This package of architectural drawings and specifications is for a construction project to upgrade telecommunications infrastructure at the Bonham VA Medical Center in Bonham, Texas. The project involves renovating and upgrading multiple buildings on the campus, including building new telecommunications rooms and upgrading existing ones. Key aspects of the project include installing new cabling, replacing network equipment, upgrading electrical systems, and renovating spaces throughout various buildings. The construction is scheduled to be completed by July 2023. The federal agency overseeing the project is the Department of Veterans Affairs.
View the file
Other files
Show 40 more
Latest 50 of 70 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
CLOSET
CLOSET
AE101
1. OVERALL PLANS ARE ONLY INCLUDED TO SHOW GENERAL LOCATION OF IN-SCOPE SPACES ON
EACH FLOOR WITHIN EACH BUILDING.
2. REFER TO ENLARGED PLANS FOR ADDITIONAL INFORMATION REGARDING DEMOLITION AND NEW
CONSTRUCTION WITHIN AND ADJACENT TO EACH IN-SCOPE ROOM.
3. WALL MOUNTED CLEAN AGENT TYPE FIRE EXTINGUISHER REQUIRED WITHIN MCR. CONTRACTOR
TO COORDINATE FINAL LOCATIONS WITH COR AT TIME OF CONSTRUCTION.
4. WALL MOUNTED CARBON DIOXIDE OR CLEAN AGENT TYPE FIRE EXTINGUISHERS REQUIRED
WITHIN 75 FT OF NEW TR. CONTRACTOR TO COORDINATE FINAL LOCATIONS WITH COR AT TIME
OF CONSTRUCTION. EXTINGUISHERS MAY NOT BE LOCATED WITHIN THE TR.
GENERAL OVERALL PLAN NOTES
CLOSET
CLOSET
113A
98 SF / 100 SF
NEW TR
116A
145 SF / 100 SF
NEW TR
AE102
AE102
AE102
AE102
AE102
AE102
AE102
AE102
AF711
PARTITION LEGEND
1 HOUR FIRE RATED
2 HOUR FIRE RATED
3 HOUR FIRE RATED
SMOKE PARTITION/BARRIER
EXISTING WALL TO REMAIN
NEW NON-RATED WALLS
EXISTING 1 HOUR FIRE
EXISTING 2 HOUR FIRE
NOTE: NOT ALL SYMBOLS MAY BE USED
PLAN LEGEND
TE LOCATIONS
AREA WITHIN ARCHITECTURAL SCOPE
AREA NOT IN SCOPE
AREA FOR NEW DATA OUTLETS ONLYth re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
CONSULTANTS:
CIVIL ENGINEER
OLSSON
550 ST LOUIS ST,
SPRINGFIELD, MO 65806
(417) 885-1736
MECH / ELEC ENGINEER
SPUR DESIGN
2519 MADISON AVE., STE. 100
KANSAS CITY, MO 64108
(913) 369-7200
FIRE PROTECTION ENGINEER
RATED ENGINEERING
609 S. KELLY AVENUE, SUITE H2
EDMOND, OK 73003
(405) 856-2965
INDUSTRIAL HYGENIST
RIVERFRONT SAFETY & HEALTH
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
TECH ENGINEER
ASPEN COMMUNICATIONS, LLC
7 KIJI-DAVA CIRCLE, SUITE A
PRESCOTT, AZ 86301
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STRUCT ENGINEER
STAND STRUCTURAL ENGINEERING
8234 ROBINSON STREET
OVERLAND PARK, KS 66204
(913) 214-2169
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Drawing #
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH REG. NO. BR 2171 EXP. 09/30/2023
ENGR REG. NO. F-17591 EXP. 02/29/2024
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
STAMP:
Drawing Number
Building Number
BUILDING 34 NOT SPRINKLERED. ALL OTHER BUILDINGS FULLY SPRINKLERED.
COMMISSIONING
ES2
13401 N. SANTA FE AVE
OKLAHOMA CITY, OK 73114
(405) 528-4500
CONTROLLED UNCLASSIFIED INFORMATION (CUI)
CONTROLLED UNCLASSIFIED INFORMATION (CUI)
C O
N T
R O
L L E
D U
N C
L A
S S
IF
IE
D I
N F
O R
M A
T
IO
N
C U
I)
/6
/2
:3
:0
A
M
100% BID DOCUMENTS
BUILDING 1 - REFERENCE PLANS
NSM 53 OF 229AJS
BONHAM EHRM
INFRASTRUCTURE
UPGRADES
07/07/2023
549A4-21-700
BONHAM VA MEDICAL CENTER
1201 E. 9TH STREET
BONHAM, TX 75418
A-101
SPUR #: 2216
N
1/16" = 1'-0"
BLDG 1 - BASEMENT1
N
1/16" = 1'-0"
BLDG 1 - LEVEL 12
KEY PLAN
N
No. REVISION DESCRIPTION DATE
148 SF / 100 SF
NEW TR
AE103
AE103
CLOSET
317A
CLOSET
317B
AF711
FIRE RISER
300G
144 SF / 100 SF
NEW TR
AE103
AE103
CLOSET
AF711
FIRE RISER
200G
150 SF / 100 SF
NEW TR
AE103
AE103
CLOSET
CLOSET
418A
AF711
FIRE RISER
400G
AE104
AE104
NEW FP
CLOSET
NEW SERVER
AF711
FIRE RISER
500E
1. OVERALL PLANS ARE ONLY INCLUDED TO SHOW GENERAL LOCATION OF IN-SCOPE SPACES ON
EACH FLOOR WITHIN EACH BUILDING.
2. REFER TO ENLARGED PLANS FOR ADDITIONAL INFORMATION REGARDING DEMOLITION AND NEW
CONSTRUCTION WITHIN AND ADJACENT TO EACH IN-SCOPE ROOM.
3. WALL MOUNTED CLEAN AGENT TYPE FIRE EXTINGUISHER REQUIRED WITHIN MCR. CONTRACTOR
TO COORDINATE FINAL LOCATIONS WITH COR AT TIME OF CONSTRUCTION.
4. WALL MOUNTED CARBON DIOXIDE OR CLEAN AGENT TYPE FIRE EXTINGUISHERS REQUIRED
WITHIN 75 FT OF NEW TR. CONTRACTOR TO COORDINATE FINAL LOCATIONS WITH COR AT TIME
OF CONSTRUCTION. EXTINGUISHERS MAY NOT BE LOCATED WITHIN THE TR.
GENERAL OVERALL PLAN NOTES
PARTITION LEGEND
1 HOUR FIRE RATED
2 HOUR FIRE RATED
3 HOUR FIRE RATED
SMOKE PARTITION/BARRIER
EXISTING WALL TO REMAIN
NEW NON-RATED WALLS
EXISTING 1 HOUR FIRE
EXISTING 2 HOUR FIRE
NOTE: NOT ALL SYMBOLS MAY BE USED
PLAN LEGEND
TE LOCATIONS
AREA WITHIN ARCHITECTURAL SCOPE
AREA NOT IN SCOPE
AREA FOR NEW DATA OUTLETS ONLY
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
CONSULTANTS:
CIVIL ENGINEER
OLSSON
550 ST LOUIS ST,
SPRINGFIELD, MO 65806
(417) 885-1736
MECH / ELEC ENGINEER
SPUR DESIGN
2519 MADISON AVE., STE. 100
KANSAS CITY, MO 64108
(913) 369-7200
FIRE PROTECTION ENGINEER
RATED ENGINEERING
609 S. KELLY AVENUE, SUITE H2
EDMOND, OK 73003
(405) 856-2965
INDUSTRIAL HYGENIST
RIVERFRONT SAFETY & HEALTH
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
TECH ENGINEER
ASPEN COMMUNICATIONS, LLC
7 KIJI-DAVA CIRCLE, SUITE A
PRESCOTT, AZ 86301
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STRUCT ENGINEER
STAND STRUCTURAL ENGINEERING
8234 ROBINSON STREET
OVERLAND PARK, KS 66204
(913) 214-2169
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Drawing #
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH REG. NO. BR 2171 EXP. 09/30/2023
ENGR REG. NO. F-17591 EXP. 02/29/2024
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
STAMP:
Drawing Number
Building Number
BUILDING 34 NOT SPRINKLERED. ALL OTHER BUILDINGS FULLY SPRINKLERED.
COMMISSIONING
ES2
13401 N. SANTA FE AVE
OKLAHOMA CITY, OK 73114
(405) 528-4500
CONTROLLED UNCLASSIFIED INFORMATION (CUI)
CONTROLLED UNCLASSIFIED INFORMATION (CUI)
C O
N T
R O
L L E
D U
N C
L A
S S
IF
IE
D I
N F
O R
M A
T
IO
N
C U
I)
/6
/2
:3
:0
A
M
100% BID DOCUMENTS
BUILDING 1 - REFERENCE PLANS
NSM 54 OF 229AJS
BONHAM EHRM
INFRASTRUCTURE
UPGRADES
07/07/2023
549A4-21-700
BONHAM VA MEDICAL CENTER
1201 E. 9TH STREET
BONHAM, TX 75418
A-102
SPUR #: 2216
N
1/16" = 1'-0"
BLDG 1 - LEVEL 32
N
1/16" = 1'-0"
BLDG 1 - LEVEL 21
N
1/16" = 1'-0"
BLDG 1 - LEVEL 43
N
1/16" = 1'-0"
BLDG 1 - LEVEL 54
KEY PLAN
N
100C
100A
AE105
AE105
AE105
AE105
196 SF / 100 SF
NEW TR
AE105
AE105
109 SF / 100 SF
NEW TR
114 SF / 100 SF
NEW TR
CLOSET
AE105
AE106
AE105
AE106
VESTIBULE
201B
HAC
201A
1. OVERALL PLANS ARE ONLY INCLUDED TO SHOW GENERAL LOCATION OF IN-SCOPE SPACES ON
EACH FLOOR WITHIN EACH BUILDING.
2. REFER TO ENLARGED PLANS FOR ADDITIONAL INFORMATION REGARDING DEMOLITION AND NEW
CONSTRUCTION WITHIN AND ADJACENT TO EACH IN-SCOPE ROOM.
3. WALL MOUNTED CLEAN AGENT TYPE FIRE EXTINGUISHER REQUIRED WITHIN MCR. CONTRACTOR
TO COORDINATE FINAL LOCATIONS WITH COR AT TIME OF CONSTRUCTION.
4. WALL MOUNTED CARBON DIOXIDE OR CLEAN AGENT TYPE FIRE EXTINGUISHERS REQUIRED
WITHIN 75 FT OF NEW TR. CONTRACTOR TO COORDINATE FINAL LOCATIONS WITH COR AT TIME
OF CONSTRUCTION. EXTINGUISHERS MAY NOT BE LOCATED WITHIN THE TR.
GENERAL OVERALL PLAN NOTES
PARTITION LEGEND
1 HOUR FIRE RATED
2 HOUR FIRE RATED
3 HOUR FIRE RATED
SMOKE PARTITION/BARRIER
EXISTING WALL TO REMAIN
NEW NON-RATED WALLS
EXISTING 1 HOUR FIRE
EXISTING 2 HOUR FIRE
NOTE: NOT ALL SYMBOLS MAY BE USED
PLAN LEGEND
TE LOCATIONS
AREA WITHIN ARCHITECTURAL SCOPE
AREA NOT IN SCOPE
AREA FOR NEW DATA OUTLETS ONLY
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
CONSULTANTS:
CIVIL ENGINEER
OLSSON
550 ST LOUIS ST,
SPRINGFIELD, MO 65806
(417) 885-1736
MECH / ELEC ENGINEER
SPUR DESIGN
2519 MADISON AVE., STE. 100
KANSAS CITY, MO 64108
(913) 369-7200
FIRE PROTECTION ENGINEER
RATED ENGINEERING
609 S. KELLY AVENUE, SUITE H2
EDMOND, OK 73003
(405) 856-2965
INDUSTRIAL HYGENIST
RIVERFRONT SAFETY & HEALTH
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
TECH ENGINEER
ASPEN COMMUNICATIONS, LLC
7 KIJI-DAVA CIRCLE, SUITE A
PRESCOTT, AZ 86301
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STRUCT ENGINEER
STAND STRUCTURAL ENGINEERING
8234 ROBINSON STREET
OVERLAND PARK, KS 66204
(913) 214-2169
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Drawing #
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH REG. NO. BR 2171 EXP. 09/30/2023
ENGR REG. NO. F-17591 EXP. 02/29/2024
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
STAMP:
Drawing Number
Building Number
BUILDING 34 NOT SPRINKLERED. ALL OTHER BUILDINGS FULLY SPRINKLERED.
COMMISSIONING
ES2
13401 N. SANTA FE AVE
OKLAHOMA CITY, OK 73114
(405) 528-4500
CONTROLLED UNCLASSIFIED INFORMATION (CUI)
CONTROLLED UNCLASSIFIED INFORMATION (CUI)
C O
N T
R O
L L E
D U
N C
L A
S S
IF
IE
D I
N F
O R
M A
T
IO
N
C U
I)
/6
/2
:3
:0
A
M
100% BID DOCUMENTS
BUILDING 2 - REFERENCE PLANS
NSM 55 OF 229AJS
BONHAM EHRM
INFRASTRUCTURE
UPGRADES
07/07/2023
549A4-21-700
BONHAM VA MEDICAL CENTER
1201 E. 9TH STREET
BONHAM, TX 75418
A-103
SPUR #: 2216
N
1/16" = 1'-0"
BLDG 2 - LEVEL 11
N
1/16" = 1'-0"
BLDG 2 - LEVEL 22
KEY PLAN
N
147 SF / 100 SF
NEW TR
301A
AE106
AE106
AE106
AE106
CORRIDOR
CLOSET
301B
CLOSET
134 SF / 100 SF
NEW TR
401A
AE106
AE107
AE106
AE107
CLOSET
401B
CORRIDOR
1. OVERALL PLANS ARE ONLY INCLUDED TO SHOW GENERAL LOCATION OF IN-SCOPE SPACES ON
EACH FLOOR WITHIN EACH BUILDING.
2. REFER TO ENLARGED PLANS FOR ADDITIONAL INFORMATION REGARDING DEMOLITION AND NEW
CONSTRUCTION WITHIN AND ADJACENT TO EACH IN-SCOPE ROOM.
3. WALL MOUNTED CLEAN AGENT TYPE FIRE EXTINGUISHER REQUIRED WITHIN MCR. CONTRACTOR
TO COORDINATE FINAL LOCATIONS WITH COR AT TIME OF CONSTRUCTION.
4. WALL MOUNTED CARBON DIOXIDE OR CLEAN AGENT TYPE FIRE EXTINGUISHERS REQUIRED
WITHIN 75 FT OF NEW TR. CONTRACTOR TO COORDINATE FINAL LOCATIONS WITH COR AT TIME
OF CONSTRUCTION. EXTINGUISHERS MAY NOT BE LOCATED WITHIN THE TR.
GENERAL OVERALL PLAN NOTES
PARTITION LEGEND
1 HOUR FIRE RATED
2 HOUR FIRE RATED
3 HOUR FIRE RATED
SMOKE PARTITION/BARRIER
EXISTING WALL TO REMAIN
NEW NON-RATED WALLS
EXISTING 1 HOUR FIRE
EXISTING 2 HOUR FIRE
NOTE: NOT ALL SYMBOLS MAY BE USED
PLAN LEGEND
TE LOCATIONS
AREA WITHIN ARCHITECTURAL SCOPE
AREA NOT IN SCOPE
AREA FOR NEW DATA OUTLETS ONLY
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
CONSULTANTS:
CIVIL ENGINEER
OLSSON
550 ST LOUIS ST,
SPRINGFIELD, MO 65806
(417) 885-1736
MECH / ELEC ENGINEER
SPUR DESIGN
2519 MADISON AVE., STE. 100
KANSAS CITY, MO 64108
(913) 369-7200
FIRE PROTECTION ENGINEER
RATED ENGINEERING
609 S. KELLY AVENUE, SUITE H2
EDMOND, OK 73003
(405) 856-2965
INDUSTRIAL HYGENIST
RIVERFRONT SAFETY & HEALTH
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
TECH ENGINEER
ASPEN COMMUNICATIONS, LLC
7 KIJI-DAVA CIRCLE, SUITE A
PRESCOTT, AZ 86301
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STRUCT ENGINEER
STAND STRUCTURAL ENGINEERING
8234 ROBINSON STREET
OVERLAND PARK, KS 66204
(913) 214-2169
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Drawing #
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH REG. NO. BR 2171 EXP. 09/30/2023
ENGR REG. NO. F-17591 EXP. 02/29/2024
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
STAMP:
Drawing Number
Building Number
BUILDING 34 NOT SPRINKLERED. ALL OTHER BUILDINGS FULLY SPRINKLERED.
COMMISSIONING
ES2
13401 N. SANTA FE AVE
OKLAHOMA CITY, OK 73114
(405) 528-4500
CONTROLLED UNCLASSIFIED INFORMATION (CUI)
CONTROLLED UNCLASSIFIED INFORMATION (CUI)
C O
N T
R O
L L E
D U
N C
L A
S S
IF
IE
D I
N F
O R
M A
T
IO
N
C U
I)
/6
/2
:3
:0
A
M
100% BID DOCUMENTS
BUILDING 2 - REFERENCE PLANS
NSM 56 OF 229AJS
BONHAM EHRM
INFRASTRUCTURE
UPGRADES
07/07/2023
549A4-21-700
BONHAM VA MEDICAL CENTER
1201 E. 9TH STREET
BONHAM, TX 75418
A-104
SPUR #: 2216
N
1/16" = 1'-0"
BLDG 2 - LEVEL 31
N
1/16" = 1'-0"
BLDG 2 - LEVEL 42
KEY PLAN
N
E T
D
AE107
AE107
153 SF / 100 SF
NEW TR
135B
OFFICE
135A
CLOSET
106A
AE108
AE108
CARPENTRY
SHOP
107A
AE108
AE108
AE108
EX. COMM
NEW TE
107A
126 SF / 100 SF
NEW TR
AE109
AE109
1. OVERALL PLANS ARE ONLY INCLUDED TO SHOW GENERAL LOCATION OF IN-SCOPE SPACES ON
EACH FLOOR WITHIN EACH BUILDING.
2. REFER TO ENLARGED PLANS FOR ADDITIONAL INFORMATION REGARDING DEMOLITION AND NEW
CONSTRUCTION WITHIN AND ADJACENT TO EACH IN-SCOPE ROOM.
3. WALL MOUNTED CLEAN AGENT TYPE FIRE EXTINGUISHER REQUIRED WITHIN MCR. CONTRACTOR
TO COORDINATE FINAL LOCATIONS WITH COR AT TIME OF CONSTRUCTION.
4. WALL MOUNTED CARBON DIOXIDE OR CLEAN AGENT TYPE FIRE EXTINGUISHERS REQUIRED
WITHIN 75 FT OF NEW TR. CONTRACTOR TO COORDINATE FINAL LOCATIONS WITH COR AT TIME
OF CONSTRUCTION. EXTINGUISHERS MAY NOT BE LOCATED WITHIN THE TR.
GENERAL OVERALL PLAN NOTES
161 SF / 100 SF
NEW TR
AE108
AE108
130 SF / 100 SF
NEW TR
201B
AE107
AE107
CLOSET
201C
AE109
CLOSET
114F
AE109
PARTITION LEGEND
1 HOUR FIRE RATED
2 HOUR FIRE RATED
3 HOUR FIRE RATED
SMOKE PARTITION/BARRIER
EXISTING WALL TO REMAIN
NEW NON-RATED WALLS
EXISTING 1 HOUR FIRE
EXISTING 2 HOUR FIRE
NOTE: NOT ALL SYMBOLS MAY BE USED
PLAN LEGEND
TE LOCATIONS
AREA WITHIN ARCHITECTURAL SCOPE
AREA NOT IN SCOPE
AREA FOR NEW DATA OUTLETS ONLY
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
CONSULTANTS:
CIVIL ENGINEER
OLSSON
550 ST LOUIS ST,
SPRINGFIELD, MO 65806
(417) 885-1736
MECH / ELEC ENGINEER
SPUR DESIGN
2519 MADISON AVE., STE. 100
KANSAS CITY, MO 64108
(913) 369-7200
FIRE PROTECTION ENGINEER
RATED ENGINEERING
609 S. KELLY AVENUE, SUITE H2
EDMOND, OK 73003
(405) 856-2965
INDUSTRIAL HYGENIST
RIVERFRONT SAFETY & HEALTH
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
TECH ENGINEER
ASPEN COMMUNICATIONS, LLC
7 KIJI-DAVA CIRCLE, SUITE A
PRESCOTT, AZ 86301
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STRUCT ENGINEER
STAND STRUCTURAL ENGINEERING
8234 ROBINSON STREET
OVERLAND PARK, KS 66204
(913) 214-2169
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Drawing #
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH REG. NO. BR 2171 EXP. 09/30/2023
ENGR REG. NO. F-17591 EXP. 02/29/2024
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
STAMP:
Drawing Number
Building Number
BUILDING 34 NOT SPRINKLERED. ALL OTHER BUILDINGS FULLY SPRINKLERED.
COMMISSIONING
ES2
13401 N. SANTA FE AVE
OKLAHOMA CITY, OK 73114
(405) 528-4500
CONTROLLED UNCLASSIFIED INFORMATION (CUI)
CONTROLLED UNCLASSIFIED INFORMATION (CUI)
C O
N T
R O
L L E
D U
N C
L A
S S
IF
IE
D I
N F
O R
M A
T
IO
N
C U
I)
/6
/2
:3
:0
A
M
100% BID DOCUMENTS
BUILDINGS 3, 4, 8, & 9 - REFERENCE
PLANS
NSM 57 OF 229AJS
BONHAM EHRM
INFRASTRUCTURE
UPGRADES
07/07/2023
549A4-21-700
BONHAM VA MEDICAL CENTER
1201 E. 9TH STREET
BONHAM, TX 75418
A-105
SPUR #: 2216
3, 4, 8, & 9
N
1/16" = 1'-0"
BLDG 3 - LEVEL 11
N
1/16" = 1'-0"
BLDG 4 - LEVEL 13
N
1/16" = 1'-0"
BLDG 8 - LEVEL 15
N
1/16" = 1'-0"
BLDG 9 - LEVEL 16
N
1/16" = 1'-0"
BLDG 4 - LEVEL 24
N
1/16" = 1'-0"
BLDG 3 - LEVEL 22
N
1/16" = 1'-0"
BLDG 9 - LEVEL 27
KEY PLAN
N
105A
127 SF / 100 SF
NEW TR
RESTROOM
AE109
AE109
AE109
AE109
AE110
AE110
106 SF / 100 SF
OFFICE
NEW TE
102A
CLOSET
AE110
AE110
120 SF / 100 SF
NEW TR
AE110
AE110
1. OVERALL PLANS ARE ONLY INCLUDED TO SHOW GENERAL LOCATION OF IN-SCOPE SPACES ON
EACH FLOOR WITHIN EACH BUILDING.
2. REFER TO ENLARGED PLANS FOR ADDITIONAL INFORMATION REGARDING DEMOLITION AND NEW
CONSTRUCTION WITHIN AND ADJACENT TO EACH IN-SCOPE ROOM.
3. WALL MOUNTED CLEAN AGENT TYPE FIRE EXTINGUISHER REQUIRED WITHIN MCR. CONTRACTOR
TO COORDINATE FINAL LOCATIONS WITH COR AT TIME OF CONSTRUCTION.
4. WALL MOUNTED CARBON DIOXIDE OR CLEAN AGENT TYPE FIRE EXTINGUISHERS REQUIRED
WITHIN 75 FT OF NEW TR. CONTRACTOR TO COORDINATE FINAL LOCATIONS WITH COR AT TIME
OF CONSTRUCTION. EXTINGUISHERS MAY NOT BE LOCATED WITHIN THE TR.
GENERAL OVERALL PLAN NOTES
PARTITION LEGEND
1 HOUR FIRE RATED
2 HOUR FIRE RATED
3 HOUR FIRE RATED
SMOKE PARTITION/BARRIER
EXISTING WALL TO REMAIN
NEW NON-RATED WALLS
EXISTING 1 HOUR FIRE
EXISTING 2 HOUR FIRE
NOTE: NOT ALL SYMBOLS MAY BE USED
PLAN LEGEND
TE LOCATIONS
AREA WITHIN ARCHITECTURAL SCOPE
AREA NOT IN SCOPE
AREA FOR NEW DATA OUTLETS ONLY
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
CONSULTANTS:
CIVIL ENGINEER
OLSSON
550 ST LOUIS ST,
SPRINGFIELD, MO 65806
(417) 885-1736
MECH / ELEC ENGINEER
SPUR DESIGN
2519 MADISON AVE., STE. 100
KANSAS CITY, MO 64108
(913) 369-7200
FIRE PROTECTION ENGINEER
RATED ENGINEERING
609 S. KELLY AVENUE, SUITE H2
EDMOND, OK 73003
(405) 856-2965
INDUSTRIAL HYGENIST
RIVERFRONT SAFETY & HEALTH
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
TECH ENGINEER
ASPEN COMMUNICATIONS, LLC
7 KIJI-DAVA CIRCLE, SUITE A
PRESCOTT, AZ 86301
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STRUCT ENGINEER
STAND STRUCTURAL ENGINEERING
8234 ROBINSON STREET
OVERLAND PARK, KS 66204
(913) 214-2169
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Drawing #
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH REG. NO. BR 2171 EXP. 09/30/2023
ENGR REG. NO. F-17591 EXP. 02/29/2024
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
STAMP:
Drawing Number
Building Number
BUILDING 34 NOT SPRINKLERED. ALL OTHER BUILDINGS FULLY SPRINKLERED.
COMMISSIONING
ES2
13401 N. SANTA FE AVE
OKLAHOMA CITY, OK 73114
(405) 528-4500
CONTROLLED UNCLASSIFIED INFORMATION (CUI)
CONTROLLED UNCLASSIFIED INFORMATION (CUI)
C O
N T
R O
L L E
D U
N C
L A
S S
IF
IE
D I
N F
O R
M A
T
IO
N
C U
I)
/6
/2
:3
:0
A
M
100% BID DOCUMENTS
BUILDINGS 10, 11, & 12 - REFERENCE
PLANS
NSM 58 OF 229AJS
BONHAM EHRM
INFRASTRUCTURE
UPGRADES
07/07/2023
549A4-21-700
BONHAM VA MEDICAL CENTER
1201 E. 9TH STREET
BONHAM, TX 75418
A-106
SPUR #: 2216
10, 11, 12, & 34
N
1/16" = 1'-0"
BLDG 10 - LEVEL 11
N
1/16" = 1'-0"
BLDG 11 - LEVEL 12
N
1/16" = 1'-0"
BLDG 12 - LEVEL 23
KEY PLAN
N
1. OVERALL PLANS ARE ONLY INCLUDED TO SHOW GENERAL LOCATION OF IN-SCOPE SPACES ON
EACH FLOOR WITHIN EACH BUILDING.
2. REFER TO ENLARGED PLANS FOR ADDITIONAL INFORMATION REGARDING DEMOLITION AND NEW
CONSTRUCTION WITHIN AND ADJACENT TO EACH IN-SCOPE ROOM.
3. WALL MOUNTED CLEAN AGENT TYPE FIRE EXTINGUISHER REQUIRED WITHIN MCR. CONTRACTOR
TO COORDINATE FINAL LOCATIONS WITH COR AT TIME OF CONSTRUCTION.
4. WALL MOUNTED CARBON DIOXIDE OR CLEAN AGENT TYPE FIRE EXTINGUISHERS REQUIRED
WITHIN 75 FT OF NEW TR. CONTRACTOR TO COORDINATE FINAL LOCATIONS WITH COR AT TIME
OF CONSTRUCTION. EXTINGUISHERS MAY NOT BE LOCATED WITHIN THE TR.
GENERAL OVERALL PLAN NOTES
AE111
127 SF / 100 SF
NEW TR
1C-111
AE111
119 SF / 100 SF
NEW TR
1B-108
AE111
AE111
CLOSET
1C-112
PARTITION LEGEND
1 HOUR FIRE RATED
2 HOUR FIRE RATED
3 HOUR FIRE RATED
SMOKE PARTITION/BARRIER
EXISTING WALL TO REMAIN
NEW NON-RATED WALLS
EXISTING 1 HOUR FIRE
EXISTING 2 HOUR FIRE
NOTE: NOT ALL SYMBOLS MAY BE USED
PLAN LEGEND
TE LOCATIONS
AREA WITHIN ARCHITECTURAL SCOPE
AREA NOT IN SCOPE
AREA FOR NEW DATA OUTLETS ONLY
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
CONSULTANTS:
CIVIL ENGINEER
OLSSON
550 ST LOUIS ST,
SPRINGFIELD, MO 65806
(417) 885-1736
MECH / ELEC ENGINEER
SPUR DESIGN
2519 MADISON AVE., STE. 100
KANSAS CITY, MO 64108
(913) 369-7200
FIRE PROTECTION ENGINEER
RATED ENGINEERING
609 S. KELLY AVENUE, SUITE H2
EDMOND, OK 73003
(405) 856-2965
INDUSTRIAL HYGENIST
RIVERFRONT SAFETY & HEALTH
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
TECH ENGINEER
ASPEN COMMUNICATIONS, LLC
7 KIJI-DAVA CIRCLE, SUITE A
PRESCOTT, AZ 86301
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STRUCT ENGINEER
STAND STRUCTURAL ENGINEERING
8234 ROBINSON STREET
OVERLAND PARK, KS 66204
(913) 214-2169
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Drawing #
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH REG. NO. BR 2171 EXP. 09/30/2023
ENGR REG. NO. F-17591 EXP. 02/29/2024
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
STAMP:
Drawing Number
Building Number
BUILDING 34 NOT SPRINKLERED. ALL OTHER BUILDINGS FULLY SPRINKLERED.
COMMISSIONING
ES2
13401 N. SANTA FE AVE
OKLAHOMA CITY, OK 73114
(405) 528-4500
CONTROLLED UNCLASSIFIED INFORMATION (CUI)
CONTROLLED UNCLASSIFIED INFORMATION (CUI)
C O
N T
R O
L L E
D U
N C
L A
S S
IF
IE
D I
N F
O R
M A
T
IO
N
C U
I)
/6
/2
:3
:0
A
M
100% BID DOCUMENTS
BUILDING 24 - REFERENCE PLAN
NSM 59 OF 229AJS
BONHAM EHRM
INFRASTRUCTURE
UPGRADES
07/07/2023
549A4-21-700
BONHAM VA MEDICAL CENTER
1201 E. 9TH STREET
BONHAM, TX 75418
A-107
SPUR #: 2216
1/16" = 1'-0"
BLDG 24 - LEVEL 11N
KEY PLAN
N
E X
IT
CLOSET
2A-108
CLOSET
2A-102
AE112
ELEC
2A-101
AE112
ELEC
2A-109
AE112
122 SF / 100 SF
NEW TR
2C-108
AE112
122 SF / 100 SF
NEW TR
2B-108
AE112
AE112
AE112
AE112
1. OVERALL PLANS ARE ONLY INCLUDED TO SHOW GENERAL LOCATION OF IN-SCOPE SPACES ON
EACH FLOOR WITHIN EACH BUILDING.
2. REFER TO ENLARGED PLANS FOR ADDITIONAL INFORMATION REGARDING DEMOLITION AND NEW
CONSTRUCTION WITHIN AND ADJACENT TO EACH IN-SCOPE ROOM.
3. WALL MOUNTED CLEAN AGENT TYPE FIRE EXTINGUISHER REQUIRED WITHIN MCR. CONTRACTOR
TO COORDINATE FINAL LOCATIONS WITH COR AT TIME OF CONSTRUCTION.
4. WALL MOUNTED CARBON DIOXIDE OR CLEAN AGENT TYPE FIRE EXTINGUISHERS REQUIRED
WITHIN 75 FT OF NEW TR. CONTRACTOR TO COORDINATE FINAL LOCATIONS WITH COR AT TIME
OF CONSTRUCTION. EXTINGUISHERS MAY NOT BE LOCATED WITHIN THE TR.
GENERAL OVERALL PLAN NOTES
PARTITION LEGEND
1 HOUR FIRE RATED
2 HOUR FIRE RATED
3 HOUR FIRE RATED
SMOKE PARTITION/BARRIER
EXISTING WALL TO REMAIN
NEW NON-RATED WALLS
EXISTING 1 HOUR FIRE
EXISTING 2 HOUR FIRE
NOTE: NOT ALL SYMBOLS MAY BE USED
PLAN LEGEND
TE LOCATIONS
AREA WITHIN ARCHITECTURAL SCOPE
AREA NOT IN SCOPE
AREA FOR NEW DATA OUTLETS ONLY
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
CONSULTANTS:
CIVIL ENGINEER
OLSSON
550 ST LOUIS ST,
SPRINGFIELD, MO 65806
(417) 885-1736
MECH / ELEC ENGINEER
SPUR DESIGN
2519 MADISON AVE., STE. 100
KANSAS CITY, MO 64108
(913) 369-7200
FIRE PROTECTION ENGINEER
RATED ENGINEERING
609 S. KELLY AVENUE, SUITE H2
EDMOND, OK 73003
(405) 856-2965
INDUSTRIAL HYGENIST
RIVERFRONT SAFETY & HEALTH
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
TECH ENGINEER
ASPEN COMMUNICATIONS, LLC
7 KIJI-DAVA CIRCLE, SUITE A
PRESCOTT, AZ 86301
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STRUCT ENGINEER
STAND STRUCTURAL ENGINEERING
8234 ROBINSON STREET
OVERLAND PARK, KS 66204
(913) 214-2169
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Drawing #
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH REG. NO. BR 2171 EXP. 09/30/2023
ENGR REG. NO. F-17591 EXP. 02/29/2024
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
STAMP:
Drawing Number
Building Number
BUILDING 34 NOT SPRINKLERED. ALL OTHER BUILDINGS FULLY SPRINKLERED.
COMMISSIONING
ES2
13401 N. SANTA FE AVE
OKLAHOMA CITY, OK 73114
(405) 528-4500
CONTROLLED UNCLASSIFIED INFORMATION (CUI)
CONTROLLED UNCLASSIFIED INFORMATION (CUI)
C O
N T
R O
L L E
D U
N C
L A
S S
IF
IE
D I
N F
O R
M A
T
IO
N
C U
I)
/6
/2
:3
:1
A
M
100% BID DOCUMENTS
BUILDING 24 - REFERENCE PLAN
NSM 60 OF 229AJS
BONHAM EHRM
INFRASTRUCTURE
UPGRADES
07/07/2023
549A4-21-700
BONHAM VA MEDICAL CENTER
1201 E. 9TH STREET
BONHAM, TX 75418
A-108
SPUR #: 2216
1/16" = 1'-0"
BLDG 24 - LEVEL 21N
KEY PLAN
N
B2200
CORRIDOR
CLOSET
B2110
CLOSET
C3112
122 SF / 100 SF
NEW TR
C3108
121 SF / 100 SF
NEW TR
B2107
AE113
AE113
AE113
AE113
AE113
AE113
AE113
AE113
1. OVERALL PLANS ARE ONLY INCLUDED TO SHOW GENERAL LOCATION OF IN-SCOPE SPACES ON
EACH FLOOR WITHIN EACH BUILDING.
2. REFER TO ENLARGED PLANS FOR ADDITIONAL INFORMATION REGARDING DEMOLITION AND NEW
CONSTRUCTION WITHIN AND ADJACENT TO EACH IN-SCOPE ROOM.
3. WALL MOUNTED CLEAN AGENT TYPE FIRE EXTINGUISHER REQUIRED WITHIN MCR. CONTRACTOR
TO COORDINATE FINAL LOCATIONS WITH COR AT TIME OF CONSTRUCTION.
4. WALL MOUNTED CARBON DIOXIDE OR CLEAN AGENT TYPE FIRE EXTINGUISHERS REQUIRED
WITHIN 75 FT OF NEW TR. CONTRACTOR TO COORDINATE FINAL LOCATIONS WITH COR AT TIME
OF CONSTRUCTION. EXTINGUISHERS MAY NOT BE LOCATED WITHIN THE TR.
GENERAL OVERALL PLAN NOTES
PARTITION LEGEND
1 HOUR FIRE RATED
2 HOUR FIRE RATED
3 HOUR FIRE RATED
SMOKE PARTITION/BARRIER
EXISTING WALL TO REMAIN
NEW NON-RATED WALLS
EXISTING 1 HOUR FIRE
EXISTING 2 HOUR FIRE
NOTE: NOT ALL SYMBOLS MAY BE USED
PLAN LEGEND
TE LOCATIONS
AREA WITHIN ARCHITECTURAL SCOPE
AREA NOT IN SCOPE
AREA FOR NEW DATA OUTLETS ONLY
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
CONSULTANTS:
CIVIL ENGINEER
OLSSON
550 ST LOUIS ST,
SPRINGFIELD, MO 65806
(417) 885-1736
MECH / ELEC ENGINEER
SPUR DESIGN
2519 MADISON AVE., STE. 100
KANSAS CITY, MO 64108
(913) 369-7200
FIRE PROTECTION ENGINEER
RATED ENGINEERING
609 S. KELLY AVENUE, SUITE H2
EDMOND, OK 73003
(405) 856-2965
INDUSTRIAL HYGENIST
RIVERFRONT SAFETY & HEALTH
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
TECH ENGINEER
ASPEN COMMUNICATIONS, LLC
7 KIJI-DAVA CIRCLE, SUITE A
PRESCOTT, AZ 86301
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STRUCT ENGINEER
STAND STRUCTURAL ENGINEERING
8234 ROBINSON STREET
OVERLAND PARK, KS 66204
(913) 214-2169
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Drawing #
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH REG. NO. BR 2171 EXP. 09/30/2023
ENGR REG. NO. F-17591 EXP. 02/29/2024
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
STAMP:
Drawing Number
Building Number
BUILDING 34 NOT SPRINKLERED. ALL OTHER BUILDINGS FULLY SPRINKLERED.
COMMISSIONING
ES2
13401 N. SANTA FE AVE
OKLAHOMA CITY, OK 73114
(405) 528-4500
CONTROLLED UNCLASSIFIED INFORMATION (CUI)
CONTROLLED UNCLASSIFIED INFORMATION (CUI)
C O
N T
R O
L L E
D U
N C
L A
S S
IF
IE
D I
N F
O R
M A
T
IO
N
C U
I)
/6
/2
:3
:1
A
M
100% BID DOCUMENTS
BUILDING 29 - REFERENCE PLAN
NSM 61 OF 229AJS
BONHAM EHRM
INFRASTRUCTURE
UPGRADES
07/07/2023
549A4-21-700
BONHAM VA MEDICAL CENTER
1201 E. 9TH STREET
BONHAM, TX 75418
A-109
SPUR #: 2216
N
1/16" = 1'-0"
BLDG 29 - LEVEL 11
KEY PLAN
N
20'-0" 19'-7"
'-2
2.89 2.89
9.71 9.71
3' -0
3'-4"
COMM
COMM
'-6
2.732.73 2.732.732.732.732.732.73 2.105
2.105
2.062.06
2' x 2' ACOUSTICAL CEILING
CEILING HEIGHT, ABOVE
FINISH FLOOR
00'-00"
REFLECTED CEILING PLAN LEGEND
DUCTLESS SPLIT INDOOR
UNIT, REF: MECHANICAL
RETURN AIR GRILLE
2 x 4 LIGHT FIXTURE
RE: ELECTRICAL
SUSPENDED LIGHT FIXTURE
RE: ELECTRICAL
2' x 2' LIGHT FIXTURE
RE: ELECTRICAL
SUPPLY AIR DIFFUSER
1. ALL NEW DOOR FRAMES TO BE LOCATED 4" FROM OUTSIDE OF FRAME TO FINISH FACE OF ADJACENT WALL
UNLESS NOTED OTHERWISE.
2. FIRE CAULK ALL PENETRATIONS IN EXISTING WALLS, FLOORS, OR CEILINGS.
3. ALL WALLS TO GO TO DECK. IF EXISTING WALL DOES NOT CURRENTLY GO TO DECK, CONTRACTOR TO EXTEND WALL SYSTEM UP TO EXISTING STRUCTURE ABOVE PRIOR TO FIRE CAULKING. MAINTAINING
EXISTING FIRE RATING.
4. ALL NEW CONSTRUCTION WALLS ARE DIMENSIONED TO CENTERLINE OF METAL STUD, UNLESS NOTED
OTHERWISE.
5. ALL EXISTING WALLS ARE DIMENSIONED TO FACE OF EXISTING FINISH, UNLESS NOTED OTHERWISE.
6. ALL EXISTING GLAZING LOCATED IN EXTERIOR WALLS WITHIN EXISTING AND NEW TELECOM ROOMS SHALL RECEIVE 15-MINUTE FORCED INTRUSION RESISTANT FILM & CONTACT SENSORS TIED TO THE SECURITY
CONTROL CENTER.
GENERAL PLAN NOTES
1. CEILINGS IN ALL TR'S ARE TO BE OPEN TO BOTTOM OF DECK, UNLESS NOTED OTHERWISE.
2. ALL SURFACES OF FURRDOWNS TO BE PAINTED TO MATCH UNLESS NOTED OTHERWISE.
3. ALL FIXTURES IN DEMOLISHED CEILINGS ARE TO FIRST BE REMOVED AND RETURNED TO OWNER, UNO.
4. RECONFIGURE SPRINKLER SYSTEM IN DEMOLISHED CEILINGS PER FIRE PROTECTION REQUIREMENTS.
GENERAL REFLECTED CEILING PLAN NOTES
EXISTING DOOR & FRAME.
REF: KEYNOTES FOR
DEMOLITION NOTES
DEMOLITION & NEW FLOOR PLAN LEGEND
AREA NOT IN CONTRACT
EXISTING WALL TO BE
DEMOLISHED IN ITS ENTIRETY
EXISTING WALL TO REMAIN
& PROTECT
EXISTING DOOR & FRAME TO
REMAIN AND PROTECT
NEW DOOR & FRAME
APPLICATION.
REF: DOOR SCHEDULE
1. ALL EXISTING WALL DIMENSIONS ARE TO FINISH FACE, UNLESS OTHERWISE NOTED
2. THE CONTRACTOR SHALL VERIFY DIMENSIONS OF AS-BUILT CONDITIONS, AND NOTIFY THE ARCHITECT IN WRITING OF ANY DISCREPANCIES. ALL INFORMATION SHOWN ON THE CONSTRUCTION DOCUMENTS IS BASED ON FIELD OBSERVATIONS AND/OR THE ORIGINAL CONSTRUCTION DOCUMENTS OF THE FACILITY.
3. DEMOLITION AND CONSTRUCTION WORK MUST BE DONE UNDER NEGATIVE PRESSURE UTILIZING HEPA
FILTRATION UNITS. SEE INFECTION CONTROL NOTES.
4. DO NOT REMOVE BARRIERS FROM WORK AREA UNTIL PROJECT IS COMPLETED AND/OR AREA HAS BEEN INSPECTED BY THE SAFETY OFFICER AND INFECTION CONTROL COORDINATOR AND THOROUGHLY CLEANED
BY ENVIRONMENTAL MANAGEMENT SERVICES.
5. THE CONTRACTOR SHALL PROVIDE PROTECTIVE COVERING FOR EXISTING FLOOR, WALL AND CEILING FINISHES IN EXISTING AREAS NOT DESIGNATED FOR DEMOLITION OR NEW CONSTRUCTION. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE REPAIR OF ANY DAMAGE CAUSED BY HIS WORK OR ANY
SUBCONTRACTOR.
6. THE CONTRACTOR SHALL VERIFY THAT NEW MECHANICAL SYSTEMS CAN BE INSTALLED IN EXISTING SPACES TO CLEAR EXISTING CEILING AND OTHER CONSTRUCTED ITEMS AND MAINTAIN FLOOR TO CEILING HEIGHTS INDICATED ON DRAWINGS. IF DISCREPANCIES OCCUR DUE TO EXISTING CONDITIONS, CONSULT WITH THE
ARCHITECT BEFORE PROCEEDING.
7. THE FINISH FACE OF MATERIAL OF NEW PARTITIONS SHALL ALIGN ON BOTH SIDES OF THE PARTITION WITH THE FACE OF THE MATERIALS ON EXISTING COLUMNS, WALLS, OR PARTITIONS, UNLESS NOTED OTHERWISE.
8. NO WORK TO BE DONE IN AREAS HATCHED GRAY IN PLANS, HOWEVER WORK MIGHT NEED TO BE PERFORMED IN CEILING OR EXISTING CHASES THROUGHOUT BUILDING. REFERENCE MECHANICAL AND ELECTRICAL DRAWINGS FOR EXTENT OF WORK. COORDINATE ACCESS TO ROOMS OUTSIDE OF SCOPE WITH
OWNER.
9. ALL EXISTING TELECOM ROOMS THAT WILL NO LONGER BE USED AS A TELECOM ROOM ARE TO BE CLASSIFIED AS CLOSETS, UNO; HAVE ALL WALLS PATCHED & REPAIRED, EXISTING CARD READER REMOVED, FLOORS TO BE LEFT AS EXISTING, AND NEW STORAGE HARDWARE SET INSTALLED. FIRE CAULK AT ANY
JOINTS OR PENETRATIONS AS REQUIRED TO MAINTAIN FIRE AND/OR SMOKE RATING.
REFERENCE: DOOR & FINISH SCHEDULE FOR SPECIFICS.
GENERAL DEMOLITION NOTES
EXISTING 2' x 2' ACOUSTICAL
CEILING TO BE DEMOLISHED
EXISTING GYPSUM BOARD
CEILING TO BE DEMOLISHED
EXISTING 2 x 2 LIGHT FIXTURE
TO BE DEMOLISHED
EXISTING 2 x 4 LIGHT
FIXTURE TO BE DEMOLISHED
EXISTING 2' x 4' ACOUSTICAL
CEILING TO BE DEMOLISHED
EXISTING RETURN AIR GRILLE
TO BE DEMOLISHED
EXISTING SUPPLY AIR
DIFFUSER TO BE DEMOLISHED
EXISTING EXHAUST AIR
GRILLE TO BE DEMOLISHED
EXISTING RECESSED CAN
LIGHT TO BE DEMOLISHED
EXISTING PENDANT LIGHT TO
BE REMOVED
DEMOLITION REFLECTED CEILING PLAN LEGEND
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
CONSULTANTS:
CIVIL ENGINEER
OLSSON
550 ST LOUIS ST,
SPRINGFIELD, MO 65806
(417) 885-1736
MECH / ELEC ENGINEER
SPUR DESIGN
2519 MADISON AVE., STE. 100
KANSAS CITY, MO 64108
(913) 369-7200
FIRE PROTECTION ENGINEER
RATED ENGINEERING
609 S. KELLY AVENUE, SUITE H2
EDMOND, OK 73003
(405) 856-2965
INDUSTRIAL HYGENIST
RIVERFRONT SAFETY & HEALTH
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
TECH ENGINEER
ASPEN COMMUNICATIONS, LLC
7 KIJI-DAVA CIRCLE, SUITE A
PRESCOTT, AZ 86301
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STRUCT ENGINEER
STAND STRUCTURAL ENGINEERING
8234 ROBINSON STREET
OVERLAND PARK, KS 66204
(913) 214-2169
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Drawing #
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH REG. NO. BR 2171 EXP. 09/30/2023
ENGR REG. NO. F-17591 EXP. 02/29/2024
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
STAMP:
Drawing Number
Building Number
BUILDING 34 NOT SPRINKLERED. ALL OTHER BUILDINGS FULLY SPRINKLERED.
COMMISSIONING
ES2
13401 N. SANTA FE AVE
OKLAHOMA CITY, OK 73114
(405) 528-4500
CONTROLLED UNCLASSIFIED INFORMATION (CUI)
CONTROLLED UNCLASSIFIED INFORMATION (CUI)
C O
N T
R O
L L E
D U
N C
L A
S S
IF
IE
D I
N F
O R
M A
T
IO
N
C U
I)
/6
/2
:3
:1
A
M
100% BID DOCUMENTS
BLDG 1 - BASEMENT - ENLARGED
PLANS
CAB 62 OF 229AJS
BONHAM EHRM
INFRASTRUCTURE
UPGRADES
07/07/2023
549A4-21-700
BONHAM VA MEDICAL CENTER
1201 E. 9TH STREET
BONHAM, TX 75418
AE101
SPUR #: 2216
N
1/4" = 1'-0" 1/ A-101
B1 - BASEMENT - 15 - DEMO PLAN2
KEYNOTE LEGEND
2.06 EXISTING DOOR AND FRAME TO REMAIN IN PLACE.
2.73 EXISTING TR EQUIPMENT TO BE REMOVED. REF: GENERAL DEMOLITION NOTE 9 & TELECOM.
2.89 RAISED FLOOR SYSTEM TO REMAIN AND PROTECT.
2.105 EXISTING ELECTRICAL EQUIPMENT TO REMAIN, REF: ELECTRICAL.
9.71 PATCH AND REPAIR EXISTING WALLS AFFECTED BY DEMOLITION WORK. FIRE CAULK AND SEAL
PENETRATIONS AS REQUIRED TO MAINTAIN FIRE AND/OR SMOKE RATING.
5'-11"
7' -2
2.96
2.73
9.71
EX. COMM
113A 2.63
2.110
2.108
2.105
'-2
6'-11"
2.32
2.22
EX. POLICE LOCKER
116A
2.92
2'-9"3'-10"4"
3' -4
'-6
/2
1/
2"
8'-4 1/2"
5'-8"
2.23
2.93
'-9
1'
-5
/2
'-2
4'-10" 2'-1"
6'-11"
2.66
9' -9
/2
15'-6"
2.32 2.228' -2
1/ 2"
1' -5
1'-9 1/2" 3'-8 1/2" 10'-0"
EX. OFFICE
/2
6' -4
2'
-7
9' -9
/2
2.101
7'-2"
'-5
2'-6"4'-8"
8' -8
5'
-9
2.96
2.06
2.73
9.71
EX. COMM
2.63
2.105
2.108
2.109
9'-0"
EX. OFFICE
2.23
8' -2
1/ 2"
1' -5
9' -9
/2
1'-9 1/2" 3'-8 1/2" 10'-0"
15'-6"
2.66
2' x 2' ACOUSTICAL CEILING
CEILING HEIGHT, ABOVE
FINISH FLOOR
00'-00"
REFLECTED CEILING PLAN LEGEND
DUCTLESS SPLIT INDOOR
UNIT, REF: MECHANICAL
RETURN AIR GRILLE
2 x 4 LIGHT FIXTURE
RE: ELECTRICAL
SUSPENDED LIGHT FIXTURE
RE: ELECTRICAL
2' x 2' LIGHT FIXTURE
RE: ELECTRICAL
SUPPLY AIR DIFFUSER
1. ALL NEW DOOR FRAMES TO BE LOCATED 4" FROM OUTSIDE OF FRAME TO FINISH FACE OF ADJACENT WALL
UNLESS NOTED OTHERWISE.
2. FIRE CAULK ALL PENETRATIONS IN EXISTING WALLS, FLOORS, OR CEILINGS.
3. ALL WALLS TO GO TO DECK. IF EXISTING WALL DOES NOT CURRENTLY GO TO DECK, CONTRACTOR TO EXTEND WALL SYSTEM UP TO EXISTING STRUCTURE ABOVE PRIOR TO FIRE CAULKING. MAINTAINING
EXISTING FIRE RATING.
4. ALL NEW CONSTRUCTION WALLS ARE DIMENSIONED TO CENTERLINE OF METAL STUD, UNLESS NOTED
OTHERWISE.
5. ALL EXISTING WALLS ARE DIMENSIONED TO FACE OF EXISTING FINISH, UNLESS NOTED OTHERWISE.
6. ALL EXISTING GLAZING LOCATED IN EXTERIOR WALLS WITHIN EXISTING AND NEW TELECOM ROOMS SHALL RECEIVE 15-MINUTE FORCED INTRUSION RESISTANT FILM & CONTACT SENSORS TIED TO THE SECURITY
CONTROL CENTER.
GENERAL PLAN NOTES
1. CEILINGS IN ALL TR'S ARE TO BE OPEN TO BOTTOM OF DECK, UNLESS NOTED OTHERWISE.
2. ALL SURFACES OF FURRDOWNS TO BE PAINTED TO MATCH UNLESS NOTED OTHERWISE.
3. ALL FIXTURES IN DEMOLISHED CEILINGS ARE TO FIRST BE REMOVED AND RETURNED TO OWNER, UNO.
4. RECONFIGURE SPRINKLER SYSTEM IN DEMOLISHED CEILINGS PER FIRE PROTECTION REQUIREMENTS.
GENERAL REFLECTED CEILING PLAN NOTES
EXISTING DOOR & FRAME.
REF: KEYNOTES FOR
DEMOLITION NOTES
DEMOLITION & NEW FLOOR PLAN LEGEND
AREA NOT IN CONTRACT
EXISTING WALL TO BE
DEMOLISHED IN ITS ENTIRETY
EXISTING WALL TO REMAIN
& PROTECT
EXISTING DOOR & FRAME TO
REMAIN AND PROTECT
NEW DOOR & FRAME
APPLICATION.
REF: DOOR SCHEDULE
1. ALL EXISTING WALL DIMENSIONS ARE TO FINISH FACE, UNLESS OTHERWISE NOTED
2. THE CONTRACTOR SHALL VERIFY DIMENSIONS OF AS-BUILT CONDITIONS, AND NOTIFY THE ARCHITECT IN WRITING OF ANY DISCREPANCIES. ALL INFORMATION SHOWN ON THE CONSTRUCTION DOCUMENTS IS BASED ON FIELD OBSERVATIONS AND/OR THE ORIGINAL CONSTRUCTION DOCUMENTS OF THE FACILITY.
3. DEMOLITION AND CONSTRUCTION WORK MUST BE DONE UNDER NEGATIVE PRESSURE UTILIZING HEPA
FILTRATION UNITS. SEE INFECTION CONTROL NOTES.
4. DO NOT REMOVE BARRIERS FROM WORK AREA UNTIL PROJECT IS COMPLETED AND/OR AREA HAS BEEN INSPECTED BY THE SAFETY OFFICER AND INFECTION CONTROL COORDINATOR AND THOROUGHLY CLEANED
BY ENVIRONMENTAL MANAGEMENT SERVICES.
5. THE CONTRACTOR SHALL PROVIDE PROTECTIVE COVERING FOR EXISTING FLOOR, WALL AND CEILING FINISHES IN EXISTING AREAS NOT DESIGNATED FOR DEMOLITION OR NEW CONSTRUCTION. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE REPAIR OF ANY DAMAGE CAUSED BY HIS WORK OR ANY
SUBCONTRACTOR.
6. THE CONTRACTOR SHALL VERIFY THAT NEW MECHANICAL SYSTEMS CAN BE INSTALLED IN EXISTING SPACES TO CLEAR EXISTING CEILING AND OTHER CONSTRUCTED ITEMS AND MAINTAIN FLOOR TO CEILING HEIGHTS INDICATED ON DRAWINGS. IF DISCREPANCIES OCCUR DUE TO EXISTING CONDITIONS, CONSULT WITH THE
ARCHITECT BEFORE PROCEEDING.
7. THE FINISH FACE OF MATERIAL OF NEW PARTITIONS SHALL ALIGN ON BOTH SIDES OF THE PARTITION WITH THE FACE OF THE MATERIALS ON EXISTING COLUMNS, WALLS, OR PARTITIONS, UNLESS NOTED OTHERWISE.
8. NO WORK TO BE DONE IN AREAS HATCHED GRAY IN PLANS, HOWEVER WORK MIGHT NEED TO BE PERFORMED IN CEILING OR EXISTING CHASES THROUGHOUT BUILDING. REFERENCE MECHANICAL AND ELECTRICAL DRAWINGS FOR EXTENT OF WORK. COORDINATE ACCESS TO ROOMS OUTSIDE OF SCOPE WITH
OWNER.
9. ALL EXISTING TELECOM ROOMS THAT WILL NO LONGER BE USED AS A TELECOM ROOM ARE TO BE CLASSIFIED AS CLOSETS, UNO; HAVE ALL WALLS PATCHED & REPAIRED, EXISTING CARD READER REMOVED, FLOORS TO BE LEFT AS EXISTING, AND NEW STORAGE HARDWARE SET INSTALLED. FIRE CAULK AT ANY
JOINTS OR PENETRATIONS AS REQUIRED TO MAINTAIN FIRE AND/OR SMOKE RATING.
REFERENCE: DOOR & FINISH SCHEDULE FOR SPECIFICS.
GENERAL DEMOLITION NOTES
EXISTING 2' x 2' ACOUSTICAL
CEILING TO BE DEMOLISHED
EXISTING GYPSUM BOARD
CEILING TO BE DEMOLISHED
EXISTING 2 x 2 LIGHT FIXTURE
TO BE DEMOLISHED
EXISTING 2 x 4 LIGHT
FIXTURE TO BE DEMOLISHED
EXISTING 2' x 4' ACOUSTICAL
CEILING TO BE DEMOLISHED
EXISTING RETURN AIR GRILLE
TO BE DEMOLISHED
EXISTING SUPPLY AIR
DIFFUSER TO BE DEMOLISHED
EXISTING EXHAUST AIR
GRILLE TO BE DEMOLISHED
EXISTING RECESSED CAN
LIGHT TO BE DEMOLISHED
EXISTING PENDANT LIGHT TO
BE REMOVED
DEMOLITION REFLECTED CEILING PLAN LEGEND
CLOSET
113A
5'-11"
7' -2
3A
-1
2.105
98 SF / 100 SF
NEW TR
116A
'-2
1'-0"
1'-8 1/2" 4'-2 1/2"
26.11 26.13
6A
-1D3
6'-11"
2'-9"3 1/
2" 3'
-4
5' -0
2'
-5
3' -1
/2
3'-10"4"
145 SF / 100 SF
NEW TR
9' -9
/2
15'-6"
1'-9 1/2" 3'-8 1/2" 10'-0"
160-1
AE601
TYP.
2'-7" 2'-5" 5'-0"
3' -0
/2
1'
-8
/2
6" 1'
-8
/2
2' -1
1/
2"
26.13
26.12
10.33
8.97
8.105
8' -2
1/ 2"
1' -5
/2
6' -4
2'
-7
9' -9
/2
CLOSET
2'-6"4'-8"
7'-2"
5' -9
8'
-8
'-5
162-1
2.105
98 SF / 100 SF
NEW TR
116A
2.74
'-2
6'-11"
23.06
2' -2
5'
-1
5' -1
1'
-1 0"
EQ. EQ.
10'-9"
145 SF / 100 SF
NEW TR
2.74
1' -5
9' -9
/2
1'-9 1/2" 3'-8 1/2" 10'-0"
15'-6"
23.06
5'-6" 7'-7" 2'-6"
2' -3
4'
-0
3' -7
8' -2
1/ 2"
9' -9
/2
10'-9" th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
CONSULTANTS:
CIVIL ENGINEER
OLSSON
550 ST LOUIS ST,
SPRINGFIELD, MO 65806
(417) 885-1736
MECH / ELEC ENGINEER
SPUR DESIGN
2519 MADISON AVE., STE. 100
KANSAS CITY, MO 64108
(913) 369-7200
FIRE PROTECTION ENGINEER
RATED ENGINEERING
609 S. KELLY AVENUE, SUITE H2
EDMOND, OK 73003
(405) 856-2965
INDUSTRIAL HYGENIST
RIVERFRONT SAFETY & HEALTH
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
TECH ENGINEER
ASPEN COMMUNICATIONS, LLC
7 KIJI-DAVA CIRCLE, SUITE A
PRESCOTT, AZ 86301
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STRUCT ENGINEER
STAND STRUCTURAL ENGINEERING
8234 ROBINSON STREET
OVERLAND PARK, KS 66204
(913) 214-2169
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Drawing #
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH REG. NO. BR 2171 EXP. 09/30/2023
ENGR REG. NO. F-17591 EXP. 02/29/2024
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
STAMP:
Drawing Number
Building Number
BUILDING 34 NOT SPRINKLERED. ALL OTHER BUILDINGS FULLY SPRINKLERED.
COMMISSIONING
ES2
13401 N. SANTA FE AVE
OKLAHOMA CITY, OK 73114
(405) 528-4500
CONTROLLED UNCLASSIFIED INFORMATION (CUI)
CONTROLLED UNCLASSIFIED INFORMATION (CUI)
C O
N T
R O
L L E
D U
N C
L A
S S
IF
IE
D I
N F
O R
M A
T
IO
N
C U
I)
/6
/2
:3
:1
A
M
100% BID DOCUMENTS
BLDG 1 - LEVEL ONE - ENLARGED
PLANS
CAB 63 OF 229AJS
BONHAM EHRM
INFRASTRUCTURE
UPGRADES
07/07/2023
549A4-21-700
BONHAM VA MEDICAL CENTER
1201 E. 9TH STREET
BONHAM, TX 75418
AE102
SPUR #: 2216
N
1/4" = 1'-0" 2/ A-101
B1 - LEVEL ONE - 113A - DEMO PLAN1
N
1/4" = 1'-0" 2/ A-101
B1 - LEVEL ONE - 116A - DEMO PLAN3
N
1/4" = 1'-0"
B1 - LEVEL ONE - 116A - DEMO RCP5
N
1/4" = 1'-0" 2/ A-101
B1 - LEVEL ONE - 160 - DEMO PLAN7
N
1/4" = 1'-0" 2/ A-101
B1 - LEVEL ONE - 162 - DEMO PLAN11
N
1/4" = 1'-0"
B1 - LEVEL ONE - 160 - DEMO RCP9
N
1/4" = 1'-0" 2/ A-101
B1 - LEVEL ONE - 113A - FLOOR PLAN2
N
1/4" = 1'-0" 2/ A-101
B1 - LEVEL ONE - 116A - NEW TR4
N
1/4" = 1'-0" 2/ A-101
B1 - LEVEL ONE - 160 - FLOOR PLAN8
N
1/4" = 1'-0" 2/ A-101
B1 - LEVEL ONE - 162 - FLOOR PLAN12
N
1/4" = 1'-0"
B1 - LEVEL ONE - 116A - RCP6
N
1/4" = 1'-0"
B1 - LEVEL ONE - 160 - RCP10
KEYNOTE LEGEND
2.06 EXISTING DOOR AND FRAME TO REMAIN IN PLACE.
2.22 DEMOLISH EXISTING FLOORING AND BASE TO EXTENTS INDICATED; CLEAN & PREPARE SUB-FLOOR
SURFACE FOR NEW FLOORING.
2.23 DEMOLISH EXISTING GRID CEILING SYSTEM, ASSOCIATED LIGHT FIXTURES, AND BORDERS.
2.32 DEMOLISH EXISTING DOOR AND FRAME IN ITS ENTIRETY.
2.63 DEMOLISH EXISTING CARD READER AND REPLACE WITH NEW BLACK METAL COVER PLATE ON WALL.
2.66 DEMOLISH EXISTING MECHANICAL EQUIPMENT; REF: MECHANICAL.
2.73 EXISTING TR EQUIPMENT TO BE REMOVED. REF: GENERAL DEMOLITION NOTE 9 & TELECOM.
2.74 OPEN TO BOTTOM OF DECK ABOVE.
2.92 DEMOLISH EXISTING WALL CONSTRUCTION TO EXTENT INDICATED AND PREPARE FOR NEW DOOR OPENING. REMOVE AND RETAIN ANY EXISTING FIXTURES FOR REINSTALLATION. REF: DOOR SCHEDULE
FOR OPENING DIMENSIONS AND DETAILS.
2.93 DEMOLISH EXISTING WALL FURR DOWN AND ALL ASSOCIATED FRAMING & LIGHT FIXTURES TO BOTTOM
OF DECK ABOVE.
2.96 REUSE EXISTING DOOR AND FRAME. REPLACE HARDWARE. REF: DOOR SCHEDULE & HARDWARE
SCHEDULE.
2.101 DEMOLISH EXISTING WINDOW SHADES / BLINDS
2.105 EXISTING ELECTRICAL EQUIPMENT TO REMAIN, REF: ELECTRICAL.
2.108 DEMOLISH EXISTING GROUND BAR, REF: ELECTRICAL.
2.109 EXISTING WALL MOUNTED RACK TO REMAIN
2.110 DEMOLISH EXISTING ELECTRICAL EQUIPMENT, REF: ELECTRICAL.
8.97 REMOVE WINDOW GASKETING AND APPLY ANTIFRAGMENTATION LAMINATION TO EACH WINDOW PANE.
REINSTALL GASKETING AND PROVIDE CONTACT SENSORS.
8.105 INSTALL INSULATED PANEL TO FIT WINDOW OPENING
9.71 PATCH AND REPAIR EXISTING WALLS AFFECTED BY DEMOLITION WORK. FIRE CAULK AND SEAL
PENETRATIONS AS REQUIRED TO MAINTAIN FIRE AND/OR SMOKE RATING.
10.33 TELECOMMUNICATION RACK, REF: TELECOM
23.06 DUCTLESS SPLIT INDOOR UNIT, REF: MECHANICAL
26.11 INSTALL NEW DUAL AUTHENTIFICATION (PIV AND PIN CODE) CARD READER. BADGE ACCESS BY OTHERS.
REF: ELECTRICAL
26.12 GROUND BAR, REF: ELECTRICAL
26.13 ELECTRICAL PANEL, REF: ELECTRICAL
NO LONGER A TR. NEW TR LOCATED
ROOM 160. REFER TO AE102
NO LONGER A TR. NEW TR LOCATED
ROOM 116A. REFER TO AE102
11'-1"
6' -7
8'
-3
11'-4"
EX. DENTAL LOBBY
EX. COMM
'-3
"2.18
2.32
2.06
9.71
2.22
2.952.95
7'-1"
3"
11'-4"
2.22
2.18 2"
2.108
2.73
8'-8"
11'-0 1/2"
EX. DENTAL LOBBY
EX. COMM
2.74
2.23
6' -7
8'
-3
'-3
11'-1"3"
11'-4"
2.66
2.66
EX. EXAM
'-6
EX. COMM
317A
7" 1'
-1
'-1
1/
2"
10 1/2"11'-1 1/2"1'-2"5'-10"
19'-5"
2"
'-5
/2
4' -3
8"
20'-0"
'-6
2.18
2.32
2.32
2.06
9.71
2.22
7"
2.182.182.182.18
2.22
2.105
2.105
2.108
2.73
2.101 2.121
2.121
2'-3"3'-4"9"5"1'-2" 10'-8 1/2" 9 1/2"
'-5
EX. COMM
EX. EXAM
9'-10" 1'-3 1/2"
20'-3"
6' -1
1/ 2"
8' -7
/2
20'-3"
2.28
2.18
2.322.32 2.06
2.229.71
7'-3 1/2"1'-5" 5"
5"
2.22
2.18
2.182.112
2.1012.101
4 1/2"1'-10 1/2"1'-7 1/2"
'-8
1'
-2
1/
4"
'-0
/4
2.108
2.114
2.109
2.73
2.105
2.63
3'-10" 3'-11"
2.116
2.18
3'-10"4'-4 1/2"
EX. COMM
EX. EXAM
2.232.74
1/
2" 8'
-7
/2
6' -1
'-5
4 1/2"9'-7 1/2"5"3'-10"6'-0"
9"
'-8
1'-3 1/2"7'-3 1/2"5"1'-5"9'-10"
20'-3"
20'-3"
2.66
2.66
2.111
9'-1"
11'-0"
EX. EXAM
EX. COMM
317A
2.232.74
'-1
1/
2" 1'
-1
'-6
7"
6'-4"6'-10"6'-3"7"
20'-0"
8" 4'
-3
'-5
/2
2"
'-6
10 1/2"11'-1 1/2"1'-2"5'-10"
19'-5"
2.66
2.129
2' x 2' ACOUSTICAL CEILING
CEILING HEIGHT, ABOVE
FINISH FLOOR
00'-00"
REFLECTED CEILING PLAN LEGEND
DUCTLESS SPLIT INDOOR
UNIT, REF: MECHANICAL
RETURN AIR GRILLE
2 x 4 LIGHT FIXTURE
RE: ELECTRICAL
SUSPENDED LIGHT FIXTURE
RE: ELECTRICAL
2' x 2' LIGHT FIXTURE
RE: ELECTRICAL
SUPPLY AIR DIFFUSER
1. ALL NEW DOOR FRAMES TO BE LOCATED 4" FROM OUTSIDE OF FRAME TO FINISH FACE OF ADJACENT WALL
UNLESS NOTED OTHERWISE.
2. FIRE CAULK ALL PENETRATIONS IN EXISTING WALLS, FLOORS, OR CEILINGS.
3. ALL WALLS TO GO TO DECK. IF EXISTING WALL DOES NOT CURRENTLY GO TO DECK, CONTRACTOR TO EXTEND WALL SYSTEM UP TO EXISTING STRUCTURE ABOVE PRIOR TO FIRE CAULKING. MAINTAINING
EXISTING FIRE RATING.
4. ALL NEW CONSTRUCTION WALLS ARE DIMENSIONED TO CENTERLINE OF METAL STUD, UNLESS NOTED
OTHERWISE.
5. ALL EXISTING WALLS ARE DIMENSIONED TO FACE OF EXISTING FINISH, UNLESS NOTED OTHERWISE.
6. ALL EXISTING GLAZING LOCATED IN EXTERIOR WALLS WITHIN EXISTING AND NEW TELECOM ROOMS SHALL RECEIVE 15-MINUTE FORCED INTRUSION RESISTANT FILM & CONTACT SENSORS TIED TO THE SECURITY
CONTROL CENTER.
GENERAL PLAN NOTES
1. CEILINGS IN ALL TR'S ARE TO BE OPEN TO BOTTOM OF DECK, UNLESS NOTED OTHERWISE.
2. ALL SURFACES OF FURRDOWNS TO BE PAINTED TO MATCH UNLESS NOTED OTHERWISE.
3. ALL FIXTURES IN DEMOLISHED CEILINGS ARE TO FIRST BE REMOVED AND RETURNED TO OWNER, UNO.
4. RECONFIGURE SPRINKLER SYSTEM IN DEMOLISHED CEILINGS PER FIRE PROTECTION REQUIREMENTS.
GENERAL REFLECTED CEILING PLAN NOTES
EXISTING DOOR & FRAME.
REF: KEYNOTES FOR
DEMOLITION NOTES
DEMOLITION & NEW FLOOR PLAN LEGEND
AREA NOT IN CONTRACT
EXISTING WALL TO BE
DEMOLISHED IN ITS ENTIRETY
EXISTING WALL TO REMAIN
& PROTECT
EXISTING DOOR & FRAME TO
REMAIN AND PROTECT
NEW DOOR & FRAME
APPLICATION.
REF: DOOR SCHEDULE
1. ALL EXISTING WALL DIMENSIONS ARE TO FINISH FACE, UNLESS OTHERWISE NOTED
2. THE CONTRACTOR SHALL VERIFY DIMENSIONS OF AS-BUILT CONDITIONS, AND NOTIFY THE ARCHITECT IN WRITING OF ANY DISCREPANCIES. ALL INFORMATION SHOWN ON THE CONSTRUCTION DOCUMENTS IS BASED ON FIELD OBSERVATIONS AND/OR THE ORIGINAL CONSTRUCTION DOCUMENTS OF THE FACILITY.
3. DEMOLITION AND CONSTRUCTION WORK MUST BE DONE UNDER NEGATIVE PRESSURE UTILIZING HEPA
FILTRATION UNITS. SEE INFECTION CONTROL NOTES.
4. DO NOT REMOVE BARRIERS FROM WORK AREA UNTIL PROJECT IS COMPLETED AND/OR AREA HAS BEEN INSPECTED BY THE SAFETY OFFICER AND INFECTION CONTROL COORDINATOR AND THOROUGHLY CLEANED
BY ENVIRONMENTAL MANAGEMENT SERVICES.
5. THE CONTRACTOR SHALL PROVIDE PROTECTIVE COVERING FOR EXISTING FLOOR, WALL AND CEILING FINISHES IN EXISTING AREAS NOT DESIGNATED FOR DEMOLITION OR NEW CONSTRUCTION. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE REPAIR OF ANY DAMAGE CAUSED BY HIS WORK OR ANY
SUBCONTRACTOR.
6. THE CONTRACTOR SHALL VERIFY THAT NEW MECHANICAL SYSTEMS CAN BE INSTALLED IN EXISTING SPACES TO CLEAR EXISTING CEILING AND OTHER CONSTRUCTED ITEMS AND MAINTAIN FLOOR TO CEILING HEIGHTS INDICATED ON DRAWINGS. IF DISCREPANCIES OCCUR DUE TO EXISTING CONDITIONS, CONSULT WITH THE
ARCHITECT BEFORE PROCEEDING.
7. THE FINISH FACE OF MATERIAL OF NEW PARTITIONS SHALL ALIGN ON BOTH SIDES OF THE PARTITION WITH THE FACE OF THE MATERIALS ON EXISTING COLUMNS, WALLS, OR PARTITIONS, UNLESS NOTED OTHERWISE.
8. NO WORK TO BE DONE IN AREAS HATCHED GRAY IN PLANS, HOWEVER WORK MIGHT NEED TO BE PERFORMED IN CEILING OR EXISTING CHASES THROUGHOUT BUILDING. REFERENCE MECHANICAL AND ELECTRICAL DRAWINGS FOR EXTENT OF WORK. COORDINATE ACCESS TO ROOMS OUTSIDE OF SCOPE WITH
OWNER.
9. ALL EXISTING TELECOM ROOMS THAT WILL NO LONGER BE USED AS A TELECOM ROOM ARE TO BE CLASSIFIED AS CLOSETS, UNO; HAVE ALL WALLS PATCHED & REPAIRED, EXISTING CARD READER REMOVED, FLOORS TO BE LEFT AS EXISTING, AND NEW STORAGE HARDWARE SET INSTALLED. FIRE CAULK AT ANY
JOINTS OR PENETRATIONS AS REQUIRED TO MAINTAIN FIRE AND/OR SMOKE RATING.
REFERENCE: DOOR & FINISH SCHEDULE FOR SPECIFICS.
GENERAL DEMOLITION NOTES
EXISTING 2' x 2' ACOUSTICAL
CEILING TO BE DEMOLISHED
EXISTING GYPSUM BOARD
CEILING TO BE DEMOLISHED
EXISTIN…