This announcement is a combined synopsis/solicitation from U.S. Immigration and Customs Enforcement seeking detention and transportation services in three areas of responsibility in California. Services are required for detention facilities to house detainees and for transportation between detention facilities and to and from hearings and removal processing centers. The period of performance is a five year base period and five one-year options. Pricing will be on a firm fixed price basis. The anticipated award date is July 2020. Responses are due by April 2020. Small businesses are encouraged to respond.

Structure Cable Plant Standards

View the file

Other files for this federal contract opportunity

Other files attached to Detention Services for California, newest first.
File Type Posted
Attachment_19_PPQ.doc DOC document
SECTION_B_10252019.docx DOCX document
Solication_Sections_D-M_FINAL_10252019.docx DOCX document
Requirement_B_PWS_Addendum_-_updated_10252019.docx DOCX document
California_Wide_PWS_-_10252019_Final.docx DOCX document
Requirement_A_PWS_Addendum_updated_10252019.docx DOCX document
Solicitation_70CDCR20R00000002_Questions_Part_3.docx DOCX document
Attachment_13-_Cost_and_Pricing_Summary_updated_10252019.docx DOCX document
Attachment_14_ICE_Dedicated_DSCS_OCT252019.xlsx XLSX spreadsheet
Solicitation_RFP_70CDCR20R00000002_Questions_and_ICE_Responses_Part_2.docx DOCX document
Solication_Sections_D-M_10232019.docx DOCX document
RFP_70CDCR20R00000002_Questions_and_Government_Answers_Part_1.pdf PDF
PWS_Addendum_D_CDR_Attachment.docx DOCX document
California_Wide_PWS_-_10222019_FINAL.docx DOCX document
ICE_Dedicated_DSCS_(V-17OCT2019)v.xlsx XLSX spreadsheet
Solicitation_Sections_D-M_Final.docx DOCX document
PWS_Addendum_Requirement_D_Final.docx DOCX document
PWS_Addendum_D_PRS_Attachment_1.docx DOCX document
PPQ.doc DOC document
Requirement_C_PWS_Addendum_Final.docx DOCX document
Addendum_B_ICE_EOIR_Design_Standards.pdf PDF
Solication_Sections_D-M_10_16_2019_.pdf PDF
RFP_Attachment_13-_Cost_and_Pricing_Summary.docx DOCX document
SECTION_B_Final.docx DOCX document
Attachment_17_Franco_settlement-agreement.pdf PDF
Addendum_D1_IHSC_Design_Standards_Supplement.pdf PDF
Zip_1_-_California_PWS_Attachments.zip ZIP file
RFP_Attachment_18_-_Franco-Gonzalez_Health_Form.docx DOCX document
Addendum_D-_Health_Service_Design_Standards_3-11-05_07-12-2019_(002).pdf PDF
Requirement_A_PWS_Addendum.docx DOCX document
Attachment_14A_-_ICE-Dedicated_DSCS_Handbook_vFinal.pdf PDF
Combined_Synopsis_Solicitation_Notice.pdf PDF
Addendum_A_-_ICE_Design_Standards_for_CDFs.pdf PDF
Attachment_14_ICE_Dedicated_Detention_Services_Cost_Statement.xlsx XLSX spreadsheet
Requirement_B_PWS_Addendum.docx DOCX document
Requirement_D_PWS_Addendum.docx DOCX document
RRU_Attachment_15_-_Preparation_of_NEPA_Document_10.16.19.docx DOCX document
RFP_Section_A.pdf PDF
Requirement_C_PWS_Addendum_.docx DOCX document
California_Wide_PWS_-_10162019.pdf PDF
Attachment_16_Lyons_Settlement_Agreement.pdf PDF
Show all 41

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Structured Cable Plant Standard

Version 5.x

Office of Chief Information Officer Network Engineering Branch

Immigration and Customs Enforcement

March 7, 2008 i Structured Cable Plant Standard Version 5.x

CONTENTS

1.0 INTRODUCTION

1.1 Purpose

1.2 Background

1.3 Scope

1.3.1 System

1.3.2 Documentation

2.0 NETWORK CABLE PLANT OBJECTIVES

3.0 STRUCTURED CABLE PLANT DESIGN

3.1 Structured Cable Plant Approach

3.2 Horizontal Workstation Cabling

3.3 Workstation Outlets

3.4 Backbone Cabling

4.0 SPECIFICATIONS

4.1 Horizontal Cables

4.2 Information Management Outlets

4.3 Backbone Cabling

4.3.1 Intra-Building Fiber Optics

4.3.2 Inter-Building Fiber Optics

4.4 Patch Cables (Workstation and Patch Panel)

4.5 Patch Panels

4.6 Equipment Racks

4.7 Cabinets and Swing Gates

5.0 COPPER CABLE INSTALLATION SPECIFICATIONS

5.1 Horizontal Cables

5.2 Patch Cables (Workstation)

5.3 Patch Cables (Rack)

5.4 Copper Cable Termination

6.0 INSTALLATION OF OPTICAL FIBER CABLES AND CONNECTORS

6.1 Fiber Horizontal Workstation Cable

6.2 Backbone Fiber Cable

6.3 Optical Fiber Cable Jacket

6.4 Optical Fiber Connector

6.5 Optical Fiber Cable Termination

7.0 FACEPLATE CONFIGURATION

8.0 PATCH PANELS

8.1 Copper Patch Panels

8.2 Fiber Optic Patch Panels

9.0 EQUIPMENT RACK

10.0 GROUNDING

March 7, 2008 ii Structured Cable Plant Standard Version 5.x

11.0 CABLE LADDERS AND FASTENERS

12.0 ADMINISTRATION AND LABELING CONVENTIONS

12.1 Building Designation

12.1.1 Floor

12.1.2 Wiring Closets

12.1.3 Cable Numbers

12.2 Information Outlet

12.3 Intra and Inter-Building Backbone Cables

12.4 Patch Panel Patch Cables

13.0 TEST AND DOCUMENTATION PROCEDURES

13.1 Testing of Installed Copper Cable

13.2 Testing of Optical Fiber Cables

14.0 BUILDING PATHWAYS, CONDUIT, AND CLOSETS

14.1 Closet Specifications (MDF and RWC)

14.1.1 General Requirements

14.1.2 Environmental

14.1.3 Construction

14.2 Conduits

15.0 DOCUMENTATION

15.1 Letter of Certification

15.2 Implementation Report

15.3 Detailed Materials List

15.4 Copper Cable Test Results

15.5 Fiber-optic backbone Cable Test Results

15.6 As-Built Site Drawings

March 7, 2008 iii Structured Cable Plant Standard Version 5.x

EXHIBITS

Exhibit 1: Typical Office Cable Planning

Exhibit 2: Workstation Faceplate, Single Gang

Exhibit 3: Workstation Faceplate with Optical Fiber Cables

Exhibit 4: Backbone Fiber Distribution

Exhibit 5: Category 6 Cable Specifications

Exhibit 6: T-568B and T-568A Pair/Pin Assignments

Exhibit 7: Typical Single Rack Layout for Smaller Installations

Exhibit 8: Typical Two Rack Layout

Exhibit 9: Typical Three Rack Layout for Larger Installations

Exhibit 10: Multimode Fiber Cable Specifications

Exhibit 11: Singlemode Fiber Cable Specifications

ATTACHMENTS

ATTACHMENT A GLOSSARY

ATTACHMENT B SAMPLE LETTER OF CERTIFICATION

ATTACHMENT C SAMPLE CONTRACTOR INFORMATION FORM

ATTACHMENT D SAMPLE IMPLEMENTATION REPORT

ATTACHMENT E SAMPLE DETAILED MATERIALS LIST

ATTACHMENT F SAMPLE CABLE TEST CERTIFICATION LETTER

ATTACHMENT G SAMPLE CABLE PLANT DATABASE

ATTACHMENT H SAMPLE FIBER CABLE TEST

ATTACHMENT I SAMPLE WIRING CLOSET DETAIL

ATTACHMENT J SAMPLE AS-BUILT DRAWING AND RACK ELEVATION

March 7, 2008 4 Structured Cable Plant Standard Version 5.x

1.0 INTRODUCTION

1.1 Purpose

This document has been prepared for the Immigration and Customs Enforcement (ICE) with the specific purpose of setting standards for structured cable plants in support of Local Area Network (LAN) and voice connectivity that will function as follows:

• Accommodate the functional requirements of present and future information services.

• Support a multi-product and multi-vendor environment.

• Facilitate the planning and installation of cabling systems that will support the diverse communication needs of building occupants.

• Ensure uniformity of structured wiring and hardware infrastructure installations in all ICE facilities.

The primary focus of this document is to define the standards for material, infrastructure, design, installation, and certification with respect to structured cabling systems for ICE facilities. This document shall replace, modify, or otherwise supersede previous releases of these standards. For questions or comments regarding this document, contact the ICE Network Engineering Implementation Section Chief.

An electronic version of this document resides in the ICE Intranet Enterprise Library, available on the Office of Chief Information Officer (OCIO) Web site.

1.2 Background

Immigration and Customs Enforcement (ICE) is a component of the U.S. Department of Homeland Security (DHS). ICE brings a unified and coordinated focus to the enforcement of federal immigration laws, customs laws, and air security laws. ICE brings to bear all of the considerable resources and authorities invested in it to fulfill its primary mission: to detect vulnerabilities and prevent violations that threaten national security.

Because of increasing demands on Service resources, ICE personnel must be able to share information rapidly and efficiently in order to succeed in fulfilling the Service mission.

In addition to this document, which establishes the cabling standards for ICE, other documents are being developed that provide additional related information such as:

• ICE LAN standards.

• ICE Wide Area Network (WAN) standards.

• Voice Communications standards.

1.3 Scope

1.3.1 System

Typical structured cabling systems include the following elements:

• Horizontal cable.

March 7, 2008 5 Structured Cable Plant Standard Version 5.x

• Horizontal cross-connects.

• Transition point (optional).

• Main cross-connect (MC).

• Intermediate cross-connect.

• Backbone cabling, intra and inter.

• Workstation locations or information management outlets (IMO).

• Remote wiring closet (RWC).

• Main distribution frame (MDF).

• Entrance facility (EF).

• Grounding

• Administration

1.3.2 Documentation

This document is intended to address the following specifications and installation practices related to structured cable plant installation:

• Recognized media.

• Closet requirements, environmental and design.

• Distribution cabling.

• Cabling specifications and limits.

• Installation practices.

• Performance testing.

• Supporting documentation.

2.0 NETWORK CABLE PLANT OBJECTIVES

The objective of this network approach is to provide ICE with a standardized, cost-effective cable plant infrastructure that will accommodate present and future voice, video, and data requirements. Workstation cabling infrastructure shall support bandwidth demands from 10 Megabits per second (Mbps) to Gigabit speeds. Backbone cable infrastructure shall support bandwidth demands from Gigabit speeds and beyond. The installation of the cable plant infrastructure shall comply with local codes, as well as, industry and Federal standards.

3.0 STRUCTURED CABLE PLANT DESIGN

The network cable plant shall utilize the following cable distribution methods to support connectivity throughout the building:

• Horizontal workstation cabling, which will connect the user workstation, or information management outlet (IMO) to the nearest Remote Wiring Closet (RWC).

March 7, 2008 6 Structured Cable Plant Standard Version 5.x

• Where appropriate, Intra and Inter-building copper backbone cable, which provides connectivity between wiring centers and the MDF.

• Work zone distribution cabling for open office space.

• Fiber optic intra and inter-building backbone cable, which also provides connectivity between wiring centers and the MDF.

3.1 Structured Cable Plant Approach

This section will describe the approach to structured cabling, identify and describe the various cable types, and provide detailed cable specifications for cable plant installation. These are minimum specifications for new cable plant installations or major renovations. These specifications follow the American National Standards Institute (ANSI)/Telecommunications Industries Association (TIA)/Electronic Industries Association (EIA) recommendations, and in addition, provide specific guidelines unique to ICE. Detailed cable plant material specifications and overall minimum characteristics are provided in Section 4.

3.2 Horizontal Workstation Cabling

All end-user workstation locations, whether occupied or vacant, shall be cabled to the nearest wiring center. Also, storage rooms, conference rooms and similar space not designated as offices shall be cabled to allow for office expansion, as shown in Exhibit 1.

In general, each RWC equipment rack shall be capable of supporting a maximum of 288 data cables. A second rack is required to support up to 288 voice cables, providing a consolidated voice and data closet. The combined racks provide ample space for a total combined 144 workstation locations (voice and data). In smaller installations, typically less than 72 workstation locations, a single equipment rack will suffice for both voice and data termination.

To comply with ANSI/TIA/EIA-568-B.1 specification distance limits, the cable run from any user workstation location to the nearest wiring center shall not exceed 100 meters (328 feet).

The actual length of a cable run is defined as the total combined length of the station cord, workstation cable, and patch-panel cable. When planning or designing office space the communications closets should be located within 90 meters (295feet) of any workstation outlet.

This design approach allows the addition of patch cables and workstation cords to connect devices, without exceeding the ANSI/TIA/EIA-568-B.1 specification distance limits.

In a building not exceeding two stories, horizontal workstation cabling may be installed to a single point, such as a computer room, wiring center, or the MDF. This scenario may be used in place of a creating a RWC, thus eliminating any need for backbone cabling systems. This installation method should be utilized when cost is a constraint and the length of the cable run does not exceed the specified distance limits.

March 7, 2008 7 Structured Cable Plant Standard Version 5.x

Exhibit 1: Typical Office Cable Planning

Public Entrance

Interview Waiting Room

Interview Waiting Room

Office Office

StorageGeneral Storage

Conference Room

Break

ADP

Room

Interview Interview Interview Interview Interview Interview

Clerk

Tele

Stairs

Guard

Employee Entrance

Office Office

Office Office Office

Office

Office areas wired for requirements; i.e., to printers, workstations, convert into office

Each outlet includes 3 cables each, all CAT6, one data, one voice and one aux.; configured per TIA/EIA 568B.

Interview Interview Interview Interview

Interview

All drop locations will be configured with three Category 6, plenum rated cables identified as “A”, “B” and “C”. All cables shall be terminated in the LAN closets on Category 6 compliant Patch Panels. This configuration allows each cable, “A”, “B” or “C”, to be used for either a voice or data device offering maximum flexibility in deploying devices throughout the facility.

Each workstation cable that is routed through a suspended ceiling area shall be secured in a manner that will keep all cable plant off of any suspended ceiling tiles, sprinkler systems, ceiling suspension hangers, and adhere to local and Federal building codes. Cable plant installed in plenum environments should provide enough slack to facilitate minor construction modifications, or cable re-locations, without the need to install new cable altogether. This installation approach normally requires approximately 20 feet of cable slack, secured in an appropriate manner, to ensure cable is minimized from radio frequency interference (RFI) and electro-magnetic interference (EMI) sources. However, installed cable shall at no time exceed the overall specifications for total lobe length of 100 meters in accordance with the ANSI/TIA/EIA standards. If required, an independent suspension system shall be installed for the cable plant, to keep the cables off of and away from the existing ceiling grid and fixtures.

All end-user workstation locations, whether occupied or vacant, shall be cabled to the nearest wiring closet. Every office should have a minimum of two drops installed. Every cubical should

March 7, 2008 8 Structured Cable Plant Standard Version 5.x have a minimum of one drop installed Storage rooms, conference rooms and similar space not designated as offices should be cabled to allow for office expansion.

When routed above a suspended ceiling, horizontal cables should be routed down the inside of walls wherever possible to ensure no exposed cable is visible. If walls cannot be fished, surface mounted (external) raceway may be used to route the cable from the ceiling to the information outlet and installed in a surface-mounted outlet box. All attempts should be made to ensure no horizontal cable is exposed within the building area, providing a neat, professional installation.

Horizontal cables shall never be exposed to outdoor elements without being protected in proper conduit/raceway systems and have proper lightning and bonding protection installed.

Optical fiber cable can also be used for horizontal workstation connectivity when the following conditions exist:

• Distance requirements exceed the 100 meter cable-length specification.

• Known high bandwidth/security requirements that exceed copper cable limitations and business case supports the installation.

• Space inside or outside of the walls to support the minimum fiber cable bend radius.

• Severe EMI or RFI in the copper cable plant.

• Adequate funding.

• Proposed fiber optic to the desktop is approved by the DSB.

If optical fiber cables are used for workstation connectivity, each workstation location shall be cabled with a 4-strand, 62.5/125 micrometer (μm), graded index, multimode optical fiber cable with proper coating to meet local fire and building codes, whereas plenum is recommended. The cable shall be labeled as described in Section 12 of this document.

3.3 Workstation Outlets

Each workstation area shall use a standard faceplate that can support a minimum of three dual-connection interfaces. Regardless of the installation contractor, all voice and data cable shall utilize a singe Information Outlet. Unless otherwise specified, the “A” jack shall be Blue, The “B” jack shall be Gray and the “C” jack shall be Ivory or White. Information outlets must be capable of future growth without the need to replace the entire Information Outlet. Information outlets can be either single gang or dual gang standard size; sizing will be determined by number of cables being installed.

March 7, 2008 9 Structured Cable Plant Standard Version 5.x

Exhibit 2: Workstation Faceplate, Single Gang

Single Gang Flush Mount Faceplate

Blank Module

C

A B

Where fiber-optic cable is installed to the desktop, the corresponding IMO faceplate shall provide space to install at least three RJ-45 jacks and at least two optical fiber connectors (see Exhibit 3).

March 7, 2008 10 Structured Cable Plant Standard Version 5.x

Exhibit 3: Workstation Faceplate with Optical Fiber Cables

Double Gang Flush Mount Faceplate Fiber Optic SC connectors

Blank Module

C

A B

March 7, 2008 11 Structured Cable Plant Standard Version 5.x

3.4 Backbone Cabling

Intra and Inter-backbone cabling may consist of either or both copper and optical fiber cables and are required where there exists more than one wire center. The intra and inter-backbone shall be installed to provide structured connectivity between closets (see Exhibit 4). The installation provides a star-topology cable infrastructure that is capable of supporting high-speed and high bandwidth requirements between key resources in an enterprise building or campus environment.

A multimode, singlemode, or combination of fiber-optic backbone structure provides the means of interconnecting all wiring closets to the MDF in a multi-segmented environment. Optical fiber not only provides extensive bandwidth capabilities to the LAN and voice, but it also provides a solution to the distance-related problems encountered with copper cables in large installations and campus environments.

Copper backbone cabling is required to support voice services, however, the specifications and designs are determined on a site-by-site basis. This is due to the variety, funding, capacity and availability of voice services and designs. Copper backbone may also be installed to support networking services, where distance limitations do not exceed the ANSI/TIA/EIA-568-B.1 specifications. Copper backbone cabling provides a redundant connectivity option in the event of a catastrophic fiber failure, and shall be installed where voice and data closets are physically separated.

Each remote wiring closet shall be connected to the MDF with a multi-strand, optical fiber backbone cable that runs directly from the wiring center to the MDF. All strands will be terminated with SC style connectors in accordance with the ANSI/TIA/EIA standards in rack-mounted patch panels. A minimum twelve-strand fiber shall be installed in any facility providing connectivity between communications closets. It is estimated that 12 strands of multimode fiber will meet most of the intra and inter backbone connectivity needs currently deployed and planned for ICE facilities. Considering the myriad of site functions, building designs, physical layout, application requirements and future technologies, backbone design is a critical element in the planning stages. To ensure facilities are properly engineered with respect to backbone fiber types and counts, the Network Engineering Branch will provide engineering design in concert with local IT Field Office (ITFO) support personnel and facilities architects.

This ensures both short-term and long-term requirements are met in a cost-effective manner.

The optical fiber Intra and Inter-backbone cabling shall have one port per strand for cross-connection, and will conform to the specifications in Sections 4 and 6 of this document.

March 7, 2008 12 Structured Cable Plant Standard Version 5.x

Exhibit 4: Backbone Fiber Distribution

Main Distribution Frame (MDF)

Inter-Backbone

Intra-Backbone

Remote Wire Closets

(RWC)

March 7, 2008 13 Structured Cable Plant Standard Version 5.x

4.0 SPECIFICATIONS

This section provides detailed component characteristics and specifications with respect to the materials used to install the structured cable plant.

4.1 Horizontal Cables

All cable, equipment, and materials shall meet applicable ANSI/TIA/EIA-568-B, National Electrical Code (NEC) 770, Institute of Electrical and Electronics Engineers (IEEE) 802 and Underwriters Laboratory (UL) Verification Program standards. All cable equipment and materials must be manufactured by facilities that are International Organization for Standardization (ISO) 9001 registered and certified.

• Shall be Category 6 rating in accordance with ANSI/TIA/EIA-568-B.2

• Four-pair, 100-Ohm, 24 American Wire Gage (AWG).

• The cable should have contiguous, 2-foot segment-length markers printed on the cable jacket.

The markings must also show the applicable performance Category 6, as well as the fire rating of the cable being installed.

• The finished cable shall be 100% plenum rated in accordance with the requirements of NEC Article 800, UL 444, NFPA 262, (UL 910), and applicable Canadian Standards Association (CSA) standards.

Note: Category 6 cables types must meet or exceed specifications listed in Exhibit 5.

Exhibit 5: Category 6 Cable Specifications

Specification Category 6

Frequency Range 1-250 MHz Attenuation (maximum) 35.8 dB NEXT (minimum) 33.1 dB PSNEXT (minimum) 30.2 dB ACR (minimum) -2.7 dB PSACR (minimum) -5.7 dB ELFEXT (minimum) 15.3 dB PSELFEXT (minimum) 12.34 dB Return Loss (minimum) 8dB Propagation Delay (maximum) 548 nanoseconds (ns) Delay Skew (maximum) 50 ns

4.2 Information Management Outlets

• Provide ANSI/TIA/EIA symbol icons for application identification (LAN, Voice, etc).

March 7, 2008 14 Structured Cable Plant Standard Version 5.x

• Provide individual label window for cable identification.

• Provides a high-density design.

• Offers solutions for secure environments.

• Must match make and model in existing facilities.

• Meets or exceeds ANSI/TIA/EIA Category 6 specifications.

• Mounts to standard electrical 2 inch and 4 inch boxes.

• Allows all modules (jacks) to be loaded and accessed from the front. No need to remove faceplate.

• Meets all Federal Communications Commission (FCC) Part 68 specifications.

• Provides standard 110D type insertion displacement connector (IDC) Printed Circuit Board (PCB) mounted connector.

• Is offered in a multitude of colors.

• Provides interchangeability between modules.

• Offers non-keyed RJ-45 style connectors.

• Offers 568SC modular fiber connectors.

• Is available in the ANSI/TIA/EIA-T568B wiring configuration.

4.3 Backbone Cabling

Backbone cabling shall be a minimum of 12-strand multimode fiber optic. In limited instances, singlemode fiber-optic cable may be used for distances that exceed 500 meters, in accordance with the Institute of Electrical and Electronics Engineers (IEEE) and the Gigabit Ethernet Alliance organizations. The IEEE 802.3z and IEEE 802.3ab published standards apply to gigabit Ethernet and overall specifications.

All fiber cable shall be of interlocking armor construction eliminating the need for conduit or plenum rated inner duct.

Fiber cable shall be colored orange to denote multimode fiber, yellow to denote singlemode.

Plenum rated fiber cable is required by the USICE for backbone cables routed within buildings.

Outside plant fiber cable shall have a water block construction and meet the requirements for compound flow and water penetration.

Category 6 copper backbone cabling shall meet the same specifications as stated in Section 4.1 (Horizontal Cabling), in addition to the multi-pair construction in increments of 25, 50 and 100 pair complements. Voice copper backbone cabling is not specified in this standards document and shall be determined on a case-by-case basis. Voice copper backbone cables are not subject to the same 100 meter distance limitations as specified for networking backbone cabling which is the Category 6 cable plant.

March 7, 2008 15 Structured Cable Plant Standard Version 5.x

4.3.1 Intra-Building Fiber Optics

Specifications for fiber backbone cabling that will interconnect closets within a single building or high-rise environment are defined in this section.

4.3.1.1 Multimode Fiber Optics

4.3.1.1.1 62.5/125-µm optical fiber plenum (OFNP) or optical fiber riser (OFNR).

• Maximum Attenuation: 3.5/1.0 dB km at 850/1300 nm.

• Minimum Bandwidth: 200/500 MHz km at 850/1300 nm.

• Tight buffered.

• Plenum or riser rated.

4.3.1.1.2 50/125-µm optical fiber plenum (OFNP) or optical fiber riser (OFNR).

• Maximum Attenuation: 3.5/1.0 dB km at 850/1300 nm.

• Minimum Bandwidth: 200/500 MHz km at 850/1300 nm.

• Tight buffered.

• Plenum or riser rated.

4.3.1.2 Singlemode Fiber Optics

4.3.1.2.1 8 µm to 10 µm OFNP or OFNR.

• Maximum Attenuation: 1.0/0.5 dB km at 1310/1550 nm.

• Tight buffered.

• Plenum or riser rated.

4.3.2 Inter-Building Fiber Optics

Specifications for fiber backbone cabling that will interconnect building within a campus environment are defined in this section.

4.3.2.1 Multimode Fiber Optics

4.3.2.1.1 62.5/125-µm OFN, OFNP, or OFNR.

• Maximum Attenuation: 3.5/1.0 dB km at 850/1300 nm.

• Minimum Bandwidth: 200/500 MHz km at 850/1300 nm.

• Loose Tube.

• Gel-filler or water blocking equivalent.

4.3.2.1.2 50/125-µm OFN, OFNP, or OFNR.

• Maximum Attenuation: 3.5/1.0 dB km at 850/1300 nm.

March 7, 2008 16 Structured Cable Plant Standard Version 5.x

• Minimum Bandwidth: 200/500 MHz km at 850/1300 nm.

• Loose Tube.

• Gel-filler or water blocking equivalent.

4.3.2.2 Singlemode Fiber Optics

4.3.2.2.1 8 µm to 10 µm OFN, OFNP, or OFNR.

• Maximum Attenuation: 1.0/0.5 dB km at 1310/1550 nm.

• Loose Tube.

• Gel-filler or water blocking equivalent.

4.4 Patch Cables (Workstation and Patch Panel)

• Shall conform to the ANSI/TIA/EIA Category 6 specifications.

• 4-pair, UTP stranded cable.

• RJ-45 connectors on both ends.

• The patch cables shall be wired in accordance with the ANSI/TIA/EIA-568-B.2 and ANSI/TIA/EIA-568-B.3 specifications.

• Certified by the manufacturer as compliant with the ANSI/TIA/EIA Category 6 criteria.

• Cables shall be available in a wide variety of colors and lengths.

4.5 Patch Panels

• Shall conform to the ANSI/TIA/EIA Category 6 specifications.

• The patch panel wiring shall be in compliance with the ANSI/TIA/EIA T568B wiring configuration.

• Provide back wire management hardware.

• Provide modular design to facilitate field repairs.

• Provides standard 110D type IDC PCB mounted connector.

• Available in low and high-density configurations.

• Meet the standard EIA-310 rack spacing specifications.

• Provide RJ-45 interface.

• Meets all FCC Part 68 specifications.

• Available in 12, 24, and 48 port capacities.

• Match make and model within existing facilities, where possible.

4.6 Equipment Racks

• Shall conform to the ANSI/TIA/EIA standards.

March 7, 2008 17 Structured Cable Plant Standard Version 5.x

• Conform to the standard EIA-310 mounting specification.

• Provide pre-tapped 10-32 threading.

• Provide a flexible modular concept.

• Provide vertical wire management.

• Provide floor-mounting hardware except for swing gate style hardware.

• Match make and model within existing facilities, where possible.

4.7 Cabinets and Swing Gates

• Shall conform to the ANSI/TIA/EIA standards.

• Conform to the standard EIA-310 mounting specification.

• Provide pre-tapped 10-32 threading.

• Provide a flexible modular concept.

• Provide vertical wire management.

• Provide floor-mounting hardware except for swing gate style hardware.

• Match make and model within existing facilities, where possible.

• Available in depths of 24 inches or more.

• Available in heights of 48 inches or more.

• Allow fan assembly installation.

• Lockable and offer matching key/lock design where multiple cabinets are installed.

• Are of a welded, uni-body construction.

• For areas located within seismic activity, meet Zone 4 earthquake vibration test conditions in accordance with National Electrical Bell Standards (NEBS) document TR-NWT-000063, Issue 4, 1992

5.0 COPPER CABLE INSTALLATION SPECIFICATIONS

This section details the specifications that are to be used when installing all copper cabling. All work shall be ANSI/TIA/EIA–568-B, ANSI/TIA/EIA-569-A, ANSI/TIA/EIA-606-A, NEC 770 and IEEE 802 standard specification quality (as applicable).

5.1 Horizontal Cables

Unless otherwise specified, horizontal cable shall be provided color coding the different jack designations. The “A” cables shall be Blue. The “B” cables shall be Gray. The “C” cables shall be white.

These are cables installed from a typical workstation location back to a central point within a building or facility. These cables connect the Information Outlet (IMO), back to a central point, the closet. The closet may be the MDF or an RWC. These cables shall be installed in

March 7, 2008 18 Structured Cable Plant Standard Version 5.x compliance with ANSI/TIA/EIA, building and industry practices. Cables should never be exposed nor create any safety hazards for the public.

All copper cables shall be positioned at a minimum distance of 4 inches from any EMI device (such as a light ballast, electrical motor, or power line). If contact is unavoidable (as in modular furniture), the copper cables shall not run more than 5 feet in parallel with the interference-generating medium. If traversing is necessary, all copper cables shall cross power lines and electrical conduits at a 90-degree angle to minimize interference.

Copper cables installed in a suspended ceiling environment shall at all times be self-suspended in the plenum air space by the use of a separate suspension system or installation in the building construction frame at the top of the permanent ceiling, if it exists. At no time shall cables be secured to the suspended ceiling grid, water pipes, or electrical conduits.

All cables should be installed as far above the suspended ceiling as possible, and should be bundled together with tie-wraps at intervals no less than 6 feet unless a dedicated cable tray system is available to support the cable. The tie-wraps should not be installed so tight as to "dent" or compress the cable jacket because this could create excessive crosstalk in the cables, causing failure during the testing of the cable to meet Category 6 specifications.

5.2 Patch Cables (Workstation)

The workstation patch cable connects the end user devices (personal computer, terminals, etc.) to the IMO. For most installations, these patch cables will be provided and left on-site for the deployment team or local ADP to install when setting up workstations and are not included in the overall cable plant certification. The workstation patch cable may be any length as long as the combined length of the workstation patch cable, the horizontal workstation cabling, and the patch-panel cable does not exceed 100 meters (328 feet). These cables are normally pre-constructed, certified and ordered in standard one-foot incremental lengths. If the installation vendor chooses, custom-length, certified station cables can be used.

5.3 Patch Cables (Rack)

The patch-panel cable connects the horizontal cable port to the voice and data electronics within a central wire center or closet, typically a RWC or MDF. These cables are identical to the workstation cables and are pre-constructed and certified by the manufacturer. It is the cable installer’s responsibility for patching all active cable locations into active ports, unless otherwise directed by the ICE manager or designated representative. These cables are pre-certified by the manufacturer; therefore, it is unnecessary to include them in the cable plant certification. Wire management and organization is important to facilitate troubleshooting, repair, and documentation and, as such, there are key elements to ensure patch cords are properly installed.

The following requirements shall be followed for patching workstation ports to electronics:

• The patch-panel cable may be any length, provided that the combined length of the workstation patch cable, the horizontal workstation cabling, and the patch-panel cable does not exceed 100 meters (328 feet).

• If the installation vendor chooses, custom-length, certified station cables can be used.

• Patch cables must be labeled and matching on both ends, in a standard one-up numeric convention. An example would be a closet that has 100 active workstations, thus 100 patch

March 7, 2008 19 Structured Cable Plant Standard Version 5.x cables are installed, one for each active node, starting with cable identification (ID) number one and ending with ID number 100. Any support personnel would be able to view the station patch panel and electronics equipment to determine which specific port a particular station is connected.

• Patch cable numbering shall be affixed to both ends of each patch cord approximately one inch from the terminator or mod plug.

• Label IDs must be legible and produced with indelible ink. The preferred method is a printed label. Installers must avoid the use of materials that will distract from the appearance of the installation, or any temporary marking.

• Ensure patch cables are installed in a manner that does not require support personnel to “tug” or “trace” cables in order to determine the active port.

• Cables must be dressed utilizing available horizontal and vertical wire management.

• Patch cables should provide a neat and organized appearance, eliminating large bundles of cables in single locations, preventing tangles and using incorrect or oversized cables that produce excess slack.

• Cables shall never exceed the minimum bend radius or have kinks or nicks in accordance with the ANSI/TIA/EIA specifications.

• Cables should utilize left and right vertical wire management to reduce cable patch congestion produce and even cable distribution within a given cabinet.

• Patch cables shall never create a trip hazard or other risk to equipment, services or personnel.

5.4 Copper Cable Termination

This section applies to both the workstation and closet cable termination practices. All copper cable terminations shall conform to ANSI/TIA/EIA-568-B standards. The key areas and specifications are highlighted below:

• Pair twists shall be maintained as close as possible to the point of termination. Untwisting shall not exceed 13mm (0.5 in.) for Category 6 links.

• Strip back only as much jacket as is required to terminate individual pairs.

• All connecting hardware shall be installed to provide well-organized cable management in accordance with manufacturer’s guidelines.

• All four pairs must be terminated.

• Pin/Pair assignments shall follow the T-568B configuration (see Exhibit 6).

March 7, 2008 20 Structured Cable Plant Standard

Exhibit 6: T-568B and T-568A Pair/Pin Assignments

6.0 INSTALLATION OF OPTICAL FIBER CABLES AND CONNECTORS

This section provides the specifications to be used when installing all optical fiber cabling.

6.1 Fiber Horizontal Workstation Cable

The fiber horizontal workstation cable connects the workstation to the wiring center. This cable shall be four-strand, multimode, 62.5/125 μm or 50/125 μm, optical fiber cable with graded index 250 or 900 μm buffer. Contiguous, 2-foot, segment-length markers shall be printed on the cable jacket.

The bend radius of any optical fiber cable installed shall be at least eight times the outside diameter of the cable. For example, a six-strand optical cable with an outside diameter of .30 inches and shall have a minimum bend radius of 2.40 inches.

Pulling tension for optical fiber cables must adhere to and not exceed manufacturer specifications.

6.2 Backbone Fiber Cable

The optical fiber home-run backbone cable shall connect each remote wiring closet to the MDF.

This cable shall be 12-, or 24-, or more strand, multimode, 62.5/125 μm or 50/125 μm, optical fiber cable with graded index, 250 or 900 μm buffer, and contiguous, 2-feet, segment-length markers printed on the cable jacket. Optical fiber cables shall be of interlocking armor construction eliminating the need for conduit or plenum rated inner duct.

Fiber-optic cable shall not share conduits with copper medium unless separation between copper and fiber is maintained. For large campus or complex backbone fiber installations where multiple conduits or pathways exist, fiber-optic cable shall be separated from the copper cable installation, wherein fiber-optic cable is dedicated to one conduit, copper to another. In retrofit or existing buildings, where pathways are insufficient to maintain separation between copper and fiber, ICE OCIO NEB shall review and approve the design prior to installation.

March 7, 2008 21 Structured Cable Plant Standard Version 5.x

6.3 Optical Fiber Cable Jacket

All overhead or above-ceiling installations shall use optical fiber cable with a plenum-graded jacket that is marked with a UL rating of “OFNP” or equivalent. All non-air-return (non-plenum) installations can use optical fiber cable with either a plenum or non-plenum jacket (such as PVC) that is marked with a UL rating of “OFNR” or equivalent.

6.4 Optical Fiber Connector

The optical fiber connector for workstation or backbone connections shall follow the ANSI/TIA/EIA standards for installation.

New buildings shall use SC type connectors for workstation and/or backbone installation.

In retrofit buildings, fiber connectors should match the existing installed connectors.

6.5 Optical Fiber Cable Termination

All optical fiber cables shall be light tested prior to installation. This is typically done while the cable is still on spools or reels and only ensures all strands pass light prior to pulling cable into conduits and pathways.

The minimum termination shall be four strands for a horizontal cable. When installing fiber-optic backbone cabling, all strands will be terminated with the appropriate connectors and capped with a dust boot. All strands shall be terminated and tested.

All optical fiber cables shall have a twenty foot storage coil (wrapped in an appropriately sized loop for the minimum bend radius of the cable) positioned at each end, where possible before being terminated with connectors. All intermediate slack in the optical fiber cable shall be loosely coiled and suspended to avoid hard bends or kinks.

7.0 FACEPLATE CONFIGURATION

Workstations that are not connected to an optical fiber cable typically utilize a single-gang faceplate that can support up to six connection ports (see Exhibit 2). Blank inserts shall be installed in all remaining positions.

Workstations that are connected to optical fiber cables shall have a double-gang faceplate and junction box installed that can support up to 12 connection ports (see Exhibit 3).

8.0 PATCH PANELS

Patch panels, both fiber and copper are the approved methods of providing connectivity between horizontal cables, Intra and Inter-backbone copper, fiber backbone, and common network service devices, such as switches, PBX, routers, and other electronics.

Patch panel installation must adhere to manufacturer specifications and installed utilizing all wire management hardware, both front and back. Panels shall be installed to best utilize both vertical and horizontal wire managers, and should be separated by horizontal wire managers. There should be a minimum of one horizontal wire manager for each horizontal patch panel. Panels must be clearly marked as to the outlet designation. Labels must be of permanent indelible typed materials.

March 7, 2008 22 Structured Cable Plant Standard Version 5.x

8.1 Copper Patch Panels

Each panel will be installed to provide the maximum use of rack space. Each panel will be mounted in an equipment rack that shall conform to the EIA-310 mounting-hole spacing standard.

Separate patch panels will segregate “A”, “B” and “C” cables. The upper patch panel will be used for “A”, the middle patch panel will be used for “B” and the lower patch panel will be used for “C”. In addition, and depending on the number of total cables, all cables may also share a single standard 7-foot equipment rack, swing gate or cabinet enclosure. Exhibits 7, 8, and 9 shall be used as a model for all new installations, and should be followed as close as possible for major retrofits and renovations with respect to existing cable plant configurations. Deviations to these layout exhibits shall be reviewed and approved by the NEB.

8.2 Fiber Optic Patch Panels

Optical fiber cable patch panels for workstation connections (also called fiber cabinets) shall provide 568SC couplers. Optical fiber cable patch panels for backbone cabling (also called fiber cabinets) shall provide 568SC couplers. The color scheme and the port numbering scheme on the patch panel shall be consistent in any given installation to reduce confusion and to prevent mistakes in making cross-connections. Fiber patch panels shall be installed in standard increments of six-position; 568SC loads or interconnect couplers, as required in each wiring closet and MDF.

9.0 EQUIPMENT RACK

There are a multitude of equipment racks and cabinets that are acceptable for use in ICE installations. Wherever possible, separate secure communication closets are recommended and are the preferred method for voice and data installation. In these dedicated communications closets, open racks, cabinets and swing gates may be used to meet the needs of the installation.

When open racks or swing gates are used, they shall be located within the wiring closets, and they shall provide structural support for the patch panels and required electronics. The open rack will be a standard 19 inches wide by 7 feet tall when used in a floor mount configuration. When space considerations mandate, it is acceptable to use an open, wall-mounted equipment rack (swing gate). If a wall mount configuration is used, the rack must be hinged, and space must be provided so that the rack can swing fully open and provide full access to the back of the rack.

All floor or wall-mounted equipment racks, cabinets and swing gates installed in earthquake-prone geographic areas shall be installed in compliance with specific seismic guidelines, regulations and codes. Special attention must be taken to ensure the proper installation techniques are followed to minimize risk to electronics and cable plant, and most importantly prevent the mounting hardware from toppling over during seismic activity.

Equipment shall be mounted on the rack via holes in the frame or by using mounting hardware that conforms to the EIA-310 mounting-hole spacing standard. As an alternative for non-rack devices, equipment may be placed on flat shelves that are attached to the rack. All racks shall be secured either to the floor or wall with bolts or other fasteners that are rated to withstand the recommended weight limits and shear loads for the rack. Each rack shall include all mounting and assembly hardware (such as nuts and bolts) for full configuration use. When multiple racks

March 7, 2008 23 Structured Cable Plant Standard Version 5.x and/or cabinets are used and they are butted together in the closet, they shall be bolted together for additional stability.

March 7, 2008 24 Structured Cable Plant Standard

Exhibit 7: Typical Single Rack Layout for Smaller Installations

48-port Patch Panel “C”

SDSD

Fiber Distribution Panel

SD

48-port Patch Panel “A”

48-port Patch Panel “B”

Wire Management Panel

Ethernet Switch

48-port Voice Riser Cable

Wire Management Panel

UPS

Vertical Wire Management

SD

Power Strip

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

CAT 6

25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

CAT 6

25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

CAT 6

25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

CAT 6

25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48

OPEN SYSTEN ARCHITECTUR

OPEN SYSTEN ARCHITECTUR

OPEN SYSTEN ARCHITECTUR

OPEN SYSTEN ARCHITECTUR

OPEN SYSTEN ARCHITECTUR

OPEN SYSTEN ARCHITECTUR Wire Management Panel

Wire Management Panel

Wire Management Panel

Wire Management Panel

March 7, 2008 25 Structured Cable Plant Standard

Exhibit 8: Typical Two Rack Layout

SDSDSDSDSDSD

SD

TX

PO

RT

RX

PS2

PS1

FAN

STATUS

RESE T

SL

OT2

SL

OT1

POW ER

EJE

CT

AUI

CONS OLE

SWITCH P ROCES SOR

SD

SD

SD

SDSD

SD

March 7, 2008 26 Structured Cable Plant Standard

Exhibit 9: Typical Three Rack Layout for Larger Installations

SDSDSD SDSDSD

TX

PORT

RX

PS2

PS1

FAN

STATUS

RESET

SLOT2

SLOT1

POW

ER

EJECT

AU I

CONSOLE

SWITCH PROCESSOR

SDSDSD

SD

S D

SD

SD

SD

SD

SD

SD

SD

SD

March 7, 2008 27 Structured Cable Plant Standard Version 5.x

Floor mounted racks and cabinets shall have a minimum of 36 inches of clearance in front of, behind, and on at least one side. Where space or room layouts limit the minimum clearances required, the installation contractor shall notify the NEB or designated representative for technical direction.

Equipment layout, specifically with respect to rack, cabinet, and swing gate location are critical design elements that ensure future growth, maintenance and flexibility are protected. Proper clearances also allow installers and maintenance personnel the required room to perform work safely and ensure electronics environmental conditions are maintained.

The patch cables shall run neatly through the wire management panels above the electronics, run down the sides of the rack, run below the electronics, and plug neatly into the respective port.

The cables between the patch panels and the electronics shall not be excessively long nor shall they lie on the floor. The patch cables shall be secured and bundled using Velcro securing straps.

Caution: The use of tie-wraps is not acceptable when bundling and securing patch cables on the rack.

A power strip with surge suppression and an on/off switch shall be mounted to the back of the rack to supply at least six outlets for AC power (120-volt, 20-amp service).

10.0 GROUNDING

The NEC provides guidelines to ensure that electrical installations in buildings meet the necessary safety practices to prevent electrical shock hazards to personnel, ensure fault clearance of unintentional electrical breakdowns that could cause fire, and prevent transient voltages from causing electrical damage to installed network components. NEC Article 800 pertains to telecommunications industry and should be consulted for specific guidelines related to this topic.

Article 800 also has references to other articles as the need arises.

In all new buildings and major retrofit projects an independent ground bus, installed in each communications closet, shall be provided. The independent ground bus in each closet should be installed by a certified electrician, or properly licensed installer. The independent ground buses are designated for, and utilized exclusively, by the communications equipment. In existing buildings, an independent ground is certainly desirable. In general, all communications systems, cable plant devices, equipment, and components shall be properly grounded and bonded.

All grounding shall be performed to meet the following published standards and guidelines:

• ANSI/TIA/EIA 607

• ANSI/IEEE C-142

• Federal Information Processing Standard (FIPS) 94

• NEC Articles 250 and 800

• UL

• ANSI CI-1978

All equipment racks, cabinets and systems must be properly connected to the independent ground bus per the ANSI/TIA/EIA 607 specifications. It is the responsibility of the cable

March 7, 2008 28 Structured Cable Plant Standard Version 5.x installer to connect all common closet equipment racks and cabinets to the provided ground bus.

It is also the responsibility of the cable installers to report to the ICE Program Manager any discrepancies with respect to improper or omitted grounding systems.

For connecting equipment within the telecommunications/data wiring closets to the ground bus, a number six wire with green insulation should be used. This ground wire should be no longer than 30 feet.

All ground wire should be routed straight, with sweeping bends, neat, and orderly. Ground wire should be routed in the most direct fashion possible to the equipment. Ground wires should be supported by tie-wraps at 12-inch intervals.

The manufacturer instructions and recommendations shall be followed when grounding the electronic equipment installed in the telecommunications/data wiring closets.

11.0 CABLE LADDERS AND FASTENERS

All cables installed in overhead spaces (such as above ceiling panels) shall be securely strapped to ceiling slab fasteners or cable ladders that are fastened to the ceiling slab to avoid contact with lighting equipment or drop ceiling supports. Wire management channels or cable ladders shall be used to provide orderly arrangement of all installed cables in and around the equipment racks.

As a general rule, all cables shall be securely suspended, fastened, tied, and bundled firmly (without damaging the cable jackets or creating kinks in the cable) to minimize the amount of space required for cabling.

12.0 ADMINISTRATION AND LABELING CONVENTIONS

Label conventions shall apply to all sites, regardless of the number of buildings at the site. This section describes the ICE standard labeling convention for all cable installations, whether new or retrofit.

12.1 Building Designation

The designation for the building shall be a two to four character alphanumeric scheme.

Buildings typically have unique names/numbers, whether in multi-story complexes or in campus environments. The first designation should represent the unique building the cable plant is wired within. This nomenclature will rarely change throughout the life of the building and allows a structured naming convention to be used for Inter-building backbone cable installations.

12.1.1 Floor

The designation for the floor shall be a two-digit number. If the floor is a single number such as “4,” place a leading zero before the single-digit, for example “04.”

12.1.2 Wiring Closets

The designation for a wiring center is a single letter. The Computer Room or MDF shall always have the wiring closet designation of “M.” Remote wiring closets that are all located on the same floor shall be labeled A-L and N-Z (“M” is reserved for the MDF). Closets that stack directly on top of each other shall have the same letter designation.

March 7, 2008 29 Structured Cable Plant Standard Version 5.x

12.1.3 Cable Numbers

The designation for the cable shall be a three-digit number, followed by an “A”, “B” and “C”.

Use leading zeros as necessary. For example, the designation for drop #3A would become 003A.

12.2 Information Outlet

The IMO is the interface for the workstation cable and the horizontal workstation cable, which terminates in a wiring closet. This is typically referred to as the “jack” in the industry, also an enhancement to the Bell Labs Universal Service Order Code (USOC) specifications. These specifications also referenced the RJ pin assignments. The ANSI/TIA/EIA now prefers to use the term 8-pin modular plug or connector when describing jack pin-outs. Each information outlet should be labeled according to the following guidelines:

The designations on single-gang and double-gang faceplates will be as follows:

• Building (AANN, or combination).

• Floor (NN, with a leading zero).

• Wiring center (A).

• Cable drop (NNN, with leading zeros).

For example: “TW-12-C-111” where: TW = TechWorld building 12 = 12th floor C = wiring center and 111 = cable drop #111.

12.3 Intra and Inter-Building Backbone Cables

These backbone cables interconnect wiring closets either within a building or interconnect buildings in a campus environment.

The naming convention applies the same for Intra and Inter backbone cable labeling. Standard nomenclature for backbone cabling shall be as follows:

• First Building (4–6 alphanumeric characters).

• First wiring closet (includes floor, closet and pair or strand designations).

• Second Building (2–4 alphanumeric characters).

• Second wiring closet (includes floor, closet and pair or strand designations).

For example, “TW801I-06-W-001 – TW800K-01-M-001” where: TW801I = TechWorld building 801 I is the first building (origination point) 6 = 6th floor W = wiring center, closet W…