This document is a Combined Synopsis/Solicitation for an Arc Flash Analysis service contract at the VA Loma Linda Healthcare System. The VA is seeking to purchase an Arc Flash Analysis to be in compliance with NFPA, IEEE, and Joint Commission requirements for regular inspections of electrical equipment. The contractor shall provide all labor, materials, tools, and software required to perform the Arc Flash Hazard Analysis, determine Arc Flash boundaries and incident energy, and place Arc Flash warning labels on evaluated equipment. The contractor must have an OSHA 30-hour safety card, electrical C-10 license, and NFPA/NICET certification. The contract period is 09/01/2024 - 08/31/2025 and is set-aside for 100% Service-Disabled Veteran-Owned Small Businesses. Quotes are due by 08/23/2024 and will be evaluated on price and past performance, with price being more important.
View the file
Other files for this federal contract opportunity
Show all 50
H959--ARC FLASH ANALYSIS - POP (09/01/2024 - 08/31/2025) has more files on GovTribe.
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Department of Veterans Affairs Loma Linda VA Medical Center 11201 Benton Street Loma Linda, CA 92357
APPROVED APPROVED AS NOTED
REJECTED REVISE AND RESUBMIT
SUBMIT SPECIFIED ITEM SEE COMMENT SHEET
REFERENCE: OP PHARMACY SUBMITTAL: 61 Coordination Study Results Approved
Date
This review is only for general conformance with the design concept of the project and general compliance with the information in the Contract Documents. Corrections or comments made on the shop drawings during this review do not relieve contractor from compliance with the requirements of the plans and specifciations. Approval of a specific item shall not include approval of an assembly of which the item is a component. Contractor is responsible for: dimension to be confrimed and correlated at the jobsite; information that pertains solely to the fabrication processes or to the means, methods, techniques, sequences and procedures of construction; coordination of the work of all trades; and for performing all work in a safe and satisfactory manner.
2/27/2015 Project Engineer
Submittal Transmittal
EwingCole
PROJECT VA-LL OP PHARMACY
20110460
DATE SENT 2/27/2015
SUBJECT 61. Coordination Study Results SUBMITTAL ID E0018
TYPE Submittal TRANSMITTAL ID 00208
PURPOSE Reviewed VIA Info Exchange
SPEC SECTION: 26 00 00
FROM
NAME COMPANY EMAIL PHONE
ESubmittals EwingCole ESubmittals@ewingcole.c om
TO
NAME COMPANY EMAIL PHONE
Rosie Soriano CalAmerica rosie@cal-am.net 951-784-4245
James Barber Veterans Administration James.Barber@va.gov 9095836826
Kevin Estrada Veterans Administration kevin.estrada@va.gov 909.583.6807
Ruby Carr EwingCole rcarr@ewingcole.com 949.417.7593
Shawn Steib CalAmerica shawn@cal-am.net (951) 784-
Terry Hinkley CalAmerica terry@cal-am.net Vincent Jackson EwingCole vjackson@ewingcole.com 949.417.6498
CONTENTS
QUANTITY: 1 DATED: 2/24/2015 NUMBER: cuts
DESCRIPTION:
61. Coordination Study Results.pdf
ACTION: For Review
REMARKS:
QUANTITY: 1 DATED: 2/27/2015 NUMBER:
DESCRIPTION:
61. Coordination Study Results - RESPONSE 2-27-15.pdf
ACTION: Reviewed
REMARKS:
Submittal Transmittal
DATE: 2/27/2015
ID: 00208
COPIES:
Kyle Kavanaugh
SUBMITTAL ACTION
SUBMISSION FIRST SECOND THIRD
REVIEWED
REVIEWED AS NOTED
REVIEWED AS NOTED RESUBMIT
REJECTED
RESUBMIT
SEE TRANSMITTAL FOR INSTRUCTIONS
This submittal has been reviewed only for conformance with the design concept of the Project and compliance with the Information given in the Contract Documents.
It is the Contractor’s contractual duty to review and act upon submittals, prior to their submission to verify that all requirements of the Contract Documents have been met or if they have not been met, to notify the Architect in writing. By the submission of this submittal to the Architect, it is assumed the Contractor has fulfiled these contractual duties. Review of this submittal by Architect does not relieve the Contractor of the duty to meet the requirements of the Contract Documents and the applicable building codes.
Any comments noted or corrections requested are for clarification of the general character of the work. Correctness of details, measurements, quantities, conformity with Contract Documents, techniques of construction and coordination with other trades shall remain the complete responsibility of the General/Prime Contractor.
BY: ------- DATE: ------
EWINGCOLE
15231 Laguna Canyon Road, Suite 200, Irvine, CA 92618
ARCHITECTS ENGINEERS INTERIOR DESIGNERS PLANNERS
Coordination Study Results Submittal Response 2/27/2015
K.K. 2/27/2015
Rock Electric Inc. 7950 Silverton Ave., Suite 211 San Diego, CA 92126 Ph: (858)566-4449 Fax: (858)536-8931
ROCK ELECTRIC INC.
Lic. No. 646958
VA Loma Linda Healthcare System “OP Pharmacy Building”
Contract VA262-14-C-0024
Engine Generators Specification Section 265100
Response to Engineers comments dated 2/2/15
Short Circuit/Coordination Power Study
General Contractor Cal American Construction, Inc.
2023 Chicago Ave., Suite B-8 Riverside, CA 92507
February 24, 2015
VA Loma Linda Pharmacy Building
Preliminary Short Circuit Study
Prepared For:
Rock Electric, Inc.
7950 Silverton Avenue, Suite 211
San Diego, CA 92126
Prepared By:
February 23, 2015
February 23, 2015
Preliminary Short Circuit Study‐ VA Loma Linda Pharmacy
MTA was contracted by Rock Electric to perform a Preliminary Short Circuit Study for the VA Loma Linda
Pharmacy Building. This Preliminary Short Circuit Study was generated using estimated feeder lengths that were provided to MTA. The Wire Sizes used for this study were taken off of the Engineer of
Record’s Singleline Diagram. It should be noted that once the actual feeder lengths are installed in the field, this study will be updated and re run which may change the Available short circuit current at each piece of electrical equipment. It is highly recommended that the EOR review the available short circuit current values provided in this study for each Distribution and Panel board.
MTA found that the feeder sizes shown on the singleline for the UPS Input and Bypass feeds were undersized for the breaker size shown on the Singleline. MTA assumed that these feeders would be
Sized at #2 AWG since the breakers were to be rated at 90Amps the #2 wire was used for this preliminary short circuit study. If this #2 AWG wire is not correct please let us know and we will update this preliminary Short Circuit Study to the correct size.
Since the 12KV contribution was unknown MTA has used 25,000A (3phase) and 25,000A (Line to
Ground) at 12,470Volts. This value is SCE maximum published 12KV contribution.
Should you have any questions or concerns about this study please do not hesitate to contact me.
Thank You, Mark Thomas, PE
President
MTA Electrical Engineers
Feb 23, 2015 16:15:28 Page 1
ALL INFORMATION PRESENTED IS FOR REVIEW, APPROVAL
INTERPRETATION AND APPLICATION BY A REGISTERED ENGINEER ONLY
SKM DISCLAIMS ANY RESPONSIBILITY AND LIABILITY RESULTING
FROM THE USE AND INTERPRETATION OF THIS SOFTWARE.
SKM POWER*TOOLS FOR WINDOWS
INPUT DATA REPORT
COPYRIGHT SKM SYSTEMS ANALYSIS, INC. 1995-2014
ALL PU VALUES ARE EXPRESSED ON A 100 MVA BASE.
Feb 23, 2015 16:15:28 Page 2
FEEDER INPUT DATA
CABLE FEEDER FROM FEEDER TO QTY VOLTS LENGTH FEEDER
NAME NAME NAME /PH L-L SIZE TYPE
FDR-1ER1A T-EL-A1A 1ER1A 1 208 20.0 FEET 1/0 Copper Duct Material: Magnetic Insulation Type: PVC Insulation Class: THWN +/- Impedance: 0.1280 + J 0.0540 Ohms/1000 ft 5.92 + J 2.50 PU Z0 Impedance: 0.4034 + J 0.1329 Ohms/1000 ft 18.65 + J 6.14 PU
FDR-1ER1B 1ER1A 1ER1B 1 208 10.0 FEET 2 Copper Duct Material: Magnetic Insulation Type: PVC Insulation Class: THWN +/- Impedance: 0.2020 + J 0.0585 Ohms/1000 ft 4.67 + J 1.35 PU Z0 Impedance: 0.6366 + J 0.1440 Ohms/1000 ft 14.71 + J 3.33 PU
FDR-ATS-E MSB ATS-E 1 480 70.0 FEET 3/0 Copper Duct Material: Magnetic Insulation Type: PVC Insulation Class: THWN +/- Impedance: 0.0805 + J 0.0519 Ohms/1000 ft 2.45 + J 1.58 PU Z0 Impedance: 0.2537 + J 0.1278 Ohms/1000 ft 7.71 + J 3.88 PU
FDR-ATSE-EM EMBD BUS-0011 1 480 60.0 FEET 3/0 Copper Duct Material: Magnetic Insulation Type: PVC Insulation Class: THWN +/- Impedance: 0.0805 + J 0.0519 Ohms/1000 ft 2.10 + J 1.35 PU Z0 Impedance: 0.2537 + J 0.1278 Ohms/1000 ft 6.61 + J 3.33 PU
FDR-ATS-ELS MSB ATS-ELS 1 480 70.0 FEET 6 Copper Duct Material: Magnetic Insulation Type: PVC Insulation Class: THWN +/- Impedance: 0.5100 + J 0.0685 Ohms/1000 ft 15.49 + J 2.08 PU Z0 Impedance: 1.61 + J 0.1687 Ohms/1000 ft 48.83 + J 5.13 PU
FDR-ATSELS-EM EMBD BUS-0010 1 480 20.0 FEET 6 Copper Duct Material: Magnetic Insulation Type: PVC Insulation Class: THWN +/- Impedance: 0.5100 + J 0.0685 Ohms/1000 ft 4.43 + J 0.5946 PU Z0 Impedance: 1.61 + J 0.1687 Ohms/1000 ft 13.95 + J 1.46 PU
FDR-DPA1 T-DPA1 DPA1 1 208 20.0 FEET 500 Copper Duct Material: Magnetic Insulation Type: PVC Insulation Class: THWN +/- Impedance: 0.0294 + J 0.0466 Ohms/1000 ft 1.36 + J 2.15 PU Z0 Impedance: 0.0926 + J 0.1147 Ohms/1000 ft 4.28 + J 5.30 PU
FDR-EL1A BUS-0015 EL1A 1 480 70.0 FEET 3/0 Copper Duct Material: Magnetic Insulation Type: PVC Insulation Class: THWN +/- Impedance: 0.0805 + J 0.0519 Ohms/1000 ft 2.45 + J 1.58 PU Z0 Impedance: 0.2537 + J 0.1278 Ohms/1000 ft 7.71 + J 3.88 PU
FDR-ELEV1 MSB DISCO-ELEV1 1 480 50.0 FEET 6 Copper Duct Material: Magnetic Insulation Type: PVC Insulation Class: THWN +/- Impedance: 0.5100 + J 0.0685 Ohms/1000 ft 11.07 + J 1.49 PU Z0 Impedance: 1.61 + J 0.1687 Ohms/1000 ft 34.88 + J 3.66 PU
Feb 23, 2015 16:15:28 Page 3
CABLE FEEDER FROM FEEDER TO QTY VOLTS LENGTH FEEDER
NAME NAME NAME /PH L-L SIZE TYPE
FDR-ELEV2 MSB DISCO-ELEV2 1 480 190.0 FEET 8 Copper Duct Material: Magnetic Insulation Type: PVC Insulation Class: THWN +/- Impedance: 0.8110 + J 0.0754 Ohms/1000 ft 66.88 + J 6.22 PU Z0 Impedance: 2.56 + J 0.1856 Ohms/1000 ft 210.77 + J 15.31 PU
FDR-ELS2 BUS-0014 ELS2 1 480 110.0 FEET 6 Copper Duct Material: Magnetic Insulation Type: PVC Insulation Class: THWN +/- Impedance: 0.5100 + J 0.0685 Ohms/1000 ft 24.35 + J 3.27 PU Z0 Impedance: 1.61 + J 0.1687 Ohms/1000 ft 76.73 + J 8.05 PU
FDR-EMDB GEN BUS EMBD 1 480 20.0 FEET 500 Copper Duct Material: Magnetic Insulation Type: PVC Insulation Class: THWN +/- Impedance: 0.0294 + J 0.0466 Ohms/1000 ft 0.2552 + J 0.4045 PU Z0 Impedance: 0.0926 + J 0.1147 Ohms/1000 ft 0.8038 + J 0.9957 PU
FDR-EX-MAN US6A EX MANHOLE 1 12470 130.0 FEET 500 Copper Duct Material: Non-Magnetic Insulation Type: EPR Insulation Class: MV +/- Impedance: 0.0284 + J 0.0421 Ohms/1000 ft 0.0024 + J 0.0035 PU Z0 Impedance: 0.0451 + J 0.1128 Ohms/1000 ft 0.0038 + J 0.0094 PU
FDR-HWP1 DPA1 DISCO-HWP1 1 208 75.0 FEET 12 Copper Duct Material: Magnetic Insulation Type: PVC Insulation Class: THWN +/- Impedance: 1.87 + J 0.0910 Ohms/1000 ft 324.17 + J 15.78 PU Z0 Impedance: 5.89 + J 0.2241 Ohms/1000 ft 1021.65 + J 38.85 PU
FDR-HWP2 DPA1 DISCO-HWP2 1 208 75.0 FEET 12 Copper Duct Material: Magnetic Insulation Type: PVC Insulation Class: THWN +/- Impedance: 1.87 + J 0.0910 Ohms/1000 ft 324.17 + J 15.78 PU Z0 Impedance: 5.89 + J 0.2241 Ohms/1000 ft 1021.65 + J 38.85 PU
FDR-L1A MSB L1A 1 480 30.0 FEET 250 Copper Duct Material: Magnetic Insulation Type: PVC Insulation Class: THWN +/- Impedance: 0.0552 + J 0.0495 Ohms/1000 ft 0.7188 + J 0.6445 PU Z0 Impedance: 0.1739 + J 0.1219 Ohms/1000 ft 2.26 + J 1.59 PU
FDR-LCP L1A LCP 1 480 15.0 FEET 12 Copper Duct Material: Magnetic Insulation Type: PVC Insulation Class: THWN +/- Impedance: 1.87 + J 0.0910 Ohms/1000 ft 12.17 + J 0.5924 PU Z0 Impedance: 5.89 + J 0.2241 Ohms/1000 ft 38.37 + J 1.46 PU
FDR-MSB T-MSB MSB 3 480 70.0 FEET 500 Copper Duct Material: Non-Magnetic Insulation Type: PVC Insulation Class: THWN +/- Impedance: 0.0276 + J 0.0373 Ohms/1000 ft 0.2795 + J 0.3777 PU Z0 Impedance: 0.0438 + J 0.0999 Ohms/1000 ft 0.4436 + J 1.01 PU
Feb 23, 2015 16:15:28 Page 4
CABLE FEEDER FROM FEEDER TO QTY VOLTS LENGTH FEEDER
NAME NAME NAME /PH L-L SIZE TYPE
FDR-NEW-MAN EX MANHOLE NEW MANHOLE 1 12470 430.0 FEET 500 Copper Duct Material: Non-Magnetic Insulation Type: EPR Insulation Class: MV +/- Impedance: 0.0284 + J 0.0421 Ohms/1000 ft 0.0079 + J 0.0116 PU Z0 Impedance: 0.0451 + J 0.1128 Ohms/1000 ft 0.0125 + J 0.0312 PU
FDR-PV-INV MSB PV-INV 1 480 70.0 FEET 6 Copper Duct Material: Magnetic Insulation Type: PVC Insulation Class: THWN +/- Impedance: 0.5100 + J 0.0685 Ohms/1000 ft 15.49 + J 2.08 PU Z0 Impedance: 1.61 + J 0.1687 Ohms/1000 ft 48.83 + J 5.13 PU
FDR-R1A DPA1 R1A 1 208 15.0 FEET 2 Copper Duct Material: Magnetic Insulation Type: PVC Insulation Class: THWN +/- Impedance: 0.2020 + J 0.0585 Ohms/1000 ft 7.00 + J 2.03 PU Z0 Impedance: 0.6366 + J 0.1440 Ohms/1000 ft 22.07 + J 4.99 PU
FDR-R2A DPA1 R2A 1 208 45.0 FEET 2 Copper Duct Material: Magnetic Insulation Type: PVC Insulation Class: THWN +/- Impedance: 0.2020 + J 0.0585 Ohms/1000 ft 21.01 + J 6.08 PU Z0 Impedance: 0.6366 + J 0.1440 Ohms/1000 ft 66.21 + J 14.98 PU
FDR-R2B DPA1 R2B 1 208 45.0 FEET 2 Copper Duct Material: Magnetic Insulation Type: PVC Insulation Class: THWN +/- Impedance: 0.2020 + J 0.0585 Ohms/1000 ft 21.01 + J 6.08 PU Z0 Impedance: 0.6366 + J 0.1440 Ohms/1000 ft 66.21 + J 14.98 PU
FDR-TDPA1 MSB BUS-0023 1 480 30.0 FEET 2/0 Copper Duct Material: Magnetic Insulation Type: PVC Insulation Class: THWN +/- Impedance: 0.1020 + J 0.0533 Ohms/1000 ft 1.33 + J 0.6940 PU Z0 Impedance: 0.3214 + J 0.1312 Ohms/1000 ft 4.18 + J 1.71 PU
FDR-TELA1A EL1A BUS-0018 1 480 15.0 FEET 6 Copper Duct Material: Magnetic Insulation Type: PVC Insulation Class: THWN +/- Impedance: 0.5100 + J 0.0685 Ohms/1000 ft 3.32 + J 0.4460 PU Z0 Impedance: 1.61 + J 0.1687 Ohms/1000 ft 10.46 + J 1.10 PU
FDR-TMSB NEW MANHOLE BUS-0005 1 12470 105.0 FEET 500 Copper Duct Material: Non-Magnetic Insulation Type: EPR Insulation Class: MV +/- Impedance: 0.0284 + J 0.0421 Ohms/1000 ft 0.0019 + J 0.0028 PU Z0 Impedance: 0.0451 + J 0.1128 Ohms/1000 ft 0.0030 + J 0.0076 PU
FDR-UPS-A UPS-MBP UPS-A 1 208 30.0 FEET 2 Copper Duct Material: Magnetic Insulation Type: PVC Insulation Class: THWN +/- Impedance: 0.2020 + J 0.0585 Ohms/1000 ft 14.01 + J 4.06 PU Z0 Impedance: 0.6366 + J 0.1440 Ohms/1000 ft 44.14 + J 9.99 PU
Feb 23, 2015 16:15:28 Page 5
CABLE FEEDER FROM FEEDER TO QTY VOLTS LENGTH FEEDER
NAME NAME NAME /PH L-L SIZE TYPE
FDR-UPS-IN DPA1 UPS1 1 208 40.0 FEET 2 Copper Duct Material: Magnetic Insulation Type: PVC Insulation Class: THWN +/- Impedance: 0.2020 + J 0.0585 Ohms/1000 ft 18.68 + J 5.41 PU Z0 Impedance: 0.6366 + J 0.1440 Ohms/1000 ft 58.86 + J 13.31 PU
FDR-UPS-OUT UPS1 UPS-MBP 1 208 1.000 FEET 2 Copper Duct Material: Magnetic Insulation Type: PVC Insulation Class: THWN +/- Impedance: 0.2020 + J 0.0585 Ohms/1000 ft 0.4669 + J 0.1352 PU Z0 Impedance: 0.6366 + J 0.1440 Ohms/1000 ft 1.47 + J 0.3328 PU
Feb 23, 2015 16:15:28 Page 6
TRANSFORMER INPUT DATA
TRANSFORMER PRIMARY RECORD VOLTS * SECONDARY RECORD VOLTS FULL-LOAD NOMINAL
NAME NO NAME L-L NO NAME L-L KVA KVA
TDPA1 BUS-0023 D 480.00 T-DPA1 YG 208.00 112.50 112.50
Pos. Seq. Z%: 2.56 + J 3.69 (Zpu 22.76 + j 32.80 ) Shell Type Zero Seq. Z%: 2.56 + J 3.69 (Sec 22.76 + j 32.80 Pri Open) Taps Pri. 0.000 % Sec. 0.000 % Phase Shift (Pri. Leading Sec.): 30.00 Deg.
TELA1A BUS-0018 D 480.00 T-EL-A1A YG 208.00 45.00 45.00
Pos. Seq. Z%: 2.73 + J 1.97 (Zpu 60.67 + j 43.78 ) Shell Type Zero Seq. Z%: 2.73 + J 1.97 (Sec 60.67 + j 43.78 Pri Open) Taps Pri. 0.000 % Sec. 0.000 % Phase Shift (Pri. Leading Sec.): 30.00 Deg.
TMSB BUS-0005 D 12470.0 T-MSB YG 480.00 862.50 750.00
Pos. Seq. Z%: 1.08 + J 5.65 (Zpu 1.44 + j 7.53 ) Shell Type Zero Seq. Z%: 1.08 + J 5.65 (Sec 1.44 + j 7.53 Pri Open) Taps Pri. 0.000 % Sec. 0.000 % Phase Shift (Pri. Leading Sec.): 30.00 Deg.
Feb 23, 2015 16:15:28 Page 7
GENERATION DATA
BUS NAME GENERATION VOLT SIZE InitKW MaxKVAR TYPE GEN BUS GENERATOR 1 pu 150.00 KW 0.00000 0.00000 SB
US6A UTIL-0002 1 pu SB Three Phase Contribution: 25000.0 AMPS X/R : 8.00 Line to Earth Contribution: 25000.0 AMPS X/R : 8.00 Pos sequence impedance (100 MVA base) 0.0230 + J 0.1838 PU Zero sequence impedance (100 MVA base) 0.0230 + J 0.1838 PU
Feb 23, 2015 16:15:28 Page 8
MOTOR LOAD DATA
BUS NAME LOAD NAME VOLT SIZE # TYPE EFF PF
DISCO-ELEV1 ELEV-1 480 20.0* 1 HP KVA 0.93 0.80 LAG
DISCO-ELEV2 ELEV-2 480 15.0* 1 HP KVA 0.93 0.80 LAG
DISCO-HWP1 HWP1 208 1.0* 1 HP KVA 0.93 0.80 LAG
DISCO-HWP2 HWP2 208 1.0* 1 HP KVA 0.93 0.80 LAG
Feb 23, 2015 16:15:29
ALL INFORMATION PRESENTED IS FOR REVIEW, APPROVAL
INTERPRETATION AND APPLICATION BY A REGISTERED ENGINEER ONLY
SKM DISCLAIMS ANY RESPONSIBILITY AND LIABILITY RESULTING
FROM THE USE AND INTERPRETATION OF THIS SOFTWARE.
SKM POWER*TOOLS FOR WINDOWS
A_FAULT SHORT CIRCUIT ANALYSIS REPORT
COPYRIGHT SKM SYSTEMS ANALYSIS, INC. 1996-2014
Feb 23, 2015 16:15:29 THREE PHASE LOW VOLTAGE DUTY PAGE 1
T H R E E P H A S E F A U L T R E P O R T
(FOR APPLICATION OF LOW VOLTAGE BREAKERS)
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
1ER1A 3P Duty: 2.894 KA AT -37.09 DEG ( 1.04 MVA) X/R: 0.76
VOLTAGE: 208. EQUIV. IMPEDANCE= 0.0331 + J 0.0250 OHMS
LOW VOLTAGE POWER CIRCUIT BREAKER 2.894 KA
MOLDED CASE CIRCUIT BREAKER < 10KA 2.894 KA
MOLDED CASE CIRCUIT BREAKER < 20KA 2.894 KA
MOLDED CASE CIRCUIT BREAKER > 20KA 2.894 KA
FDR-1ER1A T-EL-A1A 2.894 KA ANG: -37.09
1ER1B 3P Duty: 2.763 KA AT -36.10 DEG ( 1.00 MVA) X/R: 0.73
VOLTAGE: 208. EQUIV. IMPEDANCE= 0.0351 + J 0.0256 OHMS
LOW VOLTAGE POWER CIRCUIT BREAKER 2.763 KA
MOLDED CASE CIRCUIT BREAKER < 10KA 2.763 KA
MOLDED CASE CIRCUIT BREAKER < 20KA 2.763 KA
MOLDED CASE CIRCUIT BREAKER > 20KA 2.763 KA
FDR-1ER1B 1ER1A 2.763 KA ANG: -36.10
ATS-E 3P Duty: 11.569 KA AT -66.47 DEG ( 9.62 MVA) X/R: 2.30
VOLTAGE: 480. EQUIV. IMPEDANCE= 0.0096 + J 0.0220 OHMS
LOW VOLTAGE POWER CIRCUIT BREAKER 11.569 KA
MOLDED CASE CIRCUIT BREAKER < 20KA 11.569 KA
MOLDED CASE CIRCUIT BREAKER > 20KA 11.569 KA
FDR-ATS-E MSB 11.569 KA ANG: -66.47
ATS-ELS 3P Duty: 6.040 KA AT -30.26 DEG ( 5.02 MVA) X/R: 0.58
VOLTAGE: 480. EQUIV. IMPEDANCE= 0.0396 + J 0.0231 OHMS
LOW VOLTAGE POWER CIRCUIT BREAKER 6.040 KA
MOLDED CASE CIRCUIT BREAKER < 10KA 6.040 KA
MOLDED CASE CIRCUIT BREAKER < 20KA 6.040 KA
MOLDED CASE CIRCUIT BREAKER > 20KA 6.040 KA
FDR-ATS-ELS MSB 6.040 KA ANG: -30.26
DISCO-ELEV1 3P Duty: 7.645 KA AT -37.52 DEG ( 6.36 MVA) X/R: 0.86
VOLTAGE: 480. EQUIV. IMPEDANCE= 0.0287 + J 0.0221 OHMS
LOW VOLTAGE POWER CIRCUIT BREAKER 7.645 KA
MOLDED CASE CIRCUIT BREAKER < 10KA 7.645 KA
MOLDED CASE CIRCUIT BREAKER < 20KA 7.645 KA
MOLDED CASE CIRCUIT BREAKER > 20KA 7.645 KA
CONTRIBUTIONS: ELEV-1 0.157 KA ANG: -84.29
FDR-ELEV1 MSB 7.539 KA ANG: -36.65
DISCO-ELEV2 3P Duty: 1.756 KA AT -15.39 DEG ( 1.46 MVA) X/R: 0.34
VOLTAGE: 480. EQUIV. IMPEDANCE= 0.1522 + J 0.0419 OHMS
Feb 23, 2015 16:15:29 THREE PHASE LOW VOLTAGE DUTY PAGE 2
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
LOW VOLTAGE POWER CIRCUIT BREAKER 1.756 KA
MOLDED CASE CIRCUIT BREAKER < 10KA 1.756 KA
MOLDED CASE CIRCUIT BREAKER < 20KA 1.756 KA
MOLDED CASE CIRCUIT BREAKER > 20KA 1.756 KA
CONTRIBUTIONS: ELEV-2 0.118 KA ANG: -84.29
FDR-ELEV2 MSB 1.717 KA ANG: -11.72
DISCO-HWP1 3P Duty: 0.784 KA AT -10.86 DEG ( 0.28 MVA) X/R: 0.21
VOLTAGE: 208. EQUIV. IMPEDANCE= 0.1504 + J 0.0288 OHMS
LOW VOLTAGE POWER CIRCUIT BREAKER 0.784 KA
MOLDED CASE CIRCUIT BREAKER < 10KA 0.784 KA
MOLDED CASE CIRCUIT BREAKER < 20KA 0.784 KA
MOLDED CASE CIRCUIT BREAKER > 20KA 0.784 KA
CONTRIBUTIONS: HWP1 0.018 KA ANG: -84.29
FDR-HWP1 DPA1 0.779 KA ANG: -9.58
DISCO-HWP2 3P Duty: 0.784 KA AT -10.86 DEG ( 0.28 MVA) X/R: 0.21
VOLTAGE: 208. EQUIV. IMPEDANCE= 0.1504 + J 0.0288 OHMS
LOW VOLTAGE POWER CIRCUIT BREAKER 0.784 KA
MOLDED CASE CIRCUIT BREAKER < 10KA 0.784 KA
MOLDED CASE CIRCUIT BREAKER < 20KA 0.784 KA
MOLDED CASE CIRCUIT BREAKER > 20KA 0.784 KA
CONTRIBUTIONS: HWP2 0.018 KA ANG: -84.29
FDR-HWP2 DPA1 0.779 KA ANG: -9.58
DPA1 3P Duty: 5.436 KA AT -58.26 DEG ( 1.96 MVA) X/R: 1.64
VOLTAGE: 208. EQUIV. IMPEDANCE= 0.0116 + J 0.0188 OHMS
LOW VOLTAGE POWER CIRCUIT BREAKER 5.436 KA
MOLDED CASE CIRCUIT BREAKER < 10KA 5.436 KA
MOLDED CASE CIRCUIT BREAKER < 20KA 5.436 KA
MOLDED CASE CIRCUIT BREAKER > 20KA 5.436 KA
FDR-HWP1 DISCO-HWP1 0.018 KA ANG: 96.91
FDR-HWP2 DISCO-HWP2 0.018 KA ANG: 96.91
FDR-DPA1 T-DPA1 5.403 KA ANG: -58.10
EL1A 3P Duty: 9.309 KA AT -59.30 DEG ( 7.74 MVA) X/R: 1.69
VOLTAGE: 480. EQUIV. IMPEDANCE= 0.0152 + J 0.0256 OHMS
LOW VOLTAGE POWER CIRCUIT BREAKER 9.309 KA
MOLDED CASE CIRCUIT BREAKER < 10KA 9.309 KA
MOLDED CASE CIRCUIT BREAKER < 20KA 9.309 KA
MOLDED CASE CIRCUIT BREAKER > 20KA 9.309 KA
FDR-EL1A BUS-0015 9.309 KA ANG: -59.30
ELS2 3P Duty: 2.757 KA AT -17.76 DEG ( 2.29 MVA) X/R: 0.32
Feb 23, 2015 16:15:29 THREE PHASE LOW VOLTAGE DUTY PAGE 3
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
VOLTAGE: 480. EQUIV. IMPEDANCE= 0.0957 + J 0.0307 OHMS
LOW VOLTAGE POWER CIRCUIT BREAKER 2.757 KA
MOLDED CASE CIRCUIT BREAKER < 10KA 2.757 KA
MOLDED CASE CIRCUIT BREAKER < 20KA 2.757 KA
MOLDED CASE CIRCUIT BREAKER > 20KA 2.757 KA
FDR-ELS2 BUS-0014 2.757 KA ANG: -17.76
EMBD 3P Duty: 1.494 KA AT -86.97 DEG ( 1.24 MVA) X/R: 18.90
VOLTAGE: 480. EQUIV. IMPEDANCE= 0.0098 + J 0.1853 OHMS
LOW VOLTAGE POWER CIRCUIT BREAKER 1.702 KA
MOLDED CASE CIRCUIT BREAKER < 10KA 2.372 KA
MOLDED CASE CIRCUIT BREAKER < 20KA 2.010 KA
MOLDED CASE CIRCUIT BREAKER > 20KA 1.807 KA
FDR-EMDB GEN BUS 1.494 KA ANG: -86.97
EX MANHOLE 3P Duty: 24.509 KA AT -82.29 DEG ( 529.35 MVA) X/R: 7.39
VOLTAGE: 12470. EQUIV. IMPEDANCE= 0.0394 + J 0.2911 OHMS
FDR-EX-MAN US6A 24.498 KA ANG: -82.29
FDR-NEW-MAN NEW MANHOLE 0.011 KA ANG: -262.22
GEN BUS 3P Duty: 1.502 KA AT -87.14 DEG ( 1.25 MVA) X/R: 20.00
VOLTAGE: 480. EQUIV. IMPEDANCE= 0.0092 + J 0.1843 OHMS
LOW VOLTAGE POWER CIRCUIT BREAKER 1.718 KA
MOLDED CASE CIRCUIT BREAKER < 10KA 2.395 KA
MOLDED CASE CIRCUIT BREAKER < 20KA 2.029 KA
MOLDED CASE CIRCUIT BREAKER > 20KA 1.824 KA
CONTRIBUTIONS: GENERATOR 1.502 KA ANG: -87.14
L1A 3P Duty: 13.461 KA AT -74.26 DEG ( 11.19 MVA) X/R: 3.56
VOLTAGE: 480. EQUIV. IMPEDANCE= 0.0056 + J 0.0198 OHMS
LOW VOLTAGE POWER CIRCUIT BREAKER 13.461 KA
MOLDED CASE CIRCUIT BREAKER < 20KA 13.867 KA
MOLDED CASE CIRCUIT BREAKER > 20KA 13.461 KA
FDR-L1A MSB 13.461 KA ANG: -74.26
LCP 3P Duty: 6.972 KA AT -32.20 DEG ( 5.80 MVA) X/R: 0.63
VOLTAGE: 480. EQUIV. IMPEDANCE= 0.0336 + J 0.0212 OHMS
LOW VOLTAGE POWER CIRCUIT BREAKER 6.972 KA
MOLDED CASE CIRCUIT BREAKER < 10KA 6.972 KA
MOLDED CASE CIRCUIT BREAKER < 20KA 6.972 KA
MOLDED CASE CIRCUIT BREAKER > 20KA 6.972 KA
FDR-LCP L1A 6.972 KA ANG: -32.20
MSB 3P Duty: 14.783 KA AT -77.90 DEG ( 12.29 MVA) X/R: 4.69
Feb 23, 2015 16:15:29 THREE PHASE LOW VOLTAGE DUTY PAGE 4
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
VOLTAGE: 480. EQUIV. IMPEDANCE= 0.0039 + J 0.0183 OHMS
LOW VOLTAGE POWER CIRCUIT BREAKER 14.783 KA
MOLDED CASE CIRCUIT BREAKER < 20KA 16.284 KA
MOLDED CASE CIRCUIT BREAKER > 20KA 14.783 KA
FDR-ELEV2 DISCO-ELEV2 0.116 KA ANG: 99.35
FDR-ELEV1 DISCO-ELEV1 0.156 KA ANG: 96.52
FDR-MSB T-MSB 14.496 KA ANG: -77.81
FDR-TDPA1 BUS-0023 0.016 KA ANG: 97.06
NEW MANHOLE 3P Duty: 22.968 KA AT -80.53 DEG ( 496.07 MVA) X/R: 5.99
VOLTAGE: 12470. EQUIV. IMPEDANCE= 0.0516 + J 0.3092 OHMS
FDR-NEW-MAN EX MANHOLE 22.957 KA ANG: -80.53
FDR-TMSB BUS-0005 0.011 KA ANG: 97.78
PV-INV 3P Duty: 6.040 KA AT -30.26 DEG ( 5.02 MVA) X/R: 0.58
VOLTAGE: 480. EQUIV. IMPEDANCE= 0.0396 + J 0.0231 OHMS
LOW VOLTAGE POWER CIRCUIT BREAKER 6.040 KA
MOLDED CASE CIRCUIT BREAKER < 10KA 6.040 KA
MOLDED CASE CIRCUIT BREAKER < 20KA 6.040 KA
MOLDED CASE CIRCUIT BREAKER > 20KA 6.040 KA
FDR-PV-INV MSB 6.040 KA ANG: -30.26
R1A 3P Duty: 4.897 KA AT -53.31 DEG ( 1.76 MVA) X/R: 1.36
VOLTAGE: 208. EQUIV. IMPEDANCE= 0.0147 + J 0.0197 OHMS
LOW VOLTAGE POWER CIRCUIT BREAKER 4.897 KA
MOLDED CASE CIRCUIT BREAKER < 10KA 4.897 KA
MOLDED CASE CIRCUIT BREAKER < 20KA 4.897 KA
MOLDED CASE CIRCUIT BREAKER > 20KA 4.897 KA
FDR-R1A DPA1 4.897 KA ANG: -53.31
R2A 3P Duty: 4.030 KA AT -45.96 DEG ( 1.45 MVA) X/R: 1.04
VOLTAGE: 208. EQUIV. IMPEDANCE= 0.0207 + J 0.0214 OHMS
LOW VOLTAGE POWER CIRCUIT BREAKER 4.030 KA
MOLDED CASE CIRCUIT BREAKER < 10KA 4.030 KA
MOLDED CASE CIRCUIT BREAKER < 20KA 4.030 KA
MOLDED CASE CIRCUIT BREAKER > 20KA 4.030 KA
FDR-R2A DPA1 4.030 KA ANG: -45.96
R2B 3P Duty: 4.030 KA AT -45.96 DEG ( 1.45 MVA) X/R: 1.04
VOLTAGE: 208. EQUIV. IMPEDANCE= 0.0207 + J 0.0214 OHMS
LOW VOLTAGE POWER CIRCUIT BREAKER 4.030 KA
MOLDED CASE CIRCUIT BREAKER < 10KA 4.030 KA
MOLDED CASE CIRCUIT BREAKER < 20KA 4.030 KA
MOLDED CASE CIRCUIT BREAKER > 20KA 4.030 KA
Feb 23, 2015 16:15:29 THREE PHASE LOW VOLTAGE DUTY PAGE 5
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
CONTRIBUTIONS TO R2B (CONTINUED)
FDR-R2B DPA1 4.030 KA ANG: -45.96
T-DPA1 3P Duty: 5.718 KA AT -58.27 DEG ( 2.06 MVA) X/R: 1.64
VOLTAGE: 208. EQUIV. IMPEDANCE= 0.0110 + J 0.0179 OHMS
LOW VOLTAGE POWER CIRCUIT BREAKER 5.718 KA
MOLDED CASE CIRCUIT BREAKER < 10KA 5.718 KA
MOLDED CASE CIRCUIT BREAKER < 20KA 5.718 KA
MOLDED CASE CIRCUIT BREAKER > 20KA 5.718 KA
FDR-DPA1 DPA1 0.036 KA ANG: 96.91
TDPA1 BUS-0023 5.685 KA ANG: -238.11
T-EL-A1A 3P Duty: 3.095 KA AT -38.09 DEG ( 1.11 MVA) X/R: 0.78
VOLTAGE: 208. EQUIV. IMPEDANCE= 0.0305 + J 0.0239 OHMS
LOW VOLTAGE POWER CIRCUIT BREAKER 3.095 KA
MOLDED CASE CIRCUIT BREAKER < 10KA 3.095 KA
MOLDED CASE CIRCUIT BREAKER < 20KA 3.095 KA
MOLDED CASE CIRCUIT BREAKER > 20KA 3.095 KA
TELA1A BUS-0018 3.095 KA ANG: 141.91
T-MSB 3P Duty: 15.568 KA AT -79.28 DEG ( 12.94 MVA) X/R: 5.30
VOLTAGE: 480. EQUIV. IMPEDANCE= 0.0033 + J 0.0175 OHMS
LOW VOLTAGE POWER CIRCUIT BREAKER 15.568 KA
MOLDED CASE CIRCUIT BREAKER < 20KA 17.612 KA
MOLDED CASE CIRCUIT BREAKER > 20KA 15.832 KA
TMSB BUS-0005 15.281 KA ANG: -259.22
FDR-MSB MSB 0.287 KA ANG: 97.72
UPS-A 3P Duty: 3.466 KA AT -41.46 DEG ( 1.25 MVA) X/R: 0.89
VOLTAGE: 208. EQUIV. IMPEDANCE= 0.0260 + J 0.0229 OHMS
LOW VOLTAGE POWER CIRCUIT BREAKER 3.466 KA
MOLDED CASE CIRCUIT BREAKER < 10KA 3.466 KA
MOLDED CASE CIRCUIT BREAKER < 20KA 3.466 KA
MOLDED CASE CIRCUIT BREAKER > 20KA 3.466 KA
FDR-UPS-A UPS-MBP 3.466 KA ANG: -41.46
UPS-MBP 3P Duty: 4.131 KA AT -46.79 DEG ( 1.49 MVA) X/R: 1.07
VOLTAGE: 208. EQUIV. IMPEDANCE= 0.0199 + J 0.0212 OHMS
LOW VOLTAGE POWER CIRCUIT BREAKER 4.131 KA
MOLDED CASE CIRCUIT BREAKER < 10KA 4.131 KA
MOLDED CASE CIRCUIT BREAKER < 20KA 4.131 KA
MOLDED CASE CIRCUIT BREAKER > 20KA 4.131 KA
FDR-UPS-OUT UPS1 4.131 KA ANG: -46.79
Feb 23, 2015 16:15:29 THREE PHASE LOW VOLTAGE DUTY PAGE 6
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
UPS1 3P Duty: 4.157 KA AT -47.00 DEG ( 1.50 MVA) X/R: 1.08
VOLTAGE: 208. EQUIV. IMPEDANCE= 0.0197 + J 0.0211 OHMS
LOW VOLTAGE POWER CIRCUIT BREAKER 4.157 KA
MOLDED CASE CIRCUIT BREAKER < 10KA 4.157 KA
MOLDED CASE CIRCUIT BREAKER < 20KA 4.157 KA
MOLDED CASE CIRCUIT BREAKER > 20KA 4.157 KA
FDR-UPS-IN DPA1 4.157 KA ANG: -47.00
US6A 3P Duty: 25.011 KA AT -82.87 DEG ( 540.20 MVA) X/R: 8.00
VOLTAGE: 12470. EQUIV. IMPEDANCE= 0.0357 + J 0.2856 OHMS
CONTRIBUTIONS: UTIL-0002 25.000 KA ANG: -82.87
FDR-EX-MAN EX MANHOLE 0.011 KA ANG: -262.22
Feb 23, 2015 16:15:29 UNBALANCED LOW VOLTAGE DUTY PAGE 1
U N B A L A N C E D F A U L T R E P O R T
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
LOCATION FAULT KA X/R EQUIVALENT (PU) ASYM. KA AT 0.5 CYCLES
VOLTAGE DUTIES (RMS) FAULT IMPEDANCE * MAX. RMS AVG. RMS *
1ER1A 3P Duty: 2.894 1. Z1= 95.8993 2.895 2.895
SLG DUTY: 2.919 1. Z2= 95.8993 2.919
208. VOLTS LN/LN: 2.507 Z0= 93.7177
LN/LN/GND: 2.977 ( 2.941 GND RETURN KA)
1ER1B 3P Duty: 2.763 1. Z1= 100.4542 2.764 2.763
SLG DUTY: 2.699 1. Z2= 100.4542 2.699
208. VOLTS LN/LN: 2.393 Z0= 108.0604
LN/LN/GND: 2.820 ( 2.634 GND RETURN KA)
ATS-E 3P Duty: 11.569 2. Z1= 10.3972 12.299 11.937
SLG DUTY: 9.963 2. Z2= 10.3972 10.241
480. VOLTS LN/LN: 10.019 Z0= 15.6949
LN/LN/GND: 11.631 ( 8.685 GND RETURN KA)
ATS-ELS 3P Duty: 6.040 1. Z1= 19.9146 6.040 6.040
SLG DUTY: 3.941 0. Z2= 19.9146 3.941
480. VOLTS LN/LN: 5.231 Z0= 52.5202
LN/LN/GND: 5.729 ( 2.901 GND RETURN KA)
DISCO-ELEV1 3P Duty: 7.645 1. Z1= 15.7326 7.650 7.648
SLG DUTY: 5.212 1. Z2= 15.7326 5.212
480. VOLTS LN/LN: 6.621 Z0= 38.7319
LN/LN/GND: 7.399 ( 3.902 GND RETURN KA)
DISCO-ELEV2 3P Duty: 1.756 0. Z1= 68.5137 1.756 1.756
SLG DUTY: 1.031 0. Z2= 68.5137 1.031
480. VOLTS LN/LN: 1.520 Z0= 213.9866
LN/LN/GND: 1.610 ( 0.728 GND RETURN KA)
DISCO-HWP1 3P Duty: 0.784 0. Z1= 353.8959 0.784 0.784
SLG DUTY: 0.474 0. Z2= 353.8959 0.474
208. VOLTS LN/LN: 0.679 Z0=1051.5007
LN/LN/GND: 0.716 ( 0.339 GND RETURN KA)
DISCO-HWP2 3P Duty: 0.784 0. Z1= 353.8959 0.784 0.784
SLG DUTY: 0.474 0. Z2= 353.8959 0.474
208. VOLTS LN/LN: 0.679 Z0=1051.5007
LN/LN/GND: 0.716 ( 0.339 GND RETURN KA)
Feb 23, 2015 16:15:29 UNBALANCED LOW VOLTAGE DUTY PAGE 2
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
LOCATION FAULT KA X/R EQUIVALENT (PU) ASYM. KA AT 0.5 CYCLES
VOLTAGE DUTIES (RMS) FAULT IMPEDANCE * MAX. RMS AVG. RMS *
DPA1 3P Duty: 5.436 2. Z1= 51.0639 5.554 5.495
SLG DUTY: 5.597 2. Z2= 51.0639 5.697
208. VOLTS LN/LN: 4.708 Z0= 46.7199
LN/LN/GND: 5.619 ( 5.765 GND RETURN KA)
EL1A 3P Duty: 9.309 2. Z1= 12.9204 9.531 9.420
SLG DUTY: 7.344 1. Z2= 12.9204 7.395
480. VOLTS LN/LN: 8.062 Z0= 23.7723
LN/LN/GND: 9.196 ( 6.007 GND RETURN KA)
ELS2 3P Duty: 2.757 0. Z1= 43.6283 2.757 2.757
SLG DUTY: 1.670 0. Z2= 43.6283 1.670
480. VOLTS LN/LN: 2.388 Z0= 129.2811
LN/LN/GND: 2.530 ( 1.196 GND RETURN KA)
EMBD 3P Duty: 1.494 19. Z1= 80.5170 2.331 1.938
SLG DUTY: 1.490 18. Z2= 80.5170 2.316
480. VOLTS LN/LN: 1.294 Z0= 81.1380
LN/LN/GND: 1.495 ( 1.486 GND RETURN KA)
EX MANHOLE 3P Duty: 24.509 7. Z1= 0.1889 33.377 29.126
SLG DUTY: 24.246 7. Z2= 0.1889 32.970
12470. VOLTS LN/LN: 21.225 Z0= 0.1950
LN/LN/GND: 24.401 ( 23.990 GND RETURN KA)
GEN BUS 3P Duty: 1.502 20. Z1= 80.0999 2.356 1.955
SLG DUTY: 1.502 20. Z2= 80.0999 2.356
480. VOLTS LN/LN: 1.300 Z0= 80.0999
LN/LN/GND: 1.502 ( 1.502 GND RETURN KA)
L1A 3P Duty: 13.461 4. Z1= 8.9353 15.596 14.549
SLG DUTY: 12.542 3. Z2= 8.9353 14.044
480. VOLTS LN/LN: 11.658 Z0= 10.9450
LN/LN/GND: 13.464 ( 11.722 GND RETURN KA)
LCP 3P Duty: 6.972 1. Z1= 17.2519 6.972 6.972
SLG DUTY: 4.643 0. Z2= 17.2519 4.643
480. VOLTS LN/LN: 6.038 Z0= 44.0646
LN/LN/GND: 6.673 ( 3.445 GND RETURN KA)
Feb 23, 2015 16:15:29 UNBALANCED LOW VOLTAGE DUTY PAGE 3
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
LOCATION FAULT KA X/R EQUIVALENT (PU) ASYM. KA AT 0.5 CYCLES
VOLTAGE DUTIES (RMS) FAULT IMPEDANCE * MAX. RMS AVG. RMS *
MSB 3P Duty: 14.783 5. Z1= 8.1364 18.247 16.563
SLG DUTY: 14.422 5. Z2= 8.1364 17.756
480. VOLTS LN/LN: 12.803 Z0= 8.7471
LN/LN/GND: 14.633 ( 14.079 GND RETURN KA)
NEW MANHOLE 3P Duty: 22.968 6. Z1= 0.2016 29.955 26.584
SLG DUTY: 22.014 6. Z2= 0.2016 28.606
12470. VOLTS LN/LN: 19.891 Z0= 0.2278
LN/LN/GND: 22.573 ( 21.136 GND RETURN KA)
PV-INV 3P Duty: 6.040 1. Z1= 19.9146 6.040 6.040
SLG DUTY: 3.941 0. Z2= 19.9146 3.941
480. VOLTS LN/LN: 5.231 Z0= 52.5202
LN/LN/GND: 5.729 ( 2.901 GND RETURN KA)
R1A 3P Duty: 4.897 1. Z1= 56.6846 4.945 4.921
SLG DUTY: 4.684 1. Z2= 56.6846 4.704
208. VOLTS LN/LN: 4.241 Z0= 65.3356
LN/LN/GND: 5.073 ( 4.465 GND RETURN KA)
R2A 3P Duty: 4.030 1. Z1= 68.8722 4.040 4.035
SLG DUTY: 3.432 1. Z2= 68.8722 3.434
208. VOLTS LN/LN: 3.490 Z0= 107.2995
LN/LN/GND: 4.072 ( 2.960 GND RETURN KA)
R2B 3P Duty: 4.030 1. Z1= 68.8722 4.040 4.035
SLG DUTY: 3.432 1. Z2= 68.8722 3.434
208. VOLTS LN/LN: 3.490 Z0= 107.2995
LN/LN/GND: 4.072 ( 2.960 GND RETURN KA)
T-DPA1 3P Duty: 5.718 2. Z1= 48.5466 5.841 5.780
SLG DUTY: 6.079 2. Z2= 48.5466 6.192
208. VOLTS LN/LN: 4.952 Z0= 39.9206
LN/LN/GND: 6.008 ( 6.488 GND RETURN KA)
T-EL-A1A 3P Duty: 3.095 1. Z1= 89.6875 3.096 3.095
SLG DUTY: 3.277 1. Z2= 89.6875 3.277
208. VOLTS LN/LN: 2.680 Z0= 74.8127
LN/LN/GND: 3.232 ( 3.480 GND RETURN KA)
Feb 23, 2015 16:15:29 UNBALANCED LOW VOLTAGE DUTY PAGE 4
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
LOCATION FAULT KA X/R EQUIVALENT (PU) ASYM. KA AT 0.5 CYCLES
VOLTAGE DUTIES (RMS) FAULT IMPEDANCE * MAX. RMS AVG. RMS *
T-MSB 3P Duty: 15.568 5. Z1= 7.7264 19.756 17.728
SLG DUTY: 15.608 5. Z2= 7.7264 19.792
480. VOLTS LN/LN: 13.482 Z0= 7.6667
LN/LN/GND: 15.594 ( 15.648 GND RETURN KA)
UPS-A 3P Duty: 3.466 1. Z1= 80.0850 3.469 3.467
SLG DUTY: 2.754 1. Z2= 80.0850 2.754
208. VOLTS LN/LN: 3.002 Z0= 145.2770
LN/LN/GND: 3.434 ( 2.262 GND RETURN KA)
UPS-MBP 3P Duty: 4.131 1. Z1= 67.1921 4.143 4.137
SLG DUTY: 3.564 1. Z2= 67.1921 3.566
208. VOLTS LN/LN: 3.578 Z0= 101.5409
LN/LN/GND: 4.189 ( 3.104 GND RETURN KA)
UPS1 3P Duty: 4.157 1. Z1= 66.7743 4.169 4.163
SLG DUTY: 3.599 1. Z2= 66.7743 3.601
208. VOLTS LN/LN: 3.600 Z0= 100.1064
LN/LN/GND: 4.219 ( 3.142 GND RETURN KA)
US6A 3P Duty: 25.011 8. Z1= 0.1851 34.583 30.004
SLG DUTY: 25.007 8. Z2= 0.1851 34.578
12470. VOLTS LN/LN: 21.660 Z0= 0.1852
LN/LN/GND: 25.009 ( 25.004 GND RETURN KA)
Feb 23, 2015 16:15:29 UNBALANCED LOW VOLTAGE DUTY PAGE 5
F A U L T S T U D Y S U M M A R Y
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
BUS RECORD VOLTAGE A V A I L A B L E F A U L T D U T I E S (KA)
NO NAME L-L 3 PHASE X/R LINE/GRND X/R
1ER1A 208. 2.894 0.76 2.919 0.71
1ER1B 208. 2.763 0.73 2.699 0.67
ATS-E 480. 11.569 2.30 9.963 1.76
ATS-ELS 480. 6.040 0.58 3.941 0.40
DISCO-ELEV1 480. 7.645 0.86 5.212 0.53
DISCO-ELEV2 480. 1.756 0.34 1.031 0.18
DISCO-HWP1 208. 0.784 0.21 0.474 0.12
DISCO-HWP2 208. 0.784 0.21 0.474 0.12
DPA1 208. 5.436 1.64 5.597 1.56
EL1A 480. 9.309 1.69 7.344 1.26
ELS2 480. 2.757 0.32 1.670 0.23
EMBD 480. 1.494 18.90 1.490 18.16
EX MANHOLE 12470. 24.509 7.39 24.246 7.33
GEN BUS 480. 1.502 20.00 1.502 20.00
L1A 480. 13.461 3.56 12.542 3.04
LCP 480. 6.972 0.63 4.643 0.42
MSB 480. 14.783 4.69 14.422 4.64
NEW MANHOLE 12470. 22.968 5.99 22.014 5.89
PV-INV 480. 6.040 0.58 3.941 0.40
R1A 208. 4.897 1.36 4.684 1.16
R2A 208. 4.030 1.04 3.432 0.81 R2B 208. 4.030 1.04 3.432 0.81
T-DPA1 208. 5.718 1.64 6.079 1.58
T-EL-A1A 208. 3.095 0.78 3.277 0.77
T-MSB 480. 15.568 5.30 15.608 5.28
UPS-A 208. 3.466 0.89 2.754 0.67
UPS-MBP 208. 4.131 1.07 3.564 0.84
UPS1 208. 4.157 1.08 3.599 0.85
US6A 12470. 25.011 8.00 25.007 8.00
36 FAULTED BUSES, 40 BRANCHES, 6 CONTRIBUTIONS
UNBALANCED FAULTS REQUESTED
*** SHORT CIRCUIT STUDY COMPLETE ***
Feb 23, 2015 16:15:29 THREE PHASE MOMENTARY DUTY PAGE 1
T H R E E P H A S E M O M E N T A R Y D U T Y R E P O R T
PRE FAULT VOLTAGE: 1.0000
MODEL TRANSFORMER TAPS: NO
1ER1A VOLTAGE: 208. ( SEE LOW VOLTAGE REPORT )
1ER1B VOLTAGE: 208. ( SEE LOW VOLTAGE REPORT )
ATS-E VOLTAGE: 480. ( SEE LOW VOLTAGE REPORT )
ATS-ELS VOLTAGE: 480. ( SEE LOW VOLTAGE REPORT )
DISCO-ELEV1 VOLTAGE: 480. ( SEE LOW VOLTAGE REPORT )
DISCO-ELEV2 VOLTAGE: 480. ( SEE LOW VOLTAGE REPORT )
DISCO-HWP1 VOLTAGE: 208. ( SEE LOW VOLTAGE REPORT )
DISCO-HWP2 VOLTAGE: 208. ( SEE LOW VOLTAGE REPORT )
DPA1 VOLTAGE: 208. ( SEE LOW VOLTAGE REPORT )
EL1A VOLTAGE: 480. ( SEE LOW VOLTAGE REPORT )
ELS2 VOLTAGE: 480. ( SEE LOW VOLTAGE REPORT )
EMBD VOLTAGE: 480. ( SEE LOW VOLTAGE REPORT )
EX MANHOLE E/Z: 24.498 KA AT -82.29 DEG ( 529.12 MVA) X/R: 7.39
SYM*1.6: 39.196 KA MOMENTARY BASED ON X/R: 33.362 KA
SYM*2.7: 66.144 KA CREST BASED ON X/R: 57.292 KA
VOLTAGE: 12470. EQUIV. IMPEDANCE= 0.0394 + J 0.2912 OHMS
FDR-EX-MAN US6A 24.498 KA ANG: -82.29
GEN BUS VOLTAGE: 480. ( SEE LOW VOLTAGE REPORT )
L1A VOLTAGE: 480. ( SEE LOW VOLTAGE REPORT )
LCP VOLTAGE: 480. ( SEE LOW VOLTAGE REPORT )
MSB VOLTAGE: 480. ( SEE LOW VOLTAGE REPORT )
NEW MANHOLE E/Z: 22.957 KA AT -80.53 DEG ( 495.84 MVA) X/R: 5.99
SYM*1.6: 36.731 KA MOMENTARY BASED ON X/R: 29.940 KA
SYM*2.7: 61.984 KA CREST BASED ON X/R: 51.685 KA
VOLTAGE: 12470. EQUIV. IMPEDANCE= 0.0516 + J 0.3093 OHMS
FDR-NEW-MAN EX MANHOLE 22.957 KA ANG: -80.53
Feb 23, 2015 16:15:29 THREE PHASE MOMENTARY DUTY PAGE 2
T H R E E P H A S E M O M E N T A R Y D U T Y R E P O R T
MODEL TRANSFORMER TAPS: NO
CONTRIBUTIONS TO NEW MANHOLE (CONTINUED)
PV-INV VOLTAGE: 480. ( SEE LOW VOLTAGE REPORT )
R1A VOLTAGE: 208. ( SEE LOW VOLTAGE REPORT )
R2A VOLTAGE: 208. ( SEE LOW VOLTAGE REPORT )
R2B VOLTAGE: 208. ( SEE LOW VOLTAGE REPORT )
T-DPA1 VOLTAGE: 208. ( SEE LOW VOLTAGE REPORT )
T-EL-A1A VOLTAGE: 208. ( SEE LOW VOLTAGE REPORT )
T-MSB VOLTAGE: 480. ( SEE LOW VOLTAGE REPORT )
UPS-A VOLTAGE: 208. ( SEE LOW VOLTAGE REPORT )
UPS-MBP VOLTAGE: 208. ( SEE LOW VOLTAGE REPORT )
UPS1 VOLTAGE: 208. ( SEE LOW VOLTAGE REPORT )
US6A E/Z: 25.000 KA AT -82.87 DEG ( 539.97 MVA) X/R: 8.00
SYM*1.6: 40.000 KA MOMENTARY BASED ON X/R: 34.568 KA
SYM*2.7: 67.500 KA CREST BASED ON X/R: 59.228 KA
VOLTAGE: 12470. EQUIV. IMPEDANCE= 0.0357 + J 0.2858 OHMS
Feb 23, 2015 16:15:29 UNBALANCED MOMENTARY DUTY PAGE 1
U N B A L A N C E D M O M E N T A R Y D U T Y R E P O R T
MODEL TRANSFORMER TAPS: NO
LOCATION FAULT E/Z X/R EQUIVALENT MOMENTARY FAULT DUTIES
VOLTAGE TYPE KA IMPEDANCE (PU) E/Z * 1.6 @ 0.5 CYCLE
3P Duty: 24.50 7.4 Z1= 0.1890 39.20 33.36
EX MANHOLE SLG DUTY: 24.24 7.3 Z2= 0.1890 38.78 32.96
12470. VOLTS LN/LN: 21.22 Z0= 0.1950
LN/LN/GND: 24.39 ( 23.99 GND RETURN KA)
3P Duty: 22.96 6.0 Z1= 0.2017 36.73 29.94
NEW MANHOLE SLG DUTY: 22.01 5.9 Z2= 0.2017 35.21 28.60
12470. VOLTS LN/LN: 19.88 Z0= 0.2278
LN/LN/GND: 22.56 ( 21.13 GND RETURN KA)
3P Duty: 25.00 8.0 Z1= 0.1852 40.00 34.57
US6A SLG DUTY: 25.00 8.0 Z2= 0.1852 40.00 34.57
12470. VOLTS LN/LN: 21.65 Z0= 0.1852
LN/LN/GND: 25.00 ( 25.00 GND RETURN KA)
Feb 23, 2015 16:15:29 UNBALANCED MOMENTARY DUTY PAGE 2
M O M E N T A R Y D U T Y S U M M A R Y R E P O R T
MODEL TRANSFORMER TAPS: NO
SOLUTION METHOD : E/Z
BUS RECORD VOLTAGE * 3 P H A S E * * * * SLG * * *
NO NAME L-L KA X/R KA X/R
EX MANHOLE 12470. 33.362 7.39 32.960 7.33
NEW MANHOLE 12470. 29.940 5.99 28.597 5.89
US6A 12470. 34.568 8.00 34.568 8.00
4 FAULTED BUSES, 40 BRANCHES, 6 CONTRIBUTIONS
Feb 23, 2015 16:15:29 THREE PHASE INTERRUPTING DUTY PAGE 1
T H R E E P H A S E I N T E R R U P U T I N G D U T Y R E P O R T
MODEL TRANSFORMER TAPS: NO
1ER1A VOLTAGE: 208. ( SEE LOW VOLTAGE REPORT )
1ER1B VOLTAGE: 208. ( SEE LOW VOLTAGE REPORT )
ATS-E VOLTAGE: 480. ( SEE LOW VOLTAGE REPORT )
ATS-ELS VOLTAGE: 480. ( SEE LOW VOLTAGE REPORT )
DISCO-ELEV1 VOLTAGE: 480. ( SEE LOW VOLTAGE REPORT )
DISCO-ELEV2 VOLTAGE: 480. ( SEE LOW VOLTAGE REPORT )
DISCO-HWP1 VOLTAGE: 208. ( SEE LOW VOLTAGE REPORT )
DISCO-HWP2 VOLTAGE: 208. ( SEE LOW VOLTAGE REPORT )
DPA1 VOLTAGE: 208. ( SEE LOW VOLTAGE REPORT )
EL1A VOLTAGE: 480. ( SEE LOW VOLTAGE REPORT )
ELS2 VOLTAGE: 480. ( SEE LOW VOLTAGE REPORT )
EMBD VOLTAGE: 480. ( SEE LOW VOLTAGE REPORT )
EX MANHOLE E/Z: 24.498 KA AT -82.29 DEG ( 529.12 MVA) X/R: 7.39
VOLTAGE: 12470. EQUIV. IMPEDANCE= 0.0394 + J 0.2912 OHMS
FDR-EX-MAN US6A 24.498 KA ANG: -82.29
GENERATOR NAME -- AT BUS -- KA VOLTS PU LOCAL/REMOTE
UTIL-0002 24.498 0.02 R
TOTAL REMOTE: 24.498 KA NACD RATIO: 1.0000
SYM2 SYM3 SYM5 SYM8
MULT. FACT: 1.000 1.000 1.000 1.000
DUTY (KA) : 24.498 24.498 24.498 24.498
TOT2 TOT3 TOT5 TOT8
MULT. FACT: 1.128 1.013 1.000 1.000
DUTY (KA) : 27.634 24.823 24.498 24.498
GEN BUS VOLTAGE: 480. ( SEE LOW VOLTAGE REPORT )
L1A VOLTAGE: 480. ( SEE LOW VOLTAGE REPORT )
Feb 23, 2015 16:15:29 THREE PHASE INTERRUPTING DUTY PAGE 2
T H R E E P H A S E I N T E R R U P U T I N G D U T Y R E P O R T
MODEL TRANSFORMER TAPS: NO
LCP VOLTAGE: 480. ( SEE LOW VOLTAGE REPORT )
MSB VOLTAGE: 480. ( SEE LOW VOLTAGE REPORT )
NEW MANHOLE E/Z: 22.957 KA AT -80.53 DEG ( 495.84 MVA) X/R: 5.99
VOLTAGE: 12470. EQUIV. IMPEDANCE= 0.0516 + J 0.3093 OHMS
FDR-NEW-MAN EX MANHOLE 22.957 KA ANG: -80.53
GENERATOR NAME -- AT BUS -- KA VOLTS PU LOCAL/REMOTE
UTIL-0002 22.957 0.09 R
TOTAL REMOTE: 22.957 KA NACD RATIO: 1.0000
SYM2 SYM3 SYM5 SYM8
MULT. FACT: 1.000 1.000 1.000 1.000
DUTY (KA) : 22.957 22.957 22.957 22.957
TOT2 TOT3 TOT5 TOT8
MULT. FACT: 1.084 1.000 1.000 1.000
DUTY (KA) : 24.889 22.957 22.957 22.957
PV-INV VOLTAGE: 480. ( SEE LOW VOLTAGE REPORT )
R1A VOLTAGE: 208. ( SEE LOW VOLTAGE REPORT )
R2A VOLTAGE: 208. ( SEE LOW VOLTAGE REPORT )
R2B VOLTAGE: 208. ( SEE LOW VOLTAGE REPORT )
T-DPA1 VOLTAGE: 208. ( SEE LOW VOLTAGE REPORT )
T-EL-A1A VOLTAGE: 208. ( SEE LOW VOLTAGE REPORT )
T-MSB VOLTAGE: 480. ( SEE LOW VOLTAGE REPORT )
UPS-A VOLTAGE: 208. ( SEE LOW VOLTAGE REPORT )
UPS-MBP VOLTAGE: 208. ( SEE LOW VOLTAGE REPORT )
UPS1 VOLTAGE: 208. ( SEE LOW VOLTAGE REPORT )
US6A E/Z: 25.000 KA AT -82.87 DEG ( 539.97 MVA) X/R: 8.00
VOLTAGE: 12470. EQUIV. IMPEDANCE= 0.0357 + J 0.2858 OHMS
Feb 23, 2015 16:15:29 THREE PHASE INTERRUPTING DUTY PAGE 3
T H R E E P H A S E I N T E R R U P T I N G D U T Y R E P O R T
MODEL TRANSFORMER TAPS: NO
NACD OPTION: INTERPOLATED
GENERATOR NAME -- AT BUS -- KA VOLTS PU LOCAL/REMOTE
UTIL-0002 25.000 0.00 R
TOTAL REMOTE: 25.000 KA NACD RATIO: 1.0000
SYM2 SYM3 SYM5 SYM8
MULT. FACT: 1.000 1.000 1.000 1.001
DUTY (KA) : 25.000 25.000 25.000 25.020
TOT2 TOT3 TOT5 TOT8
MULT. FACT: 1.147 1.023 1.000 1.000
DUTY (KA) : 28.680 25.570 25.000 25.000
Feb 23, 2015 16:15:29 UNBALANCED INTERRUPTING DUTY PAGE 1
U N B A L A N C E D I N T E R R U P T I N G D U T Y R E P O R T
MODEL TRANSFORMER TAPS: NO
NACD OPTION: INTERPOLATED
LOCATION FAULT E/Z X/R ANSI AC/DC INTERRUPTING
TYPE KA DECREMENT FACT. DUTIES (KA)
3 PHASE SLG 3 PHASE SLG
EX MANHOLE 3P Duty: 24.50 7.4 SYM2: 1.00 1.00 24.50 24.24
VOLTS: 12470.0 SLG: 24.24 7.3 SYM3: 1.00 1.00 24.50 24.24
NACD: 1.000 LN/LN: 21.22 SYM5: 1.00 1.00 24.50 24.24
LN/LN/GND: 24.39 SYM8: 1.00 1.00 24.50 24.24
GND RETURN: 23.99 TOT2: 1.13 1.13 27.63 27.30
Z1(PU): 0.18899 TOT3: 1.01 1.01 24.82 24.54
Z2(PU): 0.18899 TOT5: 1.00 1.00 24.50 24.24
Z0(PU): 0.19504 TOT8: 1.00 1.00 24.50 24.24
NEW MANHOLE 3P Duty: 22.96 6.0 SYM2: 1.00 1.00 22.96 22.01
VOLTS: 12470.0 SLG: 22.01 5.9 SYM3: 1.00 1.00 22.96 22.01
NACD: 1.000 LN/LN: 19.88 SYM5: 1.00 1.00 22.96 22.01
LN/LN/GND: 22.56 SYM8: 1.00 1.00 22.96 22.01
GND RETURN: 21.13 TOT2: 1.08 1.08 24.89 23.79
Z1(PU): 0.20168 TOT3: 1.00 1.00 22.96 22.01
Z2(PU): 0.20168 TOT5: 1.00 1.00 22.96 22.01
Z0(PU): 0.22779 TOT8: 1.00 1.00 22.96 22.01
US6A 3P Duty: 25.00 8.0 SYM2: 1.00 1.00 25.00 25.00
VOLTS: 12470.0 SLG: 25.00 8.0 SYM3: 1.00 1.00 25.00 25.00
NACD: 1.000 LN/LN: 21.65 SYM5: 1.00 1.00 25.00 25.00
LN/LN/GND: 25.00 SYM8: 1.00 1.00 25.02 25.02
GND RETURN: 25.00 TOT2: 1.15 1.15 28.68 28.68
Z1(PU): 0.18520 TOT3: 1.02 1.02 25.57 25.57
Z2(PU): 0.18520 TOT5: 1.00 1.00 25.00 25.00
Z0(PU): 0.18520 TOT8: 1.00 1.00 25.00 25.00
Feb 23, 2015 16:15:29 UNBALANCED INTERRUPTING DUTY PAGE 2
I N T E R R U P T I N G D U T Y S U M M A R Y R E P O R T
MODEL TRANSFORMER TAPS: NO
NACD OPTION: INTERPOLATED
BUS RECORD VOLTAGE NACD * 3 P H A S E * * * * S L G * * *
NO NAME L-L RATIO E/Z KA X/R E/Z KA X/R
EX MANHOLE 12470. 1.000 24.498 7.39 24.239 7.33
NEW MANHOLE 12470. 1.000 22.957 5.99 22.007 5.89
US6A 12470. 1.000 25.000 8.00 25.000 8.00
4 FAULTED BUSES, 40 BRANCHES, 6 CONTRIBUTIONS