Attachment - 01 General Drawings_100percent Bid Docs.pdf

PDF 992 KB Posted

Attached to
Z2DA--EHRM Bonham, TX Construction 549A4-21-700 EHRM Construction (VA-23-00092679)
Solicitation number
36C77624B0007_1
Issued by

About this file

This document set includes construction drawings and specifications for infrastructure upgrades at the Bonham VA Medical Center in Bonham, Texas. The project involves renovations and repairs to buildings 1, 2, 3, 4, 8, 9, 10, 11, 12, 24, 29, and 34. Work includes upgrades to mechanical, electrical, plumbing, fire protection, and telecommunications systems. Infection control protocols are specified, requiring barriers and negative air containment for dust-generating activities. Drawings depict demolition plans, site utilities, structural details, architectural floor plans, and schematics for fire alarms, sprinklers and HVAC, electrical, telecom, and security systems. Consultants include Olsson for civil engineering and Spur Design for architectural/engineering services. The construction manager is ES2. The estimated award date is July 2023.

View the file

Other files

File Type Posted
Attachment 56 - Abstract of Bids OF 1419 - CONST-Bonham - Signed.pdf PDF
Attachment 57 - Abstract of Bids OF 1419 A - CONST-Bonham.pdf PDF
36C77624B0007 0012.docx DOCX document
Attachment- 54 Sheet GS020 DETAILS.pdf PDF
Attachment- 53 Sheet GS019 EROSION CONTROL DETAILS.pdf PDF
Attachment- 51 TR Matrix Bonham.pdf PDF
Attachment- 55 Solicitation-RFIs-Tech Responses 36C77624B0007.pdf PDF
Attachment- 52 Hydrology Map.pdf PDF
36C77624B0007 0011.pdf PDF
36C77624B0007 0010.pdf PDF
36C77624B0007 0009.pdf PDF
Att 50 CLARIFICATION of Site Visit-Duct banks not available for use.pdf PDF
36C77624B0007 0008.pdf PDF
36C77624B0007 0007.docx DOCX document
Attachment - 49 S04-sign in sheet-pg 1 Site Visit Bonham TX 1.9.24.pdf PDF
36C77624B0007 0006.docx DOCX document
36C77624B0007 0005.pdf PDF
Attachment - 48 S04-sign in sheet Site Visit Bonham TX 1.9.24.pdf PDF
Attachment - 47 Clarifications-Additional Technical Questions.pdf PDF
36C77624B0007 0004.pdf PDF
Attachment - 46 Answers to Solicitation-RFIs-MISSING SECTION-36C77624B0007_1.pdf PDF
36C77624B0007 0003.pdf PDF
Attachment- 29 Bonham VA - Geotech Rpt 3-30-16-For Soil.pdf PDF
Attachment- 35 01 Bonham EHRM- Narrative.pdf PDF
Attachment- 36 01 Environmental Narrative.pdf PDF
Attachment- 44 Station Pictures for electrical.pdf PDF
Attachment- 28 Bonham EHRM- ICRA Form.pdf PDF
Attachment- 41 07 Electrical Narrative.pdf PDF
Attachment- 30 SPCC-PIPP Plan VANTHCS_Bonham.pdf PDF
Attachment- 38 03 Structural Narrative.pdf PDF
Attachment- 27 Answers to Solicitation-RFIs-36C77624B0007_1.pdf PDF
Attachment- 42 08 Telecom Narrative.pdf PDF
Attachment- 43 09 Security Narrative.pdf PDF
36C77624B0007 0002.pdf PDF
Attachment- 37 02 Civil Narrative.pdf PDF
Attachment- 32 V2 549A4-21-700 100 Bid Document Specifications.pdf PDF
Attachment- 45 IT Closet Proposed lay down.pdf PDF
Attachment- 39 05 Fire Protection Narrative.pdf PDF
Attachment- 34 00 General Narrative.pdf PDF
Attachment- 33 AE Physical Security Risk Mitigation Design Guidance.pdf PDF
Attachment- 31 site plan fiber runs Bonham.pdf PDF
Attachment- 40 06 Mechanical Narrative.pdf PDF
36C77624B0007 0001.pdf PDF
36C77624B0007_1-tech questions date updated.pdf PDF
36C77624B0007_1.pdf PDF
Attachment - 13 Asbestos 3_ VA Checklist_Environ.pdf PDF
Attachment - 03 Civil Drawings_100percent Bid Docs.pdf PDF
Attachment - 24 Limitations on Subcontracting - Construction.pdf PDF
Attachment - 16 CABINET DIMENSIONAL DATA.pdf PDF
Attachment - 05 Architectural Drawings_100percent Bid Docs.pdf PDF
Show 40 more

Latest 50 of 70 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

CONSULTANTS:

U.S. DEPARTMENT OF VETERANS AFFAIRS

CIVIL ENGINEER

OLSSON

550 ST LOUIS ST,

SPRINGFIELD, MO 65806

(417) 885-1736

MECH / ELEC ENGINEER

SPUR DESIGN

2519 MADISON AVE., STE. 100

KANSAS CITY, MO 64108

(913) 369-7200

FIRE PROTECTION ENGINEER

RATED ENGINEERING

609 S. KELLY AVENUE, SUITE H2

EDMOND, OK 73003

(405) 856-2965

INDUSTRIAL HYGENIST

RIVERFRONT SAFETY & HEALTH

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

TECH ENGINEER

ASPEN COMMUNICATIONS, LLC

7 KIJI-DAVA CIRCLE, SUITE A

PRESCOTT, AZ 86301

(928) 774-0992

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STRUCT ENGINEER

STAND STRUCTURAL ENGINEERING

8234 ROBINSON STREET

OVERLAND PARK, KS 66204

(913) 214-2169

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Drawing #

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH REG. NO. BR 2171 EXP. 09/30/2023

ENGR REG. NO. F-17591 EXP. 02/29/2024

The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.

STAMP:

Drawing Number

Building Number

BUILDING 34 NOT SPRINKLERED. ALL OTHER BUILDINGS FULLY SPRINKLERED.

COMMISSIONING

ES2

13401 N. SANTA FE AVE

OKLAHOMA CITY, OK 73114

(405) 528-4500

CONTROLLED UNCLASSIFIED INFORMATION (CUI)

CONTROLLED UNCLASSIFIED INFORMATION (CUI)

C O

N T

R O

L L E

D U

N C

L A

S S

IF

IE

D I

N F

O R

M A

T

IO

N

C U

I)

/5

/2

:1

:0

A

M

100% BID DOCUMENTS

BONHAM EHRM INFRASTRUCTURE

UPGRADES

VA PROJECT NUMBER: 549A4-21-700

BONHAM VA MEDICAL CENTER

1201 E. 9TH STREET

BONHAM, TX 75418

100% BID DOCUMENTS

COVER SHEET

NSM 1 OF 229AJS

BONHAM EHRM

INFRASTRUCTURE

UPGRADES

07/07/2023

549A4-21-700

BONHAM VA MEDICAL CENTER

1201 E. 9TH STREET

BONHAM, TX 75418

GI000

SPUR #: 2216

NN

LOCATION

PLAN

AREA

PLAN

PROJECT LOCATION

B1

B29

B24

B2 B3

B4

B12

B11 B8

B34

B9B10

E 9TH ST

L Y

N N

S T

L

IP

S C

O M

B B

L V

D

E 8TH ST

E 7TH ST

E 10TH ST

E 11TH ST

E E

L M

S T

L Y

N N

S T

E 9TH ST

V E

TE

R

A N

S B

LV

D

SEVEN OAKS RD

1, 2, 3, 4, 8, 9, 10, 11, 12, 24, 29, & 34

No. REVISION DESCRIPTION DATE th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

CONSULTANTS:

CIVIL ENGINEER

OLSSON

550 ST LOUIS ST,

SPRINGFIELD, MO 65806

(417) 885-1736

MECH / ELEC ENGINEER

SPUR DESIGN

2519 MADISON AVE., STE. 100

KANSAS CITY, MO 64108

(913) 369-7200

FIRE PROTECTION ENGINEER

RATED ENGINEERING

609 S. KELLY AVENUE, SUITE H2

EDMOND, OK 73003

(405) 856-2965

INDUSTRIAL HYGENIST

RIVERFRONT SAFETY & HEALTH

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

TECH ENGINEER

ASPEN COMMUNICATIONS, LLC

7 KIJI-DAVA CIRCLE, SUITE A

PRESCOTT, AZ 86301

(928) 774-0992

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STRUCT ENGINEER

STAND STRUCTURAL ENGINEERING

8234 ROBINSON STREET

OVERLAND PARK, KS 66204

(913) 214-2169

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Drawing #

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH REG. NO. BR 2171 EXP. 09/30/2023

ENGR REG. NO. F-17591 EXP. 02/29/2024

The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.

STAMP:

Drawing Number

Building Number

BUILDING 34 NOT SPRINKLERED. ALL OTHER BUILDINGS FULLY SPRINKLERED.

COMMISSIONING

ES2

13401 N. SANTA FE AVE

OKLAHOMA CITY, OK 73114

(405) 528-4500

CONTROLLED UNCLASSIFIED INFORMATION (CUI)

CONTROLLED UNCLASSIFIED INFORMATION (CUI)

C O

N T

R O

L L E

D U

N C

L A

S S

IF

IE

D I

N F

O R

M A

T

IO

N

C U

I)

/5

/2

:1

:0

A

M

100% BID DOCUMENTS

SHEET INDEX

NSM 2 OF 229AJS

BONHAM EHRM

INFRASTRUCTURE

UPGRADES

07/07/2023

549A4-21-700

BONHAM VA MEDICAL CENTER

1201 E. 9TH STREET

BONHAM, TX 75418

GI001

SPUR #: 2216

SHEET INDEX

SEQUENCE NUMBER SHEET NAME

[01] GENERAL

1 GI000 COVER SHEET

2 GI001 SHEET INDEX

3 GI002 GENERAL INFORMATION

4 GI003 ICRA CONSTRUCTION DETAILS

[02] HAZARDOUS MATERIALS

5 HA010 BUILDING 1 - BASEMENT - ENVIRONMENTAL HAZARDS

6 HA011 BUILDING 1 - FLOOR 1 - ENVIRONMENTAL HAZARDS

7 HA012 BUILDING 1 - FLOOR 2 - ENVIRONMENTAL HAZARDS

8 HA013 BUILDING 1 - FLOOR 3 - ENVIRONMENTAL HAZARDS

9 HA014 BUILDING 1 - FLOOR 4 - ENVIRONMENTAL HAZARDS

10 HA015 BUILDING 1 - FLOOR 5 - ENVIRONMENTAL HAZARDS

11 HA021 BUILDING 2 - FLOOR 1 - ENVIRONMENTAL HAZARDS

12 HA022 BUILDING 2 - FLOOR 2 - ENVIRONMENTAL HAZARDS

13 HA023 BUILDING 2 - FLOOR 3 - ENVIRONMENTAL HAZARDS

14 HA024 BUILDING 2 - FLOOR 4 - ENVIRONMENTAL HAZARDS

15 HA031 BUILDING 3 - FLOOR 1 - ENVIRONMENTAL HAZARDS

16 HA032 BUILDING 3 - FLOOR 2 - ENVIRONMENTAL HAZARDS

17 HA041 BUILDING 4 - ENVIRONMENTAL HAZARDS

18 HA081 BUILDING 8 - ENVIRONMENTAL HAZARDS

19 HA091 BUILDING 9 - ENVIRONMENTAL HAZARDS

20 HA101 BUILDING 10 - FLOOR 1 - ENVIRONMENTAL HAZARDS

21 HA111 BUILDING 11 - FLOOR 1 - ENVIRONMENTAL HAZARDS

22 HA121 BUILDING 12 - FLOOR 1 - ENVIRONMENTAL HAZARDS

23 HA122 BUILDING 12 - FLOOR 2 - ENVIRONMENTAL HAZARDS

24 HA123 BUILDING 12 - ROOF - ENVIRONMENTAL HAZARDS

25 HA241 BUILDING 24 - ROOF - ENVIRONMENTAL HAZARDS

26 HA291 BUILDING 29 - ENVIRONMENTAL HAZARDS

27 HA340 BUILDING 34 - FLOOR 1 - ENVIRONMENTAL HAZARDS

[03] CIVIL

28 GS001 GENERAL LAYOUT PLAN

29 GS002 OVERALL SITE AND DEMOLITION PLAN

30 GS003 SITE AND DEMOLITION PLAN 1

31 GS004 SITE AND DEMOLITION PLAN 2

32 GS005 SITE AND DEMOLITION PLAN 3

33 GS006 SITE AND DEMOLITION PLAN 4

34 GS007 GRADING PLAN 1

35 GS008 GRADING PLAN 2

36 GS009 GRADING PLAN 3

37 GS010 GRADING PLAN 4

38 GS011 UTILITY PLAN 1

39 GS012 UTILITY PLAN 2

40 GS013 UTILITY PLAN 3

41 GS014 UTILITY PLAN 4

42 GS015 EROSION CONTROL PLAN 1

43 GS016 EROSION CONTROL PLAN 2

44 GS017 EROSION CONTROL PLAN 3

45 GS018 EROSION CONTROL PLAN 4

46 GS019 EROSION CONTROL DETAILS

47 GS020 DETAILS

[04] STRUCTURAL

48 S-001 STRUCTURAL GENERAL NOTES

49 S-201 BUILDING 1 ROOF PLAN

50 S-202 BUILDINGS 2 & 3 ROOF PLANS

51 S-203 BUILDINGS 4, 9, 10 & 12 ROOF PLANS

52 S-204 BUILDING 24 ROOF PLAN

SHEET INDEX

SEQUENCE NUMBER SHEET NAME

[05] ARCHITECTURAL

53 A-101 BUILDING 1 - REFERENCE PLANS

54 A-102 BUILDING 1 - REFERENCE PLANS

55 A-103 BUILDING 2 - REFERENCE PLANS

56 A-104 BUILDING 2 - REFERENCE PLANS

57 A-105 BUILDINGS 3, 4, 8, & 9 - REFERENCE PLANS

58 A-106 BUILDINGS 10, 11, & 12 - REFERENCE PLANS

59 A-107 BUILDING 24 - REFERENCE PLAN

60 A-108 BUILDING 24 - REFERENCE PLAN

61 A-109 BUILDING 29 - REFERENCE PLAN

62 AE101 BLDG 1 - BASEMENT - ENLARGED PLANS

63 AE102 BLDG 1 - LEVEL ONE - ENLARGED PLANS

64 AE103 BLDG 1 - LEVEL TWO, LEVEL THREE, & LEVEL FOUR - ENLARGED PLANS

65 AE104 BLDG 1 - LEVEL FIVE - ENLARGED PLANS

66 AE105 BLDG 2 - LEVEL ONE & LEVEL TWO - ENLARGED PLANS

67 AE106 BLDG 2 - LEVEL TWO, LEVEL THREE, & LEVEL FOUR - ENLARGED PLANS

68 AE107 BLDG 2 - LEVEL FOUR, BLDG 3 - ENLARGED PLANS

69 AE108 BLDG 4 & 8 - ENLARGED PLANS

70 AE109 BLDG 9 & 10 - ENLARGED PLANS

71 AE110 BLDG 11 & 12 - ENLARGED PLANS

72 AE111 BLDG 24 - LEVEL ONE - ENLARGED PLANS

73 AE112 BLDG 24 - LEVEL TWO - ENLARGED PLANS

74 AE113 BLDG 29 - ENLARGED PLANS

75 AE601 DOOR SCHEDULE & DETAILS

76 AF711 PARTITION, FINISH SCHEDULES & DETAILS

[06] FIRE PROTECTION

77 FA001 FIRE ALARM NOTES MATRIX AND RISER DIAGRAM

78 FA101 BUILDING 1 - REFERENCE PLANS

79 FA102 BUILDING 1 - REFERENCE PLANS

80 FA103 BUILDING 2 - REFERENCE PLANS

81 FA104 BUILDING 2 - REFERENCE PLANS

82 FA105 BUILDINGS 3, 4, 8, & 9 - REFERENCE PLANS

83 FA106 BUILDINGS 10, 11, 12, & 34 - REFERENCE PLANS

84 FA107 BUILDING 24 - REFERENCE PLAN

85 FA108 BUILDING 24 - REFERENCE PLAN

86 FA109 BUILDING 29 - REFERENCE PLAN

87 FA401 BLDG 1 - BASEMENT - ENLARGED PLANS

88 FA402 BLDG 1 - ENLARGED PLANS

89 FA403 BLDG 2 & 3 - ENLARGED PLANS

90 FA404 BLDG 4 & 8 - ENLARGED PLANS

91 FA405 BLDG 9 & 10 - ENLARGED PLANS

92 FA406 BLDG 24 - ENLARGED PLANS

93 FA407 BLDG 29 - ENLARGED PLANS

94 FA500 FIRE ALARM DETAILS

95 FX001 FIRE SPRINKLER NOTES

96 FX101 BUILDING 1 - REFERENCE PLANS

97 FX102 BUILDING 1 - REFERENCE PLANS

98 FX103 BUILDING 2 - REFERENCE PLANS

99 FX104 BUILDING 2 - REFERENCE PLANS

100 FX105 BUILDINGS 3, 4, 8, & 9 - REFERENCE PLANS

101 FX106 BUILDINGS 10, 11, 12, & 34 - REFERENCE PLANS

102 FX107 BUILDING 24 - REFERENCE PLAN

103 FX108 BUILDING 24 - REFERENCE PLAN

104 FX109 BUILDING 29 - REFERENCE PLAN

105 FX401 BLDG 1 - BASEMENT - ENLARGED PLANS

106 FX402 BLDG 1 - ENLARGED PLANS

107 FX403 BLDG 2 & 3 - ENLARGED PLANS

108 FX404 BLDG 4 & 8 - ENLARGED PLANS

109 FX405 BLDG 9 & 10 - ENLARGED PLANS

110 FX406 BLDG 24 - ENLARGED PLANS

111 FX407 BLDG 29 - ENLARGED PLANS

112 FX500 FIRE SPRINKLER DETAILS

BONHAM EHRM INFRASTRUCTURE

UPGRADES

VA PROJECT NUMBER: 549A4-21-700

SHEET INDEX

SEQUENCE NUMBER SHEET NAME

[07] MECHANICAL

113 M-000 LEGEND AND ABBREVIATIONS

114 M-101 BUILDING 1 HVAC REFERENCE PLANS

115 M-102 BUILDING 1 HVAC REFERENCE PLANS

116 M-103 BUILDING 2 HVAC REFERENCE PLANS

117 M-104 BUILDING 2 HVAC REFERENCE PLANS

118 M-105 BUILDING 3 HVAC REFERENCE PLANS

119 M-106 BUILDING 4, 8, 9, 10, 11, 12, & 34 HVAC REFERENCE PLANS

120 M-107 BUILDING 24 HVAC REFERENCE PLANS

121 M-108 BUILDING 24 HVAC REFERENCE PLANS

122 M-109 BUILDING 29 HVAC REFERENCE PLANS

123 M-201 BUILDING 1 HVAC ROOF PLAN

124 M-202 BUILDING 2 & 3 HVAC ROOF PLANS

125 M-203 BUILDING 4, 9, 10, & 12 HVAC ROOF PLANS

126 M-204 BUILDING 24 HVAC ROOF PLAN

127 M-401 BUILDING 1 HVAC ENLARGED PLANS

128 M-402 BUILDING 1 HVAC ENLARGED PLANS CONTINUED

129 M-403 BUILDING 2 HVAC ENLARGED PLANS

130 M-404 BUILDING 2, 3, & 4 HVAC ENLARGED PLANS CONTINUED

131 M-405 BUILDING 8, 9, 10, 11, & 12 HVAC ENLARGED PLANS

132 M-406 BUILDING 24 HVAC ENLARGED PLANS

133 M-407 BUILDING 29 HVAC ENLARGED PLANS

134 M-501 MECHANICAL DETAILS

135 M-502 MECHANICAL DETAILS

136 M-601 MECHANICAL SCHEDULES

137 M-701 MECHANICAL CONTROLS

[08] ELECTRICAL

138 E-001 ELECTRICAL LEGEND AND ABBREVIATIONS

139 E-101 BUILDING 1 - REFERENCE PLANS

140 E-102 BUILDING 1 - REFERENCE PLANS

141 E-103 BUILDING 2 - REFERENCE PLAN

142 E-104 BUILDING 2 - REFERENCE PLAN

143 E-105 BUILDINGS 3, 4, 8, & 9 - REFERENCE PLANS

144 E-106 BUILDINGS 10, 11, 12, & 34 - REFERENCE PLANS

145 E-107 BUILDING 24 - REFERENCE PLAN

146 E-108 BUILDING 24 - REFERENCE PLAN

147 E-109 BUILDING 29 - REFERENCE PLAN

148 E-201 BUILDING 1 - ROOF PLANS

149 E-202 BUILDINGS 2 & 3 - ROOF PLANS

150 E-203 BUILDINGS 4, 8, 9, 10, & 12 - ROOF PLANS

151 E-204 BUILDING 24 - ROOF PLANS

152 E-401 BLDG 1 - BASEMENT ELECTRICAL ROOM - ENLARGED PLANS

153 E-402 BLDG 1 - BASEMENT - ENLARGED PLANS

154 E-403 BLDG 1 - LEVEL ONE - ENLARGED PLANS

155 E-404 BLDG 1 - LEVELS TWO, THREE, AND FOUR - ENLARGED PLANS

156 E-405 BLDG 1 - LEVEL FIVE - ENLARGED PLAN

157 E-406 BLDG 2 - LEVELS ONE AND TWO - ENLARGED PLANS

158 E-407 BLDG 2 - LEVELS TWO, THREE, AND FOUR - ENLARGED PLANS

159 E-408 BLDG 3 - LEVEL FOUR - ENLARGED PLANS

160 E-409 BLDG 4 & 8 - ENLARGED PLANS

161 E-410 BLDG 9 & 10 - ENLARGED PLANS

162 E-411 BLDG 11 & 12 - ENLARGED PLANS

163 E-412 BLDG 24 - LEVEL ONE - ENLARGED PLANS

164 E-413 BLDG 24 - LEVEL TWO - ENLARGED PLANS

165 E-414 BLDG 29 - ENLARGED PLANS

166 E-415 BLDG 1, 2, & 3 - ENLARGED MECHANICAL POWER PLANS

167 E-416 BLDG 4, 8, 9, 10, 12, & 24 - ENLARGED MECHANICAL POWER PLANS

168 E-501 ELECTRICAL DETAILS

169 E-502 ELECTRICAL DETAILS

170 E-503 ELECTRICAL DETAILS

171 E-504 ELECTRICAL DETAILS

172 E-601 BUILDING 1 - ELECTRICAL ONE-LINE DIAGRAM

173 E-602 BUILDING 2 - ELECTRICAL ONE-LINE DIAGRAM

174 E-603 BUILDING 3 & 4 - ELECTRICAL ONE-LINE DIAGRAM

175 E-604 BUILDING 8 - ELECTRICAL ONE-LINE DIAGRAM

176 E-605 BUILDING 9, 10, 11, & 12 - ELECTRICAL ONE-LINE DIAGRAM

177 E-606 BUILDING 24 - ELECTRICAL ONE-LINE DIAGRAM

178 E-607 BUILDING 29 - ELECTRICAL ONE-LINE DIAGRAM

179 E-701 BUILDING 1 & 2 - PANEL SCHEDULES

180 E-702 BUILDING 2, 3 & 4- PANEL SCHEDULES

181 E-703 BUILDING 9, 10, 12, & 24 - PANEL SCHEDULES

182 E-704 BUILDING 29 - PANEL SCHEDULES

183 E-705 ELECTRICAL SCHEDULES

1, 2, 3, 4, 8, 9, 10, 11, 12, 24, 29, & 34

SHEET INDEX

SEQUENCE NUMBER SHEET NAME

[09] TELECOMMUNICATION

184 T-000 TELECOM SYMBOLS & ABBREVIATIONS

185 T-100 BUILDING 1 - TELECOM PLANS

186 T-101 BUILDING 1 - TELECOM PLANS

187 T-102 BUILDING 2 - TELECOM PLANS

188 T-103 BUILDING 2 - TELECOM PLANS

189 T-104 BUILDING 3, 4, 8 & 9 - TELECOM PLANS

190 T-105 BUILDING 10, 11, 12 & 34 - TELECOM PLANS

191 T-106 BUILDING 24 - TELECOM PLANS

192 T-107 BUILDING 24 - TELECOM PLANS

193 T-108 BUILDING 29 - TELECOM PLANS

194 T-200 TELECOM SITE PLANS

195 T-201 TELECOM BACKBONE PATHWAYS - BLDG 2, 3, 10, 24 & 4

196 T-202 TELECOM BACKBONE PATHWAYS - BLDG 8, 9, 11, 12 & 29

197 T-203 RISER DIAGRAM - BUILDING 1 FIBER OPTIC BACKBONE

198 T-204 RISER DIAGRAM - CAMPUS FIBER BACKBONE 'A' & 'B'

199 T-300 BUILDING 1 - TELECOM ENLARGED PLANS

200 T-301 BUILDING 1 - TELECOM ENLARGED PLANS

201 T-302 BUILDING 1 - TELECOM ENLARGED PLANS

202 T-303 BUILDING 2 - TELECOM ENLARGED PLANS

203 T-304 BUILDING 2, 3, 4 & 8 - TELECOM ENLARGED PLANS

204 T-305 BUILDING 9, 10, 11 & 12 - TELECOM ENLARGED PLANS

205 T-306 BUILDING 24 - TELECOM ENLARGED PLANS

206 T-307 BUILDING 29 - TELECOM ENLARGED PLANS

207 T-400 TELECOM DETAILS

208 T-401 TELECOM TR DETAILS

209 T-402 TELECOM MCR DETAILS

[10] SECURITY

210 TY000 ABBREVIATIONS, SYMBOLS, LEGENDS & NOTES

211 TY101 BUILDING 1 - REFERENCE PLANS

212 TY102 BUILDING 1 - REFERENCE PLANS

213 TY103 BUILDING 2 - REFERENCE PLAN

214 TY104 BUILDING 2 - REFERENCE PLAN

215 TY105 BUILDINGS 3, 4, 8, & 9 - REFERENCE PLANS

216 TY106 BUILDINGS 10, 11, & 12 - REFERENCE PLANS

217 TY107 BUILDING 24 - REFERENCE PLAN

218 TY108 BUILDING 24 - REFERENCE PLAN

219 TY109 BUILDING 29 - REFERENCE PLAN

220 TY400 BLDG 1 - SECURITY ENLARGED PLANS

221 TY401 BLDG 1 - SECURITY ENLARGED PLANS

222 TY402 BLDG 1 - SECURITY ENLARGED PLANS

223 TY403 BLDG 2 - SECURITY ENLARGED PLANS

224 TY404 BLDG 3, 4, 8 - SECURITY ENLARGED PLANS

225 TY405 BLDG 9, 10, 11, 12 - SECURITY ENLARGED PLANS

226 TY406 BLDG 24 - SECURITY ENLARGED PLANS

227 TY407 BLDG 29 - SECURITY ENLARGED PLANS

228 TY500 SECURITY DETAILS

229 TY600 SECURITY RISERS AND DIAGRAMS

TOTAL SHEETS: 229

100% BID DOCUMENTS

ABBREVIATIONS CODES STANDARDS AND EXECUTIVE ORDERS

4' -0

M

A X

4' -0

M

A X

2' -1

0" M

A X

2' -3

M

IN

1'-6" MIN

1. GENERAL CONTRACTOR TO PROVIDE METAL SUPPORT

BLOCKING FOR ALL WALL MOUNTED ACCESSORIES,

FIXTURES, AND EQUIPMENT.

2. PROVIDE ADA SUPPORT BRACKETS PLACED AT ALL OPEN

COUNTERTOPS @ 36"-48" MAX ON CENTER.

3. SPECIFIED MAXIMUMS ARE MEASURED FROM AFTER

FINISHED FLOOR TO THE OPERABLE PART OF THE FIXTURE.

4. FIXTURES SHOWN ARE REPRESENTATIONAL ONLY. NOT ALL

FIXTURES MAY BE USED. REFER TO SPECIFICATIONS FOR

FIXTURE TYPES USED IN THIS PROJECT.

5. FIXTURES MAY OVERLAP WAINSCOT. WHERE APPLICABLE,

BACKING TO BE PROVIDED AS SHIM FOR FLUSH

APPLICATION. SHIM TO MATCH SCHEDULED WALL FINISH.

6" MAX

9" M

IN

SHOWER

VA TOILET ROOM

TURNING RADIUS

DRINKING

FOUNTAIN

PAPER TOWEL

DISPENSER

SANITARY

NAPKIN

DISPENSER

4' -0

"M A

X

WASTE

RECEPTACLE

LAVATORY

WITH MIRROR

ON CENTER

WALL

4' -0

M

A X

SOAP

DISPENSER

2' -1

0" M

A X

T O

B .O

. R E

F

LE

C T

IV

E

S U

R F

A C

E

3' -4

"M A

X

17 MIN

2' -3

M

IN

3' -0

M

A X

1'-6" MIN

WALL

2' -9

" 4' -0

M

IN

2'-0" MIN

8" MIN

WALL

LAVATORY

WITH APRON

1' -5

M

A X

1'-6" MIN

URINAL

WALL

1'-5" - 1'-7" (AMBULATORY)

1'-4" - 1'-6" (WHEELCHAIR)

CLEAR FLOOR

5'-6"

CLEAR FLOOR

6'-0"

3'-0" MIN

2' -9

3' -0

1'-0" MIN

3'-6" MIN 1'-0"MAX

4'-6" MIN

1' -5

'-7

1' -6

M

IN

A N

S I I

C C

A

7.

1)

1' -3

M

IN

A D

A /A

B A

2' -9

'-0

WALL

WALL

4' -0

M

A X

WALL HOOK

7' -0

CLOCK

WALL

FINISHED FLOOR

FIRE EXTINGUISHER

CABINET

WEIGHT > 40LBS

FIRE EXTINGUISHER

CABINET

WEIGHT < 40LBS

4' -0

"M A

X

4' -0

M

A X

TOILET SEAT

COVER

DISPENSER

BABY

CHANGING

STATION

CLEAR FLOOR SPACE

@ WATER CLOSET

5'-6"

2'-6"

4' -0

2'-6"

4' -0

HANDRAILS AND

BUMPER GUARDS

FIXTURE MOUNTING HEIGHTS AND CLEARANCES

18" MIN

M

IN

FRONT APPROACH,

PULL SIDE

36" MIN

M

IN

HINGE APPROACH,

PULL SIDE

HINGE APPROACH,

PULL SIDE

*12" MIN48

M

IN

FRONT APPROACH,

PUSH SIDE

M

IN

HINGE APPROACH,

PUSH SIDE

22" MIN 24" MIN

*4 8"

M

IN

LATCH APPROACH,

PULL SIDE

24" MIN*4

2"

M

IN

LATCH APPROACH,

PUSH SIDE

*IF BOTH CLOSER

AND LATCH ARE

PROVIDED

*54" MIN IF CLOSER

IS PROVIDED

*48" IF CLOSER IS

PROVIDED

FRONT APPROACH,

PUSH SIDE

M

IN

42" MIN

DOOR AND FIXTURE CLEARANCES

MATERIALS LEGEND

PURPOSE: THE PUBLIC BUILDINGS AMENDMENT ACT OF 1988, PUBLIC LAW (PUB. L.) 100-678 REQUIRES FEDERAL AGENCIES TO FOLLOW NATIONAL RECOGNIZED "MODEL" BUILDING CODES. THE FEDERAL PARTICIPATION IN THE DEVELOPMENT AND USE OF VOLUNTARY STANDARDS, OFFICE OF MANAGEMENT AND BUDGET (OMB) CIRCULAR A-119, REQUIRES ALL EXECUTIVE AGENCIES TO RELY ON VOLUNTARY STANDARDS, BOTH DOMESTIC AND INTERNATIONAL, WHENEVER FEASIBLE, AND TO PARTICIPATE IN

VOLUNTARY STANDARD BODIES.

GENERAL: VA HAS ADOPTED THE LATEST EDITION OF THE FOLLOWING CODES AND STANDARDS AS A MINIMUM FOR ALL PROJECTS PERFORMED IN THE MODERNIZATION, ALTERATION, ADDITION, OR IMPROVEMENT OF ITS REAL PROPERTY AND THE CONSTRUCTION OF NEW STRUCTURES. VA DESIGN MANUALS AND MASTER SPECIFICATIONS

SPECIFY OTHER CODES AND STANDARDS THAT VA FOLLOWS ON ITS PROJECTS:

• VA DIRECTIVES, DESIGN MANUALS, MASTER SPECIFICATIONS, VA NATIONAL CAD STANDARD APPLICATION GUIDE, AND OTHER GUIDANCE ON THE TECHNICAL

INFORMATION LIBRARY (TIL) (HTTP://WWW.CFM.VA.GOV/TIL/).

• 2021 INTERNATIONAL BUILDING CODE (IBC) (ONLY WHEN SPECIFICALLY REFERENCED IN VA DESIGN DOCUMENTS, SEE NOTES BELOW)

• 2021 INTERNATIONAL EXISTING BUILDING CODE (IEBC) (IF APPLICABLE)

• 2021 NFPA 101 LIFE SAFETY CODE (SEE NOTES BELOW)

• 2021 NATIONAL FIRE CODES (NFPA)

• OCCUPATIONAL, SAFETY AND HEALTH ADMINISTRATION (OSHA) STANDARDS.

• 2020 VA SEISMIC DESIGN REQUIREMENTS, H-18-8

• 2021 INTERNATIONAL MECHANICAL CODE

• 2020 NATIONAL ELECTRICAL CODE (NEC), NFPA 70

• 2021 INTERNATIONAL PLUMBING CODE (IPC)

• 2016 SAFETY CODE FOR ELEVATORS AND ESCALATORS, AMERICAN SOCIETY OF MECHANICAL ENGINEERS (ASME) A 17.1.

• 2015 ARCHITECTURAL BARRIERS ACT (ABA) STANDARDS INCLUDING VA SUPPLEMENT, VA BARRIER FREE DESIGN STANDARD (PG-18-13)

• 2017 ANSI ICC A117.1 ACCESSIBLE AND USABLE BUILDINGS AND FACILITIES

• 2019 BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE AND COMMENTARY, AMERICAN CONCRETE INSTITUTE AND COMMENTARY (ACI 318-19)

• 2017 STEEL CONSTRUCTION MANUAL (15TH EDITION), AMERICAN INSTITUTE OF STEEL CONSTRUCTION (AISC)

• ENERGY POLICY ACT OF 2005 (EPACT)

• 2007 DOE INTERIM FINAL RULE: ENERGY CONSERVATION STANDARDS FOR NEW FEDERAL, COMMERCIAL AND MULTI-FAMILY HIGH-RISE RESIDENTIAL BUILDINGS AND

NEW LOW-RISE RESIDENTIAL BUILDINGS, 10 CFR PARTS 433, 434 AND 435.

• 2006 FEDERAL LEADERSHIP IN HIGH PERFORMANCE AND SUSTAINABLE BUILDINGS: MEMORANDUM OF UNDERSTANDING (MOU)

• 2018 EXECUTIVE ORDER 13834: EFFICIENT FEDERAL OPERATIONS

• 2021 THE PROVISIONS FOR CONSTRUCTION AND SAFETY SIGNS. STATED IN THE GENERAL REQUIREMENTS SECTION 010000 OF THE VA MASTER CONSTRUCTION

SPECIFICATION.

• 2019 VENTILATION FOR ACCEPTABLE INDOOR AIR QUALITY – ASHRAE STANDARD 62.1

• 2019 SAFETY STANDARD FOR REFRIGERATION SYSTEMS – ASHRAE STANDARD 15

LOCAL CODES: AS AN AGENCY OF THE FEDERAL GOVERNMENT, VA IS NOT SUBJECT TO LOCAL IMPOSITION OF CODE ENFORCEMENT PROCEDURES (DRAWING REVIEWS, BUILDING PERMITS, INSPECTIONS, FEES, ETC.). VA MUST FUNCTION AS THE AUTHORITY HAVING JURISDICTION (AHJ) AND THUS HAS THE RESPONSIBILITY TO GUARD PUBLIC HEALTH AND SAFETY THROUGH ENFORCING ITS ADOPTED CODES. HOWEVER, LOCAL AUTHORITIES SHOULD BE NOTIFIED ABOUT PLANNED PROJECTS AND GIVEN OPPORTUNITY TO REVIEW DRAWINGS PROVIDED THAT VA DOES NOT PAY FOR REVIEW OR INSPECTION FEES.

NOTES:

1. NFPA 101 PRIMARILY ADDRESSES LIFE SAFETY AND FIRE PROTECTION FEATURES WHILE THE IBC ADDRESSES A WIDE RANGE OF CONSIDERATIONS, INCLUDING, BUT

NOT LIMITED TO, STRUCTURAL STRENGTH, SEISMIC STABILITY, SANITATION, ADEQUATE LIGHT AND VENTILATION, AND ENERGY CONSERVATION. VA BUILDINGS MUST MEET THE REQUIREMENTS OF NFPA 101 AND DOCUMENTS REFERENCED BY NFPA 101 IN ORDER TO COMPLY WITH THE ACCREDITATION REQUIREMENTS OF THE JOINT COMMISSION. THEREFORE, DESIGNS SHALL COMPLY WITH THE REQUIREMENTS OF THE LATEST EDITION OF NFPA 101 AND DOCUMENTS REFERENCED THEREIN.

DESIGN FEATURES NOT ADDRESSED BY NFPA 101 OR DOCUMENTS REFERENCED THEREIN SHALL COMPLY WITH THE REQUIREMENTS OF THE LATEST EDITION OF THE IBC OR AS OTHERWISE ADDRESSED ABOVE IN THIS PROGRAM GUIDE. FOR DESIGN FEATURES THAT ARE ADDRESSED BY BOTH THE IBC AS WELL AS NFPA 101 OR A DOCUMENT REFERENCED BY NFPA 101, THE REQUIREMENTS OF NFPA 101 OR THE DOCUMENT REFERENCED BY NFPA 101 SHALL BE USED EXCLUSIVELY (THIS APPLIES

EVEN IF THE IBC REQUIREMENTS ARE DIFFERENT).

2. CONFLICTS BETWEEN NATIONALLY RECOGNIZED CODES AND STANDARDS AND VA REQUIREMENTS – SHOULD A CONFLICT EXIST BETWEEN VA REQUIREMENTS AND VA ADOPTED NATIONALLY RECOGNIZED CODES AND STANDARDS, THE CONFLICT SHALL BE BROUGHT TO THE ATTENTION OF VA. THE RESOLUTION OF THE CONFLICT SHALL BE MADE BY THE AUTHORITY HAVING JURISDICTION FOR VA TO ENSURE A CONSISTENCY SYSTEM WIDE.

ASHRAE 90.1 - 2019 EDITION

BUILDING LOCATION: BONHAM, TEXAS

CLIMATE ZONE (TABLE ANNEX 1-1): ZONE 3A

INTERIOR DESIGN CONDITIONS:

THE INTERIOR DESIGN TEMPERATURES FOR HEATING AND COOLING AS DEPICTED IN THE PROJECT DESIGN CONDITIONS SCHEDULE IN THE MECHANICAL CONTROL DRAWINGS SHALL BE THE MAXIMUM

AND MINIMUM VALUES FOR THE ASSOCIATED TEMPERATURE CONTROL ZONES.

BUILDING ENVELOPE REQUIREMENTS (5.5 )

BUILDING ENVELOPE REQUIREMENTS FOR CLIMATE ZONE 4 (A,B,C)

ROOFS REQUIRED DESIGNED

INSULATION: R-30 c.i. EXISTING METAL BUILDINGS: R-19 + R-11 Ls or R-25 + R-8 Ls EXISTING

ATTIC AND OTHER: R-49 EXISTING

WALLS, ABOVE GRADE

MASS: R-9.5 c.i. EXISTING METAL BUILDING: R-0 + R-15.8 c.i. EXISTING STEEL-FRAMED: R-13 + R-7.5 c.i. EXISTING WOOD-FRAMED AND OTHER: R-13 + R-3.8 c.i. or R-20 EXISTING

WALL, BELOW GRADE

BELOW-GRADE WALL: R-7.5 c.i. EXISTING

FLOORS

MASS: R-14.6 c.i. EXISTING

STEEL-FRAMED: R-30 EXISTING

WOOD-FRAMED AND OTHER: R-30 EXISTING

SLAB-ON-GRADE FLOORS

UNHEATED SLABS: R-15 for 24 in. EXISTING HEATED SLABS: R-20 for 24 in. EXISTING

OPAQUE DOORS

SWINGING: U-0.370 EXISTING

NONSWINGING: U-0.310 EXISTING

FENESTRATION (TABLE 5.5-4):

VERTICAL FENESTRATION, U-FACTOR

FIXED: U-0.36 EXISTING

OPERABLE: U-0.45 EXISTING

ENTRANCE DOOR: U-0.63 EXISTING

DEFINITIONS

c.i = CONTINUOUS INSULATION Ls = LINEAR SYSTEM

NR = NO (INSULATION) REQUIREMENT

ENERGY REQUIREMENTS

N

1. DRAWINGS ARE PART OF A COMPLETE DOCUMENTS SET. CONTRACTOR SHALL

CONFIRM ALL ITEMS REQUIRED BASED UPON THE OVERALL DESIGN INTENT OF THE

ENTIRE DOCUMENT SET.

2. CONTRACTOR SHALL VERIFY ALL EXISTING CONDITIONS, PRIOR TO BEGINNING ANY

WORK, TO CONFIRM THE ACCURACY OF THE DRAWINGS AND REPORT ANY

DISCREPANCIES TO THE ARCHITECT. DO NOT SCALE THE DRAWINGS. FIELD VERIFY

ALL DIMENSIONS AND EXISTING STRUCTURAL CONDITIONS.

3. ALL AREAS NOT INVOLVED IN THE SCOPE OF WORK FOR THIS PROJECT SHALL BE KEPT

CLEAN AND FREE OF OBSTRUCTIONS AT ALL TIMES.

4. ERECT BARRICADES AND WARNING SIGNS TO DIVERT AND WARN PASSERS-BY OF THE

CONSTRUCTION WORK. PROVIDE DUST PROOFING ENCLOSURES TO SEPARATE WORK

AREAS FROM THE EXISTING FACILITIES.

5. ALL TRASH AND DEBRIS TO BE REMOVED ON A DAILY BASIS.

6. PROVIDE PROTECTION FOR ALL EXISTING SURFACES AND CONDITIONS TO REMAIN IN

PLACE DURING THE SCOPE OF WORK. SHOULD ANY DAMAGE OCCUR, PATCH AND

REPAIR ANY DAMAGE TO ADJACENT FINISHES TO MATCH EXISTING.

7. ANY DAMAGE CAUSED TO THE BUILDING OR OWNER EQUIPMENT SHALL BE REPAIRED

OR REPLACED BACK TO ITS ORIGINAL CONDITIONS AT NO ADDITIONAL COST TO THE

OWNER.

8. COVER ALL RETURN AIR GRILLES WITHIN THE AREA OF CONSTRUCTION TO PREVENT

PARTICULATE MATERIAL FROM EXHAUSTING INTO SURROUNDING SPACES.

9. APPROPRIATE LIGHT FIXTURES SHALL BE TEMPORARILY SUSPENDED TO PROVIDE

ADEQUATE LIGHTING LEVELS FOR CONSTRUCTION.

10. CONTRACTOR AND SUBCONTRACTORS ARE REQUIRED TO COORDINATE WITH OTHER

DISCIPLINES TO INSTALL COMPLETE AND OPERATIONAL SYSTEMS. DRAWINGS, AS A

WHOLE, REPRESENT A COMPLETE SET AND DEPICT REQUIREMENTS FOR COMPLETE

AND OPERATIONAL SYSTEMS. INDIVIDUAL DRAWINGS MAY NOT DEPICT COMPLETE AND

ACCURATE INFORMATION TO COORDINATE COMPLETE AND OPERATIONAL SYSTEMS,

BUT DO SO AS AN ENTIRE DOCUMENT TO BE REFERENCED WITH OTHER INDIVIDUAL

DRAWINGS. CONTRACTOR AND SUBCONTRACTORS ARE REQUIRED TO REFERENCE

OTHER SHEETS AND SPECIFICATIONS AS AN ENTIRE SET OF CONSTRUCTION

DOCUMENTS THAT REFLECT WORK REQUIRED TO ACHIEVE A COMPLETE AND

OPERATIONAL GOAL. LACK OF COORDINATION AND REVIEW OF DRAWINGS AND

SPECIFICATIONS AS AN ENTIRE DOCUMENT TO INSTALL COMPLETE AND OPERATIONAL

SYSTEMS, BEING OBVIOUS AND TYPICAL INDUSTRY STANDARD, IDENTIFIED IN THE

DRAWINGS AND SPECIFICATIONS, SHALL NOT BE IN ANY WAY AN ADDITIONAL COST TO

THE GOVERNMENT.

11. CONTRACTOR SHALL SUBMIT A REQUEST, IN WRITING, TO INTERRUPT ANY SUCH

SERVICES TO COR (CONTRACTING OFFICER’S REPRESENTATIVE) 48 HOURS IN

ADVANCE OF PROPOSED INTERRUPTION. REQUEST SHALL STATE REASON, DATE,

EXACT TIME OF, AND APPROXIMATE DURATION OF SUCH INTERRUPTION. MAJOR

INTERRUPTIONS OF ANY SYSTEM MUST BE REQUESTED, IN WRITING, AT LEAST 60

CALENDAR DAYS PRIOR TO THE DESIRED TIME AND SHALL BE PERFORMED AS

DIRECTED BY THE COR. MAJOR INTERRUPTIONS SHALL BE COORDINATED WITH OTHER

MAJOR INTERRUPTIONS AND MAY NOT BE SCHEDULED FOR ONE DISCIPLINE MORE

THAN TWICE THROUGHOUT THE OVERALL CONSTRUCTION SCHEDULE UNLESS

REQUESTED IN WRITING AND APPROVED BY THE COR. CONTRACTOR WILL BE ADVISED,

IN WRITING, OF APPROVAL OF REQUEST, OR OF WHICH OTHER DATE AND/OR TIME

SUCH INTERRUPTION WILL CAUSE THE LEAST INCONVENIENCE TO OPERATIONS OF

THE MEDICAL CENTER. INTERRUPTION TIME APPROVED BY THE MEDICAL CENTER MAY

OCCUR AT TIMES OTHER THAN CONTRACTOR'S NORMAL WORKING HOURS. SCHEDULE

INTERRUPTION MAY BE ON WEEKENDS OR LATE HOURS AND MAY NOT BE AN

ADDITIONAL COST TO THE GOVERNMENT. COORDINATE ALL INTERRUPTIONS THAT MAY

AFFECT THE NORMAL OPERATION OF THE FACILITY WITH THE COR WHEN SUBMITTING

THE CONSTRUCTION SCHEDULE OR UPDATES TO THE CONSTRUCTION SCHEDULE.

12. NO ASBESTOS CONTAINING MATERIALS ARE TO BE USED ON THIS PROJECT. SPUR

DESIGN, THE A/E OF RECORD, CAN CERTIFY THAT NO ASBESTOS CONTAINING

BUILDING MATERIALS (ACBM) OR LEAD BASED PAINT (LBP) PRODUCTS WERE

DESIGNED/SPECIFIED AS BUILDING MATERIAL IN ANY OF THE CONSTRUCTION

DOCUMENTS.

GENERAL NOTES

AREA NAME

150 SF

A101

A101

SIM

A

00.0

A101

1 1

A101

LEVEL NAME

00'-00"

00'-00" 4B

3A

FIBERGLASS BATT

INSULATION

RIGID INSULATION

CONCRETE / PRECAST

CONCRETE

EARTH / SOIL

SAND, EIFS FINISH, OR

PLASTER FINISH

GYPSUM BOARD FINISH

BRICK

CONCRETE MASONRY

UNIT

STONE / CAST STONE

GYPSUM BOARD SECTION

EXTERIOR SHEATHING

BOARD SECTION

PLYWOOD SECTION

CLEAN UTILITY

000A

150 SF / 100 SF

/1 A101

X0000

6"

3' -0

M

A X

ROOM TAG

TOTAL SQUARE FEET/

REQUIRED MIN. SQUARE FEET

AREA TAG

SPECIALTY EQUIPMENT TAG

DOOR TAG

KEYED NOTE TAG

WALL TAG

WINDOW TAG

A101

SIM

A101

SIM

A

ACB ACOUSTIC CEILING BAFFLE

ACP ACOUSTIC CEILING PANEL

ACST ACOUSTIC

ADA AMERICANS WITH DISABILITIES ACT

ACT ACOUSTICAL CEILING TILE

ADDL ADDITIONAL

ADDN ADDITION

ADJ ADJACENT, ADJOINING, OR

ADJUSTABLE

ADMIN ADMINISTRATION

AE ARCHITECT/ENGINEER

AF ACCESS FLOORING

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

AHJ AUTHORITY HAVING JURISDICTION

AIA AMERICAN INSTITUTE OF

ARCHITECTS

ALT ALTERNATE

ALT NO ALTERNATE NUMBER

ALUM ALUMINUM (TRIM)

AMT AMOUNT

APPROX APPROXIMATE

ARCH ARCHITECT

ASC ABOVE SUSPENDED CEILING

AT ACOUSTIC CEILING TILE

AVG AVERAGE

B

BD BOARD

BLDG BUILDING

BLKG BLOCKING

BLT IN BUILT-IN

BOS BOTTOM OF STEEL

BOT BOTTOM

BRKT BRACKET

BTWN BETWEEN

C

CAB CABINET

CAV CAVITY

CBB CONCRETE BACKER BOARD

CD CONSTRUCTION DOCUMENTS

CFM CUBIC FEET PER MINUTE

CFS CUBIC FEET PER SECOND

CG CORNER GUARD

CH BD CHALK BOARD

CIP CAST-IN-PLACE

CJ CONTROL JOINT

CL CENTER LINE

CLG CEILING

CLG HT CEILING HEIGHT

CLR CLEAR

CMU CONCRETE MASONRY UNIT

CO CONTRACTING OFFICER

COL COLUMN

COMM COMMUNICATION

CONC CONCRETE

CONT CONTINUOUS

COORD COORDINATE

COR CONTRACTING OFFICER'S

REPRESENTATIVE

CP CONTRACTOR PROVIDED

CP/CI CONTRACTOR PROVIDED /

CONTRACTOR INSTALLED

CPT CARPET/CARPET TILE

CS CONCRETE SEALED

CSWK CASEWORK

CT CERAMIC TILE

CTB CERAMIC TILE BASE

CTR CENTER

CU FT CUBIC FEET

D

DBL DOUBLE

DEMO DEMOLITION

DEPT DEPARTMENT

DET DETAIL

DIA DIAMETER

DIR DIRECTION

DIST DISTANCE

DOC DOCUMENT

DR DOOR

DS DOWNSPOUT

DWG DRAWING

DWP DIMENSIONAL WALL PANEL

E

EA EACH

EJ EXPANSION JOINT

EL ELEVATION

ELEV ELEVATOR

ENTR ENTRANCE

EPY EPOXY FLOORING

EQ EQUAL

ETR EXISTING TO REMAIN

EX EXISTING

EXP EXPOSED

EXT EXTERIOR

F

FAB FABRIC

FED FEDERAL

FF FINISH FACE

FF EL FINISH FLOOR ELEVATION

FIN FINISH

FIN BS FINISH BOTH SIDES

FIN FLR FINISH FLOOR

FIN GR FINISH GRADE

FIXT FIXTURE

FLDG FOLDING

FLEX FLEXIBLE

FLG FLOORING

FLMT FLUSH MOUNT

FLR FLOOR

FOC FACE OF CONCRETE

FOM FACE OF MASONRY

FP FIRE PROTECTION

FR FIRE RESISTANT

FT FEET

FTG FOOTING

FV FIELD VERIFY

FWC FABRIC WALL COVERING

G

GDR GUARDRAIL

GL GLASS/GLAZING

GRAN GRANITE

GR FL GROUND FLOOR

GT GROUT

GSM GALVANIZED SHEET METAL

GYP BD GYPSUM BOARD

H

HDW HARDWARE

HEPA HIGH EFFICIENCY

PARTICULATE AIR (FILTER)

HM HOLLOW METAL

HORIZ HORIZONTAL

HR HANDRAIL

HT HEIGHT

I

IBC INTERNATIONAL BUILDING CODE

INSUL INSULATION

INT INTERIOR

ILO IN LIEU OF

J

J-BOX JUNCTION BOX

L

LAV LAVATORY

LBS POUND

LDG LANDING

LF LINEAR FEET (FOOT)

LIN LINEAR

LN LINOLEUM

LOC LOCATION

LT LIGHT

LVR LOUVER

LVT LUXURY VINYL TILE

M

MAT CARPET MAT / WALK-OFF MAT

MATL MATERIAL

MAX MAXIMUM

MECH MECHANICAL

MEMB MEMBRANE

MFR MANUFACTURER

MID MIDDLE

MIL STD MILITARY STANDARD

MIN MINIMUM

MISC MISCELLANEOUS

MO MASONRY OPENING

MOD MODIFY

MTG MOUNTING

MTL METAL

MVBL MOVABLE

N

NA NOT APPLICABLE

NIC NOT IN CONTRACT

NO NUMBER

NOM NOMINAL

NTS NOT TO SCALE

O

OA OVERALL

OC ON CENTER

OD OUTSIDE DIAMETER

OPNG OPENING

OPP OPPOSITE

OPR OPERABLE

ORD OVERFLOW ROOF DRAIN

ORIG ORIGINAL

P

P PAINT

PA PUBLIC ADDRESS

PBD PARTICLE BOARD

PCF POUNDS PER CUBIC FOOT

PCT PERCENT

PERF PERFORATED

PERIM PERIMETER

PERP PERPENDICULAR

PL PROPERTY LINE

PLAM PLASTIC LAMINATE

PLBG PLUMBING

PNL PANEL

PR PAIR

PRB PROFILE BASE

PRKG PARKING

PSF POUNDS PER SQUARE FOOT

PSI POUNDS PER SQUARE INCH

PT PORCELAIN TILE

PWR POWER

Q

QA QUALITY ASSURANCE

QC QUALITY CONTROL

QTY QUANTITY

REFERENCE SYMBOLS IDENTIFICATION TAGS

NOTE: NOT ALL ABBREVIATIONS OR SYMBOLS WILL BE UTILIZED FOR THIS PROJECT.

GRID HEAD AND

LINE

LEVEL INDICATOR

MATCH LINE AND

VIEW REFERENCE

NORTH ARROW W/

PROJECT NORTH

SPOT ELEVATION

DETAIL

SECTION

**48" MIN IF BOTH CLOSER

AND LATCH PROVIDED

WALL

SECTION

BUILDING

SECTION

DETAIL

ELEVATION

INTERIOR

ELEVATION

BUILDING

ELEVATION

1 1

6'- 0"

5'- 6"

BARIATRIC TOILET ROOM

TURNING RADIUS

CLEAR FLOOR SPACE

@ ADA LAVATORY

CLEAR FLOOR SPACE @ ADA

DRINKING FOUNTAIN

4"

6"

3"

6" 1'

-6

6" MAX

7" - 9" 11" MIN

17" - 25"

M

IN

6' -0

(ANSI ICC A117.1)

39"- 41"

(A N

S I I

C C

A

7.

1)

M

IN

(A N

S I I

C C

A

7.

1)

1"

3' -6

M

A X

5' -0

M

A X

R

RAF RESILIENT ATHETIC FLOORING

RB RUBBER BASE/RESILIENT BASE

RCP REFLECTED CEILING PLAN

RD ROOF DRAIN

REC RECESSED

REF REFERENCE

REM REMOVABLE

REP REPAIR

REPL REPLACE

REQ REQUIRE

REQD REQUIRED

RES RESINOUS FLOORING

RES-W RESINOUS / EPOXY WALL / CEILING

RF RUBBER FLOORING

RFG ROOFING

RM ROOM

RO ROUGH OPENING

RP RESIN PANEL

RSF RESILIENT SHEET FLOORING

RV ROOF VENT

RWC RIGID VINYL WALLCOVERING

S

SC SPECIALTY COATING

SD STATIC DISSIPATIVE FLOORING/TILE

SCHED SCHEDULE

SECT SECTION

SF SQUARE FOOT (FEET)

SGL SINGLE

SIM SIMILAR

SJ SCORED JOINT

SLNT SEALANT

SM SHEET METAL

SPEC SPECIFICATION

SQ SQUARE

SQ IN SQUARE INCH

SQ YD SQUARE YARD

SS SOLID SURFACE

ST STONE

STD STANDARD

STOR STORAGE

SV SHEET VINYL (ROLLED OR TILE)

T

TEL TELEPHONE

TEMP TEMPORARY

TER TERRAZZO

TOF TOP OF FOOTING/ FOUNDATION

TOM TOP OF MASONRY

TOS TOP OF SLAB/ STEEL

U

UNO UNLESS NOTED OTHERWISE

UTIL UTILITY

V

VAR VARIES

VC VA PROVIDED / CONTRACTOR

INSTALLED

VCT VINYL COMPOSITION TILE

VFAT VINYL FACED ACOUSTICAL TILE

VP VENEERED PLASTER

VT VINYL TILE

VV VA PROVIDED / VA INSTALLED

VWC VINYL WALLCOVERING

VWF VINYL WALL FABRIC

W

W/ WITH

W/O WITHOUT

W/C WATER CLOSET

WC WHEELCHAIR

WD WOOD

WFAB WALL FABRIC

WPM WATERPROOF MEMBRANE

WSF WELDED SHEET FLOOR

X

X BRACE CROSS BRACE

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

CONSULTANTS:

CIVIL ENGINEER

OLSSON

550 ST LOUIS ST,

SPRINGFIELD, MO 65806

(417) 885-1736

MECH / ELEC ENGINEER

SPUR DESIGN

2519 MADISON AVE., STE. 100

KANSAS CITY, MO 64108

(913) 369-7200

FIRE PROTECTION ENGINEER

RATED ENGINEERING

609 S. KELLY AVENUE, SUITE H2

EDMOND, OK 73003

(405) 856-2965

INDUSTRIAL HYGENIST

RIVERFRONT SAFETY & HEALTH

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

TECH ENGINEER

ASPEN COMMUNICATIONS, LLC

7 KIJI-DAVA CIRCLE, SUITE A

PRESCOTT, AZ 86301

(928) 774-0992

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STRUCT ENGINEER

STAND STRUCTURAL ENGINEERING

8234 ROBINSON STREET

OVERLAND PARK, KS 66204

(913) 214-2169

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Drawing #

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH REG. NO. BR 2171 EXP. 09/30/2023

ENGR REG. NO. F-17591 EXP. 02/29/2024

The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.

STAMP:

Drawing Number

Building Number

BUILDING 34 NOT SPRINKLERED. ALL OTHER BUILDINGS FULLY SPRINKLERED.

COMMISSIONING

ES2

13401 N. SANTA FE AVE

OKLAHOMA CITY, OK 73114

(405) 528-4500

CONTROLLED UNCLASSIFIED INFORMATION (CUI)

CONTROLLED UNCLASSIFIED INFORMATION (CUI)

C O

N T

R O

L L E

D U

N C

L A

S S

IF

IE

D I

N F

O R

M A

T

IO

N

C U

I)

/5

/2

:1

:0

A

M

100% BID DOCUMENTS

GENERAL INFORMATION

NSM 3 OF 229AJS

BONHAM EHRM

INFRASTRUCTURE

UPGRADES

07/07/2023

549A4-21-700

BONHAM VA MEDICAL CENTER

1201 E. 9TH STREET

BONHAM, TX 75418

GI002

SPUR #: 2216

OUTSIDE OF BUILDING

WEEKLY CHANGED HEPA FILTER

HEPA NEGATIVE AIR UNIT

WEEKLY CHANGED (OR

MORE AS NEEDED) PRE-

FILTER

FIRE RATED PLYWOOD

F

LE

X D

U C

T

SUPPLY DUCTS EITHER KEEP

RUNNING OR COVER WHEN

RUNNING TO KEEP DUST OUT.

TAPE ALL SERVICES

TO PROTECT AGAINST

CONTAMINATION A

O

VFIRE EXTINGUISHER ON PORTABLE

FLOOR BRACKET (ILSM MAY

REQUIRE MORE THAN ONE)

SUSPENDED PLASTIC

ZIPPER WALL CURTAIN

BARRIER 6 MIL PLASTIC

TEMPORARY DIGITAL MANOMETER FOR NEGATIVE PRESSURE

MONITORING OUTSIDE OF ICRA BARRIER FOR VA'S INSPECTION.

INDICATOR SHALL BE AT -0.01 OR GREATER (VERIFY DAILY). IF NOT,

VERIFY ALL OPENINGS, SUCH AS DOOR CLOSED, AND/OR CHANGE OUT

NEGATIVE AIR PRE-FILTER.

PROVIDE STICKY MAT, DRY MAT, WET MAT (CHANGED END OF

SHIFT OR MORE IF NECESSARY TO MAINTAIN CLEANLINESS)

PROVIDE WIPES AND SPRAY FOR WET MAT

POST ICRA ILSM FIRE

INSPECTION SHEETS

CONTAINER VISIBLE TO PUBLIC

COVER ALL RETURNS AT THE

GRATE/DIFFUSERS

OPTIONAL EXHAUST DUCTS

(COVER THE GRATES AND THE DIFFUSERS)

E

DOOR OPENING

VENT TO OUTSIDE ROUTE

TO BE APPROVED BY COR.

FIRE PULL STATION WITH

AUDIO/ VISUAL

ILSM SIGNAGE

ICRA BARRIER, SEE PLANS FOR TYPE AND LOCATION

GI003

GI003

PLASTIC WINDOW

SWIVEL CASTERS

WITH TWO LOCKING

BRAKES

MOBILE CART

A D

JU

S

T A

B

LE

H E

IG

H

T

HEPA NEGATIVE AIR

UNIT

EXISTING WALL

EXISTING CEILING

FLEX DUCT

HEATED DETECTOR CUT-OFF

BASIS OF DESIGN: HEPA NEGATIVE AIR

UNIT INTEGRAL WITH EDGEGUARD

BARRIER SYSTEM.

FIRE RATED PLYWOOD (TEMP.

REMOVE GLASS PANEL)

EXISTING WINDOW FRAME

TYPE A OR C ICRA BARRIER, SEE

PLANS FOR TYPE AND LOCATION

TYPE B OR D ICRA

BARRIER, SEE PLANS FOR

TYPE AND LOCATION

EXISTING CEILING

EXISTING CONCRETE SLAB FLOORING

FINISHED FLOORING TO BE KEPT

CLEAN. FLOORS NOT BEING

REPLACED MUST BE PROTECTED.

COVER WITH ROSIN PAPER/ FIRE

RATED PLYWOOD.

WHEN WORKING ABOVE CEILING

WITH BARRIERS THAT

TERMINATE AT CEILING,

PROVIDE PLASTIC ENCLOSURE

IN PLENUM SPACE.

AREA UNDER CONSTRUCTION

PERSONNEL ENTERING MUST HAVE: HARD HAT,

SAFETY GLASSES AND PROPER I.D.

--DESCRIPTION ON NEWLY PROPOSED OCCUPANCY--

COMING SOON!!!

XXXXXX

XXXXXX

XXXXXX

POST ICRA, ILSM, FIRE

INSPECTION SHEETS VISIBLE

TO THE PUBLIC

SUSPENDED PLASTIC ZIPPER

WALL CURTAIN BARRIER

INDICATOR MUST MAINTAIN -0.01 INCHES OR MORE

NEGATIVE (VERIFY DAILY), IF NOT VERIFY ALL

OPENINGS SUCH AS DOORS ARE CLOSED AND/OR

CHNAGE OUT NEGATIVE AIR PRE-FILTER.

4' -0

"A .F

.F

ICRA, ISLM, FIRE

WATCH, MISC. FORMS

PAPER CADDY

INDICATOR (REFER TO PLAN

AND ELEVATION) FRAMED PICTURE

OF C.O.R. WITH

CONTACT

INFORMATION

CONSTRUCTION SUPERVISOR

NAME AND CELL PHONE

XXXXX

BOILER/CHILLER PLANT AFTER

HOURS CONTACT PHONE XXXXX

FIRE EMERGENCY DIAL 911

THIS IS A RESTRICTED AREA

3 5/8" INSULATED WALL WITH 16

GAUGE METAL STUDS @ 16" O.C.

(2) LAYERS 5/8" GYPSUM BOARD

EACH SIDE. WALL TO EXTEND TO

UNDERSIDE OF DECK

5/8" FIRE RESISTANT GYPSUM

BOARD - BOTH SIDES

EXISTING CEILING SYSTEM

BASE - TO MATCH EXISTING

AREA

EXISTING FLOOR

UNDERSIDE OF EXISTING DECK

C E

IL

IN

G H

E

IG

H T

V A

R

IE

S F

IE

L D

V E

R

IF

Y

W A

L L

H E

IG

H

T V

A R

IE

S

F

IE

L D

V E

R

IF

Y

6 1/8"

D

FIRE RESISTANT SEALANT, BOTH

SIDES

2-HR RATED AND SMOKE

RATED

U.L. DESIGN NO. U404A

PLASTIC SHEET BARRIER

NON RATED

PLASTIC SHEET

BARRIER

EXISTING WALL

ASSEMBLY

EXISTING

CEILING

BOTTOM SEALING RUNNER

TOP SEALING

RUNNER

SUPPORT POLES,

QUANTITY PER MANUF.

RECOMMENDATIONS

REQU.

AS

5/8" FIRE RESISTANT GYPSUM

BOARD - BOTH SIDES

EXISTING CEILING SYSTEM

BASE - TO MATCH EXISTING

AREA

EXISTING FLOOR

UNDERSIDE OF EXISTING DECK

C E

IL

IN

G H

E

IG

H T

V A

R

IE

S F

IE

L D

V E

R

IF

Y

/2

4 7/8"

3 5/8" 16 GAUGE METAL STUDS @

16" O.C. WALL TO EXTEND TO

UNDERSIDE OF DECK

B

FIRE RESISTANT SEALANT, BOTH

SIDES

SMOKE RATED

3 5/8" INSULATED WALL WITH 16

GAUGE METAL STUDS @ 16" O.C.

WALL TO EXTEND TO UNDERSIDE

OF DECK

5/8" FIRE RESISTANT GYPSUM

BOARD - BOTH SIDES

EXISTING CEILING SYSTEM

BASE - TO MATCH EXISTING

AREA

EXISTING FLOOR

UNDERSIDE OF EXISTING DECK

C E

IL

IN

G H

E

IG

H T

V A

R

IE

S F

IE

L D

V E

R

IF

Y

W A

L L

H E

IG

H

T V

A R

IE

S

F

IE

L D

V E

R

IF

Y

4 7/8"

C

FIRE RESISTANT SEALANT, BOTH

SIDES

1-HR RATED AND SMOKE RATED

U.L. DESIGN NO. U404

MATRIX OF PRECAUTIONS FOR CONSTRUCTION & RENOVATION

INSPECTION AND NON-INVASIVE ACTIVITIES

INCLUDES BUT NOT LIMITED TO:

• REMOVAL OF CEILING TILES FOR VISUAL INSPECTION LIMITED TO 1 TILE PER 50 SQUARE FEET.

• PAINTING (BUT NOT SANDING).

• WALL COVERING, ELECTRICAL TRIM, MINOR PLUMBING AND ACTIVITIES WHICH DO NOT GENERATE DUST OR

REQUIRE CUTTING OF WALLS OR ACCESS TO CEILINGS OTHER THAN FOR VISUAL INSPECTION.

TYPE A

SMALL SCALE, SHORT DURATION ACTIVITIES WHICH CREATES MINIMAL DUST

INCLUDES BUT NOT LIMITED TO:

• INSTALLATION OF TELEPHONE AND COMPUTER CABLING.

• ACCESS TO CHASE SPACES.

• CUTTING OF WALLS OR CEILING WHERE DUST MIGRATION CAN BE CONTROLLED.

TYPE B

WORK THAT GENERATES A MODERATE TO HIGH LEVEL OF DUST OR REQUIRES DEMOLITION OR REMOVAL OF

ANY FIXED BUILDING COMPONENTS OR ASSEMBLIES

INCLUDES BUT NOT LIMITED TO:

• SANDING OF WALLS FOR PAINTING OR WALL COVERING.

• REMOVAL OF FLOOR COVERINGS, CEILING TILES OR CASEWORK.

• NEW WALL CONSTRUCTION.

• MINOR DUCT WORK OR ELECTRICAL WORK ABOVE CEILINGS.

• MAJOR CABLING ACTIVITIES.

• ANY ACTIVITY WHICH CANNOT BE COMPLETED WITHIN A SINGLE WORK SHIFT.

TYPE C

MAJOR DEMOLITION AND CONSTRUCTION PROJECTS

INCLUDES BUT NOT LIMITED TO:

• ACTIVITIES WHICH REQUIRE CONSECUTIVE WORK SHIFTS.

• REQUIRES HEAVY DEMOLITION OR REMOVAL OF A COMPLETE CABLING SYSTEM.

• NEW CONSTRUCTION.

TYPE D

PATIENT RISK GROUPS

LOW RISK MEDIUM RISK HIGH RISK HIGHEST RISK

• OFFICE AREAS • CARDIOLOGY

• ECHOCARDIOGRAPHY

• ENDOSCOPY

• NUCLEAR MEDICINE

• PHYSICAL THERAPY

• RADIOLOGY/MRI

• RESPIRATORY THERAPY

• CCU

• EMERGENCY ROOM

• LABOR & DELIVERY

• LABORATORY (SPECIMEN)

• NEWBORN NURSERY

• OUTPATIENT SURGERY

• PEDIATRICS

• PHARMACY

• POST ANESTHESIA CARE UNIT

• SURGICAL UNITS

• ANY AREA FOR IMMUNOCOMPROMISED PATIENTS

• BURN UNIT

• CARDIAC CATH LAB

• CENTRAL STERILE SUPPLY

• INTENSIVE CARE UNITS

• MEDICAL UNIT

• NEGATIVE PRESSURE ISOLATION ROOMS

• ONCOLOGY

• OPERATING ROOMS INCLUDING

• C-SECTION ROOMS

IC MATRIX - CLASS OF PRECAUTIONS:

CONSTRUCTION PROJECT BY PATIENT RISK

NOTE:

INFECTION CONTROL APPROVAL WILL BE REQUIRED WHEN THE CONSTRUCTION ACTIVITY AND RISK LEVEL INDICATE THAT CLASS III OR CLASS IV

CONTROL PROCEDURES ARE NECESSARY.

RISK RELATED GROUP

LOW RISK GROUP

MEDIUM RISK GROUP

HIGH RISK GROUP

HIGHEST RISK GROUP

TYPE A TYPE B TYPE C TYPE D

I

I

I

II III/IV IV

IV

IV

II

II

II

II

III

III/IV

III/IV

III/IV

INFECTION CONTROL RISK ASSESSMENT (ICRA)

CONSTRUCTION PROJECT TYPE

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

CONSULTANTS:

CIVIL ENGINEER

OLSSON

550 ST LOUIS ST,

SPRINGFIELD, MO 65806

(417) 885-1736

MECH / ELEC ENGINEER

SPUR DESIGN

2519 MADISON AVE., STE. 100

KANSAS CITY, MO 64108

(913) 369-7200

FIRE PROTECTION ENGINEER

RATED ENGINEERING

609 S. KELLY AVENUE, SUITE H2

EDMOND, OK 73003

(405) 856-2965

INDUSTRIAL HYGENIST

RIVERFRONT SAFETY & HEALTH

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

TECH ENGINEER

ASPEN COMMUNICATIONS, LLC

7 KIJI-DAVA CIRCLE, SUITE A

PRESCOTT, AZ 86301

(928) 774-0992

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STRUCT ENGINEER

STAND STRUCTURAL ENGINEERING

8234 ROBINSON STREET

OVERLAND PARK, KS 66204

(913) 214-2169

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Drawing #

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH REG. NO. BR 2171 EXP. 09/30/2023

ENGR REG. NO. F-17591 EXP. 02/29/2024

The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.

STAMP:

Drawing Number

Building Number

BUILDING 34 NOT SPRINKLERED. ALL OTHER BUILDINGS FULLY SPRINKLERED.

COMMISSIONING

ES2

13401 N. SANTA FE AVE

OKLAHOMA CITY, OK 73114

(405) 528-4500

CONTROLLED UNCLASSIFIED INFORMATION (CUI)

CONTROLLED UNCLASSIFIED INFORMATION (CUI)

C O

N T

R O

L L E

D U

N C

L A

S S

IF

IE

D I

N F

O R

M A

T

IO

N

C U

I)

/5

/2

:1

:0

A

M

100% BID DOCUMENTS

ICRA CONSTRUCTION DETAILS

NSM 4 OF 229AJS

BONHAM EHRM

INFRASTRUCTURE

UPGRADES

07/07/2023

549A4-21-700

BONHAM VA MEDICAL CENTER

1201 E. 9TH STREET

BONHAM, TX 75418

GI003

SPUR #: 2216

1/2" = 1'-0"

GENERAL ICRA CONSTRUCTION PLAN LAYOUT13/8" = 1'-0"

ICRA MOBILE CONTAINMENT CART23/8" = 1'-0"

SECTION AT ICRA CONSTRUCTION PLAN3

3/8" = 1'-0"

ICRA ELEVATION4

3/4" = 1'-0"

ICRA BARRIER WALL TYPES5

Sheets
GI000 - COVER SHEET
GI001 - SHEET INDEX
GI002 - GENERAL INFORMATION
GI003 - ICRA CONSTRUCTION DETAILS