Pages from Addendum1_Vol2_1of2__20241209.pdf
PDF 12 MB Posted
- Solicitation number
- 36C77624B0026_1
About this file
These are architectural drawings showing cable tray plans and electrical infrastructure upgrades for the VA Medical Center in Topeka, KS. The drawings detail telecommunications/IT infrastructure installations across multiple buildings (Buildings 1-5) and floor levels, including basement, first, second and third floors where applicable. The plans show basket cable tray routing, mechanical fire sleeve locations, and telecommunications room locations with specific requirements for CAT 6A cabling infrastructure.
The drawings include detailed capacity planning charts for cable tray sizing based on CAT 6A cable quantities, with specifications for 20% initial fill and 20% spare capacity (50% future capacity). Key requirements include basket type cable trays with minimum 4" depth x 12" width, fire-rated mechanical sleeve assemblies at partition penetrations, and maintaining maximum 295-foot cabling distances. The plans incorporate both normal and emergency power distribution, with separate conduit requirements for UPS power (on emergency critical branch) versus equipment power for cooling systems (on equipment branch). Detailed general notes address requirements for protecting existing equipment, coordinating with VA IT prior to work in data centers, and maintaining continuous operation of existing systems.
View the file
Other files
Show all 49
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
GENERAL - DRAWING INDEX (VOLUME 2
OF 3)
DA JM
G-003
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
K:
\C
C G
_P R
O
JE
C
TS
\2
1\
-1
T op ek a
EH
R M
C
1R
\4
- D es
D oc s\
2- D ra w in gs
\W O
R
KI
N G
\A ut oC
AD
\G
3-
VO
L2 .d w g
3/
/2
5:
:0
PM
ISSUE FOR BIDOffice of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
EHRM INFRASTRUCTURE
UPGRADES
COLMERY O'NEIL VA HEALTH CARE
21-116
Revisions: Date:
www. bancroft-ae.com
3300 Dundee RD.
Northbrook, IL 60062
T: 847.952.9362
03/22/2024Bancroft Project No: 21-116ISSUE FOR BID R2 03-22-24
ADDENDUM #1 11-15-24
OS
TO NORMAL PNL
TO EM PNL
OS
TO NORMAL PNL
TO EM PNL
OS4
TO EM PNL
TO NORMAL PNL
A/C
TO PNL
TO NORMAL PNL
TO EM PNL
2 3 2 3
CORRIDOR
A/C
TO PNL TO EM PNL
2 3
TO NORMAL PNL
A/C
TO PNL
TO EM PNL
TO NORMAL PNL
3 OS
TO NORMAL PNL
TO EM PNL
A/C
TO PNL
TO EM PNL
TO NORMAL PNL
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
K:
\C
C G
_P R
O
JE
C
TS
\2
1\
-1
T op ek a
EH
R M
C
1R
\4
- D es
D oc s\
2- D ra w in gs
\W O
R
KI
N G
\A ut oC
AD
\E le ct ric al \E
3.
dw g
/2
0/
:1 0:
A
M
ISSUE FOR BIDOffice of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
EHRM INFRASTRUCTURE
UPGRADES
COLMERY O'NEIL VA HEALTH CARE
21-116
Revisions: Date:
www. bancroft-ae.com
3300 Dundee RD.
Northbrook, IL 60062
T: 847.952.9362
03/22/2024Bancroft Project No: 21-116ISSUE FOR BID R2 03-22-24
GENERAL NOTES ELECTRICAL DEMOLITION:
A. NEW TR ROOMS SHALL BE PREPARED SUCH THAT WHEN COMPLETED, ONLY CIRCUITRY SHOWN
ON DRAWING E003 REMAINS. ALL PREVIOUS CIRCUITRY SHALL BE REMOVED BACK TO SOURCES.
B. REMOVE AVERAGE OF TWO LIGHTING FIXTURES, CONDUIT AND SWITCH(ES) BACK TO BRANCH
PANEL, AND PROPERLY DISPOSE OF FIXTURES, BALLASTS, AND ALL HARDWARE, FROM NEW TR
ROOM AREA.
C. REMOVE AVERAGE OF THREE RECEPTACLES (EMERGENCY AND NORMAL POWER) AND CONDUIT
BACK TO BRANCH PANEL, FROM TR ROOM AREA.
D. CERTIFIED FIRE PROTECTION CONTRACTOR TO REMOVE FIRE ALARM / FIRE DETECTION
COMPONENT FROM NEW TR ROOM AREA. THIS IS NOTED ON SPECIFIC DRAWINGS.
E. CERTIFIED FIRE PROTECTION CONTRACTOR TO DOCUMENT LOCATIONS OF FIRE ALARM / FIRE
DETECTION COMPONENTS REMOVED OR RELOCATED TO THEN UPDATE THE FIRE ALARM / FIRE
DETECTION ALARM SOFTWARE. SOME FIRE ALARM / FIRE DETECTION COMPONENTS REMAIN
BUT ARE RELOCATED. NO NEW FIRE ALARM / FIRE DETECTION ARE INSTALLED AS PART OF THE
EHRM PROJECT.
GENERAL NOTES ELECTRICAL:
A. CONTACT VA IT PRIOR TO WORKING IN DATA CENTER OR IT CLOSET.
B. USE PRECAUTIONS TO AVOID SNAGGING WIRING OR DAMAGING EQUIPMENT.
C. PROTECT IT EQUIPMENT FROM DUST, DURING WORK THAT CREATES DUST.
D. A WIRING MATRIX IS SHOWN FOR EVERY NEW TR ROOM. BREAKER SIZES ARE LISTED FOR UPS
AND OTHER EHRM ROOM EQUIPMENT. UTILIZE 20A CIRCUIT BREAKERS FOR ROOM LIGHTS AND
WALL RECEPTACLES (SIZES ARE NOT SHOWN ON DRAWINGS).
TR ROOM SPECIFIC NOTES:
A. RECEPTACLES TO POWER RACKS SHALL ALWAYS BE ABOVE RACKS.
B. POWER TO ONE, TWO, OR THREE RACKS AS SHOWN ON THIS DRAWING.
C. POWER FOR FOUR RACKS IS A COMBINATION OF THREE RACK AND ONE RACK DETAILS.
E. POWER FOR SIX RACKS IS A COMBINATION OF TWO THREE RACK DETAILS.
F. INSTALL LIGHTING CONTROLS PER nlight LIGHTING DETAIL ON DETAIL DRAWING .
G. NOTE THAT ONLY FAN COIL POWER IS REQUIRED IN BUILDINGS WITH CHILLED WATER.
H. BUILDINGS THAT DO NOT HAVE CHILLED WATER NEED POWER TO FAN COIL (EVAPORATOR) AND
ALSO POWER TO THE OUTDOOR CONDENSERS. SEE SUGGESTED WIRING DETAIL ON DRAWING
E-501. IF SELECTED VENDOR WIRING DETAIL IS DIFFERENT FOLLOW THE VENDOR'S WIRING
DETAIL.
I. SOME VENDOR'S EVAPORATOR UNITS DO NOT PROVIDE POWER TO THE SMALL CONDENSATE
PUMP. FOR THESE SITUATIONS INSTALL A 15A 1-POLE DISCONNECT FROM THE ROOM EM
LIGHTING CIRCUIT.
1. ONLY BRANCH CIRCUIT SHOWN FROM POWER PANEL TO COOLING UNIT, ELECTRICAL
CONTRACTOR TO WORK WITH MECHANICAL CONTRACTOR TO ROUTE POWER AND TUBING
TO OUTDOOR UNIT.
2. NORMAL POWER TO ROOM RECEPTACLES, AND LIGHTS, AND RACKS. CONTACT COR PRIOR
TO INSTALLING LIGHTING TO DETERMINE OPTIMUM LOCATION FOR LIGHT FIXTURES.
3. EMERGENCY POWER TO ROOM RECEPTACLES, AND LIGHTS, AND RACKS. CONTACT COR
PRIOR TO INSTALLING LIGHTING TO DETERMINE OPTIMUM LOCATION FOR LIGHT FIXTURES.
4. OCCUPANCY SENSOR - HIGH MOUNT.
ELECTRICAL - TR ROOMS LIGHTING
AND POWER EXAMPLE
WG BX E-003
ADDENDUM #1 11-20-24
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text
AutoCAD SHX Text 1'
AutoCAD SHX Text 2'
AutoCAD SHX Text 4'
AutoCAD SHX Text 8'
AutoCAD SHX Text 1/4"=1'-0"
AutoCAD SHX Text
AutoCAD SHX Text
EXAMPLE - LIGHTING PLAN FOR FOUR RACK ROOM
AutoCAD SHX Text
AutoCAD SHX Text 1'
AutoCAD SHX Text 2'
AutoCAD SHX Text 4'
AutoCAD SHX Text 8'
AutoCAD SHX Text 1/4"=1'-0"
AutoCAD SHX Text
AutoCAD SHX Text
EXAMPLE - POWER PLAN FOR FOUR RACK ROOM
AutoCAD SHX Text
AutoCAD SHX Text 1'
AutoCAD SHX Text 2'
AutoCAD SHX Text 4'
AutoCAD SHX Text 8'
AutoCAD SHX Text 1/4"=1'-0"
AutoCAD SHX Text
AutoCAD SHX Text
EXAMPLE - LIGHTING PLAN FOR TWO RACK ROOM
AutoCAD SHX Text
AutoCAD SHX Text 1'
AutoCAD SHX Text 2'
AutoCAD SHX Text 4'
AutoCAD SHX Text 8'
AutoCAD SHX Text 1/4"=1'-0"
AutoCAD SHX Text
AutoCAD SHX Text
EXAMPLE - POWER PLAN FOR TWO RACK ROOM
AutoCAD SHX Text
AutoCAD SHX Text 1'
AutoCAD SHX Text 2'
AutoCAD SHX Text 4'
AutoCAD SHX Text 8'
AutoCAD SHX Text 1/4"=1'-0"
AutoCAD SHX Text
AutoCAD SHX Text
EXAMPLE - LIGHTING PLAN FOR THREE RACK ROOM
AutoCAD SHX Text
AutoCAD SHX Text 1'
AutoCAD SHX Text 2'
AutoCAD SHX Text 4'
AutoCAD SHX Text 8'
AutoCAD SHX Text 1/4"=1'-0"
AutoCAD SHX Text
AutoCAD SHX Text
EXAMPLE - POWER PLAN FOR THREE RACK ROOM
AutoCAD SHX Text
AutoCAD SHX Text 1'
AutoCAD SHX Text 2'
AutoCAD SHX Text 4'
AutoCAD SHX Text 8'
AutoCAD SHX Text 1/4"=1'-0"
AutoCAD SHX Text
AutoCAD SHX Text
EXAMPLE - LIGHTING PLAN FOR ONE RACK ROOM
AutoCAD SHX Text
AutoCAD SHX Text 1'
AutoCAD SHX Text 2'
AutoCAD SHX Text 4'
AutoCAD SHX Text 8'
AutoCAD SHX Text 1/4"=1'-0"
AutoCAD SHX Text
AutoCAD SHX Text
EXAMPLE - POWER PLAN FOR ONE RACK ROOM
AutoCAD SHX Text
ELECTRICAL GENERAL NOTES
AutoCAD SHX Text
ELECTRICAL KEY NOTES
AutoCAD SHX Text
UP
UP
UP
UP
UP
UP
UP
UP
UP
UP
UP
UP
DN
A
B
C
D
E
F
1 3 4 5 11 13 16 18 19 21 23 25 26 27 286 8 9
11.1
14 15 17
K
L
M
29 30
G
O
Q
S
T
U
V
P
S.2
S.1
Q.1
U.1
V.1
V.2
W.1
X
Y
8.26.36.2 10.19.3 12.111.23.8
Z.4
4.7 6.1 8.1 11.7
Z.3
Z.2
24 31 32
N
7 222010 12
18B 20B 22B 24B 24C
H
I
J
R
W
Z.1
22D
UPUP
UP
B23
B23G
B23A B23B
B23E B23D B23C
C03A
A9E
A9C A9D
B5
C3
A17
A12
A30
A21
A21E
A21A
A13A A13B
A1
A10F
A3B
A3
A3A
A13
A20E
A20
A17F
C7
C7B
C4EC3EC3F
A19D
C7A
C7G
C7C
C7D
A19
C5
C7H
C7I
C6A19B
C1A18
A18A C2
A17A
A5
B1E
A7A8A9
A10E
A10
A4
A7E
A9A
A11
A14
A15
B4
B3
B13E
B22
B14A
B14
A2
A2A
A2B
A2C A2D
A19DC0-1
C8A
C20
C23
C24 C25
C28
C27
C26
C22 C21
C18C19
C17
C8
C9
C12
C14
C8B
C10 C11
C13
C15 C14A
C14B C14C
C16 C16A
C04
A16D
B2 B2B
B2A
B15B16 B17
B1
A16
A16C
A16A
A16E A16B
B22E
B1B
C0-2
C1A
B21
A19C
B1C
B6C
A16G
A9B
B43M B42
B42A B39
B38
C0-5B
C0-5A
C0-3
A9C
C114C
C11A
CB-8
B6D
A0-E3
A0-E1
A0-E2
A0-E4
B42B
B41
B40
B6P
B6 B8A
B7
B13CB13
B12
B9
B10
B11
B11A
B6M
B7M
B8 C0-3E
C0-3C
C0-3B B8C
B13B
B13A
A10G
A10B
A10A
A10C A10D
B20
B23F
C20A A19A
1/A-01-100.2
1/A-01-100.3
1/A-01-100.1
1/A-01-100.3
1/A -01
-10 0.2
1/A -01
-10 0.1
1/A-01-100.3
1/A-01-100.4
1/A-01-100.3
1/A-01-100.4
1/A-01-100.3
1/A-01-100.5
1/A -01
-10 0.5
1/A -01
-10 0.4
A7E
A14
A20E
B13E
B22E
C3E C4E
BD BA
-2
BA
BA
-1
EM BC
-1
BB-1
LS-BB
BB-2
MP1-B
PP1-B
ELS1-B
ECR1-B
EE1-B
C20A
B3
SECURITY PANEL
ECB-SURGERY
ATS-RADIOLOGY
DPEM
B C T
EDS
CBDP
ELEVATOR DP
ECB-2
EBTR
EBDP-1
LSDP
1200A
ATS-CBTJ-1
0 K
VA
0/2
V
EBDP-2
400A UPSTS ATS
LSTS-1 400A DISC
BP
UPSTS
400A DISCEDP
PU
LL
BO
X
ME
TE
R
AT
S
FIR
E P
UM
P
DIS
C B
LD
G 5
30 KVA
208/120V
EM-TELECOM
CBDP-2, EM
A2 EB
TS
-2
TRANSFER SWITCHTR
EM-ATS C-2
LS&C-ATS C-1
SW
ITC
HB
OA
RD
DP
1-B
AT
S
TR
0 M
CM
EM PNL, ES-1
EM PNL, ES-1A
BC
BOX
A19A
1-B-E-EHRM
1-B-N-EHRM
NORMAL CONDUIT # 1, 2, 3, 4, 5
EM CONDUIT # 1, 2, 3, 4, 5
NORMAL CONDUIT # 1, 2, 3, 4, 5
NORMAL CONDUIT # 6, UP
NORMAL CONDUIT # 7
EM CONDUIT # 7
EMERGENCY CONDUIT # 6, UP
ELECTRICAL - BUILDING 1 - BASEMENT
LEVEL PLAN
WG BX
EP-B01-100
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
K:
\C
C G
_P R
O
JE
C
TS
\2
1\
-1
T op ek a
EH
R M
C
1R
\4
- D es
D oc s\
2- D ra w in gs
\W O
R
KI
N G
\A ut oC
AD
\E le ct ric al \E
P- B0
1-
0.
dw g
/2 0/
0:
:3
AM
ISSUE FOR BIDOffice of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
EHRM INFRASTRUCTURE
UPGRADES
COLMERY O'NEIL VA HEALTH CARE
21-116
Revisions: Date:
www. bancroft-ae.com
3300 Dundee RD.
Northbrook, IL 60062
T: 847.952.9362
03/22/2024Bancroft Project No: 21-116ISSUE FOR BID R2 03-22-24
A. THIS PROJECT ALSO INVOLVES RESOLVING ELECTRICAL DEFICIENCIES. THIS WORK IS SHOWN ON
SEPARATE DRAWINGS FROM TR ROOM DRAWINGS.
B. EACH TR ROOM INVOLVES THREE TYPES OF WIRING:
a. POWER TO RACKS, SEE DRAWINGS E-003 AND E-004 FOR DETAILS.
b. POWER TO RECEPTACLES AND LIGHTING SHOWN FOR EACH TR ROOM.
c. POWER TOFAN COIL UNITS AND SPLIT COOLERS SEE DRAWING DETAIL E-501.
C. CONTRACTOR TO DETERMINE DETAILED CONDUIT ROUTING BASED ON FIELD CONDITIONS.
D. CONDUIT ON PLAN DRAWINGS IS SHOWN FOR GENERAL ROUTING PURPOSES ONLY. SEE WIRING
AND PANEL DRAWINGS FOR WIRING AND CONDUIT SIZES.
E. WHEN WALLS ARE DEMOLITIONED THAT CONTAIN RECEPTACLES FEEDING EQUIPMENT,
CONTRACTOR TO RELOCATE RECEPTACLES TO REMAINING WALL TO CONTINUE POWERING
REMAINING EQUIPMENT. IF NO CONNECTED EQUIPMENT REMAINS CONNECTED TO
DEMOLITIONED WALLS, CONTRACTOR TO REMOVE THE WIRING AND CONDUIT BACK TO THE
SOURCE.
F. UPS POWER IS ON THE EMERGENCY CRITICAL BRANCH AND MUST BE IN SEPARATE CONDUITS
FROM NORMAL POWER.
G. EQUIPMENT POWER TO TECHNOLOGY ROOM FANS AND CONDENSERS IS FROM EQUIPMENT
BRANCH OF EMERGENCY POWER AND MUST BE IN CONDUITS SEPARATE FROM NORMAL POWER.
CONDUITS FROM TR ROOMS TO OUTDOOR CONDENSERS WILL USE SAME ROUTING AND
SUPPORTS AS CONDENSER REFRIGERANT TUBING.
H. CONTACT VA IT PRIOR TO WORKING IN IT CLOSET.
I. FOLLOW VA & NFPA 70E LOCK OUT TAG OUT PROCEDURES FOR SAFETY.
J. SEE THE ELECTRICAL EQUIPMENT SCHEDULE FOR EQUIPMENT DETAILS.
K. SEE PANEL SCHEDULES ON DRAWING SERIES E600 FOR PANEL SCHEDULES AND CIRCUIT
NUMBERS.
L. SEE DRAWING SERIES E700 FOR SINGLE LINE DRAWINGS.
M. UPS POWER TO RACKS / CABINETS IN NEW TR's MUST BE PROVIDED TO THE TOP OF THE RACKS /
CABINETS. NO POWER WIRING ON FLOORS!
N. INSTALL LIGHTING FIXTURES PER LIGHTING SCHEDULE. CONTACT COR PRIOR TO INSTALLING
LIGHTING TO DETERMINE OPTIMUM LOCATION FOR LIGHT FIXTURES.
O. INSTALL LIGHTING CONTROLS PER Nlight DETAIL ON DRAWING E-501.
1. SEE FEEDER SCHEDULE ON THIS DRAWING. CONTRACTOR TO EXAMINE ELECTRICAL CLOSET
DIRECTLY ABOVE TO DETERMINE WHERE TO CORE DRILL TO ROUTE THE CONDUITS FROM BELOW
INTO ELECTRICAL ROOMS ABOVE. FLOOR MUST BE X-RAYED TO AVOID CUTTING REBARS. TO
MINIMIZE CONCENTRATION OF CONDUITS IN AREA SHOWN, CONTRACTOR MAY ROUTE SOME
CONDUITS INTO TR ROOM A19A, THEN UP TO 1ST FLOOR IT ROOM A101D. CONTINUE ON
DRAWING EP-B01-101
ADDENDUM #1 11-20-24
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text N
AutoCAD SHX Text
AutoCAD SHX Text 4'
AutoCAD SHX Text 8'
AutoCAD SHX Text 16'
AutoCAD SHX Text 32'
AutoCAD SHX Text 1/16"=1'-0"
AutoCAD SHX Text
AutoCAD SHX Text
BUILDING 1 - BASEMENT LEVEL PLAN
AutoCAD SHX Text
ELECTRICAL GENERAL NOTES
AutoCAD SHX Text
ELECTRICAL KEY NOTES
1/A-01-101.2
1/A-01-101.3
1/A-01-101.1
1/A-01-101.3
1/A -01
-10 1.2
1/A -01
-10 1.1
1/A-01-101.3
1/A-01-101.4
1/A-01-101.3
1/A-01-101.4
UP
UP
UP
UP
UP
UP
DN
UP
DN
UP
UPUP
UP
A
B
C
D
E
F
1 3 4 5 11 13 16 18 19 21 23 25 26 27 286 8 9
11.1
14 15
K
L
M
29 30
G
O
Q
S
T
U
V
P
S.2
S.1
Q.1
U.1
V.1
V.2
W.1
X
Y
8.26.36.2 10.19.3 12.111.2
2.1
3.1
4.1
3.8
Z.4
4.7 6.1 8.1 11.7
Z.3
Z.2
24 31 32
N
7 222010 12
18B 20B 22B 24B 24C
H
I
J
R
W
Z.1
22D
AC101A AC130
AC101B
AC101C
AC133
AC128
AC129 AC134 AC135
AC131
AC131
AC101D
AC136
B1-03C
AC119
B113
AC127A
AC127B
C100
AC100
AC101
AC104
A140
A141A128C
A1
B103 B105
C110C109C107 C108
C116F C116A
C116
C116B
C105
C104
C106
C115
A1
A143F
A121AA119A118
A117A
A116B
A116A
A120 A121 A121B
A115
A115H
A115A A115I
A115J
A115BA115C
A115G
A122
A115E
A121E A122F
A102G
A102A
A1
A102BA102C
A102D
A108
A109
AC101J
AC101I
AC101H
AC101G
A127 A127BA127A
C116C
C116D
C119
C120C124
C125
C121
C122
C123
C123BC123A
C126
C127
C1-02
A145
C117 C104F C116E C105E
A143
A102E A101E
C102C101A144 C103
A111
A112
A104A
A104
A106
A105A110
A136
B149B1
B116
B148
B147
B146
AC120A
AC120
A116HA116G
A116E A116F
A116D
A116C
A116
A107
A104B
A115D
AC119AC118AC115
AC112
AC112A
AC114
AC109
A135
B145
B133
B134
B136 B135
B131 B132B130
B138
B129
B139B140
B128
B127
B137
B126
B141
B124B119
B123E
B143 B142
B133AB120
B143E
B120F
AC135
AC110
AC111
AC121
AC116E
AC122
AC122A
AC125
AC106E
AC113
AC124
AC123
AC117
B118
A137
B117A
A134A
C113 C112C111
C114D
C114-E
C114B
C114C
C114C
C114-W
C1-03A103
B123 B125
A1-04 A1-03
A140E
A134
A128B
A128D
A128A
AC105AC106
A1
A
A129
A128H A128G
AC108
AC1-5
B114
B106B107
B108
B113
B109A B109
B111
B1
B115
B104
B116C
B116D B1-03
A1-01
A101
A138
A142A
AC101K
B1-04B1-01
B1-02
A101A
A101G A101C
A113
B101
A101D
A141E
C1-01
C114T
A114
AC147 AC148 AC149 AC150 AC151 AC152 AC153 AC154 AC155 AC156
AC158 AC157
AC165AC164AC161
AC160
AC143 AC143A
AC145AC146
AC144 AC141 AC162 AC163 AC166
AC167
AC
1-
AC
1-
AC
1-
A615P
A6
Q
AC1-2
AC159
A1-02
A1-E1
A1-E2
A1-E3 A1-E4
A101H
A101J
AC134A AC136AAC135A
AC134C B1-03D
B116A
1/A-01-101.3
1/A-01-101.5
1/A -01
-10 1.5
1/A -01
-10 1.3
A101E
A115E
AC106E
AC116E
AC144
B143E
C116E
C105E
A102E
A121E
A141E
A140E
B123E
LS-1A1A
ECR1-1 ECR2-1
LS
-1C
1C -1
1C -2
LS-1B
1B
LP1-1
PP1-1
PP2-1
ID-
ID-
AC160
B116A
A144A
PP3-1
ECR3-1
1-1-N-EHRM
1-1 -E-
EH
RM
NORMAL CONDUIT # 1, 2, 3, 4, 5
EM CONDUIT # 1, 2, 3, 4, 5
NORMAL CONDUIT # 6
EM CONDUIT # 6
ELECTRICAL - BUILDING 1 - LEVEL 1
PLAN
WG BX
EP-B01-101
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
K:
\C
C G
_P R
O
JE
C
TS
\2
1\
-1
T op ek a
EH
R M
C
1R
\4
- D es
D oc s\
2- D ra w in gs
\W O
R
KI
N G
\A ut oC
AD
\E le ct ric al \E
P- B0
1-
1.
dw g
/2 0/
0:
:4
AM
ISSUE FOR BIDOffice of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
EHRM INFRASTRUCTURE
UPGRADES
COLMERY O'NEIL VA HEALTH CARE
21-116
Revisions: Date:
www. bancroft-ae.com
3300 Dundee RD.
Northbrook, IL 60062
T: 847.952.9362
03/22/2024Bancroft Project No: 21-116ISSUE FOR BID R2 03-22-24
A. THIS PROJECT ALSO INVOLVES RESOLVING ELECTRICAL DEFICIENCIES. THIS WORK IS SHOWN ON
SEPARATE DRAWINGS FROM TR ROOM DRAWINGS.
B. EACH TR ROOM INVOLVES THREE TYPES OF WIRING:
a. POWER TO RACKS, SEE DRAWINGS EP-01-500 AND EP-01-501 FOR DETAILS,
b. POWER TO FAN COIL UNITS AND SPLIT COOLERS SEE DRAWING DETAIL ???,
c. POWER TO RECEPTACLES AND LIGHTING SHOWN FOR EACH TR ROOM.
C. CONTRACTOR TO DETERMINE DETAILED CONDUIT ROUTING BASED ON FIELD CONDITIONS.
D. CONDUIT ON PLAN DRAWINGS IS SHOWN FOR GENERAL ROUTING PURPOSES ONLY. SEE WIRING
AND PANEL DRAWINGS FOR WIRING AND CONDUIT SIZES.
E. WHEN WALLS ARE DEMOLITIONED THAT CONTAIN RECEPTACLES FEEDING EQUIPMENT,
CONTRACTOR TO RELOCATE RECEPTACLES TO REMAINING WALL TO CONTINUE POWERING
REMAINING EQUIPMENT. IF NO CONNECTED EQUIPMENT REMAINS CONNECTED TO
DEMOLITIONED WALLS, CONTRACTOR TO REMOVE THE WIRING AND CONDUIT BACK TO THE
SOURCE.
F. UPS POWER IS ON THE EMERGENCY CRITICAL BRANCH AND MUST BE IN SEPARATE CONDUITS
FROM NORMAL POWER.
G. EQUIPMENT POWER TO TECHNOLOGY ROOM FANS AND CONDENSERS IS FROM EQUIPMENT
BRANCH OF EMERGENCY POWER AND MUST BE IN CONDUITS SEPARATE FROM NORMAL POWER.
CONDUITS FROM TR ROOMS TO OUTDOOR CONDENSERS WILL USE SAME ROUTING AND
SUPPORTS AS CONDENSER REFRIGERANT TUBING.
H. CONTACT VA IT PRIOR TO WORKING IN IT CLOSET.
I. FOLLOW VA & NFPA 70E LOCK OUT TAG OUT PROCEDURES FOR SAFETY.
J. SEE THE ELECTRICAL EQUIPMENT SCHEDULE FOR EQUIPMENT DETAILS.
K. SEE PANEL SCHEDULES ON DRAWING SERIES E600 FOR PANEL SCHEDULES AND CIRCUIT
NUMBERS.
L. SEE DRAWING SERIES E700 FOR SINGLE LINE DRAWINGS.
M. UPS POWER TO RACKS / CABINETS IN NEW TR's MUST BE PROVIDED TO THE TOP OF THE RACKS /
CABINETS. NO POWER WIRING ON FLOORS!
N. INSTALL LIGHTING FIXTURES PER LIGHTING SCHEDULE. CONTACT COR PRIOR TO INSTALLING
LIGHTING TO DETERMINE OPTIMUM LOCATION FOR LIGHT FIXTURES.
O. INSTALL LIGHTING CONTROLS PER Nlight DETAIL ON DRAWING E502.
1. CONTINUE ROUTING CONDUITS FROM BELOW INTO ROOMS A141E AND A101D
2. CONSOLIDATE ALL CONDUITS INTO ROOM A141E AND ROUTE THEM TO UPPER FLOORS.
ADDENDUM #1 11-20-24
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text N
AutoCAD SHX Text
AutoCAD SHX Text 4'
AutoCAD SHX Text 8'
AutoCAD SHX Text 16'
AutoCAD SHX Text 32'
AutoCAD SHX Text 1/16"=1'-0"
AutoCAD SHX Text
AutoCAD SHX Text
BUILDING 1 - LEVEL 1 PLAN
AutoCAD SHX Text
ELECTRICAL GENERAL NOTES
ELECTRICAL KEY NOTES
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
K:
\C
C G
_P R
O
JE
C
TS
\2
1\
-1
T op ek a
EH
R M
C
1R
\4
- D es
D oc s\
2- D ra w in gs
\W O
R
KI
N G
\A ut oC
AD
\T T-
0-
1.
dw g
/2
5/
1:
:1
AM
ISSUE FOR BIDOffice of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
EHRM INFRASTRUCTURE
UPGRADES
COLMERY O'NEIL VA HEALTH CARE
21-116
Revisions: Date:
www. bancroft-ae.com
3300 Dundee RD.
Northbrook, IL 60062
T: 847.952.9362
ISSUE FOR BID R2 03-22-24
12/28/2023Bancroft Project No: 21-116
ADDENDUM #1 11-22-24
ICT - GENERAL NOTES, SYMBOLS +
ABBREVIATIONS
JG JG
TT-00-001
SX
SX
R
RM
TTB
S
SPEAKER, CEILING MOUNTED, "X" INDICATES THE TYPE, PROVIDE SCHEDULE ON LEGEND
SPEAKER, WALL MOUNTED, "X" INDICATES THE TYPE, PROVIDE SCHEDULE ON LEGEND
MTD. 7'-6" (2286mm) AFF UNLESS OTHERWISE NOTED
RADIO CHANNEL SELECTOR FACILITIES, MTD. 4'-6" (1372 mm) AFF
UNLESS OTHERWISE NOTED.
SPEAKER PROGRAM SELECTOR SWITCH & VOLUME CONTROL MTD.
4'-6" (1372 mm) AFF UNLESS OTHERWISE NOTED.
COMMUNICATION SYMBOLS
TELECOMMUNICATION TERMINAL CABINET
TELEPHONE BACKBOARD (WALL MOUNTED)
REMOTE DICTATING OUTLET MTD 1'-6" (457 mm) AFF. UNLESS OTHERWISE NOTED
INTERCOM STATION (REFER TO SPECS. FOR FUNCTIONAL
OPERATION OF INSTRUMENT & TYPE REQUIRED)
INTERCOM STAFF STATION.
ADO AUTOMATIC DOOR OPENER
WAP
PAS
SMS SOUND MASKING (WHITE NOISE) SYSTEM
SPEAKER.
EMS EMERGENCY MANAGEMENT SYSTEM TEXT-
TO-SPEECH WALL MOUNTED SPEAKER.
ICS INTERCOM SYSTEM SPEAKER.
PAS
PUBLIC ADDRESS SYSTEM
WALL MOUNTED SPEAKER
PAS
SOUND MASKING (WHITE NOISE) SYSTEM LOCAL
KEYPAD STATION
V
DB DURESS BUTTON
DAS ANTENNA CELLULAR
DAP
DAC
N P N D
N BI
N SA
N DS
N ST
N CB
D
N MS
Z
CR
AIP
CR/K
REX
KP
RX
ES
ML
CCP
MID
GB
DC
WS
DIVERSITY PATCH ANTENNA
NURSE CALL SYMBOLS
PA
ELECTRONIC SAFETY AND SECURITY SYMBOLS
SECURITY / DURESS-ALARM BUTTON MOUNTED 3" ABOVE COUNTER TOP
/ COUNTER TOP BACK SPLAH.
CEILING MOUNTED SECURITY CAMERA, X REPERSENTS VIEW RANGE OF CAMERA
WALL MOUNTED CARD READER
AIPHONE
KEYPAD LOCK
ACCESS CONTROL PANEL
ROOF POLE MOUNTED SECURITY CAMERA
CAMERA CONTROL PANEL
WALL MOUNTED CARD READER WITH KEYPAD
REQUEST TO EXIT MOTION
DOOR LOCKING MECHANISM/ELECT STRIKE
DOOR LOCKING MECHANISM/MAG LOCK
ACCESS CONTROL POWER SUPPLY
REQUEST TO EXIT PUSH BUTTON
MOTION INTRUSION DETECTOR
GLASS BREAK SENSOR
DOOR CONTACT
DOOR OPENER WAVE SENSOR FOR MOTORIZED DOOR
ESSEX ELECTORNICS #32NF3X.
NURSE CALL, WALL MOUNTED DOME LIGHT
NURSE CALL, WALL MOUNTED BED INTERFACE
NURSE CALL, WALL MOUNTED STAFF ASSIST
NURSE CALL, WALL MOUNTED DUTY STATION
NURSE CALL, CEILING MOUNTED DOME LIGHT
NURSE CALL, WALL MOUNTED PULL CORD
NURSE CALL, WALL MOUNTED STAFF TERMINAL
NURSE CALL, COUNTER MOUNTED MASTER STATION
NURSE CALL, WALL MOUNTED CODE BLUE
NURSE CALL ZONE LIGHT - CEILING MOUNTEDN
N
X
RFID WALL MOUNTED PATIENT WRISTBAND READER
OVER THE DOOR ALARM SENSOR PERVENTIVEDS
ACP
ACPS
WALL MOUNTED SECURITY CAMERA, X REPERSENTS VIEW RANGE OF CAMERAX
+H P#
P#
P#
+H P#
+H P#
E P#
E P#
CATV
CCTV
FO
T I S
NC
R C
CABLE TELEVISION LINE = CATV
CLOSED CIRCUIT TELEVISION LINE = CCTV. MINIMUM 1"
(25mm) CONDUIT
FIBEROPTICS LINE = FO
TELEPHONE LINE = T
INTERCOM LINE = I. MINIMUM 3/4" (19mm) CONDUIT.
SOUND LINE = S
NURSE CALL LINE = NC. MINIMUM 3/4" (19mm) CONDUIT.
RADIO CONDUIT RUN, MINIMUM 3/4" (19mm) CONDUIT.
TELECOMMUNICATIONS MANHOLE
GENERAL SYMBOLS
TV T#
H
TVT#
H
WALL MOUNTED - TELEPHONE OUTLET P# =
NUMBER OF VOICE / DATA PORTS IN FACEPLATE, IF
NOT SHOWN PROVIDE 1 PORTS + H =INSTALLATION
HEIGHT IN INCHES AT CENTER OF OUTLET, IF NOT
SHOWN INSTALL AT TYPICAL 18" RECEPTACLE
HEIGHT. COORDINATE WITH ELECTRICAL
WALL MOUNTED - VOICE / DATA OUTLET P# = NUMBER
OF VOICE / DATA PORTS IN FACEPLATE, IF NOT
SHOWN PROVIDE 4 PORTS + H =INSTALLATION HEIGHT
IN INCHES AT CENTER OF OUTLET, IF NOT SHOWN
INSTALL AT TYPICAL 18" RECEPTACLE HEIGHT.
COORDINATE WITH ELECTRICAL
CEILING MOUNTED - VOICE / DATA OUTLET P# =
NUMBER OF VOICE / DATA FACEPLATE, IF NOT
SHOWN PROVIDE 4 PORTS IN PORTS
FLOOR MOUNTED-TELEPHONE/DATA OUTLET
P# = NUMBER OF VOICE / DATA PORTS IN
FACEPLATE, IF NOT SHOWN PROVIDE 4
PORTS
WALL MOUNTED - GETWELL NETWORK DATA OUTLET
P# = NUMBER OF VOICE / DATA PORTS IN
FACEPLATE, IF NOT SHOWN PROVIDE 1 PORTS + H
=INSTALLATION HEIGHT IN INCHES AT CENTER OF
OUTLET, IF NOT SHOWN INSTALL AT TYPICAL 72"
RECEPTACLE HEIGHT. COORDINATE WITH
ELECTRICAL
CEILING MOUNTED - OUTLET FOR WIRELESS ACCESS POINT
P# = NUMBER OF VOICE / DATA PORTS IN FACEPLATE, IF
NOT SHOWN PROVIDE 2 PORTS
FLOOR BOX- VOICE / DATA OUTLETS P# = NUMBER OF
VOICE / DATA PORTS IN FACEPLATE, NOT SHOWN
PROVIDE 4 PORTS IF E= POWER OUTLET- REFER TO
ELECTRICAL PLANS FOR DETAILS
POKE THRU- VOICE / DATA OUTLETS P# = NUMBER OF
VOICE / DATA PORTS IN FACEPLATE, NOT SHOWN
PROVIDE 4 PORTS IF E= POWER OUTLET- REFER TO
ELECTRICAL PLANS FOR DETAILS
WALL MOUNTED TV OUTLET PROVIDE 1 DATA PORT
AND 1 COAX PORT UNLESS OTHERWISE NOTED T# =
TYPE OF OUTLET SEE TELECOMMUNICATION DETAILS
+ H =INSTALLATION HEIGHT IN INCHES AT CENTER OF
OUTLET, IF NOT SHOWN INSTALL AT TYPICAL 72"
RECEPTACLE HEIGHT. COORDINATE WITH
ELECTRICAL
CEILING MOUNTED TV OUTLET PROVIDE 1 DATA PORT
AND 1 COAX PORT UNLESS OTHERWISE NOTED T# =
TYPE OF OUTLET SEE TELECOMMUNICATION DETAILS
+ H =INSTALLATION HEIGHT IN INCHES AT CENTER OF
OUTLET, IF NOT SHOWN INSTALL AT TYPICAL 72"
RECEPTACLE HEIGHT. COORDINATE WITH
ELECTRICAL
PUBLIC ADDRESS SYSTEM 2X2 RECESSED SPEAKER
PUBLIC ADDRESS SYSTEM CEILING RECESSED ROUND SPEAKER
GENERAL TELECOMMUNICATIONS NOTES
1. FOR GENERAL TELECOMMUNICATIONS INFORMATION AND SOW, REFER TO DESIGN NARRATIVE / BASIS
OF DESIGN NARRATIVE.
2. CONTRACTOR SHALL VERIFY EXISTING CONDITIONS AND PROMPTLY REPORT ANY DRAWING
DISCREPANCIES TO THE VA AND ARCHITECT / ENGINEER.
3. ALL CATEGORY CABLING BEING REPLACED SHALL BE REMOVED / DEMOLISHED AS PART OF THIS
PROJECT. TURN DEMOLISHED CATEGORY CABLING OVER TO VA FOR RECYCLING.
4. ALL AREAS SHALL BE CONSIDERED PLENUM SPACES, UNLESS OTHERWISE NOTED. COMPLY WITH ALL
CODES PERTAINING TO PLENUM SPACES. PROVIDE RATED PLENUM AND OEM CERTIFIED FOR
INSTALLATION WITHIN PLENUM SPACES.
5. OSP OPTICAL FIBER CABLE SHALL BE CONSTRUCTED WITH AN ALUMINUM INTERLOCKING ARMORED
JACKET AND INSTALLED WITHIN A CONCRETE ENCASED DUCTBANK.
6. ISP OPTICAL FIBER CABLING INSTALLED WITHIN CABLE TRAY SHALL BE CONSTRUCTED WITH
ALUMINUM INTERLOCKING ARMORED JACKET. OPTIONAL, WITH VA APPROVAL, IS NON-ARMORED
PLENUM RATED OPTICAL FIBER CABLE WITHIN A PLENUM RATED CORRUGATED INNERDUCT.
7. NO SYSTEMS OR COMPONENTS SHALL BE DISRUPTED OUT OF PROJECT SEQUENCE. COORDINATE ALL
SERVICE DISRUPTIONS WITH VA.
8. CARE SHALL BE TAKEN NOT TO DISRUPT OR DAMAGE ANY EXISTING SYSTEMS INCLUDING, BUT NOT
LIMITED TO: CATV, ACCESS CONTROL, FIRE ALARM, NURSE CALL, BUILDING AUTOMATION,
DISTRIBUTED ANTENNA, PAGING AND BIO-MED.
9. ALL EQUIPMENT ADDED TO EXISTING TELECOM ROOMS SHALL BE BONDED TO THE GROUNDING
SYSTEM WITHIN TELECOM ROOM.
10. CONTRACTOR SHALL VERIFY ALL COMPONENTS BONDED TO EXISTING TELECOMMUNICATIONS
GROUNDING BUSBAR HAVE BEEN TAKEN OUT OF SERVICE OR HAVE BEEN BONDED TO NEW
TELECOMMUNICATIONS GROUNDING / BONDING SYSTEM PRIOR TO REMOVING ANY EXISTING
GROUNDING COMPONENTS.
11. NEW TELECOM ROOMS SHALL HAVE COMPLETE GROUNDING SYSTEM INSTALLED AND CONNECTED TO
NEAREST TELECOMMUNICATIONS GROUNDING BACKBONE.
12. CONTRACTOR SHALL PROVIDE AND INSTALL BASKET TYPE CABLE TRAY ALONG PRIMARY CABLE PATHWAYS. MINIMUM CABLE TRAY SIZE IS 4" x 12". CONTRACTOR SHALL SIZE CABLE TRAY DEPENDENT UPON ACTUAL NUMBER OF CAT 6A CABLES TO BE INSTALLED WITHIN A GIVEN AREA. SIZE SUCH THAT FILL IS 20% OF TOTAL CAPACITY. THIS LEAVES 20% FILL CAPACITY (50% FUTURE CAPACITY) AS TOTAL
FILL IS LIMITED TO 40%.
13. IN ADDITION TO PRIMARY PATHWAYS, CABLE TRAY SHALL BE INSTALLED FOR CABLE BUNDLES OVER 12
CABLES, EVEN IF NOT SHOWN ON DRAWINGS.
14. IF ANY AREA IS TOO CONGESTED BY EXISTING UTILITIES TO ALLOW INSTALLION OF CABLE TRAY, CONTRACTOR SHALL NOTIFY VA AND ARCHITECT / ENGINEER. ACCEPTABLE ALTERNATIVES IS TO RE-ROUTE CABLE TRAY OR INSTALL EQUIVALENT CAPACITY OF CONDUITS TO SPAN THESE AREAS.
15. J-HOOKS ARE NOT ALLOWED EXCEPT BY SPECIAL PERMISSION FROM VA, WHICH WILL BE EVALUATED
ON A CASE-BY-CASE BASIS.
16. FIRE RATED MECHANICAL SLEEVES ASSEMBLIES SHALL BE INSTALLED WHEN PASSING THROUGH PARTITIONS. MAINTAIN RATING OF ALL PARTITIONS. ASSUMING 40% FILL PER SLEEVES, ALSO PROVIDE 50% FUTURE SPARE CAPACITY (ONE EMPTY SLEEVE FOR EVERY TWO FILLED SLEEVES). AT A MINIMUM
THERE SHALL ONE EMPTY SPARE SLEEVE INSTALLED.
17. CONTRACTOR SHALL FIRE STOP ANY EXISTING PENETRATION ON BOTH SIDES (SUCH AS CONDUIT
SLEEVES) THEY RE-USE OR REMOVE EXISTING CABLING FROM DURING PROJECT.
18. EXISTING ROUTING TO TELECOM OUTLETS SHALL BE MAINTAINED TO FULLEST EXTENT POSSIBLE.
EXISTING CONDUIT TO TELECOM BACKBOX TO BE REUSED IF VIAIBLE.
19. CONDUIT THAT IS ONLY INSTALLED TO ABOVE CEILING SHALL BE EXTENDED TO CABLE TRAY.
20. MAXIMUM 295 FEET CABLING DISTANCE LIMITATION SHALL BE MAINTAINED AT ALL TIMES AND SHALL BE
VERIFIED DURING TESTING. IF THIS REQUIREMENT CANNOT BE MAINTAINED FOR ANY REASON, CONTACT VA AND ARCHITECT / ENGINEER IMMEDIATELY.
21. ALL CABLING TO WIRELESS ACCESS POINTS (WAP's) SHALL BE REPLACED WITH TW0 (2) CAT 6A CABLES. TOTAL NUMBER OF WAP's SHALL BE FIELD VERIFIED. PROVIDE MINIMUM OF 10' SERVICE LOOP AND NEW DUEL JACK SURFACE MOUNTED BOX (aka BISCUIT) OR MODULAR PLUG TERMINATED LINK (MPTL) ABOVE CEILING WHERE EXISTING WAP's ARE LOCATED. ALL EXISTING WAP's SHALL REMAIN IN
PLACE DURING CONSTRUCTION.
22. HYBRID CABLES FOR MM/SM OPTICAL FIBER CABLE SHALL NOT BE PERMITTED.
23. OUTSIDE PLANT (OSP) OS2 OPTICAL FIBER CABLING SHALL BE INDOOR / OUTDOOR RATED SO THAT
BUILDING DISTRIBUTORS SHALL NOT BE REQUIRED AT BUILDING ENTRANCE POINTS.
24. CONTRACTOR SHALL LOCATE EXISTING REINFORCING PRIOR TO ANY CORING FOR CONDUIT OR
MECHANICAL FIRE SLEEVES. DO NOT CUT ANY REINFORCING. CORES SHALL HAVE MINIMUM OF 4" CLEAR BETWEEN CORE AND REINFORCING. ADJUST CORE LOCATIONS AS REQUIRED. LOCATIONS WITH
MORE THAN TWO (2) CORES THROUGH CMU WALL, SPACE CORE MINIMUM 16" ON CENTER.
25. ALL PERSONAL ENTERING PATIENT MENTAL HEALTH WARD MUST HAVE ADDITIONAL TRAINING AND
APPROVAL FROM NURSE MANAGER PRIOR TO ENTRY.
26. ANY NOTES, DETAILS OR SPECIFICATION WITHIN CONSTRUCTION DOCUMENTS THAT HAVE MORE
STRINGENT REQUIREMENTS THAN LISTED HERE SHALL HAVE PRECEDENCE OVER ITEMS LISTED
ABOVE.
T101 T102
CAMPUS ROUTING PLAN
JG JG
TT-00-002
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
K:
\C
C G
_P R
O
JE
C
TS
\2
1\
-1
T op ek a
EH
R M
C
1R
\4
- D es
D oc s\
2- D ra w in gs
\W O
R
KI
N G
\A ut oC
AD
\T T-
0-
2.
dw g
/6
/2
:3 7:
A
M
ISSUE FOR BIDOffice of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
EHRM INFRASTRUCTURE
UPGRADES
COLMERY O'NEIL VA HEALTH CARE
21-116
Revisions: Date:
www. bancroft-ae.com
3300 Dundee RD.
Northbrook, IL 60062
T: 847.952.9362
ISSUED FOR BID R2 03-22-24
12/28/2023Bancroft Project No: 21-116
ADDENDUM #1 11-22-24
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text N
AutoCAD SHX Text 1" = 100'-0"
AutoCAD SHX Text
CAMPUS ROUTING PLAN KEYNOTES
AutoCAD SHX Text
1. NEW (2) 4" SCHEDULE 40 PVC CONCRETE ENCASED CONDUIT IN A 1X2 NEW (2) 4" SCHEDULE 40 PVC CONCRETE ENCASED CONDUIT IN A 1X2 CONFIGURATION. INSTALL A MINIMUM 30" BFG. INSTALL (3) 3-CELL MAXCELL FABRIC INTERDUCTS IN (1) OF THE TWO 4" CONDUITS. 2. NEW (4) 4" SCHEDULE 40 PVC CONCRETE ENCASED CONDUIT IN A 2X2 NEW (4) 4" SCHEDULE 40 PVC CONCRETE ENCASED CONDUIT IN A 2X2 CONFIGURATION. INSTALL A MINIMUM 30" BFG. INSTALL (3) 3-CELL MAXCELL FABRIC INTERDUCTS IN (2) OF THE FOUR 4" CONDUITS. 3. EXISTING LOWER ROUTE IN UTILITY TUNNEL AND UPPER ROUTE IN CEILING EXISTING LOWER ROUTE IN UTILITY TUNNEL AND UPPER ROUTE IN CEILING PLENUM OF WALKWAY BUILDING. CONTRACTOR SHALL PROVIDE AND INSTALL NEW CONTRACTOR SHALL PROVIDE AND INSTALL NEW BASKET STYLE CABLE TRAY FOR SUPPORT OF NEW CABLES THROUGH BOTH LEVELS. 4. NEW PULLBOX. SEE DETAILS THIS SHEET AND CIVIL PLANS FOR MORE NEW PULLBOX. SEE DETAILS THIS SHEET AND CIVIL PLANS FOR MORE INFORMATION. 5. NEW (6) 4" SCHEDULE 40 PVC CONCRETE ENCASED CONDUIT IN A 3X2 NEW (6) 4" SCHEDULE 40 PVC CONCRETE ENCASED CONDUIT IN A 3X2 CONFIGURATION. INSTALL A MINIMUM 30" BFG. INSTALL (3) 3-CELL MAXCELL FABRIC INTERDUCTS IN (4) OF THE SIX 4" CONDUITS. 6. ENTER BLDG 21 CRAWL SPACE AT APPROXIMATELY THIS LOCATION. ROUTE ENTER BLDG 21 CRAWL SPACE AT APPROXIMATELY THIS LOCATION. ROUTE CONDUITS THROUGH CRAWL SPACE TO CORRIDOR IN BLDG 21 NEAREST CONNECTION TO BLDG 19. 7. FIBER PATHWAY 'A' THROUGH CEILING OF WALKWAY TO BUILDING 19. PROVIDE FIBER PATHWAY 'A' THROUGH CEILING OF WALKWAY TO BUILDING 19. PROVIDE (6) 4" CONDUIT. SEAL FOR WATER INTRUSION. (SEE BUILDING ENTRY WATER PROOFING NOTES THIS SHEET) 8. FIBER PATHWAY 'B' THROUGH STEAM TUNNEL TO BUILDING 19. PROVIDE (6) 4" FIBER PATHWAY 'B' THROUGH STEAM TUNNEL TO BUILDING 19. PROVIDE (6) 4" CONDUIT. SEAL FOR WATER INTRUSION. (SEE BUILDING ENTRY WATER PROOFING NOTES THIS SHEET)
AutoCAD SHX Text
CAMPUS ROUTING PLAN GENERAL NOTES
AutoCAD SHX Text A. THIS DRAWING IS FOR DIAGRAMMATIC PURPOSE ONLY. REFER TO CIVIL DRAWINGS THIS DRAWING IS FOR DIAGRAMMATIC PURPOSE ONLY. REFER TO CIVIL DRAWINGS FOR ENTRANCE AND EXIT POINTS AT BUILDINGS AND PATH OF DUCTBANK. B. CONDUIT ENTRY INTO EXISTING BUILDINGS SHALL BE PROPERLY WATER SEALED CONDUIT ENTRY INTO EXISTING BUILDINGS SHALL BE PROPERLY WATER SEALED AND PATHWAY SHALL UTILIZE SMARTLB FOR THOSE AREAS REQUIRING ABOVE GROUND ENTRY. C. NEW PULLBOX SHALL BE CONCRETE MINIMUM TIER 22 AND 24"X36"X30" DEEP NEW PULLBOX SHALL BE CONCRETE MINIMUM TIER 22 AND 24"X36"X30" DEEP OPEN BOTTOM WITH 24" AGGREGATE BASE.
AutoCAD SHX Text
AutoCAD SHX Text
CAMPUS ROUTING PLAN
AutoCAD SHX Text
CABLE
AutoCAD SHX Text
HANGER
AutoCAD SHX Text
EACH CABLE MUST BE LABELED WITH SNAP AROUND LABEL. WILLIAM FRICK WFS-ES-0004.
AutoCAD SHX Text BONDING POINT FOR LOCATE WIRE. PROVIDE A GREEN INSULATED #12 COPPER WIRE THROUGHOUT NEW CONDUIT SYSTEM. BOND AT THE TOP OF EACH NEW PULLBOX FOR CONNECTION TO LOCATE SYSTEM.
AutoCAD SHX Text
UPPER RUNG IS RESERVED FOR RUNS INTO BUILDING.
AutoCAD SHX Text
REFER TO BUSINESS CONTINUITY SET.
AutoCAD SHX Text
END WALL
AutoCAD SHX Text
CONDUIT ENTRIES
AutoCAD SHX Text
CONDUIT ENTRIES
AutoCAD SHX Text
PULLING EYE
AutoCAD SHX Text 30"
AutoCAD SHX Text
END WALL
AutoCAD SHX Text
CONDUIT ENTRIES
AutoCAD SHX Text
CONDUIT ENTRIES
AutoCAD SHX Text
PULLING EYE
AutoCAD SHX Text 30"
AutoCAD SHX Text 36"
AutoCAD SHX Text
SIDE WALL
AutoCAD SHX Text 30"
AutoCAD SHX Text 24"
AutoCAD SHX Text
CABLE RACK
AutoCAD SHX Text
SIDE WALL
AutoCAD SHX Text 30"
AutoCAD SHX Text TYPICAL 24"x36"x30" CONCRETE PULLBOX UNLESS OTHERWISE NOTED
AutoCAD SHX Text
CABLE RACK
AutoCAD SHX Text
CABLE RACK
AutoCAD SHX Text
CABLE RACK
AutoCAD SHX Text PULLBOX NOTES: 1. ANSI/SCTE 77 TIER 15 RATED. ANSI/SCTE 77 TIER 15 RATED. 2. 36" LONG x 24" WIDE x 30" DEEP. 36" LONG x 24" WIDE x 30" DEEP. 3. LABELING TO BE APPROVED BY DTSS AND DISNEY TELECOM. LABELING TO BE APPROVED BY DTSS AND DISNEY TELECOM. 4. TWO PIECE METALLIC LID WITH TORSION ASSIST. TWO PIECE METALLIC LID WITH TORSION ASSIST. 5. OPEN BOTTOM. OPEN BOTTOM. 6. CABLE RACKING ON TWO (2) SIDE WALLS. CABLE RACKING ON TWO (2) SIDE WALLS. 7. ALL CONDUITS SHALL BE PLACED WITH A MINIMUM 30" CLEAR COVER.ALL CONDUITS SHALL BE PLACED WITH A MINIMUM 30" CLEAR COVER.
AutoCAD SHX Text
FINISHED GRADE
AutoCAD SHX Text
LID
AutoCAD SHX Text
GRAVEL
AutoCAD SHX Text
CONDUIT
AutoCAD SHX Text
(FOR OPEN TRENCH ONLY)
AutoCAD SHX Text
24" MINIMUM
AutoCAD SHX Text
30" MINIMUM
AutoCAD SHX Text
NOT TO SCALE
AutoCAD SHX Text
AutoCAD SHX Text
NEW TIER 22 PULLBOX BUTTERFLY DETAIL
AutoCAD SHX Text
NOT TO SCALE
AutoCAD SHX Text
AutoCAD SHX Text
NEW PULLBOX RACKING DETAIL
AutoCAD SHX Text
NOT TO SCALE
AutoCAD SHX Text
AutoCAD SHX Text
NEW PULLBOX PENETRATION DETAIL
NEW CONDUIT BUILDING PENETRATION NOTES: 1. CONDUIT LOW POINT SHALL BE MANHOLE, PULLBOX, ETC. CONDUIT LOW POINT SHALL BE MANHOLE, PULLBOX, ETC. 2. CONDUITS SHALL BE ENCASED IN CONCRETE TO AND THROUGH CONDUITS SHALL BE ENCASED IN CONCRETE TO AND THROUGH FOUNDATION OR EXTERIOR WALL. 3. INSIDE OF CONDUITS WITHIN FOUNDATION WALL SHALL BE SEALED. INSIDE OF CONDUITS WITHIN FOUNDATION WALL SHALL BE SEALED. 4. DUCT SEAL, THORNE & DERRICK, CAT# 280010 OR APPROVED DUCT SEAL, THORNE & DERRICK, CAT# 280010 OR APPROVED EQUAL.
AREA D SEE SHT. AE203
AREA F SEE SHT. AE205
UP
UP
UP
UP
UP
UP
UP
UP
UP
UP
UP
UP
UP
DN
UPUP
UP
B23
B23G
B23A B23B
B23E B23D B23C
C0-3A
A9E
A9C A9D
B5
C3
A17
A12
A30
A21
A21E
A21A
A13A A13B
A1
A10F
A3B
A3
A3A
A13
A20E
A20
A17F
C7
C7B
C4EC3EC3F
A19D
C7A
C7G
C7C
C7D
A19
C5
C7H
C7I
C6A19B
C1A18
A18A C2
A17A
A5
B1E
A7A8A9
A10E
A10
A4
A7E
A9A
A11
A14
A15
B4
B3
B13E
B22
B14A
B14
A2
A2A
A2B
A2C A2D
A19DC0-1
C8A
C20
C23
C24 C25
C28
C27
C26
C22 C21
C18C19
C17
C8
C9
C12
C14
C8B
C10 C11
C13
C15 C14A
C14B C14C
C16 C16A
C0-4
A16D
B2 B2B
B2A
B15B16 B17
B1
A16
A16C
A16A
A16E A16B
B22E
B1B
C0-2
C1A
B21
A19C
B1C
B6C
A16G
A9B
B43M B42
B42A B39
B38
C0-5B
C0-5A
C0-3
A9C
C114C
C11A
CB-8
B6D
A0-E3
A0-E1
A0-E2
A0-E4
B42B
B41
B40
B6P
B6 B8A
B7
B13CB13
B12
B9
B10
B11
B11A
B6M
B7M
B8 C0-3E
C0-3C
C0-3B B8C
B13B
B13A
A10G
A10B
A10A
A10C A10D
B3A B20
B23F
C20A A19A
ICT - BUILDING 1 - BASEMENT LEVEL
CABLE TRAY PLAN
JG JG
TT-B01-100
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
K:
\C
C G
_P R
O
JE
C
TS
\2
1\
-1
T op ek a
EH
R M
C
1R
\4
- D es
D oc s\
2- D ra w in gs
\W O
R
KI
N G
\A ut oC
AD
\T T-
B0 1-
0.
dw g
/7
/2
5:
:3
PM
ISSUE FOR BIDOffice of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
EHRM INFRASTRUCTURE
UPGRADES
COLMERY O'NEIL VA HEALTH CARE
21-116
Revisions: Date:
www. bancroft-ae.com
3300 Dundee RD.
Northbrook, IL 60062
T: 847.952.9362
12/28/2023Bancroft Project No: 21-116
ADDENDUM #1 11-22-24
ISSUED FOR BID R2 03-22-24
GENERAL NOTES
A. FOR GENERAL NOTES AND LEGENDS REFER TO SHEET TT-00-001.
B. EXISTING IT / TR / OI&T ROOMS BEING RENOVATED OR RELOCATED TO REMAIN ACTIVE DURING CONSTRUCTION.
G.C. TO PROTECT EQUIPMENT FROM DUST, DEBRIS, OR OTHER DAMAGE DURING CONSTRUCTION WITH PRODUCT SUCH AS VISQUEEN. CONTRACTOR TO ENSURE CONTINUOUS OPERATION OF EQUIPMENT, INCLUDING PROPER VENTILATION / COOLING.
C. NOT ALL KEY NOTES APPLY TO ALL PLAN SHEETS. G.C. TO APPLY ONLY AS INDICATED PER EACH SHEET.
D. APPLY FIRE RATED SEALANT TO ALL EXISTING PENETRATIONS IN EXISTING WALLS THAT THE CONTRACTOR
USES / REUSES. FIRE RATING OF EXISTING WALLS SHALL BE A MINIMUM OF 1 HR ASSEMBLY OR MATCH FIRE RATING OF EXISTING PARTITION IF MORE THAN 1 HOUR. BASIS OF DESIGN FOR 1 HR WALL IS UL 419 ASSEMBLY.
E. CONTRACTOR SHALL PROVIDE AND INSTALL NEW MECHANICAL FIRE RATED SLEEVES AS NECESSARY AND ASSEMBLED PER UL DETAIL APPROPRIATE FOR WALL / FLOOR AND RACEWAY / CABLE TYPES. MINIMUM FIRE
RATING SHALL BE 1 HOUR, OR MATCH FIRE RATING OF EXISTING PARTITION.
FLOOR PLAN KEYNOTESX
FLOOR PLAN LEGEND
BASKET CABLE TRAY.
1. PROVIDE BASKET TYPE CABLE TRAY TO SUPPORT OPTICAL FIBER BACKBONE AND NEW CAT 6A HORIZONTAL CABLING. CABLE TRAY TO BE SIZED AS PER CABLE TRAY CAPACITY PLANNING ON FLOOR PLAN LEGEND.
2. ASSUMING 40% TOTAL FILL CAPACITY, INITIAL FILL SHALL BE 20% WITH 20% OF SPARE CAPACITY (WHICH
EQUATES TO 50% FUTURE CAPACITY).
3. ROUTING SHOWN INDICATES PRIMARY PATHWAYS. IN ADDITION TO PRIMARY PATHWAYS, CABLE TRAY SHALL
BE PROVIDED WHEN CABLE BUNDLES EXCEED 24 CABLES.
4. MECHANICAL FIRE RATED SLEEVE ASSEMBLIES SHALL BE PROVIDED WHEN PASSING THROUGH FIRE RATED PARTITIONS. ASSUMING 40% FILL, INSTALL ONE (1) EMPTY MECHANICAL FIRE SLEEVE FOR EVERY TWO (2) FILLED FIRE SLEEVES, THUS PROVIDING 50% SPARE CAPACITY. MINIMUM OF ONE (1) EMPTY MECHANICAL FIRE
RATE SLEEVE PER PENETRATION LOCATION.
4 12
CF105/300
CF105/450
CF105/500
CF105/600
CF150/150
CF150/200
CF150/300
CF150/450
CF150/500
CF150/600
CF150/900
CATALOG
NUMBER
DEPTH
(IN)
WIDTH
(IN)
CAT 6A 4-pr
PLENUM
(0.35" DIA.)*
50% FILL
CAT 6A 4-pr
PLENUM
(0.35" DIA.)*
40% FILL
CAT 6A 4-pr
PLENUM
(0.35" DIA.)*
20% FILL
248 198 100 373 298 149 414 331 166 497 398 199
186 149 74 238 190 95 357 286 143 536 429 214 596 477 238 715 572 286
1078 862 431
* : FILL RATIO CALCULATIONS BASED ON WORST CASE SCENARIO.
CONTRACTOR SHALL PERFORM FILL CALCULATIONS BASED ON ACTUAL CAT 6A
CABLE BEING INSTALLED AND SUBMIT TO BOTH THE VA AND ENGINEER.
- CABLE TRAY CAPACITY PLANNING CHART
- PROPOSED CABLE TRAY
=> CABLOFIL 4" DEEP x 12" WIDE MINIMUM
-- (SIZE COMMENSURATE WITH DISTRIBUTION REQUIREMENTS)
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
SERVICE ENTRANCE LOCATION
AutoCAD SHX Text
KEY PLAN
AutoCAD SHX Text N
AutoCAD SHX Text
AutoCAD SHX Text 4'
AutoCAD SHX Text 8'
AutoCAD SHX Text 16'
AutoCAD SHX Text 32'
AutoCAD SHX Text 1/16"=1'-0"
AutoCAD SHX Text
AutoCAD SHX Text
BUILDING 1 - BASEMENT LEVEL CABLE TRAY PLAN
NORTH
UP
UP
UP
UP
DN
UP
DN
UP
UPUP
UP
DF
DF
DF
DF DF
AC101A AC130
AC101B
AC101C
AC133
AC128
AC129 AC134 AC135
AC131
AC131
AC101D
AC136
B1-03C
AC119
B113
AC127A
AC127B
C100
AC100
AC101
AC104
A140
A141A128C
A1
B103 B105
C110C109C107 C108
C116F C116A
C116
C116B
C105
C104
C106
C115
A1
A143F
A121AA119A118
A117A
A116B
A116A
A120 A121 A121B
A115
A115H
A115A A115I
A115J
A115BA115C
A115G
A122
A115E
A121E A122F
A102G
A102A
A1
A102BA102C
A102D
A108
A109
AC101J
AC101I
AC101H
AC101G
A127 A127BA127A
C116C
C116D
C119
C120C124
C125
C121
C122
C123
C123BC123A
C126
C127
C1-02
A145
C117 C104F C116E C105E
A143
A102E A101E
C102C101A144 C103
A111
A112
A104A
A104
A106
A105A110
A136
B149B1
B116
B148
B147
B146
AC120A
AC120
A116HA116G
A116E A116F
A116D
A116C
A116
A107
A104B
A115D
AC119AC118AC115
AC112
AC112A
AC114
AC109
A135
B145
B133
B134
B136 B135
B131 B132B130
B138
B129
B139B140
B128
B127
B137
B126
B141
B124B119
B123E
B143 B142
B133AB120
B143E
B120F
AC135
AC110
AC111
AC121
AC116E
AC122
AC122A
AC125
AC106E
AC113
AC124
AC123
AC117
B118
A137
B117A
A134A
C113 C112C111
C114D
C114-E
C114B
C114C
C114C
C114-W
C1-03A103
B123 B125
A1-04 A1-03
A140E
A134
A128B
A128D
A128A
AC105AC106
A1
A
A129
A128H A128G
AC108
AC1-5
B114
B106B107
B108
B113
B109A B109
B111
B1
B115
B104
B116C
B116D B1-03
A1-01
A101
A138
A142A
AC101K
B1-04B1-01
B1-02
A101A
A101G A101C
A113
B101
A101D
A141E
C1-01
C114T
A114
AC147 AC148 AC149 AC150 AC151 AC152 AC153 AC154 AC155 AC156
AC158 AC157
AC165AC164AC161
AC160
AC143 AC143A
AC145AC146
AC144 AC141 AC162 AC163 AC166
AC167
AC
1-
AC
1-
AC
1-
A615P
A6
Q
AC1-2
AC159
A1-02
A1-E1
A1-E2
A1-E3 A1-E4
A101H
A101J
4'-11"
10'-8"
1'-11 12" 21'-9"
AC134A AC136AAC135A
AC134C B1-03D
B116A
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
K:
\C
C G
_P R
O
JE
C
TS
\2
1\
-1
T op ek a
EH
R M
C
1R
\4
- D es
D oc s\
2- D ra w in gs
\W O
R
KI
N G
\A ut oC
AD
\T T-
B0 1-
1.
dw g
/7
/2
5:
:3
PM
ISSUE FOR BIDOffice of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
EHRM INFRASTRUCTURE
UPGRADES
COLMERY O'NEIL VA HEALTH CARE
21-116
Revisions: Date:
www. bancroft-ae.com
3300 Dundee RD.
Northbrook, IL 60062
T: 847.952.9362
ISSUED FOR BID R2 03-22-24
12/28/2023Bancroft Project No: 21-116
ADDENDUM #1 11-22-24
ICT - BUILDING 1 - LEVEL 1 CABLE TRAY
PLAN
JG JG
TT-B01-101
GENERAL NOTES
A. FOR GENERAL NOTES AND LEGENDS REFER TO SHEET TT-00-001.
B. EXISTING IT / TR / OI&T ROOMS BEING RENOVATED OR RELOCATED TO REMAIN ACTIVE DURING CONSTRUCTION.
G.C. TO PROTECT EQUIPMENT FROM DUST, DEBRIS, OR OTHER DAMAGE DURING CONSTRUCTION WITH PRODUCT SUCH AS VISQUEEN. CONTRACTOR TO ENSURE CONTINUOUS OPERATION OF EQUIPMENT, INCLUDING PROPER VENTILATION / COOLING.
C. NOT ALL KEY NOTES APPLY TO ALL PLAN SHEETS. G.C. TO APPLY ONLY AS INDICATED PER EACH SHEET.
D. APPLY FIRE RATED SEALANT TO ALL EXISTING PENETRATIONS IN EXISTING WALLS THAT THE CONTRACTOR
USES / REUSES. FIRE RATING OF EXISTING WALLS SHALL BE A MINIMUM OF 1 HR ASSEMBLY OR MATCH FIRE RATING OF EXISTING PARTITION IF MORE THAN 1 HOUR. BASIS OF DESIGN FOR 1 HR WALL IS UL 419 ASSEMBLY.
E. CONTRACTOR SHALL PROVIDE AND INSTALL NEW MECHANICAL FIRE RATED SLEEVES AS NECESSARY AND ASSEMBLED PER UL DETAIL APPROPRIATE FOR WALL / FLOOR AND RACEWAY / CABLE TYPES. MINIMUM FIRE
RATING SHALL BE 1 HOUR, OR MATCH FIRE RATING OF EXISTING PARTITION.
FLOOR PLAN KEYNOTESX
FLOOR PLAN LEGEND
BASKET CABLE TRAY.
1. PROVIDE BASKET TYPE CABLE TRAY TO SUPPORT OPTICAL FIBER BACKBONE AND NEW CAT 6A HORIZONTAL CABLING. CABLE TRAY TO BE SIZED AS PER CABLE TRAY CAPACITY PLANNING ON FLOOR PLAN LEGEND.
2. ASSUMING 40% TOTAL FILL CAPACITY, INITIAL FILL SHALL BE 20% WITH 20% OF SPARE CAPACITY (WHICH
EQUATES TO 50% FUTURE CAPACITY).
3. ROUTING SHOWN INDICATES PRIMARY PATHWAYS. IN ADDITION TO PRIMARY PATHWAYS, CABLE TRAY SHALL
BE PROVIDED WHEN CABLE BUNDLES EXCEED 24 CABLES.
4. MECHANICAL FIRE RATED SLEEVE ASSEMBLIES SHALL BE PROVIDED WHEN PASSING THROUGH FIRE RATED PARTITIONS. ASSUMING 40% FILL, INSTALL ONE (1) EMPTY MECHANICAL FIRE SLEEVE FOR EVERY TWO (2) FILLED FIRE SLEEVES, THUS PROVIDING 50% SPARE CAPACITY. MINIMUM OF ONE (1) EMPTY MECHANICAL FIRE
RATE SLEEVE PER PENETRATION LOCATION.
4 12
CF105/300
CF105/450
CF105/500
CF105/600
CF150/150
CF150/200
CF150/300
CF150/450
CF150/500
CF150/600
CF150/900
CATALOG
NUMBER
DEPTH
(IN)
WIDTH
(IN)
CAT 6A 4-pr
PLENUM
(0.35" DIA.)*
50% FILL
CAT 6A 4-pr
PLENUM
(0.35" DIA.)*
40% FILL
CAT 6A 4-pr
PLENUM
(0.35" DIA.)*
20% FILL
248 198 100 373 298 149 414 331 166 497 398 199
186 149 74 238 190 95 357 286 143 536 429 214 596 477 238 715 572 286
1078 862 431
* : FILL RATIO CALCULATIONS BASED ON WORST CASE SCENARIO.
CONTRACTOR SHALL PERFORM FILL CALCULATIONS BASED ON ACTUAL CAT 6A
CABLE BEING INSTALLED AND SUBMIT TO BOTH THE VA AND ENGINEER.
- CABLE TRAY CAPACITY PLANNING CHART
- PROPOSED CABLE TRAY
=> CABLOFIL 4" DEEP x 12" WIDE MINIMUM
-- (SIZE COMMENSURATE WITH DISTRIBUTION REQUIREMENTS)
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
KEY PLAN
AutoCAD SHX Text N
AutoCAD SHX Text
AutoCAD SHX Text 4'
AutoCAD SHX Text 8'
AutoCAD SHX Text 16'
AutoCAD SHX Text 32'
AutoCAD SHX Text 1/16"=1'-0"
AutoCAD SHX Text
AutoCAD SHX Text
BUILDING 1 - LEVEL 1 CABLE TRAY PLAN
AutoCAD SHX Text
NORTH
AutoCAD SHX Text
KEY PLAN
N
A213 A212
A221A A220
A214
A219
A217 A215
A2-03 A221E A212EA216A A218
A218A A218B A221 DNDN DN
DN UPDNUP
UP
UP UP
A229C
A226
A222FA212A
A222
A211
A203E
A204
A202E
A202A A202A203
A223
A229B
A229E
A225
A226E
A227
B201
A230A A230F A2
B202
B226E
B211M B230
A2-04
A2-01
A2-05
A2-02
B2-01
B2-02
B211
A228
B216E
B223A B223
B223B
B220B
B2
B218A
B217
B224A
B224
B219
B225
B221A B222
B226
B221B
B221
B231
B231C
B2
A
B231B
B230A
B213
B214
B231D
B2
G
A229
A229A
B212
B215
B210
B210A
B204 B204C
B205
B206 B206F
B208A
B208
B2
B
B208C B209AB209
B2
B
B2
B2
B
B204A
B203
C208A
C208B
C208M
C208
C203E
C211E C201F
C204 C207C206
C210 C210A
C211
C203
C212
C213
C214
C202
C2-01 C209
C215
C201A
C201
C201B A232A231 A233
C2-02
A234
A235A
A236
A201
A201A
B216
B2-04
B2-03 B218B215F
A2-E1
A2-E2
A2-E3 A2-E4
A223
A206F
A207 A206D
A206E A206C
A208
A209A
A209
A210
A210A A2-04
A206 A206B
A206A
B226A
A223A
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
K:
\C
C G
_P R
O
JE
C
TS
\2
1\
-1
T op ek a
EH
R M
C
1R
\4
- D es
D oc s\
2- D ra w in gs
\W O
R
KI
N G
\A ut oC
AD
\T T-
B0 1-
2.
dw g
/7
/2
5:
:0
PM
ISSUE FOR BIDOffice of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
EHRM INFRASTRUCTURE
UPGRADES
COLMERY O'NEIL VA HEALTH CARE
21-116
Revisions: Date:
www. bancroft-ae.com
3300 Dundee RD.
Northbrook, IL 60062
T: 847.952.9362
ISSUED FOR BID R2 03-22-24
12/28/2023Bancroft Project No: 21-116
ADDENDUM #1 11-22-24
ICT - BUILDING 1 - LEVEL 2 CABLE TRAY
PLAN
JG JG
TT-B01-102
GENERAL NOTES
A. FOR GENERAL NOTES AND LEGENDS REFER TO SHEET TT-00-001.
B. EXISTING IT / TR / OI&T ROOMS BEING RENOVATED OR RELOCATED TO REMAIN ACTIVE DURING CONSTRUCTION.
G.C. TO PROTECT EQUIPMENT FROM DUST, DEBRIS, OR OTHER DAMAGE DURING CONSTRUCTION WITH PRODUCT SUCH AS VISQUEEN. CONTRACTOR TO ENSURE CONTINUOUS OPERATION OF EQUIPMENT, INCLUDING PROPER VENTILATION / COOLING.
C. NOT ALL KEY NOTES APPLY TO ALL PLAN SHEETS. G.C. TO APPLY ONLY AS INDICATED PER EACH SHEET.
D. APPLY FIRE RATED SEALANT TO ALL EXISTING PENETRATIONS IN EXISTING WALLS THAT THE CONTRACTOR
USES / REUSES. FIRE RATING OF EXISTING WALLS SHALL BE A MINIMUM OF 1 HR ASSEMBLY OR MATCH FIRE RATING OF EXISTING PARTITION IF MORE THAN 1 HOUR. BASIS OF DESIGN FOR 1 HR WALL IS UL 419 ASSEMBLY.
E. CONTRACTOR SHALL PROVIDE AND INSTALL NEW MECHANICAL FIRE RATED SLEEVES AS NECESSARY AND ASSEMBLED PER UL DETAIL APPROPRIATE FOR WALL / FLOOR AND RACEWAY / CABLE TYPES. MINIMUM FIRE
RATING SHALL BE 1 HOUR, OR MATCH FIRE RATING OF EXISTING PARTITION.
FLOOR PLAN KEYNOTESX
FLOOR PLAN LEGEND
BASKET CABLE TRAY.
1. PROVIDE BASKET TYPE CABLE TRAY TO SUPPORT OPTICAL FIBER BACKBONE AND NEW CAT 6A HORIZONTAL CABLING. CABLE TRAY TO BE SIZED AS PER CABLE TRAY CAPACITY PLANNING ON FLOOR PLAN LEGEND.
2. ASSUMING 40% TOTAL FILL CAPACITY, INITIAL FILL SHALL BE 20% WITH 20% OF SPARE CAPACITY (WHICH
EQUATES TO 50% FUTURE CAPACITY).
3. ROUTING SHOWN INDICATES PRIMARY PATHWAYS. IN ADDITION TO PRIMARY PATHWAYS, CABLE TRAY SHALL
BE PROVIDED WHEN CABLE BUNDLES EXCEED 24 CABLES.
4. MECHANICAL FIRE RATED SLEEVE ASSEMBLIES SHALL BE PROVIDED WHEN PASSING THROUGH FIRE RATED PARTITIONS. ASSUMING 40% FILL, INSTALL ONE (1) EMPTY MECHANICAL FIRE SLEEVE FOR EVERY TWO (2) FILLED FIRE SLEEVES, THUS PROVIDING 50% SPARE CAPACITY. MINIMUM OF ONE (1) EMPTY MECHANICAL FIRE
RATE SLEEVE PER PENETRATION LOCATION.
4 12
CF105/300
CF105/450
CF105/500
CF105/600
CF150/150
CF150/200
CF150/300
CF150/450
CF150/500
CF150/600
CF150/900
CATALOG
NUMBER
DEPTH
(IN)
WIDTH
(IN)
CAT 6A 4-pr
PLENUM
(0.35" DIA.)*
50% FILL
CAT 6A 4-pr
PLENUM
(0.35" DIA.)*
40% FILL
CAT 6A 4-pr
PLENUM
(0.35" DIA.)*
20% FILL
248 198 100 373 298 149 414 331 166 497 398 199
186 149 74 238 190 95 357 286 143 536 429 214 596 477 238 715 572 286
1078 862 431
* : FILL RATIO CALCULATIONS BASED ON WORST CASE SCENARIO.
CONTRACTOR SHALL PERFORM FILL CALCULATIONS BASED ON ACTUAL CAT 6A
CABLE BEING INSTALLED AND SUBMIT TO BOTH THE VA AND ENGINEER.
- CABLE TRAY CAPACITY PLANNING CHART
- PROPOSED CABLE TRAY
=> CABLOFIL 4" DEEP x 12" WIDE MINIMUM
-- (SIZE COMMENSURATE WITH DISTRIBUTION REQUIREMENTS)
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
KEY PLAN
AutoCAD SHX Text N
AutoCAD SHX Text
AutoCAD SHX Text 4'
AutoCAD SHX Text 8'
AutoCAD SHX Text 16'
AutoCAD SHX Text 32'
AutoCAD SHX Text 1/16"=1'-0"
AutoCAD SHX Text
AutoCAD SHX Text
BUILDING 1 - LEVEL 2 CABLE TRAY PLAN
AutoCAD SHX Text
NORTH
AutoCAD SHX Text
KEY PLAN
DN
UP
UP
DNA343
A327
B309F
B324E
B310
B310B B310A
B310E
B311 B309 B309B
B309A
A301
A331
A302E
A302
A335 A301E
A332A330A328
A327FA326E
A323 A322
A325
A324
A324A
A324C
A325E
A326
A326A
A321 A343F
A348A301A
A324B
A303
C307
C308
A315B
A314A315
A315A
A313 A313A
A312
A312A
A311 A311A
C3-3
A316
A319
A305
A329
A320
A318
A318A
A310
A306
A307 A307A
A308A317
A309
A304
A346 C301
C311
C306
C309
C305B
A3-04
C319
C318
C317
C314
C315
C313
C313A
C316
C320
C321
C322
C325
C326
C326A
C324
C323
C327
C313B
C328 C312
B312B3
A
B312B B314A B315
B315A
B317 B319A
B318AB319
B319C
B319B
B320
B3
B3
A
B3
B323B307
B325AB325B
C310
C303
C311A
C305
C305AA3
A347
A344
A347A
A3-06A3-05
A345
C329
C302
C304F C305E C306EA343A
C304 A326B
A333A
A333B
A333C
A3
D
B306E
B305
B122 B308
C305C
B3-01
C3-01A3-02 A300
A3-01
A322A
A3-E1
A3-E2
B304
B301A
B302 A337D B303
B303AA337F
B300
B301
A339B
A337B
A339A
A337 A338
A337C
A339
A338
A334B A322L
A334
B325
B326
B328
B329
A329A
A340A
A340
A341
A341A
A300B A3-E4A336
A3-E3
A3-03
A342E
A337E
B3-02
A3-01
A337A
A348A
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
K:
\C
C G
_P R
O
JE
C
TS
\2
1\
-1
T op ek a
EH
R M
C
1R
\4
- D es
D oc s\
2- D ra w in gs
\W O
R
KI
N G
\A ut oC
AD
\T T-
B0 1-
3.
dw g
/7
/2
5:
:0
PM
ISSUE FOR BIDOffice of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
EHRM INFRASTRUCTURE
UPGRADES
COLMERY O'NEIL VA HEALTH CARE
21-116
Revisions: Date:
www. bancroft-ae.com
3300 Dundee RD.
Northbrook, IL 60062
T: 847.952.9362
ISSUED FOR BID R2 03-22-24
12/28/2023Bancroft Project No: 21-116
ADDENDUM #1 11-22-24
ICT - BUILDING 1 - LEVEL 3 CABLE TRAY
PLAN
JG JG
TT-B01-103
GENERAL NOTES
A. FOR GENERAL NOTES AND LEGENDS REFER TO SHEET TT-00-001.
B. EXISTING IT / TR / OI&T ROOMS BEING RENOVATED OR RELOCATED TO REMAIN ACTIVE DURING CONSTRUCTION.
G.C. TO PROTECT EQUIPMENT FROM DUST, DEBRIS, OR OTHER DAMAGE DURING CONSTRUCTION WITH PRODUCT SUCH AS VISQUEEN. CONTRACTOR TO ENSURE CONTINUOUS OPERATION OF EQUIPMENT, INCLUDING PROPER VENTILATION / COOLING.
C. NOT ALL KEY NOTES APPLY TO ALL PLAN SHEETS. G.C. TO APPLY ONLY AS INDICATED PER EACH SHEET.
D. APPLY FIRE RATED SEALANT TO ALL EXISTING PENETRATIONS IN EXISTING WALLS THAT THE CONTRACTOR
USES / REUSES. FIRE RATING OF EXISTING WALLS SHALL BE A MINIMUM OF 1 HR ASSEMBLY OR MATCH FIRE RATING OF EXISTING PARTITION IF MORE THAN 1 HOUR. BASIS OF DESIGN FOR 1 HR WALL IS UL 419 ASSEMBLY.
E. CONTRACTOR SHALL PROVIDE AND INSTALL NEW MECHANICAL FIRE RATED SLEEVES AS NECESSARY AND ASSEMBLED PER UL DETAIL APPROPRIATE FOR WALL / FLOOR AND RACEWAY / CABLE TYPES. MINIMUM FIRE
RATING SHALL BE 1 HOUR, OR MATCH FIRE RATING OF EXISTING PARTITION.
FLOOR PLAN KEYNOTESX
FLOOR PLAN LEGEND
BASKET CABLE TRAY.
1. PROVIDE BASKET TYPE CABLE TRAY TO SUPPORT OPTICAL FIBER BACKBONE AND NEW CAT 6A HORIZONTAL CABLING. CABLE TRAY TO BE SIZED AS PER CABLE TRAY CAPACITY PLANNING ON FLOOR PLAN LEGEND.
2. ASSUMING 40% TOTAL FILL CAPACITY, INITIAL FILL SHALL BE 20% WITH 20% OF SPARE CAPACITY (WHICH
EQUATES TO 50% FUTURE CAPACITY).
3. ROUTING SHOWN INDICATES PRIMARY PATHWAYS. IN ADDITION TO PRIMARY PATHWAYS, CABLE TRAY SHALL
BE PROVIDED WHEN CABLE BUNDLES EXCEED 24 CABLES.
4. MECHANICAL FIRE RATED SLEEVE ASSEMBLIES SHALL BE PROVIDED WHEN PASSING THROUGH FIRE RATED PARTITIONS. ASSUMING 40% FILL, INSTALL ONE (1) EMPTY MECHANICAL FIRE SLEEVE FOR EVERY TWO (2) FILLED FIRE SLEEVES, THUS PROVIDING 50% SPARE CAPACITY.