Atch 28 AMEND_3 _ Q10.07_FX101 - BASEMENT -1st FLOOR.pdf

PDF 977 KB Posted

Attached to
Y1QA--Project 621-24-103 Restoration of B35 Theater
Solicitation number
36C24926R0055
Issued by

About this file

This document is a set of architectural and mechanical/electrical/plumbing (MEP) construction drawings for the Restoration of Building 35 Theater at James H. Quillen VA Medical Center in Mountain Home, Tennessee. The drawings are designated as 100% Construction Documents dated May 30, 2025, and are prepared by the consulting firm FFF Architects and Heavey Engineering as the Architect/Engineer of Record.

The drawings depict basement and first floor new work plans for a fully sprinklered theater facility. Key fire suppression and mechanical systems shown include: dry-pipe risers serving building sprinklers, wet standpipe risers serving hose stations and fire department connections (FDC), a nitrogen generator with integral air compressor (skid-mounted, PGEN-20 basis of design or equal, 20-gallon capacity, 2 PH 208VAC/3 PH 60Hz and 120VAC/1PH 60Hz electrical requirements), double check detector assemblies, fire service backflow prevention equipment, and coordinated electrical requirements referenced to Division 26. The facility includes auditorium spaces, stage areas, dressing rooms, mechanical/electrical rooms, an IT closet, and support spaces. Architectural details specify firestop materials and methods for penetrations of fire-rated membranes in accordance with Specifications Section 07 84 00. The drawings indicate that all loose components must be installed and that electrical requirements for the nitrogen plant compressor must be coordinated with Division 26 contractors.

View the file

Other files

File Type Posted
Atch 40 AMEND_4 SCA WD 2015-4641.pdf PDF
Atch 39 AMEND_4 Davis-Bacon WD TN20260191.pdf PDF
S02 AMEND_36C24926R0055 0004 B35.pdf PDF
Atch 26 AMEND_3 _10.06_FS100 - SITE PLAN.pdf PDF
Atch 23 AMEND_3 _ 10_32 17 23 - PAVEMENT MARKINGS.pdf PDF
Atch 21 AMEND_3 _09 93 00 Staining - Transparent Finish.pdf PDF
Atch 31 AMEND_3 _ 10.09_FX103 - AUDITORIUM ATTIC- STAGE NEW WORK.pdf PDF
Atch 22 AMEND_3 _ 10_32 12 16 - ASPHALT PAVING.pdf PDF
Atch 20 AMEND_3 _ 09 01 90.52 - Maintenance Repainting.pdf PDF
S02 AMEND_36C24926R0055 0003 B35.pdf PDF
Atch 35 AMEND_3 Worksheet - S ENG AUTOCAD AUTOCADPUBLIC PDC PROJ 7.xlsx XLSX spreadsheet
Atch 36 AMEND_3 Section 01 45 00 Quality Control.docx DOCX document
Atch 17 AMEND_3 Updated Solicitation 36C24926R0055.pdf PDF
Atch 33 AMEND_3 QUES 186 _doc11604520260625102926.pdf PDF
Atch 34 AMEND_3 Section 01 45 35 Schedule of Special Inspections.docx DOCX document
Atch 38 AMEND_3 VA Mtn Home El Walkway_Geotech Rpt.pdf PDF
Atch 24 AMEND_3 _ 10-10_32 90 00 PLANTING.pdf PDF
Atch 19 AMEND_3 _ 00 01 10 - SPECS - Table Of Contents.pdf PDF
Atch 29 AMEND_3 _ 10.07_FX101 - BASEMENT- 1st FLOOR NEW WORK PLAN.pdf PDF
Atch 30 AMEND_3 _ 10.08_FX102 - BALCONY 2nd FLOOR - CEILING.pdf PDF
Atch 32 AMEND_3 _ 210.05_FD901-WET-PIPE FIRE SUPPRESSION ISOMETRIC.pdf PDF
Atch 25 AMEND_3 _ Limited HazMat Report.pdf PDF
Atch 27 AMEND_3_10.06_FS100 - FIRE SUPPRESSION SITE PLAN.pdf PDF
Atch 37 AMEND_3 Past Performance Questionnaire -PPQ Template.docx DOCX document
Atch 18 AMEND_3 FINISH REVISIONS_ Rev 2 06-30-2026.pdf PDF
S02 AMEND_36C24926R0055 0002 B35.pdf PDF
Atch AMEND_1 Site Visit Attendance Sheet of 621-24-103.pdf PDF
S02 AMEND_36C24926R0055 0001 B35.pdf PDF
S02 SOL 36C24926R0055_1 B35 _ R2.pdf PDF
Atch 16 WD TN20260191 01.02.2026.docx DOCX document
Atch 5_BID SPEC ENG_4288 SUBMITTAL REG.pdf PDF
Atch 14 General Conditions Breakout.xlsx XLSX spreadsheet
36C24926R0055_1.docx DOCX document
Atch 3_BID SPEC App1_B35 HazMat Report.pdf PDF
Atch 12 Calc. of Self Performed Work.xlsx XLSX spreadsheet
Atch 9_621-24-103 Drawing part 4 of 6.pdf PDF
Atch 2_BID MAppE_B35 Existing Conditions.pdf PDF
Atch 1_BID SPECIFICATIONS-1.pdf PDF
Atch 4_BID SPEC App2_B35 Historic SHPO.pdf PDF
Atch 13 Contractor EMR Certification Form.docx DOCX document
Atch 6_621-24-103 drawing part 1 of 6.pdf PDF
Atch 11_621-24-103 Drawing part 6 of 6.pdf PDF
Atch 8_621-24-103 drawing part 3 of 6.pdf PDF
Atch 15 WD TN20260191 01.02.2026.docx DOCX document
Atch 7_621-24-103 drawing part 2 of 6.pdf PDF
Atch 10_621-24-103 Drawing part 5 of 6.pdf PDF
Atch 15 Price Breakout Schedule.xlsx XLSX spreadsheet
Show all 47

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

B F

P

FS

MECH/ELEC

ROOM

ELECTRICAL

ROOM

MECH/ELEC

ROOM

MECH/ELEC

ROOM

OH

OH

OH

OH

4" UP TO FDC

1 1

UNEXCAVATEDUNEXCAVATED

A

F501

OH

003A

IT CLOSET

NP-1

DPV

F201

DRY-PIPE RISER .

SERVES SPRINKLERS BELOW

CATWALK AND STAIRS.

F201

WET STANDPIPE RISER.

SERVES HOSE STATION

AND FDV'S.

WET STANDPIPE RISER.

SERVES HOSE STATION

AND FDV'S.

S

DRY-PIPE RISER .

SERVES BUILDING SPRINKLERS.

WOMEN'S

MEN'S

BOOTH

101B

BOOTH

101D

STORAGE

CORRIDOR

TOILET

TOILET

DRESSING

ROOM

LOBBY

AUDITORIUM

STAGE

FAMILY TOILET

110A

FAMILY TOILET

111A FDC

OH

OH

OH

OH

1 1

OH

OH

7MECHANICAL

111B

MECHANICAL

110B

ORCHESTRA PIT

CORRIDOR

101C

RELOCATED

SPRINKLER

RISER

STAIRS REMOVED

FOR CLARITY

STAIRS REMOVED

FOR CLARITY

STAIRS REMOVED

FOR CLARITY

JANITOR

DRESSING

ROOM

WET STANDPIPE UP.

SERVES FDV

ABOVE CATWALK.

DRY-PIPE RISER .

DRY-PIPE RISER.

SERVES SECOND FLOOR

BACK OF HOUSE

DRY-PIPE RISER.

SERVES BELOW CATWALK,

AUDITORIUM ATTIC SPACE,

BELOW STAGE ATTIC AND

STAGE ATTIC.

STANDPIPE UP.

SERVES FDV

ABOVE CATWALK

DN

F201

F201

GENERAL NOTES

A. REFER TO SHEET F001 FOR ABBREVIATIONS, LEGEND & DESIGN NOTES.

B. UTILIZE EXISTING SPRINKLER LOCATIONS WHERE POSSIBLE IN AUDITORIUM AND LOBBY CEILINGS.

C. FOLLOW EXISTING EXPOSED BRANCH AND MAIN PIPE ROUTING IN AUDITORIUM AND LOBBY.

D. EXPOSED PIPING SHALL MATCH ADJACENT PAINTED SURFACES.

E. SPRINKLER PIPING TO BE ROUTED IN CEILING WHERE CEILING SPACE ALLOWS. ( ROOMS 110, 110A, 111, 111A,104, 105, 106, 108 & 109.)

F. UTILIZE EXISTING TEST LOCATIONS AND DRAIN ROUTING.

S

FD

S

FLOORNITROGEN PLANT

WITH INTEGRAL COMPRESSOR

COORDINATE ELECTRICAL

REQUIREMENTS WITH DIVISION 26

DRAIN LINE

AUX DRAIN

DRIP CUP ASSEMBLY

ALARM PRESSURE

WATER FLOW SWITCH

DRY PIPE VALVE

ASSEMBLY COMPLETE

WITH ALL ACCESSORIES

ALARM PRESSURE CONDUIT

AND SIGNAL WIRING TO

CENTRAL ALARM PANEL

TO DRY PIPE

SPRINKLER SYSTEM

FROM FIRE MAIN

DISCONNECT AND

STARTER

AIR MAINTENANCE

DEVICE

UTILIZE EXISTING DRAIN

ROUTING.

DISCHARGE

TO FLOOR

DRAIN OR

BASIN

AIR PRESSURE

SUPERVISORY SWITCH

LOW AIR PRESSURE CONDUIT

AND SIGNAL WIRING TO

CENTRAL ALARM PANEL

MOUNT TO

BACK WALL

TO FDC

1. PRE-MANUFACTURED DRUM DRIP ASSEMBLIES MAY BE

USED IN LIEU OF INDIVIDUAL COMPONENTS.

2. FOLLOW EXISTING DRAIN ROUTING.

NOTES

1" VALVE

2x1 CONCENTRIC

REDUCER

2x12" NIPPLE

2x1 CONCENTRIC

REDUCER

1" VALVE

1" PLUG

1" REMOVABLE PIPE

SECTION

1" UNION

END SPRINKLER

LINE

1" PIPING

1" TIE IN DRAIN

CONNECTING

3 LINES TOGETHER

DRAIN TO SUITABLE LOCATION

6" [1 m m

1" [2

5m m

6" [1 m m

INSULATE

PIPE OR DUCT

PIPE SLEEVE

WHERE SPECIFIED

FLOOR

WELD

1/4" [6.4mm]

ANCHOR ROD FOR

NEW CONSTRUCTION

FIRESTOP MATERIAL

3/4" [19mm]

APPROVED FIRESTOP

INSULATION WITH

VAPOR BARRIER

3/4" [19mm] APPROVED

FIRESTOP INSULATION WITH

VAPOR BARRIER 6"

[150mm]

MASONRY

PARTITION INSULATED

PIPE OR

DUCT

6" [150mm]

FIRESTOP

MATERIAL

DRYWALL PARTITION

PARTITION SUPPORT

FLOOR OR DECK PENETRATION

6" [150mm]

6" [150mm]

PARTITION OR CHASE PENETRATION

NOTE:

1. APPLICABLE TO PENETRATIONS OF ALL FIRE RATED MEMBRANES,IN ACCORDANCE WITH NFPA 101.

REFER TO SPECIFICATIONS SECTION 07 84 00, FIRE STOPPING SYSTEMS.

2. REFER TO ARCHITECTURAL DRAWINGS FOR RATED WALLS.

TO DRY-PIPE SYSTEM

PRESSURE GAUGE

DOUBLE CHECK DETECTOR

ASSEMBLY

STRAINER

REDUCER

6"

FLOOR DRAIN

INCREASER

AIRGAP FITTING

FLOOR

6" FIRE SERVICE

FS

SS

P

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

NOT F

OR C

ONSTRUCTIO

N

Date:Revisions:No.

PROJECT NO.

A u to d e s k D o c s /M t H o m e V

A

R e s to ra ti o n o f B

T h e a te r/

-0

-M

E P

-C e n tr a l.

rv t

/2

/2

:0

:3

P

M

FX101

BASEMENT AND FIRST FLOOR

NEW WORK PLANS

05/30/2025 EWL RLC

RESTORATION OF BUILDING 35

HISTORIC THEATER

621-24-103

MT. HOME, TENNESSEE

100% CONSTRUCTION

DOCUMENTS 35

JAMES H.

QUILLEN VA

MEDICAL

CENTER

Approved: VAMC

2024-05141

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

NOT F

OR C

ONSTRUCTIO

N

Date:Revisions:No.

PROJECT NO.

A u to d e s k D o c s /M t H o m e V

A

R e s to ra ti o n o f B

T h e a te r/

-0

-M

E P

-C e n tr a l.

rv t

/2

/2

:0

:3

P

M

FX101

BASEMENT AND FIRST FLOOR

NEW WORK PLANS

05/30/2025 EWL RLC

RESTORATION OF BUILDING 35

HISTORIC THEATER

621-24-103

MT. HOME, TENNESSEE

100% CONSTRUCTION

DOCUMENTS 35

JAMES H.

QUILLEN VA

MEDICAL

CENTER

Approved: VAMC

2024-05141

PLAN

NORTH

SCALE: 1/8" = 1'-0"

BASEMENT FLOOR PLAN

SCALE: 1/8" = 1'-0"

FIRST FLOOR PLAN

PLAN NOTES

1. PROVIDE NEW DRY-PIPE SPRINKLER SYSTEM (SIZED PER HYDRAULIC CALCULATIONS) COMBINED WITH WET-STANDPIPE SYSTEM

(STAGE AREA ONLY) TO SERVE BUILDING.

2. DRY-PIPE SPRINKLER SYSTEM WITH NITROGEN GENERATOR PLANT. NITROGEN PLANT SHALL COMPLY WITH NFPA STANDARDS AND BE INSTALLED PER MANUFACTURER'S INSTALLATION REQUIREMENTS. WATER TO REACH MOST REMOTE

SPRINKLER WITH-IN 30 SECONDS.

3. PROVIDE DOUBLE CHECK DETECTOR ASSEMBLY ON FIRE SERVICE.

4. ONLY SPRINKLER PIPING SERVING ROOM'S SPRINKLER(S) SHALL BE EXTEND ABOVE THIS ROOM. PIPING SHALL NOT BE LOCATED

DIRECTLY OVER ELECTRICAL EQUIPMENT.

5. PROVIDE NEW FIRE DEPARTMENT CONNECTION.

6. UNEXCAVATED SPACE - SPRINKLERS NOT REQUIRED.

7. HARD CEILING IN THIS LOCATION (GYPSUM BOARD/ PLASTER/ WOOD). REFER TO ARCHITECTURAL DRAWINGS FOR

ADDITIONAL INFORMATION.

8. PROVIDE SEMI-RECESSED SPRINKLERS IN LOBBY RESTROOMS (110, 110A, 111 & 111A)

9. PROVIDE FACTORY COLORED SPRINKLERS IN LOBBY AND AUDITORIUM (SHOP OR FIELD PAINTING IS NOT PERMITTED.). MATCH ADJACENT PAINTED SURFACES. NON-COLORED SPRINKLERS PERMITTED IN ATTIC, RAFTERS, STAGE, BACK-OF-HOUSE, MECHANICAL, ELECTRICAL AND PROJECTION ROOMS.

10. RE-USE EXISTING HOSE STATION/ FDV STANDPIPES AND FIRE RISER LOCATIONS UNLESS OTHERWISE NOTED.

11. ROUTE SPRINKLER PIPING IN CEILING AS SPACE ALLOWS.

12. EXTEND WET-PIPE BRANCHES TO HOSE STATION/ FDV RISERS. SIZED PER HYDRAULIC CALCULATIONS. AREA IS HEAVILY CONGESTED

WITH MECHANICAL EQUIPMENT.

13. DRY-PIPE SYSTEM RISER TO SERVE STAIRS AND BELOW CATWALK. AREA IS HEAVILY CONGESTED WITH MECHANICAL EQUIPMENT.

14. PROVIDE 1.5" HOSE CABINET, 100 FT OF HOSE WITH ADJUSTABLE NOZZLE.

25% SCHEMATIC DESIGN 10/31/2024

75% DESIGN DEVELOPMENT 01/29/2025

95% CONSTRUCTION DOCUMENTS 03/31/2024

100% CONSTRUCTION DOCUMENTS 05/30/2025

25% SCHEMATIC DESIGN 10/31/2024

75% DESIGN DEVELOPMENT 01/29/2025

95% CONSTRUCTION DOCUMENTS 03/31/2024

100% CONSTRUCTION DOCUMENTS 05/30/2025

NTS

A

DRY PIPE VALVE ASSEMBLY WITH NITROGEN PLANT - SCHEMATIC

GENERAL NOTES:

A. INSTALL ALL "LOOSE" COMPONENTS.

FIRE SUPPRESSION EQUIPMENT

MARK DESCRIPTION C

A

P A

C

IT

Y

HP

ELECTRICAL

(VOLTAGE -

PHASE)

WATER

CONNECTIONS

APPROX.

DIMENSIONS

S E

E N

O T

E

IN OUT W

ID

T H

D

IA

L E

N G

T H

H E

IG

H

T

NP-1 NITROGEN GENERATOR W/ AIR

COMPRESSOR, SKID MOUNTED. BASIS OF

DESIGN: PGEN-20 OR EQUAL (208VAC)

GALLON

2 PH 208VAC/3 PH, 60Hz

& 120VAC/ 1PH,

60Hz

- - 32" 40" 57"

NTS

B

DRUM DRIP DRAIN ASSEMBLY

NTS

D

PIPE/ DUCT PENETRATION OF SMOKE/ FIRE BARRIERS

NTS

C

FIRE SERVICE BACKFLOW PREVENTION - SCHEMATIC

Sheets
FX101 - BASEMENT AND FIRST FLOOR NEW WORK PLANS