Atch 11_621-24-103 Drawing part 6 of 6.pdf
PDF 27 MB Posted
- Solicitation number
- 36C24926R0055
About this file
This file is a set of mechanical engineering drawings for the restoration of Building 35 Historic Theater at James H. Quillen VA Medical Center in Mt. Home, Tennessee, issued July 1, 2025 as part of bid documents for Project 621-24-103. The drawings comprise six sheets detailing mechanical demolition and new work plans across basement, first floor, balcony, second floor, attic, and roof levels, with accompanying mechanical sections and details.
The demolition plans specify removal of existing HVAC components including air handling units (AHU-A1, AHU-A2, AHU-S1, AHU-S2, AHU-B, AHU-L1, AHU-L2), variable air volume boxes (VAV-A, VAV-S, VAV-L1, VAV-L2, VAV-B), fan coil units, exhaust fans, ductwork, and associated piping, with notation for retention and salvage of specific components for reuse. The new work plans introduce replacement HVAC systems including new air handling units with sound attenuators, ductwork routing (ranging from 6" to 56" dimensions), chilled water and hot water piping (3/4" to 4" sizes), four-pipe fan coil units (BCU-1 and BCU-2 with 1,050 CFM capacity each), supply diffusers, exhaust grilles, dedicated outdoor air supply (DOAS-1), and a ductless split air conditioning system (ODU-1/IDU-1 with 375 CFM). The mechanical details sheets provide standard construction specifications including fire-rated flexible duct connections, volume damper installations, duct transitions, vane elbow configurations, and fan coil unit control sequences. Equipment schedules specify sound attenuating devices for eight AHU units with insertion loss ratings across octave bands, cooling and heating capacities for fan coil units, and a split-system air conditioner with 18 MBH capacity serving a training room.
View the file
Other files
Show all 47
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
(E)10"x16" SA (UP)(E)40"x18" OA (UP)
(E )1
2" x8
(E)32"x12"
(E )1
2" x8
(E)22"x16" (E)22"x10" (E)22"x10"
(E) (E) VAV-A
(E) DOAS-1
(E )3
8" x1
2" (E
)3 8" x1 2"
(E )2
0" x1
0"
(E)38"x12" OA (UP)
(E)38"x12"
(E)38"x12"
(E)20"x20" SA (E) AHU-S2
(E) AHU-A2
(E) AHU-D2
(E) AHU-S1
23.04
(E)18"ø SA(E)15"ø SA(E)11"ø SA (E)20"ø SA
2"ø HWS 2"ø HWR
(E) (E) VAV-S
(E)20"x20"
(E) AHU-A1
(E)20"x20"(E)18"x18"(E)15"x15"(E)11"x11"
23.04
23.04
(E)26"x26" RA
(E)18"x10" SA (UP) (E)18"x10" SA (UP)
(E) AHU-D1
(E)38"x18" RA (UP)
(E) 1 1/4"ø CHS
(E) 1 1/4"ø CHR
(E) 1 1/4"ø HWS
(E) 1 1/4"ø HWR
(E)8"x10" (E)12"x6" SA (UP)
(E)6"ø SA (UP)
(E)12"x6" SA (UP)
(E)8"x8" SA
(E)12"x6" SA (UP)
(E)12"x6" SA (UP)
(E) 3/4"ø CHR
(E) 3/4"ø CHS
(E) 3/4"ø HWR
(E) 3/4"ø HWS
23.04
23.04
23.04
23.04
23.04
3/4"ø CHS 3/4"ø CHR
3/4"ø HWS 3/4"ø HWR
(E) 3/4"ø D
(E) CH-1
23.12
(E) 3/4"ø D
(E) FAN
23.13
(E)8"x6" SA (UP)
23.14
23.15
23.16
23.15
23.14
23.16
(E) 3/4"ø HWS UP
(E) 3/4"ø HWR UP
(E)10"x16" SA
4"ø EA (UP)
(E)38"x12" OA
(E) EF-2
(E) EF-1
(E) FCU-2
(E) FCU-1
(E)12"x28" SA
(E)12"x28" SA
(E)12"x22" SA
(E)9"x22" SA(E)6"x12" SA
(E) 2"ø CHR UP & DN
(E) 2"ø CHS UP & DN
(E) 2"ø HWR UP & DN
(E) 2"ø HWS UP & DN
23.05
23.05
(E) SD (E) SD
(E) SD
(E) SD (E) SD (E) SD
(E) RG
(E) RG
(E)40"x18" OA (DN)
(E)28"x12" SA (DN)
(E) SD
(E) SD
(E) RG
(E) SD
(E) SD
(E) SD
23.07
23.08
23.10
(E) RG
(E) SD
(E) SD
(E) SD(E) SD
(E) SD
(E) SD
(E) SD (E) SD (E) SD (E) SD
(E)8"x6" SA (DN)
(E) SD
23.17
(E) EG
(E) EG
23.17
23.18
23.18
23.19
23.04
(E) SD
(E)36"x8" SA (UP)
(E) SD
(E)36"x8" SA (UP)
23.54
23.54
23.54
23.54
23.54
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Date:Revisions:No.
Au to de sk
D oc s:
//M t H om e
VA
R es to ra tio n of
B
T he at er
/F
FE
_M t H om e
- T he at er
_B
_M
EP
(2
4) .rv t 7/
1/
:5 3:
P
M
MD101
BASEMENT AND FIRST FLOOR
DEMOLITION PLANS
07/01/2025 KF KG
RESTORATION OF BUILDING 35
HISTORIC THEATER
621-24-403
MT. HOME, TENNESSEE
BID DOCUMENTS
JAMES H.
QUILLEN VA
MEDICAL
CENTER Approved: Owner
1/8" = 1'-0"1 MECHANICAL BASEMENT DEMOLITION PLAN
D R A W I N G N O T E S :
23.04 REMOVE SECTION OF DUCT TO ACCOMMODATE NEW SOUND ATTENUATOR.
23.05 REMOVE SUPPLY DIFFUSER AND DUCT TO BELOW FLOOR. RETAIN SUPPLY DIFFUSER FOR REUSE IN NEW WORK.
23.07 REMOVE SECTION OF DUCT. RETAIN SUPPLY DIFFUSERS FOR REUSE IN NEW WORK.
23.08 REMOVE EXHAUST GRILLE AND DUCT UP TO SECOND FLOOR.
23.10 REMOVE EXHAUST FAN IN WINDOW. COORDINATE WINDOW REPAIR WITH GENERAL CONTRACTOR.
23.12 EXISTING REFRIGERANT PIPING BELOW GRADE OUT TO CH-1.
23.13 REMOVE VERTICAL TO FIRST FLOOR. PREPARE FOR EXTENSION IN NEW WORK. SEE NEW WORK ON M101.
23.14 REMOVE EXISTING CONDENSATE DRAIN PIPING ENTIRELY BACK TO BELOW STAGE.
23.15 REMOVE EXISTING CHILLED WATER AND HEATING HOT WATER PIPING FROM FAN COIL ABOVE TO THIS LOCATION.
PREPARE FOR EXTENSION TO NEW FAN COIL UNIT IN NEW WORK. SEE NEW WORK ON M101.
23.16 REMOVE DUCTWORK FROM SUPPLY GRILLE ABOVE MAIN. PREPARE FOR EXTENSION TO NEW SUPPLY GRILLE LOCATION
IN NEW WORK. SEE NEW WORK ON M101.
23.17 REMOVE EXHAUST FAN, DUCT, AND GRILLE.
23.18 REMOVE FAN COIL AND ASSOCIATED PIPING TO BELOW FLOOR.
23.19 REMOVE DUCTWORK FROM BELOW FLOOR AND UP TO SECOND FLOOR.
23.54 RETAIN SUPPLY DIFFUSERS FOR REUSE IN NEW WORK.
1/8" = 1'-0"2 MECHANICAL FIRST FLOOR DEMOLITION PLAN
PLAN
NORTH
BID DOCUMENTS 07/01/2025
LOBBY
MECH/ELEC
BALCONY
(E) AHU-L2
(E) AHU-L1
(E) VAV-L1
(E) SD
(E) SD
(E) SD
(E)12"x14" OA (UP)
(E)14"x14" OA (UP)
2"ø HWS UP 2"ø HWR UP 2"ø CHS UP 2"ø CHR UP
(E)10"x8" SA
(E)10"x10" SA
(E)10"x8" SA
(E)40"x18" OA (DN)
(E)10"x16" SA (DN)
(E)4"ø EA (E)6"ø EA
(E)38"x12" OA (DN)(E) 2"ø HWS DN
(E) 2"ø HWR DN
(E) 2"ø CHS DN
(E) 2"ø CHR DN
23.26 23.08
(E) SD
(E) SD
(E)20"x40" RA
23.26
23.25
PROJECTOR BOOTH
LOBBY
(E) AHU-B
(E) VAV-B
(E) EF-4
(E)12"x14" OA (UP)
23.21
23.04 (E)14"x14" OA (UP)
"x
(E)38"x12" OA (UP)
(E) SD
(E) SD
(E) SD
23.20
(E) VAV-L2 23.22
23.23
(E) 2"ø CHR UP
(E) 2"ø CHS UP
(E) 2"ø HWR UP
(E) 2"ø HWS UP
23.24
23.26
23.26
(E)12"x38" OA
(E)20"x32" RA
(E)20"x32" RA
(E)14"x26" SA (DN)
(E) 2"ø CHR DN
(E) 2"ø CHS DN
(E) 2"ø HWR DN
(E) 2"ø HWS DN
(E )3
8" x1
2" O
A
(E )1
8" x1
2" S
A
(E)36"x8" SA (DN)
(E)20"x8" SA (DN)
(E)27"x8" SA (DN)
(E)10"ø SA (E)8"ø SA
(E)8"ø SA
(E)40"x20" RA (DN)
(E)12"x38" OA (DN)
(E) 2"ø CHR DN
(E) 2"ø CHS DN
(E) 2"ø HWR DN
(E) 2"ø HWS DN
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Date:Revisions:No.
Au to de sk
D oc s:
//M t H om e
VA
R es to ra tio n of
B
T he at er
/F
FE
_M t H om e
- T he at er
_B
_M
EP
(2
4) .rv t 7/
1/
:5 3:
P
M
MD102
BALCONY, SECOND FLOOR, AND
ATTIC DEMOLITION PLANS
07/01/2025 KF KG
RESTORATION OF BUILDING 35
HISTORIC THEATER
621-24-403
MT. HOME, TENNESSEE
BID DOCUMENTS
JAMES H.
QUILLEN VA
MEDICAL
CENTER Approved: Owner
D R A W I N G N O T E S :
23.04 REMOVE SECTION OF DUCT TO ACCOMMODATE NEW SOUND ATTENUATOR.
23.08 REMOVE EXHAUST GRILLE AND DUCT UP TO SECOND FLOOR.
23.20 REMOVE AHU-B AND CONTROLS. SALVAGE FOR RELOCATION IN NEW WORK. REMOVE SUPPLY DUCTWORK TO ABOVE
CEILING OF LOBBY. SEE NEW WORK PLANS ON M102.
23.21 DISCONNECT CHILLED WATER AND HEATING HOT WATER PIPING FROM AHU-B. REMOVE BACK TO MAIN AND CAP.
23.22 OA SUPPLY VAV TO REMAIN.
23.23 REMOVE OA SUPPLY VAV BOX ALONG WITH CONTROLS AND SALVAGE FOR RELOCATION IN NEW WORK. SEE NEW WORK
PLANS ON M102.
23.24 REMOVE OA DUCTWORK FROM CONNECTION AND RETURN BACK TO MAIN AND CAP.
23.25 REMOVE ALL SUPPLY AIR DUCTWORK DOWN TO FIRST FLOOR.
23.26 REMOVE SECTION OF DUCT. RE-ROUTE IN NEW WORK.
1/8" = 1'-0"1 MECHANICAL BALCONY DEMOLITION PLAN
1/8" = 1'-0"2 MECHANICAL BACK LEVEL 2 DEMOLITION PLAN
1/8" = 1'-0"3 MECHANICAL PROJECTOR BOOTH DEMOLITION PLAN
PLAN
NORTH
1/8" = 1'-0"4 MECHANICAL ATTIC DEMOLITION PLAN
(E) ATTIC VENT (E) ATTIC VENT
(E) THEATER VENT
BLOCKED OFF IN
PREVIOUS PROJECT
(E) ROOF ACCESS HATCH
23.27
(E) ERV-1
(E) ERV-2
(E)20"x40" RA
(E)20"x20" RA (E)18"x20" OA
(E)20"x20" RA
(E)18"x20" OA
(E)20"x20" RA
40"x18" OA (DN)
(E) EF-3
(E) ROOF ACCESS HATCH
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Date:Revisions:No.
Au to de sk
D oc s:
//M t H om e
VA
R es to ra tio n of
B
T he at er
/F
FE
_M t H om e
- T he at er
_B
_M
EP
(2
4) .rv t 7/
1/
:5 3:
P
M
MD103
ROOF DEMOLITION PLANS
07/01/2025 KF KG
RESTORATION OF BUILDING 35
HISTORIC THEATER
621-24-403
MT. HOME, TENNESSEE
BID DOCUMENTS
JAMES H.
QUILLEN VA
MEDICAL
CENTER Approved: Owner
1/8" = 1'-0"1 MECHANICAL ROOF DEMOLITION PLAN
1/8" = 1'-0"2 MECHANICAL BACK ROOF DEMOLITION PLAN
PLAN
NORTH
D R A W I N G N O T E S :
23.27 REMOVE ATTIC VENT AND CAP ROOF CURB PER NEW WORK PLANS. SEE NEW WORK ON M103.
ELECTRICAL ROOM
MECH/ELEC ROOM
MECH/ELEC ROOM
MECH/ELEC ROOM
M301
(E) AHU-S1
(E) AHU-A1
AHU-A1R23.09
AHU-A123.09
AHU-S1
(E) RG
(E) RG
AHU-A2
(E) AHU-A2
23.09
23.09
(E) AHU-D1
(E) AHU-D2
(E) AHU-S2
(E) DOAS-1
(E) VAV-A
(E) VAV-S
(E)40"x18" OA (UP) (E)38"x18" RA (UP)
(E) 3/4"ø HWS UP
(E) 3/4"ø HWR UP
(E) 2"ø HWS UP
(E) 2"ø HWR UP
(E) 2"ø CHS UP
(E) 2"ø CHR UP
(E)38"x12" OA (UP)
AHU-A2R23.09
(E)26"x26" RA
(E)12"x8" OA
AHU-S1R 23.09
AHU-S223.09
AHU-S2R23.09
(E)34"x14" RA (UP)
(E)32"x12" RA 26"x18" RA
(E)22"x10" SA(E)22"x10" SA
M301
(E) 3/4"ø CHS
(E) 3/4"ø CHR
(E) 3/4"ø HWS
(E) 3/4"ø HWR
23.11
23.11
3/4"ø HWR UP3/4"ø CHR UP 3/4"ø CHS UP 3/4"ø HWS UP
3/4"ø HWR UP 3/4"ø CHS UP 3/4"ø HWS UP 3/4"ø CHR UP
(E) 3/4"ø HWR
(E) 3/4"ø HWS
(E) 3/4"ø CHS
(E) 3/4"ø CHR
6"x46" SA (UP)
6"x46" SA (UP)
(E)11"x11" SA (E)15"x15" SA (E)18"x18" SA (E)20"x20" SA
(E)11"ø SA (E)15"ø SA (E)18"ø SA (E)20"ø SA
(E) CH-1
(E)8"x10" (E)12"x6" SA (UP)
(E)8"x8"
(E)12"x6" SA (UP)
(E) 1"ø RL
(E) 1"ø RL
(E) 2"ø RS
(E) 2"ø RS
23.28
23.28
M301
M301
ODU-1
IU-1
23.37
23.39
23.40
23.38
3/4"ø D
10"x16" SA (UP)
(E)12"x6" SA (UP) (E)8"x6" SA (UP)
(E)8"x10" SA (E)16"x10" SA (E)16"x10" RA
(E) HX-1
(E) 4"ø CHS
(E) 4"ø CHS
(E) 4"ø HWS
(E) 4"ø HWR
(E) FAN
RL
RS
STAGE
STORAGE
DRESSING ROOM
CORRIDOR
TOILET
TOILET
DRESSING ROOM
BOOTH
101B
AUDITORIUM
BOOTH
101D
CORRIDOR
101A
CORRIDOR
101C
WOMEN'S
TOILET
111A
LOBBY
TOILET
110A
MEN'S
(E)9"x22" SA
(E) SD
725 CFM
(E)6"x12" SA
9"x22" SA 12"x22" SA 12"x28" SA
38"x12" OA (UP)
(E)28"x12" SA (UP)
(E) 2"ø CHR UP & DN
(E) 2"ø CHS UP & DN
(E) 2"ø HWR UP & DN
(E) 2"ø HWS UP & DN
M301
6"ø EA ER-2
100 CFM
SD-2
75 CFM6"ø SA
4"ø
SD-1
35 CFM
ER-1
50 CFM
4"ø
"x
8"
20"x8"
9"x9" EA
EF-2
BCU-2
10"x10" 9"x9"
BCU-1
EF-1
SR-1
940 CFM
RG-1
(E) SG
590 CFM
RG-1
ER-1
50 CFM
ER-1
50 CFM
4"x8" EA (UP)(E) SG
590 CFM
SR-1
940 CFM
20"x8" SA
6"ø SA
SD-2
75 CFM ER-2
100 CFM
6"ø EA
ER-1
50 CFM
SD-1
35 CFM
9"x9" EA 4"ø SA
4"ø 10"x10"
9"x9"
(E) SD (E) SD (E) SD
(E) SD (E) SD (E) SD
(E) RG(E) RG
40"x18" OA (DN)
(E) RG
JANITOR
(E) SD
160 CFM
(E) SD
(E) SD
(E) RG
(E) SD
(E) SD
(E) SD(E) SD
(E) SD
(E) SD
3/4"ø HWR 3/4"ø HWS
(E) SD
260 CFM
(E) SD
40 CFM
(E) SD
230 CFM
(E) SD
40 CFM
10"x16" SA (UP)
(E) SD
725 CFM
(E) SD(E) SD
M301
23.29
23.29
23.30
23.30
M101
23.31
23.31
M101
M301
M301
MECHANICAL
110B
MECHANICAL
111B
23.32
23.32
23.33
23.34
23.34
23.34
23.35
23.36
(E)36"x8" SA (UP)
(E)36"x8" SA (UP)
23.34 23.34
M301
M301
BCU-2
EF-2
1 1/4"ø D DN 3/4"ø HWR DN3/4"ø HWS DN
3/4"ø CHS DN 3/4"ø CHR DN
MECHANICAL
111B
TOILET
111A
LOBBY
M301
M301
EF-1
BCU-1
1 1/4"ø D DN 3/4"ø HWR DN
3/4"ø HWS DN 3/4"ø CHS DN 3/4"ø CHR DN
LOBBY
TOILET
110A
MECHANICAL
110B
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Date:Revisions:No.
Au to de sk
D oc s:
//M t H om e
VA
R es to ra tio n of
B
T he at er
/F
FE
_M t H om e
- T he at er
_B
_M
EP
(2
4) .rv t 7/
1/
:5 3:
P
M
M101
BASEMENT AND FIRST FLOOR
PLANS
07/01/2025 KF KG
RESTORATION OF BUILDING 35
HISTORIC THEATER
621-24-403
MT. HOME, TENNESSEE
BID DOCUMENTS
JAMES H.
QUILLEN VA
MEDICAL
CENTER Approved: Owner
D R A W I N G N O T E S :
23.09 INSTALL NEW SOUND ATTENUATOR.
23.11 EXTEND CHILLED WATER AND HEATING WATER PIPING TO NEW UNIT LOCATION ON FIRST FLOOR.
23.28 CONNECT 46"X6" SA DUCTWORK TO EXISTING.
23.29 CONNECT EXHAUST FAN DISCHARGE DUCT TO NEW WALL LOUVER. SEE ARCHITECTURAL PLANS.
23.30 SUSPEND FAN FROM STAIR STRUCTURE WITH NEOPRENE ISOLATORS.
23.31 SET UNIT ON FLOOR WITH NEOPRENE PAD AND SECONDARY DRAIN PAN BELOW. PROVIDE MOISTURE SENSOR TO SHUT
OFF UNIT WHEN MOISTURE IS SENSED.
23.32 LOCATE EXISTING GRILLE IN FLOOR OF NEW CONSTRUCTION. ROUTE SUPPLY AIR DUCT TO BASEMENT CRAWL SPACE
BELOW FIRST FLOOR.
23.33 ROUTE DUCTWORK TO AVOID NEW STAIR STRUCTURE.
23.34 REINSTALL EXISTING GRILLE AND BALANCE TO CFM INDICATED.
23.35 ROUTE DUCT FROM BASEMENT UP TO SECOND FLOOR. SEE M102 FOR CONTINUATION UP.
23.36 ROUTE DUCT UP TO SECOND FLOOR. SEE M102 FOR CONTINUATION.
23.37 SUPPORT ODU-1 FROM WALL. MOUNT LEVEL. ROUTE REFRIGERANT LINES TO UNIT IN BASEMENT.
23.38 RL AND RS PIPING SIZED BY MANUFACTURER.
23.39 MOUNT UNIT WITH BOTTOM AT 7'-0" MINIMUM.
23.40 TERMINATE CONDENSATE DRAIN OVER NEAREST FLOOR DRAIN.
1/8" = 1'-0"1 MECHANICAL BASEMENT NEW WORK PLAN
1/8" = 1'-0"2 MECHANICAL FIRST FLOOR NEW WORK PLAN
PLAN
NORTH
1/4" = 1'-0"3 MECHANICAL 111B
1/4" = 1'-0"4 MECHANICAL 110B
DRESSING ROOM
TOILET
TOILET
CORRIDOR
DRESSING ROOM
STAGE
(E)40"x18" OA
(E)38"x12" OA (DN)
(E)20"x40" RA
23.06
8"x8" EA
4"x8" EA (DN)
ER-1
50 CFM
ER-1
50 CFM
6"x4" EA
6"x4" EA
8"x8" EA
8"x8" EA (UP)
12"x38" OA
12"x38" OA
(E) SD
170 CFM
(E) SD
170 CFM
(E)8"ø SA (UP)
(E)8"ø SA (UP)
SR-2
185 CFM
SR-2
190 CFM
SR-4
40 CFM
SR-4
40 CFM
SR-3
260 CFM
SR-3
475 CFMTG-1
TG-1
16"x8" SA
20"x40" RA
(E) 2"ø HWS DN
(E) 2"ø HWR DN
(E) 2"ø CHS DN
(E) 2"ø CHR DN
23.41
23.41
23.42
23.43
16"x8" SA
16"x8" SA 10"x16" SA (DN)
23.44
MECH/ELEC
LOBBY
BALCONY
(E) VAV-L1(E)18"x12" RA(E)12"x8" SA
M301
(E)14"x14" OA (UP) (E)20"x20" RA (UP)
(E) AHU-L2
(E) AHU-L1
(E)12"x14" OA (UP)
(E) SD
890 CFM
(E) SD
480 CFM
(E) SD
890 CFM
(E) 2"ø HWS UP
(E) 2"ø HWR UP
(E) 2"ø CHS UP
(E) 2"ø CHR UP
8"ø SA (UP)
(E) SD
170 CFM
(E) RADIATOR
(E) RADIATOR
(E) SD
170 CFM
(E)8"ø SA (UP)
(E) SD
(E) RG
M301
(E)12"x14" OA (UP)
(E) SD
890 CFM
(E) SD
480 CFM
(E) SD
890 CFM
(E) VAV-L2
(E)38"x12" OA (UP)
(E)14"x14" OA (DN)
(E) EF-4
PROJECTOR BOOTH
LOBBY
(E) 2"ø CHR UP
(E) 2"ø CHS UP
(E) 2"ø HWR UP
(E) 2"ø HWS UP
M301
(E)12"x38" OA
(E)20"x32" RA
20"x32" RA
12"x38" OA (DN)
20"x40" RA (DN)
10"ø SA 8"ø SA
8"ø SA
2"ø CHR DN 2"ø CHS DN
2"ø HWS DN 2"ø HWR DN
FD 23.45
FD 23.45
M301
(E) AHU-B
AHU-B
AHU-BR
14"x26" RA
26"x14" SA
(E) VAV-B
10"ø OA
(E)26"x14" SA
(E)38"x12" OA
16"x15" OA
23.09
23.09
1"ø HWS 1"ø HWR 1"ø CHS 1"ø CHR
23.53
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Date:Revisions:No.
Au to de sk
D oc s:
//M t H om e
VA
R es to ra tio n of
B
T he at er
/F
FE
_M t H om e
- T he at er
_B
_M
EP
(2
4) .rv t 7/
1/
:5 3:
P
M
M102
BALCONY, SECOND FLOOR, AND
ATTIC PLANS
07/01/2025 KF KG
RESTORATION OF BUILDING 35
HISTORIC THEATER
621-24-403
MT. HOME, TENNESSEE
BID DOCUMENTS
JAMES H.
QUILLEN VA
MEDICAL
CENTER Approved: Owner
D R A W I N G N O T E S :
23.06 8X8 EXHAUST DUCT UP TO ROOF.
23.09 INSTALL NEW SOUND ATTENUATOR.
23.41 ROUTE DUCTWORK TO AVOID THE THEATRICAL CURTAINS AND SUPPORTS. SEE STAGE DUCTWORK FOR ISOMETRIC ON M301.
23.42 ROUTE DUCTWORK FROM FIRST FLOOR TIGHT TO CEILING.
23.43 INSTALL DUCTWORK TIGHT TO CEILING.
23.44 ROUTE DUCTWORK DOWN TO FIRST FLOOR.
23.45 RELOCATE EXISTING FIRE DAMPER.
23.53 SET UNIT ON FLOOR WITH NEOPRENE PAD AND SECONDARY DRAIN PAN BELOW. PROVIDE MOISTURE SENSOR TO SHUT
OFF UNIT WHEN MOISTURE IS SENSED.
1/8" = 1'-0"4 MECHANICAL BACK LEVEL 2 NEW WORK PLAN
1/8" = 1'-0"3 MECHANICAL BALCONY NEW WORK PLAN
PLAN
NORTH
1/8" = 1'-0"2 MECHANICAL PROJECTOR BOOTH NEW WORK PLAN
1/8" = 1'-0"1 MECHANICAL ATTIC NEW WORK PLAN
35-SEF-2
56"ø56"ø
35-SEF-1
M301
56"ø 56"ø 56"x56"
56"x56"
23.01 23.01
23.0123.01
(E) THEATER VENT
BLOCKED OFF IN
PREVIOUS PROJECT
(E) ROOF ACCESS HATCH
(E) ATTIC VENT(E) ATTIC VENT 23.46
23.46
23.47
23.47
23.48 23.48
23.48 23.48
23.49
23.49
23.5023.51
23.51
23.52
M301
56"x56"
56"x56"
(E) ERV-1
(E) ERV-2
(E)20"x20" RA
(E)18"x20" OA
(E)18"x20" OA
(E)20"x20" RA
(E)20"x40" RA
(E)40"x18" OA (DN)
(E) EF-3
ROOF ACCESS HATCH
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Date:Revisions:No.
Au to de sk
D oc s:
//M t H om e
VA
R es to ra tio n of
B
T he at er
/F
FE
_M t H om e
- T he at er
_B
_M
EP
(2
4) .rv t 7/
1/
:5 3:
P
M
M103
ROOF PLANS
07/01/2025 KF KG
RESTORATION OF BUILDING 35
HISTORIC THEATER
621-24-403
MT. HOME, TENNESSEE
BID DOCUMENTS
JAMES H.
QUILLEN VA
MEDICAL
CENTER Approved: Owner
1/8" = 1'-0"1 MECHANICAL ROOF NEW WORK PLAN
1/8" = 1'-0"2 MECHANICAL BACK ROOF NEW WORK PLAN
PLAN
NORTH
D R A W I N G N O T E S :
23.01 PROVIDE FIRE RATED FLEXIBLE CONNECTIONS AT DUCT CONNECTION TO EACH SIDE OF FAN. FABRIC ASSOCIATED WITH
THE DUCT CONNECTION SHALL MEET ASTM E119-20 AND A TEMPERATURE RATING OF 155 DEG F.
23.46 PROVIDE 56"X56" MOTORIZED DAMPER INTERLOCK WITH SMOKE EXHAUST FAN.
23.47 PROVIDE BIRD SCREEN OVER OPENING.
23.48 PROVIDE EQUIPMENT RAILS AND UNI-STRUT SUPPORT FOR DUCTWORK.
23.49 INTERLOCK FAN TO FIRE ALARM SYSTEM.
23.50 POSITION DUCTWORK, WALL OPENING AND FAN TO ALLOW ROOF ACCESS HATCH TO OPEN FULLY.
23.51 PROVIDE EQUIPMENT RAILS FOR FAN SUPPORT. PROVIDE HOUSED SPRING ISOLATORS FOR FAN.
23.52 CAP CURB WITH A INSULATED PANEL SUITABLE FOR WALKING ON. DISABLE DAMPER AND SECURE IN CLOSED POSITION.
CONTRACTOR TO VERIFY CURB DIMENSIONS IN THE FIELD.
02.1-BACK LEVEL 2
1728' - 4
02.3 BOH T.O. ROOF
1737' - 4
04.2-ATTIC
1756' - 0
01.2-FIRST FLOOR
1718' - 6"
01.2-FIRST FLOOR
1718' - 6"
04.3-T.O. ROOF
1768' - 10 1/4"
04.2-ATTIC
1756' - 0"
35-SEF-2 35-SEF-1
(E)10"ø SA
2"ø CHR 2"ø CHS 2"ø HWR 2"ø HWS
(E)12"x38" OA (E)32"x20" RA
M301
(E)20"x32" RA
(E)20"x20" RA (E)18"x20" OA
(E)28"x12" SA
12"x28" SA
(E)38"x12" OA
12"x38" OA
(E)12"x38" OA
FD
12"x22" SA
9"x22" SA
(E)20"x40" RA
(E)20"x20" RA
(E)18"x20" OA
(E)40"x18" OA SA FROM BASEMENT
(E)OA TO BASEMENT
(E)RA TO ERV
(E)OA FROM ERV
(E)OA FROM ERV
(E)RA TO ERV
(E)OA FROM BASEMENT
(E)RA FROM AUDITORIUM
(E)OA TO PROJECTOR ROOM
(E)9"x22" SA (E)6"x12" SA
FD
20"x40" RA
20"x40" RA
20"x32" RA
(E)20"x40" RA
AHU-S1
01.2-FIRST FLOOR
1718' - 6"
M301
EF-2
10"x10" EA
8"x20" SA9"x9" EA
SD-1
35 CFM
ER-1
50 CFM
BCU-2
3/4"ø CHR 3/4"ø CHS 3/4"ø HWS 3/4"ø HWR
1 1/4"ø D
TOILET
111A
MECHANICAL
111B
01.2-FIRST FLOOR
1718' - 6"
M301
RG-1
8"x20" SA
BCU-2
3/4"ø CHR
3/4"ø HWS 3/4"ø HWR
1 1/4"ø D3/4"ø CHS
MECHANICAL
111B
01.2-FIRST FLOOR
1718' - 6"
M301
SD-1
35 CFM
ER-1
50 CFM
9"x9" EA8"x20" SA
EF-1
BCU-1
10"x10" EA
1 1/4"ø D
3/4"ø CHR 3/4"ø CHS
3/4"ø HWS 3/4"ø HWR
TOILET
110A
MECHANICAL
110B
01.2-FIRST FLOOR
1718' - 6"
M301
3/4"ø CHR
3/4"ø HWS 3/4"ø HWR
3/4"ø CHS 1 1/4"ø D
RG-1
BCU-1
8"x20" SA
MECHANICAL
110B
04.3-T.O. ROOF
1768' - 10 1/4"
05-RAFTERS
1772' - 5"
04.2-ATTIC
1756' - 0"
M301
35-SEF-2
56"ø 56"ø
56"x56"
(E) ATTIC VENT
(E) THEATER VENT
BLOCKED OFF IN
PREVIOUS PROJECT
(E)10"ø SA
(E)8"ø SA
(E)8"ø SA
23.01 23.01
23.52
BCU-1
3/4"ø CHR 3/4"ø CHS 3/4"ø HWS
3/4"ø HWR
RG-1
20"x8" SA SR-1
SD-2
ER-2
6"ø EA
9"x9" EA 4"ø EA
10"x10" EA
EF-1
6"ø SA
4"ø SASD-1
1 1/4"ø D
BCU-2
RG-1
20"x8" SA
10"x10" EA
EF-2
4"ø EA9"x9" EA 6"ø EA
4"ø SA
6"ø SA
SD-2
SR-1
ER-2
3/4"ø CHR 3/4"ø CHS3/4"ø HWS
3/4"ø HWR 1 1/4"ø D
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Date:Revisions:No.
Au to de sk
D oc s:
//M t H om e
VA
R es to ra tio n of
B
T he at er
/F
FE
_M t H om e
- T he at er
_B
_M
EP
(2
4) .rv t 7/
1/
:5 3:
P
M
M301
MECHANICAL SECTIONS
07/01/2025 KF KG
RESTORATION OF BUILDING 35
HISTORIC THEATER
621-24-403
MT. HOME, TENNESSEE
BID DOCUMENTS
JAMES H.
QUILLEN VA
MEDICAL
CENTER Approved: Owner
1/4" = 1'-0"1 ROOF SMOKE EXHAUST SECTION
3 STAGE DUCTWORK ISOMETRIC
1/4" = 1'-0"4 MECHANICAL ROOM BELOW STAIRS - SOUTH
1/4" = 1'-0"5 MECHANICAL ROOM BELOW STAIRS - EAST
1/4" = 1'-0"6 MECHANICAL ROOM BELOW STAIRS - NORTH
1/4" = 1'-0"7 MECHANICAL ROOM BELOW STAIRS - EAST
1/4" = 1'-0"8 ROOF SECTION - SMOKE EXHAUST - NORTH
2 BCU-1 ISOMETRIC 9 BCU-2 ISOMETRIC
D R A W I N G N O T E S :
23.01 PROVIDE FIRE RATED FLEXIBLE CONNECTIONS AT DUCT CONNECTION TO EACH SIDE OF FAN. FABRIC ASSOCIATED WITH
THE DUCT CONNECTION SHALL MEET ASTM E119-20 AND A TEMPERATURE RATING OF 155 DEG F.
23.52 CAP CURB WITH A INSULATED PANEL SUITABLE FOR WALKING ON. DISABLE DAMPER AND SECURE IN CLOSED POSITION.
CONTRACTOR TO VERIFY CURB DIMENSIONS IN THE FIELD.
DRAW THRU
BLOW THRU
2" [50mm]
PLUS X
1" [25mm]
MINIMUM
X
2X
UNIT TYPE A B
WHERE X = STATIC PRESSURE IN PAN
DRAIN LINE SHALL BE AT LEAST THE SAME SIZE
AS THE NIPPLE ON THE DRAIN PAN PIPING SHALL
BE RIGID COPPER TYPE L OR TYPE M UNLESS
NOTE BELOW IS MET
PITCH DOWN
TOWARD DRAIN
CLEAN OUT
FLOOR SINK
DRAIN
PAN
DIELECTRIC
FITTING
1.
2.
NOTE:
CPVC PIPE MAY BE USED ONLY IF APPROVED BYLOCAL VA AND IS
INDOORS AND DOES NOT PASS THROUGHRATED BARRIERS.
DIELECTRIC FITTING TO BE USED WHEN TWO DISSIMILARMETALS ARE
TO BE CONNECTED.
B A
1" [2
5m m]
MV
COIL
TEST PLUG (TYP.)
REDUCER, IF REQUIRED
WATER RETURN
MANUAL AIR VENT
UNION CONNECTIONS (TYP.)
WATER SUPPLY
SHUT OFF VALVE
DRAIN WITH HOSE CONNECTION
MODULATION CONTROL VALVE
1.
2.
3.
4.
NOTE:
ALL VANE ELBOWS SHALL BE CONSTRUCTED AND INSTALLED AS DETAILED BY SMACNA.
WHEN W1 DOES NOT EQUAL W2, VANE SHALL BE SINGLE THICKNESS VANE TYPE REGARDLESS OF W DIMENSION.
ALL SINGLE THICKNESS VANES SHALL HAVE A 2" [50mm] RADIUS, 1 1/2" [40mm] MAXIMUM SPACE BETWEEN VANES AND A 3/4" [20mm] TRAILING EDGE.
WHEN W EQUALS W2 AND W1 IS GREATER THAN 20" [500mm] VANES SHALL BE DOUBLE VANE TYPE.
W
W1
VANE VANE
R SHALL
EQUAL OR
BE
GREATER
THAN W.
R SHALL
EQUAL OR
BE
GREATER
THAN 1/3W.
R SHALL
EQUAL OR
BE
GREATER
THAN 1/6W.
STANDARD RADIUS OR
LONG RADIUS ELBOW
SHORT RADIUS ELBOW
WITH ONE VANE SHORT RADIUS ELBOW
WITH TWO VANES
R
R
W
W
1/3 W
2/3 W
W
R 1/6 W
1/2 W
1/3 W
1.
2.
NOTE:
THE INTERIOR SURFACE OF ALL RADIUS ELBOWS SHALL BE MADE ROUND.
ALL STANDARD RADIUS ELBOWS CAN BE SUBSTITUTED WITH SHORT RADIUS ELBOWS. ALL
SHORT RADIUS ELBOWS SHALL HAVE VANES. VANES SHALL BE CONSTRUCTED, SUPPORTED
AND FASTENED AS RECOMMENDED BY SMACNA.
EQ
UI
PM
EN
T
TYPICAL DUCTWORK TRANSITION
PLAN OR SIDE VIEW
TYPICAL DUCTWORK TRANSITION WITH
EQUIPMENT MOUNTED IN DUCT
PLAN OR SIDE VIEW
15° M
AX.
° M
AX
30° M
AX.15
° M
AX
AIR FLOW AIR FLOW
° M
AX
15° M
AX.
NOTE:
UNLESS OTHERWISE INDICATED ON PLANS, MAXIMUM ANGLES SHOWN SHALL APPLY. AIR SPLIT DUCT TAKE-OFF PLAN VIEW BRANCH DUCT TAKE-OFF PLAN VIEW
SUPPLY REGISTER OR
BRANCH DUCT
TURNING VANES
MAIN SUPPLY DUCT
SEE FLOOR PLAN FOR SPLIT
DIMENSION
PROVIDE VOLUME
DAMPER
PROVIDE
VOLUME
DAMPER
1/4 W OR 4" [100mm] MIN.
AIR FLOW
MAIN SUPPLY
DUCT
AI
R
FL
OW
W
AI
R
FL
OW
AIR FLOW
AIR FLOW
MAIN EXHAUST OR RETURN
PLAN VIEW
AIR FLOW
AIR FLOW
PROVIDE VOLUME DAMPER AT
EACH BRANCH DUCT
1/4W OR 4"
[100mm] MIN.
BRANCH DUCT
VD
AI
R
FL
OW
W
1.
2.
3.
NOTE:
DELETE INSULATION STAND-OFF ON DUCTWORK WITHOUT EXTERIOR INSULATION.
DETAIL SHOWS SINGLE BLADE DAMPER. DAMPER INSTALLATION SHALL BE SIMILAR FOR MULTI-BLADE DAMPERS
& ROUND DAMPERS.
SEE GENERAL NOTES ON MECHANICAL NEW WORK SHEETS REGARDING VOLUME DAMPER LOCATIONS AND
ABOUT REMOTE ADJUSTMENT DEVICE OPTION FOR INACCESSIBLE CEILINGS.
INSULATION SEE
SPECIFICATION
DAMPER BLADE
1/8" [6mm]
CLEARANCE ALL
AROUND
OUTSIDE END BEARING
INSIDE END BEARING
HANDLE WITH
LOCKING
QUADRANT
INSULATION
STAND-OFF
1/2" [15mm] ROUND ROD PIN
DUCT
STIFFEN BLADE AS
REQUIRED
SIDE ELEVATION SECTION
1/2" 1/2" 1 1/2"
ROUND FLEXIBLE CONNECTION
RECTANGULAR FLEXIBLE CONNECTION
FLANGED
CONNECTION
ON FAN SIDE
WASHER
1 1/2" [40mm] MIN. TO 3" [75mm] MAX. INSTALLED. 6" [150mm] NOMINAL WITH MATERIAL TAUT
FLEXIBLE
MATERIAL AS
SPECIFIED
1"x1/8" [25x3mm] DRAW BAND
1"x1/8" [25x3mm] BAND IRON
BOLT ON 4" [100mm] CENTERS
5/16" [8mm] FLANGE
DUCT
SHEET METAL SCREWS ON 12"
[300mm] CENTERS
RIVET ON 4" [100mm]
CENTERS
SHEET METAL AS
SPECIFIED FOR
DUCTWORK.
1"x1/8" [25x3mm] BAND IRON
BOLT ON 4" [100mm] CENTERS
1" [25mm] FLANGE & HEM
ALTERNATE
POSITION OF
BOLT
1 1/2" [40mm] POCKET SLIP
DUCT
SHEET METAL AS
SPECIFIED FOR
DUCTWORK.
[15mm] [15mm] [40mm]
1 1/2" [40mm] MIN. TO 3" [75mm] MAX. INSTALLED. 6" [150mm] NOMINAL WITH MATERIAL TAUT
FLANGED CONNECTION ON FAN
SIDE
WASHER
FLEXIBLE MATERIAL AS
SPECIFIED
1"
SLEEVE, NOTE 2
DUCT
CONNECTION
NOTE 4
DAMPER,
NOTE 1
DAMPER COLLAR
EXTENSION INTEGRAL
PART OF SLEEVE
SLEEVE, NOTE 2
NOTE 6
FIRE BARRIER
PARTITION OR CHASE
TYPICAL DUCT
INSULATION
PERIMETER ANGLE, NOTE 3
(NOTE FASTENED TO PARTITION)
ACCESS PANEL
NOTE 5
[25 mm
1.
2.
3.
4.
5.
6.
7.
NOTE:
A VERTICAL DAMPER IS SHOWN. HORIZONTAL DAMPER INSTALLATION, 1S SIMILAR. FOLLOW DAMPER MANUFACTURER'S INSTRUCTIONS, INCLUDING FASTENER OPTIONS AND GAGES FOR SLEEVE AND PERIMETER ANGLES. FIRE DAMPERS MUST BE INSTALLED IN THE PARTITION OR FLOOR AND NOT
OUTSIDE THE PENETRATION.
GALVANIZED SLEEVE: GAGE NOT LESS THAN CONNECTING DUCT. FASTEN SLEEVE TO DAMPER FRAME AND TO PERIMETER ANGLES.
PERIMETER ANGELS: GALVANIZED STEEL, NOT LESS THAN 1 1/2"x1 1/2" [40x40mm], 14 GAGE, TO PROVIDE 1" [25mm] MINIMUM OVERLAP OF OPENING
ON ALL 4 SIDES.
BREAKAWAY DUCT CONNECTION: CONTRACTOR'S OPTION OF TYPES SHOWN IN SMACNA. ACCESS PANELS: SIZE AND LOCATION TO PERMIT
SERVICING THE FUSIBLE LINK OR LINKS.
PROVIDE 1/4" TO 1/2" [6 TO 15mm] CLEARANCE ON HEIGHT AND WIDTH. FILL OPEN SPACE WITH ROCK WOOL FIRESTOP FIBER.
ALL DUCT WORK RISERS WHICH ARE RUN EXPOSED, SUCH AS THRU ATTIC FLOORS AND MECHANICAL ROOM FLOORS, SHALL BE PROVIDED WITH 3" [75mm] HIGH CONCRETE CURB AROUND OPENING FOR DUCT.
PLACE ACTUATOR IN ROOM WITH LAY-IN CEILING.
FLEXIBLE DUCT SIZE
SAME AS DIFFUSER
INLET: 5'-0" MAX LENGTH.
12"
CEILING
SUPPORT SADDLE
FROM STRUCTURE
VOLUME DAMPER
W/LOCKING QUAD
SHEET METAL
SADDLE
CONICAL OUTLET
BRANCH DUCT
USE RIGID ELBOWS FOR
CHANGE OF DIRECTION
GREATER THAN 45°
[300mm]
SEE SPECIFICATIONS FOR CLAMPS AND
SEALANT (TYP.)
NOTE:
THE USE OF FLEXIBLE AIR DUCT CONNECTORS ARE NOT PERMITTED FOR THE
DEDICATED AHU SERVING THE SURGICAL SUITE.
TYPICAL
DIFFUSER OR
REGISTER IN
LAY-IN CLG.
THERMAL INSULATION SEE
SPECIFICATIONS
FAN COIL SEQUENCE OF OPERATION (PATIENT ROOMS)
FAN COIL UNIT SHALL OPERATE ON A SCHEDULE AS SET BY THE ECC. FAN SHALL
RUN CONTINUOUSLY. FAN STATUS SHALL BE MONITORED AND AN ALARM MESSAGE SHALL
BE GENERATED IN THE EVENT THE UNIT FAILS TO RUN. THE ADJUSTABLE FROM TEMP
SET POINT WILL BE 70* - 75* WITH 0.5* HEATING/COOLING OFFSETS. VALVE V-1 & V-2
WILL NOT BE OPEN SIMULTANEOUSLY. ROOM OCCUPANT WILL HAVE ABILITY OF ADJUSTING
ROOM TEMPERATURE BETWEEN 70* - 75*.
FAN COIL SEQUENCE OF OPERATION (OUTPATIENT ROOMS)
FAN COIL SHALL OPERATE ON A SCHEDULE AS SET BY ECC. FAN SHALL RUN CONTINUOUSLY
IN OCCUPIED MODE. FAN STATUS SHALL BE MONITORED AND AN ALARM MESSAGE SHALL BE
GENERATED IN THE EVENT THE UNIT FAILS TO RUN BETWEEN THE RANGE OF 70* _75* SPACE
TEMPERATURE BOTH V-1 & V-2 SHALL BE CLOSED. UPON RISE IN TEMPERATURE ABOVE 75*
V-2 SHALL MODULATE OPEN TO MAINTAIN 75* F. UPON FALL IN TEMPERATURE BELOW 70*F.
HEATING VALVE V-1 SHALL MODULATE TO OPEN TO MAINTAIN 70* F.
RA
HEATING COIL COOLING COIL
FAN
CS
TTFILTER
V - 1
HWR
HWS
V - 2
CHR
CHS
PC
T T - 1
HS SST
ROOM TEMPERATURE SENSOR WITH SPACE ADJUSTABLE WALL MOUNTED
48" [1200mm] AFF.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Date:Revisions:No.
Au to de sk
D oc s:
//M t H om e
VA
R es to ra tio n of
B
T he at er
/F
FE
_M t H om e
- T he at er
_B
_M
EP
(2
4) .rv t 7/
1/
:5 3:
P
M
M501
MECHANICAL DETAILS
07/01/2025 KF KG
RESTORATION OF BUILDING 35
HISTORIC THEATER
621-24-403
MT. HOME, TENNESSEE
BID DOCUMENTS
JAMES H.
QUILLEN VA
MEDICAL
CENTER Approved: Owner
NTS1 AIR HANDLING UNIT DRAIN TRAP DETAIL
NTS2 TERMINAL UNIT WATER COILS - PIPING CONNECTIONS
NTS3 DUCTWORK SQUARE VANE ELBOWS
NTS4 DUCTWORK RADIUS ELBOWS
NTS5 DUCTWORK TRANSITIONS (WITH EQUIPMENT MOUNTED IN DUCT)
NTS6 SUPPLY DUCTWORK TAKE-OFFS
NTS7 EXHAUST OR RETURN BRANCH DUCTWORK
NTS8 VOLUME DAMPER DETAIL
NTS9 FLEXIBLE DUCT CONNECTIONS
NTS10 SECTION THROUGH FIRE DAMPER INSTALLATION
NTS11 FLEXIBLE AIR DUCT CONNECTOR
NTS12 FOUR PIPE FAN COIL UNIT CONTROLS
SOUND ATTENUATING DEVICE SCHEDULE
MARK LOCATION SYSTEM AND/OR
SERVICE TYPE
AIRFLOW APD INLET SIZE LENGTH
DYNAMIC INSERTION LOSS DB OCTAVE BAND AND MID-FREQUENCY [CPS]
REMARKS63 125 250 500 1000 2000 4000 8000
CFM [L/s] IN WG [Pa] IN [mm] IN [mm] 1 2 3 4 5 6 7 8
AHU-A1 BASEMENT AHU-A1 (SUPPLY) RECTANGULAR 2600 [ 1200 ] 0.17 [ 43 ] 20 x 20 490 X 490 48 [ 1200 ] 7 11 15 23 18 14 11 9 ----
AHU-A1R BASEMENT AHU-A1 (RETURN) RECTANGULAR ELBOW -2600 [ -1000 ] 0.09 [ 23 ] 26 x 16 640 x 400 40 [ 1000 ] 5 10 19 24 33 31 25 22 ----
AHU-A2 BASEMENT AHU-A2 (SUPPLY) CIRCULAR 2600 [ 1200 ] 0.16 [ 40 ] 20 [ 490 ] 120 [ 3000 ] 10 16 44 55 55 54 47 46 ----
AHU-A2R BASEMENT AHU-A2 (RETURN) RECTANGULAR ELBOW -2600 [ -1000 ] 0.09 [ 23 ] 26 x 16 640 x 400 40 [ 1000 ] 5 10 19 24 33 31 25 22 ----
AHU-B BOOTH AHU-B (SUPPLY) RECTANGULAR 2600 [ 1200 ] 0.14 [ 35 ] 26 x 14 640 x 340 48 [ 1200 ] 6 9 15 24 20 16 12 10 ----
AHU-BR BOOTH AHU-B (RETURN) RECTANGULAR ELBOW -2600 [ -1000 ] 0.09 [ 23 ] 20 x 20 490 X 490 36 [ 900 ] 6 10 17 21 27 24 21 18 ----
AHU-S1 STAGE AHU-S1 (SUPPLY) RECTANGULAR 2900 [ 1400 ] 0.2 [ 50 ] 28 x 12 690 x 300 60 [ 1500 ] 6 11 18 31 27 20 13 10 ----
AHU-S1R BASEMENT AHU-S1 (RETURN) RECTANGULAR ELBOW -2900 [ -1000 ] 0.05 [ 13 ] 36 x 14 880 x 340 50 [ 1300 ] 6 11 19 24 30 28 23 20 ----
AHU-S2 BASEMENT AHU-S2 (SUPPLY) RECTANGULAR 2900 [ 1400 ] 0.22 [ 55 ] 22 x 16 540 x 400 72 [ 1800 ] 7 12 21 35 32 24 17 13 ----
AHU-S2R BASEMENT AHU-S2 (RETURN) RECTANGULAR ELBOW -2900 [ -1000 ] 0.07 [ 18 ] 26 x 18 640 x 440 40 [ 1000 ] 5 10 19 24 33 31 25 22 ----
FOUR PIPE FAN COIL UNIT SCHEDULE
MARK LOCATION TYPE
FAN AIR FLOW EXTERNAL APD
COOLING REQUIREMENTS HEATING REQUIREMENTS
FILTER
FAN MOTOR
MIN SENS CAPACITY MIN TOTAL CAPACITY
EAT
FLOW EWT WPD RUNOUT SIZE MIN CAPACITY EAT Db FLOW EWT WPD RUNOUT SIZE POWER
PHASE VOLT RPM SPEED
CONTROL REMARKSDb Wb
CFM [L/s] IN WG [Pa] BTUH [W] BTUH [W] °F [°C] °F [°C] GPM [L/s] °F [°C] FT [kPa] IN [mm] BTUH W °F [°C] GPM [L/m] °F [°C] FT [kPa] IN [mm] MERV
RATING HP [W]
BCU-1 111A VERTICAL 1050 [ 500 ] 0.5 [ 130 ] 16800 [ 4900 ] 23200 [ 6800 ] 75 [ 24 ] 65 [ 18 ] 3.1 [ 41 ] 44 [ 7 ] 6.27 [ 19 ] 0.75 [ 19 ] 29400 [ 8600 ] 68 [ 20 ] 1.9 [ 7 ] 155 [ 68 ] 0.08 [ ] 1 [ 25 ] 8 0.5 [ 370 ] 1 115 1332 ECM 1, 2
BCU-2 110A VERTICAL 1050 [ 500 ] 0.5 [ 130 ] 16800 [ 4900 ] 23200 [ 6800 ] 75 [ 24 ] 65 [ 18 ] 3.1 [ 41 ] 44 [ 7 ] 6.27 [ 19 ] 0.75 [ 19 ] 29400 [ 8600 ] 68 [ 20 ] 1.9 [ 7 ] 155 [ 68 ] 0.08 [ ] 1 [ 25 ] 8 0.5 [ 370 ] 1 115 1332 ECM 1, 2
REMARK:
1. 2" MERV 8 FILTER, MOTOR SPEED SHALL BE MANUAL ADJUSTED AT THE UNIT.
2. PROVIDE SECONDARY DRAIN PAN WITH MOISTURE SENSOR TO SHUT COOLING VALVE ON THE UNIT. BASIS OF DESIGN TITUS TVBD SIZE 12 (TITUS SQ 50517)
SPLIT SYSTEM AIR CONDITIONER GAS/ELECTRIC SCHEDULE
MARK LOCATION
AREA
AND/OR
BLDG
SERVED
TYPE
TOTAL SUPPLY AIR
FLOW
MIN. OUTSIDE AIR
FLOW
EXT STATIC
PRESSURE
COOLING CAPACITY
AIR FILTER
MARK NO
ELECTRICAL DATA
REMARKSMIN TOTAL
CAPACITY MIN SENS CAPACITY MIN
SEER
EAT
OSA DESIGN TEMP
COMP Kw
INDOOR FAN OUTDOOR UNIT (FAN/COMP)
Db Wb
CFM [L/s] CFM [L/s] IN [Pa] MBH [kW] MBH [kW] °F [°C] °F [°C] °F [°C] HP [W] CONTROL MCA [W] CONTROL
ODU-1/IDU-1 OUTSIDE/INSIDE TR ROOM DUCTLESS SPLIT 375 [ 180 ] 0 [ ] 1.5 [ 380 ] 18 [ 61 ] [ ] 19.5 75 [ 24 ] 64 [ 18 ] [ 95 ] [ 35 ] -- MERV 7 0.04 [ 30 ] TEMPERATURE SENSOR 16 [ 12000 ] BACnet 1, 2, 3, 4
REMARKS:
1. PROVIDE WALL MOUNTED INDOOR UNIT (IDU-1) WITH WALL MOUNTED THERMOSTAT FOR CONTROL OF THE UNIT AND BACnet INTEGRATION TO BAS SYSTEM.
2. PROVIDE WALL MOUNTING BRACKETS FOR THE OUTDOOR UNIT.
3. PROVIDE 1/2" TWIN TUBE LINESET WITH INSULATION. SUITABLE FOR THE LENGTH REQUIRED FOR INDOOR TO OUTDOOR UNIT.
4. PROVIDE ADVANCED MINI CONDENSATE PUMP WITH RESERVOIR AND SENSOR. BASIS OF DESIGN MITSUBISHI PUY-AK18NL / PKA-AL18NL
AIR DEVICE SCHEDULE (SUPPLY)
MARK TYPE
AIR FLOW
MAX APD
MOUNTING
PANEL/FRAME SIZE NECK SIZE
NC DAMPER FINISH REMARKSMIN MAX
IN x IN [mm x mm] IN [mm ] CFM [L/s] CFM [L/s] IN WG [Pa]
SD-1 LOUVERED FACE 35 [ 17 ] 75 [ 35 ] 0.046 [ 12 ] CEILING 12 x 12 [ 300 x 300 ] 4 [ 100 ] <15 OBD WHITE 1
SD-2 LOUVERED FACE 75 [ 35 ] 150 [ 71 ] 0.105 [ 26 ] CEILING 12 x 12 [ 300 x 300 ] 6 [ 150 ] 23 OBD WHITE 1
SR-1 SUPPLY REGISTER 600 [ 280 ] 1000 [ 470 ] 0.150 [ 38 ] WALL 22 x 10 [ 540 x 250 ] 20 x 8 [ 490 x 200 ] 35 OBD -- 2
SR-2 SUPPLY REGISTER 170 [ 80 ] 275 [ 130 ] 0.131 [ 33 ] WALL, DUCT 12 x 8 [300 x 200 ] 10 x 6 [ 250 x 150 ] 30 OBD -- 2
SR-3 SUPPLY REGISTER 260 [ 120 ] 500 [ 240 ] 0.100 [ 25 ] WALL, DUCT 18 x 10 [ 440 x 250 ] 16 x 8 [400 x 200 ] 26 OBD -- 2
SR-4 SUPPLY REGISTER 35 [ 17 ] 115 [ 54 ] 0.074 [ 19 ] WALL, DUCT 8 x 8 [200 x 200 ] 6 x 6 [ 150 x 150 ] 26 OBD -- 2
REMARKS:
1. PROVIDE SQUARE TO ROUND ADAPTER.
2. SEE SPECIFICATION 23 37 00 FOR FINISH INFORMATION.
AIR DEVICE SCHEDULE (RETURN)
MARK TYPE
AIR FLOW
MAX APD
MOUNTING
PANEL/FRAME SIZE NECK SIZE
NC DAMPER FINISH REMARKSMIN MAX
CFM [L/s] CFM [L/s] IN WG [Pa] IN x IN [mm x mm] IN x IN [mm x mm]
RG-1 LOUVERED HEAVY
DUTY 1000 [ 470 ] 2000 [ 940 ] 0.023 5.800 WALL 26 x 42 [ 600 x 980 ] 24 x 40 [ 600 x 980 ] 20 NONE -- 2
TG-1 LOUVERED HEAVY
DUTY 260 [ 120 ] 475 [ 220 ] 0.051 13.000 WALL 32 x 8 [ 790 x 200 ] 30 x 6 [ 740 x 150 ] 12 NONE -- 2
ER-1 EXHAUST REGISTER 50 [ 24 ] -- [ ] 0.016 4.000 CEILING / WALL 8 x 8 [ 200 x 200 ] 6 x 6 [ 150 x 150 ] <15 OBD -- 1, 2
ER-2 EXHAUST REGISTER 100 [ 47 ] -- [ ] 0.016 4.000 CEILING 12 x 12 [ 305 x 305 ] 8 x 8 [ 203 x 203 ] <15 OBD WHITE 1
REMARKS:
1. PROVIDE SQUARE TO ROUND ADAPTOR WHERE NECESSARY ON PLANS.
2. SEE SPECIFICATION 23 37 00 FOR FINISH INFORMATION.
FAN SCHEDULE
MARK LOCATION AREA AND/OR
BLDG SERVED
SYSTEM
AND/OR
SERVICE
AIR FLOW TSP
FAN MOTOR ELECTRICAL
CONTROL
SEQUENCE REMARKS
TYPE WHEEL CLASS
ARRANGEMENT,
ROTATION, AND
DISCHARGE
DIAMETER MIN %
EFF DRIVE FAN MAX
RPM
NOMINAL POWER
PHASE VOLT RPM SPEED
CONTROLCFM [L/s] IN [Pa] IN [mm] BHP HP [kW]
35-SEF-1 ROOF STAGE SMOKE EXHAUST 38750 [ 18000 ] 1.8 [ 450 ] TUBULAR CENTRIFUGAL MIXED FLOW II ARR 9, CLOCKWISE, HORIZONTAL 40 [ 1000 ] 63% BELT 1304 23.79 30 [ 22 ] 3 208 1725 CONSTANT ON/OFF 1, 2
35-SEF-2 ROOF STAGE SMOKE EXHAUST 38750 [ 18000 ] 1.8 [ 450 ] TUBULAR CENTRIFUGAL MIXED FLOW II ARR 9, CLOCKWISE, HORIZONTAL 40 [ 1000 ] 63% BELT 1304 23.79 30 [ 22 ] 3 208 1725 CONSTANT ON/OFF 1, 2
EF-1 110A RESTROOM GENERAL
EXHAUST 150 [ 71 ] 0.4 [ 100 ] SQUARE INLINE FAN PLENUM -- -- 8 [ 200 ] 24% DIRECT 1750 0.04 0.067 [ ] 1 115 1750 ECM ON/OFF 3, 4
EF-2 111A RESTROOM GENERAL
EXHAUST 150 [ 71 ] 0.4 [ 100 ] SQUARE INLINE FAN PLENUM -- -- 8 [ 200 ] 24% DIRECT 1750 0.04 0.067 [ ] 1 115 1750 ECM ON/OFF 3, 4
REMARKS:
1. UL LISTED FOR SMOKE CONTROL (300F/5 HRS, 392 F/2 HRS, 572F/1 HR) (CLASS F INSULATED MTR.)
2. PROVIDE UTILITY RAILS AND HOUSED SPRING ISOLATORS FOR MOUNTING TO THE ROOF.
3. SIDE DISCHARGE HOUSING WITH MOTOR SPEED ADJUSTED MANUAL ON THE MOTOR.
4. PROVIDE NEOPRENE ISOLATORS FOR SUSPENDED SUPPORT. BASIS OF DESIGN GREENHECK SQ-70-VG, QEI-44
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Date:Revisions:No.
Au to de sk
D oc s:
//M t H om e
VA
R es to ra tio n of
B
T he at er
/F
FE
_M t H om e
- T he at er
_B
_M
EP
(2
4) .rv t 7/
1/
:5 3:
P
M
M600
MECHANICAL SCHEDULES
07/01/2025 KF KG
RESTORATION OF BUILDING 35
HISTORIC THEATER
621-24-403
MT. HOME, TENNESSEE
BID DOCUMENTS
JAMES H.
QUILLEN VA
MEDICAL
CENTER Approved: Owner
F
F
F
F
F
S F
KF
S
H
C
D
FS
V
R W
SD
FT
PS
AM
C/I
PIV
K S
H
S S/R
S/R
FACP
ABBREVIATIONS
AAP - AREA ALARM PANEL - MEDICAL GAS
ACC - ACCESS
ADJ - ADJUSTABLE
AF - ARC FAULT CIRCUIT INTERRUPTER
AFCI - ARC FAULT CIRCUIT INTERRUPTER
AFF - ABOVE FINISHED FLOOR TO BOTTOM OF ITEM
AFG - ABOVE FINISHED GRADE TO BOTTOM OF ITEM
ALT - ALTERNATE
AP - ACCESS PANEL
APPROX - APPROXIMATE
ARCH - ARCHITECT OR ARCHITECTURAL
ASSY - ASSEMBLY
ATS - AUTOMATIC TRANSFER SWITCH
BLDG - BUILDING
BOE - BOTTOM OF EQUIPMENT
BOT - BOTTOM
BTWN - BETWEEN
CFCI - CONTRACTOR FURNISHED CONTRACTOR INSTALLED
CKT - CIRCUIT
CLG - CEILING
CMU - CONCRETE MASONRY UNIT
CONN - CONNECT OR CONNECTION
CONTR - CONTRACTOR
CORR - CORRIDOR
CTR - CENTER
D - DEPTH
DET - DETAIL
DIA - DIAMETER
DIM - DIMENSION
DIV - DIVISION
DN - DOWN
DWG - DRAWING
EA - EACH
EC - ELECTRICAL (DIVISION 26)
EJ - EXPANSION JOINT
ELEC - ELECTRICAL
ELEV - ELEVATION OR ELEVATOR
EM - EMERGENCY
EQ - EQUAL
EQS - EQUIPMENT SUPPLIER
EQUIP - EQUIPMENT
E/R - EXISTING TO BE RELOCATED
EX - EXISTING TO REMAIN
EXP - EXPANSION
EXT - EXTERIOR
FCE - FIRE CONTROL EQUIPMENT
FF - FINISHED FLOOR ELEVATION
FLR - FLOOR
FSC - FIRE SUPPRESSION (DIVISION 21)
FT - FEET
FTG - FOOTING
GC - GENERAL TRADES (DIVISION 01)
GF - GROUND FAULT CIRCUIT INTERRUPTER
GFCI - GROUND FAULT CIRCUIT INTERRUPTER OR
GOVERNMENT FURNISHED CONTRACTOR INSTALLED
GFFT - GROUND FAULT FEED THRU
HC - HVAC (DIVISION 23)
HP - HORSE POWER OR HIGH POINT
HVAC - HEATING, VENTILATING, AND AIR CONDITIONING
ID - INSIDE DIAMETER
IN - INCHES
KEC - KITCHEN EQUIPMENT CONTRACTOR
L - LENGTH
LBS - POUNDS
MAP - MASTER ALARM PANEL (MEDICAL GAS)
MAX - MAXIMUM
MEZZ - MEZZANINE
MFR - MANUFACTURER
MH - MANHOLE OR MOUNTING HEIGHT TO CENTER LINE OF
ITEM
MIN - MINIMUM OR MINUTE
MISC - MISCELLANEOUS
MTD - MOUNTED
MTG - MOUNTING
NIC - NOT IN CONTRACT
NOM - NOMINAL
NTS - NOT TO SCALE
OD - OUTSIDE DIAMETER
OFCI - OWNER FURNISHED CONTRACTOR INSTALLED
OFOI - OWNER FURNISHED OWNER INSTALLED
PC - PLUMBING (DIVISION 22)
PLBG - PLUMBING
RAD - RADIUS
REC - RECESSED
REQD - REQUIRED
RI - ROUGH-IN
S - SURFACE MOUNTED
SC - SECURITY (DIVISION 28)
SCH - SCHEDULE
SHT - SHEET
SMS - SECURITY MANAGEMENT SYSTEM
SPEC - SPECIFICATIONS
SQ - SQUARE
SS - STAINLESS STEEL
STD - STANDARD
STRUC - STRUCTURAL OR STRUCTURE
SUC - SITE UTILITY CONTRACTOR
TC - TECHNOLOGY CONTRACTOR
TEMP - TEMPERATURE
TOE - TOP OF EQUIPMENT
TYP - TYPICAL
UNO - UNLESS NOTED OTHERWISE
VFD - VARIABLE FREQUENCY DRIVE
VOL - VOLUME
W/ - WITH
W/O - WITHOUT
WC - WATER COOLER
WP - WEATHERPROOF
ZVC - ZONE VALVE CABINET
E2
B
E2
LUMINAIRE SYMBOLS
LIGHTING FIXTURE. CAPITAL LETTER DENOTES FIXTURE TYPE, LOWER CASE LETTER DENOTES
SWITCHING ARRANGEMENT.
LIGHTING FIXTURE ON NIGHT LIGHT OR EMERGENCY CIRCUIT.
EXIT LIGHTING FIXTURE, ARROWS AS INDICATED.
A a
NOTE:
ALL SYMBOLS AND ABBREVIATIONS ARE SUBJECT TO
MODIFICATIONS ON OTHER DRAWINGS.
ALL SYMBOLS OR ABBREVIATIONS MIGHT NOT
NECESSARILY BE USED ON THIS PROJECT.
FIRE ALARM SYMBOLS
FIRE ALARM BELL & SIGNAL LIGHT (88" AFF). # WHEN SHOWN INDICATES CANDELA RATING OF STROBE. WHEN A # IS NOT SHOWN, THE STROBE SHALL BE RATED 15 CANDELA IN CORRIDORS AND 30 CANDELA FOR ALL OTHER LOCATIONS.
FIRE ALARM SPEAKER & SIGNAL LIGHT (88" AFF). # WHEN SHOWN INDICATES CANDELA RATING OF STROBE. WHEN A # IS NOT SHOWN, THE STROBE SHALL BE RATED 15 CANDELA IN CORRIDORS AND 30 CANDELA FOR ALL OTHER LOCATIONS.
FIRE ALARM CHIME & SIGNAL LIGHT (88" AFF). # WHEN SHOWN INDICATES CANDELA RATING OF STROBE. WHEN A # IS NOT SHOWN, THE STROBE SHALL BE RATED 15 CANDELA IN CORRIDORS AND 30 CANDELA FOR ALL OTHER LOCATIONS.
FIRE ALARM HORN & SIGNAL LIGHT (88" AFF). # WHEN SHOWN INDICATES CANDELA RATING OF STROBE. WHEN A # IS NOT SHOWN, THE STROBE SHALL BE RATED 15 CANDELA IN CORRIDORS AND 30 CANDELA FOR ALL OTHER LOCATIONS.
FIRE ALARM SIGNAL LIGHT (88" AFF). # WHEN SHOWN INDICATES CANDELA RATING OF STROBE. WHEN A # IS NOT SHOWN, THE STROBE SHALL BE RATED 15 CANDELA IN CORRIDORS AND 30 CANDELA FOR ALL OTHER LOCATIONS.
CEILING MOUNTED FIRE ALARM SPEAKER.
FIRE ALARM CONTROL PANEL.
CEILING MOUNTED FIRE ALARM SPEAKER & SIGNAL LIGHT. # WHEN SHOWN INDICATES CANDELA RATING OF STROBE.
WHEN A # IS NOT SHOWN, THE STROBE SHALL BE RATED 15 CANDELA IN CORRIDORS AND 30 CANDELA FOR ALL OTHER
LOCATIONS.
FIRE ALARM MANUAL STATION (46" MH UNLESS NOTED OTHERWISE). SUBSCRIPT "K" INDICATES KEY OPERATED.
CEILING MOUNTED SMOKE DETECTOR.
CEILING MOUNTED HEAT DETECTOR.
DUCT MOUNTED SMOKE DETECTOR. SUBSCRIPT "S" INDICATES SUPPLY. SUBSCRIPT "R" INDICATES RETURN.
DUCT MOUNTED HEAT DETECTOR. SUBSCRIPT "S" INDICATES SUPPLY. SUBSCRIPT "R" INDICATES RETURN.
ELECTRIC RELEASE DOOR CLOSER.
ELECTRO-MAGNETIC DOOR HOLDER.
WATER FLOW SWITCH.
VALVE SUPERVISORY SWITCH.
CEILING MOUNTED REMOTE TEST STATION AND ALARM INDICATOR LIGHT FOR DUCT DETECTOR. SUBSCRIPT "W" INDICATES
WALL MOUNTED.
SMOKE DAMPER.
FIRE FIGHTER'S TELEPHONE (60" MH UNLESS NOTED OTHERWISE).
PRESSURE SWITCH.
ADDRESSABLE MODULE. SUBSCRIPT "I" INDICATES INPUT. SUBSCRIPT "C" INDICATES CONTROL.
POST INDICATOR VALVE.
KNOX BOX (46" MH UNLESS NOTED OTHERWISE). SUBSCRIPT "S" INDICATES SUPERVISED UNIT.
FIRE ALARM BELL (88" AFF UNLESS NOTED OTHERWISE). SUBSCRIPT "W" INDICATES EXTERIOR WEATHERPROOF UNIT.
BEAM DETECTOR. SUBSCRIPT "T" INDICATES TRANSMITTER FUNCTION. SUBSCRIPT "R" INDICATES RECEIVER FUNCTION.
AIR SAMPLING SMOKE DETECTOR SAMPLING PORT.
REMOTE ANNUNCIATOR PANEL.
NOTIFICATION APPLIANCE CIRCUIT EXTENDER PANEL.
AIR SAMPLING SMOKE DETECTOR BASE UNIT.
SURFACE MOUNTED FIRE ALARM SPEAKER (88" AFF). SUBSCRIPT "R" INDICATES RECESSED MOUNTING.
DETAIL: B = DETAIL DESIGNATION
E2 = SHEET WHERE DETAIL IS LOCATED
SECTION: 1 = SECTION DESIGNATION
E2 = SHEET WHERE SECTION IS LOCATED
PLAN NOTE. APPLIES ONLY TO THE SHEET WHICH IT IS SHOWN.
DETAIL NOTE. APPLIES ONLY TO THE ASSOCIATED DETAIL.
GENERAL FLOOR PLAN NOTES
WIRE & CONDUIT IN WALL OR ABOVE CEILING.
WIRE & CONDUIT IN OR BELOW SLAB OR GRADE.
EACH ARROWHEAD REPRESENTS ONE COMPLETE CIRCUIT; "X" DENOTES PANEL NAME; NUMBER(S)
DENOTES CIRCUIT(S).
LADDER TRAY, 12" x 4" DEEP UNLESS NOTED OTHERWISE.
CONDUIT FOR DATA CIRCUITRY.DAT
WIRE & CONDUIT FOR FIRE ALARM CIRCUITRY.FA
WIRE & CONDUIT FOR NURSE CALL CIRCUITRY.NC
EXISTING WIRE & CONDUIT TO REMAIN.EX
CONDUIT TO BE REMOVED.
WIRE & CONDUIT FOR NIGHT LIGHT CIRCUITRY.NL
CONDUIT FOR PHONE CIRCUITRY.PHO
WIRE & CONDUIT FOR SECURITY SYSTEM CIRCUITRY.SEC
WIRE RUN IN SURFACE WIREWAY.W
CABLE MANAGEMENT SYSTEM PATHWAY.CM
X - 1,2
WIRE & CONDUIT FOR EMERGENCY CIRCUITRY.EM
WIRE & CONDUIT FOR SOUND SYSTEM CIRCUITRY.S
WIRE & CONDUIT FOR INTERCOM SYSTEM CIRCUITRY.I
WIRE & CONDUIT FOR TELEVISION SYSTEM CIRCUITRY.TV
CABLE TRAY, 12" x 4" DEEP UNLESS NOTED OTHERWISE.
4"
4"
4"
T2 1 ELEVATION: 1 = ELEVATION DESIGNATION
T2 = SHEET WHERE ELEVATION IS LOCATED
RAP
NAC
ASSD
F W
S F
S R
A
B T/R
CEILING MOUNTED FIRE ALARM SIGNAL LIGHT. # WHEN SHOWN INDICATES CANDELA RATING OF STROBE. WHEN A # IS NOT SHOWN, THE STROBE SHALL BE RATED 15 CANDELA IN CORRIDORS AND 30 CANDELA FOR ALL OTHER LOCATIONS.
F
LIGHTING CONTROL DETAIL NOTE. APPLIES TO THE LIGHTING CONTROL SEQUENCE OF OPERATIONS
SCHEDULE FOR ROOM CONTROL.
3 DEVICE QUANTITY - POWER NOTE. REFER TO DEVICE QUANTITIES - POWER SCHEDULE.
CEILING MOUNTED FIRE ALARM HORN & SIGNAL LIGHT. # WHEN SHOWN INDICATES CANDELA RATING OF STROBE. WHEN A # IS NOT SHOWN, THE STROBE SHALL BE RATED 15 CANDELA IN CORRIDORS AND 30 CANDELA FOR ALL OTHER LOCATIONS.
F
ELECTRICAL SYMBOLS
EXISTING OUTLET OR DEVICE TO REMAIN. MAINTAIN EXISTING CIRCUITING.
DASH SYMBOL INDICATES PARTICULAR OUTLET OR DEVICE TO BE REMOVED AND CIRCUITRY MADE CONTINUOUS WHERE
REQUIRED.
ELECTRICAL CONNECTION.
20A-125V SINGLE RECEPTACLE, NEMA 5-20R (18" MH UNLESS NOTED OTHERWISE).
SPECIAL PURPOSE RECEPTACLE. REFER TO NOTE ON PLAN.
20A-125V DOUBLE DUPLEX RECEPTACLE. NEMA 5-20R, (18" MH UNLESS NOTED OTHERWISE) TWO GANG ASSEMBLY.
20A-125V DUPLEX RECEPTACLE, NEMA 5-20R WITH BOTTOM OUTLET CONTROLLED BY WALL SWITCH. (18" MH UNLESS
NOTED OTHERWISE).
20A-125V DUPLEX RECEPTACLE, NEMA 5-20R, WITH GROUND FAULT CIRCUIT INTERRUPTER (18" MH UNLESS NOTED
OTHERWISE).
20A-125V WEATHERPROOF DUPLEX RECEPTACLE, NEMA 5-20R (HORIZONTAL 18" MH UNLESS NOTED OTHERWISE) WITH
TAYMAC #MM420G EXTRA DUTY GRAY COVER, VERTICAL MOUNT.
20A-125V WEATHERPROOF DUPLEX RECEPTACLE, NEMA 5-20R WITH GROUND FAULT CIRCUIT INTERRUPTER (18" MH UNLESS NOTED OTHERWISE), WITH TAYMAC #MM420G EXTRA DUTY GRAY COVER, VERTICAL MOUNT.
20A-125V POWERLOCK GROUNDING TYPE RECEPTACLE, HOSPITAL USE (66" MH UNLESS NOTED OTHERWISE).
20A-125V DUPLEX PEDESTAL TYPE FLOOR RECEPTACLE, NEMA 5-20R, IN HUBBELL BA-2527 FLOOR BOX WITH SA-2525
COVERPLATE AND SC-3091 HOUSING. PROVIDE CARPET FLANGE WHERE REQUIRED.
20-125V DUPLEX RECEPTACLE, NEMA 5-20R, WITH ISOLATED GROUND (18" MH UNLESS NOTED OTHERWISE).
20A-125/250V-1PH-4W SINGLE RECEPTACLE, NEMA 14-20R (18" MH UNLESS NOTED OTHERWISE).
30A-125/250V-1PH-4W SINGLE RECEPTACLE, NEMA 14-30R (18" MH UNLESS NOTED OTHERWISE).
50A-125/250V-1PH-4W SINGLE RECEPTACLE, NEMA 14-50R (18" MH UNLESS NOTED OTHERWISE).
20A-250V-3PH-4W SINGLE RECEPTACLE, NEMA 15-20R (18" MH UNLESS NOTED OTHERWISE).
30A-250V-3PH-4W SINGLE RECEPTACLE, NEMA 15-30R (18" MH UNLESS NOTED OTHERWISE).
50A-250V-3PH-4W SINGLE RECEPTACLE, NEMA 15-50R (18" MH UNLESS NOTED OTHERWISE).
JUNCTION BOX. SQUARE DEVICE INDICATES A CONNECTION TO CRITICAL POWER.
MULTI-OUTLET RECEPTACLES ASSEMBLY, NEMA 5-15R (SINGLE OUTLETS ON 18" CENTERS) (46" MH UNLESS NOTED
OTHERWISE).
CLOCK HANGER OUTLET, SINGLE NEMA 5-15R RECESSED IN COVER PLATE (84" MH UNLESS NOTED OTHERWISE).
SINGLE POLE SWITCH (46" MH UNLESS NOTED OTHERWISE).
TWO POLE WALL SWITCH (46" MH UNLESS NOTED OTHERWISE).
MULTI-WAY WALL SWITCH, # INDICATES NUMBER OF WAYS (46" MH UNLESS NOTED OTHERWISE).
SWITCH WITH NEON PILOT LIGHT. ONE-GANG ASSEMBLY (46" MH UNLESS NOTED OTHERWISE).
KEY OPERATED WALL SWITCH (46" MH UNLESS NOTED OTHERWISE).
LIGHTING DIMMER SWITCH (46" MH UNLESS NOTED OTHERWISE) 1000 WATTS UNLESS OTHERWISE INDICATED.
SWITCH WITH RECEPTACLE (46" MH UNLESS NOTED OTHERWISE) STANDARD TWO-GANG ASSEMBLY OF SWITCH AND
RECEPTACLE.
FLUSH FRACTIONAL HORSEPOWER MOTOR STARTER WITH NEON PILOT LIGHT. ONE-GANG ASSEMBLY (46" MH UNLESS
NOTED OTHERWISE).
HP RATED WALL SWITCH (46" MH UNLESS NOTED OTHERWISE).
DISCONNECT SWITCH.
MOTOR STARTER.
COMBINATION MOTOR STARTER AND DISCONNECT SWITCH.
ELECTRIC MOTOR.
ELECTRICAL PANEL OR SWITCHBOARD PER DRAWINGS.
PULL BOX.
LINE VOLTAGE THERMOSTAT.
UNIT HEATER.
FAN COIL.
ELECTRIC BASEBOARD HEATER.
AIR CONDITIONER.
CONDENSING UNIT.
UNIT VENTILATOR.
CORD REEL.
POWER POLE.
PHOTOELECTRIC SENSOR.
LIGHTING CONTACTOR.
CEILING MOUNTED OCCUPANCY SENSOR.
WALL MOUNTED OCCUPANCY SENSOR.
CEILING MOUNTED DAYLIGHT SENSOR.
OCCUPANCY SENSOR POWER PACK.
PUSHBUTTON (46" MH UNLESS NOTED OTHERWISE) EDWARDS 852 (120 VOLT).
BUZZER (90" MH UNLESS NOTED OTHERWISE) EDWARDS 340-A (120 VOLT).
4" DIAMETER (90" MH UNLESS NOTED OTHERWISE) EDWARDS "ADAPTABEL" (120 VOLT).
GF
WP
WP/GF
T
IG
20A
30A
50A
20A
50A
30A
J
P
K
DM
R
H
UH
FC
AC
CU
UV
PP
OS
OS
DS
OP
PC
T
B
20A-125V DUPLEX RECEPTACLE, NEMA 5-20R (46" MH UNLESS NOTED OTHERWISE).
C
M
CR
LC
P/B
ELAPSED TIME INDICATOR CLOCK (90" MH UNLESS NOTED OTHERWISE) WITH RESET SWITCH (46" MH UNLESS NOTED
OTHERWISE).
INTERCOM SYSTEM DESK MOUNTED MASTER CONTROL STATION. SUBSCRIPT "W" INDICATES WALL MOUNT (46" MH
UNLESS NOTED OTHERWISE).
INTERCOM STAFF STATION (46" MH UNLESS NOTED OTHERWISE).
INTERCOM HORN TYPE SPEAKER (84" MH UNLESS NOTED OTHERWISE).
INTERCOM SPEAKER FLUSH MOUNT IN CEILING.
I
M
H
S
DUCT HEATER.H
DH
H
EB
LOW-VOLTAGE MOMENTARY WALL SWITCH (46" MH UNLESS NOTED OTHERWISE).
L
WIREMOLD RACEWAY, AS NOTED ON PLANS.
20A-125V DUPLEX RECEPTACLE, NEMA 5-20R WITH 2 INTEGRAL USB CHARGERS (18" MH UNLESS NOTED OTHERWISE).
SQUARE DEVICE INDICATES A CONNECTION TO CRITICAL POWER. SPECIFICATION IS SAME AS RESPECTIVE ROUND DEVICE.
J
20A-125V DUPLEX RECEPTACLE, NEMA 5-20R, IN HUBBELL BA-2527 FLUSH FLOOR BOX WITH ROUND SA-3925 COVERPLATE.
PROVIDE CARPET FLANGE WHERE REQUIRED.
20A-125V DUPLEX RECEPTACLE, NEMA 5-20R (18" MH UNLESS NOTED OTHERWISE). WHEN SHOWN, RECEPTACLE TO HAVE
"CONTROLLED" MARKINGS.
CEILING MOUNTED VACANCY SENSOR.
WALL MOUNTED VACANCY SENSOR.
VS
VS
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Date:Revisions:No.
PROJECT NO.
A u to d e s k D o c s /M t H o m e V
A
R e s to ra ti o n o f B
T h e a te r/
-0
-M
E P
-C e n tr a l.
rv t
/1 /2
:1
:4
P M
E001
ABBREVIATIONS, LEGEND &
GENERAL NOTES
07/01/2025 MSG SAP
RESTORATION OF BUILDING 35
HISTORIC THEATER
621-24-103
MT. HOME, TENNESSEE
BID DOCUMENTS
JAMES H.
QUILLEN VA
MEDICAL
CENTER
Approved: VAMC
2024-05141
1. ALL WORK SHALL COMPLY WITH THE LATEST NFPA 101 LIFE SAFETY CODE, INTERNATIONAL BUILDING CODES,AND OTHER CODES AS IDENTIFIED IN VA PROGRAM GUIDE PG-18-3, TOPIC 01, CODES, STANDARDS AND EXECUTIVE ORDERS WHICH CAN BE FOUND ON THE DEPARTMENT OF VETERAN AFFAIRS, TECHNICAL
INFORMATION LIBRARY WEBSITE.
2. ALL WORK SHALL COMPLY WITH REQUIREMENTS OF THE LATEST ARCHITECTURAL BARRIERS ACT ACCESSIBILITY STANDARD (ABAAS) AND DEPARTMENT OF VETERANS AFFAIRS BARRIER FREE DESIGN GUIDE PG-18-13 WHICH CAN BE FOUND ON THE DEPARTMENT OF VETERANS AFFAIRS TECHNICAL INFORMATION LIBRARY WEBSITE.
3. CONTRACTOR IS RESPONSIBLE TO REPAIR AND/OR REFINISH, TO MATCH ADJACENT EXISTING SURFACES, ANY EXISTING MATERIALS TO REMAIN THAT ARE DAMAGED DURING THE COURSE OF DEMOLITION OR NEW WORK.
4. WHERE REMOVAL OF EXISTING WORK IS REQUIRED FOR INSTALLATION OF NEW WORK, CONTRACTOR SHALL REPAIR EXISTING CONSTRUCTION TO REMAIN OR PROVIDE NEW CONSTRUCTION TO MATCH EXISTING ADJACENT
SURFACES TO REMAIN.
5. CONTRACTOR IS RESPONSIBLE TO FIELD VERIFY ALL CONDITIONS AND DIMENSIONS PRIOR TO ORDERING, FABRICATING OR INSTALLING NEW MATERIALS.
6. CONTRACTOR IS RESPONSIBLE TO VERIFY SIZES OF ALL EQUIPMENT, ETC. TO BE INSTALLED AS PART OF THIS PROJECT, AND WHERE NECESSARY, MAKE SPECIAL PROVISIONS TO INSTALL EQUIPMENT THAT IS TOO LARGE TO
FIT THROUGH FINISHED OPENINGS.
7. CONTRACTOR SHALL PROVIDE COMPLETE AND FULLY OPERATIONAL SYSTEMS WHICH COMPLY WITH STATED CODES AND REGULATIONS. WHERE THE OMISSION OF A PART OR ELEMENT OF A SYSTEM WOULD RESULT IN THE NON-OPERATION, OR INCORRECT OPERATION OF A SYSTEM, CONTRACTOR SHALL INCLUDE SAID PART OR
ELEMENT AS PART OF THE WORK.
8. ALL PENETRATIONS THROUGH NEW AND/OR EXISTING SMOKE OR FIRE RATED WALLS SHALL BE SMOKE/FIRESTOPPED AS REQUIRED BY THE RATING OF THE WALL. WHERE CONDUIT IS REMOVED THROUGH
RATED WALLS, SMOKE/FIRESTOP PENETRATION.
9. FIRESTOP ALL FLOOR PENETRATIONS AT THE END OF EACH WORKING SHIFT.
10. CONTRACTOR SHALL ENGAGE A SUB-SURFACE UTILITY MARKING COMPANY TO LOCATE ALL UNDERGROUND
LINES PRIOR TO EXCAVATION.
11. REMOVAL OF ELECTRICAL ITEMS SHALL INCLUDE REMOVALS BACK TO THE EXISTING ELECTRICAL DISTRIBUTION
CENTER, PANEL OR LAST ACTIVE OUTLET, FIXTURE OR DEVICE REMAINING.
12. ALL CONDUIT AND WIRING LOCATED INSIDE DEMO WALLS SHALL BE RE-ROUTED TO ENSURE A COMPLETE AND
FUNCTIONAL SYSTEM WHILE ACCOMMODATING THE WALL REMOVAL.
13. ALL ABANDONED EXTRANEOUS CONDUITS, SUPPORTS, CONTROLS, ETC. SHALL BE REMOVED.
14. REMOVALS OF RECEPTACLES, TELEPHONE, DATA OUTLETS, ETC. INCLUDE REMOVAL OF THE DEVICE, BACKBOX, CONDUIT, WIRING, ETC.
15. ALL EXISTING FLUORESCENT LAMPS AND BALLASTS REMOVED ARE TO BE PUT INTO CONTAINERS AND DISPOSED
OF BY A QUALIFIED PARTY AT AN APPROVED DISPOSAL FACILITY.
16. ALL ELECTRICAL DEVICES, LIGHTING FIXTURES, RECEPTACLES, SPEAKERS, MISCELLANEOUS EQUIPMENT, JUNCTION BOXES, WIRE, CONDUITS, ETC. WITHIN THE RENOVATION AREAS ARE TO BE REMOVED UNLESS
OTHERWISE INDICATED.
17. ALL EXISTING CONDUIT, EQUIPMENT, CONTROLS, ETC. SHOWN DASHED SHALL BE REMOVED. THE MAJORITY OF ELECTRICAL WORK TO BE REMOVED IS SHOWN. REMOVE ALL INCIDENTAL ITEMS ASSOCIATED WITH THE
DEMOLITION WORK.
18. ALL EXISTING FIRE ALARM EQUIPMENT AND DEVICES SHALL BE REMOVED AS NOTED. CONTRACTOR SHALL SALVAGE EQUIPMENT AS DIRECTED BY THE COR AND STORE IN A LOCATION DESIGNATED BY THE COR. ALL OTHER EQUIPMENT AND DEVICES NOT SALVAGED SHALL BE REMOVED AS DIRECTED FROM THE PREMISE.
19. CONTRACTOR SHALL COORDINATE WITH THE COR IN REGARD TO REMOVALS. CONTRACTOR SHALL SALVAGE EQUIPMENT AS DIRECTED BY THE OWNER AND STORE IN A LOCATION DESIGNATED BY THE COR. ALL OTHER
EQUIPMENT AND MATERIALS NOT SALVAGED SHALL BE REMOVED FROM THE PREMISE.
20. WHERE EQUIPMENT IS SHOWN TO BE REMOVED, DISCONNECT ELECTRICAL SOURCE TO EQUIPMENT AND
REMOVE FEEDER BACK TO SOURCE.
21. THE EXISTING THEATER SPACE WILL BE RENOVATED UNDER THIS CONTRACT; REFER TO ARCHITECTURAL DRAWINGS FOR AREAS WHERE NEW WORK RENOVATIONS WILL OCCUR, REMOVE (AND RELOCATE AS REQUIRED) ANY EXISTING ELECTRICAL PATHWAYS AND/OR UTILITIES ASSOCIATED WITH DIVISION 26, 27, AND 28
TO ACCOMMODATE ALL NEW CONSTRUCTION IN THESE AREAS.
22. ALL EQUIPMENT, LIGHT FIXTURES, CONDUIT, CONDUCTORS, FIRE ALARM WIRING, AND ANY OTHER ELECTRICAL RELATED EQUIPMENT BEING MOUNTED IN THE CEILING OR ABOVE THE CEILING SHALL BE PLENUM RATED.
23. CLOSELY COORDINATE ALL NEW WORK ABOVE CEILING WITH H.C. AND P.C. PRIOR TO ROUGH-IN TO
ACCOMMODATE ALL NEW DUCT WORK AND PLUMBING. IF REQUIRED, RELOCATE ANY EXISTING
CONDUIT/BRANCH CIRCUITS TO ACCOMMODATE HVAC AND PLUMBING.
24. PROVIDE EXTERIOR MOUNTED…