Attachment 14 - VOL_6a-TELECOM-VA_CT_West_Haven_EHRM_IU-689-22-700.pdf
PDF 35 MB Posted
- Attached to
- Z2DA--689-22-700 EHRM IU West Haven VAMC This ONLY for the PCAC VISN 1 Construction MATOC Pool
- Solicitation number
- 36C77626R0106
About this file
This file is a telecommunications infrastructure design document (Volume 6 of construction documents) for EHRM Infrastructure Upgrades at West Haven VA Medical Center in Connecticut. The project encompasses Building 001 and multiple associated structures at 950 Campbell Avenue, West Haven, CT 06516, with work scope including improvements, reconfiguration, expansion, and renovation of existing spaces to accommodate new telecommunication rooms, a data center, generator enclosure, and fuel yard across 41 buildings.
The telecommunications scope requires installation of Category 6A (CAT6A) cabling infrastructure throughout the facility, replacing existing Category 6 and below cabling systems. Key deliverables include: providing new work area outlets (WAOs) with standard density (2 CAT6A ports) and high-density (4 CAT6A ports) configurations; installing copper and fiber optic patch cords in telecommunications rooms (TRs); providing 1,127 square feet of telecommunications space within room SG105B; establishing backbone fiber optic cabling with OM4, OS1, and OS2 fiber types; implementing proper cable management, labeling, and bonding per TIA standards; and sealing all fire-rated penetrations. The contractor must provide an additional 10% of all WAO materials and labor as contingency, furnish all patch cords with specific color-coding requirements (blue or white for copper; aqua for OM4, yellow for OS1/OS2 fiber), install tamper switches on all telecommunications equipment (TE) doors, and maintain as-built documentation with alpha-numeric grid annotations in data center areas per ANSI/TIA standards. Work requires manufacturer certification for all personnel, coordination with multiple trades, field verification of existing conditions prior to bid, and compliance with BICSI TDMM standards and NEC requirements.
View the file
Other files
Show all 42
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
950 CAMPBELL AVENUE, WEST HAVEN, CT 06516-2770
11A
12A
14A
15A
24 27
35A
36A
2B
DATA CENTER
GENERATOR
ENCLOSURE
FUEL YARD
BUILDINGS WITHIN THE SCOPE OF THIS PROJECT
16A
ARCHITECTURAL
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
PHONE: (206) 590-2118
DESIGN TEAM
STRUCTURAL
MECHANICAL
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
PHONE: (206) 590-2118
SIGNATURE LINE
COR
FIRE PROTECTION
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
PHONE: (206) 590-2118
CIVIL
WSP USA, INC.
33301 9TH AVENUE SOUTH
FEDERAL WAY, WA 98003-2600
PHONE: (206) 431-2300
PLUMBING
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
PHONE: (206) 590-2118
ELECTRICAL
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
PHONE: (206) 590-2118
WSP USA, INC.
33301 9TH AVENUE SOUTH
FEDERAL WAY, WA 98003-2600
PHONE: (206) 431-2300
PROJECT INFORMATION
STATE:
COUNTY:
JURISDICTION:
OWNER:
CODE ANALYSIS
PROJECT DESCRIPTION
THE PROPOSED DESIGN SHALL IMPROVE,
RECONFIGURE, EXPAND AND RENOVATE EXISTING
SPACES FOR NEW TELECOMMUNICATION ROOMS,
DATA CENTER, GENERATOR ENCLOSURE, AND
FUEL YARD.
APPLICABLE BUILDING
BUILDING 1, 2, 2B, 3, 4, 5, 6, 11, 11A, 12, 12A,
14A, 15, 15A, 16, 16A, 21, 22, 24, 27-34, 35, 35A, 36, 36A, 41 (DATA CENTER),
42 (GENERATOR ENCLOSURE, FUEL YARD)
ICRA CLASS REQUIREMENTS
REQUIREMENTS DEPENDENT ON
EACH INDIVIDUAL ROOM LOCATION.
CONNECTICUT
NEW HAVEN
WEST HAVEN
DEPARTMENT OF VETERANS
AFFAIRS
BUILDING TYPES
BUILDING 01 - HEALTHCARE
BUILDING 02 - HEALTHCARE
BUILDING 2B - ADMIN
BUILDING 03 - HEALTHCARE
BUILDING 04 - ADMIN
BUILDING 05 - HEALTHCARE
BUILDING 06 - ADMIN
BUILDING 11 - ADMIN
BUILDING 11A - ADMIN
BUILDING 12 - ADMIN
BUILDING 12A - ADMIN
BUILDING 14A - ADMIN
BUILDING 15 - ADMIN
BUILDING 15A - ADMIN
BUILDING 16 - ADMIN
BUILDING 16A - ADMIN
BUILDING 21 - ADMIN
BUILDING 22 - ADMIN
BUILDING 24 - ADMIN
BUILDING 27-34 - ADMIN
BUILDING 35 - ADMIN
BUILDING 35A - ADMIN
BUILDING 36 - HEALTHCARE
BUILDING 36A - ADMIN
41 (DATA CENTER) - ADMIN
42 (GENERATOR ENCLOSURE) - ADMIN
1. COORDINATE WORK WITH ALL CONTRACT DOCUMENTS, INCLUDING BUT NOT LIMITED TO DRAWINGS &
SPECIFICATIONS.
2. SPECIFICATIONS SHALL SUPERSEDE DRAWINGS IN THE CASE OF ANY CONFLICTING INFORMATION.
BRING TO THE AWARENESS OF AND VERIFY WITH VA COR PRIOR TO PROCEEDING.
3. THE CONTRACTOR AND ANY SUB CONTRACTORS SHALL FAMILIARIZE THEMSELVES WITH EXISTING CONDITIONS AND PROJECT REQUIREMENTS PRIOR TO SUBMITTING A BID OR BEGINNING WORK. NO ALLOWANCES WILL BE MADE ON BEHALF OF THE CONTRACTOR OR SUB-CONTRACTORS FOR FAILURE
TO VISIT THE SITE.
4. THE CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS BEFORE BEGINNING WORK. ANY CONFLICTS BETWEEN EXISTING CONDITIONS AND THE CONTRACT DOCUMENTS SHALL BE BROUGHT
IMMEDIATELY TO THE ATTENTION OF THE COR.
5. ALL WORK SHALL BE PERFORMED WITH A HIGH-LEVEL OF WORKMANSHIP.
6. THE CONTRACTOR SHALL VERIFY ALL PRODUCT TYPES AND QUANTITIES DURING SITE
WALKTHROUGH, PRIOR TO PURCHASING ANY MATERIALS, EQUIPMENT, PRODUCTS OR LABOR.
7. THE CONTRACTOR SHALL VERIFY AND COORDINATE WITH ALL INSTALLERS TO ENSURE COMPLIANCE
WITH THE CONTRACT DOCUMENTS.
GENERAL NOTES
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ ENGINEER OF RECORD
A/E:
STAMPCONSULTANT/ DISCIPLINE
321 4 5 6 7 8 9 10
DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
08/05/2026 7:15:41 am
Autodesk Docs://689-22-700 VA CT West Haven EHRM
IU/VAWH_GEN
SHEETS_SDB.rvt
G-001
COVER PAGE
JS/JRS JRS
100% CONSTRUCTION
DOCUMENTS
04/20/2026
689-22-700EHRM INFRASTRUCTURE
UPGRADES - WEST HAVEN
VA CT WEST HAVEN
950 CAMPBELL AVENUE, WEST HAVEN, CT 06516
1" = 30'-0"
LOCATION MAP
PROJECT
NORTH
PROJECT
NORTH
1" = 150'-0"
SITE PLAN
EHRM INFRASTRUCTURE UPGRADES
950 CAMPBELL AVENUE, WEST HAVEN, CT 06516-2770
PROJECT #: 689-22-700
Revisions: Date:
jamesstoddard Text Box
VOLUME 6 - TELECOM SHEETS
A B B R E V I A T I O N S
1PH SINGLE-PHASE
1P SINGLE POLE
2/C TWO-CONDUCTOR
3/C THREE-CONDUCTOR
3PH THREE-PHASE
4/C FOUR-CONDUCTOR
4W FOUR-WIRE
A/C AIR CONDITIONING UNIT
A/E ARCHITECT/ENGINEER
AAP ALARM ANNUNCIATOR PANEL
AC ALTERNATING CURRENT OR ARMORED CABLE
ACC ACCESSIBLE
ADDL ADDITIONAL
ADJ ADJACENT, ADJOINING
AF AMPERE FRAME OR AMP FUSE
AFC ABOVE FINISHED COUNTER, AUTOMATIC
FREQUENCY CONTROL, OR AVAILABLE
FAULT CURRENT
AFCI ARC-FAULT CURRENT INTERRUPTER
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AH AMPERE HOUR
AHJ AUTHORITY HAVING JURISDICTION
AIC AMPERE INTERRUPTING CAPACITY
ALT ALTERNATE
AMB AMBIENT
AMP AMPERE
ARCH ARCHITECT
ASC AMPS SHORT CIRCUIT
AT AMPERE TRIP
ATS AUTOMATIC TRANSFER SWITCH
AUTO AUTOMATIC
AV AUDIO VISUAL
BAT BATTERY
BD BOARD
BFF BELOW FINISH FLOOR
BLDG BUILDING
BRKR BREAKER
BYP BY PASS
C CONDUIT
CAB CABINET
CALC CALCULATE
CAP CAPACITY
CAT CATALOG
CATV COMMUNITY ANTENNA TELEVISION
CCR CONTROL CONTACTOR
CCTV CLOSED CIRCUIT TELEVISION
CD CANDELA
CD CONSTRUCTION DOCUMENTS
CF CONTRACTOR FURNISHED
CF/CI CONTRACTOR FURNISHED/
CONTRACTOR INSTALLED
CF/OI CONTRACTOR FURNISHED/
OWNER INSTALLED
CFE CONTRACTOR FURNISHED EQUIPMENT
CHW CHILLED WATER
CHWP CHILLED WATER PUMP
CKT CIRCUIT
C/B CIRCUIT BREAKER
CL CONNECTOR LIGHTING
CLF CURRENT LIMITING FUSE
CLG CEILING
CO CONDUIT ONLY
COAX COAX CABLE
COMM COMMUNICATION
COMPT COMPARTMENT
CONC CONCRETE
CONT CONTINUE
CONTR CONTRACTOR
COORD COORDINATE
CPT CONTROL POWER TRANSFORMER
CRI COLOR RENDERING INDEX
CT CURRENT TRANSFORMER
CTV CABLE TELEVISION
CU COPPER
CUR CURRENT
DB DECIBEL
DC DIRECT CURRENT
DCP DIMMER CONTROL PANEL
DDC DIRECT DIGITAL CONTROLS
DEG C DEGREES CELSIUS
DEG F DEGREES FAHRENHEIT
DEMO DEMOLITION
DIAG DIAGRAM
DISC DISCONNECT
DP DISTRIBUTION PANEL
DMR SW DIMMER SWITCH
DPDT DOUBLE POLE, DOUBLE THROW
DPST DOUBLE POLE, SINGLE THROW
DRSW DOOR SWITCH
DS DISCONNECT SWITCH
DWG DRAWING
EC ELECTRICAL CONTRACTOR
EL ELEVATION OR EXISTING TO BE RELOCATED
ELEC ELECTRIC OR ELECTRICAL
ELEV ELEVATOR
EMER/EM EMERGENCY
EMI ELECTROMAGNETIC INTERFERENCE
EMT ELECTRICAL METALLIC TUBING
EN EXISTING IN NEW LOCATION
ENCL ENCLOSURE
EPO EMERGENCY POWER OFF
EPRF EXPLOSION PROOF
ER EXISTING TO REMAIN
ESMT EASEMENT
EWC ELECTRIC WATER COOLER
EWH ELECTRIC WATER HEATER
EXIST(E) EXISTING
FA FIRE ALARM
FAAP FIRE ALARM ANNUNCIATOR PANEL
FACP FIRE ALARM CONTROL PANEL
FC FOOTCANDLE
FCIO FURNISHED BY CONTRACTOR,
INSTALLED BY OWNER
FOIC FURNISHED BY OWNER,
INSTALLED BY CONTRACTOR
FIXT FIXTURE
FLA FULL LOAD AMPS
FLUOR FLUORESCENT
FP FIRE PROTECTION
FT FEET OR FOOT
FU SW FUSED SWITCH
FVNR FULL VOLTAGE NON-REVERSING
FVR FULL VOLTAGE REVERSING
G ELECTRICAL GROUND
GEN GENERATOR
GFCI GROUND FAULT
CIRCUIT INTERRUPTER
GFP GROUND FAULT PROTECTION
GND GROUND
HID HIGH INTENSITY DISCHARGE
HOA HAND-OFF-AUTOMATIC
HP HORSEPOWER
HT HEIGHT
HZ HERTZ
IG ISOLATED GROUND
IESNA ILLUMINATION ENGINEERING
SOCIETY OF NORTH AMERICA
IMC INTERMEDIATE METAL CONDUIT
INCAND INCANDESCENT
IR INFRARED
IWH INSTANTANEOUS WATER HEATER
J-BOX JUNCTION BOX
KV KILOVOLT
KVA KILOVOLT AMPERE
KVAH KILOVOLT AMPERE PER HOUR
KVAR KILOVOLT AMPERE REACTIVE
KW KILOWATT
KWH KILOWATT HOUR
KWHM KILOWATT HOUR METER
LCP LIGHTING CONTROL PANEL
LED LIGHT EMITTING DIODE
LF LINEAR FEET (FOOT)
LP LIGHT POLE
LPS LOW PRESSURE SODIUM
LRA LOCKED ROTOR AMPS
LT LIGHT
LTG LIGHTING
LTG PNL LIGHTING PANEL
LTNG LIGHTNING
LV LOW VOLTAGE
MAX MAXIMUM
MC METAL-CLAD
MCA MINIMUM CIRCUIT AMPS
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MDP MAIN DISTRIBUTION PANEL
MECH MECHANICAL
MH MANHOLE
MIN MINIMUM
MOCP MAXIMUM OVERCURRENT PROTECTION
MLO MAIN LUGS ONLY
MS MOTOR STARTER
MT MOUNT
MTD MOUNTED
MTG MOUNTING
MTS MANUAL TRANSFER SWITCH
MV MEDIUM VOLTAGE
MVA MEGAVOLT-AMPERE
MW MEGAWATT
NA NOT APPLICABLE
NAC NOTIFICATION APPLIANCE CABINET
NC NORMALLY CLOSED
NEC NATIONAL ELECTRICAL CODE
NEMA NATIONAL ELECTRICAL
MANUFACTURERS ASSOCIATION
NEUT, N NEUTRAL
NFC NOT FOR CONSTRUCTION
NFPA NATIONAL FIRE PROTECTION ASSOCIATION
NIC NOT IN CONTRACT
NL NIGHT LIGHT
NO NORMALLY OPEN
NTS NOT TO SCALE
OC ON CENTER
OD OUTSIDE DIAMETER
OH OVERHEAD
OL OVERLOAD
OS OCCUPANCY SENSOR
P POLE
PB PULL BOX
PEC PHOTOELECTRIC CELL
PED PEDESTAL
PEND PENDANT
PIV POST INDICATOR VALVE
PF POWER FACTOR
PH PHASE
PNL PANEL
PS POWER SUPPLY
PT POTENTIAL TRANSFORMER
PVC POLYVINYL CHLORIDE (PLASTIC)
PWR POWER
R EXISTING TO BE REMOVED
RCP REFLECTED CEILING PLAN
REC RECESSED
RECPT RECEPTACLE
RM ROOM
RMC RIGID METAL CONDUIT
RMS ROOT MEAN SQUARE
REQD REQUIRED
SAC SMALL APPLIANCE CIRCUIT
SCC SHORT CIRCUIT CAPACITY
SD SMOKE DETECTOR
SF SQUARE FOOT (FEET)
SHT SHEET
SI INTERNATIONAL SYSTEM OF UNITS
SM SMART METER
SPD SURGE PROTECTIVE DEVICE
SPEC SPECIFICATION
SPST SINGLE POLE, SINGLE THROW
SURF SURFACE
SW SWITCH
SWBD OR SB SWITCHBOARD
SWGR OR SG SWITCHGEAR
TEL TELEPHONE
TR TAMPER RESISTANT
TV TELEVISION
TYP TYPICAL
UFD UNDERFLOOR DUCT
UGND UNDERGROUND
UL UNDERWRITERS LABORATORY
UON UNLESS OTHERWISE NOTED
UPS UNINTERRUPTIBLE POWER
POWER SUPPLY
UTIL UTILITY
V VOLT
VA VOLT AMPERE
VAR VOLT AMPERE REACTIVE
VFD VARIABLE FREQUENCY DRIVE
VOLT VOLTAGE
W WATT/WEATHERPROOF
(WHILE IN USE)
WH WATER HEATER
WP/W WEATHERPROOF
XFER TRANSFER
XFMR TRANSFORMER
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
19.
20.
21.
22.
23.
24.
25.
26.
27.
28.
29.
30.
31.
32.
33.
34.
35.
36.
37.
38.
39.
40.
THESE "GENERAL NOTES" SHALL APPLY TO ALL DRAWINGS WITHIN THIS DRAWING SET.
IF THE SPECIFICATIONS OR DRAWINGS CONFLICT WITH EACH OTHER THE MORE STRINGENT CRITERIA/SCOPE OF WORK SHALL BE REQUIRED.
BLACKENED OR BOLDED EQUIPMENT INDICATES THE EQUIPMENT SHALL BE PROVIDED AND INSTALLED BY THE CONTRACTOR. ITEMS NOT DIRECTLY FURNISHED BY THE CONTRACTOR SHALL HAVE A DESIGNATION SUCH AS OFCI (OWNER FURNISHED CONTRACTOR INSTALLED), OFOI (OWNER FURNISHED OWNER INSTALLED), OR NIC (NOT IN CONTRACT). GRAY OR GRAY-SCALED EQUIPMENT SHALL BE ASSUMED TO BE EXISTING OR SHOWN FOR EQUIPMENT LOCATION COORDINATION. EXISTING CIRCUITS ASSOCIATED WITH THE PROJECT AREA OF WORK ARE TO BE DE-ENERGIZED DURING CONSTRUCTION.
ALL TELECOMMUNICATIONS SYSTEMS ARE DESIGNED IN ACCORDANCE WITH THE BICSI TDMM LATEST EDITION. ALL CONTRACTOR PERSONNEL WORKING ON THIS PROJECT SHALL BE TRAINED AND CERTIFIED BY THE MANUFACTURER OF THOSE PRODUCTS AND SHALL SUPPLY AS PART OF THE SUBMITTAL PROCESS THOSE CERTIFICATIONS PRIOR TO THE START OF ANY WORK.
ALL CONDUIT, SLEEVES, AND PATHWAYS SHALL BE FREE OF DEBRIS OR BLOCKAGES. ALL FIELD CUT RAW EDGES SHALL BE DEBURRED BY THE INSTALLING CONTRACTOR. ALL CONDUITS THAT FEED CATEGORY 6A CABLE TO A WORK AREA OUTLET (WAO)
BOX SHALL HAVE A PLASTIC BUSHING PLACED ON THE END OF THE CONDUIT.
ALL TERMINATIONS, CONNECTING BLOCKS, PATCH PANELS, RACKS, GROUND BARS, AND ASSOCIATED COMMUNICATIONS EQUIPMENT SHALL BE LABELED AND RECORDED BY THE CONTRACTOR. AS BUILT DOCUMENTS SHALL BE COMPILED BY THE CONTRACTOR AND FURNISHED TO THE ENGINEER AT THE END OF THE PROJECT INDICATING THE LOCATION OF ALL INSTALLED COMPONENTS AND THE LABELING OF THOSE COMPONENTS.
THE INSTALLATION OF ALL COMMUNICATIONS PATHWAYS, SLEEVES, AND CABLE TRAYS SHALL BE LAID OUT BY THE CONTRACTOR AND SUBMITTED TO THE ENGINEER FOR APPROVAL PRIOR TO ANY WORK. DRAWINGS SHALL SHOW PROPOSED ROUTES THAT WILL NOT CONFLICT WITH OTHER TRADES SUCH AS HVAC, ELECTRICAL, AND ARCHITECTURAL.
PRIOR TO INSTALLING CABLING, ALL EXISTING CABLES SHALL BE SEGREGATED INTO DIFFERENT GROUP TYPES; ONCE SEPARATED, CONTRACTOR SHALL DETERMINE WHICH CABLES SHALL BE REMOVED AND WHICH SHALL REMAIN. DEMOLISH ALL CABLES
TO BE REMOVED BACK TO SOURCE IN ITS ENTIRETY, UNLESS OTHERWISE NOTED.
MINIMUM CONDUIT SIZE SHALL BE 4” IN DIAMETER FOR EXTERIOR AND UNDERGROUND CONDUIT. MINIMUM CONDUIT SIZE SHALL BE 3/4 ” IN DIAMETER FOR INTERIOR CONDUIT. ALL CONDUIT SHALL BE CONCEALED. THE ABOVE COMMENTS SHALL BE
ADHERED TO UNLESS OTHERWISE NOTED ON THE DRAWINGS.
EQUIPMENT CIRCUITS SHALL BE ROUTED INDEPENDENT FROM OTHER CIRCUIT TYPES; ENSURE NEC 700.10 REQUIREMENTS ARE MET.
LOW VOLTAGE VOICE AND DATA CABLING SHALL NOT BE INSTALLED IN THE SAME CONDUIT AS 120 VAC POWER CABLES.
ALL EQUIPMENT AND DEVICES INCLUDING, BUT NOT LIMITED TO LOW VOLTAGE EQUIPMENT, DATA OUTLETS, FIBER OPTIC CABLE, AND SPECIAL SYSTEM DEVICES, SHALL HAVE THEIR EXACT LOCATION COORDINATED WITH ARCHITECTURAL DRAWINGS AND
ALL TRADES PRIOR TO COMMENCING WORK.
ALL CONDUIT/SLEEVE FLOOR AND WALL PENETRATIONS SHALL BE SEALED WITH FIRE RATED ASSEMBLIES, CAULKING, AND APPURTENANCES. ELECTRICAL BOXES LOCATED IN FIRE RATED WALLS SHALL BE RATED FOR USE IN FIRE RATED WALLS.
ALL EQUIPMENT AND INSTALLATION METHODS SHALL BE LISTED AND LABELED PER NEC, UL LISTED, OR REVIEWED EQUAL.
FOR ALL EQUIPMENT, COORDINATE WITH ALL TRADES (ARCHITECTURAL, MECHANICAL, PLUMBING, ETC) FOR ELECTRICAL AND LOW VOLTAGE REQUIREMENTS AND INSTALLATION LOCATIONS PRIOR TO INSTALLATION.
ALL LOW-VOLTAGE SYSTEM CABLING NOT INSTALLED IN CONDUIT TO WALL MOUNTED DEVICE SHALL HAVE A MINIMUM 1"C ROUTED FROM DEVICE THROUGH WALL INTO THE ACCESSIBLE CEILING SPACE; CABLING SHALL NOT BE ROUTED IN WALLS OR IN AN
INACCESSIBLE LOCATION WITHOUT CONDUIT.
NO STRUCTURAL MEMBERS SHALL BE CUT, DRILLED, OR NOTCHED WITHOUT PRIOR WRITTEN CONSENT FROM THE STRUCTURAL ENGINEER OR ARCHITECT.
MULTI-GANG BACKBOXES FOR DIFFERENT VOLTAGES AND TYPES OF EMERGENCY AND NORMAL BRANCH WIRING DEVICES SHALL HAVE DIVIDERS BETWEEN DEVICES.
FOR EXISTING EQUIPMENT, SUCH AS LOW VOLTAGE DEVICES, WIRING DEVICES, CONDUITS, ETC., SHOWN ON PLANS TO BE REMOVED, COMPLETELY CUT/CAP CONDUITS AT THE AREA OF WORK PERIMETER AND REMOVE CONDUIT WITHIN THE WORK AREA, DISCONNECT WIRING AT THE OVERCURRENT PROTECTIVE DEVICE AND REMOVE WIRING COMPLETELY FROM THE ABANDONED CONDUITS.
MAINTAIN AND RESTORE, IF INTERRUPTED, ALL CONDUITS AND CONDUCTORS PASSING THROUGH RENOVATED AREAS AND SERVICING UNDISTURBED AREAS.
CONTRACTOR SHALL PROVIDE, INSTALL, AND TERMINATE HORIZONTAL CAT6A CABLING FROM EACH WAO (WORK AREA OUTLET) TO ITS RESPECTIVE TR, UNLESS OTHERWISE NOTED.
ALL SSTV AND ACCESS CONTROL CABLE WILL BE INSTALLED BY MANUFACTURER'S CERTIFIED INSTALLER.
THE DATA CENTER SHALL HAVE AN ALPHA-NUMERIC GRID ANNOTATED ON THE WALLS IN ACCORDANCE WITH ANSI/TIA 606-C. STARTING IN THE NORTHWEST CORNER WORKING THE ALPHABET LEFT TO RIGHT AND NUMBERS TOP TO BOTTOM IN 24-INCH INCREMENTS USING BLACK LETTERS AND NUMBERS FOUR INCHES MINIMUM IN HEIGHT NOT PLACED MORE THAN SIX INCHES BELOW THE CEILING. (REFER TO TN507 FOR EXAMPLES).
ALL CEILING TILES WILL BE REINSTALLED BETWEEN WORK SHIFTS.
ALL FIRE RATED PENETRATIONS WILL HAVE PROPER TEMPORARY FIRESTOP INSTALLED IN-BETWEEN SHIFTS AND UNTIL PERMANENT FIRESTOPPING IS COMPLETE.
DEMO’D TR’s SUPPORTING EXISTING/REMAINING SYSTEMS – COPPER & FIBER PHASING.
COPPER: CONTRACTOR TO PULL (12) CAT6A CABLES FROM DEMO’D TR TO NEW TR. TERMINATE, TEST AND COIL UP ON BOTH ENDS.
FIBER: CONTRACTOR TO PULL (12-STRAND OM4 AND 12-STRAND SM FROM DEMO’D TR TO NEW TR. TERMINATE WITH LC CONNECTORS ON NEW TR END, MATCH CONNECTOR TYPE WITH EXISTING EQUIPMENT ON DEMO ’D TR END. TEST AND COIL UP
ON BOTH ENDS.
DDx DEMO WAO (x = DEMO QUANTITY)
N2 - NEW WAO WITH (2) CAT6A JACKS & CABLES
Example: DEMO 5, REPLACE WITH 2 CAT6A JACKS & CABLE
FOR DEMO’D WAO’s THAT WON’T BE REPLACED: CABLE WILL BE REMOVED BACK TO THE SOURCE, A BLANK FACEPLATE WILL BE INSTALLED OVER THE DEMO ’S BOX. CONDUIT WILL REMAIN.
ALL EXISTING WAOs ARE DEMO'D TO STANDARD DENSITY (SD) WAO's WITH (2) CAT6A DATA PORTS. AREAS THAT REQUIRE HIGH DENSITY (HD) WAO's (A MAXIMUM OF (4) CAT6A DATA OUTLETS IN A SINGLE FACEPLATE) TO BE IDENTIFIED BY THE STATION.
HORIZONTAL RACK BONDING BUSBAR MOUNTED AT THE TOP, BACKSIDE OF THE TE. PER TIA-607-D HORIZONTAL RACK BONDING BUSBAR MOUNTED AT THE TOP, BACKSIDE OF THE RACK OR CABINET. PER TIA-607-D
ALL NEW AND REMODELED TR’s WILL HAVE ¾” FIRE RATED PLYWOOD ON ALL THREE WALLS, PAINTED WHITE, NOT TO COVER THE FIRE RATING LABEL.
ANY ACTIVE ANALOG PORT WILL BE PHASED. REFER TO TN505 CALL OUT 3.
GROUNDING & BONDING: AN ANTIOXIDANT SHALL BE USED ON ALL MECHANICAL CONNECTIONS AND TERMINATIONS.
THE CONTRACTOR SHALL PROVIDE ALL COPPER CATEGORY 6A PATCH CORDS FOR ALL TRS IN SCOPE. TR CATEGORY 6A PATCH CORDS SHALL BE 50% 3 FEET IN LENGTH AND 50% 5 FEET IN LENGTH. 28 AWG STRANDED PATCH CORDS ARE NOT ALLOWED.
CONTRACTOR SHALL PROVIDE 48 CATEGORY 6A PATCH CORDS FOR EACH 48-PORT SWITCH. JACKET COLORS SHALL BE BLUE OR WHITE. CONTRACTOR SHALL ALSO PROVIDE FIBER OPTIC PATCH CABLES (JUMPERS) FOR ALL FIBER OPTIC CABLES TERMINATED IN THE TRS. THESE CABLES MUST MATCH THE FIBER TYPE, OM4, OS1 AND OS2. FIBER OPTIC PATCH CABLES SHALL BE JACKETED WITH TWO (2) STRANDS EACH AND BE FACTORY TERMINATED WITH LC STYLE CONNECTORS. THE QUANTITY OF FIBER OPTIC PATCH CORDS SHALL MATCH THE NUMBER OF STRANDS TO EACH TR. FOR EXAMPLE, A TR HAVING 24 STRANDS OF OM4 FIBER OPTIC CABLE SHALL HAVE 12 OM4 FIBER OPTIC PATCH CABLES. IN THE TRS THE FIBER OPTIC PATCH CORDS WILL
BE 5 FEET IN LENGTH AND BE JACKETED AS FOLLOWS: OM4 AQUA, OS1 AND OS2 YELLOW.
THE CONTRACTOR SHALL PROVIDE ALL FACTORY TERMINATED CATEGORY 6A CABLES IN QUANTITIES LISTED IN THE DRAWINGS WITHIN THE MCR. 28 AWG STRANDED PATCH CORDS ARE NOT ACCEPTABLE. CABLE LENGTHS SHALL BE DETERMINED BY THE CONTRACTOR AFTER ALL CABINETS AND WIRE MANAGEMENT HAVE BEEN INSTALLED. CABLES SHALL HAVE AS LITTLE SLACK AS POSSIBLE, AND THAT SLACK SHALL BE CONTAINED WITHIN THE VERTICAL WIRE MANAGERS. CABLE JACKET COLORS SHALL BE BLUE OR WHITE. CONTRACTOR SHALL PROVIDE ALL FACTORY TERMINATED FIBER OPTIC PATCH CABLES REQUIRED AS LISTED IN THE DRAWINGS FOR THE MCR. THESE FIBER OPTIC CABLES, SHALL MATCH THE FIBER OPTIC CABLE TYPE. THESE CABLE TYPES ARE OM4, OS1 AND OS2. EACH PATCH CORD SHALL BE JACKETED TO MATCH THE FIBER TYPE, OM4 AQUA, OS1 AND OS2 YELLOW. EACH FIBER OPTIC PATCH CORD SHALL CONSIST OF TWO STRANDS OF THE CORRECT FIBER TYPE TERMINATED ON LC STYLE CONNECTORS. FIBER OPTIC PATCH CORD LENGTHS SHALL NOT HAVE IN EXCESS OF 1 FOOT OF SLACK ON EACH END.
ANY GREEN JACKET WAO DATA CABLES ARE NOT TO BE REPLACED. GREEN JACKET WAO DATA CABLES ARE SUPPORTING YALE.
EXISTING WIRELESS ACCESS POINTS TO BE RE-FED WITH (1) CAT6A CABLE.
CONTRACTOR SHALL PROVIDE IN THEIR BID AN ADDITIONAL 10% TOTAL OF ALL WAO'S IN THE PROJECT. A STANDARD WAO CONSISTS OF 2 - CATEGORY 6A CABLES, 2 - CATEGORY 6A RATED JACK INSERTS, AND A 2 PORT FACEPLATE. THIS SHALL INCLUDE
ALL MATERIALS AND LABOR FOR INSTALLATION, TESTING AND LABELING.
ALL TE'S SHALL BE FITTED WITH TAMPER SWITCHES FOR THE DOORS BOTH FRONT AND REAR. TAMPER SWITCHES SHALL BE CONNECTED TO THE EXISTING PACS SYSTEM FOR MONITORING. ALL TE'S SHALL ALSO BE FITTED WITH KEYED LOCKS AND THE KEYS SHALL BE PROVIDED TO THE COR FOR INCLUSION INTO THE STATION KEY AND LOCK PROGRAM. A MINIMUM OF TWO KEYS FOR EACH TE DOOR LOCK SHALL BE PROVIDED.
CONTRACTOR SHALL INCLUDE IN THEIR BID, 2,000 LINEAL FEET OF 1 1/4-INCH EMT, 50 4-INCH SQUARE BOXES AND 50 SINGLE GANG REDUCING MUD RINGS. CONTRACTOR SHALL NOT PURCHASE THIS EQUIPMENT UNTIL IT IS REQUIRED.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
5/ 5/
:3
6:
A M
Au to de sk
D oc s:
//6
-2
2-
VA
C T
W es t H av en E
H R
M
IU
/V
AW
H _G
EN
ER
AL
SH
EE
TS
_E L_
SD
B.
rv t
TNG001
ABBREVIATIONS AND GENERAL NOTES
DCW/MMM RTS/JGD
100% CONSTRUCTION
DOCUMENTS
04/20/2026
689-22-700EHRM INFRASTRUCTURE
UPGRADES - WEST HAVEN
VA CT WEST HAVEN
950 CAMPBELL AVENUE, WEST HAVEN, CT 06516
G E N E R A L N O T E S
N2
DD5
Revisions: Date:
A A
B B
B B
B B
SCALE
SECTION LETTER
SHEET WHERE
SECTION IS
TAKEN FROM
SECTION LETTER
DETAIL NUMBER
SHEET ON WHICH
DETAIL APPEARS
DETAIL AREA
XXX CONDUIT & WIRE TAG
(REFER TO CONDUIT
AND WIRE SCHEDULE)
XX FAULT CURRENT TAG
(3 PH, SYM AMPS)
KEY NOTE
FIGURE OR PHOTO
DETAIL NUMBER
IF PHOTO, ARROW
DENOTES DIRECTION
TAKEN
SHEET WHERE
DETAIL IS
TAKEN FROM
DETAIL/PLAN
DETAIL/PLAN NUMBER
SHEET WHERE
SECTION IS
TAKEN FROM
XXX
A
XXX
SECTION A
XXX
XXX
XD|XV|XA
1-HR FIRE RATED WALL
2-HR FIRE RATED WALL
SMOKE RATED WALL
DD2
N2 "DD#" = THE NUMBER OF ETHERNET CABLES TO BE DEMOLISHED
"N#" = THE NUMBER OF NEW ETHERNET DROPS TO BE INSTALLED
'A' SIDE FIBER, CONCEALED WHERE POSSIBLE.
'B' SIDE FIBER, CONCEALED WHERE POSSIBLE.
'A' SIDE FIBER, UNDERGROUND / UNDERFLOOR.
'B' SIDE FIBER, UNDERGROUND / UNDERFLOOR.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
5/ 5/
:3
6:
A M
Au to de sk
D oc s:
//6
-2
2-
VA
C T
W es t H av en E
H R
M
IU
/V
AW
H _G
EN
ER
AL
SH
EE
TS
_E L_
SD
B.
rv t
TNG002
TELECOMMUNICATIONS LEGENDS
DCW/MMM RTS/JGD
100% CONSTRUCTION
DOCUMENTS
04/20/2026
689-22-700EHRM INFRASTRUCTURE
UPGRADES - WEST HAVEN
VA CT WEST HAVEN
950 CAMPBELL AVENUE, WEST HAVEN, CT 06516
G E N E R A L S Y M B O L D I V 2 7 - L E G E N D D I V 2 8 - L E G E N D
OUTLET, COMBINATION TELEPHONE/DATA COMMUNICATION
CABLE TELEVISION LINE = CATV
CLOSED CIRCUIT TELEVISION LINE = CCTV. MINIMUM 1" [25mm] CONDUIT
FIBEROPTICS LINE = FO
SPEAKER, CEILING MOUNTED, "X" INDICATES THE TYPE, PROVIDE SCHEDULE ON
LEGEND
SPEAKER, WALL MOUNTED, "X" INDICATES THE TYPE, PROVIDE SCHEDULE
ON LEGEND. MTD. 7'-6" [2286mm] AFF UNLESS OTHERWISE NOTED.
TELEPHONE LINE = T
INTERCOM LINE = I. MINIMUM 3/4" [19mm] CONDUIT.
SOUND LINE = S
NURSE CALL LINE = NC. MINIMUM 3/4" [19mm] CONDUIT.
RADIO CONDUIT RUN, MINIMUM 3/4" [19mm] CONDUIT.
RADIO CHANNEL SELECTOR FACILITIES, MTD. 4'-6" [1372mm] AFF UNLESS
OTHERWISE NOTED.
SPEAKER PROGRAM SELECTOR SWITCH & VOLUME
CONTROL MTD. 4'-6" [1372mm] AFF UNLESS OTHERWISE NOTED.
OUTLET, TELEVISION
BLANK =4 11/16" [119mm] MASTER ANTENNA OUTLET BOX W/BLANK
COVER, MTD. 18" [457mm] AFF UNLESS OTHERWISE NOTED.
C = CAMERA (CCTV SYSTEM), MTD 18" [457mm] AFF
M = MONITOR (CTTV SYSTEM).
NURSE'S CALL MASTER STATION MTD ON
NURSE'S COUNTER TOP UNLESS OTHERWISE NOTED.
NURSE CALL TERMINAL CABINET.
NURSE CALL STATION.
2 = DUPLICATE FACILITIES FOR TWO BEDS (SEPARATE INDICATORS AT MASTER
STATION) MTD 5'-0" [1524mm] AFF UNLESS OTHERWISE NOTED.
D = DUTY STATION. MTD 5'-0" [1524mm] AFF UNLESS NOTED OTHERWISE.
E = MTD 6'-0" [1829mm] AFF FOR SHOWER LOCATION, MTD 4'-6" [1372mm] AFF FOR
TUB LOCATION, & MTD 3'-0" [914mm] AFF FOR TOILET LOCATION.
P = PSYCHIATRIC CORRIDOR STATION WITH KEY SWITCH
S = AUDIO VISUAL MALL STATION (STAFF) MTD 5'-0" [1524mm] AFF UNLESS
OTHERWISE NOTED.
U = UTILITY CALL STATION, MTD 5'-0" [1524mm] AFF UNLESS OTHERWISE NOTED.
NURSE CALL STATION.
2 = NURSE'S CALL DOME LIGHT (SUFFIX INDICATES No OF
LAMP) MTD 6" [152mm] ABOVE DOOR.
D = CORRIDOR DOME LIGHT.
I = AUXILIARY INTERSECTIONAL DOME LIGHT.
TELEPHONE TERMINAL CABINET
TELEPHONE BACKBOARD (WALL MOUNTED)
3-POLE TWIST-LOCK RECEPTACLE FOR MICROPHONE, MTD. 4'-6" 1372mm]
AFF.
REMOTE DICTATING OUTLET MTD 1'-6" [457mm] AFF. UNLESS OTHERWISE NOTED.
INTERCOM STATION (REFER TO SPECS. FOR FUNCTIONAL
OPERATION OF INSTRUMENT & TYPE REQUIRED).
INTERCOM STAFF STATION.
TELECOMMUNICATIONS MANHOLE
DATA/COMMUNICATION AUDIO DEVICE; LETTER INDICATES AS FOLLOWS:
M=MOUNT
C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION
P-PEDESTAL R-RACK S-SURFACE W-WALL
T=TECHNOLOGY/TYPE
B-BELL C-CHIME H-HORN K-KLAXON
L-LISTEN-IN M-MICROPHONE S-SOUNDER S-SPEAKER Z-BUZZER
BI-STATIC BEAM SENSOR; LETTER INDICATES AS FOLLOWS:
M=MOUNT
C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION
P-PEDESTAL R-RACK S-SURFACE W-WALL
T=TECHNOLOGY/TYPE
I-INFRARED M-MICROWAVE
F=FUNCTION
RX-RECEIVE TX-TRANSMIT
BIOMETRICS ACCESS CONTROL DEVICE; LETTER INDICATES AS FOLLOWS:
M=MOUNT
C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION
P-PEDESTAL R-RACK S-SURFACE W-WALL
T=TECHNOLOGY/TYPE
F-FINGER PRINT H-HAND GEOMETRY I-EYE IRIS
R-EYE RETINA V-VOICE
CARD ACCESS READER; LETTER INDICATES AS FOLLOWS:
M=MOUNT
C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION
P-PEDESTAL R-RACK S-SURFACE W-WALL
T=TECHNOLOGY/TYPE
B-BARCODE F-ELEVATOR FLOOR CALL H-ELEVATOR HALL CALL
M-MAG STRIP P-PROXIMITY S-SMART CARD
T-TOKEN
CARD READER WITH KEYPAD; LETTER INDICATES AS FOLLOWS:
M=MOUNT
C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION
P-PEDESTAL R-RACK S-SURFACE W-WALL
CARD READER WITH TIME AND ATTENDANCE; LETTER INDICATES ASFOLLOWS:
M=MOUNT
C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION
P-PEDESTAL R-RACK S-SURFACE W-WALL
CENTRAL PROCESSING UNIT
CONTROL PANEL; LETTER INDICATES AS FOLLOWS:
M=MOUNT
C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION
P-PEDESTAL R-RACK S-SURFACE W-WALL
T=TECHNOLOGY/TYPE
B-BURGLAR D-DOOR F-FIRE P-PERIMETER
ELECTRONIC LOCK; LETTER INDICATES AS FOLLOWS:
M=MOUNT
C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION
P-PEDESTAL R-RACK S-SURFACE W-WALL
T=TECHNOLOGY/TYPE
D-DEADBOLT H-HYBRID L-LATCH SET M-MAGNETIC S-STRIKE
EXIT DEVICE; LETTER INDICATES AS FOLLOWS:
T=TECHNOLOGY/TYP E
D-DELAYED EGRESS E-ELECTRIFIED M-MECHANICAL X-HIGH SECURITY
FIBER OPTIC MODULE; LETTER INDICATES AS FOLLOWS:
M=MOUNT
C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION
P-PEDESTAL R-RACK S-SURFACE W-WALL
T=TECHNOLOGY/TYPE
R-RECEIVERT-TRANSCEIVER TX-TRANSMITTER
FIELD PANEL; LETTER INDICATES AS FOLLOWS:
M=MOUNT
C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION
P-PEDESTAL R-RACK S-SURFACE W-WALL
T=TECHNOLOGY/TYPE
A-ALARM C-CARD READER
GLASS BREAKAGE SENSOR; LETTER INDICATES AS FOLLOWS:
M=MOUNT
C-CEILING D-DESK F-FLUSH H-HIDDEN
M-MULLION
P-PEDESTAL R-RACK S-SURFACE W-WALL
T=TECHNOLOGY/TYPE
A-AUDIO S-SHOCK
INTERCOM; LETTER INDICATES AS FOLLOWS:
M=MOUNT
C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION
P-PEDESTAL R-RACK S-SURFACE W-WALL
T=TECHNOLOGY/TYPE
M-MASTER S-SUBSTATION
KEYBOARD
KEYPAD DEVICE; LETTER INDICATES AS FOLLOWS:
M=MOUNT
C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION
P-PEDESTAL R-RACK S-SURFACE W-WALL
MONITOR; LETTER INDICATES AS FOLLOWS:
M=MOUNT
C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION
P-PEDESTAL R-RACK S-SURFACE W-WALL
T=TECHNOLOGY/TYPE
D-DATA G-GRAPHIC M-MULTISCREEN V-VIDEO
MOTION DETECTOR; LETTER INDICATES AS FOLLOWS:
M=MOUNT
C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION
P-PEDESTAL R-RACK S-SURFACE W-WALL
T=TECHNOLOGY/TYPE
D-DUAL TECHNOLOGY IR-INFRARED M-MICROWAVE U-ULTRASONIC
X-REQUEST-FOR-EXIT
RECORDER; LETTER INDICATES AS FOLLOWS:
M=MOUNT
C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION
P-PEDESTAL R-RACK S-SURFACE W-WALL
T=TECHNOLOGY/TYPE
A-AUDIO D-DIGITAL V-VIDEO
SECURITY ACCESS, ANNUNCIATOR PANEL
SECURITY ACCESS, BUZZER. MTD 1'-6" [457mm] AFF
UNLESS OTHERWISE NOTED
SECURITY ACCESS, CONTROL UNIT WITH
CLOSED CIRCUIT TELEVISION CAMERA
SECURITY ACCESS, GENERIC "X" INDICATES THE
TYPE, PROVIDE SCHEDULE OR LEGEND
SECURITY ACCESS, HORN OR SIREN
SECURITY ACCESS, OUTDOOR MICROWAVE TRANSMISSION UNIT
SECURITY ACCESS, PANIC ALARM
SECURITY ACCESS, VIDEO CAMERA WITH LENS
M = MOTION DETECTOR
PZ = MOTION DETECTOR WITH PAN AND ZOOM
PTZ= MOTION DETECTOR WITH PAN, TILT, AND ZOOM
SECURITY ACCESS, VOLUMETRIC SENSOR
SECURITY SCREEN WITH ALARM; LETTER INDICATES ASFOLLOWS:
T=TECHNOLOGY/TYPE
B-BLIND S-SHADE
SECURITY WINDOW SCREEN; LETTER INDICATES ASFOLLOWS:
T=TECHNOLOGY/TYPE
B-BLIND
VIDEO CONTROL KEYBOARD
VIDEO MOTION DETECTOR
SECURITY ACCESS, PANNING CAMERA TRAVERSE ANGLE
C = CEILING MOUNTED.
SECURITY ACCESS, SENSOR, BURIED VEHICULAR
SECURITY ACCESS, SWITCH, BALANCED MAGNETIC CONTROL
SECURITY ACCESS, TELEPHONE HANDSET
SECURITY ACCESS, VIDEO CAMERA WITH LENS, ANGLE OF VIEW
ALARM, CHECK VALVE
ALARM, FIRE, COMMUNICATOR
ALARM, FIRE, PANEL; LETTERS INDICATE AS FOLLOWS:
FACC = CENTRAL CONSOLE FACP = CONTROL PANEL
MFACP= MASTER CONTROL PANELFAAP = ANNUNCIATORPANEL
ALARM, FIRE, MANUAL PULL STATION
ALARM, GONG
ALARM, HORN/LIGHT, ONE ASSEMBLY WITH CHIME
ALARM, HORN/LIGHT, SEPARATE ASSEMBLY
ALARM, LAMP LIGHT, SIGNAL LIGHT, STROBE
ALARM, MANUAL CONTROL
ALARM, MINI HORN
ALARM, SPRINKLER SYSTEM WATER FLOW BELL
ALARM, TAMPER SWITCH
DETECTION, GAS
DETECTION, SMOKE CONTROL AND PRESSURE PANEL
DETECTION SWITCH, ABORT
DETECTION SWITCH, VALVE TAMPER
DETECTOR, FLAME FLICKER
DETECTOR, FLOW SWITCH
DETECTOR, HEAT
DETECTOR, HEAT; LETTER INDICATES AS FOLLOWS:
R/T = COMBINATION F = FIXED TEMPERATURERISE
R/C = RATE COMPENSATION R = RATE OF
DETECTOR; LETTER INDICATES AS FOLLOWS:
BLANK = SMOKE DETECTOR
H = HEAT SMOKE
I = IONIZATION SMOKE
P = PHOTOELECTRIC SMOKE
IH = IONIZATION AND HEAT SMOKE
IP = IONIZATION AND PHOTOELECTRIC SMOKE
PH = PHOTOELECTRIC AND HEAT SMOKE
IPH = IONIZATION, PHOTOELECTRIC, AND HEAT
DETECTOR, SMOKE, FOR DUCT
DETECTOR, SWITCH LEVEL
PUSH BUTTON; LETTER INDICATES AS FOLLOWS:
M=MOUNT
C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION
P-PEDESTAL R-RACK S-SURFACE W-WALL
T=TECHNOLOGY/TYPE
B-BELL PUSH D-DURESS P-PANIC R-DOOR RELEASE
X-REQUEST-FOR-EXIT
CODE ONE CONTROL AND ALARM STATION. MTD 5'-0"
AFF UNLESS OTHERWISE NOTED.
CODE ONE TERMINAL CABINET.
CODE ONE ANNUNCIATOR PANEL.
CODE ONE BEDSIDE STATION.
CODE ONE DUTY STATION, MTD 5'-0" AFF UNLESS
OTHERWISE NOTED.
ALARM, FIRE; LETTERS INDICATE AS FOLLOWS:
BATT =BATTERIESCHR = CHARGER FAR = RECORDER
ALARM, FIRE, VALVE SUPERVISORY SWITCH.
ALARM, FIRE, TERMINAL CABINET.
ALARM, FIRE, POST INDICATOR VALVE.
ALARM, TRANSPONDER OR TRANSMITTER
ALARM, VOICE COMMUNICATION PANEL
FIRE ALARM STATION, MANUAL PULL
FIRE ALARM LINE = FA
ELECTROMAGNETIC TYPE DOOR HOLDER OUTLET
CITY FIRE ALARM MASTER STATION MTD 5'-6" [1676mm] AFF UNLESS
NOTED.
FIRE ALARM TRANSMITTER (BASE LOOP) NUMERALS DENOTE CODE.
FIRE ALARM TROUBLE TRANSMITTER (BASE LOOP) NUMERALS DENOTE
CODE.
ALARM, HORN/LIGHT, ONE ASSEMBLY C = WITH CHIME
360°
40°
X
M PTZ
FAT
2-4-6
FAT
2-4-6
AP
NIPNIP
NITNIT
NIANIA
NINI
NIDNID
FAC
FACP
P
C
BATT
OSY
FATC
PIV
M
TS
FTR
SCCP
HD
R/T
HD
H
FS
N
TTB
S X
S X
M
N
R M
C
DH
R
R M
NCS
NCT
S
WB
M
T
M
T
M
F
T
M
T
T
M
M
M
M
T
T
M
T
M
T
M
T
M
T
M
M
T
M
T
M
T
M
T
T
T
CP
EPO
FA
CATV
CCTV
FO
T
I
S
NC
R
= 3 - BUTTON EMERGENCY STATION. MTD 5'-0" AFF.3
WIRELESS ACCESS POINT.
"S" = STAFF; "G" = GUEST. IF NOTED LIKE THIS "S,G", CONTRACTOR SHALL PROVIDE
(2) SEPARATE WAPs, (1) WAP FOR EACH SERVICE.
XWAP
CONDUIT OR EQUIPMENT TO BE REMOVED
CONDUIT CONCEALED IN WALL, CEILING, UNDER FLOOR,
IN FLOOR SLAB, OR ROUTED UNDERGROUND
CONDUIT CONCEALED WHERE POSSIBLE, OTHERWISE
EXPOSED
EXTRA-HARD USAGE FLEXIBLE CORD
FLEXIBLE CONDUIT
CONDUIT TURNED UP OR TOWARD
CONDUIT TURNED DOWN OR AWAY
CONDUIT CAPPED
M-MULLION
THESE ARE GENERAL LEGENDS. NOT ALL SYMBOLS MAY BE SHOWN.
REFERENCE PLANS FOR ALL UTILIZED SYMBOLS.
P/D POWER/DATA POLE
COMBINATION OUTLET, "X" INDICATES NUMBER OF OUTLET PORTS.
D = DATA
V = VOICE
A = ANALOG
H HAND HOLE FOR BUILDING ENTRY
WAP
WAP
WAP
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 18 20 23 26 27 28 31 32 35 36 39 41 4442 43 4540
JJ
HH
GG
FF
EE'
EE
CC'
AA
CC
DD
BB
Z'
Z
Y'
Y
X
W'
U
T
S
R
Q
P
M
L K
E
C
A
B
G
H
J
V
W
O
21 22 24 29 30 33 34 37 38
TOILET
SS-8-M
JANITOR
CLOSET
SS-7-M
STAIR 5
SS005
AUTOPSY RM
SS-5-M
VESTIBULE
SS-2-M
CORRIDOR
SSC1-01
ELEV. MECH.
RM.
SS-4-M
EMBALMING
RM
SS-3-M
MECH. RM
SS-6-M
COOLER
SS-1-M
CONDENSATE
PUMP SLAB
CS-6
DATA OUTLETS AND DEVICES IN THIS AREA SHALL BE SERVED
FROM TELECOMMUNICATIONS ROOM SG105B ON LEVEL 0SG.
N2
N2N2
DD3
DD3
DD3
TYP.
N2
N2
N2
N2
DD3DD3
DD3
DD3
DD3
N2
2" SLEEVE FROM SG105
FOR 6A DATA OUTLETS
46 47 48
BLDG 001
AREA SHOWN
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
5/ 5/
:1
7:
A M
Au to de sk
D oc s:
//6
-2
2-
VA
C T
W es t H av en E
H R
M
IU
/V
AW
H _0
1_
EL
_S D
B.
rv t
001TN100SSG
BLDG 001 - LEVEL 0SSG -
TELECOMMUNICATIONS PLAN
DCW/MMM RTS/JGD
100% CONSTRUCTION
DOCUMENTS
04/20/2026
689-22-700EHRM INFRASTRUCTURE
UPGRADES - WEST HAVEN
VA CT WEST HAVEN
950 CAMPBELL AVENUE, WEST HAVEN, CT 06516
- 1" = 20'-0"
1 BLDG 001 - LEVEL 0SSG - TELECOMMUNICATIONS PLAN
TRUE
NORTH
0 20' 40'10'
PROJECT
NORTH
1 PROVIDE TELECOMMUNICATIONS OUTLET WITH PORT QUANTITY SHOWN TO REPLACE
EXISTING TELECOMMUNICATIONS OUTLET; EXISTING OUTLET CONDUIT SHALL REMAIN
AND BE UTILIZED TO FEED NEW CABLING; REFERENCE SHEET DETAIL '1' ON SHEET
TN501 AND THE GENERAL NOTES ON THIS SHEET FOR ADDITIONAL INFORMATION.
COORDINATE WITH VA FOR EXACT OUTLET PLACEMENT.
EXISTING WIRELESS ACCESS POINT TO BE RE-FED WITH (1) CAT6A CABLE.2
GENERAL NOTES
KEY NOTES
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR CLARITY. CONTRACTOR SHALL
FIELD VERIFY ALL DEVICES AND ASSOCIATED CABLING AS REQUIRED. ALL RACEWAYS
AND CABLING ASSOCIATED WITH EQUIPMENT TO BE DEMOLISHED SHALL BE
DEMOLISHED BACK TO ITS SOURCE, UNLESS OTHERWISE NOTED.
PROTECT ALL EXISTING WORK FROM DAMAGE DURING CONSTRUCTION. ANY
DAMAGED MATERIALS, SYSTEMS, COMPONENTS, AND FINISHES SHALL BE REPAIRED
OR REPLACED AT THE EXPENSE OF THE CONTRACTOR TO THE ACCEPTANCE OF THE
OWNER.
SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE
RATING OR NEW FIRE RATING. COORDINATE WITH ARCHITECTURAL DRAWINGS AS
REQUIRED.
ALL TELECOMMUNICATIONS CABLING CATEGORY 6 AND BELOW SHALL BE REMOVED
AND REPLACED WITH CAT6A PORTS AND CABLE QUANTITIES INDICATED, UNLESS
NOTED OTHERWISE.
TELECOMMUNICATIONS CABLES SHALL BE ROUTED IN EXISTING PATHWAY VACATED
BY EXISTING CABLING AS CONDUIT FILL ALLOWS. PROVIDE ADDITIONAL RACEWAYS
TO EXTEND TO ASSOCIATED TR AS REQUIRED.
TELECOMMUNICATIONS WAO UPGRADE SHALL INCLUDE, BUT IS NOT LIMITED TO
REMOVING AND DISPOSING OF EXISTING CABLING, JACKS AND FACEPLATES AS
REQUIRED; PROVIDING ALL LABOR, MATERIALS, TOOLS, TEST INSTRUMENTS, AND
CONSUMABLES REQUIRED FOR INSTALLATION, TERMINATION, TESTING, LABELING,
AND CERTIFICATION OF A FULLY FUNCTIONAL CATEGORY 6A OUTLET WITH PORT
QUANTITY INDICATED.
WHEN PROVIDING A WAO IN LOCATIONS WHERE AN EXISTING WAO CURRENTLY DOES
NOT EXIST, PROVIDE (1) 4-INCH SQUARE BACKBOX WITH SINGLE-GANG REDUCING
MUD RING AND (1) 1-1/4" CONDUIT EXTENDING FROM BACKBOX TO ACCESSIBLE
CEILING SPACE. ONCE IN ACCESSIBLE CEILING SPACE, CABLING SHALL EXTEND TO
ITS ASSOCIATED TR VIA CABLE TRAY; UTILIZE J-HOOKS EVERY 48 ” WHEN
TRANSITIONING TO OR FROM CABLE TRAY. IF CABLE TRAY IS NON-EXISTENT, EXTEND
HORIZONTAL CABLING FROM WAO TO TR VIA J-HOOKS ONLY.
PROVIDE PULL BOXES SIZED PER ANSI/TIA-569 AT 100-FT INTERVALS IN STRAIGHT
CONDUIT RUNS, OR CONDUIT CONTAINING BENDS TOTALING MORE THAN 180
DEGREES.
PROVIDE CONDUITS AND SLEEVES AS REQUIRED FOR ROUTING AND INSTALLATION
OF HORIZONTAL AND BACKBONE CABLING. PROVIDE FIRE-STOP MATERIALS TO SEAL
IN AND AROUND CONDUIT PER CODE. REFER TO ARCHITECTURAL DRAWINGS FOR
PARTITION TYPES AND WALL HEIGHTS.
OUTLET LOCATIONS ARE APPROXIMATE. DETERMINE EXACT LOCATIONS IN FIELD;
DOCUMENT VARIANCES BASED ON AS-BUILT DRAWINGS. WAO'S INSTALLED ON
OPPOSITE SIDES OF WALLS WILL BE OFFSET 24" CENTER TO CENTER.
ALL DATA CABLING SHALL BE SEGREGATED FROM OTHER SPECIAL SYSTEMS
INCLUDING, BUT NOT LIMITED TO, SECURITY, FIRE ALARM, AND NURSE CALL
SYSTEMS. WHEN ROUTED THROUGH CONDUIT, DATA CABLING SHALL HAVE ITS OWN
RACEWAY. WHEN DATA CABLING IS ROUTED THROUGH A COMMON SPECIAL SYSTEMS
CABLE TRAY, CABLING SHALL BE BUNDLED WITH LIKE SYSTEMS; ADDITIONALLY,
CABLE TRAYS SHALL BE PROVIDED WITH TRAY DIVIDERS AS REQUIRED TO
SEGREGATE SYSTEMS FROM ONE ANOTHER.
FIBER-OPTIC CABLING ROUTES AND ASSOCIATED RACEWAYS/CABLE TRAY ARE
DIAGRAMMATICAL. COORDINATE EXACT ROUTING WITH EXISTING CONDITIONS,
ARCHITECTURAL FEATURES, MECHANICAL DUCTWORK, PIPING, EQUIPMENT, AND ANY
OTHER OBSTRUCTIONS PRIOR TO INSTALLATION.
THE CONTRACTOR SHALL BID AND INSTALL CAT6A CABLE WITH AN OD NOT GREATER
THAN 0.250 INCH (6.35mm) (4) CAT6A CABLES WITH AN 0.250 INCH (6.35mm) OD OR
SMALLER CAN BE INSTALLED IN A ¾” CONDUIT SUPPORTING A 40% FILL RATIO.
ANY GREEN JACKET WAO DATA CABLES ARE NOT TO BE REPLACED. GREEN JACKET
WAO DATA CABLES ARE SUPPORTING YALE.
KEY PLAN
WAP
WAPWAP
WAP WAP
WAP
WAP
WAP W
AP
WAP
W
AP
WAP
WAP
WAP WAPWAP
FACP
A
A
A A A A A A A A A A A A A A A A A A A A A A A A A
A
A
A
A
A
A
A
A
AAA
A
A
BBBBBBB
B B B B B B B B B B B B B B
B
B
B
B
B
B
B
B
B
B B B B B B
B B B B B B B B B B B B B B B B
BBBBBBB
A A
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 18 20 23 26 27 28 31 32 35 36 39 41 4442 43 4540
JJ
HH
GG
FF
EE'
EE
CC'
AA
CC
DD
BB
Z'
Z
Y'
Y
X
W'
U
T
S
R
Q
P
M
L
K
E
C
A
B
G
H
J
V
W
O
21 22 24 29 30 33 34 37 38
001TN400SGb
001TN400SGb
001TN400SGb
001TN400SGb
001TN400SGa
001TN400SGa
001TN400SGa
001TN400SGa
STORAGE
SG200E-1-W
MECH. EQUIP.
SG180F
FIRE PUMP
EQUIP.
SG180E
MASON
SUPPLIES
SG180C
EQUIP.
STORAGE
SG180D VESTIBULE
SG178
CAPPED FIRE
RISER
SG179
MECH
SG182
MASON
SUPPLIES
SG180
CORRIDOR
SGC5A-01
HAC
SG193A
SG177
MECH.
SG180A
MECH.
SG180B
CORRIDOR
SGC5-01
SG174
TR
SG171 OFFICE
SG172MAIL RM.
SG168
CHASE
SG166 STAIR #1
SG001
CORRIDOR
SGC4-01
ADP
SG164
LINEN CHUTE
SG165
CLEAN CART
LIFT RM
SG200
BULK
STORAGE
SG199
ELECT.
SG199A
STAIR #9
SG009
STORAGE
SG186
MENS L L T S
BATHROOM
SG195
WOMENS L L T
S BATH RM.
SG196
CORRIDOR
SGC6A-01
XQC PPE
STORAGE
SG198
STER-OPER
SG197
ETO
STERILIZATION
SG192A
SOILED AND
DECONTAMINATION
SG193
STERIL-OPER
SG194
PREP.
SG192
STORAGE
SG192B
LOCKER
SG202
LOCKER
SG203
AIR
CONDITIONING
AND EQUIP.
RM.
SG101
HAC
SG102
CHASE
SG101A
CORRIDOR
SGC1-01
HAC
SG103
MECH.
SG104 STAIR #5
SG005
SUPV
SG105C
MEN'S TOILET
SG107
WOMEN'S
TOILET
SG108
COMPUTER/
STORAGE
SG109A
ELECT.
SG109B
ELECT.
SG109
CORRIDOR
SGC1A-01
VESTIBULE
SG105A
ADP
SG105
1127 SF CORRIDOR
SGC1B-01
STORAGE
SG106
STORAGE
SG106A
MRI RM
SG106B
STORAGE
SG106C
LOAD
CENTER-1
SG110
ELECT.
SG110A
ELEV.
SG017
EQUIPMENT
RM
SG129
MSR
SG128B
CONTROL
AREA
SG128
OFFICE
SG128A
WAITING/
RECEPTION
SG126
INTERVIEW
SG126A
TOILET/CHANGE
SG126B
OTHER SPACE
SG127
COMPUTER
SG114C
HOOD RM
SG125
OFFICE
SG120
TOILET
SG116
EXAM/
TREATMENT
RM
SG114
TOILET
SG112
EXAM
SG114A
OFFICE CLERK
SG121
CORRIDOR
SGC3A-01
OFFICE
SG122
SPRINKLER
SG127B
ELECTRICAL
SG123
MECHANICAL
SG127A
MECH.
HOUSEKEEPING
CLOSET
SG124
PASSAGE
SG031
PASSAGE
SG033
OTHER SPACE
SG114B
VICE CHIEF
OFFICE
SG119
OFFICE/CHIEF
SG118
OFFICE/
PHYSICIAN
SG117
EXAM/
PHYSICIAN
SG115
WAITING
SG111
CORRIDOR
SGC3-01
OFFICE
SG157
CORRIDOR
SGC2C-01
STORAGE
SG156
TRAINING/
BREAK
SG155
EQUIP. RM.
SG138
LOCKER
SG137
STAIR #8
SG008
MRI EXAM
RM-1
SG139
SHARED MRI
CONTROL
SG140
MRI EXAM
RM-2
SG141
CORRIDOR
SGC2B-01
STRECHER
HOLD
SG136
DRESSING
SG135
DRESSING
SG134
STORAGE
SG144
LOUNGE
SG150
PATIENTS
TOILET
SG133
STAFF TOILET
SG151
READING RM-2
SG146
READING RM-1
SG145
EQUIP. RM
SG142
RADIOLOGY
X-RAY FILE RM
SG160A
STAIR #2
SG002
ELECT.
SG160
CORRIDOR
SGC2-01
RECEPTION/
SECT.
SG130A
WAITING
SG130
WOMEN'S
TOILET
SG131
MEN'S
BATHROOM
SG132
ELECT.
SG148
HAC
SG149
PATIENT REC.
SG130B
CORRIDOR
SGC2A-01
LAUNDRY RM
SG161
ADP CLOSET
SG162
CLEAN
STORAGE
SG201
CLOSET
SG191C
PASSENGER
ELEV. #3
SG012
PASSENGER
ELEV. #4
SG011
SVC
SG015
PASSENGER
ELEV. #1
SG013
PASSENGER
ELEV. #2
SG014
CORRIDOR
SGC1C-01
BATH/
SHOWER
SG176
BATH/
SHOWER
SG175
SPD INT STAFF
CIRC
SG191
STORAGE
SG191A
SVC ELEV. #S2
SG016
CORRIDOR
SGC6-01
AUXILIARY
WORK AREA
SG173
CRAWL SPACE
FAC
CRAWL SPACE
CLEAN LIFT
#C1
EXTERIOR
SPACE
CRAWL SPACE
DUCT
DUCT
-CRAWL SPACE
CS 1
DUCT
DUCT
FIREMAN'S
CLOSET
FEC
CHASE
DW1
DW2
CLOSET
COMPUTER
RM
SG126
MECH. EQUIP.
SG138
(UNDER
CONSTRUCTION)
MECH
SG184
STORAGE
SUPPLY
SG193C
MANUAL CART
WASH
SG193B
SOILED LIFT
#C2
TR
SG105B
DATA OUTLETS AND DEVICES IN THIS AREA SHALL BE SERVED
FROM TELECOMMUNICATIONS ROOM SG171 AND SG105D.
001TN400SGc
001TN400SGd
001TN400SGc
001TN400SGd
001TN400SGc
001TN400SGc
001TN400SGd
001TN400SGd
001TN400SGe
001TN400SGf
DATA OUTLETS AND
DEVICES IN THIS AREA
SHALL BE SERVED FROM
TELECOMMUNICATIONS
ROOM SG105B.
DATA OUTLETS AND
DEVICES IN THIS AREA
SHALL BE SERVED FROM
TELECOMMUNICATIONS
ROOM SG171.
DATA OUTLETS AND
DEVICES IN THIS AREA
SHALL BE SERVED FROM
TELECOMMUNICATIONS
ROOM SG105B.
DATA OUTLETS AND
DEVICES IN THIS AREA
SHALL BE SERVED FROM
TELECOMMUNICATIONS
ROOM SG171.
DD3
N2
DD3
DD3
DD3
DD3
DD3 DD3
DD3 DD3
DD3
DD3
N2
N2 N2 N2 N2
N2 N2
N2
N2
N2
DD3
DD6
N2
N2
DD4
DD4
DD3
DD2 DD1
DD1
DD6
DD1
DD3
N2
N2
N2
N2
N2
N2 N2
N2
N2
N2
DD3
N2
N2
N2
N2 DD1
DD1
DD3
DD3
DD1
N2
N2
N2
DD1
DD32
DD3
DD7
DD3
DD3
DD3
DD3
DD3
N2 N2 N2
DD3
N2 N2 N2
N2 N2
2N2 N2
DD6 DD3
DD1
DD3 DD1
DD3
N2
N2N2
N2
DD3
DD2
DD7
N2 N2
N2
DD3
DD1
DD3
DD2
DD1
DD5
DD9
DD3
DD3
DD3
DD3
N2
N2
N2
N2
N2
N2
N2 N2
N2
N2
N2
TYP.
A
B
4" SLEEVE
FROM G149
4" SLEEVE
FROM G195A
EXISTING MCR
TO BE MOVED
2" SLEEVE &
VERTICAL LADDER
RACK FOR DATA
OUTLETS IN LEVEL
0SSG
24 STRAND SM
BIOMED TO
NEW MCR
OFFICE
SG170
OFFICE
SG170A
46 47 48
12-STRAND (MATCH FIBER TYPE &
CONNECTOR NEEDED)
THIS WILL RUN BACK TO NEW MCR.
6-STRAND OM4 TO
POLICE SECURITY IN
ROOM G1221A
B
BLDG 001
AREA SHOWN
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
5/ 5/
:1
7:
A M
Au to de sk
D oc s:
//6
-2
2-
VA
C T
W es t H av en E
H R
M
IU
/V
AW
H _0
1_
EL
_S D
B.
rv t
001TN100SG
BLDG 001 - LEVEL 0SG -
TELECOMMUNICATIONS PLAN
DCW/MMM RTS/JGD
100% CONSTRUCTION
DOCUMENTS
04/20/2026
689-22-700EHRM INFRASTRUCTURE
UPGRADES - WEST HAVEN
VA CT WEST HAVEN
950 CAMPBELL AVENUE, WEST HAVEN, CT 06516
- 1" = 20'-0"
1 BLDG 001 - LEVEL 0SG - TELECOMMUNICATIONS PLAN
GENERAL NOTES
KEY NOTES
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR CLARITY. CONTRACTOR SHALL
FIELD VERIFY ALL DEVICES AND ASSOCIATED CABLING AS REQUIRED. ALL RACEWAYS
AND CABLING ASSOCIATED WITH EQUIPMENT TO BE DEMOLISHED SHALL BE
DEMOLISHED BACK TO ITS SOURCE, UNLESS OTHERWISE NOTED.
PROTECT ALL EXISTING WORK FROM DAMAGE DURING CONSTRUCTION. ANY
DAMAGED MATERIALS, SYSTEMS, COMPONENTS, AND FINISHES SHALL BE REPAIRED
OR REPLACED AT THE EXPENSE OF THE CONTRACTOR TO THE ACCEPTANCE OF THE
OWNER.
SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE
RATING OR NEW FIRE RATING. COORDINATE WITH ARCHITECTURAL DRAWINGS AS
REQUIRED.
ALL TELECOMMUNICATIONS CABLING CATEGORY 6 AND BELOW SHALL BE REMOVED
AND REPLACED WITH CAT6A PORTS AND CABLE QUANTITIES INDICATED, UNLESS
NOTED OTHERWISE.
TELECOMMUNICATIONS CABLES SHALL BE ROUTED IN EXISTING PATHWAY VACATED
BY EXISTING CABLING AS CONDUIT FILL ALLOWS. PROVIDE ADDITIONAL RACEWAYS
TO EXTEND TO ASSOCIATED TR AS REQUIRED.
TELECOMMUNICATIONS WAO UPGRADE SHALL INCLUDE, BUT IS NOT LIMITED TO
REMOVING AND DISPOSING OF EXISTING CABLING, JACKS AND FACEPLATES AS
REQUIRED; PROVIDING ALL LABOR, MATERIALS, TOOLS, TEST INSTRUMENTS, AND
CONSUMABLES REQUIRED FOR INSTALLATION, TERMINATION, TESTING, LABELING,
AND CERTIFICATION OF A FULLY FUNCTIONAL CATEGORY 6A OUTLET WITH PORT
QUANTITY INDICATED.
WHEN PROVIDING A WAO IN LOCATIONS WHERE AN EXISTING WAO CURRENTLY DOES
NOT EXIST, PROVIDE (1) 4-INCH SQUARE BACKBOX WITH SINGLE-GANG REDUCING
MUD RING AND (1) 1-1/4" CONDUIT EXTENDING FROM BACKBOX TO ACCESSIBLE
CEILING SPACE. ONCE IN ACCESSIBLE CEILING SPACE, CABLING SHALL EXTEND TO
ITS ASSOCIATED TR VIA CABLE TRAY; UTILIZE J-HOOKS EVERY 48 ” WHEN
TRANSITIONING TO OR FROM CABLE TRAY. IF CABLE TRAY IS NON-EXISTENT, EXTEND
HORIZONTAL CABLING FROM WAO TO TR VIA J-HOOKS ONLY.
PROVIDE PULL BOXES SIZED PER ANSI/TIA-569 AT 100-FT INTERVALS IN STRAIGHT
CONDUIT RUNS, OR CONDUIT CONTAINING BENDS TOTALING MORE THAN 180
DEGREES.
PROVIDE CONDUITS AND SLEEVES AS REQUIRED FOR ROUTING AND INSTALLATION
OF HORIZONTAL AND BACKBONE CABLING. PROVIDE FIRE-STOP MATERIALS TO SEAL
IN AND AROUND CONDUIT PER CODE. REFER TO ARCHITECTURAL DRAWINGS FOR
PARTITION TYPES AND WALL HEIGHTS.
OUTLET LOCATIONS ARE APPROXIMATE. DETERMINE EXACT LOCATIONS IN FIELD;
DOCUMENT VARIANCES BASED ON AS-BUILT DRAWINGS. WAO'S INSTALLED ON
OPPOSITE SIDES OF WALLS WILL BE OFFSET 24" CENTER TO CENTER.
ALL DATA CABLING SHALL BE SEGREGATED FROM OTHER SPECIAL SYSTEMS
INCLUDING, BUT NOT LIMITED TO, SECURITY, FIRE ALARM, AND NURSE CALL
SYSTEMS. WHEN ROUTED THROUGH CONDUIT, DATA CABLING SHALL HAVE ITS OWN
RACEWAY. WHEN DATA CABLING IS ROUTED THROUGH A COMMON SPECIAL SYSTEMS
CABLE TRAY, CABLING SHALL BE BUNDLED WITH LIKE SYSTEMS; ADDITIONALLY,
CABLE TRAYS SHALL BE PROVIDED WITH TRAY DIVIDERS AS REQUIRED TO
SEGREGATE SYSTEMS FROM ONE ANOTHER.
FIBER-OPTIC CABLING ROUTES AND ASSOCIATED RACEWAYS/CABLE TRAY ARE
DIAGRAMMATICAL. COORDINATE EXACT ROUTING WITH EXISTING CONDITIONS,
ARCHITECTURAL FEATURES, MECHANICAL DUCTWORK, PIPING, EQUIPMENT, AND ANY
OTHER OBSTRUCTIONS PRIOR TO INSTALLATION.
THE CONTRACTOR SHALL BID AND INSTALL CAT6A CABLE WITH AN OD NOT GREATER
THAN 0.250 INCH (6.35mm) (4) CAT6A CABLES WITH AN 0.250 INCH (6.35mm) OD OR
SMALLER CAN BE INSTALLED IN A ¾” CONDUIT SUPPORTING A 40% FILL RATIO.
ANY GREEN JACKET WAO DATA CABLES ARE NOT TO BE REPLACED. GREEN JACKET
WAO DATA CABLES ARE SUPPORTING YALE.
KEY PLAN
TRUE
NORTH
0 20' 40'10'
PROJECT
NORTH
1 PROVIDE TELECOMMUNICATIONS OUTLET WITH PORT QUANTITY SHOWN TO REPLACE
EXISTING TELECOMMUNICATIONS OUTLET; EXISTING OUTLET CONDUIT SHALL REMAIN
AND BE UTILIZED TO FEED NEW CABLING; REFERENCE SHEET DETAIL '1' ON SHEET
TN501 AND THE GENERAL NOTES ON THIS SHEET FOR ADDITIONAL INFORMATION.
COORDINATE WITH VA FOR EXACT OUTLET PLACEMENT.
EXISTING WIRELESS ACCESS POINT TO BE RE-FED WITH (1) CAT6A CABLE.2
WAPWAP
WAP
WAPWAP
WAP WAP
WAP WAP
WAP
WAP WAP
WAP
WAP
WAP
WAP
WAP
WAP
WAP
WAP
WAP
WAP
WAP
WAP
WAP
WAP
WAP WAP
WAP
WAP
WAP
WAP
WAP
WAP
WAP
WAP
WAP
WAP
WAP
WAP
WAP
WAP
WAP
WAP
WAP
WAP
WAP
AAAAAAA
A
A
A A A A A A A
AAAAAAA
AAAAAAA A A A A A A A A A A A A A A
A
A
A
AAAAAA
A
A
A
A
A
A
A
AAAAAAA
AAAAAAA
BBBBBBB
BBBBBBB
A
A
A
AA
A
A
A
A
A
A
A
A
A
A
A B
B
B
B
B
B
B
B
B
B
B B B
B
BBBBBBB
B
B
BBBBB
BBBBBBB B
B
BBBBBBB
B B B B B B
B
B
B
BBBBBBB
BBBBBBB
BBBBBBB
BBBBBBB
B
B
B
B B B B B B B B
B
B
B
B
B
B
B
B
B
B
B
B
BBBBBB BB B B B B B
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 18 20 23 26 27 28 31 32 35 36 39 41 4442 43 4540
JJ
HH
GG
FF
EE'
EE
CC'
AA
CC
DD
BB
Z'
Z
Y'
Y
X
W'
U
T
S
R
Q
P
M
L
K
E
C
A
B
G
H
J
V
W
O
21 22 24 29 30 33 34 37 38
001TN400Ga
001TN400Ga
001TN400Ga
001TN400Ga
001TN400Gb
001TN400Gb
001TN400Gb
001TN400Gb
BUFFER RM
G220G
CHEMO RM
G220F
ANTE RM
G220E
CLEAN PREP
G220H
LOBBY
G220DHAC
G220I
OFFICE
G220B
COMPOUNDING
RM
G220A
PHARM
G220
OFFICE
G220C
CHIEF
PHYSIATRY
G229
PHYSICAL
THERAPY
OFFICE
G230
PHYSICAL
MED AND
REHAB OFFICE
G231
PHYSICAL
MED AND
REHAB OFFICE
G232
CHIEF OF
PHARM
OFFICE
G236A
PHARM
G236
PHARM
G235A
HAC
G228
HC TOILET
G227
RECEPTION
G222
G223
PHARM
G224
FOOD AND
NUTRITION
G225
STORAGE
G233
FILE RM
G234
CORRIDOR
GC7B-01
CORRIDOR
GC7-01
HC TOILET
G217
PHARM
STORAGE
G215
TOILET
G218
PHARM
STORAGE
G215A
STAIR #1
G001
STORAGE
G259
STORAGE
G260
STORAGE
G259A
STORAGE
G261 TOILET
G261A
CORRIDOR
GC11-01
ELECT.
G260A
PRESSURE
WASH
G262
HAZARDOUS
WASTE
G263
HAZARDOUS
WASTE
G264
NUCLEAR
WASTE
G265
OFFICE
G266
WALK-IN
REFRIGERATOR
G267
RECYCLE
G268
CORRIDOR
GC11A-01
OFFICE
G271A
PLUMBING
SHOP
G273
CORRIDOR
GC10-01
CORRIDOR
GC10A-01
CART WASH
G258
STORAGE
G257B
STORAGE
G257
FRUIT AND
VEGETABLE
STORAGE
G257A
WAREHOUSE
G271
MEAT
REFRIGERATOR
G272A COOKS
STORAGE
G278
TR
G277
CLEAN LINEN
G277
SOILED LINEN
G276
VEGETABLE
STORAGE
G272C
BAKERS
G281COOKS
G279
COOKS
G280
DEEP FREEZE
G281A
CO-PREP
G283
STORAGE
GENERAL
G255B
DAIRY
REFRIGERATOR
G255
FROZEN FOOD
G255A
ELECT.
G212
KITCHEN
G211
STORAGE
G195A
EXAM/
TREATMENT
RM
G195
ADP
G196
OFFICE
G197
ADMIN COMP
AND PENSION
OFFICE
G198
EXAM
G199
EXAM
G200
EXAM
G201
EXAM
G206
EXAM
G202
OFFICE
G203
VESTIBULE
G204
EXAM
G205
EXAM
G207
EXAM
G208
COMP. AND
PENSION
CHECK IN/OUT
G210
CORRIDOR
GC6-01
FEC
STORAGE
G187M
STAFF TOILET
G187L
PICKER CT
EQUIP
G187E
PICKER CT
SCAN RM
G187F
CORRIDOR
GC5A-01
EQUIP RM
G187J
PHYSICIAN
G187I
TOSHIBA CT
SCAN RM
G187H
SHARED
CONTROL
G187G
CORRIDOR
GC5-01
HANDICAP
DRESSING
G187D
ELECT.
G253
ELECT.
G252A
ELECT.
G275A
OFFICE
DIETITIAN
G286
OFFICE
G287
STAIR #9
G009
KITCHEN
G288A
CORRIDOR
GC9A-01
WALK-IN REF.
G288
OFFICE
G287A
WOMEN'S
TOILET
G287B
LIFT SHAFT
#C2
KITCHEN
DIETETICS
G252
SUPPLY REF.
G252B
DISH WASHING
MACH.
G249
MECH
G249A
TELECOMM
OPERATORS
G250
TELECOM.
EQUIP. RM
G251A
TELECOMM
EQUIP. RM
G251B
TELECOMM
OPERATORS
G251
CORRIDOR
GC9-01
TOILET
G250A
RESIDENT
OFFICE
G240C
STORAGE
G240B
GTEC OFFICE
G235C
OFFICE
G235D
PHARM
G240
OFFICE
G240A
SVC ELEV. #S2
G016
STORAGE
G240D
VAULT
G240E
TOILET
G242
HAC
G243
CLOSET
STORAGE
G245
PASSENGER
ELEV #1
G013
PASSENGER
ELEV #2
G014
STAIR #6
G006
TRAY PREP
SILVER RAP
DRY STORAGE
G292
MECH
G291B
BREAK RM
G291A
KITCHEN
G291
STORAGE
EQUIP.
G290
STORAGE
GENERAL
G290A
STORAGE
EQUIPMENT
G290B
TOILET
G304
WOMEN'S
TOILET
G303AWOMEN'S
LOCKER
G303
SVC ELEV. #S1
G015
TR
G192
OFFICE
G191
PATIENT HC
TOILET
G190
SECURITY
G1221
SECURITY
G1211
DRESSING
G187C
STORAGE
G187N
READING
G187K
RECEPTION
G186B
CAT SCAN
WAITING
G186
MAIN KITCHEN
G275
OFFICE
G107
CARDIO LAB
G108
TOILET
G109
CHIEF
CARDIOTHORACIC
SURGY.
G110
STAFF
CARDIOLOGIST
G111
EMER EXIT
CORRIDOR
G112
CATH LAB
MGR OFFICE
G113
DIRECTOR OF
NON INVASIVE
LAB
G114
STAFF
CARDIOLOGIST
G115
CHIEF
CARDIOLOGIST
G116 ASSOCIATE
CHIEF
CARDIO-
VASCULAR
G117
CHIEF
CARDIOVASCULAR
MEDICINE
G118
STORAGE
G119
INTERN
G120
ADMINISTRATIVE
OFFICE
G121
CORRIDOR
GC3A-01
ELECT.
G123
ELECT.
G124
CARDIOLOGIST
G125HAC
G126
STORAGE
G104A
CONFERENCE
RM
G104
PRIVACY
RECEPTION
G149
RECEPTION
AREA
G148
WAITING AREA
G167
OFFICE
G150
CARDIO
RESEARCH RM
G168
ELECT.
G169
STAIR #2
G002
STORAGE
G178
RESTROOM
G180
CORRIDOR
GC2A-01
ELECT.
G170
STAFF
G186A
CHIEF
NUCLEAR MED
G183
STAFF
RADIOLOGIST
G182
CORRIDOR
GC1-01
CORRIDOR
GC2-01
ELECT.
G181
HAC
G152
SUPPLY
G151
EXAM/
TREATMENT
RM
G166 PATIENT DOSE
G165
RESTROOM
G164
NUCLEAR MED
OFFICE
G163
G162
ECHO LAB
G176
STRESS LAB
G172
SUPPLIES
G176B
CARDIO ECHO
LAB
G174
WAITING
G171
EKG LAB
G157
EKG CHECK IN
G158
EKG EXAM
G159
TOILET
G175
LAB STORAGE
G161
PATIENT EXAM
G160
READING
CONSULT
G147
IMAGING RM
G146
NM STRESS
LAB
G144
ELECT.
G145
IMAGING RM
G140
RADIO PHARM
G141
CORRIDOR
GC3C-01
EXAM/
TREATMENT
RM
G132
EXAM/
TREATMENT
RM
G133
EXAM/
TREATMENT
RM
G134
RADIO
NUCLEAR
WASTE
STORAGE
G135
RFG STATION
G136
SUPV NM
TECK
G137
CONTROL RM
G138
IMAGING RM
G139
CORRIDOR
GC4-01
TOILET
G127C
TR
G108
109 SF
CARDIO
RESEARCH
CLINIC
G128
CORRIDOR
GC3-01
CORRIDOR
GC3B-01
STAIR #5
G005
HAC
G129
RECEPT
G172
ELECT.
G153
ADMIN
OFFICER
G179
STAFF OFFICE
G154
NEURO
CARDIAC
RESEARCH
PGM
G155
ECHO
READING RM
G156
CARDIARRYTHMIA
EXAM
G131
CARDIOLOGY
G130
STAIR #8
G008
DINING RM
G291
ELEV #5
G018
LOBBY
G298
BATHROOM
G299
STORAGE
WARD
SUPPLIES
G305
PASSENGER
ELEV #3
G012
PASSENGER
ELEV #4
G011
STAIR #3
G003
STAFF OFFICE
G100
FELLOWS
G101
OFFICE
G102
OFFICE
G103
STORAGE
G105
CORRIDOR
GC12-01
LOAD CENTER
G301
CORRIDOR
GC8-01
CORRIDOR
GC7A-01
CHIEF
PHYSICAL
MEDICINE AND
REHAB
G226
OFFICE
DIETITIAN
G289DW3
DW4
VACANT
G272
001TN400Gd
001TN400Gd
001TN400Ge
001TN400Ge
001TN400Ge
001TN400Ge
001TN400Gd
DATA OUTLETS AND DEVICES IN THIS
AREA SHALL BE SERVED FROM
TELECOMMUNICATIONS ROOM G277.
DATA OUTLETS AND DEVICES IN THIS
AREA SHALL BE SERVED FROM
TELECOMMUNICATIONS ROOM G192.
DATA OUTLETS AND DEVICES IN THIS
AREA SHALL BE SERVED FROM
TELECOMMUNICATIONS ROOM G277.
DATA OUTLETS AND DEVICES IN THIS
AREA SHALL BE SERVED FROM
TELECOMMUNICATIONS ROOM G108.
2 2
2 2
2 2
2 2
TYP.
DD3
N2
DD3
N2
DD9
N2
DD4
N2
DD4
N2
DD2
N2
DD3
N2
DD5
N2
DD1
N2
DD2
N2 DD3
N2
DD3
N2
DD3
N2
DD3
N2
DD3
N2
DD3
N2
DD3
N2
DD2
N2
DD4
N2
DD3
N2
DD6
N2
DD3
N2
DD5
N2
DD5
N2
DD3
N2
DD3
N2
DD9
N2
DD5
N2
DD2
N2
DD5
N2
DD5
N2
DD8
N2
DD5
N2
DD5
N2
DD5
N2
DD5
N2DD5
N2
DD3
N2
DD3
N2 DD3
N2
DD3
N2
DD4
N2
DD3
N2
DD4
N2
DD3
N2
DD3
N2
DD3
N2
DD6
N2
DD3
N2
DD6
N2
DD3
N2DD3
N2
DD3
N2
DD3
N2
DD3
N2
DD6
N2
DD1
N2
DD7
N2
DD3
N2
DD4
N2
DD4
N2DD4
N2
DD3
N2
DD3
N2
N2
DD6
N2
DD3
N2
DD3
N2
DD5
N2
DD3
N2
DD3
N2
DD3
N2
DD1
N2
DD3
N2
DD3
N2
DD3
N2
DD3
N2
DD3
N2
DD6
N2
DD3
N2
DD3
N2
DD3
N2
DD3
N2
DD3
N2
DD3
N2
DD3
N2
DD3
N2
DD5
N2
DD2N2
DD2
N2
DD5
N2
DD3
N2
DD3
N2
DD3
DD3
N2
DD5
N2
N2
DD6
N2
DD6
N2
DD3
N2
DD6
N2
DD3
N2
DD3
N2
DD3
N2
DD3
N2
DD3
DD3
N2
DD3
N2
DD7
N2
DD12
N2
N2
DD3
DD1
N2
N2
DD3
N2
DD3
N2
DD3
DD6
N2
DD3
N2
N2
DD3
N2
DD3
N2
DD6
N2
DD6
N2
DD3
N2
DD3
N2
DD3
N2
DD3
N2
DD3
N2
DD3
N2
DD3
N2
DD3
N2
DD3
N2
DD5
N2
DD3
N2
DD3
N2
DD3
N2
DD3
N2
DD3
N2
DD3
N2DD3
N2
DD2
N2
DD1
N2
DD3
N2
DD3
N2
DD3
N2
DD3
N2
DD3
N2
DD5
N2
DD3
N2
DD3
N2
DD3
N2
DD3
N2
DD3
N2
DD3
N11
DD11
N2
DD3
N2
DD3
N2
DD2
N2
DD3
N2
DD12
N2
DD5
N2
DD3
N2
DD3
N2
DD4
N2
DD12
N2
DD3
N2
DD4
N2
DD4
N2
DD4
N2
DD4
N2
DD4
N2
DD4
N2
DD4
N2
DD4
N2
DD4
N2
DD4
N2
DD4 N2
DD4
N2
DD4
N2
DD3
N2
DD3N2
DD3
N2DD3
N2
DD3
N2
DD3
N2
DD3
N2
DD3
N2
DD3
N2
DD3
N2
DD3
N2
DD3
N2
DD3
N2
DD3
N2
DD3
N2
DD3
N2
DD3
B
A
4" SLEEVE AND VERTICAL
LADDER RACK TO 1146
4" SLEEVE AND VERTICAL LADDER RACK
FROM CRAWL SPACE IN LEVEL 0SG
H
H
6-STRAND OM4
TO RM SG141
LOCKER
G192C
46 47 48
001TN400Gc
001TN400Gc
001TN400Gc
001TN400Gc
OFFICE
G192A
B
BLDG 001
AREA SHOWN
Project…
This is the start of the file's text. The full file is on GovTribe.