This document is a combined synopsis/solicitation for commercial products and commercial services related to an Arc Flash Analysis at the VA Loma Linda Healthcare System (VALLHCS). The VA is seeking to purchase an Arc Flash Analysis and is issuing this solicitation as an RFQ. The contract is set-aside for 100% Service-Disabled Veteran-Owned Small Business (SDVOSB) and the NAICS code is 238210. The scope requires the contractor to provide all labor, materials, and services to complete the Arc Flash Analysis, including data collection, analysis, generating one-line diagrams, and placing Arc Flash warning labels. The contract has a period of performance from 09/01/2024 to 08/31/2025. Responses are due by 08/23/2024. The award will be based on a comparative evaluation of price and past performance, with price being more important. The VA will provide one-line diagrams upon request after contract award.
View the file
Other files for this federal contract opportunity
Show all 50
H959--ARC FLASH ANALYSIS - POP (09/01/2024 - 08/31/2025) has more files on GovTribe.
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
INVERTER INV
MOUNTING FLUSH MAIN MLO
NEMA 3R NO 1 BUS 125A
FEED THRU NO 3 A.I.C. SERIES
N O T E S
LOCATION
A B
L T G
C O N V
K I T
R E C P
M I S C
B K R
C I R C
C I R C
B K R
M I S C
R E C P
K I T
C O N V
L T G
A B
LOCATION
N O T E S
PARKING LIGHTS 1100 13 1 20-1 1 2 20-1 4 1850 3RD AND 4TH POLE LTG
A= 2950 B= 0
277V-1Φ-3W
DOUBLE LUG NO VOLTS 277
200% NEUTRAL NO PHASE
GROUND BUS NO WIRE
PANEL "L"
MOUNTING MAIN NO
NEMA 3R NO 3 BUS 225A
FEED THRU YES 4 A.I.C. SERIES
N O T E S
LOCATION
A B C
L T G
C O N V
K I T
R E C P
M I S C
B K R
C I R C
C I R C
B K R
M I S C
R E C P
K I T
C O N V
L T G
A B C
LOCATION
N O T E S
SPARE. 20-1 1 2 20-1 10 1750 1ST LEVEL PARKING LTS
20-1 3 4 20-1 11 1925 1ST LEVEL PARKING LTS
20-1 5 6 20-1 10 27 2200 1st LEVEL PARKING LTS
3RD&4TH LEVEL P. LTS 1600 4 20-1 7 8 20-1 8 16 1800 1st LEVEL PARKING LTS
20-1 9 10 20-1 2 150 1ST LEVEL EXTERIOR LTS
20-1 11 12 20-1 SPARE
20-1 13 14 20-1 12 2100 2ND LEVEL PARKING LTS
20-1 15 16 20-1 13 2275 2ND LEVEL PARKING LTS
20-1 17 18 20-1 10 23 2000 2ND LEVEL PARKING LTS
20-1 19 20 20-1 20-1 21 22 20-1 20-1 23 24 20-1 20-1 25 26 20-1 20-1 27 28 20-1 20-1 29 30 20-1 20-1 31 32 20-1 20-1 33 34 20-1 20-1 35 36 20-1 20-1 37 38 20-1 20-1 39 40 20-1
SPACE 20-1 41 42 20-1 3500 3.5 KW INVERTER
A= 7250 B= C= 7700
TOTAL VA= 19300 W/LCL= 23250 15800 X .25 = 3950
HIGH PHASE VA= 7700 W/LCL= 8750 4200 X .25 = 1050
TOTAL LCL=
HIGH PHASE AMPS= 31.6 HIGH PHASE LCL=
AMPS= 28
200% NEUTRAL NO PHASE
I/G BUS NO WIRE
480Y/277V-3P-4W
SURFACE DOUBLE LUG YES VOLTS 480/277
PANEL P
MOUNTING MAIN MLO
NEMA 3R NO 3 BUS 125A
FEED THRU NO 4 A.I.C. SERIES
N O T E S
LOCATION
A B C
L T G
C O N V
K I T
R E C P
M I S C
B K R
C I R C
C I R C
B K R
M I S C
R E C P
K I T
C O N V
L T G
A B C
LOCATION
N O T E S
FACP 1000 1 20-1 1 2 20-1 5 900 1ST, 2ND& 3RD LEVEL
LCP-1 500 1 20-1 3 4 20-1 5 900 1ST, 2ND& 3RD LEVEL
CONTROL BOX RELAY 500 1 20-1 5 6 20-1 5 900 1ST, 2ND& 3RD LEVEL
FIRE BELL 500 1 20-1 7 8 20-1 5 900 1ST, 2ND& 3RD LEVEL
20-1 9 10 20-1 5 900 1ST, 2ND& 3RD LEVEL
20-1 11 12 20-1 1 180 ELEVATOR PIT
20-1 13 14 20-1 1 100 ELEVATOR PIT
20-1 15 16 20-1 20-1 17 18 20-1 20-1 19 20 20-1 20-1 21 22 20-1 20-1 23 24 20-1 20-1 25 26 20-1 20-1 27 28 20-1 20-1 29 30 20-1
20-1 31 32 20-2 1 1 980 DUPLEX SUMP-PUMP
20-1 33 34 800
20-1 35 36 20-2 1 850 AC-1 IN 1ST LEVEL.
20-1 37 38 850
20-1 39 40 30-2 1 1800 HP-1 IN 1ST LEVEL
20-1 41 42 1800
A= 5230 B= C= 4230
TOTAL VA= 14360 W/LCL= 14385 100 X .25 = 25
HIGH PHASE VA= 5230 W/LCL= 5255 100 X .25 = 25
AMPS= 40 TOTAL LCL=
HIGH PHASE AMPS= 44 HIGH PHASE LCL=
200% NEUTRAL NO PHASE
I/G BUS NO WIRE
208Y/120V-3Φ-4W
SURFACE DOUBLE LUG NO VOLTS 208/120
File details come from the government source that posted it. Updated .