Attachment 14 - Newington EHRM Drawings - Part 5 of 16.pdf

PDF 17 MB Posted

Attached to
Z2DA--689A4-22-700 EHRM Infrastructure, Newington CONSTRUCTION SOLICITATION (VA-24-00028377)
Solicitation number
36C77624B0015_1
Issued by

About this file

This document appears to be Part 5 of 16 of architectural/engineering drawings for the Electronic Health Record Modernization (EHRM) infrastructure project at the VA Medical Center in Newington, CT. The drawings detail technical specifications and layouts related to IT and communications infrastructure upgrades required to support the Cerner system implementation. Without access to view the actual drawings, the specific technical details cannot be summarized, but these would typically include network infrastructure layouts, equipment locations, cable pathways, and related construction details for the affected buildings (1C, 2E, 2C, 2W, 3, 12, 32, 33, 34, 42, 65).

View the file

Other files

File Type Posted
Technical Questions Tracking Spreadsheet - 2-13-25 - 36C77624B0015 - Construct EHRM Infrastructure Upgrades Newington CT.pdf PDF
Newington EHRM Infrastructure Upgrades - 36C77624B0015 Amendment - 0007.pdf PDF
Attachment 34 - 689A4-22-700.EHRM.Newington.Add3.20250211.pdf PDF
Newington EHRM Infrastructure Upgrades - 36C77624B0015 Amendment - 0006.pdf PDF
Attachment 27 - Wage Rates 01.31.25- Hartford.pdf PDF
Bid Opening Details - Newington CT - 36C76624B0015.pdf PDF
Site Visit Sign In Sheet 2.3.25.pdf PDF
Newington EHRM Infrastructure Upgrades - 36C77624B0015 Amendment - 0005.pdf PDF
Attachment 33 - Site Visit Instructions - Updated 1.27.25.pdf PDF
Attachment 2 - 689A4-22-700.EHRM.Newington.Spec.Final.20240806.Part1.pdf PDF
Attachment 21 - 689A4-22-700.Newington.EHRM.IFC.B32_33_34.20240703.part2.pdf PDF
Attachment 13 - 689A4-22-700.Newington.EHRM.IFC.B01_02.20241008.part4.pdf PDF
Attachment 17 - 689A4-22-700.Newington.EHRM.IFC.B03_42.20240703.part2.pdf PDF
Newington EHRM Infrastructure Upgrades - 36C77624B0015 Amendment - 0004.pdf PDF
Attachment 22 - 689A4-22-700.Newington.EHRM.IFC.B65.20240703.part1.pdf PDF
Attachment 32 - 689A4-22-700.EHRM.Newington -.20250114 - Addendum 2.pdf PDF
Attachment 3 - 689A4-22-700.EHRM.Newington.Spec.Final.20240806.Part2.pdf PDF
Attachment 12 - 689A4-22-700.Newington.EHRM.IFC.B01_02.20241008.part3.pdf PDF
Attachment 15 - 689A4-22-700.Newington.EHRM.IFC.B01_02.20241008.part6.pdf PDF
Attachment 20 - 689A4-22-700.Newington.EHRM.IFC.B32_33_34.20240703.part1.pdf PDF
Attachment 33 - Site Visit Instructions - Updated 1.23.25.pdf PDF
Attachment 18 - 689A4-22-700.Newington.EHRM.IFC.B03_42.20240703.part3.pdf PDF
Attachment 23 - 689A4-22-700.Newington.EHRM.IFC.B65.20240703.part2.pdf PDF
Attachment 19 - 689A4-22-700.Newington.EHRM.IFC.B12.20240703.pdf PDF
Attachment 14 - 689A4-22-700.Newington.EHRM.IFC.B01_02.20241008.part5.pdf PDF
Attachment 10 - 689A4-22-700.Newington.EHRM.IFC.B01_02.20241008.part1.pdf PDF
Technical Questions Tracking Spreadsheet - 1-23-25 - 36C77624B0015 - Construct EHRM Infrastructure Upgrades Newington CT .pdf PDF
Attachment 16 - 689A4-22-700.Newington.EHRM.IFC.B03_42.20240703.part1.pdf PDF
Attachment 24 - 689A4-22-700.Newington.EHRM.IFC.SITE.20240703.pdf PDF
Attachment 11 - 689A4-22-700.Newington.EHRM.IFC.B01_02.20241008.part2.pdf PDF
Attachment 31 - EHRM Newington-Pre Bid Presentation.010725.R02.pdf PDF
Technical Questions Tracking Spreadsheet - 1-6-25 - 36C77624B0015 - Construct EHRM Infrastructure Upgrades Newington CT.pdf PDF
Newington EHRM Infrastructure Upgrades - 36C77624B0015 Amendment - 0003.pdf PDF
2025-01-07 Preproposal conference sign in list.pdf PDF
Attachment 30 - Price Schedule - 36C77624B0015 - 689A4-22-700 EHRM Infrastructure Newington.pdf PDF
Attachment 28 - Site Visit Instructions - Updated 1.6.25.pdf PDF
Newington EHRM Infrastructure Upgrades - 36C77624B0015 Amendment - 0002.pdf PDF
Attachment 19 - Newington EHRM Drawings - Part 10 of 16 - 12.31.24.pdf PDF
Newington EHRM Infrastructure Upgrades - 36C77624B0015 Amendment - 0001.pdf PDF
Attachment 29 - 689A4-22-700.EHRM.Newington.Add1.20241213.pdf PDF
Attachment 28 - Site Visit Instructions.pdf PDF
Attachment 24 - Newington EHRM Drawings - Part 15 of 16.pdf PDF
Attachment 11 - Newington EHRM Drawings - Part 2 of 16.pdf PDF
Attachment 26 - Newington VAHC campus map.pdf PDF
Attachment 22 - Newington EHRM Drawings - Part 13 of 16.pdf PDF
Attachment 23 - Newington EHRM Drawings - Part 14 of 16.pdf PDF
Attachment 3 - 689A4-22-700.EHRM.Newington.Spec.Final.20240806.Part2.pdf PDF
Attachment 10 - Newington EHRM Drawings - Part 1 of 16.pdf PDF
Attachment 27 - Wage Rates 8.9.24- Hartford.pdf PDF
Attachment 9 - Underground Utility Locating.pdf PDF
Show 40 more

Latest 50 of 68 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

NOTE: NOT ALL ABBREVIATIONS AND

SYMBOLS APPLY TO THIS PROJECT.

ELECTRICAL ABBREVIATIONS

CR

MD

MD

DC

ES

RX

SECURITY DOOR CONTACT. PROVIDE AND INSTALL 4S BACK BOX ABOVE DOOR WITH A 1" EMT

CONDUIT STUBBED INTO NEAREST ACCESSIBLE CEILING SPACE. PROVIDE ALL CONDUIT,

CONDUIT SUPPORT, CONNECTORS, COUPLINGS, PLASTIC BUSHINGS, PULL STRINGS, OUTLET

BOX AND MUD RING.

WALL MOUNTED SINGLE SENSOR CAMERA. PROVIDE AND INSTALL 4S BACK BOX W/ A 1" EMT

CONDUIT HOMERUN TO CABLE TRAY. PROVIDE ALL CONDUIT, CONDUIT SUPPORT, CONNECTORS,

COUPLINGS, PLASTIC BUSHINGS, PULL STRINGS, OUTLET BOX AND MUD RING. EACH CAMERA TO HAVE ONE(1) CATEGORY 6a CABLE PROVIDED BY SECURITY CONTRACTOR. PROVIDE WITH

MANUFACTURER'S WALL MOUNTING ACCESSORIES.

CARD READER OUTLET. PROVIDE AND INSTALL 4S BACK BOX AT SWITCH HEIGHT WITH A 3/4" EMT

CONDUIT CONNECTED TO THE DOOR CONTACT OUTLET BOX. PROVIDE ALL CONDUIT, CONDUIT

SUPPORT, CONNECTORS, COUPLINGS, PLASTIC BUSHINGS, PULL STRINGS, OUTLET BOX AND MUD

RING.

DATA/VOICE OUTLET - FLOORBOX. PROVIDE AND INSTALL (4) CAT 6a CMP CABLES/JACKS TERMINATED IN FLOOR BOX. PROVIDE AND INSTALL (2) 1-1/4" CONDUIT STUBBED TO NEAREST FURRED WALL , ROUTE CONDUIT TO ACCESSIBLE LOCATION ABOVE FINISHED CEILING. PROVIDE BUSHINGS AND PULLSTRING, U.O.N. USE EXISTING CONDUIT RISERS IN-WALL AND EXTEND ALL

CABLES TO NEW CABLE TRAY AND ROUTE TO TR INDICATED. SEE T-700 SERIES SHEETS FOR

NUMBER OF CABLES REQUIRED AT EACH WAO.

DATA/VOICE OUTLET - WALL MOUNTED. PROVIDE AND INSTALL (4) CAT 6a CMP CABLES / JACKS TERMINATED IN 6-PORT FACEPLATE AT 18" AFF. PROVIDE AND INSTALL 5S JBOX WITH SINGLE GANG MUDRING AND 1-1/4" CONDUIT STUBBED TO ACCESSIBLE CEILING LOCATION. PROVIDE BUSHINGS AND PULLSTRING, U.O.N. (SLASH INDICATES MOUNTING ABOVE FINISH COUNTER). USE EXISTING

CONDUIT RISERS IN-WALL AND EXTEND ALL CABLES TO NEW CABLE TRAY AND ROUTE TO TR

INDICATED. SEE T-700 SERIES SHEETS FOR NUMBER OF CABLES REQUIRED AT EACH WAO.

DATA/VOICE OUTLET - CEILING MOUNTED. PROVIDE AND INSTALL (2) CAT 6a CMP CABLES / JACKS

TERMINATED IN A 2-PORT FACEPLATE AT FINISHED CEILING. (NOTE: AT HARDLID CEILING

LOCATIONS PROVIDE AND INSTALL 5SJBOX WITH 1-1/4" CONDUIT STUBBED TO ACCESSIBLE CEILING LOCATION. PROVIDE BUSHINGS AND PULLSTRING, U.O.N.) SURFACE TYPE ("F" DENOTES FLUSH TYPE) USE EXISTING CONDUIT RISERS IN-WALL AND EXTEND ALL CABLES TO NEW CABLE TRAY AND ROUTE TO TR INDICATED. SEE T-700 SERIES SHEETS FOR NUMBER OF CABLES REQUIRED AT EACH

WAO.

REQUEST-TO-EXIT. ELECTRICAL CONTRACTOR SHALL PROVIDE AND INSTALL 1" EMT CONDUIT

CONNECTED TO THE DOOR POSITION SWITCH BOX. PROVIDE ALL CONDUIT, CONDUIT SUPPORT,

CONNECTORS, COUPLINGS, PLASTIC BUSHINGS, PULL STRINGS, OUTLET BOX AND MUD RING.

ELECTRIFIED DOOR HARDWARE. PROVIDE AND INSTALL 3/4" EMT CONDUIT CONNECTED TO THE

DOOR CONTACT OUTLET BOX.

CEILING MOUNTED SECURITY MOTION SENSOR. PROVIDE AND INSTALL 1-GANG BACK BOX AND (1) 1" CONDUIT STUBBED UP TO ACCESSIBLE CEILING SPACE. PROVIDE BUSHINGS AND PULLSTRING, U.O.N.

WALL MOUNTED SECURITY MOTION SENSOR. PROVIDE AND INSTALL 1-GANG BACK BOX AND (1) 1" CONDUIT STUBBED UP TO ACCESSIBLE CEILING SPACE. PROVIDE BUSHINGS AND PULLSTRING, U.O.N.

DATA/VOICE OUTLET - ABOVE CEILING.

A INTERCOMMUNICATION SYSTEM ( AI PHONE)

D D

FURNITURE/EQUIPMENT FEED DEDICATED JUNCTION BOX. PROVIDE AND INSTALL RACO 260 5S

JUNCTION BOX WITH (1) 1-1/4" CONDUIT TO ACCESSIBLE CEILING. EXTEND TO CABLE TRAY.

MOUNTING HEIGHT NOTES:

1. ALL ELEVATIONS ARE TO CENTER LINE OF DEVICE, UNLESS OTHERWISE NOTED.

2. REFER TO EQUIPMENT ELEVATION DRAWINGS FOR COORDINATION WITH

CASEWORK.

3. MOUNT MANUAL MOTOR STARTER ADJACENT TO OR ON UNIT.

4. REFER TO ARCHITECTURAL A0 SERIES FOR ADDITIONAL ELECTRICAL DEVICE

MOUNTING HEIGHTS AND DEVICE ALIGNMENT RULES.

WALL SWITCHES

RECEPTACLES

TELECOMMUNICATIONS OUTLETS

TELECOMMUNICATIONS OUTLETS - WALL PHONE

CLOCK OUTLETS

TV OUTLETS

PUSHBUTTONS

VOLUME CONTROLS

NURSE CALL STATIONS

NURSE CALL DOME LIGHTS

DIMMERS

ACCESS CONTROL DEVICES

VANITY LIGHT IN TOILET

INTERCOM

FIREMAN'S PHONE

FIRE ALARM - PULL STATIONS

FIRE ALARM DEVICES HORN/SPEAKERS/STROBES

(MOUNTING HEIGHT AT THE TOP OF THE FIRE ALARM DEVICE OR

6" BELOW CEILING WHICH IS LOWER)

4'-0" AFF

1'-6" AFF

1'-6" AFF

4'-0" AFF

7'-0" AFF

1'-6" AFF

4'-0" AFF

4'-0" AFF

4'-0" AFF

7'-6" AFF

4'-0" AFF

4'-0" AFF TO TOP

6" ABOVE THE MIRROR, UON

4'-0" AFF TO TOP

4'-0" AFF

4'-0" AFF

7'-2" AFF TO TOP

SECURITY SYSTEM SYMBOLS

TELECOMMUNICATION SYMBOLS

MOUNTING HEIGHTS

REFERENCE SYMBOLS

SECTION NUMBER

DETAIL NUMBER

DRAWING NUMBER WHERE DRAWN

DRAWING NUMBER WHERE DRAWN

E1-1.0 KEY NOTE

E1-1.0

DISCONNECT SWITCHES

MOTOR STARTERS

PANELBOARDS & CABINETS

INDIVIDUAL CIRCUIT BREAKERS

5'-6" AFF

5'-6" AFF

6'-0" AFF TO TOP

5'-6" AFF

WAP

WIRELESS ACCESS POINT OUTLET - CEILING MOUNTED. PROVIDE AND INSTALL (1) CAT 6a CMP CABLES / JACKS TERMINATED IN A SURFACE MOUNT BOX ABOVE FINISHED CEILING. (NOTE: AT HARDLID CEILING LOCATIONS, PROVIDE AND INSTALL 5S JBOX WITH 1-1/4" CONDUIT STUBBED TO ACCESSIBLE CEILING LOCATION. PROVIDE BUSHINGS AND PULLSTRING, U.O.N. TERMINATE CABLES ON JACKS IN 2-PORT FACE PLATE. PROVIDE 25FT. SLACK ON EVERY CABLE IF THE DISTANCE ALLOWS. PROVIDE (1) CAT 6a CMP GREEN TO VA-IDF.

SPST

SWBD

SYM

STD

SW

SPEC(S)

SPDT

SPKR

SF

SEC

SINGLE POLE SINGLE THROW

SINGLE POLE DOUBLE THROW

SYMMETRICAL

SWITCHBOARD

STANDARD

SWITCH

SECONDARY

SQUARE FOOT

SPECIFICATION(S)

SPEAKER

PRI

RCLP

RM

SCH, SCHED

RP

REF

REC/RCPT

RSC

RLA

RF

R, RE

QTY

PWR

PT

PVC

PA

PH, ∅

PF

PNL

PE

PB

P

OPP

OHE/T

OH

OFOI

OFCI

NO., NUM, #

OC

NTS

AMERICAN WIRE GAUGE

ABOVE FINISHED FLOOR

ABOVE FINISHED GRADE

AUTOMATIC TRANSFER SWITCH

AMPERE INTERRUPTING CAPACITY

ALTERNATING CURRENT

ABOVE FINISHED COUNTER

AWG

BDF

B/BUR

BUILDING DISTRIBUTION FRAME

BURIED

AUTO

AUX

ARCH

AT

ATS

ALT

AFG

AIC

AFC

AFF

AC

AF

AUXILIARY

ALTERNATE

ARCHITECT

AUTOMATIC

AMPERES TRIP

AMPERE FRAME (BREAKER RATING)

MTG

NC

NEMA

NO

NIC

NEC

N

MV

MH

MOCP

MTD

MLO

MIN

MISC

MECH

MCC

MFR

MCA

MCB

RIGID STEEL CONDUIT

RATED (RUNNING) LOAD AMPS

RECEPTACLE PANELBOARD

ROOM

SCHEDULE

RADIO FREQUENCY

RECEPTACLE

REFRIGERATOR

RELOCATE AS SHOWN

POTENTIAL TRANSFORMER

POLYVINYL CHLORIDE

REMOTE CONTROL LIGHTING PANEL

QUANTITY

POWER

PUBLIC ADDRESS

PANEL

PRIMARY

PULL BOX

POWER FACTOR

PHOTO ELECTRIC

PHASE

POLE

OPPOSITE

OWNER FURNISHED, CONTRACTOR INSTALLED

OWNER FURNISHED, OWNER INSTALLED

OVERHEAD ELECTRIC/TELEPHONE

OVERHEAD

ON CENTER

NOT TO SCALE

NUMBER

MOUNTING

NATIONAL ELECTRICAL CODE

MEDIUM VOLTAGE (OVER 600V LESS THAN

35KV)

NORMALLY CLOSED

NORMALLY OPEN

NOT IN CONTRACT

NEUTRAL

MINIMUM CIRCUIT AMPACITY

MAIN CIRCUIT BREAKER

MOTOR CONTROL CENTER

MAXIMUM OVERCURRENT PROTECTION

MOUNTED

MISCELLANEOUS

MAIN LUGS ONLY

MINIMUM

MANHOLE

MANUFACTURER

MECHANICAL

SWGR SWITCHGEAR

AIR HANDLING UNITAHU

MTS MANUAL TRANSFER SWITCH

PDP POWER DISTRIBUTION PANEL

AMPERESA OR AMP

OCPD OVERCURRENT PROTECTION DEVICE

A

M

B

N

O

P

Q

R

S

T

SPD SURGE PROTECTIVE DEVICE

OD OUTLET DESIGNATOR

LOW VOLTAGE (BELOW 50 VOLTS)

L-L L-N

LTG

LV

LIGHTING

LINE TO LINE

LINE TO NEUTRAL

1000 CIRCULAR mils

KILOVOLTS (THOUSAND VOLTS)

KILOWATTS (THOUSAND WATTS)

LIGHTNING ARRESTOR

LOCAL AREA NETWORK

KILOVOLTS-AMPERES (THOUSAND VOLT-AMPS)

ISOLATED GROUND

KWH

LAN

LA

KW

KVA

Kcmil

KV

KILOWATT-HOURS

IR

KEY INTERLOCK

JUNCTION BOX

INCH/INCHES (")

INFRARED

GROUND FAULT INTERRUPTER

HAND-OFF-AUTOMATIC

HIGH PRESSURE SODIUM

HEATING VENTILATION AND AIR CONDITIONING

HERTZ

HVAC

HZ

HTR

HR

HT

HPS

HOA

HP

HEATER

HEIGHT

HORSEPOWER

HOUR

GFI

G, GND, GRD

GEN

FLUOR

FL, FLR

GROUND

GENERATOR

FOOT/FEET (')

FLUORESCENT

FLOOR

CMP

FIRE ALARM ANNUNCIATOR PANEL

EQUIPMENT GROUND

FAAP

FLA

FDR

FA

FULL LOAD AMPS

FEEDER

FIRE ALARM

FUSE

EG

CONTROL POWER TRANSFORMER

CURRENT TRANSFORMER

DBB

dB

DAS

DISPLAY BACKBOX

DISTRIBUTED ANTENNA SYSTEM

DECIBEL

CPT

CU

CT

COM, COMM

CKT

CLG

COPPER

COMMUNICATIONS

CIRCUIT

CEILING

COMMUNICATIONS PLENUM (CABLE JACKET

RATING)

CB CONDUIT BANK

COMMUNICATIONS RISER (CABLE JACKET RATING)

FIRE ALARM CONTROL PANELFACP

FIRE ALARM EXTENDER PANELFAEP

CCTV CLOSED CIRCUIT TELEVISION

CP CONSOLIDATION POINT

FLEX FLEXIBLE

HAND HOLEHH

LIGHTING CONTROL PANELLC, LCP

LIGHTING PANEL

L-G LINE TO GROUND

CMR

F

FT

IN

IG

JB, JBOX

K

LP

FOOT CANDLEFC

DMARC POINT OF DEMARCATION BETWEEN UTILITIES OR

BETWEEN UTILITIES AND OWNER PREMISE

EQUIPMENT

C

D

E

F

G

H

I

J

K

L

HORIZONTAL MOUNTINGH

COR CONTRACTING OFFICER'S REPRESENTATIVE

X

XFMR

WP

WHM

W/ W/O

W

VFD

VA

V

UPS

UL

UON

UG

UGS

UGT

UGP

TYP

TV

TP

TEL,TELE

TELECOM

TC

TRANSFORMER

REMOVE DEVICE

WATT HOUR METER

WEATHERPROOF

VOLTS

VARIABLE FREQUENCY DRIVE/

VARIABLE FREQUENCY MOTOR

CONTROLLER

WITHOUT

WITH

WATTS

VETERANS ADMINISTRATION

UNDERGROUND PRIMARY

UNDERGROUND SECONDARY

UNDERGROUND TELEPHONE

UNDERWRITER'S LABORATORY

UNLESS OTHERWISE NOTED

UNINTERRUPTIBLE POWER SUPPLY

UNDERGROUND

TELECOMMUNICATIONS

TYPICAL

TELEVISION

TAMPERPROOF

TIME CLOCK

TELEPHONE

TB TERMINAL BLOCK

TBB TELEPHONE BACKBOARD

U

V

W

X

Z

TPST TRIPLE POLE SINGLE THROW

FDS FORWARD DEPLOYED SERVICES

JOINT SECURITY ARCHITECTUREJSA

PIV PERSONAL IDENTITY VERIFICATION

GENERAL NOTES

1. ALL TELECOMMUNICATIONS WORK SHALL COMPLY WITH THE LATEST EDITION OF VA STANDARDS TELECOMMUNICATIONS INFRASTRUCTURE STANDARDS AND CURRENT MANUFACTURER AND BICSI

INSTALLATION PRACTICES. THESE STANDARDS HAVE BEEN ESTABLISHED TO EXCEED ALL CURRENT CODE AND BICSI INSTALLATION PRACTICE. ANY ITEMS THAT RAISE QUESTION SHALL BE BROUGHT TO THE ATTENTION OF THE CONSTRUCTION MANAGER AND REPRESENTATIVE IN WRITING. IT IS ALWAYS A BEST PRACTICE TO PROVIDE THE AHJ WITH DETAIL ON ANY AND ALL CONSTRUCTION ITEMS THAT COULD BE QUESTIONED BY THE AHJ. THE PROJECT DOCUMENTATION PACKAGE STANDARDS ARE NOT TO BE INTERPRETED NOR CONSIDERED AS AUTHORIZATION TO DEVIATE FROM ANY CODE OR REGULATION. IT IS THE CONTRACTOR ’S RESPONSIBILITY TO VALIDATE THAT THESE REQUIREMENTS WILL MEET THE EQUIPMENT MANUFACTURER ’S REQUIREMENT TO

PROVIDE A MINIMUM 25-YEAR SCS FOR ALL LABOR AND MATERIALS WARRANTIES.

2. IN THE EVENT OF A CONFLICT OR INCONSISTENCY BETWEEN ITEMS INDICATED ON THE PLANS AND/OR SPECIFICATIONS OR WITH THE AHJ REQUIREMENTS, THE DOCUMENT WHICH PRESCRIBES AND ESTABLISHES THE COMPLETE JOB AS PER MANUFACTURER OR THE HIGHER STANDARD SHALL PREVAIL. ALL DISCREPANCIES ARE TO BE BROUGHT TO THE ATTENTION OF THE CONSTRUCTION

MANAGER AND THE VA REPRESENTATIVE IN WRITING IMMEDIATELY UPON DISCOVERY.

3. OMISSIONS FROM THE DRAWINGS OR FROM THE SPECIFICATIONS OR THE MISDESCRIPTION OF DETAILS OF WORK WHICH ARE CLEAR AND NECESSARY TO CARRY OUT THE INTENT FOR THE DRAWINGS AND SPECIFICATIONS, OR WHICH ARE CUSTOMARILY PERFORMED SHALL NOT RELIEVE THE CONTRACTOR FROM PERFORMING SUCH OMITTED OR MISDESCRIBED DETAILS OF THE WORK.

THE CONTRACTOR SHALL NOTIFY THE CONSTRUCTION MANAGER AND VA REPRESENTATIVE UPON IDENTIFICATION OF SUCH OMISSIONS, MISDESCRIPTION, AND UNCLEAR DIRECTIONS IMMEDIATELY.

THE CONTRACTOR SHALL PERFORM ALL PROJECT TASKS AND ASSEMBLY BUILDS AS PER BICSI STANDARDS AND MANUFACTURER ’S REQUIREMENTS ALONG WITH COORDINATING AND WORKING

WITH THE VA TO CORRECT SUCH DOCUMENTATION ERRORS.

4. THE CONTRACTOR SHALL CHECK ALL DRAWINGS FURNISHED IMMEDIATELY UPON THEIR RECEIPT AND PROMPTLY NOTIFY THE VA OF ANY DISCREPANCIES. THIS INCLUDES BUT NOT LIMITED TO, DISCREPANCIES BETWEEN DRAWINGS AND SPECIFICATIONS, OR DRAWINGS AND MANUFACTURER INSTALLATION INSTRUCTIONS, OR DRAWINGS AND GOVERNING CODES AND BEST PRACTICES. THE CONTRACTOR SHALL BRING TO THE ATTENTION OF THE CONSTRUCTION MANAGER AND VA COR ANY DISCREPANCIES BETWEEN DRAWINGS AND HOW THE CONTRACTOR NORMALLY DELIVERS THE

SERVICES DESCRIBED IN THE DRAWINGS OR SPECIFICATIONS.

5. ALL MATERIALS AND EQUIPMENT FURNISHED AND INSTALLED SHALL BE NEW AND FREE FROM ANY KNOWN DEFECT. ALL EQUIPMENT SHALL BEAR THE UNDERWRITERS LABORATORIES LABEL (UL™) LISTING, CLASSIFIED, AND/OR PERFORMANCE VERIFIED MARK OR FROM A VA APPROVED ALTERNATIVE TESTING ORGANIZATION. ALL MATERIALS SHALL BE INSTALLED AND USED IN THE MANNER FOR WHICH THE MANUFACTURER INTEND THEM FOR. THIS APPLIES FOR BOTH PIECE PARTS AND COMPLETE FUNCTIONING ASSEMBLIES.

6. CONTRACTOR IS REQUIRED TO RECEIVE WRITTEN APPROVAL FOR ALL RECOMMENDED AND REQUIRED WORK DEVIATIONS AND CLARIFICATIONS TO THE PLANS AND SPECIFICATIONS OF THIS

PROJECT BY THE VA AND ITS REPRESENTATIVES PRIOR TO ANY FIELD ACTIVITY.

7. ALL WORK MUST BE COMPLETED IN AS PER MANUFACTURER INSTALLATION REQUIREMENTS AND BICSI INSTALLATION PRACTICES. THE VA DEMANDS THE UTMOST PROFESSIONALISM WHEN WORK IS BEING PERFORMED ON CAMPUS AND HOLDS ALL CONTRACTORS TO THAT LEVEL OF PROFESSIONALISM. THE WORK SITE SHALL BE KEPT CLEAN AND FREE FROM DEBRIS. IT IS EVERY CONTRACTOR AND ALL THEIR REPRESENTATIVE’S RESPONSIBILITY TO GUARD AGAINST ANY DAMAGE TO VA PROPERTY AND THE IMMEDIATE REPAIR IF ANY DAMAGE IS CAUSED. THE CONTRACTOR SHALL BE RESPONSIBLE FOR CONDUCTING A FINAL CLEANUP OF THE WORK SITE PRIOR TO FINAL SYSTEM ACCEPTANCE AS PART OF THE PUNCH-LIST PROCESS.

8. THE CONTRACTOR SHALL NOT BORE, NOTCH, OR IN ANY WAY CUT INTO ANY STRUCTURAL MEMBER WITHOUT WRITTEN APPROVAL FROM THE VA, ARCHITECT, AND STRUCTURAL ENGINEER. WITH PERMISSION FROM THE ABOVE AND PRIOR TO ALL CUTTING, DRILLING, NOTCHING, CORING, ETC. OF CONCRETE STRUCTURE AND FAÇADE THESE SURFACES SHALL BE X-RAYED OR GROUND PENETRATING RADAR USED TO ACCURATELY LOCATE REBAR, POST-TENSION CABLES & RODS, CONDUITS, AND ANY OTHER EMBEDDED POTENTIAL OBSTRUCTIONS TO

ENSURE THAT NO DAMAGE IS CAUSED TO ANY STRUCTURAL REINFORCEMENTS.

9. FOR THE PURPOSE OF CLEARNESS AND LEGIBILITY THE TELECOM DRAWINGS ARE ESSENTIALLY DIAGRAMMATIC. THE SIZE AND LOCATION OF EQUIPMENT IS SHOWN TO SCALE WHEREVER POSSIBLE. THE CONTRACTOR SHALL VERIFY ALL FIELD CONDITIONS WITH INFORMATION INDICATED ON THE DRAWINGS AND DESCRIBED IN THE SPECIFICATION SECTIONS WHERE TELECOM WORK

INTERFACES WITH OTHER TRADES.

10. THE CONTRACTOR SHALL TAKE SPECIAL PRECAUTIONS WHEN WORKING IN AREAS WITH EXISTING CEILINGS AND SHALL BE RESPONSIBLE FOR REMOVAL AND REPLACEMENT OF CEILING TILES WITHOUT DAMAGING OR SOILING THE CEILING TILES. CHIPPED, DAMAGED, CRACKED, OR BROKEN TILES ARE THE CONTRACTOR ’S RESPONSIBILITY TO REPLACE WITH LIKE TILES.

11. ALL FOOTAGES IDENTIFIED ON DRAWINGS OR SCALED OFF OF DRAWINGS ARE TO BE CONSIDERED ESTIMATES AND ARE RECOMMENDED TO BE FIELD VERIFIED BY CONTRACTOR PRIOR TO

ORDERING OF MATERIAL

12. ALL CABLE TRAYS, LADDER (TYPE) RACKING, CONDUIT, EQUIPMENT RACKS, PROTECTION PANELS, AND CABLE SHEATHS SHALL BE BONDED TO AN APPROVED TELECOMMUNICATIONS BONDING

ASSEMBLY.

13. ACCORDING TO TIA STANDARDS AND BICSI METHODOLOGIES PULL-BOXES LOCATED WITHIN A STRUCTURE ARE TO BE PLACED AT 100 ’ INCREMENTS AND PROPERLY SPACED WITHIN RUNS OF MORE THAN 150’. PULL-BOXES ARE TO BE PLACED IN CONDUIT RUNS THAT EXCEED A MAXIMUM OF 180-DEGREES IN CHANGES OF DIRECTION. TELECOMMUNICATIONS PULL-BOXES ARE TO BE SIZED AT A MINIMUM OF TWELVE (12) TIMES THE DIAMETER OF THE LARGEST CONDUIT. PULL-BOXES SHOULD NOT BE USED FOR CHANGES OF DIRECTION. THESE STANDARDS ARE TO BE ADHERED TO WHERE EVER PRACTICAL AND ANY DEVIATION TO THESE STANDARDS REQUIRES A SHOP-DRAWING, IF DISCOVERED DURING THE SUBMITTAL PHASE, TO REMEDIATE THE ISSUE OR BY AN RFI DURING THE CONSTRUCTION INSTALLATION PHASE. THE VA MAY ELECT TO INCREASE THE CONDUIT SIZE OR QUANTITY OF CONDUITS TO MITIGATE THE ISSUE FOR THE EXCESS LENGTH, ADDITIONAL QUANTITY OF CHANGES OF DIRECTION, AND/OR THE REDUCED SIZE OF PULL-BOXES WITHIN THE GIVEN PATHWAY. THE CONTRACTOR IS REQUIRED TO HAVE APPROVAL IN WRITING PRIOR TO ANY ROUGH-IN

WORK OR MATERIAL PROCUREMENT.

14. AS A STANDARD, ALL INTER-BUILDING PATHWAYS SHALL HAVE A MINIMUM OF 20% AVAILABLE CAPACITY AT THE SCHEDULED END OF THE PROJECT. SHOULD THIS PERCENTAGE NOT BE ACHIEVABLE, THIS ISSUE MUST BE BROUGHT TO THE ATTENTION OF THE CONSTRUCTION MANAGER AND THE VA REPRESENTATIVE.

15. WHERE PATHWAY CONSISTS OF MULTIPLE CONDUITS OR SLEEVES, A PATHWAY MUST BE FILLED TO CURRENT TIA AND BICSI INSTALLATION RECOGNIZED MAXIMUM FILL BEFORE UTILIZING THE NEXT

VACANT OR PARTIALLY FILLED PATHWAY.

16. OVERHEAD AND WALL MOUNTED LADDER (TYPE) RACKING INSTALLATION SHALL MATCH THE DRAWINGS AS CLOSELY AS POSSIBLE AND REQUIRES A SHOP DRAWING FOR EACH ROOM LOCATION.

THE PACKAGE IS TO INCLUDE A BILL OF MATERIALS WITH PART NUMBERS FROM RACKING MANUFACTURER FOR MOUNTING AND CONNECTION PIECE PARTS. PRIOR TO ANY ROUGH-IN WORK BEING

PERFORMED THESE SUBMITTALS MUST BE APPROVED BY THE VA REPRESENTATIVE.

17. ALL CABLING AND THEIR PATHWAYS PASSING THROUGH A RATED FIRE OR SMOKE BARRIER MUST BE PROPERLY SLEEVED AND FIRE STOPPED USING APPROVED (UL CLASSIFIED) FIRE STOP ASSEMBLIES. FIRESTOP ASSEMBLIES ARE TO BE INSTALLED PER THE MANUFACTURER ’S INSTRUCTIONS FOR THE TYPE OF BARRIER, PATHWAY SIZE, AND QUANTITY OF CABLES THE FIRESTOP ASSEMBLY IS BEING INSTALLED FOR. CONTRACTOR IS REQUIRED TO MAINTAIN TRAINING RECORDS FOR ALL STAFF PERFORMING FIRESTOP ASSEMBLY INSTALLATION WORK.

18. CABLE PULLING – LINE/ROPE/TAPE SHALL BE PLACED IN ALL NEW CONDUITS. ALL CONDUITS SHALL ALSO BE CAPPED AND/OR PROPERLY FIRE STOPPED IN A MANNER APPROVED BY THE VA AND THE

AHJ.

19. EACH OSP CABLE SHALL BE EQUIPPED WITH A PERMANENT LABEL INDICATING CABLE TYPE, PAIR OR OPTICAL STRAND COUNTS, DISTANT END COMMONLY USED BUILDING NAME/NUMBER AND CABLE LENGTH. BOTH ENDS OF EACH CABLE SHALL BE LABELED CLEARLY SO THAT THEY CAN BE EASILY MATCHED TO EACH OTHER.

20. ALL CABLE SPLICES SHALL BE CONTAINED WITHIN AN APPROVED SPLICE CASE DESIGNED FOR THE LOCATION AND PURPOSE. THE SUBMITTAL FOR THE ENCLOSURE SHALL IDENTIFY WEATHER THE ENCLOSURE IS RE-ENTERABLE. AS PART OF THE SUBMITTAL A LISTING OF ANY AND ALL ADDITIONAL PARTS ARE REQUIRED TO RESTORE THE INTEGRITY OF THE ENCLOSURE SHOULD THE SPLICE

CASE BE REQUIRED TO BE ENTERED OPERATIONALLY.

21. OPTICAL FIBER CABLE SHALL BE PLACED WITH A MINIMUM OF THREE (3) METER MAINTENANCE LOOP AT EACH END OF THE RUN, AT EACH SIDE OF A SEISMIC JOINT, IN EACH MAINTENANCE HOLE (MH), VAULT, ETC. THE MAINTENANCE LOOP SHALL BE SECURED IN SUCH A MANNER TO PROVIDE MECHANICAL PROTECTION OF THE CABLE. AS PART OF THE SUBMITTAL PHASE THE CONTRACTOR IS TO PROVIDE SINGLE-LINE SHOP DRAWINGS OF THE LOCATIONS OF ALL MAINTENANCE LOOPS AND TO INCLUDE ANY RECOMMENDED LOOPS TO BE ADDED IN PULL-BOXES FOR EACH INDIVIDUAL

PATHWAY RUNS.

22. ALL OPTICAL FIBER CABLE SHALL BE TESTED USING ANSI/TIA STANDARDS AND BICSI INSTALLATION APPROVED TESTING PLATFORM. THIS TEST MUST BE PERFORMED BI-DIRECTIONALLY ON ALL STRANDS AND ALL RECORDS ARE TO BE OPENED AND VIEWED IN A STANDARD PLATFORM THAT DOES NOT CAUSE THE VA TO PURCHASE OR LICENSE FOR SUCH VIEWING. THE VA AT ITS DESECRATION MAY REQUIRE TO SEE THE TESTER’S CALIBRATION RECORD AND WILL NOTIFY THE CONTRACTOR OF THIS REQUEST PRIOR TO OR POST TESTING OPERATION. ALL BI- DIRECTIONAL

TESTING SHALL PERFORM TO THE FOLLOWING STANDARDS:

A. ANSI/TIA - 568.3-D

B. ANSI/TIA - 526.7

C. ANSI/TIA - 455

23. OPTICAL FIBER CABLE SPLICING SHALL UTILIZE FUSION SPLICING TECHNIQUES AND REQUIRE A SHOP DRAWING DURING THE SUBMITTAL PHASE OF THE PROJECT PRIOR TO ANY ROUGH-IN. ANY AND ALL CABLE SPICING REQUIRES A WRITTEN APPROVAL BY THE VA BEFORE ANY MATERIAL PURCHASING OR ROUGH-IN.

24. CONTRACTOR TO COORDINATE WAO AND SUPPORTING CONDUIT AND CABLE TRAY WITH THE ELECTRICAL CONTRACTOR WHERE THE ELECTRICAL CONTRACTOR IS A DIFFERENT ORGANIZATION

THAN LOW-VOLTAGE CABLING/CONDUIT CONTRACTOR FOR PROPER PLACEMENT.

25. ALL STATION CABLES SHALL BE NEATLY DRESSED AND SECURED EVERY FIVE FEET AT A MINIMUM.

26. ALL VA-IT STATION CABLES SHALL BE TERMINATED ON THE SAME FLOOR AS THE FLOOR SERVING BDF/IDF UNLESS OTHERWISE NOTED IN THESE DRAWINGS.

27. ALL STATION CABLING IS TO BE MECHANICALLY PROTECTED IN PLACE UNLESS OTHERWISE IDENTIFIED IN THESE DRAWINGS, BY A CONTRACT CHANGE RECORD, OR BY A RFI RESPONSE FROM THE

VA REPRESENTATIVE IN WRITING DIRECTING SURFACE-MOUNT EXPOSED AS THE CABLE INSTALLATION MEANS.

28. ALL NEW STATION CABLES SHALL BE TESTED AND DOCUMENTED USING RECOGNIZED MANUFACTURER INSTALLATION REQUIREMENTS AND BICSI INSTALLATION PRACTICES. UTP (CATEGORY) CABLE

TESTING RESULTS SHALL BE ONE TEST RECORD FOR EACH CABLE AND THE RECORD MUST INCLUDE THE VA APPROVED CABLE IDENTIFICATION STANDARD NAMING/NUMBERING SCHEME. OPTICAL FIBER TESTING SHALL FOLLOW ALL VA AND MANUFACTURER INSTALLATION PRACTICES. COAX TESTING SHALL FOLLOW BOTH VA AND SCTE CABLE TESTING PRACTICES.

29. THE VA REQUIRES A ONE (1) METER SLACK LOOP FOR ALL WAO SUPPORTED BY OPEN CEILING CABLE DISTRIBUTION. THE SLACK LOOP MUST BE SUPPORTED ABOVE THE WAO IN NEAT AND REPEATABLE FASHION THAT MEETS BOTH BICSI INSTALLATION AND MANUFACTURER PRACTICES.

30. ALL STATION OUTLETS, WAO, AND TERMINATION POINTS INCLUDING EXISTING WAO UTILIZED UNDER THIS PROJECT SCOPE SHALL BE PROPERLY LABELED AND IDENTIFIED USING THE STANDARD VA INTERNAL DISTRIBUTION NAMING/NUMBERING SCHEME. ALL LABELS ARE TO BE MACHINE GENERATED AND AN EXCEL TYPE MATRIX CREATED DEFINING LOCATION OF BOTH ENDS OF EACH LABELED CABLE. AS-BUILT CLOSEOUT PACKAGE MUST INCLUDE THESE STATION AND TERMINATION POINTS IDENTIFIED ON FLOOR PLANS FOR EACH LEVEL/FLOOR IN ADDITION TO THE STATION CABLING MATRIX. THE SAME CABLE IDENTIFICATION IS ALSO REQUIRED TO BE INCLUDED ON EACH CABLE TESTED RECORD BOTH HARD AND SOFT-COPY RECORD.

31. STANDARD WORKSTATION OUTLET (AKA WORK AREA OUTLETS OR WAO) SHALL CONSIST OF A 5S X 2-7/8 ” DEEP METAL BOX, FED WITH A MINIMUM 1-1/4” CONDUIT. BACK BOX TO BE FITTED WITH

SINGLE-GANG FINISH RING FOR 6-PORT FACEPLATE.

32. STANDARD WAO FACEPLATE SHALL CONSIST OF A SINGLE-GANG PLATE, 6-POSITION, WHITE IN COLOR, AND UNIVERSAL MULTI-PURPOSE PORTS TO SUPPORT THE FOLLOWING TERMINATIONS; UTP, SCTP, COAX, OPTICAL FIBER, USB, VARIOUS A/V CONNECTORS, ETC. ALL UNUSED PORTS SHALL BE FITTED WITH BLANK INSERTS.

33. STANDARD WORKSTATION CONSISTS OF A MINIMUM OF FOUR (4) CATEGORY 6a, CMP, GRAY, BLUE, AND WHITE CABLES.

34. INCLUDED AS PART OF THE CABLING AS-BUILT DOCUMENTATION PACKAGE, IT IS THE CONTRACTOR ’S RESPONSIBILITY TO PROVIDE TO THE VA THE STRUCTURED CABLING SOLUTION

MANUFACTURER’S 25-YEAR WARRANTY CERTIFICATE FOR THE PROJECT.

35. THE WAO UTP 8-CONDUCTOR JACKS ARE DESCRIBED WITHIN THIS DOCUMENT SET AS RJ-45 JACKS/INSERTS. THE DESIGNERS ARE AWARE THAT ABBREVIATION RJ-45 IS A FCC –REGISTERED JACK

WITH 8-CONDUCTORS AND DESCRIPTION IN THIS DOCUMENT SET IS FOR A UTP CATEGORY CABLE RATED JACK/INSERT AND NOT FOR FCC INTERFACE JACKS.

36. ALL NEW CABLING SHALL CONFORM TO THE SCS INCLUDING BEING INSTALLED BY A CERTIFIED INSTALLER AND SIGNED OFF BY A MANUFACTURER REPRESENTATIVE.

37. NOT ALL SYMBOLS AND ABBREVIATIONS SHOWN ON THIS SHEET ARE USED IN THE DRAWING SET CURRENTLY, BUT ARE THERE, SHOULD THE SCOPE GROW TO INCLUDE SUCH WORK.

38. THE CONTRACTOR SHALL PROVIDE WIRE GUARDS FOR ALL EXPOSED AUDIO, VISUAL, AND NETWORK DEVICES LOCATED IN AREAS THAT CAN BE SUBJECT TO VANDALISM SUCH AS WAITING ROOMS, RESTROOMS, LOCKER AND SHOWER ROOMS, MULTI-PURPOSE/DINING, CHECK-IN AREAS/LABS, & ASSEMBLY ROOMS. AND ALL HALLWAYS AND CORRIDORS ASSOCIATED WITH THESE SPACES

39. ALL CONDUITS CROSSING BUILDING SEISMIC SEPARATIONS OR EXPANSION JOINTS SHALL BE PROVIDED WITH APPROVED CONNECTORS. REFER TO ARCHITECTURAL PLANS FOR ALL EXPANSION

JOINT LOCATIONS.

40. COORDINATE INSTALLATION OF LIGHTING FIXTURES WITH CABLE TRAY AND EQUIPMENT IN BDF, IDF, AND ALL A/V ROOMS/SPACES TO MAINTAIN REQUIRED LIGHTING LEVELS WITH ALL EQUIPMENT IN

PLACE.

41. FOR THOSE ELEMENTS THAT DO NOT REQUIRE DETAILS OR SHOP DRAWINGS ON THE APPROVED DRAWINGS, THE INSTALLATION SHALL BE SUBJECT TO THE APPROVAL OF THE ELECTRICAL

ENGINEER AND THE FIELD REPRESENTATIVE FOR THE VA.

42. VA, MANUFACTURER, BICSI INSTALLATION PRACTICES FOR PROJECT SUBMITTALS AND SHOP DRAWINGS ARE IDENTIFIED IN SPECIFICATIONS SECTIONS LISTED IN DIVISION 26, 27, AND 28, OF THE

PROJECT CONTRACT DOCUMENTATION SET.

43. J-HOOK ROUTING IS AN "IN-THE-FIELD" INSTALLATION CHOICE AND SHALL BE REQUIRED TO BE DOCUMENTED ON ALL AS-BUILT PACKAGES. SLEEVES REQUIRED TO COMPLETE THESE J- HOOK

ROUTINGS SHALL BE CONSIDERED AND INCLUDED IN THE J-HOOK ROUTE EQUIPMENT PACKAGE FROM THE CONTRACTOR AS CPCI PATHWAY EQUIPMENT. J-HOOK SLEEVES THROUGH RATED AND NON-RATED ASSEMBLIES SHALL NOT BE A REQUIREMENT OF THIS DRAWING PACKAGE AS THEY ARE FIELD DEFINED LOCATIONS AND QUANTITIES.

44. CONTRACTOR SHALL SUBMIT COORDINATION DRAWINGS SHOWING ALL PROPOSED CABLE ROUTING, CABLE TRAY LOCATIONS AND SIZING, J-HOOK LOCATIONS, PENETRATIONS, DEVICE LOCATIONS, EQUIPMENT LOCATIONS, WAO LOCATIONS, ETC. PRIOR TO BEGINNING WORK. THESE DRAWINGS SHALL BE COORDINATED WITH NEW AND EXISTING SYSTEMS TO MAINTAIN ALL REQUIRED CLEARANCES AND ACCESS FOR NEW AND EXISTING EQUIPMENT. COORDINATION DRAWINGS MUST BE REVIEWED AND APPROVED BY VA/AE PRIOR TO BEGINNING INSTALLATION WORK.

45. CONTRACTOR SHALL SUBMIT PROPOSED NEW RACK ELEVATIONS FOR EACH TELECOMMUNICATIONS ROOM/ RACK PRIOR TO BEGINNING WORK. TERMINATION LOCATIONS AND RACK

CONFIGURATIONS SHALL BE APPROVED PRIOR TO BEGINNING WORK.

46. CONTRACTOR SHALL SUBMIT WEEKLY CABLE TESTING/ TERMINATION REPORTS FOR VA/AE REVIEW AS AREAS ARE COMPLETED TO ENSURE CABLE PERFORMANCE MEETS BICSI AND CONTRACT

REQUIREMENTS.

47. INFECTION CONTROL PROTOCOL SHALL BE MAINTAINED AT ALL TIMES, INCLUDING NEGATIVE AIR HEPA FILTERED CONTAINMENTS. MOBILE HEPA CARTS SHALL BE USED FOR CABLE PULLING ACTIVITIES AS REQUIRED BY THE SPECIFICATIONS. COORDINATE ALL ACTIVITY WITH THE VA. SEE SPECIFICATION SECTION 01 35 26 SAFETY REQUIREMENTS FOR ADDITIONAL INFORMATION.

STANDARD OUTLET INFORMATION

X ROOM NUMBER - OUTLET DESIGNATOR

W WALL PHONE JACK @ +42" AFF (ADA)

H WALL PHONE JACK @ +84" AFF (ADA)

WP WEATHERPROOF

AV AUDIO VIDEO CABLES (SPECIFIC USE,

INSTALLED POINT TO POINT)

# NUMBER (IDENTIFICATION) OR COUNT

(#) NUMBER IS QUANTITY

A/E ARCHITECT/ENGINEER

AH AMPERE HOUR

AUTHORITY HAVING JURISDICTIONAHJ

ASSISTIVE LISTENING SYSTEMALS

ACCESS POINTAP

ALUMINUM, STEEL, POLYETHYLENEASP

AMERICAN SOCIETY FOR TESTING AND MATERIALSASTM

AUDIOVISUAL CONTRACTORAVC

BMS

BLDG

BUILDING

BUILDING

BS-IDF

BRKR, BKR

BUILDING SERVICES INTERMEDIATE DISTRIBUTION

FRAME

BREAKER

BTU BRITISH THERMAL UNIT

CATV COMMUNITY ANTENNA TELEVISION (CABLE

TELEVISION)

C CONDUIT

CONDUIT ONLY - WITH PULL WIREC.O.

CONSOLIDATION POINTCP

CAPTURED SCREW CONNECTORCSC

DISTRIBUTION PANEL

DOUBLE POLE SINGLE THROW

DOUBLE POLE DOUBLE THROWDPDT

DWG

DPST

DIST

DISC

DC

DP

DN

DRAWING

DISTRIBUTION

DIRECT CURRENT

DISCONNECT

DOWN

DIV DIVISION

ELECTRIC WATER COOLER

ELECTRIC WATER HEATER

ELECTRIC, ELECTRICAL

ELECTRIC METALLIC CONDUIT

ELECTRICAL CONTRACTOR

EWC

EWH

ELEC

EQ, EQUIP

EM, EMERG

EMT

ELEV

ENCL

E.C.

EQUIPMENT

ELEVATOR

EMERGENCY

ENCLOSURE

EXISTINGE, EX, EXIST

X EMPTY (OUTLET WITH NO CABLE,

FUTURE USE).

F FURNITURE SYSTEM JACK

C COAXIAL CABLE RG-11

M WALL MOUNTED MONITOR

T VOIP - TELEPHONE

TV TELEVISION OUTLET

WAP WIRELESS ACCESS POINT

NOTES

1. WORK AREA OUTLET CONDUIT HAS BEEN DESIGNED FOR CATEGORY 6a CMP CABLE DISTRIBUTION WITH 5S BACK-BOX AND

1-1/4" IN CONDUIT.

2. FILL FACTOR IS CALCULATED USING 0.265 IN O.D. FOR SUPERIOR ESSEX CAT 6a CMP 77-246-YB AT A WEIGHT OF 23 LBS/KFT.

EACHEA

ENTRANCE FACILITYEF

EMI ELECTROMAGNETIC INTERFERENCE

EMS EMERGENCY MANAGEMENT SYSTEM

ENT ELECTRICAL NONMETALLIC TUBING

FLOOR BOXFB

FDC OPTICAL - FIBER DISTRIBUTION CENTER

FEXT FAR END CROSSTALK

FIN FINISH

FIXT FIXTURE

FOC FIBER OPTIC CABLE

FPS FRAMES PER SECOND

GA GAUGE

GC GENERAL CONTRACTOR

GALVANIZD RIGID CONDUITGRC

INTERCOM

IDF

INSIDE DIAMETER OR INSIDE DIMENSION

INTERMEDIATE DISTRIBUTION FRAME

ID

IC

ISP INTERNET SERVICE PROVIDER

M METER

MAC MEDIA ACCESS CONTROL

MDF MAIN DISTRIBUTION FRAME

MM MULTI-MODE

MOB MEDICAL OFFICE BUILDING

MTU MULTI TENNET UNIT

WS WORK STATION

WiFi WIRELESS FIDELITY (LOCALIZED WIRELESS USER

ACCESS INTERNET/NETWORK)

WAO WORK AREA OUTLET / WORK STATION OUTLET

WBS WORK BREAKDOWN STRUCTURE

V-A VOLTS-AMPERES

ND NETWORK DEVICE

NE NETWORK ENCLOSURE

NATIONAL ELECTRICAL MANUFACTURERS

ASSOCIATION

NEXT NEAR END CROSSTALK

OF OPTICAL FIBER

OSP OUTSIDE PLANT

OTDR OPTICAL TIME DOMAIN REFLECTOMETER

POE POWER OVER ETHERNET

PPF PIXELS PER FOOT

PR PAIR

PSU POWER SUPPLY UNIT

PTP POINT-TO-POINT

REQ'D REQUIRED

RM ROOM

RMC RIGID METAL CONDUIT

RMS RACK MOUNTED SPACE

RNC RIGID NONMETALLIC CONDUIT

RU RACK UNIT

SAC SECURITY AND ACCESS CONTROL

SCS STUCTURED CABLING SOLUTION

ScTP SCREENED TWISTED PAIR

SM SINGLE-MODE

SNR SIGNAL TO NOISE RATIO

SQ SQUARE

STP SHIELDED TWISTED PAIR

SYS SYSTEM

TCP/IP TRANSMISSION CONTROL PROTOCOL/

INTERNET PROTOCOL

TE TELECOMMUNICATION ENCLOSURE

TGB TELECOMMUNICATIONS GROUNDING BUSBAR

TMGB TELECOMMUNICATIONS MAIN GROUNDING BUSBAR

TR TELECOMMUNICATIONS ROOM OR SPACE

UD UNDERGROUND DUCT

UTP UNSHIELDED TWISTED PAIR

11/09/2023

11/09/2023

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

CONSULTANT

321 4 5 6 7 8 9 10

TRIPLE C - The A/E Group 201 E. Jefferson Street, Suite 200 Syracuse, NY 13202

MAT PERKINS

(315) 484-5958

STAMP

01_02

Au to de sk

D oc s:

//6

A4

-2 2-

0_

N ew in gt on _V

AM

C

_E H

R M

_I U

-1

2/

9A 4-

-7

.N ew in gt on

.E H

R M

.M

EP

.G en er al

.S he et s.

rv t

-0

1-

2:

:0

AM

01T-001

TELECOMMUNICATION ABBREVIATIONS AND

SYMBOLS

689A4-22-700

11/09/2023 M. Perkins K. McDermott

ISSUED FOR

CONSTRUCTION

EHRM INFRASTRUCTURE

UPGRADES

555 Willard Avenue, Newington, CT 06111

Revisions: Date:

UP

UP

UP

UP

UP

ELEV MACH RM

2C-B00

ELEV #S3

E8

STAIR #7

CS007

SVC LOBBY

CB-25

CANTEEN STORAGE

CB-24A

CORRIDOR

CB-24

CANTEEN OFFICE

B-103HAC

B-102

RETAIL STOCK RM

B-101

RETAIL STORAGE

B-112

AREAWAY EXTERIOR

OF BLDG.

CANTEEN OFFICE

E10

ELECT.

B-162

LAB PRESCR PICKUP

2E-B116B

LAB ENTRY AND MAIL

2E-B118

LAB

2E-B15A

LAB

2E-B119

AREAWAY EXTERIOR

OF BLDG.

LAB OFFICE

2E-B124E

LAB OFFICE

2E-B124F

LAB STORAGE

2E-B124D

STAIR #1

B001

DRIVE DOWN

CONCRETE PAVEMENT

OFFICE LAB

2E-B124C

HAC

2E-B123

LAB OFFICE

2E-B124

LAB EQUIP. RM

2E-B124B

STORAGE LAB

2E-B124A

CORRIDOR

B033

CORRIDOR

B032

CORRIDOR

B030

CORRIDOR

B116

CORRIDOR

B117

LAB EMPLOYEE

LOUNGE

2E-B131

LAB STAFF LOCKER

2E-B130

TOILET

2E-B131A

TOILET

2E-B130A

LAB BREAK RM

2E-B129

REF. STORAGE

2E-B128 MEDICAL RECORDS

2E-B127

TELECOM ROOM

2E-B140

STAFF TOILET

2E-B135B

STAFF TOILET

2E-B135A

STAIR #2

B002

C O M M U N

IC

A

TI

O N

2E -B

WAITING

2E-B042

ELECTRICAL

2E-B139

C O R R

ID

O R

B

CONFERENCE RM

2E-B137A

HIMS SPVSP

2E-B137B

HIMS SUPV OFFICE

2E-B137C

OFFICE

2E-B140G

WORK RM

2E-B137

MECH EQUIP.

2E-B133

ELEV #P3

2E-B013

ELEV #P2

2E-B012

ELEV. #P1

2E-B011

ELEV #S2

2E-B015

ELEV #S1

2E-B014

C O M M U N

IC

A

TI

O N

C

LO

SE

T

2E -B

LI

N

EN

2E -B

TR

A

SH

2E -B

B U

IL

D

IN

G S

TO

R A G E

2E -B

EL

EC

TR

IC

A L

2E -B

STAIR #3

B003

CORRIDOR

B056

PATIENT ELEVATOR

LOBBY

B021

CORRIDOR

B022

FE

M A

LE

S

TA

FF

LO

C K

ER

2E -B

STAFF LOUNGE

2E-B154

TOILET

2E-B155A

TOILET

2E-B153A

AREA

B050

HAC

2E-B149

CORRIDOR

B048

DISPATCH

2E-B049

CLEAN RECEIVING AND

BREAKOUT

2E-B148

BULK STORAGE

2E-B148A

WORK RM

2E-B147

CHIEF SPD

2E-B146A

SPD CLERKS

2E-B146

SU

M P R M

2E -B

C O R R

ID

O R

B

CORRIDOR

B043

MALE STAFF LOCKER

2E-B153

MECH. EQUIP.

2E-B157B

SOILED RECEIVING/

DECONTAM

2E-B156

STERILE

2E-B157A

PREP. ASSEMBLY AND

STERILIZATION

2E-B157

HAC

2E-B152

MANUAL EQUIP. WASH

2E-B150

AUTO CART WASH

2E-B151

STERILE/ NON-

STERILE STORAGE

2E-B144

CORRIDOR

B052

ETO

2E-B158

ETO

2E-B158A

HOLDING RM

2E-B144A

WOMEN'S TOILET

B-108

MENS TOILET

B-109

ENTRY/ EXIT

B-118

FOOD PREP

B-107

STORAGE

B-106

SERVING

B-105

CASHIER

B-110

FOOD COURT

B-111

DINING RM

B-115

CORRIDOR

B-119

PREP.

B-100

DISH WASHING

B-104

GENERATOR ROOM

ROOM

ROOM

ROOM

ROOM

STAIRS

VESTIBULE

TELECOM ROOM

2E-B127A

02T-403 F7

262' - 0"

11/09/2023

11/09/2023

N

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

CONSULTANT

321 4 5 6 7 8 9 10

GENERAL NOTES

KEY PLAN

KEYNOTES

2W

TRIPLE C - The A/E Group 201 E. Jefferson Street, Suite 200 Syracuse, NY 13202

MAT PERKINS

(315) 484-5958

2C 2E

STAMP

Au to de sk

D oc s:

//6

A4

-2 2-

0_

N ew in gt on _V

AM

C

_E H

R M

_I U

-1

2/

9A 4-

-7

.N ew in gt on

.E H

R M

.M

EP

.B

_0 2_

R

.rv t

-0

1-

0:

:3

T-100

TELECOMMUNICATION PLAN - OVERALL

BUILDING FLOOR PLAN - BASEMENT

689A4-22-700

01_02

11/09/2023 M. Perkins K.

MCDERMOTT

ISSUED FOR

CONSTRUCTION

EHRM INFRASTRUCTURE

UPGRADES

555 Willard Avenue, Newington, CT 06111

A.

B.

C.

D.

E.

F.

G.

H.

I.

J.

K.

L.

M.

N.

PROPERLY FIRE STOP AND SEAL ALL PENETRATIONS THROUGH WALLS,

FLOORS, CEILINGS, AND ROOF AS PER OWNER, CODE, AND AHJ.

PRIOR TO INSTALLATION OF CABLE TRAY COORDINATE LOCATIONS WITH ALL

OTHER TRADES AND PROVIDE COORDINATION DRAWINGS FOR REVIEW. ALL

NEW CABLE, CABLE TRAY, J HOOKS SHALL BE INDEPENDENTLY SUPPORTED &

NOT CAUSE ADDITIONAL LOAD ON OTHER SYSTEMS.

NOT ALL PARTS AND PIECES ARE SHOWN FOR A COMPLETE SYSTEM.

CONTRACTOR IS RESPONSIBLE FOR PROVIDING A COMPLETE END-TO-END

WARRANTED SOLUTION FOR THE CABLING.

ALL CABLING TO BE PLENUM RATED THROUGHOUT THE BUILDING.

ALL COMMUNICATIONS AND WIRELESS ACCESS POINT CABLING TO MEET OR

EXCEED CATEGORY 6A STANDARDS.

SEE E-501 FOR DEVICE STANDARD MOUNTING HEIGHTS.

ALL CONDUITS FOR TELECOMMUNICATIONS OUTLETS SHALL BE STEEL THIN

WALL ELECTRICAL METALLIC TUBING (TYPE EMT) UNLESS OTHERWISE NOTED.

UNDER NO CIRCUMSTANCES SHALL FLEXIBLE CONDUIT BE USED FOR

PATHWAYS INDICATED ON THIS DRAWING. ALL CONDUITS ARE TO BE, AT A

MINIMUM, 1-1/4" TRADE SIZE, UNLESS OTHERWISE NOTED. ALL CONDUITS FOR

TELECOMMUNICATIONS OUTLETS ARE TO BE STUBBED TO NEAREST CABLE

TRAY. CONTRACTOR IS TO ENSURE THAT NO CONDUIT EXCEEDS 40% FILL. IF

EXISTING CONDUIT IS NOT LARGE ENOUGH TO SUPPORT NEW CAT 6A CABLE

TO REPLACE ALL EXISTING CIRCUITS ONE-FOR-ONE, CONTRACTOR SHALL

PROVIDE THE MAXIMUM ALLOWABLE NEW CAT 6A CIRCUITS TO REPLACE

EXISTING. THE ADDITIONAL NEW CIRCUITS TO COMPLETE THE ONE-FOR-ONE

REPLACEMENT SHALL BE PROVIDED AT THE NEAREST AVAILABLE DROP WITH

EXISTING CONDUIT CAPACITY.

ALL CONDUIT PATHWAYS SHALL BE PROVIDED WITH NYLON BUSHINGS TO

PROTECT CABLES, REGARDLESS OF WHETHER THEY TERMINATE IN A DEVICE

OR JUNCTION BOX.

TERMINATE, TEST, LABEL AND DOCUMENT ALL TELECOMMUNICATION CABLES.

CONTRACTOR SHALL AVOID ALL SYSTEMS SHUTDOWNS, INSTALL NEW

EQUIPMENT PRIOR TO THE RENOVATION OF EXISTING EQUIPMENT; PROVIDE

TEMPORARY UTILITIES AS REQUIRED TO MEET THIS REQUIREMENT.

THE DEMOLITION OF DEVICES SHALL INCLUDE ALL ASSOCIATED CABLING

BACK TO THE RACK.

LABEL DEVICE PLATES WITH A PERMANENT ADHESIVE LABEL FOLLOWING ALL

STANDARDS AND REQUIREMENTS, SEE DETAIL SHEETS FOR ADDITIONAL

INFORMATION

CONTRACTOR SHALL PROVIDE TWO SETS OF LAMINATED FINAL

TELECOMMUNICATION ONE-LINE, RACK ELEVATION, AND CABLE SCHEDULE

DOCUMENTS. HANG ON THE WALL WITHIN THE TELECOM ROOM.

REFER TO R-900 SERIES SHEETS FOR PHOTO DOCUMENTATION OF EXISTING

CONDITIONS.

O. FOR EXISTING SECURITY CAMERAS BEING RE-CABLED, MAINTAIN EXISTING

CAMERA ANGLE AND PROTECT IN PLACE.

P. ALL EXISTING PENETRATIONS NO LONGER BEING USED WILL BE FILLED WITH

RATED ASSEMBLY.

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

12.

13.

14.

15.

16.

17.

18.

19.

20.

21.

22.

23.

24.

PROVIDE NEW TELECOMMUNICATIONS OUTLET IN EXISTING LOCATION WITH

EXISTING EMT STUB UP TO NEAREST ACCESSIBLE CEILING SPACE. SEE DETAILS

ON SHEET T-501 FOR ADDITIONAL INFORMATION.

EXISTING WIRELESS ACCESS POINT TO BE RETAINED AND REUSED. PROVIDE

NEW CABLING AND TELECOMMUNICATIONS OUTLET. REFER TO DETAILS ON

SHEET T-501 FOR ADDITIONAL INFORMATION.

PROVIDE NEW 4-POST RACK, PDU, UPS AND WIRE MANAGEMENT COMPONENTS

AS SHOWN ON T-500 SERIES AND T-600 SERIES SHEETS AND IN THE

SPECIFICATIONS. PHASE TO PROVIDE NEW RACK IN A TEMPORARY LOCATION

AND TRANSFER DATA CIRCUITS FROM THE EXISTING RACK TO THE NEW RACK.

PROVIDE TEMPORARY EXTRA LENGTH JUMPER CABLES TO EXISTING SWITCHES

AND OTHER DEVICES TO ENSURE UNINTERRUPTED SERVICE. ONCE ALL EXISTING

DATA CIRCUITS ARE RELOCATED TO NEW PATCH PANELS ON THE NEW RACK AND

ALL EXISTING DEVICES TO REMAIN ARE TRANSFERRED TO THE NEW RACK,

REMOVE THE EXISTING RACK AND INSTALL THE NEW RACKS IN THE FINAL

PERMANENT POSITION.

PROVIDE NEW VERTICAL WIRE MANAGEMENT SYSTEM, SEE SPECIFICATIONS FOR

ADDITIONAL INFORMATION.

EXISTING CABLING CONDUIT AND WIREWAYS ARE TO REMAIN AND BE CAREFULLY

PROTECTED IN PLACE. ALL EXISTING DEVICES ON THE EXISTING RACK SHALL BE

TRANSFERRED TO THE NEW SECOND LEVEL LOCATION ON THE NEW RACK.

CONTRACTOR SHALL PROVIDE SHOP DRAWINGS SHOWING THE PROPOSED NEW

RACK ELEVATION AND PROVIDE A PHASING PLAN FOR TRANSFERRING ALL

EXISTING DEVICES TO REMAIN TO THE NEW RACKS.

PROVIDE NEW CABLE TRAY PER REQUIREMENTS LISTED IN CABLE TRAY

SCHEDULE. COORDINATE WITH EXISTING CONDITIONS AND SUBMIT

COORDINATION DRAWINGS FOR REVIEW PRIOR TO COMMENCING WORK.

COORDINATE FIXTURES WITH OVERHEAD TRAY. SEE T-500 SERIES SHEETS FOR

ADDITIONAL REQUIREMENTS. COORDINATE LIGHT FIXTURES WITH OVERHEAD

CABLE TRAY.

PROVIDE NEW IP ADDRESSABLE NETWORK CAMERA, POE+, PTZ, MOTION

SENSOR, AUTO-TRACKING, DOME WITH WALL MOUNT. BASIS OF DESIGN WISENET

XNP-6320. MOUNT AT 8’ – 6” A.F.F. TO TOP OF WALL BRACKET. INTEGRATE

CAMERA INTO EXISTING VMS. PROVIDE CONTROLLABILITY THROUGH EXISTING IT

NETWORK.

PROVIDE NEW DATA OUTLET, STUB-UP, AND BACK-BOX IN NEW LOCATION IN TR.

NEW 4” SPEED CONDUIT SLEEVE THROUGH WALL ABOVE CEILING GRID FOR

HORIZONTAL VOICE/DATA CABLING OR FIBER WITH PLASTIC BUSHINGS ON BOTH

ENDS TO PROTECT CABLES. FIRE CAULK PENETRATION PER SPECIFICATIONS.

EXISTING CONDUIT THROUGH WALL OR FLOOR WITH OPTICAL CABLE TO BE

PROTECTED IN PLACE UNTIL NEW SPEED CONDUIT SLEEVE AND FIBER IS

INSTALLED. DEMOLISH EXISTING CONDUIT ONCE NEW SPEED CONDUIT SLEEVE

AND FIBER ARE OPERATIONAL. CONTRACTOR SHALL PROVIDE A PHASING PLAN

FOR TRANSFERRING FIBER.

EXISTING EQUIPMENT TO REMAIN, PROTECT-IN-PLACE.

EXISTING WALL MOUNTED FIBER SPLICE WITH MULTI-MODE OPTICAL CABLE TO

BE PROTECTED IN PLACE UNTIL NEW SPEED FIBER IS INSTALLED. DEMOLISH

EXISTING FIBER SPLICE ONCE NEW SPEED CONDUIT SLEEVE AND FIBER ARE

OPERATIONAL. CONTRACTOR SHALL PROVIDE A PHASING PLAN FOR

TRANSFERRING FIBER.

PROVIDE NEW iSTAR EDGE (ESTAR002) ACCESS CONTROL SYSTEM. INSTALL PER

MANUFACTURERS RECOMMENDATIONS.

ALL EXISTING ANALOG PHONE CABLE DEVICES AND TERMINATIONS ETC. SHALL

REMAIN OPERATIONAL AT ALL TIMES AND SHALL BE RETAINED AND REUSED.

PROTECT IN PLACE.

HORIZONTAL CABLE LENGTH LIMITATIONS PER STANDARD 3.1.

VERTICAL ROUTE FOR TELECOM RISER. SEAL ALL FLOOR PENETRATIONS TO

MAINTAIN FIRE RATING.

CONTRACTOR SHALL FIELD VERIFY EXISTING TELECOMMUNICATIONS EQUIPMENT

TO BE DEMOLISHED PRIOR TO COMMENCING WORK.

BATTERY AND UPS CABINET ENCLOSURE, SEE SHEET 01E-601 FOR ADDITIONAL

INFORMATION.

PROVIDE NEW 20" X 4" BONDING BAR, SET OF INSULATORS STAND-OFF

BRACKETS, AND STAINLESS STEEL SCREWS. PROVIDE ALL GROUNDING CABLE

AND CONNECTORS AND INSTALL PER TYPICAL DETAIL ON T-500 SERIES SHEETS.

PROVIDE INDOOR COMPUTER ROOM AIR CONDITIONER (CRAC) UNIT. NEW CRAC

UNITS SHALL BE INTEGRATED WITH FACILITY AUTOMATED LOGIC CONTROLS

BUILDING MANAGEMENT SYSTEM. COORDINATE FINAL LOCATION AND CRAC

DESIGNATION WITH COR.

PROVIDE NEW 16" X 4" BONDING BAR, SET OF INSULATORS STAND-OFF

BRACKETS, AND STAINLESS STEEL SCREWS. PROVIDE ALL GROUNDING CABLE

AND CONNECTORS AND INSTALL PER TYPICAL DETAIL ON T-500 SERIES SHEETS.

EXISTING PACS AND EQUIPMENT RACKS

FUTURE PACS/FMS HEAD-END EQUIPMENT

NEW INDOOR UNIT

NOTE: NOT ALL KEYNOTES

ARE USED ON EACH SHEET

SCALE: 1/16" = 1'-0"F1

TELECOMMUNICATION PLAN -

OVERALL BUILDING FLOOR PLAN -

BASEMENT

SCALE: 1" = 100'-0"B7

DIAMOND ANALYSIS - OVERALL

BUILDING FLOOR PLAN - BASEMENT

LEVEL

UP

UP

UP

UP

UP

UP

UP

UP

UP

UP

UP

TRNG BATH

1N-101A

TRNG KITCHEN

1N-101

OCCUPATIONAL

THERAPY

1N-109

STORAGE

1N-109B

OCCUPATIONAL

THERAPY

1N-109A

COMMUNICATION

ELECTRICAL

1N-110

1N-112

1N-115

C O R R

ID

O R

1N -C 1-

1N-114

1N-116

PROSTHETIC STORAGE

RM

1C-146

1-146A

ELEV

ELEV

STAIR #2

OFFICE EXAM

OFFICE EXAM

172 OFFICE EXAM

CONTROL RM

174A

EXAM RM

174B

1S-175A

WAITING ARA

1S-168

1S-170A

TOILET

1S-169

1S-170C

ISOTOPIC ST

1S-175

OFFICE

1S-177

ELECTRICAL RM

1S-179

CORRIDOR

1S-C1-4

MECH

1S-176

ISOTOPIC ST

1S-178

PUMP RM

1S-180

RECEPTION

1S-171A

C O R R

ID

O R

1S -C 1-

TELEPHONE RM

1S-164

MECH RM

1S-167

TELEPHONE RM

1C-143

TELECOM ROOM

1C-142

1C-141

C O R R

ID

O R

1C -C 1-

CORRIDOR

1C-C1-7

LOCK SMITH

1C-145

STAIR #1

HOSPITAL WHEEL

CHAIR STORAGE

1C-147

TOILET

1C-148G

CORRIDOR

1C-C1-8

ELECT.

1S-162-0

H O T W A

TE

R H

EA

TE

R S

1S -1 -0

MECH

1S-165

TOILET

1S-166

COMM-ELEC

WALK IN COOLER

1S-170B

CONTROL RM

174C

CONTROL RM

174F

EXAM RM

174D

EXAM RM

174E

AUDIOLOGY TEST

BOOTH

1N-117

1N-117A

C O R R

ID

O R

1N -C 1-

MSA

WAITING

STAFF

STAFF TLT

CORRIDOR

STORAGE

SOILED UTILITY

STRETCHER AREA

PIPE CHASE

106A

CONTROL

CORRIDOR

109 CT

INJECTION

CHANGING ROOM

TOILET

HSA

TOILET

READING

CORRIDOR

1N-C1-3

ELECTRICAL SERVICE

ROOM

TELECOM ROOM

2C-1155 EXAM RM

2C-1158

ANTI COAGULATION

CLINIC EXAM RM

2C-1154

EXAM RM

2C-1159

IT

2C-1156 O

FF

IC

E

2C -1

MECH. EQUIP.

2E-1160

SMALL STATION

2E-1169

SMALL STATION

2E-1170

SMALL STATION

2E-1171

LARGE STATION

2E-1172

ELECT

2E-1166

STAIR #2

COMMUNICATION

2E-1165

SOILED UTILITY

2E-1163

HAC

2E-1162

CHASE

MEDS

2E-1168

CLEAN UTILITY

2E-1164

EXAM RM

2E-1159

EXAM RM

2E-1158

STAFF TOILET

2E-1180

ST

A

FF

L O C K

ER

2E -1

EXAM RM

2E-1157

PHARMACY OFFICE

2E-1182

C O R R

ID

O R

EXAM RM

2E-1184

EXAM RM

2E-1185

NURSE OFFICE

2E-1183

CLINICAL PHARMACIST

OFFICE

2E-1156

EXAM RM

2E-1186

ELECTRICAL

2E-1187

TOILET

2E-1190

HAC

2E-1200

EXAM RM (TB)

2E-1191

EXAM RM

2E-1192

EXAM RM

2E-1193

EXAM RM

2E-1194

ECG RM

2E-1195 C H

EC

K

- I N W A

LK

-IN

2E -1

TELECOM ROOM

2E-1178

URGENT CARE

STATION

2E-1050

SMALL STATION

2E-1173

LIFE SUPPORT

2E-1174

LIFE SUPPORT

2E-1175

STRETCHER STORAGE

2E-1197

TOILET

2E-1176

TRIAGE RM

2E-1177

VESTIBULE

2E-1053

CHASE

WAITING RM

2E-1198FEMALE TOILET

2E-1198A

MALE TOILET

2E-1198B

DIR. OFFICE

2E-1199A

OFFICE

2E-1199B

PR

IM

A R Y M

EN

TA

L

H

EA

LT

H C A R E O

FF

IC

E

2E -1

SHAFT

LINEN CHUTE

LINEN CHUTE

TRASH

2E-1203

LINEN

2E-1202

EL

EC

T

2E -1

STAIR #3

ELEV. #S1

2E-1014

ELEV #S2

2E-1015

EXAM RM

2E-1189

EXAM RM

2E-1188

ELEV #P3

2E-1013

ELEV #P2

2E-1012

ELEV #P1

2E-1011

C O M M U N

IC

A

TI

O N

C

LO

SE

T

2E -1

SVC ELEV LOBBY

2E-1064 PSYCHIATRIC

INITIATIVE

2E-1063

CORRIDOR

CORRIDOR

CORRIDOR

CORRIDOR

C O R R

ID

O R

C 1-

CORRIDOR

CORRIDOR

C O R R

ID

O R

CORRIDOR

CONFERENCE RM

2E-1147

EXAM RM

2E-1146

EXAM RM

2E-1140

EXAM RM

2E-1145

EXAM RM

2E-1144

TOILET

2E-1139

CORRIDOR

C O R R

ID

O R

TELEPHONE

EXAM RM (TB)

2E-1143

EXAM RM

2E-1142

POLICE STORAGE

2E-1149A

PO

LI

C E

LO

C K

ER

2E -1

MALE TOILET

2E-1103

FEMALE TOILET

2E-1104

MALE TOILET

2E-1105

FEMALE TOILET

2E-1111

CORRIDOR

EXAM RM

2E-1117

ST

A

FF

T O

IL

ET

2E -1

MALE TOILET

2E-1112

EXAM RM

2E-1115

EXAM RM

2E-1116 TO

IL

ET

2E -1 6A

EXAM RM

2E-1123

TO

IL

ET

2E -1 3A

EXAM RM

2E-1124

EXAM RM

2E-1125

CORRIDOR

C O R R

ID

O R

CLEAN UTILITY

2E-1133

INTAKE

2E-1132

STAFF TOILET

2E-1109A

MEDS

2E-1109B

TRIAGE 2

2E-1138

TRIANGE 1

2E-1109

WORK RM

2E-1109

WORK RM

2E-1109

EXAM RM

2E-1135

FIRM MGR

2E-1136

EXAM RM

2E-1137

N U R

SE

M G R O

FF

IC

E

2E -1

EXAM RM (TB)

2E-1119

EXAM RM

2E-1120

EXAM RM

2E-1121

EXAM RM

2E-1122

EXAM RM

2E-1131

EXAM RM

2E-1130

EXAM RM

2E-1129

EXAM RM

2E-1128

EXAM RM

2E-1141

EXAM RM

2E-1154

SHAFT

PATIENT ELEVATOR

LOBBY

EXAM RM

2E-1155

INFO BOOTH

2E-1031

VET ID CARD OFFICE

2E-1151

REGISTRATION

2E-1150

CORRIDOR

WAITING

2E-1026

C O R R

ID

O R

VA POLICE

2E-1027

FIRM 2 ADMIN.

2E-1101

REGISTRATION

2E-1030

WAITING

2E-1029

CORRIDOR

CORRIDOR

WAITING

2E-1041

CHECK-IN 1ST FLOOR

PRIMARY CARE

2E-1036

C O R R

ID

O R

CORRIDOR

C1-2

2E-1023

OFFICE

2C-1136

ELECT

2C-1135

ROOM

2E-1028

PATIENT ADVOCATE

OFFICE

2C-1130

OFFICE

2C-1129

COMP AND PAN

2C-1128

AUDIOLOGY

CONFERENCE RM

2C-1127

COMP AND PAN RM

2C-1126

EYE CLINIC

2C-1125

EXAM TELEHEALTH

2C-1124

TELEHEALTH

STORAGE

2C-1123

TELEHEALTH OFFICE

2C-1140

ROOM

2E-1043

COMP AND PAN OFFICE

2C-1138

AUDIOLOGY OFFICE

2C-1137

MECH BELOW

C O R R

ID

O R

2C -C 1-

WAITING

2C-1141

CHASE

ELEV #S3

STAIR #7

SVC LOBBY

2C-C1-9

TOILET

2C-1119B

STORAGE

2C-1119A

CASHIER

2C-1120

COMMUNICATION

2C-1121

COMMUNICATION CTR

2C-1119

C O R R

ID

O R

2C -1

ELECTRICAL

2C-1122

CASE MGR OFFICE

2C-1116

RN OFFICE

2C-1115

WAITING

2C-1029

OFFICE

2C-1117

SOCIAL WORKER

2C-1118

STAIR #6

DAV TRANSPORTATION

2C-1108B

TOILET

2C-1108C

DRIVERS OFFICE

2C-1108A

FIRMI ADMIN. OFFICE

2C-1101

STORAGE FOR

PRIMARY CARE

2C-1100

BLOOD DRAW

2C-1111

STAIR #5

PR

O

ST

H

ET

IC

S

2C -1

CORRIDOR

2C-C1-3

OFFICE

2C-1112

HAC

2C-1113

PROSTHETICS

2C-1114

HR/ PIV OFFICE

2C-1131

MALE TOILET

2C-1132

FEMALE TOILET

2C-1133

CORRIDOR

2C-1031

CORRIDOR

2C-1032

CORRIDOR

2C-1027

DAV TRANSPORTATION

2C-1108

ACCENT OFFICE

2C-1107

DAV TRANSPORTATION

OFFICE

2C-1108D

TOILET

2C-1106

TOILET

2C-1105

VENDING RM

2C-1104

ST

O R A G E

M A

LE

T O

IL

ET

2C -1

COUMADIN

2C-1153

ANTI COAGULATION

CLINIC

2C-1160

STAIR #4

COMP AND PEN CLINIC

EXAM RM

2C-1152

COMP AND PEN CLINIC

2C-1151

ANTI COAGULATION

CLINIC

2C-1162

ELEV MACH RM

2C-1163

TOILET

2C-1161

C O R R

ID

O R

2C -C 1-

ELEV

PA

TI

EN

T

EL

EV

L O B B Y

2C -C 1-

EXAM

2W-114

M A

LE

T O

IL

ET

2W -1

FEMALE PATIENT

TOILET

2W-116

TELECOM ROOM

2W-121

EXAM

2W-123

CHASE

OPEN OFFICE

2W-117

EXAM

2W-118

EXAM

2W-120

EXAM

2W-119

CORRIDOR

2W-1C4

SOILED UTILITY

2W-122

A N

TE

2W -1

WOMEN ISO/ PROC

2W-125

WAITING

2C-C1-11 WAITING

2C-C1-15

CORRIDOR

2C-C1-17

ELECTRICAL SWITCH

GEAR

2E-1161

EMERGENCY

GENERATOR

2E-1161B

CORRIDOR

NURSE MGR OFFICE

2E-1113

CONFERENCE RM

2E-1114

EXAM RM

2E-1127

HAC

2E-1126

C1-1

C1-2

C O R R

ID

O R

2E -C 1-

FE

M A

LE

T O

IL

ET

2C -1

TOILET

2C-1145

TRIAGE

2C-1144

TOILET

2C-1143

CORRIDOR

2C-C1-1041

RECEPTION

2C-1146

STAIR #8

2C-S8

VESTIBULE

2W-215

ELECTRICAL

2C-1164

OPEN OFFICE

2C-1165

EXAM

2C-1168

EXAM

2C-1167

EXAM

2C-1166

C O R R

2C -C 2-

EXAM

2C-1173

EXAM

2C-1172

EXAM

2C-1171

PCMH

2C-1170

SM

A

LL

M

ED

2C -1

C O R R

2C -C 2-

EXAM

2C-1174

EXAM

2C-1175

EXAM

2C-1176

EXAM

2C-1177

EXAM

2C-1179

EXAM

2C-1180

OPEN OFFICE

2C-1178

HSS

2C-1182

LINEN

2C-1181

OPEN OFFICE

2W-102

EXAM

2W-105A

EXAM

2W-105B

CONFERENCE ROOM

2W-107A

EXAM

2W-107B

EXAM

2W-108A

EXAM

2W-109A

EXAM

2W-112

TOILET

2W-106

TOILET

2W-104

EXAM

2W-101

NURSE MANAGER

2W-100

CORRIDOR

1C1-02W

CORRIDOR

2W-1C2

PHARM D

2W-132B

OIT COMM

2W-132A

EXAM

2W-130B

EXAM

2W-130A

EXAM

2W-103B

C

LE

A N S

TO

R A G E

2W -1 A

C H A

SE -

EXAM

2W-108B

EQUIP

2W-109B

TO

IL

ET

2W -1

TO

IL

ET

2W -1

13 CHASE

ELEC

2W-129

H A C

2W -1 A

CLEAN UTIL

2W-131B

MED

2W-131C

FM

S C O M M

2W -1

ST

A

IR

2W -S

EXAM

2W-127

TOILET

2W-126

C O R R

ID

O R

2W -1 C

C O R R

ID

O R

2W -1 C

COMPUTER RM

1C-148D

01T-401 F2

01T-401 F2

01T-401 F1

01T-401 C1

01T-401 F6

01T-402 C5

01T-402 F5

FIBER PATH A

(2) 24F OS2 CABLE

(5) 24F OM4/12F OS1

BLDG 3 (2) OS2 CABLE

FIBER PATH B

(1) 24F OS2 CABLE

(6) 24F OM4/12F OS1

BLDG 42 (1) OS2 CABLE

FIBER PATH B

(1) 24F OS2 CABLE

(1) 24F OM4/12F OS1

BLDG 2W (1) OS2 CABLE

FIBER PATH A

(5) 24F OM4/12F OS1

BLDG 2C (4) OS1 CABLE

BLDG 2W (1) OS1 CABLE

FIBER PATH A

(11) 24F OM4/12F OS1

BLDG 1/2E (11) OS1 CABLE

FIBER PATH B

(9) 24F OM4/12F OS1CABLE

BLDG 2E (9) OS1 CABLE

02T-101W F4

02T-401 F7

02T-403 F4

FIBER PATH A

(1) 24F OM4/12F OS1

BLDG 32 (1) OS1 CABLE

TELECOM ROOM

2E-1178

266 SF

FIBER PATH B

(5) 24F OM4/12F OS1

BLDG 1 (5) OS1 CABLE

262' - 0"

262' - 0"

262' - 0"

262' - 0"

FIBER PATH A

FIBER PATH B

FIBER PATH LEGEND

SERVICE PROVIDER A

SERVICE PROVIDER B

11/09/2023

11/09/2023

N

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

CONSULTANT

321 4 5 6 7 8 9 10

GENERAL NOTES

KEY PLAN

KEYNOTES

2W

TRIPLE C - The A/E Group 201 E. Jefferson Street, Suite 200 Syracuse, NY 13202

MAT PERKINS

(315) 484-5958

2C 2E

STAMP

Au to de sk

D oc s:

//6

A4

-2 2-

0_

N ew in gt on _V

AM

C

_E H

R M

_I U

-1

2/

9A 4-

-7

.N ew in gt on

.E H

R M

.M

EP

.B

_0 2_

R

.rv t

-0

1-

0:

:4

T-101

TELECOMMUNICATION PLAN - OVERALL

BUILDING FLOOR PLAN - FIRST LEVEL

689A4-22-700

01_02

11/09/2023 M. Perkins K.

MCDERMOTT

ISSUED FOR

CONSTRUCTION

EHRM INFRASTRUCTURE

UPGRADES

555 Willard Avenue, Newington, CT 06111

A.

B.

C.

D.

E.

F.

G.

H.

I.

J.

K.

L.

M.

N.

PROPERLY FIRE STOP AND SEAL ALL PENETRATIONS THROUGH WALLS,

FLOORS, CEILINGS, AND ROOF AS PER OWNER, CODE, AND AHJ.

PRIOR TO INSTALLATION OF CABLE TRAY COORDINATE LOCATIONS WITH ALL

OTHER TRADES AND PROVIDE COORDINATION DRAWINGS FOR REVIEW. ALL

NEW CABLE, CABLE TRAY, J HOOKS SHALL BE INDEPENDENTLY SUPPORTED &

NOT CAUSE ADDITIONAL LOAD ON OTHER SYSTEMS.

NOT ALL PARTS AND PIECES ARE SHOWN FOR A COMPLETE SYSTEM.

CONTRACTOR IS RESPONSIBLE FOR PROVIDING A COMPLETE END-TO-END

WARRANTED SOLUTION FOR THE CABLING.

ALL CABLING TO BE PLENUM RATED THROUGHOUT THE BUILDING.

ALL COMMUNICATIONS AND WIRELESS ACCESS POINT CABLING TO MEET OR

EXCEED CATEGORY 6A STANDARDS.

SEE E-501 FOR DEVICE STANDARD MOUNTING HEIGHTS.

ALL CONDUITS FOR TELECOMMUNICATIONS OUTLETS SHALL BE STEEL THIN

WALL ELECTRICAL METALLIC TUBING (TYPE EMT) UNLESS OTHERWISE NOTED.

UNDER NO CIRCUMSTANCES SHALL FLEXIBLE CONDUIT BE USED FOR

PATHWAYS INDICATED ON THIS DRAWING. ALL CONDUITS ARE TO BE, AT A

MINIMUM, 1-1/4" TRADE SIZE, UNLESS OTHERWISE NOTED. ALL CONDUITS FOR

TELECOMMUNICATIONS OUTLETS ARE TO BE STUBBED TO NEAREST CABLE

TRAY. CONTRACTOR IS TO ENSURE THAT NO CONDUIT EXCEEDS 40% FILL. IF

EXISTING CONDUIT IS NOT LARGE ENOUGH TO SUPPORT NEW CAT 6A CABLE

TO REPLACE ALL EXISTING CIRCUITS ONE-FOR-ONE, CONTRACTOR SHALL

PROVIDE THE MAXIMUM ALLOWABLE NEW CAT 6A CIRCUITS TO REPLACE

EXISTING. THE ADDITIONAL NEW CIRCUITS TO COMPLETE THE ONE-FOR-ONE

REPLACEMENT SHALL BE PROVIDED AT THE NEAREST AVAILABLE DROP WITH

EXISTING CONDUIT CAPACITY.

ALL CONDUIT PATHWAYS SHALL BE PROVIDED WITH NYLON BUSHINGS TO

PROTECT CABLES, REGARDLESS OF WHETHER THEY TERMINATE IN A DEVICE

OR JUNCTION BOX.

TERMINATE, TEST, LABEL AND DOCUMENT ALL TELECOMMUNICATION CABLES.

CONTRACTOR SHALL AVOID ALL SYSTEMS SHUTDOWNS, INSTALL NEW

EQUIPMENT PRIOR TO THE RENOVATION OF EXISTING EQUIPMENT; PROVIDE

TEMPORARY UTILITIES AS REQUIRED TO MEET THIS REQUIREMENT.

THE DEMOLITION OF DEVICES SHALL INCLUDE ALL ASSOCIATED CABLING

BACK TO THE RACK.

LABEL DEVICE PLATES WITH A PERMANENT ADHESIVE LABEL FOLLOWING ALL

STANDARDS AND REQUIREMENTS, SEE DETAIL SHEETS FOR ADDITIONAL

INFORMATION

CONTRACTOR SHALL PROVIDE TWO SETS OF LAMINATED FINAL

TELECOMMUNICATION ONE-LINE, RACK ELEVATION, AND CABLE SCHEDULE

DOCUMENTS. HANG ON THE WALL WITHIN THE TELECOM ROOM.

REFER TO R-900 SERIES SHEETS FOR PHOTO DOCUMENTATION OF EXISTING

CONDITIONS.

O. FOR EXISTING SECURITY CAMERAS BEING RE-CABLED, MAINTAIN EXISTING

CAMERA ANGLE AND PROTECT IN PLACE.

P. ALL EXISTING PENETRATIONS NO LONGER BEING USED WILL BE FILLED WITH

RATED ASSEMBLY.

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

12.

13.

14.

15.

16.

17.

18.

19.

20.

21.

22.

23.

24.

PROVIDE NEW TELECOMMUNICATIONS OUTLET IN EXISTING LOCATION WITH

EXISTING EMT STUB UP TO NEAREST ACCESSIBLE CEILING SPACE. SEE DETAILS

ON SHEET T-501 FOR ADDITIONAL INFORMATION.

EXISTING WIRELESS ACCESS POINT TO BE RETAINED AND REUSED. PROVIDE

NEW CABLING AND TELECOMMUNICATIONS OUTLET. REFER TO DETAILS ON

SHEET T-501 FOR ADDITIONAL INFORMATION.

PROVIDE NEW 4-POST RACK, PDU, UPS AND WIRE MANAGEMENT COMPONENTS

AS SHOWN ON T-500 SERIES AND T-600 SERIES SHEETS AND IN THE

SPECIFICATIONS. PHASE TO PROVIDE NEW RACK IN A TEMPORARY LOCATION

AND TRANSFER DATA CIRCUITS FROM THE EXISTING RACK TO THE NEW RACK.

PROVIDE TEMPORARY EXTRA LENGTH JUMPER CABLES TO EXISTING SWITCHES

AND OTHER DEVICES TO ENSURE UNINTERRUPTED SERVICE. ONCE ALL EXISTING

DATA CIRCUITS ARE RELOCATED TO NEW PATCH PANELS ON THE NEW RACK AND

ALL EXISTING DEVICES TO REMAIN ARE TRANSFERRED TO THE NEW RACK,

REMOVE THE EXISTING RACK AND INSTALL THE NEW RACKS IN THE FINAL

PERMANENT POSITION.

PROVIDE NEW VERTICAL WIRE MANAGEMENT SYSTEM, SEE SPECIFICATIONS FOR

ADDITIONAL INFORMATION.

EXISTING CABLING CONDUIT AND WIREWAYS ARE TO REMAIN AND BE CAREFULLY

PROTECTED IN PLACE. ALL EXISTING DEVICES ON THE EXISTING RACK SHALL BE

TRANSFERRED TO THE NEW SECOND LEVEL LOCATION ON THE NEW RACK.

CONTRACTOR SHALL PROVIDE SHOP DRAWINGS SHOWING THE PROPOSED NEW

RACK ELEVATION AND PROVIDE A PHASING PLAN FOR TRANSFERRING ALL

EXISTING DEVICES TO REMAIN TO THE NEW RACKS.

PROVIDE NEW CABLE TRAY PER REQUIREMENTS LISTED IN CABLE TRAY

SCHEDULE. COORDINATE WITH EXISTING CONDITIONS AND SUBMIT

COORDINATION DRAWINGS FOR REVIEW PRIOR TO COMMENCING WORK.

COORDINATE FIXTURES WITH OVERHEAD TRAY. SEE T-500 SERIES SHEETS FOR

ADDITIONAL REQUIREMENTS. COORDINATE LIGHT FIXTURES WITH OVERHEAD

CABLE TRAY.

PROVIDE NEW IP…