Pages from Addendum1_Vol2_1of2__20241209.pdf

PDF 12 MB Posted

Attached to
Y1DA--589A5-21-700 EHRM INFRASTRUCTURE UPGRADES (VA-24-00076324) Topeka, KS
Solicitation number
36C77624B0026_1
Issued by

About this file

These are architectural drawings showing cable tray plans and electrical infrastructure upgrades for the VA Medical Center in Topeka, KS. The drawings detail telecommunications/IT infrastructure installations across multiple buildings (Buildings 1-5) and floor levels, including basement, first, second and third floors where applicable. The plans show basket cable tray routing, mechanical fire sleeve locations, and telecommunications room locations with specific requirements for CAT 6A cabling infrastructure.

The drawings include detailed capacity planning charts for cable tray sizing based on CAT 6A cable quantities, with specifications for 20% initial fill and 20% spare capacity (50% future capacity). Key requirements include basket type cable trays with minimum 4" depth x 12" width, fire-rated mechanical sleeve assemblies at partition penetrations, and maintaining maximum 295-foot cabling distances. The plans incorporate both normal and emergency power distribution, with separate conduit requirements for UPS power (on emergency critical branch) versus equipment power for cooling systems (on equipment branch). Detailed general notes address requirements for protecting existing equipment, coordinating with VA IT prior to work in data centers, and maintaining continuous operation of existing systems.

View the file

Other files

File Type Posted
36C77624B0026 0007.docx DOCX document
36C77624B0026 0006.docx DOCX document
Government Answers to Contractor questions.docx DOCX document
Add Spec Section 23 21 13 Attachment A.pdf PDF
Revised Vol3 Drawing_M503.pdf PDF
Revised Spec Section 23 21 13.pdf PDF
36C77624B0026 0005.docx DOCX document
Pages from Addendum1_Vol2_2of2__20241209.pdf PDF
Colmery-ONeil VA Medical Center - Asbestos and Lead Survey Report signed.pdf PDF
Submittal 024 Pipe - Valve- Fittings 8-8-17.pdf PDF
589A5-21-700_TOPEKA_EHRM_SURVEY LOCATIONS-Markup.pdf PDF
EHRM Contractor Parking and Laydown.pdf PDF
Addendum1_Specifications_20241209.pdf PDF
Addendum1_Vol3_2of3_20241209.pdf PDF
230415-000 Topeka VA Geotech Final Report_S.pdf PDF
Addendum1_Vol3_1of3_20241209.pdf PDF
Addendum1_Vol3_3of3_20241209.pdf PDF
36C77624B0026 0004.docx DOCX document
589A5-21-700_Topeka KS_EHRM_Tech Q1_20241210.docx DOCX document
589A5-21-700_Topeka EHRM_IFB_BOD_Blast.pdf PDF
589A5-21-700_19550421_Steam Distro Plot Plan.pdf PDF
Submittal 023B Perma Pipe Fittings 8-21-17.pdf PDF
589A5-21-700_Topeka KS_EHRM_Tech Q2_20241210.docx DOCX document
Addendum1_Vol1_20241209.pdf PDF
36C77624B0026 0003.docx DOCX document
36C77624B0026 0002.docx DOCX document
S04_Site Visit Sign-in Sheet_Topeka KS.pdf PDF
S06- 36C77624B0026 0001.docx DOCX document
Attachment 1 - 589A5-21-700_Topeka EHRM__SOWV3.docx DOCX document
Attachment 16 - 589A5-21-700_Topeka EHRM_IFB R2 Drawings_Vol 3_1.pdf PDF
Attachment 15 - 589A5-21-700_Topeka EHRM_IFB R2 Drawings_Vol 2-8.pdf PDF
Attachment 10 -589A5-21-700_Topeka EHRM_IFB R2 Drawings_Vol 91-129.pdf PDF
Attachment 3 - DB Wage Determination Topeka-KS.pdf PDF
Attachment 8 -589A5-21-700_Topeka EHRM_IFB R2 Drawings_Vol 3_1-90.pdf PDF
Attachment 4 -589A5-21-700_Topeka EHRM_IFB R2 Drawings_Vol 2_118-180.pdf PDF
Attachment 11 -589A5-21-700_Topeka EHRM_IFBR2_Spec-VOL1_032224.pdf PDF
Attachment 5 -589A5-21-700_Topeka EHRM_IFB R2 Drawings_Vol 2_181-240.pdf PDF
Attachment 14 - 589A5-21-700_Topeka EHRM_IFB R2 Drawings_Vol 1_134-204.pdf PDF
Attachment 13 - 589A5-21-700_Topeka EHRM_IFB R2 Drawings_Vol 1_1-18.pdf PDF
Attachment 9 -589A5-21-700_Topeka EHRM_IFB R2 Drawings_Vol 3-2.pdf PDF
Attachment 12 -589A5-21-700_Topeka EHRM_IFBR2_Spec-VOL2_032224.pdf PDF
Attachment 20 -Site Visit Instructions.docx DOCX document
Attachment 19 -589A5-21-700_Topeka EHRM_IFB R2 Drawings_Vol 2_111-117.pdf PDF
Attachment 6 -589A5-21-700_Topeka EHRM_IFB R2 Drawings_Vol 2_241-281.pdf PDF
Attachment 18 -589A5-21-700_Topeka EHRM_IFB R2 Drawings_Vol 2_1-110.pdf PDF
36C77624B0026_1.docx DOCX document
Attachment 2- Limitations on Subcontracting - Construction.docx DOCX document
Attachment 7 -589A5-21-700_Topeka EHRM_IFB R2 Drawings_Vol 2-7.pdf PDF
Attachment 17 -589A5-21-700_Topeka EHRM_IFB R2 Drawings_Vol 1_19-133.pdf PDF
Show all 49

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

GENERAL - DRAWING INDEX (VOLUME 2

OF 3)

DA JM

G-003

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

K:

\C

C G

_P R

O

JE

C

TS

\2

1\

-1

T op ek a

EH

R M

C

1R

\4

- D es

D oc s\

2- D ra w in gs

\W O

R

KI

N G

\A ut oC

AD

\G

3-

VO

L2 .d w g

3/

/2

5:

:0

PM

ISSUE FOR BIDOffice of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

EHRM INFRASTRUCTURE

UPGRADES

COLMERY O'NEIL VA HEALTH CARE

21-116

Revisions: Date:

www. bancroft-ae.com

3300 Dundee RD.

Northbrook, IL 60062

T: 847.952.9362

03/22/2024Bancroft Project No: 21-116ISSUE FOR BID R2 03-22-24

ADDENDUM #1 11-15-24

OS

TO NORMAL PNL

TO EM PNL

OS

TO NORMAL PNL

TO EM PNL

OS4

TO EM PNL

TO NORMAL PNL

A/C

TO PNL

TO NORMAL PNL

TO EM PNL

2 3 2 3

CORRIDOR

A/C

TO PNL TO EM PNL

2 3

TO NORMAL PNL

A/C

TO PNL

TO EM PNL

TO NORMAL PNL

3 OS

TO NORMAL PNL

TO EM PNL

A/C

TO PNL

TO EM PNL

TO NORMAL PNL

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

K:

\C

C G

_P R

O

JE

C

TS

\2

1\

-1

T op ek a

EH

R M

C

1R

\4

- D es

D oc s\

2- D ra w in gs

\W O

R

KI

N G

\A ut oC

AD

\E le ct ric al \E

3.

dw g

/2

0/

:1 0:

A

M

ISSUE FOR BIDOffice of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

EHRM INFRASTRUCTURE

UPGRADES

COLMERY O'NEIL VA HEALTH CARE

21-116

Revisions: Date:

www. bancroft-ae.com

3300 Dundee RD.

Northbrook, IL 60062

T: 847.952.9362

03/22/2024Bancroft Project No: 21-116ISSUE FOR BID R2 03-22-24

GENERAL NOTES ELECTRICAL DEMOLITION:

A. NEW TR ROOMS SHALL BE PREPARED SUCH THAT WHEN COMPLETED, ONLY CIRCUITRY SHOWN

ON DRAWING E003 REMAINS. ALL PREVIOUS CIRCUITRY SHALL BE REMOVED BACK TO SOURCES.

B. REMOVE AVERAGE OF TWO LIGHTING FIXTURES, CONDUIT AND SWITCH(ES) BACK TO BRANCH

PANEL, AND PROPERLY DISPOSE OF FIXTURES, BALLASTS, AND ALL HARDWARE, FROM NEW TR

ROOM AREA.

C. REMOVE AVERAGE OF THREE RECEPTACLES (EMERGENCY AND NORMAL POWER) AND CONDUIT

BACK TO BRANCH PANEL, FROM TR ROOM AREA.

D. CERTIFIED FIRE PROTECTION CONTRACTOR TO REMOVE FIRE ALARM / FIRE DETECTION

COMPONENT FROM NEW TR ROOM AREA. THIS IS NOTED ON SPECIFIC DRAWINGS.

E. CERTIFIED FIRE PROTECTION CONTRACTOR TO DOCUMENT LOCATIONS OF FIRE ALARM / FIRE

DETECTION COMPONENTS REMOVED OR RELOCATED TO THEN UPDATE THE FIRE ALARM / FIRE

DETECTION ALARM SOFTWARE. SOME FIRE ALARM / FIRE DETECTION COMPONENTS REMAIN

BUT ARE RELOCATED. NO NEW FIRE ALARM / FIRE DETECTION ARE INSTALLED AS PART OF THE

EHRM PROJECT.

GENERAL NOTES ELECTRICAL:

A. CONTACT VA IT PRIOR TO WORKING IN DATA CENTER OR IT CLOSET.

B. USE PRECAUTIONS TO AVOID SNAGGING WIRING OR DAMAGING EQUIPMENT.

C. PROTECT IT EQUIPMENT FROM DUST, DURING WORK THAT CREATES DUST.

D. A WIRING MATRIX IS SHOWN FOR EVERY NEW TR ROOM. BREAKER SIZES ARE LISTED FOR UPS

AND OTHER EHRM ROOM EQUIPMENT. UTILIZE 20A CIRCUIT BREAKERS FOR ROOM LIGHTS AND

WALL RECEPTACLES (SIZES ARE NOT SHOWN ON DRAWINGS).

TR ROOM SPECIFIC NOTES:

A. RECEPTACLES TO POWER RACKS SHALL ALWAYS BE ABOVE RACKS.

B. POWER TO ONE, TWO, OR THREE RACKS AS SHOWN ON THIS DRAWING.

C. POWER FOR FOUR RACKS IS A COMBINATION OF THREE RACK AND ONE RACK DETAILS.

E. POWER FOR SIX RACKS IS A COMBINATION OF TWO THREE RACK DETAILS.

F. INSTALL LIGHTING CONTROLS PER nlight LIGHTING DETAIL ON DETAIL DRAWING .

G. NOTE THAT ONLY FAN COIL POWER IS REQUIRED IN BUILDINGS WITH CHILLED WATER.

H. BUILDINGS THAT DO NOT HAVE CHILLED WATER NEED POWER TO FAN COIL (EVAPORATOR) AND

ALSO POWER TO THE OUTDOOR CONDENSERS. SEE SUGGESTED WIRING DETAIL ON DRAWING

E-501. IF SELECTED VENDOR WIRING DETAIL IS DIFFERENT FOLLOW THE VENDOR'S WIRING

DETAIL.

I. SOME VENDOR'S EVAPORATOR UNITS DO NOT PROVIDE POWER TO THE SMALL CONDENSATE

PUMP. FOR THESE SITUATIONS INSTALL A 15A 1-POLE DISCONNECT FROM THE ROOM EM

LIGHTING CIRCUIT.

1. ONLY BRANCH CIRCUIT SHOWN FROM POWER PANEL TO COOLING UNIT, ELECTRICAL

CONTRACTOR TO WORK WITH MECHANICAL CONTRACTOR TO ROUTE POWER AND TUBING

TO OUTDOOR UNIT.

2. NORMAL POWER TO ROOM RECEPTACLES, AND LIGHTS, AND RACKS. CONTACT COR PRIOR

TO INSTALLING LIGHTING TO DETERMINE OPTIMUM LOCATION FOR LIGHT FIXTURES.

3. EMERGENCY POWER TO ROOM RECEPTACLES, AND LIGHTS, AND RACKS. CONTACT COR

PRIOR TO INSTALLING LIGHTING TO DETERMINE OPTIMUM LOCATION FOR LIGHT FIXTURES.

4. OCCUPANCY SENSOR - HIGH MOUNT.

ELECTRICAL - TR ROOMS LIGHTING

AND POWER EXAMPLE

WG BX E-003

ADDENDUM #1 11-20-24

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text

AutoCAD SHX Text 1'

AutoCAD SHX Text 2'

AutoCAD SHX Text 4'

AutoCAD SHX Text 8'

AutoCAD SHX Text 1/4"=1'-0"

AutoCAD SHX Text

AutoCAD SHX Text

EXAMPLE - LIGHTING PLAN FOR FOUR RACK ROOM

AutoCAD SHX Text

AutoCAD SHX Text 1'

AutoCAD SHX Text 2'

AutoCAD SHX Text 4'

AutoCAD SHX Text 8'

AutoCAD SHX Text 1/4"=1'-0"

AutoCAD SHX Text

AutoCAD SHX Text

EXAMPLE - POWER PLAN FOR FOUR RACK ROOM

AutoCAD SHX Text

AutoCAD SHX Text 1'

AutoCAD SHX Text 2'

AutoCAD SHX Text 4'

AutoCAD SHX Text 8'

AutoCAD SHX Text 1/4"=1'-0"

AutoCAD SHX Text

AutoCAD SHX Text

EXAMPLE - LIGHTING PLAN FOR TWO RACK ROOM

AutoCAD SHX Text

AutoCAD SHX Text 1'

AutoCAD SHX Text 2'

AutoCAD SHX Text 4'

AutoCAD SHX Text 8'

AutoCAD SHX Text 1/4"=1'-0"

AutoCAD SHX Text

AutoCAD SHX Text

EXAMPLE - POWER PLAN FOR TWO RACK ROOM

AutoCAD SHX Text

AutoCAD SHX Text 1'

AutoCAD SHX Text 2'

AutoCAD SHX Text 4'

AutoCAD SHX Text 8'

AutoCAD SHX Text 1/4"=1'-0"

AutoCAD SHX Text

AutoCAD SHX Text

EXAMPLE - LIGHTING PLAN FOR THREE RACK ROOM

AutoCAD SHX Text

AutoCAD SHX Text 1'

AutoCAD SHX Text 2'

AutoCAD SHX Text 4'

AutoCAD SHX Text 8'

AutoCAD SHX Text 1/4"=1'-0"

AutoCAD SHX Text

AutoCAD SHX Text

EXAMPLE - POWER PLAN FOR THREE RACK ROOM

AutoCAD SHX Text

AutoCAD SHX Text 1'

AutoCAD SHX Text 2'

AutoCAD SHX Text 4'

AutoCAD SHX Text 8'

AutoCAD SHX Text 1/4"=1'-0"

AutoCAD SHX Text

AutoCAD SHX Text

EXAMPLE - LIGHTING PLAN FOR ONE RACK ROOM

AutoCAD SHX Text

AutoCAD SHX Text 1'

AutoCAD SHX Text 2'

AutoCAD SHX Text 4'

AutoCAD SHX Text 8'

AutoCAD SHX Text 1/4"=1'-0"

AutoCAD SHX Text

AutoCAD SHX Text

EXAMPLE - POWER PLAN FOR ONE RACK ROOM

AutoCAD SHX Text

ELECTRICAL GENERAL NOTES

AutoCAD SHX Text

ELECTRICAL KEY NOTES

AutoCAD SHX Text

UP

UP

UP

UP

UP

UP

UP

UP

UP

UP

UP

UP

DN

A

B

C

D

E

F

1 3 4 5 11 13 16 18 19 21 23 25 26 27 286 8 9

11.1

14 15 17

K

L

M

29 30

G

O

Q

S

T

U

V

P

S.2

S.1

Q.1

U.1

V.1

V.2

W.1

X

Y

8.26.36.2 10.19.3 12.111.23.8

Z.4

4.7 6.1 8.1 11.7

Z.3

Z.2

24 31 32

N

7 222010 12

18B 20B 22B 24B 24C

H

I

J

R

W

Z.1

22D

UPUP

UP

B23

B23G

B23A B23B

B23E B23D B23C

C03A

A9E

A9C A9D

B5

C3

A17

A12

A30

A21

A21E

A21A

A13A A13B

A1

A10F

A3B

A3

A3A

A13

A20E

A20

A17F

C7

C7B

C4EC3EC3F

A19D

C7A

C7G

C7C

C7D

A19

C5

C7H

C7I

C6A19B

C1A18

A18A C2

A17A

A5

B1E

A7A8A9

A10E

A10

A4

A7E

A9A

A11

A14

A15

B4

B3

B13E

B22

B14A

B14

A2

A2A

A2B

A2C A2D

A19DC0-1

C8A

C20

C23

C24 C25

C28

C27

C26

C22 C21

C18C19

C17

C8

C9

C12

C14

C8B

C10 C11

C13

C15 C14A

C14B C14C

C16 C16A

C04

A16D

B2 B2B

B2A

B15B16 B17

B1

A16

A16C

A16A

A16E A16B

B22E

B1B

C0-2

C1A

B21

A19C

B1C

B6C

A16G

A9B

B43M B42

B42A B39

B38

C0-5B

C0-5A

C0-3

A9C

C114C

C11A

CB-8

B6D

A0-E3

A0-E1

A0-E2

A0-E4

B42B

B41

B40

B6P

B6 B8A

B7

B13CB13

B12

B9

B10

B11

B11A

B6M

B7M

B8 C0-3E

C0-3C

C0-3B B8C

B13B

B13A

A10G

A10B

A10A

A10C A10D

B20

B23F

C20A A19A

1/A-01-100.2

1/A-01-100.3

1/A-01-100.1

1/A-01-100.3

1/A -01

-10 0.2

1/A -01

-10 0.1

1/A-01-100.3

1/A-01-100.4

1/A-01-100.3

1/A-01-100.4

1/A-01-100.3

1/A-01-100.5

1/A -01

-10 0.5

1/A -01

-10 0.4

A7E

A14

A20E

B13E

B22E

C3E C4E

BD BA

-2

BA

BA

-1

EM BC

-1

BB-1

LS-BB

BB-2

MP1-B

PP1-B

ELS1-B

ECR1-B

EE1-B

C20A

B3

SECURITY PANEL

ECB-SURGERY

ATS-RADIOLOGY

DPEM

B C T

EDS

CBDP

ELEVATOR DP

ECB-2

EBTR

EBDP-1

LSDP

1200A

ATS-CBTJ-1

0 K

VA

0/2

V

EBDP-2

400A UPSTS ATS

LSTS-1 400A DISC

BP

UPSTS

400A DISCEDP

PU

LL

BO

X

ME

TE

R

AT

S

FIR

E P

UM

P

DIS

C B

LD

G 5

30 KVA

208/120V

EM-TELECOM

CBDP-2, EM

A2 EB

TS

-2

TRANSFER SWITCHTR

EM-ATS C-2

LS&C-ATS C-1

SW

ITC

HB

OA

RD

DP

1-B

AT

S

TR

0 M

CM

EM PNL, ES-1

EM PNL, ES-1A

BC

BOX

A19A

1-B-E-EHRM

1-B-N-EHRM

NORMAL CONDUIT # 1, 2, 3, 4, 5

EM CONDUIT # 1, 2, 3, 4, 5

NORMAL CONDUIT # 1, 2, 3, 4, 5

NORMAL CONDUIT # 6, UP

NORMAL CONDUIT # 7

EM CONDUIT # 7

EMERGENCY CONDUIT # 6, UP

ELECTRICAL - BUILDING 1 - BASEMENT

LEVEL PLAN

WG BX

EP-B01-100

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

K:

\C

C G

_P R

O

JE

C

TS

\2

1\

-1

T op ek a

EH

R M

C

1R

\4

- D es

D oc s\

2- D ra w in gs

\W O

R

KI

N G

\A ut oC

AD

\E le ct ric al \E

P- B0

1-

0.

dw g

/2 0/

0:

:3

AM

ISSUE FOR BIDOffice of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

EHRM INFRASTRUCTURE

UPGRADES

COLMERY O'NEIL VA HEALTH CARE

21-116

Revisions: Date:

www. bancroft-ae.com

3300 Dundee RD.

Northbrook, IL 60062

T: 847.952.9362

03/22/2024Bancroft Project No: 21-116ISSUE FOR BID R2 03-22-24

A. THIS PROJECT ALSO INVOLVES RESOLVING ELECTRICAL DEFICIENCIES. THIS WORK IS SHOWN ON

SEPARATE DRAWINGS FROM TR ROOM DRAWINGS.

B. EACH TR ROOM INVOLVES THREE TYPES OF WIRING:

a. POWER TO RACKS, SEE DRAWINGS E-003 AND E-004 FOR DETAILS.

b. POWER TO RECEPTACLES AND LIGHTING SHOWN FOR EACH TR ROOM.

c. POWER TOFAN COIL UNITS AND SPLIT COOLERS SEE DRAWING DETAIL E-501.

C. CONTRACTOR TO DETERMINE DETAILED CONDUIT ROUTING BASED ON FIELD CONDITIONS.

D. CONDUIT ON PLAN DRAWINGS IS SHOWN FOR GENERAL ROUTING PURPOSES ONLY. SEE WIRING

AND PANEL DRAWINGS FOR WIRING AND CONDUIT SIZES.

E. WHEN WALLS ARE DEMOLITIONED THAT CONTAIN RECEPTACLES FEEDING EQUIPMENT,

CONTRACTOR TO RELOCATE RECEPTACLES TO REMAINING WALL TO CONTINUE POWERING

REMAINING EQUIPMENT. IF NO CONNECTED EQUIPMENT REMAINS CONNECTED TO

DEMOLITIONED WALLS, CONTRACTOR TO REMOVE THE WIRING AND CONDUIT BACK TO THE

SOURCE.

F. UPS POWER IS ON THE EMERGENCY CRITICAL BRANCH AND MUST BE IN SEPARATE CONDUITS

FROM NORMAL POWER.

G. EQUIPMENT POWER TO TECHNOLOGY ROOM FANS AND CONDENSERS IS FROM EQUIPMENT

BRANCH OF EMERGENCY POWER AND MUST BE IN CONDUITS SEPARATE FROM NORMAL POWER.

CONDUITS FROM TR ROOMS TO OUTDOOR CONDENSERS WILL USE SAME ROUTING AND

SUPPORTS AS CONDENSER REFRIGERANT TUBING.

H. CONTACT VA IT PRIOR TO WORKING IN IT CLOSET.

I. FOLLOW VA & NFPA 70E LOCK OUT TAG OUT PROCEDURES FOR SAFETY.

J. SEE THE ELECTRICAL EQUIPMENT SCHEDULE FOR EQUIPMENT DETAILS.

K. SEE PANEL SCHEDULES ON DRAWING SERIES E600 FOR PANEL SCHEDULES AND CIRCUIT

NUMBERS.

L. SEE DRAWING SERIES E700 FOR SINGLE LINE DRAWINGS.

M. UPS POWER TO RACKS / CABINETS IN NEW TR's MUST BE PROVIDED TO THE TOP OF THE RACKS /

CABINETS. NO POWER WIRING ON FLOORS!

N. INSTALL LIGHTING FIXTURES PER LIGHTING SCHEDULE. CONTACT COR PRIOR TO INSTALLING

LIGHTING TO DETERMINE OPTIMUM LOCATION FOR LIGHT FIXTURES.

O. INSTALL LIGHTING CONTROLS PER Nlight DETAIL ON DRAWING E-501.

1. SEE FEEDER SCHEDULE ON THIS DRAWING. CONTRACTOR TO EXAMINE ELECTRICAL CLOSET

DIRECTLY ABOVE TO DETERMINE WHERE TO CORE DRILL TO ROUTE THE CONDUITS FROM BELOW

INTO ELECTRICAL ROOMS ABOVE. FLOOR MUST BE X-RAYED TO AVOID CUTTING REBARS. TO

MINIMIZE CONCENTRATION OF CONDUITS IN AREA SHOWN, CONTRACTOR MAY ROUTE SOME

CONDUITS INTO TR ROOM A19A, THEN UP TO 1ST FLOOR IT ROOM A101D. CONTINUE ON

DRAWING EP-B01-101

ADDENDUM #1 11-20-24

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text N

AutoCAD SHX Text

AutoCAD SHX Text 4'

AutoCAD SHX Text 8'

AutoCAD SHX Text 16'

AutoCAD SHX Text 32'

AutoCAD SHX Text 1/16"=1'-0"

AutoCAD SHX Text

AutoCAD SHX Text

BUILDING 1 - BASEMENT LEVEL PLAN

AutoCAD SHX Text

ELECTRICAL GENERAL NOTES

AutoCAD SHX Text

ELECTRICAL KEY NOTES

1/A-01-101.2

1/A-01-101.3

1/A-01-101.1

1/A-01-101.3

1/A -01

-10 1.2

1/A -01

-10 1.1

1/A-01-101.3

1/A-01-101.4

1/A-01-101.3

1/A-01-101.4

UP

UP

UP

UP

UP

UP

DN

UP

DN

UP

UPUP

UP

A

B

C

D

E

F

1 3 4 5 11 13 16 18 19 21 23 25 26 27 286 8 9

11.1

14 15

K

L

M

29 30

G

O

Q

S

T

U

V

P

S.2

S.1

Q.1

U.1

V.1

V.2

W.1

X

Y

8.26.36.2 10.19.3 12.111.2

2.1

3.1

4.1

3.8

Z.4

4.7 6.1 8.1 11.7

Z.3

Z.2

24 31 32

N

7 222010 12

18B 20B 22B 24B 24C

H

I

J

R

W

Z.1

22D

AC101A AC130

AC101B

AC101C

AC133

AC128

AC129 AC134 AC135

AC131

AC131

AC101D

AC136

B1-03C

AC119

B113

AC127A

AC127B

C100

AC100

AC101

AC104

A140

A141A128C

A1

B103 B105

C110C109C107 C108

C116F C116A

C116

C116B

C105

C104

C106

C115

A1

A143F

A121AA119A118

A117A

A116B

A116A

A120 A121 A121B

A115

A115H

A115A A115I

A115J

A115BA115C

A115G

A122

A115E

A121E A122F

A102G

A102A

A1

A102BA102C

A102D

A108

A109

AC101J

AC101I

AC101H

AC101G

A127 A127BA127A

C116C

C116D

C119

C120C124

C125

C121

C122

C123

C123BC123A

C126

C127

C1-02

A145

C117 C104F C116E C105E

A143

A102E A101E

C102C101A144 C103

A111

A112

A104A

A104

A106

A105A110

A136

B149B1

B116

B148

B147

B146

AC120A

AC120

A116HA116G

A116E A116F

A116D

A116C

A116

A107

A104B

A115D

AC119AC118AC115

AC112

AC112A

AC114

AC109

A135

B145

B133

B134

B136 B135

B131 B132B130

B138

B129

B139B140

B128

B127

B137

B126

B141

B124B119

B123E

B143 B142

B133AB120

B143E

B120F

AC135

AC110

AC111

AC121

AC116E

AC122

AC122A

AC125

AC106E

AC113

AC124

AC123

AC117

B118

A137

B117A

A134A

C113 C112C111

C114D

C114-E

C114B

C114C

C114C

C114-W

C1-03A103

B123 B125

A1-04 A1-03

A140E

A134

A128B

A128D

A128A

AC105AC106

A1

A

A129

A128H A128G

AC108

AC1-5

B114

B106B107

B108

B113

B109A B109

B111

B1

B115

B104

B116C

B116D B1-03

A1-01

A101

A138

A142A

AC101K

B1-04B1-01

B1-02

A101A

A101G A101C

A113

B101

A101D

A141E

C1-01

C114T

A114

AC147 AC148 AC149 AC150 AC151 AC152 AC153 AC154 AC155 AC156

AC158 AC157

AC165AC164AC161

AC160

AC143 AC143A

AC145AC146

AC144 AC141 AC162 AC163 AC166

AC167

AC

1-

AC

1-

AC

1-

A615P

A6

Q

AC1-2

AC159

A1-02

A1-E1

A1-E2

A1-E3 A1-E4

A101H

A101J

AC134A AC136AAC135A

AC134C B1-03D

B116A

1/A-01-101.3

1/A-01-101.5

1/A -01

-10 1.5

1/A -01

-10 1.3

A101E

A115E

AC106E

AC116E

AC144

B143E

C116E

C105E

A102E

A121E

A141E

A140E

B123E

LS-1A1A

ECR1-1 ECR2-1

LS

-1C

1C -1

1C -2

LS-1B

1B

LP1-1

PP1-1

PP2-1

ID-

ID-

AC160

B116A

A144A

PP3-1

ECR3-1

1-1-N-EHRM

1-1 -E-

EH

RM

NORMAL CONDUIT # 1, 2, 3, 4, 5

EM CONDUIT # 1, 2, 3, 4, 5

NORMAL CONDUIT # 6

EM CONDUIT # 6

ELECTRICAL - BUILDING 1 - LEVEL 1

PLAN

WG BX

EP-B01-101

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

K:

\C

C G

_P R

O

JE

C

TS

\2

1\

-1

T op ek a

EH

R M

C

1R

\4

- D es

D oc s\

2- D ra w in gs

\W O

R

KI

N G

\A ut oC

AD

\E le ct ric al \E

P- B0

1-

1.

dw g

/2 0/

0:

:4

AM

ISSUE FOR BIDOffice of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

EHRM INFRASTRUCTURE

UPGRADES

COLMERY O'NEIL VA HEALTH CARE

21-116

Revisions: Date:

www. bancroft-ae.com

3300 Dundee RD.

Northbrook, IL 60062

T: 847.952.9362

03/22/2024Bancroft Project No: 21-116ISSUE FOR BID R2 03-22-24

A. THIS PROJECT ALSO INVOLVES RESOLVING ELECTRICAL DEFICIENCIES. THIS WORK IS SHOWN ON

SEPARATE DRAWINGS FROM TR ROOM DRAWINGS.

B. EACH TR ROOM INVOLVES THREE TYPES OF WIRING:

a. POWER TO RACKS, SEE DRAWINGS EP-01-500 AND EP-01-501 FOR DETAILS,

b. POWER TO FAN COIL UNITS AND SPLIT COOLERS SEE DRAWING DETAIL ???,

c. POWER TO RECEPTACLES AND LIGHTING SHOWN FOR EACH TR ROOM.

C. CONTRACTOR TO DETERMINE DETAILED CONDUIT ROUTING BASED ON FIELD CONDITIONS.

D. CONDUIT ON PLAN DRAWINGS IS SHOWN FOR GENERAL ROUTING PURPOSES ONLY. SEE WIRING

AND PANEL DRAWINGS FOR WIRING AND CONDUIT SIZES.

E. WHEN WALLS ARE DEMOLITIONED THAT CONTAIN RECEPTACLES FEEDING EQUIPMENT,

CONTRACTOR TO RELOCATE RECEPTACLES TO REMAINING WALL TO CONTINUE POWERING

REMAINING EQUIPMENT. IF NO CONNECTED EQUIPMENT REMAINS CONNECTED TO

DEMOLITIONED WALLS, CONTRACTOR TO REMOVE THE WIRING AND CONDUIT BACK TO THE

SOURCE.

F. UPS POWER IS ON THE EMERGENCY CRITICAL BRANCH AND MUST BE IN SEPARATE CONDUITS

FROM NORMAL POWER.

G. EQUIPMENT POWER TO TECHNOLOGY ROOM FANS AND CONDENSERS IS FROM EQUIPMENT

BRANCH OF EMERGENCY POWER AND MUST BE IN CONDUITS SEPARATE FROM NORMAL POWER.

CONDUITS FROM TR ROOMS TO OUTDOOR CONDENSERS WILL USE SAME ROUTING AND

SUPPORTS AS CONDENSER REFRIGERANT TUBING.

H. CONTACT VA IT PRIOR TO WORKING IN IT CLOSET.

I. FOLLOW VA & NFPA 70E LOCK OUT TAG OUT PROCEDURES FOR SAFETY.

J. SEE THE ELECTRICAL EQUIPMENT SCHEDULE FOR EQUIPMENT DETAILS.

K. SEE PANEL SCHEDULES ON DRAWING SERIES E600 FOR PANEL SCHEDULES AND CIRCUIT

NUMBERS.

L. SEE DRAWING SERIES E700 FOR SINGLE LINE DRAWINGS.

M. UPS POWER TO RACKS / CABINETS IN NEW TR's MUST BE PROVIDED TO THE TOP OF THE RACKS /

CABINETS. NO POWER WIRING ON FLOORS!

N. INSTALL LIGHTING FIXTURES PER LIGHTING SCHEDULE. CONTACT COR PRIOR TO INSTALLING

LIGHTING TO DETERMINE OPTIMUM LOCATION FOR LIGHT FIXTURES.

O. INSTALL LIGHTING CONTROLS PER Nlight DETAIL ON DRAWING E502.

1. CONTINUE ROUTING CONDUITS FROM BELOW INTO ROOMS A141E AND A101D

2. CONSOLIDATE ALL CONDUITS INTO ROOM A141E AND ROUTE THEM TO UPPER FLOORS.

ADDENDUM #1 11-20-24

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text N

AutoCAD SHX Text

AutoCAD SHX Text 4'

AutoCAD SHX Text 8'

AutoCAD SHX Text 16'

AutoCAD SHX Text 32'

AutoCAD SHX Text 1/16"=1'-0"

AutoCAD SHX Text

AutoCAD SHX Text

BUILDING 1 - LEVEL 1 PLAN

AutoCAD SHX Text

ELECTRICAL GENERAL NOTES

ELECTRICAL KEY NOTES

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

K:

\C

C G

_P R

O

JE

C

TS

\2

1\

-1

T op ek a

EH

R M

C

1R

\4

- D es

D oc s\

2- D ra w in gs

\W O

R

KI

N G

\A ut oC

AD

\T T-

0-

1.

dw g

/2

5/

1:

:1

AM

ISSUE FOR BIDOffice of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

EHRM INFRASTRUCTURE

UPGRADES

COLMERY O'NEIL VA HEALTH CARE

21-116

Revisions: Date:

www. bancroft-ae.com

3300 Dundee RD.

Northbrook, IL 60062

T: 847.952.9362

ISSUE FOR BID R2 03-22-24

12/28/2023Bancroft Project No: 21-116

ADDENDUM #1 11-22-24

ICT - GENERAL NOTES, SYMBOLS +

ABBREVIATIONS

JG JG

TT-00-001

SX

SX

R

RM

TTB

S

SPEAKER, CEILING MOUNTED, "X" INDICATES THE TYPE, PROVIDE SCHEDULE ON LEGEND

SPEAKER, WALL MOUNTED, "X" INDICATES THE TYPE, PROVIDE SCHEDULE ON LEGEND

MTD. 7'-6" (2286mm) AFF UNLESS OTHERWISE NOTED

RADIO CHANNEL SELECTOR FACILITIES, MTD. 4'-6" (1372 mm) AFF

UNLESS OTHERWISE NOTED.

SPEAKER PROGRAM SELECTOR SWITCH & VOLUME CONTROL MTD.

4'-6" (1372 mm) AFF UNLESS OTHERWISE NOTED.

COMMUNICATION SYMBOLS

TELECOMMUNICATION TERMINAL CABINET

TELEPHONE BACKBOARD (WALL MOUNTED)

REMOTE DICTATING OUTLET MTD 1'-6" (457 mm) AFF. UNLESS OTHERWISE NOTED

INTERCOM STATION (REFER TO SPECS. FOR FUNCTIONAL

OPERATION OF INSTRUMENT & TYPE REQUIRED)

INTERCOM STAFF STATION.

ADO AUTOMATIC DOOR OPENER

WAP

PAS

SMS SOUND MASKING (WHITE NOISE) SYSTEM

SPEAKER.

EMS EMERGENCY MANAGEMENT SYSTEM TEXT-

TO-SPEECH WALL MOUNTED SPEAKER.

ICS INTERCOM SYSTEM SPEAKER.

PAS

PUBLIC ADDRESS SYSTEM

WALL MOUNTED SPEAKER

PAS

SOUND MASKING (WHITE NOISE) SYSTEM LOCAL

KEYPAD STATION

V

DB DURESS BUTTON

DAS ANTENNA CELLULAR

DAP

DAC

N P N D

N BI

N SA

N DS

N ST

N CB

D

N MS

Z

CR

AIP

CR/K

REX

KP

RX

ES

ML

CCP

MID

GB

DC

WS

DIVERSITY PATCH ANTENNA

NURSE CALL SYMBOLS

PA

ELECTRONIC SAFETY AND SECURITY SYMBOLS

SECURITY / DURESS-ALARM BUTTON MOUNTED 3" ABOVE COUNTER TOP

/ COUNTER TOP BACK SPLAH.

CEILING MOUNTED SECURITY CAMERA, X REPERSENTS VIEW RANGE OF CAMERA

WALL MOUNTED CARD READER

AIPHONE

KEYPAD LOCK

ACCESS CONTROL PANEL

ROOF POLE MOUNTED SECURITY CAMERA

CAMERA CONTROL PANEL

WALL MOUNTED CARD READER WITH KEYPAD

REQUEST TO EXIT MOTION

DOOR LOCKING MECHANISM/ELECT STRIKE

DOOR LOCKING MECHANISM/MAG LOCK

ACCESS CONTROL POWER SUPPLY

REQUEST TO EXIT PUSH BUTTON

MOTION INTRUSION DETECTOR

GLASS BREAK SENSOR

DOOR CONTACT

DOOR OPENER WAVE SENSOR FOR MOTORIZED DOOR

ESSEX ELECTORNICS #32NF3X.

NURSE CALL, WALL MOUNTED DOME LIGHT

NURSE CALL, WALL MOUNTED BED INTERFACE

NURSE CALL, WALL MOUNTED STAFF ASSIST

NURSE CALL, WALL MOUNTED DUTY STATION

NURSE CALL, CEILING MOUNTED DOME LIGHT

NURSE CALL, WALL MOUNTED PULL CORD

NURSE CALL, WALL MOUNTED STAFF TERMINAL

NURSE CALL, COUNTER MOUNTED MASTER STATION

NURSE CALL, WALL MOUNTED CODE BLUE

NURSE CALL ZONE LIGHT - CEILING MOUNTEDN

N

X

RFID WALL MOUNTED PATIENT WRISTBAND READER

OVER THE DOOR ALARM SENSOR PERVENTIVEDS

ACP

ACPS

WALL MOUNTED SECURITY CAMERA, X REPERSENTS VIEW RANGE OF CAMERAX

+H P#

P#

P#

+H P#

+H P#

E P#

E P#

CATV

CCTV

FO

T I S

NC

R C

CABLE TELEVISION LINE = CATV

CLOSED CIRCUIT TELEVISION LINE = CCTV. MINIMUM 1"

(25mm) CONDUIT

FIBEROPTICS LINE = FO

TELEPHONE LINE = T

INTERCOM LINE = I. MINIMUM 3/4" (19mm) CONDUIT.

SOUND LINE = S

NURSE CALL LINE = NC. MINIMUM 3/4" (19mm) CONDUIT.

RADIO CONDUIT RUN, MINIMUM 3/4" (19mm) CONDUIT.

TELECOMMUNICATIONS MANHOLE

GENERAL SYMBOLS

TV T#

H

TVT#

H

WALL MOUNTED - TELEPHONE OUTLET P# =

NUMBER OF VOICE / DATA PORTS IN FACEPLATE, IF

NOT SHOWN PROVIDE 1 PORTS + H =INSTALLATION

HEIGHT IN INCHES AT CENTER OF OUTLET, IF NOT

SHOWN INSTALL AT TYPICAL 18" RECEPTACLE

HEIGHT. COORDINATE WITH ELECTRICAL

WALL MOUNTED - VOICE / DATA OUTLET P# = NUMBER

OF VOICE / DATA PORTS IN FACEPLATE, IF NOT

SHOWN PROVIDE 4 PORTS + H =INSTALLATION HEIGHT

IN INCHES AT CENTER OF OUTLET, IF NOT SHOWN

INSTALL AT TYPICAL 18" RECEPTACLE HEIGHT.

COORDINATE WITH ELECTRICAL

CEILING MOUNTED - VOICE / DATA OUTLET P# =

NUMBER OF VOICE / DATA FACEPLATE, IF NOT

SHOWN PROVIDE 4 PORTS IN PORTS

FLOOR MOUNTED-TELEPHONE/DATA OUTLET

P# = NUMBER OF VOICE / DATA PORTS IN

FACEPLATE, IF NOT SHOWN PROVIDE 4

PORTS

WALL MOUNTED - GETWELL NETWORK DATA OUTLET

P# = NUMBER OF VOICE / DATA PORTS IN

FACEPLATE, IF NOT SHOWN PROVIDE 1 PORTS + H

=INSTALLATION HEIGHT IN INCHES AT CENTER OF

OUTLET, IF NOT SHOWN INSTALL AT TYPICAL 72"

RECEPTACLE HEIGHT. COORDINATE WITH

ELECTRICAL

CEILING MOUNTED - OUTLET FOR WIRELESS ACCESS POINT

P# = NUMBER OF VOICE / DATA PORTS IN FACEPLATE, IF

NOT SHOWN PROVIDE 2 PORTS

FLOOR BOX- VOICE / DATA OUTLETS P# = NUMBER OF

VOICE / DATA PORTS IN FACEPLATE, NOT SHOWN

PROVIDE 4 PORTS IF E= POWER OUTLET- REFER TO

ELECTRICAL PLANS FOR DETAILS

POKE THRU- VOICE / DATA OUTLETS P# = NUMBER OF

VOICE / DATA PORTS IN FACEPLATE, NOT SHOWN

PROVIDE 4 PORTS IF E= POWER OUTLET- REFER TO

ELECTRICAL PLANS FOR DETAILS

WALL MOUNTED TV OUTLET PROVIDE 1 DATA PORT

AND 1 COAX PORT UNLESS OTHERWISE NOTED T# =

TYPE OF OUTLET SEE TELECOMMUNICATION DETAILS

+ H =INSTALLATION HEIGHT IN INCHES AT CENTER OF

OUTLET, IF NOT SHOWN INSTALL AT TYPICAL 72"

RECEPTACLE HEIGHT. COORDINATE WITH

ELECTRICAL

CEILING MOUNTED TV OUTLET PROVIDE 1 DATA PORT

AND 1 COAX PORT UNLESS OTHERWISE NOTED T# =

TYPE OF OUTLET SEE TELECOMMUNICATION DETAILS

+ H =INSTALLATION HEIGHT IN INCHES AT CENTER OF

OUTLET, IF NOT SHOWN INSTALL AT TYPICAL 72"

RECEPTACLE HEIGHT. COORDINATE WITH

ELECTRICAL

PUBLIC ADDRESS SYSTEM 2X2 RECESSED SPEAKER

PUBLIC ADDRESS SYSTEM CEILING RECESSED ROUND SPEAKER

GENERAL TELECOMMUNICATIONS NOTES

1. FOR GENERAL TELECOMMUNICATIONS INFORMATION AND SOW, REFER TO DESIGN NARRATIVE / BASIS

OF DESIGN NARRATIVE.

2. CONTRACTOR SHALL VERIFY EXISTING CONDITIONS AND PROMPTLY REPORT ANY DRAWING

DISCREPANCIES TO THE VA AND ARCHITECT / ENGINEER.

3. ALL CATEGORY CABLING BEING REPLACED SHALL BE REMOVED / DEMOLISHED AS PART OF THIS

PROJECT. TURN DEMOLISHED CATEGORY CABLING OVER TO VA FOR RECYCLING.

4. ALL AREAS SHALL BE CONSIDERED PLENUM SPACES, UNLESS OTHERWISE NOTED. COMPLY WITH ALL

CODES PERTAINING TO PLENUM SPACES. PROVIDE RATED PLENUM AND OEM CERTIFIED FOR

INSTALLATION WITHIN PLENUM SPACES.

5. OSP OPTICAL FIBER CABLE SHALL BE CONSTRUCTED WITH AN ALUMINUM INTERLOCKING ARMORED

JACKET AND INSTALLED WITHIN A CONCRETE ENCASED DUCTBANK.

6. ISP OPTICAL FIBER CABLING INSTALLED WITHIN CABLE TRAY SHALL BE CONSTRUCTED WITH

ALUMINUM INTERLOCKING ARMORED JACKET. OPTIONAL, WITH VA APPROVAL, IS NON-ARMORED

PLENUM RATED OPTICAL FIBER CABLE WITHIN A PLENUM RATED CORRUGATED INNERDUCT.

7. NO SYSTEMS OR COMPONENTS SHALL BE DISRUPTED OUT OF PROJECT SEQUENCE. COORDINATE ALL

SERVICE DISRUPTIONS WITH VA.

8. CARE SHALL BE TAKEN NOT TO DISRUPT OR DAMAGE ANY EXISTING SYSTEMS INCLUDING, BUT NOT

LIMITED TO: CATV, ACCESS CONTROL, FIRE ALARM, NURSE CALL, BUILDING AUTOMATION,

DISTRIBUTED ANTENNA, PAGING AND BIO-MED.

9. ALL EQUIPMENT ADDED TO EXISTING TELECOM ROOMS SHALL BE BONDED TO THE GROUNDING

SYSTEM WITHIN TELECOM ROOM.

10. CONTRACTOR SHALL VERIFY ALL COMPONENTS BONDED TO EXISTING TELECOMMUNICATIONS

GROUNDING BUSBAR HAVE BEEN TAKEN OUT OF SERVICE OR HAVE BEEN BONDED TO NEW

TELECOMMUNICATIONS GROUNDING / BONDING SYSTEM PRIOR TO REMOVING ANY EXISTING

GROUNDING COMPONENTS.

11. NEW TELECOM ROOMS SHALL HAVE COMPLETE GROUNDING SYSTEM INSTALLED AND CONNECTED TO

NEAREST TELECOMMUNICATIONS GROUNDING BACKBONE.

12. CONTRACTOR SHALL PROVIDE AND INSTALL BASKET TYPE CABLE TRAY ALONG PRIMARY CABLE PATHWAYS. MINIMUM CABLE TRAY SIZE IS 4" x 12". CONTRACTOR SHALL SIZE CABLE TRAY DEPENDENT UPON ACTUAL NUMBER OF CAT 6A CABLES TO BE INSTALLED WITHIN A GIVEN AREA. SIZE SUCH THAT FILL IS 20% OF TOTAL CAPACITY. THIS LEAVES 20% FILL CAPACITY (50% FUTURE CAPACITY) AS TOTAL

FILL IS LIMITED TO 40%.

13. IN ADDITION TO PRIMARY PATHWAYS, CABLE TRAY SHALL BE INSTALLED FOR CABLE BUNDLES OVER 12

CABLES, EVEN IF NOT SHOWN ON DRAWINGS.

14. IF ANY AREA IS TOO CONGESTED BY EXISTING UTILITIES TO ALLOW INSTALLION OF CABLE TRAY, CONTRACTOR SHALL NOTIFY VA AND ARCHITECT / ENGINEER. ACCEPTABLE ALTERNATIVES IS TO RE-ROUTE CABLE TRAY OR INSTALL EQUIVALENT CAPACITY OF CONDUITS TO SPAN THESE AREAS.

15. J-HOOKS ARE NOT ALLOWED EXCEPT BY SPECIAL PERMISSION FROM VA, WHICH WILL BE EVALUATED

ON A CASE-BY-CASE BASIS.

16. FIRE RATED MECHANICAL SLEEVES ASSEMBLIES SHALL BE INSTALLED WHEN PASSING THROUGH PARTITIONS. MAINTAIN RATING OF ALL PARTITIONS. ASSUMING 40% FILL PER SLEEVES, ALSO PROVIDE 50% FUTURE SPARE CAPACITY (ONE EMPTY SLEEVE FOR EVERY TWO FILLED SLEEVES). AT A MINIMUM

THERE SHALL ONE EMPTY SPARE SLEEVE INSTALLED.

17. CONTRACTOR SHALL FIRE STOP ANY EXISTING PENETRATION ON BOTH SIDES (SUCH AS CONDUIT

SLEEVES) THEY RE-USE OR REMOVE EXISTING CABLING FROM DURING PROJECT.

18. EXISTING ROUTING TO TELECOM OUTLETS SHALL BE MAINTAINED TO FULLEST EXTENT POSSIBLE.

EXISTING CONDUIT TO TELECOM BACKBOX TO BE REUSED IF VIAIBLE.

19. CONDUIT THAT IS ONLY INSTALLED TO ABOVE CEILING SHALL BE EXTENDED TO CABLE TRAY.

20. MAXIMUM 295 FEET CABLING DISTANCE LIMITATION SHALL BE MAINTAINED AT ALL TIMES AND SHALL BE

VERIFIED DURING TESTING. IF THIS REQUIREMENT CANNOT BE MAINTAINED FOR ANY REASON, CONTACT VA AND ARCHITECT / ENGINEER IMMEDIATELY.

21. ALL CABLING TO WIRELESS ACCESS POINTS (WAP's) SHALL BE REPLACED WITH TW0 (2) CAT 6A CABLES. TOTAL NUMBER OF WAP's SHALL BE FIELD VERIFIED. PROVIDE MINIMUM OF 10' SERVICE LOOP AND NEW DUEL JACK SURFACE MOUNTED BOX (aka BISCUIT) OR MODULAR PLUG TERMINATED LINK (MPTL) ABOVE CEILING WHERE EXISTING WAP's ARE LOCATED. ALL EXISTING WAP's SHALL REMAIN IN

PLACE DURING CONSTRUCTION.

22. HYBRID CABLES FOR MM/SM OPTICAL FIBER CABLE SHALL NOT BE PERMITTED.

23. OUTSIDE PLANT (OSP) OS2 OPTICAL FIBER CABLING SHALL BE INDOOR / OUTDOOR RATED SO THAT

BUILDING DISTRIBUTORS SHALL NOT BE REQUIRED AT BUILDING ENTRANCE POINTS.

24. CONTRACTOR SHALL LOCATE EXISTING REINFORCING PRIOR TO ANY CORING FOR CONDUIT OR

MECHANICAL FIRE SLEEVES. DO NOT CUT ANY REINFORCING. CORES SHALL HAVE MINIMUM OF 4" CLEAR BETWEEN CORE AND REINFORCING. ADJUST CORE LOCATIONS AS REQUIRED. LOCATIONS WITH

MORE THAN TWO (2) CORES THROUGH CMU WALL, SPACE CORE MINIMUM 16" ON CENTER.

25. ALL PERSONAL ENTERING PATIENT MENTAL HEALTH WARD MUST HAVE ADDITIONAL TRAINING AND

APPROVAL FROM NURSE MANAGER PRIOR TO ENTRY.

26. ANY NOTES, DETAILS OR SPECIFICATION WITHIN CONSTRUCTION DOCUMENTS THAT HAVE MORE

STRINGENT REQUIREMENTS THAN LISTED HERE SHALL HAVE PRECEDENCE OVER ITEMS LISTED

ABOVE.

T101 T102

CAMPUS ROUTING PLAN

JG JG

TT-00-002

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

K:

\C

C G

_P R

O

JE

C

TS

\2

1\

-1

T op ek a

EH

R M

C

1R

\4

- D es

D oc s\

2- D ra w in gs

\W O

R

KI

N G

\A ut oC

AD

\T T-

0-

2.

dw g

/6

/2

:3 7:

A

M

ISSUE FOR BIDOffice of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

EHRM INFRASTRUCTURE

UPGRADES

COLMERY O'NEIL VA HEALTH CARE

21-116

Revisions: Date:

www. bancroft-ae.com

3300 Dundee RD.

Northbrook, IL 60062

T: 847.952.9362

ISSUED FOR BID R2 03-22-24

12/28/2023Bancroft Project No: 21-116

ADDENDUM #1 11-22-24

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text N

AutoCAD SHX Text 1" = 100'-0"

AutoCAD SHX Text

CAMPUS ROUTING PLAN KEYNOTES

AutoCAD SHX Text

1. NEW (2) 4" SCHEDULE 40 PVC CONCRETE ENCASED CONDUIT IN A 1X2 NEW (2) 4" SCHEDULE 40 PVC CONCRETE ENCASED CONDUIT IN A 1X2 CONFIGURATION. INSTALL A MINIMUM 30" BFG. INSTALL (3) 3-CELL MAXCELL FABRIC INTERDUCTS IN (1) OF THE TWO 4" CONDUITS. 2. NEW (4) 4" SCHEDULE 40 PVC CONCRETE ENCASED CONDUIT IN A 2X2 NEW (4) 4" SCHEDULE 40 PVC CONCRETE ENCASED CONDUIT IN A 2X2 CONFIGURATION. INSTALL A MINIMUM 30" BFG. INSTALL (3) 3-CELL MAXCELL FABRIC INTERDUCTS IN (2) OF THE FOUR 4" CONDUITS. 3. EXISTING LOWER ROUTE IN UTILITY TUNNEL AND UPPER ROUTE IN CEILING EXISTING LOWER ROUTE IN UTILITY TUNNEL AND UPPER ROUTE IN CEILING PLENUM OF WALKWAY BUILDING. CONTRACTOR SHALL PROVIDE AND INSTALL NEW CONTRACTOR SHALL PROVIDE AND INSTALL NEW BASKET STYLE CABLE TRAY FOR SUPPORT OF NEW CABLES THROUGH BOTH LEVELS. 4. NEW PULLBOX. SEE DETAILS THIS SHEET AND CIVIL PLANS FOR MORE NEW PULLBOX. SEE DETAILS THIS SHEET AND CIVIL PLANS FOR MORE INFORMATION. 5. NEW (6) 4" SCHEDULE 40 PVC CONCRETE ENCASED CONDUIT IN A 3X2 NEW (6) 4" SCHEDULE 40 PVC CONCRETE ENCASED CONDUIT IN A 3X2 CONFIGURATION. INSTALL A MINIMUM 30" BFG. INSTALL (3) 3-CELL MAXCELL FABRIC INTERDUCTS IN (4) OF THE SIX 4" CONDUITS. 6. ENTER BLDG 21 CRAWL SPACE AT APPROXIMATELY THIS LOCATION. ROUTE ENTER BLDG 21 CRAWL SPACE AT APPROXIMATELY THIS LOCATION. ROUTE CONDUITS THROUGH CRAWL SPACE TO CORRIDOR IN BLDG 21 NEAREST CONNECTION TO BLDG 19. 7. FIBER PATHWAY 'A' THROUGH CEILING OF WALKWAY TO BUILDING 19. PROVIDE FIBER PATHWAY 'A' THROUGH CEILING OF WALKWAY TO BUILDING 19. PROVIDE (6) 4" CONDUIT. SEAL FOR WATER INTRUSION. (SEE BUILDING ENTRY WATER PROOFING NOTES THIS SHEET) 8. FIBER PATHWAY 'B' THROUGH STEAM TUNNEL TO BUILDING 19. PROVIDE (6) 4" FIBER PATHWAY 'B' THROUGH STEAM TUNNEL TO BUILDING 19. PROVIDE (6) 4" CONDUIT. SEAL FOR WATER INTRUSION. (SEE BUILDING ENTRY WATER PROOFING NOTES THIS SHEET)

AutoCAD SHX Text

CAMPUS ROUTING PLAN GENERAL NOTES

AutoCAD SHX Text A. THIS DRAWING IS FOR DIAGRAMMATIC PURPOSE ONLY. REFER TO CIVIL DRAWINGS THIS DRAWING IS FOR DIAGRAMMATIC PURPOSE ONLY. REFER TO CIVIL DRAWINGS FOR ENTRANCE AND EXIT POINTS AT BUILDINGS AND PATH OF DUCTBANK. B. CONDUIT ENTRY INTO EXISTING BUILDINGS SHALL BE PROPERLY WATER SEALED CONDUIT ENTRY INTO EXISTING BUILDINGS SHALL BE PROPERLY WATER SEALED AND PATHWAY SHALL UTILIZE SMARTLB FOR THOSE AREAS REQUIRING ABOVE GROUND ENTRY. C. NEW PULLBOX SHALL BE CONCRETE MINIMUM TIER 22 AND 24"X36"X30" DEEP NEW PULLBOX SHALL BE CONCRETE MINIMUM TIER 22 AND 24"X36"X30" DEEP OPEN BOTTOM WITH 24" AGGREGATE BASE.

AutoCAD SHX Text

AutoCAD SHX Text

CAMPUS ROUTING PLAN

AutoCAD SHX Text

CABLE

AutoCAD SHX Text

HANGER

AutoCAD SHX Text

EACH CABLE MUST BE LABELED WITH SNAP AROUND LABEL. WILLIAM FRICK WFS-ES-0004.

AutoCAD SHX Text BONDING POINT FOR LOCATE WIRE. PROVIDE A GREEN INSULATED #12 COPPER WIRE THROUGHOUT NEW CONDUIT SYSTEM. BOND AT THE TOP OF EACH NEW PULLBOX FOR CONNECTION TO LOCATE SYSTEM.

AutoCAD SHX Text

UPPER RUNG IS RESERVED FOR RUNS INTO BUILDING.

AutoCAD SHX Text

REFER TO BUSINESS CONTINUITY SET.

AutoCAD SHX Text

END WALL

AutoCAD SHX Text

CONDUIT ENTRIES

AutoCAD SHX Text

CONDUIT ENTRIES

AutoCAD SHX Text

PULLING EYE

AutoCAD SHX Text 30"

AutoCAD SHX Text

END WALL

AutoCAD SHX Text

CONDUIT ENTRIES

AutoCAD SHX Text

CONDUIT ENTRIES

AutoCAD SHX Text

PULLING EYE

AutoCAD SHX Text 30"

AutoCAD SHX Text 36"

AutoCAD SHX Text

SIDE WALL

AutoCAD SHX Text 30"

AutoCAD SHX Text 24"

AutoCAD SHX Text

CABLE RACK

AutoCAD SHX Text

SIDE WALL

AutoCAD SHX Text 30"

AutoCAD SHX Text TYPICAL 24"x36"x30" CONCRETE PULLBOX UNLESS OTHERWISE NOTED

AutoCAD SHX Text

CABLE RACK

AutoCAD SHX Text

CABLE RACK

AutoCAD SHX Text

CABLE RACK

AutoCAD SHX Text PULLBOX NOTES: 1. ANSI/SCTE 77 TIER 15 RATED. ANSI/SCTE 77 TIER 15 RATED. 2. 36" LONG x 24" WIDE x 30" DEEP. 36" LONG x 24" WIDE x 30" DEEP. 3. LABELING TO BE APPROVED BY DTSS AND DISNEY TELECOM. LABELING TO BE APPROVED BY DTSS AND DISNEY TELECOM. 4. TWO PIECE METALLIC LID WITH TORSION ASSIST. TWO PIECE METALLIC LID WITH TORSION ASSIST. 5. OPEN BOTTOM. OPEN BOTTOM. 6. CABLE RACKING ON TWO (2) SIDE WALLS. CABLE RACKING ON TWO (2) SIDE WALLS. 7. ALL CONDUITS SHALL BE PLACED WITH A MINIMUM 30" CLEAR COVER.ALL CONDUITS SHALL BE PLACED WITH A MINIMUM 30" CLEAR COVER.

AutoCAD SHX Text

FINISHED GRADE

AutoCAD SHX Text

LID

AutoCAD SHX Text

GRAVEL

AutoCAD SHX Text

CONDUIT

AutoCAD SHX Text

(FOR OPEN TRENCH ONLY)

AutoCAD SHX Text

24" MINIMUM

AutoCAD SHX Text

30" MINIMUM

AutoCAD SHX Text

NOT TO SCALE

AutoCAD SHX Text

AutoCAD SHX Text

NEW TIER 22 PULLBOX BUTTERFLY DETAIL

AutoCAD SHX Text

NOT TO SCALE

AutoCAD SHX Text

AutoCAD SHX Text

NEW PULLBOX RACKING DETAIL

AutoCAD SHX Text

NOT TO SCALE

AutoCAD SHX Text

AutoCAD SHX Text

NEW PULLBOX PENETRATION DETAIL

NEW CONDUIT BUILDING PENETRATION NOTES: 1. CONDUIT LOW POINT SHALL BE MANHOLE, PULLBOX, ETC. CONDUIT LOW POINT SHALL BE MANHOLE, PULLBOX, ETC. 2. CONDUITS SHALL BE ENCASED IN CONCRETE TO AND THROUGH CONDUITS SHALL BE ENCASED IN CONCRETE TO AND THROUGH FOUNDATION OR EXTERIOR WALL. 3. INSIDE OF CONDUITS WITHIN FOUNDATION WALL SHALL BE SEALED. INSIDE OF CONDUITS WITHIN FOUNDATION WALL SHALL BE SEALED. 4. DUCT SEAL, THORNE & DERRICK, CAT# 280010 OR APPROVED DUCT SEAL, THORNE & DERRICK, CAT# 280010 OR APPROVED EQUAL.

AREA D SEE SHT. AE203

AREA F SEE SHT. AE205

UP

UP

UP

UP

UP

UP

UP

UP

UP

UP

UP

UP

UP

DN

UPUP

UP

B23

B23G

B23A B23B

B23E B23D B23C

C0-3A

A9E

A9C A9D

B5

C3

A17

A12

A30

A21

A21E

A21A

A13A A13B

A1

A10F

A3B

A3

A3A

A13

A20E

A20

A17F

C7

C7B

C4EC3EC3F

A19D

C7A

C7G

C7C

C7D

A19

C5

C7H

C7I

C6A19B

C1A18

A18A C2

A17A

A5

B1E

A7A8A9

A10E

A10

A4

A7E

A9A

A11

A14

A15

B4

B3

B13E

B22

B14A

B14

A2

A2A

A2B

A2C A2D

A19DC0-1

C8A

C20

C23

C24 C25

C28

C27

C26

C22 C21

C18C19

C17

C8

C9

C12

C14

C8B

C10 C11

C13

C15 C14A

C14B C14C

C16 C16A

C0-4

A16D

B2 B2B

B2A

B15B16 B17

B1

A16

A16C

A16A

A16E A16B

B22E

B1B

C0-2

C1A

B21

A19C

B1C

B6C

A16G

A9B

B43M B42

B42A B39

B38

C0-5B

C0-5A

C0-3

A9C

C114C

C11A

CB-8

B6D

A0-E3

A0-E1

A0-E2

A0-E4

B42B

B41

B40

B6P

B6 B8A

B7

B13CB13

B12

B9

B10

B11

B11A

B6M

B7M

B8 C0-3E

C0-3C

C0-3B B8C

B13B

B13A

A10G

A10B

A10A

A10C A10D

B3A B20

B23F

C20A A19A

ICT - BUILDING 1 - BASEMENT LEVEL

CABLE TRAY PLAN

JG JG

TT-B01-100

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

K:

\C

C G

_P R

O

JE

C

TS

\2

1\

-1

T op ek a

EH

R M

C

1R

\4

- D es

D oc s\

2- D ra w in gs

\W O

R

KI

N G

\A ut oC

AD

\T T-

B0 1-

0.

dw g

/7

/2

5:

:3

PM

ISSUE FOR BIDOffice of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

EHRM INFRASTRUCTURE

UPGRADES

COLMERY O'NEIL VA HEALTH CARE

21-116

Revisions: Date:

www. bancroft-ae.com

3300 Dundee RD.

Northbrook, IL 60062

T: 847.952.9362

12/28/2023Bancroft Project No: 21-116

ADDENDUM #1 11-22-24

ISSUED FOR BID R2 03-22-24

GENERAL NOTES

A. FOR GENERAL NOTES AND LEGENDS REFER TO SHEET TT-00-001.

B. EXISTING IT / TR / OI&T ROOMS BEING RENOVATED OR RELOCATED TO REMAIN ACTIVE DURING CONSTRUCTION.

G.C. TO PROTECT EQUIPMENT FROM DUST, DEBRIS, OR OTHER DAMAGE DURING CONSTRUCTION WITH PRODUCT SUCH AS VISQUEEN. CONTRACTOR TO ENSURE CONTINUOUS OPERATION OF EQUIPMENT, INCLUDING PROPER VENTILATION / COOLING.

C. NOT ALL KEY NOTES APPLY TO ALL PLAN SHEETS. G.C. TO APPLY ONLY AS INDICATED PER EACH SHEET.

D. APPLY FIRE RATED SEALANT TO ALL EXISTING PENETRATIONS IN EXISTING WALLS THAT THE CONTRACTOR

USES / REUSES. FIRE RATING OF EXISTING WALLS SHALL BE A MINIMUM OF 1 HR ASSEMBLY OR MATCH FIRE RATING OF EXISTING PARTITION IF MORE THAN 1 HOUR. BASIS OF DESIGN FOR 1 HR WALL IS UL 419 ASSEMBLY.

E. CONTRACTOR SHALL PROVIDE AND INSTALL NEW MECHANICAL FIRE RATED SLEEVES AS NECESSARY AND ASSEMBLED PER UL DETAIL APPROPRIATE FOR WALL / FLOOR AND RACEWAY / CABLE TYPES. MINIMUM FIRE

RATING SHALL BE 1 HOUR, OR MATCH FIRE RATING OF EXISTING PARTITION.

FLOOR PLAN KEYNOTESX

FLOOR PLAN LEGEND

BASKET CABLE TRAY.

1. PROVIDE BASKET TYPE CABLE TRAY TO SUPPORT OPTICAL FIBER BACKBONE AND NEW CAT 6A HORIZONTAL CABLING. CABLE TRAY TO BE SIZED AS PER CABLE TRAY CAPACITY PLANNING ON FLOOR PLAN LEGEND.

2. ASSUMING 40% TOTAL FILL CAPACITY, INITIAL FILL SHALL BE 20% WITH 20% OF SPARE CAPACITY (WHICH

EQUATES TO 50% FUTURE CAPACITY).

3. ROUTING SHOWN INDICATES PRIMARY PATHWAYS. IN ADDITION TO PRIMARY PATHWAYS, CABLE TRAY SHALL

BE PROVIDED WHEN CABLE BUNDLES EXCEED 24 CABLES.

4. MECHANICAL FIRE RATED SLEEVE ASSEMBLIES SHALL BE PROVIDED WHEN PASSING THROUGH FIRE RATED PARTITIONS. ASSUMING 40% FILL, INSTALL ONE (1) EMPTY MECHANICAL FIRE SLEEVE FOR EVERY TWO (2) FILLED FIRE SLEEVES, THUS PROVIDING 50% SPARE CAPACITY. MINIMUM OF ONE (1) EMPTY MECHANICAL FIRE

RATE SLEEVE PER PENETRATION LOCATION.

4 12

CF105/300

CF105/450

CF105/500

CF105/600

CF150/150

CF150/200

CF150/300

CF150/450

CF150/500

CF150/600

CF150/900

CATALOG

NUMBER

DEPTH

(IN)

WIDTH

(IN)

CAT 6A 4-pr

PLENUM

(0.35" DIA.)*

50% FILL

CAT 6A 4-pr

PLENUM

(0.35" DIA.)*

40% FILL

CAT 6A 4-pr

PLENUM

(0.35" DIA.)*

20% FILL

248 198 100 373 298 149 414 331 166 497 398 199

186 149 74 238 190 95 357 286 143 536 429 214 596 477 238 715 572 286

1078 862 431

* : FILL RATIO CALCULATIONS BASED ON WORST CASE SCENARIO.

CONTRACTOR SHALL PERFORM FILL CALCULATIONS BASED ON ACTUAL CAT 6A

CABLE BEING INSTALLED AND SUBMIT TO BOTH THE VA AND ENGINEER.

- CABLE TRAY CAPACITY PLANNING CHART

- PROPOSED CABLE TRAY

=> CABLOFIL 4" DEEP x 12" WIDE MINIMUM

-- (SIZE COMMENSURATE WITH DISTRIBUTION REQUIREMENTS)

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

SERVICE ENTRANCE LOCATION

AutoCAD SHX Text

KEY PLAN

AutoCAD SHX Text N

AutoCAD SHX Text

AutoCAD SHX Text 4'

AutoCAD SHX Text 8'

AutoCAD SHX Text 16'

AutoCAD SHX Text 32'

AutoCAD SHX Text 1/16"=1'-0"

AutoCAD SHX Text

AutoCAD SHX Text

BUILDING 1 - BASEMENT LEVEL CABLE TRAY PLAN

NORTH

UP

UP

UP

UP

DN

UP

DN

UP

UPUP

UP

DF

DF

DF

DF DF

AC101A AC130

AC101B

AC101C

AC133

AC128

AC129 AC134 AC135

AC131

AC131

AC101D

AC136

B1-03C

AC119

B113

AC127A

AC127B

C100

AC100

AC101

AC104

A140

A141A128C

A1

B103 B105

C110C109C107 C108

C116F C116A

C116

C116B

C105

C104

C106

C115

A1

A143F

A121AA119A118

A117A

A116B

A116A

A120 A121 A121B

A115

A115H

A115A A115I

A115J

A115BA115C

A115G

A122

A115E

A121E A122F

A102G

A102A

A1

A102BA102C

A102D

A108

A109

AC101J

AC101I

AC101H

AC101G

A127 A127BA127A

C116C

C116D

C119

C120C124

C125

C121

C122

C123

C123BC123A

C126

C127

C1-02

A145

C117 C104F C116E C105E

A143

A102E A101E

C102C101A144 C103

A111

A112

A104A

A104

A106

A105A110

A136

B149B1

B116

B148

B147

B146

AC120A

AC120

A116HA116G

A116E A116F

A116D

A116C

A116

A107

A104B

A115D

AC119AC118AC115

AC112

AC112A

AC114

AC109

A135

B145

B133

B134

B136 B135

B131 B132B130

B138

B129

B139B140

B128

B127

B137

B126

B141

B124B119

B123E

B143 B142

B133AB120

B143E

B120F

AC135

AC110

AC111

AC121

AC116E

AC122

AC122A

AC125

AC106E

AC113

AC124

AC123

AC117

B118

A137

B117A

A134A

C113 C112C111

C114D

C114-E

C114B

C114C

C114C

C114-W

C1-03A103

B123 B125

A1-04 A1-03

A140E

A134

A128B

A128D

A128A

AC105AC106

A1

A

A129

A128H A128G

AC108

AC1-5

B114

B106B107

B108

B113

B109A B109

B111

B1

B115

B104

B116C

B116D B1-03

A1-01

A101

A138

A142A

AC101K

B1-04B1-01

B1-02

A101A

A101G A101C

A113

B101

A101D

A141E

C1-01

C114T

A114

AC147 AC148 AC149 AC150 AC151 AC152 AC153 AC154 AC155 AC156

AC158 AC157

AC165AC164AC161

AC160

AC143 AC143A

AC145AC146

AC144 AC141 AC162 AC163 AC166

AC167

AC

1-

AC

1-

AC

1-

A615P

A6

Q

AC1-2

AC159

A1-02

A1-E1

A1-E2

A1-E3 A1-E4

A101H

A101J

4'-11"

10'-8"

1'-11 12" 21'-9"

AC134A AC136AAC135A

AC134C B1-03D

B116A

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

K:

\C

C G

_P R

O

JE

C

TS

\2

1\

-1

T op ek a

EH

R M

C

1R

\4

- D es

D oc s\

2- D ra w in gs

\W O

R

KI

N G

\A ut oC

AD

\T T-

B0 1-

1.

dw g

/7

/2

5:

:3

PM

ISSUE FOR BIDOffice of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

EHRM INFRASTRUCTURE

UPGRADES

COLMERY O'NEIL VA HEALTH CARE

21-116

Revisions: Date:

www. bancroft-ae.com

3300 Dundee RD.

Northbrook, IL 60062

T: 847.952.9362

ISSUED FOR BID R2 03-22-24

12/28/2023Bancroft Project No: 21-116

ADDENDUM #1 11-22-24

ICT - BUILDING 1 - LEVEL 1 CABLE TRAY

PLAN

JG JG

TT-B01-101

GENERAL NOTES

A. FOR GENERAL NOTES AND LEGENDS REFER TO SHEET TT-00-001.

B. EXISTING IT / TR / OI&T ROOMS BEING RENOVATED OR RELOCATED TO REMAIN ACTIVE DURING CONSTRUCTION.

G.C. TO PROTECT EQUIPMENT FROM DUST, DEBRIS, OR OTHER DAMAGE DURING CONSTRUCTION WITH PRODUCT SUCH AS VISQUEEN. CONTRACTOR TO ENSURE CONTINUOUS OPERATION OF EQUIPMENT, INCLUDING PROPER VENTILATION / COOLING.

C. NOT ALL KEY NOTES APPLY TO ALL PLAN SHEETS. G.C. TO APPLY ONLY AS INDICATED PER EACH SHEET.

D. APPLY FIRE RATED SEALANT TO ALL EXISTING PENETRATIONS IN EXISTING WALLS THAT THE CONTRACTOR

USES / REUSES. FIRE RATING OF EXISTING WALLS SHALL BE A MINIMUM OF 1 HR ASSEMBLY OR MATCH FIRE RATING OF EXISTING PARTITION IF MORE THAN 1 HOUR. BASIS OF DESIGN FOR 1 HR WALL IS UL 419 ASSEMBLY.

E. CONTRACTOR SHALL PROVIDE AND INSTALL NEW MECHANICAL FIRE RATED SLEEVES AS NECESSARY AND ASSEMBLED PER UL DETAIL APPROPRIATE FOR WALL / FLOOR AND RACEWAY / CABLE TYPES. MINIMUM FIRE

RATING SHALL BE 1 HOUR, OR MATCH FIRE RATING OF EXISTING PARTITION.

FLOOR PLAN KEYNOTESX

FLOOR PLAN LEGEND

BASKET CABLE TRAY.

1. PROVIDE BASKET TYPE CABLE TRAY TO SUPPORT OPTICAL FIBER BACKBONE AND NEW CAT 6A HORIZONTAL CABLING. CABLE TRAY TO BE SIZED AS PER CABLE TRAY CAPACITY PLANNING ON FLOOR PLAN LEGEND.

2. ASSUMING 40% TOTAL FILL CAPACITY, INITIAL FILL SHALL BE 20% WITH 20% OF SPARE CAPACITY (WHICH

EQUATES TO 50% FUTURE CAPACITY).

3. ROUTING SHOWN INDICATES PRIMARY PATHWAYS. IN ADDITION TO PRIMARY PATHWAYS, CABLE TRAY SHALL

BE PROVIDED WHEN CABLE BUNDLES EXCEED 24 CABLES.

4. MECHANICAL FIRE RATED SLEEVE ASSEMBLIES SHALL BE PROVIDED WHEN PASSING THROUGH FIRE RATED PARTITIONS. ASSUMING 40% FILL, INSTALL ONE (1) EMPTY MECHANICAL FIRE SLEEVE FOR EVERY TWO (2) FILLED FIRE SLEEVES, THUS PROVIDING 50% SPARE CAPACITY. MINIMUM OF ONE (1) EMPTY MECHANICAL FIRE

RATE SLEEVE PER PENETRATION LOCATION.

4 12

CF105/300

CF105/450

CF105/500

CF105/600

CF150/150

CF150/200

CF150/300

CF150/450

CF150/500

CF150/600

CF150/900

CATALOG

NUMBER

DEPTH

(IN)

WIDTH

(IN)

CAT 6A 4-pr

PLENUM

(0.35" DIA.)*

50% FILL

CAT 6A 4-pr

PLENUM

(0.35" DIA.)*

40% FILL

CAT 6A 4-pr

PLENUM

(0.35" DIA.)*

20% FILL

248 198 100 373 298 149 414 331 166 497 398 199

186 149 74 238 190 95 357 286 143 536 429 214 596 477 238 715 572 286

1078 862 431

* : FILL RATIO CALCULATIONS BASED ON WORST CASE SCENARIO.

CONTRACTOR SHALL PERFORM FILL CALCULATIONS BASED ON ACTUAL CAT 6A

CABLE BEING INSTALLED AND SUBMIT TO BOTH THE VA AND ENGINEER.

- CABLE TRAY CAPACITY PLANNING CHART

- PROPOSED CABLE TRAY

=> CABLOFIL 4" DEEP x 12" WIDE MINIMUM

-- (SIZE COMMENSURATE WITH DISTRIBUTION REQUIREMENTS)

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

KEY PLAN

AutoCAD SHX Text N

AutoCAD SHX Text

AutoCAD SHX Text 4'

AutoCAD SHX Text 8'

AutoCAD SHX Text 16'

AutoCAD SHX Text 32'

AutoCAD SHX Text 1/16"=1'-0"

AutoCAD SHX Text

AutoCAD SHX Text

BUILDING 1 - LEVEL 1 CABLE TRAY PLAN

AutoCAD SHX Text

NORTH

AutoCAD SHX Text

KEY PLAN

N

A213 A212

A221A A220

A214

A219

A217 A215

A2-03 A221E A212EA216A A218

A218A A218B A221 DNDN DN

DN UPDNUP

UP

UP UP

A229C

A226

A222FA212A

A222

A211

A203E

A204

A202E

A202A A202A203

A223

A229B

A229E

A225

A226E

A227

B201

A230A A230F A2

B202

B226E

B211M B230

A2-04

A2-01

A2-05

A2-02

B2-01

B2-02

B211

A228

B216E

B223A B223

B223B

B220B

B2

B218A

B217

B224A

B224

B219

B225

B221A B222

B226

B221B

B221

B231

B231C

B2

A

B231B

B230A

B213

B214

B231D

B2

G

A229

A229A

B212

B215

B210

B210A

B204 B204C

B205

B206 B206F

B208A

B208

B2

B

B208C B209AB209

B2

B

B2

B2

B

B204A

B203

C208A

C208B

C208M

C208

C203E

C211E C201F

C204 C207C206

C210 C210A

C211

C203

C212

C213

C214

C202

C2-01 C209

C215

C201A

C201

C201B A232A231 A233

C2-02

A234

A235A

A236

A201

A201A

B216

B2-04

B2-03 B218B215F

A2-E1

A2-E2

A2-E3 A2-E4

A223

A206F

A207 A206D

A206E A206C

A208

A209A

A209

A210

A210A A2-04

A206 A206B

A206A

B226A

A223A

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

K:

\C

C G

_P R

O

JE

C

TS

\2

1\

-1

T op ek a

EH

R M

C

1R

\4

- D es

D oc s\

2- D ra w in gs

\W O

R

KI

N G

\A ut oC

AD

\T T-

B0 1-

2.

dw g

/7

/2

5:

:0

PM

ISSUE FOR BIDOffice of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

EHRM INFRASTRUCTURE

UPGRADES

COLMERY O'NEIL VA HEALTH CARE

21-116

Revisions: Date:

www. bancroft-ae.com

3300 Dundee RD.

Northbrook, IL 60062

T: 847.952.9362

ISSUED FOR BID R2 03-22-24

12/28/2023Bancroft Project No: 21-116

ADDENDUM #1 11-22-24

ICT - BUILDING 1 - LEVEL 2 CABLE TRAY

PLAN

JG JG

TT-B01-102

GENERAL NOTES

A. FOR GENERAL NOTES AND LEGENDS REFER TO SHEET TT-00-001.

B. EXISTING IT / TR / OI&T ROOMS BEING RENOVATED OR RELOCATED TO REMAIN ACTIVE DURING CONSTRUCTION.

G.C. TO PROTECT EQUIPMENT FROM DUST, DEBRIS, OR OTHER DAMAGE DURING CONSTRUCTION WITH PRODUCT SUCH AS VISQUEEN. CONTRACTOR TO ENSURE CONTINUOUS OPERATION OF EQUIPMENT, INCLUDING PROPER VENTILATION / COOLING.

C. NOT ALL KEY NOTES APPLY TO ALL PLAN SHEETS. G.C. TO APPLY ONLY AS INDICATED PER EACH SHEET.

D. APPLY FIRE RATED SEALANT TO ALL EXISTING PENETRATIONS IN EXISTING WALLS THAT THE CONTRACTOR

USES / REUSES. FIRE RATING OF EXISTING WALLS SHALL BE A MINIMUM OF 1 HR ASSEMBLY OR MATCH FIRE RATING OF EXISTING PARTITION IF MORE THAN 1 HOUR. BASIS OF DESIGN FOR 1 HR WALL IS UL 419 ASSEMBLY.

E. CONTRACTOR SHALL PROVIDE AND INSTALL NEW MECHANICAL FIRE RATED SLEEVES AS NECESSARY AND ASSEMBLED PER UL DETAIL APPROPRIATE FOR WALL / FLOOR AND RACEWAY / CABLE TYPES. MINIMUM FIRE

RATING SHALL BE 1 HOUR, OR MATCH FIRE RATING OF EXISTING PARTITION.

FLOOR PLAN KEYNOTESX

FLOOR PLAN LEGEND

BASKET CABLE TRAY.

1. PROVIDE BASKET TYPE CABLE TRAY TO SUPPORT OPTICAL FIBER BACKBONE AND NEW CAT 6A HORIZONTAL CABLING. CABLE TRAY TO BE SIZED AS PER CABLE TRAY CAPACITY PLANNING ON FLOOR PLAN LEGEND.

2. ASSUMING 40% TOTAL FILL CAPACITY, INITIAL FILL SHALL BE 20% WITH 20% OF SPARE CAPACITY (WHICH

EQUATES TO 50% FUTURE CAPACITY).

3. ROUTING SHOWN INDICATES PRIMARY PATHWAYS. IN ADDITION TO PRIMARY PATHWAYS, CABLE TRAY SHALL

BE PROVIDED WHEN CABLE BUNDLES EXCEED 24 CABLES.

4. MECHANICAL FIRE RATED SLEEVE ASSEMBLIES SHALL BE PROVIDED WHEN PASSING THROUGH FIRE RATED PARTITIONS. ASSUMING 40% FILL, INSTALL ONE (1) EMPTY MECHANICAL FIRE SLEEVE FOR EVERY TWO (2) FILLED FIRE SLEEVES, THUS PROVIDING 50% SPARE CAPACITY. MINIMUM OF ONE (1) EMPTY MECHANICAL FIRE

RATE SLEEVE PER PENETRATION LOCATION.

4 12

CF105/300

CF105/450

CF105/500

CF105/600

CF150/150

CF150/200

CF150/300

CF150/450

CF150/500

CF150/600

CF150/900

CATALOG

NUMBER

DEPTH

(IN)

WIDTH

(IN)

CAT 6A 4-pr

PLENUM

(0.35" DIA.)*

50% FILL

CAT 6A 4-pr

PLENUM

(0.35" DIA.)*

40% FILL

CAT 6A 4-pr

PLENUM

(0.35" DIA.)*

20% FILL

248 198 100 373 298 149 414 331 166 497 398 199

186 149 74 238 190 95 357 286 143 536 429 214 596 477 238 715 572 286

1078 862 431

* : FILL RATIO CALCULATIONS BASED ON WORST CASE SCENARIO.

CONTRACTOR SHALL PERFORM FILL CALCULATIONS BASED ON ACTUAL CAT 6A

CABLE BEING INSTALLED AND SUBMIT TO BOTH THE VA AND ENGINEER.

- CABLE TRAY CAPACITY PLANNING CHART

- PROPOSED CABLE TRAY

=> CABLOFIL 4" DEEP x 12" WIDE MINIMUM

-- (SIZE COMMENSURATE WITH DISTRIBUTION REQUIREMENTS)

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

KEY PLAN

AutoCAD SHX Text N

AutoCAD SHX Text

AutoCAD SHX Text 4'

AutoCAD SHX Text 8'

AutoCAD SHX Text 16'

AutoCAD SHX Text 32'

AutoCAD SHX Text 1/16"=1'-0"

AutoCAD SHX Text

AutoCAD SHX Text

BUILDING 1 - LEVEL 2 CABLE TRAY PLAN

AutoCAD SHX Text

NORTH

AutoCAD SHX Text

KEY PLAN

DN

UP

UP

DNA343

A327

B309F

B324E

B310

B310B B310A

B310E

B311 B309 B309B

B309A

A301

A331

A302E

A302

A335 A301E

A332A330A328

A327FA326E

A323 A322

A325

A324

A324A

A324C

A325E

A326

A326A

A321 A343F

A348A301A

A324B

A303

C307

C308

A315B

A314A315

A315A

A313 A313A

A312

A312A

A311 A311A

C3-3

A316

A319

A305

A329

A320

A318

A318A

A310

A306

A307 A307A

A308A317

A309

A304

A346 C301

C311

C306

C309

C305B

A3-04

C319

C318

C317

C314

C315

C313

C313A

C316

C320

C321

C322

C325

C326

C326A

C324

C323

C327

C313B

C328 C312

B312B3

A

B312B B314A B315

B315A

B317 B319A

B318AB319

B319C

B319B

B320

B3

B3

A

B3

B323B307

B325AB325B

C310

C303

C311A

C305

C305AA3

A347

A344

A347A

A3-06A3-05

A345

C329

C302

C304F C305E C306EA343A

C304 A326B

A333A

A333B

A333C

A3

D

B306E

B305

B122 B308

C305C

B3-01

C3-01A3-02 A300

A3-01

A322A

A3-E1

A3-E2

B304

B301A

B302 A337D B303

B303AA337F

B300

B301

A339B

A337B

A339A

A337 A338

A337C

A339

A338

A334B A322L

A334

B325

B326

B328

B329

A329A

A340A

A340

A341

A341A

A300B A3-E4A336

A3-E3

A3-03

A342E

A337E

B3-02

A3-01

A337A

A348A

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

K:

\C

C G

_P R

O

JE

C

TS

\2

1\

-1

T op ek a

EH

R M

C

1R

\4

- D es

D oc s\

2- D ra w in gs

\W O

R

KI

N G

\A ut oC

AD

\T T-

B0 1-

3.

dw g

/7

/2

5:

:0

PM

ISSUE FOR BIDOffice of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

EHRM INFRASTRUCTURE

UPGRADES

COLMERY O'NEIL VA HEALTH CARE

21-116

Revisions: Date:

www. bancroft-ae.com

3300 Dundee RD.

Northbrook, IL 60062

T: 847.952.9362

ISSUED FOR BID R2 03-22-24

12/28/2023Bancroft Project No: 21-116

ADDENDUM #1 11-22-24

ICT - BUILDING 1 - LEVEL 3 CABLE TRAY

PLAN

JG JG

TT-B01-103

GENERAL NOTES

A. FOR GENERAL NOTES AND LEGENDS REFER TO SHEET TT-00-001.

B. EXISTING IT / TR / OI&T ROOMS BEING RENOVATED OR RELOCATED TO REMAIN ACTIVE DURING CONSTRUCTION.

G.C. TO PROTECT EQUIPMENT FROM DUST, DEBRIS, OR OTHER DAMAGE DURING CONSTRUCTION WITH PRODUCT SUCH AS VISQUEEN. CONTRACTOR TO ENSURE CONTINUOUS OPERATION OF EQUIPMENT, INCLUDING PROPER VENTILATION / COOLING.

C. NOT ALL KEY NOTES APPLY TO ALL PLAN SHEETS. G.C. TO APPLY ONLY AS INDICATED PER EACH SHEET.

D. APPLY FIRE RATED SEALANT TO ALL EXISTING PENETRATIONS IN EXISTING WALLS THAT THE CONTRACTOR

USES / REUSES. FIRE RATING OF EXISTING WALLS SHALL BE A MINIMUM OF 1 HR ASSEMBLY OR MATCH FIRE RATING OF EXISTING PARTITION IF MORE THAN 1 HOUR. BASIS OF DESIGN FOR 1 HR WALL IS UL 419 ASSEMBLY.

E. CONTRACTOR SHALL PROVIDE AND INSTALL NEW MECHANICAL FIRE RATED SLEEVES AS NECESSARY AND ASSEMBLED PER UL DETAIL APPROPRIATE FOR WALL / FLOOR AND RACEWAY / CABLE TYPES. MINIMUM FIRE

RATING SHALL BE 1 HOUR, OR MATCH FIRE RATING OF EXISTING PARTITION.

FLOOR PLAN KEYNOTESX

FLOOR PLAN LEGEND

BASKET CABLE TRAY.

1. PROVIDE BASKET TYPE CABLE TRAY TO SUPPORT OPTICAL FIBER BACKBONE AND NEW CAT 6A HORIZONTAL CABLING. CABLE TRAY TO BE SIZED AS PER CABLE TRAY CAPACITY PLANNING ON FLOOR PLAN LEGEND.

2. ASSUMING 40% TOTAL FILL CAPACITY, INITIAL FILL SHALL BE 20% WITH 20% OF SPARE CAPACITY (WHICH

EQUATES TO 50% FUTURE CAPACITY).

3. ROUTING SHOWN INDICATES PRIMARY PATHWAYS. IN ADDITION TO PRIMARY PATHWAYS, CABLE TRAY SHALL

BE PROVIDED WHEN CABLE BUNDLES EXCEED 24 CABLES.

4. MECHANICAL FIRE RATED SLEEVE ASSEMBLIES SHALL BE PROVIDED WHEN PASSING THROUGH FIRE RATED PARTITIONS. ASSUMING 40% FILL, INSTALL ONE (1) EMPTY MECHANICAL FIRE SLEEVE FOR EVERY TWO (2) FILLED FIRE SLEEVES, THUS PROVIDING 50% SPARE CAPACITY.

This is the start of the file's text. The full file is on GovTribe.