This document is a combined synopsis/solicitation for an Arc Flash Analysis service contract at the VA Loma Linda Healthcare System. The VA is seeking a contractor to provide labor, materials, and equipment to perform an Arc Flash Hazard Analysis on the facility's electrical distribution system, including the collection of data, analysis, reporting, and placement of Arc Flash warning labels. The contract is set-aside for 100% Service-Disabled Veteran-Owned Small Businesses (SDVOSB) and has a period of performance from 09/01/2024 to 08/31/2025. Quotes are due by 08/23/2024 and award will be based on price and past performance, with price being more important. Contractors must possess specific certifications and licenses to be considered for award. The VA will provide one-line diagrams upon request after award. This is a firm-fixed-price contract with no option periods.
View the file
Other files for this federal contract opportunity
Show all 50
H959--ARC FLASH ANALYSIS - POP (09/01/2024 - 08/31/2025) has more files on GovTribe.
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
E-114
ONE-LINE DIAGRAM
SERVICE BAY 5-7 - D1YH
t h r e e q u a r t e r s i n c h o n e f o o t o n e q u a r t e r i n c h o n e f o o t o n e e i g h t h i n c h o n e f o o t t h r e e e i g h t h s i n c h o n e f o o t
F o n e h a l f i n c h o n e f o o t
E
D
2 3 4 5 o n e i n c h o n e f o o t
C o n e h a l f i n c h o n e f o o t
B t h r e e i n c h e s o n e f o o t
A
1 2 3 4 5
Project Location
Building Number
6 7 8
Drawing Title
Scale
Revision
No. Date
VA MEDICAL CENTER
LOMA LINDA, CA
U.S. GOVERNMENT PRINTING OFFICE: 1983-400-285
DWG. Of
Checked
SAB
Drawn
DRAWING NO.
F E
D
6 7 8
C B
A
NO SCALE
Fax: 757-471-4205
Ph: 757-471-0537
Norfolk, VA 23510
101 West Main Street, Suite 7000
World Trade Center
ELT
LLCMiller-Remick
FAX: (856)429-5002
PHONE: (856)429-4000
CHERRY HILL, NEW JERSEY 08034
1010 KINGS HIGHWAY SOUTH
M.E.P. & Structural Engineering
Small Business
A Service Disabled Veteran Owned
A S e r v ic e D i s a b le d V eteran Ow ne d S m a l l B u s in e ss
SDVOSB
EVC
434.947.1901 | wileywilson.com | 100% Employee-Owned
127 Nationwide Drive | Lynchburg, VA 24502
NO SCALE
SERVICE BAY 5-7 - D1UH ONE-LINE DIAGRAM
Beginning of Single-Phase
SEE "SWBD MDBU -- SERVICE BAY 5-7 US-3B ONE-LINE DIAGRAM"
FOR CONTINUATION
F: 1_D1UH
(2) #350 THWN; 15 ft
SWBD: 1_D1UH
480V, 600A
65k SCAR
FU: 1_1ULE XFMR
EDISON (ECSR)
20 A
FU: 1_Outpatient Bldg
BUSSMANN (KTS-R)
200 A
FU: 1_BUH
BUSSMANN (FRS-R)
90 A
FU: 1_1UHA
BUSSMANN (FRS-R)
90 A
FU: 1_XFMR T-U1
BUSSMANN (JKS)
225 A
F: 1_1ULE XFMR
(1) #10 THWN; 25 ft
F: 1_Outpatient Bldg
(1) #3/0 THWN; 180 ft
CB: 51_1SW/HA Main
CUTLER-HAMMER (HFD)
200 A
F: 1_BUH
(1) #2 THWN; 45 ft
CB: 1_BUH Main
CUTLER-HAMMER (HFD)
100 A
PNL: 1_BUH
480V, 250A
200k SCAR
F: 1_1UHA
(1) #3 THWN; 45 ft
PNL: 1_1UHA
480V, 250A
200k SCAR
F: 1_XFMR T-U1
(1) #4/0 THWN; 35 ft
S
P
XF: 1_T-U1
150kVA; 3.46%Z
Pri: 480V
Sec: 208V
F: 1_SWBD D1UL
(2) #350 THWN; 15 ft
SWBD: 1_D1UL
208V, 600A
65k SCAR
FU: 1_Outpatient Pnl 1SW/LA/LB
BUSSMANN (LPJ-400SP)
400 A
FU: 1_1ULA
BUSSMANN (KTN-R)
150 A
FU: 1_1ULB
BUSSMANN (LPN-RK-100SP)
100 A
FU: 1_1ULC
BUSSMANN (KTN-R)
125 A
FU: 1_1ULD
BUSSMANN (KTN-R)
125 A
F: 1_Outpatient Pnl 1SW/LA/LB
(1) #500 THWN; 150 ft
CB: 1_1SW/LA Main
CUTLER-HAMMER (LD)
400 A
PNL: 1_1SW/LA
208V, 400A
200k SCAR
F: 1_1ULA
(1) #1/0 THWN; 20 ft
PNL: 1_1ULA
208V, 225A
10k SCAR
F: 1_1ULB
(1) #3 THWN; 25 ft
PNL: 1_1ULB
208V, 225A
10k SCAR
F: 1_1ULC
(1) #1/0 THWN; 30 ft
PNL: 1_1ULC
208V, 225A
10k SCAR
F: 1_1ULD
(1) #1/0 THWN; 30 ft
CB: 1_HI BOYS
CUTLER-HAMMER (FD)
50 A
F: 1_HI BOYS
(1) #6 THWN; 1 ft
S
P
XF: 1_T-1ULE
15kVA; 3.24%Z
Pri: 480V
Sec: 208V
F: 1_Pnl 1ULE
(1) #6 THWN; 10 ft
CB: 1_1ULE Main
CUTLER-HAMMER (BAB)
50 A
PNL: 1_1ULE
208V, 50A
200k SCAR
PNL: 1_1ULD
208V, 225A
10k SCAR
CB: 1_1G210 LASER
CUTLER-HAMMER (BAB)
25 A
CB: 1_1G210 LASER2
CUTLER-HAMMER (BAB)
25 A
F: 1_Pnl 1SW/LB
(1) #500 THWN; 15 ft
F: 1_1G210 LASER
(1) #6 THWN; 1 ft
F: 1_1G210 LASER2
(1) #6 THWN; 1 ft
PNL: 1_1SW/LB
208V, 400A
200k SCAR
CB: 1_Hot Water Htr
CUTLER-HAMMER (EB)
40 A
F: 1_Hot Water Htr
(1) #6 THWN; 1 ft
PNL: 51_1SW/HA
480V, 250A
200k SCAR
CB: 51_EF-1
CUTLER-HAMMER (HFD)
15 A
CB: 51_EF-3
CUTLER-HAMMER (HFD)
15 A
CB: 51_AHU-1 RF-1
CUTLER-HAMMER (HFD)
25 A
CB: 51_AHU-1 SF-1
CUTLER-HAMMER (HFD)
60 A
F: 51_EF-1
(1) #10 THWN; 1 ft
F: 51_EF-3
(1) #10 THWN; 1 ft
F: 51_AHU-1 RF-1
(1) #10 THWN; 70 ft
F: 51_AHU-1 SF-1
(1) #6 THWN; 55 ft
FU: 1_Building 52
BUSSMANN (KTS-R)
300 A
MTR: 51_AHU-1 SF-1
1 @ 25 hp
MTR: 51_AHU-1 RF-1
1 @ 7.5 hp
E-114 - SB 5-7.dgn 3/30/2018 8:35:49 AM