Attachment 23 - 689A4-22-700.Newington.EHRM.IFC.B65.20240703.part2.pdf

PDF 18 MB Posted

Attached to
Z2DA--689A4-22-700 EHRM Infrastructure, Newington CONSTRUCTION SOLICITATION (VA-24-00028377)
Solicitation number
36C77624B0015_1
Issued by

About this file

This appears to be a partial PDF construction drawing set or specification document for Building 65 as part of the Electronic Health Record Modernization (EHRM) infrastructure upgrades at the VA Medical Center in Newington, Connecticut. Without being able to view the actual contents of this "part 2" PDF file, I cannot provide specific details about what is contained in this particular document segment. However, based on the file naming convention and related solicitation details, this is likely technical construction documentation for Building 65 improvements that are part of a larger IT and communications infrastructure upgrade project to support the Cerner electronic health record system implementation. The overall project involves multiple buildings on campus including Buildings 1C, 2E, 2C, 2W, 3, 12, 32, 33, 34, 42, and 65.

View the file

Other files

File Type Posted
Technical Questions Tracking Spreadsheet - 2-13-25 - 36C77624B0015 - Construct EHRM Infrastructure Upgrades Newington CT.pdf PDF
Newington EHRM Infrastructure Upgrades - 36C77624B0015 Amendment - 0007.pdf PDF
Attachment 34 - 689A4-22-700.EHRM.Newington.Add3.20250211.pdf PDF
Newington EHRM Infrastructure Upgrades - 36C77624B0015 Amendment - 0006.pdf PDF
Attachment 27 - Wage Rates 01.31.25- Hartford.pdf PDF
Bid Opening Details - Newington CT - 36C76624B0015.pdf PDF
Site Visit Sign In Sheet 2.3.25.pdf PDF
Newington EHRM Infrastructure Upgrades - 36C77624B0015 Amendment - 0005.pdf PDF
Attachment 33 - Site Visit Instructions - Updated 1.27.25.pdf PDF
Attachment 2 - 689A4-22-700.EHRM.Newington.Spec.Final.20240806.Part1.pdf PDF
Attachment 21 - 689A4-22-700.Newington.EHRM.IFC.B32_33_34.20240703.part2.pdf PDF
Attachment 13 - 689A4-22-700.Newington.EHRM.IFC.B01_02.20241008.part4.pdf PDF
Attachment 17 - 689A4-22-700.Newington.EHRM.IFC.B03_42.20240703.part2.pdf PDF
Newington EHRM Infrastructure Upgrades - 36C77624B0015 Amendment - 0004.pdf PDF
Attachment 22 - 689A4-22-700.Newington.EHRM.IFC.B65.20240703.part1.pdf PDF
Attachment 32 - 689A4-22-700.EHRM.Newington -.20250114 - Addendum 2.pdf PDF
Attachment 3 - 689A4-22-700.EHRM.Newington.Spec.Final.20240806.Part2.pdf PDF
Attachment 12 - 689A4-22-700.Newington.EHRM.IFC.B01_02.20241008.part3.pdf PDF
Attachment 15 - 689A4-22-700.Newington.EHRM.IFC.B01_02.20241008.part6.pdf PDF
Attachment 20 - 689A4-22-700.Newington.EHRM.IFC.B32_33_34.20240703.part1.pdf PDF
Attachment 33 - Site Visit Instructions - Updated 1.23.25.pdf PDF
Attachment 18 - 689A4-22-700.Newington.EHRM.IFC.B03_42.20240703.part3.pdf PDF
Attachment 19 - 689A4-22-700.Newington.EHRM.IFC.B12.20240703.pdf PDF
Attachment 14 - 689A4-22-700.Newington.EHRM.IFC.B01_02.20241008.part5.pdf PDF
Attachment 10 - 689A4-22-700.Newington.EHRM.IFC.B01_02.20241008.part1.pdf PDF
Technical Questions Tracking Spreadsheet - 1-23-25 - 36C77624B0015 - Construct EHRM Infrastructure Upgrades Newington CT .pdf PDF
Attachment 16 - 689A4-22-700.Newington.EHRM.IFC.B03_42.20240703.part1.pdf PDF
Attachment 24 - 689A4-22-700.Newington.EHRM.IFC.SITE.20240703.pdf PDF
Attachment 11 - 689A4-22-700.Newington.EHRM.IFC.B01_02.20241008.part2.pdf PDF
Attachment 31 - EHRM Newington-Pre Bid Presentation.010725.R02.pdf PDF
Technical Questions Tracking Spreadsheet - 1-6-25 - 36C77624B0015 - Construct EHRM Infrastructure Upgrades Newington CT.pdf PDF
Newington EHRM Infrastructure Upgrades - 36C77624B0015 Amendment - 0003.pdf PDF
2025-01-07 Preproposal conference sign in list.pdf PDF
Attachment 30 - Price Schedule - 36C77624B0015 - 689A4-22-700 EHRM Infrastructure Newington.pdf PDF
Attachment 28 - Site Visit Instructions - Updated 1.6.25.pdf PDF
Newington EHRM Infrastructure Upgrades - 36C77624B0015 Amendment - 0002.pdf PDF
Attachment 19 - Newington EHRM Drawings - Part 10 of 16 - 12.31.24.pdf PDF
Newington EHRM Infrastructure Upgrades - 36C77624B0015 Amendment - 0001.pdf PDF
Attachment 29 - 689A4-22-700.EHRM.Newington.Add1.20241213.pdf PDF
Attachment 28 - Site Visit Instructions.pdf PDF
Attachment 24 - Newington EHRM Drawings - Part 15 of 16.pdf PDF
Attachment 11 - Newington EHRM Drawings - Part 2 of 16.pdf PDF
Attachment 26 - Newington VAHC campus map.pdf PDF
Attachment 22 - Newington EHRM Drawings - Part 13 of 16.pdf PDF
Attachment 23 - Newington EHRM Drawings - Part 14 of 16.pdf PDF
Attachment 3 - 689A4-22-700.EHRM.Newington.Spec.Final.20240806.Part2.pdf PDF
Attachment 14 - Newington EHRM Drawings - Part 5 of 16.pdf PDF
Attachment 10 - Newington EHRM Drawings - Part 1 of 16.pdf PDF
Attachment 27 - Wage Rates 8.9.24- Hartford.pdf PDF
Attachment 9 - Underground Utility Locating.pdf PDF
Show 40 more

Latest 50 of 68 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ELECTRICAL ABBREVIATIONS

J J

M

V

SP

R

GB

VFD

LCP

LRP

AFB

NCC

MS

1P

2P

E

DS

SS

B

MO

FBX

ET

M

M

C

DTDT

A-1

PH

D

P

K a

L

OS

R

B

CB

MD

MD

SP

VP

TV

XX

DC

C

DM

R/D

DGP

RX

ELM

DO

AC

KAC

E

K

ATS

TBB

T

TMH

EMH

EHH

X

PSD

EMU

FB

UG

GB

G

PB

SR-X

6-30R

UPS

CT

DOOR CONTACT SWITCH

ACCESS FLOOR BOX ("X" DENOTES TYPE AS SPECIFIED)

FLOOR BOX ("X" DENOTES TYPE AS SPECIFIED)

CONTACTOR

VARIABLE FREQUENCY DRIVE/VARIABLE FREQUENCY MOTOR CONTROLLER

MANUAL MOTOR STARTER WITH PILOT LIGHT AS INDICATED.

PUSHBUTTON STATION

CCTV SURVEILLANCE CAMERA OUTLET - WALL MTD, UON

DOOR MONITOR SWITCH

RECEIVER/DRIVER UNIT

NURSE CALL CONTROL EQUIPMENT PANEL (RECESSED/SURFACE)

NURSE CALL EMERGENCY STATION - PULL CORD TYPE IN

TOILETS & SHOWERS, PUSH-BUTTON TYPE IN ALL OTHER

PLACES

NURSE CALL BEDSIDE STATION, DOUBLE PATIENT

NURSE CALL BEDSIDE STATION, SINGLE PATIENT

NURSE CALL MASTER STATION

GLASS BREAK DETECTOR

NURSE CALL DOME LIGHT

PATIENT MONITORING OUTLET

CODE BLUE CALL STATION

NURSE CALL STAFF STATION

NURSE CALL DUTY STATION

LIGHTING FIXTURE TYPE DESIGNATION - "XX" INDICATES SPECIFIC TYPE

EXIT LIGHT - WALL/CEILING MOUNTED - DIRECTIONAL

ARROWS AS INDICATED SHADING INDICATES ILLUMINATED

FACE

LIGHTING TRACK - "X" DENOTES TYPE

UTILITY LIGHTING FIXTURE - TYPE AS INDICATED

WALL MOUNTED LIGHTING FIXTURE- TYPE AS INDICATED

SITE LIGHTING FIXTURE TYPE AS INDICATED

LIGHTING FIXTURE - TYPE AS INDICATED (SUBSCRIPT INDICATES SWITCH CONTROL)

JUNCTION BOX - CEILING OR WALL MOUNTED - INDICATED IN POWER, LIGHTING & FIRE

ALARM SYSTEMS PLANS.

DIRECT CONNECTION TO EQUIPMENT

SINGLE POLE SWITCH (SUBSCRIPT INDICATES FIXTURES CONTROLLED)

DIMMER SWITCH

SINGLE OR DOUBLE, REMOTE EMERGENCY LIGHTING FIXTURE

THREE-WAY SWITCH (S3P-THREE-WAY SWITCH WITH PILOT LIGHT)

KEY OPERATED SWITCH

SINGLE POLE SWITCH WITH PILOT LIGHT

FOUR - WAY SWITCH

FUSED SWITCH

DELTA CONNECTION

CPT

PASSIVE INFRARED/ULTRASONIC OCCUPANCY SENSOR (WALL/CEILING)

ELECTRIC INTERLOCK SYSTEM

CONTROL POWER TRANSFORMER

CURRENT TRANSFORMER

POTENTIAL TRANSFORMER

PHOTO CELL

KEY INTERLOCKING SYSTEM

WYE CONNECTION - SOLID GROUND

SWITCH - SINGLE THROW

TELECOMMUNICATIONS BACKBOARD

MOTOR CONTROL CENTER

TELEPHONE MANHOLE

ELECTRIC MANHOLE

FUSE

BUS DUCT PLUG-IN UNIT

GROUND

AUTOMATIC TRANSFER SWITCH

DRAWOUT TYPE, CIRCUIT BREAKER

STATIONARY CIRCUIT BREAKER

DISCONNECT SWITCH, FUSED.

PROVIDE SWITCH AND FUSE AMACITY EQUAL TO OR GREATER THAN FEEDER AMPACITY,

UON

GROUND ROD

DISCONNECT SWITCH, NON-FUSED

PROVIDE SWITCH AMPACITY EQUAL TO OR GREATER THAN FEEDER AMPACITY, UON

TELECOMMUNICATIONS COMBINATION VOICE/DATA OUTLET, FLOOR MTD SERVICE FITTING,

SURFACE TYPE ("F" DENOTES FLUSH TYPE, "P" DENOTES POKE THRU TYPE)

TELECOMMUNICATIONS COMBINATION VOICE/DATA OUTLET, WALL MTD.

(SLASH INDICATES MOUNTING ABOVE FINISH COUNTER)

TRANSFORMER - TYPE AND RATING AS INDICATED

COMBINATION MOTOR STARTER WITH DISCONNECT SWITCH.

PROVIDE SWITCH AND FUSE AMACITY EQUAL TO OR GREATER THAN FEEDER

AMPACITY, UON

PANELBOARD - (FLUSH/SURFACE)

DISTRIBUTION PANELBOARD

ELECTRIC HANDHOLE

LIGHTING CONTROL PANEL, SURFACE MTD. UON.

LOW VOLTAGE LIGHTING RELAY PANEL, SURFACE MTD. UON

UNINTERRUPTIBLE POWER SUPPLY

SHADING INDICATES FIXTURE [CONNECTED TO CRITICAL BRANCH]

[CONNECTED TO GENERATOR CIRCUIT (SWITCHED)]

[W/FLUORESCENT BATTERY/INVERTER UNIT (SWITCHED)]

SHADING INDICATES FIXTURE [CONNECTED TO LIFE SAFETY BRANCH

(UNSWITCHED)] [W/FLUORESCENT BATTERY/INVERTER UNIT (UNSWITCHED)]

a

LOW VOLTAGE SWITCH

JUNCTION BOX - CEILING MOUNTED - 60A 3P - NORMAL

TELECOMMUNICATIONS COMBINATION VOICE/DATA OUTLET, CEILING MTD SERVICE

FITTING,

SURFACE TYPE ("F" DENOTES FLUSH TYPE)

MOTOR AND CONNECTION

EMERGENCY POWER OFF

REQUEST-FOR-EXIT SENSOR

ELECTRIC LOCKING/LATCHING AND MONITORING HARDWARE

ACCESS CONTROL STATION - KEYPAD TYPE

ACCESS CONTROL STATION - CARD TYPE

DOOR OPERATING EQUIPMENT

DATA GATHERING PANEL

NURSE CALL DOME LIGHT CEILING MTD

("Z" SUBSCRIPT DENOTES ZONE DOME LIGHT)

CODE BLUE WITH RED PHONE, WALL MTD, MOUNTED 48" AFF

CODE BLUE WITH BLUE LIGHT, WALL MTD, MOUNTED 48" AFF

MOTION DETECTOR - CEILING MTD

MOTION DETECTOR - WALL MTD

POWER SUPPLY FOR DOOR(S) WITH ELECTRICAL HARDWARE

OVERHEAD EMERGENCY DUPLEX RECEPTACLE NEMA L21-20, 20A, 125V, 3P, 4W.

SPECIAL PURPOSE RECEPTACLE. TYPE AS INDICATED ON DRAWINGS.

COORDINATE RECEPTACLE TYPE WITH ACTUAL EQUIPMENT PRIOR TO INSTALLATION.

SWITCHED DUPLEX RECEPTACLE, 20A, 125V, 2P, 3W.

EMERGENCY DUPLEX RECEPTACLE, 20A, 125V, 2P, 3W.

FLOOR MOUNTED QUADRUPLEX ISOLATED GROUND RECEPTACLE, (2)20A, 125V,

2P, 3W, DUPLEX ISOLATED GROUND RECEPTACLES WITH A COMMON

FACEPLATE.

FLOOR MOUNTED QUADRUPLEX RECEPTACLE, (2)20A, 125V, 2P, 3W, DUPLEX

RECEPTACLES WITH A COMMON FACEPLATE.

FLOOR MOUNTED DUPLEX ISOLATED GROUND RECEPTACLE, 20A, 125V, 2P, 3W.

FLOOR MOUNTED DUPLEX RECEPTACLE, 20A, 125V, 2P, 3W. PROVIDE CORE

DRILL PACKAGE TO MAINTAIN FIRE RATING OF FLOOR. EXTEND CONDUIT

AND WIRING IN CEILING SPACE OF FLOOR BELOW TO ELECTRICAL CLOSET

OR PANELBOARD.

FLOOR MOUNTED SINGLE ISOLATED GROUND RECEPTACLE, 20A, 125V, 2P, 3W.

CEILING MOUNTED QUADRUPLEX ISOLATED GROUND RECEPTACLE, (2)20A, 125V,

2P, 3W, DUPLEX ISOLATED GROUND RECEPTACLES WITH A COMMON FACEPLATE.

FLOOR MOUNTED SINGLE RECEPTACLE, 20A, 125V, 2P, 3W.

CEILING MOUNTED DUPLEX ISOLATED GROUND RECEPTACLE, 20A, 125V, 2P, 3W.

CEILING MOUNTED SINGLE ISOLATED GROUND RECEPTACLE, 20A, 125V, 2P, 3W.

CEILING MOUNTED SINGLE RECEPTACLE, 20A, 125V, 2P, 3W.

SINGLE ISOLATED GROUND RECEPTACLE, 20A, 125V, 2P,

3W. (SLASH INDICATES MOUNTING ABOVE FINISH

COUNTER)

QUADRUPLEX ISOLATED GROUND RECEPTACLE, (2)20A, 125V, 2P, 3W,

DUPLEX ISOLATED GROUND RECEPTACLES WITH A COMMON

FACEPLATE. (SLASH INDICATES MOUNTING ABOVE FINISH COUNTER)

DUPLEX ISOLATED GROUND RECEPTACLE, 20A, 125V, 2P, 3W.

(SLASH INDICATES MOUNTING ABOVE FINISH COUNTER)

DUPLEX RECEPTACLE, 20A, 125V, 2P, 3W. (SLASH INDICATES MOUNTING ABOVE FINISH COUNTER)

SINGLE RECEPTACLE, 20A, 125V, 2P, 3W. (SLASH INDICATES MOUNTING ABOVE FINISH COUNTER)

RECEPTACLES MOUNTED ABOVE THE CEILING.

QUADRUPLEX RECEPTACLE, (2)20A, 125V, 2P, 3W, DUPLEX RECEPTACLES

WITH A COMMON FACEPLATE. (SLASH INDICATES MOUNTING ABOVE FINISH

COUNTER)

CEILING MOUNTED QUADRUPLEX RECEPTACLE, (2)20A, 125V, 2P, 3W, DUPLEX

RECEPTACLES WITH A COMMON FACEPLATE.

GFI, DUPLEX RECEPTACLE, 20A, 125V, 2P, 3W. (SLASH INDICATES MOUNTING ABOVE FINISH COUNTER)

ELECTRONIC METERING UNIT

GROUND BUS

GROUND CABLE, SIZE AS INDICATED

PLUG-IN BUSWAY

FEEDER BUSWAY

UNDERGROUND CONDUIT/DUCTBANK

CABLE TRAY

CONDUIT TURNED DOWN

CONDUIT TURNED UP

CONDUIT CAST IN CONCRETE OR BELOW SLAB

CONDUIT RUN CONCEALED IN FINISHED AREAS, EXPOSED IN UNFINISHED

AREAS OR BELOW ACCESS FLOORS

HOMERUN TO PANEL WITH CIRCUIT NUMBER(S) AS INDICATED

TELECOMMUNICATIONS DATA OUTLET ABOVE CEILING

COMBINATION TV OUTLET AND DUPLEX RECEPTACLE ON SINGLE

FACEPLATE

SPEAKER - WALL MTD

PA VOLUME CONTROL

MICROPHONE OUTLET - CEILING MTD

MICROPHONE OUTLET - WALL MTD

MICROPHONE OUTLET - FLOOR MTD

SPEAKER - CEILING MTD

RECORDING OUTLET

COMBINATION VIDEO PROJECTOR OUTLET AND DUPLEX RECEPTACLE

CLOCK OUTLET, W/RECPT AND HANGER

CLOCK OUTLET, MASTER CLOCK

CLOCK OUTLET, ELAPSED TIME

GENERATORG

SURFACE RACEWAY ("X" DENOTES TYPE AS SPECIFIED)

WALLWASH LIGHT FIXTURE,

DEMOLITION WORK

OCCUPANCY SENSOR WALL SWITCH

M

HC ADA PUSH BUTTON.

ELECTRICAL LIGHTING SYMBOLS ELECTRICAL POWER SYMBOLS GENERAL NOTES

A INTERCOMMUNICATION SYSTEM ( AI PHONE)

A B C A B C

P P

PD PD

D D

POWER SERVICE FITTING (FLOOR/WALL) MOUNTED FOR CONNECTION TO FURNITURE

SYSTEM AS SPECIFIED.

COMBINATION POWER AND TELECOMMUNICATIONS FLOOR OR WALL MOUNTED BOX FOR

POWER AND DATA CONNECTION - INDICATED IN POWER & SPECIAL SYSTEMS PLANS.

JUNCTION BOX FLOOR OR WALL MOUNTED FOR CONNECTION TO FURNITURE SYSTEM

ELTD EMERGENCY LIGHTING TRANSFER DEVICE

SECURITY SYSTEM SYMBOLS

TELECOMMUNICATION SYMBOLS

NURSE CALL SYSTEM SYMBOLS

MOUNTING HEIGHTS

ELECTRICAL EQUIPMENT SYMBOLS

ELECTRICAL WIRING SYMBOLS

DISTRIBUTION AND DIAGRAM SYMBOLS

REFERENCE SYMBOLS

SECTION NUMBER

DETAIL NUMBER

DRAWING NUMBER WHERE DRAWN

DRAWING NUMBER WHERE DRAWN

E1-1.0 KEY NOTE

1 DEMO KEY NOTE

SPECIAL SYSTEM OUTLET SYMBOLS

CB

E1-1.0

*REFER TO DETAIL ON E-501

x

WAP WIRELESS ACCESS POINT, CEILING MOUNTED

NOTE: NOT ALL ABBREVIATIONS AND

SYMBOLS APPLY TO THIS PROJECT.

SPST

SWBD

SYM

STD

SW

SPEC(S)

SPDT

SPKR

SF

SEC

SINGLE POLE SINGLE THROW

SINGLE POLE DOUBLE THROW

SYMMETRICAL

SWITCHBOARD

STANDARD

SWITCH

SECONDARY

SQUARE FOOT

SPECIFICATION(S)

SPEAKER

PRI

RCLP

RM

SCH, SCHED

RP

REF

RCPT

RSC

RLA

RF

R, RE

QTY

PWR

PT

PVC

PA

PH, ∅

PF

PNL

PE

PB

P

OPP

OHE/T

OH

OFOI

OFCI

NO., NUM, #

OC

NTS

AMERICAN WIRE GAUGE

ABOVE FINISHED FLOOR

ABOVE FINISHED GRADE

AUTOMATIC TRANSFER SWITCH

AMPERE INTERRUPTING CAPACITY

ALTERNATING CURRENT

ABOVE FINISHED COUNTER

AWG

BLDG

BRKR, BKR

BUILDING

BREAKER

AUTO

AUX

ARCH

AT

ATS

ALT

AFG

AIC

AFC

AFF

AC

AF

AUXILIARY

ALTERNATE

ARCHITECT

AUTOMATIC

AMPERES TRIP

AMPERE FRAME (BREAKER RATING)

MTG

NC

NEMA

NO

NIC

NEC

N

MV

MH

MOCP

MTD

MLO

MIN

MISC

MECH

MCC

MFR

MCA

MCB

RIGID STEEL CONDUIT

RATED (RUNNING) LOAD AMPS

RECEPTACLE PANELBOARD

ROOM

SCHEDULE

RADIO FREQUENCY

RECEPTACLE

REFRIGERATOR

RELOCATE AS SHOWN

POTENTIAL TRANSFORMER

POLYVINYL CHLORIDE

REMOTE CONTROL LIGHTING PANEL

QUANTITY

POWER

PUBLIC ADDRESS

PANEL

PRIMARY

PULL BOX

POWER FACTOR

PHOTO ELECTRIC

PHASE

POLE

OPPOSITE

OWNER FURNISHED, CONTRACTOR INSTALLED

OWNER FURNISHED, OWNER INSTALLED

OVERHEAD ELECTRIC/TELEPHONE

OVERHEAD

ON CENTER

NOT TO SCALE

NUMBER

MOUNTING

NATIONAL ELECTRICAL CODE

MEDIUM VOLTAGE (OVER 600V LESS THAN 35KV)

NORMALLY CLOSED

NORMALLY OPEN

NOT IN CONTRACT

NEUTRAL

MINIMUM CIRCUIT AMPACITY

MAIN CIRCUIT BREAKER

MOTOR CONTROL CENTER

MAXIMUM OVERCURRENT PROTECTION

MOUNTED

MISCELLANEOUS

MAIN LUGS ONLY

MINIMUM

MANHOLE

MANUFACTURER

MECHANICAL

SWGR SWITCHGEAR

AIR HANDLING UNITAHU

MTS MANUAL TRANSFER SWITCH

PDP POWER DISTRIBUTION PANEL

AMPERESAMP

OCPD OVERCURRENT PROTECTION DEVICE

A M

B N

O

P

Q

R

S

T

SPD SURGE PROTECTIVE DEVICE

OD OUTLET DESIGNATOR

LOW VOLTAGE (BELOW 50 VOLTS)

L-L L-N

LTG

LV

LIGHTING

LINE TO LINE

LINE TO NEUTRAL

1000 CIRCULAR mils

KILOVOLTS (THOUSAND VOLTS)

KILOWATTS (THOUSAND WATTS)

LIGHTNING ARRESTOR

LOCAL AREA NETWORK

KILOVOLTS-AMPERES (THOUSAND VOLT-AMPS)

ISOLATED GROUND

KWH

LAN

LA

KW

KVA

Kcmil

KV

KILOWATT-HOURS

INCAND

KEY INTERLOCK

JUNCTION BOX

INCH/INCHES (")

INCANDESCENT

GROUND FAULT INTERRUPTER

HAND-OFF-AUTOMATIC

HIGH PRESSURE SODIUM

HEATING VENTILATION AND AIR CONDITIONING

HERTZ

HVAC

HZ

HTR

HR

HT

HPS

HOA

HP

HEATER

HEIGHT

HORSEPOWER

HOUR

GFI

G, GND, GRD

GEN

FLUOR

FL, FLR

GROUND

GENERATOR

FOOT/FEET (')

FLUORESCENT

FLOOR

CATV

ELECTRIC WATER COOLER

ELECTRIC WATER HEATER

FIRE ALARM ANNUNCIATOR PANEL

ELECTRIC, ELECTRICAL

ELECTRIC METALLIC CONDUIT

EQUIPMENT GROUND

EWC

FAAP

FLA

FDR

EWH

FA

FULL LOAD AMPS

FEEDER

FIRE ALARM

FUSE

ELEC

EQ, EQUIP

EM, EMERG

EMT

ELEV

ENCL

EG

EQUIPMENT

ELEVATOR

EMERGENCY

ENCLOSURE

DISTRIBUTION PANEL

DOUBLE POLE SINGLE THROW

DOUBLE POLE DOUBLE THROW

CONTROL POWER TRANSFORMER

CURRENT TRANSFORMER

DPDT

DWG

DPST

DIST

DISC

DC

DP

DN

DRAWING

DISTRIBUTION

DIRECT CURRENT

DISCONNECT

DOWN

CPT

CU

CT

COM, COMM

CKT

CLG

COPPER

COMMUNICATIONS

CIRCUIT

CEILING

CABLE TELEVISION

CB CIRCUIT BREAKER

CONDUIT

FIRE ALARM CONTROL PANELFACP

FIRE ALARM EXTENDER PANELFAEP

CCTV CLOSED CIRCUIT TELEVISION

CP CONTROL PANEL

FLEX FLEXIBLE

HAND HOLEHH

LIGHTING CONTROL PANELLC, LCP

LIGHTING PANEL

L-G LINE TO GROUND

C

F

EXISTINGE, EX, EXIST

FT

IN

IG

JB, JBOX

K

LP

FOOT CANDLEFC

DIV DIVISION

C

D

E

F

G

H

I

J

K

L

HORIZONTAL MOUNTINGH

COR CONTRACTING OFFICER'S REPRESENTATIVE

X

XFMR

WP

WHM

W/ W/O

W

VFD

VA

V

UPS

UL

UON

UG

UGS

UGT

UGP

TYP

TV

TP

TEL,TELE

TELECOM

TC

TRANSFORMER

REMOVE DEVICE

WATT HOUR METER

WEATHERPROOF

VOLTS

VARIABLE FREQUENCY DRIVE/

VARIABLE FREQUENCY MOTOR

CONTROLLER

WITHOUT

WITH

WIRE

VOLT-AMPERES

UNDERGROUND PRIMARY

UNDERGROUND SECONDARY

UNDERGROUND TELEPHONE

UNDERWRITER'S LABORATORY

UNLESS OTHERWISE NOTED

UNINTERRUPTIBLE POWER SUPPLY

UNDERGROUND

TELECOMMUNICATIONS

TYPICAL

TELEVISION

TAMPERPROOF

TIME CLOCK

TELEPHONE

TB TERMINAL BLOCK

TBB TELEPHONE BACKBOARD

U

V

W

X

Z

TPST TRIPLE POLE SINGLE THROW

FDS FORWARD DEPLOYED SERVICES

JOINT SECURITY ARCHITECTUREJSA

PIV PERSONAL IDENTITY VERIFICATION

A.

B.

C.

D.

E.

F.

G.

H.

I.

J.

K.

L.

M.

N.

O.

P.

Q.

PROVIDE 1#12 + 1#12N + 1#12G FOR 20A BRANCH CIRCUITING, UON; MAXIMUM OF THREE

CIRCUITS PER CONDUIT; MINIMUM CONDUIT SIZE OF 3/4" C, UON.

PROVIDE A DEDICATED NEUTRAL WIRE FOR EACH BRANCH CIRCUIT. IF AN EXISTING

CIRCUIT DOES NOT HAVE A DEDICATED NEUTRAL, CONTRACTOR SHALL PROVIDE A

NEW BRANCH CIRCUIT WITH DEDICATED NEUTRAL CONDUCTOR. COORDINATE DEVICE

LOCATIONS AND MOUNTING HEIGHTS WITH ARCHITECTURAL DRAWINGS PRIOR TO

ROUGH-IN.

PROVIDE FIRE STOPPING FOR CONDUITS AND ELECTRICAL EQUIPMENT FOR FLOOR

SLABS, WALLS AND CEILINGS TO MAINTAIN FIRE RATING.

INSTALL ELECTRICAL WORK IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE

AND LOCAL BUILDING AND FIRE CODES, IN A NEAT AND WORKMANLIKE MANNER.

LIMIT VOLTAGE DROP TO 2% FOR FEEDERS AND 2% FOR BRANCH CIRCUITS. INCLUDE

DERATING FACTOR FOR ROOF-MOUNTED CONDUITS PER 310.15(B)(2). FOR ANY

INCREASE IN UNGROUNDED CONDUCTOR SIZE, INCREASE GROUNDED CONDUCTOR

PROPORTIONALLY PER NEC.

REFER TO ARCH. REFLECTED CEILING PLANS FOR EXACT LOCATION OF CEILING

MOUNTED DEVICES AND LIGHT FIXTURES, UNLESS OTHERWISE INDICATED.

WHERE MULTIPLE SWITCHES, RECEPTACLES, AND OTHER OUTLETS (EXCEPT WALL

PHONES) ARE INDICATED PROVIDE MULTI-GANG BACK BOXES WITH GANG BARRIERS

AND A COMMON FACEPLATE.

WHERE DIFFERENT RECESSED ELECTRICAL DEVICES WITH THE SAME MOUNTING

HEIGHTS ARE INDICATED SIDE-BY-SIDE, MOUNT THE DEVICES SO THAT THERE IS FOUR

INCHES BETWEEN ADJACENT VERTICAL EDGES OF THE FACEPLATES, UON.

WHERE TECHNOLOGY DEVICES (LOW VOLTAGE/SIGNAL) ARE LOCATED IN THE SAME

AREA ALIGN DEVICES VERTICALLY THROUGH THEIR CENTERLINES, UON.

WHERE EXIT SIGNS ARE INDICATED ABOVE DOOR MOUNT AS FOLLOWS, CENTER THE

EXIT SIGN BETWEEN TOP OF DOOR FRAME AND CEILING IF DISTANCE BETWEEN TOP OF

DOOR FRAME AND CEILING IS 24 INCHES OR LESS; OTHERWISE MOUNT BOTTOM OF EXIT

SIGN 6 INCHES FROM TOP OF DOOR FRAME, MOUNT OTHER WALL MOUNTED EXIT SIGNS

IN THE SAME AREA AT THE SAME HEIGHT. COORDINATE WITH ARCHITECTURAL DETAILS.

PROVIDE TYPE "L1" FIXTURE IN SCHEDULE, UON.

PROVIDE SEPARATE NEUTRALS FOR DIMMING CIRCUITS.

PROVIDE FEEDERS AND BRANCH CIRCUITS WHICH HAVE AN AMPACITY EQUAL TO OR

GREATER THAN THE CIRCUIT OVERCURRENT PROTECTIVE DEVICE RATING, U.O.N.

FURNITURE LAYOUTS ARE FOR REFERENCE ONLY. COORDINATE THE FINAL LOCATION

OF ELECTRICAL DEVICES AND OUTLETS WITH ARCHITECT, OWNER AND FINAL

FURNITURE PLANS PRIOR TO INSTALLATION.

MOUNT DEVICES FLUSH WITH CONCEALED CONDUIT, EXCEPT AS NOTED ON THE

DRAWINGS AND IN MECHANICAL AND ELECTRICAL EQUIPMENT ROOMS.

THE DRAWINGS REPRESENT ELECTRICAL DESIGN INTENT. THEY ARE DIAGRAMMATIC.

PROVIDE ALL COMPONENTS NECESSARY FOR COMPLETE OPERATING ELECTRICAL

SYSTEMS.

WHEN MORE THAN ONE 20A., 1P., 120 VOLT CIRCUIT FEEDS A SURFACE RACEWAY

CONNECT RECEPTACLES TO ALTERNATE CIRCUITS AS FOLLOWS - U.O.N.

ES ELECTRIC STRIKE

JUNCTION BOX - CEILING MOUNTED - 60A 3P - EMERGENCY

CR CARD READER

OVERHEAD DUPLEX RECEPTACLE NEMA L21-20, 20A, 125V, 3P, 4W.

OVERHEAD DUPLEX RECEPTACLE NEMA L21-30, 30A, 125V, 3P, 4W.

OVERHEAD EMERGENCY DUPLEX RECEPTACLE NEMA L21-30, 30A, 125V, 3P, 4W.

NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION

NFDS NON-FUSED DISCONNECT SWITCH

07/03/2024

07/03/2024

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

CONSULTANT

321 4 5 6 7 8 9 10

TRIPLE C - The A/E Group 201 E. Jefferson Street, Suite 200 Syracuse, NY 13202

MAT PERKINS

(315) 484-5958

STAMP

Au to de sk

D oc s:

//6

A4

-2 2-

0_

N ew in gt on _V

AM

C

_E H

R M

_I U

-1

2/

9A 4-

-7

.N ew in gt on

.E H

R M

.M

EP

.G en er al

.S he et s.

rv t

-0

7-

8:

:3

65E-001

ELECTRICAL ABBREVIATIONS AND SYMBOLS 689A4-22-700

07/03/2024 M. Perkins K. McDermott

ISSUED FOR

CONSTRUCTION

EHRM INFRASTRUCTURE

UPGRADES

555 Willard Avenue, Newington, CT 06111

Revisions: Date:

07/03/2024

07/03/2024

07/03/2024

07/03/2024

DATE 07/03/2024

DN

UP

CR

ES

DC

RX

MD

JJ J JJ

J J

CHP PLANT

65-120

VST

65-100

PASS

65-101

OFFICE

65-102

OFFICE

65-103

OFFICE

65-104

LOCKER

65-105

CONTROL

65-106

WORK ROOM

65-107

AHU

65-108

ELEC

65-109

DATA

65-110

201 SF

MT

65-111

HSKP

65-112

F T/SH

65-113

SWCHGR

65-114

UREA STORAGE

65-115

BREAK-MULTI-PUR

65-116

WTR

65-117

SH

65-111A

65E-101 D1

65E-101 F1

DATA

65-110

201 SF

B65-TR65110BB65-TR65110A

B65-TR65110B- 3

B65-TR65110B- 3

B65-TR65110B- 3

B65-TR65110B- 3

IU-01-1

L1

B65-TR65110B- 2

B6 5-

TR

0B

- 8 ,1

0, B6 5-

TR

0A

- 2 ,4

,6

B65-TR65110A- 3

B65-TR65110A- 3

B65-TR65110A- 3

B65-TR65110A- 3

B65-TR65110B- 1

1 TYP.

915 16

TYP.

TYP.

TYP.

7 8

CU-01-1

B65-TR65110B- 4,6

B65-TR65110A- 1

B65-TR65110B- 2

L1

L1 L1B

B65-TR65110B- 2 B65-TR65110B- 2

MT

65-111

SH

65-111A

PASS

65-101

AHU

65-108

VFD-CU-01-1

VFD-CU-01-124

TYP.

TYP.

DATA

65-110

TYP.

TYP.

TYP.

MT

65-111

SH

65-111A

PASS

65-101

AHU

65-108

SCALE: 1/8" = 1'-0"F5 ELECTRICAL PLAN - FIRST LEVEL

07/03/2024

07/03/2024

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

CONSULTANT

321 4 5 6 7 8 9 10

GENERAL NOTES

KEYNOTES

TRIPLE C - The A/E Group 201 E. Jefferson Street, Suite 200 Syracuse, NY 13202

MAT PERKINS

(315) 484-5958

STAMP

Au to de sk

D oc s:

//6

A4

-2 2-

0_

N ew in gt on _V

AM

C

_E H

R M

_I U

-1

2/

9A 4-

-7

.N ew in gt on

.E H

R M

.M

EP

.B

_R

.rv t

-0

7-

1:

:5

65E-101

ELECTRICAL PLAN - FIRST LEVEL 689A4-22-700

07/03/2024 M. Perkins J. Schooley

ISSUED FOR

CONSTRUCTION

EHRM INFRASTRUCTURE

UPGRADES

555 Willard Avenue, Newington, CT 06111

SCALE: 1/2" = 1'-0"D1

ELECTRICAL ENLARGED PLAN - FIRST

LEVEL - ROOM 65-110 - NEW

SCALE: 1/2" = 1'-0"F1

ELECTRICAL ENLARGED PLAN - FIRST

LEVEL - ROOM 65-110 - DEMO

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

12.

13.

14.

15.

16.

17.

18.

19.

20.

21.

22.

23.

24.

PROVIDE NEW 20" x 4" BONDING BAR, SET OF INSULATORS STAND-OFF

BRACKETS, AND STAINLESS STEEL SCREWS. PROVIDE ALL GROUNDING CABLE

AND CONNECTORS AND INSTALL PER TYPICAL DETAIL ON T-500 SERIES SHEETS.

NEW 5KW RACK-MOUNTED 208 V UNINTERRUPTIBLE POWER SUPPLY (UPS) WITH

NEMA 20A L21-20P INPUT AND L21-20R OUTPUT. PROVIDE NEW 208V 3-PHASE

CIRCUIT AND RECEPTACLE ON EMERGENCY POWER CIRCUIT. SEE T-500 SERIES

SHEETS FOR MORE DETAILS.

PROVIDE ONE NEW EMERGENCY AND ONE NEW NORMAL POWER BRANCH

120/208 TPST CIRCUIT BREAKER FED FROM ABOVE FOR EACH RACK UPS

CIRCUIT. PROVIDE NEW CONDUIT, CONDUCTORS, AND DEVICES TO SUPPLY

EACH NEW RECEPTACLE. SEE T-500 SERIES SHEETS FOR MORE DETAILS.

NEW NORMAL POWER RECEPTACLE, SEE PANEL SCHEDULE FOR ADDITIONAL

INFORMATION.

NEW EMERGENCY POWER RECEPTACLE, SEE PANEL SCHEDULE FOR

ADDITIONAL INFORMATION.

PROVIDE NEW GFCI WEATHER RESISTANT RECEPTACLE. PROVIDE WITH A

WEATHERPROOF, EXTRA-DUTY, IN-USE COVER PER NEC 406.9.

NEW MECHANICAL INDOOR AND OUTDOOR UNITS, SEE MECHANICAL SHEETS

FOR ADDITIONAL INFORMATION.

SUB-METERING OF NEW DEDICATED ROOM AIR CONDITIONING, NON-IT LOAD

ONLY. PANEL SERVING UNIT SHALL BE EQUIPPED WITH NEW MONITORED

POWER METER INTEGRATED INTO PANEL. BASIS OF DESIGN: EATON OR

SQUARE-D.

SUB-METERING OF NEW DEDICATED TR, IT LOAD ONLY. PANEL SERVING TR

SHALL BE EQUIPPED WITH NEW MONITORED POWER METER INTEGRATED INTO

PANEL. BASIS OF DESIGN: EATON OR SQUARE D.

NEW POWER SUPPLY AND BATTERY BACKUP FOR NEW PACS EQUIPMENT.

PROVIDE A 20 AMP CIRCUIT PER NEC AND MANUFACTURERS

RECOMMENDATIONS.

PROVIDE NEW ACCESS CONTROL PER SPECIFICATIONS. HDP12 COMPLIANT,

CARD READER WITH PINPAD CARD, PIV READY.

LIGHTS SHALL BE WIRED TO THE NEW WALL MOUNTED SINGLE POLE SWITCH AT

THE CLOSET ENTRANCE. THE CONTROL SCHEME FOR THE LIGHTING CONTROL

SHALL BE MANUAL ON/ MANUAL OFF. COORDINATE FIXTURES WITH OVERHEAD

CABLE TRAY.

INDOOR UNIT IS POWERED BY OUTDOOR UNIT.

REMOVE EXISTING LIGHT FIXTURES.

NEW NORMAL POWER ELECTRICAL PANEL, FIELD COORDINATE LOCATION WITH

EXISTING AND NEW CONDITIONS. SEE E-600 AND E-700 SERIES SHEETS FOR

ADDITIONAL INFORMATION.

NEW EMERGENCY POWER ELECTRICAL PANEL, FIELD COORDINATE LOCATION

WITH EXISTING AND NEW CONDITIONS. SEE E-600 AND E-700 SERIES SHEETS

FOR ADDITIONAL INFORMATION.

REMOVE EXISTING RECEPTACLES.

REMOVE EXISTING LIGHTING SWITCHES.

REMOVE EXISTING JUNCTION BOX.

PROVIDE HEAVY DUTY NEMA 3R RATED 600V NON-FUSED DISCONNECT SWITCH

FOR MECHANICAL UNIT. SEE ELECTRICAL SCHEDULES ON E-700 SERIES SHEETS

FOR ADDITIONAL INFORMATION. COORDINATE LOCATION WITH NEW AND

EXISTING CONDITIONS.

2#10, #10 GND - 3/4"C. 30A DISCONNECT.

PROVIDE TRI-TECH (PIR, MICROWAVE, DOPLER) MOTION SENSOR.

NEW 4” SPEED CONDUIT SLEEVE THROUGH WALL ABOVE CEILING GRID FOR

HORIZONTAL VOICE/DATA CABLING OR FIBER WITH PLASTIC BUSHINGS ON BOTH

ENDS TO PROTECT CABLES,CABLE TRAY AND SPEED SLEEVE FILL SHALL NOT

EXCEED 40%. FIRE CAULK PENETRATION PER SPECIFICATIONS.

VFD FURNISHED BY MECHANICAL CONTRACTOR, INSTALLED BY ELECTRICAL

CONTRACTOR. COORDINATE FINAL LOCATION WITH MECHANICAL CONTRACTOR.

NOTE: NOT ALL KEYNOTES

ARE USED ON EACH SHEET

A.

B.

C.

D.

E.

F.

G.

H.

I.

J.

K.

L.

M.

N.

O.

P.

CONTRACTOR SHALL COORDINATE ALL EQUIPMENT, DUCTWORK AND PIPING

WITH STRUCTURAL, MECHANICAL, AND ELECTRICAL SYSTEMS AND SHALL

PROVIDE NECESSARY OFFSETS TO AVOID CONFLICTS AND TO MAINTAIN

REQUIRED EQUIPMENT ACCESS AND SERVICEABILITY.

EXISTING CONDITIONS ARE BASED ON EXISTING PLANS AND FIELD VERIFICATION

WHERE FEASIBLE. CONSTRUCTION AREA CONDITIONS MAY DIFFER FROM

THOSE INDICATED.

MINIMUM BRANCH CIRCUIT SIZE SHALL BE 2#12, 1#12G., 3/4"C.

CONTRACTOR SHALL COORDINATE FINAL POINT OF CONNECTIONS

WITH VA COR PRIOR TO ROUGH-IN.

PROVIDE NEMA 3R ENCLOSURES FOR EQUIPMENT INSTALLED

OUTDOORS

SIZE BRANCH CIRCUITS AND FEEDERS TO EQUIPMENT PER PANEL

SCHEDULE AND FEEDER AND BRANCH CIRCUIT SIZING TABLE ON E-701.

COORDINATE FINAL EQUIPMENT CONNECTIONS AT EQUIPMENT WITH

EQUIPMENT SUPPLIER, PRIOR TO ROUGH-IN.

LABEL DEVICE PLATES WITH A PERMANENT ADHESIVE LABEL LISTING

PANEL AND CIRCUIT FEEDING THE WIRING DEVICE.

UPDATE PANEL SCHEDULES AFFECTED BY RENOVATION.

NEW CIRCUIT BREAKERS PROVIDED SHALL MATCH THE EXISTING TYPE

AND AIC RATING OF CIRCUIT BREAKERS IN PANEL BEING RENOVATED.

CONTRACTOR SHALL FIELD COORDINATE CABLE TRAY LAYOUT WITH

EXISTING UTILITIES ROUTED THROUGH THE RENOVATED SPACE.

CONTRACTOR SHALL COMPLY WITH NEC 300.22 FOR CONDUIT ROUTED IN

PLENUM SPACES.

REFER TO E-901 FOR CUTSHEETS.

COMPLY WITH NEC 220.87 FOR ALL 30-DAY LOAD MEASUREMENTS OF

PANELBOARDS.

LOCATE DISCONNECT SWITCHES TO MAINTAIN WORKING CLEARANCES

PER NEC 110.26.

CONTRACTOR SHALL LABEL ALL JUNCTION BOX COVERS WITH THE CIRCUITS

CONTAINED AND SOURCE PANEL IDENTIFIED.

Revisions: Date:

07/03/2024

07/03/2024

07/03/2024

FLOOR

CEILING

CR

3/4" EMT

DOOR

POSITION

SWITCH

J

1" EMT STUBBED INTO

NEAREST ACCESSIBLE CEILING

SPACE.

4" SQ BOX WITH BLANK FACEPLATE

(OPPOSITE SIDE OF DOOR FROM

CARD READER) POSITIONED

CENTERED ABOVE DOOR FOR

FUTURE POSSIBLE REQUEST TO EXIT

DEVICE.

3/4" EMT

ELECTRIC

STRIKE. SEE DOOR

SCHEDULE

4" SQ BOX FOR CARD

READER. SEE

SPECIFICATIONS.

DRILL HOLE THROUGH DOOR

FRAME FOR CABLE PATHWAY

ELECTRIC STRIKE.

WALL

1"EMT CONDUIT

JUNCTION BOX

8'-6" AFF

CABLE TRAY TO

TELECOMMUNICATIONS

RACK

07/03/2024

07/03/2024

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

CONSULTANT

321 4 5 6 7 8 9 10

TRIPLE C - The A/E Group 201 E. Jefferson Street, Suite 200 Syracuse, NY 13202

MAT PERKINS

(315) 484-5958

STAMP

Au to de sk

D oc s:

//6

A4

-2 2-

0_

N ew in gt on _V

AM

C

_E H

R M

_I U

-1

2/

9A 4-

-7

.N ew in gt on

.E H

R M

.M

EP

.G en er al

.S he et s.

rv t

-0

7-

8:

:4

65E-501

ELECTRICAL DETAILS 689A4-22-700

07/03/2024 M. Perkins K. McDermott

ISSUED FOR

CONSTRUCTION

EHRM INFRASTRUCTURE

UPGRADES

555 Willard Avenue, Newington, CT 06111

NTSF9 DOOR ROUGH-IN - ACCESS CONTROLLED DOOR

NTSF7 CAMERA INTERIOR WALL MOUNTING

Revisions: Date:

07/03/2024

07/03/2024

07/03/2024

B65-TR65110A

208/120V

125A-PANEL

60A-MCB

B65-TR65110B

208/120V

125A-PANEL

60A-MCB

60A 3P 6 60A

3P 6

GROUND LEVEL

5 5

(E) TBD

208/120V, 3P, 4W

(E) TBD

208/120V, 3P, 4W

1 18 8

07/03/2024

07/03/2024

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

CONSULTANT

321 4 5 6 7 8 9 10

GENERAL NOTES

TRIPLE C - The A/E Group 201 E. Jefferson Street, Suite 200 Syracuse, NY 13202

MAT PERKINS

(315) 484-5958

STAMP

Au to de sk

D oc s:

//6

A4

-2 2-

0_

N ew in gt on _V

AM

C

_E H

R M

_I U

-1

2/

9A 4-

-7

.N ew in gt on

.E H

R M

.M

EP

.B

_R

.rv t

-0

7-

1:

:5

65E-601

ELECTRICAL ONE-LINE DIAGRAMS 689A4-22-700

07/03/2024 M. Perkins J. Schooley

ISSUED FOR

CONSTRUCTION

EHRM INFRASTRUCTURE

UPGRADES

555 Willard Avenue, Newington, CT 06111

KEYNOTES NOTE: NOT ALL KEYNOTES ARE

USED ON EACH SHEET.

ALL NEW FEEDER CONDUCTORS SHALL BE CONTINUOUS

WITH NO SPLICES.

ALL FEEDERS SHALL BE COPPER WITH 90° C. (THHN/THWN)

INSULATION.

NEW CIRCUIT BREAKERS SHALL BE TYPE TO MATCH

EXISTING, U.N.O. PROVIDE ALL REQUIRED MOUNTING

HARDWARE, LUGS AND COVERPLATES FOR A COMPLETE

INSTALLATION.

FEEDER VOLTAGE DROP CALCULATIONS ARE INDICATED FOR

FEEDERS EXCEEDING 100'-0".

CONTRACTOR TO PROVIDE SHORT CIRCUIT, OVERCURRENT

PROTECTIVE DEVICE COORDINATION AND ARC FLASH

ANALYSIS FOR ALL NEW PANELS, SWITCHBOARDS AND

SWITCHGEAR. STUDY SHALL INCLUDE EXISTING SYSTEM TO

THE EXTENT THAT THE FAULT CURRENT, COORDINATION AND

ARC FLASH PREPARED IN COMPLIANCE WITH 2018 NFPA 70E

FOR THE NEW PANELS CAN BE CALCULATED. CONTRACTOR

IS RESPONSIBLE FOR ALL DATA COLLECTION REQUIRED TO

COMPLETE THE ANALYSIS. REPORT OF THE ANALYSIS SHALL

BE PREPARED SUMMARIZING THE INPUT DATA, SINGLE-LINE

USED IN CALCULATION, AND RESULTS INCLUDING ARC FLASH

LABELS. REPORT SHALL BE STAMPED AND SIGNED BY

PROFESSIONAL ENGINEER UNDER WHOSE DIRECTION THE

STUDY WAS PERFORMED. CONTRACTOR TO INSTALL ARC

FLASH LABELS ON PANELS IN COMPLIANCE WITH 2018 NFPA

70E. ELECTRICAL EQUIPMENT SUBMITTALS SHALL REFLECT

RESULTS OF SHORT CIRCUIT ANALYSIS. CONTRACTOR SHALL

SET ALL ADJUSTABLE CIRCUIT BREAKERS PER

OVERCURRENT PROTECTIVE DEVICE STUDY. MINIMAL

INFORMATION INCLUDED ON ARC FLASH LABELS INCLUDE:

• NOMINAL SYSTEM VOLTAGE

• ARC FLASH BOUNDARY

• AT LEAST ONE OF THE FOLLOWING:

A. EITHER THE AVAILABLE INCIDENT

ENERGY AND THE CORRESPONDING

WORKING DISTANCE, OR THE ARC

FLASH PPE CATEGORY FOR THE

EQUIPMENT, BUT NOT BOTH.

B. MINIMUM ARC RATING OF CLOTHING.

C. SITE-SPECIFIC LEVEL OF PPE.

ANALYSIS SHALL BE PREPARED PRIOR TO OR CONCURRENT

WITH ELECTRICAL SWITCHGEAR, SWITCHBOARDS AND

PANEL SUBMITTALS. EQUIPMENT SUBMITTALS WITHOUT

ANALYSIS SHALL BE REJECTED AND NOT REVIEWED.

EEOR CAN NOT BE RESPONSIBLE FOR ANALYSIS UNLESS

SEPARATELY AND SPECIFICALLY CONTRACTED TO DO SO.

CONTRACTOR SHALL PROVIDE A 30 DAY LOAD

MEASUREMENT OF EQUIPMENT INDICATED AND PROVIDE

THE RESULTS TO THE ELECTRICAL ENGINEER OF RECORD

(EEOR) TO VERIFY THE EQUIPMENT HAS CAPACITY TO

SUPPORT ADDITIONAL LOAD.

1.

2.

3.

4.

5.

6.

7.

CONTRACTOR SHALL PROVIDE A 30 DAY LOAD MEASUREMENT

OF EQUIPMENT INDICATED AND PROVIDE THE RESULTS TO THE

ELECTRICAL ENGINEER OF RECORD (EEOR) TO VERIFY THE

EQUIPMENT HAS CAPACITY TO SUPPORT ADDITIONAL LOAD.

PROVIDE SPD DEVICE INTEGRATED INTO PANEL BOARD.

PROVIDE SUB-METERING OF NEW DEDICATED TR, IT LOAD ONLY.

CIRCUITS SHALL BE EQUIPPED WITH NEW MONITORED POWER

METER INTEGRATED INTO PANEL. BASIS OF DESIGN: EATON OR

SQUARE D.

PROVIDE SUB-METERING OF NEW DEDICATED ROOM HVAC

SYSTEM(S). CIRCUITS SHALL BE EQUIPPED WITH NEW

MONITORED POWER METER INTEGRATED INTO PANEL. BASIS OF

DESIGN: EATON OR SQUARE D.

PROVIDE NEW FEED BASE ON LOAD INDICATED. REFER TO

SHEET E-701 FOR SIZING.

PROVIDE CIRCUIT BREAKER INDICATED IN AVAILABLE SPACE.

NEW PANELBOARD TO HAVE PXR20 SERIES BASIS OF DESIGN OR

SIMILAR ELECTRONIC TRIP CIRCUIT BREAKER AND BE

COORDINATED. COORDINATION STUDY TO BE SUBMITTED PRIOR

TO MAIN BREAKER SELECTION.

8. CONTRACTOR TO DETERMINE PANEL BOARD AND VERIFY

EXISTING AVAILABLE SPACE FOR NEW CIRCUIT BREAKER.

Revisions: Date:

07/03/2024

07/03/2024

07/03/2024

FEEDER & BRANCH CIRCUIT SIZING SCHEDULE -

GENERAL PURPOSE

2/0 6 1 1/2" 2" 2"

1 1/2"

2 1/2"

2-2 1/2"

3-2 1/2"

4-2 1/2"

5-2 1/2"

6-2 1/2"

2-500

2-600

3-400

4-350

5-400

6-400

5-4/0

6-250

2-1/0

2-1/0

3-2/0

4-3/0

2-3"

2-3"

3/0

4/0

2-4/0

2-250

2-350

3"3

2-2

2-2

2-1

3 3"

2-2"

2-2"

2"

2"

6-3"

3-3"

4-3"

5-3"

2-3"

2-3"

6-3"

2-3 1/2"

3-3"

4-3"

5-3"

2-4"

3"

2-2 1/2"

4"

2-2"

2-3"

2 1/2"

3"

2"

2"

3 1/2"

2-2 1/2"

2-3"

4"

2-2 1/2"

2 1/2"

3"

2"

2 1/2"

3/4"(1")

3/4"(1")

3/4"

3/4"

3/4"

3/4"

1"(1 1/4")

1 1/4"

1 1/4"

1 1/4"

2 WIRE

8(6)

6(4)

6(4)

4(2)

3(2)

2(1)

1/0

1(1/0)

8 1"

PHASE

& NEUTRAL

WIRE SIZE - AWG OR KCMIL

E.G.

3/4" 3/4"

1 1/4"(1 1/2")1 1/4"(1 1/2")

1 1/2"

1 1/2"

1 1/4"

3/4"(1")

3/4"(1")

3/4"

1"(1 1/4")

2"

1 1/2"(2")

1 1/4"

1"(1 1/4")

1"(1 1/4")

1 1/4"

3/4"(1")

CONDUIT SIZE

3/4"

3/4"

3 WIRE

3/4"

3/4"

4 WIRE

(3PH & 1N) NOTE

1.

2.

3.

4.

CIRCUIT MAXIMUM DISTANCE IS BASED ON

NEC CHAPTER 9, TABLE 8 CONDUCTOR

PROPERTIES FOR COATED COPPER

CONDUCTORS AT 75 DEGREES CELSIUS.

MAXIMUM CIRCUIT LOAD FOR DISTANCE IS

BASED ON NEC 220-10(b)

BASED ON THHN/THWN, 90°., 600V.,

INSULATED, COPPER WIRE APPLIED AT 75°FOR

TERMINATIONS RATED AT 60°C/75°C AND 75°C.

FOR TERMINATIONS RATED AT 60°C PROVIDE

WIRE AND CONDUIT SIZES INDICATED IN

PARENTHESIS.

BASED ON WIRE OUTSIDE DIAMETERS AND

RIGID METALLIC CONDUIT INSIDE DIAMETERS

AS PROVIDED IN THE NEC. DO NOT REDUCE

CONDUIT SIZE FOR NON-RIGID METALLIC

APPLICATION. REFER TO NEC FOR CONDUIT

TYPES MORE RESTRICTIVE THAN RIGID

METALLIC.

NOTES:

(NOTES 1 & 2)

120V. SINGLE PHASE CIRCUIT LENGTH TABLE 208V. THREE PHASE CIRCUIT LENGTH TABLE

LOAD

(VOLT-AMPS)

MAX.

CIRCUIT

17280

14400

11520

(AMPS)

AMPACITY

BREAKER

CURRENT

(AMPS)

MAX.

CIRCUIT

NO.8

MAXIMUM LENGTH IN FEET

- 58

110 174

NO.12

NO.10

73 116

117-

NO.4

NO.6

(AMPS)

BREAKER

AMPACITY

LOAD

(VOLT-AMPS)

CIRCUIT

MAX.

CURRENT

(AMPS)

CIRCUIT

MAX.

234-- --

116-

NO.10

NO.12

233127

294 468

177 281

221 351139

NO.6

NO.4

NO.8

MAXIMUM LENGTH IN FEET

35-40

45-50

80-90

15-20

25-30

OVERCURRENT

DEVICE RATING

(AMPERES)

07/03/2024

07/03/2024

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

CONSULTANT

321 4 5 6 7 8 9 10

TRIPLE C - The A/E Group 201 E. Jefferson Street, Suite 200 Syracuse, NY 13202

MAT PERKINS

(315) 484-5958

STAMP

Au to de sk

D oc s:

//6

A4

-2 2-

0_

N ew in gt on _V

AM

C

_E H

R M

_I U

-1

2/

9A 4-

-7

.N ew in gt on

.E H

R M

.M

EP

.B

_R

.rv t

-0

7-

1:

:5

65E-701

ELECTRICAL SCHEDULES 689A4-22-700

07/03/2024 M. Perkins J. Schooley

ISSUED FOR

CONSTRUCTION

EHRM INFRASTRUCTURE

UPGRADES

555 Willard Avenue, Newington, CT 06111

1.

2.

PROVIDE A 30 DAY LOAD MEASUREMENT OF PANELBOARD

INDICATED. PROVIDE THE REPORT TO THE COR AND AE PRIOR

TO COMMENCEMENT OF PANELBOARD RENOVATION. PANEL

DEMAND IS CALCULATED BY LOADING EACH CIRCUIT BREAKER

TO 80% CAPACITY.

NEW ELECTRICAL PANEL AND CIRCUIT BREAKERS SIZED AS

INDICATED, SEE E-100 SERIES FOR PANEL LOCATION.

KEYNOTES

NOTE: NOT ALL KEYNOTES ARE USED ON EACH SHEET

LUMINAIRE SCHEDULE

TYPE DESCRIPTION MOUNTING VOLTS LAMPS DRIVER LOAD MANUFACTURER AND MODEL NO.

L1 4'0" LINEAR, WRAP AROUND ACRYLIC LENS, LED STRIP,

PENDANT 6” ABOVE CABLETRAY WITH PENDANT MOUNTING

KIT

PENDANT

9'0" AFF

MVOLT 3500k

85CRI

0-10V

DIMMABLE

42 VA COLUMBIA #LCL SERIES OR APPROVED EQUAL

L1B 4'0" LINEAR (BATTERY BACKED), WRAP AROUND ACRYLIC

LENS, LED STRIP, PENDANT 6” ABOVE CABLETRAY WITH

PENDANT MOUNTING KIT.

PENDANT

9'0" AFF

MVOLT 3500k

85CRI

0-10V

DIMMABLE

42 VA COLUMBIA #LCL SERIES OR APPROVED EQUAL

1. ADD SPD DEVICES TO ALL NEW TELECOM PANELBOARDS (SQ D OR EQUAL) FOR TYPE 2 PROTECTION.

2. ADD PXR 20 TRIP UNITS FOR ADJUSTING CIRCUIT BREAKERS (EATON OR EQUAL).

Notes:

Total Est. Demand: 19 A ACCESS CONTROLLER 83 VA 100.00% 83 VA Total Conn.: 19 A LTG 168 VA 125.00% 210 VA Total Est. Demand: 6791 VA NC 2288 VA 100.00% 2288 VA Total Conn. Load: 6751 VA Receptacle 4220 VA 100.00% 4220 VA Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Total Amps: 12 A 26 A 20 A Total Load: 1410 VA 3031 VA 2311 VA

29 SPD 20 A 1 0 VA -- 1 -- SPACE 30

27 SPD 20 A 1 0 VA -- 1 -- SPACE 28

25 SPD 20 A 1 0 VA -- 1 -- SPACE 26

23 SPACE -- 1 -- -- 1 -- SPACE 24

21 SPACE -- 1 -- -- 1 -- SPACE 22

19 SPACE -- 1 -- -- 1 -- SPACE 20

17 SPACE -- 1 -- 0 VA 1 20 A SPARE 18

15 SPACE -- 1 -- 0 VA 1 20 A SPARE 16

13 SPACE -- 1 -- 0 VA 1 20 A SPARE 14

11 SPACE -- 1 -- 1167... 12

9 SPACE -- 1 -- 1167... 10

7 SPARE 20 A 1 0 VA 1167...

3 20 A TR RM65-110 RACK RECEPTACLES

5 SPARE 20 A 1 0 VA 1144... 6

3 TR RM65-110 RECEPTACLE 20 A 1 720 VA 1144...

2 25 A VFD-CU-01-1

1 ACCESS CONTROLLER 20 A 1 83 VA 168 VA 1 20 A TR RM65-110 LIGHTING 2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Enclosure: Indoor MCB Rating: 60 A Mounting: Surface Wires: 4 Mains Rating: 125 A

Supply From: Phases: 3 Mains Type: MCB Location: DATA 65-110 Volts: 208Y/120 A.I.C. Rating: 10kA

Branch Panel: B65-TR65110B

1. ADD SPD DEVICES TO ALL NEW TELECOM PANELBOARDS (SQ D OR EQUAL) FOR TYPE 2 PROTECTION.

2. ADD PXR 20 TRIP UNITS FOR ADJUSTING CIRCUIT BREAKERS (EATON OR EQUAL).

Notes:

Total Est. Demand: 12 A Total Conn.: 12 A

Total Est. Demand: 4400 VA Total Conn. Load: 4400 VA

Receptacle 4400 VA 100.00% 4400 VA Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Total Amps: 11 A 16 A 10 A Total Load: 1347 VA 1887 VA 1167 VA

29 SPD 20 A 1 0 VA -- 1 -- SPACE 30

27 SPD 20 A 1 0 VA -- 1 -- SPACE 28

25 SPD 20 A 1 0 VA -- 1 -- SPACE 26

23 SPACE -- 1 -- -- 1 -- SPACE 24

21 SPACE -- 1 -- -- 1 -- SPACE 22

19 SPACE -- 1 -- -- 1 -- SPACE 20

17 SPACE -- 1 -- -- 1 -- SPACE 18

15 SPACE -- 1 -- -- 1 -- SPACE 16

13 SPACE -- 1 -- -- 1 -- SPACE 14

11 SPACE -- 1 -- 0 VA 1 20 A SPARE 12

9 SPACE -- 1 -- 0 VA 1 20 A SPARE 10

7 SPACE -- 1 -- 0 VA 1 20 A SPARE 8

5 SPACE -- 1 -- 1167... 6

3 TR RM65-110 RECEPTACLE 20 A 1 720 VA 1167... 4

1 RECEPTACLE FOR OUTDOOR UNIT 20 A 1 180 VA 1167...

3 20 A TR RM65-110 RACK RECEPTACLES

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Enclosure: Indoor MCB Rating: 60 A Mounting: Surface Wires: 4 Mains Rating: 125 A

Supply From: Phases: 3 Mains Type: MCB Location: DATA 65-110 Volts: 208Y/120 A.I.C. Rating: 10kA

Branch Panel: B65-TR65110A2 2

Revisions: Date:

07/03/2024

07/03/2024

07/03/2024

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

CONSULTANT

321 4 5 6 7 8 9 10

TRIPLE C - The A/E Group 201 E. Jefferson Street, Suite 200 Syracuse, NY 13202

MAT PERKINS

(315) 484-5958

STAMP

Au to de sk

D oc s:

//6

A4

-2 2-

0_

N ew in gt on _V

AM

C

_E H

R M

_I U

-1

2/

9A 4-

-7

.N ew in gt on

.E H

R M

.M

EP

.G en er al

.S he et s.

rv t

-0

7-

9:

:0

65E-902

ELECTRICAL CUTSHEETS & BASIS OF DESIGN 689A4-22-700

07/03/2024 M. Perkins K. McDermott

ISSUED FOR

CONSTRUCTION

EHRM INFRASTRUCTURE

UPGRADES

555 Willard Avenue, Newington, CT 06111

4 35 ED UHL ELL14

Revisions: Date:

07/03/2024

07/03/2024

07/03/2024

NOTE: NOT ALL ABBREVIATIONS AND

SYMBOLS APPLY TO THIS PROJECT.

ELECTRICAL ABBREVIATIONS

CR

MD

MD

DC

ES

RX

SECURITY DOOR CONTACT. PROVIDE AND INSTALL 4S BACK BOX ABOVE DOOR WITH A 1" EMT

CONDUIT STUBBED INTO NEAREST ACCESSIBLE CEILING SPACE. PROVIDE ALL CONDUIT,

CONDUIT SUPPORT, CONNECTORS, COUPLINGS, PLASTIC BUSHINGS, PULL STRINGS, OUTLET

BOX AND MUD RING.

WALL MOUNTED SINGLE SENSOR CAMERA. PROVIDE AND INSTALL 4S BACK BOX W/ A 1" EMT

CONDUIT HOMERUN TO CABLE TRAY. PROVIDE ALL CONDUIT, CONDUIT SUPPORT, CONNECTORS,

COUPLINGS, PLASTIC BUSHINGS, PULL STRINGS, OUTLET BOX AND MUD RING. EACH CAMERA TO

HAVE ONE(1) CATEGORY 6A CABLE PROVIDED BY SECURITY CONTRACTOR. PROVIDE WITH

MANUFACTURER'S WALL MOUNTING ACCESSORIES.

CARD READER OUTLET. PROVIDE AND INSTALL 4S BACK BOX AT SWITCH HEIGHT WITH A 3/4" EMT

CONDUIT CONNECTED TO THE DOOR CONTACT OUTLET BOX. PROVIDE ALL CONDUIT, CONDUIT

SUPPORT, CONNECTORS, COUPLINGS, PLASTIC BUSHINGS, PULL STRINGS, OUTLET BOX AND MUD

RING.

DATA/VOICE OUTLET - FLOORBOX. PROVIDE AND INSTALL, LIKE FOR LIKE, CAT 6A CMP

CABLES/JACKS TERMINATED IN FLOOR BOX. PROVIDE AND INSTALL (2) 1-1/4" CONDUIT STUBBED TO NEAREST FURRED WALL , ROUTE CONDUIT TO ACCESSIBLE LOCATION ABOVE FINISHED CEILING.

PROVIDE BUSHINGS AND PULLSTRING, U.O.N. USE EXISTING CONDUIT RISERS IN-WALL AND EXTEND ALL CABLES TO NEW CABLE TRAY AND ROUTE TO TR INDICATED. SEE T-700 SERIES SHEETS FOR

NUMBER OF CABLES REQUIRED AT EACH WAO.

DATA/VOICE OUTLET - WALL MOUNTED. PROVIDE AND INSTALL, LIKE FOR LIKE, CAT 6a CMP CABLES / JACKS TERMINATED IN 6-PORT FACEPLATE AT 18" AFF. PROVIDE AND INSTALL 5S JBOX WITH SINGLE GANG MUDRING AND 1-1/4" CONDUIT STUBBED TO ACCESSIBLE CEILING LOCATION. PROVIDE BUSHINGS AND PULLSTRING, U.O.N. (SLASH INDICATES MOUNTING ABOVE FINISH COUNTER). USE EXISTING CONDUIT RISERS IN-WALL AND EXTEND ALL CABLES TO NEW CABLE TRAY AND ROUTE TO

TR INDICATED. SEE T-700 SERIES SHEETS FOR NUMBER OF CABLES REQUIRED AT EACH WAO.

DATA/VOICE OUTLET - CEILING MOUNTED. PROVIDE AND INSTALL (2) CAT 6A CMP CABLES / JACKS

TERMINATED IN A 2-PORT FACEPLATE AT FINISHED CEILING. (NOTE: AT HARDLID CEILING

LOCATIONS PROVIDE AND INSTALL 5SJBOX WITH 1-1/4" CONDUIT STUBBED TO ACCESSIBLE CEILING LOCATION. PROVIDE BUSHINGS AND PULLSTRING, U.O.N.) SURFACE TYPE ("F" DENOTES FLUSH TYPE) USE EXISTING CONDUIT RISERS IN-WALL AND EXTEND ALL CABLES TO NEW CABLE TRAY AND ROUTE TO TR INDICATED. SEE T-700 SERIES SHEETS FOR NUMBER OF CABLES REQUIRED AT EACH

WAO.

REQUEST-TO-EXIT. ELECTRICAL CONTRACTOR SHALL PROVIDE AND INSTALL 1" EMT CONDUIT

CONNECTED TO THE DOOR POSITION SWITCH BOX. PROVIDE ALL CONDUIT, CONDUIT SUPPORT,

CONNECTORS, COUPLINGS, PLASTIC BUSHINGS, PULL STRINGS, OUTLET BOX AND MUD RING.

ELECTRIFIED DOOR HARDWARE. PROVIDE AND INSTALL 3/4" EMT CONDUIT CONNECTED TO THE

DOOR CONTACT OUTLET BOX.

CEILING MOUNTED SECURITY MOTION SENSOR. PROVIDE AND INSTALL 1-GANG BACK BOX AND (1) 1" CONDUIT STUBBED UP TO ACCESSIBLE CEILING SPACE. PROVIDE BUSHINGS AND PULLSTRING, U.O.N.

WALL MOUNTED SECURITY MOTION SENSOR. PROVIDE AND INSTALL 1-GANG BACK BOX AND (1) 1" CONDUIT STUBBED UP TO ACCESSIBLE CEILING SPACE. PROVIDE BUSHINGS AND PULLSTRING, U.O.N.

DATA/VOICE OUTLET - ABOVE CEILING.

A INTERCOMMUNICATION SYSTEM ( AI PHONE)

D D

FURNITURE/EQUIPMENT FEED DEDICATED JUNCTION BOX. PROVIDE AND INSTALL RACO 260 5S

JUNCTION BOX WITH (1) 1-1/4" CONDUIT TO ACCESSIBLE CEILING. EXTEND TO CABLE TRAY.

MOUNTING HEIGHT NOTES:

1. ALL ELEVATIONS ARE TO CENTER LINE OF DEVICE, UNLESS OTHERWISE NOTED.

2. REFER TO EQUIPMENT ELEVATION DRAWINGS FOR COORDINATION WITH

CASEWORK.

3. MOUNT MANUAL MOTOR STARTER ADJACENT TO OR ON UNIT.

4. REFER TO ARCHITECTURAL A0 SERIES FOR ADDITIONAL ELECTRICAL DEVICE

MOUNTING HEIGHTS AND DEVICE ALIGNMENT RULES.

WALL SWITCHES

RECEPTACLES

TELECOMMUNICATIONS OUTLETS

TELECOMMUNICATIONS OUTLETS - WALL PHONE

CLOCK OUTLETS

TV OUTLETS

PUSHBUTTONS

VOLUME CONTROLS

NURSE CALL STATIONS

NURSE CALL DOME LIGHTS

DIMMERS

ACCESS CONTROL DEVICES

VANITY LIGHT IN TOILET

INTERCOM

FIREMAN'S PHONE

FIRE ALARM - PULL STATIONS

FIRE ALARM DEVICES HORN/SPEAKERS/STROBES

(MOUNTING HEIGHT AT THE TOP OF THE FIRE ALARM DEVICE OR

6" BELOW CEILING WHICH IS LOWER)

4'-0" AFF

1'-6" AFF

1'-6" AFF

4'-0" AFF

7'-0" AFF

1'-6" AFF

4'-0" AFF

4'-0" AFF

4'-0" AFF

7'-6" AFF

4'-0" AFF

4'-0" AFF TO TOP

6" ABOVE THE MIRROR, UON

4'-0" AFF TO TOP

4'-0" AFF

4'-0" AFF

7'-2" AFF TO TOP

SECURITY SYSTEM SYMBOLS

TELECOMMUNICATION SYMBOLS

MOUNTING HEIGHTS

REFERENCE SYMBOLS

SECTION NUMBER

DETAIL NUMBER

DRAWING NUMBER WHERE DRAWN

DRAWING NUMBER WHERE DRAWN

E1-1.0 KEY NOTE

E1-1.0

DISCONNECT SWITCHES

MOTOR STARTERS

PANELBOARDS & CABINETS

INDIVIDUAL CIRCUIT BREAKERS

5'-6" AFF

5'-6" AFF

6'-0" AFF TO TOP

5'-6" AFF

WAP

WIRELESS ACCESS POINT OUTLET - CEILING MOUNTED. PROVIDE AND INSTALL (2) CAT 6A CMP CABLES / JACKS TERMINATED IN A SURFACE MOUNT BOX ABOVE FINISHED CEILING. (NOTE: AT HARDLID CEILING LOCATIONS, PROVIDE AND INSTALL 5S JBOX WITH 1-1/4" CONDUIT STUBBED TO ACCESSIBLE CEILING LOCATION. PROVIDE BUSHINGS AND PULLSTRING, U.O.N. TERMINATE CABLES ON JACKS IN 2-PORT FACE PLATE. PROVIDE 25FT. SLACK ON EVERY CABLE IF THE DISTANCE

ALLOWS. PROVIDE (1) CAT6A CMP GREEN TO VA-IDF.

SPST

SWBD

SYM

STD

SW

SPEC(S)

SPDT

SPKR

SF

SEC

SINGLE POLE SINGLE THROW

SINGLE POLE DOUBLE THROW

SYMMETRICAL

SWITCHBOARD

STANDARD

SWITCH

SECONDARY

SQUARE FOOT

SPECIFICATION(S)

SPEAKER

PRI

RCLP

RM

SCH, SCHED

RP

REF

REC/RCPT

RSC

RLA

RF

R, RE

QTY

PWR

PT

PVC

PA

PH, ∅

PF

PNL

PE

PB

P

OPP

OHE/T

OH

OFOI

OFCI

NO., NUM, #

OC

NTS

AMERICAN WIRE GAUGE

ABOVE FINISHED FLOOR

ABOVE FINISHED GRADE

AUTOMATIC TRANSFER SWITCH

AMPERE INTERRUPTING CAPACITY

ALTERNATING CURRENT

ABOVE FINISHED COUNTER

AWG

BDF

B/BUR

BUILDING DISTRIBUTION FRAME

BURIED

AUTO

AUX

ARCH

AT

ATS

ALT

AFG

AIC

AFC

AFF

AC

AF

AUXILIARY

ALTERNATE

ARCHITECT

AUTOMATIC

AMPERES TRIP

AMPERE FRAME (BREAKER RATING)

MTG

NC

NEMA

NO

NIC

NEC

N

MV

MH

MOCP

MTD

MLO

MIN

MISC

MECH

MCC

MFR

MCA

MCB

RIGID STEEL CONDUIT

RATED (RUNNING) LOAD AMPS

RECEPTACLE PANELBOARD

ROOM

SCHEDULE

RADIO FREQUENCY

RECEPTACLE

REFRIGERATOR

RELOCATE AS SHOWN

POTENTIAL TRANSFORMER

POLYVINYL CHLORIDE

REMOTE CONTROL LIGHTING PANEL

QUANTITY

POWER

PUBLIC ADDRESS

PANEL

PRIMARY

PULL BOX

POWER FACTOR

PHOTO ELECTRIC

PHASE

POLE

OPPOSITE

OWNER FURNISHED, CONTRACTOR INSTALLED

OWNER FURNISHED, OWNER INSTALLED

OVERHEAD ELECTRIC/TELEPHONE

OVERHEAD

ON CENTER

NOT TO SCALE

NUMBER

MOUNTING

NATIONAL ELECTRICAL CODE

MEDIUM VOLTAGE (OVER 600V LESS THAN

35KV)

NORMALLY CLOSED

NORMALLY OPEN

NOT IN CONTRACT

NEUTRAL

MINIMUM CIRCUIT AMPACITY

MAIN CIRCUIT BREAKER

MOTOR CONTROL CENTER

MAXIMUM OVERCURRENT PROTECTION

MOUNTED

MISCELLANEOUS

MAIN LUGS ONLY

MINIMUM

MANHOLE

MANUFACTURER

MECHANICAL

SWGR SWITCHGEAR

AIR HANDLING UNITAHU

MTS MANUAL TRANSFER SWITCH

PDP POWER DISTRIBUTION PANEL

AMPERESA OR AMP

OCPD OVERCURRENT PROTECTION DEVICE

A

M

B

N

O

P

Q

R

S

T

SPD SURGE PROTECTIVE DEVICE

OD OUTLET DESIGNATOR

LOW VOLTAGE (BELOW 50 VOLTS)

L-L L-N

LTG

LV

LIGHTING

LINE TO LINE

LINE TO NEUTRAL

1000 CIRCULAR mils

KILOVOLTS (THOUSAND VOLTS)

KILOWATTS (THOUSAND WATTS)

LIGHTNING ARRESTOR

LOCAL AREA NETWORK

KILOVOLTS-AMPERES (THOUSAND VOLT-AMPS)

ISOLATED GROUND

KWH

LAN

LA

KW

KVA

Kcmil

KV

KILOWATT-HOURS

IR

KEY INTERLOCK

JUNCTION BOX

INCH/INCHES (")

INFRARED

GROUND FAULT INTERRUPTER

HAND-OFF-AUTOMATIC

HIGH PRESSURE SODIUM

HEATING VENTILATION AND AIR CONDITIONING

HERTZ

HVAC

HZ

HTR

HR

HT

HPS

HOA

HP

HEATER

HEIGHT

HORSEPOWER

HOUR

GFI

G, GND, GRD

GEN

FLUOR

FL, FLR

GROUND

GENERATOR

FOOT/FEET (')

FLUORESCENT

FLOOR

CMP

FIRE ALARM ANNUNCIATOR PANEL

EQUIPMENT GROUND

FAAP

FLA

FDR

FA

FULL LOAD AMPS

FEEDER

FIRE ALARM

FUSE

EG

CONTROL POWER TRANSFORMER

CURRENT TRANSFORMER

DBB

dB

DAS

DISPLAY BACKBOX

DISTRIBUTED ANTENNA SYSTEM

DECIBEL

CPT

CU

CT

COM, COMM

CKT

CLG

COPPER

COMMUNICATIONS

CIRCUIT

CEILING

COMMUNICATIONS PLENUM (CABLE JACKET

RATING)

CB CONDUIT BANK

COMMUNICATIONS RISER (CABLE JACKET RATING)

FIRE ALARM CONTROL PANELFACP

FIRE ALARM EXTENDER PANELFAEP

CCTV CLOSED CIRCUIT TELEVISION

CP CONSOLIDATION POINT

FLEX FLEXIBLE

HAND HOLEHH

LIGHTING CONTROL PANELLC, LCP

LIGHTING PANEL

L-G LINE TO GROUND

CMR

F

FT

IN

IG

JB, JBOX

K

LP

FOOT CANDLEFC

DMARC POINT OF DEMARCATION BETWEEN UTILITIES OR

BETWEEN UTILITIES AND OWNER PREMISE

EQUIPMENT

C

D

E

F

G

H

I

J

K

L

HORIZONTAL MOUNTINGH

COR CONTRACTING OFFICER'S REPRESENTATIVE

X

XFMR

WP

WHM

W/ W/O

W

VFD

VA

V

UPS

UL

UON

UG

UGS

UGT

UGP

TYP

TV

TP

TEL,TELE

TELECOM

TC

TRANSFORMER

REMOVE DEVICE

WATT HOUR METER

WEATHERPROOF

VOLTS

VARIABLE FREQUENCY DRIVE/

VARIABLE FREQUENCY MOTOR

CONTROLLER

WITHOUT

WITH

WATTS

VETERANS ADMINISTRATION

UNDERGROUND PRIMARY

UNDERGROUND SECONDARY

UNDERGROUND TELEPHONE

UNDERWRITER'S LABORATORY

UNLESS OTHERWISE NOTED

UNINTERRUPTIBLE POWER SUPPLY

UNDERGROUND

TELECOMMUNICATIONS

TYPICAL

TELEVISION

TAMPERPROOF

TIME CLOCK

TELEPHONE

TB TERMINAL BLOCK

TBB TELEPHONE BACKBOARD

U

V

W

X

Z

TPST TRIPLE POLE SINGLE THROW

FDS FORWARD DEPLOYED SERVICES

JOINT SECURITY ARCHITECTUREJSA

PIV PERSONAL IDENTITY VERIFICATION

GENERAL NOTES

1. ALL TELECOMMUNICATIONS WORK SHALL COMPLY WITH THE LATEST EDITION OF VA STANDARDS TELECOMMUNICATIONS INFRASTRUCTURE STANDARDS AND CURRENT MANUFACTURER AND BICSI

INSTALLATION PRACTICES. THESE STANDARDS HAVE BEEN ESTABLISHED TO EXCEED ALL CURRENT CODE AND BICSI INSTALLATION PRACTICE. ANY ITEMS THAT RAISE QUESTION SHALL BE BROUGHT TO THE ATTENTION OF THE CONSTRUCTION MANAGER AND REPRESENTATIVE IN WRITING. IT IS ALWAYS A BEST PRACTICE TO PROVIDE THE AHJ WITH DETAIL ON ANY AND ALL CONSTRUCTION ITEMS THAT COULD BE QUESTIONED BY THE AHJ. THE PROJECT DOCUMENTATION PACKAGE STANDARDS ARE NOT TO BE INTERPRETED NOR CONSIDERED AS AUTHORIZATION TO DEVIATE FROM ANY CODE OR REGULATION. IT IS THE CONTRACTOR ’S RESPONSIBILITY TO VALIDATE THAT THESE REQUIREMENTS WILL MEET THE EQUIPMENT MANUFACTURER ’S REQUIREMENT TO

PROVIDE A MINIMUM 25-YEAR SCS FOR ALL LABOR AND MATERIALS WARRANTIES.

2. IN THE EVENT OF A CONFLICT OR INCONSISTENCY BETWEEN ITEMS INDICATED ON THE PLANS AND/OR SPECIFICATIONS OR WITH THE AHJ REQUIREMENTS, THE DOCUMENT WHICH PRESCRIBES AND ESTABLISHES THE COMPLETE JOB AS PER MANUFACTURER OR THE HIGHER STANDARD SHALL PREVAIL. ALL DISCREPANCIES ARE TO BE BROUGHT TO THE ATTENTION OF THE CONSTRUCTION

MANAGER AND THE VA REPRESENTATIVE IN WRITING IMMEDIATELY UPON DISCOVERY.

3. OMISSIONS FROM THE DRAWINGS OR FROM THE SPECIFICATIONS OR THE MISDESCRIPTION OF DETAILS OF WORK WHICH ARE CLEAR AND NECESSARY TO CARRY OUT THE INTENT FOR THE DRAWINGS AND SPECIFICATIONS, OR WHICH ARE CUSTOMARILY PERFORMED SHALL NOT RELIEVE THE CONTRACTOR FROM PERFORMING SUCH OMITTED OR MISDESCRIBED DETAILS OF THE WORK.

THE CONTRACTOR SHALL NOTIFY THE CONSTRUCTION MANAGER AND VA REPRESENTATIVE UPON IDENTIFICATION OF SUCH OMISSIONS, MISDESCRIPTION, AND UNCLEAR DIRECTIONS IMMEDIATELY.

THE CONTRACTOR SHALL PERFORM ALL PROJECT TASKS AND ASSEMBLY BUILDS AS PER BICSI STANDARDS AND MANUFACTURER ’S REQUIREMENTS ALONG WITH COORDINATING AND WORKING

WITH THE VA TO CORRECT SUCH DOCUMENTATION ERRORS.

4. THE CONTRACTOR SHALL CHECK ALL DRAWINGS FURNISHED IMMEDIATELY UPON THEIR RECEIPT AND PROMPTLY NOTIFY THE VA OF ANY DISCREPANCIES. THIS INCLUDES BUT NOT LIMITED TO, DISCREPANCIES BETWEEN DRAWINGS AND SPECIFICATIONS, OR DRAWINGS AND MANUFACTURER INSTALLATION INSTRUCTIONS, OR DRAWINGS AND GOVERNING CODES AND BEST PRACTICES. THE CONTRACTOR SHALL BRING TO THE ATTENTION OF THE CONSTRUCTION MANAGER AND VA COR ANY DISCREPANCIES BETWEEN DRAWINGS AND HOW THE CONTRACTOR NORMALLY DELIVERS THE

SERVICES DESCRIBED IN THE DRAWINGS OR SPECIFICATIONS.

5. ALL MATERIALS AND EQUIPMENT FURNISHED AND INSTALLED SHALL BE NEW AND FREE FROM ANY KNOWN DEFECT. ALL EQUIPMENT SHALL BEAR THE UNDERWRITERS LABORATORIES LABEL (UL™) LISTING, CLASSIFIED, AND/OR PERFORMANCE VERIFIED MARK OR FROM A VA APPROVED ALTERNATIVE TESTING ORGANIZATION. ALL MATERIALS SHALL BE INSTALLED AND USED IN THE MANNER FOR WHICH THE MANUFACTURER INTEND THEM FOR. THIS APPLIES FOR BOTH PIECE PARTS AND COMPLETE FUNCTIONING ASSEMBLIES.

6. CONTRACTOR IS REQUIRED TO RECEIVE WRITTEN APPROVAL FOR ALL RECOMMENDED AND REQUIRED WORK DEVIATIONS AND CLARIFICATIONS TO THE PLANS AND SPECIFICATIONS OF THIS

PROJECT BY THE VA AND ITS REPRESENTATIVES PRIOR TO ANY FIELD ACTIVITY.

7. ALL WORK MUST BE COMPLETED IN AS PER MANUFACTURER INSTALLATION REQUIREMENTS AND BICSI INSTALLATION PRACTICES. THE VA DEMANDS THE UTMOST PROFESSIONALISM WHEN WORK IS BEING PERFORMED ON CAMPUS AND HOLDS ALL CONTRACTORS TO THAT LEVEL OF PROFESSIONALISM. THE WORK SITE SHALL BE KEPT CLEAN AND FREE FROM DEBRIS. IT IS EVERY CONTRACTOR AND ALL THEIR REPRESENTATIVE’S RESPONSIBILITY TO GUARD AGAINST ANY DAMAGE TO VA PROPERTY AND THE IMMEDIATE REPAIR IF ANY DAMAGE IS CAUSED. THE CONTRACTOR SHALL BE RESPONSIBLE FOR CONDUCTING A FINAL CLEANUP OF THE WORK SITE PRIOR TO FINAL SYSTEM ACCEPTANCE AS PART OF THE PUNCH-LIST PROCESS.

8. THE CONTRACTOR SHALL NOT BORE, NOTCH, OR IN ANY WAY CUT INTO ANY STRUCTURAL MEMBER WITHOUT WRITTEN APPROVAL FROM THE VA, ARCHITECT, AND STRUCTURAL ENGINEER. WITH PERMISSION FROM THE ABOVE AND PRIOR TO ALL CUTTING, DRILLING, NOTCHING, CORING, ETC. OF CONCRETE STRUCTURE AND FAÇADE THESE SURFACES SHALL BE X-RAYED OR GROUND PENETRATING RADAR USED TO ACCURATELY LOCATE REBAR, POST-TENSION CABLES & RODS, CONDUITS, AND ANY OTHER EMBEDDED POTENTIAL OBSTRUCTIONS TO

ENSURE THAT NO DAMAGE IS CAUSED TO ANY STRUCTURAL REINFORCEMENTS.

9. FOR THE PURPOSE OF CLEARNESS AND LEGIBILITY THE TELECOM DRAWINGS ARE ESSENTIALLY DIAGRAMMATIC. THE SIZE AND LOCATION OF EQUIPMENT IS SHOWN TO SCALE WHEREVER POSSIBLE. THE CONTRACTOR SHALL VERIFY ALL FIELD CONDITIONS WITH INFORMATION INDICATED ON THE DRAWINGS AND DESCRIBED IN THE SPECIFICATION SECTIONS WHERE TELECOM WORK

INTERFACES WITH OTHER TRADES.

10. THE CONTRACTOR SHALL TAKE SPECIAL PRECAUTIONS WHEN WORKING IN AREAS WITH EXISTING CEILINGS AND SHALL BE RESPONSIBLE FOR REMOVAL AND REPLACEMENT OF CEILING TILES WITHOUT DAMAGING OR SOILING THE CEILING TILES. CHIPPED, DAMAGED, CRACKED, OR BROKEN TILES ARE THE CONTRACTOR ’S RESPONSIBILITY TO REPLACE WITH LIKE TILES.

11. ALL FOOTAGES IDENTIFIED ON DRAWINGS OR SCALED OFF OF DRAWINGS ARE TO BE CONSIDERED ESTIMATES AND ARE RECOMMENDED TO BE FIELD VERIFIED BY CONTRACTOR PRIOR TO

ORDERING OF MATERIAL

12. ALL CABLE TRAYS, LADDER (TYPE) RACKING, CONDUIT, EQUIPMENT RACKS, PROTECTION PANELS, AND CABLE SHEATHS SHALL BE BONDED TO AN APPROVED TELECOMMUNICATIONS BONDING

ASSEMBLY.

13. ACCORDING TO TIA STANDARDS AND BICSI METHODOLOGIES PULL-BOXES LOCATED WITHIN A STRUCTURE ARE TO BE PLACED AT 100 ’ INCREMENTS AND PROPERLY SPACED WITHIN RUNS OF MORE THAN 150’. PULL-BOXES ARE TO BE PLACED IN CONDUIT RUNS THAT EXCEED A MAXIMUM OF 180-DEGREES IN CHANGES OF DIRECTION. TELECOMMUNICATIONS PULL-BOXES ARE TO BE SIZED AT A MINIMUM OF TWELVE (12) TIMES THE DIAMETER OF THE LARGEST CONDUIT. PULL-BOXES SHOULD NOT BE USED FOR CHANGES OF DIRECTION. THESE STANDARDS ARE TO BE ADHERED TO WHERE EVER PRACTICAL AND ANY DEVIATION TO THESE STANDARDS REQUIRES A SHOP-DRAWING, IF DISCOVERED DURING THE SUBMITTAL PHASE, TO REMEDIATE THE ISSUE OR BY AN RFI DURING THE CONSTRUCTION INSTALLATION PHASE. THE VA MAY ELECT TO INCREASE THE CONDUIT SIZE OR QUANTITY OF CONDUITS TO MITIGATE THE ISSUE FOR THE EXCESS LENGTH, ADDITIONAL QUANTITY OF CHANGES OF DIRECTION, AND/OR THE REDUCED SIZE OF PULL-BOXES WITHIN THE GIVEN PATHWAY. THE CONTRACTOR IS REQUIRED TO HAVE APPROVAL IN WRITING PRIOR TO ANY ROUGH-IN

WORK OR MATERIAL PROCUREMENT.

14. AS A STANDARD, ALL INTER-BUILDING PATHWAYS SHALL HAVE A MINIMUM OF 20% AVAILABLE CAPACITY AT THE SCHEDULED END OF THE PROJECT. SHOULD THIS PERCENTAGE NOT BE ACHIEVABLE, THIS ISSUE MUST BE BROUGHT TO THE ATTENTION OF THE CONSTRUCTION MANAGER AND THE VA REPRESENTATIVE.

15. WHERE PATHWAY CONSISTS OF MULTIPLE CONDUITS OR SLEEVES, A PATHWAY MUST BE FILLED TO CURRENT TIA AND BICSI INSTALLATION RECOGNIZED MAXIMUM FILL BEFORE UTILIZING THE NEXT

VACANT OR PARTIALLY FILLED PATHWAY.

16. OVERHEAD AND WALL MOUNTED LADDER (TYPE) RACKING INSTALLATION SHALL MATCH THE DRAWINGS AS CLOSELY AS POSSIBLE AND REQUIRES A SHOP DRAWING FOR EACH ROOM LOCATION.

THE PACKAGE IS TO INCLUDE A BILL OF MATERIALS WITH PART NUMBERS FROM RACKING MANUFACTURER FOR MOUNTING AND CONNECTION PIECE PARTS. PRIOR TO ANY ROUGH-IN WORK BEING

PERFORMED THESE SUBMITTALS MUST BE APPROVED BY THE VA REPRESENTATIVE.

17. ALL CABLING AND THEIR PATHWAYS PASSING THROUGH A RATED FIRE OR SMOKE BARRIER MUST BE PROPERLY SLEEVED AND FIRE STOPPED USING APPROVED (UL CLASSIFIED) FIRE STOP ASSEMBLIES.

This is the start of the file's text. The full file is on GovTribe.

File details come from the government source that posted it. Updated .