This document appears to be Attachment 5 - 589A5-21-700_Topeka EHRM_IFB R2 Drawings_Vol 2_181-240.pdf, which is related to the federal contract opportunity Solicitation Number 36C77624B0026_1 for Y1DA--589A5-21-700 EHRM INFRASTRUCTURE UPGRADES (VA-24-00076324) in Topeka, KS. The solicitation is issued by the Department of Veterans Affairs Technology Acquisition Center Austin. This attachment appears to contain technical drawings related to the infrastructure upgrades described in the contract opportunity. No additional details about required products or services, response dates, pricing, or set-asides are provided in this specific document. This appears to be a technical drawing document rather than a solicitation, performance work statement, or other key contract document.
View the file
Other files
Show all 49
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
TYP
ES DC
TYP
MID
RX
CR/K
ICT - BUILDING 03 - LEVEL1 - ENLARGED
PLANS
JG JG
TT-B03-411
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
K:
\C
C G
_P R
O
JE
C
TS
\2
1\
-1
T op ek a
EH
R M
C
1R
\4
- D es
D oc s\
2- D ra w in gs
\W O
R
KI
N G
\A ut oC
AD
\T T-
B0 3-
1.
dw g
3/
/2
:2 6:
A
M
ISSUE FOR BIDOffice of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
EHRM INFRASTRUCTURE
UPGRADES
COLMERY O'NEIL VA HEALTH CARE
21-116
Revisions: Date:
www. bancroft-ae.com
3300 Dundee RD.
Northbrook, IL 60062
T: 847.952.9362
35% SCHEMATIC DESIGN SUBMISSION 07-12-22
95% CONSTRUCTION DOCUMENTS SUBMISSION 10-31-23
100% CONSTRUCTION DOCUMENTS SUBMISSION
12/28/2023
12-19-23
Bancroft Project No: 21-116
35% SCHEMATIC DESIGN SUBMISSION R1 09-21-22
35% SUBMITTAL II 06-13-23
65% DESIGN DEVELOPMENT SUBMITTAL 09-12-23
ISSUED FOR BID 12-28-23
GENERAL NOTES
A. FOR GENERAL NOTES AND LEGENDS REFER TO SHEET TT001.
B. EXISTING IT/TR/OI&T ROOMS TO REMAIN ACTIVE DURING CONSTRUCTION. G.C. TO PROTECT EQUIPMENT
DURING CONSTRUCTION WITH VISQUEEN. CONTRACTOR TO ENSURE CONTINUOUS OPERATION OF
EQUIPMENT.
C. NOT ALL KEY NOTES APPLY TO ALL PLAN SHEETS. G.C. TO APPLY ONLY AS INDICATED PER EACH SHEET.
D. APPLY FIRE RATED SEALANT TO ALL EXISTING AND NEW PENETRATIONS IN EXISTING WALLS TO MAKE
EXISTING WALLS A 1 HR ASSEMBLY. BASIS OF DESIGN FOR 1 HR WALL IS UL 419 ASSEMBLY.
E. CONTRACTOR SHALL PROVIDE AND INSTALL FIRE RATED SLEEVES AS NECESSARY AND ASSEMBLED PER UL
DETAIL APPROPRIATE FOR WALL/FLOOR AND RACEWAY/CABLE TYPES.
F. TELECOMMUNICATION ROOM (TR) RACK MOUNTED PDU CORDSETS:
1. SHALL BE IEC 60320 C14-C15 DEVICE POWER CORDSETS, FUNCTIONALLY EQUIVALENT TO CISCO SYSTEMS
PART# CAB-C15-CBN.
2. SHALL BE RATED FOR: a. AT LEAST 250 VAC b.13 AMPS c.60HZ d.120 DEGREES C (248 DEGREES F)
3. UL LISTED
4. MAXIMUM OF 4 FEET IN LENGTH. SHORTER LENGTHS MAY BE USED TO REDUCE EXCESSIVE SLACK.
5. COUPLER TERMINATIONS ON CORDSET: a. IEC 60320 C14 PLUG CONNECTOR (RACK PDU END) b.IEC 60320 C15 PLUG (DEVICE END)
6. SELECTION OF DISTINCT CONTRASTING CORDSET COLORS TO INDICATE DIVERSE (A/B) POWER
DISTRIBUTION SOURCES.
a. BLACK AND GRAY RECOMMENDED.
7. QUANTITY:
a. PROVIDE ONE SET OF C14-C15 POWER CORDS PER DEVICE TO BE CONNECTED TO RACK
MOUNTED PDU’S.
i. ONE SET SHALL CONSIST OF TWO (2) POWER CORDS FOR CONNECTION TO
DIVERSE (A/B) POWER DISTRIBUTION SOURCES.
b. PROVIDE MINIMUM OF ONE SET OF C14-C15 POWER CORDS PER SET OF RACK MOUNTED PDU’S.
c. PROVIDE MINIMUM OF ONE SET OF C14-C15 POWER CORDS PER RACK INSTALLED IN EACH TR.
d. IN ADDITION OF QUANTITIES LISTED ABOVE, PROVIDE ONE SPARE SET OF C14-C15 POWER CORDS
PER TR.
FLOOR PLAN KEYNOTESX
FLOOR PLAN LEGEND
BACKBOARD PROVIDED AND INSTALLED BY OTHERS.
DEMO PLAN GENERAL NOTES
1. REMOVE EXISTING WALL MOUNTED SERVER RACK.
2. RELOCATE EXISTING UTILITY PIPING AS REQUIRED TO ACCOMMODATE NEW
SERVER RACK. COORDINATE FINAL LOCATIONS WITH VA/COR.
3. PROVIDE AND INSTALL VISQUEEN TYPE PLASTIC SHEET AND ZIPPER DOOR AS
REQUIRED TO MAINTAIN TYPE V INFECTION CONTROL PRECAUTIONS. EXTEND
AND SEAL TO ROOF DECK/STRUCTURE ABOVE.
4. SUPPLY AND INSTALL WALK OFF MATS.
5. PROTECT EXISTING FINISHES FROM DUST AND DAMAGE.
1. PROVIDE MIGHTY MO 20 RACK, OR-MM20730B (OR EQUIVALENT)
2. PROVIDE VERTICAL WIRE MANAGER, OR-MM20VMD706 (OR EQUIVALENT)
3. PROVIDE 4'X8' AC GRADE 3/4" TRADE SIZE FIRE RATED PLYWOOD BACKBOARD PAINTED HIGH GLOSS WHITE WITH
(2) COATS OF PAINT FOR SERVICE PROVIDER/SECURITY/VIDEO/ETC. AROUND PERIMETER WALLS OF TR"s AND ENTRANCE ROOMS AS SHOWN. ENSURE THAT FIRE RATING STAMP IS TO REMAIN UNCOVERED BY PAINT.
4. PROVIDE FIXED CAMERA WITH PASSIVE INFRARED(PIR) SUPPLEMENTAL LIGHTING ON TELECOM ROOM CORNER.
5. PROVIDE ACCESS CONTROL DEVICES ON SECURITY DOOR.
6. PROVIDE COPPER GROUNDING BUSBAR AT 5' AFF IN LOCATION SHOWN. SEE GROUNDING BAR DETAIL FOR
ADDITIONAL REQUIREMENTS.
7. BASKET STYLE CABLE TRAY MINIMUM 4"X18" SHALL BE USED. ALL TRAY MUST BE INSTALLED AT 7'8" AFF, SUPPORTED PER MANUFACTURER REQUIREMENTS, AND PROPERLY BONDED TO GROUND.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
ROOM A-129B
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 1'
AutoCAD SHX Text 2'
AutoCAD SHX Text 4'
AutoCAD SHX Text 8'
AutoCAD SHX Text 1/4"=1'-0"
AutoCAD SHX Text
AutoCAD SHX Text
BUILDING 03 - ENLARGED PLAN RM A-129B
AutoCAD SHX Text
AutoCAD SHX Text 1'
AutoCAD SHX Text 2'
AutoCAD SHX Text 4'
AutoCAD SHX Text 8'
AutoCAD SHX Text 1/4"=1'-0"
AutoCAD SHX Text
AutoCAD SHX Text
BUILDING 03 - ENLARGED RCP RM A-129B
AutoCAD SHX Text
KEY PLAN
AutoCAD SHX Text N mgonser Snapshot mgonser Snapshot mgonser Snapshot mgonser Snapshot
TYPTYP
ES DC
TYP
MID
RX
CR/K
ICT - BUILDING 03 - LEVEL 2 -
ENLARGED PLANS
JG JG
TT-B03-421
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
K:
\C
C G
_P R
O
JE
C
TS
\2
1\
-1
T op ek a
EH
R M
C
1R
\4
- D es
D oc s\
2- D ra w in gs
\W O
R
KI
N G
\A ut oC
AD
\T T-
B0 3-
1.
dw g
3/
/2
:3 1:
A
M
ISSUE FOR BIDOffice of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
EHRM INFRASTRUCTURE
UPGRADES
COLMERY O'NEIL VA HEALTH CARE
21-116
Revisions: Date:
www. bancroft-ae.com
3300 Dundee RD.
Northbrook, IL 60062
T: 847.952.9362
35% SCHEMATIC DESIGN SUBMISSION 07-12-22
95% CONSTRUCTION DOCUMENTS SUBMISSION 10-31-23
100% CONSTRUCTION DOCUMENTS SUBMISSION
12/28/2023
12-19-23
Bancroft Project No: 21-116
35% SCHEMATIC DESIGN SUBMISSION R1 09-21-22
35% SUBMITTAL II 06-13-23
65% DESIGN DEVELOPMENT SUBMITTAL 09-12-23
ISSUED FOR BID 12-28-23
GENERAL NOTES
A. FOR GENERAL NOTES AND LEGENDS REFER TO SHEET TT001.
B. EXISTING IT/TR/OI&T ROOMS TO REMAIN ACTIVE DURING CONSTRUCTION. G.C. TO PROTECT EQUIPMENT
DURING CONSTRUCTION WITH VISQUEEN. CONTRACTOR TO ENSURE CONTINUOUS OPERATION OF
EQUIPMENT.
C. NOT ALL KEY NOTES APPLY TO ALL PLAN SHEETS. G.C. TO APPLY ONLY AS INDICATED PER EACH SHEET.
D. APPLY FIRE RATED SEALANT TO ALL EXISTING AND NEW PENETRATIONS IN EXISTING WALLS TO MAKE
EXISTING WALLS A 1 HR ASSEMBLY. BASIS OF DESIGN FOR 1 HR WALL IS UL 419 ASSEMBLY.
E. CONTRACTOR SHALL PROVIDE AND INSTALL FIRE RATED SLEEVES AS NECESSARY AND ASSEMBLED PER UL
DETAIL APPROPRIATE FOR WALL/FLOOR AND RACEWAY/CABLE TYPES.
F. TELECOMMUNICATION ROOM (TR) RACK MOUNTED PDU CORDSETS:
1. SHALL BE IEC 60320 C14-C15 DEVICE POWER CORDSETS, FUNCTIONALLY EQUIVALENT TO CISCO SYSTEMS
PART# CAB-C15-CBN.
2. SHALL BE RATED FOR: a. AT LEAST 250 VAC b.13 AMPS c.60HZ d.120 DEGREES C (248 DEGREES F)
3. UL LISTED
4. MAXIMUM OF 4 FEET IN LENGTH. SHORTER LENGTHS MAY BE USED TO REDUCE EXCESSIVE SLACK.
5. COUPLER TERMINATIONS ON CORDSET: a. IEC 60320 C14 PLUG CONNECTOR (RACK PDU END) b.IEC 60320 C15 PLUG (DEVICE END)
6. SELECTION OF DISTINCT CONTRASTING CORDSET COLORS TO INDICATE DIVERSE (A/B) POWER
DISTRIBUTION SOURCES.
a. BLACK AND GRAY RECOMMENDED.
7. QUANTITY:
a. PROVIDE ONE SET OF C14-C15 POWER CORDS PER DEVICE TO BE CONNECTED TO RACK
MOUNTED PDU’S.
i. ONE SET SHALL CONSIST OF TWO (2) POWER CORDS FOR CONNECTION TO
DIVERSE (A/B) POWER DISTRIBUTION SOURCES.
b. PROVIDE MINIMUM OF ONE SET OF C14-C15 POWER CORDS PER SET OF RACK MOUNTED PDU’S.
c. PROVIDE MINIMUM OF ONE SET OF C14-C15 POWER CORDS PER RACK INSTALLED IN EACH TR.
d. IN ADDITION OF QUANTITIES LISTED ABOVE, PROVIDE ONE SPARE SET OF C14-C15 POWER CORDS
PER TR.
FLOOR PLAN KEYNOTESX
FLOOR PLAN LEGEND
BACKBOARD PROVIDED AND INSTALLED BY OTHERS.
DEMO PLAN GENERAL NOTES
1. REMOVE EXISTING WALL MOUNTED SERVER RACK.
2. RELOCATE EXISTING UTILITY PIPING AS REQUIRED TO ACCOMMODATE NEW
SERVER RACK. COORDINATE FINAL LOCATIONS WITH VA/COR.
3. PROVIDE AND INSTALL VISQUEEN TYPE PLASTIC SHEET AND ZIPPER DOOR AS
REQUIRED TO MAINTAIN TYPE V INFECTION CONTROL PRECAUTIONS. EXTEND
AND SEAL TO ROOF DECK/STRUCTURE ABOVE.
4. SUPPLY AND INSTALL WALK OFF MATS.
5. PROTECT EXISTING FINISHES FROM DUST AND DAMAGE.
1. PROVIDE MIGHTY MO 20 RACK, OR-MM20730B (OR EQUIVALENT)
2. PROVIDE VERTICAL WIRE MANAGER, OR-MM20VMD706 (OR EQUIVALENT)
3. PROVIDE 4'X8' AC GRADE 3/4" TRADE SIZE FIRE RATED PLYWOOD BACKBOARD PAINTED HIGH GLOSS WHITE WITH
(2) COATS OF PAINT FOR SERVICE PROVIDER/SECURITY/VIDEO/ETC. AROUND PERIMETER WALLS OF TR"s AND ENTRANCE ROOMS AS SHOWN. ENSURE THAT FIRE RATING STAMP IS TO REMAIN UNCOVERED BY PAINT.
4. PROVIDE FIXED CAMERA WITH PASSIVE INFRARED(PIR) SUPPLEMENTAL LIGHTING ON TELECOM ROOM CORNER.
5. PROVIDE ACCESS CONTROL DEVICES ON SECURITY DOOR.
6. PROVIDE COPPER GROUNDING BUSBAR AT 5' AFF IN LOCATION SHOWN. SEE GROUNDING BAR DETAIL FOR
ADDITIONAL REQUIREMENTS.
7. BASKET STYLE CABLE TRAY MINIMUM 4"X18" SHALL BE USED. ALL TRAY MUST BE INSTALLED AT 7'8" AFF, SUPPORTED PER MANUFACTURER REQUIREMENTS, AND PROPERLY BONDED TO GROUND.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
ROOM A-229A
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 1'
AutoCAD SHX Text 2'
AutoCAD SHX Text 4'
AutoCAD SHX Text 8'
AutoCAD SHX Text 1/4"=1'-0"
AutoCAD SHX Text
AutoCAD SHX Text
BUILDING 03 - ENLARGED PLAN RM A-229A
AutoCAD SHX Text
AutoCAD SHX Text 1'
AutoCAD SHX Text 2'
AutoCAD SHX Text 4'
AutoCAD SHX Text 8'
AutoCAD SHX Text 1/4"=1'-0"
AutoCAD SHX Text
AutoCAD SHX Text
BUILDING 03 - ENLARGED RCP RM A-229A
AutoCAD SHX Text
KEY PLAN
AutoCAD SHX Text N mgonser Snapshot mgonser Snapshot mgonser Snapshot
DNDN
UP
UPUP
C0-C1A0-C1B0-C1 B09
B09A
B09B
C17
C17A
C17B
C17F C18
C19E
C15 C15B
C15A
C19
C23 C22
A14
A24A24A
A24B
A13A0-S1
A12F A11
A2E A01E B04B05
B07E
B08FB08
B07 B03
A01A
A01A02 C20
A0-E9
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
K:
\C
C G
_P R
O
JE
C
TS
\2
1\
-1
T op ek a
EH
R M
C
1R
\4
- D es
D oc s\
2- D ra w in gs
\W O
R
KI
N G
\A ut oC
AD
\T T-
B0 4-
0.
dw g
1/
/2
2:
:0
PM
ISSUE FOR BIDOffice of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
EHRM INFRASTRUCTURE
UPGRADES
COLMERY O'NEIL VA HEALTH CARE
21-116
Revisions: Date:
www. bancroft-ae.com
3300 Dundee RD.
Northbrook, IL 60062
T: 847.952.9362
35% SCHEMATIC DESIGN SUBMISSION 07-12-22
95% CONSTRUCTION DOCUMENTS SUBMISSION 10-31-23
100% CONSTRUCTION DOCUMENTS SUBMISSION
12/28/2023
12-19-23
Bancroft Project No: 21-116
35% SCHEMATIC DESIGN SUBMISSION R1 09-21-22
35% SUBMITTAL II 06-13-23
65% DESIGN DEVELOPMENT SUBMITTAL 09-12-23
ISSUED FOR BID 12-28-23
ICT - BUILDING 4 BASEMENT LEVEL
CABLE TRAY PLAN
JG JG
TT-B04-100
GENERAL NOTES
A. FOR GENERAL NOTES AND LEGENDS REFER TO SHEET TT001.
B. EXISTING IT/TR/OI&T ROOMS TO REMAIN ACTIVE DURING CONSTRUCTION. G.C. TO PROTECT EQUIPMENT
DURING CONSTRUCTION WITH VISQUEEN. CONTRACTOR TO ENSURE CONTINUOUS OPERATION OF EQUIPMENT.
C. NOT ALL KEY NOTES APPLY TO ALL PLAN SHEETS. G.C. TO APPLY ONLY AS INDICATED PER EACH SHEET.
D. APPLY FIRE RATED SEALANT TO ALL EXISTING AND NEW PENETRATIONS IN EXISTING WALLS TO MAKE
EXISTING WALLS A 1 HR ASSEMBLY. BASIS OF DESIGN FOR 1 HR WALL IS UL 419 ASSEMBLY.
E. CONTRACTOR SHALL PROVIDE AND INSTALL FIRE RATED SLEEVES AS NECESSARY AND ASSEMBLED PER UL
DETAIL APPROPRIATE FOR WALL/FLOOR AND RACEWAY/CABLE TYPES
FLOOR PLAN KEYNOTESX
FLOOR PLAN LEGEND
BASKET CABLE TRAY.
1. PROVIDE BASKET TYPE CABLE TRAY TO SUPPORT OPTICAL FIBER BACKBONE AND NEW CAT 6A HORIZONTAL CABLING. CABLE TRAY TO BE SIZED AS PER CABLE TRAY CAPACITY PLANNING ON FLOOR PLAN LEGEND, ASSUMING 40% FILL AND 25% SPARE CAPACITY. ROUTING SHOWN INDICATES PRIMARY PATHWAYS. IN ADDITION TO PRIMARY PATHWAYS, CABLE TRAY SHALL BE PROVIDED WHEN CABLE BUNDLES EXCEED 24 CABLES. FIRE RATED MECHANICAL SLEEVE ASSEMBLIES SHALL BE PROVIDED WHEN PASSING THROUGH FIRE
RATED PARTITIONS. ASSUMING 40% FILL AND 50% SPARE CAPACITY.
CAT. NO
CF105/300
CF105/450
CF105/500
CF105/600
CF150/150
CF150/200
CF150/300
CF150/450
CF150/500
CF150/600
CF150/900
DEPTH
(IN)
WIDTH
(IN)
CAT 6A 4 PAIR
PLENUM (0.35")
- CABLE TRAY CAPACITY PLANNING.
- PROPOSED CABLE TRAY:
CABLOFIL 4" DEEP X 12" WIDE MINIMUM
(SIZE COMMENSURATE WITH DISTRIBUTION
REQUIREMENT) WHITE POWERCOAT TRAY INSERT.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
KEY PLAN
AutoCAD SHX Text N
AutoCAD SHX Text
AutoCAD SHX Text 4'
AutoCAD SHX Text 8'
AutoCAD SHX Text 16'
AutoCAD SHX Text 32'
AutoCAD SHX Text 1/16"=1'-0"
AutoCAD SHX Text
AutoCAD SHX Text
BUILDING 4 - BASEMENT LEVEL CABLE TRAY PLAN
AutoCAD SHX Text
NORTH
mgonser Snapshot mgonser Snapshot mgonser Snapshot
UPUP
C0-C1A0-C1B0-C1 B09
B09A
B09B
C17
C17A
C17B
C17F C18
C19E
C15 C15B
C15A
C19
C23 C22
A14
A24A24A
A24B
A13A0-S1
A12F A11
A2E A01E B04B05
B07E
B08FB08
B07 B03
A01A
A01A02 C20
A0-E9
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
K:
\C
C G
_P R
O
JE
C
TS
\2
1\
-1
T op ek a
EH
R M
C
1R
\4
- D es
D oc s\
2- D ra w in gs
\W O
R
KI
N G
\A ut oC
AD
\T T-
B0 4-
0R
P.
dw g 3/
/2
6:
:1
PM
ISSUE FOR BIDOffice of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
EHRM INFRASTRUCTURE
UPGRADES
COLMERY O'NEIL VA HEALTH CARE
21-116
Revisions: Date:
www. bancroft-ae.com
3300 Dundee RD.
Northbrook, IL 60062
T: 847.952.9362
35% SCHEMATIC DESIGN SUBMISSION 07-12-22
95% CONSTRUCTION DOCUMENTS SUBMISSION 10-31-23
100% CONSTRUCTION DOCUMENTS SUBMISSION
12/28/2023
12-19-23
Bancroft Project No: 21-116
35% SCHEMATIC DESIGN SUBMISSION R1 09-21-22
35% SUBMITTAL II 06-13-23
65% DESIGN DEVELOPMENT SUBMITTAL 09-12-23
ISSUED FOR BID 12-28-23
ICT - BUILDING 4 BASEMENT LEVEL -
ROUTING PLAN
JG JG
TT-B04-100RP
GENERAL NOTES
A. FOR GENERAL NOTES AND LEGENDS REFER TO SHEET TT001.
B. EXISTING IT/TR/OI&T ROOMS TO REMAIN ACTIVE DURING CONSTRUCTION. G.C. TO PROTECT EQUIPMENT
DURING CONSTRUCTION WITH VISQUEEN. CONTRACTOR TO ENSURE CONTINUOUS OPERATION OF EQUIPMENT.
C. NOT ALL KEY NOTES APPLY TO ALL PLAN SHEETS. G.C. TO APPLY ONLY AS INDICATED PER EACH SHEET.
D. APPLY FIRE RATED SEALANT TO ALL EXISTING AND NEW PENETRATIONS IN EXISTING WALLS TO MAKE
EXISTING WALLS A 1 HR ASSEMBLY. BASIS OF DESIGN FOR 1 HR WALL IS UL 419 ASSEMBLY.
E. CONTRACTOR SHALL PROVIDE AND INSTALL FIRE RATED SLEEVES AS NECESSARY AND ASSEMBLED PER UL
DETAIL APPROPRIATE FOR WALL/FLOOR AND RACEWAY/CABLE TYPES
FLOOR PLAN KEYNOTESX
1. PROVIDE SLEEVES, CONDUITS OR MECHANICAL FIRE-PROOF ASSEMBLIES AS REQUIRED THROUGH WALLS OR FLOORS AS REQUIRED TO MAINTAIN EXISTING RATING. REFER TO ONE-LINE CABLE RISER DIAGRAMS FOR CABLE QUANTITY AND TYPE. CONTRACTOR SHALL SIZE PATHWAYS TO ACCOMMODATE DAY ONE CABLING
PLUS 40 PERCENT SPARE FUTURE CAPACITY.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
KEY PLAN
AutoCAD SHX Text N
AutoCAD SHX Text
AutoCAD SHX Text 4'
AutoCAD SHX Text 8'
AutoCAD SHX Text 16'
AutoCAD SHX Text 32'
AutoCAD SHX Text 1/16"=1'-0"
AutoCAD SHX Text
AutoCAD SHX Text
BUILDING 4 - BASEMENT LEVEL ROUTING PLAN
AutoCAD SHX Text
NORTH
mgonser Snapshot mgonser Snapshot mgonser Snapshot
UP UP
UPUP UP
A1-S1
A101
A138A
A136
A139
A136A
A137
A141
A143
A140
A144 A145
A102
B134
A102EA103E
A103
A1-C4
A138
B112
B104B105
B1-C2
B131
B108
B132
B132A
B130
B129
B129A
B128
B106 B107
B125F
B1-S3
B125
B125A
B126
B126A
B127
B127A
B133
B123
B115E
B122
B113
B114
B115
B121E
B116
B116A
B117B118
B121
B121AB120
B109
B119
B119A
A101A
C1-3
C163E
C163 C164
C165
C166 C167
C168
C169C169AC170
C148
C149
C150
C151
C153
C154 C155
C156
C157
C158C158F
C162
C161
C160C142A
C145 C146
C143
C143A
C143B
C142
C144
C175A C174A
C172
C171
C170E
C152
C173
C174C175
C147
C1-C1A1-C2
A1-C1
A1-C3
B110
C1-C2
B1-C1
B1-C4
B1-C3
C144A
C163A
A1-E9
C1-S2 C150A
B130A
A138B
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
K:
\C
C G
_P R
O
JE
C
TS
\2
1\
-1
T op ek a
EH
R M
C
1R
\4
- D es
D oc s\
2- D ra w in gs
\W O
R
KI
N G
\A ut oC
AD
\T T-
B0 4-
1.
dw g
1/
/2
2:
:0
PM
ISSUE FOR BIDOffice of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
EHRM INFRASTRUCTURE
UPGRADES
COLMERY O'NEIL VA HEALTH CARE
21-116
Revisions: Date:
www. bancroft-ae.com
3300 Dundee RD.
Northbrook, IL 60062
T: 847.952.9362
35% SCHEMATIC DESIGN SUBMISSION 07-12-22
95% CONSTRUCTION DOCUMENTS SUBMISSION 10-31-23
100% CONSTRUCTION DOCUMENTS SUBMISSION
12/28/2023
12-19-23
Bancroft Project No: 21-116
35% SCHEMATIC DESIGN SUBMISSION R1 09-21-22
35% SUBMITTAL II 06-13-23
65% DESIGN DEVELOPMENT SUBMITTAL 09-12-23
ISSUED FOR BID 12-28-23
ICT - BUILDING 4 - LEVEL 1 CABLE TRAY
PLAN
JG JG
TT-B04-101
GENERAL NOTES
A. FOR GENERAL NOTES AND LEGENDS REFER TO SHEET TT001.
B. EXISTING IT/TR/OI&T ROOMS TO REMAIN ACTIVE DURING CONSTRUCTION. G.C. TO PROTECT EQUIPMENT
DURING CONSTRUCTION WITH VISQUEEN. CONTRACTOR TO ENSURE CONTINUOUS OPERATION OF EQUIPMENT.
C. NOT ALL KEY NOTES APPLY TO ALL PLAN SHEETS. G.C. TO APPLY ONLY AS INDICATED PER EACH SHEET.
D. APPLY FIRE RATED SEALANT TO ALL EXISTING AND NEW PENETRATIONS IN EXISTING WALLS TO MAKE
EXISTING WALLS A 1 HR ASSEMBLY. BASIS OF DESIGN FOR 1 HR WALL IS UL 419 ASSEMBLY.
E. CONTRACTOR SHALL PROVIDE AND INSTALL FIRE RATED SLEEVES AS NECESSARY AND ASSEMBLED PER UL
DETAIL APPROPRIATE FOR WALL/FLOOR AND RACEWAY/CABLE TYPES
FLOOR PLAN KEYNOTESX
FLOOR PLAN LEGEND
BASKET CABLE TRAY.
1. PROVIDE BASKET TYPE CABLE TRAY TO SUPPORT OPTICAL FIBER BACKBONE AND NEW CAT 6A HORIZONTAL CABLING. CABLE TRAY TO BE SIZED AS PER CABLE TRAY CAPACITY PLANNING ON FLOOR PLAN LEGEND, ASSUMING 40% FILL AND 25% SPARE CAPACITY. ROUTING SHOWN INDICATES PRIMARY PATHWAYS. IN ADDITION TO PRIMARY PATHWAYS, CABLE TRAY SHALL BE PROVIDED WHEN CABLE BUNDLES EXCEED 24 CABLES. FIRE RATED MECHANICAL SLEEVE ASSEMBLIES SHALL BE PROVIDED WHEN PASSING THROUGH FIRE
RATED PARTITIONS. ASSUMING 40% FILL AND 50% SPARE CAPACITY.
CAT. NO
CF105/300
CF105/450
CF105/500
CF105/600
CF150/150
CF150/200
CF150/300
CF150/450
CF150/500
CF150/600
CF150/900
DEPTH
(IN)
WIDTH
(IN)
CAT 6A 4 PAIR
PLENUM (0.35")
- CABLE TRAY CAPACITY PLANNING.
- PROPOSED CABLE TRAY:
CABLOFIL 4" DEEP X 12" WIDE MINIMUM
(SIZE COMMENSURATE WITH DISTRIBUTION
REQUIREMENT) WHITE POWERCOAT TRAY INSERT.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 4'
AutoCAD SHX Text 8'
AutoCAD SHX Text 16'
AutoCAD SHX Text 32'
AutoCAD SHX Text 1/16"=1'-0"
AutoCAD SHX Text
AutoCAD SHX Text
BUILDING 4 - LEVEL 1 CABLE TRAY PLAN
AutoCAD SHX Text
NORTH
AutoCAD SHX Text
KEY PLAN
AutoCAD SHX Text N mgonser Snapshot mgonser Snapshot mgonser Snapshot
UPUP UP
A1-S1
A101
A138A
A136
A139
A136A
A137
A141
A143
A140
A144 A145
A102
B134
A102EA103E
A103
A1-C4
A138
B112
B104B105
B1-C2
B131
B108
B132
B132A
B130
B129
B129A
B128
B106 B107
B125F
B1-S3
B125
B125A
B126
B126A
B127
B127A
B133
B123
B115E
B122
B113
B114
B115
B121E
B116
B116A
B117B118
B121
B121AB120
B109
B119
B119A
A101A
C1-3
C163E
C163 C164
C165
C166 C167
C168
C169C169AC170
C148
C149
C150
C151
C153
C154 C155
C156
C157
C158C158F
C162
C161
C160C142A
C145 C146
C143
C143A
C143B
C142
C144
C175A C174A
C172
C171
C170E
C152
C173
C174C175
C147
C1-C1A1-C2
A1-C1
A1-C3
B110
C1-C2
B1-C1
B1-C4
B1-C3
C144A
C163A
A1-E9
C1-S2 C150A
B130A
A138B
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
K:
\C
C G
_P R
O
JE
C
TS
\2
1\
-1
T op ek a
EH
R M
C
1R
\4
- D es
D oc s\
2- D ra w in gs
\W O
R
KI
N G
\A ut oC
AD
\T T-
B0 4-
1R
P.
dw g 3/
/2
6:
:2
PM
ISSUE FOR BIDOffice of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
EHRM INFRASTRUCTURE
UPGRADES
COLMERY O'NEIL VA HEALTH CARE
21-116
Revisions: Date:
www. bancroft-ae.com
3300 Dundee RD.
Northbrook, IL 60062
T: 847.952.9362
35% SCHEMATIC DESIGN SUBMISSION 07-12-22
95% CONSTRUCTION DOCUMENTS SUBMISSION 10-31-23
100% CONSTRUCTION DOCUMENTS SUBMISSION
12/28/2023
12-19-23
Bancroft Project No: 21-116
35% SCHEMATIC DESIGN SUBMISSION R1 09-21-22
35% SUBMITTAL II 06-13-23
65% DESIGN DEVELOPMENT SUBMITTAL 09-12-23
ISSUED FOR BID 12-28-23
ICT - BUILDING 4 - LEVEL 1 - ROUTING
PLAN
JG JG
TT-B04-101RP
GENERAL NOTES
A. FOR GENERAL NOTES AND LEGENDS REFER TO SHEET TT001.
B. EXISTING IT/TR/OI&T ROOMS TO REMAIN ACTIVE DURING CONSTRUCTION. G.C. TO PROTECT EQUIPMENT
DURING CONSTRUCTION WITH VISQUEEN. CONTRACTOR TO ENSURE CONTINUOUS OPERATION OF EQUIPMENT.
C. NOT ALL KEY NOTES APPLY TO ALL PLAN SHEETS. G.C. TO APPLY ONLY AS INDICATED PER EACH SHEET.
D. APPLY FIRE RATED SEALANT TO ALL EXISTING AND NEW PENETRATIONS IN EXISTING WALLS TO MAKE
EXISTING WALLS A 1 HR ASSEMBLY. BASIS OF DESIGN FOR 1 HR WALL IS UL 419 ASSEMBLY.
E. CONTRACTOR SHALL PROVIDE AND INSTALL FIRE RATED SLEEVES AS NECESSARY AND ASSEMBLED PER UL
DETAIL APPROPRIATE FOR WALL/FLOOR AND RACEWAY/CABLE TYPES
FLOOR PLAN KEYNOTESX
1. PROVIDE SLEEVES, CONDUITS OR MECHANICAL FIRE-PROOF ASSEMBLIES AS REQUIRED THROUGH WALLS OR FLOORS AS REQUIRED TO MAINTAIN EXISTING RATING. REFER TO ONE-LINE CABLE RISER DIAGRAMS FOR CABLE QUANTITY AND TYPE. CONTRACTOR SHALL SIZE PATHWAYS TO ACCOMMODATE DAY ONE CABLING
PLUS 40 PERCENT SPARE FUTURE CAPACITY.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 4'
AutoCAD SHX Text 8'
AutoCAD SHX Text 16'
AutoCAD SHX Text 32'
AutoCAD SHX Text 1/16"=1'-0"
AutoCAD SHX Text
AutoCAD SHX Text
BUILDING 4 - LEVEL 1 ROUTING PLAN
AutoCAD SHX Text
NORTH
AutoCAD SHX Text
KEY PLAN
AutoCAD SHX Text N mgonser Snapshot mgonser Snapshot mgonser Snapshot
A201
A236
A271
A234F
A2 -S
A238
A237
A269 C268 C267 C265
C239A
C240 C239
C249
C250
C256
C255A
C254
C253A
C253
C263 C255
C262
C256E
C251E
C257
C258
C2-S2
C247
C243A
C243
C242
C246A
C246
C247F
C247G
C244A
C264
C2-C1
C2-C2
C252
C241
C2-C3
C251A C251
C244
C247A
B231 A234A234A
A202EA203E
B204B205B206
B232
B230
B225F
B2-C1
B225
B225A
B223
B222
B221E
B215EB2-C3
B213
B214
B215
B216A
B217B218
B226A
B226
B209 B208
B207 A203
B232A
B233
B229A
B229
B227A
B227 B228
B2 -S
B218A
B219 B220A B220
B221
B216 A202 A270
B210B212
B2-C4
B2-C2
C266
C261
C2-C4
C259
A2-9
C242AB230A
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
K:
\C
C G
_P R
O
JE
C
TS
\2
1\
-1
T op ek a
EH
R M
C
1R
\4
- D es
D oc s\
2- D ra w in gs
\W O
R
KI
N G
\A ut oC
AD
\T T-
B0 4-
2.
dw g
1/
/2
2:
:0
PM
ISSUE FOR BIDOffice of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
EHRM INFRASTRUCTURE
UPGRADES
COLMERY O'NEIL VA HEALTH CARE
21-116
Revisions: Date:
www. bancroft-ae.com
3300 Dundee RD.
Northbrook, IL 60062
T: 847.952.9362
35% SCHEMATIC DESIGN SUBMISSION 07-12-22
95% CONSTRUCTION DOCUMENTS SUBMISSION 10-31-23
100% CONSTRUCTION DOCUMENTS SUBMISSION
12/28/2023
12-19-23
Bancroft Project No: 21-116
35% SCHEMATIC DESIGN SUBMISSION R1 09-21-22
35% SUBMITTAL II 06-13-23
65% DESIGN DEVELOPMENT SUBMITTAL 09-12-23
ISSUED FOR BID 12-28-23
ICT - BUILDING 4 - LEVEL 2 CABLE
TRAY PLAN
JG JG
TT-B04-102
GENERAL NOTES
A. FOR GENERAL NOTES AND LEGENDS REFER TO SHEET TT001.
B. EXISTING IT/TR/OI&T ROOMS TO REMAIN ACTIVE DURING CONSTRUCTION. G.C. TO PROTECT EQUIPMENT
DURING CONSTRUCTION WITH VISQUEEN. CONTRACTOR TO ENSURE CONTINUOUS OPERATION OF EQUIPMENT.
C. NOT ALL KEY NOTES APPLY TO ALL PLAN SHEETS. G.C. TO APPLY ONLY AS INDICATED PER EACH SHEET.
D. APPLY FIRE RATED SEALANT TO ALL EXISTING AND NEW PENETRATIONS IN EXISTING WALLS TO MAKE
EXISTING WALLS A 1 HR ASSEMBLY. BASIS OF DESIGN FOR 1 HR WALL IS UL 419 ASSEMBLY.
E. CONTRACTOR SHALL PROVIDE AND INSTALL FIRE RATED SLEEVES AS NECESSARY AND ASSEMBLED PER UL
DETAIL APPROPRIATE FOR WALL/FLOOR AND RACEWAY/CABLE TYPES
FLOOR PLAN KEYNOTESX
FLOOR PLAN LEGEND
BASKET CABLE TRAY.
1. PROVIDE BASKET TYPE CABLE TRAY TO SUPPORT OPTICAL FIBER BACKBONE AND NEW CAT 6A HORIZONTAL CABLING. CABLE TRAY TO BE SIZED AS PER CABLE TRAY CAPACITY PLANNING ON FLOOR PLAN LEGEND, ASSUMING 40% FILL AND 25% SPARE CAPACITY. ROUTING SHOWN INDICATES PRIMARY PATHWAYS. IN ADDITION TO PRIMARY PATHWAYS, CABLE TRAY SHALL BE PROVIDED WHEN CABLE BUNDLES EXCEED 24 CABLES. FIRE RATED MECHANICAL SLEEVE ASSEMBLIES SHALL BE PROVIDED WHEN PASSING THROUGH FIRE
RATED PARTITIONS. ASSUMING 40% FILL AND 50% SPARE CAPACITY.
CAT. NO
CF105/300
CF105/450
CF105/500
CF105/600
CF150/150
CF150/200
CF150/300
CF150/450
CF150/500
CF150/600
CF150/900
DEPTH
(IN)
WIDTH
(IN)
CAT 6A 4 PAIR
PLENUM (0.35")
- CABLE TRAY CAPACITY PLANNING.
- PROPOSED CABLE TRAY:
CABLOFIL 4" DEEP X 12" WIDE MINIMUM
(SIZE COMMENSURATE WITH DISTRIBUTION
REQUIREMENT) WHITE POWERCOAT TRAY INSERT.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 4'
AutoCAD SHX Text 8'
AutoCAD SHX Text 16'
AutoCAD SHX Text 32'
AutoCAD SHX Text 1/16"=1'-0"
AutoCAD SHX Text
AutoCAD SHX Text
BUILDING 4 - LEVEL 2 CABLE TRAY PLAN
AutoCAD SHX Text
NORTH
AutoCAD SHX Text
KEY PLAN
AutoCAD SHX Text N mgonser Snapshot mgonser Snapshot mgonser Snapshot
A201
A236
A271
A234F
A2 -S
A238
A237
A269 C268 C267 C265
C239A
C240 C239
C249
C250
C256
C255A
C254
C253A
C253
C263 C255
C262
C256E
C251E
C257
C258
C2-S2
C247
C243A
C243
C242
C246A
C246
C247F
C247G
C244A
C264
C2-C1
C2-C2
C252
C241
C2-C3
C251A C251
C244
C247A
B231 A234A234A
A202EA203E
B204B205B206
B232
B230
B225F
B2-C1
B225
B225A
B223
B222
B221E
B215EB2-C3
B213
B214
B215
B216A
B217B218
B226A
B226
B209 B208
B207 A203
B232A
B233
B229A
B229
B227A
B227 B228
B2 -S
B218A
B219 B220A B220
B221
B216 A202 A270
B210B212
B2-C4
B2-C2
C266
C261
C2-C4
C259
A2-9
C242AB230A
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
K:
\C
C G
_P R
O
JE
C
TS
\2
1\
-1
T op ek a
EH
R M
C
1R
\4
- D es
D oc s\
2- D ra w in gs
\W O
R
KI
N G
\A ut oC
AD
\T T-
B0 4-
2R
P.
dw g 3/
/2
6:
:0
PM
ISSUE FOR BIDOffice of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
EHRM INFRASTRUCTURE
UPGRADES
COLMERY O'NEIL VA HEALTH CARE
21-116
Revisions: Date:
www. bancroft-ae.com
3300 Dundee RD.
Northbrook, IL 60062
T: 847.952.9362
35% SCHEMATIC DESIGN SUBMISSION 07-12-22
95% CONSTRUCTION DOCUMENTS SUBMISSION 10-31-23
100% CONSTRUCTION DOCUMENTS SUBMISSION
12/28/2023
12-19-23
Bancroft Project No: 21-116
35% SCHEMATIC DESIGN SUBMISSION R1 09-21-22
35% SUBMITTAL II 06-13-23
65% DESIGN DEVELOPMENT SUBMITTAL 09-12-23
ISSUED FOR BID 12-28-23
ICT - BUILDING 4 - LEVEL 2 - ROUTING
PLAN
JG JG
TT-B04-102RP
GENERAL NOTES
A. FOR GENERAL NOTES AND LEGENDS REFER TO SHEET TT001.
B. EXISTING IT/TR/OI&T ROOMS TO REMAIN ACTIVE DURING CONSTRUCTION. G.C. TO PROTECT EQUIPMENT
DURING CONSTRUCTION WITH VISQUEEN. CONTRACTOR TO ENSURE CONTINUOUS OPERATION OF EQUIPMENT.
C. NOT ALL KEY NOTES APPLY TO ALL PLAN SHEETS. G.C. TO APPLY ONLY AS INDICATED PER EACH SHEET.
D. APPLY FIRE RATED SEALANT TO ALL EXISTING AND NEW PENETRATIONS IN EXISTING WALLS TO MAKE
EXISTING WALLS A 1 HR ASSEMBLY. BASIS OF DESIGN FOR 1 HR WALL IS UL 419 ASSEMBLY.
E. CONTRACTOR SHALL PROVIDE AND INSTALL FIRE RATED SLEEVES AS NECESSARY AND ASSEMBLED PER UL
DETAIL APPROPRIATE FOR WALL/FLOOR AND RACEWAY/CABLE TYPES
FLOOR PLAN KEYNOTESX
1. PROVIDE SLEEVES, CONDUITS OR MECHANICAL FIRE-PROOF ASSEMBLIES AS REQUIRED THROUGH WALLS OR FLOORS AS REQUIRED TO MAINTAIN EXISTING RATING. REFER TO ONE-LINE CABLE RISER DIAGRAMS FOR CABLE QUANTITY AND TYPE. CONTRACTOR SHALL SIZE PATHWAYS TO ACCOMMODATE DAY ONE CABLING
PLUS 40 PERCENT SPARE FUTURE CAPACITY.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 4'
AutoCAD SHX Text 8'
AutoCAD SHX Text 16'
AutoCAD SHX Text 32'
AutoCAD SHX Text 1/16"=1'-0"
AutoCAD SHX Text
AutoCAD SHX Text
BUILDING 4 - LEVEL 2 ROUTING PLAN
AutoCAD SHX Text
NORTH
AutoCAD SHX Text
KEY PLAN
AutoCAD SHX Text N mgonser Snapshot mgonser Snapshot mgonser Snapshot
ES DC
TYP
MID RX
CR/K
ICT - BUILDING 04 - BASEMENT LEVEL -
ENLARGED PLANS
JG JG
TT-B04-401
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
K:
\C
C G
_P R
O
JE
C
TS
\2
1\
-1
T op ek a
EH
R M
C
1R
\4
- D es
D oc s\
2- D ra w in gs
\W O
R
KI
N G
\A ut oC
AD
\T T-
B0 4-
1.
dw g
3/
/2
:3 5:
A
M
ISSUE FOR BIDOffice of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
EHRM INFRASTRUCTURE
UPGRADES
COLMERY O'NEIL VA HEALTH CARE
21-116
Revisions: Date:
www. bancroft-ae.com
3300 Dundee RD.
Northbrook, IL 60062
T: 847.952.9362
35% SCHEMATIC DESIGN SUBMISSION 07-12-22
95% CONSTRUCTION DOCUMENTS SUBMISSION 10-31-23
100% CONSTRUCTION DOCUMENTS SUBMISSION
12/28/2023
12-19-23
Bancroft Project No: 21-116
35% SCHEMATIC DESIGN SUBMISSION R1 09-21-22
35% SUBMITTAL II 06-13-23
65% DESIGN DEVELOPMENT SUBMITTAL 09-12-23
ISSUED FOR BID 12-28-23
GENERAL NOTES
A. FOR GENERAL NOTES AND LEGENDS REFER TO SHEET TT001.
B. EXISTING IT/TR/OI&T ROOMS TO REMAIN ACTIVE DURING CONSTRUCTION. G.C. TO PROTECT EQUIPMENT
DURING CONSTRUCTION WITH VISQUEEN. CONTRACTOR TO ENSURE CONTINUOUS OPERATION OF
EQUIPMENT.
C. NOT ALL KEY NOTES APPLY TO ALL PLAN SHEETS. G.C. TO APPLY ONLY AS INDICATED PER EACH SHEET.
D. APPLY FIRE RATED SEALANT TO ALL EXISTING AND NEW PENETRATIONS IN EXISTING WALLS TO MAKE
EXISTING WALLS A 1 HR ASSEMBLY. BASIS OF DESIGN FOR 1 HR WALL IS UL 419 ASSEMBLY.
E. CONTRACTOR SHALL PROVIDE AND INSTALL FIRE RATED SLEEVES AS NECESSARY AND ASSEMBLED PER UL
DETAIL APPROPRIATE FOR WALL/FLOOR AND RACEWAY/CABLE TYPES.
F. TELECOMMUNICATION ROOM (TR) RACK MOUNTED PDU CORDSETS:
1. SHALL BE IEC 60320 C14-C15 DEVICE POWER CORDSETS, FUNCTIONALLY EQUIVALENT TO CISCO SYSTEMS
PART# CAB-C15-CBN.
2. SHALL BE RATED FOR: a. AT LEAST 250 VAC b.13 AMPS c.60HZ d.120 DEGREES C (248 DEGREES F)
3. UL LISTED
4. MAXIMUM OF 4 FEET IN LENGTH. SHORTER LENGTHS MAY BE USED TO REDUCE EXCESSIVE SLACK.
5. COUPLER TERMINATIONS ON CORDSET: a. IEC 60320 C14 PLUG CONNECTOR (RACK PDU END) b.IEC 60320 C15 PLUG (DEVICE END)
6. SELECTION OF DISTINCT CONTRASTING CORDSET COLORS TO INDICATE DIVERSE (A/B) POWER
DISTRIBUTION SOURCES.
a. BLACK AND GRAY RECOMMENDED.
7. QUANTITY:
a. PROVIDE ONE SET OF C14-C15 POWER CORDS PER DEVICE TO BE CONNECTED TO RACK
MOUNTED PDU’S.
i. ONE SET SHALL CONSIST OF TWO (2) POWER CORDS FOR CONNECTION TO
DIVERSE (A/B) POWER DISTRIBUTION SOURCES.
b. PROVIDE MINIMUM OF ONE SET OF C14-C15 POWER CORDS PER SET OF RACK MOUNTED PDU’S.
c. PROVIDE MINIMUM OF ONE SET OF C14-C15 POWER CORDS PER RACK INSTALLED IN EACH TR.
d. IN ADDITION OF QUANTITIES LISTED ABOVE, PROVIDE ONE SPARE SET OF C14-C15 POWER CORDS
PER TR.
FLOOR PLAN KEYNOTESX
FLOOR PLAN LEGEND
BACKBOARD PROVIDED AND INSTALLED BY OTHERS.
DEMO PLAN GENERAL NOTES
1. REMOVE EXISTING WALL MOUNTED SERVER RACK.
2. RELOCATE EXISTING UTILITY PIPING AS REQUIRED TO ACCOMMODATE NEW
SERVER RACK. COORDINATE FINAL LOCATIONS WITH VA/COR.
3. PROVIDE AND INSTALL VISQUEEN TYPE PLASTIC SHEET AND ZIPPER DOOR AS
REQUIRED TO MAINTAIN TYPE V INFECTION CONTROL PRECAUTIONS. EXTEND
AND SEAL TO ROOF DECK/STRUCTURE ABOVE.
4. SUPPLY AND INSTALL WALK OFF MATS.
5. PROTECT EXISTING FINISHES FROM DUST AND DAMAGE.
1. PROVIDE MIGHTY MO 20 RACK, OR-MM20730B (OR EQUIVALENT)
2. PROVIDE VERTICAL WIRE MANAGER, OR-MM20VMD706 (OR EQUIVALENT)
3. PROVIDE 4'X8' AC GRADE 3/4" TRADE SIZE FIRE RATED PLYWOOD BACKBOARD PAINTED HIGH GLOSS WHITE WITH
(2) COATS OF PAINT FOR SERVICE PROVIDER/SECURITY/VIDEO/ETC. AROUND PERIMETER WALLS OF TR"s AND ENTRANCE ROOMS AS SHOWN. ENSURE THAT FIRE RATING STAMP IS TO REMAIN UNCOVERED BY PAINT.
4. PROVIDE FIXED CAMERA WITH PASSIVE INFRARED(PIR) SUPPLEMENTAL LIGHTING ON TELECOM ROOM CORNER.
5. PROVIDE ACCESS CONTROL DEVICES ON SECURITY DOOR.
6. PROVIDE COPPER GROUNDING BUSBAR AT 5' AFF IN LOCATION SHOWN. SEE GROUNDING BAR DETAIL FOR
ADDITIONAL REQUIREMENTS.
7. BASKET STYLE CABLE TRAY MINIMUM 4"X18" SHALL BE USED. ALL TRAY MUST BE INSTALLED AT 7'8" AFF, SUPPORTED PER MANUFACTURER REQUIREMENTS, AND PROPERLY BONDED TO GROUND.
AutoCAD SHX Text
ROOM C-20
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 1'
AutoCAD SHX Text 2'
AutoCAD SHX Text 4'
AutoCAD SHX Text 8'
AutoCAD SHX Text 1/4"=1'-0"
AutoCAD SHX Text
AutoCAD SHX Text
BUILDING 04 - ENLARGED PLAN RM C-20
AutoCAD SHX Text
AutoCAD SHX Text 1'
AutoCAD SHX Text 2'
AutoCAD SHX Text 4'
AutoCAD SHX Text 8'
AutoCAD SHX Text 1/4"=1'-0"
AutoCAD SHX Text
AutoCAD SHX Text
BUILDING 04 - ENLARGED RCP RM C-20
AutoCAD SHX Text N
AutoCAD SHX Text
KEY PLAN
mgonser Snapshot mgonser Snapshot mgonser Snapshot
ES
DC
TYP
MID
RXCR/K
TYP
TYP
ES
DC
TYP
RX
CR/K
MID
ICT - BUILDING 04 - LEVEL 1 -
ENLARGED PLANS
JG JG
TT-B04-411
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
K:
\C
C G
_P R
O
JE
C
TS
\2
1\
-1
T op ek a
EH
R M
C
1R
\4
- D es
D oc s\
2- D ra w in gs
\W O
R
KI
N G
\A ut oC
AD
\T T-
B0 4-
1.
dw g
3/
/2
:3 8:
A
M
ISSUE FOR BIDOffice of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
EHRM INFRASTRUCTURE
UPGRADES
COLMERY O'NEIL VA HEALTH CARE
21-116
Revisions: Date:
www. bancroft-ae.com
3300 Dundee RD.
Northbrook, IL 60062
T: 847.952.9362
35% SCHEMATIC DESIGN SUBMISSION 07-12-22
95% CONSTRUCTION DOCUMENTS SUBMISSION 10-31-23
100% CONSTRUCTION DOCUMENTS SUBMISSION
12/28/2023
12-19-23
Bancroft Project No: 21-116
35% SCHEMATIC DESIGN SUBMISSION R1 09-21-22
35% SUBMITTAL II 06-13-23
65% DESIGN DEVELOPMENT SUBMITTAL 09-12-23
ISSUED FOR BID 12-28-23
GENERAL NOTES
A. FOR GENERAL NOTES AND LEGENDS REFER TO SHEET TT001.
B. EXISTING IT/TR/OI&T ROOMS TO REMAIN ACTIVE DURING CONSTRUCTION. G.C. TO PROTECT EQUIPMENT
DURING CONSTRUCTION WITH VISQUEEN. CONTRACTOR TO ENSURE CONTINUOUS OPERATION OF
EQUIPMENT.
C. NOT ALL KEY NOTES APPLY TO ALL PLAN SHEETS. G.C. TO APPLY ONLY AS INDICATED PER EACH SHEET.
D. APPLY FIRE RATED SEALANT TO ALL EXISTING AND NEW PENETRATIONS IN EXISTING WALLS TO MAKE
EXISTING WALLS A 1 HR ASSEMBLY. BASIS OF DESIGN FOR 1 HR WALL IS UL 419 ASSEMBLY.
E. CONTRACTOR SHALL PROVIDE AND INSTALL FIRE RATED SLEEVES AS NECESSARY AND ASSEMBLED PER UL
DETAIL APPROPRIATE FOR WALL/FLOOR AND RACEWAY/CABLE TYPES.
F. TELECOMMUNICATION ROOM (TR) RACK MOUNTED PDU CORDSETS:
1. SHALL BE IEC 60320 C14-C15 DEVICE POWER CORDSETS, FUNCTIONALLY EQUIVALENT TO CISCO SYSTEMS
PART# CAB-C15-CBN.
2. SHALL BE RATED FOR: a. AT LEAST 250 VAC b.13 AMPS c.60HZ d.120 DEGREES C (248 DEGREES F)
3. UL LISTED
4. MAXIMUM OF 4 FEET IN LENGTH. SHORTER LENGTHS MAY BE USED TO REDUCE EXCESSIVE SLACK.
5. COUPLER TERMINATIONS ON CORDSET: a. IEC 60320 C14 PLUG CONNECTOR (RACK PDU END) b.IEC 60320 C15 PLUG (DEVICE END)
6. SELECTION OF DISTINCT CONTRASTING CORDSET COLORS TO INDICATE DIVERSE (A/B) POWER
DISTRIBUTION SOURCES.
a. BLACK AND GRAY RECOMMENDED.
7. QUANTITY:
a. PROVIDE ONE SET OF C14-C15 POWER CORDS PER DEVICE TO BE CONNECTED TO RACK
MOUNTED PDU’S.
i. ONE SET SHALL CONSIST OF TWO (2) POWER CORDS FOR CONNECTION TO
DIVERSE (A/B) POWER DISTRIBUTION SOURCES.
b. PROVIDE MINIMUM OF ONE SET OF C14-C15 POWER CORDS PER SET OF RACK MOUNTED PDU’S.
c. PROVIDE MINIMUM OF ONE SET OF C14-C15 POWER CORDS PER RACK INSTALLED IN EACH TR.
d. IN ADDITION OF QUANTITIES LISTED ABOVE, PROVIDE ONE SPARE SET OF C14-C15 POWER CORDS
PER TR.
FLOOR PLAN KEYNOTESX
FLOOR PLAN LEGEND
BACKBOARD PROVIDED AND INSTALLED BY OTHERS.
DEMO PLAN GENERAL NOTES
1. REMOVE EXISTING WALL MOUNTED SERVER RACK.
2. RELOCATE EXISTING UTILITY PIPING AS REQUIRED TO ACCOMMODATE NEW
SERVER RACK. COORDINATE FINAL LOCATIONS WITH VA/COR.
3. PROVIDE AND INSTALL VISQUEEN TYPE PLASTIC SHEET AND ZIPPER DOOR AS
REQUIRED TO MAINTAIN TYPE V INFECTION CONTROL PRECAUTIONS. EXTEND
AND SEAL TO ROOF DECK/STRUCTURE ABOVE.
4. SUPPLY AND INSTALL WALK OFF MATS.
5. PROTECT EXISTING FINISHES FROM DUST AND DAMAGE.
1. PROVIDE MIGHTY MO 20 RACK, OR-MM20730B (OR EQUIVALENT)
2. PROVIDE VERTICAL WIRE MANAGER, OR-MM20VMD706 (OR EQUIVALENT)
3. PROVIDE 4'X8' AC GRADE 3/4" TRADE SIZE FIRE RATED PLYWOOD BACKBOARD PAINTED HIGH GLOSS WHITE WITH
(2) COATS OF PAINT FOR SERVICE PROVIDER/SECURITY/VIDEO/ETC. AROUND PERIMETER WALLS OF TR"s AND ENTRANCE ROOMS AS SHOWN. ENSURE THAT FIRE RATING STAMP IS TO REMAIN UNCOVERED BY PAINT.
4. PROVIDE FIXED CAMERA WITH PASSIVE INFRARED(PIR) SUPPLEMENTAL LIGHTING ON TELECOM ROOM CORNER.
5. PROVIDE ACCESS CONTROL DEVICES ON SECURITY DOOR.
6. PROVIDE COPPER GROUNDING BUSBAR AT 5' AFF IN LOCATION SHOWN. SEE GROUNDING BAR DETAIL FOR
ADDITIONAL REQUIREMENTS.
7. BASKET STYLE CABLE TRAY MINIMUM 4"X18" SHALL BE USED. ALL TRAY MUST BE INSTALLED AT 7'8" AFF, SUPPORTED PER MANUFACTURER REQUIREMENTS, AND PROPERLY BONDED TO GROUND.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
ROOM B-130A
AutoCAD SHX Text
ROOM C-146
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 1'
AutoCAD SHX Text 2'
AutoCAD SHX Text 4'
AutoCAD SHX Text 8'
AutoCAD SHX Text 1/4"=1'-0"
AutoCAD SHX Text
AutoCAD SHX Text
BUILDING 04 - ENLARGED PLAN RM B-130A
AutoCAD SHX Text
AutoCAD SHX Text 1'
AutoCAD SHX Text 2'
AutoCAD SHX Text 4'
AutoCAD SHX Text 8'
AutoCAD SHX Text 1/4"=1'-0"
AutoCAD SHX Text
AutoCAD SHX Text
BUILDING 04 - ENLARGED PLAN RM C-146
AutoCAD SHX Text
AutoCAD SHX Text 1'
AutoCAD SHX Text 2'
AutoCAD SHX Text 4'
AutoCAD SHX Text 8'
AutoCAD SHX Text 1/4"=1'-0"
AutoCAD SHX Text
AutoCAD SHX Text
BUILDING 04 - ENLARGED RCP RM C-146
AutoCAD SHX Text
AutoCAD SHX Text 1'
AutoCAD SHX Text 2'
AutoCAD SHX Text 4'
AutoCAD SHX Text 8'
AutoCAD SHX Text 1/4"=1'-0"
AutoCAD SHX Text
AutoCAD SHX Text
BUILDING 04 - ENLARGED RCP RM B-130A
AutoCAD SHX Text N
AutoCAD SHX Text
KEY PLAN
mgonser Snapshot mgonser Snapshot mgonser Snapshot
ES
DC
TYP
TYP
MID
RX
CR/K
TYP
TYP
ES
DC
TYP
MID
RX CR/K
ICT - BUILDING 04 - LEVEL 2 -
ENLARGED PLANS
JG JG
TT-B04-421
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
K:
\C
C G
_P R
O
JE
C
TS
\2
1\
-1
T op ek a
EH
R M
C
1R
\4
- D es
D oc s\
2- D ra w in gs
\W O
R
KI
N G
\A ut oC
AD
\T T-
B0 4-
1.
dw g
3/
/2
:4 0:
A
M
ISSUE FOR BIDOffice of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
EHRM INFRASTRUCTURE
UPGRADES
COLMERY O'NEIL VA HEALTH CARE
21-116
Revisions: Date:
www. bancroft-ae.com
3300 Dundee RD.
Northbrook, IL 60062
T: 847.952.9362
35% SCHEMATIC DESIGN SUBMISSION 07-12-22
95% CONSTRUCTION DOCUMENTS SUBMISSION 10-31-23
100% CONSTRUCTION DOCUMENTS SUBMISSION
12/28/2023
12-19-23
Bancroft Project No: 21-116
35% SCHEMATIC DESIGN SUBMISSION R1 09-21-22
35% SUBMITTAL II 06-13-23
65% DESIGN DEVELOPMENT SUBMITTAL 09-12-23
ISSUED FOR BID 12-28-23
GENERAL NOTES
A. FOR GENERAL NOTES AND LEGENDS REFER TO SHEET TT001.
B. EXISTING IT/TR/OI&T ROOMS TO REMAIN ACTIVE DURING CONSTRUCTION. G.C. TO PROTECT EQUIPMENT
DURING CONSTRUCTION WITH VISQUEEN. CONTRACTOR TO ENSURE CONTINUOUS OPERATION OF
EQUIPMENT.
C. NOT ALL KEY NOTES APPLY TO ALL PLAN SHEETS. G.C. TO APPLY ONLY AS INDICATED PER EACH SHEET.
D. APPLY FIRE RATED SEALANT TO ALL EXISTING AND NEW PENETRATIONS IN EXISTING WALLS TO MAKE
EXISTING WALLS A 1 HR ASSEMBLY. BASIS OF DESIGN FOR 1 HR WALL IS UL 419 ASSEMBLY.
E. CONTRACTOR SHALL PROVIDE AND INSTALL FIRE RATED SLEEVES AS NECESSARY AND ASSEMBLED PER UL
DETAIL APPROPRIATE FOR WALL/FLOOR AND RACEWAY/CABLE TYPES.
F. TELECOMMUNICATION ROOM (TR) RACK MOUNTED PDU CORDSETS:
1. SHALL BE IEC 60320 C14-C15 DEVICE POWER CORDSETS, FUNCTIONALLY EQUIVALENT TO CISCO SYSTEMS
PART# CAB-C15-CBN.
2. SHALL BE RATED FOR: a. AT LEAST 250 VAC b.13 AMPS c.60HZ d.120 DEGREES C (248 DEGREES F)
3. UL LISTED
4. MAXIMUM OF 4 FEET IN LENGTH. SHORTER LENGTHS MAY BE USED TO REDUCE EXCESSIVE SLACK.
5. COUPLER TERMINATIONS ON CORDSET: a. IEC 60320 C14 PLUG CONNECTOR (RACK PDU END) b.IEC 60320 C15 PLUG (DEVICE END)
6. SELECTION OF DISTINCT CONTRASTING CORDSET COLORS TO INDICATE DIVERSE (A/B) POWER
DISTRIBUTION SOURCES.
a. BLACK AND GRAY RECOMMENDED.
7. QUANTITY:
a. PROVIDE ONE SET OF C14-C15 POWER CORDS PER DEVICE TO BE CONNECTED TO RACK
MOUNTED PDU’S.
i. ONE SET SHALL CONSIST OF TWO (2) POWER CORDS FOR CONNECTION TO
DIVERSE (A/B) POWER DISTRIBUTION SOURCES.
b. PROVIDE MINIMUM OF ONE SET OF C14-C15 POWER CORDS PER SET OF RACK MOUNTED PDU’S.
c. PROVIDE MINIMUM OF ONE SET OF C14-C15 POWER CORDS PER RACK INSTALLED IN EACH TR.
d. IN ADDITION OF QUANTITIES LISTED ABOVE, PROVIDE ONE SPARE SET OF C14-C15 POWER CORDS
PER TR.
FLOOR PLAN KEYNOTESX
FLOOR PLAN LEGEND
BACKBOARD PROVIDED AND INSTALLED BY OTHERS.
DEMO PLAN GENERAL NOTES
1. REMOVE EXISTING WALL MOUNTED SERVER RACK.
2. RELOCATE EXISTING UTILITY PIPING AS REQUIRED TO ACCOMMODATE NEW
SERVER RACK. COORDINATE FINAL LOCATIONS WITH VA/COR.
3. PROVIDE AND INSTALL VISQUEEN TYPE PLASTIC SHEET AND ZIPPER DOOR AS
REQUIRED TO MAINTAIN TYPE V INFECTION CONTROL PRECAUTIONS. EXTEND
AND SEAL TO ROOF DECK/STRUCTURE ABOVE.
4. SUPPLY AND INSTALL WALK OFF MATS.
5. PROTECT EXISTING FINISHES FROM DUST AND DAMAGE.
1. PROVIDE MIGHTY MO 20 RACK, OR-MM20730B (OR EQUIVALENT)
2. PROVIDE VERTICAL WIRE MANAGER, OR-MM20VMD706 (OR EQUIVALENT)
3. PROVIDE 4'X8' AC GRADE 3/4" TRADE SIZE FIRE RATED PLYWOOD BACKBOARD PAINTED HIGH GLOSS WHITE WITH
(2) COATS OF PAINT FOR SERVICE PROVIDER/SECURITY/VIDEO/ETC. AROUND PERIMETER WALLS OF TR"s AND ENTRANCE ROOMS AS SHOWN. ENSURE THAT FIRE RATING STAMP IS TO REMAIN UNCOVERED BY PAINT.
4. PROVIDE FIXED CAMERA WITH PASSIVE INFRARED(PIR) SUPPLEMENTAL LIGHTING ON TELECOM ROOM CORNER.
5. PROVIDE ACCESS CONTROL DEVICES ON SECURITY DOOR.
6. PROVIDE COPPER GROUNDING BUSBAR AT 5' AFF IN LOCATION SHOWN. SEE GROUNDING BAR DETAIL FOR
ADDITIONAL REQUIREMENTS.
7. BASKET STYLE CABLE TRAY MINIMUM 4"X18" SHALL BE USED. ALL TRAY MUST BE INSTALLED AT 7'8" AFF, SUPPORTED PER MANUFACTURER REQUIREMENTS, AND PROPERLY BONDED TO GROUND.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
ROOM B-230A
AutoCAD SHX Text
ROOM C-242A
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text N
AutoCAD SHX Text
AutoCAD SHX Text 1'
AutoCAD SHX Text 2'
AutoCAD SHX Text 4'
AutoCAD SHX Text 8'
AutoCAD SHX Text 1/4"=1'-0"
AutoCAD SHX Text
AutoCAD SHX Text
BUILDING 04 - ENLARGED PLAN RM B-230A
AutoCAD SHX Text
AutoCAD SHX Text 1'
AutoCAD SHX Text 2'
AutoCAD SHX Text 4'
AutoCAD SHX Text 8'
AutoCAD SHX Text 1/4"=1'-0"
AutoCAD SHX Text
AutoCAD SHX Text
BUILDING 04 - ENLARGED PLAN RM C-242A
AutoCAD SHX Text
AutoCAD SHX Text 1'
AutoCAD SHX Text 2'
AutoCAD SHX Text 4'
AutoCAD SHX Text 8'
AutoCAD SHX Text 1/4"=1'-0"
AutoCAD SHX Text
AutoCAD SHX Text
BUILDING 04 - ENLARGED RCP RM B-230A
AutoCAD SHX Text
AutoCAD SHX Text 1'
AutoCAD SHX Text 2'
AutoCAD SHX Text 4'
AutoCAD SHX Text 8'
AutoCAD SHX Text 1/4"=1'-0"
AutoCAD SHX Text
AutoCAD SHX Text
BUILDING 04 - ENLARGED RCP RM C-242A
AutoCAD SHX Text
KEY PLAN
mgonser Snapshot mgonser Snapshot mgonser Snapshot
DN
UP
A0-C1 C0-C2B0-C3
A8
A6F
A6
A5
A2E A1E B3F B3A
B3E
C9D C9H
C10F
C11E
C11
C9B
C9AC9
B2E
B3B
C10
C12C12C
A9
A1A
A1 B2
C9G
B3
C12B
A13B
A13 C11A
DF
EEWS
EL-1
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
K:
\C
C G
_P R
O
JE
C
TS
\2
1\
-1
T op ek a
EH
R M
C
1R
\4
- D es
D oc s\
2- D ra w in gs
\W O
R
KI
N G
\A ut oC
AD
\T T-
B0 5-
0.
dw g
1/
/2
2:
:0
PM
ISSUE FOR BIDOffice of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
EHRM INFRASTRUCTURE
UPGRADES
COLMERY O'NEIL VA HEALTH CARE
21-116
Revisions: Date:
www. bancroft-ae.com
3300 Dundee RD.
Northbrook, IL 60062
T: 847.952.9362
35% SCHEMATIC DESIGN SUBMISSION 07-12-22
95% CONSTRUCTION DOCUMENTS SUBMISSION 10-31-23
100% CONSTRUCTION DOCUMENTS SUBMISSION
12/28/2023
12-19-23
Bancroft Project No: 21-116
35% SCHEMATIC DESIGN SUBMISSION R1 09-21-22
35% SUBMITTAL II 06-13-23
65% DESIGN DEVELOPMENT SUBMITTAL 09-12-23
ISSUED FOR BID 12-28-23
ICT - BUILDING 05 - BASEMENT LEVEL
CABLE TRAY PLAN
JG JG
TT-B05-100
GENERAL NOTES
A. FOR GENERAL NOTES AND LEGENDS REFER TO SHEET TT001.
B. EXISTING IT/TR/OI&T ROOMS TO REMAIN ACTIVE DURING CONSTRUCTION. G.C. TO PROTECT EQUIPMENT
DURING CONSTRUCTION WITH VISQUEEN. CONTRACTOR TO ENSURE CONTINUOUS OPERATION OF EQUIPMENT.
C. NOT ALL KEY NOTES APPLY TO ALL PLAN SHEETS. G.C. TO APPLY ONLY AS INDICATED PER EACH SHEET.
D. APPLY FIRE RATED SEALANT TO ALL EXISTING AND NEW PENETRATIONS IN EXISTING WALLS TO MAKE
EXISTING WALLS A 1 HR ASSEMBLY. BASIS OF DESIGN FOR 1 HR WALL IS UL 419 ASSEMBLY.
E. CONTRACTOR SHALL PROVIDE AND INSTALL FIRE RATED SLEEVES AS NECESSARY AND ASSEMBLED PER UL
DETAIL APPROPRIATE FOR WALL/FLOOR AND RACEWAY/CABLE TYPES
FLOOR PLAN KEYNOTESX
FLOOR PLAN LEGEND
BASKET CABLE TRAY.
1. PROVIDE BASKET TYPE CABLE TRAY TO SUPPORT OPTICAL FIBER BACKBONE AND NEW CAT 6A HORIZONTAL CABLING. CABLE TRAY TO BE SIZED AS PER CABLE TRAY CAPACITY PLANNING ON FLOOR PLAN LEGEND, ASSUMING 40% FILL AND 25% SPARE CAPACITY. ROUTING SHOWN INDICATES PRIMARY PATHWAYS. IN ADDITION TO PRIMARY PATHWAYS, CABLE TRAY SHALL BE PROVIDED WHEN CABLE BUNDLES EXCEED 24 CABLES. FIRE RATED MECHANICAL SLEEVE ASSEMBLIES SHALL BE PROVIDED WHEN PASSING THROUGH FIRE
RATED PARTITIONS. ASSUMING 40% FILL AND 50% SPARE CAPACITY.
CAT. NO
CF105/300
CF105/450
CF105/500
CF105/600
CF150/150
CF150/200
CF150/300
CF150/450
CF150/500
CF150/600
CF150/900
DEPTH
(IN)
WIDTH
(IN)
CAT 6A 4 PAIR
PLENUM (0.35")
- CABLE TRAY CAPACITY PLANNING.
- PROPOSED CABLE TRAY:
CABLOFIL 4" DEEP X 12" WIDE MINIMUM
(SIZE COMMENSURATE WITH DISTRIBUTION
REQUIREMENT) WHITE POWERCOAT TRAY INSERT.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
NORTH
AutoCAD SHX Text
KEY PLAN
AutoCAD SHX Text N
AutoCAD SHX Text
AutoCAD SHX Text 4'
AutoCAD SHX Text 8'
AutoCAD SHX Text 16'
AutoCAD SHX Text 32'
AutoCAD SHX Text 1/16"=1'-0"
AutoCAD SHX Text
AutoCAD SHX Text
BUILDING 5 - BASEMENT LEVEL CABLE TRAY PLAN
mgonser Snapshot mgonser Snapshot mgonser Snapshot
UP
A0-C1 C0-C2B0-C3
A8
A6F
A6
A5
A2E A1E B3F B3A
B3E
C9D C9H
C10F
C11E
C11
C9B
C9AC9
B2E
B3B
C10
C12C12C
A9
A1A
A1 B2
C9G
B3
C12B
A13B
A13 C11A
DF
EEWS
EL-1
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
K:
\C
C G
_P R
O
JE
C
TS
\2
1\
-1
T op ek a
EH
R M
C
1R
\4
- D es
D oc s\
2- D ra w in gs
\W O
R
KI
N G
\A ut oC
AD
\T T-
B0 5-
0R
P.
dw g 3/
/2
7:
:3
PM
ISSUE FOR BIDOffice of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
EHRM INFRASTRUCTURE
UPGRADES
COLMERY O'NEIL VA HEALTH CARE
21-116
Revisions: Date:
www. bancroft-ae.com
3300 Dundee RD.
Northbrook, IL 60062
T: 847.952.9362
35% SCHEMATIC DESIGN SUBMISSION 07-12-22
95% CONSTRUCTION DOCUMENTS SUBMISSION 10-31-23
100% CONSTRUCTION DOCUMENTS SUBMISSION
12/28/2023
12-19-23
Bancroft Project No: 21-116
35% SCHEMATIC DESIGN SUBMISSION R1 09-21-22
35% SUBMITTAL II 06-13-23
65% DESIGN DEVELOPMENT SUBMITTAL 09-12-23
ISSUED FOR BID 12-28-23
ICT - BUILDING 05 - BASEMENT LEVEL
ROUTING PLAN
JG JG
TT-B05-100RP
GENERAL NOTES
A. FOR GENERAL NOTES AND LEGENDS REFER TO SHEET TT001.
B. EXISTING IT/TR/OI&T ROOMS TO REMAIN ACTIVE DURING CONSTRUCTION. G.C. TO PROTECT EQUIPMENT
DURING CONSTRUCTION WITH VISQUEEN. CONTRACTOR TO ENSURE CONTINUOUS OPERATION OF EQUIPMENT.
C. NOT ALL KEY NOTES APPLY TO ALL PLAN SHEETS. G.C. TO APPLY ONLY AS INDICATED PER EACH SHEET.
D. APPLY FIRE RATED SEALANT TO ALL EXISTING AND NEW PENETRATIONS IN EXISTING WALLS TO MAKE
EXISTING WALLS A 1 HR ASSEMBLY. BASIS OF DESIGN FOR 1 HR WALL IS UL 419 ASSEMBLY.
E. CONTRACTOR SHALL PROVIDE AND INSTALL FIRE RATED SLEEVES AS NECESSARY AND ASSEMBLED PER UL
DETAIL APPROPRIATE FOR WALL/FLOOR AND RACEWAY/CABLE TYPES
FLOOR PLAN KEYNOTESX
1. PROVIDE SLEEVES, CONDUITS OR MECHANICAL FIRE-PROOF
ASSEMBLIES AS REQUIRED THROUGH WALL OR FLOORS AS REQUIRED
TO MAINTAIN EXISTING RATING. REFER TO ONE-LINE CABLE RISER
DIAGRAMS FOR CABLE QUANTITY AND TYPE. CONTRACTOR SHALL SIZE
PATHWAYS TO ACCOMMODATE DAY ONE CABLING PLUS 40 PERCENT
SPARE CAPACITY.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
ROUTE 'B' TO TR 'A160' ON LEVEL 1 ABOVE
AutoCAD SHX Text
TR 'A160' ABOVE (STACKED)
AutoCAD SHX Text
ROUTE 'A' FROM TR 'A160' ON LEVEL 1 ABOVE
AutoCAD SHX Text ROUTE 'A' FROM STEAM TUNNEL. EXACT LOCATION OF ENTRANCE FROM STEAM TUNNEL TO BE FIELD COORDINATED.
AutoCAD SHX Text
NORTH
AutoCAD SHX Text
KEY PLAN
AutoCAD SHX Text N
AutoCAD SHX Text
AutoCAD SHX Text 4'
AutoCAD SHX Text 8'
AutoCAD SHX Text 16'
AutoCAD SHX Text 32'
AutoCAD SHX Text 1/16"=1'-0"
AutoCAD SHX Text
AutoCAD SHX Text
BUILDING 5 - BASEMENT LEVEL ROUTING PLAN
mgonser Snapshot mgonser Snapshot mgonser Snapshot
DN
DN DNUPUP
UP
A1-C1
A101A
A101
A101C
A101B
A130
A130A A130B
A131
A129 A132 A128F
A128 A127
A102E A101E
A1
A134
C142B120
B103 B104B106
B126AB114C
B117
B113B114B114A
B114B B114D
B115 B1
B111 B110
B119
B108
B109
B126
B105 B102
B125
B124
B123C
B123B
B122
B123A
B123D
B120F
B1-C1
A135 C136
C159
C136B
C156 C157
C154
C153
C145C143 C147E
C147 C148B
C148C
C148A C148
C148D C150
C140A
C139C
C1-C3
C141F
C138 C140
C137 C141
C139
C139A C139B
C150P
C151
C1
C150E
B1
P
C155A
C155
B123
B107A
B107
B126B
B112 C158
C136A
B111E
C144
C149
A130P
C1-C1
C157A
EL-1
B126B
A160
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
K:
\C
C G
_P R
O
JE
C
TS
\2
1\
-1
T op ek a
EH
R M
C
1R
\4
- D es
D oc s\
2- D ra w in gs
\W O
R
KI
N G
\A ut oC
AD
\T T-
B0 5-
1.
dw g
1/
/2
2:
:0
PM
ISSUE FOR BIDOffice of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
EHRM INFRASTRUCTURE
UPGRADES
COLMERY O'NEIL VA HEALTH CARE
21-116
Revisions: Date:
www. bancroft-ae.com
3300 Dundee RD.
Northbrook, IL 60062
T: 847.952.9362
35% SCHEMATIC DESIGN SUBMISSION 07-12-22
95% CONSTRUCTION DOCUMENTS SUBMISSION 10-31-23
100% CONSTRUCTION DOCUMENTS SUBMISSION
12/28/2023
12-19-23
Bancroft Project No: 21-116
35% SCHEMATIC DESIGN SUBMISSION R1 09-21-22
35% SUBMITTAL II 06-13-23
65% DESIGN DEVELOPMENT SUBMITTAL 09-12-23
ISSUED FOR BID 12-28-23
ICT - BUILDING 5 - LEVEL 1 CABLE TRAY
PLAN
JG JG
TT-B05-101
GENERAL NOTES
A. FOR GENERAL NOTES AND LEGENDS REFER TO SHEET TT001.
B. EXISTING IT/TR/OI&T ROOMS TO REMAIN ACTIVE DURING CONSTRUCTION. G.C. TO PROTECT EQUIPMENT
DURING CONSTRUCTION WITH VISQUEEN. CONTRACTOR TO ENSURE CONTINUOUS OPERATION OF EQUIPMENT.
C. NOT ALL KEY NOTES APPLY TO ALL PLAN SHEETS. G.C. TO APPLY ONLY AS INDICATED PER EACH SHEET.
D. APPLY FIRE RATED SEALANT TO ALL EXISTING AND NEW PENETRATIONS IN EXISTING WALLS TO MAKE
EXISTING WALLS A 1 HR ASSEMBLY. BASIS OF DESIGN FOR 1 HR WALL IS UL 419 ASSEMBLY.
E. CONTRACTOR SHALL PROVIDE AND INSTALL FIRE RATED SLEEVES AS NECESSARY AND ASSEMBLED PER UL
DETAIL APPROPRIATE FOR WALL/FLOOR AND RACEWAY/CABLE TYPES
FLOOR PLAN KEYNOTESX
FLOOR PLAN LEGEND
BASKET CABLE TRAY.
1. PROVIDE BASKET TYPE CABLE TRAY TO SUPPORT OPTICAL FIBER BACKBONE AND NEW CAT 6A HORIZONTAL CABLING. CABLE TRAY TO BE SIZED AS PER CABLE TRAY CAPACITY PLANNING ON FLOOR PLAN LEGEND, ASSUMING 40% FILL AND 25% SPARE CAPACITY. ROUTING SHOWN INDICATES PRIMARY PATHWAYS. IN ADDITION TO PRIMARY PATHWAYS, CABLE TRAY SHALL BE PROVIDED WHEN CABLE BUNDLES EXCEED 24 CABLES. FIRE RATED MECHANICAL SLEEVE ASSEMBLIES SHALL BE PROVIDED WHEN PASSING THROUGH FIRE
RATED PARTITIONS.