Tbl 3-1_2 Prot Dev Eval.pdf
PDF 68 KB Posted
- Attached to
- H959--ARC FLASH ANALYSIS - POP (09/01/2024 - 08/31/2025) Federal contract opportunity
- Solicitation number
- 36C26224Q1724
About this file
This document is a combined synopsis/solicitation for a federal contract opportunity for an Arc Flash Analysis at the VA Loma Linda Healthcare System.
The Department of Veterans Affairs (VA) is seeking to purchase an Arc Flash Analysis for the VA Loma Linda Healthcare System. The contract will be set aside for 100% Service-Disabled Veteran-Owned Small Businesses (SDVOSBs), with a base period of performance from September 1, 2024 to August 31, 2025. The contractor will be required to provide all labor, materials, and equipment to conduct the Arc Flash Analysis, including collecting electrical data, performing the analysis, providing a detailed report, and placing Arc Flash warning labels on the evaluated equipment. Key requirements include compliance with OSHA, NFPA 70E, and IEEE standards, as well as providing qualified personnel and submitting deliverables within 30 days of work completion. Proposals are due by August 23, 2024, and the contract will be awarded based on a comparative evaluation of price and past performance.
View the file
Other files for this federal contract opportunity
Show all 50
H959--ARC FLASH ANALYSIS - POP (09/01/2024 - 08/31/2025) has more files on GovTribe.
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
VA Loma Linda - Jerry L. Pettis VAHCS - Loma Linda, California Electrical Condition Assessment - Equipment Evaluation
Prepared for: Dept. of Veterans Affairs Section 3 Page 31 Prepared by: Wiley|Wilson
DEVICE
RATING
(kAIC)
MAXIMUM
AVAILABLE 3-PH
SCA (kAIC)
PERCENT
RATING
DEVICE
RATING
(kAIC)
CALCULATED
(kAIC)
PERCENT
RATING
MV system CB 1_FDR B-3 SWGR: 1_SOUTH 12000 22.50 (*N2) 7.50 33.33 58.00 11.21 19.33 Adequate MV system CB: 1_1B SWGR: 1_SOUTH 12000 22.50 (*N2) 7.50 33.33 58.00 11.21 19.33 Adequate MV system CB: 1_2A SWGR: 1_NORTH 12000 22.50 (*N2) 7.50 33.33 58.00 11.21 19.33 Adequate MV system CB: 1_FDR A-1 SWGR: 1_NORTH 12000 22.50 (*N2) 7.50 33.33 58.00 11.21 19.33 Adequate MV system CB: 1_FDR A-2 SWGR: 1_NORTH 12000 22.50 (*N2) 7.50 33.33 58.00 11.21 19.33 Adequate MV system CB: 1_FDR A-3 SWGR: 1_NORTH 12000 22.50 (*N2) 7.50 33.33 58.00 11.21 19.33 Adequate MV system CB: 1_FDR A-4 SWGR: 1_NORTH 12000 22.50 (*N2) 7.50 33.33 58.00 11.21 19.33 Adequate MV system CB: 1_FDR B-1 SWGR: 1_SOUTH 12000 22.50 (*N2) 7.50 33.33 58.00 11.21 19.33 Adequate MV system CB: 1_FDR B-2 SWGR: 1_SOUTH 12000 22.50 (*N2) 7.50 33.33 58.00 11.21 19.33 Adequate MV system CB: 1_Tie SWGR: 1_NORTH 12000 22.50 (*N2) 7.50 33.33 58.00 11.21 19.33 Adequate MV system CB: 1_US-7 SWGR: 1_US-7 12000 25.00 6.98 27.92 68.00 9.46 13.91 Adequate MV system FU: 1_Outpatient Pharmacy SWGR: 1_US-7 12000 50.00 6.98 13.96 80.00 9.46 11.83 Adequate MV system FU: 1_T-FCH BUS-0073 12000 2.00 *7.29 *364.53 3.20 *10.45 *326.52 Inadequate MV system FU: 1_US-1A West BUS: 1_US-1A West Pri 12000 85.00 7.04 8.29 129.34 9.66 7.47 Adequate MV system FU: 1_US-1B West BUS: 1_US-1B West Pri 12000 85.00 7.03 8.27 129.34 9.63 7.44 Adequate MV system FU: 1_US-2A East BUS: 1_US-2A East Pri 12000 85.00 7.28 8.57 129.34 10.49 8.11 Adequate MV system FU: 1_US-2B East BUS: 1_US-2B East Pri 12000 85.00 7.28 8.56 129.34 10.46 8.09 Adequate MV system FU: 1_US-3A West BUS: 1_US-3A West Pri 12000 85.00 6.96 8.19 129.34 9.46 7.31 Adequate MV system FU: 1_US-3B West BUS: 1_US-3B West Pri 12000 85.00 6.95 8.18 129.34 9.43 7.29 Adequate MV system FU: 1_US-4A East BUS: 1_US-4A East Pri 12000 85.00 7.36 8.66 129.34 10.71 8.28 Adequate MV system FU: 1_US-4B East BUS: 1_US-4B East Pri 12000 85.00 7.35 8.65 129.34 10.68 8.25 Adequate MV system FU: 1_US-5A East BUS: 1_US-5A East Pri 12000 85.00 7.35 8.64 129.34 10.65 8.24 Adequate MV system FU: 1_US-5B East BUS: 1_US-5A West Pri0 12000 85.00 7.33 8.63 129.34 10.61 8.21 Adequate MV system FU: 1_US-6 East BUS: 1_US-6 East Pri 12000 50.00 7.33 14.66 80.00 10.61 13.26 Adequate MV system FU: 1_XF Outpatient Pharmacy BUS-0077 12000 2.00 *6.55 *327.40 3.20 *7.62 *238.24 Inadequate MV system FU: 1_XF US-7 SWGR: 1_US-7 12000 50.00 6.98 13.96 80.00 9.46 11.83 Adequate MV system SW: 1_US-1A West-1 BUS: 1_SW US-1A West 12000 25.00 7.16 28.65 40.00 10.02 25.04 Adequate MV system SW: 1_US-1B West-2 BUS: 1_SW US-1B West 12000 25.00 7.15 28.60 40.00 9.98 24.95 Adequate MV system SW: 1_US-2A East-2 BUS: 1_SW US-2A East 12000 25.00 7.41 29.63 40.00 10.92 27.29 Adequate MV system SW: 1_US-2B East-1 BUS: 1_ SW US-2B East 12000 25.00 7.40 29.59 40.00 10.88 27.20 Adequate MV system SW: 1_US-3A West-1 BUS: 1_SW US-3A West 12000 25.00 7.08 28.30 40.00 9.79 24.48 Adequate
MEDIUM VOLTAGE
TABLE 3.1 - PROTECTIVE DEVICE EVALUATION
BLDG NO. PROTECTIVE DEVICE NAME BUS OR EQUIPMENT
DESIGNATION
NOMINAL
L-L VOLTS
INTERRUPTING CLOSE - LATCH
STATUS
Prepared for: Dept. of Veterans Affairs Section 3 Page 32 Prepared by: Wiley|Wilson
DEVICE
RATING
(kAIC)
MAXIMUM
AVAILABLE 3-PH
SCA (kAIC)
PERCENT
RATING
DEVICE
RATING
(kAIC)
CALCULATED
(kAIC)
PERCENT
RATING
TABLE 3.1 - PROTECTIVE DEVICE EVALUATION
BLDG NO. PROTECTIVE DEVICE NAME BUS OR EQUIPMENT
DESIGNATION
NOMINAL
L-L VOLTS
INTERRUPTING CLOSE - LATCH
STATUS
MV system SW: 1_US-3B West-1 BUS: 1_ SW US-3B West 12000 25.00 7.07 28.27 40.00 9.76 24.41 Adequate MV system SW: 1_US-4A East-2 BUS: 1_SW US-4A East 12000 25.00 7.48 29.94 40.00 11.15 27.89 Adequate MV system SW: 1_US-4B East-1 BUS: 1_SW US-4B East 12000 25.00 7.47 29.90 40.00 11.12 27.79 Adequate MV system SW: 1_US-5A East-1 BUS: 1_SW US-5A East 12000 25.00 7.47 29.88 40.00 11.09 27.74 Adequate MV system SW: 1_US-5B East-2 BUS: 1_SW US-5B East 12000 25.00 7.46 29.83 40.00 11.05 27.62 Adequate MV system SW: 1_US-6 East BUS: 1_SW US-6 East 12000 25.00 7.46 29.82 40.00 11.04 27.61 Adequate MV system SW: 1_US-7 A-3 BUS: 1_US-7-1 12000 25.00 6.98 27.92 40.00 9.46 23.65 Adequate
(*N2) Dev Isc kA modified based on Max Rating Voltage and K Factor.
(*Device Voltage) Device did not pass. Device is either Marginal (100%) or Failed (100%) of the device voltage rating.
(*Calc INT kA) Device did not pass. Device is either Marginal (100%) or Failed (100%) of the device library interrupting rating.
(*Calc C-L kA) Device did not pass. Device is either Marginal (100%) or Failed (100%) of the device library close-latch / momentary rating.
Prepared for: Dept. of Veterans Affairs Section 3 Page 33 Prepared by: Wiley|Wilson
DEVICE
RATING
(kAIC)
MAXIMUM
AVAILABLE 3-PH
SCA (kAIC)
PERCENT
RATING
MV system FU: 1_T-FCH BUS-0073 12000 2.00 *7.29 *364.53 Note 1 - Inadequate MV system FU: 1_XF Outpatient Pharmacy BUS-0077 12000 2.00 *6.55 *327.40 Note 1 - Inadequate
Note 1. Based on conversations with Cooper Power Systems - The predominant supplier of medium voltage transformer fuses - the use of Dual Sensing bayonet fuses in series with isolation links provides adequate transformer and downstream system protection. The bayonet fuses provide downstream overcurrent protection as well as overload protection. The isolation link provides very fast response to high current transformer faults. Based on this information, and the lack of nuisance tripping, it appears that this combination of fusing is working properly, and our recommendation is to keep these fuses as-is.
TABLE 3.2 - PROTECTIVE DEVICE ANALYSIS & RECOMMENDATIONS
BLDG NO. PROTECTIVE DEVICE NAME BUS OR EQUIPMENT
DESIGNATION
NOMINAL
L-L VOLTS
INTERRUPTING
STATUSANALYSIS AND RECOMMENDATIONS APPROXIMATE
COST
MEDIUM VOLTAGE
| 3.1 - Evaluation Report |
| 3.2 - Analysis Report |