E-111.pdf

PDF 702 KB Posted

Attached to
H959--ARC FLASH ANALYSIS - POP (09/01/2024 - 08/31/2025)
Solicitation number
36C26224Q1724
Issued by

About this file

This document is a combined synopsis/solicitation for a commercial services contract for an Arc Flash Analysis at the VA Loma Linda Healthcare System (VALLHCS) in Loma Linda, CA. The VA is seeking a contractor to provide all labor, materials, and services to complete the Arc Flash Analysis, which is required every 5 years to comply with NFPA 99, NFPA 70E, IEEE, and Joint Commission standards. The analysis will cover the 12kV, 408/277V, and 208/120V electrical systems at the facility, including transformers, power panels, load centers, and disconnects. The contractor must possess specific qualifications, including a 30-hour OSHA safety card, electrical C-10 license, and NFPA/NICET certification. The period of performance is 09/01/2024 - 08/31/2025, and the contract is set aside for 100% Service-Disabled Veteran-Owned Small Businesses (SDVOSB). Proposals are due by 08/23/2024 at 10:00 PDT.

View the file

Other files

File Type Posted
Loma Linda-60pc.pdf PDF
Tbl 3_3 Equip Eval.pdf PDF
E-110.pdf PDF
EYE Clinic One Line Drawings.docx DOCX document
E-115.pdf PDF
E-114.pdf PDF
116801E5.1.8.pdf PDF
E1.1 AUDIOLOGY.pdf PDF
Arc Flash Study CLC Ph 2.pdf PDF
116801E5.1.5.pdf PDF
Tbl 6-1_2_Arc_Flash.pdf PDF
116801E5.1.3.pdf PDF
116801E5.1.11.pdf PDF
Short Circuit Study - Op Pharmacy.pdf PDF
E-112.pdf PDF
E601 BEHAVIORAL HEALTH BUILDING.pdf PDF
116801E5.1.1.pdf PDF
116801E5.1.2.pdf PDF
116801E5.1.10.pdf PDF
E-102.pdf PDF
36C26224Q1724_1.docx DOCX document
116801E5.1.4.pdf PDF
E-001.pdf PDF
116801E5.1.6.pdf PDF
116801E5.1.7.pdf PDF
116801E5.1.9.pdf PDF
E-105.pdf PDF
022712 SCC and OCPD Coordination Study - VA Loma Linda.pdf PDF
lf_calc format.pdf PDF
VALL Electrical Single Line Diagrams.pdf PDF
E-101.pdf PDF
Cover.pdf PDF
E-108.pdf PDF
E-104.pdf PDF
20110460 - Sheet - E-611 - SINGLE LINE DIAGRAM OP Pharmacy.pdf PDF
Arc Flash Study CLC Reb.pdf PDF
E-107.pdf PDF
CANCER CENTER SIGNAL LINE DRAWINGS 2017.png PNG image
input_data format.pdf PDF
Arc Flash Study 2016 Schneider Full Facility.pdf PDF
E-106.pdf PDF
79of89-EE002 PARKING GARAGE.pdf PDF
116801E5.1.12.pdf PDF
E-113.pdf PDF
MV Coordination Descrip Tbl.pdf PDF
CLC PC SIGNAL LINE DRAWINGS.png PNG image
E-103.pdf PDF
CLC ReHab SIGNAL LINE DRAWINGS.png PNG image
Tbl 4_1 MV Prot Dev Settingsa.pdf PDF
Loma Linda MV TCCs.pdf PDF
Show 40 more

Latest 50 of 54 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

E-111

ONE-LINE DIAGRAM

SERVICE BAY 5-7 - US-3A

t h r e e q u a r t e r s i n c h o n e f o o t o n e q u a r t e r i n c h o n e f o o t o n e e i g h t h i n c h o n e f o o t t h r e e e i g h t h s i n c h o n e f o o t

F o n e h a l f i n c h o n e f o o t

E

D

2 3 4 5 o n e i n c h o n e f o o t

C o n e h a l f i n c h o n e f o o t

B t h r e e i n c h e s o n e f o o t

A

1 2 3 4 5

Project Location

Building Number

6 7 8

Drawing Title

Scale

Revision

No. Date

VA MEDICAL CENTER

LOMA LINDA, CA

U.S. GOVERNMENT PRINTING OFFICE: 1983-400-285

DWG. Of

Checked

SAB

Drawn

DRAWING NO.

F E

D

6 7 8

C B

A

NO SCALE

Fax: 757-471-4205

Ph: 757-471-0537

Norfolk, VA 23510

101 West Main Street, Suite 7000

World Trade Center

ELT

LLCMiller-Remick

FAX: (856)429-5002

PHONE: (856)429-4000

CHERRY HILL, NEW JERSEY 08034

1010 KINGS HIGHWAY SOUTH

M.E.P. & Structural Engineering

Small Business

A Service Disabled Veteran Owned

A S e r v ic e D i s a b le d V eteran Ow ne d S m a l l B u s in e ss

SDVOSB

EVC

434.947.1901 | wileywilson.com | 100% Employee-Owned

127 Nationwide Drive | Lynchburg, VA 24502

NO SCALE

SERVICE BAY 5-7 - US-3A ONE-LINE DIAGRAM

SEE "ATS 3SB7 -- SERVICE BAY 5-7 US-3A

ONE-LINE DIAGRAM" FOR CONTINUATION

SEE "SWBD US-3B -- SERVICE BAY 5-7 US-3B ONE-LINE DIAGRAM"

FOR CONTINUATION

SEE "ATS EM -- SERVICE BAY 5-6 PNLS CU, EU, CM, EM

ONE-LINE DIAGRAM" FOR CONTINUATION

SEE "SWBD D4MH -- SERVICE BAY 5-7 D4MH

ONE-LINE DIAGRAM" FOR CONTINUATION

SEE "BUS 1_SW US-3B WEST -- SERVICE BAY 5-7 US-3B

ONE-LINE DIAGRAM" FOR CONTINUATION

SEE "BUS 1_SW US-3B WEST -- SERVICE BAY 5-7 US-3B

ONE-LINE DIAGRAM" FOR CONTINUATION

SEE "ATS CM -- SERVICE BAY 5-6 PNLS

CU, EU, CM, EM ONE-LINE DIAGRAM"

FOR CONTINUATION

SEE "SWBD D1MH -- SERVICE BAY 5-7 D1MH

ONE-LINE DIAGRAM" FOR CONTINUATION

SEE "SWBD D2MH -- SERVICE BAY 5-7 D2MH

ONE-LINE DIAGRAM" FOR CONTINUATION

SEE "SWBD DPMHA -- SERVICE BAY 5-7

DPMHA ONE-LINE DIAGRAM" FOR

CONTINUATION

SWBD: 1_US 3A

480V, 2500A

65k SCAR

CB: 1_US 3A Main

WESTINGHOUSE (DS-632)

2400 A, 2400 A Plug

CB: 1_D3MH

WESTINGHOUSE (SPB-100)

600 A, 600 A Plug

CB: 1_MCC-MMA

WESTINGHOUSE (SPB-100)

400 A, 400 A Plug

CB: 1_D4MH

WESTINGHOUSE (SPB-100)

600 A, 600 A Plug

CB: 1_DPMH

WESTINGHOUSE (SPB-100)

200 A, 200 A Plug

CB: 1_D2MH

WESTINGHOUSE (SPB-100)

600 A, 600 A Plug

CB: 1_HXRP-A

WESTINGHOUSE (SPB-100)

600 A, 600 A Plug

CB: 1_D1MH

WESTINGHOUSE (SPB-100)

800 A, 800 A Plug

CB: 1_DPMHA Penthouse 4

WESTINGHOUSE (SPB-100)

800 A, 800 A Plug

CB: 1_HXRP-B

WESTINGHOUSE (SPB-100)

400 A, 400 A Plug

F: 1_Disc SW-CM

(2) #350 THWN; 10 ft

F: 1_Disc SW-EM

(1) #1/0 THWN; 10 ft

F: 1_SWBD US 3A

(1) #2500 Class B; 2 ft

F: 1_D3MH

(2) #250 THWN; 70 ft

SWBD: 1_D3MH

480V, 600A

65k SCAR

F: 1_MCC-MMA

(1) #500 THWN; 50 ft

MCC: 1_MMA

480V, 600A

65k SCAR

F: 1_DPMH

(1) #250 THWN; 180 ft

SWBD: 1_DPMH

480V, 400A

65k SCAR

F: 1_D2MH

(2) #250 THWN; 50 ft F: 1_HXRP-A

(2) #350 THWN; 220 ft

PNL: 1_HXRP-A

480V, 600A

100k SCAR

F: 1_D1MH

(2) #500 THWN; 30 ft

F: 1_DPMHA Penthouse 4

(2) #400 THWN; 280 ftF: 1_HXRP-B

(1) #500 THWN; 200 ft

PNL: 1_HXRP-B

480V, 600A

200k SCAR

DISC: 1_SW-CM

480V, 600A

DISC: 1_SW-EM

480V, 150A

CB: 1_ATS-CM N

SQUARE D (LX / LXI)

600 A, 600 A Plug

F: 1_ATS-CM N

(2) #350 THWN; 45 ft

FU: 1_Symbia 4E32 IPPA

FERRAZ SHAWMUT (TRS)

100 A

FU: 1_Symbia 4E32 IPPB

FERRAZ SHAWMUT (TRS)

100 A

FU: 1_Switch 1 Pnl A 3E26

LITTELFUSE (FLSR)

150 A

FU: 1_Switch4 CT-4E30

FERRAZ SHAWMUT (TRS)

200 A

F: 1_Symbia 4E32 IPPA

(1) #1 THWN; 30 ft

CB: 1_IPPA Main

GE (SELA)

100 A, 100 A Plug

PNL: 1_IPPA

480V, 225A

18k SCAR

F: 1_Symbia 4E32 IPPB

(1) #1 THWN; 1 ft

F: 1_Switch 1 Pnl A 3E26

(1) #1/0 THWN; 70 ft

DISC: 1_PDB1

480V, F: 1_Switch4 CT-4E30

(1) #2/0 THWN; 20 ft

CB: 1_CT-4E30 MP Main

GE (SFHA)

225 A, 225 A Plug

PNL: 1_CT-4E30 MP

480V, 225A

14k SCAR

CB: 1_PDB1

GE (SFLA)

150 A, 150 A Plug

F: 1_PDB1

(1) #1/0 THWN; 1 ft

CB: 1_Line Conn Box

GE (TEY)

80 A

F: 1_Line Conn Box

(1) #4 THWN; 1 ft

CB: 1_PDU

GE (TED)

150 A, 150 A Plug

CB: 1_Indoor Heat Cabinet

GE (TEY)

40 A

F: 1_PDU

(1) #1/0 THWN; 1 ft

F: 1_Indoor Heat Cabinet

(1) #6 THWN; 1 ft

CB: 1_Elev 3

CUTLER-HAMMER (HFD)

100 A

CB: 1_Elev P-1

CUTLER-HAMMER (HFD)

100 A

CB: 1_Elev P-2

CUTLER-HAMMER (HFD)

100 A

F: 1_Elev 3

(1) #2 THWN; 25 ft

F: 1_Elev P-1

(1) #2 THWN; 20 ft

F: 1_Elev P-2

(1) #2 THWN; 25 ft

FU: 1_MRI Rm 3A-9E

FERRAZ SHAWMUT (TRS)

150 A

FU: 1_3MHB

FERRAZ SHAWMUT (TRS)

125 A

FU: 1_ALT T-U3 3SB7 ATS-E

BUSSMANN (FRS-R)

100 A

FU: 1_3MHA

BUSSMANN (KTS-R)

125 A

FU: 1_XFMR M-3

BUSSMANN (JKS)

225 A

F: 1_MRI Rm 3A-9E

(1) #2/0 THWN; 10 ft

DISC: 1_MRI-2

480V, F: 1_3MHB

(1) #1 THWN; 40 ft

PNL: 1_3MHB

480V, 250A

200k SCAR

F: 1_ALT T-U3 3SB7 ATS-E

(1) #2 THWN; 120 ft

F: 1_3MHA

(1) #1 THWN; 45 ft

PNL: 1_3MHA

480V, 250A

200k SCAR

F: 1_XFMR M-3

(1) #4/0 THWN; 30 ft

S

P

XF: 1_T-M3

150kVA; 3.46%Z

Pri: 480V

Sec: 208V

F: 1_SWBD D3ML

(2) #350 THWN; 15 ft

SWBD: 1_D3ML

208V, 600A

65k SCAR

FU: 1_3MLD

GOULD SHAWMUT (A2D)

200 A

FU: 1_UPS SB5

BUSSMANN (LPN-RK-150SP)

150 A

FU: 1_3MLC

BUSSMANN (LPN-RK-100SP)

100 A

FU: 1_3MLB

BUSSMANN (KTN-R)

175 A

FU: 1_3MLA

BUSSMANN (KTN-R)

175 A

F: 1_3MLD

(1) #3/0 THWN; 10 ft

PNL: 1_3MLD

208V, 225A

65k SCAR

F: 1_UPS SB5

(1) #1/0 THWN; 40 ft

F: 1_3MLC

(1) #2 THWN; 30 ft

PNL: 1_3MLC

208V, 225A

10k SCAR

F: 1_3MLB

(1) #2/0 THWN; 30 ft

PNL: 1_3MLB

208V, 225A

10k SCAR

F: 1_3MLA

(1) #2/0 THWN; 25 ft

PNL: 1_3MLA

208V, 225A

10k SCAR

CB: 1_MRI HU-1

CUTLER-HAMMER (EB)

15 A

F: 1_MRI HU-1

(1) #12 THWN; 30 ft

DISC: 1_HU-1

208V, FU: 1_HU-1

LITTELFUSE (FLNR)

10 A

F: 1_HU-1

(1) #12 THWN; 1 ft

CB: 1_EH-1 Rm 3E-26 IGS

GE (THQB)

30 A

F: 1_EH-1 Rm 3E-26 IGS

(1) #10 THWN; 1 ft

CB: 1_RM 3A-41

CUTLER-HAMMER (EB)

50 A

CB: 1_LASER A-34

CUTLER-HAMMER (EB)

30 A

F: 1_RM 3A-41

(1) #6 THWN; 1 ft

F: 1_LASER A-34

(1) #10 THWN; 1 ft

FU: 1_MRI-2

FERRAZ SHAWMUT (TRS)

125 A

F: 1_MRI-2

(1) #2/0 THWN; 1 ft

CB: 1_AH-1

CUTLER-HAMMER (FD)

20 A

CB: 1_UNK 2-4-6 4TH OR PH

CUTLER-HAMMER (FD)

80 A

CB: 1_UNK 1-3-5

CUTLER-HAMMER (FD)

20 A

F: 1_AH-1

(1) #10 THWN; 35 ft

DISC: 1_AH-1

480V, F: 1_UNK 2-4-6 4TH OR PH

(1) #4 THWN; 45 ft

DISC: 1_Backup Chiller 480V, F: 1_UNK 1-3-5

(1) #12 THWN; 1 ft

FU: 1_AH-1 SB5 3RDFLR

FERRAZ SHAWMUT (TRS)

30 A

F: 1_AH-1 SB5 3RDFLR

(1) #10 THWN; 1 ft

FU: 1_Backup Chiller

FERRAZ SHAWMUT (TRS)

90 A

F: 1_Backup Chiller

(1) #4 THWN; 15 ft

CB: 1_UNK 19-21-23

CUTLER-HAMMER (FD)

40 A

CB: 1_3MLD XFMR

CUTLER-HAMMER (EHD)

30 A

CB: 1_T-MHA-1

CUTLER-HAMMER (HFD)

50 A

F: 1_UNK 19-21-23

(1) #8 THWN; 1 ft

F: 1_3MLD XFMR

(1) #10 THWN; 45 ft

F: 1_T-MHA-1

(1) #6 THWN; 40 ft

S

P

XF: 1_T-3MLD

15kVA; 3.24%Z

Pri: 480V

Sec: 208V

F: 1_Pnl 3MLD-2

(1) #6 THWN; 10 ft

CB: 1_3MLD-2 Main

CUTLER-HAMMER (BAB)

50 A

PNL: 1_3MLD-2

208V, 50A

200k SCAR

CB: 1_AH-13 SF

CUTLER-HAMMER (HFD)

100 A

CB: 1_AH-21 SF

CUTLER-HAMMER (HFD)

100 A

CB: 1_R-4 RF

CUTLER-HAMMER (HFD)

15 A

MCP: 1_S-5 Tunnel SF

CUTLER-HAMMER (HMCP)

7 A, 7 A Plug

CB: 1_AH-29 SF

CUTLER-HAMMER (HFD)

100 A

CB: 1_R-25 RF

CUTLER-HAMMER (HFD)

15 A

CB: 1_R-11 RF

CUTLER-HAMMER (HFD)

15 A

CB: 1_R-16 RF

CUTLER-HAMMER (HFD)

15 A

CB: 1_SUMP PUMP PP-14 PP-15

CUTLER-HAMMER (HFD)

15 A

CB: 1_AH-5 SF

CUTLER-HAMMER (HFD)

60 A

F: 1_AH-13 SF

(1) #6 THWN; 50 ft

F: 1_AH-21 SF

(1) #1 THWN; 65 ft

F: 1_R-4 RF

(1) #12 THWN; 45 ft

F: 1_S-5 Tunnel SF

(1) #10 THWN; 1 ft

F: 1_AH-29 SF

(1) #1 THWN; 80 ft

F: 1_R-25 RF

(1) #10 THWN; 85 ft

F: 1_R-11 RF

(1) #12 THWN; 50 ft

F: 1_R-16 RF

(1) #4 THWN; 60 ft

F: 1_SUMP PUMP PP-14 PP-15

(1) #10 THWN; 1 ft

F: 1_AH-5 SF

(1) #4 THWN; 35 ft

CB: 1_MP-CT

SIEMENS (HJD6-A)

250 A, 250 A Plug

CB: 1_PNL MP-GAMMA RM 4E-30

SIEMENS (HEB)

100 A

F: 1_MP-CT

(1) #4/0 THWN; 20 ft

CB: 1_MP CT Main

SIEMENS (FXD6)

250 A, 250 A Plug

PNL: 1_MP CT

480V, 250A

200k SCAR

F: 1_PNL MP-GAMMA RM 4E-30

(1) #2 THWN; 40 ft

CB: 1_MP GAMMA Main

SIEMENS (ED4)

100 A

PNL: 1_MP GAMMA

480V, 125A

200k SCAR

CB: 1_ATS-EM N

SQUARE D (LX / LXI)

250 A, 150 A Plug

F: 1_ATS-EM N

(1) #1/0 THWN; 40 ft

CB: 1_Gantry

SIEMENS (ED4)

80 A

F: 1_Gantry

(1) #3 THWN; 1 ft

CB: 1_Pwr Cabinet B

SIEMENS (ED4)

125 A

CB: 1_Pwr Cabinet A

SIEMENS (ED4)

125 A

CB: 1_Surge Suppresor

SIEMENS (ED4)

60 A

CB: 1_Heat Exchanger

SIEMENS (ED4)

30 A

F: 1_Pwr Cabinet B

(1) #1 THWN; 1 ft

F: 1_Pwr Cabinet A

(1) #1 THWN; 1 ft

F: 1_Surge Suppresor

(1) #6 THWN; 1 ft

F: 1_Heat Exchanger

(1) #6 THWN; 1 ft

PNL: 1_3MHA-1

208V, 100A

10k SCAR

CB: 1_3MHA-1 Main

GE (TED)

40 A, 40 A Plug

S

P

XF: 1_3MHA-1

15kVA; 3.70%Z

Pri: 480V

Sec: 208V

CB: 1_3MHA-1 Sec

GE (THQL)

50 A, 50 A Plug

UPS: 1_SB5

VFD: AH-29 SF

MTR: 1_AH-29 SF

1 @ 50 hp

VFD: AH-29 RF

MTR: 1_AH-29 RF

1 @ 15 hp

VFD: 1_Elev P-2

FU: 1_Elev P-2 VFD

LITTELFUSE (FLSR)

60 A

MTR: 1_Elev P-2

1 @ 40 hp

VFD: 1_Elev P-3

MTR: 1_Elev P-3

1 @ 40 hp

VFD: 1_Elev P-1

FU: 1_Elev P-1 VFD

LITTELFUSE (FLSR)

60 A

MTR: 1_Elev P-1

1 @ 40 hp

BUS: 1_Backup Chiller 480V, MTR: 1_BU Chiller Comp

2 @ 5 hp

MTR: 1_BU Chiller Pump

2 @ 2 hp

MTR: 1_BU Chiller Fans

2 @ 1.5 hp

MTR: 1_BU Chiller Small Fans

2 @ 0.5 hp

VFD: 1_AH-5 SF

MTR: 1_AH-5 SF

1 @ 40 hp

VFD: 1_AH-5 RF

MTR: 1_AH-5 RF

1 @ 5 hp

VFD: AH-13 SF

MTR: 1_AH-13 SF

1 @ 30 hp

VFD: AH-13 RF

MTR: 1_AH-13 RF

1 @ 5 hp

VFD: AH-21 SF

MTR: 1_AH-21 SF

1 @ 50 hp

VFD: AH-21 RF

MTR: 1_AH-21 RF

1 @ 20 hp

BUS: 1_US-3A West Sec 480V, S

P

XF: 1_US-3A West

1500kVA; 5.79%Z

Pri: 12000V

Sec: 480V

BUS: 1_UB-3A West Pri 12000V, BUS: 1_SW US-3A West 12000V, FU: 1_US-3A West

WESTINGHOUSE (125 X)

125 A

BUS: 1_US-3A West

SW: 1_US-3A West-1

F: 1_A-3-2

(1) #350 133%; 30 ft

UTIL: 1_FDR A-3-2

Isc 3P 0 MVA

Isc SLG 0 MVA

BUS: 1_FDR A-3-2

12000V, Open SW: 1_US-3A West-2

F: 1_B-3-2

(1) #350 133%; 30 ft

UTIL: 1_FDR B-3-2

Isc 3P 0 MVA

Isc SLG 0 MVA

BUS: 1_FDR B-3-2

12000V, F: 1_TIE

(1) #2000 Class B; 25 ft

F: 1_D4MH

(2) #250 THWN; 90 ft

F: 1_A-3-6

(1) #350 133%; 30 ft

F: 1_B-3-6

(1) #350 133%; 30 ft

E-111 - SB 5-7.dgn 3/30/2018 8:34:20 AM