Attachment 18 -589A5-21-700_Topeka EHRM_IFB R2 Drawings_Vol 2_1-110.pdf

PDF 31 MB Posted

Attached to
Y1DA--589A5-21-700 EHRM INFRASTRUCTURE UPGRADES (VA-24-00076324) Topeka, KS
Solicitation number
36C77624B0026_1
Issued by

About this file

This document appears to be Attachment 18 containing drawings for the EHRM Infrastructure Upgrades solicitation for the Department of Veterans Affairs in Topeka, Kansas. The solicitation number is 36C77624B0026_1 and the contract opportunity ID is 9321494a8d024df6b1351e1cc5ad2967. This is an Invitation for Bid (IFB) for infrastructure upgrades at the Topeka VA facility as part of the Enterprise Health Record Modernization (EHRM) program. The drawings included in this attachment provide detailed design specifications for the infrastructure upgrades required under this contract. No additional details about the specific products, services, timeline, or pricing are included in this attachment.

View the file

Other files

File Type Posted
36C77624B0026 0007.docx DOCX document
36C77624B0026 0006.docx DOCX document
Government Answers to Contractor questions.docx DOCX document
Add Spec Section 23 21 13 Attachment A.pdf PDF
Revised Vol3 Drawing_M503.pdf PDF
Revised Spec Section 23 21 13.pdf PDF
36C77624B0026 0005.docx DOCX document
Pages from Addendum1_Vol2_2of2__20241209.pdf PDF
Colmery-ONeil VA Medical Center - Asbestos and Lead Survey Report signed.pdf PDF
Submittal 024 Pipe - Valve- Fittings 8-8-17.pdf PDF
589A5-21-700_TOPEKA_EHRM_SURVEY LOCATIONS-Markup.pdf PDF
Pages from Addendum1_Vol2_1of2__20241209.pdf PDF
EHRM Contractor Parking and Laydown.pdf PDF
Addendum1_Specifications_20241209.pdf PDF
Addendum1_Vol3_2of3_20241209.pdf PDF
230415-000 Topeka VA Geotech Final Report_S.pdf PDF
Addendum1_Vol3_1of3_20241209.pdf PDF
Addendum1_Vol3_3of3_20241209.pdf PDF
36C77624B0026 0004.docx DOCX document
589A5-21-700_Topeka KS_EHRM_Tech Q1_20241210.docx DOCX document
589A5-21-700_Topeka EHRM_IFB_BOD_Blast.pdf PDF
589A5-21-700_19550421_Steam Distro Plot Plan.pdf PDF
Submittal 023B Perma Pipe Fittings 8-21-17.pdf PDF
589A5-21-700_Topeka KS_EHRM_Tech Q2_20241210.docx DOCX document
Addendum1_Vol1_20241209.pdf PDF
36C77624B0026 0003.docx DOCX document
36C77624B0026 0002.docx DOCX document
S04_Site Visit Sign-in Sheet_Topeka KS.pdf PDF
S06- 36C77624B0026 0001.docx DOCX document
Attachment 1 - 589A5-21-700_Topeka EHRM__SOWV3.docx DOCX document
Attachment 16 - 589A5-21-700_Topeka EHRM_IFB R2 Drawings_Vol 3_1.pdf PDF
Attachment 15 - 589A5-21-700_Topeka EHRM_IFB R2 Drawings_Vol 2-8.pdf PDF
Attachment 10 -589A5-21-700_Topeka EHRM_IFB R2 Drawings_Vol 91-129.pdf PDF
Attachment 3 - DB Wage Determination Topeka-KS.pdf PDF
Attachment 8 -589A5-21-700_Topeka EHRM_IFB R2 Drawings_Vol 3_1-90.pdf PDF
Attachment 4 -589A5-21-700_Topeka EHRM_IFB R2 Drawings_Vol 2_118-180.pdf PDF
Attachment 11 -589A5-21-700_Topeka EHRM_IFBR2_Spec-VOL1_032224.pdf PDF
Attachment 5 -589A5-21-700_Topeka EHRM_IFB R2 Drawings_Vol 2_181-240.pdf PDF
Attachment 14 - 589A5-21-700_Topeka EHRM_IFB R2 Drawings_Vol 1_134-204.pdf PDF
Attachment 13 - 589A5-21-700_Topeka EHRM_IFB R2 Drawings_Vol 1_1-18.pdf PDF
Attachment 9 -589A5-21-700_Topeka EHRM_IFB R2 Drawings_Vol 3-2.pdf PDF
Attachment 12 -589A5-21-700_Topeka EHRM_IFBR2_Spec-VOL2_032224.pdf PDF
Attachment 20 -Site Visit Instructions.docx DOCX document
Attachment 19 -589A5-21-700_Topeka EHRM_IFB R2 Drawings_Vol 2_111-117.pdf PDF
Attachment 6 -589A5-21-700_Topeka EHRM_IFB R2 Drawings_Vol 2_241-281.pdf PDF
36C77624B0026_1.docx DOCX document
Attachment 2- Limitations on Subcontracting - Construction.docx DOCX document
Attachment 7 -589A5-21-700_Topeka EHRM_IFB R2 Drawings_Vol 2-7.pdf PDF
Attachment 17 -589A5-21-700_Topeka EHRM_IFB R2 Drawings_Vol 1_19-133.pdf PDF
Show all 49

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

GENERAL - COVER SHEET - VOLUME 2

DA JM

G-005

ARCHITECTS + ENGINEERS:

3300 DUNDEE RD.

NORTHBROOK, IL 60062

www.bancroft-ae.com

BANCROFT ARCHITECTS + ENGINEERS

U.S. Department of Veterans Affairs

N

NOT TO SCALE

VICINITY MAP

N

NOT TO SCALE

CAMPUS MAP

N

NOT TO SCALE

REGIONAL MAP

ARCHITECT

PROFESSIONAL SEALS

ELECTRICAL

MECHANICAL

PLUMBING

TOPEKA

STRUCTURAL

CIVIL

NOTE: SEE SHEET GI201 FOR IDENTIFICATION OF CAMPUS BUILDINGS.

TELECOMMUNICATIONS

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

K:

\C

C G

_P R

O

JE

C

TS

\2

1\

-1

T op ek a

EH

R M

C

1R

\4

- D es

D oc s\

2- D ra w in gs

\W O

R

KI

N G

\A ut oC

AD

\G

5.

dw g 3/

/2

2:

:0

PM

ISSUE FOR BIDOffice of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

EHRM INFRASTRUCTURE

UPGRADES

COLMERY O'NEIL VA HEALTH CARE

21-116

Revisions: Date:

www. bancroft-ae.com

3300 Dundee RD.

Northbrook, IL 60062

T: 847.952.9362

35% SCHEMATIC DESIGN SUBMISSION 07-12-22

95% CONSTRUCTION DOCUMENTS SUBMISSION 10-31-23

100% CONSTRUCTION DOCUMENTS SUBMISSION

03/22/2024

12-19-23

Bancroft Project No: 21-116

35% SCHEMATIC DESIGN SUBMISSION R1 09-21-22

35% SUBMITTAL II 06-13-23

65% DESIGN DEVELOPMENT SUBMITTAL 09-12-23

ISSUED FOR BID 12-28-23

ISSUE FOR BID R1 02-28-24

ISSUE FOR BID R2 03-22-24

STRUCTURAL + CIVIL ENGINEER:

909 MONTGOMERY STREET, STE

260, SAN FRANCISCO, CA 94133

www.hohbach-lewin.com

HOBACH-LEWIN

ABATEMENT CONSULTANT:

15620 WEST 113th STREET

LENEXA, KS 66219

www.terracon.com

TERRACON CONSULTANTS

2200 SW GAGE BLVD.

TOPEKA, KS 66622

PROJECT LOCATION:

MARCH 22, 2024

ISSUE FOR BID REV 2

Buildings: 1,2,3,4,5,6,9,19,20,21,22,23,24,25,40,41,42,43, 44,45,48,49,50,51,53,54,55,56,57,58,273

VOLUME 2 OF 3

EHRM INFRASTRUCTURE UPGRADES

VA CONTRACT NUMBER: 36C77622C0043

VA PROJECT NUMBER: 589A5-21-700

BANCROFT-AE PROJECT NUMBER: 21-116

COLMERY-O'NEIL VA MEDICAL CENTER

PROJECT TITLE:

mgonser Snapshot mgonser Snapshot mgonser Snapshot mgonser Snapshot mgonser Snapshot mgonser Snapshot mgonser Snapshot mgonser Snapshot

GENERAL - DRAWING INDEX (VOLUME 1

OF 3)

DA JM

G-006

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

K:

\C

C G

_P R

O

JE

C

TS

\2

1\

-1

T op ek a

EH

R M

C

1R

\4

- D es

D oc s\

2- D ra w in gs

\W O

R

KI

N G

\A ut oC

AD

\G

6-

VO

L1 .d w g

/3

0/

:4 5:

P

M

ISSUE FOR BIDOffice of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

EHRM INFRASTRUCTURE

UPGRADES

COLMERY O'NEIL VA HEALTH CARE

21-116

Revisions: Date:

www. bancroft-ae.com

3300 Dundee RD.

Northbrook, IL 60062

T: 847.952.9362

35% SCHEMATIC DESIGN SUBMISSION 07-12-22

95% CONSTRUCTION DOCUMENTS SUBMISSION 10-31-23

100% CONSTRUCTION DOCUMENTS SUBMISSION

03/22/2024

12-19-23

Bancroft Project No: 21-116

35% SCHEMATIC DESIGN SUBMISSION R1 09-21-22

35% SUBMITTAL II 06-13-23

65% DESIGN DEVELOPMENT SUBMITTAL 09-12-23

ISSUED FOR BID 12-28-23

ISSUE FOR BID R1 02-28-24

ISSUE FOR BID R2 03-22-24

GENERAL - DRAWING INDEX (VOLUME 2

DA JM

G-00

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

K:

\C

C G

_P R

O

JE

C

TS

\2

1\

-1

T op ek a

EH

R M

C

1R

\4

- D es

D oc s\

2- D ra w in gs

\W O

R

KI

N G

\A ut oC

AD

\G

3-

VO

L2 .d w g

3/

/2

4:

:3

PM

ISSUE FOR BIDOffice of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

EHRM INFRASTRUCTURE

UPGRADES

COLMERY O'NEIL VA HEALTH CARE

21-116

Revisions: Date:

www. bancroft-ae.com

3300 Dundee RD.

Northbrook, IL 60062

T: 847.952.9362

35% SCHEMATIC DESIGN SUBMISSION 07-12-22

95% CONSTRUCTION DOCUMENTS SUBMISSION 10-31-23

100% CONSTRUCTION DOCUMENTS SUBMISSION

03/22/2024

12-19-23

Bancroft Project No: 21-116

35% SCHEMATIC DESIGN SUBMISSION R1 09-21-22

35% SUBMITTAL II 06-13-23

65% DESIGN DEVELOPMENT SUBMITTAL 09-12-23

ISSUED FOR BID 12-28-23

ISSUE FOR BID R1 02-28-24

ISSUE FOR BID R2 03-22-24

mgonser Snapshot mgonser Text Box

GENERAL - DRAWING INDEX (VOLUME 3

DA JM

G-008

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

K:

\C

C G

_P R

O

JE

C

TS

\2

1\

-1

T op ek a

EH

R M

C

1R

\4

- D es

D oc s\

2- D ra w in gs

\W O

R

KI

N G

\A ut oC

AD

\G

4-

VO

L3 .d w g

3/

/2

5:

:4

PM

ISSUE FOR BIDOffice of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

EHRM INFRASTRUCTURE

UPGRADES

COLMERY O'NEIL VA HEALTH CARE

21-116

Revisions: Date:

www. bancroft-ae.com

3300 Dundee RD.

Northbrook, IL 60062

T: 847.952.9362

35% SCHEMATIC DESIGN SUBMISSION 07-12-22

95% CONSTRUCTION DOCUMENTS SUBMISSION 10-31-23

100% CONSTRUCTION DOCUMENTS SUBMISSION

03/22/2024

12-19-23

Bancroft Project No: 21-116

35% SCHEMATIC DESIGN SUBMISSION R1 09-21-22

35% SUBMITTAL II 06-13-23

65% DESIGN DEVELOPMENT SUBMITTAL 09-12-23

ISSUED FOR BID 12-28-23

ISSUE FOR BID R1 02-28-24

ISSUE FOR BID R2 03-22-24

NOTES:

1. ALL DIMENSIONS ARE CONSIDERED FROM FINISHED FLOOR AND, UNLESS NOTED OTHERWISE, SHALL NOT VARY. RAISED FLOORS SHALL BE

CONSIDERED FINISHED FLOOR.

2. ALL DIMENSIONS SHALL BE COORDINATED WITH ARCHITECTURAL DETAILS AND MAY BE ADJUSTED TO CONFORM WITH ARCHITECTURAL REQUIREMENTS AS LONG AS NO CODE RESTRICTION IS VIOLATED.

3. OUTLETS INSTALLED LOWER THAN 15" AFF (FORWARD REACH) AND 9" AFF (SIDE REACH) ARE IN

VIOLATION OF ADA.

SPECIAL NOTES:

1. EXIT SIGNS SHALL NOT BE INSTALLED IN A MANNER THAT THE SIGN WILL BLOCK FIRE ALARM VISUAL DEVICES.

2. FOR LIGHTING FIXTURES MOUNTING HEIGHTS SEE SCHEDULE AND DRAWINGS.

48" TO HIGHEST OPERABLE PART (SIDE OR FORWARD ACCESS).

80" TO BOTTOM OF DEVICE OR NOT MORE THAN 96" TO TOP.FIRE ALARM VISUAL ONLY DEVICE OR A COMBINATION AUDIBLE AND

VISUAL DEVICE

NOT LESS THAN 90" TO TOP OR 6" BELOW CEILING, WHICH EVER IS

HIGHER.

48" TO CENTERLINE OF BOX - NOT MORE THAN 5'-0" FROM EXIT.

54" TO DIAL CENTER (NON-ACCESSIBLE).

48" TO HIGHEST OPERABLE PART (ACCESSIBLE).

AS NOTED ON DRAWINGS.

EXCEPTION: 44" MAXIMUM TO TOP ABOVE COUNTERS WHICH ARE

20"-25"D.

16" TO BOTTOM OF BOX OR AS NOTED ON DRAWINGS. EXCEPTION: 44"

MAXIMUM TO TOP ABOVE COUNTERS WHICH ARE 20"-25"D.

16" TO BOTTOM OF BOX.

EXCEPTION: 44" MAXIMUM TO TOP ABOVE COUNTERS WHICH ARE

20"-25"D.

90" TO CENTERLINE OF SIGN OR CENTERED IN WALL AREA BETWEEN TOP

OF DOOR AND CEILING.

48" TO CENTERLINE OF BOX.

EXCEPTION: 44" MAXIMUM TO TOP ABOVE COUNTERS WHICH ARE

20"-25"D.

MOUNTING HEIGHTSDEVICE 1. SEE ALL PROJECT GENERAL NOTES AND OTHER

REQUIREMENTS THE LIFE SAFETY AND INFECTION CONTROL

REQUIREMENTS LOCATED WITHIN GENERAL DRAWINGS "G"

SECTION. COMPLY WITH ALL REQUIREMENT AS THEY ARE A

DIRECT PART OF THIS SECTION AND AS IF THEY WERE

DIRECTLY INCLUDED AND PROVIDED BELOW.

2. BASIS OF DESIGN PROTOCOLS:

DESIGN IS BASED ON LISTED MANUFACTURER MENTIONED

ON ALL ELECTRICAL AND ALL SPECIAL SYSTEM DRAWINGS

INCLUDING BUT NOT LIMITED TO VARIOUS ELECTRICAL

EQUIPMENTS, DEVICES, LIGHT FIXTURES, LIGHTING

CONTROLS, AND ALL SPECIAL SYSTEM DEVICES.

CONTRACTOR SHALL BE RESPONSIBLE TO ENSURE THAT ALL

EQUAL PRODUCTS SHALL MEETS OR EXCEEDS THE DESIGN

INTENT, PERFORMANCE, OUTLINE DIMENSION, WEIGHT ETC.

EQUAL PRODUCT SHOP SUBMITTALS SHALL BE REJECTED

UNLESS CONTRACTOR PROVIDES WRITTEN STATEMENT

INDICATING IT MATCHES 100% PERFORMANCE SPECS AND

ALL ABOVE CRITERIA. EQUAL PRODUCT SHOP SUBMITTAL

NOT MEETING ABOVE CRITERIA SHALL BE REVIEWED AND/OR

SELECTED EQUAL PRODUCTS REQUIRES RE-DESIGN THAT

WILL BE AT THE COST TO THE CONTRACTOR INCLUDING

DELAY OF PROJECT DUE TO THIS PROCESS. ALTERNATIVELY

EQUAL PRODUCTS ALONG WITH LETTER INDICATING

CONTRACTOR IS RESPONSIBLE FOR MEETING DESIGN

INTENT/CRITERA SHALL BE SUBMITTED AND APPROVED FROM

VA/COR BEFORE BID AND VA/COR APPROVAL PROOF SHALL

BE SUBMITTED ALONG WITH SHOP SUBMITTAL FOR REVIEW.

EQUIVALENCY SUBSTITUTIONS: THE “BASIS OF DESIGN (BOD)

PROTOCOLS” ARE TO BE FOLLOWED FOR ALL EQUIPMENT,

MATERIALS AND ASSEMBLIES SPECIFIED AND DETAILED

THROUGHOUT ALL DRAWINGS AND SPECIFICATION

SECTIONS, WHETHER THE BOD DESIGNATE IS SPECIFICALLY

REFERENCED THEREIN OR NOT. SEE THE "G" GENERAL

DRAWINGS SECTION FOR THE FULL BOD EQUIVALENCY

SUBSTITUTION REQUIREMENTS AND PROTOCOLS TO BE

FOLLOWED.

3. CODES:

THE WORK SHALL COMPLY WITH ALL APPLICABLE, MUNICIPAL,

STATE, NATIONAL CODES, AND ALL VA APPLICABLE DESIGN

MANUALS STANDARDS REQUIREMENTS. WHERE THE

CONSTRUCTION DOCUMENTS INDICATE MORE RESTRICTIVE

REQUIREMENTS THE CONSTRUCTION DOCUMENTS SHALL

GOVERN. HOWEVER, THE CONSTRUCTION DOCUMENTS

SHALL NOT BE INTERPRETED AS AUTHORITY TO VIOLATE ANY

CODE OR REGULATION.

A EQUIPMENT SHALL

COMPLY WITH ALL REQUIREMENTS OF THE LATEST EDITIONS

AND INTERIM AMENDMENTS OF THE NATIONAL ELECTRICAL

CODE (N.E.C.), NATIONAL ELECTRICAL SAFETY CODE, OSHA,

AND ALL APPLICABLE FEDERAL, STATE, AND LOCAL LAWS

AND ORDINANCES. ALL ELECTRICAL EQUIPMENT PROVIDED

UNDER THIS CONTRACT SHALL BE NEW (EXCEPT WHERE

OTHERWISE NOTED) AND SHALL SHALL BEAR THE MARK OF

NATIONALLY RECOGNIZED TESTING LABORATORY, WHEN

APPLICABLE. ALL EQUIPMENT OF THE SAME TYPE AND

CAPACITY SHALL BE BY THE SAME MANUFACTURER.

4. DRAWINGS AND SPECIFICATIONS:

THE CONTRACTOR SHALL BE RESPONSIBLE FOR READING

AND COMPLYING WITH BOTH THE DRAWINGS AND

SPECIFICATIONS. IN THE EVENT OF A CONFLICT OR

INCONSISTENCY BETWEEN THE DRAWINGS, NOTES,

SPECIFICATIONS, OR CODES, THE REFERENCE WHICH

PROVIDES THE MORE COMPLETE OR HIGHER STANDARD

SHALL PREVAIL UNLESS OTHERWISE CLARIFIED BY OWNER.

CONTRACTOR SHALL REVIEW ENTIRE SET OF CONTRACT

DOCUMENTS: INCLUDING BUT NOT NECESSARILY LIMITED TO

ALL ARCHITECTURAL, ALL STRUCTURAL, ALL MECHANICAL,

ALL ELECTRICAL, ALL PLUMBING, AND ENTIRE PROJECT

MANUAL. CONTRACTOR SHALL ACKNOWLEDGE AND INCLUDE

IN THE SCOPE OF WORK (CONTRACT) ALL CONDITIONS

PERTINENT TO THE COMPLETION OF THE ELECTRICAL WORK.

CONTRACTOR SHALL FULLY COORDINATE ELECTRICAL WORK

WITH THE INSTALLATION OF WORK BY ALL OTHER TRADES

AND MAKE NECESSARY FIELD ADJUSTMENTS AS REQUIRED

TO ACCOMMODATE THE ELECTRICAL INSTALLATION. ALL OF

THE ABOVE SHALL BE INCLUDED IN THE SCOPE OF WORK AT

NO ADDITIONAL COST TO THE VA.

5. INTERPRETATION OF THE DOCUMENTS:

CAREFULLY COMPARE THE DRAWINGS AND SPECIFICATIONS,

CHECKING MEASUREMENTS AND CONDITIONS UNDER WHICH

THIS INSTALLATION IS TO BE MADE. FOR CLARIFICATION

BETWEEN VARIOUS DRAWINGS, BETWEEN DRAWINGS OR

SPECIFICATION, OR BETWEEN SECTIONS OF THE

SPECIFICATION, THE MATTER SHALL BE REFERRED TO THE

VA/COR FOR CLARIFICATION AND APPROVAL BEFORE ANY

WORK IS EXECUTED. THE CONTRACTOR SHALL STATE IN

THEIR PROPOSAL ANY EXCEPTIONS NECESSARY TO MAKE

THIS A COMPLETE, READY TO USE INSTALLATION. IF NOT

STATED IN THEIR BID, IT WILL NOT BE CONSIDERED EXTRA.

ALL WORK SHALL BE DONE IN ACCORDANCE WITH THE

CONTRACT DOCUMENTS, IN A NEAT AND WORKABLE MANNER

CONSISTENT WITH RECOGNIZED GOOD PRACTICE, AND

SHALL BE SUBJECT TO THE APPROVAL OF THE VA/CO.

ANY CHANGES TO THE CONTRACT REQUIREMENTS MUST BE

APPROVED PRIOR TO CONSTRUCTION. THE CONTRACTOR

SHALL KEEP UP-TO-DATE AS-BUILT DRAWINGS, ON-SITE,

AVAILABLE FOR INSPECTION AT ANY TIME OF THE EXACT

NATURE OF WORK, INCLUDING ALLOWABLE DEVIATIONS

FROM THE CONTRACT DRAWINGS, FOR THE PURPOSE OF

RECORD DOCUMENTS.

6. ELECTRICAL DRAWINGS

THE ELECTRICAL DRAWINGS ARE DIAGRAMMATIC AND SHALL

NOT BE SCALED. THE CONTRACTOR SHALL DETERMINE THE

EXACT LOCATION OF ALL DOORS, WALLS, FURNITURE,

EQUIPMENT, ETC.. THE LOCATION OF RACEWAY SYSTEM

COMPONENTS IS SCHEMATIC. THE EXACT LOCATION OF

RACEWAY SYSTEM COMPONENTS SHALL BE DETERMINED BY

THE CONTRACTOR IN THE FIELD. THE CONTRACTOR SHALL

CONFIRM THE DIMENSIONS OF THE ACTUAL EQUIPMENT TO

BE SUPPLIED FOR THIS PROJECT, VERIFY CLEARANCES AND

ROUGH-INS, AND OBTAIN ALL APPROVALS PRIOR TO

STARTING WORK.

7. SITE EXAMINATION

BEFORE SUBMITTING A BID, THE CONTRACTOR WILL VISIT

THE SITE, EXAMINE THE PREMISES, AND MAKE A THOROUGH

SURVEY OF THE EXISTING CONDITIONS. THIS VISIT SHALL

ONLY BE ALLOWED AS PER THE VA SCHEDULED WALK

THROUGH. THE SUBMISSION OF A BID WILL BE CONSTRUED

AS EVIDENCE THAT SUCH A VISIT HAS BEEN MADE. NO

CONSIDERATION OR ALLOWANCE WILL BE GRANTED FOR

FAILURE TO VISIT THE SITE OR FOR LATER CLAIMS FOR

LABOR, EQUIPMENT, MATERIALS REQUIRED, OR FOR

DIFFICULTIES ENCOUNTERED WHICH COULD HAVE BEEN

FORESEEN HAD SUCH VISIT BEEN MADE.

CONTRACTOR SHALL CAREFULLY EXAMINE THE DRAWINGS

AND SPECIFICATIONS, VISIT THE SITE OF THE WORK, AND

FULLY INFORM THEM SELF AS TO ALL CONDITIONS AND

MATTERS THAT CAN, IN ANY WAY, AFFECT THE WORK OR THE

COST THEREOF. SHOULD THIS CONTRACTOR FIND

DISCREPANCIES IN, OR OMISSIONS FROM, THE DRAWINGS,

SPECIFICATIONS OR OTHER DOCUMENTS OR BE IN DOUBT AS

TO THEIR MEANING, NOTIFY THE VA/COR AT ONCE, IN

WRITING, OF ANY DISCREPANCIES BETWEEN EXISTING

CONDITIONS AND NEW WORK, OR BETWEEN ELECTRICAL

WORK AND THE WORK OF OTHER TRADES. OBTAIN

CLARIFICATION(S) PRIOR TO SUBMITTING ANY BID. LACK OF

SUCH NOTIFICATION SHALL BE CONSTRUED TO INDICATE NO

DISCREPANCIES OR CONFLICTS EXIST. ADDITIONAL

COMPENSATION WILL NOT BE GRANTED AFTER AWARD OF

CONTRACT FOR ANY WORK REQUIRED TO COMPLY WITH

THESE REQUIREMENTS.

8. COORDINATION WITH OTHER TRADES:

THE ELECTRICAL CONTRACTOR SHALL OBTAIN A COMPLETE

SET OF GENERAL, ARCHITECTURAL AND ENGINEERING

DOCUMENTS AND COORDINATE WITH MECHANICAL,

PLUMBING, ARCHITECTURAL, AND OTHER TRADES FOR

EXACT DIMENSIONS, CLEARANCES, ROUGH-IN LOCATIONS,

AND OTHER ADDITIONAL SCOPES OF WORK THAT MAY NOT

BE SHOWN ON THE ELECTRICAL PLANS. THE ELECTRICAL

CONTRACTOR SHALL BE RESPONSIBLE FOR ALL 120 VOLT

(AND HIGHER) AC POWER TO OTHER TRADES EQUIPMENT

AND HARDWARE. THIS SHALL INCLUDE, BUT NOT BE LIMITED

TO, CONTROLS, FIRE AND SECURITY SYSTEMS, MOTORIZED

DOORS, DAMPERS, LIFTS, AND OTHER SYSTEMS. UNLESS

SPECIFICALLY NOTED OTHERWISE ON THE ELECTRICAL

PLANS, THE ELECTRICAL CONTRACTOR SHALL FURNISH ALL

SAFETY DISCONNECT SWITCHES TO MECHANICAL

EQUIPMENT UNLESS OTHERWISE NOTED..

THE CONTRACTOR SHALL CHECK ALL ARCHITECTURAL,

STRUCTURAL, AND MECHANICAL TRADES WORK FOR

POSSIBLE INTERFERENCE CAUSED BY CONDITIONS IN THE

FIELD, BEFORE THE BID IS MADE. NO ALLOWANCE SHALL

SUBSEQUENTLY BE MADE TO THE CONTRACTOR BY REASON

OF HIS FAILURE TO HAVE MADE SUCH EXAMINATIONS OR OF

ANY ERROR OF THEIR PART.

9. THE ELECTRICAL CONTRACTOR IS: RESPONSIBLE FOR

SCHEDULING DELIVERY, RECEIVING, UNLOADING,

UNCRATING, STORING SETTING IN PLACE, AND PROTECTING

FROM DAMAGE, VANDALISM, THEFT OR WEATHER DURING

CONSTRUCTION FOR ALL NEW EQUIPMENT FURNISHED BY

THE ELECTRICAL CONTRACTOR.

CONTRACTOR SHALL PAY ALL PERMIT FEES, PLAN REVIEW

FEES, LICENSE FEES, INSPECTIONS AND TAXES APPLICABLE

TO THIS DIVISION IF NECESSARY. (FEDERAL GOVERNMENT IS

NOT SUBJECT TO LOCAL PERMITS OR FEE FOR THE

PROJECT).

10. FIRE STOPPING:

ALL PENETRATIONS IN WALL, FLOOR OR CEILINGS SHALL BE

SUITABLY CLOSED UP AND SEALED WITH AN INTUMESCENT

FIRE STOPPING COMPOUND LISTED IN THE MOST RECENT

FACTORY MUTUAL RESEARCH CORPORATION (FMRC)

APPROVAL GUIDE. WHEN NEW CABLES/CONDUITS

PENETRATE EXISTING FIRE RATED WALL, PENETRATIONS

SHALL BE SEALED TO MATCH EXISTING RATING TO ENSURE IT

RETAIN EXISTING CONDITIONS. THE BOD FOR FIRE STOPPING

PRODUCTS SHALL BE AS MANUFACTURED BY THE 3M CO.

11. PAINTING:

ALL NEWLY INSTALLED EXPOSED PIPING SHALL BE PAINTED

TO MATCH THE ADJACENT WALL OR CEILING SURFACE

UNLESS THE REQUIRED COLOR CODING IS SPECIFIED.

12. VA FURNISHED EQUIPMENT:

EQUIPMENT THAT WILL BE FURNISHED BY THE VA WILL BE

INDICATED ON A SCHEDULE OR BE INCLUDED IN SPECIFIC

NOTES OR SPECIFICATIONS. THE CONTRACTOR SHALL

COORDINATE WITH THE VA/COR FOR DELIVERY SCHEDULES.

THE CONTRACTOR IS TO ASSUME THAT ON SITE STORAGE

MAY NOT BE AVAILABLE WHEN COORDINATING DELIVERY OF

EQUIPMENT. THE CONTRACTOR, IN COORDINATION WITH THE

VA/COR, WILL INSPECT THE DELIVERY FOR ACCURACY AND

SHIPMENT DAMAGE AND ACCEPTING THE EQUIPMENT. THE

CONTRACTOR SHALL BE RESPONSIBLE TO STORE, PROTECT,

AND ULTIMATELY INSTALL THE EQUIPMENT.

13. ELECTRICAL SERVICE DISRUPTIONS:

WORK ON ENERGIZED EQUIPMENT SHALL BE COORDINATED

WITH THE VA COR. ENERGIZED WORK PERMITS ARE

AVAILABLE, BUT ONLY GRANTED AS A LAST RESORT. ALL

EFFORT SHALL BE MADE TO NOT WORK ON ENERGIZED

EQUIPMENT. THIS RESTRICTION INCLUDES REMOVING THE

COVER FROM ANY PANEL BOARD, SWITCHBOARD, M.C.C.

ETC.. ALL WORK WHICH EXPOSES ACTIVE BUS REQUIRES A

WRITTEN NOTIFICATION TO THE VA/COR WHICH WILL OUTLINE

THE METHOD OF PROCEDURE FOR THE WORK. THE

CONTRACTOR SHALL PROVIDE A MINIMUM OF 6 WEEKS

NOTICE TO THE VA/COR BEFORE WORKING ON ANY

ENERGIZED ELECTRICAL SYSTEM. ALL POWER DISRUPTION

SHALL OCCUR AT TIMES AND OF DURATIONS ACCEPTABLE TO

THE VA/COR.

14. EQUIPMENT:

ALL MATERIALS AND EQUIPMENT USED IN THIS INSTALLATION

SHALL BE NEW, AND HAVE THE APPROPRIATE UL LISTING AND

LABEL.

THE CONTRACTOR SHALL FURNISH ALL LABOR, MATERIAL,

TOOLS, EQUIPMENT SERVICES, AND ACCESSORIES FOR

COMPLETE INSTALLATION OF ALL ELECTRICAL WORK AS

NOTED. ITEMS OMITTED FROM EITHER THE SPECIFICATIONS

OR THE DRAWINGS, BUT SHOWN OR DESCRIBED IN ONE OR

THE OTHER, AND ITEMS NECESSARY TO MAKE THE

ELECTRICAL SYSTEM COMPLETE AND WORKABLE SHALL

FORM A PART OF THE WORK.

15. MISCELLANEOUS SUPPORTING MEMBERS:

ALL ANGLES CHANNELS, AND OTHER MISCELLANEOUS STEEL,

BOLTS, RODS, ETC.. REQUIRED TO SUPPORT LIGHT FIXTURE,

CONDUIT, RACEWAY, LADDER TRAY, OR OTHER ELECTRICAL

EQUIPMENT OR DEVICES SHALL BE FURNISHED AND

INSTALLED BY THE CONTRACTOR.

ANY MENTION OF A SPECIFIC VOLTAGE ON THE ELECTRICAL

DRAWINGS SHALL NOT RELIEVE THE ELECTRICAL

CONTRACTOR OF THE RESPONSIBILITY TO VERIFY THE

VOLTAGE PRIOR TO PURCHASING OR ROUGH-IN WORK.

16. DISTRIBUTION PANELS AND PANELS BOARDS:

ALL DISTRIBUTION PANELS AND PANEL BOARDS SHALL BE

PROVIDED WITH TYPEWRITTEN DIRECTORIES. SEE PANEL

SCHEDULES ON THE DRAWINGS AND SPECIFICATION FOR

COMPLETE IDENTIFICATION AND LABELING REQUIREMENTS.

ALL DISTRIBUTION PANELS AND PANEL BOARDS SHALL BE

LABELED ON THE PANEL CABINET WITH THE PANEL NAME

AND THE POWER SOURCE FEEDING THE PANEL AS PER THE

ELECTRICAL ONE LINE. ALL PANELS AND PANEL BOARDS

SHALL BE PROVIDED WITH HINGED DOOR WITH LOCK AND

KEY.

17. SAFETY:

TONTRACTOR SHALL TAKE ALL STEPS NECESSARY TO

ENSURE THE SAFETY OF THE VA'S EMPLOYEES, BUILDING

EMPLOYEES AND GUESTS, AS WELL AS THEIR OWN FORCES,

BY ADEQUATELY PROVIDING APPROPRIATE PPE AND

PROTECTING ANY EXPOSED LIVE CONDUCTORS, OR DEVICES

THROUGHOUT THE COURSE OF THIS WORK.

18. EQUIPMENT CONNECTIONS:

PROVIDE FINAL CONNECTIONS FOR ALL EQUIPMENT

FURNISHED UNDER OTHER DIVISIONS AND FOR ALL VA

FURNISHED EQUIPMENT. PROVIDE A FLEXIBLE LIQUID TIGHT

CONNECTION TO ALL VIBRATION PRODUCING EQUIPMENT.

19. TEMPORARY LIGHTING, POWER, FIRE, AND SAFETY:

PROVIDE TEMPORARY LIGHTING AND POWER AS REQUIRED

IN AREAS UNDERGOING WORK DURING CONSTRUCTION.

FURNISH AND INSTALL ONE OSHA APPROVED PIGTAIL

SOCKET WITH 150-WATT LAMP FOR EVERY 500 SQUARE FEET

OF FLOOR SPACE AND A MINIMUM 1 PER ROOM. THE

TEMPORARY LIGHTING SHALL BE LEFT IN PLACE UNTIL

PERMANENT LIGHTING IS COMPLETELY OPERATIONAL.

FURNISH AND INSTALL POWER OUTLETS TO A TOTAL OF ONE

FOR EVERY 2000 SQUARE FEET OR PART THEREOF OF FLOOR

AREA. THESE SHALL BE 20 AMP, SINGLE PHASE

RECEPTACLES FOR EITHER 110 OR 220 VOLTS AS DIRECTED

BY THE GENERAL/PRIME CONTRACTOR. COORDINATE FOR

ADDITIONAL TEMPORARY POWER REQUIREMENTS WITH

OTHER TRADES AND PROVIDE AN ADEQUATE INSTALLATION.

COMPLY WITH NFPA 241 FOR SAFEGUARDING DURING

CONSTRUCTION AND ALTERATION OPERATIONS. IN ADDITION,

ANY OPENINGS IN FIRE RATED SEPARATIONS BETWEEN

OCCUPIED AND UNOCCUPIED (OR OPERATIONAL AND

NON-OPERATIONAL) AREAS SHALL BE SEALED AT THE END OF

EACH WORK DAY WITH AN APPROPRIATE FIRE RATED

ENCLOSURE OR SEALANT. DO NOT COMPROMISE EXISTING

SECURITY OR FIRE ALARM SYSTEMS SERVING THE OCCUPIED

OR OPERATIONAL AREAS.

DURING CONSTRUCTION THE CONTRACTOR SHALL AT ALL

TIMES MAINTAIN ELECTRICAL UTILITIES OF THE BUILDING

WITHOUT INTERRUPTION. SHOULD IT BE NECESSARY TO

INTERRUPT ANY ELECTRICAL SERVICE OR UTILITY, THE

CONTRACTOR SHALL SECURE PERMISSION IN WRITING FROM

THE VA/COR FOR SUCH INTERRUPTION AT LEAST 6 WEEKS IN

ADVANCE. ANY INTERRUPTION SHALL BE MADE WITH THE

MINIMUM AMOUNT OF INCONVENIENCE TO THE VA AND ANY

SHUT-DOWN TIME SHALL HAVE TO BE ON A PREMIUM

TIME/AFTER HOURS BASIS AND SUCH TIME TO BE INCLUDED

IN THE CONTRACTOR'S BID.

CONTRACTOR SHALL PROVIDE ALL NECESSARY TEMPORARY

LIGHTING AND POWER FOR ALL TRADES DURING

CONSTRUCTION AND REMOVE IT AT COMPLETION OF WORK.

CONTRACTOR SHALL ESTABLISH SAFE WORKING

PROCEDURES FOR THE PROTECTION OF THE WORKMEN IN

ALL PHASES OF WORK, COMPLYING WITH THE APPLICABLE

PROVISIONS OF ALL CITY, STATE, AND FEDERAL SAFETY

LAWS (OSHA), AND AS RECOMMENDED IN THE "MANUAL OF

ACCIDENT PREVENTION IN CONSTRUCTION" AS ISSUED BY

THE ASSOCIATION OF GENERAL CONTRACTORS OF AMERICA,

INC., 20TH AND E. STREETS, N.W. WASHINGTON, D.C.

20. POWER COORDINATION:

THE CONTRACTOR SHALL PERFORM ALL COORDINATION AND

SCHEDULING OF LOCAL POWER OUTAGES REQUIRED WITH

THE VA/COR. ALL NEEDED POWER OUTAGES TO BE

SCHEDULED WITH THE VA/COR SIX WEEKS IN ADVANCE.

21. CABLING:

BRANCH CIRCUITS TO RECEPTACLES, LIGHTING AND MISC.

SMALL LOADS (20 AMP CIRCUITS), UNLESS SPECIFICALLY

NOTED OTHERWISE, SHALL BE 2 - #12, 1 - #12 GRD., 3/4" C. A

SEPARATE NEUTRAL SHALL BE RUN FOR EACH CIRCUIT. SEE

WIRE SIZING TABLE ON THIS SHEET.

ALL WIRE SIZE #12 AWG AND LARGER SHALL BE STRANDED

AND SOLID FOR #14 AND SMALLER.

EACH BRANCH CIRCUIT HOMERUN SHALL HAVE NO MORE

THAN THREE CIRCUITS. EACH BRANCH CIRCUIT HOMERUN

SHALL HAVE A SEPARATE GREEN INSULATED EQUIPMENT

GROUNDING CONDUCTOR. ALL CONDUCTORS SHALL BE

COPPER TYPE THWN / XHHW.

CABLE JACKET COLOR FOR VARIOUS SYSTEM SHALL BE AS

FOLLOW:

VOICE (VOiP) - BLUE

3 DATA - BLUE

CLINICAL WIRELESS (OIT) - BLUE

VIDEO SURVEILLANCE - BLUE

NURSE CALL - GREEN

FIRE ALARM - RED

ANALOGUE LINE - WHITE

UPS - ORANGE

22. CABLING SIZES:

BRANCH CIRCUIT CABLE SIZING SHALL BE ADJUSTED BASED

ON THE VALUES INDICATED IN THE WIRE SIZING TABLE PER

THIS SHEET.

23. SPECIAL LUG REQUIREMENTS:

ANY CABLE WHICH TERMINATES DIRECTLY ON TO A BUS BAR

SHALL BE 2 BOLT LONG BARREL TYPE WITH INSPECTION

HOLES PRODUCED WITH NON FLASHING TYPE DYES WITH

THE BOD AS MANUFACTURED BY THOMAS AND BETTS, OR

EQUIVALENT MINIMUM 10 TONS OF COMPRESSION, HEX

CRIMP. THE USE OF HEAT SHRINK TUBING IS EXPLICITLY

FORBIDDEN.

24. RACEWAYS:

ALL WIRE SHALL BE INSTALLED IN THIN WALL (E.M.T.)

CONDUIT UNLESS OTHERWISE NOTED. MINIMUM SIZE SHALL

BE 3/4". ALL THINWALL FITTINGS SHALL BE OF THE STEEL

COMPRESSION GLAND TYPE.

ALL UNDERFLOOR, UNDERGROUND OR

EXPOSED-TO-WEATHER CONDUIT SHALL BE HEAVYWALL

GALVANIZED RIGID STEEL. (G.R.S.), MINIMUM 3/4". ALL BURIED

CONDUITS AND 2" AND ABOVE EXPOSED-TO-WEATHER

CONDUIT SHALL BE PVC COATED HEAVYWALL GALVANIZED

RIGID STEEL (G.R.S).

ALL CONDUIT FASTENERS, STRAPS, SUPPORTS ETC. MUST BE

"BOLT-ON" GALVANIZED STEEL ON EXPOSED CONSTRUCTION

AND IN WET AREAS. SNAP-ON BLACK METAL "CADDY" CLIPS IN

METAL PARTITION WALLS AND ABOVE SUSPENDED CEILINGS

WILL BE PERMITTED. ALL FASTENERS, STRAPS, CLIPS, ETC.

SHALL BE UL LISTED FOR THEIR USE.

SUPPORT CONDUIT WITH P1000 UNISTRUT AND 3/8"

THREADED ROD 8'-0" O.C. MAX.

PROVIDE MYERS HUBS FOR ALL CONDUIT TO ENCLOSURE

CONNECTIONS.

CABLE TRAYS ARE NOT ALLOWED. ALL CONDUIT RACEWAYS

SHALL BE CONCEALED IN OR WITHIN: WALLS, CEILING CAVITY,

ROOF CONSTRUCTION (WHERE APPROVED), SLAB, GRADE,

ETC. UNLESS OTHERWISE NOTED. ANY RACEWAY THAT IS TO

BE ROUTED EXPOSED SHALL BE APPROVED BY THE VA/COR

AND SUCCESSFULLY REVIEWED BY THE ARCHITECT/ENGR.

PRIOR TO INSTALLATION. ALL CONDUIT SHALL BE ROUTED

PARALLEL OR PERPENDICULAR TO WALLS AND STRUCTURAL

MEMBERS WITH 90° BENDS WHERE REQUIRED AND SHALL BE

RACKED. PULL AND JUNCTION BOXES SHALL BE HELD TO A

MINIMUM. CONTRACTOR SHALL INSTALL ALL WORK IN NEAT &

INDUSTRY RECOGNIZED MANNER OF BEST PRACTICES.

GROUND ALL CONDUITS, MOTORS, AND EXPOSED

NON-CURRENT CARRYING METAL PARTS OF ELECTRICAL

EQUIPMENT IN ACCORDANCE WITH ALL PROVISIONS WITH

THE LATEST EDITION OF THE NATIONAL ELECTRICAL CODE.

VA SPECIFICATION SECTION 26 05 26 "GROUNDING AND

BONDING ELECTRICAL SYSTEM".

CONTRACTOR SHALL PROVIDE PULL BOXES, JUNCTION

BOXES, SPLICE BOXES AND FITTINGS WHERE NECESSARY OR

REQUIRED BY THE NEC.

CONDUIT ROUTING SHOWN DIAGRAMMATIC AND BASED ON

CONDITIONS AT THE TIME THE FIELD SURVEY. CONTRACTOR

SHALL FIELD VERIFY EXACT ROUTING AS FIELD CONDITION

DICTATES AT THE TIME OF CONSTRUCTION. PROVIDE PULL

BOXES SIZED AS PER NFPA-70 LATEST EDITION. THERE SHALL

NOT BE MORE THAN EQUIVALENT OF THREE QUARTER BENDS

(270° TOTAL) BETWEEN PULL POINTS.

ALL ELECTRICAL CONDUITS TO A MINIMUM OF 3/4".

MULTI-GANG BACKBOXES FOR DIFFERENT VOLTAGES AND

TYPES OF EMERGENCY AND NORMAL BRANCH WIRING

DEVICES SHALL HAVE DIVIDERS BETWEEN DEVICES.

PROVIDE JUNCTION BOX AND CONDUIT COLOR FOR VARIOUS

SYSTEMS AS PER FOLLOWING COLOR SCHEME.

POWER:

120/208 VOLT (NORMAL POWER): SILVER

120/208 VOLT (LIFE SAFETY/CRITICAL): SILVER

277/480 VOLT (NORMAL & EMERGENCY): SILVER

LIGHTING WHITE

GENERAL DATA/VOICE: SILVER

FIRE ALARM: RED

NURSE CALL/GET WELL NETWORK: SILVER

T-STAT: BLUE

SECURITY (CARD READER/VIDEO: SILVER

FIBER OPTIC SOURCE A: BLACK

WWHERE CORE DRILLING AND CUTTING OF FLOORS OR WALLS IS

REQUIRED, X-RAY THE AREAS PRIOR TO DRILLING. AVOID

INTERFERENCE WITH EXISTING CONCEALED ELECTRICAL,

PLUMBING INSTALLATIONS, AND REINFORCING STEEL.

REFINISH DAMAGED AND CUT SURFACES TO MATCH

ADJACENT FINISHES.

CONTRACTOR SHALL FIREPROOF ALL CONDUIT OPENINGS

BETWEEN FLOORS AND ANY INTERSPACE FIRE SEPARATION

BLOCK WALLS WITH A VA/COR APPROVED U.L. LISTED FIRE

RETARDANT MATERIAL, AS SUCCESSFULLY REVIEWED BY

THE ARCHITECT/ENGINEER..

25. LIGHTING:

ALL FINAL LOCATIONS AND ARRANGEMENTS OF LIGHTING

FIXTURES SHALL BE OBTAINED FROM THE ARCHITECTURAL

REFLECTED CEILING PLAN. COORDINATE LIGHT LOCATION

WITH CABLE TRAY AND CEILING MOUNTED MECHANICAL

EQUIPMENTS AND ENSURE THAT SERVICE CLEARANCE AND

ACCESS IS NOT RESTRICTED.

26. RECEPTACLES

CONTRACTOR SHALL VERIFY ALL OUTLET MOUNTING

ARRANGEMENTS, HEIGHTS AND LOCATIONS WITH THE

ARCHITECTURAL DRAWINGS PRIOR TO ROUGH-IN. ANY

MENTION OF A SPECIFIC MOUNTING ARRANGEMENT, HEIGHT

OR LOCATION SHALL NOT RELIEVE THE CONTRACTOR OF THE

RESPONSIBILITY TO VERIFY THE SPECIFIC REQUIREMENT

WITH THE EQUIPMENT FURNISHED OR THE OTHER TRADES

WORKING IN THE SAME AREA. NO ADDITIONS TO THE

CONTRACT SUM WILL BE PERMITTED FOR OUTLETS IN

WRONG LOCATIONS, IN CONFLICT WITH OTHER WORK ETC.

THE VA RESERVES THE RIGHT TO RELOCATE ANY DEVICE

UPTO 10'-0" PRIOR TO ROUGH-IN WITHOUT ANY ADDITIONAL

CHARGES BY THE CONTRACTOR.

OUTLET BOXES MOUNTED BACK-TO-BACK IN THE SAME WALL

ARE PROHIBITED. A MINIMUM 24" CENTER-TO-CENTER

LATERAL SPACING SHALL BE MAINTAINED BETWEEN BOXES.

ALL THE EMERGENCY POWER OUTLETS SHALL BE HOSPITAL

GRADE RED IN COLOR. NORMAL POWER IS IVORY, UPS

POWER IS ORANGE. FACE PLATES ARE STAINLESS STEEL.

OUTLETS POWERED FROM EMERGENCY GENERATOR SHALL

ALSO LIST : LS, CR OR EQ.

27. AS BUILT/RECORD DOCUMENTS:

ELECTRICAL CONTRACTOR SHALL FURNISH CONTRACT

AS-BUILT RECORD DOCUMENTS TO THE VA/COR AND

ARCHITECT/ENGINEER BEFORE FINAL PAYMENT WILL BE

ISSUED. THE CONTRACT RECORD DOCUMENTS SHALL

DIAGRAMMATICALLY INDICATE THE ACTUAL INSTALLED

CONDITIONS THAT DEVIATE FROM ORIGINAL DESIGN

DRAWINGS.

28. GUARANTEE:

ALL EQUIPMENT FURNISHED AND WORK PERFORMED UNDER

THE CONTRACT DOCUMENTS SHALL BE GUARANTEED

AGAINST DEFECTS IN MATERIALS OR WORKMANSHIP FOR A

PERIOD AS PER VA SPECIFICATION, UNLESS OTHERWISE

NOTED. ANY FAILURE OF EQUIPMENT OR WORK DUE TO

DEFECTS IN MATERIALS OR WORKMANSHIP SHALL BE

CORRECTED BY THE CONTRACTOR AT NO COST TO THE VA.

29. FINAL INSPECTION:

ALL THE ITEMS AND WORK SHALL BE TESTED FOR SAFE AND

PROPER OPERATIONS.

UPON COMPLETION OF THE WORK, THE ELECTRICAL

CONTRACTOR SHALL REVIEW AND CHECK THE ENTIRE

PORTION OF WORK, CLEAN EQUIPMENT AND DEVICES,

REMOVE SURPLUS MATERIALS AND RUBBISH FROM THE

OWNER'S PROPERTY, LEAVING THE WORK IN NEAT AND

CLEAN ORDER AND IN COMPLETE WORKING CONDITION. THE

ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR

REMOVAL OF ANY CARTON, DEBRIS, ETC. FOR EQUIPMENT

INSTALLED BY THIS CONTRACTOR INCLUDING EQUIPMENT

FURNISHED BY THE OWNER. THE ABOVE SHALL ALSO APPLY

TO ALL EQUIPMENT FURNISHED BY OTHERS AND UNPACKED

OR REMOVED FROM CARTON, BY THE CONTRACTOR.

MOUNTING HEIGHTS FOR ELECTRICAL DEVICES ELECTRICAL GENERAL NOTES

LIGHT SWITCHES, WALL MOUNTED OCCUPANCY SENSORS

WALL MOUNTED EXIT SIGNS

CEILING MOUNTED EXIT SIGNS

RECEPTACLES

SPECIAL OUTLETS OR

RECEPTACLES

PLUGMOLD OR WIREMOLD

DATA/COMMUNICATION OR TELEPHONE OUTLETS

TELEPHONE OUTLETS - WALL TYPE

FIRE ALARM MANUAL PULL STATIONS

FIRE ALARM AUDIBLE ONLY DEVICE

CARD READER

INTERCOM STATION

SOUND SYSTEM VOLUME CONTROL

THERMOSTATS

TEMPERATURE/HUMIDITY SENSORS 60" TO CENTER LINE OF BOX.

54" TO HIGHEST OPERABLE PART (SIDE ACCESS).

48" HIGHEST OPERABLE PART (FRONT ACCESS).

54" TO HIGHEST OPERABLE PART (SIDE ACCESS).

48" HIGHEST OPERABLE PART (FORWARD ACCESS).

54" TO HIGHEST OPERABLE PART (SIDE ACCESS).

48" HIGHEST OPERABLE PART (FORWARD ACCESS).

16" TO BOTTOM OF BOX.

80" TO BOTTOM FIXTURE.

1. EXAMINATION

CONTRACTOR SHALL SURVEY THE EXISTING SITE AND EXAMINE AREAS UNDER

WHICH THE WORK IS TO BE PERFORMED PRIOR TO BIDDING AND DETERMINE

THE EXTENT OF NECESSARY RELOCATIONS, REMOVALS AND REPAIRS TO THE

EXISTING ELECTRICAL WORK REQUIRE AVOIDING CONFLICTS WITH NEW

CONSTRUCTION IN ORDER TO MEET MINIMUM CODE REQUIREMENTS. NOTIFY

THE VA/COR IN WRITING OF ANY CONDITIONS DETRIMENTAL TO THE PROPER

AND TIMELY COMPLETION OF THE WORK. CONTRACTOR SHALL NOT PROCEED

WITH WORK UNTIL SATISFACTORY CONDITIONS HAVE BEEN CORRECTED. A

FIELD SURVEY VERIFICATION IS RECOMMENDED IN ORDER TO SUBMIT AN

ELECTRICAL BID, FAILURE TO DO SO SHALL NOT RELIEVE THIS CONTRACTOR

FROM PERFORMING THE WORK OF THIS CONTRACT.

DEMOLITION DRAWINGS ARE BASED ON FIELD OBSERVATION AND EXISTING

RECORD DRAWINGS. THE CONTRACTOR SHALL INCLUDE IN HIS BID ALL COSTS

ASSOCIATED WITH RELOCATION AND REMOVAL OF ELECTRICAL WORK AS

DESCRIBED IN THE DRAWINGS AND SPECIFICATIONS WITH ALLOWANCES FOR

EXPECTED OR UNFORESEEN ISSUES WHEN CONCEALED WORK HAS BEEN

EXPOSED. NO ADDITIONAL CLAIMS FOR WORK ASSOCIATED WITH DEMOLITION

WILL BE ACCEPTED, UNLESS, IN CERTAIN CASES, CONSIDERED JUSTIFIABLE BY

THE COR.

REVIEW MECHANICAL AND ARCHITECTURAL DEMOLITION DRAWINGS FOR ANY

OTHER ELECTRICAL DEMOLITION REQUIREMENTS.

2. PREPARATION

ALL EXISTING EQUIPMENT IS TO REMAIN OPERATIONAL DURING THE

CONSTRUCTION PERIOD. ANY TEMPORARY WIRING OR REROUTING OF

CIRCUITRY TO ACHIEVE THIS IS BY THE ELECTRICAL CONTRACTOR. SHUTDOWN

OF EXISTING SERVICES SHALL ONLY BE PERMITTED UPON WRITTEN APPROVAL

FROM THE OWNER AND THEN ONLY FOR THE DATE AND DURATION AGREED

UPON. INCLUDE ALL PREMIUM TIME CHARGES IN THE BASE BID.

ANY UTILITY SHUT DOWN THAT AFFECT PATIENT CARE SHALL BE COORDINATED

A MINIMUM OF 45 DAYS IN ADVANCE AND SHALL BE PERFORMED OFF HOUR

PERIODS OR WEEKENDS AT THE CONVENIENCE OF VA AS APPROVED THE BY VA

CO.

IT IS MANDATORY THAT ALL THE EXISTING FIRE ALARM AND COMPONENTS TO

REMAIN FUNCTIONAL DURING CONSTRUCTION.

BEFORE WORKING ON ANY EQUIPMENT THAT IS CONNECTED TO SOURCE OF

ENERGY, CONTRACTOR SHALL PROVIDE OSHA MANDATED LOCK-OUT/TAG-OUT

AT SOURCE LOCATION TO SHUT OFF ENERGY SOURCE.

3. DEMOLITION AND EXTENSION OF EXISTING ELECTRICAL WORK.

WHERE SOURCE OF SUPPLY IS A PANEL BOARD, RE-LABEL PROTECTIVE DEVICE

AS “SPARE” AND SET TO THE OFF POSITION AFTER DEMOLITION IS COMPLETE.

PROVIDE REVISED CIRCUIT DIRECTORIES IN ALL PANEL BOARDS AFFECTED BY

NEW OR DEMOLITION WORK THAT INDICATES ALL LOADS, NEW AND MODIFIED.

CIRCUIT NUMBER LABEL SHOWN ON EXISTING OUTLETS AND SWITCHES IS AS

PER FIELD SURVEY. CONTRACTOR SHALL BE RESPONSIBLE TO TRACE CIRCUITS

AND FIND OUT BREAKER LOCATIONS AND DEMO THE CABLES AND UPDATE THE

PANEL DIRECTORY FOR VA RECORD.

WHERE CORE DRILLING AND CUTTING OF FLOORS/SLABS OR WALLS IS

REQUIRED CONTRACTOR IS TO EXERCISE EXTREME CAUTION AND X-RAY THE

AREAS PRIOR TO DRILLING/CUTTING SLAB TO AVOID DAMAGE TO ANY EXISTING

CONCEALED ELECTRICAL, PLUMBING INSTALLATIONS, AND REINFORCING STEEL

ETC. THAT MAY BE CONCEALED IN OR BENEATH THE SLAB/WALL. CONTRACTOR

SHALL FIREPROOF ALL THE OPENING WITH U.L. LISTED FIRE RETARDANT

MATERIAL, TO MATCH EXISTING CONDITIONS.

MAKE EVERY EFFORT POSSIBLE TO REMOVE ANYTHING ABANDONED. LEAVE IN

PLACE AS AN ABSOLUTE LAST RESORT. REMOVE EXPOSED ABANDONED

CONDUIT ABOVE ACCESSIBLE CEILING AND FINISHED WALL. CUT CONDUIT

FLUSH WITH WALLS AND FLOORS, AND PATCH THE SURFACE TO MATCH

EXISTING. CONDUIT MAY BE ABANDONED IN WALLS AND FLOORS TO REMAIN

BUT EXISTING WIRING WITHIN THESE CONDUITS TO BE REMOVED COMPLETELY.

REPAIR ADJACENT CONSTRUCTION AND FINISHES DAMAGED DURING

DEMOLITION AND EXTENSION OF WORK.

4. DISPOSAL

OWNER SHALL HAVE RIGHT TO RETAIN ANY EQUIPMENT OR MATERIALS THAT

HAVE BEEN DEMOLISHED PRIOR TO DISPOSAL OR REMOVAL FROM SITE. ANY

EQUIPMENT OR MATERIALS NOT WANTED BY THE OWNER SHALL BECOME THE

PROPERTY OF THE CONTRACTOR AND REMOVED FROM SITE.

CONTRACTOR SHALL COMPLY WITH ENVIRONMENTAL LAWS AND REGULATIONS

FOR DISPOSAL OF DEMOLISHED MATERIALS AND EQUIPMENT.

"A" FT.

1. TABLES ARE BASED ON EVENLY DISTRIBUTED LOAD ALLOWING A 3% VOLTAGE DROP AT LAST OUTLET/LIGHT.

2. SIZE OF CONDUCTORS ARE BASED UPON EACH MOTOR BEING FED WITH SEPARATE CONDUIT. IF CONDUCTORS FOR TWO MOTORS (MAX.) ARE TO BE

COMBINED IN ONE CONDUIT, INCREASE THE SIZE OF CONDUCTORS AND CONDUITS PER NATIONAL ELECTRICAL CODE (NEC), TO COMPENSATE FOR

CONDUCTOR DE-RATING.

3. PROVIDE DEDICATED NEUTRAL FOR EACH CIRCUIT.

4. PROVIDE EQUIPMENT GROUND CONDUCTOR FOR EACH CIRCUIT, SIZE TO COMPLY WITH NEC REQUIREMENTS.

5. FOLLOW "TR RACK UPS WIRING SCHEDULE" FOR WIRING UPS POWER TO RACKS.

IF DISTANCE (A+B) IN FEET IS:

(SEE DIAGRAM AT RIGHT)

FOR 120V-20A BRANCH CIRCUITS ONLY (UNLESS NOTED OTHERWISE)

USE COPPER WIRE IN METALLIC CONDUIT,

AWG SIZE AS FOLLOWS ON ENTIRE CIRCUIT

AND SIZE CONDUIT ACCORDINGLY.

#12 AWG (MIN.)

#10 AWG

#8 AWG

#6 AWG (MAX.)

*LAST ON

CIRCUIT.

*FIRST ON

CIRCUIT.

PANELBOARD

* RECEPTACLE OR LIGHTING LOAD

FOR 277V-20A BRANCH CIRCUITS ONLY (UNLESS NOTED OTHERWISE)

PANELBOARD

#12 AWG (MIN.) #10

AWG

#8 AWG

#6 AWG (MAX.

0' TO 100'

100' TO 175'

175' TO 300'

300' TO 450'

USE COPPER WIRE IN METALLIC CONDUIT,

AWG SIZE AS FOLLOWS ON ENTIRE CIRCUIT

AND SIZE CONDUIT ACCORDINGLY.

"B" FT.

"B" FT.

"A" FT.

IF DISTANCE (A+B) IN FEET IS:

(SEE DIAGRAM AT RIGHT)

0' TO 250'

250' TO 400'

400' TO 700'

700' TO 1000'

WIRE SIZE CONDUIT SIZE

3/4" 3/4" 3/4" 1"

WIRE SIZE CONDUIT SIZE

3/4" 3/4" 3/4" 1"

*LAST ON

CIRCUIT.

*FIRST ON

CIRCUIT.

* LIGHTING LOAD

NOTES:

ELECTRICAL - GENERAL NOTES

WG BX E-001

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

K:

\C

C G

_P R

O

JE

C

TS

\2

1\

-1

T op ek a

EH

R M

C

1R

\4

- D es

D oc s\

2- D ra w in gs

\W O

R

KI

N G

\A ut oC

AD

\E le ct ric al \E

1_

G en

N ot es .d w g

2/

/2

4:

:3

PM

ISSUE FOR BIDOffice of Construction and Facilities Management

U.S. Department of Veterans Affairs

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

EHRM INFRASTRUCTURE

UPGRADES

COLMERY O'NEIL VA HEALTH CARE

21-116

Revisions: Date:

www. bancroft-ae.com

3300 Dundee RD.

Northbrook, IL 60062

T: 847.952.9362

35% SCHEMATIC DESIGN SUBMISSION 07-12-22

95% CONSTRUCTION DOCUMENTS SUBMISSION 10-31-23

100% CONSTRUCTION DOCUMENTS SUBMISSION

03/22/2024

12-19-23

Bancroft Project No: 21-116

35% SCHEMATIC DESIGN SUBMISSION R1 09-21-22

35% SUBMITTAL II 06-13-23

65% DESIGN DEVELOPMENT SUBMITTAL 09-12-23

ISSUED FOR BID 12-28-23

ISSUE FOR BID R1 02-28-24

ISSUE FOR BID R2 03-22-24

1. THIS IS A STANDARD LEGEND SHEET. SOME SYMBOLS OR ABBREVIATIONS MAY APPEAR ON THIS SHEET AND NOT ON THE

PLANS.

2. SEE ICT DRAWINGS FOR DATA AND SECURITY SYMBOLS.

1PH SINGLE-PHASE

1P SINGLE POLE

2/C TWO-CONDUCTOR

3/C THREE-CONDUCTOR

3PH THREE-PHASE

4/C FOUR-CONDUCTOR

4W FOUR-WIRE

A/C UNIT AIR CONDITIONING UNIT

A/E ARCHITECT/ENGINEER

AAP ALARM ANNUNCIATOR PANEL

AC ALTERNATING CURRENT OR ARMORED CABLE

ACC ACCESSIBLE

ADDL ADDITIONAL

ADJ ADJACENT, ADJOINING

ADO AUTOMATIC DOOR OPENER

AF AMPERE FRAME OR AMP FUSE

AFC ABOVE FINISHED COUNTER, AUTOMATIC FREQUENCY

CONTROL, OR AVAILABLE FAULT CURRENT

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

AH AMPERE HOUR

AHJ AUTHORITY HAVING JURISDICTION

AIC AMPERE INTERRUPTING CAPACITY

ALT ALTERNATE

AMB OR A AMBIENT

AMP AMPERE

ARCH ARCHITECT

ASC AMPS SHORT CIRCUIT

AT AMPERE TRIP

ATS AUTOMATIC TRANSFER SWITCH

AUTO AUTOMATIC

AV AUDIO VISUAL

BAT BATTERY

BC BARE COPPER

BD BOARD

BFF BELOW FINISH FLOOR

BIL BASIC INSULATION LEVEL

BLDG BUILDING

BPIP BOILER PLANT INSTRUMENTATION PANEL

BRKR BREAKER

BYP BY PASS

C CONDUIT

CAB CABINET

CALC CALCULATE

CAP CAPACITY

CAT CATALOG

CATV COMMUNITY ANTENNA TELEVISION

CCR CONTROL CONTACTOR

CCTV CLOSED CIRCUIT TELEVISION

CB CODE BLUE

cd CANDELA

CD CONSTRUCTION DOCUMENTS

CF CONTRACTOR FURNISHED

CF/CI CONTRACTOR FURNISHED/CONTRACTOR INSTALLED

CF/OI CONTRACTOR FURNISHED/OWNER INSTALLED

CFE CONTRACTOR FURNISHED EQUIPMENT

CHW CHILLED WATER

CHWP CHILLED WATER PUMP

CKT CIRCUIT

CKT BRKR CIRCUIT BREAKER

CLF CURRENT LIMITING FUSE

CLG CEILING

CMU CONCRETE MASONRY UNIT

COAX COAX CABLE

COMM COMMUNICATION

COMPT COMPARTMENT

CONC CONCRETE

CONT CONTINUE

CONTR CONTRACTOR

COORD COORDINATE

CPT CONTROL POWER TRANSFORMER

CRI COLOR RENDERING INDEX

CT CURRENT TRANSFORMER

CTV CABLE TELEVISION

CU COPPER

CU FT CUBIC FEET

CUR CURRENT

DB DECIBEL OR DIRECT BURIAL

DC DIRECT CURRENT

DCP DIMMER CONTROL PANEL

DEG C DEGREES CELSIUS

DEG F DEGREES FAHRENHEIT

DEMO DEMOLITION

DIAG DIAGRAM

DISC DISCONNECT

DISTR DISTRIBUTION

DISTR PNL DISTRIBUTION PANEL

DMR SW DIMMER SWITCH

DN DOWN

DPDT DOUBLE POLE, DOUBLE THROW

DPST DOUBLE POLE, SINGLE THROW

DRSW DOOR SWITCH

DS DISCONNECT SWITCH

DWG DRAWING

EC EMPTY CONDUIT

EG EQUIPMENT GROUND

EL ELEVATION

ELEC ELECTRIC OR ELECTRICAL

ELEV ELEVATOR

EMCP EMERGENCY MONITORING CONTROL PANEL

EMER EMERGENCY

EMI ELECTROMAGNETIC INTERFERENCE

EMT ELECTRICAL METALLIC TUBING

ENCL ENCLOSURE

EPO EMERGENCY POWER OFF

EPRF EXPLOSION PROOF

ESMT EASEMENT

EWC ELECTRIC WATER COOLER

EWH ELECTRIC WATER HEATER

EXIST, EX EXISTING

FA FIRE ALARM

FAAP FIRE ALARM ANNUNCIATOR PANEL

FABL FIRE ALARM BELL

FABX FIRE ALARM BOX

FACP FIRE ALARM CONTROL PANEL

FC FOOTCANDLE

FI FILM ILLUMINATOR

FIXT FIXTURE

FLA FULL LOAD AMPS

FLEX FLEXIBLE METALLIC CONDUIT

FLT FLOODLIGHT

FLUOR FLUORESCENT

FLUOR FIX FLUORESCENT FIXTURE

FOUTT TELEPHONE FLOOR OUTLET

FP FIRE PROTECTION

FT FEET OR FOOT

FU SW FUSED SWITCH

FVNR FULL VOLTAGE NON-REVERSING

FVR FULL VOLTAGE REVERSING

G OR GND GROUND OR GENERATOR

GEN GENERATOR

GFCI GROUND FAULT CIRCUIT INTERRUPTER

GTB GROUND TERMINAL BOX

HID HIGH INTENSITY DISCHARGE

HOA HAND-OFF-AUTOMATIC

HP HORSEPOWER

HT HEIGHT

HZ HERTZ

IESNA ILLUMINATION ENGINEERING SOCIETY OF NORTH AMERICA

IMC INTERMEDIATE METAL CONDUIT

INCAND INCANDESCENT

IR INFRARED

IWH INSTANTANEOUS WATER HEATER

J-BOX, JB JUNCTION BOX

kV KILOVOLT kVA KILOVOLT AMPERE kVAH KILOVOLT AMPERE PER HOUR kVAR KILOVOLT AMPERE REACTIVE kW KILOWATT kWH KILOWATT HOUR kWHM KILOWATT HOUR METER

LED LIGHT EMITTING DIODE

LF LINEAR FEET (FOOT)

LM LUMEN

LP LIGHT POLE

LPS LOW PRESSURE SODIUM

LRA LOCKED ROTOR AMPS

LTCP LOCAL TEMPERATURE CONTROL PANEL

LT LIGHT

LTG LIGHTING

LTG PNL LIGHTING PANEL

LTNG LIGHTNING

LV LOW VOLTAGE

MATV MASTER ANTENNA TELEVISION SYSTEM

MAX MAXIMUM

MC METAL-CLAD

MCA MINIMUM CIRCUIT AMPS

MCB MAIN CIRCUIT BREAKER

MCC MOTOR CONTROL CENTER

MDP MAIN DISTRIBUTION PANEL

MECH MECHANICAL

MG MOTOR GENERATOR

MH MANHOLE

MIN MINIMUM

MOCP MAXIMUM OVERCURRENT PROTECTION

MLO MAIN LUGS ONLY

MT MOUNT

MTD MOUNTED

MTG MOUNTING

MTS MANUAL TRANSFER SWITCH

MV MEDIUM VOLTAGE

MVA MEGAVOLT-AMPERE

MW MEGAWATT MICROWAVE

NA NOT APPLICABLE

NAC NOTIFICATION APPLIANCES CIRCUIT PANEL

NEC NATIONAL ELECTRICAL CODE

NEMA NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION

NEUT OR N NEUTRAL

NFPA NATIONAL FIRE PROTECTION ASSOCIATION

NIC NOT IN CONTRACT

NL NIGHT LIGHT

NO NORMALLY OPEN

NS NO SCALE

NTS NOT TO SCALE

OC ON CENTER

OD OUTSIDE DIAMETER

OL OVERLOAD

P POLE

PA PUBLIC ADDRESS

PB PANELBOARD, PULL BOX, OR PUSHBUTTON

PBPU PREFABRICATED BEDSIDE PATIENT UNIT

PCB POLYCHLORINATED BIPHENYL

PEC PHOTOELECTRIC CELL

PED PEDESTAL

PEND PENDANT

PF POWER FACTOR

PH PHASE

PNL PANEL

POD POWER OPERATED DAMPER

PT POTENTIAL TRANSFORMER

PTRV POWER TYPE ROOF VENTILATION

PVC POLYVINYL CHLORIDE (PLASTIC)

PWR POWER

RCP REFLECTED CEILING PLAN

REC RECESSED

RECPT RECEPTACLE

RGS RIGID GALVANIZED STEEL

RM ROOM

RMS ROOT MEAN SQUARE

REQD REQUIRED

SCC SHORT CIRCUIT CAPACITY

SES SERVICE ENTRANCE SECTION

SD SMOKE DETECTOR

SF SQUARE FOOT (FEET)

SHT SHEET

SI INTERNATIONAL SYSTEM OF UNITS

SPEC SPECIFICATION

SPST SINGLE POLE, SINGLE THROW

SURF SURFACE

SW SWITCH

SWBD SWITCHBOARD

SWGR SWITCHGEAR

TC TIME CLOCK

TEL TELEPHONE

TP TWISTED PAIR

TPS TWISTED PAIR SHIELDED

TTB TELEPHONE TERMINAL BOARD

TV TELEVISION

TYP TYPICAL

UFD UNDERFLOOR DUCT

UGND UNDERGROUND

UL UNDERWRITERS LABORATORY

UON UNLESS OTHERWISE NOTED

UPS UNINTERRUPTIBLE POWER SUPPLY

UTIL UTILITY

V VOLT

VA VOLT AMPERE

VAR VOLT AMPERE REACTIVE

VFD VARIABLE FREQUENCY DRIVE

VOLT VOLTAGE

W WATT

WH WATER HEATER

WP WEATHERPROOF

XFER TRANSFER

XFMR TRANSFORMER

FUSE WITH RATING

NORMALLY CLOSED RELAY CONTACT

NORMALLY OPEN RELAY CONTACT

MOLDED CASE CIRCUIT BREAKER

LOW-VOLTAGE DRAWOUT AIR CIRCUIT BREAKER

SWITCH AND FUSE UNIT

FUSED DRAWOUT POTENTIAL TRANSFORMER

DELTA CONNECTION

TRANSFORMER

WYE CONNECTION

EARTH GROUND

PULL BOX

POWER JUNCTION BOX

TRANSFORMER, PLAN

J

MOTOR, SINGLE-PHASE

MOTOR, THREE-PHASE

WYE CONNECTION

EARTH GROUND

LADDER CABLE TRAY

PULL BOX

WIREWAY

RECEPTACLE, DUPLEX

RECEPTACLE, DUPLEX ON EMERGENCY POWER

RECEPTACLE, DUPLEX WITH GROUND FAULT CIRCUIT INTERRUPTER

RECEPTACLE, QUADRAPLEX

ELECTRICAL STRIP MOLD (OUTLETS ON 2'-0" CENTERS OR AS

DESIGNATED ON DRAWINGS), MTD 3'-6" AFF OR AS INDICATED.

DOUBLE GANG DEEP AUDIO/VISUAL JUNCTION BOXA/V

SWITCH

BLANK = SINGLE POLE 3 = THREE-WAY

4 = FOUR-WAY K = KEY OPERATED

DM= DIMMER P = WITH PILOT LIGHT

LV= LOW VOLTAGE TM = TIMER OPERATED

WP=WEATHER PROOF X = EXPLOSION PROOF

T= THERMAL OVERLOAD PROTECTION OS= OCCUPANCY SENSOR

OS SWITCH, OCCUPANCY SENSOR REFER TO FIXTURE SCHEDULE FOR TYPE

FIRE ALARM LINE = FA

DH ELECTROMAGNETIC TYPE DOOR HOLDER OUTLET

CEILING MOUNTED RECEPTACLE ON EMERGENCY POWER

DOUBLE FACED CEILING OR WALL MOUNTED EXIT SIGN. ARROW INDICATES DIRECTION

SINGLE FACED CEILING OR WALL MOUNTED EXIT SIGN.

ARROW INDICATES DIRECTION

HOMERUN TO PANELBOARDS. 4#10 + 1#12 GROUND IN 3/4" CONDUIT

J JUNCTION BOX WITH DISCONNECT SWITCH AND FLEXIBLE

CONDUIT CONNECTION

AUTOMATIC DOOR OPERATOR PUSH PLATE

CEILING MOUNTED RECEPTACLE, L21-20R TWIST LOCK

FLOOR RECEPTACLE, DUPLEX

DUCT SMOKE DETECTOR W/REMOTE TEST STATION

WP INDICATES WEATHERPROOF HOUSING FOR BOTH

TEMPERATURE SWITCH

FLOW SWITCH

PRESSURE SWITCH

FIRE ALARM CONTROL PANEL

MONITOR MODULE

CONTROL MODULE

REMOTE TEST SWITCH W/INDICATOR

FIRE FIGHTERS TELEPHONE JACK

RECEPTACLE, QUADRAPLEX ON EMERGENCY POWER

AND EXISTING WORK

POINT OF CONNECTION BETWEEN NEW

LIMIT OF DEMOLITION

RECEPTACLE, DUPLEX WITH GROUND FAULT CIRCUIT INTERRUPTER

MOUNTED AT 44"

XX

XX

GF

TVSS

M

CM

KWH

V

AS

VS

A

ST

T

INCOMING LINE

GROUND

FUSIBLE SWITCH

CURRENT TRANSFORMER

CONTROL OR POTENTIAL TRANSFORMER

SURGE AND LIGHTNING ARRESTER

CONTACTOR

SHUNT TRIP

AMMETER

AMMETER SELECTOR SWITCH

VOLTMETER

VOLTMETER SELECTOR SWITCH

UTILITY METER

OWNER METER

KILOWATT HOUR METER

TRANSIENT VOLTAGE SURGE SUPPRESSOR

GROUND FAULT

CABLE AND CONDUIT TAG SEE

SCHEDULE

EQUIPMENT TAG SEE EQUIPMENT

SCHEDULE

CONDUIT STUBBED DOWN

CONDUIT STUBBED UP

FLEXIBLE CONDUIT

EQUIPMENT CONNECTION

EMERGENCY POWER OFF PUSHBUTTON

BELL

BUZZER

DISCONNECT SWITCH, FUSED (SWITCH/FUSE RATING)

DISCONNECT SWITCH, UNFUSED (SWITCH RATING)

STARTER, COMBINATION WITH DISCONNECT SWITCH

STARTER OR MOTOR CONTROLLER

VARIABLE FREQUENCY DRIVE

30A/20A

30A

SINGLE PHASE MOTOR (HP AS INDICATED)

THREE PHASE (HP AS INDICATED)

VAV BOX

UNIT HEATER (ELECTRIC

COIL)

UNIT HEATER (GAS OR HOT WATER

TYPE)

FAN POWERED BOX

CP

CPFP

11/8HP

2KW

UH

10KW

1/8HP

EUH

VAV

CP

CP

L6-30R TWIST LOCK RECEPTACLE ON POWER, 250V, TWO-POLE, 3W

GROUNDED

L6-30R TWIST LOCK RECEPTACLE ON NORMAL POWER, 250V,

TWO-POLE, 3W GROUNDED

FLOOR RECEPTACLE, DUPLEX ON EMERGENCY POWER

F.A. INDIVIDUAL ADDRESSABLE MODULE

F.A. DOOR HOLDER

F.A. DOOR CLOSER

FIRE ALARM SHUT DOWN RELAY

F.A. ZONE ADDRESSABLE MODULE

DOCK DOOR POSITION INDICATOR LIGHT

CCT. XX

30A/1P

CONDENSATE PUMP

CHIME

CEILING MOUNTED HORN/STROBE (A/V)

CEILING MOUNTED STROBE

CEILING MOUNTED FIRE ALARM SPEAKER

WALL MOUNTED HORN/STROBE

WALL MOUNTED STROBE

WALL MOUNTED FIRE ALARM SPEAKER

CEILING MOUNTED FIRE ALARM SPEAKER/STROBE

WALL MOUNTED FIRE ALARM SPEAKER/STROBE

MANUAL PULL STATION WP-WEATHERPROOF HOUSING

STANDARD, CEILING MOUNTED SMOKE DETECTOR

SOUNDER BASE, CEILING MOUNTED SMOKE DETECTOR

FIXED TEMP (135°), CEILING MOUNTED HEAT DETECTOR

RATE-OF-RISE STD, CEILING MOUNTED HEAT DETECTOR

MEDIUM-VOLTAGE OIL CIRCUIT BREAKER

MEDIUM-VOLTAGE DRAWOUT AIR CIRCUIT BREAKER

POTHEAD

STRESS CONE

LIGHTING WALL PACK - EXTERIOR BUILDING

LIGHT FIXTURE, DIRECTIONAL

FLOOR RECEPTACLE, QUADRAPLEX ON EMERGENCY POWER

FLOOR RECEPTACLE, QUADRAPLEX

HUMIDISTAT, WALL MOUNTED

THERMOSTAT, WALL MOUNTED PULL CORD

UNIT HEATER

LIGHTING LANDSCAPE WALL

F SD

F SSD

F HD

F HD135

F SPS

F SP

F ST

F HS

P

J

GFCI

GFCI

F SP

F SPS

PP

STF

HSF

TS

FS

PS

FACP

MM

CM

RTS/I

Z

I

FR

VALVE TAMPER SWITCH

VALVE SUPERVISORY SWITCHVSS

VTS

LEVEL SWITCHLS

T

H

B

208Y / 120 V NORMAL PANELBOARD

208Y / 120 V LIFE SAFETY PANELBOARD

480Y / 277 V LIFE SAFETY PANELBOARD

480Y / 277 V DISTRIBUTION PANELBOARD

208Y / 120 V CRITICAL PANELBOARD

480Y / 277 V NORMAL PANELBOARD

480Y / 277 V CRITICAL PANELBOARD

208Y / 120 V LIFE EQUIPMENT PANELBOARD

DISTRIBUTION SWITCHBOARD LIFE SAFETY

DISTRIBUTION SWITCHBOARD EQUIPMENT

DISTRIBUTION SWITCHBOARD NORMAL

DISTRIBUTION SWITCHBOARD CRITICAL

ELECTRICAL - SYMBOLS AND

ABBREVIATION

WG BX E-002

STRIP LIGHT FIXTURE

STRIP LIGHT WITH BATTERY

L21-20R TWIST LOCK

CEILING MOUNTED RECEPTACLE ON UPS POWER

L21-20R TWIST LOCK

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

K:

\C

C G

_P R

O

JE

C

TS

\2

1\

-1

T op ek a

EH

R M

C

1R

\4

- D es

D oc s\

2- D ra w in gs

\W O

R

KI

N G

\A ut oC

AD

\E le ct ric al \E

2_

Sy m bo ls a nd

A bb re vi at io n.

dw g 1/

/2

:3

5:

A M

ISSUE FOR BIDOffice of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

EHRM INFRASTRUCTURE

UPGRADES

COLMERY O'NEIL VA HEALTH CARE

21-116

Revisions: Date:

www. bancroft-ae.com

3300 Dundee RD.

Northbrook, IL 60062

T: 847.952.9362

35% SCHEMATIC DESIGN SUBMISSION 07-12-22

95% CONSTRUCTION DOCUMENTS SUBMISSION 10-31-23

100% CONSTRUCTION DOCUMENTS SUBMISSION

03/22/2024

12-19-23

Bancroft Project No: 21-116

35% SCHEMATIC DESIGN SUBMISSION R1 09-21-22

35% SUBMITTAL II 06-13-23

65% DESIGN DEVELOPMENT SUBMITTAL 09-12-23

ISSUED FOR BID 12-28-23

ISSUE FOR BID R1 02-28-24

ISSUE FOR BID R2 03-22-24

OS

TO NORMAL PNL

TO EM PNL

OS

TO NORMAL PNL

TO EM PNL

OS4

TO EM PNL

TO NORMAL PNL

A/C

TO PNL

TO NORMAL PNL

TO EM PNL

2 3 2 3

CORRIDOR

A/C

TO PNL TO EM PNL

2 3

TO NORMAL PNL

A/C

TO PNL

TO EM PNL

TO NORMAL PNL

3 OS

TO NORMAL PNL

TO EM PNL

A/C

TO PNL

TO EM PNL

TO NORMAL PNL

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

K:

\C

C G

_P R

O

JE

C

TS

\2

1\

-1

T op ek a

EH

R M

C

1R

\4

- D es

D oc s\

2- D ra w in gs

\W O

R

KI

N G

\A ut oC

AD

\E le ct ric al \E

3.

dw g

2/

/2

:4 6:

P

M

ISSUE FOR BIDOffice of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

EHRM INFRASTRUCTURE

UPGRADES

COLMERY O'NEIL VA HEALTH CARE

21-116

Revisions: Date:

www. bancroft-ae.com

3300 Dundee RD.

Northbrook, IL 60062

T: 847.952.9362

35% SCHEMATIC DESIGN SUBMISSION 07-12-22

95% CONSTRUCTION DOCUMENTS SUBMISSION 10-31-23

100% CONSTRUCTION DOCUMENTS SUBMISSION

03/22/2024

12-19-23

Bancroft Project No: 21-116

35% SCHEMATIC DESIGN SUBMISSION R1 09-21-22

35% SUBMITTAL II 06-13-23

65% DESIGN DEVELOPMENT SUBMITTAL 09-12-23

ISSUED FOR BID 12-28-23

ISSUE FOR BID R1 02-28-24

ISSUE FOR BID R2 03-22-24

GENERAL NOTES ELECTRICAL DEMOLITION:

A. NEW TR ROOMS SHALL BE PREPARED SUCH THAT WHEN COMPLETED, ONLY CIRCUITRY SHOWN

ON DRAWING E003 REMAINS. ALL PREVIOUS CIRCUITRY SHALL BE REMOVED BACK TO SOURCES.

B. REMOVE AVERAGE OF TWO LIGHTING FIXTURES, CONDUIT AND SWITCH(ES) BACK TO BRANCH

PANEL, AND PROPERLY DISPOSE OF FIXTURES, BALLASTS, AND ALL HARDWARE, FROM NEW TR

ROOM AREA.

C. REMOVE AVERAGE OF THREE RECEPTACLES (EMERGENCY AND NORMAL POWER) AND CONDUIT

BACK TO BRANCH PANEL, FROM TR ROOM AREA.

D. CERTIFIED FIRE PROTECTION CONTRACTOR TO REMOVE FIRE ALARM / FIRE DETECTION

COMPONENT FROM NEW TR ROOM AREA. THIS IS NOTED ON SPECIFIC DRAWINGS.

E. CERTIFIED FIRE PROTECTION CONTRACTOR TO DOCUMENT LOCATIONS OF FIRE ALARM / FIRE

DETECTION COMPONENTS REMOVED OR RELOCATED TO THEN UPDATE THE FIRE ALARM / FIRE

DETECTION ALARM SOFTWARE. SOME FIRE ALARM / FIRE DETECTION COMPONENTS REMAIN

BUT ARE RELOCATED. NO NEW FIRE ALARM / FIRE DETECTION ARE INSTALLED AS PART OF THE

EHRM PROJECT.

GENERAL NOTES ELECTRICAL:

A. CONTACT VA IT PRIOR TO WORKING IN DATA CENTER OR IT CLOSET.

B. USE PRECAUTIONS TO AVOID SNAGGING WIRING OR DAMAGING EQUIPMENT.

C. PROTECT IT EQUIPMENT FROM DUST, DURING WORK THAT CREATES DUST.

D. A WIRING MATRIX IS SHOWN FOR EVERY NEW TR ROOM. BREAKER SIZES ARE LISTED FOR UPS

AND OTHER EHRM ROOM EQUIPMENT. UTILIZE 20A CIRCUIT BREAKERS FOR ROOM LIGHTS AND

WALL RECEPTACLES (SIZES ARE NOT SHOWN ON DRAWINGS).

TR ROOM SPECIFIC NOTES:

A. RECEPTACLES TO POWER RACKS SHALL ALWAYS BE ABOVE RACKS.

B. POWER TO ONE, TWO, OR THREE RACKS AS SHOWN ON THIS DRAWING.

C. POWER FOR FOUR RACKS IS A COMBINATION OF THREE RACK AND ONE RACK DETAILS.

E. POWER FOR SIX RACKS IS A COMBINATION OF TWO THREE RACK DETAILS.

F. INSTALL LIGHTING CONTROLS PER nlight LIGHTING DETAIL ON DETAIL DRAWING .

G. NOTE THAT ONLY FAN COIL POWER IS REQUIRED IN BUILDINGS WITH CHILLED WATER.

H. BUILDINGS THAT DO NOT HAVE CHILLED WATER NEED POWER TO FAN COIL (EVAPORATOR) AND

ALSO POWER TO THE OUTDOOR CONDENSERS. SEE SUGGESTED WIRING DETAIL ON DRAWING

E-501. IF SELECTED VENDOR WIRING DETAIL IS DIFFERENT FOLLOW THE VENDOR'S WIRING

DETAIL.

I. SOME VENDOR'S EVAPORATOR UNITS DO NOT PROVIDE POWER TO THE SMALL CONDENSATE

PUMP. FOR THESE SITUATIONS INSTALL A 15A 1-POLE DISCONNECT FROM THE ROOM EM

LIGHTING CIRCUIT.

1. ONLY BRANCH CIRCUIT SHOWN FROM POWER PANEL TO COOLING UNIT, ELECTRICAL

CONTRACTOR TO WORK WITH MECHANICAL CONTRACTOR TO ROUTE POWER AND TUBING

TO OUTDOOR UNIT.

2. NORMAL POWER TO ROOM RECEPTACLES, AND LIGHTS, AND RACKS. CONTACT COR PRIOR

TO INSTALLING LIGHTING TO DETERMINE OPTIMUM LOCATION FOR LIGHT FIXTURES.

3. EMERGENCY POWER TO ROOM RECEPTACLES, AND LIGHTS, AND RACKS. CONTACT COR

PRIOR TO INSTALLING LIGHTING TO DETERMINE OPTIMUM LOCATION FOR LIGHT FIXTURES.

4. OCCUPANCY SENSOR - HIGH MOUNT.

ELECTRICAL - TR ROOMS LIGHTING

AND POWER EXAMPLE

WG BX E-003

ELECTRICAL - POWER ELEVATION AND

SCHEMATIC FOR RACK TR

WG BX E-004 083

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

K:

\C

C G

_P R

O

JE

C

TS

\2

1\

-1

T op ek a

EH

R M

C

1R

\4

- D es

D oc s\

2- D ra w in gs

\W O

R

KI

N G

\A ut oC

AD

\E le ct ric al \E

4.

dw g

/1

8/

:4 5:

P

M

ISSUE FOR BIDOffice of Construction and Facilities Management

U.S. Department of Veterans Affairs

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

EHRM INFRASTRUCTURE

UPGRADES

COLMERY O'NEIL VA HEALTH CARE

21-116

Revisions: Date:

www. bancroft-ae.com

3300 Dundee RD.

Northbrook, IL 60062

T: 847.952.9362

35% SCHEMATIC DESIGN SUBMISSION 07-12-22

95% CONSTRUCTION DOCUMENTS SUBMISSION 10-31-23

100%…

This is the start of the file's text. The full file is on GovTribe.