E-112.pdf
PDF 536 KB Posted
- Attached to
- H959--ARC FLASH ANALYSIS - POP (09/01/2024 - 08/31/2025) Federal contract opportunity
- Solicitation number
- 36C26224Q1724
About this file
This document is a combined synopsis/solicitation for a federal contract opportunity issued by the Department of Veterans Affairs (VA) Veterans Health Administration (VHA) for an Arc Flash Analysis at the VA Loma Linda Healthcare System (VALLHCS) in Loma Linda, CA.
The VA is seeking to purchase an Arc Flash Analysis, which will determine the Arc Flash Boundary, incident energy, and required personal protective equipment for the VALLHCS electrical system. The contractor will collect data, analyze it using electrical engineering software, produce one-line diagrams, and provide a detailed written report. The Arc Flash Analysis must comply with NFPA 70E, IEEE 1584, and other relevant standards. The contract is set-aside for 100% Service-Disabled Veteran-Owned Small Businesses (SDVOSB) and has a period of performance from 09/01/2024 to 08/31/2025. Quotes are due by 08/23/2024, and award will be based on price and past performance, with price being more important. The NAICS code is 238210 with a small business size standard of $19.0 million.
View the file
Other files for this federal contract opportunity
Show all 50
H959--ARC FLASH ANALYSIS - POP (09/01/2024 - 08/31/2025) has more files on GovTribe.
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
E-112
DPMHA ONE-LINE DIAGRAMS
SERVICE BAY 5-7 D2MH, D4MH,
t h r e e q u a r t e r s i n c h o n e f o o t o n e q u a r t e r i n c h o n e f o o t o n e e i g h t h i n c h o n e f o o t t h r e e e i g h t h s i n c h o n e f o o t
F o n e h a l f i n c h o n e f o o t
E
D
2 3 4 5 o n e i n c h o n e f o o t
C o n e h a l f i n c h o n e f o o t
B t h r e e i n c h e s o n e f o o t
A
1 2 3 4 5
Project Location
Building Number
6 7 8
Drawing Title
Scale
Revision
No. Date
VA MEDICAL CENTER
LOMA LINDA, CA
U.S. GOVERNMENT PRINTING OFFICE: 1983-400-285
DWG. Of
Checked
SAB
Drawn
DRAWING NO.
F E
D
6 7 8
C B
A
NO SCALE
Fax: 757-471-4205
Ph: 757-471-0537
Norfolk, VA 23510
101 West Main Street, Suite 7000
World Trade Center
ELT
LLCMiller-Remick
FAX: (856)429-5002
PHONE: (856)429-4000
CHERRY HILL, NEW JERSEY 08034
1010 KINGS HIGHWAY SOUTH
M.E.P. & Structural Engineering
Small Business
A Service Disabled Veteran Owned
A S e r v ic e D i s a b le d V eteran Ow ne d S m a l l B u s in e ss
SDVOSB
EVC
434.947.1901 | wileywilson.com | 100% Employee-Owned
127 Nationwide Drive | Lynchburg, VA 24502
NO SCALE
SERVICE BAY 5-7 D2MH ONE-LINE DIAGRAM
NO SCALE
SERVICE BAY 5-7 D4MH ONE-LINE DIAGRAM
NO SCALE
SERVICE BAY 5-7 DPMHA ONE-LINE DIAGRAM
Beginning of Single-Phase
SEE "SWBD US-3A -- SERVICE BAY 5-7 US-3A ONE-LINE DIAGRAM"
FOR CONTINUATION
F: 1_D2MH
(2) #250 THWN; 50 ft
SWBD: 1_D2MH
480V, 600A
65k SCAR
FU: 1_2 MLD XFMR
EDISON (ECSR)
25 A
FU: 1_2MHA
BUSSMANN (KTS-R)
150 A
FU: 1_XFMR T-M2
BUSSMANN (JKS)
350 A
F: 1_2 MLD XFMR
(1) #10 THWN; 20 ft
F: 1_2MHA
(1) #1 THWN; 35 ft
PNL: 1_2MHA
480V, 250A
200k SCAR
F: 1_XFMR T-M2
(1) #500 THWN; 25 ft
S
P
XF: 1_T-2MLD
15kVA; 3.24%Z
Pri: 480V
Sec: 208V
F: 1_Pnl 2MLD
(1) #6 THWN; 10 ft
CB: 1_2MLD Main
CUTLER-HAMMER (BAB)
50 A
PNL: 1_2MLD
208V, 50A
200k SCAR
S
P
XF: 1_T-M2
225kVA; 3.60%Z
Pri: 480V
Sec: 208V
F: 1_SWBD D2ML
(2) #600 THWN; 20 ft
SWBD: 1_D2ML
208V, 800A
65k SCAR
FU: 1_2MLB
BUSSMANN (KTN-R)
175 A
FU: 1_2MLC
BUSSMANN (LPN-RK-70SP)
70 A
FU: 1_PMR-A
BUSSMANN (KTN-R)
175 A
FU: 1_2MLA
BUSSMANN (KTN-R)
150 A
F: 1_2MLB
(1) #1/0 THWN; 30 ft
PNL: 1_2MLB
208V, 225A
10k SCAR
F: 1_2MLC
(1) #4 THWN; 30 ft
PNL: 1_2MLC
208V, 100A
10k SCAR
F: 1_PMR-A
(1) #2/0 THWN; 1 ft
F: 1_2MLA
(1) #1/0 THWN; 35 ft
PNL: 1_2MLA
208V, 225A
10k SCAR
CB: 1_Chill Water Pump
CUTLER-HAMMER (EB)
20 A
F: 1_Chill Water Pump
(1) #12 THWN; 75 ft
DISC: 1_Pump Rm 2SB5 208V, FU: 1_Pump Rm 2SB5
FERRAZ SHAWMUT (TR10R)
10 A
FU: 1_PMR-B
BUSSMANN (LPN-RK-100SP)
100 A
SEE "SWBD US-3A -- SERVICE BAY 5-7 US-3A ONE-LINE DIAGRAM"
FOR CONTINUATION
F: 1_D4MH
(2) #250 THWN; 90 ft
SWBD: 1_D4MH
480V, 600A
65k SCAR
FU: 1_CH-1
FERRAZ SHAWMUT (TRS)
100 A
FU: 1_CH-2
FERRAZ SHAWMUT (TRS)
100 A
FU: 1_MCC-MMB
BUSSMANN (LPS-RK)
125 A
FU: 1_4MHA
BUSSMANN (LPS-RK)
125 A
FU: 1_XFMR T-M4
BUSSMANN (JKS)
225 A
F: 1_CH-1
(1) #2 THWN; 20 ft
DISC: 1_CH-1
480V, F: 1_CH-2
(1) #2 THWN; 30 ft
DISC: 1_CH-2
480V, F: 1_MCC-MMB
(1) #1 THWN; 80 ft
MCC: 1_MMB
480V, 600A
65k SCAR
F: 1_4MHA
(1) #1 THWN; 50 ft
PNL: 1_4MHA
480V, 250A
200k SCAR
F: 1_XFMR T-M4
(1) #2/0 THWN; 30 ft
S
P
XF: 1_T-M4
150kVA; 3.46%Z
Pri: 480V
Sec: 208V
F: 1_SWBD D4ML
(2) #350 THWN; 20 ft
SWBD: 1_D4ML
208V, 600A
65k SCAR
FU: 1_CH1
FERRAZ SHAWMUT (TRS)
70 A
F: 1_CH1
(1) #2 THWN; 5 ft
FU: 1_CH2
FERRAZ SHAWMUT (TRS)
90 A
F: 1_CH2
(1) #2 THWN; 5 ft
CB: 1_4MLE XFMR
CUTLER-HAMMER (EHD)
30 A
F: 1_4MLE XFMR
(1) #10 THWN; 40 ft
S
P
XF: 1_T-4MLE
15kVA; 3.24%Z
Pri: 480V
Sec: 208V
F: 1_Pnl 4MLE
(1) #6 THWN; 5 ft
CB: 1_4MLE Main
CUTLER-HAMMER (BAB)
50 A
PNL: 1_4MLE
208V, 50A
200k SCAR
FU: 1_PNL A RM 4E33
FERRAZ SHAWMUT (TR)
30 A
FU: 1_4MLC
BUSSMANN (KTN-R)
175 A
FU: 1_4MLB
BUSSMANN (KTN-R)
125 A
FU: 1_4MLA
BUSSMANN (KTN-R)
125 A
FU: 1_4MLD
Unknown (Unknown)
100 A
FU: 1_CU-1
Unknown (Unknown)
40 A
F: 1_PNL A RM 4E33
(1) #6 THWN; 1 ft
F: 1_4MLC
(1) #2/0 THWN; 35 ft
PNL: 1_4MLC
208V, 225A
10k SCAR
F: 1_4MLB
(1) #1 THWN; 35 ft
PNL: 1_4MLB
208V, 225A
10k SCAR
F: 1_4MLA
(1) #1 THWN; 30 ft
PNL: 1_4MLA
208V, 225A
10k SCAR
F: 1_4MLD
(1) #2 THWN; 40 ft
PNL: 1_4MLD
208V, 100A
200k SCAR
F: 1_CU-1
(1) #8 THWN; 1 ft
CB: 1_4MLC 6-8-10 UNK
CUTLER-HAMMER (EB)
70 A
F: 1_4MLC 6-8-10 UNK
(1) #4 THWN; 1 ft
CB: 1_Comp rm fan coil
CUTLER-HAMMER (EB)
20 A
F: 1_Comp rm fan coil
(1) #10 THWN; 1 ft
CB: 1_EX Fan XRAY RM12
CUTLER-HAMMER (EHB)
15 A
F: 1_EX Fan XRAY RM12
(1) #12 THWN; 1 ft
MCP: 1_EF E-67
CUTLER-HAMMER (HMCP)
15 A, 15 A Plug
MCP: 1_EF E-60
CUTLER-HAMMER (HMCP)
7 A, 7 A Plug
MCP: 1_EF E-11
CUTLER-HAMMER (MCP)
30 A, 30 A Plug
MCP: 1_EF E-12
CUTLER-HAMMER (MCP)
3 A, 3 A Plug
MCP: 1_EF E-13
CUTLER-HAMMER (MCP)
3 A, 3 A Plug
MCP: 1_EF E-14
CUTLER-HAMMER (MCP)
7 A, 7 A Plug
MCP: 1_EF E-15
CUTLER-HAMMER (MCP)
15 A, 15 A Plug
MCP: 1_AH-39
CUTLER-HAMMER (MCP)
3 A, 3 A Plug
CB: 1_MCC SUBFEED 2BL
CUTLER-HAMMER (HFB)
100 A
MCP: 1_EF E-66
CUTLER-HAMMER (MCP)
15 A, 15 A Plug
F: 1_EF E-67
(1) #10 THWN; 1 ft
F: 1_EF E-60
(1) #12 THWN; 25 ft
DISC: 1_EF60
480V, F: 1_EF E-11
(1) #10 THWN; 1 ft
F: 1_EF E-12
(1) #10 THWN; 1 ft
F: 1_EF E-13
(1) #12 THWN; 40 ft
DISC: 1_EF-13
480V, F: 1_EF E-14
(1) #10 THWN; 1 ft
F: 1_EF E-15
(1) #10 THWN; 1 ft
F: 1_AH-39
(1) #10 THWN; 1 ft
F: 1_MCC SUBFEED 2BL
(1) #3 THWN; 1 ft
F: 1_EF E-66
(1) #10 THWN; 25 ft
DISC: 1_EF-66
480V, FU: 1_EF13
LITTELFUSE (FLSR)
20 A
F: 1_EF13
(1) #12 THWN; 1 ft
FU: 1_EF60
LITTELFUSE (FLSR)
20 A
F: 1_EF60
(1) #12 THWN; 1 ft
FU: 1_EF66
BUSSMANN (FRS-R)
15 A
F: 1_EF66
(1) #10 THWN; 1 ft
BUS: 1_CH-2
480V, MTR: 1_CH-2 Compr
2 @ 15 hp
MTR: 1_CH-2 Fan Motor
4 @ 1 hp
MTR: 1_CH-2 Water Pump
1 @ 3.5 hp
BUS: 1_CH-1
480V, MTR: 1_CH-1 Compr
2 @ 15 hp
MTR: 1_CH-1 Fan Motor
4 @ 1 hp
MTR: 1_CH-1 Water Pump
1 @ 3.5 hp
SEE "SWBD US-3A - SERVICE BAY 5-7 - US-3A
ONE-LINE DIAGRAM" FOR CONTINUATION
F: 1_DPMHA Penthouse 4
(2) #400 THWN; 280 ft
CB: 1_DPMHA Main
GE (SKLA)
800 A, 800 A Plug
SWBD: 1_DPMHA
480V, 800A
65k SCAR
CB: 1_CHILLER
GE (SGLA)
400 A, 400 A Plug
CB: 1_DPMBH
GE (SFLA)
225 A, 225 A Plug
CB: 1_CWP1
GE (SELA)
40 A, 40 A Plug
CB: 1_CWP2
GE (SELA)
40 A, 40 A Plug
CB: 1_9KVA XFMR
GE (SELA)
20 A, 20 A Plug
F: 1_CHILLER
(1) #500 THWN; 50 ft
DISC: 1_Chiller Roof 480V, F: 1_DPMBH
(1) #4/0 THWN; 10 ft
PNL: 1_DPMHB
480V, 250A
200k SCAR
F: 1_CWP1
(1) #10 THWN; 25 ft
F: 1_CWP2
(1) #10 THWN; 30 ft
F: 1_9KVA XFMR
(1) #12 THWN; 5 ft
S
P
XF: 1_9KVA XFMR
9kVA; 2.65%Z
Pri: 480V
Sec: 208V
F: 1_Pnl 5MLA
(1) #8 THWN; 10 ft
CB: 1_5MLA Main
GE (THQB)
40 A
PNL: 1_5MLA
208V, 125A
10k SCAR
FU: 1_Chiller roof
FERRAZ SHAWMUT (TRS)
350 A
F: 1_Chiller roof
(1) #500 THWN; 40 ft
CB: 1_CIRC PUMP1
SIEMENS (BQD)
20 A
CB: 1_CIRC PUMP2
SIEMENS (BQD)
20 A
CB: 1_Chiller 3rd Flr Comp
SIEMENS (BQD)
60 A
F: 1_CIRC PUMP1
(1) #12 THWN; 1 ft
F: 1_CIRC PUMP2
(1) #12 THWN; 1 ft
F: 1_Chiller 3rd Flr Comp
(1) #6 THWN; 1 ft
DISC: 1_Chiller DPMHB-4 480V, FU: 1_Chiller Comp Rm
LITTELFUSE (FLSR)
60 A
F: 1_Chiller Comp Rm
(1) #6 THWN; 20 ft
TAP: 1_SWBD DPMHA
480V, F: Solar PV Disc SW-2
(2) #350 THWN; 10 ft
F: 1_DPMHA
(2) #500 THWN; 2 ft
DISC: 1_Solar PV Disc SW-2 480V, BUS: 1_Chiller Comp Rm 480V, MTR: 1_Ch Comp Rm Compr A/B
2 @ 12.5 hp MTR: 1_Ch Comp Rm Fans
2 @ 0.8 hp
MTR: 1_CWP2
1 @ 10 hp
MTR: 1_CWP1
1 @ 10 hp
BUS: 1_Chiller Roof 480V, MTR: 1_Chiller Roof Compr 1
1 @ 100 hp
MTR: 1_Chiller Roof Compr 2
1 @ 125 hp
MTR: 1_Chiller Roof
6 @ 2.1 hp
E-112 - SB 5-7.dgn 3/30/2018 8:33:04 AM
File details come from the government source that posted it. Updated .