This is a set of bid documents and construction drawings for the restoration of Building 35 Historic Theater (Project 621-24-103) at the James H. Quillen VA Medical Center in Mountain Home, Tennessee. The project involves comprehensive restoration of a historic theater facility totaling 16,120 gross square feet across basement, first floor, balcony, second floor, and projector booth levels. The building will be restored to Assembly (A-3) use classification and must comply with NFPA 101 Life Safety Code, IBC 2024, and applicable VA standards. Key construction requirements include a fully sprinklered fire suppression system, new wet-pipe sprinkler installation, fire alarm system with voice evacuation, accessibility compliance throughout (excluding the second-floor balcony), and structural repairs to maintain Type III (200) construction. The occupancy load is calculated at 1,003 total occupants with 769 actual occupants, including 302 fixed auditorium seats and 252 balcony seats.
The construction scope encompasses selective slate tile roof replacement (with alternate for full synthetic tile replacement), complete interior restoration, MEP system upgrades, theater systems installation (audio-visual, rigging, lighting control), and exterior site work including new concrete pavement, drainage improvements, and landscaping. Structural work includes basement foundation repairs, floor framing stabilization, and new exit stairs for the orchestra pit. Two bid alternates are offered: full theater seating replacement with integral aisle lighting and full synthetic roof tile replacement. The contractor must maintain pedestrian and vehicular access throughout construction, implement tree protection measures, coordinate with the VA Contracting Officer's Representative, and provide online construction management software. All drawings are in color and include 163 total sheets covering civil, structural, architectural, MEP, fire suppression, audio-visual, and theater systems disciplines. The project is fully sprinklered and requires compliance with VA Directive 1013 regarding worker immunization documentation.
View the file
Other files
Show all 47
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
A. THE CONTRACT DRAWINGS AND PROJECT MANUAL (INDICATED BY THE SAME PROJECT NUMBER) ARE COMPLEMENTARY. NOTIFY THE CONTRACTING OFFICER'S REPRESENTATIVE (C.O.R.) OF ANY
DISCREPANCIES FOUND DURING BIDDING AND THROUGH CONSTRUCTION.
B. DO NOT SCALE DRAWINGS; DIMENSIONS SHALL GOVERN.
C. VERIFY ALL EXISTING DIMENSIONS AND FIELD CONDITIONS PRIOR TO DEMOLITION AND
CONSTRUCTION. IF PROVIDED, EXAMINE EXISTING BUILDING DOCUMENTS AND BRING
DISCREPANCIES TO THE IMMEDIATE ATTENTION OF THE C.O.R.
D. VERIFY SIZES AND DIMENSIONS OF ALL EXISTING UTILITIES APPARATUSES IMPACTING NEW
CONSTRUCTION. DETERMINE EXACT SIZE AND LOCATION OF PENETRATION WITHIN NEW
CONSTRUCTION, TIGHTLY SEAL AND CAULK.
E. THE CONTRACTOR IS RESPONSIBLE FOR THE PROTECTION OF EXISTING ITEMS TO REMAIN
DURING DEMOLITION AND CONSTRUCTION.
F. IN COMPLIANCE WITH VA DIRECTIVE 1013, PROVIDE A CERTIFICATION THAT ALL WORKERS ON
THIS CONTRACT HAVE BEEN IMMUNIZED WITH THE FLU SHOT OF THE CURRENT YEAR.
G. MAINTAIN ACCESSIBLE EGRESS FOR THE DURATION OF THE PROJECT. THE CONTRACTOR IS
RESPONSIBLE FOR THE PROTECTION OF ALL CONSTRUCTION ROUTES BEYOND THE AREAS OF
WORK AND THE ROUTES MUST BE RETURNED TO THEIR ORIGINAL CONDITION AT THE END OF
THE PROJECT.
H. PENETRATIONS THROUGH EXISTING FIRE RATED CONSTRUCTION MUST BE PROPERLY CLOSED
AND FIRE SAFE’D TO ACHIEVE THE REQUIRED FIRE RATING BY THE END OF CONSTRUCTION
OPERATIONS FOR EACH DAY.
I. PERFORM ALL WORK IN ACCORDANCE WITH APPLICABLE CODES AND FEDERAL AUTHORITIES,
RULES AND REGULATIONS.
J. THESE DOCUMENTS SHOW DESIGN INTENT WITH MINIMUM CONSTRUCTION REQUIREMENTS AND
MINIMUM QUALITY OF WORK EXPECTED. THE CONTRACTOR IS RESPONSIBLE FOR ALL MEANS,
METHODS AND TECHNIQUES FOR CONSTRUCTION TO REACH THE EXPECTED QUALITY.
K. ALL MATERIALS USED SHALL BE NEW UNLESS OTHERWISE NOTED TO BE SALVAGED AND
REFURBISHED. MATERIAL QUALITY SHALL MEET OR EXCEED APPLICABLE INDUSTRY STANDARDS.
L. COORDINATING EQUIPMENT INSTALLATION AND VERIFY ROUGH-IN DIMENSIONS WITH THE
EQUIPMENT MANUFACTURER AND C.O.R. PRIOR TO CONSTRUCTION.
M. PREPARE EXISTING SURFACES THAT WILL SERVE AS SUBSTRATE TO RECEIVE THE NEW
MATERIALS FOR A LEVEL AND SMOOTH FINISH.
N. HOST ONLINE CONSTRUCTION MANAGEMENT SOFTWARE FOR THE DURATION OF THE PROJECT.
O. UNLESS DESIGNATED AS EXISTING, ALL ELEMENTS SHOWN ARE NEW.
P. REMOVE, CUT, ALTER, REPLACE, PATCH AND REPAIR EXISTING WORK AS NECESSARY TO INSTALL
NEW WORK. UPON COMPLETION OF CONTRACT, DELIVER WORK COMPLETE AND UNDAMAGED.
EXISTING WORK (WALLS, CEILINGS, PARTITIONS, FLOORS, MECHANICAL AND ELECTRICAL WORK, LAWNS, PAVING, ROADS, WALKS, ETC.) DISTURBED OR REMOVED AS A RESULT OF PERFORMING
REQUIRED NEW WORK, SHALL BE PATCHED, REPAIRED, REINSTALLED, OR REPLACED WITH NEW
WORK, AND REFINISHED AND LEFT IN AS GOOD CONDITION AS EXISTED BEFORE COMMENCING
WORK.
Q. DRAWING SET UTILIZES COLOR. FULL DRAWING SET MUST BE PRINTED IN COLOR.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Date:Revisions:No.
A u to d e s k D o c s /M t H o m e V
A
R e s to ra ti o n o f B
T h e a te r/ F
F E
M t H o m e
T h e a te r_ B
A
R C
H rv t
/1
/2
:2
:4
P M
GI000
COVER SHEET
05/30/2025 SS CD
RESTORATION OF BUILDING 35
HISTORIC THEATER
621-24-103
MT. HOME, TENNESSEE
BID DOCUMENTS
JAMES H.
QUILLEN VA
MEDICAL
CENTER
Approved: Owner
RESTORATION OF B35 THEATER
PROJECT NUMBER: 621-24-103
JAMES H. QUILLEN DEPARTMENT OF
VETERANS AFFAIRS MEDICAL CENTER
LAMONT STREET & VETERANS WAY,
MOUNTAIN HOME, TN 37604
CAMPUS LOCATION
SHEET INDEX
SHEET
NUMBER SHEET NAME
GENERAL
GI000 COVER SHEET
GI001 SYMBOLS AND ABBREVIATIONS
GI002 PARTITION TYPES AND NOTES
GI003 ACCESSIBILITY REQUIREMENTS
GI004 ACCESSIBILITY REQUIREMENTS
GI005 LIFE SAFETY PLAN
GI006 SITE AND CONSTRUCTION LAYDOWN PLAN
GI007 EXTERIOR 3D VIEWS
CIVIL
C-001 GENERAL NOTES, LEGEND, AND ABBREVIATIONS
VF101 EXISTING SITE CONDITIONS
CD101 SITE DEMOLITION PLAN
CD501 SITE DEMOLITION DETAILS
CS101 SITE PLAN
CS501 SITE DETAILS
CG101 SITE GRADING PLAN
CG401 ROOF DRAIN PROFILES
CG501 SITE GRADING DETAILS
STRUCTURAL
S-001 LEGEND
S-002 GENERAL NOTES
S-003 GENERAL NOTES
S-101 BASEMENT FOUNDATION PLAN
S-102 FIRST FLOOR PLAN
S-103 STAGE PLANS
S-104 CHANNEL GRID FRAMING PLANS
S-105 ATTIC LEVEL FRAMING PLAN
S-301 BUILDING SECTIONS
S-302 BUILDING SECTIONS
S-401 ENLARGED PLANS
S-501 FRAMING DETAILS
S-502 FRAMING DETAILS
S-503 FRAMING DETAILS
S-504 FRAMING DETAILS
S-505 TYPICAL DETAILS
ARCHITECTURE
AD101 BASEMENT AND FIRST FLOOR DEMOLITION PLAN
AD102 BALCONY, SECOND FLOOR, BOOTH, ATTIC & RAFTERS DEMO PLAN
AD103 DEMOLITION ELEVATIONS
AD104 DEMOLITION REFLECTED CEILING PLANS
AE101 BASEMENT AND FIRST FLOOR PLAN
AE102 BALCONY, SECOND FLOOR, BOOTH, ATTIC & RAFTERS PLANS
AE131 ROOF PLAN
AC141 REFLECTED CEILING PLANS
AE201 BUILDING ELEVATIONS
AE202 BUILDING ELEVATIONS
AE311 WALL SECTIONS
AE321 ENLARGED PLAZA PLAN AND DETAILS
AE322 ENLARGED RAMP AND STAIR PLAN AND SECTION DETAILS
AE401 ENLARGED PLANS
AE402 ENLARGED PLANS
AE403 ENLARGED SECTIONS
AE404 ENLARGED PLANS AND SECTION DETAILS
AE405 ENLARGED SECTION DETAILS
AE410 INTERIOR ELEVATIONS
AE411 INTERIOR SECTIONS & ELEVATIONS - LOBBY
AE412 INTERIOR SECTIONS & ELEVATIONS - LOBBY & BASEMENT
AE413 INTERIOR ELEVATIONS - STAGE
AE414 INTERIOR ELEVATIONS - STAGE
AE420 BUILDING SECTION - AUDITORIUM
AE421 BUILDING SECTION - AUDITORIUM
AE422 BUILDING SECTION - AUDITORIUM
AE423 BUILDING SECTION - AUDITORIUM
AE501 ENLARGED DETAILS
AE601 SCHEDULES
AE602 HEAD, JAMB & SILL DETAILS
AE603 TYPICAL DOOR ELEVATIONS
AE604 TYPICAL WINDOW ELEVATIONS
AE605 TYPICAL CURTAIN ELEVATIONS
AE700 PHOTOS - EXISTING CONDITIONS - P1-20
AE701 PHOTOS - EXISTING CONDITIONS - P21-41
AE702 PHOTOS - EXISTING CONDITIONS - P42-46
AE801 BASEMENT & FIRST FLOOR FINISH & SIGNAGE PLAN
AE802 BALCONY, SECOND FLOOR, CATWALK FINISH & SIGNAGE PLANS
AE803 FINISH DETAILS
FIRE SUPPRESSION
F001 ABBREVIATIONS, LEGEND & DESIGN NOTES
FD101 BASEMENT AND FIRST FLOOR DEMOLITION PLANS
FD102 BALCONY, SECOND FLOOR AND CEILING DEMOLITION PLANS
FD103 AUDITORIUM ATTIC AND STAGE ATTIC DEMOLITION PLANS
FD901 WET-PIPE FIRE SUPPRESSION ISOMETRIC
FS100 FIRE SUPPRESSION SITE PLAN
FX101 BASEMENT AND FIRST FLOOR NEW WORK PLANS
FX102 BALCONY, SECOND FLOOR AND CEILING NEW WORK PLANS
FX103 AUDITORIUM ATTIC AND STAGE ATTIC NEW WORK PLAN
F201 SECTIONS
LOCATION OF THEATERLOCATION MAP VICINITY MAP GENERAL NOTES
TRUE
NORTH
TRUE
NORTH
SHEET INDEX
SHEET
NUMBER SHEET NAME
PLUMBING
P001 ABBREVIATIONS, LEGEND & GENERAL NOTES
PD101 FOUNDATION AND BASEMENT DEMOLITION PLANS
PD102 FIRST AND SECOND FLOOR DEMOLITION PLANS
PS100 PLUMBING SITE PLAN
PP101 FOUNDATION AND BASEMENT NEW WORK PLANS
PP102 FIRST AND SECOND FLOOR NEW WORK PLANS
P401 ENLARGED PLANS
P601 DETAILS AND SCHEDULES
P901 DRAINAGE ISOMETERIC
P902 DISTRIBUTION ISOMETERIC
AUDIO-VISUAL
AV001 AUDIO VISUAL SYMBOLS & NOTES
AV002 AUDIO-VISUAL SCHEDULES
AV101 ENLARGED PLANS
AV102 ENLARGED PLANS
AV103 ENLARGED PLANS
AV104 ENLARGED PLANS
AV201 REFLECTED CEILING PLANS
AV202 REFLECTED CEILING PLANS
AV203 REFLECTED CEILING PLANS
AV301 SECTIONS
AV302 SECTIONS
AV401 BLOCK DIAGRAMS
AV402 BLOCK DIAGRAMS
AV403 BLOCK DIAGRAMS
AV404 BLOCK DIAGRAMS
AV405 BLOCK DIAGRAMS
AV406 BLOCK DIAGRAMS
AV501 AUDIO-VISUAL DETAILS
AV502 AUDIO-VISUAL DETAILS
THEATER
TE001 THEATER SYSTEMS SYMBOLS & NOTES
TE002 THEATER SYSTEMS SCHEDULES
TE101 ENLARGED PLANS
TE102 ENLARGED PLANS
TE103 ENLARGED PLANS
TE104 ENLARGED PLANS
TE201 REFLECTED CEILING PLANS
TE301 SECTIONS
TE302 SECTIONS
TE303 SECTIONS
TE304 RIGGING ELEVATIONS
TE305 RIGGING ELEVATIONS
TE306 RIGGING ELEVATIONS
TE307 RIGGING ELEVATIONS
TE308 RIGGING ELEVATIONS
TE309 RIGGING ELEVATIONS
TE310 RIGGING ELEVATIONS
TE311 RIGGING DETAILS
TE312 RIGGING DETAILS
TE401 THEATER SYSTEMS CONTROL RISER
TE402 THEATER SYSTEMS CIRCUIT SCHEDULES
TE403 POWER & CONTROL DISTRIBUTION
TE404 POWER & CONTROL DISTRIBUTION
MECHANICAL
M001 MECHANICAL LEGEND
MD101 BASEMENT AND FIRST FLOOR DEMOLITION PLANS
MD102 BALCONY, SECOND FLOOR, AND ATTIC DEMOLITION PLANS
MD103 ROOF DEMOLITION PLANS
M101 BASEMENT AND FIRST FLOOR PLANS
M102 BALCONY, SECOND FLOOR, AND ATTIC PLANS
M103 ROOF PLANS
M301 MECHANICAL SECTIONS
M501 MECHANICAL DETAILS
M600 MECHANICAL SCHEDULES
ELECTRICAL
E001 ABBREVIATIONS, LEGEND & GENERAL NOTES
E002 SINGLE LINE
E100 ELECTRICAL SITE PLAN
ED101 DEMOLITION PLANS
EP101 BASEMENT NEW WORK PLANS
EP102 FIRST FLOOR NEW WORK PLANS
EP103 SECOND FLOOR NEW WORK PLANS
EP104 ATTIC, RAFTERS, & ROOF NEW WORK PLANS
E200 PANEL SCHEDULES
E300 SCHEDULES
TECHNOLOGY
T001 ABBREVIATIONS, LEGEND & GENERAL NOTES
TD101 DEMOLITION PLANS
TD401 DATA/TELECOM ELEVATION
T101 NEW WORK PLANS
T102 ATTIC AND RAFTERS NEW WORK PLANS
T401 ENLARGED IT ROOM 003A AND ELEVATIONS
T601 DETAILS
T602 DETAILS
T603 PACS DETAILS
TOTAL SHEETS: 163
ALTERNATE
ALTERNATE
FULL REPLACEMENT OF ALL THEATER SEATING, WITH INTEGRAL
LIGHTING AT WALKWAYS BUILT INTO AISLE CHAIRS.
DEDUCT ALTERNATE
DEDUCE ALTERNATE 1
FULL REPLACEMENT OF SLATE TILE ROOF WITH SYNTHETIC TILES.
OMIT SELECTIVE REPLACEMENT OF SLATE TILES.
BID DOCUMENTS 07/01/2025
A101
SIM
GRID HEAD
CALL OUT HEAD W/ SHEET NUMBER
PLAN NORTH
(SEE CIVIL FOR TRUE NORTH)
SYMBOLS
A101
SIM BUILDING SECTION NUMBER W/ SHEET NUMBER
DOOR TAG
WALL TAGA1
2D-124
KEYNOTE
REVISION TAG
CEILING HEIGHT TAG
00.00
9' - 0"
WINDOW TAGA
MATERIAL TAGP-1
EQUIPMENT TAG - JSN NUMBERF0340
ROOM TAG WITH NAME AND NUMBER
FIRST 2 DIGITS CORRESPOND TO SPEC DIVISION
EXPANSION JOINTEJ
ROOM NAME
1D-124
CARD READER - 44" MH
KEYPAD - 44" MH
REQUEST TO EXIT BUTTON - 44" MH
AUTO OPERATOR MOTOR - ABOVE DOOR
ELECTRIC DOOR LATCH - MOUNTED IN PANIC HARDWARE. PROVIDE
ELECTRIC TRANSFER ON HINGE SIDE OF DOOR FRAME.
ELECTRIC DOOR STRIKE - MOUNT IN DOOR FRAME
DOOR CONTACT - MOUNT TOP OF DOOR NEAR LATCH SIDE OF DOOR.
N
PS
N
FIRE ALARM CONTROL PANEL
FIRE ALARM ANNUNCIATOR PANEL
FIRE ALARM STROBE
FIRE ALARM SPEAKER/STROBE. 80" MH.
FIRE ALARM CHIME/STROBE. 80" MH.
FIRE ALARM SPEAKER/STROBE CEILING MOUNTED
SMOKE DETECTOR
DUCT DETECTOR. "R" INDICATES RETURN DUCT. "S"
INDICATES SUPPLY DUCT.
DUCT REMOTE TEST STATION
KNOX BOX
FIRE ALARM CONTROL RELAY. C- CONTROL, I-INPUT.
DOOR HOLDER
HEAT DETECTOR
FACP
FAA
F
F
F
S
H
S
R
K
AM
D
R
C
FIRE ALARM
DATA/TELEPHONE
NURSE CALL - A/V
SECURITY / ACCESS CONTROL
LIGHTING
DATA/TELEPHONE OUTLET. PROVIDE (2) CAT 6a CABLES WITHIN
CONDUIT OR OTHER APPROVED RACEWAY FROM OUTLET TO
NEAREST IT CLOSET OR CABLE TRAY. SUBSCRIPT INDICATES # OF
DATA CABLES.
NURSE CALL STATION
PS = PATIENT STATION
TS = TOILET STATION WITH PULL STRING
SW = SHOWER STATION
DS = DUTY STATION
MS = MASTER STATION
SS = STAFF STATION
NURSE CALL STATION
ZL = ZONE INDICATING DOME LIGHT FOR CORRIDOR
NURSE CALL SIGNAL
BEDSIDE TELEVISION
PA SPEAKER, CEILING MOUNTED
TV
1' x 4' LAYIN LED FIXTURE. UPPERCASE INDICATES TYPE PER THE FIXTURE SCHEDULE. LOWER CASE LETTER "a" INDICATES SWITCH ZONE.
2' x 4' LED LAYIN FIXTURE.
WALL MOUNTED FIXTURE OR SURFACE MOUNTED
FIXTURE.
WALL MOUNTED FIXTURE.
SINGLE FACE EXIT SIGN WITH DIRECTIONAL ARROWS AS INDICATED
RECESSED FIXTURE, DOWNLIGHT
3-WAY, 20 AMP, 125 VOLT TOGGLE SWITCH MOUNTED 44" AFF.
4-WAY, 20 AMP, 125 VOLT TOGGLE SWITCH MOUNTED 44" AFF.
WALL MOUNTED OCCUPANCY SENSOR WITH OVERRIDE SWITCH.
CEILING MOUNTED OCCUPANCY SENSOR, VACANCY SENSOR
20 AMP, 125 VOLT SINGLE-POLE TOGGLE SWITCH MOUNTED 44" AFF.
a - CONTROLS LIGHTS WITH "a" DESIGNATION
LIGHTING CONTROLLER
20A, 125V DIMMER SWITCH MOUNTED 42" AFF. 0-10V CONTROL.
2' x 2' LED LAYIN FIXTURE.
CEILING MOUNTED DAYLIGHT SENSOR
PHOTOCELL
A1 a a
OS
D
OS
DS
LC#
PC
BOLLARD LIGHT FIXTURE
D
EMERGENCY LIGHT FIXTURE. 90 MIN. BATTERY. PROVIDE HI
CAPACITY BATTERY WHERE REMOTE HEADS ARE REQUIRED.
DOUBLE-POLE, 20 AMP, 125 VOLT TOGGLE SWITCH MOUNTED 44" AFF.
20 AMP, 125 VOLT SINGLE-POLE TOGGLE PILOT LIGHT SWITCH
MOUNTED 44" AFF. P
A2
A3
LIGHTING CONTROLS
S
POLE LIGHT
F
F FIRE ALARM SENDING STATION. 44" AFF.
20 AMP, 125 VOLT MOTOR RATED SWITCH.
M
DOUBLE FACE EXIT SIGN WITH DIRECTIONAL ARROWS AS INDICATED
SINGLE FACE EXIT SIGN WITH TWIN EMERGENCY HEADS. 90 MIN. BATTERY
VALVE TAMPER SWITCHVS
FLOW SWITCHFS
PRESSURE SWITCHPS
CR
KP
RE
A
DL
DS
DC
CC
REQUEST TO EXIT MOTION DETECTOR - ABOVE DOORRM
CCTV CAMERA - DOME TYPE-1. MOUNTED IN CEILING. SEE CAMERA
SCHEDULE FOR CAMERA TYPE, MOUNTING HARDWARE.
MAG LOCK - MOUNT LATCH SIDE TOP OF DOOR. PROVIDE 120V POWER FOR
MAG POWER SUPPLY ABOVE DOOR. (OR LOCATION AS INDICATED).
ML
AP WIRELESS ACCESS POINT - CEILING MOUNT
POST INDICATOR VALVEPIV
NOTE: NOT ALL SYMBOLS HAVE
NECESSARILY BEEN USED IN THIS PROJECT
PENDANT FIXTURE
POWER
FLUSH FLOOR MOUNTED NEMA 5-20R DUPLEX
RECEPTACLE UNLESS NOTED OTHERWISE
FLUSH FLOOR MOUNTED NEMA 5-20R QUAD RECEPTACLE
UNLESS NOTED OTHERWISE
NEMA 5-20R DUPLEX RECEPTACLE MOUNTED 18" AFF
UNLESS NOTED OTHERWISE
SUBSCRIPT: WP - WEATHERPROOF, GF - GROUND FAULT CIRCUIT
INTERRUPTER, T - TAMPER RESISTANT
NEMA 5-20R DOUBLE DUPLEX RECEPTACLE MOUNTED 18" AFF
UNLESS NOTED OTHERWISE
NEMA 5-20R DUPLEX RECEPTACLE MOUNTED 44" AFF
UNLESS NOTED OTHERWISE
RECEPTACLE, (NEMA CONFIGURATION AS NOTED)
NEMA 5-20R DUPLEX RECEPTACLE WITH USB CHARGER MOUNTED 18" AFF
UNLESS NOTED OTHERWISE
NEMA 5-20R DUPLEX SPLIT RECEPTACLE MOUNTED 18" AFF
UNLESS NOTED OTHERWISE
NEMA 5-20R SIMPLEX RECEPTACLE MOUNTED 18" AFF
UNLESS NOTED OTHERWISE
JUNCTION BOX
POWER CONNECTION
MOTOR
NON-FUSED DISCONNECT SWITCH. SIZE SHOWN AS INDICATED OR IN THE
MOTOR SCHEDULE
FUSED DISCONNECT SWITCH. 30A/30F - 30A DISCONNECT, 30A FUSE
COMBINATION STARTER
SURFACE MOUNTED PANELBOARD.
RECESSED MOUNTED PANELBOARD
WP/GF
6-30R
J
EMERGENCY LIGHTING
SOLID FILL INDICATES FIXTURE ON LIFE SAFETY OR EMERGENCY CIRCUIT.
(WHERE GENERATOR POWER IS NOT AVAILABLE PROVIDE A UNIT BATTERY
AT 1400 LM)
DIAGONAL FILL INDICATES FIXTURE ON CRITICAL CIRCUIT.
MECHANICAL
CEILING ACCESS PANEL
SUPPLY - LINEAR DIFFUSER
SUPPLY
RETURN
EXHAUST
ABBREVIATIONS
ACT ACOUSTICAL CEILING TILE
AFF ABOVE FINISH FLOOR
ALT. ALTERNATE
ALUM ALUMINUM
APPROX. APPROXIMATE
ARCH. ARCHITECT/ ARCHITECTURAL
B.U.R. BUILT-UP ROOFING
BLDG. BUILDING
BOT. BOTTOM
C.J. CONSTRUCTION JOINT
C.O. CONTRACTING OFFICER
C.O.R. CONTRACTING OFFICER'S REPRESENTATIVE
CC CONTRACTOR FURNISHED AND INSTALLED
CLR. CLEAR
CMU CONCRETE MASONRY UNIT
COL COLUMN
CONC. CONCRETE
CONT CONTINUOUS
CPT CARPET
CT CERAMIC TILE
CTR. CENTER
CV CONTRACTOR FURNISHED/ V.A. INSTALLED
DIA. DIAMETER
DIM. DIMENSION
DIV. DIVISION
DWGS DRAWINGS
(E) EXISTING
E.A. EACH
E.J. EXPANSION JOINT
EQ EQUAL
ETR EXISTING TO REMAIN
EX. EXAMPLE
EXP. A. EXPANSION ANCHOR
EXT. EXTERIOR
F.D. FLOOR DRAIN
F.E. FIRE EXTINGUISHER
F.E.C. FIRE EXTINGUISHER CABINET
F.O.B. FACE OF BUILDING
FTG. FOOTING
G.B. GRAB BAR
GA. GAUGE
GALV. GALVANIZED
GSF GROSS SQUARE FOOTAGE
GYP GYPSUM BOARD
H.M. HOLLOW METAL
H.S.S. HOLLOW STRUCTURAL STEEL
ICRA INFECTION CONTROL RISK ASSESSMENT
M.E.P. MECHANICAL, ELECTRICAL, PLUMBING
MAX MAXIMUM
MECH. MECHANICAL
MIN. MINIMUM
MISC. MISCELLANEOUS
MTD. MOUNTED
(N) NEW
N.I.C. NOT IN CONTRACT
N.T.S. NOT TO SCALE
O.C. ON CENTER
OPNG OPENING
OPP. OPPOSITE
P. PAINT
P.S.F. POUNDS PER SQUARE FOOT
P.S.I. POUNDS PER SQUARE INCH
PL. PLATE
PT PORCELAIN TILE
Q.T. QUARRY TILE
R.C.P. REFLECTED CEILING PLAN
R.D. ROOF DRAIN
R.O. ROUGH OPENING
RAD. RADIUS
RB RUBBER BASE
REF. REFERENCE
REINF. REINFORCING
RES RESINOUS FLOORING
SF SQUARE FOOT (FEET)
SIM. SIMILAR
SOG SLAB ON GRADE
SPEC. SPECIFICATION
SS STAINLESS STEEL
T.O.C. TOP OF CURB
T.O.P. TOP OF PAVEMENT
TME TO MATCH EXISTING
TYP. TYPICAL
U.N.O. UNLESS NOTED OTHERWISE
V.C.T. VINYL COMPOSITION TILE
V.I.F. VERIFY IN FIELD
VB VAPOR BARIER
VC V.A. FURNISHED/ CONTRACTOR INSTALLED
VT VINYL TILE
VV V.A. FURNISHED AND INSTALLED
W.C. WATER CLOSET
W.W.F. WELDED WIRE FABRIC
WSF WELDED SEAM SHEET FLOORING
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Date:Revisions:No.
A u to d e s k D o c s /M t H o m e V
A
R e s to ra ti o n o f B
T h e a te r/ F
F E
M t H o m e
T h e a te r_ B
A
R C
H rv t
/1
/2
:2
:4
P M
GI001
SYMBOLS AND ABBREVIATIONS
05/30/2025 SS CD
RESTORATION OF BUILDING 35
HISTORIC THEATER
621-24-103
MT. HOME, TENNESSEE
BID DOCUMENTS
JAMES H.
QUILLEN VA
MEDICAL
CENTER
Approved: Owner
WALL BASE - SEE FINISH SCHEDULE
2 X 4 BOTTOM PLATE
FINISHED FLOOR - SEE SCHEDULE
(1) LAYER GYPSUM BOARD ON
EACH SIDE
FULL HEIGHT SOUND
ATTENUATION BLANKET
2 X 4 WOOD STUDS AT 16" O.C.
CEILING SEE ROOM FINISH SCHEDULE FOR TYPE
AND LOCATION
2 X 4 TOP PLATE - EXTEND STUDS TO
UNDERSIDE OF EXISTING STRUCTURE ABOVE
CONTINUOUS OR ACOUSTIC SEALANT IN ALL
VOIDS ABOVE TRACK ON BOTH SIDES OF
PARTITION.
STRUCTURE ABOVE
SUBSTRATE [1] SIDE SUBSTRATE [2] SIDE
FULL HEIGHT 1/2" PLYWOOD SHEATHING BETWEEN
STUDS (ON BATHROOM SIDE OF WALL ONLY)
BLOCKING AS RERQUIRED FOR PLYWOOD SHEATHING
WALL BASE - SEE FINISH SCHEDULE
FINISHED FLOOR - SEE SCHEDULE
(1) LAYER GYPSUM BOARD, BACKER BOARD,
AND/OR FIRE RATED PLYWOOD
CEILING SEE ROOM FINISH SCHEDULE FOR
TYPE AND LOCATION
STRUCTURE ABOVE
RIGID INSULATION
SUBSTRATE [1] SIDE SUBSTRATE [2] SIDE
EXISTING CONTRUCTION
VARIES - SEE BELOW
2 X 4 BOTTOM PLATE
CONTINUOUS OR ACOUSTIC SEALANT IN ALL
VOIDS ABOVE TRACK ON BOTH SIDES OF
PARTITION.
2 X 4 WOOD STUDS AT 16" O.C.
1 1/2"
FULL HEIGHT 1/2" PLYWOOD SHEATHING BETWEEN
STUDS (ON BATHROOM SIDE OF WALL ONLY)
BLOCKING AS RERQUIRED FOR PLYWOOD SHEATHING
WALL TILE
FINISHED FLOOR - SEE SCHEDULE
(1) 1/2" BACKER BOARD
FULL HEIGHT SOUND
ATTENUATION BLANKET
CEILING SEE ROOM FINISH SCHEDULE FOR
TYPE AND LOCATION
SLIP HEAD CONNECTION AT HEAD
STRUCTURE ABOVE
SUBSTRATE [1] SIDE SUBSTRATE [2] SIDE
(1) LAYER MOISTURE RESISTANT GYPSUM BOARD
CONTINUOUS POLYETHYLENE
MEMBRANE
2 X 4 BOTTOM PLATE
2 X 4 TOP PLATE - EXTEND STUDS TO
UNDERSIDE OF EXISTING STRUCTURE ABOVE
WALL BASE - SEE FINISH SCHEDULE
FULL HEIGHT 1/2" PLYWOOD SHEATHING BETWEEN
STUDS (ON BATHROOM SIDE OF WALL ONLY)
BLOCKING AS RERQUIRED FOR PLYWOOD SHEATHING
(2) LAYER 5/8" TYPE-X GYPSUM WALL
BOARD
CEILING SEE ROOM FINISH SCHEDULE FOR
TYPE AND LOCATION
WALL BASE - SEE SCHEDULE
FINISHED FLOOR - SEE SCHEDULE
3 1/2" MINERAL WOOL
INSULATION
2 X 4 WOOD STUD AT 16" O.C.
CONTINUOUS OR ACOUSTIC SEALANT IN ALL
VOIDS ABOVE TRACK ON BOTH SIDES OF
PARTITION.
STRUCTURE ABOVE
SUBSTRATE [1] SIDE -
SHAFT INTERIOR
SUBSTRATE [2] SIDE
(2) LAYER 5/8" TYPE-X GYPSUM WALL
BOARD
2 X 4 DOUBLE TOP PLATE
2 X 4 BOTTOM PLATE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Date:Revisions:No.
A u to d e s k D o c s /M t H o m e V
A
R e s to ra ti o n o f B
T h e a te r/ F
F E
M t H o m e
T h e a te r_ B
A
R C
H rv t
/1
/2
:2
:5
P M
GI002
PARTITION TYPES AND NOTES
05/30/2025 SS CD
RESTORATION OF BUILDING 35
HISTORIC THEATER
621-24-103
MT. HOME, TENNESSEE
BID DOCUMENTS
JAMES H.
QUILLEN VA
MEDICAL
CENTER
Approved: Owner
P. TYPICAL PARTITION
P5 - 2 X 6 WOOD STUD (1) 5/8" GYPSUM BOARD 3 1/2" SOUND ATTENUATION BLANKET 16" O.C. - - -
P4 6 3/4" (1) 5/8" GYPSUM BOARD 2 X 6 WOOD STUD (1) 5/8" GYPSUM BOARD 3 1/2" SOUND ATTENUATION BLANKET 16" O.C. - - 44
P3 5 1/2" (1) 5/8" GYPSUM BOARD 2 X 4 WOOD STUD
(1) 5/8" GYPSUM BOARD
(1) 3/4" FIRE RATED
PLYWOOD
3 1/2" SOUND ATTENUATION BLANKET 16" O.C. - - -
P2 4 1/8" - 2 X 4 WOOD STUD (1) 5/8" GYPSUM BOARD 3 1/2" SOUND ATTENUATION BLANKET 16" O.C. - - -
P1 4 3/4" (1) 5/8" GYPSUM BOARD 2 X 4 WOOD STUD (1) 5/8" GYPSUM BOARD 3 1/2" SOUND ATTENUATION BLANKET 16" O.C. - - 44
NUMBER
WALL
THICKNESS
SUBSTRATE [1] CORE STRUCTURE SUBSTRATE [2] INSULATION / BATT STUD SPACING
FIRE
RATING
UL STC
F. FURR-OUT PARTITION
F5 2 7/8" 1'-0" AIR GAP 2 X 4 WOOD STUD
(1) 5/8" GYPSUM BOARD
(1) 3/4" FIRE RATED
PLYWOOD
1 1/2" RIGID INSULATION 16" O.C. -- -- --
F4 2 1/8" -- 2 X 4 WOOD STUD (1) 5/8" GYPSUM BOARD 1 1/2" RIGID INSULATION 16" O.C. -- -- --
F3 2 7/8" 1" AIR GAP 2 X 4 WOOD STUD
(1) 5/8" GYPSUM BOARD
(1) 3/4" FIRE RATED
PLYWOOD
1 1/2" RIGID INSULATION 16" O.C. -- -- --
F2 2 1/2" 1" AIR GAP 2 X 4 WOOD STUD
(1) 1/2" BACKER BOARD
(1) 1/2" WALL TILE
1 1/2" RIGID INSULATION 16" O.C. -- -- --
F1 2 1/8" 1" AIR GAP 2 X 4 WOOD STUD (1) 5/8" GYPSUM BOARD 1 1/2" RIGID INSULATION 16" O.C. -- -- --
NUMBER
WALL
THICKNESS
SUBSTRATE [1] CORE STRUCTURE SUBSTRATE [2] INSULATION / BATT STUD SPACING
FIRE
RATING
UL STC
T. TILE PARTITION
T2 5 1/8"
(1) 5/8" MOISTURE
RESISTANT GYPSUM
BOARD
COLD FORMED METAL
(1) 1/2" BACKER BOARD
(1) 1/2" WALL TILE
3 1/2" SOUND ATTENUATION BLANKET 16" O.C. - - 44
T1 4 1/2" - COLD FORMED METAL
(1) 1/2" BACKER BOARD
(1) 1/2" WALL TILE
3 1/2" SOUND ATTENUATION BLANKET 16" O.C. - - 44
NUMBER
WALL
THICKNESS
SUBSTRATE [1] CORE STRUCTURE SUBSTRATE [2] INSULATION / BATT STUD SPACING
FIRE
RATING
UL STC
A. REFER TO GI000 FOR GENERAL NOTES.
B. REFERENCE FLOOR PLANS FOR PARTITION TYPE LOCATION.
C. COORDINATE WITH MECHANICAL, ELECTRICAL, AND PLUMBING PLANS FOR OPENINGS THAT ACCOMMODATE NEW
MECHANICAL, ELECTRICAL, AND PLUMBING WORK.
D. ANCHOR GYPSUM BOARD WITH SCREWS AT 8" O.C. MAX. ON EDGES AT 12" O.C. MAX. IN FIELD PER UL DESIGN
NUMBERS LISTED.
E. LABEL ALL RATED PARTITIONS ABOVE CEILING WITH PLAQUE OR STENCILED SIGN READING: "(SMOKE BARRIER/ FIRE
BARRIER/ SMOKE RESISTIVE) : SEAL AND PROTECT ALL OPENINGS". REFER TO PARTITION SCHEDULE ON THIS SHEET
FOR RATING TYPE. SIGN SHALL BE PLACED ON BOTH SIDES OF PARTITIONS.
F. COORDINATE FRAMING WITH FIRE AND SMOKE DAMPERS AT PENETRATIONS IN RATED PARTITIONS.
G. PROVIDE CONTINUOUS FIRE RATED SEALANT AT THE PERIMETER OF ALL FIRE RATED WALLS AND CHASES, INCLUDING
THE TOP, BOTTOM, AND SIDE EDGES ON BOTH SIDES OF WALL.
H. ROUGH OPENING FRAMING CONFIGURATIONS DEPICTED BY THE FRAME OF THE WALL ROUGH OPENING DIAGRAM ARE
BASED ON COLD FORMED METAL STUD FRAMED WALL PARTITIONS AND ARE CONCEPTUAL IN NATURE - REFER TO
ENLARGED DETAILS FOR FURTHER CONTEXT.
I. PROVIDE A MINIMUM OF ONE STUD SEPARATION BETWEEN OUTLET BOXES AND OTHER PENETRATIONS OCCURRING AT
OPPOSITE FACE OF WALLS.
J. PROVIDE WALL REINFORCEMENT BETWEEN STUDS WHERE REQUIRED BY INSTALLATION OF MILLWORK AND/OR WALL
HUNG EQUIPMENT.
K. PROVIDE ADDITIONAL BRACING AS REQUIRED AT ALL WALL STUD INSTALLATIONS EXCEEDING STUD MANUFACTURER
REQUIREMENTS FOR MAXIMUM ALLOWED HEIGHT AND DEFLECTION.
L. PROVIDE MOISTURE RESISTIVE GYPSUM BOARD SHEATHING IN ALL AREAS THAT ARE PRONE TO HIGH HUMIDITY SUCH
AS BATHROOMS, KITCHENS, LAUNDRY ROOMS OR OTHER AREAS WITH PLUMBING FIXTURES.
M. PROVIDE CONTINUOUS NON-HARDENING ACOUSTICAL SEALANT AT TOP, SIDES AND EDGES OF BOTH SIDES OF WALL AT ALL NON-RATED GYPSUM BOARD PARTITIONS SCHEDULED TO RECEIVE SOUND ATTENUATION BLANKETS.
N. ALL PENETRATIONS AT NON-RATED WALLS SHALL BE SLEEVED AND PACKED AIRTIGHT WITH SAFING INSULATION AND SEALANT. ALL JOINT OF GYPSUM BOARD PANELS SHALL BE STAGGERED, TAPED, AND SEALED. FRAMING TO 1/2" +/-
CLEARANCE AT PERIMETER OF MECHANICAL DUCTWORK.
O. PLACE SOUND ATTENUATION BATTS (SAB) IN ALL PARTITIONS THAT ENCLOSE A ROOM UNLESS NOTED OTHERWISE.
P. WHERE WALL TYPE GRAPHICS DEPICT REINFORCED CONCRETE OR MASONRY UNIT CONSTRUCTION, REINFORCING
SYMBOLS ARE OMITTED FOR CLARITY. REFER TO STRUCTURAL DRAWINGS FOR REINFORCEMENT DESIGN.
Q. UNLESS NOTED, THE CONNECTION AT THE TOP OF THE PARTITION TO THE STRUCTURE ABOVE MUST ALLOW FOR 1"
MINIMUM VERTICAL MOVEMENT, EITHER UP OR DOWN. AT FIRE RATED COLD-FORMED STEEL FRAMING PARTITIONS, THE TOP CONNECTION MUST BE A FIRE STOP CONNECTION THAT ALLOWS FOR 1" MINIMUM VERTICAL MOVEMENT, EITHER UP OR DOWN. HOLD GYPSUM WALL BOARD AND STEEL STUDS 1" FROM THE BOTTOM OF THE STRUCTURE ABOVE. DO NOT SCREW-ATTACH STEEL VERTICAL STUDS OR GYPSUM WALL BOARD TO THE TOP TRACK. INSTALL
BRIDGING 12" MINIMUM FROM THE TOP OF THE STUDS.
R. PARTITION SCHEDULE IS BASED ON THE USE OF GYPSUM WALL BOARD (GWB), BUT FACING BOARD MAY VARY, DEPENDENT ON FINAL FINISH SCHEDULED FOR THAT PARTITION: USE CEMENTITIOUS BACKER BOARD (CBB) WHERE CERAMIC TILE SCHEDULED IN "WET" AREAS; USE GYPSUM LATH (BLUE BOARD) WHERE VENEER PLASTIC IS SCHEDULED. SEE FINISH SCHEDULE AND SPECIFICATIONS FOR PARTICULARS. AT ALL PLUMBING FIXTURES INSTALL
4X8 (MR) MOISTURE RESISTANT BOARD CENTERED ON FIXTURE.
GENERAL PARTITION NOTES
S. SHAFT PARTITION
S1 6"
(2) LAYER 5/8" TYPE-X
GYPSUM WALL BOARD
2 X 4 WOOD STUD
(2) LAYER 5/8" TYPE-X
GYPSUM WALL BOARD
3 1/2" MINERAL WOOL
INSULATION
3 1/2" 12" O.C. 2 HR U301 58
NUMBER
WALL
THICKNESS
SUBSTRATE [1] CORE STRUCTURE SUBSTRATE [2] INSULATION / BATT
STUD
SIZE
STUD SPACING
FIRE
RATING
UL STC
M
IN
FRONT APPROACH, PUSH SIDE
M
IN
FRONT APPROACH, PUSH SIDE, DOOR
PROVIDED WITH BOTH CLOSER AND LATCH
M
IN
12" MIN
M
IN
HINGE APPROACH, PULL SIDE
36" MIN
M
IN
HINGE APPROACH, PULL SIDE
42" MIN
HINGE APPROACH, PUSH SIDE
M
IN
22" MIN
HINGE APPROACH, PUSH SIDE, DOOR
PROVIDED WITH BOTH CLOSER AND
LATCH
M
IN
22" MIN 48
M
IN
LATCH APPROACH, PULL SIDE
24" MIN 54
M
IN
LATCH APPROACH, PULL SIDE, DOOR PROVIDED
WITH CLOSER
24" MIN
LATCH APPROACH, PUSH SIDE
M
IN
24" MIN
LATCH APPROACH, PUSH SIDE, DOOR
PROVIDED WITH CLOSER
M
IN
24" MIN
18" MIN
FRONT APPROACH, PULL SIDE
RECESSED DOOR/ GATE (RECESSED
GREATER THAN 8"
M
IN
M
IN
18" MIN
12"
FINISH FLOOR
FINISH FLOOR
CARPET
1:2 SLOPE MAX
1:2 SLOPE MAX
DOOR
1/ 4"
1/ 2"
1/ 4"
1/ 4"
M A
X
1/ 2"
M A
X
1/ 2"
M A
X
FINISH FLOOR
FRONT APPROACH
M
IN
M
IN
SIDE APPROACH
22" MIN
POCKET OR HINGE APPROACH
M
IN
STOP OR LATCH APPROACH
24" MIN
M
IN
30" MIN
M
IN
CLEAR FLOOR OR GROUND CLEARANCE
30" MIN
M
IN
FORWARD APPROACH
48" MIN
M
IN
PARALLEL APPROACH
60" MIN
X
CLEARANCE, ALCOVE, PARALLEL APPROACH
36" MIN
X
CLEARANCE, ALCOVE, FORWARD APPROACH
M
IN
1/
2"
1 1/2" MIN
NOMINAL DIM. 1 1/4"
DIA MIN - 1 1/2" DIA
MAX, TYP
SURFACE-MOUNTED HANDRAIL
SECTION
ABSOLUTE
1 1/2"
3" MAX
1/
2" M
IN
1'
-6
M
IN
RECESSED HANDRAIL SECTION
HANDRAIL NOTES
1. HANDRAIL ENDS SHALL BE RETURNED SMOOTHLY TO A WALL, GUARD, LANDING
SURFACE OR CONTINUOUS TO THE HANDRAIL OF AN ADJACENT RAMP.
2. HANDGRIP PORTION OF HANDRAILS SHALL HAVE A SMOOTH SURFACE WITH NO
SHARP CORNERS AND UNINTERRUPTED. EDGES SHOULD HAVE A 1/8" RADIUS.
3. WALLS OR OTHER SURFACES ADJACENT TO THE HANDRAILS SHALL BE FREE OF
SHARP OR ABRASIVE ELEMENTS.
M
IN
25" MAX
SIDE VIEW
PLAN
FINISH
FLOOR
8" MIN
11" MIN
M
IN
9" M
IN
ELEMENT
ELEMENT
4" MAX
X
7"
M
IN
PROTRUDING
OBJECTS
M
IN
M A
X
UNOBSTRUCTED FORWARD APPROACH OBSTRUCTED HIGH FORWARD APPROACH
>20" - 25" MAX
M A
X
M A
X
M
IN 48
M
A X
10" MAX
M A
X
M A
X
10" MAX
UNOBSTRUCTED SIDE APPROACH OBSTRUCTED HIGH SIDE APPROACH
M A
X
M A
X
>10" - 24" MAX
20" MAX
18" MIN
M
IN
CENTERED ON
TACTILE CHARACTERS
9" M
IN
M
IN
17" - 25"
SIDE VIEW
PLAN
6" MAX
FINISH FLOOR
ELEMENT
ELEMENT
30"
CIRCULAR TURNING SPACE
6" MAX 8" MIN
9" M
IN
M
IN
15" MIN 5" MAX
M A
X
FRONT VIEW SIDE VIEW
NOTE:
1. LOW SPOUT OUTLET SHALL BE 36" MAX
AFF / GROUND; 27" MIN. CLEAR TO
UNDERSIDE OF FIXTURE
2. HIGH SPOUT OUTLET SHALL BE 38" MIN
AFF / GROUND AND 43" MAX AFF
LOW SPOUT
OUTLET
HIGH SPOUT
OUTLET
ALCOVE INSTALLATION
30"X48" APPROACH
SPACE
M A
X
M
IN
ACCESSIBLE
DRINKING
FOUNTAIN
STANDING
DRINKING
FOUNTAIN
M A
X
9" M
IN
48" MIN
M
IN
M
IN
R E
F E
R T
O P
LA
N
S
15" MIN
PLAN VIEW
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Date:Revisions:No.
A u to d e s k D o c s /M t H o m e V
A
R e s to ra ti o n o f B
T h e a te r/ F
F E
M t H o m e
T h e a te r_ B
A
R C
H rv t
/1
/2
:2
:5
P M
GI003
ACCESSIBILITY REQUIREMENTS
05/30/2025 SS CD
RESTORATION OF BUILDING 35
HISTORIC THEATER
621-24-103
MT. HOME, TENNESSEE
BID DOCUMENTS
JAMES H.
QUILLEN VA
MEDICAL
CENTER
Approved: Owner
12" = 1'-0"
ACCESSIBILITY SYMBOL
1/4" = 1'-0"
ACCESSIBLE SWING DOOR CLEARANCES
3" = 1'-0"
CHANGE OF ELEVATION
1/4" = 1'-0"
DOORWAY CLEARANCES
3/8" = 1'-0"
GROUND AND FLOOR CLEARANCE
1/2" = 1'-0"
HANDRAIL REQUIREMENTS
1/2" = 1'-0"
KNEE CLEARANCE
3/8" = 1'-0"
PROTRUDING OBJECTS CLEARANCE
1/4" = 1'-0"
REACH RANGE
1/2" = 1'-0"
TACTILE SIGN LOCATION AT DOORS
1/2" = 1'-0"
TOE CLEARANCE
1/4" = 1'-0"
TURNING SPACE
1/2" = 1'-0"
DRINKING FOUNTAIN CLEARANCE
15" MIN 3
M A
X
R E
F L E
C T
E D
S U
R F
A C
E
M A
X
M A
X
M
IN
SIDE VIEWFRONT VIEW
M
IN
6" MAX
MIRROR
LAVATORY
1'-3" MIN
M
IN
30" MIN
INSULATE EXPOSED PIPING
M A
X
M
IN
M
IN
6"
1"
KNEE CLEARANCE
RISES FROM 9" AT 6:1
30"X48" APPROACH
SPACE
11" MIN
KNEE CLEARANCE 6:1
RISE RATE
M A
X
48" MIN
30"X48"
APPROACH
3"
TOE CLEARANCE
KNEE
CLEARANCE
KNEE CLEARANCE
25" MAX
17" MIN
TOE CLEARANCE
PLAN
M A
X
M
IN
SOAP DISPENSER
SURFACE
COMBINATION PAPER TOWEL
DISPENSER / WASTE
RECEPTACLE
M A
X
DIAPER CHANGING
STATION
M A
X
M
IN
P R
E F
E R
R E
D H
E
IG
H T
M A
X
MIRROR
EXAMPLE
R E
Q U
IR
E
D A
C C
E S
S
IB
L E
M A
X
R E
Q U
IR
E
D A
C C
E S
S
IB
L E
M
IN
P R
E F
E R
R E
D H
E
IG
H T
P R
E F
E R
R E
D H
E
IG
H T
P R
E F
E R
R E
D H
E
IG
H T
25" MAX
SANITARY NAPKIN
DISPOSAL
P R
E F
E R
R E
D H
E
IG
H T
M A
X
M
IN
M
IN
P R
E F
E R
R E
D H
E
IG
H T
TOILET PAPER
DISPENSER
7"- 9"
C E
N T
E R
L
IN
E O
F
D
IS
P E
N S
E R
U N
IT
F R
O N
T O
F T
O
IL
E T
M
IN
M A
X
M
IN
SANITARY NAPKIN
DISPOSAL
MAINTAIN SIDE GRAB BAR
CLEARANCES IN BOTH WHEELCHAIR
ACCESSIBLE AND AMBULATORY
ACCESSIBLE WATER CLOSETS
12" MIN 24" MIN
36" MIN
16"- 18"
TRANSFER SIDE
M A
X
SIDE VIEWFRONT VIEW
NO MOUNTED ITEMS
BEHIND GRAB BAR
MOUNT BELOW GRAB
BAR IF POSSIBLE
39"-41"
54" MIN
42" MIN12" MAX
17"-19"
AMBULATORY
ACCESSIBLE WATER
CLOSET
WHEELCHAIR
ACCESSIBLE WATER
CLOSETS
16"-18"
3'-0" MIN 5'-0" MIN
2"
'-8
M
IN
GRAB BARS REQUIRED
IN ALL STALLS
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Date:Revisions:No.
A u to d e s k D o c s /M t H o m e V
A
R e s to ra ti o n o f B
T h e a te r/ F
F E
M t H o m e
T h e a te r_ B
A
R C
H rv t
/1
/2
:2
:5
P M
GI004
ACCESSIBILITY REQUIREMENTS
05/30/2025 SS CC
RESTORATION OF BUILDING 35
HISTORIC THEATER
621-24-103
MT. HOME, TENNESSEE
BID DOCUMENTS
JAMES H.
QUILLEN VA
MEDICAL
CENTER
Approved: Owner
1/2" = 1'-0"
ACCESSIBLE LAVATORY CLEARANCE
1/2" = 1'-0"
TOILET FIXTURES AND ACCESSORIES
1/2" = 1'-0"
WHEELCHAIR ACCESSIBLE WATER CLOSET CLEARANCES
1/2" = 1'-0"
WATER CLOSET TYPE REQUIREMENTS
EXIT SIGN (WITH DIRECTIONAL ARROWS)
FULLY RECESSED FIRE EXTINGUISHER CABINET
AUTOMATIC ELECTRONIC DEFIBRILLATOR
FIRE DEPARTMENT CONNECTION
COMMON PATH
TRAVEL DISTANCE
AED
FE-1
FDC
SURFACE MOUNTED FIRE EXTINGUISHER CABINET
FE
LOBBY
MEN'S
TOILET
110A
TOILET
111A
TOILET
TOILET
DRESSING ROOM
STAGE
AUDITORIUM
CORRIDOR
101A
BOOTH
101B
CORRIDOR
101C
BOOTH
101D
UP
UP
DN
DN
DN
UP
DN
UP
UP
UP
DN
DN
DN
UP
STORAGE
DRESSING ROOM
CORRIDOR
WOMEN'S
DN
MECHANICAL
110B
MECHANICAL
111B
EXIT TRAVEL DISTANCE
75'-0"
FE-A
FE-B
FE-C
FE-A
F E
-1
UP
DOOR EXIT CAPACITY:
70" / 0.22 = 318 OCCUPANTS
DOOR EXIT CAPACITY:
70" / 0.22 = 318 OCCUPANTS
DOOR EXIT CAPACITY:
70" / 0.22 = 318 OCCUPANTS DOOR EXIT CAPACITY:
70" / 0.22 = 318 OCCUPANTS
DOOR EXIT CAPACITY:
70" / 0.22 = 318 OCCUPANTS
DOOR EXIT CAPACITY:
70" / 0.22 = 318 OCCUPANTS
DOOR EXIT CAPACITY:
70" / 0.22 = 318 OCCUPANTS
DOOR EXIT CAPACITY:
40" / 0.22 = 182 OCCUPANTS
DOOR EXIT CAPACITY:
73" / 0.22 = 331 OCCUPANTS
1:
S
LO
P E 1:
S
LO
P E
1:
S
LO
P E
DN
" 4' - 10"
4' - 10"
3' - 0"
3' - 0"
4' - 6"
(MAINTENANCE STAIR USE ONLY)
STAIR EXIT CAPACITY:
30" / 0.3 = 100 OCCUPANTS
OCCUPANCY LOAD
ASSEMBLY - LESS CONCENTRATED
15 NSF
OCCUPANCY LOAD
ASSEMBLY - STAGE 15 NSF
OCCUPANCY LOAD
ASSEMBLY - FIXED SEATING
OCCUPANCY LOAD
ASSEMBLY - WAITING
5 NSF
LOBBY
BALCONY
MECH/ELEC
TOILET
TOILET
DRESSING ROOM
DN
DN
DN
UP
DN
DN
DN
DN
DN
DN
DN
DN
OPEN TO
BELOW
OPEN TO
BELOW
OPEN TO
BELOW
EXIT TRAVEL
DISTANCE 112'-0"
FE-B
FE-B
DN
FE-C
DN
DOOR EXIT CAPACITY:
36" / 0.22 = 164 OCCUPANTS
DOOR EXIT CAPACITY:
36" / 0.22 = 164 OCCUPANTS
STAIR EXIT CAPACITY:
44" / 0.3 = 147 OCCUPANTS
STAIR EXIT CAPACITY:
44" / 0.3 = 147 OCCUPANTS
STAIR EXIT CAPACITY:
49" / 0.3 = 163 OCCUPANTS
STAIR EXIT CAPACITY:
49" / 0.3 = 163 OCCUPANTS
STAIR EXIT CAPACITY:
41" / 0.3 = 137 OCCUPANTS
STAIR EXIT CAPACITY:
41" / 0.3 = 137 OCCUPANTS
STAIR EXIT CAPACITY:
42" / 0.3 = 140 OCCUPANTS
OCCUPANCY LOAD
ASSEMBLY - LESS CONCENTRATED
15 NSF
OCCUPANCY LOAD
ASSEMBLY - FIXED SEATING
OCCUPANCY LOAD
ASSEMBLY - WAITING
5 NSF
OCCUPANCY LOAD
ASSEMBLY - LIGHTING & ACCESS
100 NSF
MECH/ELEC ROOM
MECH/ELEC ROOM
MECH/ELEC ROOM
ELECTRICAL ROOM
ORCHESTRA PIT
UP
UP
UP
CRAWL SPACE
E X
IT
T
R A
V E
L D
IS
T
A N
C E
8' -0
F E
-C
FE-C
STAIR EXIT CAPACITY:
42" / 0.3 = 140 OCCUPANTS
STAIR EXIT CAPACITY:
28" / 0.3 = 93 OCCUPANTS
OCCUPANCY LOAD
ASSEMBLY - LESS CONCENTRATED
15 NSF
OCCUPANCY LOAD
STORAGE
500 GSF
IT CLOSET
003A
EMERG ELEC ROOM
006PROJECTOR BOOTH
DN
EXIT TRAVEL
DISTANCE 114'-0"
FE-C
STAIR EXIT CAPACITY:
41" / 0.3 = 137 OCCUPANTS
STAIR EXIT CAPACITY:
49" / 0.3 = 163 OCCUPANTS
OCCUPANCY LOAD
ASSEMBLY - LIGHTING & ACCESS
100 NSF
A-3 USE
(ASSEMBLY)
WATER CLOSETS
LAVATORIES
DRINKING FOUNTAINS
SERVICE SINKS 1 SERVICE SINK
CODE TABLE
MALE FEMALE
1 PER 500
1 PER 200
1 PER 125 1 PER 65
1 SERVICE SINK
REQUIRED
MALE FEMALE
3 6
1 SERVICE SINK
PROPOSED
MALE FEMALE
2+1 URINAL 3
UNISEX
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Date:Revisions:No.
A u to d e s k D o c s /M t H o m e V
A
R e s to ra ti o n o f B
T h e a te r/ F
F E
M t H o m e
T h e a te r_ B
A
R C
H rv t
/1
/2
:2
:1
P M
GI005
LIFE SAFETY PLAN
05/30/2025 SS CD
RESTORATION OF BUILDING 35
HISTORIC THEATER
621-24-103
MT. HOME, TENNESSEE
BID DOCUMENTS
JAMES H.
QUILLEN VA
MEDICAL
CENTER
Approved: Owner
CODE SUMMARY
PROJECT DESCRIPTION AND PURPOSE
THE PURPOSE OF THE PROJECT IS TO RESTORE THE HISTORIC BUILDING 35 THEATER BUILDING TO BE IN USABLE CONDITION. THE DESIGN TEAM WILL ASSESS THE EXISTING CONDITIONS AND EXISTING DOCUMENTS TO DETERMINE THE EXTENT OF REPAIR NEEDED. THE EXTERIOR BRICK, STONE, WOODWORK, SLATE ROOF, MEMBRANE ROOF, WINDOWS, AND DOORS AND MEP SYSTEMS WILL BE REVIEWED AND REPAIRED AS NEEDED. THE USE OF THE BUILDING WILL BE FOR MINOR LOCAL STAGE PROJECTION, CONFERENCES, AND PRESENTATIONS. TOURING “BROADWAY” (OR SIMILAR) PRODUCTIONS WILL NOT BE A USE FOR THE SPACE.
WITH BROADWAY PERFORMANCES IT IS ASSUMED THAT THE USE OF PYROTECHNICS, WATER, SUSPENDED PERSON, ETC. IS TYPICAL IN THOSE TYPES OF PRODUCTIONS AND THIS WILL NOT BE USED WITH THIS SPACE, AS THAT IS THE DIRECTION FROM THE VA. THIS PROJECT WAS ORIGINALLY CONSTRUCTED AS A THEATER USE AND WILL REMAIN A THEATER USE INDICATING THAT THIS IS NOT A CHANGE OF USE OR CONSTRUCTION TYPE. THE PROJECT WILL BRING THE SPACE UP TO CODE COMPLIANCE FOR
ACCESSIBILITY THROUGHOUT THE THEATER EXCLUDING THE SECOND-FLOOR BALCONY AREA.
THE EXISTING LOBBY AREAS, BOTH FIRST AND SECOND FLOORS, WILL FUNCTION AS ORIGINALLY INTENDED, TEMPORARY STANDING/ COMMUNICATION SPACES BEFORE, BETWEEN, AND DURING THE EXISTING OF ALL THEATER SHOWS. THERE WILL NEVER BE A SITUATION WHERE THE THEATER IS AT MAXIMUM CAPACITY ALONG WITH MAXIMUM CAPACITY AT BOTH LOBBIES.
THESE LOBBIES ARE SIMPLY TRANSITION SPACES FOR THE OCCUPANTS ALREADY ACCOUNTED FOR IN THE AUDITORIUM SEATING
AREAS.
AUTHORITY HAVING JURISDICTION:
U.S. DEPARTMENT OF VETERANS AFFAIRS
VA CODES, STANDARDS AND EXECUTIVE ORDERS
NFPA 101 PRIMARILY ADDRESSES LIFE SAFETY AND FIRE PROTECTION FEATURES WHILE THE IBC ADDRESSES A WIDE RANGE OF CONSIDERATIONS, INCLUDING, BUT NOT LIMITED TO, STRUCTURAL STRENGTH, SEISMIC STABILITY, SANITATION, ADEQUATE LIGHT AND VENTILATION, AND ENERGY CONSERVATION. VA BUILDINGS MUST MEET THE REQUIREMENTS OF NFPA 101 AND DOCUMENTS REFERENCED BY NFPA 101 IN ORDER TO COMPLY WITH THE ACCREDITATION REQUIREMENTS OF THE JOINT COMMISSION.
THEREFORE, DESIGNS SHALL COMPLY WITH THE REQUIREMENTS OF THE LATEST EDITION OF NFPA 101 AND DOCUMENTS REFERENCED THEREIN. DESIGN FEATURES NOT ADDRESSED BY NFPA 101 OR DOCUMENTS REFERENCED THEREIN SHALL COMPLY WITH THE REQUIREMENTS OF THE LATEST EDITION OF THE IBC OR AS OTHERWISE ADDRESSED ABOVE IN THIS PROGRAM GUIDE.
FOR DESIGN FEATURES THAT ARE ADDRESSED BY BOTH THE IBC AS WELL AS NFPA 101 OR A DOCUMENT REFERENCED BY NFPA 101, THE REQUIREMENTS OF NFPA 101 OR THE DOCUMENT REFERENCED BY NFPA 101 SHALL BE USED EXCLUSIVELY (THIS
APPLIES EVEN IF THE IBC REQUIREMENTS ARE DIFFERENT).
APPLICABLE CODES & STANDARDS
• NFPA 101 LIFE SAFETY CODE, 2024
• NFPA 220 STANDARD ON TYPES OF BUILDING CONSTRUCTION, 2024
• INTERNATIONAL BUILDING CODE, 2024
• OCCUPATIONAL, SAFETY, AND HEALTH ADMINISTRATION (OSHA) STANDARDS
• NFPA 70, NATIONAL ELECTRIC CODE, 2023
• NFPA 72, NATIONAL FIRE ALARM AND SIGNALING CODE, 2022
• INTERNATIONAL PLUMBING CODE, 2021
• NFPA 13 STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS, 2025
• ASHRAE 90.1, ENERGY STANDARD; 2013 AND 2016
• NFPA 90A STANDARD FOR THE INSTALLATION OF AIRCONDITIONING AND VENTILATING SYSTEMS, 2024
• NFPA 92 STANDARD FOR SMOKE CONTROL SYSTEMS, 2024
• NFPA 110 STANDARD FOR EMERGENCY AND STANDBY POWER SYSTEMS, 2025
• ASME CODE FOR PRESSURE PIPING
• ARCHITECTURAL BARRIERS ACT ACCESSIBILITY STANDARDS (ABAAS) INCLUDING VA SUPPLEMENT, BARRIER FREE
DESIGN GUIDE (PG-18-13), AMERICAN DISABILITY ACT 2010
• VA SUSTAINABLE DESIGN MANUAL
• PHYSICAL SECURITY RESILIENCY DESIGN MANUAL, 2024
• VA PHYSICAL SECURITY DESIGN STANDARDS DATA DEFINITIONS
• VA SEISMIC DESIGN REQUIREMENT
• VA HVAC DESIGN MANUAL (REVISED 2022)
• VA FIRE PROTECTION DESIGN MANUAL (9TH EDITION)
• SAFETY CODE FOR ELEVATORS AND ESCALATORS, A 17.1, AMERICAN SOCIETY OF MECHANICAL ENGINEERS (ASME)
PSRDM RISK CATEGORY (PHYSICAL SECURITY RESILIENCY DESIGN MANUAL, 2024)
PROPOSED BUILDING ANCILLARY
SEISMIC DESIGN CATEGORY (VA SEISMIC DESIGN REQUIREMENT)
PROPOSED BUILDING CATEGORY B
BUILDING GROSS SQUARE FEET
BASEMENT FLOOR 2,990 GSF
FIRST FLOOR 8,290 GSF
BALCONY FLOOR 3,753 GSF
SECOND FLOOR 898 GSF
PROJECTOR FLOOR 189 GSF
TOTAL 16,120 GSF
USE GROUP CLASSIFICATIONS (NFPA 101, SECTION 13.1.2)
EXISTING ASSEMBLY (A-3)
PROPOSED ASSEMBLY (A-3)
TYPE OF CONSTRUCTION (NFPA 220, TABLE 4.1.1)
EXISTING TYPE III (200)
PROPOSED TYPE III (200)
BUILDING HEIGHT & AREA LIMITATIONS - FULLY SPRINKLERED
EXISTING (NO CHANGE) 2
EXISTING (NO CHANGE)
BASEMENT FLOOR 2,990 GSF
FIRST FLOOR 8,290 GSF
BALCONY FLOOR 3,753 GSF
SECOND FLOOR 898 GSF
PROJECTOR FLOOR 189 GSF
TOTAL 16,120 GSF
OCCUPANCY LOAD (NFPA 101, SECTION 7.3.1.2)
ASSEMBLY 15 NSF
ASSEMBLY (FIXED SEATING) NUMBER OF FIXED SEATS
ASSEMBLY - STAGE 15 NSF
ASSEMBLY - LESS CONCENTRATED 15 NSF
WAITING SPACES 5 SF (NFPA 101, SECTION 13.1.7.1.1)
STORAGE (LESS THAN 10%) 500 GSF
LIGHTING AND ACCESS 100 NSF
AREA TOTAL OCCUPANTS PER SPACE
BASEMENT FLOOR 2,990 / 500 = 5.98 6
FIRST FLOOR BACK OF HOUSE 558 / 15 = 37.2 37
FIRST FLOOR STAGE 1,777 / 15 = 118.46 118
FIRST FLOOR AUDITORIUM 302 FIXED SEATS (INCLUDING ADA) 302
FIRST FLOOR ORCHESTRA PIT 202 / 15 = 13.46 13
FIRST FLOOR LOBBY 701 / 5 = 140.2 140
SECOND FLOOR BACK OF HOUSE 534 / 15 = 35.6 36
SECOND FLOOR MECHANICAL 160 / 500 = 3.12 3
BALCONY FLOOR 252 FIXED SEATS 252
BALCONY LOBBY 472 / 5 = 94.4 94
PROJCTOR FLOOR 173 / 100 = 1.7 2
TOTAL OCCUPANTS PER SPACE 1,003
TOTAL ACTUAL OCCUPANTS* 769
*OCCUPANCY OF THE FIRST FLOOR LOBBY AND BALCONY LOBBY WILL NOT BE OCCUPIED AT THE SAME TIME AS THE REST OF
THE FACILITY.
FIRE-RESISTANCE RATING REQUIREMENTS FOR BUILDING ELEMENTS (NFPA 220 TABLE 4.1.1)
EXISTING/ PROPOSED
EXTERIOR BEARING WALLS 2-HOUR RATING
INTERIOR BEARING WALLS 2-HOUR RATING
COLUMNS 2-HOUR RATING
BEAMS, GIRDERS, TRUSSES, AND ARCHES 0 HOUR RATING
FLOOR-CEILING CONTRUCTION 0-HOUR RATING
ROOF-CEILING CONSTRUCTION 0-HOUR RATING
INTERIOR BEARING WALLS 0-HOUR RATING
EXTERIOR NONBEARING WALLS 0-HOUR RATING
WALLS AND CEILING FINISHES
ALL INTERIOR FINISHES SHALL MEET THE REQUIREMENTS FOR A FULLY-SPRINKLERED, (A-3) USE GROUP
MEANS OF EGRESS (NFPA 101, SECTION 13.2.4.3)
EXISTING
MINIMUM NUMBER OF EXITS
ABOVE GROUND LEVELS 3 REQUIRED
PROPOSED ASSEMBLY USE SPACES WITH ANCILLARY SPACES
ABOVE GROUND LEVELS
FIRST FLOOR 9 PROVIDED
(INCLUDING LOBBY, AUDITORIUM, ORCHESTRA PIT, BACK OF HOUSE, AND STAGE)
BALCONY FLOOR 4 PROVIDED
(INCLUDING LOBBY AND MECHANCIAL ROOM)
BASEMENT FLOOR 1 PROVIDED*
*THE MECHANICAL AREA ONLY REQUIRES 1 MEANS OF EGRESS. ORCHESTRA PIT OCCUPANTS WILL HAVE A NEW EXIT
STAIR. PER NFPA 101 CHAPTER 42, SECTION 42.2.4.1.
EXIT DOORS (NFPA 101, 13.2.2.2)
ALL EXIT DOORS SHALL BE EASILY OPENABLE FROM THE EXIT SIDE WITHOUT THE USE OF A KEY, SPECIAL KNOWLEDGE, OR
EFFORT. ALL EXIT DOORS ARE EQUIPPED WITH PUSH BAR PANIC HARDWARE.
EGRESS CAPACITY OCCUPANT LOAD (NFPA 101, TABLE 13.2.3.2)
EGRESS CAPACITY FACTOR STAIRS 0.3 INCH
DOORWAYS 0.22 INCH
REFER TO LIFE SAFETY PLANS ON THIS SHEET FOR OCCUPANT NUMBERS FOR STAIRS AND EGRESS DOORS.
MINIMUM WIDTH OF DOOR CLEARANCE
REQUIRED = 32” MIN.
PROVIDED = 34" MIN. (FOR ALL SINGLE DOORS)
NEW AISLE STAIRS (NFPA 101, 13.2.5.8.6)
PROPOSED RISER = 6.5
PROPOSED RUN = 11"
HANDRAILS (NFPA 101, 7.2.2.4)
ALL PROPOSED HANDRAILS/ GUARDS MEET THE REQUIRMENTS OUTLINED IN NFPA 101, SECTION 7.2.2.4.5. SEE DRAWINGS
FOR ADDITIONAL DETAILS ON HEIGHTS, LENGTH, AND GRASPABILITY (1 1/4" DIA).
-ALL PROPOSED AND EXISTING STAIRS CONSTRUCTUED WITH HANDRAILS ON BOTH SIDES, CONTINUOUS.
-ALL PROPOSED RAMPS ARE CONSTRUCTED WITH HANDRAILS/ GUARDS ON BOTH SIDES, CONTINUOUS BETWEEN
LANDINGS.
ALL EXISTING HANDRAILS ARE TO REMAIN
NEW EXTERIOR RAMPS (NFPA 101, 13.2.2.6 & TABLE 7.2.5.3(a))
PROPOSED SLOPE = 1:12 WITH MAXIMUM RISE NOT TO EXCEED 30"
COMMON PATH OF EGRESS TRAVEL DISTANCE (NFPA 101, 13.2.5.2)
REQUIRED = 20' MAX
PROVIDED BASEMENT FLOOR = 0’-0” (SINGLE EXIT ONLY REQUIRED)
PROVIDED FIRST FLOOR = 0’-0” (TWO EXITS VISIABLE AT ALL ASSEMBLY AREAS)
PROVIDED BALCONY = 0’-0” (TWO EXITS VISIABLE AT ALL ASSEMBLY AREAS)
PROVIDED PROJECTOR FLOOR = (SINGLE EXIT ONLY REQUIRED)
EXIT ACCESS TRAVEL DISTANCE (NFPA 101, TABLE 13.2.6.2 (1))
REQUIRED = 250' MAX (FULL SUPRESSED)
PROVIDED LOWER LEVEL = 158’-0”
PROVIDED FIRST FLOOR = 75’-0”
PROVIDED BALCONY FLOOR = 112’-0”
PROVIDED PROJECTOR FLOOR = 114’-0”
DEAD END CORRIDORS (NFPA 101, 13.2.5.3)
REQUIRED = 20' MAX
PROJECT HAS NO DEAD-END CORRIDORS
MINIMUM CORRIDOR WIDTH
REQUIRED = 44" REQUIRED
PROVIDED = 48" MINIMUM.
EXIT DISCHARGE
EXITS SHALL DISCHARGE DIRECTLY TO THE EXTERIOR OF THE BUILDING. THE EXIT DISCHARGE SHALL BE AT GRADE OR SHALL
PROVIDE A DIRECT PATH OF EGRESS TRAVEL TO GRADE.
DOOR OPERATIONS
ALL EGRESS DOORS SHALL BE READILY OPENABLE FROM THE EGRESS SIDE WITHOUT THE USE OF A KEY OR SPECIAL
KNOWLEDGE OR EFFORT.
ACCESSIBILITY REQUIREMENTS
A. THE PROPOSED ALTERATION COMPLIES WITH THE REQUIREMENTS OF ADA. THE ROUTE TO THE AREA OF PRIMARY
FUNCTION SHALL BE ACCESSIBLE AND THE AMENITIES SERVING THE PRIMARY FUNCTION SHALL BE ACCESSIBLE.
B. ALL NEW RESTROOM FACILITIES, INCLUDING DRINKING FOUNTAINS ARE FULLY COMPLIANT WITH ACCESSIBILITY
REQUIREMENTS.
C. WITHIN THE ALTERATION SPACE, ALL NEW DOORS SHALL RECEIVE LEVER HANDLES AND PUSH BAR PANIC
HARDWARE AT ALL EGRESS DOORS.
FIRE PROTECTION SYSTEMS
EXISTING
FULLY SPRINKLERED IN ACCORDANCE WITH NFPA 13
AUTOMATIC WET STANDPIPES EXISTING
PROPOSED
FIRE ALARM SYSTEM WITH VOICE EVACUATION THROUGHOUT IN ACCORDANCE WITH NFPA 72.
PROPOSED
PORTABLE FIRE EXTINGUISHERS IN COMPLIANCE WITH NFPA 10 FOR CLASS A. EXTINGUISHER INSTALLED ALL WITHIN 75’ OF
TRAVEL.
PROVIDED
BASEMENT FLOOR 2
FIRST FLOOR 5
BALCONY FLOOR 3
PROJECTOR FLOOR 1
TOTAL 11
ENERGY CODE COMPLIANCE
ENERGY CODE COMPLIANCE IS IN ACCORDANCE WITH ASHRAE 90.1, PER THE 2018
INTERNATIONAL ENERGY CONSERVATION CODE THE COMPLIANCE PATH IS ENVELOPE TRADE OFF (USING ENERGY
MODELING)
PLUMBING FIXTURE COUNT (IBC SECTION 2902, TABLE 2902.1)
BASED ON 770 OCCUPANTS SPLIT EVENLY BETWEEN MALE AND FEMALE
LIFE SAFETY LEGEND
3/32" = 1'-0"
FIRST FLOOR LIFE SAFETY PLAN
3/32" = 1'-0"
BALCONY & SECOND FLOOR LIFE SAFETY PLAN
3/32" = 1'-0"
BASEMENT LIFE SAFETY PLAN
3/32" = 1'-0"
PROJECTOR BOOTH LIFE SAFETY PLAN
32.01
32.03
32.03
32.03
32.01
BUILDING 16
CONTRACTOR
LAYDOWN AREA
BUILDING 35
M E
M O
R
IA
L A
V E
1.21
1.21
3.24
1.21
1.22
32.01
32.01
32.01
BUILDING NOT IN PROJECT SCOPE
1.23
1.23
1.24
LEGEND
CONTRACTOR SITE FENCE - SEE CIVIL DRAWINGS
TEMPORARY ACCESS ROAD
GENERAL NOTES
A. CONTRACTOR IS RESPONSIBLE FOR ANY PHASING COORDINATION WITH COR PRIOR TO START OF THE WORK.
B. PEDESTRIAN ACCESS AND EGRESS MUST BE MAINTAINED AT ALL TIMES DURING CONSTRUCTION.
C. ANY AND ALL DAMAGE TO EXISTING LAWNS, TREES, VEGETATION, HARDSCAPES, STREETSCAPES, CONCRETE, OR
OTHER EXISTING ITEMS OUTSIDE THE PROJECT SCOPE SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO REPAIR IN
KIND BEFORE THE PROJECT'S COMPLETION.
D. SEE DEMOLITION AND NEW WORK PLANS FOR PROJECT SPECIFICS.
E. SEE CIVIL DRAWINGS FOR SITE WORK.
F. SEE CIVIL DRAWINGS FOR ALL NEW PAVEMENT STRIPING AND MARKING.
G. THE CONTRACTOR MUST SECURE THE SITE WITH PERIMETER FENCING AND IS RESPONSIBLE FOR ITS MAINTENANCE.
SIZE AND AREA OF CONTRACTOR LAYDOWN DO BE ABROVED BY THE VA PRIOR TO CONSTRUCTION. COORDINATE WIH
THE COR.
H. COORDINATE ALL CONTRACTOR PARKING WITH THE VA PRIOR TO PROJECT ROLLOUT.
I. CONTRACTOR TO MAINTAIN NORMAL TRAFFIC PATTERNS UNLESS RECIVING APPROVAL FROM THE VA AND
COORDINATED WITH THE COR.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Date:Revisions:No.
A u to d e s k D o c s /M t H o m e V
A
R e s to ra ti o n o f B
T h e a te r/ F
F E
M t H o m e
T h e a te r_ B
A
R C
H rv t
/1
/2
:2
:2
P M
GI006
SITE AND CONSTRUCTION
LAYDOWN PLAN
05/30/2025 SS CD
RESTORATION OF BUILDING 35
HISTORIC THEATER
621-24-103
MT. HOME, TENNESSEE
BID DOCUMENTS
JAMES H.
QUILLEN VA
MEDICAL
CENTER
Approved: Owner
DRAWING NOTES:
1.21 PROTECT ALL EXISTING TRESS OUT TO DRIP LINE - NO WORK TO HAPPEN IN OR AROUND EXISTING TREES
1.22 TEMPORARY ACCESS ROAD FOR BUILDING 16 - COORDINATE WITH COR PRIOR TO CONSTRUCTION.
1.23 CONTRACTOR TO REPLACE SECTION OF SIDEWALK AT TEMPORARY ROAD ONCE ROAD IS REMOVED. SIDEWALKS TO
MATCH EXISTING
1.24 PROVIDE TEMPORARY ASPHALT CURB SLOPE AT EXISTING CURB. REPLACE SECTION OF CURB ONCE ROAD IS REMOVED.
NEW CURB TO MATCH EXISTING. DOWEL-IN NEW CURB TO EXISTING.
3.24 NEW CONCRETE GENERATOR PAD - SEE CIVIL DRAWINGS
32.01 PAINTED STRIPING - SEE CIVIL DRAWINGS
32.03 EXTERIOR CONCRETE DRIVE. PHASE WORK IN COORDINATION WITH VA COR AND ACCESS REQUIREMENTS TO BUILDING
16 - SEE CIVIL DRAWINGS
TRUE
NORTH
1/16" = 1'-0"
SITE PLAN
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Date:Revisions:No.
A u to d e s k D o c s /M t H o m e V
A
R e s to ra ti o n o f B
T h e a te r/ F
F E
M t H o m e
T h e a te r_ B
A
R C
H rv t
/1
/2
:0
:5
P M
GI007
EXTERIOR 3D VIEWS
05/30/2025 SS CD
RESTORATION OF BUILDING 35
HISTORIC THEATER
621-24-103
MT. HOME, TENNESSEE
BID DOCUMENTS
JAMES H.
QUILLEN VA
MEDICAL
CENTER
Approved: Owner
NTS
3D - NORTHEAST
NTS
3D - NORTHWEST
NTS
3D - SOUTHEAST
NTS
3D - SOUTHWEST
CONCRETE SIDEWALK
DOMESTIC WATER LINE
FIRE HYDRANT & VALVE ASSEMBLY
STORM DRAIN PIPE
SANITARY SEWER
SANITARY SEWER MANHOLE (SSMH)
FIRE WATER LINE
CONCRETE CURB
Wx
FW x
SS x
SD x
W
FW
SS
SD
STEAM & CONDENSATE LINE ST
LEGEND
BUILDING
ASPHALT PAVING
DESCRIPTION EXISTING REQ'D DEMOLITION
CONCRETE PAVING
SS x
UNDERGROUND STEAM ST x
X X X
ST x
ROOF DRAIN RD x RD RD x
POINT OF CONNECTION
SPOT ELEVATION
CONTOUR
ABBREVIATIONS LEGEND
ABANDONED
ASPHALTIC CONCRETE
BUILDING
BENCHMARK
TELECOMMUNICATIONS MANHOLE
EXISTING
FIRE HYDRANT
LIGHT POLE
DRAIN MANHOLE
SANITARY SEWER
SEWER MANHOLE
STEAM SUPPORT
EXISTING UNDERGROUND POWER
EXISTING UNDERGROUND COMM
UNDER GROUND
UNKNOWN
WATER
WATER METER
WATER GATE VALVE
ABND
AS
BLDG
BM
TMH
EX OR EXST
FH
LP
DMH
SS
SMH
STEM
EUP
EUC
UG
UNK
W
WM
WV
ABBREVIATION WORD
CLEANOUTCO
ELECTRICAL MANHOLEEMH
730.00 730+00 OR 730.00+ OR
TOP OF CURBTC
BACK OF CURBBC
STEAM MANHOLE St.MH
SMH
LIMITS OF DISTURBANCE LOD
XX.XX
FENCE X X
INVERT ELEVATIONIE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Date:Revisions:No.
Au to de sk
D oc s:
//M t H om e
VA
R es to ra tio n of
B
T he at er
/F
FE
_M t H om e
- T he at er
_B
_A R
C H
(2
4) .rv t
CDB BDS
RESTORATION OF BUILDING 35
HISTORIC THEATER
621-24-103
MT. HOME, TENNESSEE
BID DOCUMENTS
JAMES H.
QUILLEN VA
MEDICAL
CENTER Approved: Owner
1 BID DOCUMENTS 07/01/2025
07/01/2025
BR
ENTSAYERS
RE
GIS
TEREDENGINEER
No . 12 8 4 0 8
COMMERCE
STATE OF TENNE
SS
EE
AGRIC8/T8RE
07/01/2025
C-001
GENERAL NOTES, LEGEND, AND
ABBREVIATIONS
CONSTRUCTION NOTES
1. THE CONTRACTOR SHALL PROTECT ALL EXISTING UTILITIES WHETHER SHOWN ON THE PLANS
OR NOT. BEFORE DISRUPTING SERVICE OF ANY UTILITY, THE CONTRACTOR SHALL CONTACT
THE CONTRACTING OFFICER AND THE RESPONSIBLE UTILITY AUTHORITY. DAMAGE TO EXISTING UTILITIES AS A RESULT OF CONSTRUCTION ACTIVITIES SHALL BE REPAIRED IMMEDIATELY BY
THE CONTRACTOR AT NO ADDITIONAL COST TO THE GOVERNMENT AND AT NO COST TO THE
AFFECTED UTILITY AUTHORITY.
2. UNLESS INDICATED OTHERWISE, EXISTING UTILITIES SHALL REMAIN IN SERVICE AND IN PLACE.
IF RELOCATION OF EXISTING UTILITIES IS FOR THE CONTRACTOR'S CONVENIENCE,
INTERRUPTION OF SERVICE SHALL BE KEPT TO A MINIMUM AND SHALL BE DONE AT THE
CONTRACTOR'S EXPENSE, AND ONLY WITH THE WRITTEN APPROVAL OF THE CONTRACTING
OFFICER. PRIOR TO RELOCATING EXISTING UTILITIES, THE CONTRACTOR SHALL COORDINATE
THE WORK WITH THE CONTRACTING OFFICER IN ORDER TO MINIMIZE DISRUPTIONS.
3. THE CONTRACTOR SHALL OBSERVE AND COMPLY WITH ALL STATE EPA REQUIREMENTS AND
FEDERAL AND LOCAL LAWS REQUIRED FOR THE PROTECTION OF PUBLIC HEALTH, SAFETY, AND
ENVIRONMENTAL QUALITY.
4. THE CONTRACTOR SHALL PROVIDE, INSTALL AND MAINTAIN ALL NECESSARY SIGNS,
BARRICADES, TEMPORARY FENCING AND OTHER PROTECTIVE FACILITIES AND SHALL TAKE ALL
NECESSARY PRECAUTIONS FOR THE PROTECTION, CONVENIENCE AND SAFETY OF THE PUBLIC.
5. THE CONTRACTOR, AT HIS/HER OWN EXPENSE, SHALL KEEP THE PROJECT AND ITS
SURROUNDING AREAS FREE FROM DUST NUISANCE. THE WORK SHALL BE IN CONFORMANCE
WITH THE SPECIFICATIONS AND AIR POLLUTION STANDARDS OF THE STATE ENVIRONMENTAL
PROTECTION AGENCY. THE CONTRACTING OFFICER MAY REQUIRE SUPPLEMENTARY
MEASURES AS NECESSARY.
6. IN THE EVENT ANY ARTIFACTS OR HUMAN REMAINS ARE UNCOVERED DURING CONSTRUCTION
OPERATION, THE CONTRACTOR SHALL IMMEDIATELY SUSPEND WORK AND NOTIFY THE
CONTRACTING OFFICER.
7. THE CONTRACTOR SHALL BE RESPONSIBLE FOR CONFORMANCE WITH THE APPLICABLE
PROVISIONS OF THE WATER QUALITY STANDARDS AND WATER POLLUTION CONTROL
STANDARDS OF THE STATE EPA.
GRADING NOTES
1. ALL GRADING WORK SHALL BE DONE IN ACCORDANCE WITH THE PLANS AND SPECIFICATIONS.
2. THE CONTRACTOR SHALL NOT PERFORM ANY GRADING OPERATION WHICH CAUSES FALLING
ROCKS, SOIL OR DEBRIS, IN ANY FORM, TO FALL, SLIDE OR FLOW INTO BASE DRAINAGE
SYSTEMS, ONTO ADJOINING STREETS OR INTO NATURAL WATERCOURSES. SHOULD SUCH
VIOLATIONS OCCUR, THE CONTRACTOR MAY BE CITED AND THE CONTRACTOR SHALL
IMMEDIATELY MAKE ALL REMEDIAL ACTIONS NECESSARY AT NO ADDITIONAL COST TO THE
GOVERNMENT.
3. ADEQUATE PROVISIONS SHALL BE MADE TO PREVENT SURFACE WATERS FROM DAMAGING THE
CUT FACE OF AN EXCAVATION OR THE SLOPED SURFACES OF A FILL. FURTHERMORE,
ADEQUATE PROVISIONS SHALL BE MADE TO PREVENT SEDIMENT-LADEN RUNOFF FROM
LEAVING THE SITE.
4. ALL SLOPES AND EXPOSED AREAS SHALL BE SODDED OR PLANTED AS SOON AS FINAL GRADES
HAVE BEEN ESTABLISHED. PLANTING SHALL NOT BE DELAYED UNTIL ALL GRADING WORK HAS
BEEN COMPLETED. GRADING TO FINAL GRADE SHALL BE CONTINUOUS AND…