Arc Flash Study CLC Ph 2.pdf
PDF 5 MB Posted
- Attached to
- H959--ARC FLASH ANALYSIS - POP (09/01/2024 - 08/31/2025) Federal contract opportunity
- Solicitation number
- 36C26224Q1724
About this file
This document is a combined synopsis/solicitation for a federal contract opportunity for an Arc Flash Analysis at the VA Loma Linda Healthcare System. The VA is seeking to purchase an Arc Flash Analysis to be in compliance with required electrical inspections, as per NFPA 99, NFPA 70E, IEEE, and the Joint Commission. The contractor will provide all labor, materials, and services to complete the Arc Flash Analysis, including data collection, analysis, reporting, and placement of Arc Flash labels. The work must comply with relevant OSHA, NFPA, IEEE, and ANSI standards. The contract is set-aside for 100% Service-Disabled Veteran-Owned Small Businesses (SDVOSB). The period of performance is 09/01/2024 - 08/31/2025. Quotes are due by 08/23/2024 and the award will be based on a comparative evaluation of price and past performance, with price being more important.
View the file
Other files for this federal contract opportunity
Show all 50
H959--ARC FLASH ANALYSIS - POP (09/01/2024 - 08/31/2025) has more files on GovTribe.
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SUBMITTAL ACTION
SUBMISSION FIRST SECOND THIRD
REVIEWED
REVIEWED AS NOTED
REVIEWED AS NOTED RESUBMIT
REJECTED
RESUBMIT
SEE TRANSMITTAL FOR INSTRUCTIONS
This submittal has been reviewed only for conformance with the design concept of the Project and compliance with the Information given in the Contract Documents.
It is the Contractor’s contractual duty to review and act upon submittals, prior to their submission to verify that all requirements of the Contract Documents have been met or if they have not been met, to notify the Architect in writing. By the submission of this submittal to the Architect, it is assumed the Contractor has fulfiled these contractual duties. Review of this submittal by Architect does not relieve the Contractor of the duty to meet the requirements of the Contract Documents and the applicable building codes.
Any comments noted or corrections requested are for clarification of the general character of the work. Correctness of details, measurements, quantities, conformity with Contract Documents, techniques of construction and coordination with other trades shall remain the complete responsibility of the General/Prime Contractor.
BY: ------- DATE: ------
EWINGCOLE
15231 Laguna Canyon Road, Suite 200, Irvine, CA 92618
ARCHITECTS ENGINEERS INTERIOR DESIGNERS PLANNERS
ewingcole.comDiscovery Business Center, 15231 Laguna Canyon Road, Suite 200, Irvine, CA 92618 TEL 949.417.7550 FAX 949.585.9391
VA LL CLC Expand Phase II Submittal Review
Electrical Power Study (Division Number 265100 )
Comments:
1. Update conductor lengths for CBL-003 from MDBU to MSB-CLC2 and CBL-0015 from SBCM to CB-EM-CLC2 in accordance with RFI-026. Verify associated electrical values for this power study are still acceptable.
D.Diaz 08/22/2017
SHORT CIRCUIT, PROTECTIVE DEVICE
COORDINATION, & ARC FLASH RISK
ASSESSMENT REPORT
VA Loma Linda Healthcare System Community Living
Center 2 Expansion: Loma Linda, CA
(Engineer of Record)
Reviewed by: Joe Dews, P.E.
Designed by: Michael McKee, P.E.
Date: August 17, 2017
Revision 0
Tables of Contents
1. SUMMARY
1.1. Introduction
1.2. Power System Study Results
1.2.1. Short-Circuit Results
1.2.2. Protective Device Coordination Results
1.2.3. Arc Flash Hazard Analysis Results
1.3. Power System Study Recommendations
1.3.2. Protective Device Coordination Study
1.3.3. Arc Flash Hazard Analysis
2. SHORT CIRCUIT ANALYSIS
2.1. Background and Procedures
2.2. Power System Modeling for Short Circuit Calculations
2.3. Data for Short Circuit Calculations
2.3.2. Power System Data
2.3.3. Assumptions
2.3.4. Short Circuit Analysis Results
3. PROTECTIVE DEVICE COORDINATION STUDY
3.1. Background and Procedures
3.1.1. Coordination Objectives
3.1.2. Coordination Results
3.1.3. Coordination Recommendations
3.1.4. Time Current Characteristic Plots
4. Arc Flash RISK ASSESSMENT
4.1. Background and Analysis
4.2. Results and Recommendations
5. STUDY ONE-LINE DIAGRAM
6. ARC FLASH LABELS
7. SHORT CIRCUIT INPUT/OUTPUT DATA
1. EXECUTIVE SUMMARY
1.1 Introduction
This report details the results of the power system engineering study for the VA
Hospital Community Living Center 2 expansion in Loma Linda, CA. The objective of this section is to briefly summarize the results of the study and point out critical issues and results. Refer to Sections 2-4 for the study details.
The electrical distribution system for the VA Community Living Center 2 expansion consists of a 600A main distribution switchboard (“MSB-CLC2”) served from a 600A breaker in existing switchboard MDBU. The distribution system also consists of a 250A enclosed circuit breaker (“CB-EM-CLC2”) served from a 250A breaker in existing switchboard SBCM.
See Section 5 for the study one-line diagram.
1.2 Power System Study Results
1.2.1 Short-Circuit Results
Of the nineteen equipment locations evaluated, all were found to have device interrupting ratings appropriate for the maximum three-phase short-circuit current to which they could be subjected. See Section 2 for the short-circuit study results.
1.2.2 Protective Device Coordination Results
Settings recommendations have been made for fourteen adjustable devices to ensure optimum selectivity, reduce arc flash incident energy, and protect equipment. Overall, the coordination study showed that acceptable levels of selectivity were achieved among devices in the system.
The protective devices in the power system should be set as recommended in
Table 3, Section 3 of the report.
1.2.3 Arc Flash Risk Assessment Results
Nineteen locations were analyzed to determine the level of arc flash incident energy to which personnel would be exposed during an arc flash event. All locations were determined to be less than 8 cal/cm2.
As stated in NFPA 70E-2015 Article 130.7(A), Informational Note No. 1 the
PPE requirements of NFPA 70E do not address protection against physical trauma other than the thermal effects of an arc flash. Protection from arc flash hazards can best be provided by working only on circuits or equipment that have been placed in an electrically safe work condition.
1.3 Power System Study Recommendations
1.3.1 Protective Device Coordination Study
All adjustable protective devices should be set per the settings table in Section
3.
1.3.2 Arc Flash Risk Assessment
Per the 2015 edition of NFPA 70E-2015 Article 130.5(2) the arc flash risk assessment shall be updated as follows:
• Intervals not to exceed five years.
• When a major modification or renovation takes place.
It is recommended that a plan is implemented to schedule a review of the arc flash risk assessment for the entire VA Loma Linda campus by 2021 or when a major modification or renovation takes place.
2. SHORT-CIRCUIT ANALYSIS
2.1 Background and Procedures
A power system short-circuit analysis is used for the following:
• To compare the calculated maximum fault currents with the interrupting ratings of overcurrent protective devices such as fuses and circuit breakers.
• To investigate applicable, short-circuit series ratings and the protection of electrical equipment by current-limiting devices.
• To verify the ability of equipment such as disconnect switches and plug-in busduct, to withstand the effects of the calculated maximum fault current levels.
• To assist in the selection and/or determination of settings for relays and circuit breakers.
• To provide input (along with overcurrent device operating characteristics) to an arc flash hazard analysis.
This study uses SKM power system analysis software to calculate the maximum available three-phase, RMS symmetrical, short-circuit amperes at each equipment location in the system. The calculation procedures are based on recommendations included in ANSI/IEEE standards C37.13, C37.010, and C37.5.
The equipment evaluation provided in Table 2 compares the short circuit current rating (SCCR) of the protective devices to the available fault current at each equipment location in the electrical distribution system. The interrupting rating of the protective devices must be greater than the calculated fault current available at the equipment location to pass the equipment evaluation. When the criteria limits are met the equipment evaluation status is set to “pass”. However, when the limits are exceeded the status is set to “fail” and these devices are over-dutied. The equipment evaluation is essential to determine if the breakers are rated to operate safely to interrupt and isolate fault currents with minimal disruption to the overall power system.
NEC section 110.9 requires protective devices to have interrupting ratings sufficient to handle the available fault current at the line terminals of the equipment. For locations where the calculated fault currents exceed the interrupting ratings of protective devices, recommendations for corrective action are provided.
For equipment with series ratings, the maximum duty rating is calculated using the series rating rather than the respective device interrupting ratings.
NEC-2017, Article 110.24(A) requires that service entrance equipment is labeled with the following information:
• Maximum available fault current.
• Date on which the fault current was calculated.
Article 110.24(B) adds that if there is a modification that may change this fault current value, it must be recalculated. The field marking must be updated to reflect the new value of maximum fault current.
Equipment short-circuit withstand and protective device interrupting ratings are expressed in symmetrical RMS current. However, power system inductance introduces a degree of asymmetry for at least the first few cycles of a fault. The magnitude and duration of this asymmetrical component depends on several factors, including characteristics of system components (conductors, transformers, and loads) and the exact point on the current waveform when the fault begins. The level of asymmetry differs from phase to phase in a three-phase system. Because of the uncertainty in asymmetry for a given fault event, the capability of devices to interrupt asymmetrical fault currents is based on the maximum possible asymmetrical fault current level at the point of application in the power system. The more inductive the circuit, as measured by the calculated system X/R ratio, the higher the magnitude of the asymmetrical component. If the calculated X/R ratio exceeds a specified value, then the increased asymmetrical duty must be considered when breaker ratings are evaluated.
Low voltage circuit breakers and fuses are tested to establish their interrupting ratings based on a circuit with a fixed X/R ratio, as defined in UL and ANSI product standards. For example, an ANSI low voltage power circuit breaker is tested in a circuit with an X/R ratio of 6.591. If this breaker is applied at a system bus with a calculated X/R ratio of 6.591 or less and the calculated RMS symmetrical fault current is within the symmetrical interrupting rating of the breaker, then it is assumed that the breaker is also able to interrupt and withstand the asymmetrical current resulting from a fault at that location. If a low voltage power circuit breaker is applied at a location with an X/R ratio greater than that of the design test circuit, the calculated fault current must be multiplied by an adjustment factor that accounts for this increased X/R ratio at the point of application. This resultant fault duty, which is greater than the calculated fault current, is then compared to the breaker’s interrupting rating to determine if the breaker is rated adequately. Different classes of low voltage breakers have different test X/R ratios, and each type has its own set of multiplication factors. Design test circuit power factors and associated X/R ratios are given in Table
1. See IEEE standard 1015-1997 (Blue Book), IEEE Recommended Practice for
Applying Low-Voltage Circuit Breakers Used in Industrial and Commercial Power
Systems, for additional details.
Table 1 - Summary of Test Power Factor and X/R Ratios for LV Devices
Device Power Factor X/R Ratio
Power circuit breaker, unfused 0.15 6.591
Power circuit breaker, fused 0.20 4.899
Molded case breaker, interrupting rating greater than 20000 A
0.15-0.20 6.591-4.899
Molded case breaker, interrupting rating
10001 to 20000 A
0.25-0.30 3.9-3.18
Molded case breaker, interrupting rating
10000 A and less
0.45-0.50 2.0-1.732
For power circuit breakers, the power factors are taken from ANSI/IEEE standard
C37.13. For molded case circuit breakers, the power factors are taken from
NEMA standard AB1. Since the NEMA standard specifies a range of test circuit power factors, the highest value (lowest X/R ratio) is used to determine the multiplying factor. This produces the most conservative (largest) multiplying factor.
2.2 Power System Modeling for Short Circuit Calculations
Short-circuit currents were calculated for a three-phase bolted fault at each bus shown on the one-line diagram found in Section 5.
To model the system for worst-case fault currents all motor contributions were added.
The following study cases were applied.
• Study Case No. 1 – MDBU as short-circuit source.
• Study Case No. 2 – SBCM as short-circuit source (only used to determine fault duty of CB-EM-CLC2, GUTTER TROUGH, CB-L, CB-C, and CB-EM-CLC1).
2.3 Data for Short Circuit Calculations
2.3.1 Power System Data
Input data for this study was obtained from the following sources:
• Contract drawing E-611
• Calray Electric
• The maximum available three-phase and line-to-ground fault currents and associated X/R ratios were obtained from the Short-Circuit, Overcurrent
Device Coordination, & Arc Flash Hazard Analyses performed by
Schneider Electric Engineering Services, LLC March 22, 2016 (Job
Number Q2C: 37151901)
2.3.2 Assumptions
The following assumptions were used in modeling the power system, and ensure conservative, worst-case results:
• All motors were assumed to be running.
• Motor subtransient reactance is assumed to be 17%.
• Motors rated less than 50 hp were modeled as lumped groups.
• System voltage is modeled at 100% nominal.
See Section 7 for detailed input information.
2.3.3 Short-Circuit Analysis Results
See Section 7 for short-circuit analysis results.
Table 2 – Equipment Evaluation Bus Manufacturer Status Type Voltage Calculated short-circuit kA
Device interrupting rating kA
Short-circuit rating %
AHU-1 (EP1)
VFD
Carrier Pass VFD 480.0 4.33 5.0 86.60
AHU-1 (EP2)
VFD
Carrier Pass VFD 480.0 2.16 5.0 43.20
ATS-C BUS Eaton Pass ATS 480.0 12.33 30.0 41.10
ATS-L BUS Eaton Pass ATS 480.0 12.12 30.0 40.40
CB-C Eaton Pass Enclosed Circuit
Breaker
480.0 5.11 35.0 14.60
CB-EM-CLC1 Eaton Pass Enclosed Circuit
Breaker
480.0 5.11 35.0 14.60
CB-EM-CLC2 Eaton Pass Enclosed Circuit
Breaker
480.0 5.29 35.0 15.11
CB-L Eaton Pass Enclosed Circuit
Breaker
480.0 5.10 14.0 36.43
CH-1 DISC Eaton Pass Safety Switch 480.0 8.20 200.0 4.10
LTG CNTRL
LCP1
nLight Pass Industrial Control
Panel
277.0 10.60 18.0 58.89
MSB-CLC2 Eaton Pass Switchboard 480.0 12.93 35.0 36.94
PANEL CH1 Eaton Pass Panelboard 480.0 11.50 35.0 32.86
PANEL CL1 Eaton Pass Panelboard 208.0 4.69 10.0 46.90
PANEL CL2 Eaton Pass Panelboard 208.0 4.57 10.0 45.70
PANEL LH1 Eaton Pass Panelboard 480.0 11.36 35.0 32.46
PANEL LL1 Eaton Pass Panelboard 208.0 1.10 10.0 11.00
PANEL NH1 Eaton Pass Panelboard 480.0 12.18 35.0 34.80
PANEL NL1 Eaton Pass Panelboard 208.0 5.36 10.0 53.60
PANEL NL2 Eaton Pass Panelboard 208.0 5.28 10.0 52.80
3. PROTECTIVE DEVICE COORDINATION STUDY
3.1 Background and Procedures
The protective device coordination study systematically applies current actuated protective devices (circuit breakers, relays, and fuses) to achieve an optimal compromise between equipment protection and power system selectivity.
The time-current characteristic curves (TCCs) were developed using SKM
CAPTOR software module. The protective device coordination study was performed in accordance with IEEE Standard 242-2001 (Buff Book), IEEE
Recommended Practice for Protection and Coordination of Industrial and
Commercial Power Systems.
Using the appropriate maximum fault currents, the TCCs were plotted as operating time versus current magnitudes on a log-log scale to show protective device operating characteristics and coordination among these devices.
Consideration was given to provide both selective isolation of faults and maximum protection of equipment such as switchboards, panelboards, cables, transformers, and motors.
To achieve optimum protection and selectivity, protective device settings should be high enough to allow the continuous full-load operation of cables and the equipment they supply, and to tolerate temporary power system disturbances such as transformer and motor in-rush currents. However, the settings should be low enough to provide overload and short-circuit protection under minimum fault conditions.
3.1.1 Coordination Objectives
Develop time-current coordination curves to derive coordinated settings for adjustable protective devices at the VA Loma Linda
Community Living Center 2.
3.1.2 Coordination Results
Analysis on the normal power branch begins at the 600A main distribution switchboard (“MSB-CLC2”) served from a 600A breaker in existing switchboard MDBU. Analysis on the emergency branch begins at the 250A enclosed circuit breaker (“CB-EM-CLC2”) served from a 250A breaker in existing switchboard SBCM.
As shown on the TCCs, each device curve is tagged with an arrow and label referencing its location on the plot's individual representative one-line diagram. This label also references the device to its’ specific manufacturer information, including ratings and settings, as indicated in the text box on each plot. The device time-current characteristics are truncated at maximum through-fault current for a downstream fault.
Efforts were made to provide the best coordination possible with the new protective devices. Areas where breaker trip curves overlap indicate areas of possible non-selective breaker operation. Where possible, efforts were made to reduce non-selective breaker operation while maintaining adequate system protection. In some cases, because of device limitations, little can be done to improve device selectivity.
Such device limitations include the fixed operating characteristic of a fuse, the built-in instantaneous or instantaneous “over-ride” elements of molded case circuit breakers, and the limited instantaneous trip range of trip units with an instantaneous trip function.
In cases involving redundant/series protective devices, non-selective breaker operation is of little or no concern. Protective devices are redundant if, regardless of which device opens, the same system outage occurs. Often, to improve overall system protection and coordination, redundant devices are intentionally set to overlap one another.
3.1.3 Coordination Recommendations
All new adjustable protective devices at the VA Loma Linda
Community Living Center 2 should be set per Table 3.
3.1.4 Time-Current Characteristic Plots
Refer to the following pages for the plotted coordination curves, which graphically demonstrate the degree of selectivity and protection obtained.
In some cases, a single TCC may be applicable to several locations in the system, where each location utilizes substantially similar devices, and serves similar loads.
0.5 1 10 1
K
K
0.010.01
0.100.10
100100
10001000
CURRENT IN AMPERES
T
IM
E
IN
S
E C
O N
D S T
IM
E
I N
S E
C O
N D
S
MSB-CLC2 MAIN
CUTLER-HAMMER
LG Frame, 310+
LGE
Trip 600.0 A Settings Phase Ir for In = 600A H (600A) LTD (2-24 Sec.) 10 STPU (2-12 x Ir) 7 (4200A) STD (Flat) 120ms (M,N,O)
INST 12 (7200A)
XFMR T-NL1 FDR
CUTLER-HAMMER
FDE/FDCE/HFDE, 310+
FDE
Trip 225.0 A Plug 175.0 A Settings Phase Ir, 225A Sensor F (175) (175A) LTD (2 - 24s) 24 STPU (2 - 12 x Ir) 12 (2100A) STD FLAT (Inst-300ms) Inst (J,K,L) INST OR Fixed (2700A)
MSB-CLC2 FDR
CUTLER-HAMMER
SPB, RMS 510/610/810/910
SPB-100
Trip 800.0 A Plug 600.0 A Settings Phase LTPU (0.5-1.0 x P) 1 (600A) LTD (2-24 Sec.) 12 STPU (2-8 x LTPU) S2(8) (4800A) STD (0.1-0.5 Sec.) 0.2 (I^2t Off) INST (2-10 x P) M2(10) (6000A) OVERRIDE (1 x ST) Fixed (25000A)
MSB-CLC2 MAIN
CUTLER-HAMMER
LG Frame, 310+
LGE
Trip 600.0 A Settings Phase Ir for In = 600A H (600A) LTD (2-24 Sec.) 10 STPU (2-12 x Ir) 7 (4200A) STD (Flat) 120ms (M,N,O)
INST 12 (7200A)
XFMR T-NL1 FDR
CUTLER-HAMMER
FDE/FDCE/HFDE, 310+
FDE
Trip 225.0 A Plug 175.0 A Settings Phase Ir, 225A Sensor F (175) (175A) LTD (2 - 24s) 24 STPU (2 - 12 x Ir) 12 (2100A) STD FLAT (Inst-300ms) Inst (J,K,L) INST OR Fixed (2700A)
MSB-CLC2 FDR
CUTLER-HAMMER
SPB, RMS 510/610/810/910
SPB-100
Trip 800.0 A Plug 600.0 A Settings Phase LTPU (0.5-1.0 x P) 1 (600A) LTD (2-24 Sec.) 12 STPU (2-8 x LTPU) S2(8) (4800A) STD (0.1-0.5 Sec.) 0.2 (I^2t Off) INST (2-10 x P) M2(10) (6000A) OVERRIDE (1 x ST) Fixed (25000A)
600AT
MSB-CLC2 FDR
CBL-0003
MSB-CLC2 MAIN
XFMR T-NL1 FDR
MSB-CLC2
MDBU
MSB-CLC2 Current Scale x 100 Reference Voltage: 480 August 15, 2017 12:52 PM SKM Systems Analysis, Inc.
K
K
0.010.01
0.100.10
100100
10001000
CURRENT IN AMPERES
T
IM
E
IN
S
E C
O N
D S T
IM
E
I N
S E
C O
N D
S
MSB-CLC2 MAIN
CUTLER-HAMMER
LG Frame, 310+
LGE
Trip 600.0 A Settings Phase Ir for In = 600A H (600A) LTD (2-24 Sec.) 10 STPU (2-12 x Ir) 7 (4200A) STD (Flat) 120ms (M,N,O)
INST 12 (7200A)
PANEL NH1 FDR
CUTLER-HAMMER
FDE/FDCE/HFDE, 310+
FDE
Trip 160.0 A Plug 100.0 A Settings Phase Ir, 160A Sensor E (100) (100A) LTD (2 - 24s) 2 STPU (2 - 12 x Ir) 12 (1200A) STD FLAT (Inst-300ms) Inst (J,K,L) INST OR Fixed (1920A)
NH1 TYP FDR
CUTLER-HAMMER
FD, 1-Pole
FD
Trip 20.0 A Settings Phase Fixed
MSB-CLC2 MAIN
CUTLER-HAMMER
LG Frame, 310+
LGE
Trip 600.0 A Settings Phase Ir for In = 600A H (600A) LTD (2-24 Sec.) 10 STPU (2-12 x Ir) 7 (4200A) STD (Flat) 120ms (M,N,O)
INST 12 (7200A)
PANEL NH1 FDR
CUTLER-HAMMER
FDE/FDCE/HFDE, 310+
FDE
Trip 160.0 A Plug 100.0 A Settings Phase Ir, 160A Sensor E (100) (100A) LTD (2 - 24s) 2 STPU (2 - 12 x Ir) 12 (1200A) STD FLAT (Inst-300ms) Inst (J,K,L) INST OR Fixed (1920A)
NH1 TYP FDR
CUTLER-HAMMER
FD, 1-Pole
FD
Trip 20.0 A Settings Phase Fixed
MSB-CLC2 MAIN
PANEL NH1 FDR
CBL-0004
PANEL NH1
NH1 TYP FDR
MSB-CLC2
PANEL NH1 Current Scale x 10 Reference Voltage: 480 August 15, 2017 12:56 PM SKM Systems Analysis, Inc.
TX Inrush
XFMR T-NL1
0.5 1 10 1
K
K
0.010.01
0.100.10
100100
10001000
CURRENT IN AMPERES
T
IM
E
IN
S
E C
O N
D S T
IM
E
I N
S E
C O
N D
S
MSB-CLC2 MAIN
CUTLER-HAMMER
LG Frame, 310+
LGE
Trip 600.0 A Settings Phase Ir for In = 600A H (600A) LTD (2-24 Sec.) 10 STPU (2-12 x Ir) 7 (4200A) STD (Flat) 120ms (M,N,O)
INST 12 (7200A)
XFMR T-NL1 FDR
CUTLER-HAMMER
FDE/FDCE/HFDE, 310+
FDE
Trip 225.0 A Plug 175.0 A Settings Phase Ir, 225A Sensor F (175) (175A) LTD (2 - 24s) 24 STPU (2 - 12 x Ir) 12 (2100A) STD FLAT (Inst-300ms) Inst (J,K,L) INST OR Fixed (2700A)
PANEL NL1 MAIN
CUTLER-HAMMER
DK
DK
Trip 400.0 A Settings Phase Thermal Curve (Fixed) INST (5-10 x Trip) 10 (4000A)
PANEL NL2 FDR
CUTLER-HAMMER
EDB, 2-3 Poles
EDB
Trip 225.0 A Settings Phase Fixed
XFMR T-NL1
MSB-CLC2 MAIN
CUTLER-HAMMER
LG Frame, 310+
LGE
Trip 600.0 A Settings Phase Ir for In = 600A H (600A) LTD (2-24 Sec.) 10 STPU (2-12 x Ir) 7 (4200A) STD (Flat) 120ms (M,N,O)
INST 12 (7200A)
XFMR T-NL1 FDR
CUTLER-HAMMER
FDE/FDCE/HFDE, 310+
FDE
Trip 225.0 A Plug 175.0 A Settings Phase Ir, 225A Sensor F (175) (175A) LTD (2 - 24s) 24 STPU (2 - 12 x Ir) 12 (2100A) STD FLAT (Inst-300ms) Inst (J,K,L) INST OR Fixed (2700A)
PANEL NL1 MAIN
CUTLER-HAMMER
DK
DK
Trip 400.0 A Settings Phase Thermal Curve (Fixed) INST (5-10 x Trip) 10 (4000A)
PANEL NL2 FDR
CUTLER-HAMMER
EDB, 2-3 Poles
EDB
Trip 225.0 A Settings Phase Fixed
XFMR T-NL1
MSB-CLC2 MAIN
XFMR T-NL1 FDR
CBL-0005
S
P
XFMR T-NL1
CBL-0012
PANEL NL1
PANEL NL1 MAIN
PANEL NL2 FDR
MSB-CLC2
PANEL NL1 Current Scale x 10 Reference Voltage: 480 August 15, 2017 12:57 PM SKM Systems Analysis, Inc.
K
K
0.010.01
0.100.10
100100
10001000
CURRENT IN AMPERES
T
IM
E
IN
S
E C
O N
D S T
IM
E
I N
S E
C O
N D
S
MSB-CLC2 MAIN
CUTLER-HAMMER
LG Frame, 310+
LGE
Trip 600.0 A Settings Phase Ir for In = 600A H (600A) LTD (2-24 Sec.) 10 STPU (2-12 x Ir) 7 (4200A) STD (Flat) 120ms (M,N,O)
INST 12 (7200A)
CHILLER CH-1 FDR
CUTLER-HAMMER
FDE/FDCE/HFDE, 310+
FDE
Trip 225.0 A Plug 110.0 A Settings Phase Ir, 225A Sensor B (110) (110A) LTD (2 - 24s) 7 STPU (2 - 12 x Ir) 10 (1100A) STD FLAT (Inst-300ms) Inst (J,K,L) INST OR Fixed (2700A)
CH-1
MSB-CLC2 MAIN
CUTLER-HAMMER
LG Frame, 310+
LGE
Trip 600.0 A Settings Phase Ir for In = 600A H (600A) LTD (2-24 Sec.) 10 STPU (2-12 x Ir) 7 (4200A) STD (Flat) 120ms (M,N,O)
INST 12 (7200A)
CHILLER CH-1 FDR
CUTLER-HAMMER
FDE/FDCE/HFDE, 310+
FDE
Trip 225.0 A Plug 110.0 A Settings Phase Ir, 225A Sensor B (110) (110A) LTD (2 - 24s) 7 STPU (2 - 12 x Ir) 10 (1100A) STD FLAT (Inst-300ms) Inst (J,K,L) INST OR Fixed (2700A)
CH-1
MSB-CLC2 MAIN
CHILLER CH-1 FDR
CBL-0006
CH-1 DISC
CH-1
MSB-CLC2
CH-1 Current Scale x 10 Reference Voltage: 480 August 15, 2017 12:51 PM SKM Systems Analysis, Inc.
K
K
0.010.01
0.100.10
100100
10001000
CURRENT IN AMPERES
T
IM
E
IN
S
E C
O N
D S T
IM
E
I N
S E
C O
N D
S
MSB-CLC2 MAIN
CUTLER-HAMMER
LG Frame, 310+
LGE
Trip 600.0 A Settings Phase Ir for In = 600A H (600A) LTD (2-24 Sec.) 10 STPU (2-12 x Ir) 7 (4200A) STD (Flat) 120ms (M,N,O)
INST 12 (7200A)
AHU-1 (EP1) FDR
CUTLER-HAMMER
FDE/FDCE/HFDE, 310+
FDE
Trip 160.0 A Plug 60.0 A Settings Phase Ir, 160A Sensor A (60) (60A) LTD (2 - 24s) 4 STPU (2 - 12 x Ir) 8 (480A) STD FLAT (Inst-300ms) Inst (J,K,L) INST OR Fixed (1920A)
AHU-1 (EP1)
MSB-CLC2 MAIN
CUTLER-HAMMER
LG Frame, 310+
LGE
Trip 600.0 A Settings Phase Ir for In = 600A H (600A) LTD (2-24 Sec.) 10 STPU (2-12 x Ir) 7 (4200A) STD (Flat) 120ms (M,N,O)
INST 12 (7200A)
AHU-1 (EP1) FDR
CUTLER-HAMMER
FDE/FDCE/HFDE, 310+
FDE
Trip 160.0 A Plug 60.0 A Settings Phase Ir, 160A Sensor A (60) (60A) LTD (2 - 24s) 4 STPU (2 - 12 x Ir) 8 (480A) STD FLAT (Inst-300ms) Inst (J,K,L) INST OR Fixed (1920A)
AHU-1 (EP1)
MSB-CLC2 MAIN
AHU-1 (EP1) FDR
CBL-0007
AHU-1 (EP1) VFD
AHU-1 (EP1)
MSB-CLC2
AHU-1 (EP1) Current Scale x 10 Reference Voltage: 480 August 15, 2017 12:49 PM SKM Systems Analysis, Inc.
K
K
0.010.01
0.100.10
100100
10001000
CURRENT IN AMPERES
T
IM
E
IN
S
E C
O N
D S T
IM
E
I N
S E
C O
N D
S
MSB-CLC2 MAIN
CUTLER-HAMMER
LG Frame, 310+
LGE
Trip 600.0 A Settings Phase Ir for In = 600A H (600A) LTD (2-24 Sec.) 10 STPU (2-12 x Ir) 7 (4200A) STD (Flat) 120ms (M,N,O)
INST 12 (7200A)
AHU-1 (EP2) FDR
CUTLER-HAMMER
FDE/FDCE/HFDE, 310+
FDE
Trip 80.0 A Plug 20.0 A Settings Phase Ir, 80A Sensor B (20) (20A) LTD (2 - 24s) 12 STPU (2 - 12 x Ir) 12 (240A) STD FLAT (Inst-300ms) Inst (J,K,L) INST OR Fixed (960A)
AHU-1 (EP2)
MSB-CLC2 MAIN
CUTLER-HAMMER
LG Frame, 310+
LGE
Trip 600.0 A Settings Phase Ir for In = 600A H (600A) LTD (2-24 Sec.) 10 STPU (2-12 x Ir) 7 (4200A) STD (Flat) 120ms (M,N,O)
INST 12 (7200A)
AHU-1 (EP2) FDR
CUTLER-HAMMER
FDE/FDCE/HFDE, 310+
FDE
Trip 80.0 A Plug 20.0 A Settings Phase Ir, 80A Sensor B (20) (20A) LTD (2 - 24s) 12 STPU (2 - 12 x Ir) 12 (240A) STD FLAT (Inst-300ms) Inst (J,K,L) INST OR Fixed (960A)
AHU-1 (EP2)
MSB-CLC2 MAIN
AHU-1 (EP2) FDR
AHU-1 (EP2) VFD
AHU-1 (EP2)
MSB-CLC2
CBL-0008
AHU-1 (EP2) Current Scale x 10 Reference Voltage: 480 August 15, 2017 12:50 PM SKM Systems Analysis, Inc.
K
K
0.010.01
0.100.10
100100
10001000
CURRENT IN AMPERES
T
IM
E
IN
S
E C
O N
D S T
IM
E
I N
S E
C O
N D
S
PANEL LH1 MAIN
CUTLER-HAMMER
FDE/FDCE/HFDE, 310+
FDE
Trip 160.0 A Plug 160.0 A Settings Phase Ir, 160A Sensor E (100) (100A) LTD (2 - 24s) 7 STPU (2 - 12 x Ir) 12 (1200A) STD FLAT (Inst-300ms) 300ms (P,Q,R) INST OR Fixed (1920A)
XFMR T-LL1 FDR
CUTLER-HAMMER
FD
FD
Trip 50.0 A Settings Phase Fixed
MSB-CLC2 MAIN
CUTLER-HAMMER
LG Frame, 310+
LGE
Trip 600.0 A Settings Phase Ir for In = 600A H (600A) LTD (2-24 Sec.) 10 STPU (2-12 x Ir) 7 (4200A) STD (Flat) 120ms (M,N,O)
INST 12 (7200A)
ATS-L FDR
CUTLER-HAMMER
FDE/FDCE/HFDE, 310+
FDE
Trip 160.0 A Plug 160.0 A Settings Phase Ir, 160A Sensor E (100) (100A) LTD (2 - 24s) 7 STPU (2 - 12 x Ir) 12 (1200A) STD FLAT (Inst-300ms) 300ms (P,Q,R) INST OR Fixed (1920A)
PANEL LH1 MAIN
CUTLER-HAMMER
FDE/FDCE/HFDE, 310+
FDE
Trip 160.0 A Plug 160.0 A Settings Phase Ir, 160A Sensor E (100) (100A) LTD (2 - 24s) 7 STPU (2 - 12 x Ir) 12 (1200A) STD FLAT (Inst-300ms) 300ms (P,Q,R) INST OR Fixed (1920A)
XFMR T-LL1 FDR
CUTLER-HAMMER
FD
FD
Trip 50.0 A Settings Phase Fixed
MSB-CLC2 MAIN
CUTLER-HAMMER
LG Frame, 310+
LGE
Trip 600.0 A Settings Phase Ir for In = 600A H (600A) LTD (2-24 Sec.) 10 STPU (2-12 x Ir) 7 (4200A) STD (Flat) 120ms (M,N,O)
INST 12 (7200A)
ATS-L FDR
CUTLER-HAMMER
FDE/FDCE/HFDE, 310+
FDE
Trip 160.0 A Plug 160.0 A Settings Phase Ir, 160A Sensor E (100) (100A) LTD (2 - 24s) 7 STPU (2 - 12 x Ir) 12 (1200A) STD FLAT (Inst-300ms) 300ms (P,Q,R) INST OR Fixed (1920A)
PANEL LH1
PANEL LH1 MAIN
XFMR T-LL1 FDR
MSB-CLC2 MAIN
ATS-L FDR
CBL-0009
EN
ATS-L
ATS-L BUS
CBL-0014
MSB-CLC2
PANEL LH1 Current Scale x 10 Reference Voltage: 480 August 15, 2017 12:55 PM SKM Systems Analysis, Inc.
K
K
0.010.01
0.100.10
100100
10001000
CURRENT IN AMPERES
T
IM
E
IN
S
E C
O N
D S T
IM
E
I N
S E
C O
N D
S
PANEL LL1 MAIN
CUTLER-HAMMER
BAB, 3-Pole
BAB
Trip 50.0 A Settings Phase Fixed
PANEL LL1 LGST
CUTLER-HAMMER
BAB, 1-Pole
BAB
Trip 20.0 A Settings Phase Fixed
PANEL LL1 MAIN
CUTLER-HAMMER
BAB, 3-Pole
BAB
Trip 50.0 A Settings Phase Fixed
PANEL LL1 LGST
CUTLER-HAMMER
BAB, 1-Pole
BAB
Trip 20.0 A Settings Phase Fixed
PANEL LL1
PANEL LL1 MAIN
PANEL LL1 LGST
PANEL LL1 Current Scale x 1 Reference Voltage: 208 August 15, 2017 12:55 PM SKM Systems Analysis, Inc.
K
K
0.010.01
0.100.10
100100
10001000
CURRENT IN AMPERES
T
IM
E
IN
S
E C
O N
D S T
IM
E
I N
S E
C O
N D
S
PANEL CH1 MAIN
CUTLER-HAMMER
FDE/FDCE/HFDE, 310+
FDE
Trip 225.0 A Plug 225.0 A Settings Phase Ir, 225A Sensor D (150) (150A) LTD (2 - 24s) 24 STPU (2 - 12 x Ir) 12 (1800A) STD FLAT (Inst-300ms) Inst (J,K,L) INST OR Fixed (2700A)
XFMR T-CL1 FDR
CUTLER-HAMMER
FD
FD
Trip 110.0 A Settings Phase Fixed
MSB-CLC2 MAIN
CUTLER-HAMMER
LG Frame, 310+
LGE
Trip 600.0 A Settings Phase Ir for In = 600A H (600A) LTD (2-24 Sec.) 10 STPU (2-12 x Ir) 7 (4200A) STD (Flat) 120ms (M,N,O)
INST 12 (7200A)
ATS-C FDR
CUTLER-HAMMER
FDE/FDCE/HFDE, 310+
FDE
Trip 225.0 A Plug 150.0 A Settings Phase Ir, 225A Sensor D (150) (150A) LTD (2 - 24s) 24 STPU (2 - 12 x Ir) 12 (1800A) STD FLAT (Inst-300ms) Inst (J,K,L) INST OR Fixed (2700A)
PANEL CH1 MAIN
CUTLER-HAMMER
FDE/FDCE/HFDE, 310+
FDE
Trip 225.0 A Plug 225.0 A Settings Phase Ir, 225A Sensor D (150) (150A) LTD (2 - 24s) 24 STPU (2 - 12 x Ir) 12 (1800A) STD FLAT (Inst-300ms) Inst (J,K,L) INST OR Fixed (2700A)
XFMR T-CL1 FDR
CUTLER-HAMMER
FD
FD
Trip 110.0 A Settings Phase Fixed
MSB-CLC2 MAIN
CUTLER-HAMMER
LG Frame, 310+
LGE
Trip 600.0 A Settings Phase Ir for In = 600A H (600A) LTD (2-24 Sec.) 10 STPU (2-12 x Ir) 7 (4200A) STD (Flat) 120ms (M,N,O)
INST 12 (7200A)
ATS-C FDR
CUTLER-HAMMER
FDE/FDCE/HFDE, 310+
FDE
Trip 225.0 A Plug 150.0 A Settings Phase Ir, 225A Sensor D (150) (150A) LTD (2 - 24s) 24 STPU (2 - 12 x Ir) 12 (1800A) STD FLAT (Inst-300ms) Inst (J,K,L) INST OR Fixed (2700A)
PANEL CH1
PANEL CH1 MAIN
XFMR T-CL1 FDR
MSB-CLC2 MAIN
ATS-C FDR
EN
ATS-C
ATS-C BUS
MSB-CLC2
CBL-0010
CBL-0016
PANEL CH1 Current Scale x 10 Reference Voltage: 480 August 15, 2017 12:53 PM SKM Systems Analysis, Inc.
TX Inrush
XFMR T-CL1
0.5 1 10 1
K
K
0.010.01
0.100.10
100100
10001000
CURRENT IN AMPERES
T
IM
E
IN
S
E C
O N
D S T
IM
E
I N
S E
C O
N D
S
PANEL CL1 MAIN
CUTLER-HAMMER
EDB, 2-3 Poles
EDB
Trip 225.0 A Settings Phase Fixed
PANEL CL2 FDR
CUTLER-HAMMER
BAB, 3-Pole
BAB
Trip 100.0 A Settings Phase Fixed
PANEL CH1 MAIN
CUTLER-HAMMER
FDE/FDCE/HFDE, 310+
FDE
Trip 225.0 A Plug 225.0 A Settings Phase Ir, 225A Sensor D (150) (150A) LTD (2 - 24s) 24 STPU (2 - 12 x Ir) 12 (1800A) STD FLAT (Inst-300ms) Inst (J,K,L) INST OR Fixed (2700A)
XFMR T-CL1 FDR
CUTLER-HAMMER
FD
FD
Trip 110.0 A Settings Phase Fixed
PANEL CL1 MAIN
CUTLER-HAMMER
EDB, 2-3 Poles
EDB
Trip 225.0 A Settings Phase Fixed
PANEL CL2 FDR
CUTLER-HAMMER
BAB, 3-Pole
BAB
Trip 100.0 A Settings Phase Fixed
PANEL CH1 MAIN
CUTLER-HAMMER
FDE/FDCE/HFDE, 310+
FDE
Trip 225.0 A Plug 225.0 A Settings Phase Ir, 225A Sensor D (150) (150A) LTD (2 - 24s) 24 STPU (2 - 12 x Ir) 12 (1800A) STD FLAT (Inst-300ms) Inst (J,K,L) INST OR Fixed (2700A)
XFMR T-CL1 FDR
CUTLER-HAMMER
FD
FD
Trip 110.0 A Settings Phase Fixed
PANEL CL1
PANEL CL1 MAIN
PANEL CL2 FDR
PANEL CH1
PANEL CH1 MAIN
XFMR T-CL1 FDR
CBL-0017
S
P
XFMR T-CL1
CBL-0020
PANEL CL1 Current Scale x 10 Reference Voltage: 208 August 15, 2017 12:54 PM SKM Systems Analysis, Inc.
K
K
0.010.01
0.100.10
100100
10001000
CURRENT IN AMPERES
T
IM
E
IN
S
E C
O N
D S T
IM
E
I N
S E
C O
N D
S
CB-EM-CLC2 FDR
SQUARE D
J-Frame, Powerpact
JJ
Trip 250.0 A Settings Phase Thermal Curve INST (5-10 x Trip) High (2500A)
CB-EM-CLC2 BKR
CUTLER-HAMMER
KD
KD
Trip 250.0 A Settings Phase Thermal Curve (Fixed) INST (5-10 x Trip) 10 (2500A)
CB-L BKR
CUTLER-HAMMER
EHD
EHD
Trip 100.0 A Settings Phase Fixed
CB-EM-CLC2 FDR
SQUARE D
J-Frame, Powerpact
JJ
Trip 250.0 A Settings Phase Thermal Curve INST (5-10 x Trip) High (2500A)
CB-EM-CLC2 BKR
CUTLER-HAMMER
KD
KD
Trip 250.0 A Settings Phase Thermal Curve (Fixed) INST (5-10 x Trip) 10 (2500A)
CB-L BKR
CUTLER-HAMMER
EHD
EHD
Trip 100.0 A Settings Phase Fixed
SBCM
CB-EM-CLC2 FDR
CBL-0015
CB-EM-CLC2
CB-EM-CLC2 BKR
CBL-0022
GUTTER TROUGH
CBL-0025
CB-L
CB-L BKR
CB-L Current Scale x 10 Reference Voltage: 480 August 7, 2017 3:42 PM SKM Systems Analysis, Inc.
K
K
0.010.01
0.100.10
100100
10001000
CURRENT IN AMPERES
T
IM
E
IN
S
E C
O N
D S T
IM
E
I N
S E
C O
N D
S
CB-EM-CLC2 FDR
SQUARE D
J-Frame, Powerpact
JJ
Trip 250.0 A Settings Phase Thermal Curve INST (5-10 x Trip) High (2500A)
CB-EM-CLC2 BKR
CUTLER-HAMMER
KD
KD
Trip 250.0 A Settings Phase Thermal Curve (Fixed) INST (5-10 x Trip) 10 (2500A)
CB-C BKR
CUTLER-HAMMER
FD
FD
Trip 150.0 A Settings Phase Fixed
CB-EM-CLC2 FDR
SQUARE D
J-Frame, Powerpact
JJ
Trip 250.0 A Settings Phase Thermal Curve INST (5-10 x Trip) High (2500A)
CB-EM-CLC2 BKR
CUTLER-HAMMER
KD
KD
Trip 250.0 A Settings Phase Thermal Curve (Fixed) INST (5-10 x Trip) 10 (2500A)
CB-C BKR
CUTLER-HAMMER
FD
FD
Trip 150.0 A Settings Phase Fixed
SBCM
CB-EM-CLC2 FDR
CBL-0015
CB-EM-CLC2
CB-EM-CLC2 BKR
CBL-0022
GUTTER TROUGH
CBL-0024
CB-C
CB-C BKR
CB-C Current Scale x 10 Reference Voltage: 480 August 7, 2017 3:40 PM SKM Systems Analysis, Inc.
K
K
0.010.01
0.100.10
100100
10001000
CURRENT IN AMPERES
T
IM
E
IN
S
E C
O N
D S T
IM
E
I N
S E
C O
N D
S
MSB-CLC2 FDR
CUTLER-HAMMER
SPB, RMS 510/610/810/910
SPB-100
Trip 800.0 A Plug 600.0 A Settings Ground GFPU (100-1200A Plug) K (600A) GFD (0.1-0.5 Sec.) 0.5 Sec. (I^2t Off)
MSB-CLC2 MAIN
CUTLER-HAMMER
LG, Series G
LGE
Trip 600.0 A Plug 600.0 A Settings Ground GFPU, (0.2 - 1 x In) 1X (600A) GFD, (Inst-300ms) 300ms (L,O,R)
NH1 TYP FDR
CUTLER-HAMMER
FD, 1-Pole
FD
Trip 20.0 A Settings Phase Fixed
PANEL NH1 FDR
CUTLER-HAMMER
FDE/FDCE/HFDE, 310+
FDE
Trip 160.0 A Plug 100.0 A Settings Ground GFPU, (0.2 - 1 x S) 1 (160A) GFD, (Inst - 300ms) 120ms (K,N,Q)
MSB-CLC2 FDR
CUTLER-HAMMER
SPB, RMS 510/610/810/910
SPB-100
Trip 800.0 A Plug 600.0 A Settings Ground GFPU (100-1200A Plug) K (600A) GFD (0.1-0.5 Sec.) 0.5 Sec. (I^2t Off)
MSB-CLC2 MAIN
CUTLER-HAMMER
LG, Series G
LGE
Trip 600.0 A Plug 600.0 A Settings Ground GFPU, (0.2 - 1 x In) 1X (600A) GFD, (Inst-300ms) 300ms (L,O,R)
NH1 TYP FDR
CUTLER-HAMMER
FD, 1-Pole
FD
Trip 20.0 A Settings Phase Fixed
PANEL NH1 FDR
CUTLER-HAMMER
FDE/FDCE/HFDE, 310+
FDE
Trip 160.0 A Plug 100.0 A Settings Ground GFPU, (0.2 - 1 x S) 1 (160A) GFD, (Inst - 300ms) 120ms (K,N,Q)
MDBU
MSB-CLC2 FDR
CBL-0003
MSB-CLC2 MAIN
MSB-CLC2
PANEL NH1 FDR
CBL-0004
PANEL NH1
NH1 TYP FDR
GROUND FAULT Current Scale x 10 Reference Voltage: 480 August 15, 2017 1:56 PM SKM Systems Analysis, Inc.
Table 3: Adjustable Breaker Settings Table Bus Device Name Manufacturer/Style Frame/Plug
(Amps)
Trip Unit LTPU LTD STPU STD INST GFPU GFD
MDBU MSB-CLC2 FDR Eaton/SPB-100 800/600 Digitrip
910 LSIG
(600A)
12s S2
(4800A)
0.2s M2
(6000A) K
(600A)
0.5s
SBCM CB-EM-CLC2 FDR Square D/JJ 250/250 T/M - - - - 10
(2500A)
MSB-CLC2 MSB-CLC2 MAIN Eaton/LGE 600/600 Digitrip
310+ LSIG
H
(600A)
10s 7
(4200A)
120ms 12
(7200A) 1 (600A) 300ms
MSB-CLC2 PANEL NH1 FDR Eaton/FDE 225/160 Digitrip
310+ LSIG
E
(100A)
2s 12
(1200A)
Inst - 1 (160A) 120ms
MSB-CLC2 XFMR T-NL1 FDR Eaton/FDE 225/225 Digitrip
310+ LSIG
F
(175A)
24s 12
(2100A)
Inst - 1 (225A) 120ms
MSB-CLC2 CHILLER CH-1 FDR Eaton/FDE 225/225 Digitrip
310+ LSIG
B
(110A)
7s 10
(1100A)
Inst - 1 (225A) 120ms
MSB-CLC2 AHU-1 (EP1) FDR Eaton/FDE 225/160 Digitrip
310+ LSIG
A
(60A)
4s 8
(480A)
Inst - 1 (160A) 120ms
MSB-CLC2 AHU-1 (EP2) FDR Eaton/FDE 225/80 Digitrip
310+ LSIG
B
(20A)
12s 12
(240A)
Inst - 1 (80A) 120ms
MSB-CLC2 ATS-L FDR Eaton/FDE 225/160 Digitrip
310+ LSIG
E
(100A)
7s 12
(1200A)
300ms - 1 (160A) 120ms
MSB-CLC2 ATS-C FDR Eaton/FDE 225/225 Digitrip
310+ LSIG
D
(150A)
24s 12
(1800A)
Inst - 1 (225A) 120ms
PANEL NL1 PANEL NL1 MAIN Eaton/DK 400/400 T/M - - - - 10
(4000A)
PANEL LH1 PANEL LH1 MAIN Eaton/FDE 225/160 Digitrip
310+ LSI
E
(100A)
7s 12
(1200A)
300ms - - -
PANEL CH1 PANEL CH1 MAIN Eaton/FDE 225/225 Digitrip
310+ LSI
D
(150A)
24s 12
(1800A)
Inst - - -
CB-EM-CLC2 CB-EM-CLC2 BKR Eaton/KD 400/250 T/M - - - - 10
(2500A)
4 ARC FLASH RISK ASSESSMENT
4.1 Background and Analysis
The 2015 edition of NFPA 70E requires that an arc flash risk assessment be performed to determine if an arc flash hazard exists, the arc flash boundary, and the PPE to be used within the arc flash boundary. NFPA 70E also requires that the risk assessment be updated when a major renovation or modification to the electrical system occurs. Any modification to the power system that could cause a change in the available short circuit current or operating time of overcurrent protective devices (OCPDs) requires an update. In addition, NFPA
70E requires a periodic review (no more than five years) to determine if any changes have occurred that could change the assessment.
The severity of an arc flash event is dependent upon the operating time of the
OCPD which isolates the fault and the magnitude of the arcing fault current.
SKM calculates the arcing fault currents at protective devices using equations defined in IEEE Standard 1584-2002, IEEE Guide for Performing Arc Flash
Hazard Calculations. Arc flash incident energies in cal/cm2 at working distances defined in IEEE Standard 1584 are then determined. Appropriate arc rated (AR) PPE can then be selected. The purpose of arc rated PPE is to protect personnel working on energized equipment from the onset of a second-degree or just curable burn. An incident energy level of 1.2 cal/cm2 is considered the energy threshold for a second-degree burn. IEEE 1584 is applicable only to three-phase arcing faults (although single-phase or phase-phase arcing faults are generally expected to escalate to three-phase faults), and does not consider the effects of arc blast or other by-products of an arcing fault such as dangerous sound levels, molten metal droplets, and toxic vapors.
Arcing durations are capped at 2 seconds per IEEE 1584 Annex B.1.2.
Situations where a 2 second cutoff may not be appropriate include workers in a lift bucket inspecting or operating overcurrent devices in elevated plug-in busduct, or in other locations where escape from the arc flash boundary during an arc flash event is not possible. An internal VA Loma Linda contingency plan should be developed to address these situations.
NFPA 70B and 70E address the issue of equipment maintenance and its potential effect on the arc flash boundary and selection of PPE. The results of this study assume that existing protective devices have been properly installed and maintained, and will operate within their specified tolerances to clear faults from the system. Non-functioning OCPDs can allow arcing faults to persist for longer than normal, resulting in elevated incident energy values.
It is important to note that the calculated arc flash incident energy levels and arc flash boundaries do not pertain to the shock hazard that exists near all energized electrical equipment. NFPA 70E 130.4(A) requires a shock risk assessment to determine the voltage to which personnel will be exposed, the boundary requirements, and the PPE necessary to minimize the possibility of electric shock to personnel. NFPA 70E Tables 130.4(D)(a) and 130.4(D)(b) provide approach boundaries for nominal system voltages.
IEEE 1584 states that during testing, arcs on 208V systems were difficult to sustain, and arc flash levels on systems operating below 240V served by transformers smaller than 125kVA are “not a concern”. NFPA 70E-2015 article
130.5 Informational Note No. 5 refers to IEEE 1584 for more information regarding arc-flash hazards for three-phase systems. Based on these guidelines from the industry consensus standards, buses operating at less than 240V served by transformers smaller than 125kVA are assumed to have an incident energy of
1.2 cal/cm2.
4.2 Results and Recommendations
The results of the arc flash hazard analysis are given in Table 4. It is important to note that both large and small available short-circuit current magnitudes could result in higher available arc flash incident energies. If the available short-circuit current increases without a decrease in the opening time of the overcurrent protective device, the arc flash energy will increase. If the available short-circuit current decreases, resulting in a longer opening time for the overcurrent protective device, arc flash energies could also increase. Thus, two arc flash fault current scenarios were considered. The results in Table 4 show the worst-case for each respective equipment location included in the study.
Arc flash scenarios:
1. Utility source (MDBU)
2. Emergency source (SBCM)
The protective devices at the VA Loma Linda Community Living Center 2 were set as low as possible to reduce incident energy levels and still provide adequate coordination as required by NEC article 517.31(G).
Table 4: Arc Flash Risk Assessment Results Bus Name
Protective Device Name
Bus kV
Bolted Fault (kA)
Bus Arcing Fault (kA)
Prot Dev Bolted Fault (kA)
Prot Dev Arcing Fault (kA)
Trip/ Delay Time (sec.)
Breaker Opening Time/Tol
(sec.)
Equip Type
Gap (mm)
Arc Flash
Boundary (in)
Working Distance
(in)
Incident Energy
(cal/cm2)
AHU-1 (EP1) VFD AHU-1 (EP1)
FDR
0.48 4.33 3.21 4.25 3.15 0.05 0.0000 PNL 25 10 18 0.49
AHU-1 (EP2) VFD AHU-1 (EP2)
FDR
0.48 2.16 1.77 2.13 1.75 0.05 0.0000 PNL 25 7 18 0.26
ATS-C BUS ATS-C FDR 0.48 12.33 6.67 12.33 6.67 0.0473 0.0000 0.0000 25 16 18 1.0
ATS-L BUS ATS-L FDR 0.48 12.12 7.73 12.12 7.73 0.0252 0.0000 0.0000 25 12 18 0.63
CB-C CB-EM-
CLC2 BKR
0.48 5.11 3.70 5.11 3.70 0.0181 0.0000 PNL 25 6 18 0.20
CB-EM-CLC1 CB-EM-
CLC2 BKR
0.48 5.11 3.70 5.11 3.70 0.0181 0.0000 PNL 25 6 18 0.20
CB-EM-CLC2 CB-EM-
CLC2 FDR
0.48 5.29 3.80 5.29 3.80 0.0161 0.0000 PNL 25 6 18 0.19
CB-L CB-EM-
CLC2 BKR
0.48 5.10 3.13 5.10 3.13 0.0216 0.0000 PNL 25 6 18 0.20
CH-1 DISC CHILLER
CH-1 FDR
0.48 8.20 5.54 7.81 5.27 0.05 0.0000 PNL 25 15 18 0.88
LTG CNTRL LCP1 PANEL NH1
FDR
0.48 10.60 5.86 10.60 5.86 0.0351 0.0000 PNL 25 12 18 0.65
MSB-CLC2 MSB-CLC2
FDR
0.48 12.93 6.94 12.24 6.57 0.24 0.0000 PNL 25 44 18 5.2
PANEL CH1 ATS-C FDR 0.48 11.50 6.28 11.50 6.28 0.05 0.0000 PNL 25 16 18 1.0
PANEL CL1 XFMR T-CL1
FDR
0.208 4.69 2.56 4.69 2.56 1.279 0.0000 PNL 25 18 18 1.2
PANEL CL2 PANEL CL2
FDR
0.208 4.57 2.51 4.57 2.51 0.01 0.0000 PNL 25 3 18 0.07
PANEL LH1 ATS-L FDR 0.48 11.36 6.22 11.36 6.22 0.0323 0.0000 PNL 25 12 18 0.64
Bus Name
Protective Device Name kV
Bolted Fault (kA)
Bus Arcing Fault (kA)
Prot Dev Bolted Fault (kA)
Prot Dev Arcing Fault (kA)
Trip/ Delay Time (sec.)
Breaker Opening Time/Tol
(sec.)
Equip Type
Gap (mm)
Arc Flash
Boundary (in)
Working Distance
(in)
Incident Energy
(cal/cm2)
PANEL LL1 XFMR T-LL1
0.208 1.10 0.92 1.10 0.92 2 0.0000 PNL 25 18 18 1.2
PANEL NH1 PANEL NH1
FDR
0.48 12.18 7.76 12.18 7.76 0.0251 0.0000 PNL 25 12 18 0.63
PANEL NL1 XFMR T-NL1
FDR
0.208 5.36 2.81 5.36 2.81 2 0.0000 PNL 25 18 18 1.2
PANEL NL2 PANEL NL2
0.208 5.28 2.78 5.28 2.78 2 0.0000 PNL 25 18 18 1.2
5 STUDY ONE-LINE DIAGRAM
See one-line diagram E-600 on the attached page.
6 ARC FLASH LABELS
See typical arc flash label on the attached page.
7 SHORT CIRCUIT INPUT/OUTPUT DATA
Aug 08, 2017 10:21:48 Page 1
ALL INFORMATION PRESENTED IS FOR REVIEW, APPROVAL
INTERPRETATION AND APPLICATION BY A REGISTERED ENGINEER ONLY
SKM DISCLAIMS ANY RESPONSIBILITY AND LIABILITY RESULTING
FROM THE USE AND INTERPRETATION OF THIS SOFTWARE.
SKM POWER*TOOLS FOR WINDOWS
INPUT DATA REPORT
COPYRIGHT SKM SYSTEMS ANALYSIS, INC. 1995-2016
ALL PU VALUES ARE EXPRESSED ON A 100 MVA BASE.
Aug 08, 2017 10:21:48 Page 2
FEEDER INPUT DATA
CABLE FEEDER FROM FEEDER TO QTY VOLTS LENGTH FEEDER
NAME NAME NAME /PH L-L SIZE TYPE
CBL-0003 MDBU MSB-CLC2 2 480 430.0 FEET 350 Copper
Duct Material: Magnetic Insulation Type: PVC Insulation Class: THWN
+/- Impedance: 0.0378 + J 0.0491 Ohms/1000 ft 3.53 + J 4.58 PU
Z0 Impedance: 0.1191 + J 0.1209 Ohms/1000 ft 11.11 + J 11.28 PU
CBL-0004 MSB-CLC2 PANEL NH1 1 480 10.0 FEET 2 Copper
Duct Material: Non-Magnetic Insulation Type: PVC Insulation Class: THWN
+/- Impedance: 0.2020 + J 0.0467 Ohms/1000 ft 0.8767 + J 0.2027 PU
Z0 Impedance: 0.3211 + J 0.1188 Ohms/1000 ft 1.39 + J 0.5156 PU
CBL-0005 MSB-CLC2 XFMR T-NL1 PRI 1 480 10.0 FEET 2/0 Copper
Duct Material: Magnetic Insulation Type: PVC Insulation Class: THWN
+/- Impedance: 0.1020 + J 0.0533 Ohms/1000 ft 0.4427 + J 0.2313 PU
Z0 Impedance: 0.3214 + J 0.1312 Ohms/1000 ft 1.39 + J 0.5694 PU
CBL-0006 MSB-CLC2 CH-1 DISC 1 480 100.0 FEET 1 Copper
+/- Impedance: 0.1600 + J 0.0456 Ohms/1000 ft 6.94 + J 1.98 PU
Z0 Impedance: 0.2543 + J 0.1160 Ohms/1000 ft 11.04 + J 5.03 PU
CBL-0007 MSB-CLC2 AHU-1 (EP1) VF 1 480 100.0 FEET 6 Copper
+/- Impedance: 0.5100 + J 0.0548 Ohms/1000 ft 22.14 + J 2.38 PU
Z0 Impedance: 0.8123 + J 0.1394 Ohms/1000 ft 35.26 + J 6.05 PU
CBL-0008 MSB-CLC2 AHU-1 (EP2) VF 1 480 100.0 FEET 10 Copper
+/- Impedance: 1.18 + J 0.0823 Ohms/1000 ft 51.22 + J 3.57 PU
Z0 Impedance: 1.88 + J 0.2093 Ohms/1000 ft 81.42 + J 9.08 PU
CBL-0009 MSB-CLC2 ATS-L (N) 1 480 10.0 FEET 2 Copper
+/- Impedance: 0.2020 + J 0.0585 Ohms/1000 ft 0.8767 + J 0.2539 PU
Z0 Impedance: 0.6366 + J 0.1440 Ohms/1000 ft 2.76 + J 0.6250 PU
CBL-0010 MSB-CLC2 ATS-C (N) 1 480 10.0 FEET 1/0 Copper
+/- Impedance: 0.1280 + J 0.0540 Ohms/1000 ft 0.5556 + J 0.2344 PU
Z0 Impedance: 0.4034 + J 0.1329 Ohms/1000 ft 1.75 + J 0.5768 PU
CBL-0011 PANEL NH1 LTG CNTRL LCP1 1 480 10.0 FEET 6 Copper
+/- Impedance: 0.5100 + J 0.0685 Ohms/1000 ft 2.21 + J 0.2973 PU
Z0 Impedance: 1.61 + J 0.1687 Ohms/1000 ft 6.98 + J 0.7322 PU
Aug 08, 2017 10:21:48 Page 3
CBL-0012 XFMR T-NL1 SEC PANEL NL1 1 208 20.0 FEET 600 Copper
Duct Material: Magnetic Insulation Type: PVC Insulation Class: THWN
+/- Impedance: 0.0257 + J 0.0463 Ohms/1000 ft 1.19 + J 2.14 PU
Z0 Impedance: 0.0809 + J 0.1140 Ohms/1000 ft 3.74 + J 5.27 PU
CBL-0013 PANEL NL1 PANEL NL2 1 208 5.0 FEET 4/0 Copper
+/- Impedance: 0.0640 + J 0.0497 Ohms/1000 ft 0.7396 + J 0.5744 PU
Z0 Impedance: 0.2017 + J 0.1224 Ohms/1000 ft 2.33 + J 1.41 PU
CBL-0014 ATS-L BUS PANEL LH1 1 480 10.0 FEET 2 Copper
CBL-0015 SBCM CB-EM-CLC2 1 480 535.0 FEET 350 Copper
+/- Impedance: 0.0378 + J 0.0491 Ohms/1000 ft 8.78 + J 11.40 PU
Z0 Impedance: 0.1191 + J 0.1209 Ohms/1000 ft 27.66 + J 28.07 PU
CBL-0016 ATS-C BUS PANEL CH1 1 480 15.0 FEET 1/0 Copper
+/- Impedance: 0.1280 + J 0.0540 Ohms/1000 ft 0.8333 + J 0.3516 PU
Z0 Impedance: 0.4034 + J 0.1329 Ohms/1000 ft 2.63 + J 0.8652 PU
CBL-0017 PANEL CH1 XFMR T-CL1 PRI 1 480 10.0 FEET 1/0 Copper
CBL-0018 PANEL LH1 XFMR T-LL1 PRI 1 480 20.0 FEET 10 Copper
+/- Impedance: 1.18 + J 0.0854 Ohms/1000 ft 10.24 + J 0.7413 PU
Z0 Impedance: 3.72 + J 0.2103 Ohms/1000 ft 32.28 + J 1.83 PU
CBL-0019 XFMR T-LL1 SEC PANEL LL1 1 208 5.0 FEET 6 Copper
+/- Impedance: 0.5100 + J 0.0685 Ohms/1000 ft 5.89 + J 0.7917 PU
Z0 Impedance: 1.61 + J 0.1687 Ohms/1000 ft 18.57 + J 1.95 PU
CBL-0020 XFMR T-CL1 SEC PANEL CL1 1 208 20.0 FEET 250 Copper
+/- Impedance: 0.0552 + J 0.0495 Ohms/1000 ft 2.55 + J 2.29 PU
Z0 Impedance: 0.1739 + J 0.1219 Ohms/1000 ft 8.04 + J 5.64 PU
Aug 08, 2017 10:21:48 Page 4
CBL-0021 PANEL CL1 PANEL CL2 1 208 5.0 FEET 2 Copper
Duct Material: Magnetic Insulation Type: PVC Insulation Class: THWN
+/- Impedance: 0.2020 + J 0.0585 Ohms/1000 ft 2.33 + J 0.6761 PU
Z0 Impedance: 0.6366 + J 0.1440 Ohms/1000 ft 7.36 + J 1.66 PU
CBL-0022 CB-EM-CLC2 GUTTER TROUGH 1 480 20.0 FEET 350 Copper
+/- Impedance: 0.0378 + J 0.0491 Ohms/1000 ft 0.3281 + J 0.4262 PU
Z0 Impedance: 0.1191 + J 0.1209 Ohms/1000 ft 1.03 + J 1.05 PU
CBL-0023 GUTTER TROUGH CB-EM-CLC1 (FU 1 480 5.0 FEET 1/0 Copper
+/- Impedance: 0.1280 + J 0.0540 Ohms/1000 ft 0.2778 + J 0.1172 PU
Z0 Impedance: 0.4034 + J 0.1329 Ohms/1000 ft 0.8754 + J 0.2884 PU
CBL-0024 GUTTER TROUGH CB-C 1 480 5.0 FEET 1/0 Copper
+/- Impedance: 0.1280 + J 0.0540 Ohms/1000 ft 0.2778 + J 0.1172 PU
Z0 Impedance: 0.4034 + J 0.1329 Ohms/1000 ft 0.8754 + J 0.2884 PU
CBL-0025 GUTTER TROUGH CB-L 1 480 5.0 FEET 2 Copper
+/- Impedance: 0.2020 + J 0.0585 Ohms/1000 ft 0.4384 + J 0.1270 PU
Z0 Impedance: 0.6366 + J 0.1440 Ohms/1000 ft 1.38 + J 0.3125 PU
CBL-0026 CB-L ATS-L (E) 1 480 10.0 FEET 2 Copper
CBL-0027 CB-C ATS-C (E) 1 480 10.0 FEET 1/0 Copper
Aug 08, 2017 10:21:48 Page 5
TRANSFORMER INPUT DATA
TRANSFORMER PRIMARY RECORD VOLTS * SECONDARY RECORD VOLTS FULL-
LOAD NOMINAL
NAME NO NAME L-L NO NAME L-L KVA KVA
XFMR T-CL1 XFMR T-CL1 PRI D 480.00 XFMR T-CL1 SEC YG 208.00 112.50 75.00
Pos. Seq. Z%: 1.03 + J 3.25 (Zpu 13.73 + j 43.34) Shell Type
Zero Seq. Z%: 1.03 + J 3.25 (Sec 13.73 + j 43.34 Pri Open)
Taps Pri. 0.000 % Sec. 0.000 % Phase Shift (Pri. Leading Sec.): 30.00 Deg.
XFMR T-LL1 XFMR T-LL1 PRI D 480.00 XFMR T-LL1 SEC YG 208.00 112.50 15.00
Pos. Seq. Z%: 1.32 + J 3.26 (Zpu 88.07 + j 217.5) Shell Type
Zero Seq. Z%: 1.32 + J 3.26 (Sec 88.07 + j 217.5 Pri Open)
XFMR T-NL1 XFMR T-NL1 PRI D 480.00 XFMR T-NL1 SEC YG 208.00 112.50 112.50
Pos. Seq. Z%: 1.27 + J 4.30 (Zpu 11.26 + j 38.20) Shell Type
Zero Seq. Z%: 1.27 + J 4.30 (Sec 11.26 + j 38.20 Pri Open)
Aug 08, 2017 10:21:48 Page 6
GENERATION CONTRIBUTION DATA
BUS CONTRIBUTION VOLTAGE
NAME NAME L-L MVA X"d X/R
MDBU MDBU SC 480.00 23.01
Three Phase Contribution: 27680.0 AMPS 6.02
Single Line to Ground Contribution: 27756.0 AMPS 5.10
Pos Sequence Impedance (100 MVA Base) 0.7121 + J 4.29 PU
Zero Sequence Impedance (100 MVA Base) 1.08 + J 4.18 PU
SBCM SBCM SC 480.00 11.23
Three Phase Contribution: 13512.0 AMPS 4.65
Single Line to Ground Contribution: 11496.0 AMPS 3.49
Pos Sequence Impedance (100 MVA Base) 1.87 + J 8.70 PU
Zero Sequence Impedance (100 MVA Base) 4.90 + J 12.77 PU
Aug 08, 2017 10:21:48 Page 7
MOTOR CONTRIBUTION DATA
BUS CONTRIBUTION VOLTAGE BASE Motor
NAME NAME L-L kVA X"d X/R Number
AHU-1 (EP1) VF AHU-1 (EP1) 480 20.05 0.1531 10.0 1.00
Pos Sequence Impedance (100 MVA Base) 76.33 + j 763.36 PU
AHU-1 (EP2) VF AHU-1 (EP2) 480 10.03 0.1531 10.0 1.00
Pos Sequence Impedance (100 MVA Base) 152.67 + j 1526.72 PU
CH-1 DISC CH-1 480 63.87 0.1531 10.0 1.00
Pos Sequence Impedance (100 MVA Base) 23.97 + j 239.67 PU
Short-Circuit Report
Aug 09, 2017 08:20:58
ALL INFORMATION PRESENTED IS FOR REVIEW, APPROVAL
INTERPRETATION AND APPLICATION BY A REGISTERED ENGINEER ONLY
SKM DISCLAIMS ANY RESPONSIBILITY AND LIABILITY RESULTING
FROM THE USE AND INTERPRETATION OF THIS SOFTWARE.
SKM POWER*TOOLS FOR WINDOWS
SHORT CIRCUIT ANALYSIS REPORT
COPYRIGHT SKM SYSTEMS ANALYSIS, INC. 1995-2016
Aug 09, 2017 08:20:58 PAGE 2
ALL PU VALUES ARE EXPRESSED ON A 100 MVA BASE
SWING GENERATORS
BUS NAME SOURCE NAME VOLTAGE ANGLE
MDBU MDBU SC 1.00 0.00
SBCM SBCM SC 1.00 0.00
Aug 09, 2017 08:20:58 PAGE 3
************* P R E - F A U L T V O L T A G E P R O F I L E **************
BUS# NAME BASE VOLTS PU VOLTS ANGLE (D)
AHU-1 (EP1) VF 480.00 1.0000 0.
AHU-1 (EP2) VF 480.00 1.0000 0.
ATS-C BUS 480.00 1.0000 0.
ATS-L BUS 480.00 1.0000 0.
CB-C 480.00 1.0000 0.
CB-EM-CLC1 (FU 480.00 1.0000 0.
CB-EM-CLC2 480.00 1.0000 0.
CB-L 480.00 1.0000 0.
CH-1 DISC 480.00 1.0000 0.
GUTTER TROUGH 480.00 1.0000 0.
LTG CNTRL LCP1 480.00 1.0000 0.
MDBU 480.00 1.0000 0.
MSB-CLC2 480.00 1.0000 0.
PANEL CH1 480.00 1.0000 0.
PANEL CL1 208.00 1.0000 -30.
PANEL CL2 208.00 1.0000 -30.
PANEL LH1 480.00 1.0000 0.
PANEL LL1 208.00 1.0000 -30.
PANEL NH1 480.00 1.0000 0.
PANEL NL1 208.00 1.0000 -30.
PANEL NL2 208.00 1.0000…