Attachment - 07 Mechanical Drawings_100percent Bid Docs.pdf

PDF 6 MB Posted

Attached to
Z2DA--EHRM Bonham, TX Construction 549A4-21-700 EHRM Construction (VA-23-00092679)
Solicitation number
36C77624B0007_1
Issued by

About this file

This document package includes mechanical drawings and plans for infrastructure upgrades at the Bonham VA Medical Center in Bonham, Texas. The drawings depict proposed HVAC system replacements and upgrades in multiple buildings on site, including new ductless split systems, thermostats, and condensing units on building roofs. Enlarged plans provide additional details on specific room layouts and equipment installations. The federal solicitation involves construction services for HVAC and related mechanical work.

View the file

Other files

File Type Posted
Attachment 56 - Abstract of Bids OF 1419 - CONST-Bonham - Signed.pdf PDF
Attachment 57 - Abstract of Bids OF 1419 A - CONST-Bonham.pdf PDF
36C77624B0007 0012.docx DOCX document
Attachment- 54 Sheet GS020 DETAILS.pdf PDF
Attachment- 53 Sheet GS019 EROSION CONTROL DETAILS.pdf PDF
Attachment- 51 TR Matrix Bonham.pdf PDF
Attachment- 55 Solicitation-RFIs-Tech Responses 36C77624B0007.pdf PDF
Attachment- 52 Hydrology Map.pdf PDF
36C77624B0007 0011.pdf PDF
36C77624B0007 0010.pdf PDF
36C77624B0007 0009.pdf PDF
Att 50 CLARIFICATION of Site Visit-Duct banks not available for use.pdf PDF
36C77624B0007 0008.pdf PDF
36C77624B0007 0007.docx DOCX document
Attachment - 49 S04-sign in sheet-pg 1 Site Visit Bonham TX 1.9.24.pdf PDF
36C77624B0007 0006.docx DOCX document
36C77624B0007 0005.pdf PDF
Attachment - 48 S04-sign in sheet Site Visit Bonham TX 1.9.24.pdf PDF
Attachment - 47 Clarifications-Additional Technical Questions.pdf PDF
36C77624B0007 0004.pdf PDF
Attachment - 46 Answers to Solicitation-RFIs-MISSING SECTION-36C77624B0007_1.pdf PDF
36C77624B0007 0003.pdf PDF
Attachment- 29 Bonham VA - Geotech Rpt 3-30-16-For Soil.pdf PDF
Attachment- 35 01 Bonham EHRM- Narrative.pdf PDF
Attachment- 36 01 Environmental Narrative.pdf PDF
Attachment- 44 Station Pictures for electrical.pdf PDF
Attachment- 28 Bonham EHRM- ICRA Form.pdf PDF
Attachment- 41 07 Electrical Narrative.pdf PDF
Attachment- 30 SPCC-PIPP Plan VANTHCS_Bonham.pdf PDF
Attachment- 38 03 Structural Narrative.pdf PDF
Attachment- 27 Answers to Solicitation-RFIs-36C77624B0007_1.pdf PDF
Attachment- 42 08 Telecom Narrative.pdf PDF
Attachment- 43 09 Security Narrative.pdf PDF
36C77624B0007 0002.pdf PDF
Attachment- 37 02 Civil Narrative.pdf PDF
Attachment- 32 V2 549A4-21-700 100 Bid Document Specifications.pdf PDF
Attachment- 45 IT Closet Proposed lay down.pdf PDF
Attachment- 39 05 Fire Protection Narrative.pdf PDF
Attachment- 34 00 General Narrative.pdf PDF
Attachment- 33 AE Physical Security Risk Mitigation Design Guidance.pdf PDF
Attachment- 31 site plan fiber runs Bonham.pdf PDF
Attachment- 40 06 Mechanical Narrative.pdf PDF
36C77624B0007 0001.pdf PDF
36C77624B0007_1-tech questions date updated.pdf PDF
36C77624B0007_1.pdf PDF
Attachment - 13 Asbestos 3_ VA Checklist_Environ.pdf PDF
Attachment - 03 Civil Drawings_100percent Bid Docs.pdf PDF
Attachment - 24 Limitations on Subcontracting - Construction.pdf PDF
Attachment - 16 CABINET DIMENSIONAL DATA.pdf PDF
Attachment - 05 Architectural Drawings_100percent Bid Docs.pdf PDF
Show 40 more

Latest 50 of 70 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ABBREVIATIONS

HVAC PIPING TYPES

GENERAL DUCT SYMBOLS

A/E ARCHITECT / ENGINEER

AAHX AIR TO AIR HEAT EXCHANGER

AB AIR BLENDER

AAV AUTOMATIC AIR VENT

ACC AIR COOLED CONDENSER

ACU AIR CONDITIONING UNIT

AF AFTER FILTER

AFCV AIR FLOW CONTROL VALVE

AFF ABOVE FINISHED FLOOR

AFW AIR FOIL WHEEL (FAN)

AHU AIR-HANDLING UNIT

AMP AMPERAGE

AP ACCESS PANEL

APD AIR PRESSURE DROP

ARI AIR CONDITIONING AND REFRIGERATION

INSTITUTE

AS AIR SEPARATOR

ASME AMERICAN SOCIETY OF MECHANICAL

ENGINEERS

AW AIR WASHER

AXF AXIAL FLOW

B

B BOILER

BD BUTTERFLY DAMPER

BDD BACKDRAFT DAMPER

BFP BACKFLOW PREVENTER

BHP BRAKE HORSEPOWER

BHX BOILER BLOWDOWN HEAT EXCHANGER

BIW BACKWARD INCLINED WHEEL (FAN)

BSC BIOLOGICAL SAFETY CABINETS

BT BLOWOFF TANK

BTU BRITISH THERMAL UNIT

BTUH BRITISH THERMAL UNIT PER HOUR

C

C CENTIGRADE (CELSIUS)

CC COOLING COIL

CCD COOLING COIL CONDENSATE DRAIN

CENT CENTRIFUGAL

CFH CUBIC FEET PER HOUR

CFM CUBIC FEET PER MINUTE

CFT CUBIC FEET

CFP CHEMICAL FEED PUMP

CH CHILLER

CHP CHILLED WATER PUMP

CHW CHILLER WATER

CHR CHILLED WATER RETURN

CHS CHILLED WATER SUPPLY

CI CAST IRON

CM CUBIC METER

CM/S CUBIC METER PER SECOND

CO CARBON MONOXIDE

CO2 CARBON DIOXIDE

COMP COMPRESSOR UNIT

COP COEFFICIENT OF PERFORMANCE

CP CONDENSATE PUMP

CS CONDENSATE STORAGE TANK

CSG CLEAN STEAM GENERATOR

CT COOLING TOWER

CU CONDENSING UNIT

CUH CABINET UNIT HEATER

CV CONSTANT VOLUME

CW COLD WATER (POTABLE)

CC CHILLED WATER COOLING COIL

CWP CONDENSER WATER PUMP

CWR CONDENSER WATER RETURN

CWS CONDENSER WATER SUPPLY

A

F

F FAHRENHEIT

F&T FLOAT AND THERMOSTATIC

FA FREE AREA

FC FLEXIBLE CONNECTION

FCU FAN COIL UNIT

FCUC FAN COIL UNIT COOLING ONLY

FCUH FAN COIL UNIT HEATING ONLY

FCW FORWARD CURVED WHEEL (FAN)

E

EA EXHAUST AIR

EAT ENTERING AIR TEMPERATURE

EC EVAPORATIVE COOLER

ECC ENGINEERING CONTROL CENTER

ECU EVAPORATIVE CONDENSER UNIT

EDH ELECTRIC DUCT HEATER

EER ENERGY EFFICIENCY RATIO

EF EXHAUST FAN

EGS EMERGENCY GAS SHUTOFF

EGT ENTERING GLYCOL TEMPERATURE

EH EXHAUST HOOD

EJ EXPANSION JOINT

EMD END OF MAIN DRIP (STEAM)

ENT ENTERING

ERC ELECTRIC REHEAT COIL

ERP ELECTRIC RADIANT PANEL

ESP EXTERNAL STATIC PRESSURE

ET EXPANSION TANK

ETO ETHYLENE OXIDE

ETR EXISTING TO REMAIN

EUH ELECTRIC UNIT HEATER

EWC EVAPORATIVE WATER COOLER

EWT ENTERING WATER TEMPERATURE

EX. EXISTING

D

DB DECIBELS

Db DRY-BULB TEMPERATURE

DDC DIRECT DIGITAL CONTROLS

DEG DEGREE

DIA DIAMETER

DIW DEIONIZED WATER

DP DEW POINT TEMPERATURE

DPA DIFFERENTIAL PRESSURE ASSEMBLY

DPS DIFFERENTIAL PRESSURE SENSOR

DX DIRECT EXPANSION

FD FIRE DAMPER

FF FINAL FILTER

FHX FLUE GAS/FEEDWATER HEAT EXCHANGER

FM FLOW METER

FOP FUEL OIL PUMP

FOT FUEL OIL TANK

FOHX FUEL OIL HEAT EXCHANGER

FPM FEET PER MINUTE

FPS FEET PER SECOND

FPTU FAN POWERED TERMINAL UNIT

FRP FIBER REINFORCED POLYESTER

FS FLOW SWITCH

FSTAT FREEZESTAT

FT FEET

FT-LB FOOT-POUND

FTR FIN TUBE RADIATION

FV FACE VELOCITY

FSD COMBINATION FIRE / SMOKE DAMPER

G

GA GAUGE

GAL GALLONS

GH GRAVITY HOOD

GPD GALLONS PER DAY

GPH GALLONS PER HOUR

GPM GALLONS PER MINUTE

GPR GAS PRESSURE REGULATOR

GS GALVANIZED STEEL

K kg KILOGRAM kg/HR KILOGRAM PER HOUR kPa KILOPASCAL kW KILOWATT kWh KILOWATT HOUR

J

J INTENTIONALLY LEFT BLANK

I/O INPUT/OUTPUT

IAQ INDOOR AIR QUALITY

IBT INVERTED BUCKET TRAP

ICF IN-LINE CENTRIFUGAL FAN

ID INSIDE DIAMETER

IFB INTEGRAL FACE AND BYPASS

IN INCHES

IN HG INCHES OF MERCURY

IN WC INCH WATER COLUMN

IN WG INCH WATER GAUGE

IN-LB INCH-POUND

IPLV INTEGRATED PART LOAD VALUE

IRH INFRARED HEATER

IS INSECT SCREEN

IU INDUCTION UNIT

IV INLET VANES

H

HU HUMIDIFIER

H&CW HOT & COLD WATER

HAC HOUSEKEEPING AID CLOSET

HB HOSE BIBB

HC HEATING COIL

HD HEAD

HOA HAND/OFF/AUTOMATIC

HP HEAT PUMP

HP HORSEPOWER

HPDT HIGH PRESSURE DRIP TRAP

HPC HIGH PRESSURE STEAM CONDENSATE RETURN

HPS HIGH PRESSURE STEAM (61-300 PSIG)

HRC HEAT RECOVERY COIL

HRD HEAT RECOVERY DEVICE

HRP HYDRONIC RADIANT (CEILING) PANEL

HRW HEAT RECOVERY WHEEL

HSTAT HUMIDISTAT

HTM HUMIDIFIER TERMINAL

HUM HUMIDIFIER UNIT MOUNTED

HVU HEATING AND VENTILATING UNIT

HW HOT WATER

HC HOT WATER HEATING COIL

HHP HEATING HOT WATER PUMP

HHR HEATING HOT WATER RETURN

HHS HEATING HOT WATER SUPPLY

HHUH HOT WATER UNIT HEATER

HX HEAT EXCHANGER

HZ HERTZ

I

L

L LITER

L/h LITERS PER HOUR (OR LITERS/HOUR) L/m LITERS PER MINUTE (OR LITERS/MINUTE) L/s LITERS PER SECOND (OR LITERS/SECOND)

LAT LEAVING AIR TEMPERATURE

LBS/HR POUNDS PER HOUR

LF LINEAR FOOT (FEET)

LGT LEAVING GLYCOL TEMPERATURE

LH LATENT HEAT

LPG LIQUID PROPANE GAS

LPC LOW PRESSURE STEAM CONDENSATE RETURN

CLPC LOW PRESSURE STEAM CONDENSATE (CLEAN)

LLHX LIQUID TO LIQUID HEAT EXCHANGER

LPS LOW PRESSURE STEAM (0-15 PSIG)

CLPS LOW PRESSURE STEAM (CLEAN)

LSD LINEAR SLOT DIFFUSER

LTCP LOCAL TEMPERATURE CONTROL PANEL

LVG LEAVING

LVR LOUVER

LWT LEAVING WATER TEMPERATURE

NOM NOMINAL

NPLV NON-STANDARD PART LOAD VALUE

NPSH NET POSITIVE SUCTION HEAD

NTS NOT TO SCALE

N

NA NOT APPLICABLE

NC NOISE CRITERIA

NG NATURAL GAS

NGFM NATURAL GAS FLOWMETER

NOAA NATIONAL OCEANIC & ATMOSPHERIC

ADMINISTRATION

M

M METER, SI UNIT

M/s METERS PER SECOND

(OR METERS/SECOND)

MA MIXED AIR

MAT MIXED AIR TEMPERATURE

MAU MAKE-UP AIR UNIT

MAV MANUAL AIR VENT

MAX MAXIMUM

MB MIXING BOX

MBH 1000 BTUH

MCA MINIMUM BRANCH CIRCUIT AMPACITY

MERV MINIMUM EFFICIENCY REPORTING VALUE

MH MANHOLE

MHP MOTOR HORSEPOWER

MIN MINIMUM

MM MILLIMETER

MOV MOTOR OPERATED VALVE

MPC MEDIUM PRESSURE STEAM CONDENSATE

RETURN

MPS MEDIUM PRESSURE STEAM (16-60 PSIG)

MTD MEAN TEMPERATURE DIFFERENCE

MVD MANUAL VOLUME DAMPER

MZ MULTI-ZONE

P

P PUMP

PA PASCAL

PC PUMPED CONDENSATE

PCF POUNDS PER CUBIC FOOT (FEET)

PD PRESSURE DROP

PF PRE-FILTER

PG PRESSURE GAGE

PGW PROPYLENE GLYCOL-WATER (SOLUTION)

PHC PREHEAT COIL

PPM PARTS PER MILLION

PRS PRESSURE REGULATING (VALVE) STATION

PRV PRESSURE REGULATING VALVE

PSI POUNDS PER SQUARE INCH

PSIA POUNDS PER SQUARE INCH – ABSOLUTE

PSIG POUNDS PER SQUARE INCH – GAGE

PSS PRIMARY SECONDARY SYSTEM

PSV PRESSURE SAFETY VALVE

PTAC PACKAGED TERMINAL AIR CONDITIONER

O

OA OUTSIDE AIR

OAI OUTSIDE AIR INTAKE

OD OUTSIDE DIAMETER

OFM OIL FLOWMETER

OSD ORGANIC SOIL FILTER

Q

Q INTENTIONALLY LEFT BLANK

T&PCV TEMPERATURE AND PRESSURE

CONTROL VALVE

TAB TESTING, ADJUSTING, BALANCE

TD TEMPERATURE DIFFERENCE

TDH TOTAL DYNAMIC HEAD

TDS TOTAL DISSOLVED SOLIDS

TG TRANSFER GRILLE

TP TRAP

TSP TOTAL STATIC PRESSURE

TSTAT THERMOSTAT

TU TERMINAL UNIT

TWU THRU-WALL UNIT

SA SUPPLY AIR

SAD SOUND ATTENUATING DEVICE

SAT SUPPLY AIR TEMPERATURE

SC SHADING COEFFICIENT

SCFM STANDARD CUBIC FEET PER MINUTE

SCR SILICON CONTROLLED RECTIFIER

DSD DUCT SMOKE DETECTOR

SD SMOKE DAMPER

SEN SENSIBLE HEAT

SF SUPPLY FAN

SH STEAM HUMIDIFIER

SHC STEAM HEATING COIL

SI SQUARE INCHES

SP STATIC PRESSURE

SP GR SPECIFIC GRAVITY

SPS STATIC PRESSURE SENSOR

SQ FT SQUARE FOOT (FEET)

SS STAINLESS STEEL

SSHX STEAM TO STEAM HEAT EXCHANGER

SSR SOLID SEPARATOR

ST STEAM TRAP

SUH STEAM UNIT HEATER

SVS STEAM VENT SILENCER

SWHX STEAM TO WATER HEAT EXCHANGER

R

R/E RETURN OR EXHAUST

RA RETURN AIR

RAD REFRIGERANT AIR DRYER

RAF RADIO FREQUENCY

RAHX ROTARY AIR HEAT EXCHANGER

RAT RETURN AIR TEMPERATURE

RCCH REMOTE CONDENSER CHILLER

RCU RECIPROCATING CHILLER UNIT

RD REFRIGERANT DISCHARGE

REA RELIEF AIR

RF RETURN FAN

RH RELATIVE HUMIDITY

RHC REHEAT COIL

RHG REFRIGERANT HOT GAS

RL REFRIGERANT LIQUID LINE

RLA RUN LOAD AMPERE

RO REVERSE OSMOSIS

RPM REVOLUTIONS PER MINUTE

RS REFRIGERANT SUCTION

RTU ROOF TOP UNIT

RV RELIEF VALVE

T

UC UNDER CUT

UH UNIT HEATER

UL UNDERWRITERS LABORATORY

URV UPBLAST UNIT VENTILATOR

U

X INTENTIONALLY LEFT BLANK

W

W WATTS

WAG WASTE ANESTHESIA GAS

Wb WET-BULB (TEMPERATURE)

WC WATER COOLED

WCCH WATER COOLED CHILLER

WCCU WATER COOLED CONDENSING UNIT

WCHP WATER COOLED HEAT PUMPS

WCPU WATER COOLED PACKAGED UNIT

WF WATER FILTER

WFM WATER FLOWMETER

WG WATER GAGE

WPD WATER SIDE PRESSURE DROP

V VALVE

VAF VANE-AXIAL FAN

VAV VARIABLE AIR VOLUME

VD VOLUME DAMPER (MANUAL OPPOSED BLADE)

VFD VARIABLE FREQUENCY DRIVE

VI VIBRATION ISOLATOR

VIV VARIABLE INLET VANES

VP VACUUM PUMP

VPS VARIABLE PRIMARY SYSTEM

VR VACUUM (STEAM CONDENSATE) RETURN

VSD VARIABLE SPEED DRIVE

VUH VERTICAL UNIT HEATER

X

V

GENERAL NOTES:

A. MECHANICAL PLANS AND SECTIONS ARE INTENDED TO ACCURATELY ILLUSTRATE THE

SCOPE OF WORK BUT ARE STILL DIAGRAMMATIC IN NATURE.

B. MECHANICAL DRAWINGS DO NOT SHOW ALL ACCESSORIES TO BE INSTALLED. THE

CONTRACTOR IS RESPONSIBLE FOR ENSURING THAT ALL SYSTEMS ARE FULLY

FUNCTIONAL AND COMPLIANT WITH APPLICABLE CODES.

C. THE EXISTING CONDITIONS DEPICTED IN THESE PLANS ARE BASED ON AS-BUILT

DOCUMENTATION AND INFORMATION OBTAINED FROM FIELD SURVEYS AND ARE AS

ACCURATE AS POSSIBLE. DUE TO OBSTRUCTIONS, CEILINGS, ETC., NOT ALL CONDITIONS

COULD BE VERIFIED. THE CONTRACTOR SHALL SURVEY THE SITE PRIOR TO BID AND

NOTIFY THE ARCHITECT/ENGINEER OF ANY CONFLICTS, OBSTRUCTIONS, OR

INCONSISTENCIES PREVENTING INSTALLATION OF THE MECHANICAL SYSTEM.

D. ALL EXPOSED UNINSULATED PIPING SHALL BE PAINTED PER THE SPECIFICATION SECTION

"PAINTING".

E. COORDINATE FAN COIL (FCU) AND TERMINAL UNIT (TU/VAV/CV) REHEAT COIL RIGHT OR

LEFT HAND COIL CONNECTIONS WITH PIPING PLANS.

F. ALL FLUE AND COMBUSTION AIR PIPING FROM GAS-FIRED EQUIPMENT SHALL BE SIZED BY

THE GAS-FIRED EQUIPMENT MANUFACTURER BASED ON THE SPECIFIC PIPE ROUTING AND

ELEVATIONS FOR THIS PROJECT. REFER TO MANUFACTURERS INSTALLATION MANUAL AND

LOCAL CODE REQUIREMENTS FOR REQUIRED FLUE AND COMBUSTION AIR PIPING

MATERIALS.

G. PROVIDE VIBRATION ISOLATION FOR ALL MECHANICAL EQUIPMENT TO PREVENT

TRANSMISSION OF VIBRATION TO BUILDING STRUCTURE.

H. PROVIDE VIBRATION ISOLATORS FOR ALL PIPING SUPPORTS CONNECTED TO AND WITHIN

50' OF ISOLATED EQUIPMENT (EXCEPT AT BASE ELBOW SUPPORTS AND ANCHOR POINTS)

THROUGHOUT MECHANICAL EQUIPMENT ROOMS. DO THE SAME FOR SUPPORTS OF STEAM

MAINS WITHIN 50' OF BOILER OR PRESSURE REDUCING VALVES.

I. COORDINATE CONSTRUCTION OF ALL MECHANICAL WORK WITH ARCHITECTURAL,

STRUCTURAL, CIVIL, ELECTRICAL WORK, ETC., SHOWN ON OTHER CONTRACT DOCUMENT

DRAWINGS.

J. MAINTAIN A MINIMUM OF 6′-8″ CLEARANCE TO UNDERSIDE OF PIPES, DUCTS, CONDUITS,

SUSPENDED EQUIPMENT, ETC., THROUGHOUT ACCESS ROUTES IN MECHANICAL ROOMS.

K. ALL TESTS SHALL BE COMPLETED BEFORE ANY MECHANICAL EQUIPMENT OR PIPING

INSULATION IS APPLIED.

L. LOCATE ALL TEMPERATURE, PRESSURE, AND FLOW MEASURING DEVICES IN ACCESSIBLE

LOCATIONS WITH STRAIGHT SECTION OF PIPE OR DUCT UP AND DOWNSTREAM AS

RECOMMENDED BY THE MANUFACTURER FOR GOOD ACCURACY.

M. COORDINATE ALL EQUIPMENT CONNECTIONS WITH MANUFACTURERS CERTIFIED

DRAWINGS. COORDINATE AND PROVIDE ALL DUCT AND PIPING TRANSITIONS REQUIRED

FOR FINAL EQUIPMENT CONNECTIONS TO FURNISHED EQUIPMENT. FIELD VERIFY AND

COORDINATE ALL DUCT AND PIPING DIMENSIONS BEFORE FABRICATION.

CWR

CWS

CD

LPC

LPS

MPC

MPS

HPC

HPS

CONDENSATE DRAIN

CONDENSER WATER SUPPLY

CONDENSER WATER RETURN

HIGH PRESSURE STEAM CONDENSATE

HIGH PRESSURE STEAM SUPPLY

MEDIUM PRESSURE STEAM CONDENSATE

MEDIUM PRESSURE STEAM SUPPLY

LOW PRESSURE STEAM CONDENSATE

LOW PRESSURE STEAM SUPPLY

VACUUM RETURN

FEEDWATER PUMP DISCHARGE

FEEDWATER PUMP SUCTION

VR

CONTINUOUS BLOWDOWN

CHEMICAL FEED

BOILER BLOWOFF BO

CF

CBD

FWPD

FWPS

A. PROVIDE ALL MATERIALS AND EQUIPMENT AND PERFORM ALL LABOR REQUIRED TO

INSTALL COMPLETE AND OPERABLE PIPING SYSTEMS AS INDICATED ON THE DRAWINGS, AS

SPECIFIED AND AS REQUIRED BY CODE.

B. ELEVATIONS AS SHOWN ON THE DRAWINGS ARE TO THE CENTERLINE OF ALL PRESSURE

PIPING AND TO THE INVERT OF ALL GRAVITY PIPING.

C. MAINTAIN A MINIMUM OF 3′-6″ OF GROUND COVER OVER ALL UNDERGROUND HVAC PIPING

(EDIT DEPTH OF GROUND COVER TO SUIT FROST LINE DEPTH AND PROJECT

REQUIREMENTS).

D. UNLESS OTHERWISE NOTED, ALL CHILLED WATER AND HEATING WATER PIPING SHALL BE

3/4" SIZE (EDIT SYSTEM TYPE OR PIPE SIZE TO SUIT PROJECT REQUIREMENTS).

E. PROVIDE AN AIR VENT AT THE HIGH POINT OF EACH DROP IN THE HEATING WATER, CHILLED

WATER, AND OTHER CLOSED WATER PIPING SYSTEMS (EDIT SYSTEM TYPES TO SUIT

PROJECT REQUIREMENTS). ALL PIPING SHALL GRADE TO LOW POINTS. PROVIDE HOSE END

DRAIN VALVES AT THE BOTTOM OF ALL RISERS AND LOW POINTS.

F. UNLESS OTHERWISE NOTED, ALL PIPING IS OVERHEAD, TIGHT TO UNDERSIDE OF

STRUCTURE OR SLAB, WITH SPACE FOR INSULATION IF REQUIRED.

G. INSTALL PIPING SO THAT ALL VALVES, STRAINERS, UNIONS, TRAPS, FLANGES, AND OTHER

APPURTENANCES REQUIRING ACCESS ARE ACCESSIBLE.

H. ALL VALVES SHALL BE INSTALLED SO THAT VALVE REMAINS IN SERVICE WHEN EQUIPMENT

OR PIPING ON EQUIPMENT SIDE OF VALVE IS REMOVED.

I. ALL BALANCING VALVES AND BUTTERFLY VALVES SHALL BE PROVIDED WITH POSITION

INDICATORS AND MAXIMUM ADJUSTABLE STOPS (MEMORY STOPS).

J. PROVIDE CHAINWHEEL OPERATORS FOR ALL VALVES IN EQUIPMENT ROOMS MOUNTED

GREATER THAN 7′-0″ ABOVE FLOOR LEVEL; CHAIN SHALL EXTEND TO 7′-0″ ABOVE FLOOR

LEVEL.

K. ALL VALVES (EXCEPT CONTROL VALVES) AND STRAINERS SHALL BE FULL SIZE OF PIPE

BEFORE REDUCING SIZE TO MAKE CONNECTIONS TO EQUIPMENT AND CONTROLS.

L. UNIONS AND/OR FLANGES SHALL BE INSTALLED AT EACH PIECE OF EQUIPMENT, IN

BYPASSES, AND IN LONG PIPING RUNS (100' OR MORE) TO PERMIT DISASSEMBLY FOR

ALTERATION AND REPAIRS.

M. PITCH STEAM PIPING DOWNWARD IN THE DIRECTION OF FLOW 1/4" IN 10' (1" IN 40') MINIMUM.

PITCH ALL STEAM RETURN LINES DOWNWARD IN THE DIRECTION OF CONDENSATE FLOW

1/2" PER 10' (1" IN 20') MINIMUM. WHERE LENGTH OF BRANCH LINES ARE LESS THAN 8', PITCH

BRANCH LINES TOWARD MAINS 1/2" PER FOOT MINIMUM.

N. PITCH UP ALL STEAM AND CONDENSATE RUNOUTS TO RISERS AND EQUIPMENT 1/2" PER

FOOT. WHERE THIS PITCH CANNOT BE OBTAINED, RUNOUTS OVER 8' IN LENGTH SHALL BE

ONE SIZE LARGER THAN NOTED.

O. TAP ALL BRANCH LINES FROM TOP OF STEAM MAINS (45° PREFERRED, 90° ACCEPTABLE).

A. PROVIDE ALL MATERIALS AND EQUIPMENT AND PERFORM ALL LABOR REQUIRED TO

INSTALL COMPLETE AND OPERABLE HVAC SYSTEMS AS INDICATED ON THE DRAWINGS, AS

SPECIFIED AND AS REQUIRED BY CODE.

B. CERTAIN ITEMS SUCH AS RISES AND DROPS IN DUCTWORK, ACCESS DOORS, VOLUME

DAMPERS, ETC., ARE INDICATED ON THE CONTRACT DOCUMENT DRAWINGS FOR CLARITY

FOR A SPECIFIC LOCATION REQUIREMENT AND SHALL NOT BE INTERPRETED AS THE

EXTENT OF THE REQUIREMENTS FOR THESE ITEMS.

C. IN CORRIDORS WHERE CEILING SPEAKERS AND AIR DIFFUSERS ARE INDICATED BETWEEN

THE SAME LIGHT FIXTURES, INSTALL BOTH DEVICES AT THE QUARTER POINTS BETWEEN

THE SAME FIXTURE.

D. UNLESS OTHERWISE SHOWN, LOCATE ALL ROOM THERMOSTATS AND HUMIDISTATS 4′-0″

(CENTERLINE) ABOVE FINISHED FLOOR.

E. ALL DUCTWORK SHALL CLEAR DOORS AND WINDOWS.

F. ALL DUCTWORK DIMENSIONS, AS SHOWN ON THE DRAWINGS, ARE INTERNAL CLEAR

DIMENSIONS AND DUCT SIZE SHALL BE INCREASED TO COMPENSATE FOR DUCT LINING

THICKNESS.

G. PROVIDE ALL 90° SQUARE ELBOWS WITH DOUBLE RADIUS TURNING VANES UNLESS

OTHERWISE INDICATED. ELBOWS IN DISHWASHER, KITCHEN, AND LAUNDRY EXHAUST

SHALL BE UNVANED SMOOTH RADIUS CONSTRUCTION WITH A RADIUS EQUAL TO 1.5 TIMES

THE WIDTH OF THE DUCT. PROVIDE ACCESS DOORS UPSTREAM OF ALL ELBOWS WITH

TURNING VANES.

H. COORDINATE DIFFUSER, REGISTER, AND GRILLE LOCATIONS WITH ARCHITECTURAL

REFLECTED CEILING PLANS, LIGHTING, AND OTHER CEILING ITEMS AND MAKE MINOR DUCT

MODIFICATIONS TO SUIT.

I. FIELD ERECTED AND FACTORY ASSEMBLED AIR HANDLING UNIT COILS SHALL BE

ARRANGED FOR REMOVAL FROM THE UPSTREAM SIDE WITHOUT DISMANTLING SUPPORTS.

PROVIDE GALVANIZED STRUCTURAL STEEL SUPPORTS FOR ALL COILS (EXCEPT LOWEST

COIL) IN BANKS OVER TWO COILS HIGH TO PERMIT INDEPENDENT REMOVAL OF ANY COIL.

J. ALL AIR HANDLING UNITS SHALL OPERATE WITHOUT MOISTURE CARRYOVER.

K. LOCATE ALL MECHANICAL EQUIPMENT (SINGLE DUCT, DUAL DUCT, VARIABLE VOLUME,

CONSTANT VOLUME AND FAN POWERED BOXES, FAN COIL UNITS, CABINET HEATERS, UNIT

HEATERS, UNIT VENTILATORS, COILS, STEAM HUMIDIFIERS, ETC.) FOR UNOBSTRUCTED

ACCESS TO UNIT ACCESS PANELS, CONTROLS AND VALVING.

L. FINNED TUBE RADIATION ENCLOSURES SHALL BE WALL TO WALL UNLESS OTHERWISE

INDICATED.

M. PROVIDE FLEXIBLE CONNECTIONS IN ALL DUCTWORK SYSTEMS (SUPPLY, RETURN, AND

EXHAUST) CONNECTED TO AIR HANDLING UNITS, FANS, AND OTHER EQUIPMENT WHICH

REQUIRE VIBRATION ISOLATION. FLEXIBLE CONNECTIONS SHALL BE PROVIDED AT THE

POINT OF CONNECTION TO THE EQUIPMENT UNLESS OTHERWISE INDICATED.

PIPING GENERAL NOTES: HVAC/SHEET METAL GENERAL NOTES:

EXISTING TO BE DEMOLISHED

LIMIT OF DEMOLITION

CONNECT NEW TO EXISTINGEXISTING TO REMAIN

NEW DUCT (INSIDE DIMENSIONS: W" X D")

RS

RL

REFRIGERANT SUCTION

REFRIGERANT LIQUID

SUPPLY AIR DUCT UP

SUPPLY AIR DUCT DOWN

H

T

H

T

26-DS-100-3

MH-100

ROOM NUMBER SERVED (ROOM 100)

EQUIPMENT ABBREVIATION (DUCTLESS MINI-SPLIT)

DETAIL NUMBER

SHEET NUMBER

SHEET NUMBER

SECTION NUMBER

THERMOSTAT

HUMIDISTAT

TEMPERATURE SENSOR

HUMIDITY SENSOR

BUILDING NUMBER WHERE EQUIPMENT IS LOCATED

26-TU-1-1

ITEM NUMBER (TERMINAL UNIT NO. 1)

ITEM (TERMINAL UNIT)

BUILDING NUMBER WHERE EQUIPMENT IS LOCATED

SERVED BY AIR HANDLER UNIT NO. 1

TERMINAL UNIT TAG

MECHANICAL EQUIPMENT TAG

1 OWNER FURNISHED, CONTRACTOR

INSTALLED EQUIPMENT DESIGNATION

EXISTING TO BE DEMOLISHED

EXISTING TO REMAIN

NEW PIPE

CONNECT NEW TO EXISTING

LIMIT OF DEMOLITION

GENERAL PIPING SYMBOLS

GENERAL ANNOTATIONS

AV

STRAINERFLOAT & THERMOSTATIC

STEAM TRAP

INVERTED BUCKET

STEAM TRAP

FLANGE CONNECTION PIPE DROP

PIPE RISER TEE DOWN

TEE UP

UNION

PRESSURE REDUCING

VALVE

BALL VALVE

ANGLE GLOBE VALVE

SAFETY RELIEF VALVE

GLOBE VALVE

MANUAL OR

AUTOMATIC AIR VENT

EXPANSION JOINT

EJ

PRESSURE AND

TEMPERATURE TEST PLUG

QUICK-COUPLE HOSE

CONNECTOR

FLOW METER

HVAC PIPING SYMBOLS

CHILLED WATER RETURN

CHILLED WATER SUPPLY

CHR

CHS

HEATING HOT WATER RETURN

HEATING HOT WATER SUPPLY

HHR

HHS QV CRYOGEN VENT

DR DRIP RETURN

CAP

REDUCER (ECCENTRIC)

TYPE

AIRFLOW (CFM)

SD-1

TYPE

AIRFLOW (CFM)

RG-1

TYPE

AIRFLOW (CFM)

EG-1

SQUARE TO ROUND TRANSITION

ELBOW WITH TURNING

VANES

ROUND ELBOW

EXHAUST, RELIEF, MAKE UP, OR

OUTSIDE AIR DUCT DOWN

EXHAUST, RELIEF, MAKE UP, OR

OUTSIDE AIR DUCT UP

RETURN DUCT DOWN

RETURN DUCT UP

BRANCH DUCT WITH HIGH EFFICIENCY

TAKE-OFF (HETO) BRANCH FITTING &

MANUAL VOLUME DAMPER

BRANCH DUCT WITH CONICAL

FITTING & MANUAL VOLUME

DAMPER

DAMPERS: (BD, FD, FSD, MD, SD, VD)

BD

XX-XX

ANCHOR

TEEDIRECTION OF FLOW

S

N. CONCRETE HOUSEKEEPING PADS TO SUIT MECHANICAL EQUIPMENT SHALL BE SIZED AND

LOCATED BY THE MECHANICAL CONTRACTOR. MINIMUM CONCRETE PAD THICKNESS SHALL

BE 4". PAD SHALL EXTEND BEYOND THE EQUIPMENT A MINIMUM OF 4" ON EACH SIDE.

CONCRETE HOUSEKEEPING PADS SHALL BE PROVIDED BY THE GENERAL CONTRACTOR. IT

SHALL BE THE RESPONSIBILITY OF THE MECHANICAL CONTRACTOR TO COORDINATE SIZE

AND LOCATION OF CONCRETE HOUSEKEEPING PADS.

O. WHEN MECHANICAL WORK (HVAC, PLUMBING, SHEET METAL, ETC.) IS SUB-CONTRACTED, IT

SHALL BE THE MECHANICAL CONTRACTOR’S RESPONSIBILITY TO COORDINATE

SUBCONTRACTORS AND THE ASSOCIATED CONTRACTS. WHEN DISCREPANCIES ARISE

PERTAINING TO WHICH CONTRACTOR PROVIDES A PARTICULAR ITEM OF THE MECHANICAL

CONTRACT OR WHICH CONTRACTOR PROVIDES FINAL CONNECTIONS FOR A PARTICULAR

ITEM OF THE MECHANICAL CONTRACT, IT SHALL BE BROUGHT TO THE ATTENTION OF THE

MECHANICAL CONTRACTOR, WHOSE DECISION SHALL BE FINAL.

P. THE LOCATIONS OF ALL ITEMS SHOWN ON THE DRAWINGS OR CALLED FOR IN THE

SPECIFICATIONS THAT ARE NOT DEFINITELY FIXED BY DIMENSIONS ARE APPROXIMATE

ONLY. THE EXACT LOCATIONS NECESSARY TO SECURE THE BEST CONDITIONS AND

RESULTS MUST BE DETERMINED BY THE PROJECT SITE CONDITIONS AND SHALL HAVE THE

APPROVAL OF THE ENGINEER BEFORE BEING INSTALLED. DO NOT SCALE DRAWINGS.

Q. ALL MISCELLANEOUS STEEL REQUIRED TO ENSURE PROPER INSTALLATION AND AS SHOWN

IN DETAILS FOR PIPING, DUCTWORK, AND EQUIPMENT (UNLESS OTHERWISE NOTED) SHALL

BE FURNISHED AND INSTALLED BY THE MECHANICAL CONTRACTOR.

R. PROVIDE ACCESS PANELS FOR INSTALLATION IN WALLS AND CEILINGS WHERE REQUIRED

TO SERVICE DAMPERS, VALVES, SMOKE DETECTORS, AND OTHER CONCEALED

MECHANICAL EQUIPMENT.

S. ALL DUCTWORK, PIPING AND EQUIPMENT SUPPORTED FROM STRUCTURAL STEEL SHALL

BE COORDINATED WITH GENERAL CONTRACTOR. ALL ATTACHMENTS TO STEEL BAR

JOISTS, TRUSSES, OR JOIST GIRDERS SHALL BE AT PANEL POINTS. PROVIDE BEAM CLAMPS

MEETING MSS STANDARDS.WELDING TO STRUCTURAL MEMBERS SHALL NOT BE

PERMITTED. THE USE OF C-CLAMPS SHALL NOT BE PERMITTED.

T. ALL ROOF MOUNTED EQUIPMENT CURBS FOR EQUIPMENT PROVIDED BY THE MECHANICAL

CONTRACTOR SHALL BE FURNISHED BY THE MECHANICAL CONTRACTOR. COORDINATE

INSTALLATION WITH GENERAL CONTRACTOR.

U. LOCATIONS AND SIZES OF ALL FLOOR, WALL, AND ROOF OPENINGS SHALL BE

COORDINATED WITH ALL OTHER TRADES INVOLVED.

V. ALL OPENINGS IN FIRE WALLS DUE TO DUCTWORK, PIPING, CONDUIT, ETC., SHALL BE FIRE

STOPPED WITH AN APPROVED FIRE STOPPING MATERIAL.

W. ALL AIR CONDITIONING CONDENSATE DRAIN LINES FROM EACH AIR HANDLING UNIT AND

ROOFTOP UNIT SHALL BE PIPED FULL SIZE OF THE UNIT DRAIN OUTLET, WITH P-TRAP, AND

PIPED TO NEAREST DRAIN. SEE DETAILS AND SPECIFICATIONS FOR DEPTH OF AIR

CONDITIONING CONDENSATE TRAP.

X. REFER TO TYPICAL DETAILS FOR DUCTWORK, PIPING, AND EQUIPMENT INSTALLATION.

P. PROVIDE AN END OF MAIN DRIP AT EACH RISE IN THE STEAM MAIN. PROVIDE CONDENSATE

DRIPS AT THE BOTTOM OF ALL STEAM RISERS, DOWNFED RUNOUTS TO EQUIPMENT,

RADIATORS, ETC., AT END OF MAINS AND LOW POINTS, AND AHEAD OF ALL PRESSURE

REGULATORS, CONTROL VALVES, ISOLATION VALVES, AND EXPANSION JOINTS.

Q. ON STRAIGHT STEAM PIPING RUNS WITH NO NATURAL DRAINAGE POINTS, INSTALL DRIP

LEGS AT INTERVALS NOT EXCEEDING 200' WHERE PIPE IS PITCHED DOWNWARD IN THE

DIRECTION OF STEAM FLOW AND A MAXIMUM OF 100' WHERE THE PIPE IS PITCHED UP SO

THAT CONDENSATE FLOW IS OPPOSITE OF STEAM FLOW.

R. STEAM TRAPS SHALL BE MINIMUM 3/4″ IN SIZE.

S. INSTALL ALL PIPING WITHOUT FORCING OR SPRINGING.

T. ALL PIPING SHALL CLEAR DOORS AND WINDOWS.

U. ALL VALVES SHALL BE ADJUSTED FOR SMOOTH AND EASY OPERATION.

V. ALL PIPING WORK SHALL BE COORDINATED WITH ALL TRADES INVOLVED. OFFSETS IN

PIPING AROUND OBSTRUCTIONS SHALL BE PROVIDED AT NO ADDITIONAL COST TO THE

OWNER.

W. PROVIDE FLEXIBLE CONNECTIONS IN ALL PIPING SYSTEMS CONNECTED TO PUMPS,

CHILLERS, COOLING TOWERS, AND OTHER EQUIPMENT WHICH REQUIRE VIBRATION

ISOLATION EXCEPT WATER COILS. FLEXIBLE CONNECTIONS SHALL BE PROVIDED AS CLOSE

TO THE EQUIPMENT AS POSSIBLE OR AS INDICATED ON THE DRAWINGS.

X. SLOPE REFRIGERANT PIPING ONE PERCENT IN THE DIRECTION OF OIL RETURN. LIQUID

LINES MAY BE INSTALLED LEVEL.

Y. INSTALL HORIZONTAL REFRIGERANT HOT GAS DISCHARGE PIPING WITH 1/2″ PER 10'

DOWNWARD SLOPE AWAY FROM THE COMPRESSOR.

Z. INSTALL HORIZONTAL REFRIGERANT SUCTION LINES WITH 1/2″ PER 10' DOWNWARD SLOPE

TO THE COMPRESSOR, WITH NO LONG TRAPS OR DEAD ENDS WHICH MAY CAUSE OIL TO

SEPARATE FROM THE SUCTION GAS AND RETURN TO THE COMPRESSOR IN DAMAGING

SLUGS.

AA. PROVIDE LINE SIZE LIQUID INDICATORS IN MAIN LIQUID LINE LEAVING CONDENSER OR

RECEIVER. INSTALL MOISTURE LIQUID INDICATORS IN LIQUID LINES BETWEEN FILTER

DRYERS AND THERMOSTATIC EXPANSION VALVES AND IN LIQUID LINE TO RECEIVER.

BB. PROVIDE LINE SIZE STRAINER UPSTREAM OF EACH AUTOMATIC VALVE. PROVIDE SHUTOFF

VALVE ON EACH SIDE OF STRAINER.

CC. PROVIDE PERMANENT FILTER DRYERS IN LOW TEMPERATURE SYSTEMS AND SYSTEMS

USING HERMETIC COMPRESSORS.

DD. PROVIDE REPLACEABLE CARTRIDGE FILTER DRYERS WITH THREE-WAY VALVE BYPASS A

ASSEMBLY FOR SOLENOID VALVES, ADJACENT TO RECEIVERS.

EE. PROVIDE REFRIGERANT CHARGING VALVE CONNECTIONS IN LIQUID LINE BETWEEN

RECEIVER SHUTOFF VALVE AND EXPANSION VALVE.

N. UNLESS OTHERWISE NOTED, ALL DUCTWORK IS OVERHEAD, TIGHT TO THE UNDERSIDE OF

THE STRUCTURE, WITH SPACE FOR INSULATION IF REQUIRED.

M. RUNS OF FLEXIBLE DUCT SHALL NOT EXCEED 5' MAXIMUM LENGTH.

O. ALL DUCTWORK SHALL BE COORDINATED WITH ALL TRADES INVOLVED. OFFSETS IN

DUCTS, INCLUDING DIVIDED DUCTS AND TRANSITIONS AROUND OBSTRUCTIONS, SHALL BE

PROVIDED AT NO ADDITIONAL COST TO THE OWNER.

P. PROVIDE ACCESS DOORS IN DUCTWORK TO PROVIDE ACCESS FOR ALL SMOKE

DETECTORS, FIRE DAMPERS, SMOKE DAMPERS, VOLUME DAMPERS, HUMIDIFIERS, COILS,

AND OTHER ITEMS LOCATED IN THE DUCTWORK WHICH REQUIRE SERVICE AND/OR

INSPECTION.

Q. PROVIDE ACCESS DOORS IN DUCTWORK FOR OPERATION, ADJUSTMENT, AND

MAINTENANCE OF ALL FANS, VALVES, AND MECHANICAL EQUIPMENT.

R. ALL DUCTS SHALL BE GROUNDED ACROSS FLEXIBLE CONNECTIONS WITH FLEXIBLE

COPPER GROUNDING STRAPS. GROUNDING STRAPS SHALL BE BOLTED OR SOLDERED TO

BOTH THE EQUIPMENT AND THE DUCT.

S. SMOKE DETECTORS SHALL BE FURNISHED AND WIRED BY THE ELECTRICAL CONTRACTOR.

THE MECHANICAL CONTRACTOR SHALL BE RESPONSIBLE FOR MOUNTING THE SMOKE

DETECTOR IN DUCTWORK AS SHOWN ON THE DRAWINGS AND IN ACCORDANCE WITH

MANUFACTURER’S PRINTED INSTRUCTIONS.

T. TERMINATE GAS VENTS FOR UNIT HEATERS, WATER HEATERS, HIGH PRESSURE PARTS

WASHER, HIGH PRESSURE CLEANER, AND OTHER GAS APPLIANCES A MINIMUM OF 3′-0″

ABOVE ROOF WITH RAIN CAP (NOTE TO DESIGNER: EDIT APPLIANCES AND HEIGHT ABOVE

ROOF TO MEET CODE AND TO SUIT PROJECT REQUIREMENTS).

U. SEE SPECIFICATIONS FOR DUCTWORK GAUGES, BRACING, HANGERS, AND OTHER

REQUIREMENTS.

V. LOUVER SIZES, LOCATIONS, MOUNTING, AND DETAILS SHALL BE COORDINATED WITH

OTHER TRADES INVOLVED. REFER TO ARCHITECTURAL SPECIFICATIONS FOR DETAILED

DESCRIPTIONS.

DIRECTION OF PIPE

PITCH (DOWN)

FM

MV

HVAC VALVE SYMBOLS

PC PUMPED CONDENSATE

SPACE TAG

FLEXIBLE CONNECTOR

PUMP

REDUCER (CONCENTRIC)

GATE VALVE

BUTTERFLY VALVE

CHECK VALVE

THERMOMETER

PRESSURE GAUGE

STRAINER WITH BLOWOFF

AND HOSE CONNECTION

YR YEAR

Y

Z INTENTIONALLY LEFT BLANK

Z

M

CONTROL VALVE

CONTROL VALVE, THREE WAY

MOTOR CONTROLLED

VALVE

M

M

NOTE: NOT ALL ABBREVIATIONS OR SYMBOLS WILL BE UTILIZED FOR THIS PROJECT.

A. MECHANICAL TRADES BIDDING DEMOLITION WORK SHALL ALLOW FOR A FULL DAY ON SITE TO REVIEW EXISTING MECHANICAL SERVICES AND EQUIPMENT IN DEMOLITION AND REMOVED AREAS. ACCESS WILL BE GIVEN TO ROOF AND EXISTING MECHANICAL AND ELECTRICAL ROOMS AS REQUIRED. VERIFY ALL EXISTING CONDITIONS PRIOR TO BEGINNING WORK. BRING ANY DISCREPANCIES FROM THE DRAWINGS AND NOTES TO THE ENGINEER OF RECORD IMMEDIATELY. MINOR CHANGES IN THE SCOPE OF THE

DEMOLITION WORK SHALL NOT JUSTIFY AN ADDITIONAL COST.

B. DEMOLISHED WORK SHALL INCLUDE FOR TEMPORARY AND PERMANENT WORK REQUIRED TO KEEP

NON-SCOPE AREAS IN OPERATION. COORDINATE UTILITY SHUT-OFFS AND TEMPORARY POWER,

STORAGE, AND ACCESS NEEDED TO COMPLETE WORK WITH GENERAL CONTRACTOR AND COR.

C. REMOVAL OF EXISTING FIXTURES AND EQUIPMENT WILL REQUIRE ISOLATION OF EXISTING PIPING BRANCHES AND/OR MAINS USING SHUTOFF VALVES. INSTALL NEW ISOLATION VALVES AS REQUIRED TO

COMPLETION DEMOLITION WORK.

D. REMOVAL OF EXISTING PLUMBING FIXTURES AND EQUIPMENT WILL REQUIRE CAPPING AND SEALING EXISTING MAINS OR BRANCHES, WITHOUT LEAVING DEAD LEGS, TO KEEP REMAINING SYSTEMS IN OPERATION. THE CONTRACTOR SHALL PROVIDE PROTECTIVE MEASURES TO PROTECT THE EXISTING

OCCUPIED AREAS AND EQUIPMENT DURING THE CONSTRUCTION WORK. THE CONTRACTOR SHALL

CLEAN THE AREAS OF ALL CONSTRUCTION DIRT DAILY, AND UPON COMPLETION OF THE WORK.

E. ALL DRAINED PIPING RISERS AND MAINS SHALL BE REFILLED AND PROPERLY VENTED BY THE

CONTRACTOR ONCE NEW WORK HAS BEEN COMPLETED.

F. COORDINATE REMOVAL, REPLACEMENT, AND/OR REPAIRS OF ANY EXISTING WALLS, CEILING, ETC.

REQUIRED FOR MECHANICAL DEMOLITION WORK WITH GENERAL CONTRACTOR.

G. PROVIDE TIGHTLY SEALED AND INSULATED TERMINATIONS FOR ALL PIPING, DUCTWORK, AND EQUIPMENT REMOVED FROM THE PROJECT. THERE SHALL BE NO "DEAD LEG" SECTIONS OF PIPING

WHERE WATER CAN SIT AND BECOME STAGNANT.

H. REFER TO THE CONTRACTING OFFICER'S REPRESENTATIVE (COR) FOR INSTRUCTIONS REGARDING THE

REMOVAL AND RETURN OR DEMOLITION OF EXISTING EQUIPMENT AND FIXTURES.

I. PORTIONS OF EXISTING SYSTEMS ARE SHOWN FOR CLARITY AND MAY NOT BE NECESSARY TO MODIFY OR REVISE THEM. ALL EXISTING SYSTEMS ARE SHOWN BASED ON AVAILABLE AS-BUILT DRAWINGS AND SITE SURVEYS OF ACCESSIBLE AREAS. THE CONTRACTOR SHALL VERIFY ALL EXISTING CONDITIONS.

J. ALL WORK MUST BE COORDINATED AND SCHEDULED WITH THE CONTRACTING OFFICER'S

REPRESENTATIVE TO ENSURE THE LEAST AMOUNT OF DISRUPTION OF BUILDING ACTIVITIES AS

POSSIBLE.

K. ALL ACCESSIBLE ABANDONED PIPING AND DUCTWORK SHALL BE REMOVED AND PROPERLY DISPOSED

OF.

L. SUPPLY AIR DUCTWORK AND PIPING NOT SHOWN HATCHED IS TO BE RETAINED, ANY DAMAGE TO

EXISTING INSULATION AND DUCTS TO BE REPAIRED TO MATCH EXISTING.

GENERAL DEMOLITION NOTES:

B-100

SPACE NAME

ITEM NUMBER (DS UNIT NO. 3)

DS DUCTLESS MINI-SPLIT UNIT

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

CONSULTANTS:

CIVIL ENGINEER

OLSSON

550 ST LOUIS ST,

SPRINGFIELD, MO 65806

(417) 885-1736

MECH / ELEC ENGINEER

SPUR DESIGN

2519 MADISON AVE., STE. 100

KANSAS CITY, MO 64108

(913) 369-7200

FIRE PROTECTION ENGINEER

RATED ENGINEERING

609 S. KELLY AVENUE, SUITE H2

EDMOND, OK 73003

(405) 856-2965

INDUSTRIAL HYGENIST

RIVERFRONT SAFETY & HEALTH

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

TECH ENGINEER

ASPEN COMMUNICATIONS, LLC

7 KIJI-DAVA CIRCLE, SUITE A

PRESCOTT, AZ 86301

(928) 774-0992

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STRUCT ENGINEER

STAND STRUCTURAL ENGINEERING

8234 ROBINSON STREET

OVERLAND PARK, KS 66204

(913) 214-2169

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Drawing #

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH REG. NO. BR 2171 EXP. 09/30/2023

ENGR REG. NO. F-17591 EXP. 02/29/2024

STAMP:

Drawing Number

Building Number

BUILDING 34 NOT SPRINKLERED. ALL OTHER BUILDINGS FULLY SPRINKLERED.

COMMISSIONING

ES2

13401 N. SANTA FE AVE

OKLAHOMA CITY, OK 73114

(405) 528-4500

CONTROLLED UNCLASSIFIED INFORMATION (CUI)

CONTROLLED UNCLASSIFIED INFORMATION (CUI)

C O

N T

R O

L L E

D U

N C

L A

S S

IF

IE

D I

N F

O R

M A

T

IO

N

C U

I)

/6

/2

:5

:2

A

M

100% BID DOCUMENTS

LEGEND AND ABBREVIATIONS

IHB 113 OF 229JRM

BONHAM EHRM

INFRASTRUCTURE

UPGRADES

07/07/2023

549A4-21-700

BONHAM VA MEDICAL CENTER

1201 E. 9TH STREET

BONHAM, TX 75418

M-000

SPUR #: 2216No. REVISION DESCRIPTION DATE

CLOSET

CLOSET

CLOSET

PHONE ROOM

CLOSET

18.5

1 1

M-401

M-401

M-401

M-401

CLOSET

NEW TR

CLOSET

113A

NEW TR

116A

M-401

M-401 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

CONSULTANTS:

CIVIL ENGINEER

OLSSON

550 ST LOUIS ST,

SPRINGFIELD, MO 65806

(417) 885-1736

MECH / ELEC ENGINEER

SPUR DESIGN

2519 MADISON AVE., STE. 100

KANSAS CITY, MO 64108

(913) 369-7200

FIRE PROTECTION ENGINEER

RATED ENGINEERING

609 S. KELLY AVENUE, SUITE H2

EDMOND, OK 73003

(405) 856-2965

INDUSTRIAL HYGENIST

RIVERFRONT SAFETY & HEALTH

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

TECH ENGINEER

ASPEN COMMUNICATIONS, LLC

7 KIJI-DAVA CIRCLE, SUITE A

PRESCOTT, AZ 86301

(928) 774-0992

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STRUCT ENGINEER

STAND STRUCTURAL ENGINEERING

8234 ROBINSON STREET

OVERLAND PARK, KS 66204

(913) 214-2169

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Drawing #

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH REG. NO. BR 2171 EXP. 09/30/2023

ENGR REG. NO. F-17591 EXP. 02/29/2024

STAMP:

Drawing Number

Building Number

BUILDING 34 NOT SPRINKLERED. ALL OTHER BUILDINGS FULLY SPRINKLERED.

COMMISSIONING

ES2

13401 N. SANTA FE AVE

OKLAHOMA CITY, OK 73114

(405) 528-4500

CONTROLLED UNCLASSIFIED INFORMATION (CUI)

CONTROLLED UNCLASSIFIED INFORMATION (CUI)

C O

N T

R O

L L E

D U

N C

L A

S S

IF

IE

D I

N F

O R

M A

T

IO

N

C U

I)

/6

/2

:5

:2

A

M

100% BID DOCUMENTS

BUILDING 1 HVAC REFERENCE PLANS

IHB 114 OF 229JRM

BONHAM EHRM

INFRASTRUCTURE

UPGRADES

07/07/2023

549A4-21-700

BONHAM VA MEDICAL CENTER

1201 E. 9TH STREET

BONHAM, TX 75418

M-101

SPUR #: 2216

N

1/16" = 1'-0"

BLDG 1 HVAC REFERENCE PLAN - BASEMENT1

N

1/16" = 1'-0"

BLDG 1 HVAC REFERENCE PLAN - LEVEL 12

KEY PLAN

N

KEYNOTES

1 NO HVAC SCOPE REQUIRED WITHIN ROOM. REFER TO ARCHITECTURAL AND ELECTRICAL DRAWINGS FOR MORE INFORMATION.

3 EXISTING MECHANICAL SYSTEMS TO BE DEMOLISHED AND REPLACED WITH NEW COOLING ONLY DUCTLESS SPLIT-SYSTEM. REFER TO

ENLARGED PLANS FOR MORE INFORMATION.

No. REVISION DESCRIPTION DATE

M-401

NEW TR

M-401

NEW TR

M-401

M-401

M-402

M-402

NEW TR

NEW SERVER

M-402

M-402 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

CONSULTANTS:

CIVIL ENGINEER

OLSSON

550 ST LOUIS ST,

SPRINGFIELD, MO 65806

(417) 885-1736

MECH / ELEC ENGINEER

SPUR DESIGN

2519 MADISON AVE., STE. 100

KANSAS CITY, MO 64108

(913) 369-7200

FIRE PROTECTION ENGINEER

RATED ENGINEERING

609 S. KELLY AVENUE, SUITE H2

EDMOND, OK 73003

(405) 856-2965

INDUSTRIAL HYGENIST

RIVERFRONT SAFETY & HEALTH

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

TECH ENGINEER

ASPEN COMMUNICATIONS, LLC

7 KIJI-DAVA CIRCLE, SUITE A

PRESCOTT, AZ 86301

(928) 774-0992

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STRUCT ENGINEER

STAND STRUCTURAL ENGINEERING

8234 ROBINSON STREET

OVERLAND PARK, KS 66204

(913) 214-2169

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Drawing #

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH REG. NO. BR 2171 EXP. 09/30/2023

ENGR REG. NO. F-17591 EXP. 02/29/2024

STAMP:

Drawing Number

Building Number

BUILDING 34 NOT SPRINKLERED. ALL OTHER BUILDINGS FULLY SPRINKLERED.

COMMISSIONING

ES2

13401 N. SANTA FE AVE

OKLAHOMA CITY, OK 73114

(405) 528-4500

CONTROLLED UNCLASSIFIED INFORMATION (CUI)

CONTROLLED UNCLASSIFIED INFORMATION (CUI)

C O

N T

R O

L L E

D U

N C

L A

S S

IF

IE

D I

N F

O R

M A

T

IO

N

C U

I)

/6

/2

:5

:2

A

M

100% BID DOCUMENTS

BUILDING 1 HVAC REFERENCE PLANS

IHB 115 OF 229JRM

BONHAM EHRM

INFRASTRUCTURE

UPGRADES

07/07/2023

549A4-21-700

BONHAM VA MEDICAL CENTER

1201 E. 9TH STREET

BONHAM, TX 75418

M-102

SPUR #: 2216

N

1/16" = 1'-0"

BLDG 1 HVAC REFERENCE PLAN - LEVEL 21

N

1/16" = 1'-0"

BLDG 1 HVAC REFERENCE PLAN - LEVEL 32

N

1/16" = 1'-0"

BLDG 1 HVAC REFERENCE PLAN - LEVEL 43

N

1/16" = 1'-0"

BLDG 1 HVAC REFERENCE PLAN - LEVEL 54

KEY PLAN

N

KEYNOTES

3 EXISTING MECHANICAL SYSTEMS TO BE DEMOLISHED AND REPLACED WITH NEW COOLING ONLY DUCTLESS SPLIT-SYSTEM. REFER TO

NEW TR

CLOSET

100C

M-403

M-403

M-403

NEW TR

M-403

M-403

CLOSET

HAC

201A

NEW TR

M-403

M-403

M-403 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

CONSULTANTS:

CIVIL ENGINEER

OLSSON

550 ST LOUIS ST,

SPRINGFIELD, MO 65806

(417) 885-1736

MECH / ELEC ENGINEER

SPUR DESIGN

2519 MADISON AVE., STE. 100

KANSAS CITY, MO 64108

(913) 369-7200

FIRE PROTECTION ENGINEER

RATED ENGINEERING

609 S. KELLY AVENUE, SUITE H2

EDMOND, OK 73003

(405) 856-2965

INDUSTRIAL HYGENIST

RIVERFRONT SAFETY & HEALTH

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

TECH ENGINEER

ASPEN COMMUNICATIONS, LLC

7 KIJI-DAVA CIRCLE, SUITE A

PRESCOTT, AZ 86301

(928) 774-0992

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STRUCT ENGINEER

STAND STRUCTURAL ENGINEERING

8234 ROBINSON STREET

OVERLAND PARK, KS 66204

(913) 214-2169

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Drawing #

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH REG. NO. BR 2171 EXP. 09/30/2023

ENGR REG. NO. F-17591 EXP. 02/29/2024

STAMP:

Drawing Number

Building Number

BUILDING 34 NOT SPRINKLERED. ALL OTHER BUILDINGS FULLY SPRINKLERED.

COMMISSIONING

ES2

13401 N. SANTA FE AVE

OKLAHOMA CITY, OK 73114

(405) 528-4500

CONTROLLED UNCLASSIFIED INFORMATION (CUI)

CONTROLLED UNCLASSIFIED INFORMATION (CUI)

C O

N T

R O

L L E

D U

N C

L A

S S

IF

IE

D I

N F

O R

M A

T

IO

N

C U

I)

/6

/2

:5

:2

A

M

100% BID DOCUMENTS

BUILDING 2 HVAC REFERENCE PLANS

IHB 116 OF 229JRM

BONHAM EHRM

INFRASTRUCTURE

UPGRADES

07/07/2023

549A4-21-700

BONHAM VA MEDICAL CENTER

1201 E. 9TH STREET

BONHAM, TX 75418

M-103

SPUR #: 2216

N

1/16" = 1'-0"

BLDG 2 HVAC REFERENCE PLAN - LEVEL 11

N

1/16" = 1'-0"

BLDG 2 HVAC REFERENCE PLAN - LEVEL 22

KEY PLAN

N

KEYNOTES

1 NO HVAC SCOPE REQUIRED WITHIN ROOM. REFER TO ARCHITECTURAL AND ELECTRICAL DRAWINGS FOR MORE INFORMATION.

3 EXISTING MECHANICAL SYSTEMS TO BE DEMOLISHED AND REPLACED WITH NEW COOLING ONLY DUCTLESS SPLIT-SYSTEM. REFER TO

301A

CLOSET

M-403

M-403

M-403

M-404

NEW TR

401A

M-404

M-404

CLOSET

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

CONSULTANTS:

CIVIL ENGINEER

OLSSON

550 ST LOUIS ST,

SPRINGFIELD, MO 65806

(417) 885-1736

MECH / ELEC ENGINEER

SPUR DESIGN

2519 MADISON AVE., STE. 100

KANSAS CITY, MO 64108

(913) 369-7200

FIRE PROTECTION ENGINEER

RATED ENGINEERING

609 S. KELLY AVENUE, SUITE H2

EDMOND, OK 73003

(405) 856-2965

INDUSTRIAL HYGENIST

RIVERFRONT SAFETY & HEALTH

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

TECH ENGINEER

ASPEN COMMUNICATIONS, LLC

7 KIJI-DAVA CIRCLE, SUITE A

PRESCOTT, AZ 86301

(928) 774-0992

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STRUCT ENGINEER

STAND STRUCTURAL ENGINEERING

8234 ROBINSON STREET

OVERLAND PARK, KS 66204

(913) 214-2169

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Drawing #

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH REG. NO. BR 2171 EXP. 09/30/2023

ENGR REG. NO. F-17591 EXP. 02/29/2024

STAMP:

Drawing Number

Building Number

BUILDING 34 NOT SPRINKLERED. ALL OTHER BUILDINGS FULLY SPRINKLERED.

COMMISSIONING

ES2

13401 N. SANTA FE AVE

OKLAHOMA CITY, OK 73114

(405) 528-4500

CONTROLLED UNCLASSIFIED INFORMATION (CUI)

CONTROLLED UNCLASSIFIED INFORMATION (CUI)

C O

N T

R O

L L E

D U

N C

L A

S S

IF

IE

D I

N F

O R

M A

T

IO

N

C U

I)

/6

/2

:5

:2

A

M

100% BID DOCUMENTS

BUILDING 2 HVAC REFERENCE PLANS

IHB 117 OF 229JRM

BONHAM EHRM

INFRASTRUCTURE

UPGRADES

07/07/2023

549A4-21-700

BONHAM VA MEDICAL CENTER

1201 E. 9TH STREET

BONHAM, TX 75418

M-104

SPUR #: 2216

N

1/16" = 1'-0"

BLDG 2 HVAC REFERENCE PLAN - LEVEL 31

N

1/16" = 1'-0"

BLDG 2 HVAC REFERENCE PLAN - LEVEL 42

KEY PLAN

N

KEYNOTES

1 NO HVAC SCOPE REQUIRED WITHIN ROOM. REFER TO ARCHITECTURAL AND ELECTRICAL DRAWINGS FOR MORE INFORMATION.

3 EXISTING MECHANICAL SYSTEMS TO BE DEMOLISHED AND REPLACED WITH NEW COOLING ONLY DUCTLESS SPLIT-SYSTEM. REFER TO

M-404

M-404

NEW TR

135B

OFFICE

135A

M-404

M-404

NEW TR

201B

CLOSET

201C th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

CONSULTANTS:

CIVIL ENGINEER

OLSSON

550 ST LOUIS ST,

SPRINGFIELD, MO 65806

(417) 885-1736

MECH / ELEC ENGINEER

SPUR DESIGN

2519 MADISON AVE., STE. 100

KANSAS CITY, MO 64108

(913) 369-7200

FIRE PROTECTION ENGINEER

RATED ENGINEERING

609 S. KELLY AVENUE, SUITE H2

EDMOND, OK 73003

(405) 856-2965

INDUSTRIAL HYGENIST

RIVERFRONT SAFETY & HEALTH

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

TECH ENGINEER

ASPEN COMMUNICATIONS, LLC

7 KIJI-DAVA CIRCLE, SUITE A

PRESCOTT, AZ 86301

(928) 774-0992

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STRUCT ENGINEER

STAND STRUCTURAL ENGINEERING

8234 ROBINSON STREET

OVERLAND PARK, KS 66204

(913) 214-2169

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Drawing #

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH REG. NO. BR 2171 EXP. 09/30/2023

ENGR REG. NO. F-17591 EXP. 02/29/2024

STAMP:

Drawing Number

Building Number

BUILDING 34 NOT SPRINKLERED. ALL OTHER BUILDINGS FULLY SPRINKLERED.

COMMISSIONING

ES2

13401 N. SANTA FE AVE

OKLAHOMA CITY, OK 73114

(405) 528-4500

CONTROLLED UNCLASSIFIED INFORMATION (CUI)

CONTROLLED UNCLASSIFIED INFORMATION (CUI)

C O

N T

R O

L L E

D U

N C

L A

S S

IF

IE

D I

N F

O R

M A

T

IO

N

C U

I)

/6

/2

:5

:2

A

M

100% BID DOCUMENTS

BUILDING 3 HVAC REFERENCE PLANS

IHB 118 OF 229JRM

BONHAM EHRM

INFRASTRUCTURE

UPGRADES

07/07/2023

549A4-21-700

BONHAM VA MEDICAL CENTER

1201 E. 9TH STREET

BONHAM, TX 75418

M-105

SPUR #: 2216

N

1/16" = 1'-0"

BLDG 3 HVAC REFERENCE PLAN - LEVEL 11

N

1/16" = 1'-0"

BLDG 3 HVAC REFERENCE PLAN - LEVEL 22

KEY PLAN

N

KEYNOTES

3 EXISTING MECHANICAL SYSTEMS TO BE DEMOLISHED AND REPLACED WITH NEW COOLING ONLY DUCTLESS SPLIT-SYSTEM. REFER TO

M-404

CLOSET

106A

M-404

M-404

NEW TR

M-405

CARPENTRY SHOP

107A

NEW TE

107A

M-405

M-405

NEW TR

M-405

M-405

M-405

RESTROOM

CLOSET

105A

NEW TR

M-405

OFFICE

NEW TE

102A

M-405

M-405

M-405

NEW TR

CLOSET

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

CONSULTANTS:

CIVIL ENGINEER

OLSSON

550 ST LOUIS ST,

SPRINGFIELD, MO 65806

(417) 885-1736

MECH / ELEC ENGINEER

SPUR DESIGN

2519 MADISON AVE., STE. 100

KANSAS CITY, MO 64108

(913) 369-7200

FIRE PROTECTION ENGINEER

RATED ENGINEERING

609 S. KELLY AVENUE, SUITE H2

EDMOND, OK 73003

(405) 856-2965

INDUSTRIAL HYGENIST

RIVERFRONT SAFETY & HEALTH

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

TECH ENGINEER

ASPEN COMMUNICATIONS, LLC

7 KIJI-DAVA CIRCLE, SUITE A

PRESCOTT, AZ 86301

(928) 774-0992

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STRUCT ENGINEER

STAND STRUCTURAL ENGINEERING

8234 ROBINSON STREET

OVERLAND PARK, KS 66204

(913) 214-2169

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Drawing #

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH REG. NO. BR 2171 EXP. 09/30/2023

ENGR REG. NO. F-17591 EXP. 02/29/2024

STAMP:

Drawing Number

Building Number

BUILDING 34 NOT SPRINKLERED. ALL OTHER BUILDINGS FULLY SPRINKLERED.

COMMISSIONING

ES2

13401 N. SANTA FE AVE

OKLAHOMA CITY, OK 73114

(405) 528-4500

CONTROLLED UNCLASSIFIED INFORMATION (CUI)

CONTROLLED UNCLASSIFIED INFORMATION (CUI)

C O

N T

R O

L L E

D U

N C

L A

S S

IF

IE

D I

N F

O R

M A

T

IO

N

C U

I)

/6

/2

:5

:2

A

M

100% BID DOCUMENTS

BUILDINGS 4, 8, 9, 10, 11, 12, & 34 HVAC

REFERENCE PLANS

IHB 119 OF 229JRM

BONHAM EHRM

INFRASTRUCTURE

UPGRADES

07/07/2023

549A4-21-700

BONHAM VA MEDICAL CENTER

1201 E. 9TH STREET

BONHAM, TX 75418

M-106

SPUR #: 2216

N

1/16" = 1'-0"

BLDG 4 HVAC REFERENCE PLAN - LEVEL 11

N

1/16" = 1'-0"

BLDG 4 HVAC REFERENCE PLAN - LEVEL 22

N

1/16" = 1'-0"

BLDG 8 HVAC REFERENCE PLAN - LEVEL 13

N

1/16" = 1'-0"

BLDG 9 HVAC REFERENCE PLAN - LEVEL 14

N

1/16" = 1'-0"

BLDG 10 HVAC REFERENCE PLAN - LEVEL 16

N

1/16" = 1'-0"

BLDG 11 HVAC REFERENCE PLAN - LEVEL 17

N

1/16" = 1'-0"

BLDG 12 HVAC REFERENCE PLAN - LEVEL 28

N

1/16" = 1'-0"

BLDG 34 HVAC REFERENCE PLAN - LEVEL 15

4, 8, 9, 10, 11, 12, & 34

KEY PLAN

N

KEYNOTES

1 NO HVAC SCOPE REQUIRED WITHIN ROOM. REFER TO ARCHITECTURAL AND ELECTRICAL DRAWINGS FOR MORE INFORMATION.

3 EXISTING MECHANICAL SYSTEMS TO BE DEMOLISHED AND REPLACED WITH NEW COOLING ONLY DUCTLESS SPLIT-SYSTEM. REFER TO

M-406

M-406

M-406

M-406

NEW TR

1B-108

NEW TR

1C-111 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

CONSULTANTS:

CIVIL ENGINEER

OLSSON

550 ST LOUIS ST,

SPRINGFIELD, MO 65806

(417) 885-1736

MECH / ELEC ENGINEER

SPUR DESIGN

2519 MADISON AVE., STE. 100

KANSAS CITY, MO 64108

(913) 369-7200

FIRE PROTECTION ENGINEER

RATED ENGINEERING

609 S. KELLY AVENUE, SUITE H2

EDMOND, OK 73003

(405) 856-2965

INDUSTRIAL HYGENIST

RIVERFRONT SAFETY & HEALTH

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

TECH ENGINEER

ASPEN COMMUNICATIONS, LLC

7 KIJI-DAVA CIRCLE, SUITE A

PRESCOTT, AZ 86301

(928) 774-0992

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STRUCT ENGINEER

STAND STRUCTURAL ENGINEERING

8234 ROBINSON STREET

OVERLAND PARK, KS 66204

(913) 214-2169

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Drawing #

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH REG. NO. BR 2171 EXP. 09/30/2023

ENGR REG. NO. F-17591 EXP. 02/29/2024

STAMP:

Drawing Number

Building Number

BUILDING 34 NOT SPRINKLERED. ALL OTHER BUILDINGS FULLY SPRINKLERED.

COMMISSIONING

ES2

13401 N. SANTA FE AVE

OKLAHOMA CITY, OK 73114

(405) 528-4500

CONTROLLED UNCLASSIFIED INFORMATION (CUI)

CONTROLLED UNCLASSIFIED INFORMATION (CUI)

C O

N T

R O

L L E

D U

N C

L A

S S

IF

IE

D I

N F

O R

M A

T

IO

N

C U

I)

/6

/2

:5

:2

A

M

100% BID DOCUMENTS

BUILDING 24 HVAC REFERENCE PLANS

IHB 120 OF 229JRM

BONHAM EHRM

INFRASTRUCTURE

UPGRADES

07/07/2023

549A4-21-700

BONHAM VA MEDICAL CENTER

1201 E. 9TH STREET

BONHAM, TX 75418

M-107

SPUR #: 2216

N

1/16" = 1'-0"

BLDG 24 HVAC REFERENCE PLAN - LEVEL 11

KEY PLAN

N

KEYNOTES

3 EXISTING MECHANICAL SYSTEMS TO BE DEMOLISHED AND REPLACED WITH NEW COOLING ONLY DUCTLESS SPLIT-SYSTEM. REFER TO

E X

IT

M-406

M-406

M-406

M-406

M-406

M-406

NEW TR

2B-108

NEW TR

2C-108

ELEC

2A-109

CLOSET

2A-108

ELEC

2A-101

CLOSET

2A-102 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

CONSULTANTS:

CIVIL ENGINEER

OLSSON

550 ST LOUIS ST,

SPRINGFIELD, MO 65806

(417) 885-1736

MECH / ELEC ENGINEER

SPUR DESIGN

2519 MADISON AVE., STE. 100

KANSAS CITY, MO 64108

(913) 369-7200

FIRE PROTECTION ENGINEER

RATED ENGINEERING

609 S. KELLY AVENUE, SUITE H2

EDMOND, OK 73003

(405) 856-2965

INDUSTRIAL HYGENIST

RIVERFRONT SAFETY & HEALTH

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

TECH ENGINEER

ASPEN COMMUNICATIONS, LLC

7 KIJI-DAVA CIRCLE, SUITE A

PRESCOTT, AZ 86301

(928) 774-0992

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STRUCT ENGINEER

STAND STRUCTURAL ENGINEERING

8234 ROBINSON STREET

OVERLAND PARK, KS 66204

(913) 214-2169

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Drawing #

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH REG. NO. BR 2171 EXP. 09/30/2023

ENGR REG. NO. F-17591 EXP. 02/29/2024

STAMP:

Drawing Number

Building Number

BUILDING 34 NOT SPRINKLERED. ALL OTHER BUILDINGS FULLY SPRINKLERED.

COMMISSIONING

ES2

13401 N. SANTA FE AVE

OKLAHOMA CITY, OK 73114

(405) 528-4500

CONTROLLED UNCLASSIFIED INFORMATION (CUI)

CONTROLLED UNCLASSIFIED INFORMATION (CUI)

C O

N T

R O

L L E

D U

N C

L A

S S

IF

IE

D I

N F

O R

M A

T

IO

N

C U

I)

/6

/2

:5

:2

A

M

100% BID DOCUMENTS

BUILDING 24 HVAC REFERENCE PLANS

IHB 121 OF 229JRM

BONHAM EHRM

INFRASTRUCTURE

UPGRADES

07/07/2023

549A4-21-700

BONHAM VA MEDICAL CENTER

1201 E. 9TH STREET

BONHAM, TX 75418

M-108

SPUR #: 2216

N

1/16" = 1'-0"

BLDG 24 HVAC REFERENCE PLAN - LEVEL 21

KEY PLAN

N

KEYNOTES

1 NO HVAC SCOPE REQUIRED WITHIN ROOM. REFER TO ARCHITECTURAL AND ELECTRICAL DRAWINGS FOR MORE INFORMATION.

3 EXISTING MECHANICAL SYSTEMS TO BE DEMOLISHED AND REPLACED WITH NEW COOLING ONLY DUCTLESS SPLIT-SYSTEM. REFER TO

B2200

CORRIDOR

M-407

M-407

M-407

M-407

M-407

M-407

NEW TR

B2107

CLOSET

B2110

NEW TR

C3108

CLOSET

C3112 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

CONSULTANTS:

CIVIL ENGINEER

OLSSON

550 ST LOUIS ST,

SPRINGFIELD, MO 65806

(417) 885-1736

MECH / ELEC ENGINEER

SPUR DESIGN

2519 MADISON AVE., STE. 100

KANSAS CITY, MO 64108

(913) 369-7200

FIRE PROTECTION ENGINEER

RATED ENGINEERING

609 S. KELLY AVENUE, SUITE H2

EDMOND, OK 73003

(405) 856-2965

INDUSTRIAL HYGENIST

RIVERFRONT SAFETY & HEALTH

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

TECH ENGINEER

ASPEN COMMUNICATIONS, LLC

7 KIJI-DAVA CIRCLE, SUITE A

PRESCOTT, AZ 86301

(928) 774-0992

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STRUCT ENGINEER

STAND STRUCTURAL ENGINEERING

8234 ROBINSON STREET

OVERLAND PARK, KS 66204

(913) 214-2169

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Drawing #

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH REG. NO. BR 2171 EXP. 09/30/2023

ENGR REG. NO. F-17591 EXP. 02/29/2024

STAMP:

Drawing Number

Building Number

BUILDING 34 NOT SPRINKLERED. ALL OTHER BUILDINGS FULLY SPRINKLERED.

COMMISSIONING

ES2

13401 N. SANTA FE AVE

OKLAHOMA CITY, OK 73114

(405) 528-4500

CONTROLLED UNCLASSIFIED INFORMATION (CUI)

CONTROLLED UNCLASSIFIED INFORMATION (CUI)

C O

N T

R O

L L E

D U

N C

L A

S S

IF

IE

D I

N F

O R

M A

T

IO

N

C U

I)

/6

/2

:5

:3

A

M

100% BID DOCUMENTS

BUILDING 29 HVAC REFERENCE PLANS

IHB 122 OF 229JRM

BONHAM EHRM

INFRASTRUCTURE

UPGRADES

07/07/2023

549A4-21-700

BONHAM VA MEDICAL CENTER

1201 E. 9TH STREET

BONHAM, TX 75418

M-109

SPUR #: 2216

N

1/16" = 1'-0"

BLDG 29 HVAC REFERNCE PLAN - LEVEL 11

KEY PLAN

N

KEYNOTES

1 NO HVAC SCOPE REQUIRED WITHIN ROOM. REFER TO ARCHITECTURAL AND ELECTRICAL DRAWINGS FOR MORE INFORMATION.

3 EXISTING MECHANICAL SYSTEMS TO BE DEMOLISHED AND REPLACED WITH NEW COOLING ONLY DUCTLESS SPLIT-SYSTEM. REFER TO

LEVEL 1 ROOF

LEVEL 4 ROOF

LEVEL 5 ROOF

PENTHOUSE ROOF

LEVEL 5 ROOF

LEVEL 4 ROOF

LEVEL 5 ROOF

LEVEL 5 ROOF

OVERHANG

CONNECTING CORRIDOR

CONNECTING CORRIDOR

LEVEL 2 ROOF

LEVEL 1 ROOF

LEVEL 1 ROOF

LEVEL 1 ROOF UPPER

LEVEL 1 ROOF

LEVEL 1 ROOF UPPER

LEVEL 1 ROOF

LEVEL 1 ROOF

OVERHANG

LEVEL 1 ROOF

1-CU-515

1-CU-222

1-CU-116A

1-CU-160158

8 15

1-ACCU-514-2

1-ACCU-514-1

8 15

1-CU-317

1-CU-418

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig…