Attachment 11 - Newington EHRM Drawings - Part 2 of 16.pdf
PDF 9 MB Posted
- Attached to
- Z2DA--689A4-22-700 EHRM Infrastructure, Newington CONSTRUCTION SOLICITATION (VA-24-00028377)
- Solicitation number
- 36C77624B0015_1
View the file
Other files
Show 40 more
Latest 50 of 68 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
FIRE PROTECTION SYMBOL LEGEND
DRAWING NUMBER WHERE DETAILED
SECTION LETTER
DRAWING NUMBER WHERE DETAILED
DETAIL NUMBER
DRAWING NUMBER WHERE DETAILED
ELEVATION LETTER
SECTION, ELEVATION, AND DETAIL TITLES
FX200
FX500
FX300
ELEVATION
DETAIL
SECTION
FX-100
A
FX500
A
C.P.
DISCHARGE NOZZLE
CONTROL PANEL
CLEAN AGENT FIRE SUPPRESSION
FIRE HOSE VALVE CABINET
FIRE HOSE CABINET
ALARM BELL
WATER MOTOR GONG
PENETRATION
TEST PLUG (PRESS/TEMP)
WH
PRESSURE GAUGE AND GAUGE COCK
NEW PIPE CONNECTION TO EXISTING PIPING
EXISTING PIPE TO BE REMOVED
EXISTING PIPING TO REMAIN
NEW PIPING
FLEXIBLE CONNECTION
ORIFICE UNION
FLANGED UNION
UNION
RISE IN PIPE
DROP IN PIPE
CAPPED OUTLET
SIDE CONNECTION
BOTTOM CONNECTION, 45° OR 90°
TOP CONNECTION, 45° OR 90°
ECCENTRIC REDUCER
REDUCER OR INCREASER
DIRECTION OF FLOW
MAV MANUAL AIR VENT (MAV)
AAV AUTOMATIC AIR VENT (AAV)
AG AIR GAP FITTING
WALL HYDRANT
POINT OF CONNECTION TO EXISTING
KEYED NOTE
SCHEMATIC SYMBOLS
ABBREVIATIONSYMBOL DESCRIPTION
XX
STANDPIPE VALVE
INSPECTOR'S TEST CONNECTION (VERTICAL)DFP
D
FP INSPECTOR'S TEST CONNECTION (HORIZONTAL)
FP WET PIPE FIRE RISERFP
(E)FDC
FDC
FLOW SWITCH
FDC (E) EXISTING FIRE DEPARTMENT INLET CONNECTION
FIRE DEPARTMENT INLET CONNECTIONFDC
FLOW CONTROL VALVE
ATMOSPHERIC VACUUM BREAKER
PRESSURE STYLE VACUUM BREAKER
DIAPHRAGM (PROCESS SYSTEMS)
OS&Y VALVE
GATE VALVE
GLOBE VALVE
BUTTERFLY VALVE
BALL VALVE
CHECK VALVE
WATER PRESSURE REDUCING VALVE
PRESSURE RELIEF VALVE
TEMPERATURE AND PRESSURE RELIEF VALVE
VALVE IN VERTICAL
REDUCED PRESSURE BACKFLOW PREVENTER (RPBP)
DRAIN VALVE
FP ROOF MANIFOLD
AUTO BALL DRIP VALVE
OR OR
OR
ABBREVIATION DESCRIPTIONSYMBOL
VALVE SYMBOLS
ABBREVIATIONS
SYMBOL DESCRIPTION
NEW PENDANT STYLE SPRINKLER HEAD
FP
SP STANDPIPE; WETSP
FP FIRE PROTECTION; WET PIPE
ABBREVIATIONSYMBOL DESCRIPTION
PIPING SYMBOLS
FIRE PROTECTION-INTERIOR
ORDINARY GROUP 1 HAZARD
ORDINARY GROUP 2 HAZARD
OH1
OH2
DEMO PENDANT STYLE SPRINKLER HEAD
NEW UPRIGHT STYLE SPRINKLER HEAD
DEMO UPRIGHT STYLE SPRINKLER HEAD
F.D.C.(E)FIRE DEPARTMENT INLET CONNECTION F.D.C.
REDUCED PRESSURE BACKFLOW PREVENTER
F.H.(E)F.H.
CONSTRUCTION
FIRE HYDRANT
VALVE WITH VALVE BOX
FIRE PROTECTION
POST INDICATOR VALVE
PIV PIV(E)
F F(E)
EXISTINGNEWDESCRIPTION
SITE UTILITY SYMBOLS
DRAWING NUMBER WHERE DETAILED
SECTION LETTER
DRAWING NUMBER WHERE DETAILED
DETAIL NUMBER
SECTION, ELEVATION, AND DETAIL SYMBOLS
FX-100
A
DRAWING NUMBER WHERE DETAILED
ELEVATION LETTER
GENERAL NOTES:
NOTE: NOT ALL ABBREVIATIONS AND
SYMBOLS APPLY TO THIS PROJECT.
1.
2.
3.
4.
5.
6.
7.
8.
ALL NEW PIPING FOR SPRINKLER HEADS SHALL BE HARD PIPED, NO FLEXIBLE CONNECTIONS ARE PERMISSIBLE.
ALL PIPING IN FINISHED ROOMS OR SPACES SHALL BE CONCEALED IN FURRED CHASES OR SUSPENDED CEILINGS, UNLESS
OTHERWISE NOTED.
PROVIDE ACCESS PANELS OR DOORS IN INACCESSIBLE CEILINGS AND/OR CHASES FOR ALL VALVES. THEY SHALL BE FURNISHED UNDER DIVISION 23 AND INSTALLED UNDER THE ARCHITECTURAL SPECIFICATION. ACCESS DOOR RATING SHALL MATCH
CLASSIFICATION OF WALL AND CEILING FIRE RATING.
COORDINATE THE LOCATION OF SPRINKLER HEADS AND ACCESS DOORS WITH THE ARCHITECTURAL REFLECTED CEILING PLAN(S).
REFER TO THE ARCHITECTURAL DRAWINGS FOR EXACT LOCATION OF ALL FIRE RATED AND/OR SMOKE RATED WALLS AND ASSEMBLIES. ALL PIPE PENETRATIONS OF FIRE, SMOKE AND FULL HEIGHT WALLS SHALL BE CAULKED AIRTIGHT TO THE ADJACENT
STRUCTURE BY MEANS OF U.L. APPROVED FIRE PROOF CAULKING MATERIAL.
CONTRACTOR SHALL COORDINATE ALL FIRE PROTECTION PIPING WITH DUCTWORK, PIPING, PLUMBING, STRUCTURAL AND ELECTRICAL SYSTEMS AND SHALL PROVIDE NECESSARY OFFSETS TO AVOID CONFLICTS AND TO MAINTAIN EQUIPMENT ACCESS
AND SERVICEABILITY.
CONTRACTOR SHALL FURNISH ALL NECESSARY STRUCTURES, INSERTS, SLEEVES, AND HANGING DEVICES FOR INSTALLATION
PIPING.
CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING ALL NECESSARY MISCELLANEOUS ANGLES, CHANNELS, UNISTRUT, ETC., AS MAY BE REQUIRED TO ADEQUATELY SUPPORT FIRE PROTECTION PIPING AND EQUIPMENT IN A MANNER APPROVED BY THE
ARCHITECT, WHICH WILL NOT OVERLOAD THE BUILDING STRUCTURAL SYSTEM.
IT IS CRITICAL THAT THE CONTRACTOR PERFORM A COMPLETE REVIEW OF ALL SUBMITTALS PRIOR TO SUBMISSION TO THE AE/COR. INCOMPLETE, INCORRECT AND UNCLEAR SUBMITTALS WILL BE REJECTS AND MARKED AS "REVISE AND RESUBMIT". ALL SUBMITTALS MUST CLEARLY INDICATE THE EQUIPMENT SELECTIONS FOR THE PROJECT. TECHNICAL DRAWINGS OF COMPLETE ASSEMBLIES, REFLECTING ACCURATE PROJECT CONDITIONS, SHALL BE SUBMITTED WITH EQUIPMENT SELECTIONS TO ENSURE SPACE ALLOWANCES ARE REFLECTED IN THE ACTUAL SPACE AVAILABLE. WHERE SIZE DEVIATIONS DIFFER FROM THE BASIS OF DESIGN CONTRACTOR SHALL HIGHLIGHT THE DIFFERENCES FOR AE.COR REVIEW WITHIN THE SUBMITTAL. CONTRACTOR SHALL PROVIDE INSTALLATION ROUTE AND VERIFICATION THAT ACCESS POINTS, PLACEMENT ROUTE, SUPPORTS, AND REQUIRED EQUIPMENT CLEARANCES ARE IDENTIFIED ON THE ROUTE DRAWING. SAFETY PROTOCOLS FOR SUBJECT STATION SHALL BE REFLECTED ON EQUIPMENT CLEARANCES. PLATFORMS AND INTERFACE AREAS (FILTER, GAUGES, MONITORS, VALVES, ETC.)
SHALL HAVE PROPER CLEARANCE AS DEFINED BY THE MANUFACTURER, VA SAFETY PERSONNEL AND SERVICE PERSONNEL.
ACCESS POINTS OF USE SHALL BE CLEARLY IDENTIFIED ON THE DRAWINGS.
1.
2.
3.
4.
5.
6.
THE DEMOLITION DRAWINGS REFLECT INFORMATION ON EXISTING BUILDING SERVICES GATHERED BY SITE INSPECTION, DISCUSSIONS WITH MAINTENANCE PERSONNEL AND PREVIOUS CONSTRUCTION DRAWINGS. THE EXACT LOCATION, ARRANGEMENT, AND SIZES OF PIPE LINES IN THE EXISTING BUILDING MAY BE DIFFERENT FROM THAT SHOWN ON THESE
DRAWINGS.
THE CONTRACTOR SHALL COORDINATE THE SHUTDOWN OF EXISTING BUILDING SERVICES FOR REMOVALS WITH OWNER
AUTHORIZED REPRESENTATIVE AND SHALL CONFORM TO THEIR REQUIREMENTS.
DISRUPTION OF NORMAL FACILITY ACTIVITIES ARE TO BE KEPT TO AN ABSOLUTE MINIMUM. DUST, DEBRIS, AND FUMES SHALL BE CONTROLLED SO AS NOT TO AFFECT THE HEALTH AND SAFETY OF OCCUPIED AREAS WITHIN THE FACILITY WHICH ARE OUTSIDE THE AREA OF WORK. COORDINATE WITH THE ARCHITECT AND THE OWNER'S REPRESENTATIVE WITH REGARD TO ALL ACTIVITIES TO BE CONDUCTED OUTSIDE OF THE SUITE REMODEL AREA WHICH MAY AFFECT THE OPERATION OF THE FACILITY. THE CONTRACTOR SHALL PROVIDE TEMPORARY VENTILATION (MAINTAIN WORK ZONE AT NEGATIVE PRESSURE), FILTRATION, AIR PURIFIERS, DUST SCREENS, ETC. FOR ALL WORK AREAS AFFECTED BY DEMOLITION FOR NEW INSTALLATION TO MINIMIZE DUST
AND FUMES.
THE CONTRACTOR SHALL PRESENT AN AREA BY AREA WORK PLAN WELL IN ADVANCE TO THE ARCHITECT AND THE OWNER'S AUTHORIZED REPRESENTATIVE FOR APPROVAL PRIOR TO BEGINNING WORK. THE WORK PLAN SHALL INCLUDE AN OUTLINE OF ALL ACTIVITIES OF ALL SUBCONTRACTORS. THE CONTRACTOR SHALL COORDINATE WITH THE OWNER'S AUTHORIZED REPRESENTATIVE TO ESTABLISH ACCEPTABLE ROUTING AND ACCESS FOR MATERIALS REQUIRED FOR THE NEW INSTALLATION.
GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATION OF ALL TRADES INCLUDING MECHANICAL, PLUMBING, ELECTRICAL, FURNITURE, AND ARCHITECTURAL. ANY DISCREPANCIES SHALL BE REPORTED IMMEDIATELY TO THE ARCHITECT
PRIOR TO START OF WORK.
ALL NEW TO EXISTING PIPE CONNECTIONS SHALL BE FIELD VERIFIED PRIOR TO ORDERING AND FABRICATING NEW PIPING OR
FITTINGS.
GENERAL DEMO NOTES:
CONTRACTOR SHALL REPLACE AND RELOCATE EXISTING FIRE SPRINKLER HEAD DROPS TO SERVE THE NEW SPRINKLERS AT THE
NEW LOCATIONS.
WHERE REQUIRED, CONTRACTOR SHALL REPLACE EXISTING FIRE PROTECTION BRANCH PIPING TO SERVE THE NEW LOCATIONS.
CONTRACTOR SHALL PROVIDE COMPLETE FIRE PROTECTION SYSTEM COORDINATION DRAWINGS TO ENSURE ALL REQUIRED CLEARANCES ARE MAINTAINED AND THAT NO CONFLICTS EXIST WITH ANY OTHER MECHANICAL, PLUMBING, ELECTRICAL, COMMUNICATIONS, OR STRUCTURAL SYSTEMS.
CONTRACTOR SHALL MAINTAIN COMPLIANCE WITH NFPA 13 FOR ALL SURROUNDING SPACES DURING RENOVATION.
FIRE PROTECTION SCOPE OF WORK:
DN DOWN
YH YARD HYDRANT
ABOVE FINISHED FLOOR
ABOVE FINISHED GRADE
BOTTOM OF PIPE
ELEVATION
FINISHED FLOOR ELEVATION
FEET
GALLONS PER MINUTE
HORSEPOWER
HEAD
INCHES
INVERT
NOT APPLICABLE
NOT IN CONTRACT
NUMBER
NORMALLY CLOSED
NORMALLY OPEN
OUTSIDE SCREW AND YOKE
PHASE
POUNDS PER SQUARE INCH GAUGE
STATIC PRESSURE
TYPICAL
YARD BOX
AFF
AFG
BOP
EL
FFE
FT
GPM
HP
HD
IN
INV
NA
NIC
No. # N.C.
N.O.
OS&Y
PSIG
SP
TYP
YB
PH
QUICK RESPONSE SPRINKLERQRS
NOT TO SCALENTS
CONTRACTING OFFICER'S REPRESENTATIVECOR
FIRE ALARM STROBE/HORN WALL MOUNTED
FIRE ALARM STROBE/HORN CEILING MOUNTED
HEAT/SMOKE DETECTORH
NEW UPRIGHT CLEAN AGENT SPRINKLER HEAD
DEMO UPRIGHT CLEAN AGENT SPRINKLER HEAD
PIPE RING HANGER
TOLCO FIG. 200
BAR JOIST OR STEEL
MEMBER BY
STRUCTURAL
1" MIN.
1" MIN.
SPRINKLER PIPE PER
PLAN
ALL THREAD ROD
TOLCO FIG. 100
REVERSIBLE BEAM CLAMP
(TYPICAL) TOLCO FIG. 65
BEAM CLAMPS TO BE COORDINATED
WITH STRUCTURAL TO VERIFY
TORSION LIMITS
RESTRAINING STRAP
(TYPICAL)
TOLCO FIG. 69/69R
BASIS OF DESIGN IS TOLCO FIGURE
NUMBERS OR APPROVED EQUAL.
PIPE PER PLAN PIPE RING HANGER
TOLCO FIG. 200
ALL THREAD ROD
TOLCO FIG. 100
USE 3/8" CONCRETE INSERT FOR
UP TO 4" PIPE
USE 1/2" CONCRETE INSERT FOR
6" AND 8" PIPE
INSERT SHALL BE PLACED WITHIN
THICKEST PORTION OF
CONCRETE DECKING, TYPICAL
CONCRETE
DECKING
BASIS OF DESIGN IS TOLCO FIGURE
NUMBERS OR APPROVED EQUAL.
INSERT IS NOT
PERMITTED WITHIN
DECKING VALLEY,
TYPICAL
11/09/2023
11/09/2023
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
CONSULTANT
321 4 5 6 7 8 9 10
TRIPLE C - The A/E Group 201 E. Jefferson Street, Suite 200 Syracuse, NY 13202
MAT PERKINS
(315) 484-5958
STAMP
01_02
Au to de sk
D oc s:
//6
A4
-2 2-
0_
N ew in gt on _V
AM
C
_E H
R M
_I U
-1
2/
9A 4-
-7
.N ew in gt on
.E H
R M
.M
EP
.G en er al
.S he et s.
rv t
-0
1-
2:
:3
AM
01FX001
FIRE PROTECTION ABBREVIATIONS, SYMBOLS,
AND DETAILS
689A4-22-700
11/09/2023 M. Perkins K. McDermott
ISSUED FOR
CONSTRUCTION
EHRM INFRASTRUCTURE
UPGRADES
555 Willard Avenue, Newington, CT 06111
NTSF1 WIDE FLANGE BEAM CLAMP
NTSF4 DROP-IN ANCHOR
Revisions: Date:
UP
01FX100
C5
01FX100
C1
ELEV MACH RM
2C-B00
ELEV #S3
E8
STAIR #7
CS007
SVC LOBBY
CB-25
CANTEEN STORAGE
CB-24A
CORRIDOR
CB-24
CANTEEN OFFICE
B-103HAC
B-102
RETAIL STOCK RM
B-101
RETAIL STORAGE
B-112
AREAWAY EXTERIOR
OF BLDG.
CANTEEN OFFICE
E10
ELECT.
B-162
LA
B P R
ES
C R P
IC
K U P
2E -B 6B
LAB ENTRY AND MAIL
2E-B118
LAB
2E-B15A
LAB
2E-B119
AREAWAY EXTERIOR
OF BLDG.
LAB OFFICE
2E-B124E
LAB OFFICE
2E-B124F
LAB STORAGE
2E-B124D
STAIR #1
B001
DRIVE DOWN
CONCRETE PAVEMENT
OFFICE LAB
2E-B124C
HAC
2E-B123
LAB OFFICE
2E-B124
LAB EQUIP. RM
2E-B124B
STORAGE LAB
2E-B124A
CORRIDOR
B033
CORRIDOR
B032
CORRIDOR
B030
C O R R
ID
O R
B
CORRIDOR
B117
LAB EMPLOYEE
LOUNGE
2E-B131
LAB STAFF LOCKER
2E-B130
TOILET
2E-B131A
TOILET
2E-B130A
LAB BREAK RM
2E-B129
REF. STORAGE
2E-B128 MEDICAL RECORDS
2E-B127
TELECOM ROOM
2E-B140
ST
A
FF
T O
IL
ET
2E -B 5B
STAFF TOILET
2E-B135A
STAIR #2
B002
C O M M U N
IC
A
TI
O N
2E -B
WAITING
2E-B042
ELECTRICAL
2E-B139
C O R R
ID
O R
B
CONFERENCE RM
2E-B137A
HIMS SPVSP
2E-B137B
HIMS SUPV OFFICE
2E-B137C
OFFICE
2E-B140G
WORK RM
2E-B137
MECH EQUIP.
2E-B133
ELEV #P3
2E-B013
ELEV #P2
2E-B012
ELEV. #P1
2E-B011
ELEV #S2
2E-B015
ELEV #S1
2E-B014
C O M M U N
IC
A
TI
O N
C
LO
SE
T
2E -B
LI
N
EN
2E -B
TR
A
SH
2E -B
B U
IL
D
IN
G S
TO
R A G E
2E -B
EL
EC
TR
IC
A L
2E -B
STAIR #3
B003
CORRIDOR
B056
PATIENT ELEVATOR
LOBBY
B021
CORRIDOR
B022
FE
M A
LE
S
TA
FF
LO
C K
ER
2E -B
STAFF LOUNGE
2E-B154
TOILET
2E-B155A
TOILET
2E-B153A
AREA
B050
HAC
2E-B149
CORRIDOR
B048
DISPATCH
2E-B049
CLEAN RECEIVING AND
BREAKOUT
2E-B148
BULK STORAGE
2E-B148A
WORK RM
2E-B147
CHIEF SPD
2E-B146A
SPD CLERKS
2E-B146
SU
M P R M
2E -B
C O R R
ID
O R
B
CORRIDOR
B043
MALE STAFF LOCKER
2E-B153
MECH. EQUIP.
2E-B157B
SOILED RECEIVING/
DECONTAM
2E-B156
STERILE
2E-B157A
PREP. ASSEMBLY AND
STERILIZATION
2E-B157
HAC
2E-B152
MANUAL EQUIP. WASH
2E-B150
AUTO CART WASH
2E-B151
STERILE/ NON-
STERILE STORAGE
2E-B144
CORRIDOR
B052
ETO
2E-B158
ETO
2E-B158A
HOLDING RM
2E-B144A
WOMEN'S TOILET
B-108
MENS TOILET
B-109
ENTRY/ EXIT
B-118
FOOD PREP
B-107
STORAGE
B-106
SERVING
B-105
CASHIER
B-110
FOOD COURT
B-111
DINING RM
B-115
CORRIDOR
B-119
PREP.
B-100
DISH WASHING
B-104
GENERATOR ROOM
ROOM
ROOM
ROOM
ROOM
STAIRS
VESTIBULE
TELECOM ROOM
2E-B127A
7'
- 5
5 6
7' - 5"
TELECOM
ROOM
2E-B127A
161 SF
MEDICAL
RECORDS
2E-B127
14' - 10" 2' - 2"
0" 3'
- 0
PROPOSED BOUNDARY
OF NEW TELECOM ROOM
MEDICAL
RECORDS
2E-B127
CORRIDOR
B034
CORRIDOR
B033
CONTRACTOR V.I.F
3' - 0"
CO
NT
RA
CT
OR
V
.I.
F
1'
- 6
CO
NT
RA
CT
OR
V
.I.
F
0"
CO
NT
RA
CT
OR
V .I.
F 3'
- 0
CONTRACTOR V.I.F
17' - 0"
2 7
11/09/2023
11/09/2023
N
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
CONSULTANT
321 4 5 6 7 8 9 10
GENERAL NOTES
KEY PLAN
KEYNOTES
2W
TRIPLE C - The A/E Group 201 E. Jefferson Street, Suite 200 Syracuse, NY 13202
MAT PERKINS
(315) 484-5958
2C 2E
STAMP
Au to de sk
D oc s:
//6
A4
-2 2-
0_
N ew in gt on _V
AM
C
_E H
R M
_I U
-1
2/
9A 4-
-7
.N ew in gt on
.E H
R M
.M
EP
.B
_0 2_
R
.rv t
-0
1-
0:
:1
01FX100
FIRE PROTECTION PLAN - BASEMENT LEVEL 689A4-22-700
01_02
11/09/2023 M. Perkins M. RIFFLE
ISSUED FOR
CONSTRUCTION
EHRM INFRASTRUCTURE
UPGRADES
555 Willard Avenue, Newington, CT 06111
A.
B.
CONTRACTOR SHALL PROVIDE THE FOLLOWING PRIOR TO
COMMENCEMENT OF WORK FOR REVIEW AND APPROVAL:
SHOP DRAWING IDENTIFYING MAIN PIPE SIZES AND LOCATIONS,
LOCATION OF PIPE BRACING, HANGERS AND SPRINKLER HEADS
AND DETAILS
CUT SHEETS AND SUBMITTAL FOR ALL PIPING, FITTINGS,
SPRINKLER HEADS, HANGERS AND SUPPORT ATTACHMENTS
A.
B.
C.
D.
E.
F.
G.
H.
I.
J.
K.
L.
M.
N.
O.
P.
Q.
R.
EXISTING CONDITIONS ARE BASED ON EXISTING PLANS AND FIELD VERIFICATION
WHERE FEASIBLE. ACTUAL CONDITIONS MAY DIFFER FROM THOSE INDICATED.
CONTRACTOR SHALL FIELD VERIFY IN ADVANCE THE LOCATION AND CONDITION
OF THE EXISTING SYSTEMS SHOWN TO BE MODIFIED OR REMOVED.
CONTRACTOR TO NOTIFY ARCHITECT SHOULD CONDITIONS BE FOUND TO DIFFER
SIGNIFICANTLY FROM THE CONSTRUCTION DOCUMENTS.
A DETAILED SCHEDULE, INCLUDING PROJECTED SERVICE INTERRUPTION DATES
WITH DURATIONS, AND DETAILED PHASING PLAN IS TO BE PROVIDED TO THE COR
PRIOR TO THE START OF WORK. THIS SUBMITTAL MUST BE ACCEPTED BY THE
COR PRIOR TO THE START OF WORK.
REFER TO ARCHITECTURAL DRAWINGS FOR EXACT DIMENSIONAL DATA, CEILING
HEIGHTS, AND SQUARE FOOTAGE.
CONTRACTOR SHALL COORDINATE ALL WORK WITH BUILDING OWNER AND
OTHER TRADES PRIOR TO CONSTRUCTION.
ALL PIPING TO BE ROUTED WITHIN CEILING SPACE OR CONCEALED IN FURRED
CHASES UNLESS NOTED OTHERWISE.
ALL AREAS ARE DESIGNED AS ORDINARY HAZARD GROUP 1 OCCUPANCY UNLESS
NOTED OTHERWISE ON PLAN.
ALL SPRINKLER SYSTEMS SHALL BE INSTALLED IN ACCORDANCE WITH THE 2022
NFPA 13.
ALL MATERIALS, DEVICES, HANGERS AND SUPPORTS SHALL BE NEW AND UL
LISTED FOR USE IN FIRE PROTECTION SYSTEMS.
ALL NEW SPRINKLERS SHALL BE PROVIDED WITH NEW ESCUTCHEONS TO MATCH
EXISTING BUILDING STANDARDS.
INSTALL QUICK RESPONSE SPRINKLERS (QRS) IN ALL AREAS, EXCEPT WHERE
SPECIFICALLY PROHIBITED AS DEFINED BY 2022 NFPA 13.
PIPING TO BE SCHEDULE 40 BLACK STEEL WITH CAST IRON FITTINGS.
ANY FLOOR, WALL, OR CEILING CUTTING OR FILLING THAT IS REQUIRED TO
COMPLETE THIS PROJECT, THE CONTRACTOR SHALL PATCH AND PAINT AND
RETURN TO MATCH EXISTING CONDITIONS AND FINISHES.
CONTRACTOR TO PROVIDE GALVANIC PROTECTION AS REQUIRED AT
CONNECTIONS BETWEEN ALL DISSIMILAR METALS.
CONTRACTOR TO VALIDATE AND VERIFY ALL FIRE RATED AND/OR SMOKE RATED
WALLS AND ASSEMBLIES INDICATED ON PLANS IN WORK AREA. PROVIDE ALL
PIPING PENETRATIONS OF FIRE, SMOKE AND FULL HEIGHT WALLS SHALL BE
CAULKED AIRTIGHT TO THE ADJACENT STRUCTURE BY MEANS OF U.L. APPROVED
FIREPROOF CAULKING MATERIAL.
ALL NEW PIPES TO BE CLEANED AND TESTED PRIOR TO COMMISSIONING.
THE SPRINKLER CONTRACTOR SHALL COORDINATE AND PERFORM ALL FIRE
PROTECTION WORK IN ACCORDANCE WITH VA REQUIREMENTS TO ENSURE THAT
CONTINUOUS SPRINKLER COVERAGE IS PROVIDED THROUGHOUT THE PROJECT.
THE SPRINKLER CONTRACTOR SHALL COORDINATE ALL FIRE PROTECTION
SYSTEM SHUTDOWNS, INCLUDING POINTS OF TIE IN, ETC. WITH THE VA PRIOR TO
PERFORMING WORK.
CONTRACTOR SHALL REPLACE EXISTING SPRINKLERS WITH NEW UPRIGHT
SPRINKLERS AT THE TIME OF CEILING REMOVAL TO MAINTAIN SPRINKLER
PROTECTION WITHIN THE CONSTRUCTION AREA.
CONTRACTOR SHALL REPAIR ANY DAMAGE TO THE EXISTING IRRIGATION SYSTEM
SPRINKLER HEAD LEGEND
SYM.
DEMO TYPE QUICK
RESPONSE TEMP "K" DEMO
QUANTITY
PENDENT
YES 170F 5.6UPRIGHT
YES 155F 5.6
NOTE: LEGEND INFORMATION IS SPECIFIC TO THIS SHEET ONLY
NEW
QUANTITY
SYM.
NEW
-1
+2
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
EXISTING SPRINKLER HEAD IN THIS LOCATION TO REMAIN, PROTECT IN PLACE.
CONTRACTOR IS RESPONSIBLE FOR MAINTAINING COMPLIANCE WITH THE 2022
NFPA 13 FOR SURROUNDING SPACING DURING AND AFTER RENOVATION.
CONTRACTOR IS RESPONSIBLE FOR FIELD VERIFYING SPRINKLER HEAD
LOCATIONS AND PIPING TO BE MODIFIED BY THE RENOVATION PRIOR TO
COMMENCING WORK.
EXISTING PENDENT SPRINKLER HEAD IN THIS LOCATION TO BE REMOVED AND
REPLACED WITH NEW UPRIGHT SPRINKLER HEAD WITH PROTECTIVE HEAD
CAGE. INSTALL SPRINKLER HEAD AND HANGERS IN ACCORDANCE WITH THE
2022 NFPA 13. SEE SHEET FX001 FOR ADDITIONAL INFORMATION.
EXISTING UPRIGHT SPRINKLER HEAD IN THIS LOCATION TO BE REMOVED AND
REPLACED WITH NEW UPRIGHT SPRINKLER HEAD WITH PROTECTIVE HEAD
CAGE. INSTALL SPRINKLER HEAD AND HANGERS IN ACCORDANCE WITH THE
2022 NFPA 13. SEE SHEET FX001 FOR ADDITIONAL INFORMATION.
NEW UPRIGHT SPRINKLER HEAD WITH PROTECTIVE HEAD CAGE. CONNECT
PIPING TO NEAREST BRANCH LINE. INSTALL SPRINKLER HEAD AND HANGERS IN
ACCORDANCE WITH THE 2022 NFPA 13. SEE SHEET FX001 FOR ADDITIONAL
INFORMATION.
NEW HEAT/SMOKE DETECTOR AND FIRE ALARM STROBE/HORN, MOUNT AND
SUPPORT FROM DECK ABOVE. COORDINATE LOCATION WITH ALL OTHER
TRADES, EXISTING CONDITIONS, AND COR. SEE ARCHITECTURAL PLANS FOR
ADDITIONAL INFORMATION.
CONTRACTOR TO V.I.F. LOCATION OF EXISTING SPRINKLER HEADS, IF
LOCATIONS MEET NFPA 13 REQUIREMENTS, USE EXISTING LOCATION FOR NEW
UPRIGHT SPRINKLER HEAD.
EXISTING HEAT/SMOKE DETECTOR IN THIS LOCATION TO BE REMOVED AND
REPLACED WITH NEW HEAT/SMOKE DETECTOR.
THIS SPACE IS DESIGNATED AS A LIGHT HAZARD SPACE.
EXISTING HEAT/SMOKE DETECTOR IN THIS LOCATION TO REMAIN, PROTECT IN
PLACE.
NOTE: NOT ALL KEYNOTES
ARE USED ON EACH SHEET
SCALE: 1/16" = 1'-0"F1
FIRE PROTECTION PLAN - OVERALL
BUILDING FLOOR PLAN - BASEMENT
LEVEL
1/2" = 1'-0"C5 FIRE PROTECTION ENLARGED PLAN - BASEMENT LEVEL -ROOM 2E-B127A - NEW 1/4" = 1'-0"C1 FIRE PROTECTION ENLARGED PLAN - BASEMENT LEVEL - ROOM 2E-B127 - DEMO
01FX401
F7
01FX401
F4
01FX401
C2
01FX401
E2
01FX401
C7
01FX401
C4
01FX101
E2
01FX101
F2
01FX405
D6
01FX405
F6
01FX406
C6
01FX406
F6
TRNG BATH
1N-101A
TRNG KITCHEN
1N-101
OCCUPATIONAL
THERAPY
1N-109
STORAGE
1N-109B
OCCUPATIONAL
THERAPY
1N-109A
COMMUNICATION
ELECTRICAL
1N-110
1N-112
1N-115
C O R R
ID
O R
1N -C 1-
1N-114
1N-116
PROSTHETIC STORAGE
RM
1C-146
1-146A
ELEV
ELEV
STAIR #2
OFFICE EXAM
OFFICE EXAM
172 OFFICE EXAM
CONTROL RM
174A
EXAM RM
174B
1S-175A
WAITING ARA
1S-168
1S-170A
TOILET
1S-169
1S-170C
ISOTOPIC ST
1S-175
OFFICE
1S-177
ELECTRICAL RM
1S-179
CORRIDOR
1S-C1-4
MECH
1S-176
ISOTOPIC ST
1S-178
PUMP RM
1S-180
RECEPTION
1S-171A
C O R R
ID
O R
1S -C 1-
TELEPHONE RM
1S-164
MECH RM
1S-167
TELEPHONE RM
1C-143
TELECOM ROOM
1C-142
1C-141
C O R R
ID
O R
1C -C 1-
CORRIDOR
1C-C1-7
LOCK SMITH
1C-145
STAIR #1
HOSPITAL WHEEL
CHAIR STORAGE
1C-147
TOILET
1C-148G
CORRIDOR
1C-C1-8
ELECT.
1S-162-0
H O T W A
TE
R H
EA
TE
R S
1S -1 -0
MECH
1S-165
TOILET
1S-166
COMM-ELEC
WALK IN COOLER
1S-170B
CONTROL RM
174C
CONTROL RM
174F
EXAM RM
174D
EXAM RM
174E
AUDIOLOGY TEST
BOOTH
1N-117
1N-117A
C O R R
ID
O R
1N -C 1-
MSA
WAITING
STAFF
STAFF TLT
CORRIDOR
STORAGE
SOILED UTILITY
STRETCHER AREA
PIPE CHASE
106A
CONTROL
CORRIDOR
109 CT
INJECTION
CHANGING ROOM
TOILET
HSA
TOILET
READING
CORRIDOR
1N-C1-3
TELECOM ROOM
2C-1155 EXAM RM
2C-1158
ANTI COAGULATION
CLINIC EXAM RM
2C-1154
EXAM RM
2C-1159
IT
2C-1156 O
FF
IC
E
2C -1
MECH. EQUIP.
2E-1160
SMALL STATION
2E-1169
SMALL STATION
2E-1170
SMALL STATION
2E-1171
LARGE STATION
2E-1172
ELECT
2E-1166
STAIR #2
COMMUNICATION
2E-1165
SOILED UTILITY
2E-1163
HAC
2E-1162
CHASE
MEDS
2E-1168
CLEAN UTILITY
2E-1164
EXAM RM
2E-1159
EXAM RM
2E-1158
STAFF TOILET
2E-1180
ST
A
FF
L O C K
ER
2E -1
EXAM RM
2E-1157
PHARMACY OFFICE
2E-1182
C O R R
ID
O R
EXAM RM
2E-1184
EXAM RM
2E-1185
NURSE OFFICE
2E-1183
CLINICAL PHARMACIST
OFFICE
2E-1156
EXAM RM
2E-1186
ELECTRICAL
2E-1187
TOILET
2E-1190
HAC
2E-1200
EXAM RM (TB)
2E-1191
EXAM RM
2E-1192
EXAM RM
2E-1193
EXAM RM
2E-1194
ECG RM
2E-1195 C H
EC
K
- I N W A
LK
-IN
2E -1
TELECOM ROOM
2E-1178
URGENT CARE
STATION
2E-1050
SMALL STATION
2E-1173
LIFE SUPPORT
2E-1174
LIFE SUPPORT
2E-1175
STRETCHER STORAGE
2E-1197
TOILET
2E-1176
TRIAGE RM
2E-1177
VESTIBULE
2E-1053
CHASE
WAITING RM
2E-1198FEMALE TOILET
2E-1198A
MALE TOILET
2E-1198B
DIR. OFFICE
2E-1199A
OFFICE
2E-1199B
PR
IM
A R Y M
EN
TA
L
H
EA
LT
H C A R E O
FF
IC
E
2E -1
SHAFT
LINEN CHUTE
LINEN CHUTE
TRASH
2E-1203
LINEN
2E-1202
EL
EC
T
2E -1
STAIR #3
ELEV. #S1
2E-1014
ELEV #S2
2E-1015
EXAM RM
2E-1189
EXAM RM
2E-1188
ELEV #P3
2E-1013
ELEV #P2
2E-1012
ELEV #P1
2E-1011
C O M M U N
IC
A
TI
O N
C
LO
SE
T
2E -1
SVC ELEV LOBBY
2E-1064 PSYCHIATRIC
INITIATIVE
2E-1063
CORRIDOR
CORRIDOR
CORRIDOR
CORRIDOR
C O R R
ID
O R
C 1-
CORRIDOR
CORRIDOR
C O R R
ID
O R
CORRIDOR
CONFERENCE RM
2E-1147
EXAM RM
2E-1146
EXAM RM
2E-1140
EXAM RM
2E-1145
EXAM RM
2E-1144
TOILET
2E-1139
CORRIDOR
C O R R
ID
O R
TELEPHONE
EXAM RM (TB)
2E-1143
EXAM RM
2E-1142
POLICE STORAGE
2E-1149A
PO
LI
C E
LO
C K
ER
2E -1
MALE TOILET
2E-1103
FEMALE TOILET
2E-1104
MALE TOILET
2E-1105
FEMALE TOILET
2E-1111
CORRIDOR
EXAM RM
2E-1117
ST
A
FF
T O
IL
ET
2E -1
MALE TOILET
2E-1112
EXAM RM
2E-1115
EXAM RM
2E-1116 TO
IL
ET
2E -1 6A
EXAM RM
2E-1123
TO
IL
ET
2E -1 3A
EXAM RM
2E-1124
EXAM RM
2E-1125
CORRIDOR
C O R R
ID
O R
CLEAN UTILITY
2E-1133
INTAKE
2E-1132
STAFF TOILET
2E-1109A
MEDS
2E-1109B
TRIAGE 2
2E-1138
TRIANGE 1
2E-1109
WORK RM
2E-1109
WORK RM
2E-1109
EXAM RM
2E-1135
FIRM MGR
2E-1136
EXAM RM
2E-1137
N U R
SE
M G R O
FF
IC
E
2E -1
EXAM RM (TB)
2E-1119
EXAM RM
2E-1120
EXAM RM
2E-1121
EXAM RM
2E-1122
EXAM RM
2E-1131
EXAM RM
2E-1130
EXAM RM
2E-1129
EXAM RM
2E-1128
EXAM RM
2E-1141
EXAM RM
2E-1154
SHAFT
PATIENT ELEVATOR
LOBBY
EXAM RM
2E-1155
INFO BOOTH
2E-1031
VET ID CARD OFFICE
2E-1151
REGISTRATION
2E-1150
CORRIDOR
WAITING
2E-1026
C O R R
ID
O R
VA POLICE
2E-1027
FIRM 2 ADMIN.
2E-1101
REGISTRATION
2E-1030
WAITING
2E-1029
CORRIDOR
CORRIDOR
WAITING
2E-1041
CHECK-IN 1ST FLOOR
PRIMARY CARE
2E-1036
C O R R
ID
O R
CORRIDOR
C1-2
2E-1023
OFFICE
2C-1136
ELECT
2C-1135
ROOM
2E-1028
PATIENT ADVOCATE
OFFICE
2C-1130
OFFICE
2C-1129
COMP AND PAN
2C-1128
AUDIOLOGY
CONFERENCE RM
2C-1127
COMP AND PAN RM
2C-1126
EYE CLINIC
2C-1125
EXAM TELEHEALTH
2C-1124
TELEHEALTH
STORAGE
2C-1123
TELEHEALTH OFFICE
2C-1140
ROOM
2E-1043
COMP AND PAN OFFICE
2C-1138
AUDIOLOGY OFFICE
2C-1137
MECH BELOW
C O R R
ID
O R
2C -C 1-
WAITING
2C-1141
CHASE
ELEV #S3
STAIR #7
SVC LOBBY
2C-C1-9
TOILET
2C-1119B
STORAGE
2C-1119A
CASHIER
2C-1120
COMMUNICATION
2C-1121
COMMUNICATION CTR
2C-1119
C O R R
ID
O R
2C -1
ELECTRICAL
2C-1122
CASE MGR OFFICE
2C-1116
RN OFFICE
2C-1115
WAITING
2C-1029
OFFICE
2C-1117
SOCIAL WORKER
2C-1118
STAIR #6
DAV TRANSPORTATION
2C-1108B
TOILET
2C-1108C
DRIVERS OFFICE
2C-1108A
FIRMI ADMIN. OFFICE
2C-1101
STORAGE FOR
PRIMARY CARE
2C-1100
BLOOD DRAW
2C-1111
STAIR #5
PR
O
ST
H
ET
IC
S
2C -1
CORRIDOR
2C-C1-3
OFFICE
2C-1112
HAC
2C-1113
PROSTHETICS
2C-1114
HR/ PIV OFFICE
2C-1131
MALE TOILET
2C-1132
FEMALE TOILET
2C-1133
CORRIDOR
2C-1031
CORRIDOR
2C-1032
CORRIDOR
2C-1027
DAV TRANSPORTATION
2C-1108
ACCENT OFFICE
2C-1107
DAV TRANSPORTATION
OFFICE
2C-1108D
TOILET
2C-1106
TOILET
2C-1105
VENDING RM
2C-1104
ST
O R A G E
M A
LE
T O
IL
ET
2C -1
COUMADIN
2C-1153
ANTI COAGULATION
CLINIC
2C-1160
STAIR #4
COMP AND PEN CLINIC
EXAM RM
2C-1152
COMP AND PEN CLINIC
2C-1151
ANTI COAGULATION
CLINIC
2C-1162
ELEV MACH RM
2C-1163
TOILET
2C-1161
C O R R
ID
O R
2C -C 1-
ELEV
PA
TI
EN
T
EL
EV
L O B B Y
2C -C 1-
EXAM
2W-114
M A
LE
T O
IL
ET
2W -1
FEMALE PATIENT
TOILET
2W-116
TE
LE
C O M R O O M
2W -1
EXAM
2W-123
CHASE
OPEN OFFICE
2W-117
EXAM
2W-118
EXAM
2W-120
EXAM
2W-119
CORRIDOR
2W-1C4
SOILED UTILITY
2W-122
A N
TE
2W -1
WOMEN ISO/ PROC
2W-125
WAITING
2C-C1-11 WAITING
2C-C1-15
CORRIDOR
2C-C1-17
ELECTRICAL SWITCH
GEAR
2E-1161
EMERGENCY
GENERATOR
2E-1161B
CORRIDOR
NURSE MGR OFFICE
2E-1113
CONFERENCE RM
2E-1114
EXAM RM
2E-1127
HAC
2E-1126
C1-1
C1-2
C O R R
ID
O R
2E -C 1-
FE
M A
LE
T O
IL
ET
2C -1
TOILET
2C-1145
TRIAGE
2C-1144
TOILET
2C-1143
CORRIDOR
2C-C1-1041
RECEPTION
2C-1146
STAIR #8
2C-S8
VESTIBULE
2W-215
ELECTRICAL
2C-1164
OPEN OFFICE
2C-1165
EXAM
2C-1168
EXAM
2C-1167
EXAM
2C-1166
C O R R
2C -C 2-
EXAM
2C-1173
EXAM
2C-1172
EXAM
2C-1171
PCMH
2C-1170
SM
A
LL
M
ED
2C -1
C O R R
2C -C 2-
EXAM
2C-1174
EXAM
2C-1175
EXAM
2C-1176
EXAM
2C-1177
EXAM
2C-1179
EXAM
2C-1180
OPEN OFFICE
2C-1178
HSS
2C-1182
LINEN
2C-1181
OPEN OFFICE
2W-102
EXAM
2W-105A
EXAM
2W-105B
CONFERENCE ROOM
2W-107A
EXAM
2W-107B
EXAM
2W-108A
EXAM
2W-109A
EXAM
2W-112
TOILET
2W-106
TOILET
2W-104
EXAM
2W-101
NURSE MANAGER
2W-100
CORRIDOR
1C1-02W
CORRIDOR
2W-1C2
PHARM D
2W-132B
OIT COMM
2W-132A
EXAM
2W-130B
EXAM
2W-130A
EXAM
2W-103B
C
LE
A N S
TO
R A G E
2W -1 A
C H A
SE -
EXAM
2W-108B
EQUIP
2W-109B
TO
IL
ET
2W -1
TO
IL
ET
2W -1
13 CHASE
ELEC
2W-129
H A C
2W -1 A
CLEAN UTIL
2W-131B
MED
2W-131C
FM
S C O M M
2W -1
ST
A
IR
2W -S
EXAM
2W-127
TOILET
2W-126
C O R R
ID
O R
2W -1 C
C O R R
ID
O R
2W -1 C
COMPUTER RM
1C-148D
TELECOM
ROOM
1C-142
156 SF
2' - 4"
10' - 4"
5'
- 1
0"
CONTRACTOR V.I.F
2' - 5"
CONTRACTOR V.I.F
8' - 7 1/2"
CO
NT
RA
CT
OR
V
.I.
F
7'
- 1
/2
CO
NT
RA
CT
OR
V
.I.
F
5'
- 1
0"
TELECOM
1C-142
37 SF
TELEPHONE
RM
1C-143
272 SF
11/09/2023
11/09/2023
N
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
CONSULTANT
321 4 5 6 7 8 9 10
GENERAL NOTES
KEY PLAN
KEYNOTES
2W
TRIPLE C - The A/E Group 201 E. Jefferson Street, Suite 200 Syracuse, NY 13202
MAT PERKINS
(315) 484-5958
2C 2E
STAMP
Au to de sk
D oc s:
//6
A4
-2 2-
0_
N ew in gt on _V
AM
C
_E H
R M
_I U
-1
2/
9A 4-
-7
.N ew in gt on
.E H
R M
.M
EP
.B
_0 2_
R
.rv t
-0
1-
0:
:2
01FX101
FIRE PROTECTION PLAN - FIRST LEVEL 689A4-22-700
01_02
11/09/2023 M. Perkins M. RIFFLE
ISSUED FOR
CONSTRUCTION
EHRM INFRASTRUCTURE
UPGRADES
555 Willard Avenue, Newington, CT 06111
A.
B.
CONTRACTOR SHALL PROVIDE THE FOLLOWING PRIOR TO
COMMENCEMENT OF WORK FOR REVIEW AND APPROVAL:
SHOP DRAWING IDENTIFYING MAIN PIPE SIZES AND LOCATIONS,
LOCATION OF PIPE BRACING, HANGERS AND SPRINKLER HEADS
AND DETAILS
CUT SHEETS AND SUBMITTAL FOR ALL PIPING, FITTINGS,
SPRINKLER HEADS, HANGERS AND SUPPORT ATTACHMENTS
A.
B.
C.
D.
E.
F.
G.
H.
I.
J.
K.
L.
M.
N.
O.
P.
Q.
R.
EXISTING CONDITIONS ARE BASED ON EXISTING PLANS AND FIELD VERIFICATION
WHERE FEASIBLE. ACTUAL CONDITIONS MAY DIFFER FROM THOSE INDICATED.
CONTRACTOR SHALL FIELD VERIFY IN ADVANCE THE LOCATION AND CONDITION
OF THE EXISTING SYSTEMS SHOWN TO BE MODIFIED OR REMOVED.
CONTRACTOR TO NOTIFY ARCHITECT SHOULD CONDITIONS BE FOUND TO DIFFER
SIGNIFICANTLY FROM THE CONSTRUCTION DOCUMENTS.
A DETAILED SCHEDULE, INCLUDING PROJECTED SERVICE INTERRUPTION DATES
WITH DURATIONS, AND DETAILED PHASING PLAN IS TO BE PROVIDED TO THE COR
PRIOR TO THE START OF WORK. THIS SUBMITTAL MUST BE ACCEPTED BY THE
COR PRIOR TO THE START OF WORK.
REFER TO ARCHITECTURAL DRAWINGS FOR EXACT DIMENSIONAL DATA, CEILING
HEIGHTS, AND SQUARE FOOTAGE.
CONTRACTOR SHALL COORDINATE ALL WORK WITH BUILDING OWNER AND
OTHER TRADES PRIOR TO CONSTRUCTION.
ALL PIPING TO BE ROUTED WITHIN CEILING SPACE OR CONCEALED IN FURRED
CHASES UNLESS NOTED OTHERWISE.
ALL AREAS ARE DESIGNED AS ORDINARY HAZARD GROUP 1 OCCUPANCY UNLESS
NOTED OTHERWISE ON PLAN.
ALL SPRINKLER SYSTEMS SHALL BE INSTALLED IN ACCORDANCE WITH THE 2022
NFPA 13.
ALL MATERIALS, DEVICES, HANGERS AND SUPPORTS SHALL BE NEW AND UL
LISTED FOR USE IN FIRE PROTECTION SYSTEMS.
ALL NEW SPRINKLERS SHALL BE PROVIDED WITH NEW ESCUTCHEONS TO MATCH
EXISTING BUILDING STANDARDS.
INSTALL QUICK RESPONSE SPRINKLERS (QRS) IN ALL AREAS, EXCEPT WHERE
SPECIFICALLY PROHIBITED AS DEFINED BY 2022 NFPA 13.
PIPING TO BE SCHEDULE 40 BLACK STEEL WITH CAST IRON FITTINGS.
ANY FLOOR, WALL, OR CEILING CUTTING OR FILLING THAT IS REQUIRED TO
COMPLETE THIS PROJECT, THE CONTRACTOR SHALL PATCH AND PAINT AND
RETURN TO MATCH EXISTING CONDITIONS AND FINISHES.
CONTRACTOR TO PROVIDE GALVANIC PROTECTION AS REQUIRED AT
CONNECTIONS BETWEEN ALL DISSIMILAR METALS.
CONTRACTOR TO VALIDATE AND VERIFY ALL FIRE RATED AND/OR SMOKE RATED
WALLS AND ASSEMBLIES INDICATED ON PLANS IN WORK AREA. PROVIDE ALL
PIPING PENETRATIONS OF FIRE, SMOKE AND FULL HEIGHT WALLS SHALL BE
CAULKED AIRTIGHT TO THE ADJACENT STRUCTURE BY MEANS OF U.L. APPROVED
FIREPROOF CAULKING MATERIAL.
ALL NEW PIPES TO BE CLEANED AND TESTED PRIOR TO COMMISSIONING.
THE SPRINKLER CONTRACTOR SHALL COORDINATE AND PERFORM ALL FIRE
PROTECTION WORK IN ACCORDANCE WITH VA REQUIREMENTS TO ENSURE THAT
CONTINUOUS SPRINKLER COVERAGE IS PROVIDED THROUGHOUT THE PROJECT.
THE SPRINKLER CONTRACTOR SHALL COORDINATE ALL FIRE PROTECTION
SYSTEM SHUTDOWNS, INCLUDING POINTS OF TIE IN, ETC. WITH THE VA PRIOR TO
PERFORMING WORK.
CONTRACTOR SHALL REPLACE EXISTING SPRINKLERS WITH NEW UPRIGHT
SPRINKLERS AT THE TIME OF CEILING REMOVAL TO MAINTAIN SPRINKLER
PROTECTION WITHIN THE CONSTRUCTION AREA.
CONTRACTOR SHALL REPAIR ANY DAMAGE TO THE EXISTING IRRIGATION SYSTEM
SPRINKLER HEAD LEGEND
SYM.
DEMO TYPE QUICK
RESPONSE TEMP "K" DEMO
QUANTITY
PENDENT
YES 170F 5.6UPRIGHT
YES 155F 5.6
NOTE: LEGEND INFORMATION IS SPECIFIC TO THIS SHEET ONLY
NEW
QUANTITY
SYM.
NEW
-2
+2
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
EXISTING SPRINKLER HEAD IN THIS LOCATION TO REMAIN, PROTECT IN PLACE.
CONTRACTOR IS RESPONSIBLE FOR MAINTAINING COMPLIANCE WITH THE 2022
NFPA 13 FOR SURROUNDING SPACING DURING AND AFTER RENOVATION.
CONTRACTOR IS RESPONSIBLE FOR FIELD VERIFYING SPRINKLER HEAD
LOCATIONS AND PIPING TO BE MODIFIED BY THE RENOVATION PRIOR TO
COMMENCING WORK.
EXISTING PENDENT SPRINKLER HEAD IN THIS LOCATION TO BE REMOVED AND
REPLACED WITH NEW UPRIGHT SPRINKLER HEAD WITH PROTECTIVE HEAD
CAGE. INSTALL SPRINKLER HEAD AND HANGERS IN ACCORDANCE WITH THE
2022 NFPA 13. SEE SHEET FX001 FOR ADDITIONAL INFORMATION.
EXISTING UPRIGHT SPRINKLER HEAD IN THIS LOCATION TO BE REMOVED AND
REPLACED WITH NEW UPRIGHT SPRINKLER HEAD WITH PROTECTIVE HEAD
CAGE. INSTALL SPRINKLER HEAD AND HANGERS IN ACCORDANCE WITH THE
2022 NFPA 13. SEE SHEET FX001 FOR ADDITIONAL INFORMATION.
NEW UPRIGHT SPRINKLER HEAD WITH PROTECTIVE HEAD CAGE. CONNECT
PIPING TO NEAREST BRANCH LINE. INSTALL SPRINKLER HEAD AND HANGERS IN
ACCORDANCE WITH THE 2022 NFPA 13. SEE SHEET FX001 FOR ADDITIONAL
INFORMATION.
NEW HEAT/SMOKE DETECTOR AND FIRE ALARM STROBE/HORN, MOUNT AND
SUPPORT FROM DECK ABOVE. COORDINATE LOCATION WITH ALL OTHER
TRADES, EXISTING CONDITIONS, AND COR. SEE ARCHITECTURAL PLANS FOR
ADDITIONAL INFORMATION.
CONTRACTOR TO V.I.F. LOCATION OF EXISTING SPRINKLER HEADS, IF
LOCATIONS MEET NFPA 13 REQUIREMENTS, USE EXISTING LOCATION FOR NEW
UPRIGHT SPRINKLER HEAD.
EXISTING HEAT/SMOKE DETECTOR IN THIS LOCATION TO BE REMOVED AND
REPLACED WITH NEW HEAT/SMOKE DETECTOR.
THIS SPACE IS DESIGNATED AS A LIGHT HAZARD SPACE.
EXISTING HEAT/SMOKE DETECTOR IN THIS LOCATION TO REMAIN, PROTECT IN
PLACE.
NOTE: NOT ALL KEYNOTES
ARE USED ON EACH SHEET
SCALE: 1" = 20'-0"F5
FIRE PROTECTION PLAN - FIRST
LEVEL
SCALE: 1/2" = 1'-0"F2
FIRE PROTECTION - FIRST LEVEL -
RM1C-142 - NEW
SCALE: 1/4" = 1'-0"E2
FIRE PROTECTION - FIRST LEVEL -
RM1C-142/1C-143 - DEMO
UPUP
01FX402
F7
01FX402
D7
01FX402
D5
01FX402
F5
01FX402
F1
01FX402
F3
EYE EXAM
1S-280
EYE EXAM
1S-279
EYE EXAM
1S-277
OPTHALMOLOGIST
OFFICE
1S-278
HAC
1S-276
SPD
1S-270
OCULAR
PHOTOGRAPHY
1S-271
SHOWER
1S-272
EXAM RM
1S-273
EXAM RM
1S-274EYE EXAM
1S-274B
REGISTRATION
1S-268
OFFICE
1S-266
OPTOMETRY EXAM RM
1S-275A
OPTOMETRY EXAM
RMS
1S-275B
PATIENT TOILET
1S-269
EXAM OPTOMETRY
1S-267
PATIENT WAITING RM
1S-264
UTILITY
1S-265
TOILET
1S-2618
EM
PL
O
YE
E
TO
IL
ET
1S -2
EXAM OPTOMETRY
1S-261
OPTOMETRY EXAM
1S-262
TELECOM ROOM
1C-242
LOBBY
1C-241
CORRIDOR
1C-C2-1
ELEV
ELEV
MAIL RM
1C-243
OPTOMETRY OFFICE
1C-246
MECH
MAIL RM OFFICE
1C-245
REPRODUCTION RM
1C-244
C O R R
ID
O R
1S -C 2-
OPTOMETRY OFFICE
SHOP
1S-266A
RECEPT OFFICE
1N-224A
FI
LM
L A B O R A
TO
R Y
1N -2
TOILET FEMALE
1N-225
TOILET MALE
1N-227
BATH RM
PI
PE
C H A
SE
1N -2
OFFICE RADIOLOGIST
RADIOLOGIST
1N-221
OFFICE
1N-219
OFFICE RADIOLOGIST
RADIOLOGIST
1N-217
OFFICE
1N-215
ELECTRICAL
1N-206
EXAM RM
1N-222
TELEPHONE RM
1N-220A
PA
SS
A G E
1N -2
X-RAY RM CHEST RM
1N-209
ST
O R A G E R M
1N -2
MECH
1N-211
X-RAY RM
1N-213
CONTROL RM
IN-213A
TOILET
TOILET
CT SCANNER RM
1N-207
CT SCANNER RM
1N-205
EQUIP CLOSET
1N-208A
PATIENTS TOILET
1N-203
1N-201
X-RAY RM
1N-214
CONTROL RM
1N-216A
FE
M A
LE
L O C K
ER
1N -2
CONFERENCE RM
1N-212A
EMPLOYEE LOUNGE
1N-212
CORRIDOR
1N-C2-5
M A
LE
L O C K
ER
S
1N -2
DARK RM
1N-206
C O R R
ID
O R
1N -C 2-
D R
ES
SI
N G R M
1N -2
ULTRASOUND RM
1N-202
STAIR#2
EXAM RM
1S-281
STAIR #1
ACTIVE STORAGE
2C-207
DISPENSING
2C-206
FILING ASSEMBLY
2C-205
MAIL OUT
2C-205A
REPACK/PREPACK
2C-209A
PHARMACY OFFICE
2C-2128
VAULT
2C-2126A
INVEST DRUGS WORK
STORAGE SECURED
DISP FLAM
2C-2126
CORRIDOR
2C-C2-9
HAC
2C-2130
STAIR#8
STAFF TOILET
2C-2125
ELECT
2C-2124
ADMIXTURE STORAGE
2C-2123
STERILE FLUIDS OR
ADMIXTURE STORAGE
2C-214
PREP AREA
2C-215
PHARMACY STORAGE
2C-2121
DRUG PROCUREMENT
RECEIVING
2C-2120
BREAK ROOM
2C-2117
CHIEF OFFICE
2C-2118
STAIR #6
C O R R
ID
O R
2C -C 2-
STAIR#4
CORRIDOR
2C-C2-3
TELECOM ROOM
2C-2139
SECY OR WAITING
2C-2138
SECY OR WAITING
2C-2138 TO
IL
ET
2C -2
DRUG INFO OR OFFICE
2C-2138C
OFFICE
2C-2138B
TO
IL
ET
2C -2
CONSULT
2C-204
PHARMACY WAITING
2C-C2-7
PRESCRIPTION
RECEIVING
2C-204A
PHARMACY
RECEPTION
2C-223
RECEPTION
2C-222
SUPV
2C-2114
C O R R
ID
O R
2C -C 2-
ELECT
2C-2115
C O
PI
ER
A R
EA
2C -2
C O R R
ID
O R
2C -C 2-
DOCTOR OFFICE
2C2101
WAITING
2C-C2-6
ELEV
LOBBY
2C-C2-5
C O R R
ID
O R
2C -C 2-
EXAM RM
2C-2101
EXAM RM
2C-2112
EXAM RM
2C-2110
STAIR#5
EXAM RM
2C-2109
RECEPTION
2C-2103
WAITING AREA
2C-2108
SUPPLY CLOSET
CORRIDOR
2C-C2-10
A C C U M U
LA
TI
O N R M
2C -2
SUPPLY CLO
2C-2111
HAC
2C-2102B
ACCUMULATION
2C-2102A
DENTAL X-RAY
2C-2102
EXAM RM
2C-2105
DENTAL LAB
2C-2106
EXAM RM
2C-2107
EXAM RM
2C-2107A
STORAGE
2C-2106A
EXAM RM
2E-2105
READING
2E-2108 EXAM RM
2E-2109
EXAM RM
2E-2110
EXAM RM
2E-2111
NEUROLOGY CLINIC
2E-2112
STORAGE
2E-2167
EYE CLINIC OFFICE
2E-2166A
EY
E C
LI
N
IC
E
XA
M R M
2E -2
EY
E C
LI
N
IC
E
XA
M R M
2E -2
U R O
LO
G Y
EX
A M R M
2E -2
SOILED UTILITY
2E-2163
GU CLINIC EXAM RM
2E-2160
WAITING UROLOGY
2E-2162
STAFF LOCKER
2E-2159
CORRIDOR
2E-2051
C O R R
ID
O R
2E -2
CAST RM
2E-2153
CORRIDOR
2E-2048
PODIATRY EXAM RM
2E-2158
PODIATRY EXAM RM
2E-2152
PODIATRY EXAM RM
2E-2151
STAFF TOILET
2E-2157
EXAM RM
2E-2103
EXAM RM
2E-2104
TOILET
2E-2113
CORRIDOR
2E-2030
EXAM RM
2E-2115
SP
C
LI
N
IC
O
FF
IC
E
2E -2
EXAM RM
2E-2144
EXAM RM
2E-2145
PATIENTS TOILET
2E-2150
SUPPLY
2E-2146
DERMATOLOGY
OFFICE
2E-2143
SHOWER
2E-2144A
EXAM RM
2E-2136E
EXAM RM
2E-2136D
ST
O R A G E
2E -2
6CWORK AREA
CORRIDOR
2E-2045
TOILET
2E-2136B
C O R R
ID
O R
DERMATOLOGY
2E-2136
EXAM RM
2E-2136A
STAIR#2
CORRIDOR
2E-2043
C O R R
ID
O R
2E -2
CONFERENCE RM
2E-2134
EXAM RM
2E-2133
EXAM RM
2E-2132
EXAM RM
2E-2131
EXAM RM
2E-2139
C O M M U N
IC
A
TI
O N
2E -2
WAITING
2E-2040
CORRIDOR
2E-2038
WAITING
2E-2037
C O R R
ID
O R
2E -2
WAITING
2E-2128
BREAK RM
2E-2148 OFFICE
2E-2147
SP CLINIC EXAM RM
2E-2140
SP CLINIC EXAM RM
2E-2141
EXAM RM
2E-2142
EL
EC
TR
IC
A L
2E -2
CORRIDOR
2E-2052
CORRIDOR
2E-2046
C O R R
ID
O R
2E -2
PATIENTS TOILET
2E-2156
PA
TI
EN
TS
T O
IL
ET
2E -2
ST
A
FF
T O
IL
ET
2E -2
OFFICE
2E-2149
N MGR OFFICE
2E-2126
WAITING
2E-2035
RECEPTION
2E-2036
CLINIC
2E-2130
EXAM RM
2E-2129
ROOM
2E-2169
VASCULAR LAB
2E-2168
GU/NURSING CLINIC
EXAM RM
2E-2161
C O R R
ID
O R
2E -2
GU/UROLOGY
CYSTOSCOPY RM
2E-2170
CHASE
G A S
ST
O R A G E
2E -2
EXAM RM
2E-2116
CHEST CLINIC
2E-2117
CHEST CLINIC
2E-2118
CLINICAL CO ORDR
OFFICE
2E-2121
NUTRITION CLINIC
2E-2122WAITING
2E-2033
C O R R
ID
O R
2E -2
C O R R
ID
O R
2E -2
COMMUNICATION
CLOSET
2E-2176
ELEV #S1
2E-2014
ELEV #S2
2E-2015
ELEV #P1
2E-2011
ELEV #P2
2E-2012
ELEV #P3
2E-2013
CORRIDOR
2E-2034
PATIENT ELEV LOBBY
2E-2021
SVC ELEV LOBBY
2E-2056
EL
EC
TR
IC
A L
2E -2
ST
A
IR
#3
LINEN
2E-2174
STORAGE
2E-2173
CHUTE
CHUTE
R
ES
P
ST
O R A G E
2E -2
SHAFT
C O R R
ID
O R
2E -2
CHECK-IN
2E-2100
WORK RM
2E-2100A
CHECK-IN
2E-2022
CARDIOLOGY
CONFERENCE RM
2E-2101
EXAM RM
2E-2102
CHIROPRACTOR
2E-2107
EXAM RM
2E-2107A
EXAM RM
2E-2106 CORRIDOR
2E-2032
C O R R
ID
O R
2E -2
ATU
2E-2119A
ATU
2E-2119
ATU
2E-2120
ATU SUPPLY RM
2E-2120A
ELECTRICAL
2E-2123
HAC
2E-2124
C O R R
ID
O R
2E -2
CORRIDOR
2E-2028
CORRIDOR
2E-2024
CORRIDOR
2E-2025
CORRIDOR
2E-2026
W A
IT
IN
G
2E -2
CORRIDOR
2C-C2-1
STAIR#7
MECH EQUIP
2C-277
MECH EQUIP
2E-2135
TELECOM ROOM
2E-2149
ELEV
#S3
LOBBY
2C-C2-13
CORRIDOR
C2-14
11/09/2023
11/09/2023
N
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
CONSULTANT
321 4 5 6 7 8 9 10
GENERAL NOTES
KEY PLAN
KEYNOTES
2W
TRIPLE C - The A/E Group 201 E. Jefferson Street, Suite 200 Syracuse, NY 13202
MAT PERKINS
(315) 484-5958
2C 2E
STAMP
Au to de sk
D oc s:
//6
A4
-2 2-
0_
N ew in gt on _V
AM
C
_E H
R M
_I U
-1
2/
9A 4-
-7
.N ew in gt on
.E H
R M
.M
EP
.B
_0 2_
R
.rv t
-0
1-
0:
:3
01FX102
FIRE PROTECTION PLAN - SECOND LEVEL 689A4-22-700
01_02
11/09/2023 M. Perkins M. RIFFLE
ISSUED FOR
CONSTRUCTION
EHRM INFRASTRUCTURE
UPGRADES
555 Willard Avenue, Newington, CT 06111
A.
B.
CONTRACTOR SHALL PROVIDE THE FOLLOWING PRIOR TO
COMMENCEMENT OF WORK FOR REVIEW AND APPROVAL:
SHOP DRAWING IDENTIFYING MAIN PIPE SIZES AND LOCATIONS,
LOCATION OF PIPE BRACING, HANGERS AND SPRINKLER HEADS
AND DETAILS
CUT SHEETS AND SUBMITTAL FOR ALL PIPING, FITTINGS,
SPRINKLER HEADS, HANGERS AND SUPPORT ATTACHMENTS
A.
B.
C.
D.
E.
F.
G.
H.
I.
J.
K.
L.
M.
N.
O.
P.
Q.
R.
EXISTING CONDITIONS ARE BASED ON EXISTING PLANS AND FIELD VERIFICATION
WHERE FEASIBLE. ACTUAL CONDITIONS MAY DIFFER FROM THOSE INDICATED.
CONTRACTOR SHALL FIELD VERIFY IN ADVANCE THE LOCATION AND CONDITION
OF THE EXISTING SYSTEMS SHOWN TO BE MODIFIED OR REMOVED.
CONTRACTOR TO NOTIFY ARCHITECT SHOULD CONDITIONS BE FOUND TO DIFFER
SIGNIFICANTLY FROM THE CONSTRUCTION DOCUMENTS.
A DETAILED SCHEDULE, INCLUDING PROJECTED SERVICE INTERRUPTION DATES
WITH DURATIONS, AND DETAILED PHASING PLAN IS TO BE PROVIDED TO THE COR
PRIOR TO THE START OF WORK. THIS SUBMITTAL MUST BE ACCEPTED BY THE
COR PRIOR TO THE START OF WORK.
REFER TO ARCHITECTURAL DRAWINGS FOR EXACT DIMENSIONAL DATA, CEILING
HEIGHTS, AND SQUARE FOOTAGE.
CONTRACTOR SHALL COORDINATE ALL WORK WITH BUILDING OWNER AND
OTHER TRADES PRIOR TO CONSTRUCTION.
ALL PIPING TO BE ROUTED WITHIN CEILING SPACE OR CONCEALED IN FURRED
CHASES UNLESS NOTED OTHERWISE.
ALL AREAS ARE DESIGNED AS ORDINARY HAZARD GROUP 1 OCCUPANCY UNLESS
NOTED OTHERWISE ON PLAN.
ALL SPRINKLER SYSTEMS SHALL BE INSTALLED IN ACCORDANCE WITH THE 2022
NFPA 13.
ALL MATERIALS, DEVICES, HANGERS AND SUPPORTS SHALL BE NEW AND UL
LISTED FOR USE IN FIRE PROTECTION SYSTEMS.
ALL NEW SPRINKLERS SHALL BE PROVIDED WITH NEW ESCUTCHEONS TO MATCH
EXISTING BUILDING STANDARDS.
INSTALL QUICK RESPONSE SPRINKLERS (QRS) IN ALL AREAS, EXCEPT WHERE
SPECIFICALLY PROHIBITED AS DEFINED BY 2022 NFPA 13.
PIPING TO BE SCHEDULE 40 BLACK STEEL WITH CAST IRON FITTINGS.
ANY FLOOR, WALL, OR CEILING CUTTING OR FILLING THAT IS REQUIRED TO
COMPLETE THIS PROJECT, THE CONTRACTOR SHALL PATCH AND PAINT AND
RETURN TO MATCH EXISTING CONDITIONS AND FINISHES.
CONTRACTOR TO PROVIDE GALVANIC PROTECTION AS REQUIRED AT
CONNECTIONS BETWEEN ALL DISSIMILAR METALS.
CONTRACTOR TO VALIDATE AND VERIFY ALL FIRE RATED AND/OR SMOKE RATED
WALLS AND ASSEMBLIES INDICATED ON PLANS IN WORK AREA. PROVIDE ALL
PIPING PENETRATIONS OF FIRE, SMOKE AND FULL HEIGHT WALLS SHALL BE
CAULKED AIRTIGHT TO THE ADJACENT STRUCTURE BY MEANS OF U.L. APPROVED
FIREPROOF CAULKING MATERIAL.
ALL NEW PIPES TO BE CLEANED AND TESTED PRIOR TO COMMISSIONING.
THE SPRINKLER CONTRACTOR SHALL COORDINATE AND PERFORM ALL FIRE
PROTECTION WORK IN ACCORDANCE WITH VA REQUIREMENTS TO ENSURE THAT
CONTINUOUS SPRINKLER COVERAGE IS PROVIDED THROUGHOUT THE PROJECT.
THE SPRINKLER CONTRACTOR SHALL COORDINATE ALL FIRE PROTECTION
SYSTEM SHUTDOWNS, INCLUDING POINTS OF TIE IN, ETC. WITH THE VA PRIOR TO
PERFORMING WORK.
CONTRACTOR SHALL REPLACE EXISTING SPRINKLERS WITH NEW UPRIGHT
SPRINKLERS AT THE TIME OF CEILING REMOVAL TO MAINTAIN SPRINKLER
PROTECTION WITHIN THE CONSTRUCTION AREA.
CONTRACTOR SHALL REPAIR ANY DAMAGE TO THE EXISTING IRRIGATION SYSTEM
SPRINKLER HEAD LEGEND
SYM.
DEMO TYPE QUICK
RESPONSE TEMP "K" DEMO
QUANTITY
PENDENT
YES 170F 5.6UPRIGHT
YES 155F 5.6
NOTE: LEGEND INFORMATION IS SPECIFIC TO THIS SHEET ONLY
NEW
QUANTITY
SYM.
NEW
SEE
FX402
SEE
FX402
SEE
FX402
SEE
FX402
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
EXISTING SPRINKLER HEAD IN THIS LOCATION TO REMAIN, PROTECT IN PLACE.
CONTRACTOR IS RESPONSIBLE FOR MAINTAINING COMPLIANCE WITH THE 2022
NFPA 13 FOR SURROUNDING SPACING DURING AND AFTER RENOVATION.
CONTRACTOR IS RESPONSIBLE FOR FIELD VERIFYING SPRINKLER HEAD
LOCATIONS AND PIPING TO BE MODIFIED BY THE RENOVATION PRIOR TO
COMMENCING WORK.
EXISTING PENDENT SPRINKLER HEAD IN THIS LOCATION TO BE REMOVED AND
REPLACED WITH NEW UPRIGHT SPRINKLER HEAD WITH PROTECTIVE HEAD
CAGE. INSTALL SPRINKLER HEAD AND HANGERS IN ACCORDANCE WITH THE
2022 NFPA 13. SEE SHEET FX001 FOR ADDITIONAL INFORMATION.
EXISTING UPRIGHT SPRINKLER HEAD IN THIS LOCATION TO BE REMOVED AND
REPLACED WITH NEW UPRIGHT SPRINKLER HEAD WITH PROTECTIVE HEAD
CAGE. INSTALL SPRINKLER HEAD AND HANGERS IN ACCORDANCE WITH THE
2022 NFPA 13. SEE SHEET FX001 FOR ADDITIONAL INFORMATION.
NEW UPRIGHT SPRINKLER HEAD WITH PROTECTIVE HEAD CAGE. CONNECT
PIPING TO NEAREST BRANCH LINE. INSTALL SPRINKLER HEAD AND HANGERS IN
ACCORDANCE WITH THE 2022 NFPA 13. SEE SHEET FX001 FOR ADDITIONAL
INFORMATION.
NEW HEAT/SMOKE DETECTOR AND FIRE ALARM STROBE/HORN, MOUNT AND
SUPPORT FROM DECK ABOVE. COORDINATE LOCATION WITH ALL OTHER
TRADES, EXISTING CONDITIONS, AND COR. SEE ARCHITECTURAL PLANS FOR
ADDITIONAL INFORMATION.
CONTRACTOR TO V.I.F. LOCATION OF EXISTING SPRINKLER HEADS, IF
LOCATIONS MEET NFPA 13 REQUIREMENTS, USE EXISTING LOCATION FOR NEW
UPRIGHT SPRINKLER HEAD.
EXISTING HEAT/SMOKE DETECTOR IN THIS LOCATION TO BE REMOVED AND
REPLACED WITH NEW HEAT/SMOKE DETECTOR.
THIS SPACE IS DESIGNATED AS A LIGHT HAZARD SPACE.
EXISTING HEAT/SMOKE DETECTOR IN THIS LOCATION TO REMAIN, PROTECT IN
PLACE.
NOTE: NOT ALL KEYNOTES
ARE USED ON EACH SHEET
SCALE: 1" = 20'-0"F4
FIRE PROTECTION PLAN - SECOND
LEVEL
01FX403
F7
01FX403
C7
01FX403
C4
01FX403
F4
01FX403
C1
01FX403
F1
OFFICE
2C-3132
M
IR
EC
C R
ES
EA
R C H
O
FF
IC
E
2C -3
OFFICE
2C-3134
PS
Y N P R A C
TI
TI
O N
ER
O
FF
IC
E
2C -3
5 OFFICE
2C-3136
STORAGE
2C-3137
O
FF
IC
E
2C -3
PATIENTS TOILET
2C-3138A
STAFF TOILET
2C-3139A
CORRIDOR
2C-C3-8C H A
SE -
PSYCHOLOGY FELLOW
OFFICE
2C-3131
R
EC
R
EA
TI
O N
TH
ER
A
PI
ST
O
FF
IC
E
2C -3
0 OFFICE
2C-3129
STAIR #8
OFFICE
2C-3128
PATIENTS TOILET
2C-3127
OFFICE
2C-3126
EXAMINATION
2C-3125
ELECT
2C-3124
OFFICE
2C-3122
EVALUATION
C3-7
OFFICE
2C-3121
HAC
2C-3120
PSY INTERN OFFICE
2C-3119
GROUP RM-A
2C-3117
TOILET
2C-3117A
TOILET
2C-3116A
SUPPLY
2C-3118
GROUP RM -B
2C-3116
CORRIDOR
2C-3115
PSY RESIDENT
2C-3114
C O
PY
R M
2C -3
DOCTORS CHART
2C-3112
PNEUMATIC TUBE
NURSES STATION
C3-3024
O
FF
IC
E
2C -3 1B
TOILET
2C-3111A
ANTE RM
2C-3111
GROUP RM -C
2C-3110 O
FF
IC
E
2C -3
SOCIAL WORKER
2C-3108
INTERN OFFICE
2C-3107
OFFICE
2C-3106
WOMENS TOILET
2C-3100
PATIENTS TOILET
2C-3101
CLOTHING RM
2C-3102
PSY OFFICE
2C-3103
TOILET
2C-3104
MED DIRECTOR OFFICE
2C-3105
STAIR
C3-2
PATIENT ELEV LOBBY
C3-3022
LOBBY
2C-3021
ELEV
ADMIN OFFICE
2C-3147
OFFICE
2C-3139A
C O R R
ID
O R
2C -C 3-
STAFF LOCKERS AND
LOUNGE
2C-3139
STORAGE
2C-3140
OFFICE
2C-3146A
CONFERENCE RM
2C-3139
COMMUNICATION
2C-3143
STAIR#4
C O R R
ID
O R
2C -C 3-
CLOSET
CORRIDOR
2C-C3-3
ROOM
C O R R
ID
O R
2E -3
C O M M U N
IC
A
TI
O N
C
LO
SE
T
2E -3
ELEV #P1
2E-3011
ELEV #P2
2E-3012
ELEV #P3
2E-3013
ELEV #S1
2E-3014
ELEV #S2
2E-3015
STAIR#3
EL
EC
T
2E -3
CHUTE
CHUTE
STORAGE
2E-3155
VBA OFFICE
2E-3154
CHASE
COMPUTER TRAINING
RM
2E-3137
M
IL
IT
A R Y O R D
ER
O F
PU
R
PL
E H
EA
R T O
FF
IC
E
2E -3
OFFICE
2E-3136A
NATIONAL SVC
OFFICER
2E-3133A
MENS RM
2E-3135
WOMENS RM
2E-3134
SECY/WAITING
2E-3133
AMERICAN LEGION
OFFICE
2E-3132
OFFICE
2E-3132A
OFFICE
2E-3132B
UNION OFFICE
2E-3129A
UNION OFFICE
2E-3129
SECY AREA
2E-3128
NATIONAL SVC
OFFICER
2E-3128A
N A
TI
O N A L
SV
C
O
FF
IC
ER
2E -3 7A
BREAK RM
2E-3126
CT DVA OFFICE
2E-3127
SHAFT
CORRIDOR
2E-3029
LOCATING RM
2E-3125
FIRM 3 SHARED TOILET
2E-3124A
MHICM RANGE PGM
SUPV OFFICE
2E-3124
MHICM RANGE PGM
TEAM OFFICE
2E-3120
STORAGE/TOILET
2E-3119A
VOLUNTARY OFFICE
2E-3119
VO
LU
N
TA
R Y
ST
O R A G E
2E -3
A
SS
T C H
IE
F
VO
LU
N
TA
R Y O
FF
IC
E
2E -3
STORAGE
2E-3117A
COPY RM VOLUNTARY
2E-3116
TOILET
2E-3115A
VOLUNTARY OFFICE
(SECRETARY)
2E-3115
K
IT
C H
EN
V O
LU
N
TA
R Y
2E -3
H A C
2E -3
ROOM
2E-3102A
PT
2E-3102B
SVC ELEV LOBBY
2E-3039
CORRIDOR
2E-3037 SHAFT
H A C
2E -3
STORAGE
2E-3110
UNION OFFICE
2E-3111
C O R R
ID
O R
2E -3
COMPUTER TRAINING
RM
2E-3112
TELECOM ROOM
2E-3113A
CHASE
STORAGE
2E-3114
RESTROOM
2E-3122
OFFFICE
2E-3131
C O M M
2E -3
ELECT
2E-3130
STAIR#2
C O R R
ID
O R
2E -3
CORRIDOR
2E-3027
CORRIDOR
2E-3026
C O R R
ID
O R
2E -3
PT
S
TO
R A G E
2E -3 5C
ELECT
2E-3106
PT TREATMENT RM
2E-3101B
WAITING
2E-3105
PT TREATMENT RM
2E-3105A
MULTIPURPOSE
CENTER
2E-3101
REHAB MEDICINE
2E-3102
OT SKILLS
2E-3101
PT OFFICE
2E-3101D
PT OFFICE
2E-3101C
CONFERENCE RM
2E-3100
PATIENT ELEV LOBBY
2E-3021
C O R R
ID
O R
2E -3
MENS TOILET
2E-3103
WOMENS TOILET
2E-3104
RECEPTION
2E-3100A
C O R R
ID
O R
2E -3
STAIR#6
CORRIDOR
2E-3032
CORRIDOR
2E-3035
TOILET
2E-3107
OFFICE
2E-3128B
ELEV
MECH
1-345
MENTAL HEALTH
OFFICE
1-343
DIRECTOR OF HEARING
AND RECOVERY PGM
1-344
MENTAL HEALTH
OFFICE
1-342
MENTAL HEALTH
GROUP RM
1-337
MENTAL HEALTH OT
1-337A
MENTAL HEALTH
THERAPIST
1-336
MENTAL HEALTH
OFFICE
1-335
M
EN
TA
L H
EA
LT
H
N U R
SE
C A
SE
M A N A G E
1-
MENTAL HEALTH
OFFICE
1-333
MENTAL HEALTH
GROUP RM
1-339
STAIR#2
CHASE
TOILET
1-338
TOILET
1-34
ELECTRICAL
1-341
CORRIDOR
1S-C3-12
CORRIDOR
1S-C3-10
WAITING
1-C3-11
CORRIDOR
1S-C3-9
C O R R
ID
O R
1S -C 3-
W/D
1-327A
MENTAL HEALTH
OFFICE
1-327
MENTAL HEALTH DAY
RM AND DINING
1-322
ELEV LOBBY
1C-C3-6
MENTAL HEALTH
OFFICE
1-323
ELEV
ELEV
TELECOM ROOM
1-324
STAIR#1
MENTAL HEALTH
OFFICE
1-321
TOILET
1-320A
MENTAL HEALTH
OFFICE
1-326
MENTAL HEALTH
OFFICE
1-328
MENTAL HEALTH
OFFICE
1-329
MENTAL HEALTH
OFFICE
1-331
MENTAL HEALTH
OFFICE
1-330
MENTAL HEALTH
OFFICE
1-332
MENTAL HEALTH
OFFICE
1-319
MENTAL HEALTH
OFFICE
1-320
MENTAL HEALTH
OFFICE
1-318
MENTAL HEALTH
OFFICE
1-315
MENTAL HEALTH
OFFICE
1-313
MENTAL HEALTH
OFFICE
1-309
MENTAL HEALTH
OFFICE
1-310
MENTAL HEALTH
OFFICE
1-312
STORAGE
1-314
MENTAL HEALTH EXAM
RM
1-316
HAC
1-317
TO
IL
ET
1-
ELECTRICAL
1-310A
COMMUNICATION
1-304A
GROUP RM-B
1-304
RECEPTION MENTAL
HEALTH
1-C3-5
C O R R
ID
O R
1N -C 3-
WAITING RM
1-302
DR OFFICES
1-300
MENTAL HEALTH
OFFICE
1-301
GROUP RM-A
1-303
CHASE
CHASE
ROOM
1N-C3-3
CORRIDOR
1N-C3-4
TOILET RM
1-305
CHASE
DIRECTOR MENTAL
HEALTH
1-306
TOILET
1-306A
COPY RM
1-308
STORAGE RM
1-307A
MENTAL HEALTH
OFFICE
1-307
NATIONAL SVC
OFFICER
2E-3127B
TELECOM ROOM
2C-3140A
COMMUNICATION
1-325
11/09/2023
11/09/2023
N
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
CONSULTANT
321 4 5 6 7 8 9 10
GENERAL NOTES
KEY PLAN
KEYNOTES
2W
TRIPLE C - The A/E Group 201 E. Jefferson Street, Suite 200 Syracuse, NY 13202
MAT PERKINS
(315) 484-5958
2C 2E
STAMP
Au to de sk
D oc s:
//6
A4
-2 2-
0_
N ew in gt on _V
AM
C
_E H
R M
_I U
-1
2/
9A 4-
-7
.N ew in gt on
.E H
R M
.M
EP
.B
_0 2_
R
.rv t
-0
1-
0:
:4
01FX103
FIRE PROTECTION PLAN - THIRD LEVEL 689A4-22-700
01_02
11/09/2023 M. Perkins M. RIFFLE
ISSUED FOR
CONSTRUCTION
EHRM INFRASTRUCTURE
UPGRADES
555 Willard Avenue, Newington, CT 06111
A.
B.
CONTRACTOR SHALL PROVIDE THE FOLLOWING PRIOR TO
COMMENCEMENT OF WORK FOR REVIEW AND APPROVAL:
SHOP DRAWING IDENTIFYING MAIN PIPE SIZES AND LOCATIONS,
LOCATION OF PIPE BRACING, HANGERS AND SPRINKLER HEADS
AND DETAILS
CUT SHEETS AND SUBMITTAL FOR ALL PIPING, FITTINGS,
SPRINKLER HEADS, HANGERS AND SUPPORT ATTACHMENTS
A.
B.
C.
D.
E.
F.
G.
H.
I.
J.
K.
L.
M.
N.
O.
P.
Q.
R.
EXISTING CONDITIONS ARE BASED ON EXISTING PLANS AND FIELD VERIFICATION
WHERE FEASIBLE. ACTUAL CONDITIONS MAY DIFFER FROM THOSE INDICATED.
CONTRACTOR SHALL FIELD VERIFY IN ADVANCE THE LOCATION AND CONDITION
OF THE EXISTING SYSTEMS SHOWN TO BE MODIFIED OR REMOVED.
CONTRACTOR TO NOTIFY ARCHITECT SHOULD CONDITIONS BE FOUND TO DIFFER
SIGNIFICANTLY FROM THE CONSTRUCTION DOCUMENTS.
A DETAILED SCHEDULE, INCLUDING PROJECTED SERVICE INTERRUPTION DATES
WITH DURATIONS, AND DETAILED PHASING PLAN IS TO BE PROVIDED TO THE COR
PRIOR TO THE START OF WORK. THIS SUBMITTAL MUST BE ACCEPTED BY THE
COR PRIOR TO THE START OF WORK.
REFER TO ARCHITECTURAL DRAWINGS FOR EXACT DIMENSIONAL DATA, CEILING
HEIGHTS, AND SQUARE FOOTAGE.
CONTRACTOR SHALL COORDINATE ALL WORK WITH BUILDING OWNER AND
OTHER TRADES PRIOR TO CONSTRUCTION.
ALL PIPING TO BE ROUTED WITHIN CEILING SPACE OR CONCEALED IN FURRED
CHASES UNLESS NOTED OTHERWISE.
ALL AREAS ARE DESIGNED AS ORDINARY HAZARD GROUP 1 OCCUPANCY UNLESS
NOTED OTHERWISE ON PLAN.
ALL SPRINKLER SYSTEMS SHALL BE INSTALLED IN ACCORDANCE WITH THE 2022
NFPA 13.
ALL MATERIALS, DEVICES, HANGERS AND SUPPORTS SHALL BE NEW AND UL
LISTED FOR USE IN FIRE PROTECTION SYSTEMS.
ALL NEW SPRINKLERS SHALL BE PROVIDED WITH NEW ESCUTCHEONS TO MATCH
EXISTING BUILDING STANDARDS.
INSTALL QUICK RESPONSE SPRINKLERS (QRS) IN ALL AREAS, EXCEPT WHERE
SPECIFICALLY PROHIBITED AS DEFINED BY 2022 NFPA 13.
PIPING TO BE SCHEDULE 40 BLACK STEEL WITH CAST IRON FITTINGS.
ANY FLOOR, WALL, OR CEILING CUTTING OR FILLING THAT IS REQUIRED TO
COMPLETE THIS PROJECT, THE CONTRACTOR SHALL PATCH AND PAINT AND
RETURN TO MATCH EXISTING CONDITIONS AND FINISHES.
CONTRACTOR TO PROVIDE GALVANIC PROTECTION AS REQUIRED AT
CONNECTIONS BETWEEN ALL DISSIMILAR METALS.
CONTRACTOR TO VALIDATE AND VERIFY ALL FIRE RATED AND/OR SMOKE RATED
WALLS AND ASSEMBLIES INDICATED ON PLANS IN WORK AREA. PROVIDE ALL
PIPING PENETRATIONS OF FIRE, SMOKE AND FULL HEIGHT WALLS SHALL BE
CAULKED AIRTIGHT TO THE ADJACENT STRUCTURE BY MEANS OF U.L. APPROVED
FIREPROOF CAULKING MATERIAL.
ALL NEW PIPES TO BE CLEANED AND TESTED PRIOR TO COMMISSIONING.
THE SPRINKLER CONTRACTOR SHALL COORDINATE AND PERFORM ALL FIRE
PROTECTION WORK IN ACCORDANCE WITH VA REQUIREMENTS TO ENSURE THAT
CONTINUOUS SPRINKLER COVERAGE IS PROVIDED THROUGHOUT THE PROJECT.
THE SPRINKLER CONTRACTOR SHALL COORDINATE ALL FIRE PROTECTION
SYSTEM SHUTDOWNS, INCLUDING POINTS OF TIE IN, ETC. WITH THE VA PRIOR TO
PERFORMING WORK.
CONTRACTOR SHALL REPLACE EXISTING SPRINKLERS WITH NEW UPRIGHT
SPRINKLERS AT THE TIME OF CEILING REMOVAL TO MAINTAIN SPRINKLER
PROTECTION WITHIN THE CONSTRUCTION AREA.
CONTRACTOR SHALL REPAIR ANY DAMAGE TO THE EXISTING IRRIGATION SYSTEM
SPRINKLER HEAD LEGEND
SYM.
DEMO TYPE QUICK
RESPONSE TEMP "K" DEMO
QUANTITY
PENDENT
YES 170F 5.6UPRIGHT
YES 155F 5.6
NOTE: LEGEND INFORMATION IS SPECIFIC TO THIS SHEET ONLY
NEW
QUANTITY
SYM.
NEW
SEE
FX403
SEE
FX403
SEE
FX403
SEE
FX403
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
EXISTING SPRINKLER HEAD IN THIS LOCATION TO REMAIN, PROTECT IN PLACE.
CONTRACTOR IS RESPONSIBLE FOR MAINTAINING COMPLIANCE WITH THE 2022
NFPA 13 FOR SURROUNDING SPACING DURING AND AFTER RENOVATION.
CONTRACTOR IS RESPONSIBLE FOR FIELD VERIFYING SPRINKLER HEAD
LOCATIONS AND PIPING TO BE MODIFIED BY THE RENOVATION PRIOR TO
COMMENCING WORK.
EXISTING PENDENT SPRINKLER HEAD IN THIS LOCATION TO BE REMOVED AND
REPLACED WITH NEW UPRIGHT SPRINKLER HEAD WITH PROTECTIVE HEAD
CAGE. INSTALL SPRINKLER HEAD AND HANGERS IN ACCORDANCE WITH THE
2022 NFPA 13. SEE SHEET FX001 FOR ADDITIONAL INFORMATION.
EXISTING UPRIGHT SPRINKLER HEAD IN THIS LOCATION TO BE REMOVED AND
REPLACED WITH NEW UPRIGHT SPRINKLER HEAD WITH PROTECTIVE HEAD
CAGE. INSTALL SPRINKLER HEAD AND HANGERS IN ACCORDANCE WITH THE
2022 NFPA 13. SEE SHEET FX001 FOR ADDITIONAL INFORMATION.
NEW UPRIGHT SPRINKLER HEAD WITH PROTECTIVE HEAD CAGE. CONNECT
PIPING TO NEAREST BRANCH LINE. INSTALL SPRINKLER HEAD AND HANGERS IN
ACCORDANCE WITH THE 2022 NFPA 13. SEE SHEET FX001 FOR ADDITIONAL
INFORMATION.
NEW HEAT/SMOKE DETECTOR AND FIRE ALARM STROBE/HORN, MOUNT AND
SUPPORT FROM DECK ABOVE. COORDINATE LOCATION WITH ALL OTHER
TRADES, EXISTING CONDITIONS, AND COR. SEE ARCHITECTURAL PLANS FOR
ADDITIONAL INFORMATION.
CONTRACTOR TO V.I.F. LOCATION OF EXISTING SPRINKLER HEADS, IF
LOCATIONS MEET NFPA 13 REQUIREMENTS, USE EXISTING LOCATION FOR NEW
UPRIGHT SPRINKLER HEAD.
EXISTING HEAT/SMOKE DETECTOR IN THIS LOCATION TO BE REMOVED AND
REPLACED WITH NEW HEAT/SMOKE DETECTOR.
THIS SPACE IS DESIGNATED AS A LIGHT HAZARD SPACE.
EXISTING HEAT/SMOKE DETECTOR IN THIS LOCATION TO REMAIN, PROTECT…