Attachment - 18 EHRM Bonham - Simulation Main Computer Rm 2 - CFD Analysis.pdf

PDF 5 MB Posted

Attached to
Z2DA--EHRM Bonham, TX Construction 549A4-21-700 EHRM Construction (VA-23-00092679)
Solicitation number
36C77624B0007_1
Issued by

About this file

This CFD analysis report details simulations conducted for the Main Computer Room of the VA medical center in Bonham, Texas. The analysis examined using two 70kW CRAC units running at half capacity to cool data center equipment operating at full load in the room, which had an initial temperature of 85 degrees Fahrenheit. Over roughly four minutes of transient simulation, the average room temperature dropped to 68 degrees Fahrenheit, with inlet temperatures to racks ranging from 62 to 74 degrees Fahrenheit and outlet temperatures from 81 to 83 degrees Fahrenheit. The simulation determined that two units at half capacity were sufficient to cool the space and equipment.

The related federal contract opportunity is for construction services for EHRM improvements at the Bonham, Texas VA medical center, with a solicitation number of 36C77624B0007_1. The opportunity was issued by the Department of Veterans Affairs Technology Acquisition Center located in Austin, Texas.

View the file

Other files

File Type Posted
Attachment 56 - Abstract of Bids OF 1419 - CONST-Bonham - Signed.pdf PDF
Attachment 57 - Abstract of Bids OF 1419 A - CONST-Bonham.pdf PDF
36C77624B0007 0012.docx DOCX document
Attachment- 54 Sheet GS020 DETAILS.pdf PDF
Attachment- 53 Sheet GS019 EROSION CONTROL DETAILS.pdf PDF
Attachment- 51 TR Matrix Bonham.pdf PDF
Attachment- 55 Solicitation-RFIs-Tech Responses 36C77624B0007.pdf PDF
Attachment- 52 Hydrology Map.pdf PDF
36C77624B0007 0011.pdf PDF
36C77624B0007 0010.pdf PDF
36C77624B0007 0009.pdf PDF
Att 50 CLARIFICATION of Site Visit-Duct banks not available for use.pdf PDF
36C77624B0007 0008.pdf PDF
36C77624B0007 0007.docx DOCX document
Attachment - 49 S04-sign in sheet-pg 1 Site Visit Bonham TX 1.9.24.pdf PDF
36C77624B0007 0006.docx DOCX document
36C77624B0007 0005.pdf PDF
Attachment - 48 S04-sign in sheet Site Visit Bonham TX 1.9.24.pdf PDF
Attachment - 47 Clarifications-Additional Technical Questions.pdf PDF
36C77624B0007 0004.pdf PDF
Attachment - 46 Answers to Solicitation-RFIs-MISSING SECTION-36C77624B0007_1.pdf PDF
36C77624B0007 0003.pdf PDF
Attachment- 29 Bonham VA - Geotech Rpt 3-30-16-For Soil.pdf PDF
Attachment- 35 01 Bonham EHRM- Narrative.pdf PDF
Attachment- 36 01 Environmental Narrative.pdf PDF
Attachment- 44 Station Pictures for electrical.pdf PDF
Attachment- 28 Bonham EHRM- ICRA Form.pdf PDF
Attachment- 41 07 Electrical Narrative.pdf PDF
Attachment- 30 SPCC-PIPP Plan VANTHCS_Bonham.pdf PDF
Attachment- 38 03 Structural Narrative.pdf PDF
Attachment- 27 Answers to Solicitation-RFIs-36C77624B0007_1.pdf PDF
Attachment- 42 08 Telecom Narrative.pdf PDF
Attachment- 43 09 Security Narrative.pdf PDF
36C77624B0007 0002.pdf PDF
Attachment- 37 02 Civil Narrative.pdf PDF
Attachment- 32 V2 549A4-21-700 100 Bid Document Specifications.pdf PDF
Attachment- 45 IT Closet Proposed lay down.pdf PDF
Attachment- 39 05 Fire Protection Narrative.pdf PDF
Attachment- 34 00 General Narrative.pdf PDF
Attachment- 33 AE Physical Security Risk Mitigation Design Guidance.pdf PDF
Attachment- 31 site plan fiber runs Bonham.pdf PDF
Attachment- 40 06 Mechanical Narrative.pdf PDF
36C77624B0007 0001.pdf PDF
36C77624B0007_1-tech questions date updated.pdf PDF
36C77624B0007_1.pdf PDF
Attachment - 13 Asbestos 3_ VA Checklist_Environ.pdf PDF
Attachment - 03 Civil Drawings_100percent Bid Docs.pdf PDF
Attachment - 24 Limitations on Subcontracting - Construction.pdf PDF
Attachment - 16 CABINET DIMENSIONAL DATA.pdf PDF
Attachment - 05 Architectural Drawings_100percent Bid Docs.pdf PDF
Show 40 more

Latest 50 of 70 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

EHRM BONHAM - MCR –

TWO UNITS HALF CAPACITY

CFD ANALYSIS

Prepared by: Spur Design, BAJ

Date: Monday, June 19, 2023

Spur Design

EHRM Bonham - MCR - CFD Analysis.cfdst Prepared by: Blake Juett

Page 1 Generated with Autodesk CFD 2021

Report Contents

Summary _________________________________________________________________________________________________ 2

Description ________________________________________________________________________________________________________2

Design 1___________________________________________________________________________________________________ 3

Two Units Half Capacity __________________________________________________________________________________________3

Materials ________________________________________________________________________________________________________3 boundary conditions ___________________________________________________________________________________________5

Initial Conditions _______________________________________________________________________________________________5

Mesh _____________________________________________________________________________________________________________6

Physics __________________________________________________________________________________________________________7

Solver Settings __________________________________________________________________________________________________7

Convergence ____________________________________________________________________________________________________7

Results __________________________________________________________________________________________________________8

Decision Center _________________________________________________________________________________________ 12

Summary Images ________________________________________________________________________________________________ 12

XY Plane Temperature Billboard – View 1 __________________________________________________________________ 12

XY Plane Temperature Billboard – View 2 __________________________________________________________________ 13

YZ Plane Temperature Billboard – View 1 __________________________________________________________________ 14

YZ Plane Temperature Billboard – View 2 __________________________________________________________________ 15

Airflow Streamer – View 1 ___________________________________________________________________________________ 16

Airflow Streamer – View 2 ___________________________________________________________________________________ 17

Page 2 Generated with Autodesk CFD 2021

Summary

DESCRIPTION

This report contains the results and images from a CFD simulation of the Main Computer Room

(MCR) for the VA medical center in Bonham, TX. This report displays the findings from a simulation of a MCR using of two 70kW CRAC units at half capacity to cool data center equipment running at full load. The initial temperature of the room was set to 85 degrees Fahrenheit. This was a transient analysis that ran for roughly 4 minutes. At the end of the 4 minutes the average room temperature was 68 degrees Fahrenheit. Inlet temperatures into the racks ranged from 62 degrees Fahrenheit to 74 degrees Fahrenheit. Outlet temperatures out of the racks ranged from

81 to 83 degrees Fahrenheit. The simulation found that two units running at half capacity were sufficient in cooling the space and the equipment.

Page 3 Generated with Autodesk CFD 2021

Design 1

Length units foot

Coordinate system Cartesian 3D

TWO UNITS HALF CAPACITY

MATERIALS

Page 4 Generated with Autodesk CFD 2021

NAME ASSIGNED TO PROPERTIES

Air Volume

Density Equation of State

Viscosity 1.817e-05 Pa-s

Conductivity 0.02563 W/m-K

Specific heat 1004.0 J/kg-K

Compressibility 1.4

Emissivity 1.0

Wall roughness 0.0 meter

Phase Vapor Pressure

Stainless Steel

(304)

Part1.1-CRU-514-2

Part1.1-CRU-514-1

X-Direction Piecewise Linear

Y-Direction Same as X-dir.

Z-Direction Same as X-dir.

Density 8.0 g/cm3

Specific heat 0.5 J/g-K

Emissivity 0.54

Transmissivity 0.0

Electrical resistivity 7.2e-05 ohm-cm

Glass Wool Part1.1-517-001

Part1.1-517-002

X-Direction 0.038 W/m-K

Z-Direction Same as X-dir.

Density 24.0 kg/m3

Specific heat 700.0 J/kg-K

Emissivity 0.8

Transmissivity 0.0

Electrical resistivity 40000000000000.0

Aluminum

Alloy (6063)

Part1.MDA-B

Part1.MDA-A

Part1.SC - 9

Part1.SC - 7

Part1.SC - 5

Part1.SC - 3

Part1.HDA-A

Part1.SC - 1

Part1.SC - 2

Part1.SC - 4

Part1.SC - 6

Part1.SC - 8

Part1.HDA-B

Part1.MDA-A (1)

Part1.MDA-B (1)

X-Direction 218.0 W/m-K

Z-Direction Same as X-dir.

Density 2.7 g/cm3

Specific heat 0.9 J/g-K

Emissivity 0.2

Transmissivity 0.0

Electrical resistivity 2.99e-06 ohm-cm

DS070 - Half

Cap

Part1.Coils - 2

Part1.Coils - 1

Flow 4500.0 ft3/min

Heat Transfer Heat Input/Extraction

Page 5 Generated with Autodesk CFD 2021

DS070 - Half

Cap

Part1.Coils - 2

Part1.Coils - 1

Flow 4500.0 ft3/min

Heat Transfer Heat Input/Extraction

BOUNDARY CONDITIONS

TYPE ASSIGNED TO

Total Heat Generation(3500 W) Part1.MDA-B

Part1.MDA-A

Part1.SC - 9

Part1.SC - 7

Part1.SC - 5

Part1.SC - 3

Part1.SC - 1

Part1.SC - 2

Part1.SC - 4

Part1.SC - 6

Part1.SC - 8

Part1.MDA-A (1)

Part1.MDA-B (1)

Total Heat Generation(2800 W) Part1.HDA-A

Part1.HDA-B

Film Coefficient(3.5

BTU/ft2/h/F, 100 Fahrenheit)

Surface:128

Surface:129

Surface:130

Surface:133

Surface:134

Surface:171

INITIAL CONDITIONS

TYPE ASSIGNED TO

Temperature(85 Fahrenheit) Volume

Page 6 Generated with Autodesk CFD 2021

MESH

Automatic Meshing Settings

Surface refinement 0

Gap refinement 0

Resolution factor 1.0

Edge growth rate 1.1

Minimum points on edge 2

Points on longest edge 10

Surface limiting aspect ratio 20

Mesh Enhancement Settings

Mesh enhancement 1

Enhancement blending 0

Number of layers 3

Layer factor 0.45

Layer gradation 1.05

Meshed Model

Number of Nodes 44675

Number of Elements 167997

Page 7 Generated with Autodesk CFD 2021

PHYSICS

Flow On

Compressibility Incompressible

Heat Transfer On

Auto Forced Convection Off

Gravity Components 0.0, 0.0, -32.174

Radiation On

Scalar No scalar

Turbulence On

SOLVER SETTINGS

Solution mode Transient

Solver computer MyComputer

Intelligent solution control Off

Advection scheme ADV 5

Turbulence model k-epsilon

CONVERGENCE

Iterations run 243

Solve time 570 seconds

Solver version 21.0.20201120

Energy Balance

Fluid Energy Balance Information (numerical) energy out - 1.8034 Btu/s heat transfer due to sources in 0.0 Btu/s heat transfer from wall to fluid 73.129 Btu/s mdotin x cp x (tout - tin) -127.01 Btu/s radiation heat balance 0.0 5.8026

Solid Energy Balance Information heat transfer due to sources in 48.39 Btu/s heat transfer from exterior to 0.45812 Btu/s heat transfer from fluid to solid -73.129 Btu/s

Mass Balance

IN OUT

Mass flow 0.0 0.0

Volume flow 0.0 f^3/s 0.0 f^3/s

Page 8 Generated with Autodesk CFD 2021

RESULTS

Inlets and Outlets inlet 1 (heat exchanger outlet - part 21) inlet bulk pressure 27.2156 psf inlet bulk temperature 55.0216 F inlet mach number 0.00477516 mass flow in 0.189419 minimum x,y,z of 0.0 node near minimum 478.0 reynolds number 135776.0 surface id 313.0 volume flow in 74.9999 f^3/s inlet 2 (heat exchanger inlet - part 21) inlet bulk pressure 27.0945 psf inlet bulk temperature 73.4054 F inlet mach number 0.00456737 mass flow in -0.173293 minimum x,y,z of 0.0

Page 9 Generated with Autodesk CFD 2021 node near minimum 485.0 reynolds number 124216.0 surface id 314.0 volume flow in -74.9994 f^3/s inlet 3 (heat exchanger outlet - part 2) inlet bulk pressure 27.2195 psf inlet bulk temperature 55.6568 F inlet mach number 0.00477695 mass flow in 0.189563 minimum x,y,z of 0.0 node near minimum 5.0 reynolds number 135879.0 surface id 23.0 inlet 4 (heat exchanger inlet - part 2) inlet bulk pressure 27.0901 psf inlet bulk temperature 73.0025 F inlet mach number 0.00457625 mass flow in -0.173424 minimum x,y,z of 0.0 node near minimum 18.0 reynolds number 124311.0 surface id 24.0 total mass flow in 0.0322644 total vol. flow in 0.00118784 f^3/s volume flow in -74.9992 f^3/s inlet 1 (heat exchanger outlet - part 21) inlet bulk pressure 27.2156 psf inlet bulk temperature 55.0216 F inlet mach number 0.00477516 mass flow in 0.189419 minimum x,y,z of 0.0 node near minimum 478.0 reynolds number 135776.0 surface id 313.0 inlet 3 (heat exchanger outlet - part 2) inlet bulk pressure 27.2195 psf inlet bulk temperature 55.6568 F inlet mach number 0.00477695 mass flow in 0.189563 minimum x,y,z of 0.0 node near minimum 5.0 reynolds number 135879.0 surface id 23.0

Page 10 Generated with Autodesk CFD 2021

Field Variable Results

VARIABLE MAX MIN

cond 0.0349583 B/f-s-R 4.11001e-06 B/f-s-R dens 15.5086 lbf-s^2/f^4 0.00221332 lbf-s^2/f^4 econd 0.275518 B/f-s-R 0.0 B/f-s-R emiss 1.0 0.0 evisc 0.0340069 lbf-s/f^2 0.0 lbf-s/f^2 gent 464.441 1/s 0.0110473 1/s press 27.5557 psf 0.0 psf ptotl 30.1397 psf 0.0 psf scal1 0.0 0.0 seebeck 0.0 V/K 0.0 V/K shgc 0.0 0.0 spech 7.71567 B-f/lbf-s^2R 3.84246 B-f/lbf-s^2R temp 100.531 F 55.0216 F transmiss 0.0 0.0 turbd 5892.34 f^2/s^3 2.03381e-07 f^2/s^3 turbk 419.088 f^2/s^2 3.79148e-10 f^2/s^2 ufactor 0.0 0.0 visc 3.79148e-07 lbf-s/f^2 0.0 lbf-s/f^2 vx vel 7.48177 f/s -73.9074 f/s vy vel 70.4696 f/s -6.44006 f/s vz vel 5.86866 f/s -74.6314 f/s wrough 0.0 f 0.0 f

Page 11 Generated with Autodesk CFD 2021

Component Thermal Summary

PART MINIMUM

TEMPERATURE

MAXIMUM

TEMPERATURE

VOLUME AVERAGED

TEMPERATURE

Part1.1-CRU-514-2 55.6568 78.3356 72.5608

Part1.Coils - 2 0 0 0

Part1.MDA-B 70.7226 81.618 75.7339

Part1.MDA-A 70.9376 81.1468 75.5717

Part1.SC - 9 68.0233 82.6541 76.5587

Part1.SC - 7 72.804 83.0893 77.1016

Part1.SC - 5 70.8001 81.1162 77.0109

Part1.SC - 3 72.381 82.7835 77.0547

Part1.HDA-A 63.0321 81.2846 75.0411

Part1.1-517-001 55.6568 100.531 85.078

Part1.1-517-002 72.6131 100.514 89.9236

Part1.SC - 1 67.5578 83.0393 76.7768

Part1.SC - 2 70.6378 82.8326 76.9915

Part1.SC - 4 71.7101 82.7775 77.0478

Part1.SC - 6 74.0673 82.9402 77.1234

Part1.SC - 8 72.8489 82.9929 76.9614

Part1.HDA-B 62.2819 81.3203 74.8499

Part1.MDA-A (1) 68.1186 81.4108 75.6753

Part1.MDA-B (1) 69.5986 81.0577 75.5698

Part1.1-CRU-514-1 55.0216 78.5522 72.5582

Part1.Coils - 1 0 0 0

Volume 55.0216 82.8671 68.1301

Fluid Forces on Walls pressx 0.20103 pounds pressy -0.19884 pounds pressz -0.88 pounds shearx -0.0063479 pounds sheary 0.019846 pounds shearz -0.020448 pounds

Page 12 Generated with Autodesk CFD 2021

Decision Center

SUMMARY IMAGES

XY PLANE TEMPERATURE BILLBOARD – VIEW 1

Temperature Distribution with Directional Airflow Vectors.

Page 13 Generated with Autodesk CFD 2021

XY PLANE TEMPERATURE BILLBOARD – VIEW 2

Page 14 Generated with Autodesk CFD 2021

YZ PLANE TEMPERATURE BILLBOARD – VIEW 1

Page 15 Generated with Autodesk CFD 2021

YZ PLANE TEMPERATURE BILLBOARD – VIEW 2

Page 16 Generated with Autodesk CFD 2021

AIRFLOW STREAMER – VIEW 1

Directional Airflow Streamers Colored by Temperature.

Page 17 Generated with Autodesk CFD 2021

AIRFLOW STREAMER – VIEW 2

Directional Airflow Streamers Colored by Temperature.