL CONVERTER
IY CURRENT SIGNAL CONVERTER
HS HAND SWITCH
FIT FLOW INDICATING TRANSMITTER
FET FLOW ELEMENT\TRANSMITTER
ESL VOLTAGE SWITCH LOW (24 VAC OR LESS)
II CURRENT INDICATOR
IT CURRENT TRANSMITTER
IS CURRENT SWITCH
IA CURRENT ALARM
FA FLOW ALARM
HSI HAND SWITCH INDICATOR
HK MANUAL VARIABLE CONTROL
FY FLOW SIGNAL CONVERTER
FT FLOW TRANSMITTER
FS FLOW SWITCH
FI FLOW INDICATOR
FE FLOW ELEMENT
FCV FLOW CONTROL VALVE
ET VOLTAGE TRANSMITTER
ES VOLTAGE SWITCH (CONTROL RELAY)
EA VOLTAGE ALARM
EI VOLTAGE INDICATOR
PY PRESSURE SIGNAL CONVERTER
PDT PRESSURE DIFFERENTIAL TRANSMITTER
PS PRESSURE SWITCH
PA PRESSURE ALARM
PT PRESSURE TRANSMITTER
PIT PRESSURE INDICATING TRANSMITTER
PIS PRESSURE INDICATING SWITCH
PI PRESSURE INDICATOR
PDS PRESSURE DIFFERENTIAL SWITCH
PDI PRESSURE DIFFERENTIAL INDICATOR
PCV PRESSURE CONTROL VALVE
MV MANUAL HAND VALVE
LT LEVEL TRANSMITTER
LS LEVEL SWITCH
LE LEVEL ELEMENT
LY LEVEL SIGNAL CONVERTER
LIT LEVEL INDICATING TRANSMITTER
LIC LEVEL INDICATING CONTROLLER
LCV LEVEL CONTROL VALVE
LC LEVEL CONTROLLER (STAND ALONE)
VA VIBRATION ALARM
VS VIBRATION SWITCH
XV SOLENOID VALVE
YS SMOKE DETECTOR
VA VIBRATION ALARM
VS VIBRATION SWITCH
YCD SMOKE DAMPER
TT TEMPERATURE TRANSMITTER
TS TEMPERATURE SWITCH
TIC TEMPERATURE INDICATING CONTROLLER
TIT TEMPERATURE INDICATING TRANSMITTER
TI TEMPERATURE INDICATOR
TET TEMPERATURE ELEMENT TRANSMITTER
TE TEMPERATURE ELEMENT
TCV TEMPERATURE CONTROL VALVE
TC TEMPERATURE CONTROLLER
TA TEMPERATURE ALARM
SCM SPEED CONTROL MANUAL
TSL FREEZE STAT
SC SPEED CONTROL
INSTRUMENTATION SOCIETY OF AMERICA TABLE
INSTRUMENTATION TYPE ABBREVIATION LIST
AIC ANALYTICAL INDICATING CONTROLLER
AET ANALYTICAL ELEMENT TRANSMITTER
A
AC ANALYTICAL CONTROLLER
AI ANALYTICAL INDICATOR
AE ANALYTICAL ELEMENT
AA ANALYTICAL ALARM
CODE DESCRIPTION
VARIABLE
FINAL CONTROL ELEMENT
CODE DESCRIPTION
KC TIME CLOCK
JY POWER SIGNAL CONVERTER
JIT POWER INDICATING TRANSMITTER
TOTALIZE
CHANGE
CONNECTION
CODE DESCRIPTION
VIEWING DEVICE
PRIMARY ELEMENT
NORMALLY CLOSED OVERLOAD CONTACTS
ABBREVIATIONS
IA INSTRUMENTATION AIR
DDC DIRECT DIGITAL CONTROL
C COMMON VALVE PORT
F.O FAIL OPEN
F.C FAIL CLOSED
SR SPRING RANGE
TR THROTTLING RANGE
PH PREHEAT
HR HEAT RECOVERY
CPA CONTROL POINT ADJUSTMENT
SPDT SINGLE POLE DOUBLE THROW
DPDT DOUBLE THROW DOUBLE POLE
DA DIRECT ACTING
RA REVERSE ACTING
EP COIL IN MOTOR STARTER
TRANSFORMER
R
C
OL
HOA
CONTACT NORMALLY OPEN
PILOT LIGHT (COLOR INDICATION)
COIL IN MOTOR STARTER
CONTACT NORMALLY CLOSED
SWITCH
FUSE
HAND-OFF-AUTO SWITCH
I UNDEFINED INTERLOCK LOGIC
GENERAL INSTRUMENT OR FUNCTION SYMBOLS
FIELD
MOUNTED MOUNTED
PANEL AUXILIARY
LOCATION
ACCESSIBLE INACCESSIBLE
LOCATION
AUXILIARY
DISCRETE INSTRUMENTS
SHARED DISPLAY, SHARED CONTROL
PROGRAMMABLE LOGIC CONTROL
OR DIRECT DIGITAL CONTROL
COMPUTER FUNCTION
DUAL (MULTI)
FUNCTION INSTRUMENT
INDICATING LIGHTS, ALARMS OR HORNS
CONTROL VALVE BODY/ DAMPER SYMBOLS
GENERAL SYMBOL
ANGLE
BUTTERFLY
ROTARY VALVE
THREE - WAY
FOUR - WAY
GLOBE
PARALLEL BLADE
OPPOSED BLADE
TEMPERATURE
DUCT MOUNTED AVERAGING
WELL MOUNTED
ELEMENT/SENSOR ELEMENT/SENSOR
ELEMENT/SENSOR ELEMENT/SENSOR
SURFACE MOUNTED
PRESSURE
DIRECT MOUNTED
ELEMENT/SENSOR
DIFFERENTIAL PRESSURE
ELEMENT/SENSOR
LEVEL
FLOAT TYPE PADDLE TYPE
LEVEL TRANSMITTER
TANK MOUNTED
SONIC OR
RADIOACTIVE
FLOW
ORIFICE PLATE
TURBINE OR
PROPELLER
TYPE
SENSOR
VORTEX
TYPE
TARGET
SENSOR TRANSMITTER
MAGNETIC
TYPE
M
TRANSIT TIME
SONIC FLOWMETER
"DOPPLER" OR
FLOW ARROW
XXX INDICATES
AIR TYPE
INSTRUMENT NAMING CONVENTION
XXX - FUNCTION ID
NNN - DEVICE NUMBER
ZZZ - USER CHOICE
CURRENT
CURRENT SENSOR/TRANSMITTER
LINE LEGEND
INTERNAL SYSTEM LINK
ELECTRICAL SIGNAL
PNEUMATIC SIGNAL
YI EQUIPMENT STATUS
YA EQUIPMENT ALARM
ZI POSITION INDICATOR
ZS POSITION SWITCH
ZC POSITION CONTROL
AAA - UNIT ASSOCIATION OR
PROCESS CODE
PROCESS CODES
TW COOLING TOWER OR CONDENSER WATER
CHW CHILLED WATER
SCHW SECONDARY CHILLED WATER
HW HOT WATER
SHW SECONDARY HOT WATER
STM STEAM
AAA-NNN
XXX
ZZZ
NT HUMIDITY TRANSMITTER
FMS SYSTEM OPERATING CONSTRAINTS
THE FMS CONTROL SYSTEM SHALL OPERATE WITHIN THE FOLLOWING SYSTEM CONSTRAINTS FOR CONTROL:
SUPPLY AIR DRYBULB TEMPERATURE
MIXED AIR DRYBULB TEMPERATURE
WATER TEMPERATURE
DUCT STATIC PRESSURE
SUPPLY/ RETURN AIR VOLUME
OUTSIDE AIR/ RELIEF AIR VOLUME
BUILDING PRESSURE
ROOM TEMPERATURE
ROOM AIR VOLUME
HUMIDITY LEVEL
WATER TEMPERATURE
WATER DIFFERENTIAL PRESSURE
+/- 0.5°F OF SETPOINT WITH HUNTING OF < 5% OF THE CONTROL SIGNAL
FT
FT
FE
FE
FEFE
L
L
L
TE
L
PD
TETE
TE
+/- 0.5°F OF SETPOINT WITH HUNTING OF < 5% OF THE CONTROL SIGNAL
+/- 1.0 PSI OF SETPOINT WITH HUNTING OF < 5% OF THE CONTROL SIGNAL
+/- 0.5°F OF SETPOINT WITH HUNTING OF < 5% OF THE CONTROL SIGNAL
+/- 0.1" W.C. OF SETPOINT WITH HUNTING OF < 5% OF THE CONTROL SIGNAL
+/- 2.5% OF SETPOINT WITH HUNTING OF < 5% OF THE CONTROL SIGNAL
+/- 2.5% OF SETPOINT WITH HUNTING OF < 5% OF THE CONTROL SIGNAL
+/- 0.01" W.C. OF SETPOINT WITH HUNTING OF < 5% OF THE CONTROL SIGNAL
+/- 1.0°F OF SETPOINT WITH HUNTING OF < 5% OF THE CONTROL SIGNAL
+/- 2.5% OF SETPOINT WITH HUNTING OF < 5% OF THE CONTROL SIGNAL
+/- 2.5% R.H. OF SETPOINT WITH HUNTING OF < 5% OF THE CONTROL SIGNAL
+/- 1.0°F OF SETPOINT WITH HUNTING OF < 5% OF THE CONTROL SIGNAL
FIRST LETTER SUCCEEDING LETTERS (3)
MEASURING OR MODIFIER READOUT OR OUTPUT MODIFIER
INITIATING PASSIVE FUNCTION FUNCTION
ANALYSIS ALARM
B BURNER FLAME USER CHOICE USER CHOICE USER CHOICE
C CONDUCTIVITY CONTROL (13)
D DENSITY DIFFERENTIAL
E VOLTAGE SENSOR
F FLOW RATE RATIO FRACTION
G GAUGE GLASS,
H HAND HIGH
I CURRENT INDICATE
J POWER SCAN
K TIME TIME RATE OF CONTROL STATION
L LEVEL LIGHT LOW
M MOTION MOMENTARY MIDDLE
INTERMEDIATE
N HUMIDITY USER DEFINED USER DEFINED USER DEFINED
O USER CHOICE ORIFICE RESTRICTION
P PRESSURE, VACUUM POINT (TEST)
Q QUANTITY INTEGRATE,
R RADIATION RECORD
S SPEED, FREQUENCY SAFETY SWITCH
T TEMPERATURE TRANSMIT
U MULTI-VARIABLE MULTI-FUNCTION MULTI-FUNCTION MULTI-FUNCTION
V VIBRATION, MECHANICAL VALVE, DAMPER
ANALYSIS LOUVER
W WEIGHT, FORCE WELL
X UNCLASSIFIED X-AXIS UNCLASSIFIED UNCLASSIFIED UNCLASSIFIED
Y EVENT, STATE OR Y-AXIS RELAY, COMPUTE
PRESENCE CONVERT
Z POSITION Z-AXIS DRIVER, ACTUATOR
DIMENSION UNCLASSIFIED
GENERAL SHEET NOTES
MECHANICAL CONTROLS GENERAL NOTES
A. TEST AND BALANCE CONTRACTOR SHALL PROVIDE A PRE-CONSTRUCTION TAB REPORT FOR
THE EQUIPMENT AND ASSOCIATED SYSTEMS SHOWN ON THE CONSTRUCTION DOCUMENTS
AND UTILIZE ALL AVAILABLE AS-BUILT DRAWINGS FROM THE OWNER. TEST AND BALANCE
CONTRACTOR SHALL VISIT SITE PRIOR TO CONSTRUCTION AND VERIFY ALL EXISTING
EQUIPMENT AND DEVICES, AND DEVELOP THEIR TEST AND BALANCE FORMS INCLUDING
DRAWINGS SHOWING EQUIPMENT LOCATIONS, AIR DISTRIBUTION DEVICE LOCATIONS AND TAG
NUMBERS. IF THERE ARE LOCATIONS WHERE THE DRAWINGS DO NOT REFLECT FIELD
CONDITIONS, THE TEST AND BALANCE CONTRACTOR SHALL INCLUDE THE AIRFLOW AND
WATER FLOW READINGS ON THE FORMS AND LOCATE THE EQUIPMENT AND/OR AIR DEVICE
ON THE DRAWINGS. REFER TO SPECIFICATION SECTION 23 50 93 FOR MORE INFORMATION.
B. ALL DATA OBTAINED VIA TESTING AND MEASURING SHALL BE UTILIZED TO ESTABLISH NEW
HVAC SYSTEM PERFORMANCE AND BALANCE DATA FOR THE RENOVATION. DATA SHALL BE
FORWARDED TO THE PROJECT ENGINEER FOR REVIEW AND COMMENT PRIOR TO
COMMENCING THE DEMOLITION AND/OR NEW WORK ASSOCIATED WITH THE FACILITY
RENOVATION.
C. THE CONTRACTOR SHALL REMOVE ALL EXISTING EQUIPMENT, DUCTWORK, PIPING, CONTROL
PANELS, CONTROL DEVICES INCLUDING PNEUMATIC TUBING, AND ASSOCIATED ITEMS WHICH
ARE BEING REPLACED, IN THEIR ENTIRETY. THE CONTRACTOR IS RESPONSIBLE FOR
REMOVING ALL DEMOLISHED ITEMS FROM THE SITE. REFER TO SPECIFICATIONS FOR MORE
INFORMATION.
D. PROVIDE AIR BALANCE REPORT PRIOR TO FINAL INSPECTION.
E. ALL NEW TO EXISTING DUCT CONNECTIONS SHALL BE FIELD VERIFIED PRIOR TO ORDERING
AND FABRICATING NEW DUCTWORK OR DAMPERS.
F. ALL CONTROL WIRING SHALL BE ROUTED IN CONDUIT TO EACH CONTROL DEVICE.
G. AS-BUILT NOTE: THE BUILDING'S VERTICAL STRUCTURE AND GRID LAYOUT IS SHOWN BASED
ON RECORD DOCUMENTS AND / OR LASER SCANS OF THE AREA. COLUMNS MAY BE OFFSET
FROM GRID LINES WITHOUT AN IDENTIFYING GRID LINE AND ALL GRID LINES MAY NOT HOST
COLUMNS ON ALL LEVELS.
H. CONTRACTOR TO PERFORM MECHANICAL EQUIPMENT REPLACEMENT DURING NIGHTS AND
WEEKENDS TO MITIGATE FACILITY DOWNTIME. ALL OUTAGES MUST BE SCHEDULED WITH AND
APPROVED BY THE VA. FACILITY HOURS OF OPERATION ARE 7:00 AM TO 4:00 PM.
1. EQUIPMENT CONTROLLERS SHALL CONTAIN COMPLETE CONTROL LOGIC, INCLUDING ALL I/O
POINTS TO PROVIDE STAND-ALONE CONTROL IN THE EVENT OF COMMUNICATION FAILURE.
2. ALL EQUIPMENT CONTROL HARDWARE SHALL USE BACNET PROTOCOL BETWEEN THE OPERATOR
WORKSTATION, WEBSERVER AND FOR COMMUNICATIONS BETWEEN CONTROLLERS.
3. ALL EQUIPMENT CONTROL HARDWARE SHALL CONFORM TO APPLICABLE BACNET DEVICE
PROFILES AND SHALL BE LISTED BY THE BACNET TESTING LABORATORIES.
4. THE MECHANICAL CONTROL SYSTEM SOFTWARE SHALL INCLUDE A GRAPHICAL USER INTERFACE WITH POINT AND CLICK NAVIGATION THAT ALLOWS THE OPERATOR TO ADJUST PROPERTIES, SET
POINTS AND ALARMS.
5. GRAPHICAL USER INTERFACE SHALL PROVIDE AT LEAST ONE GRAPHIC FOR EACH PIECE OF
EQUIPMENT AND ZONE. GRAPHICAL USER INTERFACE SHALL USE DYNAMIC COLORS TO
REPRESENT EACH ZONE'S TEMPERATURE RELATIVE TO ITS SETPOINT.
6. CONTROL SYSTEM SHALL INCLUDE AN ENERGY REPORTING TOOL AND SCHEDULING
FUNCTIONALITY.
7. CONTRACTOR SHALL PROVIDE ALL THE TOOLS AND FUNCTIONALITY NECESSARY FOR THE
OPERATOR TO MAINTAIN AND ADJUST THE SYSTEM, INCLUDING: CONFIGURING THE DATABASE;
DOWNLOADING MEMORY TO THE CONTROLLERS; ADD, DELETE AND CONTROL PRIVILEGES FOR
EACH OPERATOR; CONFIGURE ALARMS, ALARM MESSAGES, AND ALARM REACTIONS; CONFIGURE
TRENDS INCLUDING SETTING THE INTERVAL RANGE OR CHANGE VALUE INCREMENT THAT
CAUSES A TREND SAMPLE TO BE RECORDED; CONFIGURE AND RUN STANDARD REPORTS TO
SHOW POINT STATUS, ALARM STATUS, LOCKED POINTS, AND OPERATOR ACTIVITY; CREATE AND
EDIT SYSTEM GRAPHICS AND TO DISPLAY DYNAMIC SYSTEM DATA ON THE GRAPHICS; AND
CREATE AND EDIT CUSTOM CONTROL PROGRAMS AND DOWNLOAD THESE PROGRAMS TO EACH
CONTROLLER.
8. SYSTEM SECURITY SHALL ALLOW AN AUTHORIZED USER TO CONTROL PRIVILEGES ASSOCIATED WITH EACH OPERATOR INCLUDING THE ABILITY TO VARY AND REGULATE ACCESS TO INDIVIDUAL
PIECES OF EQUIPMENT.
on e-ei gh th ne fo ot on e-qu ar te r ne fo ot th re e-ei gh th s ne fo ot on e-ha lf ne fo ot th re e-qu ar te r ne fo ot in ch on e ne fo ot on e an d on e-ha lf ne fo ot th re e in ne fo ot
REVISIONS DATE
General Notes:
GENERAL CONTRACTOR AND/OR ALL SUBCONTRACTORS SHALL FIELD VERIFY ALL DIMENSIONS SHOWN ON THESE PLANS AND SHALL BE RESPONSIBLE FOR VARIATIONS BETWEEN PLAN DIMENSIONS AND ACTUAL FIELD DIMENSIONS. WHERE VARIATIONS ARE FOUND TO OCCUR, THE CONTRACTOR SHALL NOTIFY THE PROJECT ENGINEER IN WRITING PRIOR TO PROCEEDING WITH CONSTRUCTION; NO ADJUSTMENT TO
THE WORK WILL BE MADE WITHOUT THE PRIOR APPROVAL OF THE PROJECT ENGINEER.
GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR GENERAL DEMOLITION INCLUDING REMOVAL OF WALLS, PARTITIONS, DOORS & CEILING & FLOORS. ANY AND ALL CUTTING OF CONCRETE FLOORS, WALLS OR STRUCTURE SHALL BE THE GENERAL CONTRACTOR'S RESPONSIBILITY. CORE DRILLING THROUGH CONCRETE WALLS, FLOORS OR STRUCTURE FOR PIPING OR CONDUIT SHALL BE THE RESPONSIBILITY OF THE SUBCONTRACTOR BY TRADE; FIRESTOPPING OF THESE OPENINGS SHALL BE DONE BY THE RESPECTIVE SUBCONTRACTOR. REMOVAL OF DEBRIS RESULTING FROM DEMOLITION, CUTTING, AND/OR DRILLING IS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR. PATCHING AND REPAIR OF CONCRETE WALLS, FLOOR, OR STRUCTURE SHALL BE THE RESPONSIBILITY OF THE GENERAL CONTRACTOR; THIS WILL BE ACCOMPLISHED UPON COMPLETION OF THE INSTALLATION OF ANY AND ALL UTILITIES INSTALLED
BY THE VARIOUS SUBCONTRACTORS.
Approved: Division Chief
Issue Date Checked Drawn
DrawingNumber
Building Number
Project NumberDrawing Title Project Title
Location Drawing Scale
Approved: Service DirectorPlot Scale U.S. Department of Veterans Affairs
Office of Construction and Facilities Management
FULLY SPRINKLERED
Phase
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
TRUE NORTH
PLAN NORTH
KEYPLAN
A/E:
TRIPLE C - The A/E Group
Mat Perkins
(520) 481-8548
A
B D
EF
G
H
J
K
L
M
C
LINE INDICATES
PHASE 1 SCOPE AREA
B
IM
/6
-2
-1
E x p a n d e d P o ly tr a u m a P ro g ra m P h a s e
/6 -2
-7
.M
P L S
.P O
L Y
T R
A U
M A
.G e n e ra l.
S h e e ts
.r v t
/3
/2
:4
:5
P
M 1/4" = 1'-0"
04/03/2023 K. Luke N. Harper
618-22-100
1390 - M-801
MECHANICAL CONTROL SYMBOL LEGEND
AND ABBREVIATIONS
1 Veterans Drive, Minneapolis, MN 55417
B70
RENOVATE FOR EXPANDED
POLYTRAUMA PROGRAM
STEAM
EXISTING GLOBAL OA
TEMPERATURE
SENSOR VIA METASYS
on e-ei gh th ne fo ot on e-qu ar te r ne fo ot th re e-ei gh th s ne fo ot on e-ha lf ne fo ot th re e-qu ar te r ne fo ot in ch on e ne fo ot on e an d on e-ha lf ne fo ot th re e in ne fo ot
REVISIONS DATE
General Notes:
GENERAL CONTRACTOR AND/OR ALL SUBCONTRACTORS SHALL FIELD VERIFY ALL DIMENSIONS SHOWN ON THESE PLANS AND SHALL BE RESPONSIBLE FOR VARIATIONS BETWEEN PLAN DIMENSIONS AND ACTUAL FIELD DIMENSIONS. WHERE VARIATIONS ARE FOUND TO OCCUR, THE CONTRACTOR SHALL NOTIFY THE PROJECT ENGINEER IN WRITING PRIOR TO PROCEEDING WITH CONSTRUCTION; NO ADJUSTMENT TO
THE WORK WILL BE MADE WITHOUT THE PRIOR APPROVAL OF THE PROJECT ENGINEER.
GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR GENERAL DEMOLITION INCLUDING REMOVAL OF WALLS, PARTITIONS, DOORS & CEILING & FLOORS. ANY AND ALL CUTTING OF CONCRETE FLOORS, WALLS OR STRUCTURE SHALL BE THE GENERAL CONTRACTOR'S RESPONSIBILITY. CORE DRILLING THROUGH CONCRETE WALLS, FLOORS OR STRUCTURE FOR PIPING OR CONDUIT SHALL BE THE RESPONSIBILITY OF THE SUBCONTRACTOR BY TRADE; FIRESTOPPING OF THESE OPENINGS SHALL BE DONE BY THE RESPECTIVE SUBCONTRACTOR. REMOVAL OF DEBRIS RESULTING FROM DEMOLITION, CUTTING, AND/OR DRILLING IS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR. PATCHING AND REPAIR OF CONCRETE WALLS, FLOOR, OR STRUCTURE SHALL BE THE RESPONSIBILITY OF THE GENERAL CONTRACTOR; THIS WILL BE ACCOMPLISHED UPON COMPLETION OF THE INSTALLATION OF ANY AND ALL UTILITIES INSTALLED
BY THE VARIOUS SUBCONTRACTORS.
Approved: Division Chief
Issue Date Checked Drawn
DrawingNumber
Building Number
Project NumberDrawing Title Project Title
Location Drawing Scale
Approved: Service DirectorPlot Scale U.S. Department of Veterans Affairs
Office of Construction and Facilities Management
FULLY SPRINKLERED
Phase
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
TRUE NORTH
PLAN NORTH
KEYPLAN
A/E:
TRIPLE C - The A/E Group
Mat Perkins
(520) 481-8548
A
B D
EF
G
H
J
K
L
M
C
LINE INDICATES
PHASE 1 SCOPE AREA
B
IM
/6
-2
-1
E x p a n d e d P o ly tr a u m a P ro g ra m P h a s e
/6 -2
-7
.M
P L S
.P O
L Y
T R
A U
M A
.G e n e ra l.
S h e e ts
.r v t
/3
/2
:4
:5
P
M As indicated
04/03/2023 K. Luke N. Harper
618-22-100
1390 - M-802
MECHANICAL CONTROL DIAGRAMS
1 Veterans Drive, Minneapolis, MN 55417
B70
RENOVATE FOR EXPANDED
POLYTRAUMA PROGRAM
ISSUED FOR BIDDING
NTS
F1
SEQUENCE OF OPERATION FOR VARIABLE AIR VOLUME AIR HANDLING UNIT WITH MINIMUM OUTSIDE AIR
NTS
F5
JACKETED STEAM HUMIDIFIER CONTROLS
MERV 8
CONTRO
L PANEL
I
I I
I
I
AHU2-1-01
PI
AHU2-04
TI
AHU2-02
PDI
AHU2-01
TCV
AHU2-03
PA
AHU2-01
HS
AHU2-01
YI
AHU2-01
SC
AHU2-03
FCV
PDT
AHU2-02
FT
AHU2-02
PT
AHU2-1-01
AHU2-01
YA
AHU2-01
TI
AHU2-01
PDI
AHU2-02
SC
AHU2-02
YI
PDT
AHU2-01
TT
AHU2-01
TCV
AHU2-01
FCV
AHU2-02
YS
AHU2-02
TT
AHU2-04
AHU2-02
HS
FCV
AHU2-02
TT
AHU2-02
AHU2-02
FCV
AHU2-02
FCV
YS
AHU2-01
AHU2-02
FI
PS
AHU2-04
PS
AHU2-03
FCV
AHU2-03
IAQ
AHU2-01
AHU2-01
IAQ
AHU2-02
YA
AHU2-02
TI
AHU2-03
PDI
PDT
AHU2-03
FIT
AHU2-01
AHU2-01
FI
AHU2-02
FI
FIT
AHU2-02
AHU2-03
TI
TT
AHU2-03
TT
AHU2-05
AHU2-05
TI
NS
AHU2-01
AHU2-03
TI
AHU2-01
NI
AHU2-02
NI
NS
AHU2-02
CHWS
CHWR
C
C
C
PH
V V
V V
V
V (2 FAN ARRAY)
FLOW STATION
PRE
FILTER
MERV 11
FINAL
FILTER
MERV 16A
FLOW STATION
(AI)S
T
A T
IC
P
R E
S S
U R
E
(AI)S
A
T E
M P
E R
A T
U R
E
(AI)(AO) F
IL
T E
R D
IF
F
P
R E
S S
V A
L V
E S
IG
N
A L
C O
O L
IN
G C
O
IL
P R
E S
S U
R E
A L A
R M
S T
A R
T /S
T O
P
S T
A T
U S
(DI)
(DO) (DI) S
P
E E
D S
IG
N
A L
(AO)
(AO)D
M
P S
IG
N
A L
VFD
S.A S.A
STATIC PRESSURE PROBE
SEE SPECIFICATION
LO HI
(DI)S
M
O K
E D
E T
E C
T O
R
(AI)
(AI)
(AO)
(DI)
(DO)S
T
A R
T /S
T O
P
S T
A T
U S
S P
E E
D S
IG
N
A L
F
IL
T E
R D
IF
F
P
R E
S S
M A
T E
M P
E R
A T
U R
E
S.A
R.A
O.A
POWER
CONTROL
POWER
CONTROL
NC
D M
P S
IG
N
A L
(AO)
D M
P S
IG
N
A L
(AO)(AI)A
IR
V O
L U
M E
NC
CONTROL
POWER
R.A
IA
Q
L E
V E
L
(AI)
S M
O K
E D
E T
E C
T O
R
(DI)
(AI)R
A
T E
M P
E R
A T
U R
E
NEW AIR HANDLING UNIT 70-AH4S-32 CONTROL DIAGRAM
F
IL
T E
R D
IF
F
P
R E
S S
(AI)
AHU2-B
VFD
AHU-2A
R .A
RELIEF AIR
(0-14,600 CFM)
RETURN AIR
NO
(AI)A
IR
F L O
W R
A F
A N
(AI)A
IR
F L O
W S
A F
A N
(AI)M
A
/P R
E H
E A
T T
E M
P E
R A
T U
R E
N.O.
(AI)H
U
M
ID
IF
IE
R T
E M
P E
R A
T U
R E
(AO)H
U
M
ID
IT
Y
S
IG
N A
L
(AI)H
U
M
ID
IT
Y
S
A
(AI)H
U
M
ID
IT
Y
R
A
NOTE:
OUTSIDE AIR FLOW MEASUREMENT SHALL BE PROVIDED BY MEANS OF RUSKIN IAQ DAMPER
ASSEMBLY COMPLETE WITH AIRFLOW STRAIGHTENING VANES, INTEGRAL MEASUREMENT PORTS, 24 VAC
ELECTRONIC MODULATING DAMPER ACTUATOR AND CONTROLLER. REFER TO MECHANICAL
EQ…