Addendum1_Vol1_20241209.pdf

PDF 6 MB Posted

Attached to
Y1DA--589A5-21-700 EHRM INFRASTRUCTURE UPGRADES (VA-24-00076324) Topeka, KS
Solicitation number
36C77624B0026_1
Issued by

About this file

This is a set of architectural drawings and details for EHRM Infrastructure Upgrades at the Colmery O'Neil VA Health Care facility in Topeka, KS. The drawings show floor plans, ceiling plans, partition details, door schedules, and signage specifications across multiple buildings including Buildings 1-6 and Building 40.

The drawings detail renovation work including ceiling demolition and installation of new mechanical, electrical, conduit and technology infrastructure. Key requirements include temporary plastic barriers during ceiling work, infection control measures, fire-rated assemblies, and coordination with VA staff for after-hours work. Specific details are provided for wall types, door frames, floor transitions, and room signage. The drawings are dated March 22, 2024 and were prepared by Bancroft Architects & Engineers. Project number is 21-116. The scope spans multiple floors across different buildings and requires careful phasing to maintain operations during construction while protecting existing equipment and ensuring continuous infection control measures.

View the file

Other files

File Type Posted
36C77624B0026 0007.docx DOCX document
36C77624B0026 0006.docx DOCX document
Government Answers to Contractor questions.docx DOCX document
Add Spec Section 23 21 13 Attachment A.pdf PDF
Revised Vol3 Drawing_M503.pdf PDF
Revised Spec Section 23 21 13.pdf PDF
36C77624B0026 0005.docx DOCX document
Pages from Addendum1_Vol2_2of2__20241209.pdf PDF
Colmery-ONeil VA Medical Center - Asbestos and Lead Survey Report signed.pdf PDF
Submittal 024 Pipe - Valve- Fittings 8-8-17.pdf PDF
589A5-21-700_TOPEKA_EHRM_SURVEY LOCATIONS-Markup.pdf PDF
Pages from Addendum1_Vol2_1of2__20241209.pdf PDF
EHRM Contractor Parking and Laydown.pdf PDF
Addendum1_Specifications_20241209.pdf PDF
Addendum1_Vol3_2of3_20241209.pdf PDF
230415-000 Topeka VA Geotech Final Report_S.pdf PDF
Addendum1_Vol3_1of3_20241209.pdf PDF
Addendum1_Vol3_3of3_20241209.pdf PDF
36C77624B0026 0004.docx DOCX document
589A5-21-700_Topeka KS_EHRM_Tech Q1_20241210.docx DOCX document
589A5-21-700_Topeka EHRM_IFB_BOD_Blast.pdf PDF
589A5-21-700_19550421_Steam Distro Plot Plan.pdf PDF
Submittal 023B Perma Pipe Fittings 8-21-17.pdf PDF
589A5-21-700_Topeka KS_EHRM_Tech Q2_20241210.docx DOCX document
36C77624B0026 0003.docx DOCX document
36C77624B0026 0002.docx DOCX document
S04_Site Visit Sign-in Sheet_Topeka KS.pdf PDF
S06- 36C77624B0026 0001.docx DOCX document
Attachment 1 - 589A5-21-700_Topeka EHRM__SOWV3.docx DOCX document
Attachment 16 - 589A5-21-700_Topeka EHRM_IFB R2 Drawings_Vol 3_1.pdf PDF
Attachment 15 - 589A5-21-700_Topeka EHRM_IFB R2 Drawings_Vol 2-8.pdf PDF
Attachment 10 -589A5-21-700_Topeka EHRM_IFB R2 Drawings_Vol 91-129.pdf PDF
Attachment 3 - DB Wage Determination Topeka-KS.pdf PDF
Attachment 8 -589A5-21-700_Topeka EHRM_IFB R2 Drawings_Vol 3_1-90.pdf PDF
Attachment 4 -589A5-21-700_Topeka EHRM_IFB R2 Drawings_Vol 2_118-180.pdf PDF
Attachment 11 -589A5-21-700_Topeka EHRM_IFBR2_Spec-VOL1_032224.pdf PDF
Attachment 5 -589A5-21-700_Topeka EHRM_IFB R2 Drawings_Vol 2_181-240.pdf PDF
Attachment 14 - 589A5-21-700_Topeka EHRM_IFB R2 Drawings_Vol 1_134-204.pdf PDF
Attachment 13 - 589A5-21-700_Topeka EHRM_IFB R2 Drawings_Vol 1_1-18.pdf PDF
Attachment 9 -589A5-21-700_Topeka EHRM_IFB R2 Drawings_Vol 3-2.pdf PDF
Attachment 12 -589A5-21-700_Topeka EHRM_IFBR2_Spec-VOL2_032224.pdf PDF
Attachment 20 -Site Visit Instructions.docx DOCX document
Attachment 19 -589A5-21-700_Topeka EHRM_IFB R2 Drawings_Vol 2_111-117.pdf PDF
Attachment 6 -589A5-21-700_Topeka EHRM_IFB R2 Drawings_Vol 2_241-281.pdf PDF
Attachment 18 -589A5-21-700_Topeka EHRM_IFB R2 Drawings_Vol 2_1-110.pdf PDF
36C77624B0026_1.docx DOCX document
Attachment 2- Limitations on Subcontracting - Construction.docx DOCX document
Attachment 7 -589A5-21-700_Topeka EHRM_IFB R2 Drawings_Vol 2-7.pdf PDF
Attachment 17 -589A5-21-700_Topeka EHRM_IFB R2 Drawings_Vol 1_19-133.pdf PDF
Show all 49

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

T101 T102

1. REMOVE AND STORE CEILING TILES IN THIS AREA AS REQUIRED FOR MECHANICAL

DUCTWORK, PIPING, ELECTRICAL CONDUIT, TECHNOLOGY EQUIPMENT AND/OR

SECURITY INSTALLATION. REINSTALL TILES AND GRID WHEN WORK IS COMPLETED.

REPLACE ANY DAMAGED TILES AND GRIDS TO MATCH EXISTING. G.C. SHALL

TEMPORARILY ERECT A SUSPENDED PLASTIC BARRIER 6 MIL AROUND AREA OF

CEILING WORK TO BE PERFORMED DURING ONE SHIFT AND G.C. SHALL REMOVE

SUSPENDED PLASTIC BARRIER AT THE END OF SHIFT. G.C. SHALL MOP CLEAN THIS

AREA OF WORK. PRIOR TO TURNING OVER AREA TO VA. AFTER WORK HOURS WILL

REQUIRE ADDITIONAL COORDINATION WITH THE VA.

2. REFER TO DETAIL 2/A-B01-101 FOR NOTES THAT APPLY TO ALL CONNECTING

CORRIDOR AREAS

CEILING DEMOLITION LEGEND

CEILING DEMOLITION KEY NOTESX

KEYNOTE 11

A. ALL WORK ASSOCIATED WITH TEMPORARY CEILING REMOVAL AND INSTALLATION

OF CABLING SHALL BE CONSIDERED AS NO MORE HAZARDOUS THAN NORMAL

OPERATIONS. INFECTION CONTROL REQUIREMENTS FOR THIS WORK SHALL

INCLUDE "VISQUEEN" TYPE BARRIER AROUND WORK AND/OR INFECTION CONTROL

MODULES WITH VA STATION APPROVAL. CONTRACTOR SHALL ALSO ADHEAR TO

"INFECTION CONTROL REQUIREMENTS BY ALL CLASSES" ON SHEET GI101.

B. AT LOCATION OF ALL CORES THROUGH FLOORS INSTALL RE-ENTERABLE FIRESTOP

ASSEMBLIES.

C. AT LOCATION OF CORES THROUGH RATED PARTITIONS INSTALL RE-ENTERABLE

FIRESTOP ASSEMBLIES (TYP.)

D. CONTRACTOR TO LOCATE EXISTING REINFORCING PRIOR TO CORING FOR

CONDUIT. DO NOT CUT REINFORCEMENT. CORES SHALL HAVE 4" CLEAR MINIMUM

BETWEEN THEM. ADJUST CORE LOCATIONS AS NEEDED. AT LOCATIONS WITH

MORE THAN TWO (2) CORES PASSING THROUGH A C.M.U. WALL, SPACE CORES AT

16" MINIMUM.

GENERAL PLAN NOTES

KEYNOTE 22

CAMPUS ROUTING PLAN CEILING

WORK

JG JG

A-101

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

K:

\C

C G

_P R

O

JE

C

TS

\2

1\

-1

T op ek a

EH

R M

C

1R

\4

- D es

D oc s\

2- D ra w in gs

\W O

R

KI

N G

\A ut oC

AD

\A -1

.d w g

/2

0/

:1 9:

A

M

ISSUE FOR BIDOffice of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

EHRM INFRASTRUCTURE

UPGRADES

COLMERY O'NEIL VA HEALTH CARE

21-116

Revisions: Date:

www. bancroft-ae.com

3300 Dundee RD.

Northbrook, IL 60062

T: 847.952.9362

03/22/2024Bancroft Project No: 21-116ISSUE FOR BID R2 03-22-24

ADDENDUM #1 11-20-24

AutoCAD SHX Text N

AutoCAD SHX Text

AutoCAD SHX Text 16'

AutoCAD SHX Text 32'

AutoCAD SHX Text 64'

AutoCAD SHX Text 128'

AutoCAD SHX Text 1/64"=1'-0"

AutoCAD SHX Text

AutoCAD SHX Text

CAMPUS PLAN / CORRIDOR CEILING WORK

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

CAMPUS PLAN KEYNOTES

AutoCAD SHX Text

CAMPUS ROUTING PLAN GENERAL NOTES

AutoCAD SHX Text A. THE INTENT OF THIS DRAWINGS IS TO IDENTIFY ALL THE CEILING WORK THAT IS THE INTENT OF THIS DRAWINGS IS TO IDENTIFY ALL THE CEILING WORK THAT IS TO BE PERFORMED IN THE CORRIDOR/LINK AREAS OF THE CAMPUS THAT ARE LOCATED THROUGHOUT THE CAMPUS AND MAY OR MAY NOT BE REPRESENTED ON OTHER BUILDING SHEETS B. REFER TO KEYNOTE 2 IN THE CEILING DEMOLITION LEGEND FOR WORK REFER TO KEYNOTE 2 IN THE CEILING DEMOLITION LEGEND FOR WORK ASSOCIATED IN CORRIDORS. C. PLEASE REFER TO CONSTRUCTION DOCUMENT SET FOR WORK TO BE PERFORMED PLEASE REFER TO CONSTRUCTION DOCUMENT SET FOR WORK TO BE PERFORMED IN CORRIDORS.

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

SEE SHEET A-B03-100

AutoCAD SHX Text

AutoCAD SHX Text

SEE SHEET A-B04-101

AutoCAD SHX Text

AutoCAD SHX Text

SEE SHEET A-B25-101

AutoCAD SHX Text

AutoCAD SHX Text

SEE SHEET A-B05-101

AutoCAD SHX Text

AutoCAD SHX Text

SEE SHEET A-B20-101

AutoCAD SHX Text

AutoCAD SHX Text

SEE SHEET A-B02-101

AutoCAD SHX Text

AutoCAD SHX Text

SEE SHEET A-B21-101

AutoCAD SHX Text

AutoCAD SHX Text

SEE SHEET A-B01-101

AutoCAD SHX Text

AutoCAD SHX Text

SEE SHEET A-B24-101

AutoCAD SHX Text

AutoCAD SHX Text

SEE SHEET A-B23-411

AutoCAD SHX Text

AutoCAD SHX Text

SEE SHEET A-B06-101

AutoCAD SHX Text

AutoCAD SHX Text

SEE SHEET A-B09-100

AutoCAD SHX Text

AutoCAD SHX Text CONTRACTOR TO DEMO/CORE THRU EXISTING MASONRY WALL AND INSTALL FIRE RATED SLEEVES AS NECESSARY AND ASSEMBLED PER UL DETAIL APPROPRIATE FOR WALL/FLOOR AND REACEWAY/CABLE TYPES IN EXISTING STRUCTURE.

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text CONTRACTOR TO MODIFY SUSPENDED CEILING AT LOCATION INDICATED PER DETAIL 3/A-B01-101 TO ALLOW FOR CABLE ROUTING THROUGH CORRIDOR ABOVE CEILING.

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

UP

UP

UP

UP

UP

DN

UP

DN

UP

UPUP

UP

A

B

C

D

E

F

1 3 4 5 11 13 16 18 19 21 23 25 26 27 286 8 9

11.1

14 15

K

L

M

29 30

G

O

Q

S

T

U

V

P

S.2

S.1

Q.1

U.1

V.1

V.2

W.1

X

Y

8.26.36.2 10.19.3 12.111.2

2.1

3.1

4.1

3.8

Z.4

4.7 6.1 8.1 11.7

Z.3

Z.2

24 31 32

N

7 222010 12

18B 20B 22B 24B 24C

H

I

J

R

W

Z.1

22D

AC101A AC130

AC101B

AC101C

AC133

AC128

AC129 AC134 AC135

AC131

AC131

AC101D

AC136

B1-03C

AC119

B113

AC127A

AC127B

C100

AC100

AC101

AC104

A140

A141A128C

A1

B103 B105

C110C109C107 C108

C116F C116A

C116

C116B

C105

C104

C106

C115

A1

A143F

A121AA119A118

A117A

A116B

A116A

A120 A121 A121B

A115

A115H

A115A A115I

A115J

A115BA115C

A115G

A122

A115E

A121E A122F

A102G

A102A

A1

A102BA102C

A102D

A108

A109

AC101J

AC101I

AC101H

AC101G

A127 A127BA127A

C116C

C116D

C119

C120C124

C125

C121

C122

C123

C123BC123A

C126

C127

C1-02

A145

C117 C104F C116E C105E

A143

A102E A101E

C102C101A144 C103

A111

A112

A104A

A104

A106

A105A110

A136

B149B1

B116

B148

B147

B146

AC120A

AC120

A116HA116G

A116E A116F

A116D

A116C

A116

A107

A104B

A115D

AC119AC118AC115

AC112

AC112A

AC114

AC109

A135

B145

B133

B134

B136 B135

B131 B132B130

B138

B129

B139B140

B128

B127

B137

B126

B141

B124B119

B123E

B143 B142

B133AB120

B143E

B120F

AC135

AC110

AC111

AC121

AC116E

AC122

AC122A

AC125

AC106E

AC113

AC124

AC123

AC117

B118

A137

B117A

A134A

C113 C112C111

C114D

C114-E

C114B

C114C

C114C

C114-W

C1-03A103

B123 B125

A1-04 A1-03

A140E

A134

A128B

A128D

A128A

AC105AC106

A1

A

A129

A128H A128G

AC108

AC1-5

B114

B106B107

B108

B113

B109A B109

B111

B1

B115

B104

B116C

B116D B1-03

A1-01

A101

A138

A142A

AC101K

B1-04B1-01

B1-02

A101A

A101G A101C

A113

B101

A101D

A141E

C1-01

C114T

A114

AC147 AC148 AC149 AC150 AC151 AC152 AC153 AC154 AC155 AC156

AC158 AC157

AC165AC164AC161

AC160

AC143 AC143A

AC145AC146

AC144 AC141 AC162 AC163 AC166

AC167

AC

1-

AC

1-

AC

1-

A615P

A6

Q

AC1-2

AC159

A1-02

A1-E1

A1-E2

A1-E3 A1-E4

A101H

A101J

AC134A AC136AAC135A

AC134C B1-03D

B116A

1&2

FP-01-412

3&4 M-01-411

1,2,3&4 A-01-411

5,6,7&8 A-01-411

1,2,3&4 A-01-412

1&2 M-01-412

1&2

FP-01-413

3&4 M-01-411

1&2

FP-01-411

CORRIDOR CONTINUES

TO BLDG 21 (A-B21-101)

CORRIDOR CONTINUES

TO BLDG 24 (A-B24-101)

RATED PARTITION LEGEND

CONTRACTOR IS REQUIRED TO MAINTAIN ALL RATED PARTITIONS.

1 HR FIRE BARRIER

2 HR FIRE BARRIER

SMOKE BARRIER

1 HR FIRE BARRIER (EXISTING)

2 HR FIRE BARRIER (EXISTING)

SMOKE BARRIER (EXISTING)

1. REMOVE AND STORE CEILING TILES IN THIS AREA AS REQUIRED FOR MECHANICAL

DUCTWORK, PIPING, ELECTRICAL CONDUIT, TECHNOLOGY EQUIPMENT AND/OR

SECURITY INSTALLATION. REINSTALL TILES AND GRID WHEN WORK IS COMPLETED.

REPLACE ANY DAMAGED TILES AND GRIDS TO MATCH EXISTING. G.C. SHALL

TEMPORARILY ERECT A SUSPENDED PLASTIC BARRIER 6 MIL AROUND AREA OF

CEILING WORK TO BE PERFORMED DURING ONE SHIFT AND G.C. SHALL REMOVE

SUSPENDED PLASTIC BARRIER AT THE END OF SHIFT. G.C. SHALL MOP CLEAN THIS

AREA OF WORK. PRIOR TO TURNING OVER AREA TO VA. AFTER WORK HOURS WILL

REQUIRE ADDITIONAL COORDINATION WITH THE VA.

2. REFER TO DETAIL 2/A-B01-101 FOR NOTES THAT APPLY TO ALL CONNECTING

CORRIDOR AREAS

A. REFER TO TECHNOLOGY AND ELECTRICAL FOR FULL REQUIRED INSTALLATION

AND DEMOLITION WORK

B. ALL EXISTING LIGHTING, CONDUIT, DUCTWORK, MECHANICAL GRILLS, &

SPRINKLER HEADS TO REMAIN IN EXISTING LOCATIONS AND PROTECTED

UNLESS OTHERWISE NOTED.

C. ANY ELECTRICAL FIXTURES AND DEVICES THAT ARE NOT IDENTIFIED ON THESE

DRAWINGS IN THE AREAS OF CEILING DEMOLITION, ARE TO BE CAREFULLY

REMOVED FROM THE CEILING, PROTECTED, TEMPORARILY HUNG AND THEN

REATTACHED IN THE SAME LOCATIONS AS WHICH THEY WERE FOUND PRIOR TO

DEMOLITION.

D. CONTRACTOR TO CAREFULLY REMOVE SECTIONS OF EXISTING CEILING TILE TO

ALLOW FOR THE INSTALLATION OF ALL REQUIRED CONDUIT AND ELECTRICAL

EQUIPMENT PER CONTRACT DRAWINGS. CONTRACTOR SHALL REINSTALL

CEILING IN EXACT LOCATION. CONTRACTOR TO REPLACE ANY CEILING

GRID/TILES DAMAGED DURING CONSTRUCTION, MATCHING EXISTING. REFER TO

ELECTRICAL SHEETS FOR ADDITIONAL INFORMATION.

E. IF A RATED ASSEMBLY IS NOT INSTALLED BY END OF SHIFT IT MUST BE

PROTECTED OVERNIGHT.

GENERAL DEMOLITION NOTES

CEILING DEMOLITION LEGEND

CEILING DEMOLITION KEY NOTESX

1. REPLACE EXISTING A,B&C TYPE FIRE EXTINGUISHER WITH CLEAN AGENT A,B&C

TYPE FIRE EXTINGUISHER.

2. INSTALL CLEAN AGENT A,B&C TYPE FIRE EXTINGUISHER IN SEMI-RECESSED

CABINET SET IN NEW GYP. BD. ON METAL STUD ASSEMBLY (1-HR RATED)

3. INSTALL CLEAN AGENT A,B&C TYPE FIRE EXTINGUISHER IN SEMI-RECESSED

CABINET IN EXISTING WALL WRAP CABINET IN TYPE 'X' GYPSUM BOARD.

FLOOR PLAN KEY NOTESX

KEYNOTE 11

A. ALL WORK ASSOCIATED WITH TEMPORARY CEILING REMOVAL AND INSTALLATION

OF CABLING SHALL BE CONSIDERED AS NO MORE HAZARDOUS THAN NORMAL

OPERATIONS. INFECTION CONTROL REQUIREMENTS FOR THIS WORK SHALL

INCLUDE "VISQUEEN" TYPE BARRIER AROUND WORK AND/OR INFECTION CONTROL

MODULES WITH VA STATION APPROVAL. CONTRACTOR SHALL ALSO ADHEAR TO

"INFECTION CONTROL REQUIREMENTS BY ALL CLASSES" ON SHEET GI101.

B. AT LOCATION OF ALL CORES THROUGH FLOORS INSTALL RE-ENTERABLE FIRESTOP

ASSEMBLIES.

C. AT LOCATION OF CORES THROUGH RATED PARTITIONS INSTALL RE-ENTERABLE

FIRESTOP ASSEMBLIES (TYP.)

D. CONTRACTOR TO LOCATE EXISTING REINFORCING PRIOR TO CORING FOR

CONDUIT. DO NOT CUT REINFORCEMENT. CORES SHALL HAVE 4" CLEAR MINIMUM

BETWEEN THEM. ADJUST CORE LOCATIONS AS NEEDED. AT LOCATIONS WITH

MORE THAN TWO (2) CORES PASSING THROUGH A C.M.U. WALL, SPACE CORES AT

16" MINIMUM.

GENERAL PLAN NOTES

CEILING LEGEND

KEYNOTE 22

ARCHITECTURAL - BUILDING 1 - LEVEL 1

PLAN

DA JM

A-B01-101

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

K:

\C

C G

_P R

O

JE

C

TS

\2

1\

-1

T op ek a

EH

R M

C

1R

\4

- D es

D oc s\

2- D ra w in gs

\W O

R

KI

N G

\A ut oC

AD

\A -B

-1

.d w g

/1

4/

2:

:1

PM

ISSUE FOR BIDOffice of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

EHRM INFRASTRUCTURE

UPGRADES

COLMERY O'NEIL VA HEALTH CARE

21-116

Revisions: Date:

www. bancroft-ae.com

3300 Dundee RD.

Northbrook, IL 60062

T: 847.952.9362

03/22/2024Bancroft Project No: 21-116ISSUE FOR BID R2 03-22-24

ADDENDUM #1 11-20-24

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text DENOTES SIGNAGE LOCATION, REFER TO SHEET AS-601 FOR SIGNAGE SCHEDULE AND RELATED DETAILS.

AutoCAD SHX Text X

AutoCAD SHX Text REMOVE AND STORE CEILING TILES IN THIS AREA AS REQUIRED FOR TECHNOLOGY EQUIPMENT AND/OR SECURITY INSTALLATION. REINSTALL TILES AND GRID WHEN WORK IS COMPLETED. REPLACE ANY DAMAGED TILES AND GRIDS TO MATCH EXISTING. G.C. SHALL TEMPORARILY ERECT A SUSPENDED PLASTIC BARRIER 6 MIL AROUND AREA OF CEILING WORK TO BE PERFORMED DURING ONE SHIFT AND G.C. SHALL REMOVE SUSPENDED PLASTIC BARRIER AT THE END OF SHIFT. G.C. SHALL MOP CLEAN THIS AREA OF WORK. PRIOR TO TURNING OVER AREA TO VA. AFTER WORK HOURS WILL REQUIRE ADDITIONAL COORDINATION WITH THE VA. PROTECT WINDOW OPENINGS WITH PLASTIC BARRIER. PENETRATIONS ENTERING PLASTIC BARRIER CONTAINMENT SHALL BE PROPERLY SEALED TO MITIGATE DUST.

AutoCAD SHX Text

2 TILES MAX.

AutoCAD SHX Text

2 TILES MAX.

AutoCAD SHX Text

DEMOLITION MAX (2) TILES FROM OFFSET OF CEILING

AutoCAD SHX Text

DEMOLITION MAX (2) TILES FROM OFFSET OF CEILING

AutoCAD SHX Text

INSTALL NEW GRID, TILE AND HANGERS SLOPED TO CONNECT DIFFERING CEILING HEIGHTS

AutoCAD SHX Text

EXISTING ROOF STRUCTURE

AutoCAD SHX Text N

AutoCAD SHX Text

AutoCAD SHX Text 4'

AutoCAD SHX Text 8'

AutoCAD SHX Text 16'

AutoCAD SHX Text 32'

AutoCAD SHX Text 1/16"=1'-0"

AutoCAD SHX Text

AutoCAD SHX Text

BUILDING 1 - LEVEL 1 PLAN

AutoCAD SHX Text

AutoCAD SHX Text 1'

AutoCAD SHX Text 2'

AutoCAD SHX Text 4'

AutoCAD SHX Text 8'

AutoCAD SHX Text 1/4"=1'-0"

AutoCAD SHX Text

AutoCAD SHX Text

TYPICAL CONNECTING CORRIDOR DEMOLITION RCP

AutoCAD SHX Text

AutoCAD SHX Text 1'

AutoCAD SHX Text 2'

AutoCAD SHX Text 4'

AutoCAD SHX Text 8'

AutoCAD SHX Text 1/4"=1'-0"

AutoCAD SHX Text

TYPICAL DETAIL @ OFFSET CEILING IN CORRIDOR

DN

MST OFFICE

B127

OPH OFFICE

B128

SP OFFICE

A119

SP STOR.

A120

SP OFFICE

A121

OPH OFFICE

B126

CORRIDOR

1CDR3

OPH OFFICE

B125

OPH OFFICE

B130

OPH OFFICE

B129

SP OFFICE

A118

CONF /

CLASSROOM

A123

SP STOR.

A117

ENGINEERING

(N.I.C.)

A139

OPH OFFICE

B124

OPH OFFICE

B131

STOR.

A110

STAIR 2

B1-S2

ADMIN OFFICE

B118

ADMIN OFFICE

B119

ADMIN OFFICE

B120

ADMIN OFFICE

B121

ADMIN OFFICE

B122

HSK.

B123

DN

ELEC

B112

ELEC

B111

P. TLT.

B133

CORRIDOR

1CDR2

S. TLT.

B104

ADMIN OFFICE

B117

ADMIN OFFICE

B116

ADMIN OFFICE

B115

ADMIN COPY

B114

ADMIN STOR.

B113

IT

B110

S. TLT.

B105

CORRIDOR

1CDR4

COPY

B103

MM STOR.

B102

MM CONSULT

B101

MM OFFICE

A109

MM OFFICE

A108

STAIR

A1-S1

TEAM RM

B108

LACTATION

B106

CHILDREN'S

WAITING

A104

P. TLT.

A105

MSA

A103

ELEC

A112

STORAGE

A114

IT

A107

ELEV #4

A1-E4

ELEV #5

A1-E5 P. TLT.

A128

SUD GROUP

THERAPY

C136

SUD OFFICE

C134

SUD OFFICE

C133

STOR.

C127

HALL

A131

J.8

J

STAFF LOUNGE

B107

LOBBY

A101

VESTIBULE

A100

L (E) K.8

VESTIBULE

A102

L.9

M.9

19 20

BHIP OFFICE

D120

BHIP OFFICE

D119

BHIP OFFICE

D118

HALL

D136

BHIP OFFICE

D121

CORRIDOR

1CDR11

BHIP OFFICE

D128

BHIP OFFICE

D122

BHIP OFFICE

D123

BHIP OFFICE

D124

BHIP OFFICE

D125

BHIP OFFICE

D126

BHIP OFFICE

D127

O

O.5

BHIP OFFICE

D134

BHIP OFFICE

D133

BHIP OFFICE

D132

CONF

D131

P

P.5

21 21.1 22.2 22.7 25.4 27 28.5 29.1 30.9 32.5 33.3 33.8

BHIP OFFICE

D130

BHIP OFFICE

D129

BHIP OFFICE

D117

BHIP OFFICE

D116

BHIP OFFICE

D115

HOLD

D101

CONSULT

D102

BHIP OFFICE

D103

BHIP OFFICE

D104

BHIP OFFICE

D105

BHIP OFFICE

D106

IT

D107

HSK

D138

CORRIDOR

1CDR10

P. TLT.

D111

ELEC

D137 M.3

CONF / CLASS

D114

N

N.5

STOR.

C132

CWT OFFICE

D108

S. TLT.

C130

COURTYARD

D135

S. TLT.

C131

STAFF LOUNGE

C129

VESTIBULE

D109

P. TLT.

D110

BHIP OFFICE

D112

STAFF WORK

D113

L

CORRIDOR

1CDR7

CAROTAS

C128

ELEC

A113

CORRIDOR

1CDR1 ALCOVE

A106

DRINKING

FOUNTAIN

A130

ELEC

C135

P. TLT.

C126

P. TLT.

C125

BHIP OFFICE

C124

BHIP OFFICE

C123

BHIP OFFICE

C122

BHIP OFFICE

C121

BHIP OFFICE

C120

P. TLT.

B132

OPH OFFICE

B134

OPH OFFICE

B135

OPH OFFICE

B136

OPH OFFICE

B137 OPH OFFICE

A111

EMS STORAGE

(N.I.C.)

A137

ELEV #6

A1-E6

GROUP

THERAPY

A127

GROUP

THERAPY

A126

SUD OFFICE

C101

IT

C102

SUD OFFICE

C103

ELEC

C104

SUD OFFICE

C105

CRASH CART

C137

HSK

C114

CORRIDOR

1CDR5

STAIR

C1-S3

BHIP OFFICE

C115

BHIP OFFICE

C116

LOADING DOCK

(N.I.C.)

A138

CORRIDOR

1CDR8

SP STOR.

A122

CORRIDOR

1CDR9

BHIP OFFICE

C108

CORRIDOR

1CDR6

GROUP

THERAPY

A124

STORAGE

A125

BHIP OFFICE

C106

BHIP OFFICE

C113 DN

BHIP OFFICE

C107

BHIP OFFICE

C112

BHIP OFFICE

C111

BHIP OFFICE

C109

BHIP OFFICE

C110

BHIP OFFICE

C117

BHIP OFFICE

C118

BHIP OFFICE

C119

L.5

M

TR

A129

1&2

FP-02-411

1&2 M-02-411

CORRIDOR CONTINUES

TO BLDG 20 (A-B20-101)

GENERAL NOTES

A. FOR GENERAL NOTES AND LEGENDS REFER TO SHEET A001.

B. FOR GENERAL INFECTION CONTROL NOTES AND DETAILS REFER TO SHEET GI101.

C. EXISTING IT/TR/OI&T ROOMS TO REMAIN ACTIVE DURING CONSTRUCTION. G.C. TO PROTECT

EQUIPMENT DURING CONSTRUCTION WITH VISQUEEN. CONTRACTOR TO ENSURE

CONTINUOUS OPERATION OF EQUIPMENT.

D. NOT ALL KEY NOTES APPLY TO ALL PLAN SHEETS. G.C. TO APPLY ONLY AS INDICATED PER

EACH SHEET.

E. MAINTAIN A 4 ' - 0" CLEAR PATH OF TRAVEL IN THE CORRIDORS AT ALL TIMES.

F. ALL WORK TO BE PERFORMED AS PART OF TR MODIFICATION SHALL BE CONSIDERED AS

TYPE IV AND FOLLOW "INFECTION CONTROL PRECAUTIONS FOR CLASS IV" ON SHEET GI101.

G. APPLY FIRE RATED SEALANT TO ALL EXISTING AND NEW PENETRATIONS IN EXISTING WALLS

TO MAKE EXISTING WALLS A 1 HR ASSEMBLY. BASIS OF DESIGN FOR 1 HR WALL IS UL 419

ASSEMBLY.

H. ALL EXISTING WALLS WITH TR'S ARE TO BE FULLY PATCHED & PREPPED TO A LIKE NEW

APPEARANCE BEFORE RECEIVING NEW PLYWOOD PANELS.

I. IN ALL EXISTING OI&T AND IRM ROOMS TO BE CONVERTED TO TR'S - ALL EXISTING PLYWOOD

PANELS TO BE REMOVED A WALLS PATCHED AND PREPPED TO RECEIVE PAINT AND NEW

PLYWOOD PANELS.

DEMOLITION PLAN KEYNOTES

DEMO CEILING KEYNOTESX CEILING PLAN KEYNOTES

FLOOR PLAN LEGEND

4'X8' AC GRADE 3/4" TRADE SIZE FIRE RATED PLYWOOD BACKBOARD

PAINTED HIGH GLOSS WHITE WITH (2) COATS OF FIRE RESISTANT PAINT

FOR SERVICE PROVIDER /SECURITY/VIDEO/ETC. AROUND PERIMETER

WALLS OF TRS AND ENTRANCE ROOMS AS SHOWN. ENSURE THAT FIRE

RATING STAMP IS TO REMAIN UNCOVERED BY PAINT.

1. REMOVE AND STORE CEILING TILES IN THIS AREA AS REQUIRED FOR

MECHANICAL DUCTWORK, PIPING, ELECTRICAL CONDUIT, TECHNOLOGY

EQUIPMENT AND/OR SECURITY INSTALLATION. REINSTALL TILES AND GRID

WHEN WORK IS COMPLETED. REPLACE ANY DAMAGED TILES AND GRIDS TO

MATCH EXISTING. G.C. SHALL TEMPORARILY ERECT A SUSPENDED PLASTIC

BARRIER 6 MIL AROUND AREA OF CEILING WORK TO BE PERFORMED DURING

ONE SHIFT AND G.C. SHALL REMOVE SUSPENDED PLASTIC BARRIER AT THE

END OF SHIFT. G.C. SHALL MOP CLEAN THIS AREA OF WORK. PRIOR TO

TURNING OVER AREA TO VA. AFTER WORK HOURS WILL REQUIRE ADDITIONAL

COORDINATION WITH THE VA.

FLOOR PLAN KEYNOTESX X

CEILING REMOVAL SCOPE

X

CONTRACTOR IS REQUIRED TO MAINTAIN ALL RATED PARTITIONS.

1HR FIRE BARRIER

1 HR FIRE BARRIER (EXISTING)

RATED PARTITION LEGEND

SMOKE BARRIER

SMOKE BARRIER (EXISTING)

2 HR FIRE BARRIER

2 HR FIRE BARRIER (EXISTING)

1. FINISH WALL CORNER TO CORNER AND FLOOR TO CEILING. PRIOR TO PAINTING THE ENTIRE WALL SURFACE WITH (1) FINISH COAT OF PAINT, PROVIDE (1) PRIME COAT AND (2) FINISH

COATS OVER PATCHED/REPAIRED WALL SURFACES.

2. INSTALL NEW HANDRAIL, NEW CRASH RAIL AND WALL BASE TO CREATE LONG CONTINUOUS

RUN. EXTEND HANDRAIL, CRASH RAIL AND WALL BASE TO NEXT ASSEMBLY JOINT. FOR

DETAILS SEE SHEET A-502.

3. EXISTING GLAZING TO REMAIN. BACK-PAINT GLASS ON INSIDE OF GLAZING. PAINT BLACK

UNLESS OTHERWISE NOTED BY VA.

4. PATCH FLOOR AND PROVIDE NEW WALL BASE AS REQUIRED TO MATCH EXISTING CONDITIONS.

5. PROVIDE INSULATED ALUMINUM PANEL WITHIN WINDOW SYSTEM TO REPLACE PREVIOUS

GLASS PANEL. ALUMINUM FINISH SHALL MATCH WINDOW SYSTEM. SEE DETAIL 3 & 4/AW-602.

6. INSTALL TELECOMMUNICATIONS ENCLOSURE. SEE ELECTRICAL AND TECHNOLOGY DRAWINGS

FOR ADDITIONAL INFORMATION.

7. NEW PARTITION AS NOTED. ALIGN PARTITION WITH EXISTING WINDOW MULLION.

8. PATCH WALLS AS REQUIRED TO MATCH ADJACENT WALLS TO REMAIN AFTER DEMOLITION OF

NOTED COMPONENTS.

9. PATCH AND PAINT ALL WALLS TO LIKE NEW CONDITION. PAINT COLOR SHALL MATCH EXISTING

CONDITIONS.

10. FIRE EXTINGUISHER CABINET & CLEAN AGENT TYPE FIRE EXTINGUISHER MOUNTED 48” A.F.F.

TO CENTERLINE OF HANDLE. SEE DETAIL 1/A502. PATCH SURROUNDING WALLS .

11. INFILL WALL TO MATCH ADJACENT WALL CONSTRUCTION, INCLUDING FIRE RATING WHERE

REQUIRED.

12. NEW FLOORING AND WALL BASE AS SCHEDULED.

D1. REMOVE EXISTING CEILING GRID TO EXTENT REQUIRED TO COMPLETE WORK SCOPE AND

ACCOMMODATE INSTALLATION OF NEW PARTITIONS. SUPPORT EXISTING CEILING . SALVAGE

CEILING TILES FOR REINSTALLATION. RETURN UNUSED CEILING TILES TO VA FOR STORAGE.

D2. REMOVE EXISTING GYPSUM BOARD CEILING AND FRAMING ABOVE.

D3. REMOVE EXISTING LIGHT FIXTURE. REFER TO ELECTRICAL DRAWINGS FOR FULL SCOPE OF

WORK RELATED TO ELECTRICAL DEMOLITION AND REWORK.

C1. INSTALL NEW CEILING GRID AND EDGE ANGLE. INSTALL SALVAGED CEILING TILES TO

MATCH EXISTING ADJACENT CONDITIONS. INSTALL NEW CEILING TILES WHERE SALVAGED

TILES DO NOT MATCH.

C2. INSTALL NEW CEILING AS SCHEDULED SEE ROOM FINISH LEGEND.

C3. REPOSITION EXISTING LIGHT FIXTURES CENTERED IN ROOM AND WITHIN CEILING GRID.

C4. EXPOSED CEILING.

2. REFER TO DETAIL 2/A-B01-101 FOR NOTES THAT APPLY TO ALL CONNECTING

COORDIOR AREAS

1. INSTALL TEMPORARY FLAME RESISTANT CONSTRUCTION PANELS WITH DOOR ENTRY. BASIS

OF DESIGN IS EDGE GUARD.

2. SUPPLY AND INSTALL WALK OFF MAT(S). SEE DETAILS ON SHEET GI101.

3. EXISTING HANDRAIL, WALL BASE AND CARPET TO BE MODIFIED TO ACCEPT NEW DOOR.

4. REMOVE EXISTING WALL BASE AND EXISTING FLOORING (I.E. CARPET, LAMINATE FLOORING, VCT) TO EXISTING CONCRETE. SCRAPE CLEAN AND REMOVE ALL ASSOCIATED ADHESIVE.

PREP AND LEVEL EXISTING FLOORING TO RECEIVE NEW FINISH PER MANUFACTURE'S

REQUIREMENT.

5. REMOVED EXISTING DOOR, FRAME AND HARDWARE IN ITS ENTIRETY FOR INSTALLATION OF

NEW DOOR AND FRAME. PORTIONS OF EXISTING WALL TO BE DEMOLISHED AND/OR INFILLED

TO RECEIVE NEW DOOR AND FRAME ASSEMBLY. PATCH ADJACENT WALLS TO MATCH

ADJACENT CONDITIONS. ADJACENT ASSEMBLIES SUCH AS CHAIR RAILS, CORNER GUARDS

AND WALL MOUNTED ITEMS MAY NEED TO BE ADJUSTED TO ACCOMMODATE NEW OPENINGS.

6. REMOVE ANY WALL MOUNTED ITEMS, EQUIPMENT, FURNITURE AND ASSOCIATED

COMPONENTS COMPLETE. CONTRACTOR TO ALLOW VA RIGHT OF FIRST REFUSAL OF ANY

REMOVED ITEMS.

7. REMOVE GLASS FROM WINDOW SYSTEM AT THIS LOCATION. PREPARE WINDOW SYSTEM TO

RECEIVE INFILL AS NOTED IN NEW WORK SCOPE.

8. REMOVE EXISTING BASE AND/OR WALL CABINETS, COUNTERTOP, AND ASSOCIATE

COMPONENTS/EQUIPMENT COMPLETE. CAP ANY ASSOCIATED PLUMBING AT SOURCE, REFER

TO PLUMBING DRAWINGS.

9. REMOVE ALL EXISTING TELECOMMUNICATIONS AND ASSOCIATED ELECTRICAL EQUIPMENT

WITHIN EXISTING DATA CENTER UPON COMPLETION OF INFRASTRUCTURE UPGRADES

OUTLINED WITHIN THESE DOCUMENTS. RETURN ALL EQUIPMENT TO THE VA UNLESS

OTHERWISE NOTED.

10. PROTECT EXISTING EQUIPMENT CONTROLS BOX DURING CONSTRUCTION. RECONFIGURE AS

REQUIRED TO ALLOW FOR NEW WALL OPENING.

11. DEMO EXISTING WALL FOR FIRE EXTINGUISHER CABINET. REFER TO FLOOR PLAN KEYNOTE

#10. MODIFY EXISTING WALL MOUNTED ASSEMBLIES TO ALLOW FOR CABINET INSTALLATION.

12. G.C. TO CAREFULLY REMOVE EXISTING WINDOW TREATMENT AND TURN OVER TO VA. VA HAS

RIGHT OF FIRST REFUSAL.

13. G.C. TO CAREFULLY REMOVE EXISTING ROOM SIGN AND TURN OVER TO VA. VA HAS RIGHT OF

FIRST REFUSAL. SEE SIGNAGE SCHEDULE FOR NEW SIGN TYPE AND COPY.

3. REMOVE GYPSUM BOARD CEILING AS REQUIRED FOR MECHANICAL DUCTWORK,

PIPING, ELECTRICAL CONDUIT, TECHNOLOGY EQUIPMENT AND/OR SECURITY

INSTALLATION.

D4. REMOVE PORTION OF CMU WALL FOR NEW MECHANICAL REGISTER LOCATION. SEE

MECHANICAL DRAWINGS FOR FURTHER INFORMATION.

14. REMOVE EXISTING PLUMBING FIXTURE IN ITS ENTIRETY. CUT AND CAP EXISTING PIPING BACK TO

NEAREST MAIN.

TR

A129

CONFERENCE

A168

CORRDIDOR

1CDR1

B B

B

A129

CONFERENCE

A168

CORRDIDOR

1CDR1

STORAGE

A169A

RR

A168ACH

AS

E

A1

P

CONFERENCE

A168

CORRDIDOR

1CDR1

STORAGE

A169A

RR

A168ACH

AS

E

A1

P TR

A129

CONFERENCE

A168

CORRDIDOR

ARCHITECTURAL - BUILDING 2 - LEVEL 1

- OVERALL & ENLARGED PLANS

DA JM

A-B02-101

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

K:

\C

C G

_P R

O

JE

C

TS

\2

1\

-1

T op ek a

EH

R M

C

1R

\4

- D es

D oc s\

2- D ra w in gs

\W O

R

KI

N G

\A ut oC

AD

\A -B

-1

.d w g

/2

0/

:5 5:

P

M

ISSUE FOR BIDOffice of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

EHRM INFRASTRUCTURE

UPGRADES

COLMERY O'NEIL VA HEALTH CARE

21-116

Revisions: Date:

www. bancroft-ae.com

3300 Dundee RD.

Northbrook, IL 60062

T: 847.952.9362

03/22/2024Bancroft Project No: 21-116ISSUE FOR BID R2 03-22-24

C5. INSTALL NEW MECHANICAL REGISTER INTO GYPSUM WALL. SEE MECHANICAL DRAWINGS

FOR FURTHER INFORMATION.

ADDENDUM #1 11-20-24

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 10'-0"

AutoCAD SHX Text 7'-0"

AutoCAD SHX Text

4'-0" MIN.

AutoCAD SHX Text 2'-0"

AutoCAD SHX Text 2'-0"

AutoCAD SHX Text 4'-8"

AutoCAD SHX Text

AutoCAD SHX Text 4'

AutoCAD SHX Text 8'

AutoCAD SHX Text 16'

AutoCAD SHX Text 32'

AutoCAD SHX Text 1/16"=1'-0"

AutoCAD SHX Text

AutoCAD SHX Text

BUILDING 2 - LEVEL 1 PLAN

AutoCAD SHX Text N

AutoCAD SHX Text

AutoCAD SHX Text 1'

AutoCAD SHX Text 2'

AutoCAD SHX Text 4'

AutoCAD SHX Text 8'

AutoCAD SHX Text 1/4"=1'-0"

AutoCAD SHX Text

AutoCAD SHX Text

BUILDING 02 - ENLARGED RCP RM A129

AutoCAD SHX Text

AutoCAD SHX Text 1'

AutoCAD SHX Text 2'

AutoCAD SHX Text 4'

AutoCAD SHX Text 8'

AutoCAD SHX Text 1/4"=1'-0"

AutoCAD SHX Text

AutoCAD SHX Text

BUILDING 02 - ENLARGED DEMO RCP RM A129

AutoCAD SHX Text

AutoCAD SHX Text 1'

AutoCAD SHX Text 2'

AutoCAD SHX Text 4'

AutoCAD SHX Text 8'

AutoCAD SHX Text 1/4"=1'-0"

AutoCAD SHX Text

AutoCAD SHX Text

BUILDING 02 - ENLARGED PLAN RM A129

AutoCAD SHX Text

AutoCAD SHX Text 1'

AutoCAD SHX Text 2'

AutoCAD SHX Text 4'

AutoCAD SHX Text 8'

AutoCAD SHX Text 1/4"=1'-0"

AutoCAD SHX Text

BUILDING 02 - ENLARGED DEMO PLAN RM A129

DN

A CB D E F G H J K

A228

A255A256 A254

A253

A252F

A229

A2-C3 C230

C231

C232

C237

C240

C239A

C239D

C239C

C239H

C239P1

C2

P2

C238

C239IC241

C242

C2

P

C243E

C230A

C233G

C233A

C236F

C236

C235

C233B

C247A

C247

C244E

C244 C243

C234

C233

C233D

A252 C245

C233C

C233H

C239B

C239G

A227A

A227GA227D

A227C

A227B

A221A213 A214 A215 A216 A217 A218

A219

A227

A211

A200

A201

A202

A203

A206

A208A209

A2

A

A210 A212

A2

B

B220

A220

A205 A204

A246

A203A

A203

A229A

1,2,3&4 A-03-102

2&4

FP-03-421

1&2 M-03-421

GENERAL NOTES

A. FOR GENERAL NOTES AND LEGENDS REFER TO SHEET A001.

B. FOR GENERAL INFECTION CONTROL NOTES AND DETAILS REFER TO SHEET GI101.

C. EXISTING IT/TR/OI&T ROOMS TO REMAIN ACTIVE DURING CONSTRUCTION. G.C. TO PROTECT

EQUIPMENT DURING CONSTRUCTION WITH VISQUEEN. CONTRACTOR TO ENSURE

CONTINUOUS OPERATION OF EQUIPMENT.

D. NOT ALL KEY NOTES APPLY TO ALL PLAN SHEETS. G.C. TO APPLY ONLY AS INDICATED PER

EACH SHEET.

E. MAINTAIN A 4 ' - 0" CLEAR PATH OF TRAVEL IN THE CORRIDORS AT ALL TIMES.

F. ALL WORK TO BE PERFORMED AS PART OF TR MODIFICATION SHALL BE CONSIDERED AS

TYPE IV AND FOLLOW "INFECTION CONTROL PRECAUTIONS FOR CLASS IV" ON SHEET GI101.

G. APPLY FIRE RATED SEALANT TO ALL EXISTING AND NEW PENETRATIONS IN EXISTING WALLS

TO MAKE EXISTING WALLS A 1 HR ASSEMBLY. BASIS OF DESIGN FOR 1 HR WALL IS UL 419

ASSEMBLY.

H. ALL EXISTING WALLS WITH TR'S ARE TO BE FULLY PATCHED & PREPPED TO A LIKE NEW

APPEARANCE BEFORE RECEIVING NEW PLYWOOD PANELS.

I. IN ALL EXISTING OI&T AND IRM ROOMS TO BE CONVERTED TO TR'S - ALL EXISTING PLYWOOD

PANELS TO BE REMOVED A WALLS PATCHED AND PREPPED TO RECEIVE PAINT AND NEW

PLYWOOD PANELS.

DEMOLITION PLAN KEYNOTES

DEMO CEILING KEYNOTESX CEILING PLAN KEYNOTES

FLOOR PLAN LEGEND

4'X8' AC GRADE 3/4" TRADE SIZE FIRE RATED PLYWOOD BACKBOARD

PAINTED HIGH GLOSS WHITE WITH (2) COATS OF FIRE RESISTANT PAINT

FOR SERVICE PROVIDER /SECURITY/VIDEO/ETC. AROUND PERIMETER

WALLS OF TRS AND ENTRANCE ROOMS AS SHOWN. ENSURE THAT FIRE

RATING STAMP IS TO REMAIN UNCOVERED BY PAINT.

1. REMOVE AND STORE CEILING TILES IN THIS AREA AS REQUIRED FOR

MECHANICAL DUCTWORK, PIPING, ELECTRICAL CONDUIT, TECHNOLOGY

EQUIPMENT AND/OR SECURITY INSTALLATION. REINSTALL TILES AND GRID

WHEN WORK IS COMPLETED. REPLACE ANY DAMAGED TILES AND GRIDS TO

MATCH EXISTING. G.C. SHALL TEMPORARILY ERECT A SUSPENDED PLASTIC

BARRIER 6 MIL AROUND AREA OF CEILING WORK TO BE PERFORMED DURING

ONE SHIFT AND G.C. SHALL REMOVE SUSPENDED PLASTIC BARRIER AT THE

END OF SHIFT. G.C. SHALL MOP CLEAN THIS AREA OF WORK. PRIOR TO

TURNING OVER AREA TO VA. AFTER WORK HOURS WILL REQUIRE ADDITIONAL

COORDINATION WITH THE VA.

FLOOR PLAN KEYNOTESX X

CEILING REMOVAL SCOPE

X

CONTRACTOR IS REQUIRED TO MAINTAIN ALL RATED PARTITIONS.

1HR FIRE BARRIER

1 HR FIRE BARRIER (EXISTING)

RATED PARTITION LEGEND

SMOKE BARRIER

SMOKE BARRIER (EXISTING)

2 HR FIRE BARRIER

2 HR FIRE BARRIER (EXISTING)

1. FINISH WALL CORNER TO CORNER AND FLOOR TO CEILING. PRIOR TO PAINTING THE ENTIRE WALL SURFACE WITH (1) FINISH COAT OF PAINT, PROVIDE (1) PRIME COAT AND (2) FINISH

COATS OVER PATCHED/REPAIRED WALL SURFACES.

2. INSTALL NEW HANDRAIL, NEW CRASH RAIL AND WALL BASE TO CREATE LONG CONTINUOUS

RUN. EXTEND HANDRAIL, CRASH RAIL AND WALL BASE TO NEXT ASSEMBLY JOINT. FOR

DETAILS SEE SHEET A-502.

3. EXISTING GLAZING TO REMAIN. BACK-PAINT GLASS ON INSIDE OF GLAZING. PAINT BLACK

UNLESS OTHERWISE NOTED BY VA.

4. PATCH FLOOR AND PROVIDE NEW WALL BASE AS REQUIRED TO MATCH EXISTING CONDITIONS.

5. PROVIDE INSULATED ALUMINUM PANEL WITHIN WINDOW SYSTEM TO REPLACE PREVIOUS

GLASS PANEL. ALUMINUM FINISH SHALL MATCH WINDOW SYSTEM. SEE DETAIL 3 & 4/AW-602.

6. INSTALL TELECOMMUNICATIONS ENCLOSURE. SEE ELECTRICAL AND TECHNOLOGY DRAWINGS

FOR ADDITIONAL INFORMATION.

7. NEW PARTITION AS NOTED. ALIGN PARTITION WITH EXISTING WINDOW MULLION.

8. PATCH WALLS AS REQUIRED TO MATCH ADJACENT WALLS TO REMAIN AFTER DEMOLITION OF

NOTED COMPONENTS.

9. PATCH AND PAINT ALL WALLS TO LIKE NEW CONDITION. PAINT COLOR SHALL MATCH EXISTING

CONDITIONS.

10. FIRE EXTINGUISHER CABINET & CLEAN AGENT TYPE FIRE EXTINGUISHER MOUNTED 48” A.F.F.

TO CENTERLINE OF HANDLE. SEE DETAIL 1/A502. PATCH SURROUNDING WALLS .

11. INFILL WALL TO MATCH ADJACENT WALL CONSTRUCTION, INCLUDING FIRE RATING WHERE

REQUIRED.

12. NEW FLOORING AND WALL BASE AS SCHEDULED.

D1. REMOVE EXISTING CEILING GRID TO EXTENT REQUIRED TO COMPLETE WORK SCOPE AND

ACCOMMODATE INSTALLATION OF NEW PARTITIONS. SUPPORT EXISTING CEILING . SALVAGE

CEILING TILES FOR REINSTALLATION. RETURN UNUSED CEILING TILES TO VA FOR STORAGE.

D2. REMOVE EXISTING GYPSUM BOARD CEILING AND FRAMING ABOVE.

D3. REMOVE EXISTING LIGHT FIXTURE. REFER TO ELECTRICAL DRAWINGS FOR FULL SCOPE OF

WORK RELATED TO ELECTRICAL DEMOLITION AND REWORK.

C1. INSTALL NEW CEILING GRID AND EDGE ANGLE. INSTALL SALVAGED CEILING TILES TO

MATCH EXISTING ADJACENT CONDITIONS. INSTALL NEW CEILING TILES WHERE SALVAGED

TILES DO NOT MATCH.

C2. INSTALL NEW CEILING AS SCHEDULED SEE ROOM FINISH LEGEND.

C3. REPOSITION EXISTING LIGHT FIXTURES CENTERED IN ROOM AND WITHIN CEILING GRID.

C4. EXPOSED CEILING.

2. REFER TO DETAIL 2/A-B01-101 FOR NOTES THAT APPLY TO ALL CONNECTING

COORDIOR AREAS

1. INSTALL TEMPORARY FLAME RESISTANT CONSTRUCTION PANELS WITH DOOR ENTRY. BASIS

OF DESIGN IS EDGE GUARD.

2. SUPPLY AND INSTALL WALK OFF MAT(S). SEE DETAILS ON SHEET GI101.

3. EXISTING HANDRAIL, WALL BASE AND CARPET TO BE MODIFIED TO ACCEPT NEW DOOR.

4. REMOVE EXISTING WALL BASE AND EXISTING FLOORING (I.E. CARPET, LAMINATE FLOORING, VCT) TO EXISTING CONCRETE. SCRAPE CLEAN AND REMOVE ALL ASSOCIATED ADHESIVE.

PREP AND LEVEL EXISTING FLOORING TO RECEIVE NEW FINISH PER MANUFACTURE'S

REQUIREMENT.

5. REMOVED EXISTING DOOR, FRAME AND HARDWARE IN ITS ENTIRETY FOR INSTALLATION OF

NEW DOOR AND FRAME. PORTIONS OF EXISTING WALL TO BE DEMOLISHED AND/OR INFILLED

TO RECEIVE NEW DOOR AND FRAME ASSEMBLY. PATCH ADJACENT WALLS TO MATCH

ADJACENT CONDITIONS. ADJACENT ASSEMBLIES SUCH AS CHAIR RAILS, CORNER GUARDS

AND WALL MOUNTED ITEMS MAY NEED TO BE ADJUSTED TO ACCOMMODATE NEW OPENINGS.

6. REMOVE ANY WALL MOUNTED ITEMS, EQUIPMENT, FURNITURE AND ASSOCIATED

COMPONENTS COMPLETE. CONTRACTOR TO ALLOW VA RIGHT OF FIRST REFUSAL OF ANY

REMOVED ITEMS.

7. REMOVE GLASS FROM WINDOW SYSTEM AT THIS LOCATION. PREPARE WINDOW SYSTEM TO

RECEIVE INFILL AS NOTED IN NEW WORK SCOPE.

8. REMOVE EXISTING BASE AND/OR WALL CABINETS, COUNTERTOP, AND ASSOCIATE

COMPONENTS/EQUIPMENT COMPLETE. CAP ANY ASSOCIATED PLUMBING AT SOURCE, REFER

TO PLUMBING DRAWINGS.

9. REMOVE ALL EXISTING TELECOMMUNICATIONS AND ASSOCIATED ELECTRICAL EQUIPMENT

WITHIN EXISTING DATA CENTER UPON COMPLETION OF INFRASTRUCTURE UPGRADES

OUTLINED WITHIN THESE DOCUMENTS. RETURN ALL EQUIPMENT TO THE VA UNLESS

OTHERWISE NOTED.

10. PROTECT EXISTING EQUIPMENT CONTROLS BOX DURING CONSTRUCTION. RECONFIGURE AS

REQUIRED TO ALLOW FOR NEW WALL OPENING.

11. DEMO EXISTING WALL FOR FIRE EXTINGUISHER CABINET. REFER TO FLOOR PLAN KEYNOTE

#10. MODIFY EXISTING WALL MOUNTED ASSEMBLIES TO ALLOW FOR CABINET INSTALLATION.

12. G.C. TO CAREFULLY REMOVE EXISTING WINDOW TREATMENT AND TURN OVER TO VA. VA HAS

RIGHT OF FIRST REFUSAL.

13. G.C. TO CAREFULLY REMOVE EXISTING ROOM SIGN AND TURN OVER TO VA. VA HAS RIGHT OF

FIRST REFUSAL. SEE SIGNAGE SCHEDULE FOR NEW SIGN TYPE AND COPY.

3. REMOVE GYPSUM BOARD CEILING AS REQUIRED FOR MECHANICAL DUCTWORK,

PIPING, ELECTRICAL CONDUIT, TECHNOLOGY EQUIPMENT AND/OR SECURITY

INSTALLATION.

I.T. / DATA

CLOSET

A229

TR

A229A

STORAGE

A229

A229A

B

D1D1

I.T. / DATA

TR

A229A

I.T. / DATA

TR

A229A

ARCHITECTURAL - BUILDING 3 - LEVEL 2

- OVERALL & ENLARGED PLANS

DA JM

A-B03-102

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

K:

\C

C G

_P R

O

JE

C

TS

\2

1\

-1

T op ek a

EH

R M

C

1R

\4

- D es

D oc s\

2- D ra w in gs

\W O

R

KI

N G

\A ut oC

AD

\A -B

-1

.d w g

2/

/2

:5 9:

A

M

ISSUE FOR BIDOffice of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

EHRM INFRASTRUCTURE

UPGRADES

COLMERY O'NEIL VA HEALTH CARE

21-116

Revisions: Date:

www. bancroft-ae.com

3300 Dundee RD.

Northbrook, IL 60062

T: 847.952.9362

03/22/2024Bancroft Project No: 21-116ISSUE FOR BID R2 03-22-24

14. PREP AND LEVEL EXISTING FLOORING TO RECEIVE NEW FINISH PER MANUFACTURER'S

REQUIREMENT.

C5. INSTALL NEW MECHANICAL REGISTER INTO GYPSUM WALL. SEE MECHANICAL DRAWINGS

FOR FURTHER INFORMATION.D4. REMOVE PORTION OF GYPSUM WALL FOR NEW MECHANICAL REGISTER LOCATION. SEE

MECHANICAL DRAWINGS FOR FURTHER INFORMATION.

ADDENDUM #1 11-20-24

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 8'-0"

AutoCAD SHX Text

4'-0" MIN.

AutoCAD SHX Text 2'-0"

AutoCAD SHX Text

AutoCAD SHX Text 4'

AutoCAD SHX Text 8'

AutoCAD SHX Text 16'

AutoCAD SHX Text 32'

AutoCAD SHX Text 1/16"=1'-0"

AutoCAD SHX Text

AutoCAD SHX Text

BUILDING 3 - LEVEL 2 PLAN

AutoCAD SHX Text N

AutoCAD SHX Text

AutoCAD SHX Text 1'

AutoCAD SHX Text 2'

AutoCAD SHX Text 4'

AutoCAD SHX Text 8'

AutoCAD SHX Text 1/4"=1'-0"

AutoCAD SHX Text

AutoCAD SHX Text

BUILDING 03 - ENLARGED PLAN RM A229A

AutoCAD SHX Text

AutoCAD SHX Text 1'

AutoCAD SHX Text 2'

AutoCAD SHX Text 4'

AutoCAD SHX Text 8'

AutoCAD SHX Text 1/4"=1'-0"

AutoCAD SHX Text

AutoCAD SHX Text

BUILDING 03 - ENLARGED DEMOLITION PLAN RM A229A

AutoCAD SHX Text

AutoCAD SHX Text 1'

AutoCAD SHX Text 2'

AutoCAD SHX Text 4'

AutoCAD SHX Text 8'

AutoCAD SHX Text 1/4"=1'-0"

AutoCAD SHX Text

AutoCAD SHX Text

BUILDING 03 - ENLARGED DEMOLITION RCP RM A229A

AutoCAD SHX Text

AutoCAD SHX Text 1'

AutoCAD SHX Text 2'

AutoCAD SHX Text 4'

AutoCAD SHX Text 8'

AutoCAD SHX Text 1/4"=1'-0"

AutoCAD SHX Text

BUILDING 03 - ENLARGED RCP RM A229A

GENERAL NOTES

A. FOR GENERAL NOTES AND LEGENDS REFER TO SHEET A001.

B. FOR GENERAL INFECTION CONTROL NOTES AND DETAILS REFER TO SHEET GI101.

C. EXISTING IT/TR/OI&T ROOMS TO REMAIN ACTIVE DURING CONSTRUCTION. G.C. TO PROTECT

EQUIPMENT DURING CONSTRUCTION WITH VISQUEEN. CONTRACTOR TO ENSURE

CONTINUOUS OPERATION OF EQUIPMENT.

D. NOT ALL KEY NOTES APPLY TO ALL PLAN SHEETS. G.C. TO APPLY ONLY AS INDICATED PER

EACH SHEET.

E. MAINTAIN A 4 ' - 0" CLEAR PATH OF TRAVEL IN THE CORRIDORS AT ALL TIMES.

F. ALL WORK TO BE PERFORMED AS PART OF TR MODIFICATION SHALL BE CONSIDERED AS

TYPE IV AND FOLLOW "INFECTION CONTROL PRECAUTIONS FOR CLASS IV" ON SHEET GI101.

G. APPLY FIRE RATED SEALANT TO ALL EXISTING AND NEW PENETRATIONS IN EXISTING WALLS

TO MAKE EXISTING WALLS A 1 HR ASSEMBLY. BASIS OF DESIGN FOR 1 HR WALL IS UL 419

ASSEMBLY.

H. ALL EXISTING WALLS WITH TR'S ARE TO BE FULLY PATCHED & PREPPED TO A LIKE NEW

APPEARANCE BEFORE RECEIVING NEW PLYWOOD PANELS.

I. IN ALL EXISTING OI&T AND IRM ROOMS TO BE CONVERTED TO TR'S - ALL EXISTING PLYWOOD

PANELS TO BE REMOVED A WALLS PATCHED AND PREPPED TO RECEIVE PAINT AND NEW

PLYWOOD PANELS.

DEMOLITION PLAN KEYNOTES

DEMO CEILING KEYNOTESX CEILING PLAN KEYNOTES

FLOOR PLAN LEGEND

4'X8' AC GRADE 3/4" TRADE SIZE FIRE RATED PLYWOOD BACKBOARD

PAINTED HIGH GLOSS WHITE WITH (2) COATS OF FIRE RESISTANT PAINT

FOR SERVICE PROVIDER /SECURITY/VIDEO/ETC. AROUND PERIMETER

WALLS OF TRS AND ENTRANCE ROOMS AS SHOWN. ENSURE THAT FIRE

RATING STAMP IS TO REMAIN UNCOVERED BY PAINT.

1. REMOVE AND STORE CEILING TILES IN THIS AREA AS REQUIRED FOR

MECHANICAL DUCTWORK, PIPING, ELECTRICAL CONDUIT, TECHNOLOGY

EQUIPMENT AND/OR SECURITY INSTALLATION. REINSTALL TILES AND GRID

WHEN WORK IS COMPLETED. REPLACE ANY DAMAGED TILES AND GRIDS TO

MATCH EXISTING. G.C. SHALL TEMPORARILY ERECT A SUSPENDED PLASTIC

BARRIER 6 MIL AROUND AREA OF CEILING WORK TO BE PERFORMED DURING

ONE SHIFT AND G.C. SHALL REMOVE SUSPENDED PLASTIC BARRIER AT THE

END OF SHIFT. G.C. SHALL MOP CLEAN THIS AREA OF WORK. PRIOR TO

TURNING OVER AREA TO VA. AFTER WORK HOURS WILL REQUIRE ADDITIONAL

COORDINATION WITH THE VA.

FLOOR PLAN KEYNOTESX X

CEILING REMOVAL SCOPE

X

CONTRACTOR IS REQUIRED TO MAINTAIN ALL RATED PARTITIONS.

1HR FIRE BARRIER

1 HR FIRE BARRIER (EXISTING)

RATED PARTITION LEGEND

SMOKE BARRIER

SMOKE BARRIER (EXISTING)

2 HR FIRE BARRIER

2 HR FIRE BARRIER (EXISTING)

1. FINISH WALL CORNER TO CORNER AND FLOOR TO CEILING. PRIOR TO PAINTING THE ENTIRE WALL SURFACE WITH (1) FINISH COAT OF PAINT, PROVIDE (1) PRIME COAT AND (2) FINISH

COATS OVER PATCHED/REPAIRED WALL SURFACES.

2. INSTALL NEW HANDRAIL, NEW CRASH RAIL AND WALL BASE TO CREATE LONG CONTINUOUS

RUN. EXTEND HANDRAIL, CRASH RAIL AND WALL BASE TO NEXT ASSEMBLY JOINT. FOR

DETAILS SEE SHEET A-502.

3. EXISTING GLAZING TO REMAIN. BACK-PAINT GLASS ON INSIDE OF GLAZING. PAINT BLACK

UNLESS OTHERWISE NOTED BY VA.

4. PATCH FLOOR AND PROVIDE NEW WALL BASE AS REQUIRED TO MATCH EXISTING CONDITIONS.

5. PROVIDE INSULATED ALUMINUM PANEL WITHIN WINDOW SYSTEM TO REPLACE PREVIOUS

GLASS PANEL. ALUMINUM FINISH SHALL MATCH WINDOW SYSTEM. SEE DETAIL 3 & 4/AW-602.

6. INSTALL TELECOMMUNICATIONS ENCLOSURE. SEE ELECTRICAL AND TECHNOLOGY DRAWINGS

FOR ADDITIONAL INFORMATION.

7. NEW PARTITION AS NOTED. ALIGN PARTITION WITH EXISTING WINDOW MULLION.

8. PATCH WALLS AS REQUIRED TO MATCH ADJACENT WALLS TO REMAIN AFTER DEMOLITION OF

NOTED COMPONENTS.

9. PATCH AND PAINT ALL WALLS TO LIKE NEW CONDITION. PAINT COLOR SHALL MATCH EXISTING

CONDITIONS.

10. FIRE EXTINGUISHER CABINET & CLEAN AGENT TYPE FIRE EXTINGUISHER MOUNTED 48” A.F.F.

TO CENTERLINE OF HANDLE. SEE DETAIL 1/A502. PATCH SURROUNDING WALLS .

11. INFILL WALL TO MATCH ADJACENT WALL CONSTRUCTION, INCLUDING FIRE RATING WHERE

REQUIRED.

12. NEW FLOORING AND WALL BASE AS SCHEDULED.

D1. REMOVE EXISTING CEILING GRID TO EXTENT REQUIRED TO COMPLETE WORK SCOPE AND

ACCOMMODATE INSTALLATION OF NEW PARTITIONS. SUPPORT EXISTING CEILING . SALVAGE

CEILING TILES FOR REINSTALLATION. RETURN UNUSED CEILING TILES TO VA FOR STORAGE.

D2. REMOVE EXISTING GYPSUM BOARD CEILING AND FRAMING ABOVE.

D3. REMOVE EXISTING LIGHT FIXTURE. REFER TO ELECTRICAL DRAWINGS FOR FULL SCOPE OF

WORK RELATED TO ELECTRICAL DEMOLITION AND REWORK.

C1. INSTALL NEW CEILING GRID AND EDGE ANGLE. INSTALL SALVAGED CEILING TILES TO

MATCH EXISTING ADJACENT CONDITIONS. INSTALL NEW CEILING TILES WHERE SALVAGED

TILES DO NOT MATCH.

C2. INSTALL NEW CEILING AS SCHEDULED SEE ROOM FINISH LEGEND.

C3. REPOSITION EXISTING LIGHT FIXTURES CENTERED IN ROOM AND WITHIN CEILING GRID.

C4. EXPOSED CEILING.

2. REFER TO DETAIL 2/A-B01-101 FOR NOTES THAT APPLY TO ALL CONNECTING

COORDIOR AREAS

1. INSTALL TEMPORARY FLAME RESISTANT CONSTRUCTION PANELS WITH DOOR ENTRY. BASIS

OF DESIGN IS EDGE GUARD.

2. SUPPLY AND INSTALL WALK OFF MAT(S). SEE DETAILS ON SHEET GI101.

3. EXISTING HANDRAIL, WALL BASE AND CARPET TO BE MODIFIED TO ACCEPT NEW DOOR.

4. REMOVE EXISTING WALL BASE AND EXISTING FLOORING (I.E. CARPET, LAMINATE FLOORING, VCT) TO EXISTING CONCRETE. SCRAPE CLEAN AND REMOVE ALL ASSOCIATED ADHESIVE.

PREP AND LEVEL EXISTING FLOORING TO RECEIVE NEW FINISH PER MANUFACTURE'S

REQUIREMENT.

5. REMOVED EXISTING DOOR, FRAME AND HARDWARE IN ITS ENTIRETY FOR INSTALLATION OF

NEW DOOR AND FRAME. PORTIONS OF EXISTING WALL TO BE DEMOLISHED AND/OR INFILLED

TO RECEIVE NEW DOOR AND FRAME ASSEMBLY. PATCH ADJACENT WALLS TO MATCH

ADJACENT CONDITIONS. ADJACENT ASSEMBLIES SUCH AS CHAIR RAILS, CORNER GUARDS

AND WALL MOUNTED ITEMS MAY NEED TO BE ADJUSTED TO ACCOMMODATE NEW OPENINGS.

6. REMOVE ANY WALL MOUNTED ITEMS, EQUIPMENT, FURNITURE AND ASSOCIATED

COMPONENTS COMPLETE. CONTRACTOR TO ALLOW VA RIGHT OF FIRST REFUSAL OF ANY

REMOVED ITEMS.

7. REMOVE GLASS FROM WINDOW SYSTEM AT THIS LOCATION. PREPARE WINDOW SYSTEM TO

RECEIVE INFILL AS NOTED IN NEW WORK SCOPE.

8. REMOVE EXISTING BASE AND/OR WALL CABINETS, COUNTERTOP, AND ASSOCIATE

COMPONENTS/EQUIPMENT COMPLETE. CAP ANY ASSOCIATED PLUMBING AT SOURCE, REFER

TO PLUMBING DRAWINGS.

9. REMOVE ALL EXISTING TELECOMMUNICATIONS AND ASSOCIATED ELECTRICAL EQUIPMENT

WITHIN EXISTING DATA CENTER UPON COMPLETION OF INFRASTRUCTURE UPGRADES

OUTLINED WITHIN THESE DOCUMENTS. RETURN ALL EQUIPMENT TO THE VA UNLESS

OTHERWISE NOTED.

10. PROTECT EXISTING EQUIPMENT CONTROLS BOX DURING CONSTRUCTION. RECONFIGURE AS

REQUIRED TO ALLOW FOR NEW WALL OPENING.

11. DEMO EXISTING WALL FOR FIRE EXTINGUISHER CABINET. REFER TO FLOOR PLAN KEYNOTE

#10. MODIFY EXISTING WALL MOUNTED ASSEMBLIES TO ALLOW FOR CABINET INSTALLATION.

12. G.C. TO CAREFULLY REMOVE EXISTING WINDOW TREATMENT AND TURN OVER TO VA. VA HAS

RIGHT OF FIRST REFUSAL.

13. G.C. TO CAREFULLY REMOVE EXISTING ROOM SIGN AND TURN OVER TO VA. VA HAS RIGHT OF

FIRST REFUSAL. SEE SIGNAGE SCHEDULE FOR NEW SIGN TYPE AND COPY.

3. REMOVE GYPSUM BOARD CEILING AS REQUIRED FOR MECHANICAL DUCTWORK,

PIPING, ELECTRICAL CONDUIT, TECHNOLOGY EQUIPMENT AND/OR SECURITY

INSTALLATION.

CONFRENCE

C150

IT

CLOSET

C146A

RESIDENT

ROOM

C146

PHARMA

CACHE

C147

CONFRENCE

C150

TR

C146

PHARMA

CACHE

C147

CONFRENCE

C150

TR

C146

CORRIDOR

C13

PHARMA

CACHE

C147

C-1

B

B

H

CONFRENCE

C150

IT

CLOSET

C142

CLOSET

C146A

RESIDENT

ROOM

C146

CORRIDOR

C13

PHARMA

CACHE

C147

SEE SHT. AE210

SEE SHT. AE211

RELAXATION

ROOM

B130

CORRIDOR

B1C2

CONFERENCE

ROOM

B132

PHONE

ALCOVE

B131 UP

RELAXATION

ROOM

B130

TR

B130A

CORRIDOR

B1C2

CONFERENCE

ROOM

B132

RESTROOM

B129A

PHONE

ALCOVE

B131

B-130A B

D1

ROOM

B130

CORRIDOR

CONFERENCE

ROOM

B132

ROOM

B130

CONFERENCE

ROOM

B132

ARCHITECTURAL - BUILDING 4 - LEVEL 1

- ENLARGED PLANS

DA JM

A-B04-411

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

K:

\C

C G

_P R

O

JE

C

TS

\2

1\

-1

T op ek a

EH

R M

C

1R

\4

- D es

D oc s\

2- D ra w in gs

\W O

R

KI

N G

\A ut oC

AD

\A -B

-4

.d w g

/1

4/

:1 5:

P

M

ISSUE FOR BIDOffice of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

EHRM INFRASTRUCTURE

UPGRADES

COLMERY O'NEIL VA HEALTH CARE

21-116

Revisions: Date:

www. bancroft-ae.com

3300 Dundee RD.

Northbrook, IL 60062

T: 847.952.9362

03/22/2024Bancroft Project No: 21-116ISSUE FOR BID R2 03-22-24

14. DEMOLISH WALL INFILL AT EXISTING DOOR.

15. REMOVE CORNER GAURD AND TURN OVER TO VA. PREP SURFACE FOR FINISH BY WALL TYPE.

13. EXISTING FRAME TO REMAIN REPAIR IF NECESSARY TO LIKE NEW CONDITION.

D4. REMOVE AND HOLD FOR REINSTALLATION OF EXISTING MECHANICAL REGISTER. SEE

MECHANICAL DRAWINGS FOR FURTHER INFORMATION.

D5. CAREFULLY REMOVE CEILING CURTAIN TRACK AND TURN OVER TO VA. PATCH DAMAGE.

C5. INSTALL NEW MECHANICAL REGISTER. SEE MECHANICAL DRAWINGS FOR FURTHER

INFORMATION.

D6. REMOVE PORTION OF GYPSUM WALL FOR NEW MECHANICAL REGISTER LOCATION. SEE

MECHANICAL DRAWINGS FOR FURTHER INFORMATION.

ADDENDUM #1 11-20-24

AutoCAD SHX Text

ROOM B130A

AutoCAD SHX Text

ROOM C146

AutoCAD SHX Text 5"

AutoCAD SHX Text 3'-4 1/2"

AutoCAD SHX Text 6'-0"

AutoCAD SHX Text

4'-0" MIN.

AutoCAD SHX Text 2'-0"

AutoCAD SHX Text 23'-0"

AutoCAD SHX Text

4'-0" MIN.

AutoCAD SHX Text 2'-0"

AutoCAD SHX Text 8'-0"

AutoCAD SHX Text 2'-0"

AutoCAD SHX Text 10'-2"

AutoCAD SHX Text 10'-2"

AutoCAD SHX Text

KEY PLAN

AutoCAD SHX Text N

AutoCAD SHX Text

AutoCAD SHX Text 1'

AutoCAD SHX Text 2'

AutoCAD SHX Text 4'

AutoCAD SHX Text 8'

AutoCAD SHX Text 1/4"=1'-0"

AutoCAD SHX Text

AutoCAD SHX Text

BUILDING 04 - ENLARGED RCP RM C146

AutoCAD SHX Text

AutoCAD SHX Text 1'

AutoCAD SHX Text 2'

AutoCAD SHX Text 4'

AutoCAD SHX Text 8'

AutoCAD SHX Text 1/4"=1'-0"

AutoCAD SHX Text

AutoCAD SHX Text

BUILDING 04 - ENLARGED PLAN RM C146

AutoCAD SHX Text

AutoCAD SHX Text 1'

AutoCAD SHX Text 2'

AutoCAD SHX Text 4'

AutoCAD SHX Text 8'

AutoCAD SHX Text 1/4"=1'-0"

AutoCAD SHX Text

AutoCAD SHX Text

BUILDING 04 - ENLARGED DEMOLITION PLAN RM C146

AutoCAD SHX Text

AutoCAD SHX Text 1'

AutoCAD SHX Text 2'

AutoCAD SHX Text 4'

AutoCAD SHX Text 8'

AutoCAD SHX Text 1/4"=1'-0"

AutoCAD SHX Text

AutoCAD SHX Text

BUILDING 04 - ENLARGED DEMOLITION RCP RM C146

AutoCAD SHX Text

AutoCAD SHX Text 1'

AutoCAD SHX Text 2'

AutoCAD SHX Text 4'

AutoCAD SHX Text 8'

AutoCAD SHX Text 1/4"=1'-0"

AutoCAD SHX Text

AutoCAD SHX Text

BUILDING 04 - ENLARGED DEMOLITION PLAN RM B130

AutoCAD SHX Text

AutoCAD SHX Text 1'

AutoCAD SHX Text 2'

AutoCAD SHX Text 4'

AutoCAD SHX Text 8'

AutoCAD SHX Text 1/4"=1'-0"

AutoCAD SHX Text

AutoCAD SHX Text

BUILDING 04 - ENLARGED PLAN RM B130A

AutoCAD SHX Text

AutoCAD SHX Text 1'

AutoCAD SHX Text 2'

AutoCAD SHX Text 4'

AutoCAD SHX Text 8'

AutoCAD SHX Text 1/4"=1'-0"

AutoCAD SHX Text

AutoCAD SHX Text

BUILDING 04 - ENLARGED DEMOLITION RCP RM B130

AutoCAD SHX Text

AutoCAD SHX Text 1'

AutoCAD SHX Text 2'

AutoCAD SHX Text 4'

AutoCAD SHX Text 8'

AutoCAD SHX Text 1/4"=1'-0"

AutoCAD SHX Text

BUILDING 04 - ENLARGED RCP RM B130A

DNDN

UP

A

B226A

B214A

B2

B

B214

B214C B215

B213 B212

B215E

B211E

B2

P

B217/B218

B211 B210

B209

B208

B223A B223B

B223

B220F

B220

B219

B221

B223C

B224

B225

B222

B207

B207A

B206 B205 B204

B203

B226B

B2-C1

B2

A202

A230

C251

C250

C2

C247 C246 C245D C245C

C245B C241

C242

C244 C245

C2

A

C240

C252A

C252

C253A C253

C239

C238F

C237

C236BC236A

C236CC236

C235

C238C234

C233BC223A

C249 C248 C255C256

A232A229

A228FB226

A2-C1 C2-C1

A231

C244E

C247E

C2

P

A201E

A202E

A227

A257

A228

A201

C254

C233

B C D E F G H J K L M N P Q R S T

EL-1 C233C

1&2 M-05-421

2&4

FP-05-421

1,2,3&4 A-05-102

GENERAL NOTES

A. FOR GENERAL NOTES AND LEGENDS REFER TO SHEET A001.

B. FOR GENERAL INFECTION CONTROL NOTES AND DETAILS REFER TO SHEET GI101.

C. EXISTING IT/TR/OI&T ROOMS TO REMAIN ACTIVE DURING CONSTRUCTION. G.C. TO PROTECT

EQUIPMENT DURING CONSTRUCTION WITH VISQUEEN. CONTRACTOR TO ENSURE

CONTINUOUS OPERATION OF EQUIPMENT.

D. NOT ALL KEY NOTES APPLY TO ALL PLAN SHEETS. G.C. TO APPLY ONLY AS INDICATED PER

EACH SHEET.

E. MAINTAIN A 4 ' - 0" CLEAR PATH OF TRAVEL IN THE CORRIDORS AT ALL TIMES.

F. ALL WORK TO BE PERFORMED AS PART OF TR MODIFICATION SHALL BE CONSIDERED AS

TYPE IV AND FOLLOW "INFECTION CONTROL PRECAUTIONS FOR CLASS IV" ON SHEET GI101.

G. APPLY FIRE RATED SEALANT TO ALL EXISTING AND NEW PENETRATIONS IN EXISTING WALLS

TO MAKE EXISTING WALLS A 1 HR ASSEMBLY. BASIS OF DESIGN FOR 1 HR WALL IS UL 419

ASSEMBLY.

H. ALL EXISTING WALLS WITH TR'S ARE TO BE FULLY PATCHED & PREPPED TO A LIKE NEW

APPEARANCE BEFORE RECEIVING NEW PLYWOOD PANELS.

I. IN ALL EXISTING OI&T AND IRM ROOMS TO BE CONVERTED TO TR'S - ALL EXISTING PLYWOOD

PANELS TO BE REMOVED A WALLS PATCHED AND PREPPED TO RECEIVE PAINT AND NEW

PLYWOOD PANELS.

DEMOLITION PLAN KEYNOTES

DEMO CEILING KEYNOTESX CEILING PLAN KEYNOTES

FLOOR PLAN LEGEND

4'X8' AC GRADE 3/4" TRADE SIZE FIRE RATED PLYWOOD BACKBOARD

PAINTED HIGH GLOSS WHITE WITH (2) COATS OF FIRE RESISTANT PAINT

FOR SERVICE PROVIDER /SECURITY/VIDEO/ETC. AROUND PERIMETER

WALLS OF TRS AND ENTRANCE ROOMS AS SHOWN. ENSURE THAT FIRE

RATING STAMP IS TO REMAIN UNCOVERED BY PAINT.

1. REMOVE AND STORE CEILING TILES IN THIS AREA AS REQUIRED FOR

MECHANICAL DUCTWORK, PIPING, ELECTRICAL CONDUIT, TECHNOLOGY

EQUIPMENT AND/OR SECURITY INSTALLATION. REINSTALL TILES AND GRID

WHEN WORK IS COMPLETED. REPLACE ANY DAMAGED TILES AND GRIDS TO

MATCH EXISTING. G.C. SHALL TEMPORARILY ERECT A SUSPENDED PLASTIC

BARRIER 6 MIL AROUND AREA OF CEILING WORK TO BE PERFORMED DURING

ONE SHIFT AND G.C. SHALL REMOVE SUSPENDED PLASTIC BARRIER AT THE

END OF SHIFT. G.C. SHALL MOP CLEAN THIS AREA OF WORK. PRIOR TO

TURNING OVER AREA TO VA. AFTER WORK HOURS WILL REQUIRE ADDITIONAL

COORDINATION WITH THE VA.

FLOOR PLAN KEYNOTESX X

CEILING REMOVAL SCOPE

X

CONTRACTOR IS REQUIRED TO MAINTAIN ALL RATED PARTITIONS.

1HR FIRE BARRIER

1 HR FIRE BARRIER (EXISTING)

RATED PARTITION LEGEND

SMOKE BARRIER

SMOKE BARRIER (EXISTING)

2 HR FIRE BARRIER

2 HR FIRE BARRIER (EXISTING)

1. FINISH WALL CORNER TO CORNER AND FLOOR TO CEILING. PRIOR TO PAINTING THE ENTIRE WALL SURFACE WITH (1) FINISH COAT OF PAINT, PROVIDE (1) PRIME COAT AND (2) FINISH

COATS OVER PATCHED/REPAIRED WALL SURFACES.

2. INSTALL NEW HANDRAIL, NEW CRASH RAIL AND WALL BASE TO CREATE LONG CONTINUOUS

RUN. EXTEND HANDRAIL, CRASH RAIL AND WALL BASE TO NEXT ASSEMBLY JOINT. FOR

DETAILS SEE SHEET A-502.

3. EXISTING GLAZING TO REMAIN. BACK-PAINT GLASS ON INSIDE OF GLAZING. PAINT BLACK

UNLESS OTHERWISE NOTED BY VA.

4. PATCH FLOOR AND PROVIDE NEW WALL BASE AS REQUIRED TO MATCH EXISTING CONDITIONS.

5. PROVIDE INSULATED ALUMINUM PANEL WITHIN WINDOW SYSTEM TO REPLACE PREVIOUS

GLASS PANEL. ALUMINUM FINISH SHALL MATCH WINDOW SYSTEM. SEE DETAIL 3 & 4/AW-602.

6. INSTALL TELECOMMUNICATIONS ENCLOSURE. SEE ELECTRICAL AND TECHNOLOGY DRAWINGS

FOR ADDITIONAL INFORMATION.

7. NEW PARTITION AS NOTED. ALIGN PARTITION WITH EXISTING WINDOW MULLION.

8. PATCH WALLS AS REQUIRED TO MATCH ADJACENT WALLS TO REMAIN AFTER DEMOLITION OF

NOTED COMPONENTS.

9. PATCH AND PAINT ALL WALLS TO LIKE NEW CONDITION. PAINT COLOR SHALL MATCH EXISTING

CONDITIONS.

10. FIRE EXTINGUISHER CABINET & CLEAN AGENT TYPE FIRE EXTINGUISHER MOUNTED 48” A.F.F.

TO CENTERLINE OF HANDLE. SEE DETAIL 1/A502. PATCH SURROUNDING WALLS .

11. INFILL WALL TO MATCH ADJACENT WALL CONSTRUCTION, INCLUDING FIRE RATING WHERE

REQUIRED.

12. NEW FLOORING AND WALL BASE AS SCHEDULED.

D1. REMOVE EXISTING CEILING GRID TO EXTENT REQUIRED TO COMPLETE WORK SCOPE AND

ACCOMMODATE INSTALLATION OF NEW PARTITIONS. SUPPORT EXISTING CEILING . SALVAGE

CEILING TILES FOR REINSTALLATION. RETURN UNUSED CEILING TILES TO VA FOR STORAGE.

D2. REMOVE EXISTING GYPSUM BOARD CEILING AND FRAMING ABOVE.

D3. REMOVE EXISTING LIGHT FIXTURE. REFER TO ELECTRICAL DRAWINGS FOR FULL SCOPE OF

WORK RELATED TO ELECTRICAL DEMOLITION AND REWORK.

C1. INSTALL NEW CEILING GRID AND EDGE ANGLE. INSTALL SALVAGED CEILING TILES TO

MATCH EXISTING ADJACENT CONDITIONS. INSTALL NEW CEILING TILES WHERE SALVAGED

TILES DO NOT MATCH.

C2. INSTALL NEW CEILING AS SCHEDULED SEE ROOM FINISH LEGEND.

C3. REPOSITION EXISTING LIGHT FIXTURES CENTERED IN ROOM AND WITHIN CEILING GRID.

C4. EXPOSED CEILING.

2. REFER TO DETAIL 2/A-B01-101 FOR NOTES THAT APPLY TO ALL CONNECTING

COORDIOR AREAS

1. INSTALL TEMPORARY FLAME RESISTANT CONSTRUCTION PANELS WITH DOOR ENTRY. BASIS

OF DESIGN IS EDGE GUARD.

2. SUPPLY AND INSTALL WALK OFF MAT(S). SEE DETAILS ON SHEET GI101.

3. EXISTING HANDRAIL, WALL BASE AND CARPET TO BE MODIFIED TO ACCEPT NEW DOOR.

4. REMOVE EXISTING WALL BASE AND EXISTING FLOORING (I.E. CARPET, LAMINATE FLOORING, VCT) TO EXISTING CONCRETE. SCRAPE CLEAN AND REMOVE ALL ASSOCIATED ADHESIVE.

PREP AND LEVEL EXISTING FLOORING TO RECEIVE NEW FINISH PER MANUFACTURE'S

REQUIREMENT.

5. REMOVED EXISTING DOOR, FRAME AND HARDWARE IN ITS ENTIRETY FOR INSTALLATION OF

NEW DOOR AND FRAME. PORTIONS OF EXISTING WALL TO BE DEMOLISHED AND/OR INFILLED

TO RECEIVE NEW DOOR AND FRAME ASSEMBLY. PATCH ADJACENT WALLS TO MATCH

ADJACENT CONDITIONS. ADJACENT ASSEMBLIES SUCH AS CHAIR RAILS, CORNER GUARDS

AND WALL MOUNTED ITEMS MAY NEED TO BE ADJUSTED TO ACCOMMODATE NEW OPENINGS.

6. REMOVE ANY WALL MOUNTED ITEMS, EQUIPMENT, FURNITURE AND ASSOCIATED

COMPONENTS COMPLETE. CONTRACTOR TO ALLOW VA RIGHT OF FIRST REFUSAL OF ANY

REMOVED ITEMS.

7. REMOVE GLASS FROM WINDOW SYSTEM AT THIS LOCATION. PREPARE WINDOW SYSTEM TO

RECEIVE INFILL AS NOTED IN NEW WORK SCOPE.

8. REMOVE EXISTING BASE AND/OR WALL CABINETS, COUNTERTOP, AND ASSOCIATE

COMPONENTS/EQUIPMENT COMPLETE. CAP ANY ASSOCIATED PLUMBING AT SOURCE, REFER

TO PLUMBING DRAWINGS.

9. REMOVE ALL EXISTING TELECOMMUNICATIONS AND ASSOCIATED ELECTRICAL EQUIPMENT

WITHIN…