B2C-TR2C-2139A
208/120V
125A-PANEL
60A-MCB
B2C-TR2C-2139B
208/120V
125A-PANEL
60A-MCB
B2C-TR2C-3140A
208/120V
125A-PANEL
60A-MCB
B2C-TR2C-3140B
208/120V
125A-PANEL
60A-MCB
B2C-TR2C-1155A
208/120V
125A-PANEL
60A-MCB
B2C-TR2C-1155B
208/120V
125A-PANEL
60A-MCB
B2W-TR2W-121B
208/120V
125A-PANEL
100A-MCB
B2W-TR2W-121A
208/120V
125A-PANEL
100A-MCB
FIRST LEVEL
60A
NON-FUSED
DISCONNECT
THIRD LEVEL
SECOND LEVEL
125A 3P 7 50A
3P 7
ROOM 2C-1155
ROOM 2C-2139
ROOM 2C-3140A
60A 3P
60A 3P
60A 3P
60A 3P
60A 3P
60A 3P
(NEW) EMERGENCY DISTRIBUTION BOARD
B2C-EP-TR, 225A, 208/120V, 3PH, 4W
(NEW) NORMAL DISTRIBUTION BOARD
B2C-NP-TR, 225A, 208/120V, 3PH, 4W
2 2 225A 3P
100A 3P 77
100A 3P
100A 3P
ROOM 2W-121ROOM 2W-121
77777777
9 9
99 9 9
9 9
10 10
125A
NON-FUSED
DISCONNECT
30KVA TRANSFORMER "T-2C-TR-A"
480V-208/120V, 3PH, 4W, 115°C
COPPER WINDINGS
#1/0
112.5KVA TRANSFORMER "T-2C-TR-B"
480V-208/120V, 3PH, 4W, 115°C
COPPER WINDINGS
#1/0
100A
NON-FUSED
DISCONNECT
225A
NON-FUSED
DISCONNECT
(E) 2C-EQDP2C-MB
225A, 480/277V, 3PH, 4W 1 (E) 2C-MDP
1200A, 480/277V, 3PH, 4W 1
FEEDER & BRANCH CIRCUIT SIZING SCHEDULE -
GENERAL PURPOSE
2/0 6 1 1/2" 2" 2"
1 1/2"
2 1/2"
2-2 1/2"
3-2 1/2"
4-2 1/2"
5-2 1/2"
6-2 1/2"
2-500
2-600
3-400
4-350
5-400
6-400
5-4/0
6-250
2-1/0
2-1/0
3-2/0
4-3/0
2-3"
2-3"
3/0
4/0
2-4/0
2-250
2-350
3"3
2-2
2-2
2-1
3 3"
2-2"
2-2"
2"
2"
6-3"
3-3"
4-3"
5-3"
2-3"
2-3"
6-3"
2-3 1/2"
3-3"
4-3"
5-3"
2-4"
3"
2-2 1/2"
4"
2-2"
2-3"
2 1/2"
3"
2"
2"
3 1/2"
2-2 1/2"
2-3"
4"
2-2 1/2"
2 1/2"
3"
2"
2 1/2"
3/4"(1")
3/4"(1")
3/4"
3/4"
3/4"
3/4"
1"(1 1/4")
1 1/4"
1 1/4"
1 1/4"
2 WIRE
8(6)
6(4)
6(4)
4(2)
3(2)
2(1)
1/0
1(1/0)
8 1"
PHASE
& NEUTRAL
WIRE SIZE - AWG OR KCMIL
E.G.
3/4" 3/4"
1 1/4"(1 1/2")1 1/4"(1 1/2")
1 1/2"
1 1/2"
1 1/4"
3/4"(1")
3/4"(1")
3/4"
1"(1 1/4")
2"
1 1/2"(2")
1 1/4"
1"(1 1/4")
1"(1 1/4")
1 1/4"
3/4"(1")
CONDUIT SIZE
3/4"
3/4"
3 WIRE
3/4"
3/4"
4 WIRE
(3PH & 1N) NOTE
1.
2.
3.
4.
CIRCUIT MAXIMUM DISTANCE IS BASED ON
NEC CHAPTER 9, TABLE 8 CONDUCTOR
PROPERTIES FOR COATED COPPER
CONDUCTORS AT 75 DEGREES CELSIUS.
MAXIMUM CIRCUIT LOAD FOR DISTANCE IS
BASED ON NEC 220-10(b)
BASED ON THHN/THWN, 90°., 600V.,
INSULATED, COPPER WIRE APPLIED AT 75°FOR
TERMINATIONS RATED AT 60°C/75°C AND 75°C.
FOR TERMINATIONS RATED AT 60°C PROVIDE
WIRE AND CONDUIT SIZES INDICATED IN
PARENTHESIS.
BASED ON WIRE OUTSIDE DIAMETERS AND
RIGID METALLIC CONDUIT INSIDE DIAMETERS
AS PROVIDED IN THE NEC. DO NOT REDUCE
CONDUIT SIZE FOR NON-RIGID METALLIC
APPLICATION. REFER TO NEC FOR CONDUIT
TYPES MORE RESTRICTIVE THAN RIGID
METALLIC.
NOTES:
(NOTES 1 & 2)
120V. SINGLE PHASE CIRCUIT LENGTH TABLE 208V. THREE PHASE CIRCUIT LENGTH TABLE
LOAD
(VOLT-AMPS)
MAX.
CIRCUIT
17280
14400
11520
(AMPS)
AMPACITY
BREAKER
CURRENT
(AMPS)
MAX.
CIRCUIT
NO.8
MAXIMUM LENGTH IN FEET
- 58
110 174
NO.12
NO.10
73 116
117-
NO.4
NO.6
(AMPS)
BREAKER
AMPACITY
LOAD
(VOLT-AMPS)
CIRCUIT
MAX.
CURRENT
(AMPS)
CIRCUIT
MAX.
234-- --
116-
NO.10
NO.12
233127
294 468
177 281
221 351139
NO.6
NO.4
NO.8
MAXIMUM LENGTH IN FEET
35-40
45-50
80-90
15-20
25-30
OVERCURRENT
DEVICE RATING
(AMPERES)
07/03/2024
07/03/2024
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
CONSULTANT
321 4 5 6 7 8 9 10
GENERAL NOTES
KEYNOTES
TRIPLE C - The A/E Group 201 E. Jefferson Street, Suite 200 Syracuse, NY 13202
MAT PERKINS
(315) 484-5958
STAMP
Au to de sk
D oc s:
//6
A4
-2 2-
0_
N ew in gt on _V
AM
C
_E H
R M
_I U
-1
2/
9A 4-
-7
.N ew in gt on
.E H
R M
.M
EP
.B
_0 2_
R
.rv t
-1
0-
6:
:2
02E-601
ELECTRICAL ONE-LINE DIAGRAMS - B2C 689A4-22-700
01_02
07/03/2024 M. Perkins J. Schooley
ISSUED FOR
CONSTRUCTION
EHRM INFRASTRUCTURE
UPGRADES
555 Willard Avenue, Newington, CT 06111
1.
2.
3.
4.
5.
CONTRACTOR SHALL PROVIDE A 30 DAY LOAD MEASUREMENT OF
EQUIPMENT INDICATED AND PROVIDE THE RESULTS TO THE
ELECTRICAL ENGINEER OF RECORD (EEOR) TO VERIFY THE
EQUIPMENT HAS CAPACITY TO SUPPORT ADDITIONAL LOAD.
PROVIDE SPD DEVICE INTEGRATED INTO PANEL BOARD. REQUIRES
THREE PHASES.
PROVIDE SUB-METERING OF NEW DEDICATED TR, IT LOAD ONLY.
CIRCUITS SHALL BE EQUIPPED WITH NEW MONITORED POWER
METER INTEGRATED INTO PANEL. BASIS OF DESIGN: EATON OR
SQUARE D.
PROVIDE SUB-METERING OF NEW DEDICATED ROOM HVAC
SYSTEM(S). CIRCUITS SHALL BE EQUIPPED WITH NEW MONITORED
POWER METER INTEGRATED INTO PANEL. BASIS OF DESIGN: EATON
OR SQUARE D.
PROVIDE 100% RATED CIRCUIT BREAKER
6. PROVIDE NEW FEED BASE ON LOAD INDICATED.
REFER TO SHEET E-701 FOR SIZING.
7. PROVIDE CIRCUIT BREAKER INDICATED IN AVAILABLE SPACE.
8. DISTRIBUTION BOARD BEING REPLACED.
9. NEW PANELBOARD TO HAVE PXR20 SERIES BASIS OF DESIGN OR
SIMILAR ELECTRONIC TRIP CIRCUIT BREAKER AND BE
COORDINATED. COORDINATION STUDY TO BE SUBMITTED PRIOR
TO MAIN BREAKER SELECTION.
10. PROVIDE 100% RATED MAIN BREAKER
ALL NEW FEEDER CONDUCTORS SHALL BE CONTINUOUS WITH NO
SPLICES.
ALL FEEDERS SHALL BE COPPER WITH 90° C. (THHN/THWN)
INSULATION.
NEW CIRCUIT BREAKERS SHALL BE TYPE TO MATCH EXISTING, U.N.O.
PROVIDE ALL REQUIRED MOUNTING HARDWARE, LUGS AND
COVERPLATES FOR A COMPLETE INSTALLATION.
FEEDER VOLTAGE DROP CALCULATIONS ARE INDICATED FOR
FEEDERS EXCEEDING 100'-0".
CONTRACTOR TO PROVIDE SHORT CIRCUIT, OVERCURRENT
PROTECTIVE DEVICE COORDINATION AND ARC FLASH ANALYSIS FOR
ALL NEW PANELS, SWITCHBOARDS AND SWITCHGEAR. STUDY SHALL
INCLUDE EXISTING SYSTEM TO THE EXTENT THAT THE FAULT
CURRENT, COORDINATION AND ARC FLASH PREPARED IN
COMPLIANCE WITH 2018 NFPA 70E FOR THE NEW PANELS CAN BE
CALCULATED. CONTRACTOR IS RESPONSIBLE FOR ALL DATA
COLLECTION REQUIRED TO COMPLETE THE ANALYSIS. REPORT OF
THE ANALYSIS SHALL BE PREPARED SUMMARIZING THE INPUT DATA,
SINGLE-LINE USED IN CALCULATION, AND RESULTS INCLUDING ARC
FLASH LABELS. REPORT SHALL BE STAMPED AND SIGNED BY
PROFESSIONAL ENGINEER UNDER WHOSE DIRECTION THE STUDY
WAS PERFORMED. CONTRACTOR TO INSTALL ARC FLASH LABELS ON
PANELS IN COMPLIANCE WITH 2018 NFPA 70E. ELECTRICAL
EQUIPMENT SUBMITTALS SHALL REFLECT RESULTS OF SHORT
CIRCUIT ANALYSIS. CONTRACTOR SHALL SET ALL ADJUSTABLE
CIRCUIT BREAKERS PER OVERCURRENT PROTECTIVE DEVICE
STUDY. MINIMAL INFORMATION INCLUDED ON ARC FLASH LABELS
INCLUDE:
• NOMINAL SYSTEM VOLTAGE
• ARC FLASH BOUNDARY
• AT LEAST ONE OF THE FOLLOWING:
A. EITHER THE AVAILABLE INCIDENT ENERGY AND THE
CORRESPONDING WORKING DISTANCE, OR THE ARC FLASH
PPE CATEGORY FOR THE EQUIPMENT, BUT NOT BOTH.
B. MINIMUM ARC RATING OF CLOTHING.
C. SITE-SPECIFIC LEVEL OF PPE.
ANALYSIS SHALL BE PREPARED PRIOR TO OR CONCURRENT WITH
ELECTRICAL SWITCHGEAR, SWITCHBOARDS AND PANEL
SUBMITTALS. EQUIPMENT SUBMITTALS WITHOUT ANALYSIS SHALL
BE REJECTED AND NOT REVIEWED.
EEOR CAN NOT BE RESPONSIBLE FOR ANALYSIS UNLESS
SEPARATELY AND SPECIFICALLY CONTRACTED TO DO SO.
CONTRACTOR SHALL PROVIDE A 30 DAY LOAD MEASUREMENT OF
EQUIPMENT INDICATED AND PROVIDE THE RESULTS TO THE
ELECTRICAL ENGINEER OF RECORD (EEOR) TO VERIFY THE
EQUIPMENT HAS CAPACITY TO SUPPORT ADDITIONAL LOAD.
NOTE: NOT ALL KEYNOTES
ARE USED ON EACH SHEET.
Revisions: Date:
B2E-TR2E-1178A
208/120V
125A-PANEL
60A-MCB
B2E-TR2E-1178B
208/120V
125A-PANEL
60A-MCB
B2E-TR2E-2149A
208/120V
125A-PANEL
60A-MCB
B2E-TR2E-2149B
208/120V
125A-PANEL
60A-MCB
B2E-TR2E-B127AA
208/120V
125A-PANEL
60A-MCB
B2E-TR2E-B127AB
208/120V
125A-PANEL
60A-MCB
B2E-TR2E-3113AB
208/120V
125A-PANEL
60A-MCB
B2E-TR2E-3113AA
208/120V
125A-PANEL
60A-MCB
B2E-TR2E-4115BB
208/120V
125A-PANEL
60A-MCB
B2E-TR2E-4115BA
208/120V
125A-PANEL
60A-MCB
B2E-TR2E-5142AA
208/120V
125A-PANEL
60A-MCB
B2E-TR2E-5142AB
208/120V
125A-PANEL
60A-MCB
HVAC-B2E
208/120V
225A-PANEL
225A-MCB
MCR-EP
208/120V
125A-PANEL
60A-MCB
SECOND LEVEL
FIRST LEVEL
BASEMENT LEVEL
2E-EDP2E-MCR
600A, 480/277V, 3PH, 4W 1(E) 2E-MDP-W
2000A, 480/277V, 3PH, 4W1
ROOM 2E-B127A
ROOM 2E-1178
ROOM 2E-2149
60A 3P
60A 3P
60A 3P
60A 3P
60A 3P
60A 3P
(NEW) EMERGENCY DISTRIBUTION BOARD
B2E-EP-TR, 400A, 208/120V, 3PH, 4W
(NEW) EMERGENCY DISTRIBUTION BOARD
B2E-NP-TR, 225A, 208/120V, 3PH, 4W
2 2 400A 3P
225A 3P 77
60A 3P
60A 3P
THIRD LEVEL
ROOM 2E-3113A
FOURTH LEVEL
60A 3P
60A 3P
FIFTH LEVEL
60A 3P
60A 3P
ROOM 2E-4115B
ROOM 2E-5142A
175A 3P 7
150KVA TRANSFORMER "T-2E-TR-B"
480V-208/120V, 3PH, 4W, 115°C
COPPER WINDINGS
125A 3P 7
75KVA TRANSFORMER "T-2E-TR-A"
480V-208/120V, 3PH, 4W, 115°C
COPPER WINDINGS
ROOM 2E-1161B ROOM 2E-1161
225A 3P
7777777777777
#1/0 #1/0
60A 3P
ROOM 1C-148D
9 9
9 9
9 9
9 9 9
9 9 10 10
10 10
07/03/2024
07/03/2024
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
CONSULTANT
321 4 5 6 7 8 9 10
GENERAL NOTES
KEYNOTES
TRIPLE C - The A/E Group 201 E. Jefferson Street, Suite 200 Syracuse, NY 13202
MAT PERKINS
(315) 484-5958
STAMP
Au to de sk
D oc s:
//6
A4
-2 2-
0_
N ew in gt on _V
AM
C
_E H
R M
_I U
-1
2/
9A 4-
-7
.N ew in gt on
.E H
R M
.M
EP
.B
_0 2_
R
.rv t
-1
0-
6:
:2
02E-602
ELECTRICAL ONE-LINE DIAGRAMS - B2E 689A4-22-700
01_02
07/03/2024 M. Perkins J. Schooley
ISSUED FOR
CONSTRUCTION
EHRM INFRASTRUCTURE
UPGRADES
555 Willard Avenue, Newington, CT 06111
1.
2.
3.
4.
5.
CONTRACTOR SHALL PROVIDE A 30 DAY LOAD MEASUREMENT OF
EQUIPMENT INDICATED AND PROVIDE THE RESULTS TO THE
ELECTRICAL ENGINEER OF RECORD (EEOR) TO VERIFY THE
EQUIPMENT HAS CAPACITY TO SUPPORT ADDITIONAL LOAD.
PROVIDE SPD DEVICE INTEGRATED INTO PANEL BOARD. REQUIRES
THREE PHASES.
PROVIDE SUB-METERING OF NEW DEDICATED TR, IT LOAD ONLY.
CIRCUITS SHALL BE EQUIPPED WITH NEW MONITORED POWER
METER INTEGRATED INTO PANEL. BASIS OF DESIGN: EATON OR
SQUARE D.
PROVIDE SUB-METERING OF NEW DEDICATED ROOM HVAC
SYSTEM(S). CIRCUITS SHALL BE EQUIPPED WITH NEW MONITORED
POWER METER INTEGRATED INTO PANEL. BASIS OF DESIGN: EATON
OR SQUARE D.
PROVIDE 100% RATED CIRCUIT BREAKER
6. PROVIDE NEW FEED BASE ON LOAD INDICATED.
REFER TO SHEET E-701 FOR SIZING.
7. PROVIDE CIRCUIT BREAKER INDICATED IN AVAILABLE SPACE.
8. DISTRIBUTION BOARD BEING REPLACED.
9. NEW PANELBOARD TO HAVE PXR20 SERIES BASIS OF DESIGN OR
SIMILAR ELECTRONIC TRIP CIRCUIT BREAKER AND BE
COORDINATED. COORDINATION STUDY TO BE SUBMITTED PRIOR
TO MAIN BREAKER SELECTION.
10. PROVIDE 100% RATED MAIN BREAKER
ALL NEW FEEDER CONDUCTORS SHALL BE CONTINUOUS WITH NO
SPLICES.
ALL FEEDERS SHALL BE COPPER WITH 90° C. (THHN/THWN)
INSULATION.
NEW CIRCUIT BREAKERS SHALL BE TYPE TO MATCH EXISTING, U.N.O.
PROVIDE ALL REQUIRED MOUNTING HARDWARE, LUGS AND
COVERPLATES FOR A COMPLETE INSTALLATION.
FEEDER VOLTAGE DROP CALCULATIONS ARE INDICATED FOR
FEEDERS EXCEEDING 100'-0".
CONTRACTOR TO PROVIDE SHORT CIRCUIT, OVERCURRENT
PROTECTIVE DEVICE COORDINATION AND ARC FLASH ANALYSIS FOR
ALL NEW PANELS, SWITCHBOARDS AND SWITCHGEAR. STUDY SHALL
INCLUDE EXISTING SYSTEM TO THE EXTENT THAT THE FAULT
CURRENT, COORDINATION AND ARC FLASH PREPARED IN
COMPLIANCE WITH 2018 NFPA 70E FOR THE NEW PANELS CAN BE
CALCULATED. CONTRACTOR IS RESPONSIBLE FOR ALL DATA
COLLECTION REQUIRED TO COMPLETE THE ANALYSIS. REPORT OF
THE ANALYSIS SHALL BE PREPARED SUMMARIZING THE INPUT DATA,
SINGLE-LINE USED IN CALCULATION, AND RESULTS INCLUDING ARC
FLASH LABELS. REPORT SHALL BE STAMPED AND SIGNED BY
PROFESSIONAL ENGINEER UNDER WHOSE DIRECTION THE STUDY
WAS PERFORMED. CONTRACTOR TO INSTALL ARC FLASH LABELS ON
PANELS IN COMPLIANCE WITH 2018 NFPA 70E. ELECTRICAL
EQUIPMENT SUBMITTALS SHALL REFLECT RESULTS OF SHORT
CIRCUIT ANALYSIS. CONTRACTOR SHALL SET ALL ADJUSTABLE
CIRCUIT BREAKERS PER OVERCURRENT PROTECTIVE DEVICE
STUDY. MINIMAL INFORMATION INCLUDED ON ARC FLASH LABELS
INCLUDE:
• NOMINAL SYSTEM VOLTAGE
• ARC FLASH BOUNDARY
• AT LEAST ONE OF THE FOLLOWING:
A. EITHER THE AVAILABLE INCIDENT ENERGY AND THE
CORRESPONDING WORKING DISTANCE, OR THE ARC FLASH
PPE CATEGORY FOR THE EQUIPMENT, BUT NOT BOTH.
B. MINIMUM ARC RATING OF CLOTHING.
C. SITE-SPECIFIC LEVEL OF PPE.
ANALYSIS SHALL BE PREPARED PRIOR TO OR CONCURRENT WITH
ELECTRICAL SWITCHGEAR, SWITCHBOARDS AND PANEL
SUBMITTALS. EQUIPMENT SUBMITTALS WITHOUT ANALYSIS SHALL
BE REJECTED AND NOT REVIEWED.
EEOR CAN NOT BE RESPONSIBLE FOR ANALYSIS UNLESS
SEPARATELY AND SPECIFICALLY CONTRACTED TO DO SO.
CONTRACTOR SHALL PROVIDE A 30 DAY LOAD MEASUREMENT OF
EQUIPMENT INDICATED AND PROVIDE THE RESULTS TO THE
ELECTRICAL ENGINEER OF RECORD (EEOR) TO VERIFY THE
EQUIPMENT HAS CAPACITY TO SUPPORT ADDITIONAL LOAD.
NOTE: NOT ALL KEYNOTES
ARE USED ON EACH SHEET.
07/03/2024
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
CONSULTANT
321 4 5 6 7 8 9 10
TRIPLE C - The A/E Group 201 E. Jefferson Street, Suite 200 Syracuse, NY 13202
MAT PERKINS
(315) 484-5958
STAMP
Au to de sk
D oc s:
//6
A4
-2 2-
0_
N ew in gt on _V
AM
C
_E H
R M
_I U
-1
2/
9A 4-
-7
.N ew in gt on
.E H
R M
.M
EP
.B
_0 2_
R
.rv t
-1
0-
6:
:2
02E-603
ELECTRICAL ONE-LINE DIAGRAMS 689A4-22-700
01_02
07/03/2024 M. Perkins J. Schooley
ISSUED FOR
CONSTRUCTION
EHRM INFRASTRUCTURE
UPGRADES
555 Willard Avenue, Newington, CT 06111
REFER TO 02E-604
REFER TO 02E-605 REFER TO 02E-605
(NEW)
175A 3P
150KVA T-2E-TR-A
480V-120/208V, 3PH, 4W
225A 3P
B2E-NP-TR
B2E-
TR2E-2149A
B2E-
TR2E-4155A
B2E-TR2E-
B127AA
B2E-
TR2E-3113AA
B2E-TR2E-4115BA
B2E-TR2E-1178A
30KVA T-2C-TR-A
480V-208/120V, 3PH, 4W
50A 3P
225A 3P
Revisions: Date:
B2C-NP-TR
B2C-TR2C-3140A
60A
B2C-TR2C-1155A
60A
B2C-TR2C-2138DA
60A
B2W-TR2W-121A
100A
(NEW)
FROM CBL-2W-ATS-EQ-N
SHEET E3
FROM CBL-2W-ATS-LS-N
SHEET E3
FROM CBL-2W-ATS-EQ-N
SHEET E3
FROM CBL-2C-ATS-LSDP2C-N
SHEET E3
FROM CBL-2C-ATS-CRDP2C-N
SHEET E3
FROM CBL-2C-ATS-EQDP2C-N
SHEET E3
FROM CBL-01-ATS-FP-01-N
SHEET E4
FROM CBL-11-ATS-FP-03-N
SHEET E5
INFO FOR THIS MB COULD
NOT BE OBTAINED.
FROM CBL-2E-ATS-6-N
SHEET E4
FROM CBL-2E-L2EATS-N
SHEET E3
FROM CBL-2E-CR2EATS-N
SHEET E3 FROM CBL-2E-EQ2EATS-N
SHEET E3
INFO FOR THIS MB COULD
NOT BE OBTAINED.
2E-GEN-11
937.5 kVA 480 V
CBL-2E-GEN-11-MB
(4) 350 AWG/kcmil 10 ft Magnetic
2E-GEN-11-MB
1200A Frame 1200A Trip 1200A Plug
CBL-2E-EDP2E
(4) 350 AWG/kcmil 10 ft Magnetic
2E-EDP2E
480V Isc 3P: 7457A Isc SLG:7431A
2E-EDP2E-1
100A Frame 100A Trip
2E-EDP2E-2
600A Frame 600A Trip
2E-EDP2E-3
600A Frame 600A Trip
CBL-2E-LS2EATS-E
(1) 2 AWG/kcmil 35 ft Magnetic
CBL-2E-CR2EATS-E
(2) 350 AWG/kcmil 25 ft Magnetic
CBL-2E-EQ2EATS-E
(3) 500 AWG/kcmil 15 ft Magnetic
E N
2E-LS2EATS
E N
2E-CR2EATS
E N
2E-EQ2EATS
CBL-2E-LS2EATS
(1) 2 AWG/kcmil 35 ft Magnetic
2E-LS2EDP
480V Isc 3P: 10163A Isc SLG:7275A
2E-LS2EDP-1
50A Frame 50A Trip
2E-LS2EDP-2
50A Frame 50A Trip
2E-LS2EDP-3
50A Frame 50A Trip
2E-LS2EDP-4
50A Frame 50A Trip
2E-LS2EDP-5
50A Frame 50A Trip
2E-LS2EDP-6
50A Frame 50A Trip
2E-LS2EDP-7
15A Frame 15A Trip
CBL-2E-EH1A
(1) 4 AWG/kcmil 145 ft Magnetic
2E-EH1A
480V Isc 3P: 3852A Isc SLG:2368A
CBL-2E-EH4C
(1) 2 AWG/kcmil 360 ft Magnetic
2E-EH4C
480V Isc 3P: 2752A Isc SLG:1677A
CBL-2E-EH2A
(1) 4 AWG/kcmil 145 ft Magnetic
2E-EH2A
480V Isc 3P: 3852A Isc SLG:2368A
CBL-2E-EH4A
(1) 4 AWG/kcmil 200 ft Magnetic
2E-EH4A
480V Isc 3P: 3092A Isc SLG:1878A
CBL-2E-EH2C
(1) 4 AWG/kcmil 310 ft Magnetic
2E-EH2C
480V Isc 3P: 2212A Isc SLG:1327A
CBL-2E-TR-EL1N
(1) 12 AWG/kcmil 20 ft Magnetic
2E-EH1A-1
30A Frame 30A Trip
CBL-2E-EHBA
(1) 6 AWG/kcmil 50 ft Magnetic
2E-EHBA
480V Isc 3P: 2857A Isc SLG:1726A
2E-EH4C-1
30A Frame 30A Trip
CBL-2E-EH5C
(1) 6 AWG/kcmil 10 ft Magnetic
2E-EH5C
480V Isc 3P: 2623A Isc SLG:1594A
2E-EH5C-1
15A Frame 15A Trip
CBL-2E-TR-ELPP
(1) 12 AWG/kcmil 90 ft Magnetic
S
P 2E-TR-ELPP
9.0 kVA Pri. 480 V Sec. 208 V
2.96 %Z
CBL-2E-ELPP
(1) 10 AWG/kcmil 6 ft Magnetic
2E-ELPP-MB
40A Frame 40A Trip
2E-ELPP
208V Isc 3P: 666A Isc SLG:702A
2E-EH2A-1
30A Frame 30A Trip
CBL-2E-EH3A
(1) 6 AWG/kcmil 10 ft Magnetic
2E-EH3A
480V Isc 3P: 3603A Isc SLG:2205A
CBL-2E-EH1C
(1) 4 AWG/kcmil 295 ft Magnetic
2E-EH1C
480V Isc 3P: 2302A Isc SLG:1382A
2E-EH1C-1
30A Frame 30A Trip
CBL-2E-EHBC
(1) 6 AWG/kcmil 10 ft Magnetic
2E-EHBC
480V Isc 3P: 2209A Isc SLG:1325A
2E-EH4A-1
30A Frame 30A Trip
CBL-2E-EH5A
(1) 6 AWG/kcmil 10 ft Magnetic
2E-EH5A
480V Isc 3P: 2928A Isc SLG:1773A
2E-EH2C-1
30A Frame 30A Trip
CBL-2E-EH3C
(1) 6 AWG/kcmil 10 ft Magnetic
2E-EH3C
480V Isc 3P: 2126A Isc SLG:1274A
S
P 2E-TR-ELIN
9.0 kVA Pri. 480 V Sec. 208 V
2.96 %Z
CBL-2E-EL1N
(1) 6 AWG/kcmil 6 ft Magnetic
2E-EL1N-MB
80A Frame 80A Trip
2E-EL1N
208V Isc 3P: 790A Isc SLG:798A
CBL-2E-CR2EATS
(2) 350 AWG/kcmil 25 ft Magnetic
2E-CR2EDP
480V Isc 3P: 16399A Isc SLG:15425A
2E-CR2EDP-1
60A Frame 60A Trip
2E-CR2EDP-2
100A Frame 100A Trip
2E-CR2EDP-3
100A Frame 100A Trip
2E-CR2EDP-4
100A Frame 100A Trip
2E-CR2EDP-5
150A Frame 150A Trip
2E-CR2EDP-6
60A Frame 60A Trip
2E-CR2EDP-7
100A Frame 100A Trip
2E-CR2EDP-8
100A Frame 100A Trip
2E-CR2EDP-9
100A Frame 100A Trip
2E-CR2EDP-10
150A Frame 150A Trip
CBL-2E-CH2B
(1) 6 AWG/kcmil 300 ft Magnetic
2E-CH2B
480V Isc 3P: 1714A Isc SLG:1017A
CBL-2E-CH2C
(1) 2 AWG/kcmil 310 ft Magnetic
2E-CH2C
480V Isc 3P: 3676A Isc SLG:2282A
CBL-2E-CH1A
(1) 2 AWG/kcmil 170 ft Magnetic
2E-CH1A
480V Isc 3P: 5917A Isc SLG:3846A
CBL-2E-CH2A
(1) 2 AWG/kcmil 160 ft Magnetic
2E-CH2A
480V Isc 3P: 6180A Isc SLG:4042A
CBL-2E-CH4A
(1) 3/0 AWG/kcmil 195 ft Magnetic
2E-CH4A
480V Isc 3P: 8340A Isc SLG:6054A
CBL-2E-CH1B
(1) 2 AWG/kcmil 220 ft Magnetic
2E-CH1B
480V Isc 3P: 4868A Isc SLG:3092A
CBL-2E-CH1C
(1) 2 AWG/kcmil 320 ft Magnetic
2E-CH1C
480V Isc 3P: 3578A Isc SLG:2217A
CBL-2E-CH4C
(1) 2 AWG/kcmil 390 ft Magnetic
2E-CH4C
480V Isc 3P: 3013A Isc SLG:1849A
CBL-2E-CH3B
(1) 3/0 AWG/kcmil 310 ft Magnetic
2E-CH3B
480V Isc 3P: 6335A Isc SLG:4363A
2E-CH2B-1
30A Frame 30A Trip
CBL-2E-TR-CL2B
(1) 10 AWG/kcmil 6 ft Magnetic
S
P 2E-TR-CL2B
15.0 kVA Pri. 480 V Sec. 208 V
2.80 %Z
CBL-2E-CL2B
(1) 8 AWG/kcmil 6 ft Magnetic
2E-CL2B-MB
50A Frame 50A Trip
2E-CL2B
208V Isc 3P: 1138A Isc SLG:1204A
2E-CH2C-1
30A Frame 30A Trip
2E-CH2C-2
60A Frame 60A Trip
CBL-2E-TR-CL2C
(1) 10 AWG/kcmil 6 ft Magnetic
CBL-2E-TR-CH3C
(1) 6 AWG/kcmil 10 ft Magnetic
2E-CH3C
480V Isc 3P: 3453A Isc SLG:2132A
S
P 2E-TR-CL2C
15.0 kVA Pri. 480 V Sec. 208 V
2.80 %Z
CBL-2E-CL2C
(1) 8 AWG/kcmil 6 ft Magnetic
2E-CL2C-MB
50A Frame 50A Trip
2E-CL2C
208V Isc 3P: 1258A Isc SLG:1289A
2E-CH1A-1
50A Frame 50A Trip
2E-CH1A-2
80A Frame 80A Trip
CBL-2E-TR-CL1A
(1) 6 AWG/kcmil 6 ft Magnetic
CBL-2E-TR-CHBA
(1) 2 AWG/kcmil 40 ft Magnetic
2E-CHBA
480V Isc 3P: 5048A Isc SLG:3219A
S
P 2E-TR-CL1A
30.0 kVA Pri. 480 V Sec. 208 V
7.80 %Z
CBL-2E-CL1A
(1) 2 AWG/kcmil 6 ft Magnetic
2E-CL1A-MB
225A Frame 150A Trip
2E-CL1A
208V Isc 3P: 994A Isc SLG:1011A
2E-CH2A-1
50A Frame 50A Trip
2E-CH2A-2
80A Frame 80A Trip
CBL-2E-TR-CL2A
(1) 6 AWG/kcmil 6 ft Magnetic
CBL-2E-TR-CH3A
(1) 2 AWG/kcmil 10 ft Magnetic
2E-CH3A
480V Isc 3P: 5917A Isc SLG:3846A
S
P 2E-TR-CL2A
15.0 kVA Pri. 480 V Sec. 208 V
2.80 %Z
CBL-2E-CL2A
(1) 8 AWG/kcmil 6 ft Magnetic
2E-CL2A-MB
50A Frame 50A Trip
2E-CL2A
208V Isc 3P: 1322A Isc SLG:1333A
CBL-2E-EQ2EATS
(3) 500 AWG/kcmil 15 ft Magnetic
2E-EQ2EDP
480V Isc 3P: 22187A Isc SLG:19767A
2E-EQ2EDP-1
60A Frame 60A Trip
2E-EQ2EDP-2
100A Frame 100A Trip
2E-EQ2EDP-3
100A Frame 100A Trip
2E-EQ2EDP-4
250A Frame 250A Trip
2E-EQ2EDP-10
300A Frame 300A Trip
2E-EQ2EDP-6
80A Frame 80A Trip
2E-EQ2EDP-7
100A Frame 100A Trip
2E-EQ2EDP-8
100A Frame 100A Trip
2E-EQ2EDP-9
225A Frame 225A Trip
2E-EQ2EDP-5
350A Frame 350A Trip
CBL-2E-QH1N
(1) 6 AWG/kcmil 15 ft Magnetic
2E-QH1N
480V Isc 3P: 16493A Isc SLG:12298A
CBL-2E-QH1C
(1) 2 AWG/kcmil 295 ft Magnetic
2E-QH1C
480V Isc 3P: 4021A Isc SLG:2453A
CBL-2E-QH1A
(1) 2 AWG/kcmil 155 ft Magnetic
2E-QH1A
480V Isc 3P: 6906A Isc SLG:4369A
CBL-2E-QMCC1
(1) 4/0 AWG/kcmil 110 ft Magnetic
2E-QMCC1
480V Isc 3P: 13944A Isc SLG:10439A
CBL-2E-QMCC2
(1) 350 AWG/kcmil 350 ft Magnetic
2E-QMCC2
480V Isc 3P: 8802A Isc SLG:6052A
CBL-2E-QHSW
(1) 2 AWG/kcmil 200 ft Magnetic
2E-QHSW
480V Isc 3P: 5621A Isc SLG:3496A
CBL-2E-QH4C
(1) 2 AWG/kcmil 345 ft Magnetic
2E-QH4C
480V Isc 3P: 3494A Isc SLG:2119A
CBL-2E-QH4A
(1) 2 AWG/kcmil 185 ft Magnetic
2E-QH4A
480V Isc 3P: 5995A Isc SLG:3746A
CBL-2E-ELEV P-1,S-2
(1) 4/0 AWG/kcmil 405 ft Magnetic
2E-BUS-0734
480V Isc 3P: 7012A Isc SLG:4456A
CBL-2E-ELEV P-2, P-3, S-1
(1) 350 AWG/kcmil 405 ft Magnetic
2E-BUS-0733
480V Isc 3P: 8498A Isc SLG:5593A
2E-QH1N-1
30A Frame 30A Trip
CBL-2E-TR-QL1N
(1) 10 AWG/kcmil 6 ft Magnetic
S
P 2E-TR-QL1N
15.0 kVA Pri. 480 V Sec. 208 V
2.80 %Z
CBL-2E-QL1N
(1) 6 AWG/kcmil 6 ft Magnetic
2E-QL1N-MB
50A Frame 50A Trip
2E-QL1N
208V Isc 3P: 1396A Isc SLG:1398A
2E-QH1C-1
50A Frame 50A Trip
CBL-2E-TR-QLBC
(1) 6 AWG/kcmil 10 ft Magnetic
S
P 2E-TR-QLBC
30.0 kVA Pri. 480 V Sec. 208 V
7.80 %Z
CBL-2E-QLBC
(1) 2 AWG/kcmil 6 ft Magnetic
2E-QLBC-MB
100A Frame 100A Trip
2E-QLBC
208V Isc 3P: 973A Isc SLG:997A
2E-QMCC2-1
80A Frame 80A Trip 2E-AC-2 CBL-2E-QHPP 39.0 hp
(1) 4 AWG/kcmil 20 ft Magnetic
2E-QHPP
480V Isc 3P: 7724A Isc SLG:5129A
2E-QHPP-1
50A Frame 50A Trip
CBL-2E-TR-QLPP
(1) 6 AWG/kcmil 6 ft Magnetic
S
P 2E-TR-QLPP
30.0 kVA Pri. 480 V Sec. 208 V
7.80 %Z
CBL-2E-QLPP
(1) 2 AWG/kcmil 6 ft Magnetic
2E-QLPP-MB
90A Frame 90A Trip
2E-QLPP
208V Isc 3P: 1000A Isc SLG:1015A
2E-QLPP-1
40A Frame 40A Trip
CBL-2E-QLPP1
(1) 6 AWG/kcmil 75 ft Magnetic
2E-QLPP1
208V Isc 3P: 840A Isc SLG:748A
03-GEN-6
218.8 kVA 208 V
CBL-03-G6-MB
(2) 350 AWG/kcmil 20 ft Non-Magnetic
03-G6-MB
600A Frame 600A Trip
CBL-03-ATS-6-E
(2) 350 AWG/kcmil 20 ft Non-Magnetic
E N
03-ATS-6
CBL-03-ATS-6-DISC
(1) 500 AWG/kcmil 10 ft Non-Magnetic
03-DISC-ATS-6
400A Frame
FU-DISC-ATS-6
400A Frame 400A Trip
CBL-03-BPMCC
(1) 500 AWG/kcmil 10 ft Non-Magnetic
03-BPMCC
208V Isc 3P: 8505A Isc SLG:6363A
03-BPMCC-1
250A Frame 175A Trip
03-BPMCC-2
90A Frame 90A Trip
CBL-03-TR-6110-0183
(1) 2/0 AWG/kcmil 20 ft Magnetic
CBL-03-TR-6110-0261-1
(1) 2 AWG/kcmil 40 ft Magnetic
03-6110-0261-MB
03-6110-0261 240V Isc 3P: 727A Isc SLG:761A
S
P 03-TR-6110-0183
75.0 kVA Pri. 208 V Sec. 240 V
4.38 %Z
CBL-03-6110-0188
(1) 2 AWG/kcmil 20 ft Magnetic
CBL-03-DISC-6110-0183
(1) 2 AWG/kcmil 20 ft Magnetic
03-6110-0188-MB
03-6110-0188 240V Isc 3P: 2416A Isc SLG:2660A
03-DISC-6110-0183
400A Frame
FU-DISC-6110-0183
100A Frame 100A Trip
CBL-03-6110-0183
(1) 2 AWG/kcmil 30 ft Magnetic 03-6110-0183 240V Isc 3P: 2242A Isc SLG:2315A
11-GEN-09
625.0 kVA 208 V
BUS-0366
208V Isc 3P: 11551A Isc SLG:11551A
11-FP-01-MB
400A Frame 400A Trip 400A Plug
11-FP-03-MB
400A Frame 400A Trip 400A Plug
CBL-11-ATS-FP-01
(1) 350 AWG/kcmil 480 ft Magnetic
CBL-11-ATS-FP-03
(1) 350 AWG/kcmil 25 ft Magnetic
E N
11-ATS-FP-03
11-FP-03
75.0 hp
E N
01-ATS-FP-01
01-FP-01
75.0 hp
CBL-2E-L2EATS-N
(1) 2 AWG/kcmil 50 ft Magnetic
CBL-2E-CR2EATS-N
(2) 350 AWG/kcmil 75 ft Magnetic
CBL-2E-EQ2EATS-N
(3) 500 AWG/kcmil 75 ft Magnetic
2E-QMCC1-SCH
2E-QMCC2-SCH
2E-QHSW-1
30A Frame 30A Trip
CBL-2E-TR-QLSW
(1) 10 AWG/kcmil 10 ft Magnetic
S
P 2E-TR-QLSW
15.0 kVA Pri. 480 V Sec. 208 V
2.80 %Z
CBL-2E-QLSW
(1) 8 AWG/kcmil 6 ft Magnetic
2E-QLSW-MB
60A Frame 60A Trip
2E-QLSW
208V Isc 3P: 1305A Isc SLG:1322A
CBL-01-ATS-FP-01-N
(1) 350 AWG/kcmil 240 ft Magnetic
CBL-11-ATS-FP-03-N
(1) 350 AWG/kcmil 230 ft Magnetic
2E-CH4A-1
100A Frame 100A Trip
CBL-2E-CH5A
(1) 2 AWG/kcmil 10 ft Magnetic
2E-CH5A
480V Isc 3P: 7931A Isc SLG:5668A
2E-CH1B-1
30A Frame 30A Trip
2E-CH1B-2
80A Frame 80A Trip
CBL-2E-TR-CL1B
(1) 10 AWG/kcmil 6 ft Magnetic
CBL-2E-TR-CHBB
(1) 4 AWG/kcmil 60 ft Magnetic
2E-CHBB
480V Isc 3P: 3661A Isc SLG:2264A
2E-CHBB-1
30A Frame 30A Trip
CBL-2E-TR-CLBB
(1) 10 AWG/kcmil 6 ft Magnetic
S
P 2E-TR-CLBB
15.0 kVA Pri. 480 V Sec. 208 V
2.80 %Z
CBL-2E-CLBB
(1) 8 AWG/kcmil 6 ft Magnetic
2E-CLBB-MB
50A Frame 50A Trip
2E-CLBB
208V Isc 3P: 1260A Isc SLG:1290A
S
P 2E-TR-CL1B
15.0 kVA Pri. 480 V Sec. 208 V
2.80 %Z
CBL-2E-CL1B
(1) 8 AWG/kcmil 6 ft Magnetic
2E-CL1B-MB
50A Frame 50A Trip
2E-CL1B
208V Isc 3P: 1293A Isc SLG:1313A
2E-CH1C-1
30A Frame 30A Trip
2E-CH1C-2
80A Frame 80A Trip
CBL-2E-TR-CL1C
(1) 10 AWG/kcmil 6 ft Magnetic
CBL-2E-CHBC
(1) 4 AWG/kcmil 10 ft Magnetic
2E-CHBC
480V Isc 3P: 3438A Isc SLG:2124A
S
P 2E-TR-CL1C
15.0 kVA Pri. 480 V Sec. 208 V
2.80 %Z
CBL-2E-CL1C
(1) 6 AWG/kcmil 6 ft Magnetic
2E-CL1C-MB
60A Frame 60A Trip
2E-CL1C
208V Isc 3P: 1267A Isc SLG:1309A
2E-CHBC-1
30A Frame 30A Trip
CBL-2E-TR-CLBC
(1) 10 AWG/kcmil 6 ft Magnetic
S
P 2E-TR-CLBC
15.0 kVA Pri. 480 V Sec. 208 V
2.80 %Z
CBL-2E-CLBC
(1) 8 AWG/kcmil 6 ft Magnetic
2E-CLBC-MB
50A Frame 50A Trip
2E-CLBC
208V Isc 3P: 1249A Isc SLG:1282A
2E-CH4C-1
100A Frame 100A Trip
CBL-2E-CH5C
(1) 2 AWG/kcmil 10 ft Magnetic
2E-CH5C
480V Isc 3P: 2947A Isc SLG:1806A
2E-CH3B-1
125A Frame 125A Trip
CBL-2E-TR-CL3B
(1) 1 AWG/kcmil 6 ft Magnetic
S
P 2E-TR-CL3B
75.0 kVA Pri. 480 V Sec. 208 V
5.10 %Z
CBL-2E-CL3B
(1) 250 AWG/kcmil 6 ft Magnetic
2E-CL3B-MB
225A Frame 225A Trip
2E-CL3B
208V Isc 3P: 3196A Isc SLG:3414A
03-6110-0310 208V Isc 3P: 5511A Isc SLG:3760A
03-6110-0310-MB
100A Frame 100A Trip
CBL-03-6110-0310
(1) 2 AWG/kcmil 45 ft Magnetic
03-BPMCC-3
100A Frame 100A Trip
CBL-03-ATS-6-N-2
(1) 500 AWG/kcmil 50 ft Non-Magnetic
S
P 03-TR-6110-0261
15.0 kVA Pri. 208 V Sec. 240 V
4.20 %Z
03-SW-TR-6110-0261
CBL-03-TR-6110-0261-2
(1) 2 AWG/kcmil 10 ft Magnetic
CBL-03-6110-0261
(1) 2 AWG/kcmil 10 ft Magnetic
2W-GEN-10
343.8 kVA 480 V
CBL-2W-GEN10-MB
(1) 500 AWG/kcmil 20 ft Magnetic
2W-GEN10-MB
400A Frame 400A Trip 400A Plug
CBL-2W-EDP2W
(2) 3/0 AWG/kcmil 10 ft Magnetic
2W-EDP2W
480V Isc 3P: 2719A Isc SLG:2703A
2W-EDP2W-2
200A Frame 200A Trip
2W-EDP2W-3
100A Frame 100A Trip
2W-EDP2W-4
80A Frame 80A Trip
2W-EDP2W-1
300A Frame 300A Trip
CBL-2W-ATS-QMCC-E
(1) 3/0 AWG/kcmil 6 ft Magnetic
CBL-2W-ATS-EQ-E
(1) 2 AWG/kcmil 80 ft Magnetic
CBL-2W-ATS-LS-E
(1) 4 AWG/kcmil 90 ft Magnetic
CBL-2C-EDP2C
(1) 350 AWG/kcmil 160 ft Magnetic
2C-EDP2C
480V Isc 3P: 2514A Isc SLG:2404A
2C-EDP2C-1
250A Frame 250A Trip
2C-EDP2C-2
100A Frame 100A Trip
2C-EDP2C-3
80A Frame 80A Trip
CBL-2C-ATS-EQDP2C-E
(1) 4/0 AWG/kcmil 10 ft Magnetic
CBL-2C-ATS-CRDP2C-E
(1) 2 AWG/kcmil 15 ft Magnetic
CBL-2C-ATS-LSDP2C-E
(1) 2 AWG/kcmil 15 ft Magnetic
E N
2C-ATS-CR
E N
2C-ATS-LS
CBL-2C-CRDP2C
(1) 2 AWG/kcmil 6 ft Magnetic
2C-CRDP2C
480V Isc 3P: 9203A Isc SLG:8416A
CBL-2C-LSDP2C
(1) 2 AWG/kcmil 6 ft Magnetic
2C-LSDP2C
480V Isc 3P: 9203A Isc SLG:8416A
E N
2C-ATS-EQ
CBL-2C-EQDP2C
(1) 4/0 AWG/kcmil 6 ft Magnetic
2C-EQDP2C-MB
225A Frame 225A Trip
2C-EQDP2C
480V Isc 3P: 9423A Isc SLG:8747A
2C-EQDP2C-2
15A Frame 15A Trip
2C-EQDP2C-3
90A Frame 90A Trip
2C-EQDP2C-4
150A Frame 150A Trip
2C-EQDP2C-5
60A Frame 60A Trip
2C-EQDP2C-1
15A Frame 15A Trip
CBL-2C-TR-QL1F
(1) 8 AWG/kcmil 60 ft Magnetic
CBL-2C-ELEV P6-1
(1) 2 AWG/kcmil 60 ft Magnetic
CBL-2C-ELEV P7-1
(1) 6 AWG/kcmil 190 ft Magnetic
CBL-2C-QHPA
(1) 2 AWG/kcmil 110 ft Magnetic
2C-QHPA
480V Isc 3P: 6014A Isc SLG:4433A
CBL-2C-TR-QLBB
(1) 10 AWG/kcmil 190 ft Magnetic
2C-QHBA-1
50A Frame 50A Trip
CBL-2C-TR-QLPA
(1) 6 AWG/kcmil 6 ft Magnetic
S
P 2C-TR-QLPA
45.0 kVA Pri. 480 V Sec. 208 V
7.80 %Z
CBL-2C-QLPA
(1) 2 AWG/kcmil 10 ft Magnetic
2C-QLPA-MB
100A Frame 100A Trip
2C-QLPA
208V Isc 3P: 1417A Isc SLG:1451A
2C-ELEV P7-MB
60A Frame 60A Trip
CBL-2C-ELEV P7-2
(1) 4 AWG/kcmil 10 ft Magnetic
ELEV P7
50.0 hp
2C-ELEV P6-MB
60A Frame 60A Trip
CBL-2C-ELEV P6-2
(1) 4 AWG/kcmil 10 ft Magnetic
ELEV P6
40.0 hp
S
P 2C-TR-QL1F
9.0 kVA Pri. 480 V Sec. 208 V
2.96 %Z
CBL-2C-QL1F
(1) 10 AWG/kcmil 10 ft Magnetic
2C-QL1F-MB
30A Frame 30A Trip
2C-QL1F
208V Isc 3P: 757A Isc SLG:752A
S
P 2C-TR-QLBB
9.0 kVA Pri. 480 V Sec. 208 V
2.96 %Z
CBL-2C-QLBB
(1) 10 AWG/kcmil 10 ft Magnetic
2C-QLBB-MB
30A Frame 30A Trip
2C-QLBB
208V Isc 3P: 671A Isc SLG:692A
2C-CRDP2C-1
60A Frame 60A Trip
2C-CRDP2C-2
80A Frame 80A Trip
CBL-2C-CH1F
(1) 6 AWG/kcmil 60 ft Magnetic
2C-CH1F
480V Isc 3P: 5292A Isc SLG:3654A
CBL-2C-CH2F
(1) 4 AWG/kcmil 75 ft Magnetic
2C-CH2F
480V Isc 3P: 5794A Isc SLG:4156A
2C-CH1F-1
50A Frame 50A Trip
CBL-2C-TR-CL1F
(1) 6 AWG/kcmil 15 ft Magnetic
2C-CH2F-2
60A Frame 60A Trip
2C-CH2F-1
50A Frame 50A Trip
CBL-2C-CH3F
(1) 6 AWG/kcmil 35 ft Magnetic
2C-CH3F
480V Isc 3P: 4377A Isc SLG:2910A
CBL-2C-TR-CL2F
(1) 6 AWG/kcmil 15 ft Magnetic
2C-CH3F-1
30A Frame 30A Trip
CBL-2C-TR-CL3F
(1) 10 AWG/kcmil 6 ft Magnetic
S
P 2C-TR-CL3F
15.0 kVA Pri. 480 V Sec. 208 V
2.80 %Z
CBL-2C-CL3F
(1) 8 AWG/kcmil 6 ft Magnetic
2C-CL3F-MB
60A Frame 60A Trip
2C-CL3F
208V Isc 3P: 1279A Isc SLG:1306A
S
P 2C-TR-CL2F
30.0 kVA Pri. 480 V Sec. 208 V
7.80 %Z
CBL-2C-CL2F
(1) 2 AWG/kcmil 15 ft Magnetic
2C-CL2F-MB
100A Frame 100A Trip
2C-CL2F
208V Isc 3P: 974A Isc SLG:988A
2C-CL2F-1
40A Frame 40A Trip
CBL-2C-CL2F1
(1) 2 AWG/kcmil 25 ft Magnetic
2C-CL2F1
208V Isc 3P: 947A Isc SLG:944A
2C-LSDP2C-1
40A Frame 40A Trip
2C-LSDP2C-2
60A Frame 60A Trip
2C-EH2F-1
20A Frame 20A Trip
CBL-2C-EH1F
(1) 2 AWG/kcmil 60 ft Magnetic
2C-EH1F
480V Isc 3P: 7105A Isc SLG:5598A
CBL-2C-EH2F
(1) 6 AWG/kcmil 80 ft Magnetic
2C-EH2F
480V Isc 3P: 4509A Isc SLG:2997A
CBL-2C-EH3F
(1) 8 AWG/kcmil 100 ft Magnetic
2C-EH3F
480V Isc 3P: 1997A Isc SLG:1210A
2C-EH1F-1
100A Frame 100A Trip
2C-LSDP2C-3
15A Frame 15A Trip
CBL-2C-TR-ELBB
(1) 6 AWG/kcmil 190 ft Magnetic
CBL-2C-TR-EL1F
(1) 12 AWG/kcmil 50 ft Magnetic
S
P 2C-TR-ELBB
9.0 kVA Pri. 480 V Sec. 208 V
2.96 %Z
CBL-2C-ELBB
(1) 10 AWG/kcmil 10 ft Magnetic
2C-ELBB-MB
30A Frame 30A Trip
2C-ELBB
208V Isc 3P: 720A Isc SLG:727A
S
P 2C-TR-EL1F
9.0 kVA Pri. 480 V Sec. 208 V
2.96 %Z
CBL-2C-EL1F
(1) 10 AWG/kcmil 6 ft Magnetic
2C-EL1F-MB
30A Frame 30A Trip
2C-EL1F
208V Isc 3P: 748A Isc SLG:759A
E N
2W-ATS-QMCC
CBL-2W-QMCC
(1) 3/0 AWG/kcmil 120 ft Magnetic
2W-QMCCW
480V Isc 3P: 12441A Isc SLG:8390A
E N
2W-ATS-EQ
CBL-2W-QHBM
(1) 2 AWG/kcmil 40 ft Magnetic
2W-QHBM-MB
100A Frame 100A Trip
2W-QHBM
480V Isc 3P: 10071A Isc SLG:6345A
2W-QHBM-1
50A Frame 50A Trip
CBL-2W-TR-QLBM
(1) 6 AWG/kcmil 10 ft Magnetic
S
P 2W-TR-QLBM
30.0 kVA Pri. 480 V Sec. 208 V
7.80 %Z
CBL-2W-QLBM
(1) 2 AWG/kcmil 10 ft Magnetic
2W-QLBM-MB
100A Frame 100A Trip
2W-QLBM
208V Isc 3P: 1015A Isc SLG:1021A
E N
2W-ATS-LS
CBL-2W-ATS-LS
(1) 4 AWG/kcmil 90 ft Magnetic
2W-EHBM-MB
80A Frame 80A Trip
2W-EHBM
480V Isc 3P: 4702A Isc SLG:2815A
2W-EHBM-1
15A Frame 15A Trip
CBL-2W-TR-ELBM
(1) 12 AWG/kcmil 10 ft Magnetic
S
P 2W-TR-ELBM
9.0 kVA Pri. 480 V Sec. 208 V
2.96 %Z
CBL-2W-ELBM
(1) 8 AWG/kcmil 10 ft Magnetic
2W-ELBM-MB
50A Frame 50A Trip
2W-ELBM
208V Isc 3P: 769A Isc SLG:770A
CBL-2W-ATS-LS-N
(1) 4 AWG/kcmil 80 ft Magnetic
CBL-2W-ATS-EQ-N
(1) 2 AWG/kcmil 70 ft Magnetic
CBL-2W-ATS-QMCC-N
(1) 3/0 AWG/kcmil 50 ft Magnetic
CBL-2C-ATS-LSDP2C-N
(1) 2 AWG/kcmil 15 ft Magnetic
CBL-2C-ATS-CRDP2C-N
(1) 2 AWG/kcmil 15 ft Magnetic
CBL-2C-ATS-EQDP2C-N
(1) 4/0 AWG/kcmil 25 ft Magnetic
2W-QMCCW-SCH
2C-QLPA-1
80A Frame 80A Trip
CBL-2C-6110-0442
(1) 6 AWG/kcmil 75 ft Magnetic 2C-6110-0442 208V Isc 3P: 1093A Isc SLG:927A
2C-LSDP2C-MB
100A Frame 100A Trip
S
P 2C-TR-CL1F
30.0 kVA Pri. 480 V Sec. 208 V
7.80 %Z
CBL-2C-CL1F
(1) 2 AWG/kcmil 10 ft Magnetic
2C-CL1F-MB
100A Frame 100A Trip
2C-CL1F
208V Isc 3P: 976A Isc SLG:995A
CBL-2C-CH1D
(1) 6 AWG/kcmil 160 ft Magnetic
2C-CH1D
480V Isc 3P: 3070A Isc SLG:1853A
BUS-0834
208V Isc 3P: 4429A Isc SLG:3175A
BUS-0833
208V Isc 3P: 7271A Isc SLG:4281A
REFER TO 02E-603REFER TO 02E-603
E N
L
BREAKER
600A
3P ADJUSTABLE
REFER TO 02E-603
FROM CBL-2E-EQ2EATS-N
REFER TO 02E-603
(NEW)
400AF
225AT
3P
UPS-A
480V 225A
REFER TO UPS ONE LINE
#250 MCM
125A
SPD
3P
CRAC-02
480V 125A
(NEW)
400AF
225AT
3P
UPS-B
480V 225A
REFER TO UPS ONE LINE
#250 MCM
(NEW)
175A 3P
150KVA T-2E-TR-B
480V-120/208V, 3PH, 4W
400A 3P
B2E-EP-TR
MCR-EP
60A
#2/0 CU
B2E-TR2E-1178B
60A
B2E-TR2E-4155B
60A
B2E-TR2E-4115BB
60A
B2E-TR2E-2149B
60A
B2E-TR2E-3113BB
60A
B2E-TR2E-B127AB
60A
125A
SPD
3P
CRAC-01
480V 125A
2E-EDP2E-MCR
600AF
600ATATS-MCR-A
07/03/2024
07/03/2024
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
CONSULTANT
321 4 5 6 7 8 9 10
TRIPLE C - The A/E Group 201 E. Jefferson Street, Suite 200 Syracuse, NY 13202
MAT PERKINS
(315) 484-5958
STAMP
Au to de sk
D oc s:
//6
A4
-2 2-
0_
N ew in gt on _V
AM
C
_E H
R M
_I U
-1
2/
9A 4-
-7
.N ew in gt on
.E H
R M
.M
EP
.B
_0 2_
R
.rv t
-1
0-
6:
:2
02E-604
ELECTRICAL ONE-LINE DIAGRAMS 689A4-22-700
01_02
07/03/2024 M. Perkins J. Schooley
ISSUED FOR
CONSTRUCTION
EHRM INFRASTRUCTURE
UPGRADES
555 Willard Avenue, Newington, CT 06111
KEYNOTES:
1.
2.
3.
4.
5.
PROVIDE NEW ATS
PROVIDE NEW UPS TO SERVE MAIN COMPUTER ROOM
EQUIPMENTS
PROVIDE NEW PANEL BOARD TO SERVE TR'S ROOMS
PROVIDE NEW CRAC TO SERVE NEW MAIN COMPUTER ROOM
PROVIDE NEW MAIN DISTRUBTION PANEL BOARD
Revisions: Date:
125A 3P
112.5KVA T-2C-TR-B
480V-120/208V, 3PH, 4W
225A 3P
B2C-EP-TR
B2C-TR2C-3140B
60A
B2C-TR2C-1155B
60A
B2C-TR2C-2138DB
60A
B2W-TR2W-121B
100A
(NEW)
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
CONSULTANT
321 4 5 6 7 8 9 10
TRIPLE C - The A/E Group 201 E. Jefferson Street, Suite 200 Syracuse, NY 13202
MAT PERKINS
(315) 484-5958
STAMP
Au to de sk
D oc s:
//6
A4
-2 2-
0_
N ew in gt on _V
AM
C
_E H
R M
_I U
-1
2/
9A 4-
-7
.N ew in gt on
.E H
R M
.M
EP
.B
_0 2_
R
.rv t
-1
0-
6:
:2
02E-605
ELECTRICAL ONE-LINE DIAGRAMS 689A4-22-700
01_02
07/03/2024 M. Perkins J. Schooley
ISSUED FOR
CONSTRUCTION
EHRM INFRASTRUCTURE
UPGRADES
555 Willard Avenue, Newington, CT 06111
B2E-NP-TR
B2E-TR2E-2149A
60A
(NEW)
125A 3P
75KVA T-2E-TR-A
480V-120/208V, 3PH, 4W
225A 3P
B2E-TR2E-4155A
60A
B2E-TR2E-4115BA
60A
B2E-TR2E-B127AA
60A
B2E-TR2E-3113AA
60A
B2E-TR2E-1178A
60A
FEEDER & BRANCH CIRCUIT SIZING SCHEDULE -
GENERAL PURPOSE
2/0 6 1 1/2" 2" 2"
1 1/2"
2 1/2"
2-2 1/2"
3-2 1/2"
4-2 1/2"
5-2 1/2"
6-2 1/2"
2-500
2-600
3-400
4-350
5-400
6-400
5-4/0
6-250
2-1/0
2-1/0
3-2/0
4-3/0
2-3"
2-3"
3/0
4/0
2-4/0
2-250
2-350
3"3
2-2
2-2
2-1
3 3"
2-2"
2-2"
2"
2"
6-3"
3-3"
4-3"
5-3"
2-3"
2-3"
6-3"
2-3 1/2"
3-3"
4-3"
5-3"
2-4"
3"
2-2 1/2"
4"
2-2"
2-3"
2 1/2"
3"
2"
2"
3 1/2"
2-2 1/2"
2-3"
4"
2-2 1/2"
2 1/2"
3"
2"
2 1/2"
3/4"(1")
3/4"(1")
3/4"
3/4"
3/4"
3/4"
1"(1 1/4")
1 1/4"
1 1/4"
1 1/4"
2 WIRE
8(6)
6(4)
6(4)
4(2)
3(2)
2(1)
1/0
1(1/0)
8 1"
PHASE
& NEUTRAL
WIRE SIZE - AWG OR KCMIL
E.G.
3/4" 3/4"
1 1/4"(1 1/2")1 1/4"(1 1/2")
1 1/2"
1 1/2"
1 1/4"
3/4"(1")
3/4"(1")
3/4"
1"(1 1/4")
2"
1 1/2"(2")
1 1/4"
1"(1 1/4")
1"(1 1/4")
1 1/4"
3/4"(1")
CONDUIT SIZE
3/4"
3/4"
3 WIRE
3/4"
3/4"
4 WIRE
(3PH & 1N) NOTE
1.
2.
3.
4.
CIRCUIT MAXIMUM DISTANCE IS BASED ON
NEC CHAPTER 9, TABLE 8 CONDUCTOR
PROPERTIES FOR COATED COPPER
CONDUCTORS AT 75 DEGREES CELSIUS.
MAXIMUM CIRCUIT LOAD FOR DISTANCE IS
BASED ON NEC 220-10(b)
BASED ON THHN/THWN, 90°., 600V.,
INSULATED, COPPER WIRE APPLIED AT 75°FOR
TERMINATIONS RATED AT 60°C/75°C AND 75°C.
FOR TERMINATIONS RATED AT 60°C PROVIDE
WIRE AND CONDUIT SIZES INDICATED IN
PARENTHESIS.
BASED ON WIRE OUTSIDE DIAMETERS AND
RIGID METALLIC CONDUIT INSIDE DIAMETERS
AS PROVIDED IN THE NEC. DO NOT REDUCE
CONDUIT SIZE FOR NON-RIGID METALLIC
APPLICATION. REFER TO NEC FOR CONDUIT
TYPES MORE RESTRICTIVE THAN RIGID
METALLIC.
NOTES:
(NOTES 1 & 2)
120V. SINGLE PHASE CIRCUIT LENGTH TABLE 208V. THREE PHASE CIRCUIT LENGTH TABLE
LOAD
(VOLT-AMPS)
MAX.
CIRCUIT
17280
14400
11520
(AMPS)
AMPACITY
BREAKER
CURRENT
(AMPS)
MAX.
CIRCUIT
NO.8
MAXIMUM LENGTH IN FEET
- 58
110 174
NO.12
NO.10
73 116
117-
NO.4
NO.6
(AMPS)
BREAKER
AMPACITY
LOAD
(VOLT-AMPS)
CIRCUIT
MAX.
CURRENT
(AMPS)
CIRCUIT
MAX.
234-- --
116-
NO.10
NO.12
233127
294 468
177 281
221 351139
NO.6
NO.4
NO.8
MAXIMUM LENGTH IN FEET
35-40
45-50
80-90
15-20
25-30
OVERCURRENT
DEVICE RATING
(AMPERES)
07/03/2024
07/03/2024
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
CONSULTANT
321 4 5 6 7 8 9 10
TRIPLE C - The A/E Group 201 E. Jefferson Street, Suite 200 Syracuse, NY 13202
MAT PERKINS
(315) 484-5958
STAMP
Au to de sk
D oc s:
//6
A4
-2 2-
0_
N ew in gt on _V
AM
C
_E H
R M
_I U
-1
2/
9A 4-
-7
.N ew in gt on
.E H
R M
.M
EP
.B
_0 2_
R
.rv t
-1
0-
6:
:3
01E-701
ELECTRICAL SCHEDULES B01 689A4-22-700
01_02
07/03/2024 M. Perkins J. Schooley
ISSUED FOR
CONSTRUCTION
EHRM INFRASTRUCTURE
UPGRADES
555 Willard Avenue, Newington, CT 06111
1.
2.
3.
4.
PROVIDE A 30 DAY LOAD MEASUREMENT OF PANELBOARD
INDICATED. PROVIDE THE REPORT TO THE COR AND AE PRIOR TO
COMMENCEMENT OF PANELBOARD RENOVATION. PANEL DEMAND
IS CALCULATED BY LOADING EACH CIRCUIT BREAKER TO 80%
CAPACITY.
NEW ELECTRICAL PANEL AND CIRCUIT BREAKERS SIZED AS
INDICATED, SEE E-100 SERIES FOR PANEL LOCATION.
RELOCATED EXISTING ELECTRICAL PANEL, CIRCUIT BREAKER AND
FEEDER. CIRCUITS TO BE REPULLED AND TERMINATED.SEE E-600
ONLINE NOTES FOR ADDITIONAL INFORMATION.
PANEL MAINS TO BE 100% RATED BREAKERS
KEYNOTES
NOTE: NOT ALL KEYNOTES ARE USED ON EACH SHEET
LUMINAIRE SCHEDULE
TYPE DESCRIPTION MOUNTING VOLTS LAMPS DRIVER LOAD MANUFACTURER AND MODEL NO.
L1 4'0" LINEAR, WRAP AROUND ACRYLIC LENS, LED STRIP,
PENDANT 6” ABOVE CABLETRAY WITH PENDANT MOUNTING
KIT
PENDANT
9'0" AFF
MVOLT 3500k
85CRI
0-10V
DIMMABLE
42 VA COLUMBIA #LCL SERIES OR APPROVED EQUAL
L1B 4'0" LINEAR (BATTERY BACKED), WRAP AROUND ACRYLIC
LENS, LED STRIP, PENDANT 6” ABOVE CABLE TRAY WITH
PENDANT MOUNTING KIT
PENDANT
9'0" AFF
MVOLT 3500k
85CRI
42 VA COLUMBIA #LCL SERIES OR APPROVED EQUAL
L2 24"X24" SQUARE LUMINAIRE RECESSED
MV
MVOLTS LED 0-10V
DIMMABLE
17 VA TRAYFIT AXIS LIGHTING
L3 2X2 RECESSED, 600 LUMENS, 82 CRI RECESSED MVOLTS LED 120 47 VA 2BLT2 60L 120V EZ1 LP835
1. INSTALL BUS EXTENDER KIT PER MANUFACTURER'S RECOMMENDATIONS FOR TWO NEW 3-POLE PANELBOARD SPACES.
2. PANEL SPACE NUMBERING 25-30 ARE THE EXISTING LARGE BREAKERS. VERIFY CAPACITY FOR THE NEW EP-TR AND HVAC BI BREAKERS.
3. ADD SPD DEVICES INTEGRAL TO ALL NEW TELECOM PANELBOARDS (SQ D OR EQUAL) FOR TYPE 2 PROTECTION.
4. ADD PXR 20 TRIP UNITS FOR ADJUSTING CIRCUIT BREAKERS (EATON OR EQUAL).
Notes:
Total Est. Demand: 98 A ACCESS CONTROLLER 415 VA 100.00% 415 VA Total Conn.: 98 A LTG 840 VA 125.00% 1050 VA Total Est. Demand: 35329 VA NC 12635 VA 100.00% 12635 VA Total Conn. Load: 35129 VA Receptacle 21280 VA 100.00% 21280 VA Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Total Amps: 92 A 105 A 97 A Total Load: 11022 VA 12582 VA 11525 VA
41 SPD 60 A 1 0 VA -- 1 -- SPACE 42
39 SPD 60 A 1 0 VA -- 1 -- SPACE 40
37 SPD 60 A 1 0 VA -- 1 -- SPACE 38
35 SPACE -- 1 -- -- 1 -- SPACE 36
33 SPACE -- 1 -- -- 1 -- SPACE 34
31 SPACE -- 1 -- -- 1 -- SPACE 32
29 1152... -- 1 -- SPACE 30
27 1258... -- 1 -- SPACE 28
B01-EP-TR 150 A 3
1102... -- 1 -- SPACE 26
23 0 VA 0 VA 24
21 0 VA 0 VA 22
1ST FLR EMERGENCY PANEL - 6110-0304 100 A 3
0 VA 0 VA
3 50 A EXISTING CIRCUIT
17 0 VA 0 VA 18
15 0 VA 0 VA 16
EXISTING CIRCUIT 60 A 3
0 VA 0 VA
3 50 A EXISTING CIRCUIT
11 0 VA 0 VA 1 20 A MECH ROOM 12
9 0 VA 0 VA 1 20 A MECH ROOM 10
MECH ROOM COMP 20 A 3
0 VA 0 VA 1 20 A SPARE 8
5 MECH ROOM 20 A 1 0 VA 0 VA 6
3 MECH ROOM 20 A 1 0 VA 0 VA 4
1 SPARE 20 A 1 0 VA 0 VA
3 100 A EXISTING CIRCUIT
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Enclosure: Indoor MCB Rating: 600 A Mounting: Surface Wires: 4 Mains Rating: 800 A
Supply From: Phases: 3 Mains Type: MCB Location: ELECT. 1S-162-0 Volts: 208Y/120 A.I.C. Rating: VIF
Branch Panel: 6110-0386
1. ADD SPD DEVICES INTEGRAL TO ALL NEW TELECOM PANELBOARDS (SQ D OR EQUAL) FOR TYPE 2 PROTECTION.
2. ADD PXR 20 TRIP UNITS FOR ADJUSTING CIRCUIT BREAKERS (EATON OR EQUAL).
Notes:
Total Est. Demand: 76 A Total Conn.: 76 A
Total Est. Demand: 27487 VA Lighting 987 VA 100.00% 987 VA Total Conn. Load: 27487 VA Receptacle 26500 VA 100.00% 26500 VA Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Total Amps: 95 A 84 A 58 A Total Load: 10960 VA 9613 VA 6913 VA
41 SPD 20 A 1 0 VA -- 1 -- SPACE 42
39 SPD 20 A 1 0 VA -- 1 -- SPACE 40
37 SPD 20 A 1 0 VA -- 1 -- SPACE 38
35 SPACE -- 1 -- -- 1 -- SPACE 36
33 SPACE -- 1 -- -- 1 -- SPACE 34
31 SPACE -- 1 -- -- 1 -- SPACE 32
29 SPACE -- 1 -- -- 1 -- SPACE 30
27 SPACE -- 1 -- -- 1 -- SPACE 28
25 SPACE -- 1 -- -- 1 -- SPACE 26
23 SPARE 20 A 1 0 VA -- 1 -- SPACE 24
21 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 22
19 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 20
17 1167... 0 VA 1 20 A SPARE 18
15 2247... 0 VA 1 20 A SPARE 16
B01-TR1C-142A 60 A 3
1887... 0 VA 1 20 A SPARE 14
11 1167... 1167... 12 9 1167... 1887... 10
B01-TR1C-242A 60 A 3
1887... 1347...
3 60 A B01-TR1-324A
5 2247... 1167... 6 3 3147... 1167... 4
B01-TR1-424A 60 A 3
3954... 1887...
3 60 A B01-TR1-524A
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Enclosure: Indoor MCB Rating: 150 A Mounting: Surface Wires: 4 Mains Rating: 150 A
Supply From: Phases: 3 Mains Type: MCB Location: TELECOM ROOM 1C-142 Volts: 208Y/120 A.I.C. Rating: 22kA
Branch Panel: B01-NP-TR
1. ADD SPD DEVICES INTEGRAL TO ALL NEW TELECOM PANELBOARDS (SQ D OR EQUAL) FOR TYPE 2 PROTECTION.
2. ADD PXR 20 TRIP UNITS FOR ADJUSTING CIRCUIT BREAKERS (EATON OR EQUAL).
Notes:
Total Est. Demand: 98 A ACCESS CONTROLLER 415 VA 100.00% 415 VA Total Conn.: 98 A LTG 840 VA 125.00% 1050 VA Total Est. Demand: 35329 VA NC 12635 VA 100.00% 12635 VA Total Conn. Load: 35129 VA Receptacle 21280 VA 100.00% 21280 VA Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Total Amps: 92 A 105 A 97 A Total Load: 11022 VA 12582 VA 11525 VA
41 SPD 20 A 1 0 VA -- 1 -- SPACE 42
39 SPD 20 A 1 0 VA -- 1 -- SPACE 40
37 SPD 20 A 1 0 VA -- 1 -- SPACE 38
35 SPACE -- 1 -- -- 1 -- SPACE 36
33 SPACE -- 1 -- -- 1 -- SPACE 34
31 SPACE -- 1 -- -- 1 -- SPACE 32
29 SPACE -- 1 -- -- 1 -- SPACE 30
27 SPACE -- 1 -- -- 1 -- SPACE 28
25 SPACE -- 1 -- -- 1 -- SPACE 26
23 SPARE 20 A 1 0 VA -- 1 -- SPACE 24
21 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 22
19 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 20
17 5172... 0 VA 1 20 A SPARE 18
15 6030... 0 VA 1 20 A SPARE 16
B01-TR1C-142B 100 A 3
5415... 0 VA 1 20 A SPARE 14
11 1209... 1372... 12 9 1887... 1929... 10
B01-TR1C-242B 60 A 3
1452... 1573...
3 60 A B01-TR1-324B
5 1887... 1887... 6 3 1369... 1369... 4
B01-TR1-424B 60 A 3
1292... 1292...
3 60 A B01-TR1-524B
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Enclosure: Indoor MCB Rating: 150 A Mounting: Surface Wires: 4 Mains Rating: 225 A
Supply From: 6110-0386 Phases: 3 Mains Type: MCB Location: TELECOM ROOM 1C-142 Volts: 208Y/120 A.I.C. Rating: 22kA
Branch Panel: B01-EP-TR
NOT TO SCALE
E1 6110-0386 DISTRIBUTION BOARD
ATS-7-2
01-ATS-7-2-LD
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
CONSULTANT
321 4 5 6 7 8 9 10
TRIPLE C - The A/E Group 201 E. Jefferson Street, Suite 200 Syracuse, NY 13202
MAT PERKINS
(315) 484-5958
STAMP
Au to de sk
D oc s:
//6
A4
-2 2-
0_
N ew in gt on _V
AM
C
_E H
R M
_I U
-1
2/
9A 4-
-7
.N ew in gt on
.E H
R M
.M
EP
.B
_0 2_
R
.rv t
-1
0-
6:
:3
01E-702
ELECTRICAL SCHEDULES B01 689A4-22-700
01_02
07/03/2024 M. Perkins J. Schooley
ISSUED FOR
CONSTRUCTION
EHRM INFRASTRUCTURE
UPGRADES
555 Willard Avenue, Newington, CT 06111
1.
2.
3.
4.
PROVIDE A 30 DAY LOAD MEASUREMENT OF PANELBOARD
INDICATED. PROVIDE THE REPORT TO THE COR AND AE PRIOR TO
COMMENCEMENT OF PANELBOARD RENOVATION. PANEL DEMAND
IS CALCULATED BY LOADING EACH CIRCUIT BREAKER TO 80%
CAPACITY.
NEW ELECTRICAL PANEL AND CIRCUIT BREAKERS SIZED AS
INDICATED, SEE E-100 SERIES FOR PANEL LOCATION.
RELOCATED EXISTING ELECTRICAL PANEL, CIRCUIT BREAKER AND
FEEDER. CIRCUITS TO BE REPULLED AND TERMINATED.SEE E-600
ONLINE NOTES FOR ADDITIONAL INFORMATION.
PANEL MAINS TO BE 100% RATED BREAKERS
KEYNOTES
NOTE: NOT ALL KEYNOTES ARE USED ON EACH SHEET
1. ADD SPD DEVICES INTEGRAL TO ALL NEW TELECOM PANELBOARDS (SQ D OR EQUAL) FOR TYPE 2 PROTECTION.
2. ADD PXR 20 TRIP UNITS FOR ADJUSTING CIRCUIT BREAKERS (EATON OR EQUAL).
Notes:
Total Est. Demand: 15 A Total Conn.: 15 A
Total Est. Demand: 5300 VA Total Conn. Load: 5300 VA
Receptacle 5300 VA 100.00% 5300 VA Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Total Amps: 17 A 20 A 10 A Total Load: 1887 VA 2247 VA 1167 VA
29 SPD 20 A 1 0 VA -- 1 -- SPACE 30
27 SPD 20 A 1 0 VA -- 1 -- SPACE 28
25 SPD 20 A 1 0 VA -- 1 -- SPACE 26
23 SPACE -- 1 -- -- 1 -- SPACE 24
21 SPACE -- 1 -- -- 1 -- SPACE 22
19 SPACE -- 1 -- -- 1 -- SPACE 20
17 SPACE -- 1 -- -- 1 -- SPACE 18
15 SPACE -- 1 -- -- 1 -- SPACE 16
13 SPACE -- 1 -- -- 1 -- SPACE 14
11 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 12
9 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 10
7 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 8
5 SPARE 20 A 1 0 VA 1167... 6
3 MCR RECEPTACLE 20 A 1 1080... 1167... 4
1 TR #1C-143 RECEPTACLE 20 A 1 720 VA 1167...
3 20 A TR #1C-143 RACK RECEPTACLE
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Enclosure: Indoor MCB Rating: 60 A Mounting: Surface Wires: 4 Mains Rating: 125 A
Supply From: B01-NP-TR Phases: 3 Mains Type: MCB Location: TELECOM ROOM 1C-142 Volts: 208Y/120 A.I.C. Rating: 10kA
Branch Panel: B01-TR1C-142A
1. ADD SPD DEVICES INTEGRAL TO ALL NEW TELECOM PANELBOARDS (SQ D OR EQUAL) FOR TYPE 2 PROTECTION.
2. ADD PXR 20 TRIP UNITS FOR ADJUSTING CIRCUIT BREAKERS (EATON OR EQUAL).
Notes:
Total Est. Demand: 46 A ACCESS CONTROLLER 83 VA 100.00% 83 VA Total Conn.: 46 A LTG 168 VA 125.00% 210 VA Total Est. Demand: 16656 VA NC 11973 VA 100.00% 11973 VA Total Conn. Load: 16616 VA Receptacle 4400 VA 100.00% 4400 VA Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Total Amps: 45 A 51 A 43 A Total Load: 5415 VA 6030 VA 5172 VA
29 SPD 20 A 1 0 VA -- 1 -- SPACE 30
27 SPD 20 A 1 0 VA -- 1 -- SPACE 28
25 SPD 20 A 1 0 VA -- 1 -- SPACE 26
23 SPACE -- 1 -- -- 1 -- SPACE 24
21 SPACE -- 1 -- -- 1 -- SPACE 22
19 SPACE -- 1 -- -- 1 -- SPACE 20
17 SPARE 20 A 1 0 VA -- 1 -- SPACE 18
15 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 16
13 3963... 0 VA 1 20 A SPARE 14
11 3963... 0 VA 1 20 A SPARE 12
VFD-CU-01 50 A 3
3963... 1167... 10
7 42 VA 1167... 8
IU-1-01 15 A 2
42 VA 1167...
3 20 A TR #1C-142 RACK RECEPTACLE
3 TR #1C-143 20 A 1 720 VA 180 VA 1 20 A CU-01 VRF UNIT RECEPTACLE 4
1 TR #1C-142 ACCESS CONTROLLER 20 A 1 83 VA 168 VA 1 20 A TR #1C-143 LIGHTING 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Enclosure: Indoor MCB Rating: 100 A Mounting: Surface Wires: 4 Mains Rating: 125 A
Supply From: B01-EP-TR Phases: 3 Mains Type: MCB Location: TELECOM ROOM 1C-142 Volts: 208Y/120 A.I.C. Rating: 10kA
Branch Panel: B01-TR1C-142B
1. ADD SPD DEVICES INTEGRAL TO ALL NEW TELECOM PANELBOARDS (SQ D OR EQUAL) FOR TYPE 2 PROTECTION.
2. ADD PXR 20 TRIP UNITS FOR ADJUSTING CIRCUIT BREAKERS (EATON OR EQUAL).
Notes:
Total Est. Demand: 12 A Total Conn.: 12 A
Total Est. Demand: 4220 VA Total Conn. Load: 4220 VA
Receptacle 4220 VA 100.00% 4220 VA Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Total Amps: 16 A 10 A 10 A Total Load: 1887 VA 1167 VA 1167 VA
29 SPD 20 A 1 0 VA -- 1 -- SPACE 30
27 SPD 20 A 1 0 VA -- 1 -- SPACE 28
25 SPD 20 A 1 0 VA -- 1 -- SPACE 26
23 SPACE -- 1 -- -- 1 -- SPACE 24
21 SPACE -- 1 -- -- 1 -- SPACE 22
19 SPACE -- 1 -- -- 1 -- SPACE 20
17 SPACE -- 1 -- -- 1 -- SPACE 18
15 SPACE -- 1 -- -- 1 -- SPACE 16
13 SPACE -- 1 -- -- 1 -- SPACE 14
11 SPACE -- 1 -- 0 VA 1 20 A SPARE 12
9 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 10
7 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 8
5 SPARE 20 A 1 0 VA 1167... 6
3 SPARE 20 A 1 0 VA 1167... 4
1 TR #1C-242 RECEPTACLE 20 A 1 720 VA 1167...
3 20 A TR #1C-242 RACK RECEPTACLE
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Enclosure: Indoor MCB Rating: 60 A Mounting: Surface Wires: 4 Mains Rating: 125 A
Supply From: B01-NP-TR Phases: 3 Mains Type: MCB Location: TELECOM ROOM 1C-242 Volts: 208Y/120 A.I.C. Rating: 10kA
Branch Panel: B01-TR1C-242A
1. ADD SPD DEVICES INTEGRAL TO ALL NEW TELECOM PANELBOARDS (SQ D OR EQUAL) FOR TYPE 2 PROTECTION.
2. ADD PXR 20 TRIP UNITS FOR ADJUSTING CIRCUIT BREAKERS (EATON OR EQUAL).
Notes:
Total Est. Demand: 13 A ACCESS CONTROLLER 83 VA 100.00% 83 VA Total Conn.: 13 A LTG 168 VA 125.00% 210 VA Total Est. Demand: 4587 VA NC 84 VA 100.00% 84 VA Total Conn. Load: 4547 VA Receptacle 4220 VA 100.00% 4220 VA Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Total Amps: 12 A 16 A 10 A Total Load: 1452 VA 1887 VA 1209 VA
29 SPD 20 A 1 0 VA -- 1 -- SPACE 30
27 SPD 20 A 1 0 VA -- 1 -- SPACE 28
25 SPD 20 A 1 0 VA -- 1 -- SPACE 26
23 SPACE -- 1 -- -- 1 -- SPACE 24
21 SPACE -- 1 -- -- 1 -- SPACE 22
19 SPACE -- 1 -- -- 1 -- SPACE 20
17 SPACE -- 1 -- -- 1 -- SPACE 18
15 SPARE 20 A 1 0 VA -- 1 -- SPACE 16
13 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 14
11 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 12
9 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 10
7 42 VA 168 VA 1 20 A TR #1C-242 LIGHTING 8
IU-1-02 15 A 2
42 VA 1167... 6
3 TR #1C-242 RECEPTACLE 20 A 1 720 VA 1167... 4
1 TR #1C-242 ACCESS CONTROLLER 20 A 1 83 VA 1167...
3 20 A TR #1C-242 RACK RECEPTACLE
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Enclosure: Indoor MCB Rating: 60 A Mounting: Surface Wires: 4 Mains Rating: 125 A
Supply From: B01-EP-TR Phases: 3 Mains Type: MCB Location: TELECOM ROOM 1C-242 Volts: 208Y/120 A.I.C. Rating: 10kA
Branch Panel: B01-TR1C-242B
1. ADD SPD DEVICES INTEGRAL TO ALL NEW TELECOM PANELBOARDS (SQ D OR EQUAL) FOR TYPE 2 PROTECTION.
2. ADD PXR 20 TRIP UNITS FOR ADJUSTING CIRCUIT BREAKERS (EATON OR EQUAL).
Notes:
Total Est. Demand: 12 A Total Conn.: 12 A
Total Est. Demand: 4400 VA Total Conn. Load: 4400 VA
Receptacle 4400 VA 100.00% 4400 VA Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Total Amps: 11 A 16 A 10 A Total Load: 1347 VA 1887 VA 1167 VA
29 SPD 20 A 1 0 VA -- 1 -- SPACE 30
27 SPD 20 A 1 0 VA -- 1 -- SPACE 28
25 SPD 20 A 1 0 VA -- 1 -- SPACE 26
23 SPACE -- 1 -- -- 1 -- SPACE 24
21 SPACE -- 1 -- -- 1 -- SPACE 22
19 SPACE -- 1 -- -- 1 -- SPACE 20
17 SPACE -- 1 -- -- 1 -- SPACE 18
15 SPACE -- 1 -- -- 1 -- SPACE 16
13 SPACE -- 1 -- -- 1 -- SPACE 14
11 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 12
9 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 10
7 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 8
5 SPARE 20 A 1 0 VA 1167... 6
3 TR #1-325 RECEPTACLE 20 A 1 720 VA 1167... 4
1 TR #1-325 RECEPTACLE 20 A 1 180 VA 1167...
3 20 A TR #1-325 RACK RECEPTACLE
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Enclosure: Indoor MCB Rating: 60 A Mounting: Surface Wires: 4 Mains Rating: 125 A
Supply From: B01-NP-TR Phases: 3 Mains Type: MCB Location: TELECOM ROOM 1-324 Volts: 208Y/120 A.I.C. Rating: 10kA
Branch Panel: B01-TR1-324A
1. ADD SPD DEVICES INTEGRAL TO ALL NEW TELECOM PANELBOARDS (SQ D OR EQUAL) FOR TYPE 2 PROTECTION.
2. ADD PXR 20 TRIP UNITS FOR ADJUSTING CIRCUIT BREAKERS (EATON OR EQUAL).
Notes:
Total Est. Demand: 14 A ACCESS CONTROLLER 83 VA 100.00% 83 VA Total Conn.: 14 A LTG 168 VA 125.00% 210 VA Total Est. Demand: 4913 VA NC 410 VA 100.00% 410 VA Total Conn. Load: 4873 VA Receptacle 4220 VA 100.00% 4220 VA Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Total Amps: 13 A 16 A 11 A Total Load: 1573 VA 1929 VA 1372 VA
29 SPD 20 A 1 0 VA -- 1 -- SPACE 30
27 SPD 20 A 1 0 VA -- 1 -- SPACE 28
25 SPD 20 A 1 0 VA -- 1 -- SPACE 26
23 SPACE -- 1 -- -- 1 -- SPACE 24
21 SPACE -- 1 -- -- 1 -- SPACE 22
19 SPACE -- 1 -- -- 1 -- SPACE 20
17 SPACE -- 1 -- -- 1 -- SPACE 18
15 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 16
13 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 14
11 42 VA 0 VA 1 20 A SPARE 12
IU-1-03 15 A 2
42 VA 0 VA 1 20 A SPARE 10
7 163 VA 1167... 8
BC-1 BRANCH CONTROLLER 15 A 2
163 VA 1167... 6
3 TR #1-324 RECEPTACLE 20 A 1 720 VA 1167...
3 20 A TR #1-324 RACK RECEPTACLE
1 TR #1-324 ACCESS CONTROLLER 20 A 1 83 VA 168 VA 1 20 A TR #1-324 LIGHTING 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Enclosure: Indoor MCB Rating: 60 A Mounting: Surface Wires: 4 Mains Rating: 125 A
Supply From:…