Attachment 01 - 36C77626R0106 Tech Questions - dated 7-31-26.docx
DOCX document 68 KB Posted
- Attached to
- Z2DA--689-22-700 EHRM IU West Haven VAMC This ONLY for the PCAC VISN 1 Construction MATOC Pool
- Solicitation number
- 36C77626R0106
About this file
This file is a Technical Questions and Solicitation Responses Tracking Sheet for solicitation 36C77626R0106, related to Project 689-22-70 EHRM IU West Haven at the Department of Veterans Affairs.
The document addresses contractor inquiries regarding access control and card reader requirements for specific doors across multiple buildings at the facility. Question 1 identifies doors listed on the Door Schedule lacking reader symbols at locations including Building 1 Level 0 (doors SG170A, G192A, G192, G192B), Building 2 Level 0 (door G132A), Building 6 Level 2 (door 223), and Building 41 Level 1 (doors 109, 110, 111). Question 2 identifies doors on the Door Schedule not appearing on drawings at Building 1 Level 9 (door 9122B), Building 2 Level 1 (doors 1238, 1239), and Building 41 Level 1 (doors 104A, 104B, 114A, 114B, 121A, 121B, 122). The VA response to both questions requires contractors to provide access control devices, door power, and associated infrastructure for all doors identified in the Architectural Door Schedule and contract drawings, with connections made to access control panels and panelboards provided in the project. The response directs contractors to reference updated sheet A-601 Electrical to confirm card reader locations. This is a questions and answers document providing clarification on contract requirements rather than a document addressing specific deliverables or pricing terms.
View the file
Other files
Show all 42
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
TECHNICAL QUESTIONS AND
| SOLICITATION #: |
| 36C77626R0106 |
| RESPONSES TRACKING SHEET |
| PROJECT TITLE: |
| 689-22-70 EHRM IU West Haven |
| # |
| CONTRACTOR QUESTION |
| VA RESPONSE |
| 1 |
| Doors listed on the Door Schedule, but missing reader symbol, will these doors require a card reader? Bldg. 1 level 0SG -door SG170A , Bldg. 1 level 0G doors G192A, G192 , G192B , Bldg. 2 level 0G – door G132A, Bldg. 6 level 2 – door 223, Bldg. 41 level 1- doors 109 , 110, 111 |
| Provide access control devices, door power, and all associated infrastructure as required for doors identified in the Architectural Door Schedule and contract drawings. Connections shall be made to the access control panels and associated panelboards provided in this project. See updated sheet A-601 Electrical to confirm card reader locations |
| 2 |
| Doors listed in the Door Schedule, but is not listed on drawing, will these doors require a card reader? Bldg. 1 level 9 – door 9122B , Bldg. 2 level 1 – doors 1238 , 1239 , Bldg. 41 level 1- doors 104A , 104B, 114A, 114B, 121A, 121B and 122 |
| Provide access control devices, door power, and all associated infrastructure as required for doors identified in the Architectural Door Schedule and contract drawings. Connections shall be made to the access control panels and associated panelboards provided in this project. See updated sheet A-601 Electrical to confirm card reader locations |
image1.jpeg