Attachment 09 - VOL_3b-ARCH-VA_CT_West_Haven_EHRM_IU-689-22-700.pdf
PDF 7 MB Posted
- Attached to
- Z2DA--689-22-700 EHRM IU West Haven VAMC This ONLY for the PCAC VISN 1 Construction MATOC Pool
- Solicitation number
- 36C77626R0106
About this file
These are 100% construction documents for the EHRM Infrastructure Upgrades project at the Department of Veterans Affairs (VA) facility located at 950 Campbell Avenue, West Haven, Connecticut 06516. Project Number 689-22-700 involves improving, reconfiguring, expanding, and renovating existing spaces across 27 applicable buildings to accommodate new telecommunication rooms, a data center, generator enclosure, and fuel yard. The design team includes SPEES DESIGN BUILD (Architectural, Structural, Mechanical, Fire Protection, Plumbing, and Electrical disciplines) located in Kent, Washington, and WSP USA, INC. (Civil discipline) located in Federal Way, Washington. The construction documents are dated April 20, 2026, at 100% completion phase.
The project encompasses multiple building types including healthcare facilities (Buildings 1, 2, 3, 5, 36) and administrative buildings (Buildings 2B, 4, 6, 11, 11A, 12, 12A, 14A, 15, 15A, 16, 16A, 21, 22, 24, 27-34, 35, 35A, 36A, and the new Buildings 41 for the data center and 42 for the generator enclosure and fuel yard). The documents include comprehensive architectural specifications covering door and louver schedules, room finish schedules, wall types, fire protection requirements, Infection Control Risk Assessment (ICRA) standards for construction zones with Class I through IV requirements, signage schedules with tactile and braille specifications, and construction details for doors, frames, walls, windows, roof penetrations, and shade structures. All work must comply with applicable codes including the 2018 International Building Code, NFPA standards, ADA accessibility requirements, VA directives, and federal contracting standards. The contractor is responsible for site verification, high-level workmanship, ICRA barrier installation and maintenance, coordination with existing building systems, material verification prior to purchase, and compliance with all specification requirements before work completion.
View the file
Other files
Show all 42
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
950 CAMPBELL AVENUE, WEST HAVEN, CT 06516-2770
11A
12A
14A
15A
24 27
35A
36A
2B
DATA CENTER
GENERATOR
ENCLOSURE
FUEL YARD
BUILDINGS WITHIN THE SCOPE OF THIS PROJECT
16A
ARCHITECTURAL
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
PHONE: (206) 590-2118
DESIGN TEAM
STRUCTURAL
MECHANICAL
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
PHONE: (206) 590-2118
SIGNATURE LINE
COR
FIRE PROTECTION
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
PHONE: (206) 590-2118
CIVIL
WSP USA, INC.
33301 9TH AVENUE SOUTH
FEDERAL WAY, WA 98003-2600
PHONE: (206) 431-2300
PLUMBING
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
PHONE: (206) 590-2118
ELECTRICAL
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
PHONE: (206) 590-2118
WSP USA, INC.
33301 9TH AVENUE SOUTH
FEDERAL WAY, WA 98003-2600
PHONE: (206) 431-2300
PROJECT INFORMATION
STATE:
COUNTY:
JURISDICTION:
OWNER:
CODE ANALYSIS
PROJECT DESCRIPTION
THE PROPOSED DESIGN SHALL IMPROVE,
RECONFIGURE, EXPAND AND RENOVATE EXISTING
SPACES FOR NEW TELECOMMUNICATION ROOMS,
DATA CENTER, GENERATOR ENCLOSURE, AND
FUEL YARD.
APPLICABLE BUILDING
BUILDING 1, 2, 2B, 3, 4, 5, 6, 11, 11A, 12, 12A,
14A, 15, 15A, 16, 16A, 21, 22, 24, 27-34, 35, 35A, 36, 36A, 41 (DATA CENTER),
42 (GENERATOR ENCLOSURE, FUEL YARD)
ICRA CLASS REQUIREMENTS
REQUIREMENTS DEPENDENT ON
EACH INDIVIDUAL ROOM LOCATION.
CONNECTICUT
NEW HAVEN
WEST HAVEN
DEPARTMENT OF VETERANS
AFFAIRS
BUILDING TYPES
BUILDING 01 - HEALTHCARE
BUILDING 02 - HEALTHCARE
BUILDING 2B - ADMIN
BUILDING 03 - HEALTHCARE
BUILDING 04 - ADMIN
BUILDING 05 - HEALTHCARE
BUILDING 06 - ADMIN
BUILDING 11 - ADMIN
BUILDING 11A - ADMIN
BUILDING 12 - ADMIN
BUILDING 12A - ADMIN
BUILDING 14A - ADMIN
BUILDING 15 - ADMIN
BUILDING 15A - ADMIN
BUILDING 16 - ADMIN
BUILDING 16A - ADMIN
BUILDING 21 - ADMIN
BUILDING 22 - ADMIN
BUILDING 24 - ADMIN
BUILDING 27-34 - ADMIN
BUILDING 35 - ADMIN
BUILDING 35A - ADMIN
BUILDING 36 - HEALTHCARE
BUILDING 36A - ADMIN
41 (DATA CENTER) - ADMIN
42 (GENERATOR ENCLOSURE) - ADMIN
1. COORDINATE WORK WITH ALL CONTRACT DOCUMENTS, INCLUDING BUT NOT LIMITED TO DRAWINGS &
SPECIFICATIONS.
2. SPECIFICATIONS SHALL SUPERSEDE DRAWINGS IN THE CASE OF ANY CONFLICTING INFORMATION.
BRING TO THE AWARENESS OF AND VERIFY WITH VA COR PRIOR TO PROCEEDING.
3. THE CONTRACTOR AND ANY SUB CONTRACTORS SHALL FAMILIARIZE THEMSELVES WITH EXISTING CONDITIONS AND PROJECT REQUIREMENTS PRIOR TO SUBMITTING A BID OR BEGINNING WORK. NO ALLOWANCES WILL BE MADE ON BEHALF OF THE CONTRACTOR OR SUB-CONTRACTORS FOR FAILURE
TO VISIT THE SITE.
4. THE CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS BEFORE BEGINNING WORK. ANY CONFLICTS BETWEEN EXISTING CONDITIONS AND THE CONTRACT DOCUMENTS SHALL BE BROUGHT
IMMEDIATELY TO THE ATTENTION OF THE COR.
5. ALL WORK SHALL BE PERFORMED WITH A HIGH-LEVEL OF WORKMANSHIP.
6. THE CONTRACTOR SHALL VERIFY ALL PRODUCT TYPES AND QUANTITIES DURING SITE
WALKTHROUGH, PRIOR TO PURCHASING ANY MATERIALS, EQUIPMENT, PRODUCTS OR LABOR.
7. THE CONTRACTOR SHALL VERIFY AND COORDINATE WITH ALL INSTALLERS TO ENSURE COMPLIANCE
WITH THE CONTRACT DOCUMENTS.
GENERAL NOTES
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ ENGINEER OF RECORD
A/E:
STAMPCONSULTANT/ DISCIPLINE
321 4 5 6 7 8 9 10
DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
08/05/2026 7:15:41 am
Autodesk Docs://689-22-700 VA CT West Haven EHRM
IU/VAWH_GEN
SHEETS_SDB.rvt
G-001
COVER PAGE
JS/JRS JRS
100% CONSTRUCTION
DOCUMENTS
04/20/2026
689-22-700EHRM INFRASTRUCTURE
UPGRADES - WEST HAVEN
VA CT WEST HAVEN
950 CAMPBELL AVENUE, WEST HAVEN, CT 06516
1" = 30'-0"
LOCATION MAP
PROJECT
NORTH
PROJECT
NORTH
1" = 150'-0"
SITE PLAN
EHRM INFRASTRUCTURE UPGRADES
950 CAMPBELL AVENUE, WEST HAVEN, CT 06516-2770
PROJECT #: 689-22-700
Revisions: Date:
jamesstoddard Text Box
VOLUME 3 - ARCHITECTURAL SHEETS
A.B.
ABA
ABV.
A.C.T.
A.C.M.
A.W.
ADA
ADJ.
A/E A.F.
A.F.F.
AGG.
ALT.
ALUM.
APPROX.
ARCH
ASPH.
A/V
BARR.
BATH
B.B.
BLDG.
BLK.
BLKG.
BLW.
BM.
B.M.T.U.
B.C.
B.O.
B.O.C.
B.O.S.
BRC
BRKT.
BRNG.
BTTM.
BTWN.
CAB.
C.F.C.I
CD
C.J.
CLG.
CLR.
CMU
C.O.
COL.
COMP.
CONC.
CONN.
CONST.
CONT.
CONTR.
COORD.
C.O.R.
CORR.
C.S.
C.T.
CTR.
C.F.V.I
AND
ANGLE
AT
CENTERLINE
DEGREES
NUMBER
ANCHOR BOLT
ARCHITECTURAL BARRIERS ACT
ABOVE
ACOUSTICAL CEILING TILE
ASBESTOS CONTAINING MATERIAL
ACOUSTICAL WALL
AMERICANS W/ DISABILITIES ACT
ADJACENT
ARCHITECT/ENGINEER
ACCESS FLOOR
ABOVE FINISH FLOOR
AGGREGATE
ALTERNATE
ALUMINUM
APPROXIMATELY
ARCHITECT OR ARCHITECTURAL
ASPHALT
AUDIO / VIDEO
BARRIER
BATHROOM
BACKER BOARD
BUILDING
BLOCK
BLOCKING
BELOW
BEAM
BONE MARROW TRANSPLANT UNIT
BOTTOM OF CONCRETE
BOTTOM OF
BOTTOM OF CURB
BOTTOM OF SLAB
BRACE, BRACING
BRACKET
BEARING
BOTTOM
BETWEEN
CABINET
CONTRACTOR FURN. CONTR. INST.
CONSTRUCTION OR CONTRACT DOCUMENTS
CONTROL JOINT
CEILING
CLEAR(ANCE)
CONCRETE MASONRY UNIT
CONTRACTING OFFICER
COLUMN
COMPOSITION
CONCRETE
CONNECTION
CONSTRUCTION
CONTINUOUS
CONTRACTOR
COORDINATE
CONTRACTING OFFICER REPRESENTATIVE
CORRIDOR
CONCRETE SEALER
CERAMIC TILE
CENTER
CONTRACTOR FURN. VA INSTALLED
HDR.
HDWE.
H.M.
HORIZ.
H.P.D.L.
HR
HGHT.
HVAC
ICRA
I.D.
I.L.S.M.
INCL.
INST.
INSUL.
INT.
JNT.
KV
LAM.
LAV.
L.C.M.
LT.
MAT.
MAX.
MDF
MECH
MEP
MFR.
MIN.
MISC.
MOD.
MTL.
N.
N/A
NEG
NO.
NOM
NTS
O.C.
OPNG
OPP
OPT.
OVHD.
PNT.
P.C.
PCRA
PL.
PLAM.
PLWD.
PNL.
PR.
PRFB.
PLSTC.
P.T.
PTN.(S)
PVMT.
QUAL.
QUANT.
HEADER
HARDWARE
HOLLOW METAL
HORIZONTAL
HIGH PRESSURE DECORATIVE LAM
HOUR
HEIGHT
HEATING, VENTILATION & AIR CONDITIONING
INFECTIOUS CONTROL RISK ASSESSMENT
INSIDE DIAMETER
INTERIM LIFE SAFETY MEASURES
INCLUDE OR INCLUDING
INSTALL
INSULATION
INTERIOR
JOINT
KILOVOLT
LAMINATE(D)
LAVATORY
LEAD CONTAINING MATERIAL(S)
LIGHT
MATERIAL OR MATERIALS
MAXIMUM
MEDIUM-DENSITY FIBREBOARD
MECHANIC(AL)
MECHANICAL, ELECTRICAL, PLUMBING
MANUFACTURE OR MANUFACTURER
MINIMUM
MISCELLANEOUS
MODIFIED
METAL
NORTH
NOT APPLICABLE
NEGATIVE
NUMBER
NOMINAL
NOT TO SCALE
ON CENTER(S)
OPENING
OPPOSITE
OPTION OR OPTIONAL
OVERHEAD
PAINT
PRECAST CONCRETE
PRE-CONSTRUCTION RISK ASSESSMENT
PLATE
PLASTIC LAMINATE
PLYWOOD
PANEL
PAIR
PREFABRICATE(D)
PLASTIC
PRESSURE TREATED
PARTITION(S)
PAVEMENT
QUALITY
QUANTITY
RAD.
R.C.P.
REF.
REINF.
REP.
REQ.D.
RESIL.
REV.
R.F.
RF.
RM.
RMV.
R.O.
S.
SCT.
SCHED.
SD
SECT.
S.F.
S.F.R.M.
SHG.
SHT.
SHTH.
SGN.
SIM.
SM.
S.O.W.
SPEC.
SQ.
ST.STL.
ST.
STNDG.
STL.
STOR.
STRUCT.
SUSP.
S.V.
SYS.
TEMP.
T&G
THK.
THRESH.
T.C.
T.O.C.
T.O.S.
T.P.H.
TRANS.
T.S.
TYP.
U.N.O.
VA
VAR.
V.B.
V.F.C.I.
VERT.
V.I.F.
V.F.V.I.
W.
W/
WD.
WIN.
WGHT.
W/O W.R.
RADIUS
REFLECTED CEILING PLAN
REFERENCE
REINFORCE(D,ING)
REPRESENTATIVE
REQUIRED OR REQUIREMENT
RESILIENT
REVERSE
RADIO FREQUENCY
ROOF
ROOM
REMOVE
ROUGH OPENING
SOUTH
SECTION
SCHEDULE
SCHEMATIC DESIGN
SECTION
SQUARE FEET
SPRAY APPLIED FIRE-RESISTIVE MATERIAL
SHINGLES
SHEET
SHEATHING
SIGN
SIMILAR
SEAM
SCOPE OF WORK
SPECIFICATION
SQUARE
STAINLESS STEEL
STAIN
STANDING
STEEL
STORAGE
STRUCTURAL
SUSPENDED
SHEET VINYL
SYSTEM
TEMPORARY
TONGUE AND GROOVE
THICK(NESS)
THRESHOLD
TOP OF CONCRETE
TABLE OF CONTENTS
TOP OF SLAB
TOILET PAPER HOLDER
TRANSITION
TUBE STEEL
TYPICAL
UNLESS NOTED OTHERWISE
VETERANS AFFAIRS
VARIES OR VARIED
VAPOR BARRIER
VA FURNISHED & CONTRACTOR INSTALLED
VERTICAL
VERIFY IN FIELD
VA FURNISHED, VA INSTALLED
WEST
WITH
WOOD
WINDOW
WEIGHT
WITHOUT
WATER RESISTANT
DBL.
D.C.
D.D.
DEMO.
DEPT.
D.G.
DTL.
DIA.
DIM.
DN.
DR.
DTL.
DWG.
E.
EA.
E.J.
ELEC.
ELEV.
ELV.
ENG.
E.O.C.
E.O.P.
EPDM
EQ.
EQUIP.
E.S.
E.T.S.
EXIST.
EXP.
EXT.
F.A.
F.D.
F.E.C.
F.F.
F.F.B.
F.F.L.
FIN.
FLSH.
FLR.
FLRSNT.
FNDN.
F.O.C.
F.O.F.
F.O.S.
F.P.
F.R.
FRM.
FT.
FTG.
FUR.
FURN.
GA.
GALV.
G.E.
G.W.B.
G.C.
G.L.
G.L.B.
G.M.U.
GOVT.
GYP.
DOUBLE
DIRECT CURRENT
DESIGN DEVELOPMENT
DEMOLISH OR DEMOLISION
DEPARTMENT
DESIGN GUIDE
DETAIL
DIAMETER
DIMENSION
DOWN
DOOR
DETAIL
DRAWING(S)
EAST
EACH
EXPANSION JOINT
ELECTRIC OR ELCTRICAL
ELEVATION
ELEVATOR
ENGINEER OR ENGINEERING
EDGE OF CURB
EDGE OF PAVEMENT
ETHYLENE PROPYLENE DIENE TERPOLYMER
EQUAL
EQUIPMENT
EACH SIDE
EXPOSED TO STRUCTURE
EXISTING
EXPANSION
EXTERIOR
FIRE ALARM
FLOOR DRAIN
FIRE EXTINGUISHER OR W/ CABINET
FACTORY FINISH
FINISH FLOOR BREAK
FINISH FLOOR LINE
FINISH OR FINISHED
FLASH OR FLASHING
FLOOR OR FLOORING
FLUORESCENT
FOUNDATION
FACE OF CONCRETE
FACE OF FINISH
FACE OF STUDS
FIRE PROOF
FIRE RATED
FRAME
FOOT OR FEET
FOOTING
FURRING
FURNISHED
GAUGE
GALVANIZED
GENERAL ELECTRIC
GYPSUM WALL BOARD
GENERAL CONTRACTOR
GRID LINE
GLUE LAMINATED BEAM
GLASS MASONRY UNIT
GOVERNMENT
GYPSUM WALL BOARD
A-101 ELEVATION11
SHEET WHERE
SECTION IS TAKEN FROM
ELEVATION NUMBER
A101
A-101
A101
BUILDING SECTION FLAG
BUILDING ELEVATION
SHEET WHERE
SECTION IS TAKEN FROM
ELEVATION NUMBER
SHEET WHERE
SECTION IS TAKEN FROM
SECTION NUMBER
CALLOUT FLAG
DETAIL NUMBER
DETAIL AREA
SHEET ON WHICH
DETAIL APPEARS
A
TRUE
NORTH
PROJECT
NORTH
ROOM
150 SF
AFF
ACT 2' x 4'
9' - 0"
01a
F01
R01
101.1
W01
A5175
IN-03.01-01
GRID LINES
TRUE NORTH ARROW
PROJECT NORTH ARROW
ELEVATION MARKER
ROOM TAG (AREA OPTIONAL)
ROOM NUMBER
ROOM AREA
ROOM NAME
CEILING TAG
CEILING TYPE
CEILING HEIGHT
KEYNOTE
WALL TAG
FLOOR TAG
ROOF TAG
DOOR TAG
WINDOW TAG
EQUIPMENT TAG
SIGNAGE TAG
X X
FEC
XFEC
1 HOUR FIRE BARRIER
2 HOUR FIRE BARRIER
FIRE WALL (2 HOUR MIN.)
SMOKE PARTITION
SMOKE BARRIER
TO DEMOLISH
EXISTING DOOR TO REMAIN
EXISTING DOOR TO DEMOLISH
NEW DOOR
EXISTING WALL TO DEMOLISH
EXISTING WALL TO REMAIN
NEW WALL
FIRE EXTINGUISHER CABINET
EXISTING FIRE EXTINGUISHER CABINET
BATT INSULATION
RIGID INSULATION
GYPSUM BOARD, TYPE X
ACOUSTICAL CEILING TILE, 2' x 2'
CONCRETE
STEEL
PLYWOOD
EARTH
ACOUSTICAL CEILING TILE, 2' x 4'
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ ENGINEER OF RECORD
A/E:
STAMPCONSULTANT/ DISCIPLINE
321 4 5 6 7 8 9 10
DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
08/05/2026 7:15:41 am
Autodesk Docs://689-22-700 VA CT West Haven EHRM
IU/VAWH_GEN
SHEETS_SDB.rvt
A-001
ARCHITECTURAL SYMBOLS & ABBREVIATIONS
JS/JRS JRS
100% CONSTRUCTION
DOCUMENTS
04/20/2026
689-22-700EHRM INFRASTRUCTURE
UPGRADES - WEST HAVEN
VA CT WEST HAVEN
950 CAMPBELL AVENUE, WEST HAVEN, CT 06516
SYMBOLS ABBREVIATIONSARCHITECTURAL SYMBOLS ARCHITECTURAL ABBREVIATIONS
Revisions: Date:
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ ENGINEER OF RECORD
A/E:
STAMPCONSULTANT/ DISCIPLINE
321 4 5 6 7 8 9 10
DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
08/05/2026 7:15:42 am
Autodesk Docs://689-22-700 VA CT West Haven EHRM
IU/VAWH_GEN
SHEETS_SDB.rvt
A-002
APPLICABLE CODES/ STANDARDS,
ARCHITECTURAL GENERAL NOTES
JS/JRS JRS
100% CONSTRUCTION
DOCUMENTS
04/20/2026
689-22-700EHRM INFRASTRUCTURE
UPGRADES - WEST HAVEN
VA CT WEST HAVEN
950 CAMPBELL AVENUE, WEST HAVEN, CT 06516
ARCHITECTURAL GENERAL NOTES
1. ALL WORK DONE BY THE CONTRACTOR OR SUB-CONTRACTORS SHALL BE PERFORMED WITH A HIGH LEVEL OF
WORKMANSHIP.
2. MAINTAIN A SAFE, CLEAN CONSTRUCTION ZONE AT ALL TIMES.
3. DO NOT SCALE DRAWINGS.
4. DIMENSIONS ARE NOT ADJUSTABLE UNLESS NOTED WITH A +/- SYMBOL. ONLY NORMAL INDUSTRY STANDARD
TOLERANCES ARE ACCEPTABLE DEVIATIONS FROM DIMENSIONS INDICATED.
5. ALL DIMENSIONS NOTED AS CLEAR SHALL MAINTAIN THE FULL SPACE INDICATED WITHOUT ENCROACHMENTS.
6. FURNISH ALL MATERIALS & PRODUCTS TO COMPLY WITH THE CONTRACT DOCUMENTS.
7. ALL VERTICAL HEIGHTS INDICATED ARE FROM THE FINISH FLOOR ELEVATION, UON.
8. ANY AND ALL WALL MOUNTED EQUIPMENT SHALL HAVE BLOCKING IN WALL BEHIND, THIS INCLUDES BACKING FOR WALL MOUNTED DOOR STOPS. ENSURE THAT ALL REQUIRED BACKING IS INSTALLED IN WALLS PRIOR TO INSTALLING
DRYWALL.
9. IN TOILET ROOMS PROVIDE STAINLESS STEEL FILLER BEHIND ANY MIRRORS AND OTHER WALL MOUNTED
ACCESSORIES WHEN ITEM IS INSTALLED PARTIALLY OVER CERAMIC TILE.
10. MOVE AND STORE ALL FURNITURE, FIXTURES, AND EQUIPMENT (FFE) AS NEEDED. FFE WILL BE COVERED WITH PLASTIC BEFORE BEING MOVED. FFE WILL BE MOVED BACK TO THE SAME LOCATION IT WAS ORIGINALLY LOCATED WHEN CONTRACTORS WORK IS COMPLETE. IF EQUIPMENT NEEDS TO BE MOVED OUTSIDE THE ROOM IT IS THE CONTRACTOR'S RESPONSIBILITY TO COVER ALL COSTS ASSOCIATED WITH MOVING, STORING, AND REINSTALLING FFE. MOVING, REMOVING ANY RETURN OF FURTNITURE WILL BE THE RESPONSIBILITY OF THE VA.
11. WHEN THE CONTRACTOR MOVES FFE, THE CONTRACTOR IS RESPONSIBLE FOR UNPLUGGING ALL EQUIPMENT FROM WALLS APPROPRIATELY. DURING REINSTALLATION OF FFE, IT IS THE CONTRACTOR'S RESPONSIBILITY TO RECONNECT
POWER PLUGS. THE VA WILL RECONNECT ALL DATA TO THE NEW CAT 6A DATA PORTS.
12. WHILE CONSTRUCTION WORK TAKES PLACE, TEMPORARY SPRINKLERS MUST PROVIDE FULL COVERAGE TO AREAS IMPACTED BY WORK, INCLUDING THE INSTALLATION OF TEMPORARY ICRA BARRIERS. PROPOSED SPRINKLER WORK MUST ALSO BE COORDINATED TO HAPPEN CONCURRENTLY WITH THE REMOVAL OF THE TR CEILING.
TEMPORARY ICRA BARRIERS ARE STILL REQUIRED PER NFPA 241. HOWEVER, THEY ARE NOT REQUIRED TO BE 1HR
RATED SINCE SPRINKLER COVERAGE IS MAINTAINED VIA TEMPORARY SPRINKLERS.
13. REINSTALL CEILING TILES AT THE END OF EVERY WORK SHIFT.
14. IF FLOOR OR RATED WALL PENETRATIONS CANNOT BE FIRESTOPPED AT THE END OF THE WORK SHIFT DUE TO THE NEED TO PULL ADDITIONAL CABLES, TEMPORARY FIRE STOPPING COMPOSED OF MINERAL WOOL SHOULD BE INSTALLED IN THE PENETRATION TO PROVIDE PROTECTION AGAINST FIRE/SMOKE SPREAD THROUGH THE UNSEALED PENETRATION.
15. ANY EXISTING FIRE EXTINGUISHER REPLACED AS PART OF THIS PROJECT WILL BE CLEAN AGENT TYPE EXTINGUISHERS
THAT MATCH OR EXCEED THE EXISTING EXTINGUISHER IN ABC RATING AND SIZE.
16. THE CONTRACTOR SHALL PROVIDE EVIDENCE THAT ALL PRODUCTS INSTALLS OR BROUGHT ONTO THE PREMISIS DO NOT CONTAIN ASBESTOS. AT THE TIME OF SUBMISSION THE CONTRACTOR SHALL PROVIDE A CERTIFIED LETTER FROM
THE PRODUCT MANUFACTURER THAT THE PRODUCTS DO NOT CONTAIN ASBESTOS.
17. CONTRACTOR SHALL PROVIDE PITTSBURG PAINT COLOR SELECTION PER VA SPECIFICATIONS. VENDOR SHALL SUBMIT
SUPPLY MIX FORMULAS.
18. PAINTS SELECTED FOR INTERIOR USE SHALL BE LOW ODOR.
19. EVALUATE EXISTING FLOOR HEIGHTS WHEN EXISTING INTERIOR WALLS ARE REMOVED. ADJACENT ROOMS MAY NOT BE AT THE SAME ELEVATION DUE TO VARIED EXISTING TOPPING SLAB ELEVATIONS. WHEN TOPPING SLAB ELEVATIONS ARE INCONSISTENT, CONTRACTOR TO PROVIDE NEW TOPPING SLAB, RAISING THE LOWER PORTIONS TO MATCH THE HEIGHT OF THE ROOM WITH THE TALLEST TOPPING SLAB. TOPPING SLAB WILL ALSO BE REQURIED IN PLACE OF THE EXISTING WALLS WHERE EXISTING WALLS ARE DEMO'D. ALL NEW / MODIFIED ROOMS WILL EACH BE AT A CONSISTENT
ELEVATION.
20. DURING CONSTRUCTION, ELEVATOR ACCESS WILL BE COORDINATED BETWEEN THE CONTRACTOR AND THE COR.
21. CONTRACTOR TO COORDINATE FINAL LOCATION OF DUMPSTER WITH COR PRIOR TO CONSTRUCTION.
22. CONTRACTOR TO COORDINATE PARKING AND EQUIPMENT STAGING WITH COR PRIOR TO CONSTRUCTION.
23. CONTRACTOR TO COORDINATE BUILDING ACCESS WITH CHIEF ENGINEER, LOCK SHOP, AND OIT.
• AS AN AGENCY OF THE FEDERAL GOVERNMENT, THE VA IS NOT SUBJECT TO LOCAL
IMPOSITIONS OF CODE ENFORCEMENT PROCEDURES ( DRAWING REVIEWS, BUILDING
PERMITS, INSPECTIONS, FEES, ETC). THE VA SHALL FUNCTION AS THE AUTHORITY HAVING
JURISTICTION (AHJ).
• VA DIRECTIVES, DESIGN MANUALS, MASTER SPECIFICATIONS, VA NATIONAL CAD STANDARD
APPLICATION GUIDE AND OTHER GUIDANCE ON THE TECHNICAL INFORMATION LIBRARY (TIL).
• INTERNATIONAL BUILDING CODE (IBC) 2018.
• INTERNATIONAL EXISTING BUILDING CODE (IEBC) 2018.
• NATIONAL FIRE PROTECTION AGENCY (NFPA) 101 LIFE SAFETY CODE. NFPA 101 TAKES
PRECEDENCE OVER IBC.
• NFPA NATIONAL FIRE CODES, WITH THE EXCEPTION OF NFPA 5000 AND NFPA 900.
• OCCUPATIONAL, SAFETY AND HEALTH ADMINISTRATION (OSHA) STANDARDS.
• VA SEISMIC DESIGN REQUIREMENTS, H-18-8.
• NATIONAL ELECTRICAL CODE (NEC)
• INTERNATIONAL PLUMBING CODE (IPC).
• SAFETY CODE FOR ELEVATORS AND ESCALATORS, AMERICAN SOCIETY OF MECHANICAL
ENGINEERS (ASME) A 17.1.
• ASME BOILER AND PRESSURE VESSEL CODE.
• ASME CODE FOR PRESSURE PIPING.
• ARCHITECTURAL BARRIER ACT ACCESSIBILITY STANDARDS (ABAAS), INCLUDING VA
SUPPLEMENT BARRIER FREE DESIGN GUIDE (PG-18-3).
• BUILDING CODE REQUIREMENTS FOR REINFORCED CONCRETE, AMERICAN CONCRETE
INSTITUE AND COMMENTARY (ACI 318).
• MANUAL OF STEEL CONSTRUCTION , LOAD AND RESISTANCE FACTOR DESIGN
SPECIFICATIONS FOR STRUCTURAL STEEL BUILDINGS, AMERICAN INSTITUTE OF STEEL
CONSTRUCTION (AISC).
• ENERGY POLICY ACT OF 2005 (EPACT).
• DOE INTERIM FINAL RULE: ENERGY CONSERVATION STANDARDS FOR NEW FEDERAL,
COMMERCIAL AND MULTI-FAMILY HIGH-RISE RESIDENTIAL BUILDINGS AND NEW LOW-RISE
RESIDENTIAL BUILDINGS, 10 CFR PARTS 433,434 AND 435.
• FEDERAL LEADERSHIP IN HIGH PERFORMANCE AND SUSTAINABLE BUILDINGS: MEMORANDUM
OF UNDERSTANDING (MOU).
• EXECUTIVE ORDER 13423: STRENGTHENING FEDERAL ENVIRONMENTAL, ENERGY AND
TRANSPORTATON MANAGEMENT.
• THE PROVISIONS FOR CONSTRUCTION AND SAFETY SIGNS. STATED IN THE GENERAL
REQUIREMENTS SECTION 01 01 0 OF THE VA MASTER CONSTRUCTION SPECIFICATION.
• VENTILATION FOR ACCEPTABLE INDOOR AIR QUALITY - ASHRAE STANDARD 62.1 - 2004.
• SAFETY STANDARD FOR REFRIDERATION SYSTEMS - ASHRAE STANDARD 15 - 2007.
• VAMC APPROVED HARDWARE LOCKING STANDARDS.
• AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI).
• AMERICAN SOCIETY FOR TESTING MATERIALS (ASTM).
• FEDERAL COMMUNICATIONS COMMISSION (FCC), ALL REGULATIONS, PROCEDURES AND
STANDARDS FOR TWO-WAY RADIO EQUIPMENT, SYSTEMS AND OPERATION.
• ILLUMINATING ENGINEERING SOCIETY OF NORTH AMERICA (IESNA).
• INSTITUTE OF ELECTRICAL AND ELECTRONIC ENGINEERS (IEEE).
• INTERNATIONAL ORGANIZATION FOR STANDARDIZATION (ISO), STANDARDS FOR PROTOCOLS
AND INTERFACES THAT INCLUDE OPEN SYSTEM INTERCONNECTIONS (OSI).
• JOINT COMMISSION ON ACCREDITATION OF HEALTHCARE ORGANIZATIONS (JACHO),
ENVIRONMENT OF CARE GUIDELINES AND STANDARDS.
• FACILITIES GUIDELINES INSTITUTE (FGI): 2010 , OR MOST CURRENT ISSUE, GUIDELINES FOR
THE DESIGN AND CONSTRUCTION OF HEALTH CARE FACILITIES.
• THE AMERICAN INSTITUTE OF ARCHITECTS (AIA) AND NATIONAL SOCIETY OF PROFESSIONAL
ENGINEERS(NSPE) RECENT ADDITIONS TO THEIR PROFESSIONAL CODES OF ETHICS
ENCOURAGING “ENVIRONMENTALLY RESPONSIBLE DESIGN”.
APPLICABLE CODES
APPLICABLE VA OR GOVT. PUBLICATIONS & STANDARDS
EXISTING SUSPENDED
CEILING TO REMAIN ON
CORRIDOR SIDE
EXISTING
WALLS TO
REMAIN
EXISTING
WALLS TO
REMAIN
EXISTING DOOR BEHIND
VISQUEEN BARRIER
NON-SKID PLATE JACK
SCREWED FROM END OF
POLE TO TOP OF CEILING,
TYPICAL
FIRE RESISTANT PLASTIC
DUST BARRIER
SURROUNDING DOOR,
TYPICAL
EXTENSION POLES, TYPICAL
NON-SKID PLATE JACK
SCREWED FROM END OF
POLE TO BOTTOM OF
FLOOR, TYPICAL
BOTTOM OF CEILING
ZIPPER OPENING, TYPICAL
STICKY TACKY MATT
INFRONT OF VISQUEEN
BARRIER
TAPE TOP OF
CONSTRUCTION BARRIER
TO BOTTOM OF CEILING
CONSTRUCTION BARRIER
SURROUNDING EXIST
DOOR, TYPICAL
TAPE BOTTOM OF
CONSTRUCTION BARRIER TO
FLOOR SURFACE, TYPICAL
TACKY MATT IN FRONT OF FIRE
RESISTANT PLASTIC BARRIER,
TYPICAL
NEGATIVE AIR MACHINE,
TYPICAL (INSTALL AT ICRA
BARRIER IF EXTERIOR
WINDOW IS NOTAVAILABLE).
TEMPORARY FIRE
RATED DOOR, TYPICAL
INSIDE OF
WORK AREA
OUTSIDE OF
WORK AREA
INSIDE OF
WORK AREA
OUTSIDE OF
WORK AREA
INSIDE OF
WORK AREA
OUTSIDE OF
WORK AREA
TYPE B
TYPE A
TYPE C
PATCH, REPAIR & PAINT WALLS & FLOORS TO
MATCH EXIST. FINISHES WHERE ICRA BARRIERS
ARE CONSTRUCTED & REMOVED.
PATCH & REPAIR CEILINGS TO MATCH EXIST.
FINISHES WHERE ICRA BARRIERS ARE
CONSTRUCTED & REMOVED.
INSIDE OF
WORK AREA
OUTSIDE OF
WORK AREA
TYPE B
PATCH, REPAIR & PAINT WALLS & FLOORS TO
MATCH EXIST. FINISHES WHERE ICRA BARRIERS
ARE CONSTRUCTED & REMOVED.
INSIDE OF
WORK AREA
OUTSIDE OF
WORK AREA
TYPE A
PATCH, REPAIR & PAINT WALLS & FLOORS TO
MATCH EXIST. FINISHES WHERE ICRA BARRIERS
ARE CONSTRUCTED & REMOVED.
PATCH & REPAIR CEILINGS TO MATCH EXIST.
FINISHES WHERE ICRA BARRIERS ARE
CONSTRUCTED & REMOVED.
ANTE
ROOM
INSIDE OF
WORK AREA
OUTSIDE OF
WORK AREA
TYPE B
TYPE A
INSIDE OF
WORK AREA
OUTSIDE OF
WORK AREA
ANTE
ROOM
PATCH, REPAIR & PAINT WALLS & FLOORS TO
MATCH EXIST. FINISHES WHERE ICRA BARRIERS
ARE CONSTRUCTED & REMOVED.
PATCH & REPAIR CEILINGS TO MATCH EXIST.
FINISHES WHERE ICRA BARRIERS ARE
CONSTRUCTED & REMOVED.
( + ) PRESSURE
CONSTRUCTION ZONE, ( - - ) PRESSURE
ANTE ROOM, ( - ) PRESSURE
TEMPORARY ICRA BARRIER
TEMPORARY ICRA DOOR
CONSTRUCTION TACKY MATT
NEGATIVE AIR MACHINE
1. PROJECT SHALL CONFORM TO CLASS I, II, III & IV ICRA
LEVEL OF INFECTION CONTROL BY PRECAUTION PER
ICRA-(VHA 2-23-1.0- TABLE 4 LEVEL ICRA & CONTROL
PRECAUTIONS & TABLE 5 REQ. ICRA BY LEVEL OF
PRECAUTIONS), OR AS DIRECTED BY THE VA.
2. CONTRACTOR IS RESPONSIBLE FOR COMPLYING WITH
ALL REQUIREMENTS LISTED IN THE INFECTION CONTROL
SECTION OF SPECIFICATION 01 35 26 - SAFETY
REQUIREMENTS.
3. CONTRACTOR IS RESPONSIBLE FOR MAINTAINING ALL
ICRA REQUIREMENTS. AT ANY TIME, THE VA's COR MAY
HALT WORK UNTIL ALL REQUIREMENTS ARE COMPLIANT.
4. CONTRACTOR IS TO REMOVE OR ISOLATE EXIST. HVAC
SYSTEMS WITHIN CONSTRUCTION AREA TO PREVENT
DUST CONTAMINATION.
5. CONTRACTOR IS TO CONTAIN ALL CONSTRUCTION WASTE
BEFORE TRANSPORT IN TIGHTLY COVERED CONTAINERS.
WHEN POSSIBLE, REMOVE CONSTRUCTION DEBRIS WHEN
AREA IS IN ACTIVE ISOLATION. CONTRACTOR IS
RESPONSIBLE FOR THE REMEDIATION OF ANY
HAZARDOUS MATERIALS IN ACCORD WITH VA, LOCAL,
STATE OR FEDERAL TRANSPORT & DISPOSAL
REQUIREMENTS.
6. CONSTRUCTION ZONE ENTRANCES & EXITS SHALL BE
LOCKED AT ALL TIMES, UNLESS IN USE BY THE
CONTRACTOR. WHEN IN USE, ACCESS WILL BE
CONTROLLED & MONITORED BY THE CONTRACTOR.
7. ADHESIVE WALK-OFF CONSTRUCTION MATS ARE TO BE
USED AT ALL CONSTRUCTION ZONES & ANTE ROOM
ENTRANCES & EXITS.
8. TEMPORARY BARRIERS & DOORS MAY ONLY BE
DEMOLISHED ONCE GIVEN FINAL APPROVAL BY THE VA's
COR.
9. SEAL OFF ANY EXIST., UNUSED DOORS WITH TAPE
DURING CONSTRUCTION, TYP.
10. DURING WORK IN AREAS DISTURBED BY CONSTRUCTION,
CLASS I, II, III, & IV ICRA BARRIERS ARE TO CONFORM TO
THE REQUIREMENTS OF THE PROJECT SPECIFICATIONS &
THE ICRA-(VHA 2023-1.0- TABLE 5- REQUIRED INFECTION
PREVENTION & CONTROL MEASURES, BY LEVEL OF
PRECAUTIONS.)- SEE SHEET AS102.
11. PRIOR TO, & IN ORDER TO SATISFY COMPLETION OF
WORK, ANY SPACE DESIGNATED WITH A CLASS I, II, III, &
IV ICRA BARRIER, ON THESE DOCUMENTS OR AS
DIRECTED BY THE VA, IS TO CONFORM TO THE
REQUIREMENTS OF THE PROJECT SPECIFICATIONS & THE
ICRA-(VHA 2023-1.0- TABLE 6- MIN. INFECTION PREVENTION
& CONTROL MEASURES REQUIRED UPON COMPLETION) &
ICRA-(VHA 2023-1.0- INFECTION PREVENTION & CONTROL
CONSTRUCTION/ RENOVATION/ MAINTENANCE PERMIT-
SEE SHEET AS102.
INSTALL TEMPORARY 1 HR CONSTRUCTION ICRA BARRIER
TO SEPARATE CONSTRUCTION AREA FROM OCCUPIED
SPACE.
INSTALL TEMPORARY POLY. FIRE RESISTANT, DUST
BARRIER. MAY ONLY BE DURING NON FUNCTIONAL
MEDICAL CENTER HOURS.
INSTALL FIRE RESISTANT TEMPORARY DOOR AT OPENING
& MATCH RATING OF ICRA BARRIER, TYP.
PLACE TACKY CONSTRUCTION WALK-OFF MATS AT
ENTRANCE & EXIT SIDE OF CONSTRUCTION ACTIVITY
AREAS, TYPICAL.
FOR CLASS III, NEGATIVE PRESSURE AIR MACHINE IS REQ.
& SHALL BE LOCATED EITHER AT THE ICRA BARRIER OR
AT AN EXTERIOR WINDOW. COORDINATE WITH VA
INFECTIOUS PREVENTION TEAM & THE VA's COR.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ ENGINEER OF RECORD
A/E:
STAMPCONSULTANT/ DISCIPLINE
321 4 5 6 7 8 9 10
DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
08/05/2026 7:15:43 am
Autodesk Docs://689-22-700 VA CT West Haven EHRM
IU/VAWH_GEN
SHEETS_SDB.rvt
AS101
ICRA DETAILS
JS/JRS ME
100% CONSTRUCTION
DOCUMENTS
04/20/2026
689-22-700EHRM INFRASTRUCTURE
UPGRADES - WEST HAVEN
VA CT WEST HAVEN
950 CAMPBELL AVENUE, WEST HAVEN, CT 06516
1/2" = 1'-0"
ICRA CLASS I DETAIL
1/2" = 1'-0"
ICRA CLASS II DETAIL
1/2" = 1'-0"
ICRA CLASS III DETAIL
1/2" = 1'-0"
TYPICAL ICRA CLASS II BARRIER - PLAN VIEW
1/2" = 1'-0"
TYPICAL ICRA CLASS III BARRIER - PLAN VIEW
1/2" = 1'-0"
TYPICAL ICRA CLASS IV BARRIER - PLAN VIEW
ICRA DETAILS KEY
ICRA GENERAL NOTES
ICRA DETAIL KEY NOTES
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ ENGINEER OF RECORD
A/E:
STAMPCONSULTANT/ DISCIPLINE
321 4 5 6 7 8 9 10
DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
08/05/2026 7:15:52 am
Autodesk Docs://689-22-700 VA CT West Haven EHRM
IU/VAWH_GEN
SHEETS_SDB.rvt
AS102
ICRA STANDARDS
JS/JRS ME
100% CONSTRUCTION
DOCUMENTS
04/20/2026
689-22-700EHRM INFRASTRUCTURE
UPGRADES - WEST HAVEN
VA CT WEST HAVEN
950 CAMPBELL AVENUE, WEST HAVEN, CT 06516
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ ENGINEER OF RECORD
A/E:
STAMPCONSULTANT/ DISCIPLINE
321 4 5 6 7 8 9 10
DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
08/05/2026 7:14:44 am
Autodesk Docs://689-22-700 VA CT West Haven EHRM
IU/VAWH_GEN
SHEETS_SDB.rvt
A-601
DOOR SCHEDULE & LOUVER SCHEDULE
JS/JRS JRS/RB
100% CONSTRUCTION
DOCUMENTS
04/20/2026
689-22-700EHRM INFRASTRUCTURE
UPGRADES - WEST HAVEN
VA CT WEST HAVEN
950 CAMPBELL AVENUE, WEST HAVEN, CT 06516
DOOR SCHEDULE - DATA CENTER
BLDG # LEVEL DOOR NUMBER
DOOR SIZE
Door Type HW
DOOR DOOR FRAME
FIRE RATING COMMENTSWIDTH HT. THK MAT FIN MAT FIN
041 LEVEL 01 104a 6' - 0" 8' - 0" 0' - 1 3/4" 5A 3E HM PAINT HM* PAINT - -
041 LEVEL 01 104b 6' - 0" 8' - 0" 0' - 1 3/4" 4A 3E HM PAINT HM* PAINT 45 MIN -
041 LEVEL 01 105 3' - 0" 8' - 0" 0' - 1 3/4" 2A SH-3D WOOD STAIN HM PAINT - -
041 LEVEL 01 106 3' - 0" 8' - 0" 0' - 1 3/4" 2A SH-3D WOOD STAIN HM PAINT 45 MIN -
041 LEVEL 01 107 3' - 0" 8' - 0" 0' - 1 3/4" 2A SH-3D WOOD STAIN HM PAINT - -
041 LEVEL 01 108 6' - 0" 8' - 0" 0' - 1 3/4" 4A 3E WOOD STAIN HM PAINT - -
041 LEVEL 01 109 2' - 10" 8' - 0" 0' - 1 3/4" 2A SH-3D WOOD STAIN HM PAINT 45 MIN -
041 LEVEL 01 110 3' - 0" 8' - 0" 0' - 1 3/4" 2A SH-3D WOOD STAIN HM PAINT 45 MIN -
041 LEVEL 01 111 3' - 0" 8' - 0" 0' - 1 3/4" 2A SH-3D WOOD STAIN HM PAINT - -
041 LEVEL 01 113 3' - 8" 7' - 0" 0' - 1 3/4" 2A SH-3D HM PAINT HM* PAINT 45 MIN -
041 LEVEL 01 114a 6' - 0" 8' - 0" 0' - 1 3/4" 4A 3E HM PAINT HM* PAINT 45 MIN BLAST RATED
041 LEVEL 01 114b 6' - 0" 8' - 0" 0' - 1 3/4" 4A 3E HM PAINT HM* PAINT 45 MIN BLAST RATED
042 LEVEL 01 121a 8' - 0" 8' - 0" 0' - 1 3/4" 5A 3E HM PAINT HM* PAINT 3 HR BLAST RATED
042 LEVEL 01 121b 6' - 0" 8' - 0" 0' - 1 3/4" 5A 3E HM PAINT HM* PAINT 3 HR BLAST RATED
042 LEVEL 01 122 8' - 0" 8' - 0" 0' - 1 3/4" 5A 3E HM PAINT HM* PAINT 3 HR BLAST RATED
LOUVER SCHEDULE
BLDG # LEVEL
LOUVER
NUMBER WIDTH HEIGHT
SILL
HEIGHT QUANTITY
042 LEVEL 01 L-01 8' - 0" 4' - 0" 1
042 LEVEL 01 L-02 8' - 0" 4' - 0" 1
DOOR SCHEDULE
BLDG # LEVEL DOOR NUMBER
DOOR SIZE DOOR
TYPE HW
DOOR DOOR FRAME
FIRE RATING CommentsWIDTH HT. THK MAT FIN MAT FIN
001 LEVEL 0SG SG171 3' - 0" 8' - 0" 0' - 1 3/4" 2A SH-3D WOOD STAIN HM PAINT - -
001 LEVEL 0SG SG105B 3' - 0" 7' - 0" 0' - 1 3/4" 2A SH-3D WOOD STAIN HM PAINT - -
001 LEVEL 0SG SG170A 3' - 0" 7' - 0" 0' - 1 3/4" 1A SH-3D WOOD STAIN HM PAINT - -
001 LEVEL 0G G277 3' - 0" 7' - 0" 0' - 1 3/4" 2A SH-3D WOOD STAIN HM PAINT - -
001 LEVEL 0G G192A 3' - 0" 7' - 0" 0' - 1 3/4" 1A SH-3D WOOD STAIN HM PAINT - -
001 LEVEL 0G G192C 3' - 0" 7' - 0" 0' - 1 3/4" 1A SH-3D WOOD STAIN HM PAINT - -
001 LEVEL 0G G192 3' - 0" 7' - 0" 0' - 1 3/4" 2A SH-3D WOOD STAIN HM PAINT - -
001 LEVEL 0G G108 3' - 0" 7' - 0" 0' - 1 3/4" 2A SH-3D WOOD STAIN HM PAINT - -
001 LEVEL 0G G192B 3' - 0" 7' - 0" 0' - 1 3/4" 3A 3A WOOD STAIN HM PAINT - -
001 LEVEL 01 1190 3' - 0" 7' - 0" 0' - 1 3/4" 2A SH-3D WOOD STAIN HM PAINT -
001 LEVEL 02 2151 3' - 0" 7' - 0" 0' - 1 3/4" 2A SH-3D WOOD STAIN HM PAINT - -
001 LEVEL 03 3154 3' - 0" 7' - 0" 0' - 1 3/4" 2A SH-3D WOOD STAIN HM PAINT - -
001 LEVEL 04 4259A 3' - 0" 8' - 0" 0' - 1 3/4" 2A SH-3D WOOD STAIN HM PAINT - -
001 LEVEL 05 5195 3' - 0" 8' - 0" 0' - 1 3/4" 2A SH-3D WOOD STAIN HM PAINT - -
001 LEVEL 06 6204 3' - 0" 8' - 0" 0' - 1 3/4" 2A SH-3D WOOD STAIN HM PAINT - -
001 LEVEL 07 7204 3' - 0" 8' - 0" 0' - 1 3/4" 2A SH-3D WOOD STAIN HM PAINT - -
001 LEVEL 08 8139 3' - 0" 7' - 0" 0' - 1 3/4" 2A SH-3D WOOD STAIN HM PAINT - -
001 LEVEL 09 9122A 3' - 0" 8' - 0" 0' - 1 3/4" 2A SH-3D WOOD STAIN HM PAINT - -
001 LEVEL 09 9122B 2' - 6" 7' - 0" 0' - 1 3/4" 1A SH-3D WOOD STAIN HM PAINT -
002 LEVEL 0G G132 6' - 0" 7' - 0" 0' - 1 3/4" 4A 3E WOOD STAIN HM PAINT - -
002 LEVEL 0G G132A 3' - 0" 7' - 0" 0' - 1 3/4" 2A SH-3D WOOD STAIN HM PAINT - -
002 LEVEL 0G G143C 3' - 0" 7' - 0" 0' - 1 3/4" 2A SH-3D WOOD STAIN HM PAINT - -
002 LEVEL 01 1303B 3' - 0" 7' - 0" 0' - 1 3/4" 2A SH-3D WOOD STAIN HM PAINT - -
002 LEVEL 01 1279A 3' - 0" 8' - 0" 0' - 1 3/4" 2A SH-3D WOOD STAIN HM PAINT - -
002 LEVEL 01 1238 3' - 0" 7' - 0" 0' - 1 3/4" 1A SH-3D WOOD STAIN HM PAINT - -
002 LEVEL 01 1239 3' - 0" 8' - 0" 0' - 1 3/4" 2A SH-3D WOOD STAIN HM PAINT - -
002 LEVEL 02 2107D 3' - 0" 7' - 0" 0' - 1 3/4" 2A SH-3D WOOD STAIN HM PAINT - -
002 LEVEL 02 2107E 3' - 0" 7' - 0" 0' - 1 3/4" 1A SH-3D WOOD STAIN HM PAINT - -
002 LEVEL 02 2228 3' - 0" 7' - 0" 0' - 1 3/4" 2A SH-3D WOOD STAIN HM PAINT - -
002 LEVEL 03 3222 3' - 0" 7' - 0" 0' - 1 3/4" 2A SH-3D WOOD STAIN HM PAINT - -
002 LEVEL 04 4222 3' - 0" 7' - 0" 0' - 1 3/4" 2A SH-3D WOOD STAIN HM PAINT - -
002 LEVEL 05 5222 3' - 0" 7' - 0" 0' - 1 3/4" 2A SH-3D WOOD STAIN HM PAINT - -
002 LEVEL 06 6209 3' - 0" 7' - 0" 0' - 1 3/4" 2A SH-3D WOOD STAIN HM PAINT - -
002 LEVEL 07 7205 3' - 0" 7' - 0" 0' - 1 3/4" 2A SH-3D WOOD STAIN HM PAINT - -
002 LEVEL 08 8141 3' - 0" 7' - 0" 0' - 1 3/4" 2A SH-3D WOOD STAIN HM PAINT - -
003 LEVEL 01 105A 3' - 0" 7' - 0" 0' - 1 3/4" 2A SH-3D WOOD STAIN HM PAINT - -
003 LEVEL 02 206 3' - 0" 8' - 0" 0' - 1 3/4" 2A SH-3D WOOD STAIN HM PAINT - -
004 LEVEL 01 110 3' - 0" 7' - 0" 0' - 1 3/4" 2A SH-3D WOOD STAIN HM PAINT - -
004 LEVEL 02 210A 3' - 0" 7' - 0" 0' - 1 3/4" 2A SH-3D WOOD STAIN HM PAINT - -
005 LEVEL 01 C-103 3' - 0" 7' - 0" 0' - 1 3/4" 2A SH-3D WOOD STAIN HM PAINT - -
005 LEVEL 02 C-244 3' - 0" 7' - 0" 0' - 1 3/4" 2A SH-3D WOOD STAIN HM PAINT - -
005 LEVEL 03 C-314 3' - 0" 8' - 0" 0' - 1 3/4" 2A SH-3D WOOD STAIN HM PAINT - -
006 LEVEL 01 128 3' - 0" 8' - 0" 0' - 1 3/4" 2A SH-3D WOOD STAIN HM PAINT - -
006 LEVEL 02 222 3' - 0" 8' - 0" 0' - 1 3/4" 2A SH-3D WOOD STAIN HM PAINT - -
006 LEVEL 02 223 3' - 0" 7' - 0" 0' - 1 3/4" 1A SH-3D WOOD STAIN HM PAINT - -
011A LEVEL 01 113 3' - 0" 7' - 0" 0' - 1 3/4" 2A SH-3D WOOD STAIN HM PAINT - -
014A LEVEL 01 102 3' - 0" 7' - 0" 0' - 1 3/4" 2A SH-3D WOOD STAIN HM PAINT - -
015 LEVEL 01 128 3' - 0" 8' - 0" 0' - 1 3/4" 2A SH-3D WOOD STAIN HM PAINT - -
015A LEVEL 01 112 3' - 0" 7' - 0" 0' - 1 3/4" 2A SH-3D WOOD STAIN HM PAINT - -
024 LEVEL 01 A-1A 3' - 0" 8' - 0" 0' - 1 3/4" 2A SH-3D WOOD STAIN HM PAINT - -
027-034 LEVEL 01 159 3' - 0" 8' - 0" 0' - 1 3/4" 2A SH-3D WOOD STAIN HM PAINT - -
035 LEVEL 00 B18 3' - 0" 7' - 0" 0' - 1 3/4" 2A SH-3D WOOD STAIN HM PAINT - -
035 LEVEL 01 115 3' - 0" 7' - 0" 0' - 1 3/4" 2A SH-3D WOOD STAIN HM PAINT - -
035A LEVEL 01 124A 3' - 0" 7' - 0" 0' - 1 3/4" 2A SH-3D WOOD STAIN HM PAINT - -
035A LEVEL 02 225A 3' - 0" 7' - 0" 0' - 1 3/4" 2A SH-3D WOOD STAIN HM PAINT - -
036 LEVEL 01 105 3' - 0" 8' - 0" 0' - 1 3/4" 2A SH-3D WOOD STAIN HM PAINT - -
036A LEVEL 01 114 3' - 0" 7' - 0" 0' - 1 3/4" 2A SH-3D WOOD STAIN HM PAINT -
* ALL EXTERIOR ENTRY DOORS AND FRAMES SHALL BE A MINIMUM OF 14GA HOLLOW METAL.
GENERAL NOTES:
- ALL FIRE RATED DOORS SHALL BE FINISHED TO MATCH EXISTING FACILITY STANDARDS AND CONFIRMED WITH COR PRIOR TO INSTALLATION.
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ ENGINEER OF RECORD
A/E:
STAMPCONSULTANT/ DISCIPLINE
321 4 5 6 7 8 9 10
DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
08/05/2026 7:14:47 am
Autodesk Docs://689-22-700 VA CT West Haven EHRM
IU/VAWH_GEN
SHEETS_SDB.rvt
A-601a
ROOM FINISH SCHEDULES
JS/JRS JRS/RB
100% CONSTRUCTION
DOCUMENTS
04/20/2026
689-22-700EHRM INFRASTRUCTURE
UPGRADES - WEST HAVEN
VA CT WEST HAVEN
950 CAMPBELL AVENUE, WEST HAVEN, CT 06516
ROOM FINISH SCHEDULE ABBREVIATIONS
AST
EXP
GWB
RB-01
TME
EXT
PAINT CODES
ANTI-STATIC COATING
EXPOSED
GYPSUM WALL BOARD
RUBBER BASE
TO MATCH EXISTING
EXTERIOR
ROOM FINISH SCHEDULE
BLDG # LEVEL ROOM NO. ROOM NAME
FLOOR BASE WALLS
CLG COMMENTSMAT FIN MAT HT
NORTH EAST SOUTH WEST
MAT FIN MAT FIN MAT FIN MAT FIN
001 LEVEL 0SG SG105 ADP - - TME TME - - - - GWB P-01 - - -
001 LEVEL 0SG SG105A VESTIBULE - - TME TME - - GWB P-01 - - - - -
001 LEVEL 0SG SG171 TR EXP AST RB-01 4" - P-00 - P-02 GWB P-00 - P-02 - P-00 - P-02 GWB P-00 - P-02 EXP
001 LEVEL 0SG SG172 OFFICE - - TME TME - - - - - - GWB P-01 -
001 LEVEL 0SG SGC1-01 CORRIDOR - - EXST EXST - P-01 - - - - - - -
001 LEVEL 0SG SGC4-01 CORRIDOR - - EXST EXST - P-01 - - - - - - -
001 LEVEL 0SG SG105B TR EXP AST RB-01 4" GWB P-02 - P-00 - P-02 - P-00 - P-02 GWB P-00 - P-02 EXP
001 LEVEL 0SG SG170 OFFICE - - TME TME - - GWB P-01 - - GWB P-01 -
001 LEVEL 0SG SG170A OFFICE - - TME TME - - GWB P-01 - P-01 - - -
001 LEVEL 0G G108 TR EXP AST RB-01 6" - P-00 - P-02 - P-00 - P-02 - P-00 - P-02 - P-00 - P-02 EXP
001 LEVEL 0G G191 OFFICE - - TME TME - - - - - - GWB P-01 -
001 LEVEL 0G G192 TR EXP AST RB-01 4" - P-02 GWB P-00 - P-02 GWB P-00 - P-02 - P-00 - P-02 EXP
001 LEVEL 0G G192A OFFICE - - TME TME - P-01 GWB P-01 GWB P-01 GWB P-01 TME
001 LEVEL 0G G192B OFFICE - - TME TME GWB P-01 - - - - GWB P-01 TME
001 LEVEL 0G G192C LOCKER - - TME TME GWB P-01 GWB P-01 - - - - -
001 LEVEL 0G G275 MAIN KITCHEN - - TME TME - - - - - - GWB P-01 -
001 LEVEL 0G G277 TR EXP AST RB-01 6" - P-00 - P-02 GWB P-00 - P-02 GWB P-02 - P-00 - P-02 EXP
001 LEVEL 0G GC1-01 CORRIDOR - - EXST EXST - - - - - P-01 - - -
001 LEVEL 0G GC3-01 CORRIDOR - - EXST EXST - P-01 - - - - - - -
001 LEVEL 01 1C1-01 CORRIDOR - - EXST EXST - P-01 - - - - - - -
001 LEVEL 01 1190 TR EXP AST RB-01 4" - P-00 - P-02 - P-00 - P-02 - P-02 - P-00 - P-02 EXP
001 LEVEL 02 2C1-01 CORRIDOR - - TME TME - - - - GWB P-01 - - -
001 LEVEL 02 2150 ANEST ON-CALL - - TME TME - - - - - - GWB P-01 -
001 LEVEL 02 2151 TR EXP AST RB-01 4" GWB P-00 - P-02 GWB P-00 - P-02 - P-02 - P-00 - P-02 EXP
001 LEVEL 03 3C1-01 CORRIDOR - - EXST EXST - - - - - P-01 - - -
001 LEVEL 03 3153 HEAD NURSE - - TME TME - - - - - - GWB P-01 -
001 LEVEL 03 3154 TR EXP AST RB-01 4" - P-00 - P-02 GWB P-00 - P-02 - P-02 - P-00 - P-02 EXP
001 LEVEL 04 4C6-01 CORRIDOR - - EXST EXST - P-01 - - - - - - -
001 LEVEL 04 4259 NURSE LOUNGE - - TME TME - - GWB P-01 GWB P-01 - - -
001 LEVEL 04 4259A TR EXP AST RB-01 4" GWB P-00 - P-02 - P-00 - P-02 - P-02 GWB P-00 - P-02 EXP
001 LEVEL 05 5C6-01 CORRIDOR - - TME TME GWB P-01 - - - - - P-01 -
001 LEVEL 05 5193 CYLINDER STORAGE - - TME TME GWB P-01 GWB P-01 GWB P-01 - - -
001 LEVEL 05 5195 TR EXP AST RB-01 4" - P-00 - P-02 - P-02 GWB P-00 - P-02 GWB P-00 - P-02 EXP
001 LEVEL 05 5196 OFFICE - - TME TME - - GWB P-01 GWB P-01 - - -
001 LEVEL 06 - CORRIDOR - - TME TME GWB P-01 - - - - - - -
001 LEVEL 06 6203 NURSES OFFICE - - TME TME - - GWB P-01 - - - - -
001 LEVEL 06 6204 TR EXP AST RB-01 4" - P-00 - P-02 GWB P-00 - P-02 GWB P-02 GWB P-00 - P-02 EXP
001 LEVEL 06 6205 NEUROLOGY-EEG - - TME TME - - - - - - GWB P-01 -
001 LEVEL 07 7C5-01 CORRIDOR - - TME TME GWB P-01 - - - - - - -
001 LEVEL 07 7204 TR EXP AST RB-01 6" - P-00 - P-02 GWB P-00 - P-02 GWB P-00 - P-02 - P-00 - P-02 EXP
001 LEVEL 07 7205 PSYCHIATRIST INTERN - - EXST EXST - - - - - - GWB P-01 -
001 LEVEL 08 8C5-01 CORRIDOR - - TME TME - - - - GWB P-01 - - -
001 LEVEL 08 8139 TR EXP AST RB-01 4" GWB P-00 - P-02 - P-00 - P-02 - P-00 - P-02 - P-00 - P-02 EXP
001 LEVEL 09 9C1-01 CORRIDOR - - EXST EXST - - - - - P-01 - - -
001 LEVEL 09 9C2-01 CORRIDOR - - EXST EXST - - - - - P-01 - - -
001 LEVEL 09 9122 DIRECTOR PSTD PGM - - TME TME - - GWB P-01 - - - - -
001 LEVEL 09 9122A TR EXP AST RB-01 4" - P-02 GWB P-00 - P-02 - P-00 - P-02 GWB P-00 - P-02 EXP
001 LEVEL 09 9122B CLOSET - - TME TME - P-01 - - - - GWB P-01 -
002 LEVEL 0G G132 STORAGE - - TME TME GWB P-01 GWB P-01 - - - - -
002 LEVEL 0G G132A TR EXP AST RB-01 6" - P-02 - P-00 - P-02 - P-00 - P-02 GWB P-00 - P-02 EXP
002 LEVEL 0G G143 STORAGE (SHARED WITH DIALYSIS) - - TME TME GWB P-01 GWB P-01 - - - - -
002 LEVEL 0G G143C TR EXP AST RB-01 4" - P-00 - P-02 - P-00 - P-02 GWB P-00 - P-02 GWB P-00 - P-02 EXP
002 LEVEL 0G GC1-02 CORRIDOR - - TME TME - - - - GWB P-01 - - -
002 LEVEL 0G GC4B-02 CORRIDOR - - EXST EXST - - - - - P-01 - - -
002 LEVEL 01 1C12A-02 CORRIDOR - - EXST EXST - - - P-01 - - - - -
002 LEVEL 01 1238 PRIVATE OFFICE - - TME TME GWB P-01 GWB P-01 - - - - -
002 LEVEL 01 1239 TR EXP AST RB-01 4" GWB P-00 - P-02 - P-00 - P-02 - P-00 - P-02 GWB P-00 - P-02 EXP
002 LEVEL 01 1279 DINING RM - - TME TME - - - - - - GWB P-01 -
002 LEVEL 01 1279A TR EXP AST RB-01 6" - P-00 - P-02 GWB P-00 - P-02 - P-00 - P-02 - P-00 - P-02 EXP
002 LEVEL 01 1303A OFFICE - - TME TME GWB P-01 - - - - - - -
002 LEVEL 01 1303B TR EXP AST RB-01 4" - P-00 - P-02 - P-02 GWB P-00 - P-02 - P-00 - P-02 EXP
002 LEVEL 01 C130 STAFF CORRIDOR - - TME TME - - - - GWB P-01 - - -
002 LEVEL 02 2C2A-02 CORRIDOR - - TME TME - - - - - - GWB P-01 -
002 LEVEL 02 2C7-02 CORRIDOR - - EXST EXST - P-01 - - - - - - -
002 LEVEL 02 2C9-02 CORRIDOR - - TME TME - - - - - - GWB P-01 -
002 LEVEL 02 2107D TR EXP AST RB-01 4" - P-00 - P-02 GWB P-00 - P-02 GWB P-00 - P-02 - P-00 - P-02 EXP
002 LEVEL 02 2107E STORAGE - - TME TME GWB P-01 GWB P-01 - - - - -
002 LEVEL 02 2228 TR EXP AST RB-01 4" - P-00 - P-02 GWB P-00 - P-02 - P-00 - P-02 - P-00 - P-02 EXP
002 LEVEL 03 3HA1-02 CORRIDOR - - TME TME GWB P-01 - - - - - - -
002 LEVEL 03 3HA5-02 CORRIDOR - - TME TME GWB P-01 - - - - - - -
002 LEVEL 03 3222 TR EXP AST RB-01 4" - P-02 - P-00 - P-02 GWB P-00 - P-02 - P-00 - P-02 EXP
002 LEVEL 04 4C1-02 CORRIDOR - - TME TME GWB P-01 - - - - - - -
002 LEVEL 04 4222 TR EXP AST RB-01 4" - P-00 - P-02 - P-00 - P-02 GWB P-00 - P-02 - P-00 - P-02 EXP
002 LEVEL 04 GC5-02 CORRIDOR - - TME TME GWB P-01 - - - - - - -
002 LEVEL 05 5C5-02 CORRIDOR - - TME TME GWB P-01 - - - - - - -
002 LEVEL 05 5222 TR EXP AST RB-01 4" - P-02 - P-00 - P-02 GWB P-00 - P-02 - P-00 - P-02 EXP
002 LEVEL 06 6C5-02 CORRIDOR - - TME TME GWB P-01 - - - - - - -
002 LEVEL 06 6208 TREAT AND EXAM - - TME TME - - GWB P-01 - - - - -
002 LEVEL 06 6209 TR EXP AST RB-01 4" - P-00 - P-02 - P-00 - P-02 GWB P-00 - P-02 GWB P-00 - P-02 EXP
002 LEVEL 07 7C1-02 CORRIDOR - - TME TME GWB P-01 - - - - - - -
002 LEVEL 07 7C5-02 CORRIDOR - - TME TME GWB P-01 - - - - - - -
002 LEVEL 07 7205 TR EXP AST RB-01 4" - P-00 - P-02 - P-00 - P-02 GWB P-00 - P-02 - P-00 - P-02 EXP
002 LEVEL 08 8C4-02 CORRIDOR - - TME TME GWB P-01 - - - - - - -
002 LEVEL 08 8141 TR EXP AST RB-01 4" - P-02 GWB P-00 - P-02 GWB P-00 - P-02 - P-00 - P-02 EXP
002 LEVEL 08 8145 LAB - - TME TME - - - - - - GWB P-01 -
002B LEVEL 01 2B-107 IT/ELECTRICAL CLOSET (TE) - - - - - P-00 - P-02 - - - - - - -
003 LEVEL 01 105A TR EXP AST RB-01 4" - P-00 - P-02 - P-00 - P-02 GWB P-02 - P-00 - P-02 EXP
003 LEVEL 01 105B STORAGE - - TME TME GWB P-01 - P-01 - - - - -
003 LEVEL 02 200 LAB - - TME TME GWB P-01 - - - - - - -
003 LEVEL 02 206 TR EXP AST RB-01 4" - P-00 - P-02 - P-00 - P-02 GWB P-00 - P-02 - P-00 - P-02 EXP
004 LEVEL 00 19 SIGNAGE (TE) - - - - GWB P-01 - - - P-00 - P-02 - - -
004 LEVEL 00 19A STORAGE - - TME TME - - - - GWB P-01 - - -
004 LEVEL 01 110 TR EXP AST RB-01 4" - P-02 - P-00 - P-02 - P-02 - P-00 - P-02 EXP
004 LEVEL 01 115 CORRIDOR - - EXST EXST - P-01 - - - - - - -
004 LEVEL 02 210 - - - TME TME - - GWB P-01 - - - - -
004 LEVEL 02 210A TR EXP AST RB-01 4" - P-00 - P-02 - P-00 - P-02 - P-00 - P-02 GWB P-00 - P-02 EXP
005 LEVEL 01 1C3-05 CORRIDOR - - EXST EXST - P-01 - - - - - - -
005 LEVEL 01 C-103 TR EXP AST RB-01 6" - P-00 - P-02 - P-00 - P-02 - P-02 - P-00 - P-02 EXP
P-01
P-02
MATCH EXISTING
SW7005 PURE WHITE
P-00 FIRE RATED PLYWOOD
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ ENGINEER OF RECORD
A/E:
STAMPCONSULTANT/ DISCIPLINE
321 4 5 6 7 8 9 10
DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
08/05/2026 7:14:51 am
Autodesk Docs://689-22-700 VA CT West Haven EHRM
IU/VAWH_GEN
SHEETS_SDB.rvt
A-601b
ROOM FINISH SCHEDULES
JS/JRS JRS/RB
100% CONSTRUCTION
DOCUMENTS
04/20/2026
689-22-700EHRM INFRASTRUCTURE
UPGRADES - WEST HAVEN
VA CT WEST HAVEN
950 CAMPBELL AVENUE, WEST HAVEN, CT 06516
ROOM FINISH SCHEDULE
BLDG # LEVEL ROOM NO. ROOM NAME
FLOOR BASE WALLS
CLG COMMENTSMAT FIN MAT HT
NORTH EAST SOUTH WEST
MAT FIN MAT FIN MAT FIN MAT FIN
005 LEVEL 02 2C2A-05 CORRIDOR - - TME TME GWB P-01 - - - - - - -
005 LEVEL 02 246 VIROLOGY STAFF LOUNGE - - TME TME - - - - - - GWB P-01 -
005 LEVEL 02 C-244 TR EXP AST RB-01 6" - P-02 GWB P-00 - P-02 GWB P-02 - P-00 - P-02 EXP
005 LEVEL 03 3C1A-05 CORRIDOR - - TME TME GWB P-01 - - - - - - -
005 LEVEL 03 315 RESEARCH PSYCHOLOGIST OF
COMPREHENSIVE PAIN MGMT
- - TME TME - - - - - - GWB P-01 -
005 LEVEL 03 C-314 TR EXP AST RB-01 4" - P-02 GWB P-00 - P-02 GWB P-00 - P-02 - P-00 - P-02 EXP
006 LEVEL 01 - CORRIDOR - - TME TME GWB P-01 - - - - - - -
006 LEVEL 01 128 TR EXP AST RB-01 4" GWB P-00 - P-02 - P-00 - P-02 GWB P-00 - P-02 - P-00 - P-02 EXP
006 LEVEL 01 129 OFFICE - - TME TME - - - - GWB P-01 - - -
006 LEVEL 02 - CORRIDOR - - TME TME - - GWB P-01 - - - - -
006 LEVEL 02 219 OFFICE - - TME TME - - - - - - GWB P-01 -
006 LEVEL 02 222 TR EXP AST RB-01 4" - P-00 - P-02 GWB P-00 - P-02 GWB P-00 - P-02 GWB P-02 EXP
006 LEVEL 02 223 STORAGE - - TME TME GWB P-01 GWB P-01 - - - - -
011 LEVEL 02 202 PROPERTY MGMT SVC (TE) - - - - - - - - - P-00 - P-02 - - -
011A LEVEL 01 - CONFERENCE - - TME TME - - GWB P-01 - - - - -
011A LEVEL 01 100 CORRIDOR - - TME TME GWB P-01 - - - - - - -
011A LEVEL 01 113 TR EXP AST RB-01 4" - P-00 - P-02 - P-00 - P-02 GWB P-00 - P-02 GWB P-00 - P-02 EXP
012 LEVEL 02 202 OFFICE (TE) - - - - - - - - - P-00 - P-02 - - -
012A LEVEL 01 119 DATA (TE) - - - - - P-00 - P-02 - - - - - - -
014A LEVEL 01 102 TR EXP AST RB-01 4" - P-00 - P-02 - P-00 - P-02 - P-00 - P-02 - P-00 - P-02 EXP
014A LEVEL 01 117 CORRIDOR - - EXST EXST - - - - - - - P-01 -
015 LEVEL 01 - ELEVATOR LOBBY - - TME TME - - - - - - GWB P-01 -
015 LEVEL 01 128 TR EXP AST RB-01 4" - P-00 - P-02 GWB P-00 - P-02 GWB P-00 - P-02 - P-00 - P-02 EXP
015A LEVEL 01 - ROOM - - EXST EXST - P-01 - - - - - - -
015A LEVEL 01 112 TR EXP AST RB-01 4" - P-00 - P-02 GWB P-00 - P-02 GWB P-00 - P-02 - P-00 - P-02 EXP
015A LEVEL 01 113 CONFERENCE ROOM - - TME TME GWB P-01 - - - - GWB P-01 -
021 LEVEL 01 2A DATA CLOSET (TE) - - RB-01 6" - P-00 - P-02 - - - - - - -
022 LEVEL 01 13 REPAIR SHOP-SUPV OF GROUNDS (TE) - - - - - P-00 - P-02 - - - - - - -
024 LEVEL 01 A-1 WARE HOUSE - - TME TME - - - - GWB P-01 GWB P-01 -
024 LEVEL 01 A-1A TR EXP AST RB-01 4" GWB P-00 - P-02 GWB P-00 - P-02 GWB P-00 - P-02 - P-00 - P-02 EXP
024 LEVEL 01 A-2 SYRINGE STORAGE - - TME TME GWB P-01 - - - - - - -
027-034 LEVEL 01 113 CORRIDOR H - - EXST EXST - - - - - - GWB P-01 -
027-034 LEVEL 01 149 STORAGE - TME TME TME - - - - GWB P-01 - - TME
027-034 LEVEL 01 159 TR EXP AST RB-01 6" - P-00 - P-02 - P-00 - P-02 - P-00 - P-02 GWB P-02 EXP
027-034 LEVEL 01 163B CORRIDOR - - TME TME - - GWB P-01 - - - - -
035 LEVEL 00 B18 TR EXP AST RB-01 6" - P-02 - P-00 - P-02 - P-00 - P-02 - P-00 - P-02 EXP
035 LEVEL 00 B24 CORRIDOR - - EXST EXST - - - - - P-01 - - -
035 LEVEL 01 - CORRIDOR - - EXST EXST - P-01 - - - - - - -
035 LEVEL 01 115 TR EXP AST RB-01 4" - P-00 - P-02 - P-00 - P-02 - P-00 - P-02 - P-00 - P-02 EXP
035A LEVEL 01 - CORRIDOR - - EXST EXST - P-01 - - - - - - -
035A LEVEL 01 124 C.E.R.C. PROJECT RESEARCH STAFF - - TME TME - - GWB P-01 - - - - -
035A LEVEL 01 124A TR EXP AST RB-01 4" - P-00 - P-02 - P-00 - P-02 - P-00 - P-02 GWB P-00 - P-02 EXP
035A LEVEL 02 - CORRIDOR - - EXST EXST - P-01 - - - - - - -
035A LEVEL 02 225 RESEARCH ASSISTANTS - - TME TME - - GWB P-01 - - - - -
035A LEVEL 02 225A TR EXP AST RB-01 4" - P-00 - P-02 - P-00 - P-02 - P-00 - P-02 GWB P-00 - P-02 EXP
036 LEVEL 01 - CORRIDOR - - EXST EXST - - - P-01 - - - - -
036 LEVEL 01 105 TR EXP AST RB-01 4" - P-00 - P-02 - P-02 - P-00 - P-02 - P-00 - P-02 EXP
36A LEVEL 01 117 CORRIDOR - - TME TME - - - - GWB P-01 - - -
036A LEVEL 01 112 PRINTER/FAX - - EXST EXST - - - - - P-01 - - -
036A LEVEL 01 114 IT / ELECT (TE) - - - - GWB P-02 - - - - - P-00 - P-02 -
ROOM FINISH SCHEDULE ABBREVIATIONS
AST
EXP
GWB
RB-01
TME
EXT
PAINT CODES
ANTI-STATIC COATING
EXPOSED
GYPSUM WALL BOARD
RUBBER BASE
TO MATCH EXISTING
EXTERIOR
ROOM FINISH SCHEDULE - DATA CENTER
BLDG # LEVEL ROOM NO. ROOM NAME
FLOOR BASE WALLS
CLG COMMENTSMAT FIN MAT HT
NORTH EAST SOUTH WEST
MAT FIN MAT FIN MAT FIN MAT FIN
041 LEVEL 01 104 CORRIDOR EXP - N/A - - P-02 - P-02 - P-02 - P-02 EXP
041 LEVEL 01 105 ENTRANCE ROOM #1 EXP AST N/A - - P-02 - P-02 - P-02 - P-02 EXP
041 LEVEL 01 106 SECURE STORAGE EXP - N/A - - P-02 - P-02 - P-02 - P-02 EXP
041 LEVEL 01 107 ENTRANCE ROOM #2 EXP AST N/A - - P-02 - P-02 - P-02 - P-02 EXP
041 LEVEL 01 108 MECH EXP - N/A - - P-02 - P-02 - P-02 - P-02 EXP
041 LEVEL 01 109 ELEC EXP - N/A - - P-02 - P-02 - P-02 - P-02 EXP
041 LEVEL 01 110 FIRE RISER EXP - N/A - - P-02 - P-02 - P-02 - P-02 EXP
041 LEVEL 01 111 ROOF ACCESS EXP - N/A - - P-02 - P-02 - P-02 - P-02 EXP
041 LEVEL 01 112 UNPACKING/ PACKING EXP - N/A - - - - P-02 - P-02 - P-02 EXP
041 LEVEL 01 113 VEST EXP - N/A - - P-02 - P-02 - P-02 - P-02 EXP
041 LEVEL 01 114 DATA CENTER EXP AST RB 4" - P-02 - P-02 - P-02 - P-02 EXP
042 LEVEL 01 121 GENERATOR ENCLOSURE EXP - N/A - - P-02 - P-02 - P-02 - P-02 EXP
042 LEVEL 01 122 FUEL YARD EXP - N/A - - P-02 - P-02 - P-02 - P-02 -
P-01
P-02
MATCH EXISTING
SW7005 PURE WHITE
P-00 FIRE RATED PLYWOOD
CAULK ALL
AROUND
ADJUSTABLE
ANCHOR
STANDARD FRAME
EXPOSED MASONRY OR BRICK
1/2"
S.F.T.U.
NOMINAL
CMU OR 1/2"
FRAMES IN MASONRY PARTITION
CASING BEAD
ADJUSTABLE
ANCHOR
STANDARD FRAME
MASONRY BLOCK PLASTERED
GROUT
5/8"
S.F.T.U.
NOMINAL
CMU OR 7/8"
PLASTER ON
METAL LATH
CAULK ALL
AROUND
GROUT
CERAMIC TILE
ADJUSTABLE
ANCHOR
STANDARD FRAME
MASONRY BLOCK WITH CERAMIC TILE FINISH
GROUT
SETTING BED
CAULK ALL
AROUND
1/2"
S.F.T.U.
NOMINAL
CMU OR 3/4"
*** FRAME WIDTH FOR NOMINAL MASONRY
4 3/4" W/ 4" CMU
6 3/4" W/ 6" CMU
8 3/4" W/ 8" CMU
METAL STUD AND PLASTER FINISH
FRAMES WITH METAL STUD
AND PLASTER PARTITIONS
GAUGE AS
SPECIFIED
ADD RETURN ON
FRAME WHERE
DRYWALL FINISH
IS REQUIRED
STANDARD DOOR FRAME
FRAMES IN METAL STUD PARTITIONS
CERAMIC TILE
FINISH WHERE
REQUIRED
CAULK ALL
AROUND BOTH
SIDES
STANDARD FRAME
FOR DRYWALL
JAMB ANCHORS
DOUBLE STUDS
BACK TO BACK
DRYWALL, THICKNESS
SINGLE OR DOUBLE AS
REQUIRED
FRAMES IN MASONRY PARTITION
FACED WITH GWB
STANDARD FRAME
ADJUSTABLE
ANCHORS
GROUT
CAULK ALL
AROUND
CERAMIC TILE
FINISH WHERE
REQUIRED
TILE FINISH
FRAME AT CONCRETE WALLS
DOUBLE EGRESS DOOR FRAME
PLAN
JAMB 'B'
HEAD 'A'
NOTE: SHOWING SWING OF
DOUBLE EGRESS DOORS
A B
C
A C
B
NOTE: SHOWING SWING OF
DOUBLE EGRESS DOORS
DOOR
DOOR
DOOR STOP (BEYOND)
PLATE WELDED
TO FRAME
/2
"2 1/2" MIN
+/- 1/4"
/4
7/8"
08 11 13-01
METAL STUDS
PER STD DTL 3/4"
1/4"
7/8"
08 11 13-01
MTL STUDS
PER STD DTL 11/16"
1/4"
1/4"
1/4"
CAULK ALL
AROUND
CASING BEAD
WHERE PLASTER
IS REQUIRED
CONCRETE
GROUT
VENEER
PLASTER ON
PLASTER BASE
TROWEL CUT
AT FRAME
EDGES
ANCHOR
STANDARD
FRAME
CONVENTIONAL
PLASTER
GYP LATH
CERAMIC TILE
CAULK BOTH
SIDES
ANCHOR
STANDARD
FRAME
CERAMIC TILE
GWB
CEMENT
BACKER BOARD
PIPE SEPARATORS
WELDED TO PLATE
F.H. CSK.
EXP. BOLT
THROAT OPENING = PARTITION
WIDTH + 1/8" MIN
1/2" 1/2"
/8
1 15/16"VARIESVARIES
UNDERSIDE OF STRUCTURE OR
INTERSTITIAL FLOOR
MTL STUD HEADER, TYPICAL
MTL RUNNER, TYPICAL
MTL STUD, TYPICAL
HM DOOR FRAME, TYPICAL
JAMB ANCHOR TYPICAL
EXISTING GB &
MTL STUD WALL
TO REMAIN
EXISTING GB &
MTL STUD WALL
TO REMAIN
HEIGHT SHALL VARY
0' - 4" TYPICAL 0' - 4" TYPICAL
DOOR WIDTH AS
SCHEDULED
MTL DOOR
FRAME
SHIM AS
REQ'D
RUNNER
BETWEEN
STUDS
1/2"
CONST
JOINT
SEE NOTE 1
VERTICAL STUDS @ 2'-0" MAX. W/
GYPSUM WALL BOARD. 1'-4" W/ GYPSUM
LATH & PLASTER DOUBLE STUDS FOR
SUPPORTING CONC. BACKER BOARD
PROVIDE CONTINUOUS BRACING
WHEN STUDS EXCEED 10'-0" AND
ARE FINISHED BOTH SIDES
JAMB ANCHOR CLIPS 3 PER
SIDE - COORDINATE W/
HINGE REINFORCEMENT
NOTE 1: OMIT BRACE WHEN 'D' DIMENSION
IS LESS THAN 2'-0" FOR GYP. WALL BOARD
OR 16" FOR PLASTER PARTITION
ELEVATION AT DOOR FRAME
DETAIL D
JAMB ANCHORS
(FURNISHED W/ FRAME)
DETAIL C
FRAME FACE
MIN
US 3/16"
E Q
E Q
D
E Q
E Q
V A
R
IE
S S
E E
D O
O R
S C
H E
D
VARIES SEE DOOR SCHED
DETAIL B
A A
1/2" M
IN
5/8" M
AX
FRAME FACE
MIN
US 3/16"
/4
M
IN
STUD
W
IDTH
/4
M
IN
JAMB DEPTH
MINUS 3/16"
STUD
W
IDTH
1/2"
DETAIL D, TYP
M A
X
DETAIL B
PROVIDE SOUND
DEADENING WHERE
REQUIRED
/8
SECTION A
DOUBLE STUDS JAMB ANCHOR
GYPSUM WALL
BOARD PANELS
CONTROL JOINT
ISOMETRIC OF CONSTRUCT JOINT
/4
M
IN
DETAIL C
SANITARY
STOP
MTL DOOR FRAME
MTL ANCHOR CLIP
SHIM AS
REQ'D
CRIPPLE STUD, DO NOT
ANCHOR TO BEARING STUD
1/2" M
IN
1A/2A
4A
SEE SCHED.
S E
E S
C H
E D
SEE SCHED.
S E
E S
C H
E D
DOOR HEIGHTS AND WIDTHS PER SCHEDULE
5A
SEE SCHED.
S E
E S
C H
E D
REMOVABLE
CENTER
MULLION
SEE SCHED.
S E
E S
C H
E D
3A
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ ENGINEER OF RECORD
A/E:
STAMPCONSULTANT/ DISCIPLINE
321 4 5 6 7 8 9 10
DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
08/05/2026 7:14:52 am
Autodesk Docs://689-22-700 VA CT West Haven EHRM
IU/VAWH_GEN
SHEETS_SDB.rvt
A-602
DOOR TYPES & DETAILS
JS/JRS RB
100% CONSTRUCTION
DOCUMENTS
04/20/2026
689-22-700EHRM INFRASTRUCTURE
UPGRADES - WEST HAVEN
VA CT WEST HAVEN
950 CAMPBELL AVENUE, WEST HAVEN, CT 06516
NTS
DOOR FRAME - DETAILS
3/4" = 1'-0"
DOOR FRAME - DETAIL
NTS
PARTITION FRAMING AT DOORS
1" = NTS
DOOR TYPES
GENERAL NOTES
1. SEE SPECIFICATION SECTION 08 71 00 - DOOR HARDWARE
FOR HW SETS.
2. CONTRACTOR TO VERIFY DOOR SIZE AND WALL THICKNESS
PRIOR TO ORDERING DOORS AND FRAMES. ALL DOOR
FRAMES ARE TO HAVE A POSITIVE RELIEF TO EXISTING
WALLS.
3. DATA CENTER AND GENERATOR ENCLOSURE EXTERIOR
DOORS, FRAMES, AND ANCHORAGE SHALL BE IN
ACCORDANCE WITH SPEC 08 11 13.
UNDERSIDE OF
STRUCTURE ABOVE
(OR INTERSTITIAL
FLOOR, WHERE
OCCURS)
DEMOLISH EXISTING ACT
ON TR SIDE ONLY,
TYPICAL
EXISTING ACT TO
REMAIN IN ADJ ROOMS,
TYPICAL
EXISTING MTL STUD, TYPICAL
EXISTING TOP PLATES
NOTE: EXTEND WALLS AT
NEW TR LOCATIONS
ONLY: B349, B400 AND
B334. ALSO WITH RFP-001
PROPOSAL.
NO. 9 3/4-INCH 10-GAUGE FLATTENED EXPANDED
STEEL SECURITY MESH. MECHANICALLY
ANCHORED TO WINDOW FRAME.
RIGID INSULATION.
INSPECT EXIST. GLAZING LITES FOR BREAKS &/
OR MULLION WATER LEAKS & BRING TO THE
ATTENTION OF THE VA'S C.O.R. FOR POSSIBLE
REPAIR OR LITE REPLACEMENT
- REPLACED LITES &/ OR REPAINT ARE NOT IN
CONTRACT.
FRT PLYWOOD IN TR'S / TYPE X GYP IN ADJACENT
SPACES
INTERIOREXTERIOR
NOTE:
1. PERFORMANCE OF THE SELECTED SYSTEM MUST BE DEMONSTRATED
WITH GLAZING…