Attachment - 04 Structural Drawings_100percent Bid Docs.pdf
PDF 607 KB Posted
- Solicitation number
- 36C77624B0007_1
About this file
This package includes structural drawings and notes for infrastructure upgrades at the Bonham VA Medical Center in Bonham, Texas. The drawings show roof plans for multiple buildings and include details for anchoring new rooftop equipment. Structural notes specify design criteria, materials, welding and fabrication requirements. Related solicitation number 36C77624B0007_1 is for construction services for project 549A4-21-700 under the Department of Veterans Affairs Technology Acquisition Center in Austin, Texas. The solicitation type is for construction of the EHRM infrastructure upgrades at the Bonham VA Medical Center as outlined in the structural drawings and notes provided.
View the file
Other files
Show 40 more
Latest 50 of 70 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
NOTES:
ROOF STRUCTURE, RE: PLAN.
POST-INSTALLED ANCHOR TO ROOF STRUCTURE.
STRUT CHANNEL BRACE
ATTACHMENT TO EQUIPMENT / CABINET.
POST-INSTALLED ANCHOR INTO FLOOR SLAB, TYP
CONCRETE FLOOR SLAB, RE: PLAN. AVOID
DAMAGING REINFORCEMENT.
ANCHORAGE BRACKET PER EQUIPMENT
MANUFACTURER
EQUIPMENT / CABINET
1 2
5 6
CONTRACTOR SHALL PROVIDE
FINAL DESIGN IN COMPLIANCE
WITH SEISMIC REQUIREMENTS
OUTLINED IN THE SPECIFICATIONS
NOTES:
CONCRETE ANCHOR (TYP)
CONCRETE TOPPED METAL
DECK, RE: PLAN
STEEL ANGLE
THREADED ROD HANGER
NOTE: SUSPENDED LOADS AT EACH HANGER
SHALL NOT EXCEED 350 LBS.
1 2
CONTRACTOR SHALL PROVIDE
FINAL DESIGN IN COMPLIANCE
WITH SEISMIC REQUIREMENTS
OUTLINED IN THE SPECIFICATIONS
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
CONSULTANTS:
CIVIL ENGINEER
OLSSON
550 ST LOUIS ST,
SPRINGFIELD, MO 65806
(417) 885-1736
MECH / ELEC ENGINEER
SPUR DESIGN
2519 MADISON AVE., STE. 100
KANSAS CITY, MO 64108
(913) 369-7200
FIRE PROTECTION ENGINEER
RATED ENGINEERING
609 S. KELLY AVENUE, SUITE H2
EDMOND, OK 73003
(405) 856-2965
INDUSTRIAL HYGENIST
RIVERFRONT SAFETY & HEALTH
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
TECH ENGINEER
ASPEN COMMUNICATIONS, LLC
7 KIJI-DAVA CIRCLE, SUITE A
PRESCOTT, AZ 86301
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STRUCT ENGINEER
STAND STRUCTURAL ENGINEERING
8234 ROBINSON STREET
OVERLAND PARK, KS 66204
(913) 214-2169
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Drawing #
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH REG. NO. BR 2171 EXP. 09/30/2023
ENGR REG. NO. F-17591 EXP. 02/29/2024
STAMP:
Drawing Number
Building Number
BUILDING 34 NOT SPRINKLERED. ALL OTHER BUILDINGS FULLY SPRINKLERED.
COMMISSIONING
ES2
13401 N. SANTA FE AVE
OKLAHOMA CITY, OK 73114
(405) 528-4500
CONTROLLED UNCLASSIFIED INFORMATION (CUI)
CONTROLLED UNCLASSIFIED INFORMATION (CUI)
C O
N T
R O
L L E
D U
N C
L A
S S
IF
IE
D I
N F
O R
M A
T
IO
N
C U
I)
/3
/2
:0
:4
P
M
100% BID DOCUMENTS
STRUCTURAL GENERAL NOTES
TJSPWS
BONHAM EHRM
INFRASTRUCTURE
UPGRADES
06/05/2023
549A4-21-700
BONHAM MEDICAL CENTER
1201 E. 9TH STREET
BONHAM, TX 75418
S-001
1,2,3,4,8,9,10,11,12,24,29,&34
03_Abbreviation Schedule
Abbreviation Abbreviation Name
+/- PLUS OR MINUS
ADDNL ADDITIONAL
ADJ ADJACENT
AESS ARCHITECTURALLY EXPOSED
STRUCTURAL STEEL
AFF ABOVE FINISHED FLOOR
ALT ALTERNATE
AR ANCHOR ROD
ARCH ARCHITECT OR ARCHITECTURAL
B/ BOTTOM OF
B/W BETWEEN
BLDG BUILDING
BLKG BLOCKING
BM BEAM
BOT BOTTOM
BRG BEARING
BWP BRACED WALL PANEL
CFS COLD FORMED STEEL
CHKD CHECKED
CIP CAST IN PLACE
CJ CONTROL JOINT
CJP COMPLETE JOINT PENETRATION
CL CENTERLINE
CLR CLEAR
COL COLUMN
CONC CONCRETE
CONN CONNECTION
CONT CONTINUOUS
CTR CENTER
db DIA OF REINF BAR, DIA OF BOLT
DBA DEFORMED BAR ANCHOR
DIA or Ø DIAMETER
DIAG DIAGONAL
DIR DIRECTION
DWL DOWEL
EA EACH
EE EXTENDED END
EJ EXPANSION JOINT
ELEV ELEVATION
EN EDGE NAILING
ENGR ENGINEER
EOD EDGE OF DECK
EOS EDGE OF SLAB
EQ EQUAL
EW EACH WAY
EXIST EXISTING
EXT EXTERIOR
FDN FOUNDATION
FLG FLANGE
FLR FLOOR
FS FAR SIDE
FTG FOOTING
FV FIELD VERIFY
GA GAUGE
GALV GALVANIZED
GB GRADE BEAM
GC GENERAL CONTRACTOR
HORIZ HORIZONTAL
HSA HEADED STUD ANCHOR
HSS HOLLOW STRUCTURAL SECTION
IF INSIDE FACE
INT INTERIOR
JST JOIST
K KIPS (1000 LBS)
LCE COMPRESSION EMBEDMENT LENGTH
LCS COMPRESSION LAP SPLICE LENGTH
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
LSH LONG SLOTTED HOLE
LTE TENSION EMBEDMENT LENGTH
LTS TENSION LAP SLICE LENGTH
LW LIGHTWEIGHT
MFCR MANUFACTURER
MTL METAL
NIC NOT IN CONTRACT
NS NEAR SIDE
NTS NOT TO SCALE
OC ON CENTER
OF OUTSIDE FACE
OPP OPPOSITE
OVS OVERSIZED
P/C PRECAST
PAF POWDER ACTUATED FASTENER
PAR PARALLEL
PEMB PRE-ENGINEERED METAL BUILDING
PEN PENETRATION
PERP PERPENDICULAR
PL PLATE
PLF POUNDS PER LINEAR FOOT
PREFAB PREFABRICATED
PRELIM PRELIMINARY
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
RC REINFORCED CONCRETE
RE: REFER TO
REINF REINFORCING
REQD REQUIRED
RF RIGID FRAME
SC SLIP CRITICAL
SDS SELF DRILLING SCREW
SIM SIMILAR
SLV SHORT LEG VERTICAL
SOG SLAB ON GRADE
SQ SQUARE
SS STAINLESS STEEL
STD STANDARD
STIR STIRRUPS
STL STEEL
SW SHEAR WALL
SYM SYMMETRIC
T&B TOP AND BOTTOM
T/ TOP OF
TRANS TRANSVERSE
TYP TYPICAL
UNO UNLESS NOTED OTHERWISE
VERT VERTICAL
W/ WITH
W/O WITHOUT
WF WIDE FLANGE
WP WORK POINT
WWR WELDED WIRE REINFORCEMENT
STRUCTURAL DESIGN CRITERIA (2021 IBC AND ASCE 7-16):
1. BUILDING OCCUPANCY RISK CATEGORY:
BUILDING 1:..........................................................CRITICAL - IV BUILDING 2:..........................................................CRITICAL - IV BUILDING 3:..........................................................ANCILLARY - II BUILDING 4:..........................................................CRITICAL - IV BUILDING 8:..........................................................ANCILLARY - II BUILDING 9:..........................................................ANCILLARY - II BUILDING 10:........................................................ANCILLARY - II BUILDING 11:........................................................CRITICAL - IV BUILDING 12:........................................................ANCILLARY - II BUILDING 24:........................................................ESSENTIAL - III BUILDING 29:........................................................ESSENTIAL - III BUIDLING 34:........................................................ANCILLARY - II
2. LIVE LOADS [UNIFORM (PSF) / POINT LOADS (KIPS)]:
-- ROOF:………………………………………...............20 PSF / 300#
-- OFFICES:………………….…..…............................50 PSF + 15 PSF
PARTITIONS / 2.0 K
-- UPPER LEVEL CORRIDORS................................80 PSF / 2.0 K
-- RESIDENTIAL CORRIDORS……………………...40 PSF
-- GROUND LEVEL SLAB ........................................100 PSF / 2.0 K
-- STAIRS ................................................................100 PSF / 300# -- LOBBIES ..............................................................100 PSF / 2.0 K --SERVER ROOM.....................................................200 PSF / 2.5 K
3. ROOF SNOW LOAD:
-- GROUND SNOW LOAD (Pg):……………………....20 PSF -- FLAT ROOF SNOW LOAD (Pf): ...........................15.4 PSF W/ DRIFT -- MIN UNIFORM ROOF SNOW LOAD (Pm):…...….20 PSF (NO DRIFT OR RAIN) -- RAIN ON SNOW SURCHARGE (Prs) ..................5.0 PSF -- SNOW EXPOSURE FACTOR (Ce):………………..1.0, EXPOSURE B & C -- SNOW LOAD IMPORTANCE FACTOR (Is):….......1.0 -- THERMAL FACTOR (Ct):……………………….......1.0
– SLOPE FACTOR (CS).............................................1.0
4. WIND DESIGN DATA:
-- BASIC WIND SPEED (3 SEC GUST):……………...116 MPH
– ASD WIND SPEED, V(ASD)....................................90 MPH
-- WIND EXPOSURE:…………………………………..C
-- GROUND ELEVATION ABOVE SEA LEVEL……..610 FT
-- DIRECTIONALITY FACTOR (Kd) ..........................0.85
5. EARTHQUAKE DESIGN DATA:
-- SEISMIC IMPORTANCE FACTOR (Ie):………......1.0 -- MAPPED SPECTRAL RESP ACCEL (Ss / S1):…..0.146 / 0.066
-- SITE CLASS:………………………………………….D
-- SPECTRAL RESPONSE COEFF (SDS / SD1):……0.156 / 0.106
-- SEISMIC DESIGN CATEGORY:
--RISK CATEGORY IV BUILDINGS:...........C
--RISK CATEGORY II/III BUILDINGS:.........B
--NON-STRUCT COMPONENT IMPORTANCE FACTOR (Ip).........1.5
STRUCTURAL GENERAL NOTES:
1. DESIGN AND CONSTRUCTION SHALL CONFORM TO THE "INTERNATIONAL
BUILDING CODE, 2021 EDITION" AS AMENDED AND ALL APPLICABLE VA DOCUMENTS,
INCLUDING HANDBOOK 18-8. REFER TO THE SPECIAL STRUCTURAL INSPECTION
NOTES FOR ADDITIONAL REQUIREMENTS.
2. CONTRACTOR TO VERIFY ALL DIMENSIONS, ELEVATIONS AND EXISTING
CONDITIONS AND REPORT ANY DISCREPANCIES TO THE ARCHITECT PRIOR TO
COMMENCING WORK.
3. IF DISCREPANCIES EXIST BETWEEN STRUCTURAL PLANS, ARCHITECTURAL
PLANS, OTHER PLANS, OR SPECIFICATIONS, THE CONTRACTOR OR
SUBCONTRACTOR SHALL PROVIDE A WRITTEN REQUEST FOR CLARIFICATION FROM
THE ARCHITECT AND/OR ENGINEER PRIOR TO PROCEEDING WITH THE WORK.
4. THE STRUCTURE IS DESIGNED TO BE SELF-SUPPORTING AND STABLE AFTER
THE BUILDING IS FULLY COMPLETED. IT IS SOLELY THE CONTRACTOR'S
RESPONSIBILITY TO EXECUTE AND DETERMINE FINAL ERECTION PROCEDURES,
SEQUENCING AND TO ENSURE THE SAFETY OF THE BUILDING AND ITS COMPONENT
PARTS DURING ERECTION. THIS INCLUDES WHATEVER SHORING, SHEETING,
TEMPORARY BRACING, GUYING OR TIE DOWNS WHICH MIGHT BE NECESSARY.
5. THE STRUCTURE AND FOUNDATIONS ARE NOT DESIGNED OR ANALYZED FOR
FUTURE EXPANSION.
6. FABRICATORS AND SUPPLIERS SHALL CLEARLY NOTE AND HIGHLIGHT CHANGES
MADE IN SHOP DRAWINGS, WHICH DO NOT COMPLY WITH THE CONTRACT
DOCUMENTS.
7. COLUMNS, BEAMS, JOISTS, OR TRUSSES SHALL NOT BE FIELD CUT OR TRIMMED
FOR ANY REASON WITHOUT THE WRITTEN APPROVAL OF THE
ARCHITECT/ENGINEER.
8. HOLES, PIPES, SLEEVES, ETC. NOT SHOWN ON THE DRAWINGS MUST BE
REVIEWED BY THE ARCHITECT/ENGINEER BEFORE PLACEMENT THROUGH
STRUCTURAL MEMBERS.
9. IF MECHANICAL AND ELECTRICAL EQUIPMENT SIZES, WEIGHTS, OR LOCATIONS
DO NOT COINCIDE WITH EQUIPMENT SHOWN ON THE PLANS, COORDINATE
ADJUSTMENTS WITH THE ARCHITECT.
10. NO AREA OF THE STRUCTURE SHALL BE LOADED WITH CONSTRUCTION
MATERIALS OR EQUIPMENT THAT EXCEEDS FINAL DESIGN CRITERIA.
11. BEAMS, COLUMNS, WALLS AND FOOTING CENTERS SHALL BE CENTERED UNDER
SUPPORTING MEMBERS (TYPICAL UNLESS NOTED OTHERWISE).
12. DELEGATED DESIGN - DEFERRED SUBMITTALS SHALL BE SIGNED/ SEALED
PRIOR TO SUBMITTAL FOR REVIEW. THESE INCLUDE:
A. NON-STRCTURAL COMPONENT SEISMIC BRACING
SUBMIT THESE SHOP DRAWINGS AND CALCULATIONS SEALED BY A STRUCTURAL
ENGINEER LICENSED TO PRACTICE IN THE JURISDICTION OF THE PROJECT SHALL
BE FURNISHED TO THE ENGINEER OF RECORD FOR REVIEW. CONTRACTOR SHALL
SUBMIT COPIES OF DEFERRED SUBMITTALS TO BUILDING DEPARTMENT AFTER
ARCH/ENG REVIEW.
13. TYPICAL DETAILS ARE SHOWN ON SHEETS DESIGNATED "S0XX". THE INCLUDED
TYPICAL DETAILS MAY OR MAY NOT BE CUT / REFERENCED ON PLANS OR
SECTIONS, BUT ARE TO BE USED AS APPLICABLE
SPECIAL INSPECTIONS:
1. PROVIDE SPECIAL STRUCTURAL INSPECTIONS AND VERIFICATIONS BY A THIRD
PARTY MEETING THE REQUIREMENTS OF CHAPTER 17 OF THE BUILDING CODE AND
THE BUILDING OFFICIAL.
2. SPECIAL INSPECTORS SHALL BE QUALIFIED AND FURNISH THEIR REPORTS IN A
TIMELY MANNER TO THE CONTRACTOR, BUILDING OFFICIALS, ARCHITECT, AND/OR
ENGINEER
3. SHOULD INSPECTOR IDENTIFY ANY DISCREPANCY, THEY SHALL NOTIFY
CONTRACTOR FIRST, AND THEN ARCHT/ ENGINEER IMMEDIATELY THEREAFTER IF
CORRECTIVE ACTION IS NEEDED.
4. SPECIAL INSPECTIONS AS REQUIRED BY CODE:
A. NON-STRUCTURAL COMPONENTS: SECTION 1705.14.2, CERTIFICATE OF
COMPLIANCE FOR SEISMIC QUALIFICATION SHALL BE SUBMITTED TO THE BUILDING
OFFICIAL. COMPLIANCE SHALL BE DETERMINED BY MEANS OF ANALYSIS, TESTING
AND/OR EXPERIENCE IN ACCORDANCE WITH ASCE 7-16 13.2.1 ITEM 2.
B. DESIGNATED SEISMIC SYSTEMS: SECTION 1705.14.3, CERTIFICATE OF
COMPLIANCE SHALL BE SUBMITTED TO THE BUILDING OFFICIAL. COMPLIANCE
SHALL BE DETERMINED BY MEANS AS DESCRIBED IN ASCE 7-16 13.2.2.
STRUCTURAL STEEL:
1. STRUCTURAL STEEL SHAPES AND PLATE MATERIAL REQUIREMENTS (TYPICAL
UNLESS NOTED OTHERWISE):
a. WIDE FLANGE SHAPES - ASTM A992 (FY = 50 KSI MIN.)
b. CHANNELS, ANGLES, AND PLATES: - ASTM A36 (FY = 36 KSI MIN)
c. ROUND HSS - ASTM A500, GR B (FY = 42 KSI)
d. RECTANGULAR HSS - ASTM A500, GR B (FY = 46 KSI)
e. PIPE - ASTM A53, GR B (FY = 35 KSI)
f. ANCHOR RODS - ASTM F1554 (FY = 36 KSI MIN.),
g. ADHESIVE ANCHORS - SIMPSON SET-3G, HILTI HIT-HY 200, OR
EQUIVALENT
2. STRUCTURAL STEEL SHALL BE NEW AND MEET THE 15TH EDITION A.I.S.C.
“SPECIFICATIONS FOR STRUCTURAL STEEL BUILDINGS AND BRIDGES”, AND THE
“CODE OF STANDARD PRACTICES FOR STEEL BUILDINGS AND BRIDGES”,
EXCLUDING SECTION 4.4.1.B.
3. THE STRUCTURAL STEEL FABRICATOR SHALL BE AN AISC QUALITY CERTIFIED
COMPANY FOR THE CATEGORY OF WORK IN THIS PROJECT OR PROVIDE A QUALITY
ASSURANCE PLAN AND SPECIAL INSPECTIONS AS DEFINED IN THE CODE.
4. USE STANDARD AISC FRAMING CONNECTIONS WITH A325-N BOLTS, F436
WASHERS, AND A563 HEAVY-HEX NUTS AS REQUIRED, UNLESS NOTED OTHERWISE.
5. STEEL BEAMS SHALL BE FABRICATED WITH MILL CAMBER UP.
6. WELDING SHALL CONFORM TO THE CURRENT AND APPLICABLE AWS STANDARDS
AND BE COMPLETED BY AN AWS CERTIFIED WELDER. ALL WELDS SHALL UTILIZE
E70xx ELECTRODES. SHOP DRAWINGS SHALL SHOW FIELD WELDS, AS
APPROPRIATE.
a. AWS D1.1 - STRUCTURAL WELDING CODE - STEEL
b. AWS D1.3 - STRUCTURAL WELDING CODE - SHEET STEEL
c. AWS D1.6 - STRUCTURAL WELDING CODE - STAINLESS STEEL
7. WELD SIZES SHALL BE INCREASED TO MEET THE REQUIRED EFFECTIVE THROAT
WIDTH IF GAPS EXIST AT THE FAYING SURFACE.
8. NO COLUMN OR BEAM SPLICES, UNLESS CLEARLY INDICATED ON THE
STRUCTURAL DRAWINGS, WILL BE ALLOWED WITHOUT WRITTEN APPROVAL OF THE
STRUCTURAL ENGINEER.
9. SEE ARCHITECTURAL PLANS FOR FIREPROOFING & FINISHING REQUIREMENTS,
AND COORDINATE STEEL PRIMING & COATINGS ACCORDINGLY.
10. GROUT WHERE INDICATED ON PLANS AT BASE PLATES SHALL BE NON-METALLIC
NON-SHRINK WITH A MINIMUM COMPRESSIVE STRENGTH OF 6000 PSI AT 28 DAYS
CONFORMING TO ASTM C1107
11. ALL POST-INSTALLED ANCHORS WHERE NOTED SHALL BE MANUFACTURED BY
SIMPSON STRONG-TIE OR HILTI, INC. AND INSTALLED PER MANUFACTURER'S
SPECIFICATIONS. SUBSTITUTIONS SHALL BE SUBMITTED FOR REVIEW AND
APPROVAL WITH APPROPRIATE IC-ES EVALUATION REPORTS.
12. ALL STEEL AND ASSOCIATED FASTENERS NOT PROTECTED FROM WEATHER OR
WHOLLY WITHIN A CONDITIONED SPACE (INCLUDING ALL MASONRY LINTELS) SHALL
BE HOT DIPPED GALVANIZED PER ASTM A123.
3/4" = 1'-0"
CONCEPTUAL EQUIPMENT BRACING AND ANCHORAGE DETAILS
1 1/2" = 1'-0"
CONCEPTUAL HANGER ATTACHMENT DETAIL2
SPUR #: 2216No. REVISION DESCRIPTION DATE
06/05/2307/07/2023 07/07/2023
MAX WT:
160 LB
MAX WT:
160 LB
MAX WT:
570 LB
MAX WT:
570 LB
MAX WT:
160 LB
MAX WT:
160 LB
SHEET NOTES:
A. REFERENCE SHEET S-00x FOR STRUCTURAL GENERAL NOTES. REVIEW NOTES & DETAILS
FOR APPLICABILITY.
B. SEE ARCHITECTURAL DRAWING FOR DETAILS & DIMENSIONS NOT SHOWN. CONTRACTOR TO FIELD
VERIFY ALL DIMENSIONS
C. ROOF PENETRATIONS FOR NEW ROOFTOP EQUIPMENT SHALL NOT CUT THROUGHT EXIST STEEL OR
CONC BEAMS AND JOISTS. CONTRACTOR TO COORD PENETRATIONS ACCORDINGLY.
PLAN NOTES:
ROOF STRUCTURE IS 2" PRECAST CONCRETE PLANKS. ANCHOR EQUIPMENT
RAILS W/ 1/4" TAPCON SCREWS x 1 1/2" LONG @ 12” AROUND THE RAIL BASE
ROOF STRUCTURE IS UNKNOWN. CONTRACTOR TO COORDINATE EXISTING ROOF
STRUCTURE W/ STRUCTURAL ENGINEER DURING CONSTRUCTION. ATTACHMENT
WILL LIKELY BE PER PLAN NOTE 3 OR 4 BELOW
ROOF STRUCTURE IS 1.5" 20GA TYPE B DECK. MAX SPAN BETWEEN SUPPORTS
IS 6'-4". ANCHOR EQUIPMENT RAILS TO METAL DECK WITH #12 SCREWS @ 6" OC
AROUND PERIMETER OF RAILS. RAIL LENGTH SHALL BE "AS REQD", BUT SHALL
BE 2'-0" LONG MIN.
ROOF STRUCTURE IS ONE WAY CONCRETE JOIST CONSTRUCTION.
CONTRACTOR TO CONFIRM THAT JOIST CONSTRUCTION. SLAB THICKNESS IS
ASSUMED TO BE 2" THICK. CONTACT ENGINEER SLAB THICKNESS ARE SMALLER
THAN PRESUMED. ANCHOR EQUIPMENT RAILS TO CONC W/ 1/4" DIA TAPCON
SCREWS X 1.5" LONG @ 12" OC AROUND PERIMETER OF RAIL BASE.
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
CONSULTANTS:
CIVIL ENGINEER
OLSSON
550 ST LOUIS ST,
SPRINGFIELD, MO 65806
(417) 885-1736
MECH / ELEC ENGINEER
SPUR DESIGN
2519 MADISON AVE., STE. 100
KANSAS CITY, MO 64108
(913) 369-7200
FIRE PROTECTION ENGINEER
RATED ENGINEERING
609 S. KELLY AVENUE, SUITE H2
EDMOND, OK 73003
(405) 856-2965
INDUSTRIAL HYGENIST
RIVERFRONT SAFETY & HEALTH
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
TECH ENGINEER
ASPEN COMMUNICATIONS, LLC
7 KIJI-DAVA CIRCLE, SUITE A
PRESCOTT, AZ 86301
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STRUCT ENGINEER
STAND STRUCTURAL ENGINEERING
8234 ROBINSON STREET
OVERLAND PARK, KS 66204
(913) 214-2169
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Drawing #
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH REG. NO. BR 2171 EXP. 09/30/2023
ENGR REG. NO. F-17591 EXP. 02/29/2024
STAMP:
Drawing Number
Building Number
BUILDING 34 NOT SPRINKLERED. ALL OTHER BUILDINGS FULLY SPRINKLERED.
COMMISSIONING
ES2
13401 N. SANTA FE AVE
OKLAHOMA CITY, OK 73114
(405) 528-4500
CONTROLLED UNCLASSIFIED INFORMATION (CUI)
CONTROLLED UNCLASSIFIED INFORMATION (CUI)
C O
N T
R O
L L E
D U
N C
L A
S S
IF
IE
D I
N F
O R
M A
T
IO
N
C U
I)
/3
/2
:0
:4
P
M
100% BID DOCUMENTS
BUILDINGS 1 ROOF PLAN
TJSPWS
BONHAM EHRM
INFRASTRUCTURE
UPGRADES
06/05/2023
549A4-21-700
BONHAM MEDICAL CENTER
1201 E. 9TH STREET
BONHAM, TX 75418
S-201
1,2,3,4,8,9,10,11,12,24,29,&34
N
1/16" = 1'-0"
BLDG 1 - ROOF PLAN
No. REVISION DESCRIPTION DATE
MAX WT:
160 LB
MAX WT:
160 LB
MAX WT:
160 LB
MAX WT:
160 LB
MAX WT:
160 LB
SHEET NOTES:
A. REFERENCE SHEET S-00x FOR STRUCTURAL GENERAL NOTES. REVIEW NOTES & DETAILS
FOR APPLICABILITY.
B. SEE ARCHITECTURAL DRAWING FOR DETAILS & DIMENSIONS NOT SHOWN. CONTRACTOR TO FIELD
VERIFY ALL DIMENSIONS
C. ROOF PENETRATIONS FOR NEW ROOFTOP EQUIPMENT SHALL NOT CUT THROUGHT EXIST STEEL OR
CONC BEAMS AND JOISTS. CONTRACTOR TO COORD PENETRATIONS ACCORDINGLY.
PLAN NOTES:
ROOF STRUCTURE IS 2" PRECAST CONCRETE PLANKS. ANCHOR EQUIPMENT
RAILS W/ 1/4" TAPCON SCREWS x 1 1/2" LONG @ 12” AROUND THE RAIL BASE
ROOF STRUCTURE IS UNKNOWN. CONTRACTOR TO COORDINATE EXISTING ROOF
STRUCTURE W/ STRUCTURAL ENGINEER DURING CONSTRUCTION. ATTACHMENT
WILL LIKELY BE PER PLAN NOTE 3 OR 4 BELOW
ROOF STRUCTURE IS 1.5" 20GA TYPE B DECK. MAX SPAN BETWEEN SUPPORTS
IS 6'-4". ANCHOR EQUIPMENT RAILS TO METAL DECK WITH #12 SCREWS @ 6" OC
AROUND PERIMETER OF RAILS. RAIL LENGTH SHALL BE "AS REQD", BUT SHALL
BE 2'-0" LONG MIN.
ROOF STRUCTURE IS ONE WAY CONCRETE JOIST CONSTRUCTION.
CONTRACTOR TO CONFIRM THAT JOIST CONSTRUCTION. SLAB THICKNESS IS
ASSUMED TO BE 2" THICK. CONTACT ENGINEER SLAB THICKNESS ARE SMALLER
THAN PRESUMED. ANCHOR EQUIPMENT RAILS TO CONC W/ 1/4" DIA TAPCON
SCREWS X 1.5" LONG @ 12" OC AROUND PERIMETER OF RAIL BASE.
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
CONSULTANTS:
CIVIL ENGINEER
OLSSON
550 ST LOUIS ST,
SPRINGFIELD, MO 65806
(417) 885-1736
MECH / ELEC ENGINEER
SPUR DESIGN
2519 MADISON AVE., STE. 100
KANSAS CITY, MO 64108
(913) 369-7200
FIRE PROTECTION ENGINEER
RATED ENGINEERING
609 S. KELLY AVENUE, SUITE H2
EDMOND, OK 73003
(405) 856-2965
INDUSTRIAL HYGENIST
RIVERFRONT SAFETY & HEALTH
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
TECH ENGINEER
ASPEN COMMUNICATIONS, LLC
7 KIJI-DAVA CIRCLE, SUITE A
PRESCOTT, AZ 86301
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STRUCT ENGINEER
STAND STRUCTURAL ENGINEERING
8234 ROBINSON STREET
OVERLAND PARK, KS 66204
(913) 214-2169
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Drawing #
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH REG. NO. BR 2171 EXP. 09/30/2023
ENGR REG. NO. F-17591 EXP. 02/29/2024
STAMP:
Drawing Number
Building Number
BUILDING 34 NOT SPRINKLERED. ALL OTHER BUILDINGS FULLY SPRINKLERED.
COMMISSIONING
ES2
13401 N. SANTA FE AVE
OKLAHOMA CITY, OK 73114
(405) 528-4500
CONTROLLED UNCLASSIFIED INFORMATION (CUI)
CONTROLLED UNCLASSIFIED INFORMATION (CUI)
C O
N T
R O
L L E
D U
N C
L A
S S
IF
IE
D I
N F
O R
M A
T
IO
N
C U
I)
/3
/2
:0
:4
P
M
100% BID DOCUMENTS
BUILDINGS 2 & 3 ROOF PLANS
TJSPWS
BONHAM EHRM
INFRASTRUCTURE
UPGRADES
06/05/2023
549A4-21-700
BONHAM MEDICAL CENTER
1201 E. 9TH STREET
BONHAM, TX 75418
S-202
1,2,3,4,8,9,10,11,12,24,29,&34
N
1/16" = 1'-0"
BLDG 2 - ROOF PLAN1
N
1/16" = 1'-0"
BLDG 3 - ROOF PLAN2
LEVEL 1
ROOF
LEVEL 2 ROOF
PENTHOUSE
LEVEL 1
ROOF
LEVEL 1 ROOF
LEVEL 1 ROOF
OVER HANG
LEVEL 1 ROOF
LEVEL 2 ROOF
SLOPED CANOPY
LEVEL 1 ROOF
LEVEL 1 ROOF LOWER
LEVEL 1 ROOF
LEVEL 2 ROOF
SLOPED CANOPY
MAX WT:
160 LB2
MAX WT:
160 LB2
MAX WT:
160 LB 2
MAX WT:
160 LB 2
SHEET NOTES:
A. REFERENCE SHEET S-00x FOR STRUCTURAL GENERAL NOTES. REVIEW NOTES & DETAILS
FOR APPLICABILITY.
B. SEE ARCHITECTURAL DRAWING FOR DETAILS & DIMENSIONS NOT SHOWN. CONTRACTOR TO FIELD
VERIFY ALL DIMENSIONS
C. ROOF PENETRATIONS FOR NEW ROOFTOP EQUIPMENT SHALL NOT CUT THROUGHT EXIST STEEL OR
CONC BEAMS AND JOISTS. CONTRACTOR TO COORD PENETRATIONS ACCORDINGLY.
PLAN NOTES:
ROOF STRUCTURE IS 2" PRECAST CONCRETE PLANKS. ANCHOR EQUIPMENT
RAILS W/ 1/4" TAPCON SCREWS x 1 1/2" LONG @ 12” AROUND THE RAIL BASE
ROOF STRUCTURE IS UNKNOWN. CONTRACTOR TO COORDINATE EXISTING ROOF
STRUCTURE W/ STRUCTURAL ENGINEER DURING CONSTRUCTION. ATTACHMENT
WILL LIKELY BE PER PLAN NOTE 3 OR 4 BELOW
ROOF STRUCTURE IS 1.5" 20GA TYPE B DECK. MAX SPAN BETWEEN SUPPORTS
IS 6'-4". ANCHOR EQUIPMENT RAILS TO METAL DECK WITH #12 SCREWS @ 6" OC
AROUND PERIMETER OF RAILS. RAIL LENGTH SHALL BE "AS REQD", BUT SHALL
BE 2'-0" LONG MIN.
ROOF STRUCTURE IS ONE WAY CONCRETE JOIST CONSTRUCTION.
CONTRACTOR TO CONFIRM THAT JOIST CONSTRUCTION. SLAB THICKNESS IS
ASSUMED TO BE 2" THICK. CONTACT ENGINEER SLAB THICKNESS ARE SMALLER
THAN PRESUMED. ANCHOR EQUIPMENT RAILS TO CONC W/ 1/4" DIA TAPCON
SCREWS X 1.5" LONG @ 12" OC AROUND PERIMETER OF RAIL BASE.
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
CONSULTANTS:
CIVIL ENGINEER
OLSSON
550 ST LOUIS ST,
SPRINGFIELD, MO 65806
(417) 885-1736
MECH / ELEC ENGINEER
SPUR DESIGN
2519 MADISON AVE., STE. 100
KANSAS CITY, MO 64108
(913) 369-7200
FIRE PROTECTION ENGINEER
RATED ENGINEERING
609 S. KELLY AVENUE, SUITE H2
EDMOND, OK 73003
(405) 856-2965
INDUSTRIAL HYGENIST
RIVERFRONT SAFETY & HEALTH
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
TECH ENGINEER
ASPEN COMMUNICATIONS, LLC
7 KIJI-DAVA CIRCLE, SUITE A
PRESCOTT, AZ 86301
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STRUCT ENGINEER
STAND STRUCTURAL ENGINEERING
8234 ROBINSON STREET
OVERLAND PARK, KS 66204
(913) 214-2169
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Drawing #
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH REG. NO. BR 2171 EXP. 09/30/2023
ENGR REG. NO. F-17591 EXP. 02/29/2024
STAMP:
Drawing Number
Building Number
BUILDING 34 NOT SPRINKLERED. ALL OTHER BUILDINGS FULLY SPRINKLERED.
COMMISSIONING
ES2
13401 N. SANTA FE AVE
OKLAHOMA CITY, OK 73114
(405) 528-4500
CONTROLLED UNCLASSIFIED INFORMATION (CUI)
CONTROLLED UNCLASSIFIED INFORMATION (CUI)
C O
N T
R O
L L E
D U
N C
L A
S S
IF
IE
D I
N F
O R
M A
T
IO
N
C U
I)
/3
/2
:0
:4
P
M
100% BID DOCUMENTS
BUILDINGS 4, 9, 10, & 12 ROOF PLANS
TJSPWS
BONHAM EHRM
INFRASTRUCTURE
UPGRADES
06/05/2023
549A4-21-700
BONHAM MEDICAL CENTER
1201 E. 9TH STREET
BONHAM, TX 75418
S-203
1,2,3,4,8,9,10,11,12,24,29,&34
N
1/16" = 1'-0"
BLDG 4 - ROOF PLAN1
N
1/16" = 1'-0"
BLDG 12 - ROOF PLAN2
N
1/16" = 1'-0"
BLDG 10 - ROOF PLAN4
N
1/16" = 1'-0"
BLDG 9 - ROOF PLAN
LEVEL 1 ROOF
SLOPED
CANOPY
SLOPED
CONNECTING CORRIDOR
LEVEL 2 ROOF
LEVEL 2 ROOF
LEVEL 2 ROOF
LEVEL 2 ROOF UPPER
LEVEL 2 ROOF UPPER
LEVEL 2 ROOF UPPER
LEVEL 2 ROOF UPPER
LEVEL 2 ROOF UPPER
LEVEL 1 ROOF
MAX WT:
160 LB
MAX WT:
160 LB
SHEET NOTES:
A. REFERENCE SHEET S-00x FOR STRUCTURAL GENERAL NOTES. REVIEW NOTES & DETAILS
FOR APPLICABILITY.
B. SEE ARCHITECTURAL DRAWING FOR DETAILS & DIMENSIONS NOT SHOWN. CONTRACTOR TO FIELD
VERIFY ALL DIMENSIONS
C. ROOF PENETRATIONS FOR NEW ROOFTOP EQUIPMENT SHALL NOT CUT THROUGHT EXIST STEEL OR
CONC BEAMS AND JOISTS. CONTRACTOR TO COORD PENETRATIONS ACCORDINGLY.
PLAN NOTES:
ROOF STRUCTURE IS 2" PRECAST CONCRETE PLANKS. ANCHOR EQUIPMENT
RAILS W/ 1/4" TAPCON SCREWS x 1 1/2" LONG @ 12” AROUND THE RAIL BASE
ROOF STRUCTURE IS UNKNOWN. CONTRACTOR TO COORDINATE EXISTING ROOF
STRUCTURE W/ STRUCTURAL ENGINEER DURING CONSTRUCTION. ATTACHMENT
WILL LIKELY BE PER PLAN NOTE 3 OR 4 BELOW
ROOF STRUCTURE IS 1.5" 20GA TYPE B DECK. MAX SPAN BETWEEN SUPPORTS
IS 6'-4". ANCHOR EQUIPMENT RAILS TO METAL DECK WITH #12 SCREWS @ 6" OC
AROUND PERIMETER OF RAILS. RAIL LENGTH SHALL BE "AS REQD", BUT SHALL
BE 2'-0" LONG MIN.
ROOF STRUCTURE IS ONE WAY CONCRETE JOIST CONSTRUCTION.
CONTRACTOR TO CONFIRM THAT JOIST CONSTRUCTION. SLAB THICKNESS IS
ASSUMED TO BE 2" THICK. CONTACT ENGINEER SLAB THICKNESS ARE SMALLER
THAN PRESUMED. ANCHOR EQUIPMENT RAILS TO CONC W/ 1/4" DIA TAPCON
SCREWS X 1.5" LONG @ 12" OC AROUND PERIMETER OF RAIL BASE.
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
CONSULTANTS:
CIVIL ENGINEER
OLSSON
550 ST LOUIS ST,
SPRINGFIELD, MO 65806
(417) 885-1736
MECH / ELEC ENGINEER
SPUR DESIGN
2519 MADISON AVE., STE. 100
KANSAS CITY, MO 64108
(913) 369-7200
FIRE PROTECTION ENGINEER
RATED ENGINEERING
609 S. KELLY AVENUE, SUITE H2
EDMOND, OK 73003
(405) 856-2965
INDUSTRIAL HYGENIST
RIVERFRONT SAFETY & HEALTH
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
TECH ENGINEER
ASPEN COMMUNICATIONS, LLC
7 KIJI-DAVA CIRCLE, SUITE A
PRESCOTT, AZ 86301
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STRUCT ENGINEER
STAND STRUCTURAL ENGINEERING
8234 ROBINSON STREET
OVERLAND PARK, KS 66204
(913) 214-2169
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Drawing #
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH REG. NO. BR 2171 EXP. 09/30/2023
ENGR REG. NO. F-17591 EXP. 02/29/2024
STAMP:
Drawing Number
Building Number
BUILDING 34 NOT SPRINKLERED. ALL OTHER BUILDINGS FULLY SPRINKLERED.
COMMISSIONING
ES2
13401 N. SANTA FE AVE
OKLAHOMA CITY, OK 73114
(405) 528-4500
CONTROLLED UNCLASSIFIED INFORMATION (CUI)
CONTROLLED UNCLASSIFIED INFORMATION (CUI)
C O
N T
R O
L L E
D U
N C
L A
S S
IF
IE
D I
N F
O R
M A
T
IO
N
C U
I)
/3
/2
:0
:4
P
M
100% BID DOCUMENTS
BUILDING 24 ROOF PLAN
TJSPWS
BONHAM EHRM
INFRASTRUCTURE
UPGRADES
06/05/2023
549A4-21-700
BONHAM MEDICAL CENTER
1201 E. 9TH STREET
BONHAM, TX 75418
S-204
1,2,3,4,8,9,10,11,12,24,29,&34
N 1/16" = 1'-0"
BLDG 24 - ROOF PLAN1
| Sheets |
| S-001 - STRUCTURAL GENERAL NOTES |
| S-201 - BUILDINGS 1 ROOF PLAN |
| S-202 - BUILDINGS 2 & 3 ROOF PLANS |
| S-203 - BUILDINGS 4, 9, 10, & 12 ROOF PLANS |
| S-204 - BUILDING 24 ROOF PLAN |
File details come from the government source that posted it. Updated .