Short Circuit Study - Op Pharmacy.pdf

PDF 1 MB Posted

Attached to
H959--ARC FLASH ANALYSIS - POP (09/01/2024 - 08/31/2025) Federal contract opportunity
Solicitation number
36C26224Q1724
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 22

About this file

This document is a Combined Synopsis/Solicitation for an Arc Flash Analysis service contract at the VA Loma Linda Healthcare System. The VA is seeking to purchase an Arc Flash Analysis to be in compliance with NFPA, IEEE, and Joint Commission requirements for regular inspections of electrical equipment. The contractor shall provide all labor, materials, tools, and software required to perform the Arc Flash Hazard Analysis, determine Arc Flash boundaries and incident energy, and place Arc Flash warning labels on evaluated equipment. The contractor must have an OSHA 30-hour safety card, electrical C-10 license, and NFPA/NICET certification. The contract period is 09/01/2024 - 08/31/2025 and is set-aside for 100% Service-Disabled Veteran-Owned Small Businesses. Quotes are due by 08/23/2024 and will be evaluated on price and past performance, with price being more important.

View the file

Other files for this federal contract opportunity

Other files attached to H959--ARC FLASH ANALYSIS - POP (09/01/2024 - 08/31/2025), newest first.
File Type Posted
Tbl 3_3 Equip Eval.pdf PDF
lf_calc format.pdf PDF
input_data format.pdf PDF
EYE Clinic One Line Drawings.docx DOCX document
E-112.pdf PDF
E-110.pdf PDF
E-108.pdf PDF
E-104.pdf PDF
CANCER CENTER SIGNAL LINE DRAWINGS 2017.png PNG image
Arc Flash Study 2016 Schneider Full Facility.pdf PDF
20110460 - Sheet - E-611 - SINGLE LINE DIAGRAM OP Pharmacy.pdf PDF
116801E5.1.5.pdf PDF
022712 SCC and OCPD Coordination Study - VA Loma Linda.pdf PDF
Tbl 4_1 MV Prot Dev Settingsa.pdf PDF
Tbl 3-1_2 Prot Dev Eval.pdf PDF
sc_calc format.pdf PDF
MV Coordination Descrip Tbl.pdf PDF
Loma Linda MV TCCs.pdf PDF
E-109.pdf PDF
E-103.pdf PDF
CLC ReHab SIGNAL LINE DRAWINGS.png PNG image
CLC PC SIGNAL LINE DRAWINGS.png PNG image
VALL Electrical Single Line Diagrams.pdf PDF
Loma Linda-60pc.pdf PDF
E601 BEHAVIORAL HEALTH BUILDING.pdf PDF
E-115.pdf PDF
E-114.pdf PDF
E-113.pdf PDF
E-101.pdf PDF
Cover.pdf PDF
116801E5.1.12.pdf PDF
116801E5.1.11.pdf PDF
116801E5.1.10.pdf PDF
116801E5.1.8.pdf PDF
116801E5.1.2.pdf PDF
116801E5.1.1.pdf PDF
Tbl 6-1_2_Arc_Flash.pdf PDF
E-111.pdf PDF
E-107.pdf PDF
E-106.pdf PDF
E-105.pdf PDF
E-102.pdf PDF
E1.1 AUDIOLOGY.pdf PDF
E-001.pdf PDF
Arc Flash Study CLC Reb.pdf PDF
Arc Flash Study CLC Ph 2.pdf PDF
116801E5.1.9.pdf PDF
116801E5.1.7.pdf PDF
116801E5.1.6.pdf PDF
36C26224Q1724.docx DOCX document
Show all 50

H959--ARC FLASH ANALYSIS - POP (09/01/2024 - 08/31/2025) has more files on GovTribe.

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Department of Veterans Affairs Loma Linda VA Medical Center 11201 Benton Street Loma Linda, CA 92357

APPROVED APPROVED AS NOTED

REJECTED REVISE AND RESUBMIT

SUBMIT SPECIFIED ITEM SEE COMMENT SHEET

REFERENCE: OP PHARMACY SUBMITTAL: 61 Coordination Study Results Approved

Date

This review is only for general conformance with the design concept of the project and general compliance with the information in the Contract Documents. Corrections or comments made on the shop drawings during this review do not relieve contractor from compliance with the requirements of the plans and specifciations. Approval of a specific item shall not include approval of an assembly of which the item is a component. Contractor is responsible for: dimension to be confrimed and correlated at the jobsite; information that pertains solely to the fabrication processes or to the means, methods, techniques, sequences and procedures of construction; coordination of the work of all trades; and for performing all work in a safe and satisfactory manner.

2/27/2015 Project Engineer

Submittal Transmittal

EwingCole

PROJECT VA-LL OP PHARMACY

20110460

DATE SENT 2/27/2015

SUBJECT 61. Coordination Study Results SUBMITTAL ID E0018

TYPE Submittal TRANSMITTAL ID 00208

PURPOSE Reviewed VIA Info Exchange

SPEC SECTION: 26 00 00

FROM

NAME COMPANY EMAIL PHONE

ESubmittals EwingCole ESubmittals@ewingcole.c om

TO

NAME COMPANY EMAIL PHONE

Rosie Soriano CalAmerica rosie@cal-am.net 951-784-4245

James Barber Veterans Administration James.Barber@va.gov 9095836826

Kevin Estrada Veterans Administration kevin.estrada@va.gov 909.583.6807

Ruby Carr EwingCole rcarr@ewingcole.com 949.417.7593

Shawn Steib CalAmerica shawn@cal-am.net (951) 784-

Terry Hinkley CalAmerica terry@cal-am.net Vincent Jackson EwingCole vjackson@ewingcole.com 949.417.6498

CONTENTS

QUANTITY: 1 DATED: 2/24/2015 NUMBER: cuts

DESCRIPTION:

61. Coordination Study Results.pdf

ACTION: For Review

REMARKS:

QUANTITY: 1 DATED: 2/27/2015 NUMBER:

DESCRIPTION:

61. Coordination Study Results - RESPONSE 2-27-15.pdf

ACTION: Reviewed

REMARKS:

Submittal Transmittal

DATE: 2/27/2015

ID: 00208

COPIES:

Kyle Kavanaugh

SUBMITTAL ACTION

SUBMISSION FIRST SECOND THIRD

REVIEWED

REVIEWED AS NOTED

REVIEWED AS NOTED RESUBMIT

REJECTED

RESUBMIT

SEE TRANSMITTAL FOR INSTRUCTIONS

This submittal has been reviewed only for conformance with the design concept of the Project and compliance with the Information given in the Contract Documents.

It is the Contractor’s contractual duty to review and act upon submittals, prior to their submission to verify that all requirements of the Contract Documents have been met or if they have not been met, to notify the Architect in writing. By the submission of this submittal to the Architect, it is assumed the Contractor has fulfiled these contractual duties. Review of this submittal by Architect does not relieve the Contractor of the duty to meet the requirements of the Contract Documents and the applicable building codes.

Any comments noted or corrections requested are for clarification of the general character of the work. Correctness of details, measurements, quantities, conformity with Contract Documents, techniques of construction and coordination with other trades shall remain the complete responsibility of the General/Prime Contractor.

BY: ------- DATE: ------

EWINGCOLE

15231 Laguna Canyon Road, Suite 200, Irvine, CA 92618

ARCHITECTS ENGINEERS INTERIOR DESIGNERS PLANNERS

Coordination Study Results Submittal Response 2/27/2015

K.K. 2/27/2015

Rock Electric Inc. 7950 Silverton Ave., Suite 211 San Diego, CA 92126 Ph: (858)566-4449 Fax: (858)536-8931

ROCK ELECTRIC INC.

Lic. No. 646958

VA Loma Linda Healthcare System “OP Pharmacy Building”

Contract VA262-14-C-0024

Engine Generators Specification Section 265100

Response to Engineers comments dated 2/2/15

Short Circuit/Coordination Power Study

General Contractor Cal American Construction, Inc.

2023 Chicago Ave., Suite B-8 Riverside, CA 92507

February 24, 2015

VA Loma Linda Pharmacy Building

Preliminary Short Circuit Study

Prepared For:

Rock Electric, Inc.

7950 Silverton Avenue, Suite 211

San Diego, CA 92126

Prepared By:

February 23, 2015

February 23, 2015

Preliminary Short Circuit Study‐ VA Loma Linda Pharmacy

MTA was contracted by Rock Electric to perform a Preliminary Short Circuit Study for the VA Loma Linda

Pharmacy Building. This Preliminary Short Circuit Study was generated using estimated feeder lengths that were provided to MTA. The Wire Sizes used for this study were taken off of the Engineer of

Record’s Singleline Diagram. It should be noted that once the actual feeder lengths are installed in the field, this study will be updated and re run which may change the Available short circuit current at each piece of electrical equipment. It is highly recommended that the EOR review the available short circuit current values provided in this study for each Distribution and Panel board.

MTA found that the feeder sizes shown on the singleline for the UPS Input and Bypass feeds were undersized for the breaker size shown on the Singleline. MTA assumed that these feeders would be

Sized at #2 AWG since the breakers were to be rated at 90Amps the #2 wire was used for this preliminary short circuit study. If this #2 AWG wire is not correct please let us know and we will update this preliminary Short Circuit Study to the correct size.

Since the 12KV contribution was unknown MTA has used 25,000A (3phase) and 25,000A (Line to

Ground) at 12,470Volts. This value is SCE maximum published 12KV contribution.

Should you have any questions or concerns about this study please do not hesitate to contact me.

Thank You, Mark Thomas, PE

President

MTA Electrical Engineers

Feb 23, 2015 16:15:28 Page 1

ALL INFORMATION PRESENTED IS FOR REVIEW, APPROVAL

INTERPRETATION AND APPLICATION BY A REGISTERED ENGINEER ONLY

SKM DISCLAIMS ANY RESPONSIBILITY AND LIABILITY RESULTING

FROM THE USE AND INTERPRETATION OF THIS SOFTWARE.

SKM POWER*TOOLS FOR WINDOWS

INPUT DATA REPORT

COPYRIGHT SKM SYSTEMS ANALYSIS, INC. 1995-2014

ALL PU VALUES ARE EXPRESSED ON A 100 MVA BASE.

Feb 23, 2015 16:15:28 Page 2

FEEDER INPUT DATA

CABLE FEEDER FROM FEEDER TO QTY VOLTS LENGTH FEEDER

NAME NAME NAME /PH L-L SIZE TYPE

FDR-1ER1A T-EL-A1A 1ER1A 1 208 20.0 FEET 1/0 Copper Duct Material: Magnetic Insulation Type: PVC Insulation Class: THWN +/- Impedance: 0.1280 + J 0.0540 Ohms/1000 ft 5.92 + J 2.50 PU Z0 Impedance: 0.4034 + J 0.1329 Ohms/1000 ft 18.65 + J 6.14 PU

FDR-1ER1B 1ER1A 1ER1B 1 208 10.0 FEET 2 Copper Duct Material: Magnetic Insulation Type: PVC Insulation Class: THWN +/- Impedance: 0.2020 + J 0.0585 Ohms/1000 ft 4.67 + J 1.35 PU Z0 Impedance: 0.6366 + J 0.1440 Ohms/1000 ft 14.71 + J 3.33 PU

FDR-ATS-E MSB ATS-E 1 480 70.0 FEET 3/0 Copper Duct Material: Magnetic Insulation Type: PVC Insulation Class: THWN +/- Impedance: 0.0805 + J 0.0519 Ohms/1000 ft 2.45 + J 1.58 PU Z0 Impedance: 0.2537 + J 0.1278 Ohms/1000 ft 7.71 + J 3.88 PU

FDR-ATSE-EM EMBD BUS-0011 1 480 60.0 FEET 3/0 Copper Duct Material: Magnetic Insulation Type: PVC Insulation Class: THWN +/- Impedance: 0.0805 + J 0.0519 Ohms/1000 ft 2.10 + J 1.35 PU Z0 Impedance: 0.2537 + J 0.1278 Ohms/1000 ft 6.61 + J 3.33 PU

FDR-ATS-ELS MSB ATS-ELS 1 480 70.0 FEET 6 Copper Duct Material: Magnetic Insulation Type: PVC Insulation Class: THWN +/- Impedance: 0.5100 + J 0.0685 Ohms/1000 ft 15.49 + J 2.08 PU Z0 Impedance: 1.61 + J 0.1687 Ohms/1000 ft 48.83 + J 5.13 PU

FDR-ATSELS-EM EMBD BUS-0010 1 480 20.0 FEET 6 Copper Duct Material: Magnetic Insulation Type: PVC Insulation Class: THWN +/- Impedance: 0.5100 + J 0.0685 Ohms/1000 ft 4.43 + J 0.5946 PU Z0 Impedance: 1.61 + J 0.1687 Ohms/1000 ft 13.95 + J 1.46 PU

FDR-DPA1 T-DPA1 DPA1 1 208 20.0 FEET 500 Copper Duct Material: Magnetic Insulation Type: PVC Insulation Class: THWN +/- Impedance: 0.0294 + J 0.0466 Ohms/1000 ft 1.36 + J 2.15 PU Z0 Impedance: 0.0926 + J 0.1147 Ohms/1000 ft 4.28 + J 5.30 PU

FDR-EL1A BUS-0015 EL1A 1 480 70.0 FEET 3/0 Copper Duct Material: Magnetic Insulation Type: PVC Insulation Class: THWN +/- Impedance: 0.0805 + J 0.0519 Ohms/1000 ft 2.45 + J 1.58 PU Z0 Impedance: 0.2537 + J 0.1278 Ohms/1000 ft 7.71 + J 3.88 PU

FDR-ELEV1 MSB DISCO-ELEV1 1 480 50.0 FEET 6 Copper Duct Material: Magnetic Insulation Type: PVC Insulation Class: THWN +/- Impedance: 0.5100 + J 0.0685 Ohms/1000 ft 11.07 + J 1.49 PU Z0 Impedance: 1.61 + J 0.1687 Ohms/1000 ft 34.88 + J 3.66 PU

Feb 23, 2015 16:15:28 Page 3

CABLE FEEDER FROM FEEDER TO QTY VOLTS LENGTH FEEDER

NAME NAME NAME /PH L-L SIZE TYPE

FDR-ELEV2 MSB DISCO-ELEV2 1 480 190.0 FEET 8 Copper Duct Material: Magnetic Insulation Type: PVC Insulation Class: THWN +/- Impedance: 0.8110 + J 0.0754 Ohms/1000 ft 66.88 + J 6.22 PU Z0 Impedance: 2.56 + J 0.1856 Ohms/1000 ft 210.77 + J 15.31 PU

FDR-ELS2 BUS-0014 ELS2 1 480 110.0 FEET 6 Copper Duct Material: Magnetic Insulation Type: PVC Insulation Class: THWN +/- Impedance: 0.5100 + J 0.0685 Ohms/1000 ft 24.35 + J 3.27 PU Z0 Impedance: 1.61 + J 0.1687 Ohms/1000 ft 76.73 + J 8.05 PU

FDR-EMDB GEN BUS EMBD 1 480 20.0 FEET 500 Copper Duct Material: Magnetic Insulation Type: PVC Insulation Class: THWN +/- Impedance: 0.0294 + J 0.0466 Ohms/1000 ft 0.2552 + J 0.4045 PU Z0 Impedance: 0.0926 + J 0.1147 Ohms/1000 ft 0.8038 + J 0.9957 PU

FDR-EX-MAN US6A EX MANHOLE 1 12470 130.0 FEET 500 Copper Duct Material: Non-Magnetic Insulation Type: EPR Insulation Class: MV +/- Impedance: 0.0284 + J 0.0421 Ohms/1000 ft 0.0024 + J 0.0035 PU Z0 Impedance: 0.0451 + J 0.1128 Ohms/1000 ft 0.0038 + J 0.0094 PU

FDR-HWP1 DPA1 DISCO-HWP1 1 208 75.0 FEET 12 Copper Duct Material: Magnetic Insulation Type: PVC Insulation Class: THWN +/- Impedance: 1.87 + J 0.0910 Ohms/1000 ft 324.17 + J 15.78 PU Z0 Impedance: 5.89 + J 0.2241 Ohms/1000 ft 1021.65 + J 38.85 PU

FDR-HWP2 DPA1 DISCO-HWP2 1 208 75.0 FEET 12 Copper Duct Material: Magnetic Insulation Type: PVC Insulation Class: THWN +/- Impedance: 1.87 + J 0.0910 Ohms/1000 ft 324.17 + J 15.78 PU Z0 Impedance: 5.89 + J 0.2241 Ohms/1000 ft 1021.65 + J 38.85 PU

FDR-L1A MSB L1A 1 480 30.0 FEET 250 Copper Duct Material: Magnetic Insulation Type: PVC Insulation Class: THWN +/- Impedance: 0.0552 + J 0.0495 Ohms/1000 ft 0.7188 + J 0.6445 PU Z0 Impedance: 0.1739 + J 0.1219 Ohms/1000 ft 2.26 + J 1.59 PU

FDR-LCP L1A LCP 1 480 15.0 FEET 12 Copper Duct Material: Magnetic Insulation Type: PVC Insulation Class: THWN +/- Impedance: 1.87 + J 0.0910 Ohms/1000 ft 12.17 + J 0.5924 PU Z0 Impedance: 5.89 + J 0.2241 Ohms/1000 ft 38.37 + J 1.46 PU

FDR-MSB T-MSB MSB 3 480 70.0 FEET 500 Copper Duct Material: Non-Magnetic Insulation Type: PVC Insulation Class: THWN +/- Impedance: 0.0276 + J 0.0373 Ohms/1000 ft 0.2795 + J 0.3777 PU Z0 Impedance: 0.0438 + J 0.0999 Ohms/1000 ft 0.4436 + J 1.01 PU

Feb 23, 2015 16:15:28 Page 4

CABLE FEEDER FROM FEEDER TO QTY VOLTS LENGTH FEEDER

NAME NAME NAME /PH L-L SIZE TYPE

FDR-NEW-MAN EX MANHOLE NEW MANHOLE 1 12470 430.0 FEET 500 Copper Duct Material: Non-Magnetic Insulation Type: EPR Insulation Class: MV +/- Impedance: 0.0284 + J 0.0421 Ohms/1000 ft 0.0079 + J 0.0116 PU Z0 Impedance: 0.0451 + J 0.1128 Ohms/1000 ft 0.0125 + J 0.0312 PU

FDR-PV-INV MSB PV-INV 1 480 70.0 FEET 6 Copper Duct Material: Magnetic Insulation Type: PVC Insulation Class: THWN +/- Impedance: 0.5100 + J 0.0685 Ohms/1000 ft 15.49 + J 2.08 PU Z0 Impedance: 1.61 + J 0.1687 Ohms/1000 ft 48.83 + J 5.13 PU

FDR-R1A DPA1 R1A 1 208 15.0 FEET 2 Copper Duct Material: Magnetic Insulation Type: PVC Insulation Class: THWN +/- Impedance: 0.2020 + J 0.0585 Ohms/1000 ft 7.00 + J 2.03 PU Z0 Impedance: 0.6366 + J 0.1440 Ohms/1000 ft 22.07 + J 4.99 PU

FDR-R2A DPA1 R2A 1 208 45.0 FEET 2 Copper Duct Material: Magnetic Insulation Type: PVC Insulation Class: THWN +/- Impedance: 0.2020 + J 0.0585 Ohms/1000 ft 21.01 + J 6.08 PU Z0 Impedance: 0.6366 + J 0.1440 Ohms/1000 ft 66.21 + J 14.98 PU

FDR-R2B DPA1 R2B 1 208 45.0 FEET 2 Copper Duct Material: Magnetic Insulation Type: PVC Insulation Class: THWN +/- Impedance: 0.2020 + J 0.0585 Ohms/1000 ft 21.01 + J 6.08 PU Z0 Impedance: 0.6366 + J 0.1440 Ohms/1000 ft 66.21 + J 14.98 PU

FDR-TDPA1 MSB BUS-0023 1 480 30.0 FEET 2/0 Copper Duct Material: Magnetic Insulation Type: PVC Insulation Class: THWN +/- Impedance: 0.1020 + J 0.0533 Ohms/1000 ft 1.33 + J 0.6940 PU Z0 Impedance: 0.3214 + J 0.1312 Ohms/1000 ft 4.18 + J 1.71 PU

FDR-TELA1A EL1A BUS-0018 1 480 15.0 FEET 6 Copper Duct Material: Magnetic Insulation Type: PVC Insulation Class: THWN +/- Impedance: 0.5100 + J 0.0685 Ohms/1000 ft 3.32 + J 0.4460 PU Z0 Impedance: 1.61 + J 0.1687 Ohms/1000 ft 10.46 + J 1.10 PU

FDR-TMSB NEW MANHOLE BUS-0005 1 12470 105.0 FEET 500 Copper Duct Material: Non-Magnetic Insulation Type: EPR Insulation Class: MV +/- Impedance: 0.0284 + J 0.0421 Ohms/1000 ft 0.0019 + J 0.0028 PU Z0 Impedance: 0.0451 + J 0.1128 Ohms/1000 ft 0.0030 + J 0.0076 PU

FDR-UPS-A UPS-MBP UPS-A 1 208 30.0 FEET 2 Copper Duct Material: Magnetic Insulation Type: PVC Insulation Class: THWN +/- Impedance: 0.2020 + J 0.0585 Ohms/1000 ft 14.01 + J 4.06 PU Z0 Impedance: 0.6366 + J 0.1440 Ohms/1000 ft 44.14 + J 9.99 PU

Feb 23, 2015 16:15:28 Page 5

CABLE FEEDER FROM FEEDER TO QTY VOLTS LENGTH FEEDER

NAME NAME NAME /PH L-L SIZE TYPE

FDR-UPS-IN DPA1 UPS1 1 208 40.0 FEET 2 Copper Duct Material: Magnetic Insulation Type: PVC Insulation Class: THWN +/- Impedance: 0.2020 + J 0.0585 Ohms/1000 ft 18.68 + J 5.41 PU Z0 Impedance: 0.6366 + J 0.1440 Ohms/1000 ft 58.86 + J 13.31 PU

FDR-UPS-OUT UPS1 UPS-MBP 1 208 1.000 FEET 2 Copper Duct Material: Magnetic Insulation Type: PVC Insulation Class: THWN +/- Impedance: 0.2020 + J 0.0585 Ohms/1000 ft 0.4669 + J 0.1352 PU Z0 Impedance: 0.6366 + J 0.1440 Ohms/1000 ft 1.47 + J 0.3328 PU

Feb 23, 2015 16:15:28 Page 6

TRANSFORMER INPUT DATA

TRANSFORMER PRIMARY RECORD VOLTS * SECONDARY RECORD VOLTS FULL-LOAD NOMINAL

NAME NO NAME L-L NO NAME L-L KVA KVA

TDPA1 BUS-0023 D 480.00 T-DPA1 YG 208.00 112.50 112.50

Pos. Seq. Z%: 2.56 + J 3.69 (Zpu 22.76 + j 32.80 ) Shell Type Zero Seq. Z%: 2.56 + J 3.69 (Sec 22.76 + j 32.80 Pri Open) Taps Pri. 0.000 % Sec. 0.000 % Phase Shift (Pri. Leading Sec.): 30.00 Deg.

TELA1A BUS-0018 D 480.00 T-EL-A1A YG 208.00 45.00 45.00

Pos. Seq. Z%: 2.73 + J 1.97 (Zpu 60.67 + j 43.78 ) Shell Type Zero Seq. Z%: 2.73 + J 1.97 (Sec 60.67 + j 43.78 Pri Open) Taps Pri. 0.000 % Sec. 0.000 % Phase Shift (Pri. Leading Sec.): 30.00 Deg.

TMSB BUS-0005 D 12470.0 T-MSB YG 480.00 862.50 750.00

Pos. Seq. Z%: 1.08 + J 5.65 (Zpu 1.44 + j 7.53 ) Shell Type Zero Seq. Z%: 1.08 + J 5.65 (Sec 1.44 + j 7.53 Pri Open) Taps Pri. 0.000 % Sec. 0.000 % Phase Shift (Pri. Leading Sec.): 30.00 Deg.

Feb 23, 2015 16:15:28 Page 7

GENERATION DATA

BUS NAME GENERATION VOLT SIZE InitKW MaxKVAR TYPE GEN BUS GENERATOR 1 pu 150.00 KW 0.00000 0.00000 SB

US6A UTIL-0002 1 pu SB Three Phase Contribution: 25000.0 AMPS X/R : 8.00 Line to Earth Contribution: 25000.0 AMPS X/R : 8.00 Pos sequence impedance (100 MVA base) 0.0230 + J 0.1838 PU Zero sequence impedance (100 MVA base) 0.0230 + J 0.1838 PU

Feb 23, 2015 16:15:28 Page 8

MOTOR LOAD DATA

BUS NAME LOAD NAME VOLT SIZE # TYPE EFF PF

DISCO-ELEV1 ELEV-1 480 20.0* 1 HP KVA 0.93 0.80 LAG

DISCO-ELEV2 ELEV-2 480 15.0* 1 HP KVA 0.93 0.80 LAG

DISCO-HWP1 HWP1 208 1.0* 1 HP KVA 0.93 0.80 LAG

DISCO-HWP2 HWP2 208 1.0* 1 HP KVA 0.93 0.80 LAG

Feb 23, 2015 16:15:29

ALL INFORMATION PRESENTED IS FOR REVIEW, APPROVAL

INTERPRETATION AND APPLICATION BY A REGISTERED ENGINEER ONLY

SKM DISCLAIMS ANY RESPONSIBILITY AND LIABILITY RESULTING

FROM THE USE AND INTERPRETATION OF THIS SOFTWARE.

SKM POWER*TOOLS FOR WINDOWS

A_FAULT SHORT CIRCUIT ANALYSIS REPORT

COPYRIGHT SKM SYSTEMS ANALYSIS, INC. 1996-2014

Feb 23, 2015 16:15:29 THREE PHASE LOW VOLTAGE DUTY PAGE 1

T H R E E P H A S E F A U L T R E P O R T

(FOR APPLICATION OF LOW VOLTAGE BREAKERS)

PRE FAULT VOLTAGE: 1.0000

MODEL TRANSFORMER TAPS: NO

1ER1A 3P Duty: 2.894 KA AT -37.09 DEG ( 1.04 MVA) X/R: 0.76

VOLTAGE: 208. EQUIV. IMPEDANCE= 0.0331 + J 0.0250 OHMS

LOW VOLTAGE POWER CIRCUIT BREAKER 2.894 KA

MOLDED CASE CIRCUIT BREAKER < 10KA 2.894 KA

MOLDED CASE CIRCUIT BREAKER < 20KA 2.894 KA

MOLDED CASE CIRCUIT BREAKER > 20KA 2.894 KA

FDR-1ER1A T-EL-A1A 2.894 KA ANG: -37.09

1ER1B 3P Duty: 2.763 KA AT -36.10 DEG ( 1.00 MVA) X/R: 0.73

VOLTAGE: 208. EQUIV. IMPEDANCE= 0.0351 + J 0.0256 OHMS

LOW VOLTAGE POWER CIRCUIT BREAKER 2.763 KA

MOLDED CASE CIRCUIT BREAKER < 10KA 2.763 KA

MOLDED CASE CIRCUIT BREAKER < 20KA 2.763 KA

MOLDED CASE CIRCUIT BREAKER > 20KA 2.763 KA

FDR-1ER1B 1ER1A 2.763 KA ANG: -36.10

ATS-E 3P Duty: 11.569 KA AT -66.47 DEG ( 9.62 MVA) X/R: 2.30

VOLTAGE: 480. EQUIV. IMPEDANCE= 0.0096 + J 0.0220 OHMS

LOW VOLTAGE POWER CIRCUIT BREAKER 11.569 KA

MOLDED CASE CIRCUIT BREAKER < 20KA 11.569 KA

MOLDED CASE CIRCUIT BREAKER > 20KA 11.569 KA

FDR-ATS-E MSB 11.569 KA ANG: -66.47

ATS-ELS 3P Duty: 6.040 KA AT -30.26 DEG ( 5.02 MVA) X/R: 0.58

VOLTAGE: 480. EQUIV. IMPEDANCE= 0.0396 + J 0.0231 OHMS

LOW VOLTAGE POWER CIRCUIT BREAKER 6.040 KA

MOLDED CASE CIRCUIT BREAKER < 10KA 6.040 KA

MOLDED CASE CIRCUIT BREAKER < 20KA 6.040 KA

MOLDED CASE CIRCUIT BREAKER > 20KA 6.040 KA

FDR-ATS-ELS MSB 6.040 KA ANG: -30.26

DISCO-ELEV1 3P Duty: 7.645 KA AT -37.52 DEG ( 6.36 MVA) X/R: 0.86

VOLTAGE: 480. EQUIV. IMPEDANCE= 0.0287 + J 0.0221 OHMS

LOW VOLTAGE POWER CIRCUIT BREAKER 7.645 KA

MOLDED CASE CIRCUIT BREAKER < 10KA 7.645 KA

MOLDED CASE CIRCUIT BREAKER < 20KA 7.645 KA

MOLDED CASE CIRCUIT BREAKER > 20KA 7.645 KA

CONTRIBUTIONS: ELEV-1 0.157 KA ANG: -84.29

FDR-ELEV1 MSB 7.539 KA ANG: -36.65

DISCO-ELEV2 3P Duty: 1.756 KA AT -15.39 DEG ( 1.46 MVA) X/R: 0.34

VOLTAGE: 480. EQUIV. IMPEDANCE= 0.1522 + J 0.0419 OHMS

Feb 23, 2015 16:15:29 THREE PHASE LOW VOLTAGE DUTY PAGE 2

PRE FAULT VOLTAGE: 1.0000

MODEL TRANSFORMER TAPS: NO

LOW VOLTAGE POWER CIRCUIT BREAKER 1.756 KA

MOLDED CASE CIRCUIT BREAKER < 10KA 1.756 KA

MOLDED CASE CIRCUIT BREAKER < 20KA 1.756 KA

MOLDED CASE CIRCUIT BREAKER > 20KA 1.756 KA

CONTRIBUTIONS: ELEV-2 0.118 KA ANG: -84.29

FDR-ELEV2 MSB 1.717 KA ANG: -11.72

DISCO-HWP1 3P Duty: 0.784 KA AT -10.86 DEG ( 0.28 MVA) X/R: 0.21

VOLTAGE: 208. EQUIV. IMPEDANCE= 0.1504 + J 0.0288 OHMS

LOW VOLTAGE POWER CIRCUIT BREAKER 0.784 KA

MOLDED CASE CIRCUIT BREAKER < 10KA 0.784 KA

MOLDED CASE CIRCUIT BREAKER < 20KA 0.784 KA

MOLDED CASE CIRCUIT BREAKER > 20KA 0.784 KA

CONTRIBUTIONS: HWP1 0.018 KA ANG: -84.29

FDR-HWP1 DPA1 0.779 KA ANG: -9.58

DISCO-HWP2 3P Duty: 0.784 KA AT -10.86 DEG ( 0.28 MVA) X/R: 0.21

VOLTAGE: 208. EQUIV. IMPEDANCE= 0.1504 + J 0.0288 OHMS

LOW VOLTAGE POWER CIRCUIT BREAKER 0.784 KA

MOLDED CASE CIRCUIT BREAKER < 10KA 0.784 KA

MOLDED CASE CIRCUIT BREAKER < 20KA 0.784 KA

MOLDED CASE CIRCUIT BREAKER > 20KA 0.784 KA

CONTRIBUTIONS: HWP2 0.018 KA ANG: -84.29

FDR-HWP2 DPA1 0.779 KA ANG: -9.58

DPA1 3P Duty: 5.436 KA AT -58.26 DEG ( 1.96 MVA) X/R: 1.64

VOLTAGE: 208. EQUIV. IMPEDANCE= 0.0116 + J 0.0188 OHMS

LOW VOLTAGE POWER CIRCUIT BREAKER 5.436 KA

MOLDED CASE CIRCUIT BREAKER < 10KA 5.436 KA

MOLDED CASE CIRCUIT BREAKER < 20KA 5.436 KA

MOLDED CASE CIRCUIT BREAKER > 20KA 5.436 KA

FDR-HWP1 DISCO-HWP1 0.018 KA ANG: 96.91

FDR-HWP2 DISCO-HWP2 0.018 KA ANG: 96.91

FDR-DPA1 T-DPA1 5.403 KA ANG: -58.10

EL1A 3P Duty: 9.309 KA AT -59.30 DEG ( 7.74 MVA) X/R: 1.69

VOLTAGE: 480. EQUIV. IMPEDANCE= 0.0152 + J 0.0256 OHMS

LOW VOLTAGE POWER CIRCUIT BREAKER 9.309 KA

MOLDED CASE CIRCUIT BREAKER < 10KA 9.309 KA

MOLDED CASE CIRCUIT BREAKER < 20KA 9.309 KA

MOLDED CASE CIRCUIT BREAKER > 20KA 9.309 KA

FDR-EL1A BUS-0015 9.309 KA ANG: -59.30

ELS2 3P Duty: 2.757 KA AT -17.76 DEG ( 2.29 MVA) X/R: 0.32

Feb 23, 2015 16:15:29 THREE PHASE LOW VOLTAGE DUTY PAGE 3

PRE FAULT VOLTAGE: 1.0000

MODEL TRANSFORMER TAPS: NO

VOLTAGE: 480. EQUIV. IMPEDANCE= 0.0957 + J 0.0307 OHMS

LOW VOLTAGE POWER CIRCUIT BREAKER 2.757 KA

MOLDED CASE CIRCUIT BREAKER < 10KA 2.757 KA

MOLDED CASE CIRCUIT BREAKER < 20KA 2.757 KA

MOLDED CASE CIRCUIT BREAKER > 20KA 2.757 KA

FDR-ELS2 BUS-0014 2.757 KA ANG: -17.76

EMBD 3P Duty: 1.494 KA AT -86.97 DEG ( 1.24 MVA) X/R: 18.90

VOLTAGE: 480. EQUIV. IMPEDANCE= 0.0098 + J 0.1853 OHMS

LOW VOLTAGE POWER CIRCUIT BREAKER 1.702 KA

MOLDED CASE CIRCUIT BREAKER < 10KA 2.372 KA

MOLDED CASE CIRCUIT BREAKER < 20KA 2.010 KA

MOLDED CASE CIRCUIT BREAKER > 20KA 1.807 KA

FDR-EMDB GEN BUS 1.494 KA ANG: -86.97

EX MANHOLE 3P Duty: 24.509 KA AT -82.29 DEG ( 529.35 MVA) X/R: 7.39

VOLTAGE: 12470. EQUIV. IMPEDANCE= 0.0394 + J 0.2911 OHMS

FDR-EX-MAN US6A 24.498 KA ANG: -82.29

FDR-NEW-MAN NEW MANHOLE 0.011 KA ANG: -262.22

GEN BUS 3P Duty: 1.502 KA AT -87.14 DEG ( 1.25 MVA) X/R: 20.00

VOLTAGE: 480. EQUIV. IMPEDANCE= 0.0092 + J 0.1843 OHMS

LOW VOLTAGE POWER CIRCUIT BREAKER 1.718 KA

MOLDED CASE CIRCUIT BREAKER < 10KA 2.395 KA

MOLDED CASE CIRCUIT BREAKER < 20KA 2.029 KA

MOLDED CASE CIRCUIT BREAKER > 20KA 1.824 KA

CONTRIBUTIONS: GENERATOR 1.502 KA ANG: -87.14

L1A 3P Duty: 13.461 KA AT -74.26 DEG ( 11.19 MVA) X/R: 3.56

VOLTAGE: 480. EQUIV. IMPEDANCE= 0.0056 + J 0.0198 OHMS

LOW VOLTAGE POWER CIRCUIT BREAKER 13.461 KA

MOLDED CASE CIRCUIT BREAKER < 20KA 13.867 KA

MOLDED CASE CIRCUIT BREAKER > 20KA 13.461 KA

FDR-L1A MSB 13.461 KA ANG: -74.26

LCP 3P Duty: 6.972 KA AT -32.20 DEG ( 5.80 MVA) X/R: 0.63

VOLTAGE: 480. EQUIV. IMPEDANCE= 0.0336 + J 0.0212 OHMS

LOW VOLTAGE POWER CIRCUIT BREAKER 6.972 KA

MOLDED CASE CIRCUIT BREAKER < 10KA 6.972 KA

MOLDED CASE CIRCUIT BREAKER < 20KA 6.972 KA

MOLDED CASE CIRCUIT BREAKER > 20KA 6.972 KA

FDR-LCP L1A 6.972 KA ANG: -32.20

MSB 3P Duty: 14.783 KA AT -77.90 DEG ( 12.29 MVA) X/R: 4.69

Feb 23, 2015 16:15:29 THREE PHASE LOW VOLTAGE DUTY PAGE 4

PRE FAULT VOLTAGE: 1.0000

MODEL TRANSFORMER TAPS: NO

VOLTAGE: 480. EQUIV. IMPEDANCE= 0.0039 + J 0.0183 OHMS

LOW VOLTAGE POWER CIRCUIT BREAKER 14.783 KA

MOLDED CASE CIRCUIT BREAKER < 20KA 16.284 KA

MOLDED CASE CIRCUIT BREAKER > 20KA 14.783 KA

FDR-ELEV2 DISCO-ELEV2 0.116 KA ANG: 99.35

FDR-ELEV1 DISCO-ELEV1 0.156 KA ANG: 96.52

FDR-MSB T-MSB 14.496 KA ANG: -77.81

FDR-TDPA1 BUS-0023 0.016 KA ANG: 97.06

NEW MANHOLE 3P Duty: 22.968 KA AT -80.53 DEG ( 496.07 MVA) X/R: 5.99

VOLTAGE: 12470. EQUIV. IMPEDANCE= 0.0516 + J 0.3092 OHMS

FDR-NEW-MAN EX MANHOLE 22.957 KA ANG: -80.53

FDR-TMSB BUS-0005 0.011 KA ANG: 97.78

PV-INV 3P Duty: 6.040 KA AT -30.26 DEG ( 5.02 MVA) X/R: 0.58

VOLTAGE: 480. EQUIV. IMPEDANCE= 0.0396 + J 0.0231 OHMS

LOW VOLTAGE POWER CIRCUIT BREAKER 6.040 KA

MOLDED CASE CIRCUIT BREAKER < 10KA 6.040 KA

MOLDED CASE CIRCUIT BREAKER < 20KA 6.040 KA

MOLDED CASE CIRCUIT BREAKER > 20KA 6.040 KA

FDR-PV-INV MSB 6.040 KA ANG: -30.26

R1A 3P Duty: 4.897 KA AT -53.31 DEG ( 1.76 MVA) X/R: 1.36

VOLTAGE: 208. EQUIV. IMPEDANCE= 0.0147 + J 0.0197 OHMS

LOW VOLTAGE POWER CIRCUIT BREAKER 4.897 KA

MOLDED CASE CIRCUIT BREAKER < 10KA 4.897 KA

MOLDED CASE CIRCUIT BREAKER < 20KA 4.897 KA

MOLDED CASE CIRCUIT BREAKER > 20KA 4.897 KA

FDR-R1A DPA1 4.897 KA ANG: -53.31

R2A 3P Duty: 4.030 KA AT -45.96 DEG ( 1.45 MVA) X/R: 1.04

VOLTAGE: 208. EQUIV. IMPEDANCE= 0.0207 + J 0.0214 OHMS

LOW VOLTAGE POWER CIRCUIT BREAKER 4.030 KA

MOLDED CASE CIRCUIT BREAKER < 10KA 4.030 KA

MOLDED CASE CIRCUIT BREAKER < 20KA 4.030 KA

MOLDED CASE CIRCUIT BREAKER > 20KA 4.030 KA

FDR-R2A DPA1 4.030 KA ANG: -45.96

R2B 3P Duty: 4.030 KA AT -45.96 DEG ( 1.45 MVA) X/R: 1.04

VOLTAGE: 208. EQUIV. IMPEDANCE= 0.0207 + J 0.0214 OHMS

LOW VOLTAGE POWER CIRCUIT BREAKER 4.030 KA

MOLDED CASE CIRCUIT BREAKER < 10KA 4.030 KA

MOLDED CASE CIRCUIT BREAKER < 20KA 4.030 KA

MOLDED CASE CIRCUIT BREAKER > 20KA 4.030 KA

Feb 23, 2015 16:15:29 THREE PHASE LOW VOLTAGE DUTY PAGE 5

PRE FAULT VOLTAGE: 1.0000

MODEL TRANSFORMER TAPS: NO

CONTRIBUTIONS TO R2B (CONTINUED)

FDR-R2B DPA1 4.030 KA ANG: -45.96

T-DPA1 3P Duty: 5.718 KA AT -58.27 DEG ( 2.06 MVA) X/R: 1.64

VOLTAGE: 208. EQUIV. IMPEDANCE= 0.0110 + J 0.0179 OHMS

LOW VOLTAGE POWER CIRCUIT BREAKER 5.718 KA

MOLDED CASE CIRCUIT BREAKER < 10KA 5.718 KA

MOLDED CASE CIRCUIT BREAKER < 20KA 5.718 KA

MOLDED CASE CIRCUIT BREAKER > 20KA 5.718 KA

FDR-DPA1 DPA1 0.036 KA ANG: 96.91

TDPA1 BUS-0023 5.685 KA ANG: -238.11

T-EL-A1A 3P Duty: 3.095 KA AT -38.09 DEG ( 1.11 MVA) X/R: 0.78

VOLTAGE: 208. EQUIV. IMPEDANCE= 0.0305 + J 0.0239 OHMS

LOW VOLTAGE POWER CIRCUIT BREAKER 3.095 KA

MOLDED CASE CIRCUIT BREAKER < 10KA 3.095 KA

MOLDED CASE CIRCUIT BREAKER < 20KA 3.095 KA

MOLDED CASE CIRCUIT BREAKER > 20KA 3.095 KA

TELA1A BUS-0018 3.095 KA ANG: 141.91

T-MSB 3P Duty: 15.568 KA AT -79.28 DEG ( 12.94 MVA) X/R: 5.30

VOLTAGE: 480. EQUIV. IMPEDANCE= 0.0033 + J 0.0175 OHMS

LOW VOLTAGE POWER CIRCUIT BREAKER 15.568 KA

MOLDED CASE CIRCUIT BREAKER < 20KA 17.612 KA

MOLDED CASE CIRCUIT BREAKER > 20KA 15.832 KA

TMSB BUS-0005 15.281 KA ANG: -259.22

FDR-MSB MSB 0.287 KA ANG: 97.72

UPS-A 3P Duty: 3.466 KA AT -41.46 DEG ( 1.25 MVA) X/R: 0.89

VOLTAGE: 208. EQUIV. IMPEDANCE= 0.0260 + J 0.0229 OHMS

LOW VOLTAGE POWER CIRCUIT BREAKER 3.466 KA

MOLDED CASE CIRCUIT BREAKER < 10KA 3.466 KA

MOLDED CASE CIRCUIT BREAKER < 20KA 3.466 KA

MOLDED CASE CIRCUIT BREAKER > 20KA 3.466 KA

FDR-UPS-A UPS-MBP 3.466 KA ANG: -41.46

UPS-MBP 3P Duty: 4.131 KA AT -46.79 DEG ( 1.49 MVA) X/R: 1.07

VOLTAGE: 208. EQUIV. IMPEDANCE= 0.0199 + J 0.0212 OHMS

LOW VOLTAGE POWER CIRCUIT BREAKER 4.131 KA

MOLDED CASE CIRCUIT BREAKER < 10KA 4.131 KA

MOLDED CASE CIRCUIT BREAKER < 20KA 4.131 KA

MOLDED CASE CIRCUIT BREAKER > 20KA 4.131 KA

FDR-UPS-OUT UPS1 4.131 KA ANG: -46.79

Feb 23, 2015 16:15:29 THREE PHASE LOW VOLTAGE DUTY PAGE 6

PRE FAULT VOLTAGE: 1.0000

MODEL TRANSFORMER TAPS: NO

UPS1 3P Duty: 4.157 KA AT -47.00 DEG ( 1.50 MVA) X/R: 1.08

VOLTAGE: 208. EQUIV. IMPEDANCE= 0.0197 + J 0.0211 OHMS

LOW VOLTAGE POWER CIRCUIT BREAKER 4.157 KA

MOLDED CASE CIRCUIT BREAKER < 10KA 4.157 KA

MOLDED CASE CIRCUIT BREAKER < 20KA 4.157 KA

MOLDED CASE CIRCUIT BREAKER > 20KA 4.157 KA

FDR-UPS-IN DPA1 4.157 KA ANG: -47.00

US6A 3P Duty: 25.011 KA AT -82.87 DEG ( 540.20 MVA) X/R: 8.00

VOLTAGE: 12470. EQUIV. IMPEDANCE= 0.0357 + J 0.2856 OHMS

CONTRIBUTIONS: UTIL-0002 25.000 KA ANG: -82.87

FDR-EX-MAN EX MANHOLE 0.011 KA ANG: -262.22

Feb 23, 2015 16:15:29 UNBALANCED LOW VOLTAGE DUTY PAGE 1

U N B A L A N C E D F A U L T R E P O R T

PRE FAULT VOLTAGE: 1.0000

MODEL TRANSFORMER TAPS: NO

LOCATION FAULT KA X/R EQUIVALENT (PU) ASYM. KA AT 0.5 CYCLES

VOLTAGE DUTIES (RMS) FAULT IMPEDANCE * MAX. RMS AVG. RMS *

1ER1A 3P Duty: 2.894 1. Z1= 95.8993 2.895 2.895

SLG DUTY: 2.919 1. Z2= 95.8993 2.919

208. VOLTS LN/LN: 2.507 Z0= 93.7177

LN/LN/GND: 2.977 ( 2.941 GND RETURN KA)

1ER1B 3P Duty: 2.763 1. Z1= 100.4542 2.764 2.763

SLG DUTY: 2.699 1. Z2= 100.4542 2.699

208. VOLTS LN/LN: 2.393 Z0= 108.0604

LN/LN/GND: 2.820 ( 2.634 GND RETURN KA)

ATS-E 3P Duty: 11.569 2. Z1= 10.3972 12.299 11.937

SLG DUTY: 9.963 2. Z2= 10.3972 10.241

480. VOLTS LN/LN: 10.019 Z0= 15.6949

LN/LN/GND: 11.631 ( 8.685 GND RETURN KA)

ATS-ELS 3P Duty: 6.040 1. Z1= 19.9146 6.040 6.040

SLG DUTY: 3.941 0. Z2= 19.9146 3.941

480. VOLTS LN/LN: 5.231 Z0= 52.5202

LN/LN/GND: 5.729 ( 2.901 GND RETURN KA)

DISCO-ELEV1 3P Duty: 7.645 1. Z1= 15.7326 7.650 7.648

SLG DUTY: 5.212 1. Z2= 15.7326 5.212

480. VOLTS LN/LN: 6.621 Z0= 38.7319

LN/LN/GND: 7.399 ( 3.902 GND RETURN KA)

DISCO-ELEV2 3P Duty: 1.756 0. Z1= 68.5137 1.756 1.756

SLG DUTY: 1.031 0. Z2= 68.5137 1.031

480. VOLTS LN/LN: 1.520 Z0= 213.9866

LN/LN/GND: 1.610 ( 0.728 GND RETURN KA)

DISCO-HWP1 3P Duty: 0.784 0. Z1= 353.8959 0.784 0.784

SLG DUTY: 0.474 0. Z2= 353.8959 0.474

208. VOLTS LN/LN: 0.679 Z0=1051.5007

LN/LN/GND: 0.716 ( 0.339 GND RETURN KA)

DISCO-HWP2 3P Duty: 0.784 0. Z1= 353.8959 0.784 0.784

SLG DUTY: 0.474 0. Z2= 353.8959 0.474

208. VOLTS LN/LN: 0.679 Z0=1051.5007

LN/LN/GND: 0.716 ( 0.339 GND RETURN KA)

Feb 23, 2015 16:15:29 UNBALANCED LOW VOLTAGE DUTY PAGE 2

PRE FAULT VOLTAGE: 1.0000

MODEL TRANSFORMER TAPS: NO

LOCATION FAULT KA X/R EQUIVALENT (PU) ASYM. KA AT 0.5 CYCLES

VOLTAGE DUTIES (RMS) FAULT IMPEDANCE * MAX. RMS AVG. RMS *

DPA1 3P Duty: 5.436 2. Z1= 51.0639 5.554 5.495

SLG DUTY: 5.597 2. Z2= 51.0639 5.697

208. VOLTS LN/LN: 4.708 Z0= 46.7199

LN/LN/GND: 5.619 ( 5.765 GND RETURN KA)

EL1A 3P Duty: 9.309 2. Z1= 12.9204 9.531 9.420

SLG DUTY: 7.344 1. Z2= 12.9204 7.395

480. VOLTS LN/LN: 8.062 Z0= 23.7723

LN/LN/GND: 9.196 ( 6.007 GND RETURN KA)

ELS2 3P Duty: 2.757 0. Z1= 43.6283 2.757 2.757

SLG DUTY: 1.670 0. Z2= 43.6283 1.670

480. VOLTS LN/LN: 2.388 Z0= 129.2811

LN/LN/GND: 2.530 ( 1.196 GND RETURN KA)

EMBD 3P Duty: 1.494 19. Z1= 80.5170 2.331 1.938

SLG DUTY: 1.490 18. Z2= 80.5170 2.316

480. VOLTS LN/LN: 1.294 Z0= 81.1380

LN/LN/GND: 1.495 ( 1.486 GND RETURN KA)

EX MANHOLE 3P Duty: 24.509 7. Z1= 0.1889 33.377 29.126

SLG DUTY: 24.246 7. Z2= 0.1889 32.970

12470. VOLTS LN/LN: 21.225 Z0= 0.1950

LN/LN/GND: 24.401 ( 23.990 GND RETURN KA)

GEN BUS 3P Duty: 1.502 20. Z1= 80.0999 2.356 1.955

SLG DUTY: 1.502 20. Z2= 80.0999 2.356

480. VOLTS LN/LN: 1.300 Z0= 80.0999

LN/LN/GND: 1.502 ( 1.502 GND RETURN KA)

L1A 3P Duty: 13.461 4. Z1= 8.9353 15.596 14.549

SLG DUTY: 12.542 3. Z2= 8.9353 14.044

480. VOLTS LN/LN: 11.658 Z0= 10.9450

LN/LN/GND: 13.464 ( 11.722 GND RETURN KA)

LCP 3P Duty: 6.972 1. Z1= 17.2519 6.972 6.972

SLG DUTY: 4.643 0. Z2= 17.2519 4.643

480. VOLTS LN/LN: 6.038 Z0= 44.0646

LN/LN/GND: 6.673 ( 3.445 GND RETURN KA)

Feb 23, 2015 16:15:29 UNBALANCED LOW VOLTAGE DUTY PAGE 3

PRE FAULT VOLTAGE: 1.0000

MODEL TRANSFORMER TAPS: NO

LOCATION FAULT KA X/R EQUIVALENT (PU) ASYM. KA AT 0.5 CYCLES

VOLTAGE DUTIES (RMS) FAULT IMPEDANCE * MAX. RMS AVG. RMS *

MSB 3P Duty: 14.783 5. Z1= 8.1364 18.247 16.563

SLG DUTY: 14.422 5. Z2= 8.1364 17.756

480. VOLTS LN/LN: 12.803 Z0= 8.7471

LN/LN/GND: 14.633 ( 14.079 GND RETURN KA)

NEW MANHOLE 3P Duty: 22.968 6. Z1= 0.2016 29.955 26.584

SLG DUTY: 22.014 6. Z2= 0.2016 28.606

12470. VOLTS LN/LN: 19.891 Z0= 0.2278

LN/LN/GND: 22.573 ( 21.136 GND RETURN KA)

PV-INV 3P Duty: 6.040 1. Z1= 19.9146 6.040 6.040

SLG DUTY: 3.941 0. Z2= 19.9146 3.941

480. VOLTS LN/LN: 5.231 Z0= 52.5202

LN/LN/GND: 5.729 ( 2.901 GND RETURN KA)

R1A 3P Duty: 4.897 1. Z1= 56.6846 4.945 4.921

SLG DUTY: 4.684 1. Z2= 56.6846 4.704

208. VOLTS LN/LN: 4.241 Z0= 65.3356

LN/LN/GND: 5.073 ( 4.465 GND RETURN KA)

R2A 3P Duty: 4.030 1. Z1= 68.8722 4.040 4.035

SLG DUTY: 3.432 1. Z2= 68.8722 3.434

208. VOLTS LN/LN: 3.490 Z0= 107.2995

LN/LN/GND: 4.072 ( 2.960 GND RETURN KA)

R2B 3P Duty: 4.030 1. Z1= 68.8722 4.040 4.035

SLG DUTY: 3.432 1. Z2= 68.8722 3.434

208. VOLTS LN/LN: 3.490 Z0= 107.2995

LN/LN/GND: 4.072 ( 2.960 GND RETURN KA)

T-DPA1 3P Duty: 5.718 2. Z1= 48.5466 5.841 5.780

SLG DUTY: 6.079 2. Z2= 48.5466 6.192

208. VOLTS LN/LN: 4.952 Z0= 39.9206

LN/LN/GND: 6.008 ( 6.488 GND RETURN KA)

T-EL-A1A 3P Duty: 3.095 1. Z1= 89.6875 3.096 3.095

SLG DUTY: 3.277 1. Z2= 89.6875 3.277

208. VOLTS LN/LN: 2.680 Z0= 74.8127

LN/LN/GND: 3.232 ( 3.480 GND RETURN KA)

Feb 23, 2015 16:15:29 UNBALANCED LOW VOLTAGE DUTY PAGE 4

PRE FAULT VOLTAGE: 1.0000

MODEL TRANSFORMER TAPS: NO

LOCATION FAULT KA X/R EQUIVALENT (PU) ASYM. KA AT 0.5 CYCLES

VOLTAGE DUTIES (RMS) FAULT IMPEDANCE * MAX. RMS AVG. RMS *

T-MSB 3P Duty: 15.568 5. Z1= 7.7264 19.756 17.728

SLG DUTY: 15.608 5. Z2= 7.7264 19.792

480. VOLTS LN/LN: 13.482 Z0= 7.6667

LN/LN/GND: 15.594 ( 15.648 GND RETURN KA)

UPS-A 3P Duty: 3.466 1. Z1= 80.0850 3.469 3.467

SLG DUTY: 2.754 1. Z2= 80.0850 2.754

208. VOLTS LN/LN: 3.002 Z0= 145.2770

LN/LN/GND: 3.434 ( 2.262 GND RETURN KA)

UPS-MBP 3P Duty: 4.131 1. Z1= 67.1921 4.143 4.137

SLG DUTY: 3.564 1. Z2= 67.1921 3.566

208. VOLTS LN/LN: 3.578 Z0= 101.5409

LN/LN/GND: 4.189 ( 3.104 GND RETURN KA)

UPS1 3P Duty: 4.157 1. Z1= 66.7743 4.169 4.163

SLG DUTY: 3.599 1. Z2= 66.7743 3.601

208. VOLTS LN/LN: 3.600 Z0= 100.1064

LN/LN/GND: 4.219 ( 3.142 GND RETURN KA)

US6A 3P Duty: 25.011 8. Z1= 0.1851 34.583 30.004

SLG DUTY: 25.007 8. Z2= 0.1851 34.578

12470. VOLTS LN/LN: 21.660 Z0= 0.1852

LN/LN/GND: 25.009 ( 25.004 GND RETURN KA)

Feb 23, 2015 16:15:29 UNBALANCED LOW VOLTAGE DUTY PAGE 5

F A U L T S T U D Y S U M M A R Y

PRE FAULT VOLTAGE: 1.0000

MODEL TRANSFORMER TAPS: NO

BUS RECORD VOLTAGE A V A I L A B L E F A U L T D U T I E S (KA)

NO NAME L-L 3 PHASE X/R LINE/GRND X/R

1ER1A 208. 2.894 0.76 2.919 0.71

1ER1B 208. 2.763 0.73 2.699 0.67

ATS-E 480. 11.569 2.30 9.963 1.76

ATS-ELS 480. 6.040 0.58 3.941 0.40

DISCO-ELEV1 480. 7.645 0.86 5.212 0.53

DISCO-ELEV2 480. 1.756 0.34 1.031 0.18

DISCO-HWP1 208. 0.784 0.21 0.474 0.12

DISCO-HWP2 208. 0.784 0.21 0.474 0.12

DPA1 208. 5.436 1.64 5.597 1.56

EL1A 480. 9.309 1.69 7.344 1.26

ELS2 480. 2.757 0.32 1.670 0.23

EMBD 480. 1.494 18.90 1.490 18.16

EX MANHOLE 12470. 24.509 7.39 24.246 7.33

GEN BUS 480. 1.502 20.00 1.502 20.00

L1A 480. 13.461 3.56 12.542 3.04

LCP 480. 6.972 0.63 4.643 0.42

MSB 480. 14.783 4.69 14.422 4.64

NEW MANHOLE 12470. 22.968 5.99 22.014 5.89

PV-INV 480. 6.040 0.58 3.941 0.40

R1A 208. 4.897 1.36 4.684 1.16

R2A 208. 4.030 1.04 3.432 0.81 R2B 208. 4.030 1.04 3.432 0.81

T-DPA1 208. 5.718 1.64 6.079 1.58

T-EL-A1A 208. 3.095 0.78 3.277 0.77

T-MSB 480. 15.568 5.30 15.608 5.28

UPS-A 208. 3.466 0.89 2.754 0.67

UPS-MBP 208. 4.131 1.07 3.564 0.84

UPS1 208. 4.157 1.08 3.599 0.85

US6A 12470. 25.011 8.00 25.007 8.00

36 FAULTED BUSES, 40 BRANCHES, 6 CONTRIBUTIONS

UNBALANCED FAULTS REQUESTED

*** SHORT CIRCUIT STUDY COMPLETE ***

Feb 23, 2015 16:15:29 THREE PHASE MOMENTARY DUTY PAGE 1

T H R E E P H A S E M O M E N T A R Y D U T Y R E P O R T

PRE FAULT VOLTAGE: 1.0000

MODEL TRANSFORMER TAPS: NO

1ER1A VOLTAGE: 208. ( SEE LOW VOLTAGE REPORT )

1ER1B VOLTAGE: 208. ( SEE LOW VOLTAGE REPORT )

ATS-E VOLTAGE: 480. ( SEE LOW VOLTAGE REPORT )

ATS-ELS VOLTAGE: 480. ( SEE LOW VOLTAGE REPORT )

DISCO-ELEV1 VOLTAGE: 480. ( SEE LOW VOLTAGE REPORT )

DISCO-ELEV2 VOLTAGE: 480. ( SEE LOW VOLTAGE REPORT )

DISCO-HWP1 VOLTAGE: 208. ( SEE LOW VOLTAGE REPORT )

DISCO-HWP2 VOLTAGE: 208. ( SEE LOW VOLTAGE REPORT )

DPA1 VOLTAGE: 208. ( SEE LOW VOLTAGE REPORT )

EL1A VOLTAGE: 480. ( SEE LOW VOLTAGE REPORT )

ELS2 VOLTAGE: 480. ( SEE LOW VOLTAGE REPORT )

EMBD VOLTAGE: 480. ( SEE LOW VOLTAGE REPORT )

EX MANHOLE E/Z: 24.498 KA AT -82.29 DEG ( 529.12 MVA) X/R: 7.39

SYM*1.6: 39.196 KA MOMENTARY BASED ON X/R: 33.362 KA

SYM*2.7: 66.144 KA CREST BASED ON X/R: 57.292 KA

VOLTAGE: 12470. EQUIV. IMPEDANCE= 0.0394 + J 0.2912 OHMS

FDR-EX-MAN US6A 24.498 KA ANG: -82.29

GEN BUS VOLTAGE: 480. ( SEE LOW VOLTAGE REPORT )

L1A VOLTAGE: 480. ( SEE LOW VOLTAGE REPORT )

LCP VOLTAGE: 480. ( SEE LOW VOLTAGE REPORT )

MSB VOLTAGE: 480. ( SEE LOW VOLTAGE REPORT )

NEW MANHOLE E/Z: 22.957 KA AT -80.53 DEG ( 495.84 MVA) X/R: 5.99

SYM*1.6: 36.731 KA MOMENTARY BASED ON X/R: 29.940 KA

SYM*2.7: 61.984 KA CREST BASED ON X/R: 51.685 KA

VOLTAGE: 12470. EQUIV. IMPEDANCE= 0.0516 + J 0.3093 OHMS

FDR-NEW-MAN EX MANHOLE 22.957 KA ANG: -80.53

Feb 23, 2015 16:15:29 THREE PHASE MOMENTARY DUTY PAGE 2

T H R E E P H A S E M O M E N T A R Y D U T Y R E P O R T

MODEL TRANSFORMER TAPS: NO

CONTRIBUTIONS TO NEW MANHOLE (CONTINUED)

PV-INV VOLTAGE: 480. ( SEE LOW VOLTAGE REPORT )

R1A VOLTAGE: 208. ( SEE LOW VOLTAGE REPORT )

R2A VOLTAGE: 208. ( SEE LOW VOLTAGE REPORT )

R2B VOLTAGE: 208. ( SEE LOW VOLTAGE REPORT )

T-DPA1 VOLTAGE: 208. ( SEE LOW VOLTAGE REPORT )

T-EL-A1A VOLTAGE: 208. ( SEE LOW VOLTAGE REPORT )

T-MSB VOLTAGE: 480. ( SEE LOW VOLTAGE REPORT )

UPS-A VOLTAGE: 208. ( SEE LOW VOLTAGE REPORT )

UPS-MBP VOLTAGE: 208. ( SEE LOW VOLTAGE REPORT )

UPS1 VOLTAGE: 208. ( SEE LOW VOLTAGE REPORT )

US6A E/Z: 25.000 KA AT -82.87 DEG ( 539.97 MVA) X/R: 8.00

SYM*1.6: 40.000 KA MOMENTARY BASED ON X/R: 34.568 KA

SYM*2.7: 67.500 KA CREST BASED ON X/R: 59.228 KA

VOLTAGE: 12470. EQUIV. IMPEDANCE= 0.0357 + J 0.2858 OHMS

Feb 23, 2015 16:15:29 UNBALANCED MOMENTARY DUTY PAGE 1

U N B A L A N C E D M O M E N T A R Y D U T Y R E P O R T

MODEL TRANSFORMER TAPS: NO

LOCATION FAULT E/Z X/R EQUIVALENT MOMENTARY FAULT DUTIES

VOLTAGE TYPE KA IMPEDANCE (PU) E/Z * 1.6 @ 0.5 CYCLE

3P Duty: 24.50 7.4 Z1= 0.1890 39.20 33.36

EX MANHOLE SLG DUTY: 24.24 7.3 Z2= 0.1890 38.78 32.96

12470. VOLTS LN/LN: 21.22 Z0= 0.1950

LN/LN/GND: 24.39 ( 23.99 GND RETURN KA)

3P Duty: 22.96 6.0 Z1= 0.2017 36.73 29.94

NEW MANHOLE SLG DUTY: 22.01 5.9 Z2= 0.2017 35.21 28.60

12470. VOLTS LN/LN: 19.88 Z0= 0.2278

LN/LN/GND: 22.56 ( 21.13 GND RETURN KA)

3P Duty: 25.00 8.0 Z1= 0.1852 40.00 34.57

US6A SLG DUTY: 25.00 8.0 Z2= 0.1852 40.00 34.57

12470. VOLTS LN/LN: 21.65 Z0= 0.1852

LN/LN/GND: 25.00 ( 25.00 GND RETURN KA)

Feb 23, 2015 16:15:29 UNBALANCED MOMENTARY DUTY PAGE 2

M O M E N T A R Y D U T Y S U M M A R Y R E P O R T

MODEL TRANSFORMER TAPS: NO

SOLUTION METHOD : E/Z

BUS RECORD VOLTAGE * 3 P H A S E * * * * SLG * * *

NO NAME L-L KA X/R KA X/R

EX MANHOLE 12470. 33.362 7.39 32.960 7.33

NEW MANHOLE 12470. 29.940 5.99 28.597 5.89

US6A 12470. 34.568 8.00 34.568 8.00

4 FAULTED BUSES, 40 BRANCHES, 6 CONTRIBUTIONS

Feb 23, 2015 16:15:29 THREE PHASE INTERRUPTING DUTY PAGE 1

T H R E E P H A S E I N T E R R U P U T I N G D U T Y R E P O R T

MODEL TRANSFORMER TAPS: NO

1ER1A VOLTAGE: 208. ( SEE LOW VOLTAGE REPORT )

1ER1B VOLTAGE: 208. ( SEE LOW VOLTAGE REPORT )

ATS-E VOLTAGE: 480. ( SEE LOW VOLTAGE REPORT )

ATS-ELS VOLTAGE: 480. ( SEE LOW VOLTAGE REPORT )

DISCO-ELEV1 VOLTAGE: 480. ( SEE LOW VOLTAGE REPORT )

DISCO-ELEV2 VOLTAGE: 480. ( SEE LOW VOLTAGE REPORT )

DISCO-HWP1 VOLTAGE: 208. ( SEE LOW VOLTAGE REPORT )

DISCO-HWP2 VOLTAGE: 208. ( SEE LOW VOLTAGE REPORT )

DPA1 VOLTAGE: 208. ( SEE LOW VOLTAGE REPORT )

EL1A VOLTAGE: 480. ( SEE LOW VOLTAGE REPORT )

ELS2 VOLTAGE: 480. ( SEE LOW VOLTAGE REPORT )

EMBD VOLTAGE: 480. ( SEE LOW VOLTAGE REPORT )

EX MANHOLE E/Z: 24.498 KA AT -82.29 DEG ( 529.12 MVA) X/R: 7.39

VOLTAGE: 12470. EQUIV. IMPEDANCE= 0.0394 + J 0.2912 OHMS

FDR-EX-MAN US6A 24.498 KA ANG: -82.29

GENERATOR NAME -- AT BUS -- KA VOLTS PU LOCAL/REMOTE

UTIL-0002 24.498 0.02 R

TOTAL REMOTE: 24.498 KA NACD RATIO: 1.0000

SYM2 SYM3 SYM5 SYM8

MULT. FACT: 1.000 1.000 1.000 1.000

DUTY (KA) : 24.498 24.498 24.498 24.498

TOT2 TOT3 TOT5 TOT8

MULT. FACT: 1.128 1.013 1.000 1.000

DUTY (KA) : 27.634 24.823 24.498 24.498

GEN BUS VOLTAGE: 480. ( SEE LOW VOLTAGE REPORT )

L1A VOLTAGE: 480. ( SEE LOW VOLTAGE REPORT )

Feb 23, 2015 16:15:29 THREE PHASE INTERRUPTING DUTY PAGE 2

T H R E E P H A S E I N T E R R U P U T I N G D U T Y R E P O R T

MODEL TRANSFORMER TAPS: NO

LCP VOLTAGE: 480. ( SEE LOW VOLTAGE REPORT )

MSB VOLTAGE: 480. ( SEE LOW VOLTAGE REPORT )

NEW MANHOLE E/Z: 22.957 KA AT -80.53 DEG ( 495.84 MVA) X/R: 5.99

VOLTAGE: 12470. EQUIV. IMPEDANCE= 0.0516 + J 0.3093 OHMS

FDR-NEW-MAN EX MANHOLE 22.957 KA ANG: -80.53

GENERATOR NAME -- AT BUS -- KA VOLTS PU LOCAL/REMOTE

UTIL-0002 22.957 0.09 R

TOTAL REMOTE: 22.957 KA NACD RATIO: 1.0000

SYM2 SYM3 SYM5 SYM8

MULT. FACT: 1.000 1.000 1.000 1.000

DUTY (KA) : 22.957 22.957 22.957 22.957

TOT2 TOT3 TOT5 TOT8

MULT. FACT: 1.084 1.000 1.000 1.000

DUTY (KA) : 24.889 22.957 22.957 22.957

PV-INV VOLTAGE: 480. ( SEE LOW VOLTAGE REPORT )

R1A VOLTAGE: 208. ( SEE LOW VOLTAGE REPORT )

R2A VOLTAGE: 208. ( SEE LOW VOLTAGE REPORT )

R2B VOLTAGE: 208. ( SEE LOW VOLTAGE REPORT )

T-DPA1 VOLTAGE: 208. ( SEE LOW VOLTAGE REPORT )

T-EL-A1A VOLTAGE: 208. ( SEE LOW VOLTAGE REPORT )

T-MSB VOLTAGE: 480. ( SEE LOW VOLTAGE REPORT )

UPS-A VOLTAGE: 208. ( SEE LOW VOLTAGE REPORT )

UPS-MBP VOLTAGE: 208. ( SEE LOW VOLTAGE REPORT )

UPS1 VOLTAGE: 208. ( SEE LOW VOLTAGE REPORT )

US6A E/Z: 25.000 KA AT -82.87 DEG ( 539.97 MVA) X/R: 8.00

VOLTAGE: 12470. EQUIV. IMPEDANCE= 0.0357 + J 0.2858 OHMS

Feb 23, 2015 16:15:29 THREE PHASE INTERRUPTING DUTY PAGE 3

T H R E E P H A S E I N T E R R U P T I N G D U T Y R E P O R T

MODEL TRANSFORMER TAPS: NO

NACD OPTION: INTERPOLATED

GENERATOR NAME -- AT BUS -- KA VOLTS PU LOCAL/REMOTE

UTIL-0002 25.000 0.00 R

TOTAL REMOTE: 25.000 KA NACD RATIO: 1.0000

SYM2 SYM3 SYM5 SYM8

MULT. FACT: 1.000 1.000 1.000 1.001

DUTY (KA) : 25.000 25.000 25.000 25.020

TOT2 TOT3 TOT5 TOT8

MULT. FACT: 1.147 1.023 1.000 1.000

DUTY (KA) : 28.680 25.570 25.000 25.000

Feb 23, 2015 16:15:29 UNBALANCED INTERRUPTING DUTY PAGE 1

U N B A L A N C E D I N T E R R U P T I N G D U T Y R E P O R T

MODEL TRANSFORMER TAPS: NO

NACD OPTION: INTERPOLATED

LOCATION FAULT E/Z X/R ANSI AC/DC INTERRUPTING

TYPE KA DECREMENT FACT. DUTIES (KA)

3 PHASE SLG 3 PHASE SLG

EX MANHOLE 3P Duty: 24.50 7.4 SYM2: 1.00 1.00 24.50 24.24

VOLTS: 12470.0 SLG: 24.24 7.3 SYM3: 1.00 1.00 24.50 24.24

NACD: 1.000 LN/LN: 21.22 SYM5: 1.00 1.00 24.50 24.24

LN/LN/GND: 24.39 SYM8: 1.00 1.00 24.50 24.24

GND RETURN: 23.99 TOT2: 1.13 1.13 27.63 27.30

Z1(PU): 0.18899 TOT3: 1.01 1.01 24.82 24.54

Z2(PU): 0.18899 TOT5: 1.00 1.00 24.50 24.24

Z0(PU): 0.19504 TOT8: 1.00 1.00 24.50 24.24

NEW MANHOLE 3P Duty: 22.96 6.0 SYM2: 1.00 1.00 22.96 22.01

VOLTS: 12470.0 SLG: 22.01 5.9 SYM3: 1.00 1.00 22.96 22.01

NACD: 1.000 LN/LN: 19.88 SYM5: 1.00 1.00 22.96 22.01

LN/LN/GND: 22.56 SYM8: 1.00 1.00 22.96 22.01

GND RETURN: 21.13 TOT2: 1.08 1.08 24.89 23.79

Z1(PU): 0.20168 TOT3: 1.00 1.00 22.96 22.01

Z2(PU): 0.20168 TOT5: 1.00 1.00 22.96 22.01

Z0(PU): 0.22779 TOT8: 1.00 1.00 22.96 22.01

US6A 3P Duty: 25.00 8.0 SYM2: 1.00 1.00 25.00 25.00

VOLTS: 12470.0 SLG: 25.00 8.0 SYM3: 1.00 1.00 25.00 25.00

NACD: 1.000 LN/LN: 21.65 SYM5: 1.00 1.00 25.00 25.00

LN/LN/GND: 25.00 SYM8: 1.00 1.00 25.02 25.02

GND RETURN: 25.00 TOT2: 1.15 1.15 28.68 28.68

Z1(PU): 0.18520 TOT3: 1.02 1.02 25.57 25.57

Z2(PU): 0.18520 TOT5: 1.00 1.00 25.00 25.00

Z0(PU): 0.18520 TOT8: 1.00 1.00 25.00 25.00

Feb 23, 2015 16:15:29 UNBALANCED INTERRUPTING DUTY PAGE 2

I N T E R R U P T I N G D U T Y S U M M A R Y R E P O R T

MODEL TRANSFORMER TAPS: NO

NACD OPTION: INTERPOLATED

BUS RECORD VOLTAGE NACD * 3 P H A S E * * * * S L G * * *

NO NAME L-L RATIO E/Z KA X/R E/Z KA X/R

EX MANHOLE 12470. 1.000 24.498 7.39 24.239 7.33

NEW MANHOLE 12470. 1.000 22.957 5.99 22.007 5.89

US6A 12470. 1.000 25.000 8.00 25.000 8.00

4 FAULTED BUSES, 40 BRANCHES, 6 CONTRIBUTIONS

61 Coordination Study Results Submittal Approved 02_27_2015.pdf
Sheet1