E-102.pdf
PDF 409 KB Posted
- Attached to
- H959--ARC FLASH ANALYSIS - POP (09/01/2024 - 08/31/2025) Federal contract opportunity
- Solicitation number
- 36C26224Q1724
About this file
This document is a solicitation for an Arc Flash Analysis of the electrical distribution system at the VA Loma Linda Healthcare System (VALLHCS) facility. The VA is seeking a Service-Disabled Veteran-Owned Small Business (SDVOSB) contractor to provide labor, materials, and equipment to complete an arc flash hazard analysis, update one-line diagrams, and place arc flash warning labels on all evaluated equipment. The analysis must comply with OSHA, NFPA, and IEEE standards. The period of performance is 09/01/2024 - 08/31/2025. Quotes are due by 08/23/2024, and award will be based on price and past performance. The NAICS code is 238210 with a $19M small business size standard. There will be a site visit on 08/19/2024. The Government has unlimited data rights to all documents and materials produced under the contract.
View the file
Other files for this federal contract opportunity
Show all 50
H959--ARC FLASH ANALYSIS - POP (09/01/2024 - 08/31/2025) has more files on GovTribe.
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
E-102
ONE-LINE DIAGRAM
SERVICE BAY 1-3 D4IH, MCC-MIA
t h r e e q u a r t e r s i n c h o n e f o o t o n e q u a r t e r i n c h o n e f o o t o n e e i g h t h i n c h o n e f o o t t h r e e e i g h t h s i n c h o n e f o o t
F o n e h a l f i n c h o n e f o o t
E
D
2 3 4 5 o n e i n c h o n e f o o t
C o n e h a l f i n c h o n e f o o t
B t h r e e i n c h e s o n e f o o t
A
1 2 3 4 5
Project Location
Building Number
6 7 8
Drawing Title
Scale
Revision
No. Date
VA MEDICAL CENTER
LOMA LINDA, CA
U.S. GOVERNMENT PRINTING OFFICE: 1983-400-285
DWG. Of
Checked
SAB
Drawn
DRAWING NO.
F E
D
6 7 8
C B
A
NO SCALE
Fax: 757-471-4205
Ph: 757-471-0537
Norfolk, VA 23510
101 West Main Street, Suite 7000
World Trade Center
ELT
LLCMiller-Remick
FAX: (856)429-5002
PHONE: (856)429-4000
CHERRY HILL, NEW JERSEY 08034
1010 KINGS HIGHWAY SOUTH
M.E.P. & Structural Engineering
Small Business
A Service Disabled Veteran Owned
A S e r v ic e D i s a b le d V eteran Ow ne d S m a l l B u s in e ss
SDVOSB
EVC
434.947.1901 | wileywilson.com | 100% Employee-Owned
127 Nationwide Drive | Lynchburg, VA 24502
NO SCALE
SERVICE BAY 1-3 - D4IH ONE-LINE DIAGRAM
NO SCALE
SERVICE BAY 1-3 - MCC-MIA ONE-LINE DIAGRAM
SEE "ATS CU -- SERVICE BAY 1-3 US-1B
ONE-LINE DIAGRAM" FOR CONTINUATION
SEE "SWBD US-1A -- SERVICE BAY 1-3 US-1A ONE-LINE DIAGRAM"
FOR CONTNUATION
SWBD: 1_D4IH
480V, 400A
200k SCAR
CB: 1_Control Rm UPS 4E-04A
CUTLER-HAMMER (FD)
225 A, 225 A Plug
CB: 1_Unknown 2
CUTLER-HAMMER (EHD)
60 A, 60 A Plug
FU: 1_Main Disc Cath Lab
RELIANCE (ECSR)
125 A
FU: 1_ABT SB1
BUSSMANN (KTS-R)
125 A
FU: 1_Pnl 4IHA
BUSSMANN (KTS-R)
125 A
FU: 1_XF & Pnl 4ILD
EDISON (ECSR)
25 A
FU: 1_XF T-14
BUSSMANN (KTS-R)
175 A
F: 1_Pnl D4IH
(1) #350 THWN; 65 ft
F: 1_Control Rm UPS 4E-04A
(1) #2/0 THWN; 1 ft
F: 1_Unknown 2
(1) #8 THWN; 1 ft
F: 1_Main Disc Cath Lab
(1) #1/0 THWN; 1 ft
F: 1_ABT SB1
(1) #1/0 THWN; 1 ft
F: 1_Pnl 4IHA
(1) #1 THWN; 45 ft
PNL: 1_4IHA
480V, 250A
200k SCAR
F: 1_XF & Pnl 4ILD
(1) #10 THWN; 15 ft
F: 1_XF T-14
(1) #3/0 THWN; 40 ft
S
P
XF: 1_T-I4
113kVA; 3.30%Z
Pri: 480V
Sec: 208V
F: 1_SWBD D4IL
(1) #600 THWN; 20 ft
SWBD: 1_D4IL
208V, 400A
200k SCAR
FU: 1_Pnl 4ILC
BUSSMANN (LPN-RK-70SP)
70 A
FU: 1_Pnl 4ILB
BUSSMANN (KTN-R)
150 A
FU: 1_Pnl 4ILA
BUSSMANN (KTN-R)
125 A
F: 1_Pnl 4ILC
(1) #4 THWN; 35 ft
PNL: 1_4LIC
208V, 225A
10k SCAR
F: 1_Pnl 4ILB
(1) #2/0 THWN; 35 ft
PNL: 1_4ILB
208V, 225A
10k SCAR
F: 1_Pnl 4ILA
(1) #1/0 THWN; 35 ft
PNL: 1_4ILA
208V, 225A
10k SCAR
CB: 1_Humidifier Over Cath Lab
CUTLER-HAMMER (EHB)
40 A, 40 A Plug
F: 1_Humidifier Over Cath Lab
(1) #6 THWN; 1 ft
CB: 1_UPS
CUTLER-HAMMER (FD)
30 A, 30 A Plug
CB: 1_Blower Pneumatic Tube-1
CUTLER-HAMMER (FD)
20 A, 20 A Plug
CB: 1_Blower Pneumatic Tube-2
CUTLER-HAMMER (FD)
20 A, 20 A Plug
CB: 1_Blower Pneumatic Tube-3
CUTLER-HAMMER (FD)
20 A, 20 A Plug
F: 1_UPS
(1) #8 THWN; 40 ft
F: 1_Blower Pneumatic Tube-1
(1) #10 THWN; 55 ft
DISC: 1_PUMP 4-3-1
480V, F: 1_Blower Pneumatic Tube-2
(1) #10 THWN; 65 ft
DISC: 1_Pump 4-3-2 480V, F: 1_Blower Pneumatic Tube-3
(1) #10 THWN; 70 ft
DISC: 1_Pump 4-3-3 480V, FU: 1_Pump 4-3-2
FERRAZ SHAWMUT (TRS)
20 A
F: 1_Pump 4-3-2
(1) #10 THWN; 5 ft
FU: 1_Pump 4-3-3
FERRAZ SHAWMUT (TRS)
20 A
F: 1_Pump 4-3-3
(1) #10 THWN; 5 ft
FU: 1_Pump 4-3-1
BUSSMANN (FRS-R)
20 A
F: 1_Pump 4-3-1
(1) #10 THWN; 5 ft
S
P
XF: 1_4ILD
15kVA; 3.24%Z
Pri: 480V
Sec: 208V
F: 1_Pnl 4ILD
(1) #6 THWN; 5 ft
CB: 1_4ILD Main
CUTLER-HAMMER (BAB)
50 A
PNL: 1_4ILD
208V, 50A
200k SCAR
CB: 1_HP-1
CUTLER-HAMMER (HFD)
30 A, 30 A Plug
F: 1_HP-1
(1) #12 THWN; 1 ft
UPS: SB04-3 UPS
CB: 1_SB04-3 UPS Main
SQUARE D (Q2)
225 A, 225 A Plug
F: 1_CB SB04-3 UPS Main
(1) #1 THWN; 5 ft
PNL: SB04-3 UPS
CB: 1_UPS unk
SQUARE D (QO)
30 A, 30 A Plug
MTR: Pump 4-3-1
1 @ 10 hp
MTR: Pump 4-3-2
1 @ 10 hp
MTR: Pump 4-3-3
1 @ 10 hp
SEE "SWBD US-1A -- SERVICE BAY 1-3 US-1A ONE-LINE DIAGRAM" FOR CONTINUATION
F: 1_MC-MIA
(1) #350 THWN; 1 ft
MCC: 1_MCC-M1A
480V, 600A
65k SCAR
CB: 1_AH-6
CUTLER-HAMMER (HFD)
50 A, 50 A Plug
CB: 1_R-5
CUTLER-HAMMER (HFD)
20 A, 20 A Plug
CB: 1_S-6
CUTLER-HAMMER (HFD)
15 A, 15 A Plug
CB: 1_AH-14
CUTLER-HAMMER (HFD)
100 A, 100 A Plug
CB: 1_R-12
CUTLER-HAMMER (HFD)
40 A, 40 A Plug
CB: 1_AH-22
CUTLER-HAMMER (HFD)
100 A, 100 A Plug
CB: 1_XF Pnl B
CUTLER-HAMMER (EHD)
100 A, 100 A Plug
CB: 1_R-19
CUTLER-HAMMER (HFD)
40 A, 40 A Plug
CB: 1_AH-30
CUTLER-HAMMER (HFD)
100 A, 100 A Plug
CB: 1_R-26
CUTLER-HAMMER (HFD)
15 A, 15 A Plug
F: 1_AH-6
(1) #8 THWN; 25 ft
F: 1_R-5
(1) #12 THWN; 30 ft
F: 1_S-6
(1) #12 THWN; 1 ft
F: 1_AH-14
(1) #4 THWN; 40 ft
F: 1_R-12
(1) #10 THWN; 45 ft
F: 1_AH-22
(1) #4 THWN; 55 ft
F: 1_XF Pnl B
(1) #3 THWN; 55 ft
F: 1_R-19
(1) #10 THWN; 60 ft
F: 1_AH-30
(1) #4 THWN; 70 ft
F: 1_R-26
(1) #6 THWN; 75 ft
S
P
XF: 1_XF Pnl B
75kVA; 4.90%Z
Pri: 480V
Sec: 208V
F: 1_Disc PNL B
(1) #4/0 THWN; 5 ft
DISC: 1_PNL B
208V, CB: 1_PNL B
GE (TQD)
200 A
F: 1_PNL B
(1) #4/0 THWN; 1 ft
DISC: 1_AJAY Elev 208V, FU: 1_AJAY Elev
FERRAZ SHAWMUT (TR)
30 A
F: 1_Disc AJAY Elev
(1) #10 THWN; 35 ft
F: 1_AJAY Elev
(1) #10 THWN; 5 ft
VFD: 1_AH-6VFD: 1_AH-6 RF
MTR: 1_AH-6
1 @ 25 hp
MTR: 1_AH-6 RF
1 @ 7.5 hp
VFD: 1_AH-14 VFD: 1_AH-14 RF
MTR: 1_AH-14
1 @ 40 hp
MTR: 1_AH-14 RF
1 @ 15 hp
MTR: 1_AJAY Elev
1 @ 3.2 hp
TAP: 1_XF Pnl B
208V, VFD: 1_AH-22
MTR: 1_AH-22
1 @ 40 hp
VFD: 1_AH-22 RF
MTR: 1_AH-22 RF
1 @ 15 hp
VFD: 1_AH-30
MTR: 1_AH-30
1 @ 40 hp
VFD: 1_AH-30 RF
MTR: 1_AH-30 RF
1 @ 15 hp
E-102 - SB 1-3.dgn 3/30/2018 8:37:22 AM
File details come from the government source that posted it. Updated .