Attachment 9 -589A5-21-700_Topeka EHRM_IFB R2 Drawings_Vol 3-2.pdf
PDF 13 MB Posted
- Solicitation number
- 36C77624B0026_1
About this file
This document appears to be Attachment 9 - 589A5-21-700_Topeka EHRM_IFB R2 Drawings_Vol 3-2.pdf related to the federal contract opportunity Solicitation Number 36C77624B0026_1, "Y1DA--589A5-21-700 EHRM INFRASTRUCTURE UPGRADES (VA-24-00076324)" issued by the Department of Veterans Affairs Technology Acquisition Center Austin.
The document contains design drawings for the EHRM (Electronic Health Record Modernization) infrastructure upgrades at the Topeka, Kansas VA facility. It is part of the information package for the Invitation for Bid (IFB) solicitation for this infrastructure upgrade project. The drawings provide detailed schematics and plans for the required electrical, network, and facility upgrades. No additional details on pricing, response dates, or other solicitation requirements are included in this attachment.
View the file
Other files
Show all 49
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
T.O. ROOF DECK
16' - 6 1/2"
T.O COPING (DCA)
19' - 0 5/8"
D
T/O STEEL (DCA)
16' - 0"
PRECAST CONCRETE COPING 1
ROOF ASSEMBLY RA -1
PER ROOF NOTES IN THIS SHEET.
6" METAL STUD FRAMING
1/2" DENSEGLAS (OR VA APPROVED
EQUAL)
TO EDGE OF SLAB; REF. STRUCT.
1' - 6 1/2"
THRU-WALL STAINLESS STEEL FLASHING
ANCHOR BOLT EMBEDED
IN EPOXY; PER SPECS.
SLOPED
STEEL MEMBER; REF. STRUCT.
5/8" GYPSUM BOARD, TYP.
1 1/2" CONTINUOUS RIGID INSULATION
(R-7.5 MIN.)
FULL-DEPTH FACE BRICK MATCHING
EXISTING VA BUILDING BRICK
SPECIFICATIONS
WEATHER BARRIER
3/4" SHEATHING
3 1/2" THICK MINERAL WOOL
INSULATION (R-13 MIN.)
2" AIR GAP
12" STRUCTURAL STEEL STUD WALL FRAMING;
REF, STRUCT. DRAWINGS
EXTEND ROOF MEMBRANE UP AND
OVER PARAPET & DOWN FRONT FACE MIN. 4"
EXTEND VAPOR BARRIER UP
AND OVER SHEATHING AND
DOWN BACK FACE MIN. 4"
CEILING, REF. CEILING PLAN
FINISH FLOOR
0"
D
CONCRETE FLOOR SLAB;
REFER STRUCTURAL
5/8" GYP. BD
1 1/2" CONTINUOUS RIGID
INSULATION (R-7.5 MIN)
FLOORING AND WALL BASE;
REF. FINISH SCHEDULE
THRU-WALL STAINLESS
STEEL FLASHING
FULLY GROUTED CAVITY
1' - 6 1/2" 8"
WEATHER BARRIER
M
IN
. T
YP
6"
T.O. ROOF DECK
16' - 6 1/2"
T.O COPING (DCA)
19' - 0 5/8"
5 6
T/O STEEL (DCA)
16' - 0"
T/O STEEL (LINK)
13' - 0"
STEEL MEMBER; REF. STRUCT.
ROOF ASSEMBLY RA -2
PER ROOF NOTES IN THIS SHEET.
PRECAST CONCRETE COPING (BEYOND)
METAL ROOF DECK; REF. STRUCT.
PRECAST CONCRETE COPING 1
ROOF ASSEMBLY RA -1
PER ROOF NOTES IN THIS SHEET.
1 1/2" CONTINUOUS RIGID INSULATION
(R-7.5 MIN.)
6" METAL STUD FRAMING
ANCHOR BOLT EMBEDED
IN EPOXY; PER SPECS.
SLOPED
THRU-WALL STAINLESS STEEL FLASHING
FULL-DEPTH FACE BRICK MATCHING
EXISTING VA BUILDING BRICK
SPECIFICATIONS
STEEL BRICK LEDGE; REF. STRUCT.
5/8" GYP. BD
THRU-WALL STAINLESS
STEEL FLASHING
1/2" DENSEGLAS (OR VA APPROVED
EQUAL)
EXTEND ROOF MEMBRANE UP AND
OVER PARAPET & DOWN
FRONT FACE MIN. 4"
EXTEND VAPOR BARRIER UP AND
OVER SHEATHING AND DOWN BACK
FACE MIN. 4"
TO EDGE OF SLAB; REF. STRUCT.
1'-6 1/2"
CEILING, REF. CEILING PLAN
STEEL MEMBER; REF. STRUCT.
T/O STEEL (LINK)
13' - 0"
7"
BLDG. JT.
2"
EXISTING WALL
TO REMAIN (BUILDING 21)
ROOF ASSEMBLY RA -2
PER ROOF NOTES IN THIS
SHEET.
PROVIDE 24 GA SURFACE MOUNTED
COUNTERFLASHING IN A BED OF
SEALANT AT EXISTING WALL. TOOL
SEALANT IN PLACE AT TOP OF
COUNTER FLASHING.
2" ALUMINUM ROOF TO WALL
EXPANSION JOINT ASSEMBLY,
MECHANICALLY FASTENED TO
EXISTING WALL AND WITH FULL
BED OF SEALANT
STEEL MEMBER;
REF. STRUCT.
METAL ROOF DECK; REF. STRUCT.
CONTINUOUS WOOD BLOCKING
16" TALL CURB
1'
- 1
0" M
IN
DENSGLASS SHEATHING
CEILING, REF. CEILING PLAN
C.3
T/O STEEL (LINK)
13' - 0"
STEEL MEMBER; REF. STRUCT.
ROOF ASSEMBLY RA -2
PER ROOF NOTES IN THIS
SHEET.
SLOPED
CEILING, REF. CEILING PLAN
STEEL LEDGE; REF. STRUCT.
THRU-WALL METAL
FLASHING
THRU-WALL STAINLESS
STEEL FLASHING
ANCHOR BOLT EMBEDED IN
EPOXY; PER SPECS
3 1/2 THICK MINERAL WOOL INSULATION (R-13 MIN.)
ROOF ASSEMBLY NOTES:
RA-1
TPO ROOFING MEMBRANE OVER 1/4" COVERBOARD, OVER RIGID INSULATION
TAPERED AS REQUIRED TO MEET 1/4" SLOPE, OVER COMPOSITE ROOF DECK PER
STRUCTURAL DRAWINGS.
RA-2
TPO ROOFING MEMBRANE OVER 1/4" COVERBOARD, OVER RIGID INSULATION
TAPERED AS REQUIRED TO MEET 1/4" SLOPE, OVER METAL ROOF DECK PER
STRUCTURAL DRAWINGS.
RETURN BRICK AT OPENINGS, TYP.
1 1/2" CONTINUOUS RIGID INSULATION (R-7.5 MIN.)
1' - 0 1/2"
*REFER BUILDING ELEVATIONS SHEET FOR TYPICAL EXTERIOR WALL ASSEMBLIES.
PRECAST CONCRETE COPING 2
EXTEND ROOF MEMBRANE UP AND OVER
PARAPET & DOWN FRONT FACE MIN. 4"
EXTEND VAPOR BARRIER UP AND OVER
SHEATHING AND DOWN BACK FACE MIN. 4"
PRECAST CONCRETE BAND
MASONARY ANCHOR
PER MANUFACTURER'S RECOMMENDATION
FINISH FLOOR
0"
C.3
CONCRETE FLOOR SLAB;
REF. STRUCT.
6" DEEP ALUMINUM STOREFRONT
SYSTEM. BASIS OF DESIGN: KAWNEER
UT601 FRONT SET SYSETM OR VA
APPROVED EQUAL
1' - 0 1/2"
RETURN BRICK AT
OPENINGS, TYP.
WALKWAY; REF.
CIVIL
SLOPED
12" STRUCTURAL STEEL STUD WALL FRAMING.
REFER TO STRUCTURAL DRAWINGS
1 1/2" CONTINUOUS RIGID INSULATION
(R-7.5 MIN.)
2'
- 8
11'- 4" TO FINISH
FLOOR
PRECAST CONCRETE BAND
3/4" SHEATHING
8" X 6" X 1/2" STEEL ANGLE
MASONARY TIE PROVIDE @ T.O.
PRECAST CONCRETE BAND AND 12" O.C.
FINISH FLOOR
0"
D 3"8"
CONCRETE FLOOR SLAB;
REFER STRUCTURAL
FLOORING AND WALL BASE;
REF. FINISH SCHEDULE
WALKWAY; REF.
CIVIL
EXT. THRESHOLD IN FULL BED
OF SEALANT
EXTERIOR DOOR AND HOLLOW
METAL FRAME (BEYOND)
2' - 2 1/2"
SLOPED
RETURN BRICK AT OPENINGS, TYP.
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
A
B
C
D
E
F
A
B
C
D
E
F
CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Drawing Title
Approved: Project Director
Phase Project Title Project Number
Building Number
Drawing NumberLocation
Issue Date Checked Drawn
VA FORM 08-6231
Bancroft Project No. VA CONTRACT NO.
02-28-24
ARCHITECTURAL - BUILDING 19 - WALL
SECTION DETAILS
EHRM INFRASTRUCTURE
UPGRADES
COLMERY-O'NEIL VA MEDICAL CENTER
589A5-21-700
A-B19-512
ISSUE FOR BID
21-116367C77622C0043
1 1/2" = 1'-0"
DETAIL - TYP. PARAPET
1 1/2" = 1'-0"
DETAIL - TYP. WALL BASE
1 1/2" = 1'-0"
DETAIL - TPO ROOF TRANSITION
1 1/2" = 1'-0"
DETAIL - EXPANSION JOINT
1 1/2" = 1'-0"
DETAIL - PARAPET AT LINK
1 1/2" = 1'-0"
DETAIL - WALL BASE AT LINK
1 1/2" = 1'-0"
DETAIL - PRECAST CONCRETE BAND
1 1/2" = 1'-0"
DETAIL - EXT. HM DOOR THRESHOLD TYP.
0 1' 1 1/2'1/2' 0 1' 1 1/2'1/2' 0 1' 1 1/2'1/2' 0 1' 1 1/2'1/2'
0 1' 1 1/2'1/2' 0 1' 1 1/2'1/2' 0 1' 1 1/2'1/2' 0 1' 1 1/2'1/2'
Revisions: Date:
35% SCHEMATIC DESIGN SUBMISSION 07-12-22
35% SCHEMATIC DESIGN SUBMISSION R1 09-21-22
35% SUBMITTAL II 06-13-23
65% DESIGN DEVELOPMENT SUBMISSION 09-12-23
95% CONSTRUCTION DOCUMENTS SUBMISSION 10-31-23
100% CONSTRUCTION DOCUMENTS SUBMISSION 12-19-23
ISSUED FOR BID 12-28-23
ISSUED FOR BID R1 02-28-24
03/22/2024
ISSUE FOR BID R2 03-22-24
COUNTERFLASHIN
G
FASTENERS AT 6" ON
CENTER
PREFABRICATED METAL CURB
BUILT-UP ROOFING TO MATCH EXISTING
CONTINUOUS
1 1/2" MIN. WELD
ROOF SLAB
RIGID INSULATION TO MATCH
EXISTING
PREMANUFACTURED
MEMBRANE FLASHING
INSTALL SEALANT OR SEALANT TAPE
BETWEEN PIPE AND PREMANUFACTURED
MEMBRANE FLASHING
PLUMBING VENT STACK
DRAWBAND
SEALANT
HOT-AIR-WELDED SEAM
BASE MEMBRANE
ATTACHMENT AS
REQUIRED FOR
SPECIFIC SYSTEM
N O
N -S
H R
IN
KI
N G
G R
O U
T
PE
N
ET
R
AT
IO
N
PE
N
ET
R
AT
IO
N
CONC. ROOF DECKCONC. ROOF DECK
MULTI-PURPOSE MB FLASHING CEMENT
NON-SHRINK GROUT
BASE AND INTERPLY SHEETS
CAP SHEET
4" (152 mm) MIN FLANGE SET IN MULTI-PURPOSE MB
FLASHING CEMENT OVER FIELD PLIES (PRIME FLANGE
BEFORE STRIPPING)
CAP SHEET
INTERPLY SHEET
POURABLE SEALER MIN 2"
COVERAGE AROUND PENETRATIONS
SHEET METAL PITCH PAN,
SOLDERED/WELDED WATERTIGHT
TREATED WOOD BLOCKING FASTENED TO EXTG CONC DECK
PATCH EXTG INSUL AS REQD
COVERBOARD
4" MIN. 3" MIN. 3" MIN.
PIPES OR CONDUITS, 1" DIA AND UNDER
STRAINER BASKET ROOFING MEMBRANE, EXTEND MEMBRANE
UNDER CLAMPING RING
BONDING ADHESIVE
TAPERED INSULATION AT DRAIN
COVER BOARD
DOWNSPOUT, SEE PLUMBING DWG.
ROOF DRAIN W/STRAINER, SEE PLUMBING
DWG.
UNDERDECK CLAMPMANUFACTURER'S DRAIN
RECIEVER
CONCRETE AND METAL DECK
CLAMPING RING
RIGID INSULATION
ROOF DRAIN EXTENSION RING
SEALANT
SEAL EXTERIOR CLOSURE
TO SCUPPER LINER WITH
MANUFACTURER'S
RECOMMENDED SEALANT
SHEET METAL SCUPPER LINER
SOLDERED/WELDED OR
FABRICATED FROM COATED
METAL
SHEET METAL SCUPPER
LINER
SOLDERED/WELDED OR
FABRICATED FROM
MEMBRANE COATED
METAL
3" MIN. FLANGE (TYP.)
4" MIN.
BONDING ADHESIVE
SEALANT WATER BLOCK
BONDING ADHESIVE
2" MIN.
WOOD BLOCKING
SHEET METAL SCUPPER
SECURED TO WALL AND
BLOCKING BELLOW
ADHERE MEMBRANE FLASHING
WITH SEAMS
SEALED PER MANUFACTURER'S
RECOMMENDATIONS
ROOFING MEMBRANE
ROOF CONSTRUCTION
STRUCTURE
STEEL COLUMN AND CAP;
REFER STRUCTURAL
RE
F.
S
TR
UC
T.
4"
RIGID INSULATION
1/
2" M
IN
COVER BOARD
LIGHTNING PROTECTION TERMINAL
SET IN SEALANT
MEMBRANE PROTECTION
PLY HOT-AIR-WELDED OR
ADHERED TO ROOF
MEMBRANE
TERMINAL SUPPORT AT COPING
ATTACH
TERMINAL TO
INSIDE FACE
OF COPING
24 GA PREFINISHED GALVANIZED EDGE METAL
WITH A 3" MIN. FLANGE. FASTENERS 3" O.C.
STAGGERED.
TWO-PLY FLASHING MEMBRANE
GUTTER SPACERS INSTALLED BETWEEN
BRACKETS
24 GA PREFINISHED STEEL GUTTER, 6"
DEEP X 8" WIDE. FRONT OF GUTTER
SHOULD BE 1" LOWER THAN THE
BACK.
INSTALL GUTTER BRACKET SUPPORT 24"
O.C.
ROOF ASSEMBLY RA -2
PER ROOF NOTES IN SHEET A-
B19-512.
SLOPED: 1/4" / 1'-0"
CAST STONE BAND
SELF-ADHERING MEMBRANE FLASHING SEALANT
SEALANT WATER BLOCK
2 X 6 MIN. WOOD NAILER
ATTACHED TO SUBSTRATE
OVERALL THICKNESS TO
MATCH INSULATION
SHEET-METAL GUTTER
THE FRONT OF THE
GUTTER SHOULD BE A MIN. 1'' LOWER THAN THE BACK
TO
ALLOW OVERFLOW. SEE THE ARCHITECTURAL METAL
FLASHING SECTION OF THE NRCA ROOFING MANUAL:
ARCHITECTURAL METAL FLASHING, CONDENSATION AND
AIR LEAKAGE CONTROL, AND REROOFING FOR OTHER
GUTTER SHAPES.
GUTTER BRACKET
SUPPORT
STIFFENING BAR
SHEET-METAL
EDGE FLASHING
GUTTER SPACERS
INSTALLED BETWEEN
GUTTER BRACKETS
BONDING ADHESIVE
FIELD SHEET OR SEPARATE
MEMBRANE SHEET
EXTENDED BELOW BLOCKING
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
A
B
C
D
E
F
A
B
C
D
E
F
CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Drawing Title
Approved: Project Director
Phase Project Title Project Number
Building Number
Drawing NumberLocation
Issue Date Checked Drawn
VA FORM 08-6231
Bancroft Project No. VA CONTRACT NO.
02-28-24
ARCHITECTURAL - BUILDING 19 - ROOF TYP.
DETAILS
EHRM INFRASTRUCTURE
UPGRADES
COLMERY-O'NEIL VA MEDICAL CENTER
589A5-21-700
A-B19-521
ISSUE FOR BID
21-116367C77622C0043
6" = 1'-0"
EQUIPMENT CURB
3" = 1'-0"
DETAIL - SCUPPER FLASHING
3" = 1'-0"
DETAIL - OVERFLOW THROUGH WALL
12" = 1'-0"
TYPICAL ROOF PENETRATION
6" = 1'-0"
BLOCKING/FLASHING AT CONDUIT/PIPE PENETRATIONS UNDER 1" DIA.
3" = 1'-0"
ROOF DRAIN - SECTION
3" = 1'-0"
ENCLOSURE AT TOP OF COLUMN
12" = 1'-0"
TYP. LIGHTING PROTECTION
1 1/2" = 1'-0"
GUTTER DETAIL AT LINK
12" = 1'-0"
GUTTER DETAIL AT LINK
0 1' 1 1/2'1/2'
NTS
NTS
0 6" 9"3" 0 6" 9"3" 0 6" 9"3" 0 6" 9"3"
0 1" 2" 3" 4"
0 1" 2" 3" 4"
NTS
Revisions: Date:
100% CONSTRUCTION DOCUMENTS SUBMISSION 12-19-23
ISSUED FOR BID 12-28-23
ISSUED FOR BID R1 02-28-24
EXISTING BRICK
TO REMAIN (BUILDING 21)
2" WALL EXPANSION JOINT. MATCH COLOR OF
ADJACENT WALL. RUN JOINT UP FRONT
OF WALL AND PARAPET, OVER THE TOP
OF PARAPET, AND DOWN THE BACK SIDE
OF THE PARAPET. PROVIDE WALL
EXPANSION JOINT BASE ENCLOSURE
WHERE JOINT MEETS ROOFING.
DENSEGLASS SHEATHING
PREFINISHED METAL
COUNTERFLASHING
AND REGLET
MECHANICALLY FASTEN FLASHING TO EXISTING CONCRETE
WALL PANEL AND EXPANSION JOINT COVER. PROVIDE BUTYL
TAPE BETWEEN EXISTING CONCRETE WALL PANEL AND
FLASHING. FLASHING TO HAVE 1/2" HEMMED EDGE (MINIMUM).
PROVIDE FULL BED OF SEALANT AND PERIMETER SEALANT.
PREFINISHED METAL
FLASHING
PREFINISHED ROOF EXPANSION JOINT COVER
PROVIDE TWO ROWS OF SEALANT TO PREVENT WATER
INTRUSION WHILE ALLOWING EXPANSION JOINT
MOVEMENT.
WEATHER BARRIER
ROOFING MEMBRANE
WEATHER BARRIER
1 1/2" CONTINUOUS RIGID
INSULATION (R-7.5 MIN.)
EX
P.
JT
2"
CAST STONE BAND
EXISTING BRICK
TO REMAIN (BUILDING 21)
MECHANICALLY FASTEN FLASHING TO EXISTING WALL.
PROVIDE BUTYL TAPE BETWEEN EXISTING WALL AND
FLASHING. FLASING TO HAVE 1/2" HEMMED EDGE (MINIMUM).
PROVIDE SEALANT AROUND PERIMETER OF FLASHING.
THRU-WALL STAINLESS
STEEL FLASHING
ANCHOR BOLT EMBEDED IN
EPOXY; PER SPECS
PRECAST CONCRETE COPING
WEATHER BARRIER
ROOFING MEMBRANE
PROVIDE AN INTERLOCKING
SLIP JOINT BETWEEN THE
COPING AND THE FLASHING.
PREFABRICATED METAL
COPING SADDLE FLASHING
2" WALL EXPANSION JOINT. MATCH EXISTING TYPE AND COLOR OF
ADJACENT WALL. RUN JOINT UP FRONT OF WALL AND PARAPET, OVER
THE TOP OF PARAPET, AND DOWN THE BACK SIDE OF THE PARAPET.
PROVIDE WALL EXPANSION JOINT BASE ENCLOSURE WHERE JOINT
MEETS ROOFING.
EXP. JT.
2"
SLOPED
A-B19-522
A-B19-522
2"2"
1/
2"
1/ 2"
PREFABRICATED METAL COPING
SADDLE FLASHING
PREFABRICATED METAL COPING
PREFINISHED METAL FLASHING
PREFINISHED METAL COUNTERFLASHING
AND REGLET
ROOFING MEMBRANE
CAST STONE COPING
CAST STONE BAND
FRAME WITH CAPFLASHING
(CORNERS FULL WELDED)
LOCK STRIKE AND
PADLOCK HASP
GASKET
(ALL AROUND COVER)
SLAM LATCH
COVER LINER
NEOPRENE GASKET
INSIDE AND OUTSIDE HANDLES WITH
PADLOCK HASPS
COVER
1" THICK FIBERGLASS
COVER INSULATION
ARM GUIDE
BRACKET
RED VINYL GRIP
HOLD OPEN
ARM
PINTLE HINGE
LIFTING MECHANISM WITH
REINFORCED COMPOSITE TUBES
AND COMPRESSION SPRINGS
1" RIGID FIBERBOARD INSULATION
FLASHING SYSTEM
PRECAST CONCRETE
DECK/SLAB
TAPERED POLYISOCYANURATE
INSULATION
STEEL LADDER NOT INDICATED FOR DRAWING
CLARITY. STEEL LADDER TO BE INSTALLED AT LOCK
HASP SIDE.
PROVIDE WOOD BLOCKING ANCHORED INTO
CONCRETE DECK/SLAB.
VERIFY FINAL HEIGHT OF
WOOD BLOCKING WITH HEIGHT
OF TAPERED INSULATION
SYSTEM HEIGHT/ELEVATION.
NOTE: PROVIDE A FIXED RAILING SYSTEM ATTACHED TO ROOF SCUTTLE
FRAME. RAILS AND MOUNTING BRACKETS WILL BE ALUMINUM MATERIAL
WITH STAINLESS STEEL HARDWARE, SELF-CLOSING AND LOCKING
GATE. PROVIDE YELLOW POWDER COAT PAINT FINISH ON RAILS. MEETS
OR EXCEEDS OSHA 29 CFR 1910.23.
3' - 0"
2' - 6"
OVERALL
3' - 1"
FRAME OPENING LENGTH
2' - 6"
O
VE
RA
LL
3'
- 7
FR
AM
E O
PE
NI
NG
W
ID
TH
3'
- 0
1'
- 2
" M
AX
1'
- 0
6' -0
" M
AX
FLOOR LINE
4" X 7" X 1/4" X 4" LONG
ANGLE BRACKET MIN. 4
PER LADDER
3/4" BAR STOCK
KNURLED RUNGS (TYP.)
1/2" X 2-1/2" BAR STOCK
(TYP.)
6" -1
2"
FRAME OPENING
NOTE: PRIME LADDERS AND
PAINT WITH ONE COAT
ALKYD ENAMEL (TYP.)
ACCESS HATCH
PROVIDE CONTINUOUS 16 GA. METAL STUD BOX COLUMN @
BRACKET LOCATIONS FOR ATTACHMENT.
NOTE:
PROVIDE STEEL LADDER
SAFETY POST @ HATCH
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
A
B
C
D
E
F
A
B
C
D
E
F
CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Drawing Title
Approved: Project Director
Phase Project Title Project Number
Building Number
Drawing NumberLocation
Issue Date Checked Drawn
VA FORM 08-6231
Bancroft Project No. VA CONTRACT NO.
02-28-24
ARCHITECTURAL - BUILDING 19 - ROOF
DETAILS
EHRM INFRASTRUCTURE
UPGRADES
COLMERY-O'NEIL VA MEDICAL CENTER
589A5-21-700
A-B19-522
ISSUE FOR BID
21-116367C77622C0043
3" = 1'-0"
PLAN DETAIL AT PARAPET - LINK TO BUILDING 21
3" = 1'-0"
SECTION DETAIL AT PARAPET - LINK TO BUILDING 21
3" = 1'-0"
SECTION DETAIL - PARAPET TERMINATION
1 1/2" = 1'-0"
SECTION AT ROOF HATCH
0 6" 9"3" 0 6" 9"3" 0 6" 9"3"
0 1' 1 1/2'1/2'
Revisions: Date:
100% CONSTRUCTION DOCUMENTS SUBMISSION 12-19-23
ISSUED FOR BID 12-28-23
ISSUED FOR BID R1 02-28-24
1 1/2" = 1'-0"
ACCESS LADDER DETAIL
FACE OF WALL OR VERTICAL
CONSTRUCTION
ACOUSTICAL CEILING TILE
STANDARD WALL ANGLE.
COLOR TO MATCH TEE.
FINISH FLOOR
0"
3"
BLDG. JT.
2"
- 1
/2
2" FLOOR EXPANSION JOINT - BASIS OF
DESIGN: INPRO 733-A01-050. TOP OF JOINT
TO ALIGN WITH TOP OF FINISHED FLOOR
MATERIAL.
2" WALL EXPANSION JOINT
(BEYOND) - BASIS OF DESIGN: INPRO
811-A07-050.
INTERIOR DOOR AND HOLLOW METAL
FRAME.
SCHEDULED WALL BASE BEYOND,
REFER FINISH PLANS AND
SCHEDULE.
EXISTING CONCRETE FLOOR
AND STRUCTURE (BLDG. 21)
SCHEDULED FLOORING, REFER
FINISH PLANS AND SCHEDULE.
PROVIDE TAPERED FLOOR
LEVELING AS REQUIRED TO
PROVIDE A SMOOTH TRANSITION
BETWEEN FLOORING MATERIALS.
MODIFY EDGE OF EXISTING CONCRETE SLAB
AS REQUIRED TO INSTALL EXPANSION JOINT.
CORNER GUARD
7"
EXISTING FLOORING TO
REMAIN.
B.9
6" DEEP ALUMINUM STOREFRONT
SYSTEM. BASIS OF DESIGN: KAWNEER
UT601 FRONT SET SYSETM OR VA
APPROVED EQUAL
3 1/2 THICK MINERAL WOOL
INSULATION (R-13 MIN.)
WEATHER BARRIER
1 1/2" CONTINUOUS RIGID INSULATION
(R-7.5 MIN.)
3/4" SHEATHING
STEEL MEMBER; REF. STRUCT.
1' - 0 1/2"
B.9
STEEL MEMBER; REF. STRUCT.
EXISTING WALL
TO REMAIN (BUILDING 21)
EXISTING BRICK
TO REMAIN (BUILDING 21)
2" WALL EXPANSION JOINT. MATCH COLOR OF
ADJACENT WALL. RUN JOINT UP FRONT
OF WALL AND PARAPET, OVER THE TOP
OF PARAPET, AND DOWN THE BACK SIDE
OF THE PARAPET. PROVIDE WALL
EXPANSION JOINT BASE ENCLOSURE
WHERE JOINT MEETS ROOFING.
6" DEEP ALUMINUM STOREFRONT
SYSTEM. BASIS OF DESIGN: KAWNEER
UT601 FRONT SET SYSETM OR VA
APPROVED EQUAL
5/8" GYPSUM BOARD, TYP.
1' - 0 1/2"
BL
DG
. J T.
2" 7"
1/
2"
3/
4"
2" FLOOR EXPANSION JOINT -
BASIS OF DESIGN: INPRO 733-A01-050.
TOP OF JOINT TO ALIGN WITH TOP
OF FINISHED FLOOR MATERIAL.
2" WALL EXPANSION
JOINT - BASIS OF DESIGN:
INPRO 811-A07-050.
A-B19-541
INTERIOR DOOR AND
HOLLOW METAL
FRAME.
3 1/2 THICK MINERAL WOOL
INSULATION (R-13 MIN.)
ANCHOR BOLT EMBEDED
IN EPOXY; PER SPECS.
CAP STRIP
FLOORING
COVE FORM
VERTICAL WALL
STUDS AT 16" ON
CENTER
CUT HORIZONTAL
FASTENER FROM
STUD. CONTRACTOR
TO COORDINATE
LOCATIONS.
FASTEN AT BOTH
ENDS WITH MIN.
4 TAPPING
SCREWS.
WALL FINISH
PLAN
ISOMET
RIC
METAL STUDS (20 GA.) AT
16" O.C.- TYP.
CONT. 8" HIGH (16 GA.)
STEEL BLOCKING PLATE,
ANCHOR TO STUDS / 2
SELF TAPING FLAT HEAD
SCREWS PER STUD
PROVIDE 8" HIGH X 48" LONG X 16 GAUGE CONTINUOUS
BACK-UP BLOCKING PLATES SECURELY ANCHORED WITH
FLAT HEAD SCREWS OVER METAL STUDS BEHIND ALL
TOILET
ACCESSORIES, BASE CABINETS, WALL CABINETS,
MILLWORK,
SHELVING, VISUAL DISPLAY BOARDS, WALL/ HANDRAIL (NEW
WALLS) AND ALL OTHER SURFACE MOUNTED ITEMS.
NOTE:
IF WOOD BLOCKING USED,
PROVIDE 1/2" MINIMUM
FIRE-RATED PLYWOOD.
ELEVATION
PLAN PARTITION PER PLAN
BRACKET SURFACE
MOUNTED FIRE
EXTINGUISHER CABINET
" A
FF
1/8" REVEAL
ELEVATION
PLAN
PARTIALLY RECESSED MET FIRE
EXTINGUISHER CAB, COORDINATE
OPENING SIZE & DEPTH
W/ MANUFACTURER
5/8" GYP BD
1-1/2"x1-1/2"x20ga MET ANGLE
@ ALL (4) SIDES OF RATED PARTITION
TYPE OPENING, ATTACH TO MET STUDS
W/ #8 SELF-TAP SM SCREWS @ 12"OC
" A
FF
1/
2"
1/8" 1/8"
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
A
B
C
D
E
F
A
B
C
D
E
F
CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Drawing Title
Approved: Project Director
Phase Project Title Project Number
Building Number
Drawing NumberLocation
Issue Date Checked Drawn
VA FORM 08-6231
Bancroft Project No. VA CONTRACT NO.
02-28-24
ARCHITECTURAL - BUILDING 19 - INTERIOR
DETAILS
EHRM INFRASTRUCTURE
UPGRADES
COLMERY-O'NEIL VA MEDICAL CENTER
589A5-21-700
A-B19-541
ISSUE FOR BID
21-116367C77622C0043
3" = 1'-0"
ACT CEILING AT WALL
3" = 1'-0"
DETAIL - FLOOR TRANSITION AT BLDG. 21
1 1/2" = 1'-0"
PLAN DETAIL - DCA TO LINK
1 1/2" = 1'-0"
PLAN DETAIL - LINK TO BLDG. 21
6" = 1'-0"
INTEGRATED COVE BASE
1/2" = 1'-0"
ANCHORAGE DETAIL
1 1/2" = 1'-0"
BACKING PLATE DETAIL
1 1/2" = 1'-0"
FEC SURFACE MOUNTED TYP.
1 1/2" = 1'-0"
FEC PARTIALLY RECESSED TYP.
0 1' 1 1/2'1/2' 0 1' 1 1/2'1/2' 0 6" 9"3"
0 1" 2" 3" 4"
0 1" 2" 3" 4"
NTS NTS NTS NTS
Revisions: Date:
35% SCHEMATIC DESIGN SUBMISSION 07-12-22
95% CONSTRUCTION DOCUMENTS SUBMISSION 10-31-23
100% CONSTRUCTION DOCUMENTS SUBMISSION 12-19-23
ISSUED FOR BID 12-28-23
ISSUED FOR BID R1 02-28-24
BUILDING 19 - DOOR AND FRAME TYPE ELEVATIONS
SE
E
DO
O
R
SC
HE
DU
LE
SEE DOOR SCHEDULE
FRAME TYPE 1
SE
E
DO
O
R
SC
HE
DU
LE
DOOR TYPE A
SEE DOOR SCHEDULE
DOOR TYPE B
SEE DOOR SCHEDULE
SE
E
DO
O
R
SC
HE
DU
LE
DOOR TYPE C
SEE DOOR SCHEDULE
SE
E
DO
O
R
SC
HE
DU
LE
3' - 6" 1' - 6"EQ EQ
2" 2"2"
SE
E
DO
O
R
SC
HE
DU
LE
SEE DOOR SCHEDULE
FRAME TYPE 2
2" 2"4"
DOOR TYPE D
SEE DOOR SCHEDULE
SE
E
DO
O
R
SC
HE
DU
LE
1 15/16" 1 9/16"
/8
1/2" 1/2"
SEE PARTITION TYPE
VARIES
SEALANT AT BOTH SIDES
HOLLOW METAL
FRAME
(2) 3 5/8" X 20 GA STUDS
VARIES
/1
/1
5/8"2"
/2
/2
S E
E P
A R
T
IT
IO
N
T Y
P E
V A
R
IE
S
FACE OF PERPENDICULAR
PARTITION
SEALANT AT BOTH SIDES
JAMB ANCHORS. (3) ANCHORS
PER JAMB
HOLLOW METAL
FRAME
RETURN FRAME. TYP.
DOUBLE STUDS BACK TO
BACK
V A
R
IE
S
18" MIN.
CONTINUOUS BACKER ROD AND
SEALANT AT EACH SIDE
5/ 8"
4" 1 15/16"1 15/16"
8" 3"
HM FRAME AND DOOR
STEEL MEMBER; REF. STRUCT.
THRU-WALL STAINLESS STEEL FLASHING
WEATHER BARRIER
RETURN BRICK AT OPENINGS TYP.
3/4" SHEATHING
3 1/2" THICK MINERAL WOOL INSULATION
(R-13 MIN.)
1 1/2" CONTINUOUS RIGID INSULATION
(R-7.5 MIN.)
5/8" GYP. BD
CONTINUOUS BACKER ROD AND
SEALANT AT EACH SIDE
5/8"2"
/1 6"
/1 6"
8"
HM FRAME AND DOOR
RETURN BRICK AT OPENINGS TYP.
5/8" GYP. BD
WEATHER BARRIER
3/4" SHEATHING
3 1/2" THICK MINERAL WOOL INSULATION
(R-13 MIN.)
1 1/2" CONTINUOUS RIGID INSULATION
(R-7.5 MIN.)
FULL-DEPTH FACE BRICK MATCHING
EXISTING VA BUILDING BRICK
SPECIFICATIONS
BL
DG
. J T.
2"
2" WALL EXPANSION JOINT - BASIS
OF DESIGN: INPRO 811-A07-050.
INTERIOR DOOR AND HOLLOW
METAL FRAME.
ANCHOR BOLT EMBEDED
IN EPOXY; PER SPECS.
2" FLOOR EXPANSION JOINT (BEYOND) -
BASIS OF DESIGN: INPRO 733-A01-050.
TOP OF JOINT TO ALIGN WITH TOP
OF FINISHED FLOOR MATERIAL.
CONTINUOUS SEALANT AT
EACH SIDE
MODIFY EDGE OF EXISTING WALL AS
REQUIRED TO INSTALL NEW
HOLLOW METAL FRAME.
5/8" GYP. BD
/1 6"
9/
3/
4"
2" 5/8"
BLDG. JT.
2"
2" WALL / CEILING EXPANSION
JOINT - BASIS OF DESIGN:
INPRO 811-A07-050.
INTERIOR DOOR AND HOLLOW
METAL FRAME.
ANCHOR BOLT EMBEDED
IN EPOXY; PER SPECS.
CONTINUOUS SEALANT AT
EACH SIDE
MODIFY EDGE OF EXISTING WALL
AS REQUIRED TO INSTALL NEW
HOLLOW METAL FRAME.
1 15/16" 1 9/16"
5 3/4"
5/8" GYP. BD
2" 5/
8"
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
A
B
C
D
E
F
A
B
C
D
E
F
CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Drawing Title
Approved: Project Director
Phase Project Title Project Number
Building Number
Drawing NumberLocation
Issue Date Checked Drawn
VA FORM 08-6231
Bancroft Project No. VA CONTRACT NO.
02-28-24
ARCHITECTURAL - BUILDING 19 - DOOR
SCHEDULE AND DETAILS
EHRM INFRASTRUCTURE
UPGRADES
COLMERY-O'NEIL VA MEDICAL CENTER
589A5-21-700
A-B19-601
ISSUE FOR BID
21-116367C77622C0043
3" = 1'-0"
TYPICAL HEADER AT STUD WALL
3" = 1'-0"
TYPICAL JAMB AT STUD WALL
BUILDING 19 - EXTERIOR DOOR SCHEDULE
FROM ROOM TO ROOM
DOOR FRAME
FIRE RATING
LABEL HARDWARE SET NOTESTAG
SIZE
MATERIAL FINISH DOOR TYPE GLAZING MATERIAL FRAME TYPE
DETAILS
WIDTH HEIGHT THICKNESS HEAD JAMB SILL
CORRIDOR XA1-01 3' - 0" 8' - 0" 1 3/4" HM PAINT A HM 2 3 / A-B19-601 4 / A-B19-601 # 2
MECHANICAL XA101 6' - 0" 8' - 0" 1 3/4" HM PAINT B HM 2 3 / A-B19-601 4 / A-B19-601 # 2
CORRIDOR XA1-02 6' - 0" 8' - 0" 1 3/4" HM PAINT B HM 2 3 / A-B19-601 4 / A-B19-601 # 2
CORRIDOR (LINK) XB1-01 3' - 4" 7' - 2" 1 3/4" D
ELECTRICAL ROOM XA108 6' - 0" 8' - 0" 1 3/4" HM PAINT B HM 2 3 / A-B19-601 4 / A-B19-601 # 2
XB1-02 6' - 0" 9' - 0" 2" 30
XB1-07 6' - 0" 9' - 0" 2" 30
3" = 1'-0"
HEAD AT EXT. BRICK WALL
3" = 1'-0"
JAMB AT EXT. BRICK WALL
3" = 1'-0"
HM JAMB AT EXISTING WALL
3" = 1'-0"
HM HEAD AT EXISTING WALL
ALUM ANOD IG-1 ALUM PER SYSTEM PER SYSTEM PER SYSTEM BASIS OF DESIGN:PER SYSTEM PER SYSTEM
BUILDING 19 - INTERIOR DOOR SCHEDULE
FROM ROOM TO ROOM
DOOR FRAME
FIRE RATING
LABEL
HARDWARE
SET NOTESTAG
SIZE
MATERIAL FINISH DOOR TYPE GLAZING MATERIAL FRAME TYPE
DETAILS
WIDTH HEIGHT THICKNESS HEAD JAMB SILL
CORRIDOR CORRIDOR (LINK) A1-01A 6' - 0" 7' - 0" 1 3/4" HM PAINT B HM 1 6 / A-B19-601 5 / A-B19-601 # 2
CORRIDOR ENTRANCE ROOM B A105 3' - 0" 8' - 0" 1 3/4" HM PAINT A HM 1 1 / A-B19-601 2 / A-B19-601
BREAKDOWN
ROOM
CORRIDOR A104 6' - 0" 8' - 0" 1 3/4" HM PAINT B HM 1 1 / A-B19-601 2 / A-B19-601
WORK ROOM IT EQUIPMENT
STORAGE
A106A 6' - 0" 8' - 0" 1 3/4" HM PAINT B HM 1 1 / A-B19-601 2 / A-B19-601
CORRIDOR MECHANICAL A101A 3' - 0" 8' - 0" 1 3/4" HM PAINT A HM 1 1 / A-B19-601 2 / A-B19-601
CORRIDOR ELECTRICAL ROOM A108 3' - 0" 8' - 0" 1 3/4" HM PAINT A HM 1 1 / A-B19-601 2 / A-B19-601 90 MIN.
CORRIDOR ENTRANCE ROOM A A109 3' - 0" 8' - 0" 1 3/4" HM PAINT A HM 1 1 / A-B19-601 2 / A-B19-601
MCR CORRIDOR A107A 6' - 0" 8' - 0" 1 3/4" HM PAINT B HM 1 1 / A-B19-601 2 / A-B19-601 45 MIN.
MCR CORRIDOR A107B 6' - 0" 8' - 0" 1 3/4" HM PAINT B HM 1 1 / A-B19-601 2 / A-B19-601 45 MIN.
CORRIDOR A101B 3' - 0" 8' - 0" 1 3/4" HM PAINT A HM 1 1 / A-B19-601 2 / A-B19-601
TOILET CORRIDOR A102 3' - 0" 8' - 0" 1 3/4" HM PAINT A HM 1 1 / A-B19-601 2 / A-B19-601
CORRIDOR HAC A103 3' - 0" 8' - 0" 1 3/4" HM PAINT A HM 1 1 / A-B19-601 2 / A-B19-601
CORRIDOR (LINK) A1-01B 6' - 0" 7' - 0" 1 3/4" HM PAINT B HM 1 3 / A-B19-601 3 / A-B19-601
WORK ROOM CORRIDOR A106 5' - 0" 8' - 0" 1 3/4" PAINT C 1 / A-B19-601 2 / A-B19-601
BUILDING 19 - DOOR SCHEDULE LEGEND AND NOTES
A. CONTRACTOR SHALL REVIEW HARDWARE SETS WITH VA COR PRIOR TO ORDERING.
B. SEE SPECIFICATIONS (DIVISION 09 OPENINGS) FOR DOOR AND FRAMES.
C. SEE SPECIFICATION SECTION 08 71 00 FOR HARDWARE SETS.
D. SEE SPECIFICATION SECTION 08 80 00 FOR GLAZING TYPES.
E. ALL WOOD DOORS ARE SOLID CORE.
F. FOR DOOR SCHEDULE, TYPES AND DETAILS ON BUILDING 19, SEE SHEET A-B19-601. FOR THE
REST OF THE DOOR SCHEDULE, TYPES AND DETAILS, SEE SHEET A-601.
GENERAL NOTES NOTES LEGEND
1. KNOCK-DOWN DOOR FRAME WITH HOSPITAL STOPS.
2. REFER TO SPECIFICATION 08 56 53 FOR BLAST REQUIREMENTS.
3. FULLY WELDED FRAME.
4. WOOD DOOR - EACH LOCATION - SPECIES, CUT AND STAIN COLOR TO MATCH EXISTING ADJACENT DOORS.
5. KNOCK-DOWN DOOR FRAME WITH STANDARD STOPS.
HM HOLLOW METAL
WD WOOD
ALUM ALUMINUM
IG INSULATED GLASS
ANOD CLEAR ANODIZED
T TEMPERED
HM HM 1
0 6" 9"3" 0 6" 9"3"
0 6" 9"3" 0 6" 9"3"
0 6" 9"3" 0 6" 9"3"
Revisions: Date:
65% DESIGN DEVELOPMENT SUBMISSION 09-12-23
95% CONSTRUCTION DOCUMENTS SUBMISSION 10-31-23
100% CONSTRUCTION DOCUMENTS SUBMISSION 12-19-23
ISSUED FOR BID 12-28-23
ISSUED FOR BID R1 02-28-24
7 7/16"
FIRE RESISTIVE
SAFETY GLAZING
1" CLEAR SRIL
(SEMI-RIGID
INTUMESCENT LAYER) TPS
POLYSULFIDE
/2
FIRE RESISTIVE
SAFETY GLAZING
1" CLEAR SRIL
(SEMI-RIGID
INTUMESCENT LAYER)
TPS
POLYSULFIDE
/4
/1
FIRE RESISTIVE
SAFETY GLAZING
1" CLEAR SRIL
(SEMI-RIGID INTUMESCENT LAYER)
TPS
2 1/2" POLYSULFIDE
/4
/1
/1
/1
5/8"2"
/2
/2
S E
E P
A R
T
IT
IO
N
T Y
P E
V A
R
IE
S
SEALANT AT BOTH
SIDES
JAMB ANCHORS. (3) ANCHORS
PER JAMB.
HOLLOW METAL FRAME
RETURN FRAME. TYP.
DOUBLE STUDS BACK TO
BACK
V A
R
IE
S
GLAZING
REMOVABLE GLASS STOP
/8
4 1/4"
/4
/2
A
IG-1 IG-1 IG-1
IG-1IG-1IG-1
IG-1 IG-1 IG-1
2" 3' - 4" 2" 3' - 4" 2" 3' - 4" 2"
4" 3'
- 8
2" 3'
- 4
2" 3'
- 4
4"
10' - 8"
4"
B
IG-1 IG-1 IG-1
IG-1 IG-1
IG-1IG-1
IG-1
2" 3' - 4" 2" 3' - 4" 2" 3' - 4" 2"
4" 3'
- 8
2" 3'
- 4
2" 3'
- 4
4"
7'
- 2
10' - 8"
4"
C
2 1/2"
1/
2" 3'
- 7
1/
2"
5 EQUAL SPACES
4'
- 0
FR-1 FR-1 FR-1 FR-1 FR-1
21' - 9"
A-B19-611
A-B19-611
A-B19-611
SEALANT AND BACKER ROD
MINERAL WOOL
SEALANT AND BACKER ROD
SEALANT AND BACKER ROD
MINERAL WOOL
SEALANT AND BACKER ROD
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
A
B
C
D
E
F
A
B
C
D
E
F
CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Drawing Title
Approved: Project Director
Phase Project Title Project Number
Building Number
Drawing NumberLocation
Issue Date Checked Drawn
VA FORM 08-6231
Bancroft Project No. VA CONTRACT NO.
02-28-24
ARCHITECTURAL - BUILDING 19 - WINDOW
SCHEDULE, DETAILS
EHRM INFRASTRUCTURE
UPGRADES
COLMERY-O'NEIL VA MEDICAL CENTER
Checker Author
589A5-21-700
A-B19-611
ISSUE FOR BID
21-116367C77622C0043
3" = 1'-0"
TYPICAL JAMB/SILL AT BORROWED LITE
1 1/2" = 1'-0"
CURTAIN WALL DETAIL
0 1' 1 1/2'1/2'
0 1' 1 1/2'1/2'
GLAZING TYPES
FR-1 CLEAR FIRE-RATED LAMINATED GLASS
IG-1 CLEAR INSULATED LAMINATED GLASS
Revisions: Date:
100% CONSTRUCTION DOCUMENTS SUBMISSION 12-19-23
ISSUED FOR BID 12-28-23
ISSUED FOR BID R1 02-28-24
6" = 1'-0"
FIRE LAMINATED GLASS - SILL DETAIL
6" = 1'-0"
FIRE LAMINATED GLASS - JAMB DETAIL
6" = 1'-0"
FIRE LAMINATED GLASS - MULLION DETAIL
CLEAR FIRE LAMINATED GLASS PREFROMANCE SPECIFICATIONS:
A. Performance Requirements: Provide a fire rated glazing manufactured, fabricated and installed to maintain performance criteria stated by manufacturer without defects, damage, or failure.
1. Fire Rating: 120 minutes with hose stream.
2. Fire resistive, safety rated glazing tested in accordance with ASTM E119, ANSI/UL 263.
3. Testing Laboratory: Fire test shall be conducted by a nationally recognized independent testing laboratory.
B. Design Requirements:
1. Glass Make-up: Comprised of multiple lites of [clear tempered] with clear, fire resistive, intumescent interlayers in between.
2. Fire Rating: Must be fire rated to 120 minutes with hose stream and meet
ASTM E-119, ANSI/UL263, ULC CAN4-S101
C. Manufacturer’s Fire Rated Glazing Material:
1. Each piece of fire-rated glazing material shall be labeled with a permanent logo including name of product, manufacturer, testing laboratory, fire rating period and safety glazing standards.
CORRIDOR
A1-01
TOILET
A102
HAC
A103
CORRIDOR
(LINK)
B1-01
FIRE WATER
RISER ROOM
A110
MCR SUPPR.
TANKS
A111
MECHANICAL
A101
MCR
A107
CORRIDOR
A1-02
ENTRANCE
ROOM A
A109
ELECTRICAL
ROOM
A108
WORK ROOM
A106
ENTRANCE
ROOM B
A105
BREAKDOWN
ROOM
A104
IT EQUIPMENT
STORAGE
A106A
TS-1
TS-1
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
A
B
C
D
E
F
A
B
C
D
E
F
CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Drawing Title
Approved: Project Director
Phase Project Title Project Number
Building Number
Drawing NumberLocation
Issue Date Checked Drawn
VA FORM 08-6231
Bancroft Project No. VA CONTRACT NO.
02-28-24
ARCHITECTURAL - BUILDING 19 - FINISH AND
SIGNAGE PLAN, FINISH, SIGNAGE AND
EQUIPMENT SCHEDULES
EHRM INFRASTRUCTURE
UPGRADES
COLMERY-O'NEIL VA MEDICAL CENTER
Checker Author
589A5-21-700
AF-B19-611
ISSUE FOR BID
21-116367C77622C0043
ROOM FINISH SCHEDULE
ROOM
NO. ROOM NAME
FLOOR BASE WALLS CEILING
REMARKS
FLOOR
MATERIAL
FLOOR
COLOR
BASE
MATERIAL
BASE
COLOR
NORTH WEST SOUTH EAST
TYPE HEIGHTMATERIAL FINISH COLOR MATERIAL FINISH COLOR MATERIAL FINISH COLOR MATERIAL FINISH COLOR
A109 ENTRANCE ROOM A SDT SDT-1 VB VB-1 GYPSUM BD. PAINT P-1 GYPSUM BD. PAINT P-1 GYPSUM BD. PAINT P-1 GYPSUM BD. PAINT P-1 OPEN TO
STRUCTURE
N/A
A105 ENTRANCE ROOM B SDT SDT-1 VB VB-1 GYPSUM BD. PAINT P-1 GYPSUM BD. PAINT P-1 GYPSUM BD. PAINT P-1 GYPSUM BD. PAINT P-1 OPEN TO
STRUCTURE
N/A
A107 MCR SDT SDT-1 VB VB-1 GYPSUM BD. PAINT P-1 GYPSUM BD. PAINT P-1 GYPSUM BD. PAINT P-1 GYPSUM BD. PAINT P-1 OPEN TO
STRUCTURE
N/A
A103 HAC SC VB VB-1 GYPSUM BD. PAINT/CERA
MIC TILE
P-1 GYPSUM BD. PAINT P-1 GYPSUM BD. PAINT P-1 GYPSUM BD. PAINT/CERA
MIC TILE
P-1 OPEN TO
STRUCTURE
N/A
A102 TOILET SC VB VB-1 GYPSUM BD. PAINT/CERA
MIC TILE
P-1 GYPSUM BD. PAINT/CERA
MIC TILE
P-1 GYPSUM BD. PAINT/CERA
MIC TILE
P-1 GYPSUM BD. PAINT/CERA
MIC TILE
P-1 ACT-1 10' - 0"
A106A IT EQUIPMENT STORAGE SDT SDT-1 VB VB-1 GYPSUM BD. PAINT P-1 GYPSUM BD. PAINT P-1 GYPSUM BD. PAINT P-1 GYPSUM BD. PAINT P-1 OPEN TO
STRUCTURE
N/A
A104 BREAKDOWN ROOM SDT SDT-1 VB VB-1 GYPSUM BD. PAINT P-1 GYPSUM BD. PAINT P-1 GYPSUM BD. PAINT P-1 GYPSUM BD. PAINT P-1 OPEN TO
STRUCTURE
N/A
A106 WORK ROOM SDT SDT-1 VB VB-1 GYPSUM BD. PAINT P-1 GYPSUM BD. PAINT P-1 GYPSUM BD. PAINT P-1 GYPSUM BD. PAINT P-1 ACT-1 10' - 0"
A108 ELECTRICAL ROOM SC VB VB-1 GYPSUM BD. PAINT P-1 GYPSUM BD. PAINT P-1 GYPSUM BD. PAINT P-1 GYPSUM BD. PAINT P-1 OPEN TO
STRUCTURE
N/A
A101 MECHANICAL SC VB VB-1 GYPSUM BD. PAINT P-1 GYPSUM BD. PAINT P-1 GYPSUM BD. PAINT P-1 GYPSUM BD. PAINT P-1 OPEN TO
STRUCTURE
N/A
A111 MCR SUPPR. TANKS SC VB VB-1 GYPSUM BD. PAINT P-1 GYPSUM BD. PAINT P-1 GYPSUM BD. PAINT P-1 GYPSUM BD. PAINT P-1 OPEN TO
STRUCTURE
N/A
A110 FIRE WATER RISER ROOM SC VB VB-1 GYPSUM BD. PAINT P-1 GYPSUM BD. PAINT P-1 GYPSUM BD. PAINT P-1 GYPSUM BD. PAINT P-1 OPEN TO
STRUCTURE
N/A
A1-02 CORRIDOR SDT SDT-1 VB VB-1 GYPSUM BD. PAINT P-1 GYPSUM BD. PAINT P-1 GYPSUM BD. PAINT P-1 GYPSUM BD. PAINT P-1 ACT-1 10' - 0"
A1-01 CORRIDOR SDT SDT-1 VB VB-1 GYPSUM BD. PAINT P-1 GYPSUM BD. PAINT P-1 GYPSUM BD. PAINT P-1 GYPSUM BD. PAINT P-1 ACT-1 10' - 0"
B1-01 CORRIDOR (LINK) SC SDT-1 VB VB-1 GYPSUM BD. PAINT P-1 GYPSUM BD. PAINT P-1 GYPSUM BD. PAINT P-1 GYPSUM BD. PAINT P-1 ACT-1 11' - 4"
N 1/8" = 1'-0"1
BUILDING 19 - FINISH/SIGNAGE PLAN - DATA CENTER
EQUIPMENT SCHEDULE
EQ.NUMBER DESCRIPTION QTY
PROVIDED
BY MOUNTING DETAIL COMMENTS
A102
TOILET
A1066 Mirror, Float Glass, With Stainless Steel Frame 1 CFCI
A5075 Dispenser, Soap 1 VFVI
A5090 Disposal, Sanitary Napkin, SS, Surface Mounted 1 CFCI
A5200 Dispenser, Toilet tissue, SS, 2-Roll, Surface Mntd 1 CFCI
F2010 Basket, Wastepaper, Stepon 1 VFVI
A103
HAC
A5135 Utility Shelf, Mop/Broom Holders, Surface Mounted 1 CFCI
NOTE: REFER SHEET AF-601 (VOL. 1) FOR ROOM FINISH LEGEND
SIGNAGE SCHEDULE
TAG SIGN TYPE
ROOM
NUMBER
TEXT QTY REMARKS
01 TYPE B A100 Data Center 1
02 TYPE A A101 - 1
03 TYPE D A102 - 1
04 TYPE A A103 - 1
05 TYPE B A107 MCR 1
06 TYPE B A104 Breakdown Room 1
07 TYPE B A106 Work Room 1
08 TYPE B A105 Entrance Room B 1
09 TYPE A A106A - 1
10 TYPE A A101 - 1
11 TYPE B A109 Entrance Room A 1
12 TYPE A A108 - 1
13 TYPE B A107 MCR 1
0 4' 8' 16'
Revisions: Date:
65% DESIGN DEVELOPMENT SUBMISSION 09-12-23
95% CONSTRUCTION DOCUMENTS SUBMISSION 10-31-23
100% CONSTRUCTION DOCUMENTS SUBMISSION 12-19-23
ISSUED FOR BID 12-28-23
ISSUED FOR BID R1 02-28-24
DN
BUILDING 19
BUILDING 21
CONNECTING CORRIDOR
BUILDING 24
(NEW CONSTRUCTION)
(EXISTING)
(EXISTING)
(EXISTING)
ASP9
ASP7
ASP8
ASP1
TYP.
ASP12
GENERATOR PAD
(EXISTING)
TRANSFORMER PAD
(NEW)
ASP6
ASP12
ASP1
ASP1
AS-B19-501
ASP13
ASP16
ASP11
ASP10
ASP17
ASP18
ASP17
ASP17
TYP.
ASP12
8'
- 0
12' - 9" 5' - 0" 13' - 10 7/8"
8'
- 8
/4
6' - 0"
5' - 0"
3/
4"
5'
- 0
1'
- 0
5' - 0"
5'
- 0
8'
- 0
4' - 11"
3' - 0" 4' - 11" 8' - 0" 2' - 6"
27' - 9 3/4"
10' - 3" 2' - 10"
9' - 10"
5'
- 8
2'
- 6
10' - 10"4'
- 6
1'
- 6
2'
- 1
0"
7'
- 4
/2
3'
- 0
3' - 6"
3' - 0"
22' - 1" 5' - 0"
5' - 11 1/4"
9' - 11 1/4"
21' - 7 5/8"
3/ 4"
1'
- 0
CLEAR OPENING FOR GATE
16' - 0"
4' - 3"
10' - 10"10' - 10" 7' - 2"
3'
- 0
EQ
EQ
EQ
EQ
16' - 1"
4'
9"
V.I.F.
+/- 8' - 10"
V.
I.F
- 3
5"
ASP20
ASP20
ASP9
2' - 5"5' - 0" 12' - 6"
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
A
B
C
D
E
F
A
B
C
D
E
F
CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Drawing Title
Approved: Project Director
Phase Project Title Project Number
Building Number
Drawing NumberLocation
Issue Date Checked Drawn
VA FORM 08-6231
Bancroft Project No. VA CONTRACT NO.
02-28-24
ARCHITECTURAL - BUILDING 19 - SITE PLAN EHRM INFRASTRUCTURE
UPGRADES
COLMERY-O'NEIL VA MEDICAL CENTER
Checker Author
589A5-21-700
AS-B19-101
ISSUE FOR BID
21-116367C77622C0043
1. REFER TO SHEET A-B19-002 FOR GENERAL SHEET NOTES AND LEGENDS.
GENERAL SHEET NOTES
N 3/32" = 1'-0"1
ARCHITECTURAL - SITE PLAN
SITE PLAN KEYNOTES
ASP1 MINERAL MULCH (DECOMPOSED GRANITE), REFER SPECIFICATIONS.
ASP6 EXISTING LANDSCAPE TO REMAIN.
ASP7 GRASSCRETE DRIVE, REFER DETAIL 4/AS-B19-501.
ASP8 EXISTING SIDEWALK, REFER TO CIVIL FOR EXTENT OF WORK.
ASP9 SECURITY ACCESS GATE. BASIS OF DESIGN: DURAGATE DGT-BS
SUPER DUTY STEEL BARRIER W/OPEN POSITION LOCK POST
INCLUDED. (16 FT. LONG KIT), INSTALL PER MANUFACTURER'S
RECOMMENDATIONS, POSTS ON CONCRETE PIERS 14" DIA. AND 36"
DEEP ON 6" OF GRANULAR FILL.
ASP10 EXISTING GENERATOR PAD TO REMAIN.
ASP11 TRANSFORMER PAD, ENCLOSURE AND ACCESS GATE. REFER CIVIL
AND ELECTRICAL DRAWINGS.
ASP12 EQUIPMENT PADS. REFER STRUCTURAL AND MECHANICAL FOR
ADDITIONAL INFORMATION.
ASP13 EXISTING CHAIN LINK FENCE TO REMAIN AS SHOWN.
ASP16 CHAIN LINK, REFER 5/AS-B19-501.
ASP17 CONCRETE SIDEWALK, REFER CIVIL DRAWINGS C-B19-C601.
ASP18 CONCRETE LANDING AND STEP, REFER CIVIL DRAWINGS C-B19-C601.
ASP20 6" CONCRETE CURB. REFER CIVIL DRAWINGS C-B19-C300 FOR
ADDITIONAL INFORMATION.
Revisions: Date:
35% SCHEMATIC DESIGN SUBMISSION 07-12-22
35% SCHEMATIC DESIGN SUBMISSION R1 09-21-22
35% SUBMITTAL II 06-13-23
65% DESIGN DEVELOPMENT SUBMISSION 09-12-23
95% CONSTRUCTION DOCUMENTS SUBMISSION 10-31-23
100% CONSTRUCTION DOCUMENTS SUBMISSION 12-19-23
ISSUED FOR BID R1 02-28-24
0 16' 24'8'
TROWEL
MARGIN
CONSULT THE TECHNICAL BULLETIN FOR
INFORMATION ON REQUIRED REINFORCEMENT.
2" - 6" MIN GRANULAR
SUB-BASE 3
4" MIN. DIA.
AGGREGATE
1" CLEAN ASTM C-33 SAND
8" AGGREGATE
CONCRETE
STANDARD EDGE DETAIL
EXPANSION JOINT AT MAX. 50 FT.
CENTERS TO BE BITUMEN
IMPREGNATED FIBER BOARD
1/ 2"
8"
3/
4"
CROSS SECTION OF BASE
COMPACTED SUBGRADE
1-1/2" METAL PIPE
RAILING W/ HANDRAILS
GRANULAR FILL
1 1/2"
REINFORCED CONCRETE, SEE CIVIL
DRAWINGS C-B19-C601 FOR ADDITIONAL
INFORMATION
CONCRETE STAIRS, SEE
CIVIL FOR ADDITIONAL
INFORMATION
3/4" METAL PIPE PICKETS
6" 4"
3' -0
" 3'
6"
7' - 10"
2"
8"
4"
1' - 0"
1'
- 0
3'
- 0
3'
- 0
6" 4"
COMPACTED SUBGRADE
GRANULAR FILL
CONCRETE STAIRS, SEE CIVIL DRAWINGS C-B19-C601
FOR ADDITIONAL INFORMATION
EXPANSION JOINT AND
SEALANT
1" NOSING
METAL
RAILING
4" 4"
4"
6"
6"
4"
1' - 0" 1' - 0"
CONCRETE STAIR
1/2" 1/2" 1 1/2"
6"
CORE DRILL HOLE,
FILL GAP W/ NON-
SHRINK GROUT
1-1/2" STAINLESS
STEEL POST
CL
GROUT AND SHIM
SPACE
WELD POST TO
BASEPLATE
3-3/4" X 3-3/4" X
1/4" SQUARE PL.
1"
CONTINUOUS BEAD OF SEALANT
AT ALL SIDES OF PLATE
NEW CHAINLINK FENCE WITH PRIVACY SCREENING
TO MATCH EXISTING IN HEIGHT COLOR AND DESIGN.
CONCRETE PIERS 14" DIA. AND 36" DEEP ON 6" OF
GRANULAR FILL .SPACING TO MATCH EXISTING.
POST TO HAVE MOUNTING PLATES AND MOUNT TO
CONCRETE FOUR (4) 1/2" X 3" CONCRETE ANCHORS.
EXISTING CHAINLINK FENCE
TWO (2) 3'-0" WIDE ACCESS DOORS WITH CHAIN
LINK AND PRIVACY SCREENING TO MATCH
EXISTING.
- 1
8'
- 9
/2
NEW TRANSFORMER PAD, REFER CIVIL AND
ELECTRICAL
EXISTING GENERATOR PAD TO REMAIN
V.
I.F
- 4
0"
0" 4'
- 0
V.I.F.
+/- 30' - 0"
V.I.F.
+/- 4' - 0"
V.I.F.
+/- 4' - 0"
11' - 7"
9'
- 6
TWO (2) 3'-0" WIDE ACCESS DOORS WITH CHAIN
LINK AND PRIVACY SCREENING TO MATCH
EXISTING. ALIGN WITH TRANSFOMER LOCATION
TO ALLOW FOR OPERATION & MAITANCE .
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
A
B
C
D
E
F
A
B
C
D
E
F
CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Drawing Title
Approved: Project Director
Phase Project Title Project Number
Building Number
Drawing NumberLocation
Issue Date Checked Drawn
VA FORM 08-6231
Bancroft Project No. VA CONTRACT NO.
02-28-24
ARCHITECTURAL - BUILDING 19 - TYPICAL
SITE DETAILS
EHRM INFRASTRUCTURE
UPGRADES
COLMERY-O'NEIL VA MEDICAL CENTER
Checker Author
589A5-21-700
AS-B19-501
ISSUE FOR BID
21-116367C77622C0043
3/4" = 1'-0"
SECTION AT STAIRS
3/4" = 1'-0"
SECTION AT STAIRS
0 2' 3'1' 0 2' 3'1' 3" = 1'-0"
POST SLEEVE DETAIL
0 6" 9"3"
1/64" = 1'-0"
DETAIL - PARTIALLY CONCEALED GRASSCRETE SYSTEM
NTS
1. REFER TO SHEET A-B19-002 FOR GENERAL SHEET NOTES AND LEGENDS.
GENERAL SHEET NOTES
Revisions: Date:
100% CONSTRUCTION DOCUMENTS SUBMISSION 12-19-23
ISSUED FOR BID 12-28-23
ISSUED FOR BID R1 02-28-24
N 1/4" = 1'-0"5
BUILDING 19 - ENLARGED PLAN - SECURITY FENCE
0 2' 4' 8'
03/22/2024
FENCE
GENERAL NOTES FOR CONTRACTORS: SEE ALL PROJECT GENERAL NOTES AND OTHER REQUIREMENTS INCLUDING THE LIFE SAFETY AND INFECTION CONTROL WORK LOCATED WITHIN THE GENERAL DRAWINGS SECTION. COMPLY WITH ALL REQUIREMENTS AS THEY ARE A DIRECT PART OF THIS SECTION AS IF THEY WERE DIRECTLY INCLUDED AND PROVIDED
HEREIN.
EQUIVALENCY SUBSTITUTIONS: THE “BASIS OF DESIGN (BOD) COMPLIANCE PROTOCOLS” ARE TO BE FOLLOWED FOR ALL MATERIALS, EQUIPMENT, ASSEMBLIES AND SYSTEMS SPECIFIED AND DETAILED THROUGHOUT ALL DRAWINGS AND SPECIFICATION SECTIONS, WHETHER THE BOD DESIGNATE IS SPECIFICALLY REFERENCED THEREIN OR NOT. SEE THE GENERAL DRAWINGS SECTION FOR THE SPECIFIC BOD COMPLIANCE REQUIREMENTS AND PROTOCOLS TO BE FOLLOWED.
1. THIS CONTRACTOR SHALL REVIEW ENTIRE SET OF CONTRACT DOCUMENTS: INCLUDING BUT NOT NECESSARILY LIMITED TO ARCHITECTURAL, STRUCTURAL, MECHANICAL, PLUMBING, FIRE PROTECTION, ELECTRICAL DRAWIINGS AND ENTIRE PROJECT MANUAL. THIS CONTRACTOR SHALL ACKNOWLEDGE AND INCLUDE IN THE SCOPE OF WORK (CONTRACT) ALL CONDITIONS PERTINENT TO THE COMPLETION OF THEIR WORK. THE CONTRACTOR SHALL FULLY COORDINATE THEIR WORK WITH THE INSTALLATION OF THEIR WORK WITH THE INSTALLATION OF WORK BY OTHER TRADES AND MAKE NECESSARY FIELD ADJUSTMENTS AS REQUIRED TO ACCOMMODATE THE INSTALLATION. ALL OF THE ABOVE SHALL BE
INCLUDED IN THE SCOPE OF WORK AT NO ADDITIONAL CHARGE TO THE VA/GOVERNMENT.
2. THIS CONTRACTOR SHALL CAREFULLY EXAMINE THE DRAWINGS AND SPECIFICATIONS, VISIT THE SITE OF THE WORK AND FULLY INFORM THEMSELVES AS TO ALL CONDITIONS AND MATTERS THAT CAN, IN ANY WAY, AFFECT THE WORK OR THE COST THEREOF. SHOULD THIS CONTRACTOR FIND DISCREPANCIES IN, OR OMISSIONS FROM THE DRAWINGS, SPECIFICATIONS OR OTHER DOCUMENTS, OR BE IN DOUBT AS TO THEIR MEANING, NOTIFY THE VA/CO AT ONCE, IN WRITING, OF ANY DISCREPANCIES BETWEEN EXISTING CONDITIONS AND NEW WORK, OR BETWEEN THEIR WORK AND THE WORK OF OTHER TRADES AND OBTAIN CLARIFICATION PRIOR TO SUBMITTING ANY BID. LACK OF SUCH NOTIFICATION SHALL BE CONSTRUED AS TO INDICATE NO DISCREPANCIES OR CONFLICTING CONDITIONS EXIST.
3. THE DRAWINGS INDICATE DIAGRAMMATICALLY THE INTENT, GENERAL CHARACTER, REQUIREMENTS AND LOCATION OF THE WORK SHOWN AND INCLUDED. THE WORK INDICATED BUT HAVING MINOR DETAILS OBVIOUSLY OMITTED SHALL BE
PROVIDED AT NO ADDITIONAL COST TO THE VA/GOVERNMENT.
4. THIS CONTRACTOR IS REQUIRED TO BID, AS SPECIFIED, ON THE DRAWINGS WITHOUT DEVIATION FROM THE BOD.
5. IT IS THE INTENT OF THESE DOCUMENTS THAT THE FIRE PROTECTION CONTRACTOR PROVIDE ALL LABOR, MATERIAL, EQUIPMENT AND TOOLS FOR THE COMPLETE INSTALLATION OF ALL WORK SHOWN ON THE PLANS AND/OR DESCRIBED HEREIN, INCLUDING ALL DEVICES, CONTROLS AND APPURTENANCES REQUIRED TO SET NEW SYSTEMS INTO
OPERATION.
6. SHOULD CONDITIONS NECESSITATE ANY REARRANGEMENTS, OR IF PIPING CAN BE RUN TO BETTER ADVANTAGE, PREPARE AND SUBMIT SHOP DRAWINGS SHOWING THE CHANGES BEFORE PROCEEDING WITH THE WORK. IF SUCH CHANGES ARE APPROVED BY THE VA/COR AND SUCCESSFULLY REVIEWED BY THE ARCHITECT, THEY SHALL BECOME A
PART OF THE CONTRACT.
7. THIS CONTRACTOR SHALL VERIFY ALL MOUNTING, ALL ARRANGEMENTS, HEIGHTS AND LOCATIONS PRIOR TO ROUGH-IN.
ANY MENTION OF A SPECIFIC MOUNTING ARRANGEMENT, WEIGHT OR LOCATION SHALL NOT RELIEVE THE CONTRACTOR OF THE RESPONSIBILITY TO VERIFY THE SPECIFIC REQUIREMENT FURNISHED OR THE OTHER TRADES WORKING IN THE SAME AREA. NO ADDITIONS TO THE CONTRACT SUM WILL BE PERMITTED FOR ITEMS INSTALLED IN WRONG LOCATIONS, IN CONFLICT WITH OTHER WORK, ETC.
8. ALL WORK SHALL BE DONE IN ACCORDANCE WITH ALL CURRENT FEDERAL BUILDING CODES, REGULATIONS, AND REQUIREMENTS, LOCAL UTILITY COMPANY REQUIREMENTS, NFPA, IPC, AND ASHRAE STANDARDS. ALL COMPONENTS
SHALL BE UL LISTED AND FM APPROVED.
9. NOT USED.
10. THIS CONTRACTOR SHALL BE LICENSED, BONDED, INSURED AND CAPABLE OF PERFORMING QUALITY WORKMANSHIP.
THIS CONTRACTOR GUARANTEES ALL OF HIS WORK AND MATERIALS FOR THE PERIOD OF ONE YEAR. FROM FINAL
ACCEPTANCE BY THE VA/GOVERNMENT.
11. THIS CONTRACTOR SHALL ESTABLISH SAFE WORKING PROCEDURES FOR THE PROTECTION OF THE WORKMEN IN ALL PHASES OF WORK, COMPLYING WITH ALL APPLICABLE PROVISIONS OF CITY, STATE, AND FEDERAL SAFETY LAWS (OSHA) AND AS RECOMMENDED IN THE "MANUAL OF ACCIDENT PREVENTION IN CONSTRUCTION" AS ISSUED BY THE ASSOCIATION OF GENERAL CONTRACTORS OF AMERICA, IN., 20TH AND E. STREETS, N.W. WASHINGTON, D.C.
12. THIS CONTRACTOR IS RESPONSIBLE FOR SCHEDULING THE PURCHASE, DELIVERY, RECEIVING, UNLOADING, UNCRATING, STORING, SETTING IN PLACE, AND PROTECTING ALL NEW EQUIPMENT FURNISHED BY THIS CONTRACTOR AND EQUIPMENT FURNISHED BY VA/GOVERNMENT FROM DAMAGE BY VANDALISM AND WEATHER DURING
CONSTRUCTION.
13. THIS CONTRACTOR SHALL PROVIDE A COMPETENT OPERATING TECHNICIAN TO INSTRUCT THE VA/GOVERNMENT IN THE
OPERATION AND MAINTENANCE OF THE NEW EQUIPMENT.
14. UPON COMPLETION OF THE WORK, THIS CONTRACTOR SHALL REVIEW AND CHECK THE ENTIRE PORTION OF WORK, CLEAN EQUIPMENT AND DEVICES. REMOVE SURPLUS MATERIALS AND RUBBISH FROM THE PROPERTY AND LEAVE THE WORK IN NEAT AND CLEAN ORDER AND IN COMPLETE WORKING CONDITION. EACH RESPECTIVE CONTRACTOR SHALL BE RESPONSIBLE FOR THE REMOVAL OF ANY CARTONS, DEBRIS, EQUIPMENT, ETC., INSTALLED BY THIS CONTRACTOR INCLUDING EQUIPMENT FURNISHED BY OTHERS AND UNPACKED OR REMOVED FROM CARTONS BY THIS CONTRACTOR.
15. THIS CONTRACTOR SHALL FURNISH AND INSTALL ALL STRUCTURAL STEEL MEMBERS, SLEEVES, AND SHIMS REQUIRED
TO LEVEL AND SUPPORT EQUIPMENT AND PIPES.
16. BEFORE PLACING WATER SYSTEM IN OPERATION, CHLORINATE ENTIRE SYSTEM IN ACCORDANCE WITH THE REQUIREMENTS OF THE SPECIFICATIONS AND IN CONJUNCTION WITH ALL LOCAL, STATE AND FEDERAL PLUMBING
CODES, SUPPLY CERTIFICATE.
17. EXISTING SERVICE VALVES AT ALL BRANCH SUPPLY PIPING SHALL REMAIN AS IS. SUCH SERVICE VALVES SHALL BE AS
PER THE SPECIFICATIONS AND/OR IN KEEPING WITH THE FACILITY STANDARDS.
18. SPRINKLER HEADS SHALL BE LOCATED IN CEILING GRID IN A SYMMETRICAL PATTERN, COORDINATED WITH OTHER DEVICES MOUNTED IN OR ON THE CEILING. PROVIDE ADDITIONAL SPRINKLER HEADS REQUIRED TO ACHIEVE
SYMMETRY. LOCATE SPRINKLER HEADS IN THE CENTER OF CEILING TILES.
19. SPRINKLER CONTRACTOR SHALL PROVIDE A COORDINATED REFLECTED CEILING PLAN AS PART OF THE SUBMITTAL TO THE VA/COR SHOWING SPRINKLER HEAD LOCATIONS COORDINATED WITH CEILING AND ALL OBJECTS MOUNTED IN OR
ON THE CEILING.
20. THE SPRINKLER CONTRACTOR SHALL BE A LICENSED, AUTHORIZED INSTALLER OF COMMERCIAL SPRINKLER SYSTEM AND SHALL HAVE HAD A MINIMUM OF THREE (3) YEARS OF EXPERIENCE IN THE INSTALLATION OF SPRINKLER SYSTEMS.
FIRE PROTECTION GENERAL NOTES FIRE PROTECTION GENERAL NOTES
21. THE CONTRACTOR IS RESPONSIBLE FOR THE COMPLETE DESIGN OF THE SPRINKLER SYSTEM AND TO SUBMIT HYDRAULIC CALCULATIONS PER NFPA 13 IN SUBMITTAL OF SHOP DRAWINGS AND FOR THE COMPLETE DESIGN OF THE SPRINKLER
SYSTEM. THE SPRINKLER SYSTEM SHALL BE:
A. A DESIGNED SYSTEM IN ACCORDANCE WITH NFPA 13, 2022 AND SPECIFICATION.
B. DESIGNED TO CONFORM WITH BUILDING STRUCTURAL, MECHANICAL, AND ELECTRICAL SYSTEM, AS
INDICATED AND DESCRIBED ON THE CONTRACT DOCUMENTS.
C. ACCEPTABLE TO THE FIRE MARSHAL AND OR ALL LOCAL AUTHORITIES HAVING JURISDICTION.
22. THE SPECIFICATIONS, THE CONTRACTOR SHALL SUBMIT FOR APPROVAL TO THE AUTHORITIES HAVING JURISDICTION, FULLY COORDINATED SHOP DRAWINGS OF SPRINKLER HEADS, HANGERS AND SUPPORTS. DESIGN PLAN SHALL BE PREPARED AND SIGNED/SEALED BY A REGISTERED FIRE PROTECTION ENGINEER IN ACCORDANCE WITH UCF
REQUIREMENT OR BY A NICET LEVEL III/IV TECHNICIAN.
23. THE SPRINKLER SYSTEM SHALL BE INSPECTED AND TESTED IN ACCORDANCE WITH THE REQUIREMENTS OF THE NATIONAL
FIRE PROTECTION CODE, AND ALL LOCAL AUTHORITIES HAVING JURISDICTION.
24. THE CONTRACTOR SHALL ARRANGE FOR INSPECTION AND TEST OF ANY OR ALL PARTS OF THE WORK AS REQUIRED BY
AUTHORITIES HAVING JURISDICTION AND PAY ALL CHARGES FOR SAME.
25. ARCHITECT/ENGINEER SHALL BE RESPONSIBLE FOR OBTAINING ACCURATE FLOW TEST DATA OR PERFORMING AN
UPDATED FLOW TEST AS PER NFPA 13 AND NFPA 25.
26. AREA SHALL BE DESIGNED IN ACCORDANCE WITH THE REQUIREMENT FOR OCCUPANCY PER NFPA 13.
27. THE AUTOMATIC WET FIRE SPRINKLER SYSTEM SHALL BE INSTALLED IN SUCH A MANNER TO PREVENT THE SYSTEM PIPING
OR SPRINKLER HEAD EXPOSURE TO TEMPERATURES LESS THAN 40 DEGREES F.
28. PAINT NEW SPRINKLER PIPING RED AND LABEL PER NFPA 13.
29. CONTRACTOR SHALL PROVIDE COORDINATED PIPE SLEEVE DRAWINGS SHOWING ALL PENETRATIONS THROUGH FLOORS.
30. NOT USED.
31. ALL FIRE PROTECTION VALVES SHALL BE "ELECTRICALLY" SUPERVISED.
32. CONTRACTOR SHALL PROVIDED COORDINATED PIPE SLEEVE DRAWINGS SHOWING ALL PENETRATIONS THROUGH
FLOORS.
33. INSTALLER QUALIFICATIONS: CONTRACTOR'S RESPONSIBILITY SHALL INCLUDE DESIGNING, FABRICATING AND INSTALLING FIRE-SUPPRESSION SYSTEMS AND PROVIDING PROFESSIONAL ENGINEERING SERVICES OR THE SERVICES OF A NICET LEVEL III/IV TECHNICIAN AS NEEDED TO ASSUME ENGINEERING RESPONSIBILITY. CALCULATIONS BASED ON RESULTS OF
THE FIRE-HYDRANT FLOW TEST(S) THEY PERFORM.
A. ENGINEERING RESPONSIBILITY: PREPARATION OF WORKING PLANS, CALCULATIONS, AND FIELD TEST
REPORTS BY A QUALIFIED PROFESSIONAL FIRE PROTECTION ENGINEER.
34. WELDING: QUALIFY PROCESSES AND OPERATORS ACCORDING TO ASME BOILER AND PRESSURE VESSEL CODE, SECTION
IX.
35. NFPA STANDARDS: FIRE SUPPRESSION SYSTEM EQUIPMENT, SPECIALTIES, ACCESSORIES, INSTALLATION AND TESTING
SHALL COMPLY WITH THE FOLLOWING:
• NFPA 13, 2022 INSTALLATION OF SPRINKLER SYSTEMS.
• NFPA 101, 2021 LIFE SAFETY CODE.
• NFPA 72 , 2022 FIRE ALARM CODE.
36. FIRE-SUPPRESSION SPRINKLER SYSTEM DESIGN SHALL BE APPROVED BY AUTHORITIES HAVING JURISDICTION.
A. MARGIN OF SAFETY FOR AVAILABLE WATER FLOW AND PRESSURE: 10 PERCENT, INCLUDING LOSSES
THROUGH WATER-SERVICE PIPING, VALVES, AND BACKFLOW PREVENTERS.
37. CONTRACTOR SHALL SUBMIT FOR REVIEW TO THE VA/COR A COMPLETE LIST OF ITEMS TO BE FURNISHED AND INSTALLED
UNDER THIS CONTRACT. INCLUDING, BUT NOT BE LIMITED TO THE FOLLOWING:
A. DIMENSIONED SHOP DRAWINGS OF MATERIALS AND FIXTURES. DIMENSIONED SHOP DRAWINGS OF
EQUIPMENT AND PIPING PLAN LAYOUT(S).
38. REQUIRED ITEMS TO BE SUBMITTED SHALL INCLUDE, BUT NOT BE LIMITED TO THE FOLLOWING:
A. PRODUCT DATA.
B. APPROVED SPRINKLER PIPING DRAWINGS: WORKING PLANS, PREPARED ACCORDING TO NFPA, AND HAVE
BEEN APPROVED BY AUTHORITIES HAVING JURISDICTION, INCLUDING HYDRAULIC CALCULATIONS.
C. FIELD QUALITY-CONTROL TEST REPORTS.
D. FIELD TEST CERTIFICATES.
E. OPERATION AND MAINTENANCE DATA.
39. SEISMIC PERFORMANCE: FIRE-SUPPRESSION PIPING SHALL BE CAPABLE OF WITHSTANDING THE EFFECTS OF EARTHQUAKE MOTIONS DETERMINED ACCORDING TO NFPA 13 AND APPLICABLE CODE REQUIREMENTS. ASCE 7, VA 11-18-8.
REFER TO ARCHITECTURAL DESIGN FOR SEISMIC HAZARD LEVEL CLASSIFICATIONS.
40. CONTRACTOR SHALL SUBMIT FOR REVIEW TO THE VA/COR A COMPLETE LIST OF ITEMS TO BE FURNISHED AND INSTALLED
UNDER THIS CONTRACT. INCLUDING, BUT NOT BE LIMITED TO THE FOLLOWING:
A. DIMENSIONED SHOP DRAWINGS OF MATERIALS, FIXTURES AND EQUIPMENT.
B. DIMENSIONED SHOP DRAWINGS OF EQUIPMENT AND PIPING PLAN LAYOUT(S).
41. FLEXIBLE CONNECTORS:
A. FLEXIBLE CONNECTORS SHALL HAVE MATERIALS SUITABLE FOR SYSTEM FLUID. INCLUDE 175 PSIG MINIMUM
WORKING-PRESSURE RATING AND ENDS ACCORDING TO THE FOLLOWING:
a. NPS 2 AND SMALLER: THREADED.
b. NPS 2-1/2 AND LARGER: GROOVED FOR USE WITH GROOVED-END PIPE COUPLINGS.
B. STAINLESS-STEEL-HOSE/STEEL PIPE, FLEXIBLE CONNECTORS: CORRUGATED, STAINLESS-STEEL, INNER TUBING COVERED WITH STAINLESS-STEEL WIRE BRAID. INCLUDE STEEL NIPPLES OR FLANGES, WELDED TO
HOSE.
C. STAINLESS-STEEL-HOSE/STAINLESS-STEEL PIPE, FLEXIBLE CONNECTORS: CORRUGATED STAINLESS-STEEL, INNER TUBING COVERED WITH STAINLESS-STEEL WIRE BRAID. INCLUDE STAINLESS-STEEL NIPPLES OR
FLANGES, WELDED TO HOSE.
D. ALL CONNECTIONS AND FLEXIBLE HOSES SHALL BE FM APPROVED.
FIRE PROTECTION GENERAL NOTES
42. EXISTING FIRE SPRINKLER PROTECTION SYSTEM:
A. THE EXISTING FIRE SPRINKLER SYSTS SHALL BE OPERATIONAL THROUGHOUT THE PROJECT.
B. THE SYSTEM MAY ONLY BE NON-OPERATIONAL FOR SCHEDULED SHUTDOWNS. THIS SHALL NOT EXCEED 16 HOURS
WITHIN A 24 HOUR PERIOD.
C. THE CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING A FIRE WATCH IF THE SYSTEM IS OUT OF SERVICE FOR
MORE THAN 4 HOURS IN AN OCCUPPIED BULDING. THIS WILL REQUIRE DEDICATED PERSONNEL TO PERFORM THE
FIRE WATCH WITH NO OTHER TAKS PERFORMED.
D. VA/COR TO COORDINATE, A FIRE PROTECTION CONTRACTOR REQUESTED SHUTDOWN WITH APPROPRIATE VA SHOP PERSONNEL. CONTRACTOR WILL SUBMIT A WRITTEN NOTIFICATION 72 HOURS PRIOR TO SHUTDOWN TO THE VA/COR
AND RECIEVE AN AUTHORIZATION APPROVAL RESPONSE FROM THE VA/COR FOR THE SHUTDOWN.
E. INSTALL TEMPORARY UPRIGHT SPRINKLERS IN ROOMS/AREAS WHERE THE CEILING SYSTEM IS BEING REMOVED FOR
MORE THAN A WORK SHIFT AT A TIME.
FIRE PROTECTION SPRINKLER SYSTEM DESIGN CRITERIA
HAZARD
CLASSIFICATION
SPACE TYPE
DISCHARGE
DENSITY
REMOTE
AREA
MAXIMUM
COVERAGE
AREA PER
SPRINKLER
MAXIMUM
SPACING
WATER
SUPPLY
DURATION
OUTSIDE
HOSE
ALLOWANCE TEMPERATURE
CLASSIFICATION
SPRINKLER
DESCRIPTION
NOTES
GPM/FT² FT² FT² FT. MINUTES GPM
LIGHT HAZARD
GENERAL,
EXCEPT AS LISTED
BELOW
0.10 1,500 225 15 30 100 ORDINARY 1
ORDINARY
HAZARD GROUP 1
ELECTRICAL
ROOMS 0.15 1,500 130 15 60-90 250 INTERMEDIATE
ORDINARY
HAZARD GROUP 2
STORAGE 0.20 1,500 130 15 60-90 250 ORDINARY
NOTES:
1. WATER DEMAND REQUIREMENTS ARE FOR HYDRAULIC CALCULATION METHOD. IF OTHER METHOD IS USED ADJUST VALUES ACCORDING TO NFPA 13 REQUIREMENTS.
HAZARD
SYMBOL
HOUSEKEEPING
CLOSET
0.15 1,500 130 15 60-90 250 ORDINARY
N/A NOT IN SCOPE N/A N/A N/A N/A N/A N/A N/A N/A
SYSTEM
TYPE
REMARKS
N/A
SEMI-RECESSED
PENDENT, QUICK
RESPONSE, UL LISTED
N/AN/A
GENERATOR
ROOM
0.20 1,500 130 15 60-90 250 INTERMEDIATE
MCR 0.10 1,500 225 15 30 100 ORDINARY
WET PIPE
WET PIPE
INTERGER
SYSTEM
WET PIPE
WET PIPE
WET PIPE
WET PIPE
SEMI-RECESSED
PENDENT, QUICK
RESPONSE, UL LISTED
STANDARD
UPRIGHT
PENDENT OR UPRIGHT,
QUICK RESPONSE,
UL LISTED
SEMI-RECESSED
PENDENT OR UPRIGHT,
QUICK RESPONSE,
UL LISTED
SEMI-RECESSED
PENDENT OR UPRIGHT,
QUICK RESPONSE,
UL LISTED
SYMBOL DESCRIPTION
CHECK VALVE
CONTROL PANEL
FLOW SWITCH
PRESSURE GAUGE
INSPECTOR TEST
SIGHT GLASS
UNION
SCOPE OF WORK BOUNDARY
FIRE SPRINKLER PIPINGSP
STANDPIPE SYSTEM PIPINGSS
WALL MOUNTED FIRE DEPARTMENT…