815CM3041 LINC Bid Set Bk-13.pdf
PDF 16 MB Posted
- Solicitation number
- 36C78624B0005
About this file
This solicitation is for a construction project at the Long Island National Cemetery located in Farmingdale, New York. The contractor shall provide all labor, materials, equipment and supervision to perform renovation, improvements and repairs as described in the Statement of Work, Specifications and Drawings. The work includes facility upgrades located at the Long Island National Cemetery for Project Number 815CM3041. The soliciting agency is the Department of Veterans Affairs National Cemetery Administration. The solicitation number is 36C78624B0005 and is an Invitation for Bid for the construction work.
View the file
Other files
Show all 49
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
K
( NOTE: SYMBOLS WITHIN THIS SCHEDULE ARE REPRESENTATIVE OF THOSE TYPICALLY FOUND ON THE DRAWINGS. ALL SYMBOLS MAY NOT APPEAR ON THIS SET OF DRAWINGS. )ELECTRICAL SYMBOLS
ABOVE FINISHED FLOOR TO CENTERLINE OF DEVICE.
EMPTY CONDUIT.
JUNCTION BOX SIZED PER NEC.
NATIONAL ELECTRICAL CODE
NIGHT LIGHTING, 24 HOUR, OPERATION. WIRE AHEAD OF ALL LOCAL SWITCHES.
ON CENTER.
TELEPHONE TERMINAL BOARD.
DIMENSION INDICATES HEIGHT, AFF, AT WHICH DEVICE IS TO BE MOUNTED.
HEADWALL. SEE PLAN FOR NUMBER.
POWER COLUMN. SEE PLAN FOR NUMBER.
SURGE PROTECTIVE DEVICE
VARIABLE SPEED DRIVE
PNEUMATIC TUBE STATION
SYMBOL LOCATION LEADER
ABBREVIATIONS
AFF
TELEPHONE OUTLET, FLUSH FLOOR MOUNTED.
TELEPHONE OUTLET, WALL MOUNTED 18" AFF TO CENTER OF DEVICE.
SECURITY SYSTEM CLOSED CIRCUIT T.V. CAMERA. SUBSCRIPT INDICATES PAN/TILT/ZOOM CONTROL.
SECURITY SYSTEM PUSHBUTTON STATION. SURFACE MOUNTED 48" AFF.
PUBLIC ADDRESS SYSTEM MICROPHONE OUTLET, WALL MOUNTED 18" AFF. COORDINATE TYPE OF
PUBLIC ADDRESS SYSTEM HORN, WALL MOUNTED 7'-6" AFF. UNLESS OTHERWISE INDICATED.
PUBLIC ADDRESS SYSTEM SPEAKER, CEILING MOUNTED.
OUTLET WITH OWNER'S EQUIPMENT.
W = WALL MOUNTED STATION
INTERCOM OUTLET WALL MOUNTED 48" AFF TO TOP OF DEVICE, WITH DESK MOUNTED STATION UNLESS
INTERCOM WALL MOUNTED 18" AFF TO CENTER OF DEVICE, WITH DESK MOUNTED STATION.
MODIFIERS FOR INTERCOM:
S = SUB STATION
M = MASTER STATION
OR 6" FROM BOTTOM OF OUTLET TO COUNTERTOP.
TELEPHONE OUTLET WALL MOUNTED 48" AFF, 2" FROM BOTTOM OF OUTLET TO BACKSPLASH,
PROVIDE FLUSH MOUNTED JUNCTION BOX WITH APPROPRIATE COVERPLATE. PROVIDE 1 1/4" EMPTY CONDUIT WITH NYLON PULL CORD FROM JUNCTION BOX TO ABOVE ACCESSIBLE CEILING FOR VOICE/DATA WIRING TO
PRE WIRED FURNITURE. COORDINATE EXACT REQUIREMENTS AND LOCATION WITH EQUIPMENT
MODIFIERS FOR VOICE/DATA & TELEPHONE OUTLETS: (DEVICE AND CONDUCTORS BY TELECOM VENDOR) a = VOICE ONLY b = STANDARD (2 DATA / 1 VOICE SPLIT) c = 1 DATA ONLY d = 4 DATA / 1 VOICE SPLIT
COMMUNICATIONS
VOICE/DATA OUTLET, FLUSH FLOOR MOUNTED.
GROUND BAR - 1/8"x1"x12" COPPER BUS IN NEMA 1 ENCLOSURE. LOCATE ABOVE SUSPENDED CEILING.
PUBLIC ADDRESS SYSTEM VOLUME CONTROL SWITCH, WALL MOUNTED 48" AFF.
CONDUIT SLEEVES. SEE PLANS FOR SIZE AND QUANTITY.
LED LIGHTING FIXTURE, WALL MOUNTED OR UNDER CABINET, CONNECTED TO NORMAL POWER.
LED LIGHTING FIXTURE, CEILING OR WALL MOUNTED,
POLE MOUNTED LIGHTING FIXTURE. SEE SCHEDULE FOR TYPE (*).
DRAWINGS. SEE SCHEDULE FOR TYPE (*). CONNECT UNSWITCHED.
CEILING OR WALL MOUNTED EXIT SIGN. PROVIDE NUMBER OF FACES AND CHEVRONS AS INDICATED ON
EMERGENCY LIGHTING FIXTURE, CEILING-MOUNTED OR WALL-MOUNTED AT 7'-6" AFF UNLESS NOTED
OTHERWISE. CONNECT UNSWITCHED.
LIGHTING
LED LIGHTING WALLWASH FIXTURE, CEILING MOUNTED.
TRACK LIGHTING FIXTURE. SEE PLANS/SCHEDULE FOR TRACK LENGTH AND NUMBER OF TRACK HEADS.
EQUIPMENT IDENTIFICATION
HORSEPOWER RATING
MOTOR CONNECTION. SPECIAL VOLTAGES AS SHOWN ON DRAWING.
ENCLOSED CIRCUIT BREAKER. NUMERAL INDICATES TRIP AMPERE RATING.
FUSED SAFETY SWITCH. NUMERAL INDICATES FUSE RATING.
NON-FUSIBLE SAFETY SWITCH. NUMERAL INDICATES AMPERE RATING.
SIZE AND BOTTOM NUMERAL INDICATES NEMA STARTER SIZE.
COMBINATION MOTOR STARTER WITH CIRCUIT BREAKER. TOP NUMERAL INDICATES CIRCUIT BREAKER
MOTOR STARTER. NUMERAL INDICATES NEMA SIZE.
AMPACITY. SEE FEEDER SCHEDULE.
ON RISERS, DESIGNATION DENOTES QUANTITY OF CURRENT CARRYING CONDUCTORS AND FEEDER
WIRING SYSTEM CONCEALED IN OR ABOVE CEILING OR IN WALL.
WIRING SYSTEM BELOW FLOOR OR BELOW GRADE.
DESIGNATION DENOTES PANEL BOARD, SWITCHBOARD, MOTOR CONTROL CENTER, ETC., AND OVERCURRENT BRANCH OR FEEDER CIRCUIT HOMERUN TO PANEL BOARD, SWITCHBOARD, MOTOR CONTROL CENTER, ETC.
WIRING SYSTEM TURNED UP.
WIRING SYSTEM TURNED DOWN.
WIRING SYSTEM EXPOSED.
PROTECTION DEVICE NUMBER.
DRY TYPE TRANSFORMER.
NEC REQUIRED GROUND.
EF-1, 10 HP.460V, 3∅
208V, 3∅
120V, 1∅
MOTOR RATED SWITCH. AMPS/POLES TO MATCH UPSTREAM BREAKER.
CONNECTION TO WALL MOUNTED FILM ILLUMINATOR. PROVIDE RECEPTACLE IN FLUSH OUTLET BOX AT
LOWER RIGHT HAND CORNER OF UNIT IF SURFACE MOUNTED. HARD WIRE IF RECESSED.
JUNCTION BOX AND CONNECTION TO EQUIPMENT OR TERMINAL STRIPS.
CEILING FAN 120V. MANUFACTURER (HUNTER#21252 GREEN FINISH W/ INTEGRATED 240W LIGHT FIXTURE)
CONNECTION TO HEADWALL UNIT. ONE NORMAL POWER CIRCUIT. ONE CRITICAL POWER CIRCUIT, CONNECTION TO FAN COIL UNIT. COORDINATE EXACT LOCATION WITH MECHANICAL CONTRACTOR.
AND ONE DEDICATED CRITICAL POWER CIRCUIT FOR VENTILATOR.
CONNECTION TO EXHAUST FAN. COORDINATE EXACT LOCATION WITH MECHANICAL CONTRACTOR.
PANELBOARD SURFACE MOUNTED.
REMOTE ALARM PANEL FOR ISOLATED POWER PANEL BOARD WALL MOUNTED AT 5'-0" AFF.
GENERATOR REMOTE ALARM ANNUNCIATOR. WALL MOUNTED AT 5'-0" AFF.
N = NORMAL BRANCH
U = UNGROUNDED (ISOLATION) PANEL
Q = EQUIPMENT BRANCH
C = CRITICAL BRANCH
L = LIFE SAFETY BRANCH
M = MOTOR CONTROL CENTER
L = 120/208 VOLT
H = 277/480 VOLT
PANELBOARD FLUSH MOUNTED.
1,2,3 = FLOOR
A,B,C = LOCATION
PANELBOARD NAMING CONVENTION
JUNCTION OR PULL BOX. W = WEATHERPROOF.
CONDUIT STUBBED INTO ACCESSIBLE CEILING SPACE.
HARDWIRE CONNECTION FROM FLUSH MOUNTED JUNCTION BOX WITH APPROPRIATE COVERPLATE AND 3/4" LIQUID TIGHT FLEXIBLE METALLIC WHIP TO PRE-WIRED FURNITURE. COORDINATE EXACT REQUIREMENTS AND LOCATION WITH EQUIPMENT SUPPLIER/INSTALLER. EIGHT(8) WIRE SYSTEM PROVIDES FOUR(4) CIRCUITS.
POWER
SURFACE MOUNTED MULTIOUTLET ASSEMBLY. 48" AFF OR 8" ABOVE COUNTER
TV = TELEVISION, SEE DETAIL.
G = GROUND FAULT CIRCUIT INTERRUPTER.
EWC = ELECTRIC WATER COOLER POWER CONNECTION, PROVIDE GROUND FAULT CIRCUIT INTERRUPTER
P = PEDESTAL
WP = WEATHERPROOF "IN-USE" COVER, PROVIDE GROUND FAULT CIRCUIT INTERRUPTER DEVICE.
DUPLEX RECEPTACLE, MOUNTED 18" AFF TO CENTER OF DEVICE. NEMA 5-20R UNLESS OTHERWISE
OR 2" ABOVE BACKSPLASH. SHADED AREA INDICATES RECEPTACLE.
DUPLEX RECEPTACLE OUTLET. FLUSH FLOOR MOUNTED.
SIMPLEX RECEPTACLE MOUNTED 18" AFF TO CENTER OF DEVICE. NEMA 5-20R UNLESS OTHERWISE
TWO DUPLEX RECEPTACLES IN 2-GANG BOX, MOUNTED 48" AFF TO TOP OF OUTLET
OR 2" FROM BOTTOM OF OUTLET TO TOP OF BACKSPLASH OR COUNTERTOP. SLASH INDICATES
OUTLET TO TOP OF BACKSPLASH OR COUNTERTOP. SLASH INDICATES CONNECTED TO THE EMERGENCY
DUPLEX RECEPTACLE, MOUNTED 48" AFF TO TOP OF OUTLET OR 2" FROM BOTTOM OF
TWO DUPLEX RECEPTACLES IN 2-GANG BOX, MOUNTED 18" AFF TO CENTER OF DEVICE. SLASH
DUPLEX RECEPTACLE OUTLET. CEILING MOUNTED.
SPECIAL RECEPTACLE OUTLET. NEMA CONFIGURATION AS INDICATED. PROVIDE MATCHING CORD & PLUG AS
NEEDED.
MODIFIERS FOR RECEPTACLES:
SPECIAL RECEPTACLE OUTLET. FLUSH FLOOR MOUNTED. NEMA CONFIGURATION AS INDICATED. PROVIDE
MATCHING CORD & PLUG AS NEEDED.
LH2A-1
CH2A
POWER POLE. DEVICE CONFIGURATION AND COLOR AS INDICATED. PROVIDE POLE HEIGHT AS REQUIRED.
EQUIPMENT CONNECTION DESIGNATION, SEE SCHEDULE FOR DETAILS.
M
RATING AND BOTTOM NUMERAL INDICATES NEMA STARTER SIZE.
COMBINATION MOTOR STARTER WITH FUSED SWITCH. TOP NUMERAL INDICATES FUSETRON AMPERE
LIGHTNING PROTECTION SYSTEM GROUND ROD.
75KVA T
LIGHTNING PROTECTION SYSTEM AIR TERMINAL.
TR = TAMPER RESISTANT
3 = THREE WAY
MODIFIERS FOR SWITCHES:
SINGLE POLE SWITCH, MOUNTED 48" AFF TO TOP OF DEVICE.
THREE SINGLE POLE SWITCHES IN A 3-GANG BOX, MOUNTED 48" AFF TO TOP OF DEVICE.
PHOTO ELECTRIC CELL MOUNTED ON CONDUIT STUBBED 6" ABOVE ROOF, FACING NORTH.
SWITCHES
TWO SINGLE POLE SWITCHES IN A 2-GANG BOX, MOUNTED 48" AFF TO TOP OF DEVICE.
PROVIDE DIVIDER FOR DIFFERENT VOLTAGES OR BRANCHES.
4 = FOUR WAY
D = DIMMER
DT = DOUBLE THROW
LV = LOW VOLTAGE
TWO SINGLE POLE SWITCHES IN A 2-GANG BOX, MOUNTED 48" AFF TO TOP OF DEVICE, TO COMPLY WITH ENERGY CODE. EITHER SWITCH INBOARD AND OUTBOARD LAMPS SEPARATELY OR STEP-DIM BOTH
PROVIDE DIVIDER(S) FOR DIFFERENT VOLTAGES OR BRANCHES.
OS = OCCUPANCY SENSOR
TIME CLOCK. PROVIDE POWER CIRCUIT AND 3/4" CONDUIT TO ACCESSIBLE CEILING SPACE.
a,b,c = MULTIPLE SWITCH LEGS
T = TIMER
INDICATED.
INDICATED. SLASH INDICATES CONNECTED TO THE EMERGENCY POWER SYSTEM.
INDICATES CONNECTED TO THE EMERGENCY POWER SYSTEM.
CONNECTED TO NORMAL POWER. SEE SCHEDULE FOR TYPE (*). SEE ARCHITECTURAL RCP FOR EXACT
LUMINAIRE, CEILING MOUNTED, CONNECTED TO THE NORMAL POWER SYSTEM (UNLESS OTHERWISE NOTED).
SEE SCHEDULE FOR TYPE (*). SEE ARCHITECTURAL RCP FOR EXACT LOCATION AND CEILING TYPE.
LOCATION AND CEILING TYPE. SLASH INDICATES CONNECTED TO THE CRITICAL BRANCH.
SEE SCHEDULE FOR TYPE (*).
SEE SCHEDULE FOR TYPE (*).
REMOTE EMERGENCY EGRESS TWIN-LAMP UNIT.
HALF-SHADED INDICATES CONNECTED TO LIFE SAFETY BRANCH.
LAMPS TO 50%.
NOTED OTHERWISE.
SUPPLIER/INSTALLER.
PTZ
SLASH INDICATES CONNECTED TO THE CRITICAL BRANCH. HALF-SHADED INDICATES CONNECTED TO THE EMERGENCY OR LIFE SAFETY BRANCH; VIA EMERGENCY GENERATOR SET OR BATTERY BALLAST, SEE PLANS.
SLASH INDICATES CONNECTED TO THE CRITICAL BRANCH. SEE SCHEDULE FOR TYPE (*).
POWER SYSTEM.
CONNECTED TO THE EMERGENCY POWER SYSTEM.
LED STRIP LUMINAIRE. CEILING MOUNTED OR SUSPENDED 8'-0" AFF TO BOTTOM OF LUMINAIRE, CONNECTED TO NORMAL POWER. SLASH INDICATES CONNECTED TO THE CRITICAL BRANCH.
HALF-SHADED INDICATES CONNECTED TO THE EMERGENCY OR LIFE SAFETY BRANCH; VIA EMERGENCY
GENERATOR SET OR BATTERY BALLAST, SEE PLANS.
CARD READER. PROVIDE BOX AND CONDUIT AS REQUIRED. COORDINATE WITH HARDWARE VENDOR.
ELECTRIC STRIKE. PROVIDE BOX AND CONDUIT AS REQUIRED. COORDINATE WITH HARDWARE VENDOR.
REMOTE LINE ISOLATION MONITOR.
CABLE TV OUTLET, MOUNTED ADJACENT TO TV RECEPTACLE, UNLESS NOTED OTHERWISE.
PUSHPAD. PROVIDE BOX AND CONDUIT AS REQUIRED. COORDINATE WITH HARDWARE VENDOR.
EXPEDITOR SYSTEM
WIRELESS TELEMETRY ANTENNA
WIRELESS TELEMETRY DEVICE
EXPEDITER BUTTON PANEL
EXAM LIGHT CONTROLLER
EMERGENCY EGRESS PUSH BUTTON
KEY PAD CARD READER
EMERGENCY RELEASE SWITCH. PROVIDE TAMPER RESISTANT COVER WITH A SOUNDING HORN.
BUTTON RELEASE.
BADGE ACCESS.
NURSE LOCATOR.
EMERGENCY MANUAL OVERRIDE.
DEVICE. INSTALL DEVICE SO IT IS CONCEALED BEHIND ENCLOSURE, COORDINATE WITH PLUMBING.
SHOWN TO CLARIFY THAT DEVICES/LUMINAIRES ON THE SAME CIRCUIT ARE CONTROLLED SEPARATELY.
POLE MOUNTED LIGHTING FIXTURE. SEE SCHEDULE FOR TYPE (*).
4/350
XXXX
ERS
GENERAL PROJECT NOTES
LIM
RA
GA
J
E
C
M
H
F
P
P
S
P
J
SS
SS
ELC
EXIT
KPCR
PP
ES
CR
ES
BR
BA
NL
EMO
SS
V
M
H
GB
PS
C
TC
PE
SS
SSS
SS
S
DUAL TECHNOLOGY CEILING MOUNTED OCCUPANCY SENSOR. PROVIDE ONE POWER PACK FOR EACHOS
SENSOR. COORDINATE WIRING REQUIREMENTS WITH EQUIPMENT SUPPLIER PRIOR TO ROUGH-IN.
WIRELESS ACCESS POINTWAP
DEMOLITION NOTES
A.
FIRE ALARM
FIRE ALARM CONTROL PANEL. MOUNT AT 6'-6" AFF TO TOP. PROVIDE SMOKE DETECTOR ABOVE PANEL.FACP
REMAINDER
VOLTS DISTANCE HOMERUN OF CIRCUIT
120/208 0' - 50' #12 #12
50' - 100' #10 #12 100 - 150' #8 #10
REMAINDER
VOLTS DISTANCE HOMERUN OF CIRCUIT
277/480 0' - 125' #12 #12
125' - 220' #10 #12 220 - 330' #8 #10
COMMUNICATIONS
LIGHTNING PROTECTION AIR TERMINAL
PUSH BUTTON DOOR RELEASE WITH SOUNDER COVER.
MAGNETIC LOCK FOR DOOR.
PB
ML
KEY PAD. PROVIDE BOX AND CONDUIT AS REQUIRED. COORDINATE WITH HARDWARE VENDOR.KP
1. THE DRAWINGS SHALL NOT BE SCALED FOR CONSTRUCTION PURPOSES. THE SCALE WHEN INDICATED IS INTENDED FOR GENERAL
REFERENCE ONLY.
2. ALL OUTAGES SHALL BE COORDINATED AND APPROVED THROUGH THE OWNERS' REPRESENTATIVE AND WILL REQUIRE ADVANCE NOTICE OF ONE WEEK. THIS TIME LENGTH MAY BE LONGER OR SHORTER FOR SOME SHUTDOWNS AND SHALL BE AT THE OWNER'S DISCRETION.
3. CONSTRUCTION DEBRIS SHALL BE REMOVED DAILY AND LEGALLY DISPOSED OFF-SITE.
4. ALL FIXED ELECTRICAL EQUIPMENT FURNISHED BY ELECTRICAL CONTRACTOR SHALL BE LISTED AND LABELED BY A U.S. NATIONALLY RECOGNIZED TESTING LABORATORY. FACTORY ASSEMBLED LISTED COMPONENTS SHALL BE LISTED AND LABELED AS AN ASSEMBLY.
ANY ELECTRICAL EQUIPMENT NOT LISTED OR LABELED MUST BE APPROVED BY THE LOCAL AUTHORITY HAVING JURISDICTION AND HAVE
A THIRD PARTY TESTING LABEL.
5. FIRE ALARM APPLIANCES AND DEVICES SHOWN INDICATE TO PROVIDE COVERAGE IN THAT AREA. ELECTRICAL CONTRACTOR SHALL PROVIDE APPLIANCES AND DEVICES AS REQUIRED BY THE LATEST EDITION OF NFPA 72 AND THE BUILDING CODE. NO CHANGE ORDERS WILL BE ALLOWED FOR APPLIANCES AND DEVICES REQUIRED BY NFPA 72 AND THE BUILDING CODE.
6. COMPLETE EXISTING ELECTRICAL WORK AS INDICATED ON THE PLANS. CONNECTIONS OF FEEDERS AND BRANCH CIRCUITS TO NEW
PANELS SHALL BE DONE TO KEEP DOWNTIME TO AN ABSOLUTE MINIMUM.
7. ALL TERMINATIONS, CONDUCTORS, AND DEVICES SHALL BE 75 DEGREE C RATED.
8. UNLESS NOTED OTHERWISE, ELECTRICAL CONTRACTOR SHALL INSTALL ALL RACEWAY, BOXES, AND CABLES.
9. A MAXIMUM OF THREE 20A, 1 POLE BRANCH CIRCUITS MAY BE COMBINED IN A COMMON HOMERUN SHARING A COMMON NEUTRAL OR WITH SEPARATE NEUTRALS, FOR A TOTAL OF SIX CURRENT CARRYING CONDUCTORS. ALL BRANCH CIRCUITS LARGER THAN 20A SHALL BE
SEPARATELY HOMERUN TO PANEL.
10. CONDUCTORS SHALL BE COPPER, RATED AT NOT LESS THAN 600 VOLTS. MINIMUM SIZE SHALL BE NO. 12 AWG UNLESS OTHERWISE NOTED ON THE DRAWINGS. ALL WIRE #8 AWG AND LARGER SHALL BE STRANDED. #10 THRU #12 AWG CONDUCTORS SHALL BE SOLID. ALL
INSULATION TYPES SHALL BE THWN OR THHN.
11. ELECTRICAL CONTRACTOR SHALL USE MULTI-POLE BREAKERS FOR ALL SHARED NEUTRALS OR PROVIDE SEPARATE NEUTRALS FOR EACH
BRANCH CIRCUIT. ADJUST PANEL SCHEDULES ACCORDINGLY TO MEET NEC 210.4.
12. BRANCH CIRCUIT WIRE SIZING WILL BE IN ACCORDANCE WITH THE FOLLOWING TABLES:
13. ADJUST ELECTRONIC TRIP FUNCTIONS FOR LOW-VOLTAGE CIRCUIT BREAKERS SO AS TO ACHIEVE SELECTIVE COORDINATION.
14. LIGHTING LAYOUTS ARE BASED ON IES STANDARD RECOMMENDED LIGHTING LEVELS. LIGHT LEVELS ARE AFFECTED BY ENVIRONMENTAL CONDITIONS SUCH AS FINISH COLOR, WINDOW TREATMENTS, AND FINAL LUMINAIRE SELECTIONS. FINAL INFORMATION IS NOT ALWAYS ESTABLISHED AT THE TIME OF CALCULATION. DESIGN BASIS LIGHT LEVEL CALCULATIONS FOR SPECIFIC AREAS CAN BE PROVIDED UPON
REQUEST.
15. LEAD PAINT IS FOUND TO EXIST ON EXISTING EXPOSED PAINTED SURFACES. REFER TO ECS HAZARDOUS MATERIALS SURVEY, DATED JULY 28, 2021, PROJECT MANUAL, APPENDIX II, AND SPECIFICATION(S) 02 28 33 - LEAD-BASED PAINT REMOVAL.
16. ASBESTOS CONTAINING MATERIALS FOUND TO EXIST IN EXISTING DIRECTOR LODGE BOILER ROOM CEILING PLASTER. REFER TO ECS HAZARDOUS MATERIALS SURVEY, DATED JULY 28, 2021, PROJECT MANUAL, APPENDIX II, AND SPECIFICATION(S) 02 28 33 - LEAD-BASED
PAINT REMOVAL.
17. ELECTRICAL CONTRACTOR SHALL BE ABLE TO DEMONSTRATE RESTORATION EXPERIENCE PER THE SECRETARY OF THE INTERIOR
HISTORICAL RESTORATION STANDARDS.
USB = RECEPTACLE WITH USB CHARGING PORT.
VOICE/DATA OUTLET, WALL MOUNTED 18" AFF TO CENTER OF DEVICE. PROVIDE BACKBOX, COVERPLATE AND 3/4"C WITH PULL CORD FROM OUTLET TO AN ACCESSIBLE SPACE ABOVE THE CORRIDOR LAY-IN CEILING.
VOICE/DATA OUTLET, WALL MOUNTED 48" AFF, 2" FROM BOTTOM OF OUTLET TO BACKSPLASH. PROVIDE BACKBOX, COVERPLATE AND 3/4"C WITH PULL CORD FROM OUTLET TO AN ACCESSIBLE SPACE ABOVE THE CORRIDOR LAY-IN
CEILING.
SMOKE DETECTOR, CEILING MOUNTED.
AFF
EC
J-BOX
NEC
NL
OC
TTB
+60"
HW#
PC#
SPD
VSD
PTS
A. COORDINATE ALL DEMOLITION WORK WITH OWNER PRIOR TO BEGINNING WORK.
B. REMOVE ALL ELECTRICAL DEVICES, WIRING AND RACEWAYS IN WALLS AND CEILINGS BEING DEMOLISHED UNLESS NOTED OTHERWISE. RECONNECT DEVICES AND FIXTURES DOWNSTREAM OF REMOVED WORK.
UNLESS OTHERWISE NOTED, WIRING AND RACEWAYS ARE TO BE REMOVED BACK TO THEIR SOURCE.
C. RELOCATE EXISTING WORK TO REMAIN WHICH INTERFERES WITH RENOVATION.
D. ELECTRICAL DEMOLITION WORK SHALL BE PHASED IN ACCORDANCE WITH PROJECT "GENERAL CONDITIONS". ELECTRICAL CONTRACTOR SHALL DEVELOP A PHASING SCHEME WHICH WILL WORK WITH
THE ARCHITECT'S OVERALL PHASING PLAN AND WITH WORK TO BE DONE BY OTHER TRADES.
E. CONTRACTOR SHALL PROVIDE TEMPORARY POWER WHERE NECESSARY AT NO EXTRA COST TO THE OWNER IN ORDER TO KEEP THE BUILDING IN OPERATION DURING EACH PHASE OF THE RENOVATION.
F. REMOVE EXISTING ELECTRICAL WORK AS INDICATED. TRANSFER OF FEEDERS AND BRANCH CIRCUITS TO NEW PANELS SHALL BE DONE IN A MANNER THAT WILL KEEP DOWNTIME TO AN ABSOLUTE MINIMUM.
G. ALL OUTAGES SHALL BE COORDINATED WITH OWNER AT LEAST 72 HOURS IN ADVANCE. OUTAGES WHICH ARE ANTICIPATED TO LAST LONGER THAN 1 HOUR SHALL BE COORDINATED WITH OWNER AT LEAST 1
WEEK IN ADVANCE.
H. ELECTRICAL CONTRACTOR SHALL REMOVE ALL ELECTRICAL WORK ASSOCIATED WITH WORK INDICATED TO BE REMOVED ON THE ARCHITECTURAL, PLUMBING, MECHANICAL AND FIRE PROTECTION DRAWINGS.
I. ELECTRICAL WORK SHOWN IS BASED ON FIELD OBSERVATIONS AND EXISTING DRAWINGS AND IS
PROVIDED TO CONVEY THE GENERAL SCOPE OF DEMOLITION WORK TO BE ACCOMPLISHED. THE
ELECTRICAL CONTRACTOR SHALL VISIT THE SITE AND OBSERVE EXISTING CONDITIONS PRIOR TO
BIDDING.
J. SEE SHEET A-001 FOR ALL HAZARDOUS MATERIALS NOTES FOR THIS PROJECT.
REFER TO FIRE ALARM DRAWING SET FOR FULL LIST OF SYMBOLS AND FIRE ALARM SCOPE OF WORK.
SYMBOLS, LEGENDS, NOTES
AND DRAWING INDEX
E-001
N C A
ATIONAL
EMETERY
DMINISTRATION
Revisions Date
Drawing Title
Approved:
Approved:
Project Title
Building Number Checked Drawn
Location
Date
Project No.
DRAWING NO.
Dwg. Of
1 2 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A B
C D
E F
A B
C D
E F
© COPYRIGHT 2021, Walker Federal Services, LLC
Walker Federal Services, LLC 7820B-162 Wormans Mill Road Frederick, Maryland 21701
WFS
FACILITY RENOVATION
LONG ISLAND NATIONAL CEMETERY
815CM3041
Final Construction Documents - Issued for Construction
5838 Monroe Road, Suite 100 Charlotte, NC 28212
704 531 3000 Project No. 4624
JCE CDH
May 22, 2023
296199
AutoCAD SHX Text
PB
AutoCAD SHX Text U
AutoCAD SHX Text N
AutoCAD SHX Text I
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text S
AutoCAD SHX Text T
AutoCAD SHX Text A
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text A
AutoCAD SHX Text M
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text I
AutoCAD SHX Text C
AutoCAD SHX Text A
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text T
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text V
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text A
AutoCAD SHX Text N
AutoCAD SHX Text S
AutoCAD SHX Text A
AutoCAD SHX Text F
AutoCAD SHX Text F
AutoCAD SHX Text A
AutoCAD SHX Text I
AutoCAD SHX Text R
AutoCAD SHX Text S
AutoCAD SHX Text
PRIME CONSULTANT
AutoCAD SHX Text
CONSULTANTS
10" 1"
.625" 2"
1.125"
3 PLS
.25" DIA
12 PLS
.50" DIA
4 PLS
3.75"
.25"
COMBINATION DUPLEX
RECEPTACLE/USB CHARGER
USB CHARGING PORT
HOSPITAL GRADE 20 AMP
125 VOLT AC DUPLEX
RECEPTACLE
EQUAL TO TD HUBBELL
USB8300 SERIES
USB
TYPICAL TELECOMMUNICATIONS
GROUNDING BAR DETAILS
NOTES:
3. ALL GROUNDING BARS SHALL BE COPPER.
TGB
TELECOMMUNICATIONS GROUNDING LEGEND
ALL CONDUCTORS SHALL BE GREEN INSULATED SOLID COPPER CONDUCTORS.
TELECOMMUNICATIONS GROUND BAR MOUNTED ON BACKBOARD.TGB
SEE DETAIL.
1. TYPICAL BUSBARS, INSULATIONS AND BACKBOARD MOUNT BRACKETS
SHOWN HERE REFLECT TIA STANDARDS-COMPLIANT DIMENSIONS.
2. MOUNT BACKBOARD-MOUNTED BUSBARS AT 6'-6" AFF UNLESS DIRECTED
OTHERWISE BY OWNER.
FEATURES
PATTERN: 180 DEGREES
COVERAGE: UP TO 900 SF
TIME DELAY: ADJUSTABLE 1 TO 30 MINUTES
OPTIONS
CONTROL: MANUAL OFF, DUAL TECHNOLOGY LIGHTING CONTROL
GENERAL DESCRIPTION
HOUSING: MEDIUM IMPACT INJECTION MOLDED ABS
MOUNTING: WALL MOUNT AT 48" AFF TO CENTER OF DEVICE.
ELECTRICAL: 120 OR 277 VOLT
FINISH: MATCH FACILITY'S STANDARDS
NOM. DIMENSIONS: 119 mm X 75 mm (4 11/16" X 2 15/16")
WALL MOUNTED DUAL TECHNOLOGY
OCCUPANCY SENSOR WITH DIMMER SWITCH
CEILING HANGER
WIRE, TYP.
RECESSED
CAN
LUMINAIRE
FIXTURE WHIP FROM JUNCTION
BOX (1829mm (6') LONG MAX)
GENERAL NOTE:
1. INSTALL IN ACCORDANCE WITH MANUFACTURER'S MOUNTING INSTRUCTIONS
AND USING RECOMMENDED MOUNTING HARDWARE
DOWNLIGHT MOUNTING - LAY-IN CEILING
ACOUSTICAL
CEILING TILE
(TYP)
RECESSED CAN
LUMINAIRE
ARCHITECTURAL
CEILING GRID
LUMINAIRE SUSPENSION
WIRES REFER TO
SPECIFICATION
SECTION 26 51 00
LUMINAIRE
BAR HANGERS
ARCHITECTURAL
CEILING GRID
WIRE TIE OR SCREW
BAR HANGER TO
ARCHITECTURAL
CEILING GRID TYP.
CEILING HANGER WIRE
ARCHITECTURAL
CEILING GRID
ARCHITECTURAL
CEILING GRID
ACOUSTICAL
CEILING TILE
(TYP)
HANGER WIRE AND
MOUNTING CHANNEL
ATTACHED TO STRUCTURE
REFER TO SPECIFICATION
SECTION 26 51 00
INTEGRAL GALVANIZED LIPPED
STEEL MOUNTING CHANNEL
JUNCTION BOX
LOCKING
SQUARE
WASHER & NUT
6.35mm (1/4") SCREW
ARCHITECTURAL
CEILING
WIRE TIE THROUGH
MOUNTING CHANNEL &
CROSS BEAM, TYP.
FIXTURE WHIP FROM
JUNCTION BOX (1829mm
(6') LONG MAX)
GENERAL NOTE:
1. INSTALL IN ACCORDANCE WITH MANUFACTURER'S MOUNTING INSTRUCTIONS
AND USING THE RECOMMENDED MOUNTING HARDWARE.
EXIT SIGN MOUNTING - LAY-IN CEILING
GRID
ACOUSTICAL CEILING TILE (TYP)
ARCHITECTURAL
CEILING
GENERAL NOTE:
1. INSTALL IN ACCORDANCE WITH MANUFACTURER'S MOUNTING INSTRUCTIONS AND
USING THE RECOMMENDED MOUNTING HARDWARE.
LUMINAIRE MOUNTING - LAY-IN CEILING
LUMINAIRE
SUSPENSION
WIRES REFER TO
SPECIFICATION
SECTION 26 51 00
3 TWIST MINIMUM
(TYP)
FIXTURE WHIP FROM JUNCTION
BOX (1829mm (6') LONG MAX.)
LUMINAIRE. REFER
TO SCHEDULE
LUMINAIRE MANUFACTURER'S
MOUNTING HARDWARE. REFER TO
SPECIFICATION SECTION 26 51 00
CEILING CROSS
BEAM
LUMINAIRE. REFER TO SCHEDULE
GENERAL NOTE:
1. INSTALL IN ACCORDANCE WITH MANUFACTURER'S MOUNTING INSTRUCTIONS AND
USING THE RECOMMENDED MOUNTING HARDWARE.
DOWNLIGHT MOUNTING - GYP. BOARD CEILING
CEILING HANGER
WIRE, TYP.
RECESSED CAN
LUMINAIRE
REFER TO
SCHEDULE.
CEILING MAIN BEAM
GYPSUM
BOARD (TYP)
WIRE TIE OR SCREW
BAR HANGER TO
CROSS BEAM TYP.
LUMINAIRE
BAR HANGERS
LUMINAIRE SUSPENSION
WIRES REFER TO
SPECIFICATION
SECTION 26 51 00
CEILING CROSS
BEAM
RECESSED CAN
LUMINAIRE
CEILING BEAM
FIXTURE WHIP FROM JUNCTION
BOX (1829mm (6') LONG MAX)
GRID
IT GROUNDING BAR CABLE LUG DETAIL
A
A
Section A-A
1. RATED WALL OR FLOOR ASSEMBLY - PROVIDE FIRE STOPPING ASSEMBLY FOR
PARTITION TYPE & RATING ENCOUNTERED.
2. THROUGH PENETRATION - PROVIDE FIRE STOPPING ASSEMBLY FOR SIZE &
MATERIAL OF THROUGH PENETRATION UTILIZED.
3. FIRE STOPPING MATERIAL - PROVIDE FIRE STOPPING MATERIAL FOR WALL
ASSEMBLY & THROUGH PENETRATION MATERIAL ENCOUNTERED. FILL VOIDS OR
CAVITY ACCORDING TO THE REQUIREMENTS OF THE FIRE STOPPING SYSTEM
UTILIZED.
ALL RATED WALLS, PARTITIONS OR FLOORS SHALL BE PROVIDED WITH A UL LISTED
FIRE STOP SYSTEM. THE SYSTEM UTILIZED SHALL MATCH THE SEPARATION
PENETRATED AND THE THROUGH PENETRATION MATERIAL.
DETAILS FOR THE INSTALLATION OF SYSTEM TYPE UTILIZED SHALL BE AVAILABLE AT
THE PROJECT SITE FOR THE DURATION OF CONSTRUCTION AND SHALL BE PROVIDED
TO THE AUTHORITY HAVING JURISDICTION AND TO THE BUILDING OWNER AT THE
PROJECT COMPLETION.
PROVIDE WALL OR FLOOR LABELS INDICATING THE SYSTEM MANUFACTURER AND UL
LISTED ASSEMBLY NUMBER AT EACH LOCATION WHERE THE FIRE STOPPING SYSTEM
IS INSTALLED.
THROUGH PENETRATION FIRESTOP SYS.
(PROVIDE UL LISTED SYSTEM)
LUMINAIRE
SUSPENSION
WIRES REFER TO
SPECIFICATION
SECTION 26 51 00
3 TWIST MINIMUM
(TYP)
FIXTURE WHIP FROM JUNCTION
BOX (1829mm (6') LONG MAX.)
CEILING MAIN
BEAM
GYPSUM BOARD
(TYP)
LUMINAIRE. REFER
TO SCHEDULE
LUMINAIRE MANUFACTURER'S
MOUNTING HARDWARE. REFER TO
SPECIFICATION SECTION 26 51 00
CEILING CROSS
BEAM
GYPSUM BOARD
CEILING CROSS
BEAM
LUMINAIRE. REFER TO SCHEDULE
DRYWALL
BORDER
GENERAL NOTE:
1. INSTALL IN ACCORDANCE WITH MANUFACTURER'S MOUNTING INSTRUCTIONS AND
USING THE RECOMMENDED MOUNTING HARDWARE.
LUMINAIRE MOUNTING - GYP. BOARD CEILING
DEVICE MOUNTING DETAIL
TOP PLATE
STUDS
JUNCTION BOX ABOVE
CEILING MOUNTED ON
BRACKET, TOP PLATE,
OR BY THREADED
ROD FROM STRUCTURE.
HOMERUN
IN EMT.
EMT
CADDY STRAP.
MOUNT TO
STUDS ON BOTH
SIDES.
SWITCH OR
RECEPTACLE.
FEATURES
PATTERN: 360 DEGREES
COVERAGE: 46-186 SQ M (500-2000SF)
TIME DELAY: ADJUSTABLE 30 SECONDS TO 30 MINUTES
OPTIONS
PROVIDE DUAL RELAY IN SPACES WITH MULTIPLE SWITCHING.
CONTROL: MANUAL OFF, DUAL TECHNOLOGY LIGHTING CONTROL
GENERAL DESCRIPTION
HOUSING: IMPACT RESISTANT INJECTION MOLDED ABS
MOUNTING: CEILING BETWEEN 2440-3050 mm (8'-10') H
ELECTRICAL: 24 VOLT DC (FROM POWER PACK), 120 OR 277
VOLT AC
INPUT
FINISH: MATCH FACILITY'S STANDARDS
NOM. DIMENSIONS: 121 mm X 102 mm (4 3/4" DIA X 4"D)
CEILING MOUNTED DUAL TECHNOLOGY
OCCUPANCY SENSOR
EXIT
12", UNLESS CEILING IS HIGHER
THAN 12'-0", THEN 24" ABOVE DOOR.
CEILING
FLOOR
WALL MOUNTED
TELEPHONE
2" TO
TOP OF
COUNTER OR
BACKSPLASH
18"
RECEPTACLE
LIGHT SWITCH
OR DIMMER
ALIGN WHERE
POSSIBLE
TELEPHONE OR
VOICE DATA OUTLET
TV OUTLET
OR CLOCK
OUTLET
FIRE ALARM DEVICES
" A
BO
VE
F
LO
O R
T O
B O
TT
O
M O
F D
EV
IC
E O
N C
O
LU
M N
S
MOUNTING HEIGHTS OF DEVICES
FOR WALL MOUNTED UNITS:
BOTTOM
OF DEVICE
N O
T
TO
E
XC
EE
D
6"
T O
B O
TT
O
M
GENERAL DETAIL NOTES:
A. PARTICULAR ATTENTION SHALL BE GIVEN TO THE ALIGNMENT OF DEVICES.
WHEREVER DEVICES, ON THIS SHEET OR OTHER SHEETS, ARE SHOWN AT
GIVEN LOCATION WITH DIFFERENT MOUNTING HEIGHTS THEY SHALL BE
ALIGNED VERTICALLY. IF THEY ARE SHOWN AT THE SAME MOUNTING HEIGHT
THEY SHALL BE ALIGNED HORIZONTALLY. REFER TO THE ARCHITECTURAL
PLANS, ELEVATIONS AND DETAILS. COORDINATE WITH ARCHITECT PRIOR TO
ROUGH-IN.
B. ALL DIMENSIONS ARE TO THE CENTER LINE OF DEVICE UNLESS INDICATED
OTHERWISE.
C. MOUNTING HEIGHTS SHOWN HERE ARE TYPICAL. PRIOR TO ROUGH-IN,
COORDINATE WITH ARCHITECTURAL PLANS, ELEVATIONS, AND DETAILS. IF A
CONFLICT OCCURS, REQUEST CLARIFICATION FROM ARCHITECT/ENGINEER
PRIOR TO ROUGH-IN.
6"
NAMEPLATE DETAIL
NORMAL
BRANCH
PANEL 'X'
208Y/120V
ENGRAVED THREE-LAYER LAMINATED
PLASTIC WITH ADHESIVE BACKING
PROVIDE ALL ELECTRICAL DISTRIBUTION EQUIPMENT WITH A NAMEPLATE AS
FOLLOWS: (SWITCHBOARDS, PANELBOARDS, BUSWAYS, DISCONNECTS, AHU,
FANS, FCU, ETC)
1/4" LETTERING
(TYPICAL)
WHITE LETTERS ON BLACK BACKGROUND
WHITE LETTERS ON RED BACKGROUND
WHITE LETTERS ON RED BACKGROUND
WHITE LETTERS ON RED BACKGROUND
NORMAL:
LIFE SAFETY:
CRITICAL:
EQUIPMENT:
3/8" LETTERING
GENERAL DETAIL NOTES:
A. PROVIDE SAMPLE FOR APPROVAL BY ENGINEERS/OWNER.
B. COORDINATE NAMING CONVENTION AND DESCRIPTIONS WITH OWNER.
SOURCE
VOLTAGE
BRANCH
NAME OF
EQUIPMENT
OR LOAD
LOCATION
FED FROM PANEL 'MDP'
LOCATED IN F-WING
4TH FLR ELECTRICAL RM
7FCL-37FCL-1
DEVICE LABELING DETAIL
PROVIDE ALL WIRING DEVICES WITH A SELF-
ADHESIVE METALLIC LABEL WITH BLACK
LETTERING INDICATING PANEL AND CIRCUIT
NUMBER SERVING THE DEVICE. THE LABEL
SHALL MATCH THE CURRENT FACILITY'S
STANDARDS FOR NORMAL AND EMERGENCY
BRANCH CIRCUITS. 1/4 " MINIMUM LETTERING
HEIGHT.
GENERAL DETAIL NOTES:
A. COORDINATE LABELING WITH OWNER PRIOR TO INSTALLATION.
NTS 5
NTS
NTS
NTS
NTS
NTS 9
NTS 8NTS 12
NTS 13
NTS
NTS 15
NTS 17
NTS 1NTS 16
NTS
T
N
DEVICE LEGEND:
LIGHT SWITCH
RECEPTACLE
VOICE/DATA OUTLET
NURSE CALL DEVICES
THERMOSTAT
RECEPTACLE GROUNDING BOX DETAIL
METALLIC
BOXCONDUIT
CONDUIT
BUSHING
GROUNDING
SCREW
"GREEN"
GROUND
WIRE
NTS
PLASTIC
THROAT
BUSHING
GROUND WIRE
SURGE PROTECTIVE DEVICE (SPD) INSTALLATION 4
GENERAL NOTE:
1. LOCATE THE SPD AS CLOSE TO THE PANELBOARD BEING PROTECTED AS POSSIBLE.
2. MINIMIZE THE LENGTHS OF THE CONDUCTORS TO THE CIRCUIT BREAKER AND THE
NEUTRAL BUS, KEEPING ALL CONDUCTORS AS SHORT AS POSSIBLE AND CLOSE TO
THE SAME LENGTH.
3. LOCATE CIRCUIT BREAKER FOR THE SPD AS CLOSE TO THE MAIN CIRCUIT BREAKER,
OR MAIN LUGS, AS POSSIBLE.
4. USE STRANDED CONDUCTORS, IF RECOMMENDED BY THE MANUFACTURERS, TO
CONNECT TO THE SPD. AVOID SHARP BENDS, SHORT DIRECT CONNECTIONS ARE
PREFERRED.
PANELBOARD
SURGE PROTECTIVE DEVICE (SPD)
CHASE NIPPLE
MAIN CIRCUIT
BREAKER OR
MAIN LUGS
3 POLE
BRANCH
CIRCUIT
BREAKER
NEUTRAL BUS
GROUND BUS
BRANCH CIRCUIT
CONDUCTORS
ELECTRICAL - DETAILS
E-002
N C A
ATIONAL
EMETERY
DMINISTRATION
Revisions Date
Drawing Title
Approved:
Approved:
Project Title
Building Number Checked Drawn
Location
Date
Project No.
DRAWING NO.
Dwg. Of
1 2 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A B
C D
E F
A B
C D
E F
© COPYRIGHT 2021, Walker Federal Services, LLC
Walker Federal Services, LLC 7820B-162 Wormans Mill Road Frederick, Maryland 21701
WFS
FACILITY RENOVATION
LONG ISLAND NATIONAL CEMETERY
815CM3041
Final Construction Documents - Issued for Construction
5838 Monroe Road, Suite 100 Charlotte, NC 28212
704 531 3000 Project No. 4624
JCE CDH
May 22, 2023
296200
AutoCAD SHX Text U
AutoCAD SHX Text N
AutoCAD SHX Text I
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text S
AutoCAD SHX Text T
AutoCAD SHX Text A
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text A
AutoCAD SHX Text M
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text I
AutoCAD SHX Text C
AutoCAD SHX Text A
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text T
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text V
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text A
AutoCAD SHX Text N
AutoCAD SHX Text S
AutoCAD SHX Text A
AutoCAD SHX Text F
AutoCAD SHX Text F
AutoCAD SHX Text A
AutoCAD SHX Text I
AutoCAD SHX Text R
AutoCAD SHX Text S
AutoCAD SHX Text
PRIME CONSULTANT
A
C
A C
A A
A
B
A
C
C
C
A A
CADWELD MOLD DETAIL
6 SCALE: NOT TO SCALE11
EXPOSED DOWNLEAD DETAIL
SCALE: NOT TO SCALE
12 SCALE: NOT TO SCALE
PVC CABLE GUARD SCALE: NOT TO SCALE
THRU-ROOF PENETRATION
SCALE: NOT TO SCALE
CADWELD MOLD - TA
MISCELLANEOUS
SCALE: NOT TO SCALE10
SCALE: NOT TO SCALE
THRU-ROOF CONNECTION
AIR TERMINAL
SCALE: NOT TO SCALE
TYPICAL DOWNLEAD DETAIL
SCALE: NOT TO SCALE5
TYPICAL DOWNLEAD DETAIL
SCALE: NOT TO SCALE1
CLASS I COPPER
LIGHTNING CONDUCTOR
AIR TERMINAL
SCALE: NOT TO SCALE
AIR TERMINAL
2 SCALE: NOT TO SCALE
AIR TERMINAL
SCALE: NOT TO SCALE3
AIR TERMINAL
SCALE: NOT TO SCALE
NOTE: ALL DETAILS MAY NOT APPLY TO THIS PROJECT.
3M VHB TAPE
SELF CONTAINED
STAINLESS STEEL NUT
AND LOCK WASHER
3M VHB TAPE
3M VHB TAPE
SELF CONTAINED
STAINLESS STEEL NUT
AND LOCK WASHER
SELF CONTAINED
STAINLESS STEEL NUT
AND LOCK WASHER
All fasteners shall have appropriate loop supports. No support penetrations shall be made in any sheet metal flashing or roof top equipment. Sheet metal screws shall not be used. Appropriate adhesive supports and construction mastic may be used on Membrane roof surfaces only.
Adhesive supports and construction mastic shall not be used on any sheet metal surfaces.
The contractor shall furnish 10 Year Adhesion Warranty on the fastener system.
1/2" X 12"
COPPER SAFETY TIPPED
AIR TERMINAL
COPPER
CABLE CLIP FASTENING SYSTEM
CLASS I
ALUMINUM MAIN CONDUCTOR
COPPER UNIVERSAL LIGHTNING ROD MOUNT
ASSEMBLY, SECURE WITH ADHESIVE
1/2" X 12"
COPPER SAFETY TIPPED
AIR TERMINAL
COPPER
ADHESIVE CABLE FASTENER
CLASS I
COPPER MAIN CONDUCTOR
COPPER 8"
SURFACE BONDING PLATE
UNIVERSAL LIGHTNING
ROD MOUNT ASSEMBLY
1/2" GALVANIZED STEEL TRIPOD
BASE
1/2" X 48"
COPPER AIR TERMINAL
COPPER ONE HOLE CABLE
STRAP
COPPER PIPE CLAMP
U-BOLT GROUND
ROD CLAMP
COPPER
CLASS I CONDUCTOR
COPPER U
BOLT CLAMP BASE
1/2" X 12"
COPPER SAFETY TIPPED
AIR TERMINAL
2 SCREW STANDING
SEAM SUPPORT
COPPER
CABLE CLIP
1/2" x 18"
COPPER CONCEALED BASE
CLASS I COPPER MAIN
CONDUCTOR
1/2" X 12" UNIVERSAL AIR
TERMINAL
SWIVEL ADAPTER, 1/2" TO 1/2"
UNIVERSAL PARALLEL CABLE SPLICER ASSEMBLY
USE TO SPLICE MAIN
SIZE CONDUCTOR TO
MAIN SIZE CONDUCTOR
BRONZE PARALLEL CLAMP
BRONZE CABLE TO FLAT
METAL CLAMP
CLASS I COPPER MAIN
CONDUCTOR
1" PVC CONDUIT
BRONZE
FLANGE BONDING
PLATE
1" PVC CONDUIT
CLASS I
COPPER MAIN CONDUCTOR
CLASS I
COPPER MAIN CONDUCTOR
BI-METAL
THRU-ROOF CONNECTOR
CLASS I
ALUMINUM MAIN CONDUCTOR
BRONZE
CROSS-RUN CABLE
CONNECTOR
BRONZE
FLANGE BONDING PLATE
BI-METAL
CONNECTOR
HEAVY
DUTY BONDING LUG
COPPER PIPE CLAMP
BONDING LUG
CABLE TO
FLAT METAL CLAMP
STRAP
TYPE PIPE CLAMP
COPPER
FLAT BONDING PLATE
COPPER
BONDING PLATE
GENERAL INSTALLATION NOTES
FINAL SYSTEM INSPECTION AND QUALITY CONTROL
CADWELD MOLD
CABLE TO CABLE CONNECTION
CLASS I
COPPER MAIN CONDUCTOR
CLASS I MAIN
CONDUCTOR COPPER
CLASS I MAIN
CONDUCTOR COPPER
FLANGE
BONDING PLATE
THRU-ROOF
ASSEMBLYCLASS I
COPPER MAIN CONDUCTOR
CLASS I
ALUMINUM MAIN CONDUCTOR
BI-METAL
CONNECTOR
PVC
CABLE GUARD
CLASS I
COPPER MAIN CONDUCTOR
PIPE GROUNDING
CLAMP
CLASS I COPPER
MAIN SIZE CONDUCTOR
BI-METAL
CONNECTOR
CLASS I
COPPER MAIN CONDUCTOR
CLASS I
COPPER MAIN CONDUCTOR
CADWELD MOLD
CABLE TO CABLE CONNECTION
CLASS I
COPPER MAIN CONDUCTOR
CADWELD MOLD
3/4" X 10 COPPER CLAD
GROUND ROD
AIR TERMINAL
MECHANICAL CONNECTION
MISC. BONDING
THRU-ROOF CONNECTOR
CLASS I ALUMINUM MAIN CONDUCTOR
CLASS I COPPER MAIN CONDUCTOR
COPPER CLAD GROUND ROD
WITH ULTRAWELD CONNECTION
TR
LEGEND
LOCATE AIR TERMINALS AS SHOWN. ENSURE THAT ALL
POINTS ARE WITHIN 2'-0" (609mm) OF OUTSIDE BUILDING
EDGE, OUTSIDE CORNERS, RIDGE ENDS, AND THAT MAX
SPACING DOES NOT EXCEED 20'-0" (6,096mm), AND THAT MIN PROJECTION ABOVE OBJECT PROTECTED IS 10" (254mm);
POINTS PROJECTING 24" (609mm) MAY BE SPACED @ 25'-0" (7,520mm) MAX.
MAINTAIN HORIZONTAL OR DOWNWARD COURSING OF MAIN
CONDUCTOR. INSURE THAT ALL BENDS HAVE AT LEAST AN 8"
(203mm) RADIUS AND DO NOT EXCEED 90 DEGREES.
ATTACH ALL EXPOSED ROOF, DOWN LEAD AND BONDING CABLES
AT 3'-0" (914mm) ON CENTER MAX. VERIFY COMPATIBILITY OF
ADHESIVE ON MEMBRANE ROOF APPLICATION PRIOR TO
INSTALLATION.
GROUND ELECTRODES SHALL BE INSTALLED AS REQUIRED.
THEY SHALL NOT BE LESS THAN 1'-0" (304mm) BELOW GRADE AND 2'-0" (609mm) FROM FOUNDATION WALL. DRIVEN RODS SHALL PENETRATE THE EARTH AT LEAST 10'-0" (3,048mm).
BOND TO WATER SERVICE AND OTHER PIPING SYSTEMS AS
REQUIRED.
MAIN SIZE LIGHTNING CONDUCTOR BONDED TO MAIN GROUND
BUS FIELD. VERIFY LOCATION. PROVIDE 1" CONDUIT FOR
ACCESS. INTERCONNECT LIGHTNING PROTECTION GROUND TO
TELEPHONE AND OTHER BUILDING GROUND SYSTEMS LOCATION
FIELD. DETERMINE OR AS REQUIRED BY CODE.
SYSTEM SHALL BE INSTALLED AS TO ENSURE PROPER CODE
COMPLIANCE AND SYSTEM CERTIFICATION. SHOP DRAWINGS
SHALL BE SUBMITTED FOR APPROVAL.
ALL MATERIALS SHALL BE UNDERWRITER'S LABORATORIES
APPROVED WITH "A" LABELS ON CONDUCTORS @ 10'-0"
INTERVALS AND "B" LABELS ON ALL AIR TERMINALS.
A) THE CONTRACTOR SHALL FURNISH AN LPI-IP
CERTIFICATE OR A UL CERTIFICATE UPON COMPLETION
OF THE INSTALLATION.
B) LPI CERTIFICATION REQUIRES A SIGNATURE BY A
REPRESENTATIVE OF THE OWNER AT MULTIPLE
STAGES OF INSTALLATION & BY THEIR THIRD PARTY
FIELD STAFF. UL CERTIFICATION REQUIRES INSPECTION
BY THEIR THIRD-PARTY FIELD STAFF AFTER
COMPLETION OF THE INSTALLATION.
C) AS-BUILT DRAWINGS SHALL BE COMPLETED AND
STAMPED BY AN LPI CERTIFIED MASTER DESIGNER
- INSTALLER OF LIGHTNING PROTECTION
SYSTEMS.
D) FINAL INSPECTION REPORT - A FINAL INSPECTION AND
INSPECTION REPORT SHALL BE COMPLETED BASED ON
ANSI/TIA/EIA 607, NEC, NFPA 780, AND UL96A
INDUSTRY STANDARDS AS APPLICABLE. THE SCOPE OF
THE INSPECTION AND REPORT SHALL INCLUDE;
a. TEST AND EVALUATION THE GROUNDING SYSTEM.
RECORD FINAL SYSTEMS TO GROUND RESISTANCE
LEVEL.
b. EVALUATION AND TESTING OF THE INTERNAL
BONDING AND GROUNDING SYSTEMS.
c. EVALUATION AND TESTING OF EQUIPMENT
GROUNDING.
d. EVALUATION OF AC SURGE SUPPRESSION
INSTALLATION.
e. EVALUATION OF TELCO SURGE SUPPRESSION
INSTALLATION.
f. COPY OF THE LPI-IP LIGHTNING PROTECTION
CERTIFICATION.
g. FINAL AS-BUILT REVIEW AND SUBMISSION.
E) REPORT SHALL INCLUDE DETAILED REPORTING AND
TEST RESULTS WITH CORRESPONDING PHOTOS OF
EACH EVALUATION CATEGORY.
ELECTRICAL - DETAILS
LIGHTNING
E-003
N C A
ATIONAL
EMETERY
DMINISTRATION
Revisions Date
Drawing Title
Approved:
Approved:
Project Title
Building Number Checked Drawn
Location
Date
Project No.
DRAWING NO.
Dwg. Of
1 2 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A B
C D
E F
A B
C D
E F
© COPYRIGHT 2021, Walker Federal Services, LLC
Walker Federal Services, LLC 7820B-162 Wormans Mill Road Frederick, Maryland 21701
WFS
FACILITY RENOVATION
LONG ISLAND NATIONAL CEMETERY
815CM3041
Final Construction Documents - Issued for Construction
5838 Monroe Road, Suite 100 Charlotte, NC 28212
704 531 3000 Project No. 4624
JCE CDH
May 22, 2023
296201
AutoCAD SHX Text
6'-0" MIN.
AutoCAD SHX Text
12" MIN. BELOW FINISH GRADE
AutoCAD SHX Text U
AutoCAD SHX Text N
AutoCAD SHX Text I
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text S
AutoCAD SHX Text T
AutoCAD SHX Text A
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text A
AutoCAD SHX Text M
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text I
AutoCAD SHX Text C
AutoCAD SHX Text A
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text T
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text V
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text A
AutoCAD SHX Text N
AutoCAD SHX Text S
AutoCAD SHX Text A
AutoCAD SHX Text F
AutoCAD SHX Text F
AutoCAD SHX Text A
AutoCAD SHX Text I
AutoCAD SHX Text R
AutoCAD SHX Text S
AutoCAD SHX Text
PRIME CONSULTANT
PANEL
"DLB-1"
200A MCB
208/120V
3PH 4W
(NEW)
BOILER
PANEL
"DLB-2"
100A MCB
120/208V
1PH 3W
(NEW)
SPD
3PH 4W
(NEW)
BASEMENT 4
DIRECTOR'S LODGE
BUILDING 2001 #2
PANEL
"DL1-1"
30A MCB
120/208V
1PH 3W
(NEW)
BASEMENT LEVEL
GROUND FLOOR
PANEL
"MDP"
400A
208/120V
3PH
(EXISTING TO
REMAIN)
ADMINISTRATION
BUILDING
MECHANICAL
ROOM
122 POWER RISER LEGEND
NEW
DEMO
EXISTING
LOBBY 2
20Y
30Y
50Y
60Y
80Y
100Y
125Y
150Y
175Y
200Y
225Y
250Y
300Y
400Y
500Y
600Y
800Y
1000Y
4 #12, 1#12 G, 3/4" C.
4 #10, 1#10 G, 3/4" C.
4 #6, 1#10 G, 1 1/4" C.
4 #2, 1#8 G, 1 1/2" C.
4 #4, 1#8 G, 1 1/4" C.
4 #6, 1#10 G, 1" C.
4 #1, 1#6 G, 2" C.
4 #1/0, 1#6 G, 2" C.
4 #2/0, 1#6 G, 2" C.
4 #3/0, 1#6 G, 2" C.
4 #4/0, 1#4 G, 2 1/2" C.
4-250 MCM, 1#4 G, 2 1/2" C.
4-350 MCM, 1#4 G, 3" C.
4-500 MCM, 1#3 G, 3 1/2"C.
2 SETS: 4-250 MCM, 1#2 G, 2 1/2" C.
2 SETS: 4-350 MCM, 1#1 G, 3" C.
2 SETS: 4-500 MCM, 1#1/0 G, 3" C.
3 SETS: 4-400 MCM, 1#2/0 G, 3" C.
BRANCH CIRCUIT AND FEEDER SCHEDULE
3-PHASE CIRCUITS + NEUTRAL + GROUND
SYMBOL
NOTE: ALL CONDUCTORS ARE COPPER, THWN / THHN.
MINIMUM SIZE CONDUCTORS AND CONDUITS
3-PHASE CIRCUITS (NO NEUTRAL) + GROUND
3 #12, 1#12 G, 3/4" C.
3 #10, 1#10 G, 3/4" C.
3 #6, 1#10 G, 1" C.
3 #6, 1#10 G, 1" C.
3 #2, 1#8 G, 1 1/2" C.
3 #4, 1#8 G, 1" C.
3 #1, 1#6 G, 2" C.
3 #1/0, 1#6 G, 2" C.
3 #2/0, 1#6 G, 2" C.
3 #3/0, 1#6 G, 2" C.
3 #4/0, 1#4 G, 2 1/2" C.
3-250 MCM, 1#4 G, 2 1/2" C.
3-350 MCM, 1#4 G, 3" C.
3-500 MCM, 1#3 G, 3"C.
2 SETS: 3-250 MCM, 1#2 G, 2 1/2" C.
2 SETS: 3-350 MCM, 1#1 G, 3" C.
2 SETS: 3-500 MCM, 1#1/0 G, 3" C.
3 SETS: 3-400 MCM, 1#2/0 G, 3" C.
BRANCH CIRCUIT AND FEEDER SCHEDULE
NOTE: ALL CONDUCTORS ARE COPPER, THWN / THHN.
SYMBOL MINIMUM SIZE CONDUCTORS AND CONDUITS
KITCHEN
PANEL
"DL1-1"
30A MCB
120/208V
1PH 3W
(DEMO)
3#10, 1#10, ¾"C
3#2, 1#8, 1-½"C
3#12, 1#12, ¾"C
POWER RISER DIAGRAM
EXISTING TO REMAIN.
RECONNECT AND
EXTEND AS NEEDED
ELECTRICAL - LUMINAIRE
SCHEDULE & RISER DIAGRAM
DIRECTOR'S LODGE
E-004
ALL SURGE PROTECTION DEVICES SHALL BE REPLACED UNDER THIS
SCOPE OF WORK.
NEW WORK KEYED NOTES
N C A
ATIONAL
EMETERY
DMINISTRATION
Revisions Date
Drawing Title
Approved:
Approved:
Project Title
Building Number Checked Drawn
Location
Date
Project No.
DRAWING NO.
Dwg. Of
1 2 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A B
C D
E F
A B
C D
E F
© COPYRIGHT 2021, Walker Federal Services, LLC
Walker Federal Services, LLC 7820B-162 Wormans Mill Road Frederick, Maryland 21701
WFS
FACILITY RENOVATION
LONG ISLAND NATIONAL CEMETERY
815CM3041
Final Construction Documents - Issued for Construction
5838 Monroe Road, Suite 100 Charlotte, NC 28212
704 531 3000 Project No. 4624
JCE CDH
May 22, 2023
296202
AutoCAD SHX Text U
AutoCAD SHX Text N
AutoCAD SHX Text I
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text S
AutoCAD SHX Text T
AutoCAD SHX Text A
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text A
AutoCAD SHX Text M
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text I
AutoCAD SHX Text C
AutoCAD SHX Text A
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text T
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text V
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text A
AutoCAD SHX Text N
AutoCAD SHX Text S
AutoCAD SHX Text A
AutoCAD SHX Text F
AutoCAD SHX Text F
AutoCAD SHX Text A
AutoCAD SHX Text I
AutoCAD SHX Text R
AutoCAD SHX Text S
AutoCAD SHX Text
PRIME CONSULTANT
20Y
30Y
50Y
60Y
80Y
100Y
125Y
150Y
175Y
200Y
225Y
250Y
300Y
400Y
500Y
600Y
800Y
1000Y
4 #12, 1#12 G, 3/4" C.
4 #10, 1#10 G, 3/4" C.
4 #6, 1#10 G, 1 1/4" C.
4 #2, 1#8 G, 1 1/2" C.
4 #4, 1#8 G, 1 1/4" C.
4 #6, 1#10 G, 1" C.
4 #1, 1#6 G, 2" C.
4 #1/0, 1#6 G, 2" C.
4 #2/0, 1#6 G, 2" C.
4 #3/0, 1#6 G, 2" C.
4 #4/0, 1#4 G, 2 1/2" C.
4-250 MCM, 1#4 G, 2 1/2" C.
4-350 MCM, 1#4 G, 3" C.
4-500 MCM, 1#3 G, 3 1/2"C.
2 SETS: 4-250 MCM, 1#2 G, 2 1/2" C.
2 SETS: 4-350 MCM, 1#1 G, 3" C.
2 SETS: 4-500 MCM, 1#1/0 G, 3" C.
3 SETS: 4-400 MCM, 1#2/0 G, 3" C.
BRANCH CIRCUIT AND FEEDER SCHEDULE
3-PHASE CIRCUITS + NEUTRAL + GROUND
SYMBOL
NOTE: ALL CONDUCTORS ARE COPPER, THWN / THHN.
MINIMUM SIZE CONDUCTORS AND CONDUITS
3-PHASE CIRCUITS (NO NEUTRAL) + GROUNDING
3 #12, 1#12 G, 3/4" C.
3 #10, 1#10 G, 3/4" C.
3 #6, 1#10 G, 1" C.
3 #6, 1#10 G, 1" C.
3 #2, 1#8 G, 1 1/2" C.
3 #4, 1#8 G, 1" C.
3 #1, 1#6 G, 2" C.
3 #1/0, 1#6 G, 2" C.
3 #2/0, 1#6 G, 2" C.
3 #3/0, 1#6 G, 2" C.
3 #4/0, 1#4 G, 2 1/2" C.
3-250 MCM, 1#4 G, 2 1/2" C.
3-350 MCM, 1#4 G, 3" C.
3-500 MCM, 1#3 G, 3"C.
2 SETS: 3-250 MCM, 1#2 G, 2 1/2" C.
2 SETS: 3-350 MCM, 1#1 G, 3" C.
2 SETS: 3-500 MCM, 1#1/0 G, 3" C.
3 SETS: 3-400 MCM, 1#2/0 G, 3" C.
BRANCH CIRCUIT AND FEEDER SCHEDULE
NOTE: ALL CONDUCTORS ARE COPPER, THWN / THHN.
SYMBOL MINIMUM SIZE CONDUCTORS AND CONDUITS
PANEL "PIC-1 "
150A MCB
120/208V
3PH 4W
PUBLIC INFORMATION
CENTER
BUILDING 1002 NO. 4
SPD
120/208V
3PH
BASEMENT
LEVEL
BASEMENT
POWER RISER LEGEND
NEW
DEMO
EXISTING
NEW NEW
METER
(EXISTING
TO
REMAIN)
ELECTRICAL - LUMINAIRE
SCHEDULE & RISER DIAGRAM
PUBLIC INFORMATION CENTER
E-005
ALL SURGE PROTECTION DEVICES SHALL BE REPLACED UNDER THIS
SCOPE OF WORK.
WIRE AND CONDUIT FEEDING THE PUBLIC INFORMATION CENTER IS
EXISTING TO REMAIN.
NEW WORK KEYED NOTES
N C A
ATIONAL
EMETERY
DMINISTRATION
Revisions Date
Drawing Title
Approved:
Approved:
Project Title
Building Number Checked Drawn
Location
Date
Project No.
DRAWING NO.
Dwg. Of
1 2 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A B
C D
E F
A B
C D
E F
© COPYRIGHT 2021, Walker Federal Services, LLC
Walker Federal Services, LLC 7820B-162 Wormans Mill Road Frederick, Maryland 21701
WFS
FACILITY RENOVATION
LONG ISLAND NATIONAL CEMETERY
815CM3041
Final Construction Documents - Issued for Construction
5838 Monroe Road, Suite 100 Charlotte, NC 28212
704 531 3000 Project No. 4624
JCE CDH
May 22, 2023
AutoCAD SHX Text U
AutoCAD SHX Text N
AutoCAD SHX Text I
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text S
AutoCAD SHX Text T
AutoCAD SHX Text A
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text A
AutoCAD SHX Text M
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text I
AutoCAD SHX Text C
AutoCAD SHX Text A
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text T
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text V
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text A
AutoCAD SHX Text N
AutoCAD SHX Text S
AutoCAD SHX Text A
AutoCAD SHX Text F
AutoCAD SHX Text F
AutoCAD SHX Text A
AutoCAD SHX Text I
AutoCAD SHX Text R
AutoCAD SHX Text S
AutoCAD SHX Text
PRIME CONSULTANT
50Y
60Y
80Y
100Y
125Y
150Y
175Y
200Y
225Y
250Y
300Y
400Y
500Y
600Y
800Y
1000Y
4 #12, 1#12 G, 3/4" C.
4 #10, 1#10 G, 3/4" C.
4 #6, 1#10 G, 1 1/4" C.
4 #2, 1#8 G, 1 1/2" C.
4 #4, 1#8 G, 1 1/4" C.
4 #6, 1#10 G, 1" C.
4 #1, 1#6 G, 2" C.
4 #1/0, 1#6 G, 2" C.
4 #2/0, 1#6 G, 2" C.
4 #3/0, 1#6 G, 2" C.
4 #4/0, 1#4 G, 2 1/2" C.
4-250 MCM, 1#4 G, 2 1/2" C.
4-350 MCM, 1#4 G, 3" C.
4-500 MCM, 1#3 G, 3 1/2"C.
2 SETS: 4-250 MCM, 1#2 G, 2 1/2" C.
2 SETS: 4-350 MCM, 1#1 G, 3" C.
2 SETS: 4-500 MCM, 1#1/0 G, 3" C.
3 SETS: 4-400 MCM, 1#2/0 G, 3" C.
BRANCH CIRCUIT AND FEEDER SCHEDULE
3-PHASE CIRCUITS + NEUTRAL + GROUND
SYMBOL
NOTE: ALL CONDUCTORS ARE COPPER, THWN / THHN.
MINIMUM SIZE CONDUCTORS AND CONDUITS
3-PHASE CIRCUITS (NO NEUTRAL) + GROUNDING
3 #12, 1#12 G, 3/4" C.
3 #10, 1#10 G, 3/4" C.
3 #6, 1#10 G, 1" C.
3 #6, 1#10 G, 1" C.
3 #2, 1#8 G, 1 1/2" C.
3 #4, 1#8 G, 1" C.
3 #1, 1#6 G, 2" C.
3 #1/0, 1#6 G, 2" C.
3 #2/0, 1#6 G, 2" C.
3 #3/0, 1#6 G, 2" C.
3 #4/0, 1#4 G, 2 1/2" C.
3-250 MCM, 1#4 G, 2 1/2" C.
3-350 MCM, 1#4 G, 3" C.
3-500 MCM, 1#3 G, 3"C.
2 SETS: 3-250 MCM, 1#2 G, 2 1/2" C.
2 SETS: 3-350 MCM, 1#1 G, 3" C.
2 SETS: 3-500 MCM, 1#1/0 G, 3" C.
3 SETS: 3-400 MCM, 1#2/0 G, 3" C.
BRANCH CIRCUIT AND FEEDER SCHEDULE
NOTE: ALL CONDUCTORS ARE COPPER, THWN / THHN.
SYMBOL MINIMUM SIZE CONDUCTORS AND CONDUITS
PANEL PR
100A MCB
120/208V
3PH 4W
(NEW;
REPLACEMENT)
PUBLIC
RESTROOM
GROUND
FLOOR
MECHANICAL
ROOM
METER
(EXISTING
TO
REMAIN)
SPD
3PH 4W
(NEW)
POWER RISER LEGEND
NEW
DEMO
EXISTING
ELECTRICAL - LUMINAIRE
SCHEDULE & RISER DIAGRAM
PUBLIC RESTROOM
E-006
LOCATE SURGE PROTECTIVE DEVICE (SPD) ADJACENT TO
PANELBOARD AND CLOSE TO BOTH CIRCUIT BREAKER AND NEUTRAL
BUS TO MINIMIZE LEAD LENGTH.
WIRE AND CONDUIT FEEDING THE BUILDING IS EXISTING TO REMAIN.
EXISTING PANELBOARD IS TO BE REMOVED AND REPLACED. REFER TO
NEW PANELBOARD SCHEDULE ON THIS SHEET. EXTEND EXISTING
FEEDER AS REQUIRED, MATCHING EXISTING IN ALL CHARACTERISTICS.
(E) - EXISTING
NEW WORK KEYED NOTES
N C A
ATIONAL
EMETERY
DMINISTRATION
Revisions Date
Drawing Title
Approved:
Approved:
Project Title
Building Number Checked Drawn
Location
Date
Project No.
DRAWING NO.
Dwg. Of
1 2 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A B
C D
E F
A B
C D
E F
© COPYRIGHT 2021, Walker Federal Services, LLC
Walker Federal Services, LLC 7820B-162 Wormans Mill Road Frederick, Maryland 21701
WFS
FACILITY RENOVATION
LONG ISLAND NATIONAL CEMETERY
815CM3041
Final Construction Documents - Issued for Construction
5838 Monroe Road, Suite 100 Charlotte, NC 28212
704 531 3000 Project No. 4624
JCE CDH
May 22, 2023
LEGEND
AutoCAD SHX Text U
AutoCAD SHX Text N
AutoCAD SHX Text I
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text S
AutoCAD SHX Text T
AutoCAD SHX Text A
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text A
AutoCAD SHX Text M
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text I
AutoCAD SHX Text C
AutoCAD SHX Text A
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text T
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text V
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text A
AutoCAD SHX Text N
AutoCAD SHX Text S
AutoCAD SHX Text A
AutoCAD SHX Text F
AutoCAD SHX Text F
AutoCAD SHX Text A
AutoCAD SHX Text I
AutoCAD SHX Text R
AutoCAD SHX Text S
AutoCAD SHX Text
PRIME CONSULTANT
50Y
60Y
80Y
100Y
125Y
150Y
175Y
200Y
225Y
250Y
300Y
400Y
500Y
600Y
800Y
1000Y
4 #12, 1#12 G, 3/4" C.
4 #10, 1#10 G, 3/4" C.
4 #6, 1#10 G, 1 1/4" C.
4 #2, 1#8 G, 1 1/2" C.
4 #4, 1#8 G, 1 1/4" C.
4 #6, 1#10 G, 1" C.
4 #1, 1#6 G, 2" C.
4 #1/0, 1#6 G, 2" C.
4 #2/0, 1#6 G, 2" C.
4 #3/0, 1#6 G, 2" C.
4 #4/0, 1#4 G, 2 1/2" C.
4-250 MCM, 1#4 G, 2 1/2" C.
4-350 MCM, 1#4 G, 3" C.
4-500 MCM, 1#3 G, 3 1/2"C.
2 SETS: 4-250 MCM, 1#2 G, 2 1/2" C.
2 SETS: 4-350 MCM, 1#1 G, 3" C.
2 SETS: 4-500 MCM, 1#1/0 G, 3" C.
3 SETS: 4-400 MCM, 1#2/0 G, 3" C.
BRANCH CIRCUIT AND FEEDER SCHEDULE
3-PHASE CIRCUITS + NEUTRAL + GROUND
SYMBOL
NOTE: ALL CONDUCTORS ARE COPPER, THWN / THHN.
MINIMUM SIZE CONDUCTORS AND CONDUITS
3-PHASE CIRCUITS (NO NEUTRAL) + GROUNDING
3 #12, 1#12 G, 3/4" C.
3 #10, 1#10 G, 3/4" C.
3 #6, 1#10 G, 1" C.
3 #6, 1#10 G, 1" C.
3 #2, 1#8 G, 1 1/2" C.
3 #4, 1#8 G, 1" C.
3 #1, 1#6 G, 2" C.
3 #1/0, 1#6 G, 2" C.
3 #2/0, 1#6 G, 2" C.
3 #3/0, 1#6 G, 2" C.
3 #4/0, 1#4 G, 2 1/2" C.
3-250 MCM, 1#4 G, 2 1/2" C.
3-350 MCM, 1#4 G, 3" C.
3-500 MCM, 1#3 G, 3"C.
2 SETS: 3-250 MCM, 1#2 G, 2 1/2" C.
2 SETS: 3-350 MCM, 1#1 G, 3" C.
2 SETS: 3-500 MCM, 1#1/0 G, 3" C.
3 SETS: 3-400 MCM, 1#2/0 G, 3" C.
BRANCH CIRCUIT AND FEEDER SCHEDULE
NOTE: ALL CONDUCTORS ARE COPPER, THWN / THHN.
SYMBOL MINIMUM SIZE CONDUCTORS AND CONDUITS
PANELBOARD
"CSA"
100A MCB
120/240V
1PH 3W
(EXISTING)
COMMITTAL SHELTER A
GROUND
PANELBOARD
"CSB"
100A MCB
COMMITTAL SHELTER B
GROUND
POWER RISER LEGEND
NEW
DEMO
EXISTING
SPD
1PH 3W
(NEW)
1 1
SPD
1PH 3W
(NEW)
120/240V
1PH 2P 3W
(EXISTING)
3#10, 1#10G, ¾"C 3#10, 1#10G, ¾"C
ELECTRICAL - LUMINAIRE
SCHEDULE & RISER DIAGRAM
COMMITTAL SHELTERS
E-009
N C A
ATIONAL
EMETERY
DMINISTRATION
Revisions Date
Drawing Title
Approved:
Approved:
Project Title
Building Number Checked Drawn
Location
Date
Project No.
DRAWING NO.
Dwg. Of
1 2 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A B
C D
E F
A B
C D
E F
© COPYRIGHT 2021, Walker Federal Services, LLC
Walker Federal Services, LLC 7820B-162 Wormans Mill Road Frederick, Maryland 21701
WFS
FACILITY RENOVATION
LONG ISLAND NATIONAL CEMETERY
815CM3041
Final Construction Documents - Issued for Construction
5838 Monroe Road, Suite 100 Charlotte, NC 28212
704 531 3000 Project No. 4624
JCE CDH
May 22, 2023
KEYED NOTES
1 TO EXISTING 24 kVA PAD MOUNTED TRANSFORMER LOCATED BETWEEN
COMMITTAL SHELTERS A & B AND FED FROM ADMINISTRATION BUILDING
(1001). 480V PRIMARY, 240/120V SECONDARY.
LEGEND
(E) EXISTING TO REMAIN
AutoCAD SHX Text U
AutoCAD SHX Text N
AutoCAD SHX Text I
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text S
AutoCAD SHX Text T
AutoCAD SHX Text A
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text A
AutoCAD SHX Text M
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text I
AutoCAD SHX Text C
AutoCAD SHX Text A
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text T
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text V
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text A
AutoCAD SHX Text N
AutoCAD SHX Text S
AutoCAD SHX Text A
AutoCAD SHX Text F
AutoCAD SHX Text F
AutoCAD SHX Text A
AutoCAD SHX Text I
AutoCAD SHX Text R
AutoCAD SHX Text S
AutoCAD SHX Text
PRIME CONSULTANT
2M
2T
2T
W es te rn
D r.
West Fourth Dr.
West Fifth Dr.
OC
PUMP
HOUSE
PUBLIC
RESTROOMS
BUILDING
MAINTENANCE
BUILDING
NIC
NIC
NIC
NIC
NIC
(NIC)
FOR TELECOM
ROUTING
NEW
TEMPORARY
RESTROOMS
NEW WATER
WELL PUMP
NEW WATER
WELL CONTROL
SPOOL
FOR POWER
ROUTING
E
Main Portal Dr.
LODGE
EMPLOYEE
ONLY
EMPLOYEE
ONLY
EMPLOYEE
ONLY
EMPLOYEE
ONLY
EMPLOYEE
ONLY
EMPLOYEE
ONLY
EMPLOYEE
ONLY
EMPLOYEE
ONLY
EMPLOYEE
ONLYNO
PARKING
EM
PLOYEE
ONLY
EM
PLOYEE
ONLY
EM
PLOYEE
ONLY
EM
PLOYEE
ONLY
EM
PLOYEE
ONLY
EM
PLOYEE
ONLY
EM
PLOYEE
ONLY
EM
PLOYEE
ONLY
EM
PLOYEE
ONLY
EM
PLOYEE
ONLY
NO
PARKING
DIRECTOR'S
LODGE
PUBLIC
INFORMATION
CENTER
ADMINISTRATION
BUILDING (NIC)
NIC
FOR
CONTINUATION
K
D
3E
C
Memorial Dr. S.
Memorial Dr. N.
Memorial Dr. S.
C
COMMITTAL
SHELTER A
COMMITTAL
SHELTER B
ELECTRICAL - OVERALL
SITE PLAN
E-010
LEGEND
N C A
ATIONAL
EMETERY
DMINISTRATION
Revisions Date
Drawing Title
Approved:
Approved:
Project Title
Building Number Checked Drawn
Location
Date
Project No.
DRAWING NO.
Dwg. Of
1 2 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A B
C D
E F
A B
C D
E F
© COPYRIGHT 2021, Walker Federal Services, LLC
Walker Federal Services, LLC 7820B-162 Wormans Mill Road Frederick, Maryland 21701
WFS
FACILITY RENOVATION
LONG ISLAND NATIONAL CEMETERY
815CM3041
Final Construction Documents - Issued for Construction
KEY
5838 Monroe Road, Suite 100 Charlotte, NC 28212
704 531 3000 Project No. 4624
NOT TO SCALE
3B
2X
2Z2Y
2W 3D
2S
2R
2Q
2D
3F
3C
2U
2T
2M
2K
H
J
C
D
N O
M L
K A
B
G
F
2L
2P2N
2M2J
2E2G
2E2G
R
Q
P
Y Z
2A
X
V
T
US
2C
2B
2VW
3A
JCE CDH
May 22, 2023
0 15 30 60 90
TRUE
NORTHGRAPHICAL SCALE
GENERAL NOTES
A. REFER TO DRAWING SERIES OF RESPECTIVE BUILDING FOR SCOPE OF WORK.
B. ALL BUILDINGS LABELED 'NIC' ARE NOT IN CONTRACT.
C. ALL BUILDINGS / STRUCTURES ARE EXISTING, UNLESS OTHERWISE NOTED.
KEYED NOTES
1 APPROXIMATE ROUTING OF EXISTING UNDERGROUND TELECOMMUNICATION
PATHWAY. PROVIDE TWO (2) PLENUM RATED SINGLE MODE FIBER CABLES FROM
EXISTING ADMINISTRATION BUILDING TELECOM ROOM TO PUBLIC INFORMATION
CENTER BASEMENT VIA EXISTING RACEWAYS. VERIFY RACEWAY INTEGRITY AND
CLEAN PRIOR TO RE-USE. CONFIRM EXACT ROUTING IN THE FIELD. REFER TO
PUBLIC INFORMATION CENTER PLANS FOR ADDITIONAL INFORMATION.
AutoCAD SHX Text
1 STORY FRAME BUILDING
AutoCAD SHX Text
BUILDING FOOTPRINT AREA=1,015± S.F.
AutoCAD SHX Text
1 STORY FRAME BUILDING
AutoCAD SHX Text
BUILDING FOOTPRINT AREA=7,570± S.F.
AutoCAD SHX Text
TRAILER
AutoCAD SHX Text
FRAME SHED
AutoCAD SHX Text
TRAILER
AutoCAD SHX Text
1 STORY FRAME BUILDING
AutoCAD SHX Text
BUILDING FOOTPRINT AREA=2,009± S.F.
AutoCAD SHX Text
1 STORY FRAME BUILDING
AutoCAD SHX Text
BUILDING FOOTPRINT AREA=983± S.F.
AutoCAD SHX Text
1 STORY FRAME BUILDING
AutoCAD SHX Text
BUILDING FOOTPRINT AREA=5,325± S.F.
AutoCAD SHX Text
FRAME SHED
AutoCAD SHX Text
FRAME SHED
AutoCAD SHX Text
1 STORY FRAME BUILDING
AutoCAD SHX Text
BUILDING FOOTPRINT…