Tbl 6-1_2_Arc_Flash.pdf

PDF 72 KB Posted

Attached to
H959--ARC FLASH ANALYSIS - POP (09/01/2024 - 08/31/2025)
Solicitation number
36C26224Q1724
Issued by

About this file

This document is a combined synopsis/solicitation for an Arc Flash Analysis contract issued by the Department of Veterans Affairs (VA) for the VA Loma Linda Healthcare System (VALLHCS) in Loma Linda, California.

The VA is seeking to award a one-year contract to provide an Arc Flash Analysis of the VALLHCS electrical distribution system, including transformers, power panels, load centers, and disconnects. The contractor will be required to collect system data, perform an Arc Flash analysis, provide a written report, and place Arc Flash warning labels on all evaluated equipment. The work must comply with OSHA, NFPA, IEEE, and other industry standards. The solicitation is set-aside for 100% Service-Disabled Veteran-Owned Small Businesses (SDVOSB). Responses are due by August 23, 2024, and a site visit is scheduled for August 19, 2024. Award will be based on a comparative evaluation of price and past performance, with price being the more important factor.

View the file

Other files

File Type Posted
Loma Linda-60pc.pdf PDF
Tbl 3_3 Equip Eval.pdf PDF
E-110.pdf PDF
EYE Clinic One Line Drawings.docx DOCX document
E-115.pdf PDF
E-114.pdf PDF
116801E5.1.8.pdf PDF
E1.1 AUDIOLOGY.pdf PDF
Arc Flash Study CLC Ph 2.pdf PDF
116801E5.1.5.pdf PDF
116801E5.1.3.pdf PDF
116801E5.1.11.pdf PDF
Short Circuit Study - Op Pharmacy.pdf PDF
E-112.pdf PDF
E601 BEHAVIORAL HEALTH BUILDING.pdf PDF
116801E5.1.1.pdf PDF
116801E5.1.2.pdf PDF
116801E5.1.10.pdf PDF
E-111.pdf PDF
E-102.pdf PDF
36C26224Q1724_1.docx DOCX document
116801E5.1.4.pdf PDF
E-001.pdf PDF
116801E5.1.6.pdf PDF
116801E5.1.7.pdf PDF
116801E5.1.9.pdf PDF
E-105.pdf PDF
022712 SCC and OCPD Coordination Study - VA Loma Linda.pdf PDF
lf_calc format.pdf PDF
VALL Electrical Single Line Diagrams.pdf PDF
E-101.pdf PDF
Cover.pdf PDF
E-108.pdf PDF
E-104.pdf PDF
20110460 - Sheet - E-611 - SINGLE LINE DIAGRAM OP Pharmacy.pdf PDF
Arc Flash Study CLC Reb.pdf PDF
E-107.pdf PDF
CANCER CENTER SIGNAL LINE DRAWINGS 2017.png PNG image
input_data format.pdf PDF
Arc Flash Study 2016 Schneider Full Facility.pdf PDF
E-106.pdf PDF
79of89-EE002 PARKING GARAGE.pdf PDF
116801E5.1.12.pdf PDF
E-113.pdf PDF
MV Coordination Descrip Tbl.pdf PDF
CLC PC SIGNAL LINE DRAWINGS.png PNG image
E-103.pdf PDF
CLC ReHab SIGNAL LINE DRAWINGS.png PNG image
Tbl 4_1 MV Prot Dev Settingsa.pdf PDF
Loma Linda MV TCCs.pdf PDF
Show 40 more

Latest 50 of 54 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

VA Loma Linda - Jerry L. Pettis VAHCS - Loma Linda, California

Electrical Condition Assessment - Arc Flash Hazard Evaluation

Prepared for: Dept. of Veterans Affairs Section 6 Page 6 Prepared by: Wiley|Wilson

BUS: 1_SW US-1A West R: 1_FDR A-3 12.000 7.160 7.160 6.990 0.0167 0.083 Yes Yes SWG 152 26 36 0.87

BUS: 1_SW US-1B West R: 1_FDR B-3 12.000 7.150 7.150 6.980 0.0167 0.083 Yes Yes SWG 152 26 36 0.87

BUS: 1_SW US-2A East R: 1_FDR B-2 12.000 7.410 7.410 7.230 0.0167 0.083 Yes Yes SWG 152 27 36 0.90

BUS: 1_SW US-2B East R: 1_FDR A-2 12.000 7.400 7.400 7.220 0.0167 0.083 Yes Yes SWG 152 27 36 0.90

BUS: 1_SW US-3A West R: 1_FDR A-3 12.000 7.080 7.080 6.910 0.0167 0.083 Yes Yes SWG 152 26 36 0.86

BUS: 1_SW US-3B West R: 1_FDR A-3 12.000 7.070 7.070 6.900 0.0167 0.083 Yes Yes SWG 152 26 36 0.86

BUS: 1_SW US-4A East R: 1_FDR B-2 12.000 7.480 7.480 7.300 0.0167 0.083 Yes Yes SWG 152 27 36 0.91

BUS: 1_SW US-4B East R: 1_FDR A-2 12.000 7.470 7.470 7.290 0.0167 0.083 Yes Yes SWG 152 27 36 0.91

BUS: 1_SW US-5A East R: 1_FDR A-1 12.000 7.470 7.470 7.280 0.0167 0.083 Yes Yes SWG 152 27 36 0.91

BUS: 1_SW US-5B East R: 1_FDR B-1 12.000 7.460 7.460 7.270 0.0167 0.083 Yes Yes SWG 152 27 36 0.91

BUS: 1_SW US-6 East R: 1_FDR A-1 12.000 7.460 7.460 7.270 0.0167 0.083 Yes Yes SWG 152 27 36 0.91

BUS: 1_US-7-1 R: 1_FDR A-3 12.000 6.980 6.980 6.820 0.0167 0.083 Yes Yes SWG 152 25 36 0.85

SWGR: 1_NORTH R: 1_2A 12.000 7.500 6.500 5.390 1.157 0.050 Yes Yes SWG 152 256 36 8.06 (*N3)

SWGR: 1_SOUTH R: 1_2A 12.000 7.500 6.500 5.390 1.157 0.050 Yes Yes SWG 152 256 36 8.06 (*N3)

SWGR: 1_US-7 R: 1_US-7 12.000 6.980 6.980 6.820 0.0167 0.083 Yes Yes SWG 152 25 36 0.85

Notes:

(*N3) - Arcing Current Low Tolerances Used NFPA 70E 2015 Annex D.4 - IEEE 1584 Bus + Line Side Report (Include Line Side + Load Side Contributions), 80% Cleared Fault Threshold, include Ind. Motors for 5.0 Cycles), mis-coordination checked

Notes

TABLE 6.1 - ARC FLASH EVALUATION REPORT

Bus Name Bus (kV)Protective Device

Name

Bus Bolted Fault (kA)

Incident Energy

(cal/cm2)

Arc Flash Boundary

(in.)

Working Distance

(in.)

Ground

Prot Dev Bolted Fault (kA)

Prot Dev Arcing Fault (kA)

Trip/ Delay Time (sec.)

Breaker Opening

Time (sec.)

Equip Type

Gap (mm)

Bus Arcing Fault (kA)

VA Loma Linda - Jerry L. Pettis VAHCS - Loma Linda, California

Electrical Condition Assessment - Arc Flash Hazard Evaluation

Prepared for: Dept. of Veterans Affairs Section 6 Page 7 Prepared by: Wiley|Wilson

EXPOSED

MOVABLE

CONDUCTOR

EXPOSED FIXED

CIRCUIT PART

BUS: 1_SW US-1A West R: 1_FDR A-3 12.000 10 ft. 0 in. 5 ft. 0 in. 2 ft. 2 in.

BUS: 1_SW US-1B West R: 1_FDR B-3 12.000 10 ft. 0 in. 5 ft. 0 in. 2 ft. 2 in.

BUS: 1_SW US-2A East R: 1_FDR B-2 12.000 10 ft. 0 in. 5 ft. 0 in. 2 ft. 2 in.

BUS: 1_SW US-2B East R: 1_FDR A-2 12.000 10 ft. 0 in. 5 ft. 0 in. 2 ft. 2 in.

BUS: 1_SW US-3A West R: 1_FDR A-3 12.000 10 ft. 0 in. 5 ft. 0 in. 2 ft. 2 in.

BUS: 1_SW US-3B West R: 1_FDR A-3 12.000 10 ft. 0 in. 5 ft. 0 in. 2 ft. 2 in.

BUS: 1_SW US-4A East R: 1_FDR B-2 12.000 10 ft. 0 in. 5 ft. 0 in. 2 ft. 2 in.

BUS: 1_SW US-4B East R: 1_FDR A-2 12.000 10 ft. 0 in. 5 ft. 0 in. 2 ft. 2 in.

BUS: 1_SW US-5A East R: 1_FDR A-1 12.000 10 ft. 0 in. 5 ft. 0 in. 2 ft. 2 in.

BUS: 1_SW US-5B East R: 1_FDR B-1 12.000 10 ft. 0 in. 5 ft. 0 in. 2 ft. 2 in.

BUS: 1_SW US-6 East R: 1_FDR A-1 12.000 10 ft. 0 in. 5 ft. 0 in. 2 ft. 2 in.

BUS: 1_US-7-1 R: 1_FDR A-3 12.000 10 ft. 0 in. 5 ft. 0 in. 2 ft. 2 in.

SWGR: 1_NORTH R: 1_2A 12.000 10 ft. 0 in. 5 ft. 0 in. 2 ft. 2 in.

SWGR: 1_SOUTH R: 1_2A 12.000 10 ft. 0 in. 5 ft. 0 in. 2 ft. 2 in.

SWGR: 1_US-7 R: 1_US-7 12.000 10 ft. 0 in. 5 ft. 0 in. 2 ft. 2 in.

Boundaries have been determined using NFPA 70E, Table 130.4(D)(a).

TABLE 6.2 - APPROACH BOUNDARIES

TO LIVE PARTS FOR SHOCK PROTECTION

BUS NAME PROTECTIVE DEVICE NAME

LINE-TO-LINE

VOLTAGE

(kV)

LIMITED APPROACH BOUNDARY RESTRICTED APPROACH

BOUNDARY; INCLUDES

INADVERTENT

MOVEMENT ADDER

Table 6.1
Table-6.2