Attachment 5 -589A5-21-700_Topeka EHRM_IFB R2 Drawings_Vol 2_181-240.pdf

PDF 27 MB Posted

Attached to
Y1DA--589A5-21-700 EHRM INFRASTRUCTURE UPGRADES (VA-24-00076324) Topeka, KS
Solicitation number
36C77624B0026_1
Issued by

About this file

This document appears to be Attachment 5 - 589A5-21-700_Topeka EHRM_IFB R2 Drawings_Vol 2_181-240.pdf, which is related to the federal contract opportunity Solicitation Number 36C77624B0026_1 for Y1DA--589A5-21-700 EHRM INFRASTRUCTURE UPGRADES (VA-24-00076324) in Topeka, KS. The solicitation is issued by the Department of Veterans Affairs Technology Acquisition Center Austin. This attachment appears to contain technical drawings related to the infrastructure upgrades described in the contract opportunity. No additional details about required products or services, response dates, pricing, or set-asides are provided in this specific document. This appears to be a technical drawing document rather than a solicitation, performance work statement, or other key contract document.

View the file

Other files

File Type Posted
36C77624B0026 0007.docx DOCX document
36C77624B0026 0006.docx DOCX document
Government Answers to Contractor questions.docx DOCX document
Add Spec Section 23 21 13 Attachment A.pdf PDF
Revised Vol3 Drawing_M503.pdf PDF
Revised Spec Section 23 21 13.pdf PDF
36C77624B0026 0005.docx DOCX document
Pages from Addendum1_Vol2_2of2__20241209.pdf PDF
Colmery-ONeil VA Medical Center - Asbestos and Lead Survey Report signed.pdf PDF
Submittal 024 Pipe - Valve- Fittings 8-8-17.pdf PDF
589A5-21-700_TOPEKA_EHRM_SURVEY LOCATIONS-Markup.pdf PDF
Pages from Addendum1_Vol2_1of2__20241209.pdf PDF
EHRM Contractor Parking and Laydown.pdf PDF
Addendum1_Specifications_20241209.pdf PDF
Addendum1_Vol3_2of3_20241209.pdf PDF
230415-000 Topeka VA Geotech Final Report_S.pdf PDF
Addendum1_Vol3_1of3_20241209.pdf PDF
Addendum1_Vol3_3of3_20241209.pdf PDF
36C77624B0026 0004.docx DOCX document
589A5-21-700_Topeka KS_EHRM_Tech Q1_20241210.docx DOCX document
589A5-21-700_Topeka EHRM_IFB_BOD_Blast.pdf PDF
589A5-21-700_19550421_Steam Distro Plot Plan.pdf PDF
Submittal 023B Perma Pipe Fittings 8-21-17.pdf PDF
589A5-21-700_Topeka KS_EHRM_Tech Q2_20241210.docx DOCX document
Addendum1_Vol1_20241209.pdf PDF
36C77624B0026 0003.docx DOCX document
36C77624B0026 0002.docx DOCX document
S04_Site Visit Sign-in Sheet_Topeka KS.pdf PDF
S06- 36C77624B0026 0001.docx DOCX document
Attachment 1 - 589A5-21-700_Topeka EHRM__SOWV3.docx DOCX document
Attachment 16 - 589A5-21-700_Topeka EHRM_IFB R2 Drawings_Vol 3_1.pdf PDF
Attachment 15 - 589A5-21-700_Topeka EHRM_IFB R2 Drawings_Vol 2-8.pdf PDF
Attachment 10 -589A5-21-700_Topeka EHRM_IFB R2 Drawings_Vol 91-129.pdf PDF
Attachment 3 - DB Wage Determination Topeka-KS.pdf PDF
Attachment 8 -589A5-21-700_Topeka EHRM_IFB R2 Drawings_Vol 3_1-90.pdf PDF
Attachment 4 -589A5-21-700_Topeka EHRM_IFB R2 Drawings_Vol 2_118-180.pdf PDF
Attachment 11 -589A5-21-700_Topeka EHRM_IFBR2_Spec-VOL1_032224.pdf PDF
Attachment 14 - 589A5-21-700_Topeka EHRM_IFB R2 Drawings_Vol 1_134-204.pdf PDF
Attachment 13 - 589A5-21-700_Topeka EHRM_IFB R2 Drawings_Vol 1_1-18.pdf PDF
Attachment 9 -589A5-21-700_Topeka EHRM_IFB R2 Drawings_Vol 3-2.pdf PDF
Attachment 12 -589A5-21-700_Topeka EHRM_IFBR2_Spec-VOL2_032224.pdf PDF
Attachment 20 -Site Visit Instructions.docx DOCX document
Attachment 19 -589A5-21-700_Topeka EHRM_IFB R2 Drawings_Vol 2_111-117.pdf PDF
Attachment 6 -589A5-21-700_Topeka EHRM_IFB R2 Drawings_Vol 2_241-281.pdf PDF
Attachment 18 -589A5-21-700_Topeka EHRM_IFB R2 Drawings_Vol 2_1-110.pdf PDF
36C77624B0026_1.docx DOCX document
Attachment 2- Limitations on Subcontracting - Construction.docx DOCX document
Attachment 7 -589A5-21-700_Topeka EHRM_IFB R2 Drawings_Vol 2-7.pdf PDF
Attachment 17 -589A5-21-700_Topeka EHRM_IFB R2 Drawings_Vol 1_19-133.pdf PDF
Show all 49

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

TYP

ES DC

TYP

MID

RX

CR/K

ICT - BUILDING 03 - LEVEL1 - ENLARGED

PLANS

JG JG

TT-B03-411

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

K:

\C

C G

_P R

O

JE

C

TS

\2

1\

-1

T op ek a

EH

R M

C

1R

\4

- D es

D oc s\

2- D ra w in gs

\W O

R

KI

N G

\A ut oC

AD

\T T-

B0 3-

1.

dw g

3/

/2

:2 6:

A

M

ISSUE FOR BIDOffice of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

EHRM INFRASTRUCTURE

UPGRADES

COLMERY O'NEIL VA HEALTH CARE

21-116

Revisions: Date:

www. bancroft-ae.com

3300 Dundee RD.

Northbrook, IL 60062

T: 847.952.9362

35% SCHEMATIC DESIGN SUBMISSION 07-12-22

95% CONSTRUCTION DOCUMENTS SUBMISSION 10-31-23

100% CONSTRUCTION DOCUMENTS SUBMISSION

12/28/2023

12-19-23

Bancroft Project No: 21-116

35% SCHEMATIC DESIGN SUBMISSION R1 09-21-22

35% SUBMITTAL II 06-13-23

65% DESIGN DEVELOPMENT SUBMITTAL 09-12-23

ISSUED FOR BID 12-28-23

GENERAL NOTES

A. FOR GENERAL NOTES AND LEGENDS REFER TO SHEET TT001.

B. EXISTING IT/TR/OI&T ROOMS TO REMAIN ACTIVE DURING CONSTRUCTION. G.C. TO PROTECT EQUIPMENT

DURING CONSTRUCTION WITH VISQUEEN. CONTRACTOR TO ENSURE CONTINUOUS OPERATION OF

EQUIPMENT.

C. NOT ALL KEY NOTES APPLY TO ALL PLAN SHEETS. G.C. TO APPLY ONLY AS INDICATED PER EACH SHEET.

D. APPLY FIRE RATED SEALANT TO ALL EXISTING AND NEW PENETRATIONS IN EXISTING WALLS TO MAKE

EXISTING WALLS A 1 HR ASSEMBLY. BASIS OF DESIGN FOR 1 HR WALL IS UL 419 ASSEMBLY.

E. CONTRACTOR SHALL PROVIDE AND INSTALL FIRE RATED SLEEVES AS NECESSARY AND ASSEMBLED PER UL

DETAIL APPROPRIATE FOR WALL/FLOOR AND RACEWAY/CABLE TYPES.

F. TELECOMMUNICATION ROOM (TR) RACK MOUNTED PDU CORDSETS:

1. SHALL BE IEC 60320 C14-C15 DEVICE POWER CORDSETS, FUNCTIONALLY EQUIVALENT TO CISCO SYSTEMS

PART# CAB-C15-CBN.

2. SHALL BE RATED FOR: a. AT LEAST 250 VAC b.13 AMPS c.60HZ d.120 DEGREES C (248 DEGREES F)

3. UL LISTED

4. MAXIMUM OF 4 FEET IN LENGTH. SHORTER LENGTHS MAY BE USED TO REDUCE EXCESSIVE SLACK.

5. COUPLER TERMINATIONS ON CORDSET: a. IEC 60320 C14 PLUG CONNECTOR (RACK PDU END) b.IEC 60320 C15 PLUG (DEVICE END)

6. SELECTION OF DISTINCT CONTRASTING CORDSET COLORS TO INDICATE DIVERSE (A/B) POWER

DISTRIBUTION SOURCES.

a. BLACK AND GRAY RECOMMENDED.

7. QUANTITY:

a. PROVIDE ONE SET OF C14-C15 POWER CORDS PER DEVICE TO BE CONNECTED TO RACK

MOUNTED PDU’S.

i. ONE SET SHALL CONSIST OF TWO (2) POWER CORDS FOR CONNECTION TO

DIVERSE (A/B) POWER DISTRIBUTION SOURCES.

b. PROVIDE MINIMUM OF ONE SET OF C14-C15 POWER CORDS PER SET OF RACK MOUNTED PDU’S.

c. PROVIDE MINIMUM OF ONE SET OF C14-C15 POWER CORDS PER RACK INSTALLED IN EACH TR.

d. IN ADDITION OF QUANTITIES LISTED ABOVE, PROVIDE ONE SPARE SET OF C14-C15 POWER CORDS

PER TR.

FLOOR PLAN KEYNOTESX

FLOOR PLAN LEGEND

BACKBOARD PROVIDED AND INSTALLED BY OTHERS.

DEMO PLAN GENERAL NOTES

1. REMOVE EXISTING WALL MOUNTED SERVER RACK.

2. RELOCATE EXISTING UTILITY PIPING AS REQUIRED TO ACCOMMODATE NEW

SERVER RACK. COORDINATE FINAL LOCATIONS WITH VA/COR.

3. PROVIDE AND INSTALL VISQUEEN TYPE PLASTIC SHEET AND ZIPPER DOOR AS

REQUIRED TO MAINTAIN TYPE V INFECTION CONTROL PRECAUTIONS. EXTEND

AND SEAL TO ROOF DECK/STRUCTURE ABOVE.

4. SUPPLY AND INSTALL WALK OFF MATS.

5. PROTECT EXISTING FINISHES FROM DUST AND DAMAGE.

1. PROVIDE MIGHTY MO 20 RACK, OR-MM20730B (OR EQUIVALENT)

2. PROVIDE VERTICAL WIRE MANAGER, OR-MM20VMD706 (OR EQUIVALENT)

3. PROVIDE 4'X8' AC GRADE 3/4" TRADE SIZE FIRE RATED PLYWOOD BACKBOARD PAINTED HIGH GLOSS WHITE WITH

(2) COATS OF PAINT FOR SERVICE PROVIDER/SECURITY/VIDEO/ETC. AROUND PERIMETER WALLS OF TR"s AND ENTRANCE ROOMS AS SHOWN. ENSURE THAT FIRE RATING STAMP IS TO REMAIN UNCOVERED BY PAINT.

4. PROVIDE FIXED CAMERA WITH PASSIVE INFRARED(PIR) SUPPLEMENTAL LIGHTING ON TELECOM ROOM CORNER.

5. PROVIDE ACCESS CONTROL DEVICES ON SECURITY DOOR.

6. PROVIDE COPPER GROUNDING BUSBAR AT 5' AFF IN LOCATION SHOWN. SEE GROUNDING BAR DETAIL FOR

ADDITIONAL REQUIREMENTS.

7. BASKET STYLE CABLE TRAY MINIMUM 4"X18" SHALL BE USED. ALL TRAY MUST BE INSTALLED AT 7'8" AFF, SUPPORTED PER MANUFACTURER REQUIREMENTS, AND PROPERLY BONDED TO GROUND.

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

ROOM A-129B

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 1'

AutoCAD SHX Text 2'

AutoCAD SHX Text 4'

AutoCAD SHX Text 8'

AutoCAD SHX Text 1/4"=1'-0"

AutoCAD SHX Text

AutoCAD SHX Text

BUILDING 03 - ENLARGED PLAN RM A-129B

AutoCAD SHX Text

AutoCAD SHX Text 1'

AutoCAD SHX Text 2'

AutoCAD SHX Text 4'

AutoCAD SHX Text 8'

AutoCAD SHX Text 1/4"=1'-0"

AutoCAD SHX Text

AutoCAD SHX Text

BUILDING 03 - ENLARGED RCP RM A-129B

AutoCAD SHX Text

KEY PLAN

AutoCAD SHX Text N mgonser Snapshot mgonser Snapshot mgonser Snapshot mgonser Snapshot

TYPTYP

ES DC

TYP

MID

RX

CR/K

ICT - BUILDING 03 - LEVEL 2 -

ENLARGED PLANS

JG JG

TT-B03-421

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

K:

\C

C G

_P R

O

JE

C

TS

\2

1\

-1

T op ek a

EH

R M

C

1R

\4

- D es

D oc s\

2- D ra w in gs

\W O

R

KI

N G

\A ut oC

AD

\T T-

B0 3-

1.

dw g

3/

/2

:3 1:

A

M

ISSUE FOR BIDOffice of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

EHRM INFRASTRUCTURE

UPGRADES

COLMERY O'NEIL VA HEALTH CARE

21-116

Revisions: Date:

www. bancroft-ae.com

3300 Dundee RD.

Northbrook, IL 60062

T: 847.952.9362

35% SCHEMATIC DESIGN SUBMISSION 07-12-22

95% CONSTRUCTION DOCUMENTS SUBMISSION 10-31-23

100% CONSTRUCTION DOCUMENTS SUBMISSION

12/28/2023

12-19-23

Bancroft Project No: 21-116

35% SCHEMATIC DESIGN SUBMISSION R1 09-21-22

35% SUBMITTAL II 06-13-23

65% DESIGN DEVELOPMENT SUBMITTAL 09-12-23

ISSUED FOR BID 12-28-23

GENERAL NOTES

A. FOR GENERAL NOTES AND LEGENDS REFER TO SHEET TT001.

B. EXISTING IT/TR/OI&T ROOMS TO REMAIN ACTIVE DURING CONSTRUCTION. G.C. TO PROTECT EQUIPMENT

DURING CONSTRUCTION WITH VISQUEEN. CONTRACTOR TO ENSURE CONTINUOUS OPERATION OF

EQUIPMENT.

C. NOT ALL KEY NOTES APPLY TO ALL PLAN SHEETS. G.C. TO APPLY ONLY AS INDICATED PER EACH SHEET.

D. APPLY FIRE RATED SEALANT TO ALL EXISTING AND NEW PENETRATIONS IN EXISTING WALLS TO MAKE

EXISTING WALLS A 1 HR ASSEMBLY. BASIS OF DESIGN FOR 1 HR WALL IS UL 419 ASSEMBLY.

E. CONTRACTOR SHALL PROVIDE AND INSTALL FIRE RATED SLEEVES AS NECESSARY AND ASSEMBLED PER UL

DETAIL APPROPRIATE FOR WALL/FLOOR AND RACEWAY/CABLE TYPES.

F. TELECOMMUNICATION ROOM (TR) RACK MOUNTED PDU CORDSETS:

1. SHALL BE IEC 60320 C14-C15 DEVICE POWER CORDSETS, FUNCTIONALLY EQUIVALENT TO CISCO SYSTEMS

PART# CAB-C15-CBN.

2. SHALL BE RATED FOR: a. AT LEAST 250 VAC b.13 AMPS c.60HZ d.120 DEGREES C (248 DEGREES F)

3. UL LISTED

4. MAXIMUM OF 4 FEET IN LENGTH. SHORTER LENGTHS MAY BE USED TO REDUCE EXCESSIVE SLACK.

5. COUPLER TERMINATIONS ON CORDSET: a. IEC 60320 C14 PLUG CONNECTOR (RACK PDU END) b.IEC 60320 C15 PLUG (DEVICE END)

6. SELECTION OF DISTINCT CONTRASTING CORDSET COLORS TO INDICATE DIVERSE (A/B) POWER

DISTRIBUTION SOURCES.

a. BLACK AND GRAY RECOMMENDED.

7. QUANTITY:

a. PROVIDE ONE SET OF C14-C15 POWER CORDS PER DEVICE TO BE CONNECTED TO RACK

MOUNTED PDU’S.

i. ONE SET SHALL CONSIST OF TWO (2) POWER CORDS FOR CONNECTION TO

DIVERSE (A/B) POWER DISTRIBUTION SOURCES.

b. PROVIDE MINIMUM OF ONE SET OF C14-C15 POWER CORDS PER SET OF RACK MOUNTED PDU’S.

c. PROVIDE MINIMUM OF ONE SET OF C14-C15 POWER CORDS PER RACK INSTALLED IN EACH TR.

d. IN ADDITION OF QUANTITIES LISTED ABOVE, PROVIDE ONE SPARE SET OF C14-C15 POWER CORDS

PER TR.

FLOOR PLAN KEYNOTESX

FLOOR PLAN LEGEND

BACKBOARD PROVIDED AND INSTALLED BY OTHERS.

DEMO PLAN GENERAL NOTES

1. REMOVE EXISTING WALL MOUNTED SERVER RACK.

2. RELOCATE EXISTING UTILITY PIPING AS REQUIRED TO ACCOMMODATE NEW

SERVER RACK. COORDINATE FINAL LOCATIONS WITH VA/COR.

3. PROVIDE AND INSTALL VISQUEEN TYPE PLASTIC SHEET AND ZIPPER DOOR AS

REQUIRED TO MAINTAIN TYPE V INFECTION CONTROL PRECAUTIONS. EXTEND

AND SEAL TO ROOF DECK/STRUCTURE ABOVE.

4. SUPPLY AND INSTALL WALK OFF MATS.

5. PROTECT EXISTING FINISHES FROM DUST AND DAMAGE.

1. PROVIDE MIGHTY MO 20 RACK, OR-MM20730B (OR EQUIVALENT)

2. PROVIDE VERTICAL WIRE MANAGER, OR-MM20VMD706 (OR EQUIVALENT)

3. PROVIDE 4'X8' AC GRADE 3/4" TRADE SIZE FIRE RATED PLYWOOD BACKBOARD PAINTED HIGH GLOSS WHITE WITH

(2) COATS OF PAINT FOR SERVICE PROVIDER/SECURITY/VIDEO/ETC. AROUND PERIMETER WALLS OF TR"s AND ENTRANCE ROOMS AS SHOWN. ENSURE THAT FIRE RATING STAMP IS TO REMAIN UNCOVERED BY PAINT.

4. PROVIDE FIXED CAMERA WITH PASSIVE INFRARED(PIR) SUPPLEMENTAL LIGHTING ON TELECOM ROOM CORNER.

5. PROVIDE ACCESS CONTROL DEVICES ON SECURITY DOOR.

6. PROVIDE COPPER GROUNDING BUSBAR AT 5' AFF IN LOCATION SHOWN. SEE GROUNDING BAR DETAIL FOR

ADDITIONAL REQUIREMENTS.

7. BASKET STYLE CABLE TRAY MINIMUM 4"X18" SHALL BE USED. ALL TRAY MUST BE INSTALLED AT 7'8" AFF, SUPPORTED PER MANUFACTURER REQUIREMENTS, AND PROPERLY BONDED TO GROUND.

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

ROOM A-229A

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 1'

AutoCAD SHX Text 2'

AutoCAD SHX Text 4'

AutoCAD SHX Text 8'

AutoCAD SHX Text 1/4"=1'-0"

AutoCAD SHX Text

AutoCAD SHX Text

BUILDING 03 - ENLARGED PLAN RM A-229A

AutoCAD SHX Text

AutoCAD SHX Text 1'

AutoCAD SHX Text 2'

AutoCAD SHX Text 4'

AutoCAD SHX Text 8'

AutoCAD SHX Text 1/4"=1'-0"

AutoCAD SHX Text

AutoCAD SHX Text

BUILDING 03 - ENLARGED RCP RM A-229A

AutoCAD SHX Text

KEY PLAN

AutoCAD SHX Text N mgonser Snapshot mgonser Snapshot mgonser Snapshot

DNDN

UP

UPUP

C0-C1A0-C1B0-C1 B09

B09A

B09B

C17

C17A

C17B

C17F C18

C19E

C15 C15B

C15A

C19

C23 C22

A14

A24A24A

A24B

A13A0-S1

A12F A11

A2E A01E B04B05

B07E

B08FB08

B07 B03

A01A

A01A02 C20

A0-E9

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

K:

\C

C G

_P R

O

JE

C

TS

\2

1\

-1

T op ek a

EH

R M

C

1R

\4

- D es

D oc s\

2- D ra w in gs

\W O

R

KI

N G

\A ut oC

AD

\T T-

B0 4-

0.

dw g

1/

/2

2:

:0

PM

ISSUE FOR BIDOffice of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

EHRM INFRASTRUCTURE

UPGRADES

COLMERY O'NEIL VA HEALTH CARE

21-116

Revisions: Date:

www. bancroft-ae.com

3300 Dundee RD.

Northbrook, IL 60062

T: 847.952.9362

35% SCHEMATIC DESIGN SUBMISSION 07-12-22

95% CONSTRUCTION DOCUMENTS SUBMISSION 10-31-23

100% CONSTRUCTION DOCUMENTS SUBMISSION

12/28/2023

12-19-23

Bancroft Project No: 21-116

35% SCHEMATIC DESIGN SUBMISSION R1 09-21-22

35% SUBMITTAL II 06-13-23

65% DESIGN DEVELOPMENT SUBMITTAL 09-12-23

ISSUED FOR BID 12-28-23

ICT - BUILDING 4 BASEMENT LEVEL

CABLE TRAY PLAN

JG JG

TT-B04-100

GENERAL NOTES

A. FOR GENERAL NOTES AND LEGENDS REFER TO SHEET TT001.

B. EXISTING IT/TR/OI&T ROOMS TO REMAIN ACTIVE DURING CONSTRUCTION. G.C. TO PROTECT EQUIPMENT

DURING CONSTRUCTION WITH VISQUEEN. CONTRACTOR TO ENSURE CONTINUOUS OPERATION OF EQUIPMENT.

C. NOT ALL KEY NOTES APPLY TO ALL PLAN SHEETS. G.C. TO APPLY ONLY AS INDICATED PER EACH SHEET.

D. APPLY FIRE RATED SEALANT TO ALL EXISTING AND NEW PENETRATIONS IN EXISTING WALLS TO MAKE

EXISTING WALLS A 1 HR ASSEMBLY. BASIS OF DESIGN FOR 1 HR WALL IS UL 419 ASSEMBLY.

E. CONTRACTOR SHALL PROVIDE AND INSTALL FIRE RATED SLEEVES AS NECESSARY AND ASSEMBLED PER UL

DETAIL APPROPRIATE FOR WALL/FLOOR AND RACEWAY/CABLE TYPES

FLOOR PLAN KEYNOTESX

FLOOR PLAN LEGEND

BASKET CABLE TRAY.

1. PROVIDE BASKET TYPE CABLE TRAY TO SUPPORT OPTICAL FIBER BACKBONE AND NEW CAT 6A HORIZONTAL CABLING. CABLE TRAY TO BE SIZED AS PER CABLE TRAY CAPACITY PLANNING ON FLOOR PLAN LEGEND, ASSUMING 40% FILL AND 25% SPARE CAPACITY. ROUTING SHOWN INDICATES PRIMARY PATHWAYS. IN ADDITION TO PRIMARY PATHWAYS, CABLE TRAY SHALL BE PROVIDED WHEN CABLE BUNDLES EXCEED 24 CABLES. FIRE RATED MECHANICAL SLEEVE ASSEMBLIES SHALL BE PROVIDED WHEN PASSING THROUGH FIRE

RATED PARTITIONS. ASSUMING 40% FILL AND 50% SPARE CAPACITY.

CAT. NO

CF105/300

CF105/450

CF105/500

CF105/600

CF150/150

CF150/200

CF150/300

CF150/450

CF150/500

CF150/600

CF150/900

DEPTH

(IN)

WIDTH

(IN)

CAT 6A 4 PAIR

PLENUM (0.35")

- CABLE TRAY CAPACITY PLANNING.

- PROPOSED CABLE TRAY:

CABLOFIL 4" DEEP X 12" WIDE MINIMUM

(SIZE COMMENSURATE WITH DISTRIBUTION

REQUIREMENT) WHITE POWERCOAT TRAY INSERT.

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

KEY PLAN

AutoCAD SHX Text N

AutoCAD SHX Text

AutoCAD SHX Text 4'

AutoCAD SHX Text 8'

AutoCAD SHX Text 16'

AutoCAD SHX Text 32'

AutoCAD SHX Text 1/16"=1'-0"

AutoCAD SHX Text

AutoCAD SHX Text

BUILDING 4 - BASEMENT LEVEL CABLE TRAY PLAN

AutoCAD SHX Text

NORTH

mgonser Snapshot mgonser Snapshot mgonser Snapshot

UPUP

C0-C1A0-C1B0-C1 B09

B09A

B09B

C17

C17A

C17B

C17F C18

C19E

C15 C15B

C15A

C19

C23 C22

A14

A24A24A

A24B

A13A0-S1

A12F A11

A2E A01E B04B05

B07E

B08FB08

B07 B03

A01A

A01A02 C20

A0-E9

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

K:

\C

C G

_P R

O

JE

C

TS

\2

1\

-1

T op ek a

EH

R M

C

1R

\4

- D es

D oc s\

2- D ra w in gs

\W O

R

KI

N G

\A ut oC

AD

\T T-

B0 4-

0R

P.

dw g 3/

/2

6:

:1

PM

ISSUE FOR BIDOffice of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

EHRM INFRASTRUCTURE

UPGRADES

COLMERY O'NEIL VA HEALTH CARE

21-116

Revisions: Date:

www. bancroft-ae.com

3300 Dundee RD.

Northbrook, IL 60062

T: 847.952.9362

35% SCHEMATIC DESIGN SUBMISSION 07-12-22

95% CONSTRUCTION DOCUMENTS SUBMISSION 10-31-23

100% CONSTRUCTION DOCUMENTS SUBMISSION

12/28/2023

12-19-23

Bancroft Project No: 21-116

35% SCHEMATIC DESIGN SUBMISSION R1 09-21-22

35% SUBMITTAL II 06-13-23

65% DESIGN DEVELOPMENT SUBMITTAL 09-12-23

ISSUED FOR BID 12-28-23

ICT - BUILDING 4 BASEMENT LEVEL -

ROUTING PLAN

JG JG

TT-B04-100RP

GENERAL NOTES

A. FOR GENERAL NOTES AND LEGENDS REFER TO SHEET TT001.

B. EXISTING IT/TR/OI&T ROOMS TO REMAIN ACTIVE DURING CONSTRUCTION. G.C. TO PROTECT EQUIPMENT

DURING CONSTRUCTION WITH VISQUEEN. CONTRACTOR TO ENSURE CONTINUOUS OPERATION OF EQUIPMENT.

C. NOT ALL KEY NOTES APPLY TO ALL PLAN SHEETS. G.C. TO APPLY ONLY AS INDICATED PER EACH SHEET.

D. APPLY FIRE RATED SEALANT TO ALL EXISTING AND NEW PENETRATIONS IN EXISTING WALLS TO MAKE

EXISTING WALLS A 1 HR ASSEMBLY. BASIS OF DESIGN FOR 1 HR WALL IS UL 419 ASSEMBLY.

E. CONTRACTOR SHALL PROVIDE AND INSTALL FIRE RATED SLEEVES AS NECESSARY AND ASSEMBLED PER UL

DETAIL APPROPRIATE FOR WALL/FLOOR AND RACEWAY/CABLE TYPES

FLOOR PLAN KEYNOTESX

1. PROVIDE SLEEVES, CONDUITS OR MECHANICAL FIRE-PROOF ASSEMBLIES AS REQUIRED THROUGH WALLS OR FLOORS AS REQUIRED TO MAINTAIN EXISTING RATING. REFER TO ONE-LINE CABLE RISER DIAGRAMS FOR CABLE QUANTITY AND TYPE. CONTRACTOR SHALL SIZE PATHWAYS TO ACCOMMODATE DAY ONE CABLING

PLUS 40 PERCENT SPARE FUTURE CAPACITY.

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

KEY PLAN

AutoCAD SHX Text N

AutoCAD SHX Text

AutoCAD SHX Text 4'

AutoCAD SHX Text 8'

AutoCAD SHX Text 16'

AutoCAD SHX Text 32'

AutoCAD SHX Text 1/16"=1'-0"

AutoCAD SHX Text

AutoCAD SHX Text

BUILDING 4 - BASEMENT LEVEL ROUTING PLAN

AutoCAD SHX Text

NORTH

mgonser Snapshot mgonser Snapshot mgonser Snapshot

UP UP

UPUP UP

A1-S1

A101

A138A

A136

A139

A136A

A137

A141

A143

A140

A144 A145

A102

B134

A102EA103E

A103

A1-C4

A138

B112

B104B105

B1-C2

B131

B108

B132

B132A

B130

B129

B129A

B128

B106 B107

B125F

B1-S3

B125

B125A

B126

B126A

B127

B127A

B133

B123

B115E

B122

B113

B114

B115

B121E

B116

B116A

B117B118

B121

B121AB120

B109

B119

B119A

A101A

C1-3

C163E

C163 C164

C165

C166 C167

C168

C169C169AC170

C148

C149

C150

C151

C153

C154 C155

C156

C157

C158C158F

C162

C161

C160C142A

C145 C146

C143

C143A

C143B

C142

C144

C175A C174A

C172

C171

C170E

C152

C173

C174C175

C147

C1-C1A1-C2

A1-C1

A1-C3

B110

C1-C2

B1-C1

B1-C4

B1-C3

C144A

C163A

A1-E9

C1-S2 C150A

B130A

A138B

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

K:

\C

C G

_P R

O

JE

C

TS

\2

1\

-1

T op ek a

EH

R M

C

1R

\4

- D es

D oc s\

2- D ra w in gs

\W O

R

KI

N G

\A ut oC

AD

\T T-

B0 4-

1.

dw g

1/

/2

2:

:0

PM

ISSUE FOR BIDOffice of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

EHRM INFRASTRUCTURE

UPGRADES

COLMERY O'NEIL VA HEALTH CARE

21-116

Revisions: Date:

www. bancroft-ae.com

3300 Dundee RD.

Northbrook, IL 60062

T: 847.952.9362

35% SCHEMATIC DESIGN SUBMISSION 07-12-22

95% CONSTRUCTION DOCUMENTS SUBMISSION 10-31-23

100% CONSTRUCTION DOCUMENTS SUBMISSION

12/28/2023

12-19-23

Bancroft Project No: 21-116

35% SCHEMATIC DESIGN SUBMISSION R1 09-21-22

35% SUBMITTAL II 06-13-23

65% DESIGN DEVELOPMENT SUBMITTAL 09-12-23

ISSUED FOR BID 12-28-23

ICT - BUILDING 4 - LEVEL 1 CABLE TRAY

PLAN

JG JG

TT-B04-101

GENERAL NOTES

A. FOR GENERAL NOTES AND LEGENDS REFER TO SHEET TT001.

B. EXISTING IT/TR/OI&T ROOMS TO REMAIN ACTIVE DURING CONSTRUCTION. G.C. TO PROTECT EQUIPMENT

DURING CONSTRUCTION WITH VISQUEEN. CONTRACTOR TO ENSURE CONTINUOUS OPERATION OF EQUIPMENT.

C. NOT ALL KEY NOTES APPLY TO ALL PLAN SHEETS. G.C. TO APPLY ONLY AS INDICATED PER EACH SHEET.

D. APPLY FIRE RATED SEALANT TO ALL EXISTING AND NEW PENETRATIONS IN EXISTING WALLS TO MAKE

EXISTING WALLS A 1 HR ASSEMBLY. BASIS OF DESIGN FOR 1 HR WALL IS UL 419 ASSEMBLY.

E. CONTRACTOR SHALL PROVIDE AND INSTALL FIRE RATED SLEEVES AS NECESSARY AND ASSEMBLED PER UL

DETAIL APPROPRIATE FOR WALL/FLOOR AND RACEWAY/CABLE TYPES

FLOOR PLAN KEYNOTESX

FLOOR PLAN LEGEND

BASKET CABLE TRAY.

1. PROVIDE BASKET TYPE CABLE TRAY TO SUPPORT OPTICAL FIBER BACKBONE AND NEW CAT 6A HORIZONTAL CABLING. CABLE TRAY TO BE SIZED AS PER CABLE TRAY CAPACITY PLANNING ON FLOOR PLAN LEGEND, ASSUMING 40% FILL AND 25% SPARE CAPACITY. ROUTING SHOWN INDICATES PRIMARY PATHWAYS. IN ADDITION TO PRIMARY PATHWAYS, CABLE TRAY SHALL BE PROVIDED WHEN CABLE BUNDLES EXCEED 24 CABLES. FIRE RATED MECHANICAL SLEEVE ASSEMBLIES SHALL BE PROVIDED WHEN PASSING THROUGH FIRE

RATED PARTITIONS. ASSUMING 40% FILL AND 50% SPARE CAPACITY.

CAT. NO

CF105/300

CF105/450

CF105/500

CF105/600

CF150/150

CF150/200

CF150/300

CF150/450

CF150/500

CF150/600

CF150/900

DEPTH

(IN)

WIDTH

(IN)

CAT 6A 4 PAIR

PLENUM (0.35")

- CABLE TRAY CAPACITY PLANNING.

- PROPOSED CABLE TRAY:

CABLOFIL 4" DEEP X 12" WIDE MINIMUM

(SIZE COMMENSURATE WITH DISTRIBUTION

REQUIREMENT) WHITE POWERCOAT TRAY INSERT.

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 4'

AutoCAD SHX Text 8'

AutoCAD SHX Text 16'

AutoCAD SHX Text 32'

AutoCAD SHX Text 1/16"=1'-0"

AutoCAD SHX Text

AutoCAD SHX Text

BUILDING 4 - LEVEL 1 CABLE TRAY PLAN

AutoCAD SHX Text

NORTH

AutoCAD SHX Text

KEY PLAN

AutoCAD SHX Text N mgonser Snapshot mgonser Snapshot mgonser Snapshot

UPUP UP

A1-S1

A101

A138A

A136

A139

A136A

A137

A141

A143

A140

A144 A145

A102

B134

A102EA103E

A103

A1-C4

A138

B112

B104B105

B1-C2

B131

B108

B132

B132A

B130

B129

B129A

B128

B106 B107

B125F

B1-S3

B125

B125A

B126

B126A

B127

B127A

B133

B123

B115E

B122

B113

B114

B115

B121E

B116

B116A

B117B118

B121

B121AB120

B109

B119

B119A

A101A

C1-3

C163E

C163 C164

C165

C166 C167

C168

C169C169AC170

C148

C149

C150

C151

C153

C154 C155

C156

C157

C158C158F

C162

C161

C160C142A

C145 C146

C143

C143A

C143B

C142

C144

C175A C174A

C172

C171

C170E

C152

C173

C174C175

C147

C1-C1A1-C2

A1-C1

A1-C3

B110

C1-C2

B1-C1

B1-C4

B1-C3

C144A

C163A

A1-E9

C1-S2 C150A

B130A

A138B

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

K:

\C

C G

_P R

O

JE

C

TS

\2

1\

-1

T op ek a

EH

R M

C

1R

\4

- D es

D oc s\

2- D ra w in gs

\W O

R

KI

N G

\A ut oC

AD

\T T-

B0 4-

1R

P.

dw g 3/

/2

6:

:2

PM

ISSUE FOR BIDOffice of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

EHRM INFRASTRUCTURE

UPGRADES

COLMERY O'NEIL VA HEALTH CARE

21-116

Revisions: Date:

www. bancroft-ae.com

3300 Dundee RD.

Northbrook, IL 60062

T: 847.952.9362

35% SCHEMATIC DESIGN SUBMISSION 07-12-22

95% CONSTRUCTION DOCUMENTS SUBMISSION 10-31-23

100% CONSTRUCTION DOCUMENTS SUBMISSION

12/28/2023

12-19-23

Bancroft Project No: 21-116

35% SCHEMATIC DESIGN SUBMISSION R1 09-21-22

35% SUBMITTAL II 06-13-23

65% DESIGN DEVELOPMENT SUBMITTAL 09-12-23

ISSUED FOR BID 12-28-23

ICT - BUILDING 4 - LEVEL 1 - ROUTING

PLAN

JG JG

TT-B04-101RP

GENERAL NOTES

A. FOR GENERAL NOTES AND LEGENDS REFER TO SHEET TT001.

B. EXISTING IT/TR/OI&T ROOMS TO REMAIN ACTIVE DURING CONSTRUCTION. G.C. TO PROTECT EQUIPMENT

DURING CONSTRUCTION WITH VISQUEEN. CONTRACTOR TO ENSURE CONTINUOUS OPERATION OF EQUIPMENT.

C. NOT ALL KEY NOTES APPLY TO ALL PLAN SHEETS. G.C. TO APPLY ONLY AS INDICATED PER EACH SHEET.

D. APPLY FIRE RATED SEALANT TO ALL EXISTING AND NEW PENETRATIONS IN EXISTING WALLS TO MAKE

EXISTING WALLS A 1 HR ASSEMBLY. BASIS OF DESIGN FOR 1 HR WALL IS UL 419 ASSEMBLY.

E. CONTRACTOR SHALL PROVIDE AND INSTALL FIRE RATED SLEEVES AS NECESSARY AND ASSEMBLED PER UL

DETAIL APPROPRIATE FOR WALL/FLOOR AND RACEWAY/CABLE TYPES

FLOOR PLAN KEYNOTESX

1. PROVIDE SLEEVES, CONDUITS OR MECHANICAL FIRE-PROOF ASSEMBLIES AS REQUIRED THROUGH WALLS OR FLOORS AS REQUIRED TO MAINTAIN EXISTING RATING. REFER TO ONE-LINE CABLE RISER DIAGRAMS FOR CABLE QUANTITY AND TYPE. CONTRACTOR SHALL SIZE PATHWAYS TO ACCOMMODATE DAY ONE CABLING

PLUS 40 PERCENT SPARE FUTURE CAPACITY.

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 4'

AutoCAD SHX Text 8'

AutoCAD SHX Text 16'

AutoCAD SHX Text 32'

AutoCAD SHX Text 1/16"=1'-0"

AutoCAD SHX Text

AutoCAD SHX Text

BUILDING 4 - LEVEL 1 ROUTING PLAN

AutoCAD SHX Text

NORTH

AutoCAD SHX Text

KEY PLAN

AutoCAD SHX Text N mgonser Snapshot mgonser Snapshot mgonser Snapshot

A201

A236

A271

A234F

A2 -S

A238

A237

A269 C268 C267 C265

C239A

C240 C239

C249

C250

C256

C255A

C254

C253A

C253

C263 C255

C262

C256E

C251E

C257

C258

C2-S2

C247

C243A

C243

C242

C246A

C246

C247F

C247G

C244A

C264

C2-C1

C2-C2

C252

C241

C2-C3

C251A C251

C244

C247A

B231 A234A234A

A202EA203E

B204B205B206

B232

B230

B225F

B2-C1

B225

B225A

B223

B222

B221E

B215EB2-C3

B213

B214

B215

B216A

B217B218

B226A

B226

B209 B208

B207 A203

B232A

B233

B229A

B229

B227A

B227 B228

B2 -S

B218A

B219 B220A B220

B221

B216 A202 A270

B210B212

B2-C4

B2-C2

C266

C261

C2-C4

C259

A2-9

C242AB230A

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

K:

\C

C G

_P R

O

JE

C

TS

\2

1\

-1

T op ek a

EH

R M

C

1R

\4

- D es

D oc s\

2- D ra w in gs

\W O

R

KI

N G

\A ut oC

AD

\T T-

B0 4-

2.

dw g

1/

/2

2:

:0

PM

ISSUE FOR BIDOffice of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

EHRM INFRASTRUCTURE

UPGRADES

COLMERY O'NEIL VA HEALTH CARE

21-116

Revisions: Date:

www. bancroft-ae.com

3300 Dundee RD.

Northbrook, IL 60062

T: 847.952.9362

35% SCHEMATIC DESIGN SUBMISSION 07-12-22

95% CONSTRUCTION DOCUMENTS SUBMISSION 10-31-23

100% CONSTRUCTION DOCUMENTS SUBMISSION

12/28/2023

12-19-23

Bancroft Project No: 21-116

35% SCHEMATIC DESIGN SUBMISSION R1 09-21-22

35% SUBMITTAL II 06-13-23

65% DESIGN DEVELOPMENT SUBMITTAL 09-12-23

ISSUED FOR BID 12-28-23

ICT - BUILDING 4 - LEVEL 2 CABLE

TRAY PLAN

JG JG

TT-B04-102

GENERAL NOTES

A. FOR GENERAL NOTES AND LEGENDS REFER TO SHEET TT001.

B. EXISTING IT/TR/OI&T ROOMS TO REMAIN ACTIVE DURING CONSTRUCTION. G.C. TO PROTECT EQUIPMENT

DURING CONSTRUCTION WITH VISQUEEN. CONTRACTOR TO ENSURE CONTINUOUS OPERATION OF EQUIPMENT.

C. NOT ALL KEY NOTES APPLY TO ALL PLAN SHEETS. G.C. TO APPLY ONLY AS INDICATED PER EACH SHEET.

D. APPLY FIRE RATED SEALANT TO ALL EXISTING AND NEW PENETRATIONS IN EXISTING WALLS TO MAKE

EXISTING WALLS A 1 HR ASSEMBLY. BASIS OF DESIGN FOR 1 HR WALL IS UL 419 ASSEMBLY.

E. CONTRACTOR SHALL PROVIDE AND INSTALL FIRE RATED SLEEVES AS NECESSARY AND ASSEMBLED PER UL

DETAIL APPROPRIATE FOR WALL/FLOOR AND RACEWAY/CABLE TYPES

FLOOR PLAN KEYNOTESX

FLOOR PLAN LEGEND

BASKET CABLE TRAY.

1. PROVIDE BASKET TYPE CABLE TRAY TO SUPPORT OPTICAL FIBER BACKBONE AND NEW CAT 6A HORIZONTAL CABLING. CABLE TRAY TO BE SIZED AS PER CABLE TRAY CAPACITY PLANNING ON FLOOR PLAN LEGEND, ASSUMING 40% FILL AND 25% SPARE CAPACITY. ROUTING SHOWN INDICATES PRIMARY PATHWAYS. IN ADDITION TO PRIMARY PATHWAYS, CABLE TRAY SHALL BE PROVIDED WHEN CABLE BUNDLES EXCEED 24 CABLES. FIRE RATED MECHANICAL SLEEVE ASSEMBLIES SHALL BE PROVIDED WHEN PASSING THROUGH FIRE

RATED PARTITIONS. ASSUMING 40% FILL AND 50% SPARE CAPACITY.

CAT. NO

CF105/300

CF105/450

CF105/500

CF105/600

CF150/150

CF150/200

CF150/300

CF150/450

CF150/500

CF150/600

CF150/900

DEPTH

(IN)

WIDTH

(IN)

CAT 6A 4 PAIR

PLENUM (0.35")

- CABLE TRAY CAPACITY PLANNING.

- PROPOSED CABLE TRAY:

CABLOFIL 4" DEEP X 12" WIDE MINIMUM

(SIZE COMMENSURATE WITH DISTRIBUTION

REQUIREMENT) WHITE POWERCOAT TRAY INSERT.

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 4'

AutoCAD SHX Text 8'

AutoCAD SHX Text 16'

AutoCAD SHX Text 32'

AutoCAD SHX Text 1/16"=1'-0"

AutoCAD SHX Text

AutoCAD SHX Text

BUILDING 4 - LEVEL 2 CABLE TRAY PLAN

AutoCAD SHX Text

NORTH

AutoCAD SHX Text

KEY PLAN

AutoCAD SHX Text N mgonser Snapshot mgonser Snapshot mgonser Snapshot

A201

A236

A271

A234F

A2 -S

A238

A237

A269 C268 C267 C265

C239A

C240 C239

C249

C250

C256

C255A

C254

C253A

C253

C263 C255

C262

C256E

C251E

C257

C258

C2-S2

C247

C243A

C243

C242

C246A

C246

C247F

C247G

C244A

C264

C2-C1

C2-C2

C252

C241

C2-C3

C251A C251

C244

C247A

B231 A234A234A

A202EA203E

B204B205B206

B232

B230

B225F

B2-C1

B225

B225A

B223

B222

B221E

B215EB2-C3

B213

B214

B215

B216A

B217B218

B226A

B226

B209 B208

B207 A203

B232A

B233

B229A

B229

B227A

B227 B228

B2 -S

B218A

B219 B220A B220

B221

B216 A202 A270

B210B212

B2-C4

B2-C2

C266

C261

C2-C4

C259

A2-9

C242AB230A

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

K:

\C

C G

_P R

O

JE

C

TS

\2

1\

-1

T op ek a

EH

R M

C

1R

\4

- D es

D oc s\

2- D ra w in gs

\W O

R

KI

N G

\A ut oC

AD

\T T-

B0 4-

2R

P.

dw g 3/

/2

6:

:0

PM

ISSUE FOR BIDOffice of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

EHRM INFRASTRUCTURE

UPGRADES

COLMERY O'NEIL VA HEALTH CARE

21-116

Revisions: Date:

www. bancroft-ae.com

3300 Dundee RD.

Northbrook, IL 60062

T: 847.952.9362

35% SCHEMATIC DESIGN SUBMISSION 07-12-22

95% CONSTRUCTION DOCUMENTS SUBMISSION 10-31-23

100% CONSTRUCTION DOCUMENTS SUBMISSION

12/28/2023

12-19-23

Bancroft Project No: 21-116

35% SCHEMATIC DESIGN SUBMISSION R1 09-21-22

35% SUBMITTAL II 06-13-23

65% DESIGN DEVELOPMENT SUBMITTAL 09-12-23

ISSUED FOR BID 12-28-23

ICT - BUILDING 4 - LEVEL 2 - ROUTING

PLAN

JG JG

TT-B04-102RP

GENERAL NOTES

A. FOR GENERAL NOTES AND LEGENDS REFER TO SHEET TT001.

B. EXISTING IT/TR/OI&T ROOMS TO REMAIN ACTIVE DURING CONSTRUCTION. G.C. TO PROTECT EQUIPMENT

DURING CONSTRUCTION WITH VISQUEEN. CONTRACTOR TO ENSURE CONTINUOUS OPERATION OF EQUIPMENT.

C. NOT ALL KEY NOTES APPLY TO ALL PLAN SHEETS. G.C. TO APPLY ONLY AS INDICATED PER EACH SHEET.

D. APPLY FIRE RATED SEALANT TO ALL EXISTING AND NEW PENETRATIONS IN EXISTING WALLS TO MAKE

EXISTING WALLS A 1 HR ASSEMBLY. BASIS OF DESIGN FOR 1 HR WALL IS UL 419 ASSEMBLY.

E. CONTRACTOR SHALL PROVIDE AND INSTALL FIRE RATED SLEEVES AS NECESSARY AND ASSEMBLED PER UL

DETAIL APPROPRIATE FOR WALL/FLOOR AND RACEWAY/CABLE TYPES

FLOOR PLAN KEYNOTESX

1. PROVIDE SLEEVES, CONDUITS OR MECHANICAL FIRE-PROOF ASSEMBLIES AS REQUIRED THROUGH WALLS OR FLOORS AS REQUIRED TO MAINTAIN EXISTING RATING. REFER TO ONE-LINE CABLE RISER DIAGRAMS FOR CABLE QUANTITY AND TYPE. CONTRACTOR SHALL SIZE PATHWAYS TO ACCOMMODATE DAY ONE CABLING

PLUS 40 PERCENT SPARE FUTURE CAPACITY.

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 4'

AutoCAD SHX Text 8'

AutoCAD SHX Text 16'

AutoCAD SHX Text 32'

AutoCAD SHX Text 1/16"=1'-0"

AutoCAD SHX Text

AutoCAD SHX Text

BUILDING 4 - LEVEL 2 ROUTING PLAN

AutoCAD SHX Text

NORTH

AutoCAD SHX Text

KEY PLAN

AutoCAD SHX Text N mgonser Snapshot mgonser Snapshot mgonser Snapshot

ES DC

TYP

MID RX

CR/K

ICT - BUILDING 04 - BASEMENT LEVEL -

ENLARGED PLANS

JG JG

TT-B04-401

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

K:

\C

C G

_P R

O

JE

C

TS

\2

1\

-1

T op ek a

EH

R M

C

1R

\4

- D es

D oc s\

2- D ra w in gs

\W O

R

KI

N G

\A ut oC

AD

\T T-

B0 4-

1.

dw g

3/

/2

:3 5:

A

M

ISSUE FOR BIDOffice of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

EHRM INFRASTRUCTURE

UPGRADES

COLMERY O'NEIL VA HEALTH CARE

21-116

Revisions: Date:

www. bancroft-ae.com

3300 Dundee RD.

Northbrook, IL 60062

T: 847.952.9362

35% SCHEMATIC DESIGN SUBMISSION 07-12-22

95% CONSTRUCTION DOCUMENTS SUBMISSION 10-31-23

100% CONSTRUCTION DOCUMENTS SUBMISSION

12/28/2023

12-19-23

Bancroft Project No: 21-116

35% SCHEMATIC DESIGN SUBMISSION R1 09-21-22

35% SUBMITTAL II 06-13-23

65% DESIGN DEVELOPMENT SUBMITTAL 09-12-23

ISSUED FOR BID 12-28-23

GENERAL NOTES

A. FOR GENERAL NOTES AND LEGENDS REFER TO SHEET TT001.

B. EXISTING IT/TR/OI&T ROOMS TO REMAIN ACTIVE DURING CONSTRUCTION. G.C. TO PROTECT EQUIPMENT

DURING CONSTRUCTION WITH VISQUEEN. CONTRACTOR TO ENSURE CONTINUOUS OPERATION OF

EQUIPMENT.

C. NOT ALL KEY NOTES APPLY TO ALL PLAN SHEETS. G.C. TO APPLY ONLY AS INDICATED PER EACH SHEET.

D. APPLY FIRE RATED SEALANT TO ALL EXISTING AND NEW PENETRATIONS IN EXISTING WALLS TO MAKE

EXISTING WALLS A 1 HR ASSEMBLY. BASIS OF DESIGN FOR 1 HR WALL IS UL 419 ASSEMBLY.

E. CONTRACTOR SHALL PROVIDE AND INSTALL FIRE RATED SLEEVES AS NECESSARY AND ASSEMBLED PER UL

DETAIL APPROPRIATE FOR WALL/FLOOR AND RACEWAY/CABLE TYPES.

F. TELECOMMUNICATION ROOM (TR) RACK MOUNTED PDU CORDSETS:

1. SHALL BE IEC 60320 C14-C15 DEVICE POWER CORDSETS, FUNCTIONALLY EQUIVALENT TO CISCO SYSTEMS

PART# CAB-C15-CBN.

2. SHALL BE RATED FOR: a. AT LEAST 250 VAC b.13 AMPS c.60HZ d.120 DEGREES C (248 DEGREES F)

3. UL LISTED

4. MAXIMUM OF 4 FEET IN LENGTH. SHORTER LENGTHS MAY BE USED TO REDUCE EXCESSIVE SLACK.

5. COUPLER TERMINATIONS ON CORDSET: a. IEC 60320 C14 PLUG CONNECTOR (RACK PDU END) b.IEC 60320 C15 PLUG (DEVICE END)

6. SELECTION OF DISTINCT CONTRASTING CORDSET COLORS TO INDICATE DIVERSE (A/B) POWER

DISTRIBUTION SOURCES.

a. BLACK AND GRAY RECOMMENDED.

7. QUANTITY:

a. PROVIDE ONE SET OF C14-C15 POWER CORDS PER DEVICE TO BE CONNECTED TO RACK

MOUNTED PDU’S.

i. ONE SET SHALL CONSIST OF TWO (2) POWER CORDS FOR CONNECTION TO

DIVERSE (A/B) POWER DISTRIBUTION SOURCES.

b. PROVIDE MINIMUM OF ONE SET OF C14-C15 POWER CORDS PER SET OF RACK MOUNTED PDU’S.

c. PROVIDE MINIMUM OF ONE SET OF C14-C15 POWER CORDS PER RACK INSTALLED IN EACH TR.

d. IN ADDITION OF QUANTITIES LISTED ABOVE, PROVIDE ONE SPARE SET OF C14-C15 POWER CORDS

PER TR.

FLOOR PLAN KEYNOTESX

FLOOR PLAN LEGEND

BACKBOARD PROVIDED AND INSTALLED BY OTHERS.

DEMO PLAN GENERAL NOTES

1. REMOVE EXISTING WALL MOUNTED SERVER RACK.

2. RELOCATE EXISTING UTILITY PIPING AS REQUIRED TO ACCOMMODATE NEW

SERVER RACK. COORDINATE FINAL LOCATIONS WITH VA/COR.

3. PROVIDE AND INSTALL VISQUEEN TYPE PLASTIC SHEET AND ZIPPER DOOR AS

REQUIRED TO MAINTAIN TYPE V INFECTION CONTROL PRECAUTIONS. EXTEND

AND SEAL TO ROOF DECK/STRUCTURE ABOVE.

4. SUPPLY AND INSTALL WALK OFF MATS.

5. PROTECT EXISTING FINISHES FROM DUST AND DAMAGE.

1. PROVIDE MIGHTY MO 20 RACK, OR-MM20730B (OR EQUIVALENT)

2. PROVIDE VERTICAL WIRE MANAGER, OR-MM20VMD706 (OR EQUIVALENT)

3. PROVIDE 4'X8' AC GRADE 3/4" TRADE SIZE FIRE RATED PLYWOOD BACKBOARD PAINTED HIGH GLOSS WHITE WITH

(2) COATS OF PAINT FOR SERVICE PROVIDER/SECURITY/VIDEO/ETC. AROUND PERIMETER WALLS OF TR"s AND ENTRANCE ROOMS AS SHOWN. ENSURE THAT FIRE RATING STAMP IS TO REMAIN UNCOVERED BY PAINT.

4. PROVIDE FIXED CAMERA WITH PASSIVE INFRARED(PIR) SUPPLEMENTAL LIGHTING ON TELECOM ROOM CORNER.

5. PROVIDE ACCESS CONTROL DEVICES ON SECURITY DOOR.

6. PROVIDE COPPER GROUNDING BUSBAR AT 5' AFF IN LOCATION SHOWN. SEE GROUNDING BAR DETAIL FOR

ADDITIONAL REQUIREMENTS.

7. BASKET STYLE CABLE TRAY MINIMUM 4"X18" SHALL BE USED. ALL TRAY MUST BE INSTALLED AT 7'8" AFF, SUPPORTED PER MANUFACTURER REQUIREMENTS, AND PROPERLY BONDED TO GROUND.

AutoCAD SHX Text

ROOM C-20

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 1'

AutoCAD SHX Text 2'

AutoCAD SHX Text 4'

AutoCAD SHX Text 8'

AutoCAD SHX Text 1/4"=1'-0"

AutoCAD SHX Text

AutoCAD SHX Text

BUILDING 04 - ENLARGED PLAN RM C-20

AutoCAD SHX Text

AutoCAD SHX Text 1'

AutoCAD SHX Text 2'

AutoCAD SHX Text 4'

AutoCAD SHX Text 8'

AutoCAD SHX Text 1/4"=1'-0"

AutoCAD SHX Text

AutoCAD SHX Text

BUILDING 04 - ENLARGED RCP RM C-20

AutoCAD SHX Text N

AutoCAD SHX Text

KEY PLAN

mgonser Snapshot mgonser Snapshot mgonser Snapshot

ES

DC

TYP

MID

RXCR/K

TYP

TYP

ES

DC

TYP

RX

CR/K

MID

ICT - BUILDING 04 - LEVEL 1 -

ENLARGED PLANS

JG JG

TT-B04-411

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

K:

\C

C G

_P R

O

JE

C

TS

\2

1\

-1

T op ek a

EH

R M

C

1R

\4

- D es

D oc s\

2- D ra w in gs

\W O

R

KI

N G

\A ut oC

AD

\T T-

B0 4-

1.

dw g

3/

/2

:3 8:

A

M

ISSUE FOR BIDOffice of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

EHRM INFRASTRUCTURE

UPGRADES

COLMERY O'NEIL VA HEALTH CARE

21-116

Revisions: Date:

www. bancroft-ae.com

3300 Dundee RD.

Northbrook, IL 60062

T: 847.952.9362

35% SCHEMATIC DESIGN SUBMISSION 07-12-22

95% CONSTRUCTION DOCUMENTS SUBMISSION 10-31-23

100% CONSTRUCTION DOCUMENTS SUBMISSION

12/28/2023

12-19-23

Bancroft Project No: 21-116

35% SCHEMATIC DESIGN SUBMISSION R1 09-21-22

35% SUBMITTAL II 06-13-23

65% DESIGN DEVELOPMENT SUBMITTAL 09-12-23

ISSUED FOR BID 12-28-23

GENERAL NOTES

A. FOR GENERAL NOTES AND LEGENDS REFER TO SHEET TT001.

B. EXISTING IT/TR/OI&T ROOMS TO REMAIN ACTIVE DURING CONSTRUCTION. G.C. TO PROTECT EQUIPMENT

DURING CONSTRUCTION WITH VISQUEEN. CONTRACTOR TO ENSURE CONTINUOUS OPERATION OF

EQUIPMENT.

C. NOT ALL KEY NOTES APPLY TO ALL PLAN SHEETS. G.C. TO APPLY ONLY AS INDICATED PER EACH SHEET.

D. APPLY FIRE RATED SEALANT TO ALL EXISTING AND NEW PENETRATIONS IN EXISTING WALLS TO MAKE

EXISTING WALLS A 1 HR ASSEMBLY. BASIS OF DESIGN FOR 1 HR WALL IS UL 419 ASSEMBLY.

E. CONTRACTOR SHALL PROVIDE AND INSTALL FIRE RATED SLEEVES AS NECESSARY AND ASSEMBLED PER UL

DETAIL APPROPRIATE FOR WALL/FLOOR AND RACEWAY/CABLE TYPES.

F. TELECOMMUNICATION ROOM (TR) RACK MOUNTED PDU CORDSETS:

1. SHALL BE IEC 60320 C14-C15 DEVICE POWER CORDSETS, FUNCTIONALLY EQUIVALENT TO CISCO SYSTEMS

PART# CAB-C15-CBN.

2. SHALL BE RATED FOR: a. AT LEAST 250 VAC b.13 AMPS c.60HZ d.120 DEGREES C (248 DEGREES F)

3. UL LISTED

4. MAXIMUM OF 4 FEET IN LENGTH. SHORTER LENGTHS MAY BE USED TO REDUCE EXCESSIVE SLACK.

5. COUPLER TERMINATIONS ON CORDSET: a. IEC 60320 C14 PLUG CONNECTOR (RACK PDU END) b.IEC 60320 C15 PLUG (DEVICE END)

6. SELECTION OF DISTINCT CONTRASTING CORDSET COLORS TO INDICATE DIVERSE (A/B) POWER

DISTRIBUTION SOURCES.

a. BLACK AND GRAY RECOMMENDED.

7. QUANTITY:

a. PROVIDE ONE SET OF C14-C15 POWER CORDS PER DEVICE TO BE CONNECTED TO RACK

MOUNTED PDU’S.

i. ONE SET SHALL CONSIST OF TWO (2) POWER CORDS FOR CONNECTION TO

DIVERSE (A/B) POWER DISTRIBUTION SOURCES.

b. PROVIDE MINIMUM OF ONE SET OF C14-C15 POWER CORDS PER SET OF RACK MOUNTED PDU’S.

c. PROVIDE MINIMUM OF ONE SET OF C14-C15 POWER CORDS PER RACK INSTALLED IN EACH TR.

d. IN ADDITION OF QUANTITIES LISTED ABOVE, PROVIDE ONE SPARE SET OF C14-C15 POWER CORDS

PER TR.

FLOOR PLAN KEYNOTESX

FLOOR PLAN LEGEND

BACKBOARD PROVIDED AND INSTALLED BY OTHERS.

DEMO PLAN GENERAL NOTES

1. REMOVE EXISTING WALL MOUNTED SERVER RACK.

2. RELOCATE EXISTING UTILITY PIPING AS REQUIRED TO ACCOMMODATE NEW

SERVER RACK. COORDINATE FINAL LOCATIONS WITH VA/COR.

3. PROVIDE AND INSTALL VISQUEEN TYPE PLASTIC SHEET AND ZIPPER DOOR AS

REQUIRED TO MAINTAIN TYPE V INFECTION CONTROL PRECAUTIONS. EXTEND

AND SEAL TO ROOF DECK/STRUCTURE ABOVE.

4. SUPPLY AND INSTALL WALK OFF MATS.

5. PROTECT EXISTING FINISHES FROM DUST AND DAMAGE.

1. PROVIDE MIGHTY MO 20 RACK, OR-MM20730B (OR EQUIVALENT)

2. PROVIDE VERTICAL WIRE MANAGER, OR-MM20VMD706 (OR EQUIVALENT)

3. PROVIDE 4'X8' AC GRADE 3/4" TRADE SIZE FIRE RATED PLYWOOD BACKBOARD PAINTED HIGH GLOSS WHITE WITH

(2) COATS OF PAINT FOR SERVICE PROVIDER/SECURITY/VIDEO/ETC. AROUND PERIMETER WALLS OF TR"s AND ENTRANCE ROOMS AS SHOWN. ENSURE THAT FIRE RATING STAMP IS TO REMAIN UNCOVERED BY PAINT.

4. PROVIDE FIXED CAMERA WITH PASSIVE INFRARED(PIR) SUPPLEMENTAL LIGHTING ON TELECOM ROOM CORNER.

5. PROVIDE ACCESS CONTROL DEVICES ON SECURITY DOOR.

6. PROVIDE COPPER GROUNDING BUSBAR AT 5' AFF IN LOCATION SHOWN. SEE GROUNDING BAR DETAIL FOR

ADDITIONAL REQUIREMENTS.

7. BASKET STYLE CABLE TRAY MINIMUM 4"X18" SHALL BE USED. ALL TRAY MUST BE INSTALLED AT 7'8" AFF, SUPPORTED PER MANUFACTURER REQUIREMENTS, AND PROPERLY BONDED TO GROUND.

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

ROOM B-130A

AutoCAD SHX Text

ROOM C-146

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 1'

AutoCAD SHX Text 2'

AutoCAD SHX Text 4'

AutoCAD SHX Text 8'

AutoCAD SHX Text 1/4"=1'-0"

AutoCAD SHX Text

AutoCAD SHX Text

BUILDING 04 - ENLARGED PLAN RM B-130A

AutoCAD SHX Text

AutoCAD SHX Text 1'

AutoCAD SHX Text 2'

AutoCAD SHX Text 4'

AutoCAD SHX Text 8'

AutoCAD SHX Text 1/4"=1'-0"

AutoCAD SHX Text

AutoCAD SHX Text

BUILDING 04 - ENLARGED PLAN RM C-146

AutoCAD SHX Text

AutoCAD SHX Text 1'

AutoCAD SHX Text 2'

AutoCAD SHX Text 4'

AutoCAD SHX Text 8'

AutoCAD SHX Text 1/4"=1'-0"

AutoCAD SHX Text

AutoCAD SHX Text

BUILDING 04 - ENLARGED RCP RM C-146

AutoCAD SHX Text

AutoCAD SHX Text 1'

AutoCAD SHX Text 2'

AutoCAD SHX Text 4'

AutoCAD SHX Text 8'

AutoCAD SHX Text 1/4"=1'-0"

AutoCAD SHX Text

AutoCAD SHX Text

BUILDING 04 - ENLARGED RCP RM B-130A

AutoCAD SHX Text N

AutoCAD SHX Text

KEY PLAN

mgonser Snapshot mgonser Snapshot mgonser Snapshot

ES

DC

TYP

TYP

MID

RX

CR/K

TYP

TYP

ES

DC

TYP

MID

RX CR/K

ICT - BUILDING 04 - LEVEL 2 -

ENLARGED PLANS

JG JG

TT-B04-421

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

K:

\C

C G

_P R

O

JE

C

TS

\2

1\

-1

T op ek a

EH

R M

C

1R

\4

- D es

D oc s\

2- D ra w in gs

\W O

R

KI

N G

\A ut oC

AD

\T T-

B0 4-

1.

dw g

3/

/2

:4 0:

A

M

ISSUE FOR BIDOffice of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

EHRM INFRASTRUCTURE

UPGRADES

COLMERY O'NEIL VA HEALTH CARE

21-116

Revisions: Date:

www. bancroft-ae.com

3300 Dundee RD.

Northbrook, IL 60062

T: 847.952.9362

35% SCHEMATIC DESIGN SUBMISSION 07-12-22

95% CONSTRUCTION DOCUMENTS SUBMISSION 10-31-23

100% CONSTRUCTION DOCUMENTS SUBMISSION

12/28/2023

12-19-23

Bancroft Project No: 21-116

35% SCHEMATIC DESIGN SUBMISSION R1 09-21-22

35% SUBMITTAL II 06-13-23

65% DESIGN DEVELOPMENT SUBMITTAL 09-12-23

ISSUED FOR BID 12-28-23

GENERAL NOTES

A. FOR GENERAL NOTES AND LEGENDS REFER TO SHEET TT001.

B. EXISTING IT/TR/OI&T ROOMS TO REMAIN ACTIVE DURING CONSTRUCTION. G.C. TO PROTECT EQUIPMENT

DURING CONSTRUCTION WITH VISQUEEN. CONTRACTOR TO ENSURE CONTINUOUS OPERATION OF

EQUIPMENT.

C. NOT ALL KEY NOTES APPLY TO ALL PLAN SHEETS. G.C. TO APPLY ONLY AS INDICATED PER EACH SHEET.

D. APPLY FIRE RATED SEALANT TO ALL EXISTING AND NEW PENETRATIONS IN EXISTING WALLS TO MAKE

EXISTING WALLS A 1 HR ASSEMBLY. BASIS OF DESIGN FOR 1 HR WALL IS UL 419 ASSEMBLY.

E. CONTRACTOR SHALL PROVIDE AND INSTALL FIRE RATED SLEEVES AS NECESSARY AND ASSEMBLED PER UL

DETAIL APPROPRIATE FOR WALL/FLOOR AND RACEWAY/CABLE TYPES.

F. TELECOMMUNICATION ROOM (TR) RACK MOUNTED PDU CORDSETS:

1. SHALL BE IEC 60320 C14-C15 DEVICE POWER CORDSETS, FUNCTIONALLY EQUIVALENT TO CISCO SYSTEMS

PART# CAB-C15-CBN.

2. SHALL BE RATED FOR: a. AT LEAST 250 VAC b.13 AMPS c.60HZ d.120 DEGREES C (248 DEGREES F)

3. UL LISTED

4. MAXIMUM OF 4 FEET IN LENGTH. SHORTER LENGTHS MAY BE USED TO REDUCE EXCESSIVE SLACK.

5. COUPLER TERMINATIONS ON CORDSET: a. IEC 60320 C14 PLUG CONNECTOR (RACK PDU END) b.IEC 60320 C15 PLUG (DEVICE END)

6. SELECTION OF DISTINCT CONTRASTING CORDSET COLORS TO INDICATE DIVERSE (A/B) POWER

DISTRIBUTION SOURCES.

a. BLACK AND GRAY RECOMMENDED.

7. QUANTITY:

a. PROVIDE ONE SET OF C14-C15 POWER CORDS PER DEVICE TO BE CONNECTED TO RACK

MOUNTED PDU’S.

i. ONE SET SHALL CONSIST OF TWO (2) POWER CORDS FOR CONNECTION TO

DIVERSE (A/B) POWER DISTRIBUTION SOURCES.

b. PROVIDE MINIMUM OF ONE SET OF C14-C15 POWER CORDS PER SET OF RACK MOUNTED PDU’S.

c. PROVIDE MINIMUM OF ONE SET OF C14-C15 POWER CORDS PER RACK INSTALLED IN EACH TR.

d. IN ADDITION OF QUANTITIES LISTED ABOVE, PROVIDE ONE SPARE SET OF C14-C15 POWER CORDS

PER TR.

FLOOR PLAN KEYNOTESX

FLOOR PLAN LEGEND

BACKBOARD PROVIDED AND INSTALLED BY OTHERS.

DEMO PLAN GENERAL NOTES

1. REMOVE EXISTING WALL MOUNTED SERVER RACK.

2. RELOCATE EXISTING UTILITY PIPING AS REQUIRED TO ACCOMMODATE NEW

SERVER RACK. COORDINATE FINAL LOCATIONS WITH VA/COR.

3. PROVIDE AND INSTALL VISQUEEN TYPE PLASTIC SHEET AND ZIPPER DOOR AS

REQUIRED TO MAINTAIN TYPE V INFECTION CONTROL PRECAUTIONS. EXTEND

AND SEAL TO ROOF DECK/STRUCTURE ABOVE.

4. SUPPLY AND INSTALL WALK OFF MATS.

5. PROTECT EXISTING FINISHES FROM DUST AND DAMAGE.

1. PROVIDE MIGHTY MO 20 RACK, OR-MM20730B (OR EQUIVALENT)

2. PROVIDE VERTICAL WIRE MANAGER, OR-MM20VMD706 (OR EQUIVALENT)

3. PROVIDE 4'X8' AC GRADE 3/4" TRADE SIZE FIRE RATED PLYWOOD BACKBOARD PAINTED HIGH GLOSS WHITE WITH

(2) COATS OF PAINT FOR SERVICE PROVIDER/SECURITY/VIDEO/ETC. AROUND PERIMETER WALLS OF TR"s AND ENTRANCE ROOMS AS SHOWN. ENSURE THAT FIRE RATING STAMP IS TO REMAIN UNCOVERED BY PAINT.

4. PROVIDE FIXED CAMERA WITH PASSIVE INFRARED(PIR) SUPPLEMENTAL LIGHTING ON TELECOM ROOM CORNER.

5. PROVIDE ACCESS CONTROL DEVICES ON SECURITY DOOR.

6. PROVIDE COPPER GROUNDING BUSBAR AT 5' AFF IN LOCATION SHOWN. SEE GROUNDING BAR DETAIL FOR

ADDITIONAL REQUIREMENTS.

7. BASKET STYLE CABLE TRAY MINIMUM 4"X18" SHALL BE USED. ALL TRAY MUST BE INSTALLED AT 7'8" AFF, SUPPORTED PER MANUFACTURER REQUIREMENTS, AND PROPERLY BONDED TO GROUND.

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

ROOM B-230A

AutoCAD SHX Text

ROOM C-242A

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text N

AutoCAD SHX Text

AutoCAD SHX Text 1'

AutoCAD SHX Text 2'

AutoCAD SHX Text 4'

AutoCAD SHX Text 8'

AutoCAD SHX Text 1/4"=1'-0"

AutoCAD SHX Text

AutoCAD SHX Text

BUILDING 04 - ENLARGED PLAN RM B-230A

AutoCAD SHX Text

AutoCAD SHX Text 1'

AutoCAD SHX Text 2'

AutoCAD SHX Text 4'

AutoCAD SHX Text 8'

AutoCAD SHX Text 1/4"=1'-0"

AutoCAD SHX Text

AutoCAD SHX Text

BUILDING 04 - ENLARGED PLAN RM C-242A

AutoCAD SHX Text

AutoCAD SHX Text 1'

AutoCAD SHX Text 2'

AutoCAD SHX Text 4'

AutoCAD SHX Text 8'

AutoCAD SHX Text 1/4"=1'-0"

AutoCAD SHX Text

AutoCAD SHX Text

BUILDING 04 - ENLARGED RCP RM B-230A

AutoCAD SHX Text

AutoCAD SHX Text 1'

AutoCAD SHX Text 2'

AutoCAD SHX Text 4'

AutoCAD SHX Text 8'

AutoCAD SHX Text 1/4"=1'-0"

AutoCAD SHX Text

AutoCAD SHX Text

BUILDING 04 - ENLARGED RCP RM C-242A

AutoCAD SHX Text

KEY PLAN

mgonser Snapshot mgonser Snapshot mgonser Snapshot

DN

UP

A0-C1 C0-C2B0-C3

A8

A6F

A6

A5

A2E A1E B3F B3A

B3E

C9D C9H

C10F

C11E

C11

C9B

C9AC9

B2E

B3B

C10

C12C12C

A9

A1A

A1 B2

C9G

B3

C12B

A13B

A13 C11A

DF

EEWS

EL-1

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

K:

\C

C G

_P R

O

JE

C

TS

\2

1\

-1

T op ek a

EH

R M

C

1R

\4

- D es

D oc s\

2- D ra w in gs

\W O

R

KI

N G

\A ut oC

AD

\T T-

B0 5-

0.

dw g

1/

/2

2:

:0

PM

ISSUE FOR BIDOffice of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

EHRM INFRASTRUCTURE

UPGRADES

COLMERY O'NEIL VA HEALTH CARE

21-116

Revisions: Date:

www. bancroft-ae.com

3300 Dundee RD.

Northbrook, IL 60062

T: 847.952.9362

35% SCHEMATIC DESIGN SUBMISSION 07-12-22

95% CONSTRUCTION DOCUMENTS SUBMISSION 10-31-23

100% CONSTRUCTION DOCUMENTS SUBMISSION

12/28/2023

12-19-23

Bancroft Project No: 21-116

35% SCHEMATIC DESIGN SUBMISSION R1 09-21-22

35% SUBMITTAL II 06-13-23

65% DESIGN DEVELOPMENT SUBMITTAL 09-12-23

ISSUED FOR BID 12-28-23

ICT - BUILDING 05 - BASEMENT LEVEL

CABLE TRAY PLAN

JG JG

TT-B05-100

GENERAL NOTES

A. FOR GENERAL NOTES AND LEGENDS REFER TO SHEET TT001.

B. EXISTING IT/TR/OI&T ROOMS TO REMAIN ACTIVE DURING CONSTRUCTION. G.C. TO PROTECT EQUIPMENT

DURING CONSTRUCTION WITH VISQUEEN. CONTRACTOR TO ENSURE CONTINUOUS OPERATION OF EQUIPMENT.

C. NOT ALL KEY NOTES APPLY TO ALL PLAN SHEETS. G.C. TO APPLY ONLY AS INDICATED PER EACH SHEET.

D. APPLY FIRE RATED SEALANT TO ALL EXISTING AND NEW PENETRATIONS IN EXISTING WALLS TO MAKE

EXISTING WALLS A 1 HR ASSEMBLY. BASIS OF DESIGN FOR 1 HR WALL IS UL 419 ASSEMBLY.

E. CONTRACTOR SHALL PROVIDE AND INSTALL FIRE RATED SLEEVES AS NECESSARY AND ASSEMBLED PER UL

DETAIL APPROPRIATE FOR WALL/FLOOR AND RACEWAY/CABLE TYPES

FLOOR PLAN KEYNOTESX

FLOOR PLAN LEGEND

BASKET CABLE TRAY.

1. PROVIDE BASKET TYPE CABLE TRAY TO SUPPORT OPTICAL FIBER BACKBONE AND NEW CAT 6A HORIZONTAL CABLING. CABLE TRAY TO BE SIZED AS PER CABLE TRAY CAPACITY PLANNING ON FLOOR PLAN LEGEND, ASSUMING 40% FILL AND 25% SPARE CAPACITY. ROUTING SHOWN INDICATES PRIMARY PATHWAYS. IN ADDITION TO PRIMARY PATHWAYS, CABLE TRAY SHALL BE PROVIDED WHEN CABLE BUNDLES EXCEED 24 CABLES. FIRE RATED MECHANICAL SLEEVE ASSEMBLIES SHALL BE PROVIDED WHEN PASSING THROUGH FIRE

RATED PARTITIONS. ASSUMING 40% FILL AND 50% SPARE CAPACITY.

CAT. NO

CF105/300

CF105/450

CF105/500

CF105/600

CF150/150

CF150/200

CF150/300

CF150/450

CF150/500

CF150/600

CF150/900

DEPTH

(IN)

WIDTH

(IN)

CAT 6A 4 PAIR

PLENUM (0.35")

- CABLE TRAY CAPACITY PLANNING.

- PROPOSED CABLE TRAY:

CABLOFIL 4" DEEP X 12" WIDE MINIMUM

(SIZE COMMENSURATE WITH DISTRIBUTION

REQUIREMENT) WHITE POWERCOAT TRAY INSERT.

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

NORTH

AutoCAD SHX Text

KEY PLAN

AutoCAD SHX Text N

AutoCAD SHX Text

AutoCAD SHX Text 4'

AutoCAD SHX Text 8'

AutoCAD SHX Text 16'

AutoCAD SHX Text 32'

AutoCAD SHX Text 1/16"=1'-0"

AutoCAD SHX Text

AutoCAD SHX Text

BUILDING 5 - BASEMENT LEVEL CABLE TRAY PLAN

mgonser Snapshot mgonser Snapshot mgonser Snapshot

UP

A0-C1 C0-C2B0-C3

A8

A6F

A6

A5

A2E A1E B3F B3A

B3E

C9D C9H

C10F

C11E

C11

C9B

C9AC9

B2E

B3B

C10

C12C12C

A9

A1A

A1 B2

C9G

B3

C12B

A13B

A13 C11A

DF

EEWS

EL-1

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

K:

\C

C G

_P R

O

JE

C

TS

\2

1\

-1

T op ek a

EH

R M

C

1R

\4

- D es

D oc s\

2- D ra w in gs

\W O

R

KI

N G

\A ut oC

AD

\T T-

B0 5-

0R

P.

dw g 3/

/2

7:

:3

PM

ISSUE FOR BIDOffice of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

EHRM INFRASTRUCTURE

UPGRADES

COLMERY O'NEIL VA HEALTH CARE

21-116

Revisions: Date:

www. bancroft-ae.com

3300 Dundee RD.

Northbrook, IL 60062

T: 847.952.9362

35% SCHEMATIC DESIGN SUBMISSION 07-12-22

95% CONSTRUCTION DOCUMENTS SUBMISSION 10-31-23

100% CONSTRUCTION DOCUMENTS SUBMISSION

12/28/2023

12-19-23

Bancroft Project No: 21-116

35% SCHEMATIC DESIGN SUBMISSION R1 09-21-22

35% SUBMITTAL II 06-13-23

65% DESIGN DEVELOPMENT SUBMITTAL 09-12-23

ISSUED FOR BID 12-28-23

ICT - BUILDING 05 - BASEMENT LEVEL

ROUTING PLAN

JG JG

TT-B05-100RP

GENERAL NOTES

A. FOR GENERAL NOTES AND LEGENDS REFER TO SHEET TT001.

B. EXISTING IT/TR/OI&T ROOMS TO REMAIN ACTIVE DURING CONSTRUCTION. G.C. TO PROTECT EQUIPMENT

DURING CONSTRUCTION WITH VISQUEEN. CONTRACTOR TO ENSURE CONTINUOUS OPERATION OF EQUIPMENT.

C. NOT ALL KEY NOTES APPLY TO ALL PLAN SHEETS. G.C. TO APPLY ONLY AS INDICATED PER EACH SHEET.

D. APPLY FIRE RATED SEALANT TO ALL EXISTING AND NEW PENETRATIONS IN EXISTING WALLS TO MAKE

EXISTING WALLS A 1 HR ASSEMBLY. BASIS OF DESIGN FOR 1 HR WALL IS UL 419 ASSEMBLY.

E. CONTRACTOR SHALL PROVIDE AND INSTALL FIRE RATED SLEEVES AS NECESSARY AND ASSEMBLED PER UL

DETAIL APPROPRIATE FOR WALL/FLOOR AND RACEWAY/CABLE TYPES

FLOOR PLAN KEYNOTESX

1. PROVIDE SLEEVES, CONDUITS OR MECHANICAL FIRE-PROOF

ASSEMBLIES AS REQUIRED THROUGH WALL OR FLOORS AS REQUIRED

TO MAINTAIN EXISTING RATING. REFER TO ONE-LINE CABLE RISER

DIAGRAMS FOR CABLE QUANTITY AND TYPE. CONTRACTOR SHALL SIZE

PATHWAYS TO ACCOMMODATE DAY ONE CABLING PLUS 40 PERCENT

SPARE CAPACITY.

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

ROUTE 'B' TO TR 'A160' ON LEVEL 1 ABOVE

AutoCAD SHX Text

TR 'A160' ABOVE (STACKED)

AutoCAD SHX Text

ROUTE 'A' FROM TR 'A160' ON LEVEL 1 ABOVE

AutoCAD SHX Text ROUTE 'A' FROM STEAM TUNNEL. EXACT LOCATION OF ENTRANCE FROM STEAM TUNNEL TO BE FIELD COORDINATED.

AutoCAD SHX Text

NORTH

AutoCAD SHX Text

KEY PLAN

AutoCAD SHX Text N

AutoCAD SHX Text

AutoCAD SHX Text 4'

AutoCAD SHX Text 8'

AutoCAD SHX Text 16'

AutoCAD SHX Text 32'

AutoCAD SHX Text 1/16"=1'-0"

AutoCAD SHX Text

AutoCAD SHX Text

BUILDING 5 - BASEMENT LEVEL ROUTING PLAN

mgonser Snapshot mgonser Snapshot mgonser Snapshot

DN

DN DNUPUP

UP

A1-C1

A101A

A101

A101C

A101B

A130

A130A A130B

A131

A129 A132 A128F

A128 A127

A102E A101E

A1

A134

C142B120

B103 B104B106

B126AB114C

B117

B113B114B114A

B114B B114D

B115 B1

B111 B110

B119

B108

B109

B126

B105 B102

B125

B124

B123C

B123B

B122

B123A

B123D

B120F

B1-C1

A135 C136

C159

C136B

C156 C157

C154

C153

C145C143 C147E

C147 C148B

C148C

C148A C148

C148D C150

C140A

C139C

C1-C3

C141F

C138 C140

C137 C141

C139

C139A C139B

C150P

C151

C1

C150E

B1

P

C155A

C155

B123

B107A

B107

B126B

B112 C158

C136A

B111E

C144

C149

A130P

C1-C1

C157A

EL-1

B126B

A160

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

K:

\C

C G

_P R

O

JE

C

TS

\2

1\

-1

T op ek a

EH

R M

C

1R

\4

- D es

D oc s\

2- D ra w in gs

\W O

R

KI

N G

\A ut oC

AD

\T T-

B0 5-

1.

dw g

1/

/2

2:

:0

PM

ISSUE FOR BIDOffice of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

EHRM INFRASTRUCTURE

UPGRADES

COLMERY O'NEIL VA HEALTH CARE

21-116

Revisions: Date:

www. bancroft-ae.com

3300 Dundee RD.

Northbrook, IL 60062

T: 847.952.9362

35% SCHEMATIC DESIGN SUBMISSION 07-12-22

95% CONSTRUCTION DOCUMENTS SUBMISSION 10-31-23

100% CONSTRUCTION DOCUMENTS SUBMISSION

12/28/2023

12-19-23

Bancroft Project No: 21-116

35% SCHEMATIC DESIGN SUBMISSION R1 09-21-22

35% SUBMITTAL II 06-13-23

65% DESIGN DEVELOPMENT SUBMITTAL 09-12-23

ISSUED FOR BID 12-28-23

ICT - BUILDING 5 - LEVEL 1 CABLE TRAY

PLAN

JG JG

TT-B05-101

GENERAL NOTES

A. FOR GENERAL NOTES AND LEGENDS REFER TO SHEET TT001.

B. EXISTING IT/TR/OI&T ROOMS TO REMAIN ACTIVE DURING CONSTRUCTION. G.C. TO PROTECT EQUIPMENT

DURING CONSTRUCTION WITH VISQUEEN. CONTRACTOR TO ENSURE CONTINUOUS OPERATION OF EQUIPMENT.

C. NOT ALL KEY NOTES APPLY TO ALL PLAN SHEETS. G.C. TO APPLY ONLY AS INDICATED PER EACH SHEET.

D. APPLY FIRE RATED SEALANT TO ALL EXISTING AND NEW PENETRATIONS IN EXISTING WALLS TO MAKE

EXISTING WALLS A 1 HR ASSEMBLY. BASIS OF DESIGN FOR 1 HR WALL IS UL 419 ASSEMBLY.

E. CONTRACTOR SHALL PROVIDE AND INSTALL FIRE RATED SLEEVES AS NECESSARY AND ASSEMBLED PER UL

DETAIL APPROPRIATE FOR WALL/FLOOR AND RACEWAY/CABLE TYPES

FLOOR PLAN KEYNOTESX

FLOOR PLAN LEGEND

BASKET CABLE TRAY.

1. PROVIDE BASKET TYPE CABLE TRAY TO SUPPORT OPTICAL FIBER BACKBONE AND NEW CAT 6A HORIZONTAL CABLING. CABLE TRAY TO BE SIZED AS PER CABLE TRAY CAPACITY PLANNING ON FLOOR PLAN LEGEND, ASSUMING 40% FILL AND 25% SPARE CAPACITY. ROUTING SHOWN INDICATES PRIMARY PATHWAYS. IN ADDITION TO PRIMARY PATHWAYS, CABLE TRAY SHALL BE PROVIDED WHEN CABLE BUNDLES EXCEED 24 CABLES. FIRE RATED MECHANICAL SLEEVE ASSEMBLIES SHALL BE PROVIDED WHEN PASSING THROUGH FIRE

RATED PARTITIONS.