Attachment 01e - Addendum R1-001TN400Ga_041TN101-Door Schedule-EHRM-689-22-700.pdf
PDF 2 MB Posted
- Attached to
- Z2DA--689-22-700 EHRM IU West Haven VAMC This ONLY for the PCAC VISN 1 Construction MATOC Pool
- Solicitation number
- 36C77626R0106
About this file
This document comprises telecommunications infrastructure plans for a federal construction project involving the upgrade and renovation of facility communications systems.
The plans detail the design and installation requirements for a comprehensive Category 6A (CAT6A) telecommunications cabling upgrade across multiple building spaces. Key requirements include the removal and replacement of all existing Category 6 and below cabling with CAT6A ports and associated infrastructure; installation of wireless access points (WAP) and data racks in designated telecommunications rooms; and the establishment of proper cable management systems including cable trays, conduit runs, and pull boxes per ANSI/TIA-569 standards. The contractor must provide all labor, materials, testing instruments, and consumables necessary for complete installation, termination, testing, labeling, and certification of fully functional Category 6A outlets. Installation specifications require 4-inch square backboxes with conduit extending to accessible ceiling space, J-hooks placed every 48 inches during cable transitions, pull boxes at 100-foot intervals in straight conduit runs or those with bends exceeding 180 degrees, and proper fire-stopping materials to maintain existing fire ratings. Data cabling must be segregated from security, fire alarm, and nurse call systems, with cable trays fitted with dividers where systems share pathways. The plans encompass multiple buildings and floor levels with detailed outlet locations, access control panels, and equipment demolition requirements, with contractors responsible for field verification of existing conditions and documentation of any variances from the provided design.
View the file
Other files
Show all 42
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
C
W
X X
S W
C X
W
S X
K
H
K
H
C
001-G192A
001-G192B
TN503
TN502
DATA RACK,
TYP.
SECONDARY
BONDING BUSBAR
LOCKER
G192C
45 SF
TR
G192
98 SF
2-DOOR
ACCESS
CONTROL
PANEL
OFFICE
G192B
70 SF
A
B
W 1
K
H
3 6
TN501 TYP.
TN501 TYP.
DATA RACK,
TYP.
LOCKER
G192C
45 SF
TR
G192
98 SF
OFFICE
G192B
70 SF
OFFICE
G192A
87 SF
A
B
G192
STORAGE
GENERAL
G192
109 SF
STORAGE
GENERAL
G192B
87 SF
STORAGE
GENERAL
G192A
88 SF
AREA SHOWN
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
7/
/2
2:
:2
AM
Au to de sk
D oc s:
//6
-2
2-
VA
C T
W es t H av en E
H R
M
IU
/V
AW
H _0
1_
EL
_S D
B.
rv t
001TN400Ga
BLDG 001 - LEVEL 0G - ENLARGED
TELECOMMUNICATIONS PLANS
DCW/MMM RTS/JGD
100% CONSTRUCTION
DOCUMENTS
04/20/2026
689-22-700EHRM INFRASTRUCTURE
UPGRADES - WEST HAVEN
VA CT WEST HAVEN
950 CAMPBELL AVENUE, WEST HAVEN, CT 06516
3/8" = 1'-0"001TN100G
1 RM G192 - DEMOLITION FLOOR PLAN
3/8" = 1'-0"001TN100G
2 RM G192 - TELECOMMUNICATIONS PLAN
- NTS
3 NOT USED
3/8" = 1'-0"001TN100G
4 RM G192 - OVERHEAD PLAN
2'0 4' 6'
PROJECT
NORTH
2'0 4' 6'
PROJECT
NORTH
2'0 4' 6'
PROJECT
NORTH
GENERAL NOTES
KEY NOTES
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR CLARITY. CONTRACTOR SHALL
FIELD VERIFY ALL DEVICES AND ASSOCIATED CABLING AS REQUIRED. ALL RACEWAYS
AND CABLING ASSOCIATED WITH EQUIPMENT TO BE DEMOLISHED SHALL BE
DEMOLISHED BACK TO ITS SOURCE, UNLESS OTHERWISE NOTED.
PROTECT ALL EXISTING WORK FROM DAMAGE DURING CONSTRUCTION. ANY
DAMAGED MATERIALS, SYSTEMS, COMPONENTS, AND FINISHES SHALL BE REPAIRED
OR REPLACED AT THE EXPENSE OF THE CONTRACTOR TO THE ACCEPTANCE OF THE
OWNER.
SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE
RATING OR NEW FIRE RATING. COORDINATE WITH ARCHITECTURAL DRAWINGS AS
REQUIRED.
ALL TELECOMMUNICATIONS CABLING CATEGORY 6 AND BELOW SHALL BE REMOVED
AND REPLACED WITH CAT6A PORTS AND CABLE QUANTITIES INDICATED, UNLESS
NOTED OTHERWISE.
TELECOMMUNICATIONS CABLES SHALL BE ROUTED IN EXISTING PATHWAY VACATED
BY EXISTING CABLING AS CONDUIT FILL ALLOWS. PROVIDE ADDITIONAL RACEWAYS
TO EXTEND TO ASSOCIATED TR AS REQUIRED.
TELECOMMUNICATIONS WAO UPGRADE SHALL INCLUDE, BUT IS NOT LIMITED TO
REMOVING AND DISPOSING OF EXISTING CABLING, JACKS AND FACEPLATES AS
REQUIRED; PROVIDING ALL LABOR, MATERIALS, TOOLS, TEST INSTRUMENTS, AND
CONSUMABLES REQUIRED FOR INSTALLATION, TERMINATION, TESTING, LABELING,
AND CERTIFICATION OF A FULLY FUNCTIONAL CATEGORY 6A OUTLET WITH PORT
QUANTITY INDICATED.
WHEN PROVIDING A WAO IN LOCATIONS WHERE AN EXISTING WAO CURRENTLY DOES
NOT EXIST, PROVIDE (1) 4-INCH SQUARE BACKBOX WITH SINGLE-GANG REDUCING
MUD RING AND (1) 1-1/4" CONDUIT EXTENDING FROM BACKBOX TO ACCESSIBLE
CEILING SPACE. ONCE IN ACCESSIBLE CEILING SPACE, CABLING SHALL EXTEND TO
ITS ASSOCIATED TR VIA CABLE TRAY; UTILIZE J-HOOKS EVERY 48 ” WHEN
TRANSITIONING TO OR FROM CABLE TRAY. IF CABLE TRAY IS NON-EXISTENT, EXTEND
HORIZONTAL CABLING FROM WAO TO TR VIA J-HOOKS ONLY.
PROVIDE PULL BOXES SIZED PER ANSI/TIA-569 AT 100-FT INTERVALS IN STRAIGHT
CONDUIT RUNS, OR CONDUIT CONTAINING BENDS TOTALING MORE THAN 180
DEGREES.
PROVIDE CONDUITS AND SLEEVES AS REQUIRED FOR ROUTING AND INSTALLATION
OF HORIZONTAL AND BACKBONE CABLING. PROVIDE FIRE-STOP MATERIALS TO SEAL
IN AND AROUND CONDUIT PER CODE. REFER TO ARCHITECTURAL DRAWINGS FOR
PARTITION TYPES AND WALL HEIGHTS.
OUTLET LOCATIONS ARE APPROXIMATE. DETERMINE EXACT LOCATIONS IN FIELD;
DOCUMENT VARIANCES BASED ON AS-BUILT DRAWINGS. WAO'S INSTALLED ON
OPPOSITE SIDES OF WALLS WILL BE OFFSET 24" CENTER TO CENTER.
ALL DATA CABLING SHALL BE SEGREGATED FROM OTHER SPECIAL SYSTEMS
INCLUDING, BUT NOT LIMITED TO, SECURITY, FIRE ALARM, AND NURSE CALL
SYSTEMS. WHEN ROUTED THROUGH CONDUIT, DATA CABLING SHALL HAVE ITS OWN
RACEWAY. WHEN DATA CABLING IS ROUTED THROUGH A COMMON SPECIAL SYSTEMS
CABLE TRAY, CABLING SHALL BE BUNDLED WITH LIKE SYSTEMS; ADDITIONALLY,
CABLE TRAYS SHALL BE PROVIDED WITH TRAY DIVIDERS AS REQUIRED TO
SEGREGATE SYSTEMS FROM ONE ANOTHER.
FIBER-OPTIC CABLING ROUTES AND ASSOCIATED RACEWAYS/CABLE TRAY ARE
DIAGRAMMATICAL. COORDINATE EXACT ROUTING WITH EXISTING CONDITIONS,
ARCHITECTURAL FEATURES, MECHANICAL DUCTWORK, PIPING, EQUIPMENT, AND ANY
OTHER OBSTRUCTIONS PRIOR TO INSTALLATION.
KEY PLAN
1 EXISTING EQUIPMENT TO BE DEMOLISHED. ASSOCIATED CONDUIT AND WIRE SHALL
BE DEMOLISHED BACK TO SOURCE.
PROVIDE RIGID CONDUIT SLEEVES FOR HORIZONTAL CABLING WITH FIRE PROOFING
AS REQUIRED. SIDE 'A' AND SIDE 'B' SLEEVES SHALL BE SEPARATED BY AT LEAST 10-
FT.
PROVIDE WIRE BASKET CABLE TRAY AS INDICATED.
PROJECT
NORTH
Revisions: Date:
07-28-2026ADDENDUM PRE-BID RFI 1
C
X
X
C
C
N2 N2 N2
N2
N2
N2
X
S
X
S
WAP
WAP
C
W
XX
S W
W
W
W
W
C
X
W S
X
W
X
W
X
S
C W
X
X
S
C
W
W
X X
S
C
270° 270°
270° 270°
270°
270° 270°
W
X C
X S
W
X
X S
X S
TYP.
TN5072
TN507
1 3 4
C
B
A
DATA
CENTER
SF
ENTRANCE
ROOM #1
189 SF
ENTRANCE
ROOM #2
106 SF
MECH
275 SF
ELEC
99 SF
SECURE
STORAGE
116 SF
FIRE RISER
45 SF
CORRIDOR
561 SF
GENERATOR
ENCLOSURE
955 SF
ROOF
ACCESS
44 SF
041-107B
041-107A
DATA RACK, TYP.
041-105B
041-105A
DATA RACK, TYP.
C
C
C
C
C
041-PNL-B
TRANSFORMER "041-TX-PNL-B" (ABOVE)
TRANSFORMER "041-TX-UPS-B" (BELOW)
041-DP-B
041-ATS-B
041-PNL-N
CRAC
CRAC
1.1
A.1
B.1
2.1
TN502
TN502
TRANSFORMER "041-TX-PNL-A" (ABOVE)
TRANSFORMER "041-TX-UPS-A" (BELOW)
041-DP-A
041-ATS-A
041-PNL-E
VEST
66 SF
UNPACKING/
PACKING
43 SF
STORAGE
ELECTRICAL
140A
TREATMENT
ROOM
ANIMAL
ROOM 2
ANTE
ROOM
041-PNL-LS
041-PNL-A2
C
C
041-PNL-A
GENERATOR CONNECTION ENCLOSURE
"041-GCE-E"
MOTOR STARTER
"041-MS-SF"
MOTOR STARTER
"041-MS-EF"
041-PNL-B2
ACCESS
CONTROL PANEL
041-CP-HT
041-PNL-HA
041-MTS
042-PNL-LS
041-042-ATS-LS
041EP201
ATS "3-4-5-ATS-A"
041-ECB-TIE
042-CP-HT
TN504TYP.
TN503 TYP.
ACCESS CONTROL
PANEL, 8-DOOR
FIRE ALARM
CONTROL PANEL
W
C
W
W
AREA SHOWN
BLDG 41
BLDG 42
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
7/
/2
3:
:0
AM
Au to de sk
D oc s:
//6
-2
2-
VA
C T
W es t H av en E
H R
M
IU
/V
AW
H _D
AT
A
C
EN
TE
R
_E L_
SD
B.
rv t
041TN101
BLDG 41 AND 42 - TELECOMMUNICATIONS
PLAN - LEVEL 01
DCW/MMM RTS/JGD
100% CONSTRUCTION
DOCUMENTS
04/20/2026
689-22-700EHRM INFRASTRUCTURE
UPGRADES - WEST HAVEN
VA CT WEST HAVEN
950 CAMPBELL AVENUE, WEST HAVEN, CT 06516
- 3/16" = 1'-0"
1 BLDG 41 AND 42 - TELECOMMUNICATIONS PLAN - LEVEL 01
GENERAL NOTES
KEY PLAN
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR
CLARITY. CONTRACTOR SHALL FIELD VERIFY ALL DEVICES
AND ASSOCIATED CABLING AS REQUIRED. ALL RACEWAYS
AND CABLING ASSOCIATED WITH EQUIPMENT TO BE
DEMOLISHED SHALL BE DEMOLISHED BACK TO ITS SOURCE,
UNLESS OTHERWISE NOTED.
PROTECT ALL EXISTING WORK FROM DAMAGE DURING
CONSTRUCTION. ANY DAMAGED MATERIALS, SYSTEMS,
COMPONENTS, AND FINISHES SHALL BE REPAIRED OR
REPLACED AT THE EXPENSE OF THE CONTRACTOR TO THE
ACCEPTANCE OF THE OWNER.
SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO
MATCH EXISTING FIRE RATING OR NEW FIRE RATING.
COORDINATE WITH ARCHITECTURAL DRAWINGS AS
REQUIRED.
ALL TELECOMMUNICATIONS CABLING CATEGORY 6 AND
BELOW SHALL BE REMOVED AND REPLACED WITH CAT6A
PORTS AND CABLE QUANTITIES INDICATED, UNLESS NOTED
OTHERWISE.
TELECOMMUNICATIONS CABLES SHALL BE ROUTED IN
EXISTING PATHWAY VACATED BY EXISTING CABLING AS
CONDUIT FILL ALLOWS. PROVIDE ADDITIONAL RACEWAYS
TO EXTEND TO ASSOCIATED TR AS REQUIRED.
TELECOMMUNICATIONS WAO UPGRADE SHALL INCLUDE,
BUT IS NOT LIMITED TO REMOVING AND DISPOSING OF
EXISTING CABLING, JACKS AND FACEPLATES AS REQUIRED;
PROVIDING ALL LABOR, MATERIALS, TOOLS, TEST
INSTRUMENTS, AND CONSUMABLES REQUIRED FOR
INSTALLATION, TERMINATION, TESTING, LABELING, AND
CERTIFICATION OF A FULLY FUNCTIONAL CATEGORY 6A
OUTLET WITH PORT QUANTITY INDICATED.
WHEN PROVIDING A WAO IN LOCATIONS WHERE AN
EXISTING WAO CURRENTLY DOES NOT EXIST, PROVIDE (1) 4-
INCH SQUARE BACKBOX WITH SINGLE-GANG REDUCING
MUD RING AND (1) 1-1/4" CONDUIT EXTENDING FROM
BACKBOX TO ACCESSIBLE CEILING SPACE. ONCE IN
ACCESSIBLE CEILING SPACE, CABLING SHALL EXTEND TO
ITS ASSOCIATED TR VIA CABLE TRAY; UTILIZE J-HOOKS
EVERY 48” WHEN TRANSITIONING TO OR FROM CABLE TRAY.
IF CABLE TRAY IS NON-EXISTENT, EXTEND HORIZONTAL
CABLING FROM WAO TO TR VIA J-HOOKS ONLY.
PROVIDE PULL BOXES SIZED PER ANSI/TIA-569 AT 100-FT
INTERVALS IN STRAIGHT CONDUIT RUNS, OR CONDUIT
CONTAINING BENDS TOTALING MORE THAN 180 DEGREES.
PROVIDE CONDUITS AND SLEEVES AS REQUIRED FOR
ROUTING AND INSTALLATION OF HORIZONTAL AND
BACKBONE CABLING. PROVIDE FIRE-STOP MATERIALS TO
SEAL IN AND AROUND CONDUIT PER CODE. REFER TO
ARCHITECTURAL DRAWINGS FOR PARTITION TYPES AND
WALL HEIGHTS.
OUTLET LOCATIONS ARE APPROXIMATE. DETERMINE EXACT
LOCATIONS IN FIELD; DOCUMENT VARIANCES BASED ON AS-
BUILT DRAWINGS. WAO's INSTALLED ON OPPOSITE SIDES
OF WALLS WILL BE OFFSET 24" CENTER TO CENTER.
ALL DATA CABLING SHALL BE SEGREGATED FROM OTHER
SPECIAL SYSTEMS INCLUDING, BUT NOT LIMITED TO,
SECURITY, FIRE ALARM, AND NURSE CALL SYSTEMS. WHEN
ROUTED THROUGH CONDUIT, DATA CABLING SHALL HAVE
ITS OWN RACEWAY. WHEN DATA CABLING IS ROUTED
THROUGH A COMMON SPECIAL SYSTEMS CABLE TRAY,
CABLING SHALL BE BUNDLED WITH LIKE SYSTEMS;
ADDITIONALLY, CABLE TRAYS SHALL BE PROVIDED WITH
TRAY DIVIDERS AS REQUIRED TO SEGREGATE SYSTEMS
FROM ONE ANOTHER.
FIBER-OPTIC CABLING ROUTES AND ASSOCIATED
RACEWAYS/CABLE TRAY ARE DIAGRAMMATICAL.
COORDINATE EXACT ROUTING WITH EXISTING CONDITIONS,
ARCHITECTURAL FEATURES, MECHANICAL DUCTWORK,
PIPING, EQUIPMENT, AND ANY OTHER OBSTRUCTIONS
PRIOR TO INSTALLATION.
THE CONTRACTOR SHALL BID AND INSTALL CAT6A CABLE
WITH AN OD NOT GREATER THAN 0.250 INCH (6.35mm) (4) CAT6A CABLES WITH AN 0.250 INCH (6.35mm) OD OR
SMALLER CAN BE INSTALLED IN A ¾” CONDUIT SUPPORTING
A 40% FILL RATIO.
KEY NOTES
PROJECT
NORTH
4'0 8' 12'
TRUE
NORTH
Revisions: Date:
PROVIDE SIGNAL CABLING AND RACEWAYS EXTENDING
FROM BUILDING 42 DEVICES INCLUDING BUT NOT LIMITED TO
CAMERAS, ACCESS CONTROL PANEL, ETC. TO THE
INDICATED MCR SERVER RACK. COORDINATE WITH VA AS
REQUIRED.
07-28-2026ADDENDUM PRE-BID RFI 1
| 041EP101 |
| 001EP400Ga |
| 041EP702 |
| 001TN400Ga |
| 041TN101 |
File details come from the government source that posted it. Updated .