Attachment- 38 03 Structural Narrative.pdf

PDF 237 KB Posted

Attached to
Z2DA--EHRM Bonham, TX Construction 549A4-21-700 EHRM Construction (VA-23-00092679)
Solicitation number
36C77624B0007_1
Issued by

About this file

This solicitation seeks a general contractor to provide infrastructure improvements for the Bonham Veterans Affairs Medical Center in Bonham, Texas. Key requirements include upgrading facility fiber and providing redundant fiber runs throughout buildings to telecommunications rooms, designing a new data center and remodeling twenty telecommunications rooms, locating spaces for three telecommunications enclosures, and upgrading facility HVAC and electrical distribution as needed. The solicitation has been issued as an invitation for bid and will be evaluated using IFB procedures. It has been set aside exclusively for Service-Disabled Veteran-Owned Small Businesses and offers from other than SDVOSBs will not be considered. The period of performance is approximately 365 calendar days from issuance of the notice to proceed. The expected magnitude of construction is between $10,000,000 and $20,000,000. Questions must be submitted in writing by a specified deadline.

View the file

Other files

File Type Posted
Attachment 56 - Abstract of Bids OF 1419 - CONST-Bonham - Signed.pdf PDF
Attachment 57 - Abstract of Bids OF 1419 A - CONST-Bonham.pdf PDF
36C77624B0007 0012.docx DOCX document
Attachment- 54 Sheet GS020 DETAILS.pdf PDF
Attachment- 53 Sheet GS019 EROSION CONTROL DETAILS.pdf PDF
Attachment- 51 TR Matrix Bonham.pdf PDF
Attachment- 55 Solicitation-RFIs-Tech Responses 36C77624B0007.pdf PDF
Attachment- 52 Hydrology Map.pdf PDF
36C77624B0007 0011.pdf PDF
36C77624B0007 0010.pdf PDF
36C77624B0007 0009.pdf PDF
Att 50 CLARIFICATION of Site Visit-Duct banks not available for use.pdf PDF
36C77624B0007 0008.pdf PDF
36C77624B0007 0007.docx DOCX document
Attachment - 49 S04-sign in sheet-pg 1 Site Visit Bonham TX 1.9.24.pdf PDF
36C77624B0007 0006.docx DOCX document
36C77624B0007 0005.pdf PDF
Attachment - 48 S04-sign in sheet Site Visit Bonham TX 1.9.24.pdf PDF
Attachment - 47 Clarifications-Additional Technical Questions.pdf PDF
36C77624B0007 0004.pdf PDF
Attachment - 46 Answers to Solicitation-RFIs-MISSING SECTION-36C77624B0007_1.pdf PDF
36C77624B0007 0003.pdf PDF
Attachment- 29 Bonham VA - Geotech Rpt 3-30-16-For Soil.pdf PDF
Attachment- 35 01 Bonham EHRM- Narrative.pdf PDF
Attachment- 36 01 Environmental Narrative.pdf PDF
Attachment- 44 Station Pictures for electrical.pdf PDF
Attachment- 28 Bonham EHRM- ICRA Form.pdf PDF
Attachment- 41 07 Electrical Narrative.pdf PDF
Attachment- 30 SPCC-PIPP Plan VANTHCS_Bonham.pdf PDF
Attachment- 27 Answers to Solicitation-RFIs-36C77624B0007_1.pdf PDF
Attachment- 42 08 Telecom Narrative.pdf PDF
Attachment- 43 09 Security Narrative.pdf PDF
36C77624B0007 0002.pdf PDF
Attachment- 37 02 Civil Narrative.pdf PDF
Attachment- 32 V2 549A4-21-700 100 Bid Document Specifications.pdf PDF
Attachment- 45 IT Closet Proposed lay down.pdf PDF
Attachment- 39 05 Fire Protection Narrative.pdf PDF
Attachment- 34 00 General Narrative.pdf PDF
Attachment- 33 AE Physical Security Risk Mitigation Design Guidance.pdf PDF
Attachment- 31 site plan fiber runs Bonham.pdf PDF
Attachment- 40 06 Mechanical Narrative.pdf PDF
36C77624B0007 0001.pdf PDF
36C77624B0007_1-tech questions date updated.pdf PDF
36C77624B0007_1.pdf PDF
Attachment - 13 Asbestos 3_ VA Checklist_Environ.pdf PDF
Attachment - 03 Civil Drawings_100percent Bid Docs.pdf PDF
Attachment - 24 Limitations on Subcontracting - Construction.pdf PDF
Attachment - 16 CABINET DIMENSIONAL DATA.pdf PDF
Attachment - 05 Architectural Drawings_100percent Bid Docs.pdf PDF
Attachment - 18 EHRM Bonham - Simulation Main Computer Rm 2 - CFD Analysis.pdf PDF
Show 40 more

Latest 50 of 70 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

PROJECT NUMBER 549A4-21-700

PROJECT NAME EHRM INFRASTRUCTURE UPGRADES,

BONHAM, TX

SUBMITTAL 100% Bid Documents

SUBJECT Structural Narrative

Structural - 1

Existing Structure

The existing structures are as detailed in the site observation report dated 11/8/2022. Further details of the existing structure for Building 1 have been identified in existing structural drawings provided by the VA.

The primary structural interest is the floor system supporting the new server and demarcation rooms (Room 514 and 515, respectively). The floor system supporting the new server and demarcation rooms consists of a concrete rib joist and one-way slab system. The dimensions of each rib joist are 0’-4” wide by 0’-8” deep at 2’-0” on center (OC). The primary negative moment reinforcement in each rib joist is (1) #4 reinforcing bar located in the lower portion of the cross-section for the entire span length. Secondary negative moment reinforcement in each rib joist is (1) #5 reinforcing bar located in the bottom portion of the rib joist near mid-span of the rib joist. The secondary negative reinforcement is bent and transitions to positive moment reinforcement at the supporting ends of the beam. The rib joists support a 0’-2 ½” thick one-way concrete slab.

Design Criteria

Design Manuals - PG-18-10 – Structural

IBC -International Building Code – 2021 Edition

Seismic Design Requirements – H-18-8

Master Construction Specifications – PG-18-1

Proposed Structural Changes

The renovations and upgrades of all rooms are primarily non-structural and currently do not cause any major changes to the vertical or lateral load path. Currently, there are no new buildings being constructed to support the EHRM project.

STAND has reviewed the details of the existing structural floor system supporting the new service and demarcation rooms on Level Five of Building 1. The observations and calculations

PROJECT NUMBER 549A4-21-700

PROJECT NAME EHRM INFRASTRUCTURE UPGRADES,

BONHAM, TX

SUBMITTAL 100% Bid Documents

SUBJECT Structural Narrative

Structural - 2 show that the slab can support a maximum service live load of 200 psf. Therefore, STAND has determined the structural floor system of Level Five in Building 1 possesses the necessary strength to support the new server and demarcation room.

As listed in sheet S001, Buildings 1,2,4 and 11 are Critical facilities and have been assigned to

Seismic Design Category (SDC) C based upon their Risk Category and the site spectral response acceleration parameters. VA Seismic Design Requirements H-18-8 requires that VA facilities assigned to SDC C are required to provide seismic bracing of non-structural components per ASCE 41 Chapter 13 for existing structures. The design of seismic bracing is to be delegated to the supplier per VA Master Construction Specifications Section 13 05 41.

Roof top units (RTU’s) are being added to the roofs. The units weigh 218 lb (use 250 lb for design). A diagram is shown on the following page (foot print is 3.34 sq ft). This is 75 psf.

Notes have been added to the structural drawings with the assumptions which need to be verified during construction.